Residential Permit
Print Date: 12/27/2018 Permit No: CBR2018-2714
Job Address:
Permit Type:
Parcel No:
Valuation:
Occupancy Group:
# Dwelling Units:
Bedrooms:
Project Title:
2406 La Macarena Ave
BLDG-Residential
2550701900
$12,400.00
Work Class: Cogen
Lot#:
Reference#:
Construction Type:
Bathrooms:
Orig. Plan Check#:
Plan Check#:
Description: TURNER: 31 FLUSH-ROOF MOUNTED PANELS, ll.16KW, NORMA, NO UPGRADE
BUILDING PERMIT FEE ($2000+)
BUILDING PLAN CHECK FEE (BLDG)
SB1473 GREEN BUILDING STATE STANDARDS FEE
STRONG MOTION-RESIDENTIAL
Total Fees: $243.28
Owner:
TRU5TTURNER FAMILY
2406 La Macarena Ave
CARLSBAD, CA 92009
Total Payments To Date: $243.28
Status:
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Contractor:
BURKE ELECTRIC INC
3283 Trade Center Dr
Riverside, CA 92507-3432
951-787-9800
Balance Due:
Please take NOTICE that approval of your project includes the "Imposition" of fees, dedications, reservations, or other exactions hereafter
collectively referred to as "fees/exaction." You have 90 days from the date this permit was issued to protest imposition of these
fees/exactions. If you protest them, you must follow the protest procedures set forth in Government Code Section 66020(a}, and file the
protest and any other required information with the City Manager for processing ln accordance with Carlsbad Municipal Code Section
3.32.030. Failure to timely follow that procedure will bar any subsequent legal action to attack, review, set aside, void, or annul their
imposition.
You are hereby FURTHER NOTIFIED that your right to protest the specified fees/exactions DOES NOT APPLY to water and sewer connection
fees and capacity changes, nor planning, zoning, grading or other similar application processing or service fees in connection with this
project. NOR DOES IT APPLY to any fees/exactions of which you have previously been given a NOTICE similar to this, or as to which the
statute of limitation has previously otherwise expired.
Closed -Finaled
10/05/2018
12/04/2018
12/27/2018 9:28:46AM
$0.00
$141.57
$99.10
$1.DO
$1.61
1635 Faraday Avenue, Carlsbad, CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
PERMIT INSPECTION HISTORY REPORT (CBR2018-2714)
Permit Type: BLDG-Residential Application Date: 10/05/2018 Owner: TRUST TURNER FAMILY
Work Class: Cogen Issue Date: 12/04/2018 Subdivision: CARLSBAD TCT#73-18 UNIT#01
Status: Closed -Finaled Expiration Date: 06/25/2019 Address: 2406 La Macarena Ave
Carlsbad, CA 92009-9123
IVR Number: 14413
Scheduled Actual
Date Start Date Inspection Type Inspection No. Inspection Status Primary Inspector Reinspection Complete
12/19/2018 12/1912018 BLDG-35 Solar 079261-2018 Cancelled Paul Burnette Relnspectlon Complete
Panel
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Final 079262-2018 Cancelled Paul Burnette Relnspectlon Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Plumbing Final No
BLOG-Mechanical Final No
BLDG-Structural Final No
BLDG-Electrical Final No
12/2712018 12/27/2018 BLDG-35 Solar 079925-2018 Passed Paul Burnette Complete
Panel
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Final 079926-2018 Passed Paul Burnette Complete
Inspection
Checklist Item COMMENTS Passed
BLDG-Building Deficiency No
BLDG-Plumbing Final No
BLOG-Mechanical Final No
BLDG-Structural Final No
BLDG-Electrical Final No
December 27, 2018 Page 1 of 1
DATE: October 30, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2018-2714
✓• EsG1I
A SAFE:.bt11lt CornpZ11,y
SET: II
PROJECT ADDRESS: 2406 La Macarena Avenue
PROJECT NAME: Turner Residence 31 Module PV System
□ APPLICANT
D JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
Janalee Howland
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: Janalee H~nd Telephone#: (619) 208-4436
Date contacted:/ (b~) Email: jhowland@fluentsolar.com
Mail Telephone Fax In Person
0 REMARKS:
By: Chris Shaver
EsGil
10/23/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
DATE: October 15, 2018
JURISDICTION: Carlsbad
PLAN CHECK#.: CBR2018-2714
✓• EsG1I
SETI
PROJECT ADDRESS: 2406 La Macarena Avenue
PROJECT NAME: Turner Residence 31 Module PV System
□ APPLICANT
□ JURIS.
D The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
[:gj The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
[:gj The applicant's copy of the check list has been sent to:
Janalee Howland
D EsGil staff did not advise the applicant that the plan check has been completed.
[:gj EsGil staff did advise the applicant that the plan check has been completed.
□
Person contacted: Janalee H_91and Telephone#: (619) 208-4436 '';!..!~~~~/ 5 (b~mail: jhowland@fluentsolar.com
By: Chris Shaver
EsGil
Fax In Person
10/8/2018
Enclosures:
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-2714
October 15, 2018
PLAN REVIEW CORRECTION LIST
RESIDENTIAL PV SYSTEM
PLAN CHECK#.: CBR2018-2714 JURISDICTION: Carlsbad
PROJECT ADDRESS: 2406 La Macarena Avenue
REMARKS:
DATE PLANS RECEIVED BY
JURISDICTION: 10/5/2018
DATE INITIAL PLAN REVIEW
COMPLETED: October 15, 2018
FOREWORD (PLEASE READ):
DATE PLANS RECEIVED BY
ESGIL CORPORATION: 10/8/2018
PLAN REVIEWER: Chris Shaver
This plan review is limited to the technical requirements contained in the California version of
the International Residential Code, International Building Code, Uniform Plumbing Code,
Uniform Mechanical Code, National Electrical Code and state laws regulating energy
conservation, noise attenuation and access for the disabled. This plan review is based on
regulations enforced by the Building Department. You may have other corrections based on
laws and ordinance by the Planning Department, Engineering Department, Fire Department or
other departments. Clearance from those departments may be required prior to the issuance of
a building permit.
Present California law mandates that construction comply with the 2016 edition of the California
Code of Regulations (Title 24), which adopts the following model codes: 2015 IRC, 2015 IBC,
2015 UPC, 2015 UMC and 2014 NEC.
The above regulations apply, regardless of the code editions adopted by ordinance.
The following items listed need clarification, modification or change. All items must be satisfied
before the plans will be in conformance with the cited codes and regulations. Per Sec. 105.4 of
the 2015 International Building Code, the approval of the plans does not permit the violation of
any state, county or city law.
To speed up the recheck process, please note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet number, specification section, etc.
Be sure to enclose the marked up list when you submit the revised plans.
Carlsbad CBR2018-2714
October 15, 2018
PLANS
1. Please make all corrections, as requested in the correction list. Submit FOUR new
complete sets of plans for commercial/industrial projects (THREE sets of plans for
residential projects). For expeditious processing, corrected sets can be submitted
in one of two ways:
1. Deliver all corrected sets of plans and calculations/reports directly to the City of
Carlsbad Building Department, 1635 Faraday Ave., Carlsbad, CA 92008, (760)
602-2700. The City will route the plans to EsGil and the Carlsbad Planning,
Engineering and Fire Departments.
2. Bring IWQ corrected set of plans and calculations/reports to EsGil, 9320
Chesapeake Drive, Suite 208, San Diego, CA 92123, (858) 560-1468. Deliver all
remaining sets of plans and calculations/reports directly to the City of Carlsbad
Building Department for routing to their Planning, Engineering and Fire
Departments.
NOTE: Plans that are submitted directly to EsGil only will not be reviewed by the
City Planning, Engineering and Fire Departments until review by EsGil is complete.
2. All sheets of plans must be signed by the person responsible for their
preparation. (California Business and Professions Code).
3. Provide the electrical meter service equipment description as having a meter
location that is either (top or bottom fed) or at a "center-fed" position. The RMA is
a new service disconnecting means. Add the following design to your plans: A
neutral bond connection at the RMA, a grounding electrode connection at the
RMA, and the following signage: "Service Disconnecting Means 1 of 2" (to be
posted at the main service disconnect) and "Service Disconnecting Means 2 of
2" (to b posted at the RMA disconnect).
ROOF ACCESS AND PATHWAYS:
4. Roof access, pathways, and setback requirements shall be provided in
accordance with Section R324.6.1 through R324.6.2.1. of the 2016 CRC. Show
setback dimensions on plans. Access and minimum spacing shall be required to
provide emergency access to the roof, to provide pathways to specific areas of
the roof, to provide for smoke ventilation opportunity areas, and to provide
emergency egress from the roof. Please provide callout for pathway dimensions
on plans. CRC R324.6
CONTINUED
Carlsbad CBR2018-2714
October 15, 2018
END OF REVIEW
5. To speed up the review process, note on this list (or a copy) where each
correction item has been addressed, i.e., plan sheet, or detail note number,
calculation page, etc.
6. Please indicate here if any changes have been made to the plans that are not a
result of corrections from this list. If there are other changes, please briefly
describe them and where they are located in the plans.
• Have changes been made to the plans not resulting from this correction
list? Please indicate:
Yes □ No □
7. The jurisdiction has contracted with EsGil, located at 9320 Chesapeake Drive,
Suite 208, San Diego, California 92123; telephone number of 858/560-1468, to
perform the plan review for your project. If you have any questions regarding
these plan review items, please contact Chris Shaver at EsGil. Thank you.
Carlsbad CBR2018-2714
October 15, 2018
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
PREPARED BY: Chris Shaver
PLAN CHECK#.: CBR2018-2714
DATE: October 15, 2018
BUILDING ADDRESS: 2406 La Macarena Avenue
BUILDING OCCUPANCY: R3
BUILDING
I
AREA
I
Valuation Reg.
PORTION ( Sq. Ft.) Multiplier Mod.
City Estimate
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Building Permit Fee ..,. I
I l';-,1 .~,-[:
1997 UBC Plan Check Fee ~ :
Type of Review: 0 Complete Review
D Repetitive Fee ...,. Repeats
□ Other
0 Hour1y
E&Gil Fee
Comments:
VALUE ($)
12,400
12,400
□ Structural Only
$86.131
Sheet 1 of 1
{City of
Carlsbad
Revision Permit
Print Date: 01/09/2019
Job Address: 2406 La Macarena Ave
Permit Type: BLDG-Permit Revision Work Class:
Parcel No: 2550701900 Lot#:
Valuation: $12,400.00 Reference#:
Occupancy Group: Construction Type:
# Dwelling Units: Bathrooms:
Bedrooms: Orig. Plan Check#:
Plan Check#:
Project Title:
Description: TURNER: CHANGE IN PANEL LAYOUT
Applicant:
BURKE ELECTRIC !NC
JENALEE HOWLAND
3283 Trade Center Dr
Riverside, CA 92507-3432
619-208-4436
FEE
BUILDING PLAN CHECK REVISION ADMIN FEE
MANUAL BUILDING PLAN CHECK FEE
Total Fees: $147.S0
Building Division
Owner:
TRUST TURNER FAMILY
2406 La Macarena Ave
CARLSBAD, CA 92009
Total Payments To Date:
Permit No: PREV2018-0300
Residential Permit Revision Status: Closed -Finaled
12/04/2018
12/17/2018
01/09/2019
CBR2018-2714
$147.50
Applied:
Issued:
Permit
Finaled:
Inspector:
Final
Inspection:
Contractor:
BURKE ELECTRIC INC
3283 Trade Center Dr
Riverside, CA 92507-3432
951-787-9800
Balance Due:
AMOUNT
$35.00
$112.50
$0.00
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-2700 I 760-602-8560 f I www.carlsbadca.gov
(cicyof
Carlsbad
PLAN CHECK REVISION OR
DEFERRED SUBMITTAL
APPLICATION
Development Services
Building Division
1635 Faraday Avenue
760-602-2719
www.carlsbadca.gov B-15
Original Plan Check Number C. f3t<.2.Df~ -'Z. 7/'-f Plan Revision Number fto,o2QIK-62,DO
Project Address 2. 'i Ob t,_,-.. m ,..,tA>t-re.~-fl-v-e.
General Scope of Revision/Deferred Submittal: Lj.--'--#M/~0 _.J_t-_C,,~h.-~--__.,~~----------
CONTACT INFORMATION:
Name J::",....Ju Phone 6 /qr tz._ ()'g -'1'1 k Fax ,__ _______ _
Address 32g 3 Tr;.,. l...~1'\+cr-D ,e_ City R,iV'~rsit:I t. Zipqif"oz
Email Address _Ji=_H_o_w_lo.,,J@_--=-'fi_1v_en_.-_,,._0_1 ... _r_._'-_o_,,,, ________________ ~
Original plans prepared by an architect or engineer, revisions must be signed & stamped by that person.
1 . Elements revised: [a-Plans D Calculations D Soils D Energy D Other
2. 3.
Describe revisions in detail List page(s) where each
revision is shown
L()..\/O<J+-C --PV2
LILJ • .,... C,.t,.-,,1 PV3
Lou,,,,... -c .. -e PV7
4. Does this revision, in any way, alter the exterior of the project? D Yes Er-No
5. Does this revision add ANY new floor area(s)? D Yes [3'1\10
6. Does this revision affect any fire related issues? D Yes ~o
7. . Is this a complete set? D Yes ~ ;ri-h/;i A!S'Signature J -::i_d Date
1635 Faraday Avenue, Carlsbad, CA 92008 Ph: 760-602-2719 Fax: 760-602-8558 Email: building@carlsbadca.gov
www.carlsbadca.gov
DATE: December 13, 2018
JURISDICTION: Carlsbad
✓• EsG1I
A S,O,FEbullt Company
PLAN CHECK#.: CBR2018-2714(PREV2018-0300) SET: I
PROJECT ADDRESS: 2406 La Macarena Avenue
PROJECT NAME: Turner Residence 31 Module PV System
□ APPLICANT
□ JURIS.
~ The plans transmitted herewith have been corrected where necessary and substantially comply
with the jurisdiction's building codes.
D The plans transmitted herewith will substantially comply with the jurisdiction's
codes when minor deficiencies identified below are resolved and checked by building
department staff.
D The plans transmitted herewith have significant deficiencies identified on the enclosed check list
and should be corrected and resubmitted for a complete recheck.
D The check list transmitted herewith is for your information. The plans are being held at EsGil
until corrected plans are submitted for recheck.
D The applicant's copy of the check list is enclosed for the jurisdiction to forward to the applicant
contact person.
D The applicant's copy of the check list has been sent to:
Janalee Howland
~ EsGil staff did not advise the applicant that the plan check has been completed.
D EsGil staff did advise the applicant that the plan check has been completed.
Person contacted: zanal e ind Telephone#: (619) 208-4436
Date contacted: (by Email: jhowland@fluentsolar.com
Mail Telephone Fax In erson
0 REMARKS:
By: Chris Shaver
EsGil
Enclosures:
12/6/2018
9320 Chesapeake Drive, Suite 208 ♦ San Diego, California 92123 ♦ (858) 560-1468 ♦ Fax (858) 560-1576
Carlsbad CBR2018-2714(PREV2018-0300)
December 13, 2018
[DO NOT PAY -THIS IS NOT AN INVOICE]
VALUATION AND PLAN CHECK FEE
JURISDICTION: Carlsbad
2714(PREV2018-0300)
PLAN CHECK#.: CBR2018-
PREPARED BY: Chris Shaver DATE: December 13, 2018
BUILDING ADDRESS: 2406 La Macarena Avenue
BUILDING OCCUPANCY: R3
BUILDING AREA Valuation
PORTION ( Sq. Ft.) Multiplier
Air Conditioning
Fire Sprinklers
TOTAL VALUE
Jurisdiction Code cb By Ordinance
1997 UBC Building Permit Fee -~
1997 UBC Plan Check Fee ·~3
Type of Review: □ Complete Review
D Repetitive Fee ~ ~7 Repeats
* Based on hourly rate
Comments:
□ Other
Hourly Q -
EsGII Fee
Reg. VALUE ($)
Mod.
□ Structural Only
1IHr.@*
~=====$=9=o=. o~o $90.001
Sheet 1 of 1