HomeMy WebLinkAboutMS 14-07; Robertson Ranch West Village; ROBERTSON RANCH PA-8 SENIOR HOUSING PROJECT; 2015-11-23r I DEXTER WILSON ENGINEERING, INC. l WATER • WASTEWATER : RECYCLED WATER CONSULTING ENGINEERS f 2234 FARADAY AVENUE • CARLSBAD, CA 92008 • . (760) 438-4422 ROBERTSON RANCH PA-8 SENIOR HOUSING PROJECT IN THE CITY OF CARLSBAD November 23, 2015 Prepared by: Dexter Wilson Engineering, Inc. 2234 Faraday Avenue Carlsbad, CA 92008 760-438-4422 Job No. 528-033 DEXTER WILSON ENGINEERING, INC. November 23, 2015 Alliance Land Planning & Engineering, Inc. 2248 Faraday Avenue Carlsbad, CA 92008 Attention: Craig Whitteker, P.E., President DEXTER S . WILSON, P.E. ANDREW M . OVEN, P .E. STEPHEN M. NIELSEN, P.E. NATALIE J. FRASCHETTI, P.E. 528-033 Subject: Robertson Ranch PA-8 Senior Housing Project in the City of Carlsbad Introduction This report will address three aspects of the water supply system for the Robertson, Ranch PA-8 Senior Housing development project. These are: 1. Sizing of the domestic water service lateral, meter, backflow preventer, and building supply piping to provide domestic service to the Senior Housing building. 2. Sizing of the frre protection system service lateral, detector check backflow preventer, and onsite private fire protection water system to ensure that the onsite private fire hydrants can deliver the necessary fire hydrant flow at greater than 20 psi residual pressure. 3. Sizing of the frre sprinkler service lateral serving the Senior Housing building which lateral will be connected to the private onsite fire protection system piping outlined in Item 2 above. 2234 FARADAY AVENUE • CARLSBAD, CA 92008 • (760) 438·4422 • FAX (760) 438-0173 Craig Whitteker, P.E. November 23, 2015 The domestic and fire protection system laterals for the Robertson Ranch PA-8 Senior Housing project will be connected to the proposed 12" 349 Pressure Zone public water system piping in Gage Drive fronting the project site on its south boundary. Since the proposed public water system is presently under construction as part of the backbone infrastructure being installed for the Robertson Ranch development, a fire hydrant flow test cannot be performed. Thus, the available hydraulic grade line in the 12" 349 Pressure Zone piping in Gage Drive was determined based on the water system analysis prepared for the master development titled, "Water System Analysis for Rancho Costera," April17, 2015, Dexter Wilson Engineering, Inc. Domestic Water System Sizing A single, separate water service lateral is planned for the domestic service to the Senior Housing building. The water meter size needed to meet the demand of this building is based on the maximum expected domestic flowrate as determined from the California Plumbing Code. Appendix A presents a spreadsheet calculation of the total estimated Water Fixture Units for the Senior Housing building. The breakdown of Water Fixture Units was obtained by reviewing the architectural floor plans for the proposed Senior Housing building. The total Water Fixture Units is estimated to be 1,136 WFU. Using Chart A-2 from the Plumbing Code, this converts to a water demand of 224 gpm. Domestic Water Meter Sizing. The City of Carlsbad Utilities Department provided the flowrate ranges for their domestic water meters in an email dated August 12, 2015. A copy of this email is in Appendix A. It shows that a 3" meter which allows a maximum flowrate of 400 gpm will be appropriate to provide service to the Senior Housing building whose demand is 224 gpm. Domestic Water Service Backflow Preventer. The reduced pressure principle backflow preventer assembly after the City domestic water meter is recommended to be a 4- inch assembly in order to minimize the pressure loss through this device. Appendix A DEXTER WILSON ENGINEERING, INC. PAGE 2 Craig Whittaker, P.E. November 23, 2015 includes the manufacturer's literature for a Wilkins Model 375 backflow preventer. This unit or any equivalent unit is to be installed after the domestic meter. Domestic Building Supplv Piping. The domestic building supply piping is sized for a flow velocity of less than 8 fps. Thus, the domestic building supply piping for the Senior Housing building is 4" diameter. At a maximum flowrate of 224 gpm, the flow velocity in a 4" line is 5. 7 fps. Available Pressure at the Base of the Domestic Service Riser. The available pressure at the Base of the Riser for the domestic service is based on a 4" domestic service lateral, a 3" meter, a 4" reduced pressure principle backflow assembly, and a 4" building supply pipe. The available hydraulic grade line in the public water main in Gage Drive was taken from the Peak Hour Demand computer modeling performed in the water system analysis prepared for the master development titled, ''Water System Analysis for Rancho Costera," April 17, 2015, Dexter Wilson Engineering, Inc. The available hydraulic grade line under Peak Hour Demands is 348 feet. The system schematic for the domestic water system and the calculations for pressure loss are included in Appendix A. The result is that the available domestic service pressure at the Base of the Riser is 72.4 psi. Under maximum static conditions, domestic service pressure will be 91.4 psi based on a maximum available hydraulic grade line of 349 feet and an estimated Base of Riser elevation of 138 feet. Since this pressure is greater than 80 psi, a pressure regulator will need to be included in the building plans to maintain internal building service pressures below 80 psi in accordance with the Plumbing Code. Private Fire Protection System Sizing A separate fire protection system is being designed for the Senior Housing building. This system is designed to carry the required fire flow plus the building fire sprinkler flow and maintain greater than 20 psi residual at the last fire hydrant on the site. DEXTER WILSON ENGINEERING, INC. PAGE 3 Craig Whitteker, P.E. November 23, 2015 The computer model run from the April 17, 2015, master water study which was used to estimate the available hydraulic grade line was the Maximum Day Demand Plus 3,000 gpm Fire Flow Split Between Nodes 106 and 110. Node 106 is at the entrance to the Senior Housing site which is on the east side of the Senior Housing building footprint. Node 110 is on the west side of the Senior Housing building at the intersection of Gage Drive and West Ranch Street. The residual hydraulic grade lines at Nodes 106 and 110 for this computer model analysis were 334.2 feet and 327.7 feet, respectively. The average hydraulic grade line is 331 feet which will be the value used in our calculations. The required fire hydrant flow is based on the building square footage and type of construction. The email in Appendix B summarizes the information and concludes that the required fire hydrant flow is 2, 750 gpm. The next email in Appendix B identifies the required fire sprinkler flow for the Senior Housing building which is 63.2 gpm. Thus, the total flow which will be calculated in the private fire protection system is 2,813.2 gpm. As mentioned earlier in this report, the available hydraulic grade line for the fire flow scenario is 331 feet in Gage Drive at the point of connection to the 12" 349 Pressure Zone public water system. Appendix C contains the hydraulic calculations for a flow of 2,814 gpm from the public water main to the second to last fire hydrant (FH2), and a flow of 1,500 gpm from the second to last fire hydrant to the last fire hydrant (FH3). The residual pressure at the last fire hydrant, FH3, is 55 psi. The private fire protection system piping includes: 12" public fire service lateral; 10" double check detector assembly; 10" piping from the 10" backflow assembly to FH2; and 8" piping from FH2 to FH3. DEXTER WILSON ENGINEERING, INC. PAGE 4 Craig Whitteker, P.E. November 23, 2015 Fire Sprinkler Service Lateral to Senior Housing Building The fire sprinkler service lateral to the Senior Housing Building has been sized by the Fire Sprinkler designer to be 4" diameter. This service lateral is connected to the private onsite frre protection system near the location of FH2. Under a fire flow scenario, where there is 2,813.2 gpm flowing in the fire protection system piping to FH2, the additional pressure loss for the 4" fire sprinkler piping results in an available pressure for the fire sprinkler system at the Base of the Riser of 61 psi. The calculations for this are included in Appendix C right after the calculations for the residual pressure at FH3 under a fire flow plus fire sprinkler flow scenario. Finally, the fifth sheet of the calculations in Appendix C determines the available pressure at the Base of the Riser for the Fire Sprinkler System with no fire hydrant flow. The available pressure is 76.6 psi at a flow of 63.2 gpm. Conclusion Thank you for the opportunity to provide water system sizing analysis services for this project. Please feel free to contact us to further discuss any aspect of the information presented in this water service analysis for the Robertson Ranch PA-8 Senior Housing project. Dz:~=nc. Andrew Oven, P.E. AO:ps cc: Erick Escobedo, Alliance Land Planning and Engineering Attachments DEXTER WILSON ENGINEERING, INC. PAGE 5 APPENDIX A DOMESTIC SERVICE DATA DEXTER WILSON ENGINEERING, INC. Ct0tv./d)'orr ~( hrsrr-e 4-.o.s> ih f,..:.vttA-e , fJQ~f..·c.. I L;aAwd a.~A f'-')/A.l~ J ~Aft$ ./v S?h.'or f/d"tttJ I I I +-I -1 . I J I . . I I I I 1 • • I . • 1 • I I I I DEXTER WILSON ENGINEERING, INC. Project Name Job Number Date Robertson Ranch PA-7 Senior Hou1ir1g 528..{)33 811812015 Water Fixture Units The basis for the Water Fixture Units is "Private" per the 2013 California Plumbing Code. DESCRIPTION CLOTHES WASHER LAUNDRY SINK MOP SINK TUB/SHOWER SHOWER KITCHEN SINK DISHWASHER LAVATORY WATER CLOSET (1.6 GPF) HOSE BIBB EACH AOOTL HB POOL FILL OTHER TOTAL Senior Housing Building UnitA1 Unit 81 FIXTURE TOTAL FIXTURE QUANTITY UNITS FIXTURE QUANTITY UNITS EACH UNITS EACH 4 0 4 1.5 0 1.5 3 0 3 1 4 4 1 4 2 0 2 1 1.5 1.5 1 1.5 1 1.5 1.5 1 1.5 1 1 1 1 1 1 2.5 2.5 1 2.5 2.5 0 2.5 1 0 1 10 0 10 1 0 1 10.5 Senlor Houslna Bulldlna Ffoor UnltA1 UnitB1 Unit B2 Laundrv 1 27 " 1 1 2 30 5 0 1 3 29 5 0 1 Total Unitl 86 1<4 1 3 Fixture Unl 903 1<47 1<4.5 52.5 Senior Housing Building total FUs TOTAL FIXTURE UNITS 0 0 0 4 0 1.5 1.5 1 2.5 0 0 0 0 10.5 Amenities 1 0 0 1 19 1136 \\artic\eng\528033\Robeftlon Ranch PA-7 Senior Housing WatM Fixture Unit Elltimaiii/Sheet1 Unit 82 FIXTURE TOTAL QUANTITY UNITS FIXTURE EACH UNITS 1 4 4 1.5 0 3 0 1 " " 2 0 1 1.5 1.5 1 1.5 1.5 1 1 1 1 2.5 2.5 2.5 0 1 0 10 0 1 0 14.5 22<4 gpm Laundry Room FIXTURE TOTAL QUANTITY UNITS FIXTURE EACH UNITS 4 4 16 1 1.5 1.5 3 0 4 0 2 0 1.5 0 1.5 0 1 0 2.5 0 2.5 0 1 0 10 0 1 0 17.5 528..{)33 [Date] Amenities FIXTURE TOTAL QUANTITY UNITS FIXTURE EACH UNITS 4 0 1.5 0 1 3 3 4 0 2 0 2 1.5 3 1.5 0 3 1 3 "' 2.5 10 2.5 0 1 0 10 0 1 0 19 7 00 00 5 00 40 0 ~ 30 CL 0 (.!) I , 22f/. ~ J1'2Q 0 CD 0 10 0 0 1 2• 500 UNIFORM PLUrv CHART A·2 Estimate Curves for Demand Load ~No.1 for sy tem predominantly for flushometer valves : No.2 for sy tem predominantly for flush tanks = 1000 1500 Fixture Units I, 131D 141f L4 2000 2500 . --1- 3000 From: To: Cc: Subject: Date: Dear Andrew, Elizabeth Shoemaker Andrew Oyen Elizabeth Shoemaker FW: Robertson Ranch -Allowable Flow Rates for Water Meters Friday, August 14, 2015 11:45:56 AM Below are your flow ranges from the City. Stuff is slowly coming in. Thanks again for being on the conference call. Much appreciated! Elizabeth Shoemaker Project Coordinator Alliance Land Planning & Engineering 2248 Faraday Avenue Carlsbad, CA 92008 Phone: (760} 431-9896 Email: eshoemaker@allianceeng.com From: Jeremy Riddle [mailto:Jeremy.Riddle@carlsbadca.gov] Sent: Friday, August 14, 2015 11:27 AM To: Elizabeth Shoemaker Subject: FW: Robertson Ranch -Allowable Flow Rates for Water Meters Here you go. From: Mario Remillard Sent: Wednesday, August 12, 2015 11:36 AM To: Kirsten Plonka; Eric Sanders Cc: Jeremy Riddle Subject: RE: Robertson Ranch -Allowable Flow Rates for Water Meters Maximum continuous flow ranges per size below. 1" -40 GPM 1 Yz-80 GPM 2" -170 GPM 3" -400 GPM 4" -800 GPM 6" -1500 GPM From: Kirsten Plonka Sent: Wednesday, August 12, 2015 11:14 AM To: Eric Sanders; Mario Remillard Cc: Jeremy Riddle Subject: Fwd : Robertson Ranch -Allowable Flow Rates for Water Meters Eric and Mario, Do either of you have this info? Thanks. Kirsten Sent from my iPhone, please excuse any typos. Begin forwarded message: From: Elizabeth Shoemaker <eshoemaker@alljanceeng.com> Date: August 12, 2015 at 10:58:52 AM PDT To: "jeremy rjddle@carlsbadca goy" <jeremy.rjddle@carlsbadca.goy> Cc: "Kirsten.Pionka@CarlsbadCA goy" <Kirsten Plonka@CarlsbadCA goy>, "Eric Sanders (Eric.Saoders@carlsbadca goy)" <Eric Sanders@carlsbadca goy> Subject: RE: Robertson Ranch -Allowable Flow Rates for Water Meters Dear Jeremy I Kristen, Thank you for meeting with the Robertson Ranch Water Team yesterday and answering questions. It was extremely helpful and accomplished a lot. Question: 1. What the allowable flowrates for the City's water meters beginning with 1" and going through 8" in size. However, I believe the City does not do or approve 8" size, so the largest would be 6 unless 8" is allowed. Any help getting that information would be much appreciated. Thank you again for your help and coordination. Sincerely, Elizabeth Shoemaker Project Coordinator Alliance Land Planning & Engineering 2248 Faraday Avenue Carlsbad, CA 92008 Phone: (760) 431-9896 Email: eshoemaker@allianceeng com 13-:-20 P. E. (Civil) License Review Manual, Volume V Thble 2.2 also shows the equivalent length of pipe for various fittings in a tabular form. Thble 2.2 Equivalent Length of Pipe for Various Fittings ,_ .._.,. D'-W..._ ~ ..... "'-R. lliL 111. au •. ZIL JIL .... IlL IlL .... IZIL lCIL 1111. JilL .... .... ...... .... 4111. i:UWM, .. u u u u L7 u 15 u 5.1 u u u II IZ IC u 211 Z3 i:Udlwt,!iflll'l ll 17 25 34 a f1 Ill 135 "' HI 2JI • • 331 • • .. no Qallt'lllwt,Gfll II 11 a 54 • Ill II ZIO 210 Dl • 4JI • 541 170 131 l,a I ,!Ill Afttltwlw, .. lO IS 2Z 21 41 57 IS Ill 140 .. .. m 211 • J40 Gil SID Ill Clilcll ,.,. u u ll 14 lJ 25 • Sl II 71 II Ill lZI 131 .. 211 2JI 211 ~-. .A.. u S.1 t 1Z u 2Z 34 " S7 f1 1S II Ill 111 Ill l1l 211 Zto ~-. ~ u 5.7 ' 1Z 17 2Z 34 " 57 r1 1S • Ill Ill IJI 171 2111 Z40 ........... ...8-.. Ll L7 u 1S 5.1 u ll IC II 21 Z3 11 • 34 4Z sz II 7Z 11"911t ..... u u u 5.4 Ll u 17 Zl 21 31 'II 4Z • sz a • • Ill II"E,...,IIII,.._ Ll L7 ZJ u 5.1 u II lC II 21 D 11 • 34 cz sz II n IIPIIIIIn .... u Ll • ll • Z3 • • iD n a IGI na 125 1511 111 ZZII • ·~ u u u u l7 u u 11 ll IS 17 ., n Z3 • 'II 44 52 a...,--..:=?-. u u u 11 u u s.a 1Z 15 II 21 Z3 Z5 • • 45 5Z n Sllldll ....... ~ uo.vc u %.7 u 5.4 Ll u u Zl • 31 'II cz • 5Z a • • Ill ~ 1/D. liZ u u u u u u II ll II IS 2Z 14 21 3l • 41 5I &I 1/D.l/C OJ u u u L7 u 15 u J.l u u u • 1Z IC 17 211 Z3 s..ldll~· JID • 114 u u u u 17 u 7.4 II ll IS 11 It n Z3 • 'II " 5Z .vo. rn u u u u u 17 5J 7.5 tJ 1Z D IS l1 II 2Z 11 ll • ti/D-l/C u u u u L7 u u u u u u u • 1Z IC 11 21 Z3 (Ref: Gallant, Robert N., "Sizing Pipe for Liquids and Vapors", Chemical Engineering, Page 104, February 24, 1969.) ·. ·. . .... 11 .,. 1,lll .. la m ··m R 131 R • • ,. IJI 11 l1 • 45 l1 \ ~ Badger Meter Recorda!~'~ Turbo Series Meters Models 160 (1-1/2"), 200 (2"), 450 (3"), 1 000 (4"), 2000 (6"), 3500 (8"}, 5500 (1 0"), & 6200 (12"); NSF/ANSI Standards 61 and 372 Certified DESCRIPTION Recorda II Turbo Series meters meet or exceed the most recent revision of AWWA Standard C701 Class II Standards and are available in a lead-free bronzealloyforsizes 1-1/2" through 10" and cast iron for 12" meters. Turbo Series meters comply with the lead-free provisions of the Safe Drinking Water Act Sizes 1-1/2" through 10" meters are also certified to NSF/ANSI Standards 61 and 372 (Trade Designation: Turbo Series LL-NS) and carry the NSF-61 mark on the housing. All components of the lead-free alloy meter (housing, measuring element, seals and so on) comprise the certified system. Models 160 through 6200 are designed for 1-1/2" through 12" appllcMtons. These meten feature: Direct coupled turbine based on an exclusive•floating rotor" design that reduces bearing friction-and associated wear and tear. Low pressure loss for improved system efficiency. Exceptional registration accuracy across low flow rate, normal operating flow rate and maximum continuous operation flow. Permanently sealed, tamper-resistant register or encoder. Integral strainer option for sizes 1-1/2" through 4" help protect your system from damaging debris and related downtime. Meters and encoders are compatible with Badger Meter AMRIAMI meter reading systems and other approved reading technologies. Applications: Recorda II Turbo Series meters are designed for cold water, commercial and industrial applications where flows are consistent medium to high flows. Applications include hotels, apartment buildings, irrigations centers and manufacturing and processing plants. Turbo Series meters help reduce day-to- day maintenance costs while delivering accurate and efficient performance. Operation llr Performance: Direct magnetic drive is achieved when the magnet carrier is driven by a gear train coupled to the rotor. The gear train consists of two sets of gears connected by a vertical transmission shaft. One gear set is at the magnet carrier, the other is a worm gear set at the rotor shaft. When water flows into the Turbo Series meter measuring element, it contacts the multi-vaned rotor. The resulting rotor rotation is then transmitted by magnetic coupling to a sealed register or encoder. The direct magnetic drive is built to provides a reliable meter-to-registration coupling. RTS-OS-00320-EN-04 (April2014) Tamper-Proof Features: Unauthorized removal of the register or encoder is inhibited by the option of a tamper detection seal wire screw, TORX• tamper-resistant seal screw or the proprietary tamper-resistant keyed seal screw. Each can be installed at the meter site or at the factory. Construction: The Recorda II Turbo Series meter is constructed in compliance with ANSI and AWWA C701 standards. It consists of the following basic components: meter housing, interchangeable, unitized measuring element and permanently sealed direct reading registers or encoders. The measuring element consists of the transmission coupling, rotor, inlet and outlet straightening vanes with nose cones, and calibration ring assembly. The unique inlet and outlet straightening vanes minimize swirl from piping arrangements upstream as well as downstream. A strainer is recommended to help ensure optimal flow conditioning and protection for the measuring element. An integral strainer is available as an option for 1-1 /2" through 4" meter sizes. The stainless steel strainer is built into the inlet end and includes a removable cover plate to permit easy access for routine cleaning. External strainers are available in sizes 2" through 12". To simplify maintenance, the registers or encoders and measuring elements can be removed without removing the meter housing. Interchangeability of certain parts between meters also minimizes spare parts inventory investment. Meter Installation: The meter is designed for installations where flow is in one direction only. Companion flanges for installation of meters on various pipe types and sizes are available in cast iron or NL bronze as an option. See the Recorda II Turbo Series Meters User Manual for specific instructions. Product Data Sheet Recordafl• Turbo Series Meters SPECIFICATIONS Turbo Ser!.s 160 200 450 1000 2000 3500 5500 6200 Madel 1-1/2" (40 mml 2"(50mml 3"(80mml 4"(100mml 6" f150mml 8"(200mm) 10"(250mm) 12"(300mm) a.-rFianges Round AWWAUS Elliptical Elliptical or Round Round Round Round Round Round AWWA 1251b PDundCius class Typical 4 ... 200gpm 4 .. .310gpm 5 ... 550gpm 10 ... 1250gpm 20 ... 2500gpm 30 ... 4500gpm 50 ... 7000gpm 90 ... 8800gpm Open~tlng Rllnve (0.9 ... 45.4 m'lhl (0.9 ... 70.4 m'/hl (1.1 •.• 124.9 m'/hl (2.3 ... 284 m'!hr) (4.5 ... 568 m'lhl (6.8 ... 1022 m'/hl (11.4 ... 1590 m'!hl (20.5 ... 1998 m'/h) (l~:tl.S ... I Twlk .. Low Flow 2.5 gpm (0.6 m'/h) 25 gpm (0.6 m'lhl 4 gpm (0.9 m'!hl 6 gpm (1.4 m'/h) 12 gpm (2.7 m'/h) 20 gpm (45 m'/h) 30gpm (6.8 m'!hJ 65gpm (ts,..mln.) (14.8m'lhl Mu.Conttn-160gr,z: 200gpm 450gpm 1000gprn 2000gpm 3500~m 5500gpm 6200gpm Flow (36m !h) (45.4m'lhl (102.2 m'!h) (227.1 m'!h) (454m'lhl (795 /h) (1250m'/hl (1408m'lhl Maximum 200gpm 310gpm 550gpm 1250gpm 2500gr,z: 4500gpm 7000gpm 8800gpm lnternlinetot Flow (45.4m'!hl (70.4m'/h) (124.9m'h) (284m'h) (568m !h) (1022m'/hl (1590m'h) (1988 m'lhl ......_loll.t Max. c.tlniiOWI 3.8 psi (0.26 bar) Flow 3.1 psi (0.21 bar) 1.8 psi (0.12 bar) 7.3 psi (050 bar) 4.8 psi (0.33 bar) 2.5 psi (0.17 bar) 1.6 psi (0.11 bar) 0.8 psi (0.05 bar) ......... loll • ..... ~ 9.9 psi (0.68 bar) 8.3 psi (057 bar) 5 psi (0.43 bar) 17.8 psi (1.2 bar) -Flow:WIIh ..._,.. StniMt' Max. Oper8tlng 150 psi (10 bar) ......... Max. Oper8tlng 120"F(49"Q y...,per.wr. Optional IJMgnl Built Into Inlet end. -Stnln• Remova~ c<M!r plate permits access to strainer for cleaning. Optional -Avalla~ for Models 200, 450, 1000, 2000,3500, 5500 and 6200. External Slnlnet T.stPiug Standard with inteQral strainer; optional for other models. I Optional for Models 2000 and 3500. I - MATERIALS Metltr Housing Lead-free alloy (EXCEPTION: Model 6200 meter housing Is blue epoxy-coated cast iron) TultlaHHd Lead-free allov Nose c-as .,_ Thermoplastic llotor Thermoplastic llotor Rlld ... a-lngs Lubricated thermoplastic llotorThru-... ring Sapphire jewels llotorltMrlngl'hob Passivated 316 stainless steel C.llbntlon MecMnlom Stainless steel & thermoplastic Magnet Ceramic Trim Stainless steel Register Housing. Cawr Thermoplastic or bronze ~IStniMr•ndTrlm Stainlesssteel Pagel Apri/2014 Recordalf• Turbo Series Meters PHYSICAL DIMENSIONS OF METERS WITHOUT STRAINER 1----A ------! Figure 1: Sample Illustration from 8" Mode/3500 Turbo Series 160 200 200 450 1000 2000 Model Meter 1-1/2" 2" Elliptical 2" Round 3" Round 4"Round 6" Round Flanges Elliptical Meterlr 1-1/2" 2" 2" 3" 4" 6" Pipe Size (40mm) (50mm) (SOmm) (80mm) (100 mm) (150mm) Net 14.31b 14.9lb 17.41b 311b 40ib 771b Weight (6.5kg) (6.8kg) (7.9 kg) (14.1 kg) (18.1 kg) (35 kg) Shipping 16.81b 16.4lb 18.9lb 34lb 451b 89lb Weight (7.6kg) (7.4kg) (8.6kg) (15.4kg) (20.4kg) (40.4kg) Qty.of 2 2 4 4 8 8 Bolts NPTTest Porta 1" 1-1/2" 1-1/2" 2" 2" 2" Test Plug (25.4mm) (40mm) (40mm) (50mm) (50mm) (50mm) (optionlll) Length 13" 10" 10" 12" 14" 18" (A) (330mm) (254mm) (254mm) (305mm) (356mm) (457mm) Width 5-7/32" 5-27/32" 6" 7-112" 9" 11" (B) (133 mm) (148mm) (152mm) (191 mm) (229mm) (280mm) Height 6-9/32" 6-1/2" 7-3/32" 8-11/16" 9-21/32" 13-S/16" (C) (1 59mm) (165 mm) (180mm) (220mm) (245mm) (338mm) Flange 51/64" 25/32" 5/8" 3/4" 13/16" 7/8" (D) (20mm) (20mm) (16mm) (19mm) (21 mm) (22mm) Bolt Circle 4" 4-1/2" 4-3/4" 6" 7-1/2" 9-1/2" (E) (102mm) (114mm) (121 mm) (152mm) (191 mm) (241 mm) Centerline 1-27/32" 2-1/16" 2-5/8" 3-11/32" 4-5/16" 5-114" (F) (47mm) (52mm) (67mm) (85mm) (109 mm) (133 mm) Page4 NPT Test Port & Test Plug (1-1/2 ..• 8") 3500 5500 8"Round 10"Round 8" 10" (200mm) (250mm) 1231b 2101b (55.7kg) (95.3 kg) 1471b 235 1b (66.6kg) (106.6kg) 8 12 2" -(50mm) 20" 26" (508mm) (660.4 mm) 13-1/2" 16" (343mml (406.4 mm) 15-3/16" 17-15/32" (385mm) (443mm) 1" 1-1/16" (25mm) (27mm) 11-3/4" 14-1 /4" (298mm) (362mm) 6-3/8" 7-7/8" (162mm) (199.4 mm) 6200 12"Round 12" (300mm) 2621b (118.8 kg) 2861b (129.7 kg) 12 - 19-11/16" (500mm) 19" (482mm) 19-11/16" (500mm) 1.26" (32mm) 17" (432mm) 8-7/8" -(226mm) Apri/2014 RecordaJ/• Turbo Series Meters PRESSURE LOSS CHART FOR METERS WITHOUT STRAINER Rate of flow In gallons per minute (gpm) "' "' 0 .....I . cu""": '-Ill ~c; "' cu .... 0.. ,...e) I~ Its•' tit tot' 3 If t?Stilk../t. p~J.r~~~r at-J_ '). £.4 3 ,, 1 10 100 ' • • • 20 .., 60 1!0 25 20 15 10 5 0 1000 10000 200 400 ... 800 2000 4000 8000 • I • • I-. lA I. I / .Y"/1 ..};' ~ ...... PRESSURE LOSS CHART FOR METERS WITH INTEGRAL STRAINER Rate of flow in gallons per minute (gpm) 10 100 1000 ' 4 • • 20 .. 60 80 200 ... ... 800 25 20 -- ~ 15 • !! ~ II I I 10 -- / 5 / / ~ 0 Page6 Apri/2014 ZURN. Model375 WILKINS Reduced Pressure Principle Assembly Application Designed for installation on potable water lines to protect against both backsiphonage and backpressure of contami- nated water into the potable water supply. The Model 375 provides protection where a potential health hazard exists. Ideal for use where lead-free• valves are required Standards Compliance (Unless Otherwise Noted, Sizes 2 1/2" Thru 10") • ASSE® Listed 1013 • IAPMO® Listed • Certified to NSF/ANSI372' by IAPMO R&T • CSA® Certified (2 1/2' thru 8") • AWWA Compliant C511 , and C550 • FM® Approved • UL® Classified • C-UL® Classified • NYC MEA 49-01-M Vol 2 • Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California. • NSF® Listed-Standard 61, Annex G' '(0.25% MAX. WEIGHTED AVERAGE LEAD CONTENT) Materials Main valve body Access covers Coatings Internals Ductile Iron ASTM A 536 Grade 4 Ductile Iron ASTM A 536 Grade 4 FDA Approved fusion epoxy finish Stainless steel, 300 Series NORYLTM, NSF Listed Fasteners Seal rings 0-rings Springs Sensing line Features Stainless Steel, 300 Series EPDM (FDA approved} Buna Nitrile (FDA approved} Stainless Steel, 300 Series Stainless Steel, braided hose Sizes: 21/2", 3", 4', 6", 8", 10' Maximum working water pressure Maximum working water temperature Hydrostatic test pressure End connections (Grooved for steel pipe) (Flanged) Relief Valve discharge port: 2 1/2"-6' 2.75 sq. in. a· -10" 3.69 sq. in. Attention: Model 375 (flange body) and Model 375A (grooved body) have different lay lengths. 175 PSI 140•F 350 PSI AWWAC606 ANSI 816.1 Class 125 Dimensions & (do not include pkg.) MODEL 375 SIZE A BLESS GATE VALVES c 0 E OS&Y OPEN E OS&Y CLOSED (:,:::.-: .. 1 Options (Suffixes can be combined) 0 -with NRS shut-off valves (standard) 0 FS -with cast iron wye type strainer (flanged only} 0 FSC -withepoxycoatedwyetypestrainer(flangedonly) 0 G -with grooved end NRS gate valves 0 GF -with grooved inlet gate connection and flanged outlet gate connection 0 FG -with flanged inlet gate connection and grooved outlet gate connection 0 L -less shut-off valves (flanged body connections) 0 MS -with Integral Relief Valve Monitor Switch 0 OSY -with OS& Y gate valves 0 PI -with Post Indicator gate valve (3"-10") 0 DOM -with Clow gate valves, 51% Buy American Act Compliant Accessories 0 Repair kit (rubber only) 0 Thermal expansion tank (Model XT) 0 OS & Y Gate valve tamper switch (OSY-40) 0 Air gap (Model AG) 0 Electronic Solenoid Timer (Model EST) 0 QT-SET Quick Test Fitting Set E NRS GATE F G WTl-OJT WITH WITH H GATE NRS OS&Y GATE VALVES VALVES VALVES ln. lmm ln. I mm ln. lmm in. lmrn ill lmr in, lm1 ln. lmm ln. m11 ln. lmrr 1n. lmm ln. mm llbs. kg lbs. ka ht1a. ka 12112 '65 3 78. 115 Tlf f4( "1/41111-4 31~ 19! 1R ::1/F 14 l:l 28!19 12 18 s 17114 1331~19f 17 111 r 9112 ill! 11:1 114 131: 112 1/S [21 114 10 If 122 11: 115 II~ ~1 0 12! 114 10 1453l~l11 1 11: 115 Jie 91 6314 Zum Industries, LLC I Wilkins 1747 Commerce Way, Paso Robles. CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 In Canada I Zum Industries Limited 3544 Nashua Drive, Mississauga, Ontario L4V 1 L2 Ph. 905-405-8272. Fax 905-405-1292 -·•urn.aam 1/~ 104t I 60 17. 111: ".2 !21 4:! 31~ 108E l BO 127 :J. 188:3 13' 98 15! 17_~ 8! 1211 171 19: 18! Rev. C Date: 12113 Document No. BF-375 Patent No. 5, 913, 331 Product No. Model375 Page 1 of2 Flow Characteristics 0.0 Ill 20 USA. 8 ... 15 ~~ 10 ~=-5 I= ll! 11. 0 MODEL 375 2 112", 3" & 4" (STANDARD & METRIC) FLOW RA lES (Vs) 12.6 25.2 37.9 2 112" (85mm) -"(80mtn) - - = 1:---· ·-- 0 Ralcd Flow (etl.lblithed by _.,.ol....,ciet) 50.5 ~ lei- 4"(1;:,) /.. ::j ;;;/ -\::,..... L 138 (/) 104 ~ 69 ~ i (/)c!!. 35 (/) ~ 8' I'( fr-(JJ..,~ l,rtJf ~r o 200 cf ,,.,.., 400 Z, 'J.-Jr . fLOW RATES (OPM) 0 11. 100 800 ~ ,, ~~Jr Jf-.J ~ t-z,'l.r MODEL 375 6", 8" & 10• (STANDARD & METRIC) 0.0 63.1 FLOW RATES (118) 126.2 ., 20 § 15 ~! 10 Ill!:. ; 5 II. 0 ~ --... (150oml,..!.. ~ .. ~) --- 0 1000 2000 fLOW RATES (GPIII) ~icallnstallation Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a minimum of 12" (305mm) and a maximum of 30' (762mm) above adequate drains with sufficient side clearance for test- ing and maintenance. The installation shall be made so that no part of the unit can be submerged. DIRECTION OF FLOW ~ INDOOR INSTALLATION (375GF) Specifications 189.3 -~Womml = --- 3000 252.4 138 ~ 104 _, 69 ~i ~c!!. 35 0 4000 ~ 11. Capacity lhru Schedule 40 Pipe (GPM} Pipe size 21/2' 3" 4" 6" 8' 10" 12" I PROTECTIVE I ENCLOSUR£ I 5 ftlsec 7.5 ftlsec 75 112 115 173 198 298 450 675 780 1169 1229 1643 1763 2644 DIRECTION OF FLOW ~ OUTDOOR INSTALLATION 10ft/sec 15ft/sec 149 224 230 346 397 595 900 1351 1559 2339 2456 3687 3525 5288 The Reduced Pressure Principle Backflow Prevention Assembly shall be certified to NSF/ANSI 372, ASSE® Listed 1013, and supplied with full port gate valves. The main body and access cover shall be epoxy coated ductile iron (ASTM A 536 Grade 4), the seat ring and check valve shall be NORYL rM, the stem shall be stainless steel (ASTM A 276) and the seat ctisc elasto- mers shall be EPDM. The checks and the relief valve shall be accessible for maintenance without removing the device from the line. The Reduced Pressure Principle Backflow Prevention Assembly shall be a ZURN WILKINS Model 375. Zurn lndustrtee, LLC I Wilkins 1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855.:663-9876, Fax 805-238-5766 In Canada I Zum lnduatrles Umited 3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292 -.zurn.cOIII Page 2 of 2 rEo-er.s ------~--------- APPENDIXB FIRE PROTECTION SERVICE DATA FIRE FLOW REQUIREMENT AND FIRE SPRINKLER FLOW REQUIREMENT From: To: Subject: Date: Andrew, Gregorv Rvan Andrew Oyen RE: Robertson Ranch PA 8 Senior Apartment Housing -Fire Flow Wednesday, November 04, 2015 1:42:35 PM Thank for the update. Cll Y 0 ~ CARLSBAD Fire Department Gregory L Ryan Deputy Fire Marshal 1635 Faraday Avenue Carlsbad, CA 92008 Gregory Ryan@carlsbadca goy 01760.602.4665 D 1760.602.4663 M I 760.484.4442 From: Andrew Oven [mailto:Andrew@dwilsoneng.com] Sent: Wednesday, November 04, 2015 10:18 AM To: Gregory Ryan Subject: RE : Robertson Ranch PA 8 Senior Apartment Housing-Fire Flow Greg, Thanks for the review. At 93,787 SF for Type VA, flow requirement is 5,500 gpm. Half of that is 2,750 gpm which is what I will use for the calculations plus adding the fire sprinkler flow. Andrew Oven, P.E. Dexter Wilson Engineering, Inc. (760) 438-4422 From: Gregory Ryan [majlto:Gregory.Ryan@carlsbadca.goy] Sent: Tuesday, November 03, 2015 4:39PM To: Andrew Oven Subject: RE: Robertson Ranch PA 8 Senior Apartment Housing-Fire Flow Andrew, CFC Appx. BB Sec. BB104 states that the calculated area shall be the total floor area of all floor levels within the exterior walls, and under the horizontal projections of the roof of a building unless Type 1A or Type 1B construction. The area separations you describe would not constitute area separations. BB104.2 Area separation. States, Portions of buildings which are separated by one or more 4-hour area separation walls constructed in accordance with the building code, without openings and provided with a 30-inch parapet, are allowed to be considered as separate fire areas. Remember, apartments fall under Title 19 and 24 and are regulated by the State Fire Marshal. In this instance you will not be granted the reduction in area because of separations. Two, the square footage must be taken from the "drip-line" of the eaves. Lastly, given the nature of the use of this building any reduction is the required fire flow will ultimately require more restrictive elements as cited above. C I I 0 ~ CARLSBAD Fire Department Gregory L Ryan Deputy Fire Marshal 1635 Faraday Avenue Carlsbad, CA 92008 Gregory Ryan@carlsbadca goy 01760.602.4665 D 1760.602.4663 M I 760.484.4442 From: Andrew Oven [majlto-Andrew@dwjlsoneng com] Sent: Tuesday, November 03, 2015 3:58 PM To: Gregory Ryan Cc: Erick Escobedo (eescobedo@alljanceeng com) Subject: Robertson Ranch PA 8 Senior Apartment Housing-Fire Flow Greg, Attached are the first four sheets of the Architectural plan set. The third sheet, G3, includes a fire area calculation. My understanding is that these three fire areas are separated by fire rated walls which allow for the fire hydrant flow requirement to be determined individually for each area. Thus, the largest area is Fire Area 2 at 33,876 SF. With Type VA construction, the fire flow requirement is 3,250 gpm. Using a 50% reduction factor for fire sprinkler systems, the fire hydrant flow requirement is 1,625 gpm. I want to make sure with you that I am understanding this correctly. Would you review this and let me know if you concur? Thank you. Andrew Oven, P.E. Dexter Wilson Engineering, Inc. 2234 Faraday Avenue Carlsbad, CA 92008 (760) 438-4422 From: To: Cc: Subject: Date: Andrew Oyen "Erjck Escobedo" Robertson Ranch Senior Building Friday, November 13, 2015 1:31:33 PM Andrew, The fire sprinkler demand for the above referenced building id 63.2 GPM. Please let me know if you require any additional information. Thank You, Charles P. Sampson Jr. INNOVATIVE FIRE PROTECTION, INC. -- 8779 Cottonwood Ave. Ste. 101 Santee, CA 92071 Tel: 619.593.8200 Fax: 619.593.9133 eel: 619.520.9226 Charlie@ifpinc.net APPENDIXC CALCULATIONS FOR FIRE HYDRANT FLOW AND FIRE SPRINKLER FLOW --,.--- DEXTER WILSON ENGINEERING, INC. I . I I ' ' ' IH"il"' ~Vt·ti,'A...,~-' G~,~: I I -~ I I r l I I I : I II I + I I ' I DEXTER WILSON ENGINEERING, INC. I , I I ' I ' I-I I I DEXTER WILSON ENGINEERING, INC. I ' I I I I . 1 ~ 1 2~ 4. ~ fl:t-f/{;6 I ' I ) ~~;,' ~"'"~..,~ I . of~ 1 ~~ I I J I ! I I I I I ' I l I I I I I ' ! i . I 5za --o"3."> -~ts~ R~ ... :i08N6. DEXTER WILSON ENGINEERING, INC. • I i a 'f M DEXTER WILSON ENGINEERING, INC. f I ~ j I I . . /o~.5 1$" : 01'0 ( t lo5f = r ; ! I I ' 7(.;.' b f·n' I , f ~) I 2-Jl.vk- • I .I I ') •I I l 13-:-20 P. E. (Civil) License Review Manual, Volume V 'Dlble 2.2 also shows the equivalent length of pipe for various fittings in a tabular form. Thble 2.2 Equivalent Length of Pipe for Various Fittings ,. ..... l'lfe DlaMir ..... f.tnllll "-" .._ ... lliL IlL .... ZIL JIL .... IlL IlL IIIL IZIL MIL IIIL IIIL .... .... .... . ... . ... Clttwlw,.,. u u u u u u 15 u u u u u II ll 14 17 21 Zl Cite YIIWI, ! ... 11 17 25 lt .. f1 .. us ua 1!5 ZID • • Dl .. • .. 711 GIMYIIWI,.-II Z7 a sc • Ill Ill Zll • Dl • • • 541 m .. 1 ... I,JI ~ltnhl ... u IS zz a 4Z 51 IS 110 1411 Ia • ZZI 2!1 211 • ca • a aa ..... u u 11 14 II 25 • 51 • 77 • Ill 121 Dll • 2111 ZID • sr...~ ... ..& u SJ ' IZ 17 zz 34 .. 57 f1 75 • • I. 131 Dl • • Sllllln ... -& u SJ ' ll 17 zz 34 44 57 17 75 • • Ill 131 Ul • • ~-. .<!:... Ll u u 15 1.1 u ll 14 II a Zl Z7 • 34 4Z sz II n •a..• u u u u Ll II 17 n • Jl J1 cz ~ sz a • • Ill •En. .... llllhl Ll u u u u u II 14 • a Zl Z7 • • 4Z 5Z 11 7Z ........... lJ u • IJ II Zl • • • 7Z a Ill Ill I2S 151 • 211 210 •a. u u u u 17 5.0 u 10 L1 IS 17 II n Zl • J1 44 5Z a...,-.. :::j:-u u u u u 5J u lZ IS II • Zl 25 3D • • sz II ............ ~ UD.V4 u t7 u u Ll 11 17 Zl • Jl Jl 4Z • 5Z a • • Ill t1 UD.tn Ll u u u u u II L1 • II zz H • ll ll 47 • • UD •ll4 u u u u u u 15 u u u u u II IZ 14 17 Zl Zl ,.... CIICictl• ~~, • v• u u 1.1 1S 17 u 7A II L1 IS 17 II Zl Zl • J7 .. 5Z J/IJ • 11'2 u u u 1.1 u 17 5.1 7J u IZ D IS 17 • 2% f1 31 • JID .J/4 u u u u u u u u u u u u II IZ 14 17 Zl Zl (Ref: Gallant, Robert N., "Sizing Pipe for Uquids and Vapors", Chemical Engineering, Page 104, February 24, 1969.) ·. .... f1 ,. ... • Ja m ·.m IZ IJI IZ Jill • 10 131 71 Z7 • • 71 \ SPECIFICATION SHEE T LEAD FREE. MasterSeries® LF856 Double Check Detector Backflow Prevention Assemblies (Type II) Size: 2W' -10" The FEBCO MasterSelies LF856 Double Check Detector Assemblies are designOO to protect drilki'lg water supples from dangerous cross-con- nections in accordance with national pkJrnbi"lg codes and water authority requirements for non-health hazard non-potable service applcations such as irrigation, fire ine, or industrial processing. This Backflow Assentlly is primar- ily used for protection of drinking water systems ll1d fre sprinkler systems, where Local Governing Code mandates protection from non-potable quality water being punped or ~ back into the pol<tje water system. Features Main Yalve: • lnine Se!viceOOie ~ • No Special Tools ~uirOO for ServiOOg • CaptlJ"ed ModUar Spri1g Assemtjy • Reversible & Replacaable llscs • Fteld AePaceable Seats • D.JctJe Iron WNe Body Design • Stainless Steel 01eck Canponen1s • Wnterization featl.le Y.1th disc retainers and v!We body ctain ports • Oapper 01eck Assant*i • Commonaity between 1st & 2nd 01eck Components • CaptlJ"ed 0-rilg Desigl Audiary Bypass: • Compact Bypass Design; Rernai1s 'M1ti1 Main WNe Assembly Profile • lnirle Selviceable ~' Backflow Asserrdy • No Special Tods Req..i'ed for SeM:i1g • Reid RepicK:eable Seats & Discs • Detect Potential Underground Water Leaks • Detect Unauthorized Water Usage Job Name---------------- Job Location --------------- Engineer ----------------- Approvru ----------------- ES-F-LF856 Model LF856 Double Check Detector Assembly Specifications The FEBCO Mastii"Series LF856 Druble 01eck Detector VaNe Assembly shal be instaled on the potOOie water supply ll1d at each poilt of cross- connection to protect against possi:Jie backpresslze and backsiphonage conditions for non-health hazard o.e., pollutant) appbtions. The asserntjy shal consist of a main line vatve body composed of two (2) indepmdently acting approved ctGwer style check modules with replaceable seats and disc rubbers. SeMcng of both check modules does not requi"e any special tools and are accessed through ildependent top entry covers. This assembly shal be fitted with approved UUFM irle!/rutlet resient seated shutoff valves and oontain four (4) poperty located resilent seated test cocks as specified by AW'NA Standcrd C510. The aLI)(jilly bypass hi cootai1s a %'x ~· {16 x 19rrvn) Water Meter that complies with ftNSl/AWNA Standa'd C700 CQl4'Jied with an approved check asserri:Jiy. The bypass lire is designed to detect leaks or unauthorized water usage of the water system whie protecting against possible backpressure and backsiP1onage conditions for non-health hazard o.e., pollutoot) application. Flow and pressLfe loss performance parameters shal meet the reqWements of AWNA Standa'd C510. The information contained herein is not intended to replace the fufl product instalation and safety nformation avaiable or the experience of a trained product instaler. You are required to thorougtvy read all installation instruc- tions and product safety information before beginning the installation of this product. "The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight. Contractor _____________ ......_ __ _ Approval ----------------- Contractor's P.O. No. -------------.,.-- Representative FEBCO product speclllca~ons In U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact FEBCO Technical Service FEBCO reserves 11le r1ght to change or modify product design, construction, spec~icaHons, or materials wltllOut pr1or notice and without Incurring any obligation to make such changes and modifications on FEBCO products previously or subsequently sold. Options -Suffix OSY: ULIFM ~oved OS&Y Gate VrJNes /ANSI/AW#A C515 Compian~ CFM: Totalizing Cubic feet/rrin 518' x 314' Wfti.PI Meter /At-SI/AW#A C700 CorrlJiarrt) GPM: Totaizilg Galons/rm 5/S'x 314' Water Meter ~/AW#A C700 Corr4:lli~ LG: Less Shutoff valves; This is NOT 111 APPROVED ASSEMBLY Example Ordering Descrtptlons: 4' LF856-0SY-GPM -VaiveAssem~fitted YMh OS&Y SllJtoffWJes & GalkJn Feet per Mnrte Water Meter 4' LF856-0SY-CFM-Viive Assembly fitted with OS&Y Shutoff Vrlves, Qbic feet per Minute Water Meter Assembly Flow Orientation: o Horizontal & Vatical Up (2W -10)-Approved by FCCCHR-USC, ~>SSE, cULus, FM, IAPMO Materials Below is a general material list ci the Model LF856. /lJ assentlles' size 21h' throJ!jl1 0' is sinilar in malarias and conslructial. Please cootact yw: klcal FE8CO Representative if you recJlie further ilformation. Main Viive 8cxtf. Ductie iron Grade 65-45-12 Coating: Fusion epoxy coated internal CJld external AW#AC550 Shutoff V<Wes: OS&Y resient wedge gate valves AWWA C515 (ULIFM) Check Seats: Disc Hdder: Bastomer Disc Spring: Oamp: Stainless Steel Stainless Steel Sl~cone StOOess Steel AW#A C606 (10' Only) Approvals o Apprt:Ned by the Foundation for Cross-Connection Control and Hydral.jc Research at The University ci Southern Caifomia (FCCCHR-USC) 0 /~SEE 1048 Listed o **UL Classified (US & Ganada) o .. FM Approved o IAPMO o AW#A StCJldard C510 Compli<Vrt o End Connections: Compmt to ASME 816.1 Class 125 & AW#A Oass D Fla1ge **Assam~ configued YMh ULIFM Apprt:Ned OS&Y Fm Gate VcWes. Less gate valve asserrtllies llll not ULIFM approved configJralions. 9 1048 Pressure -Temperature Max. Working Presrue: 175 psi (12.1 tal Min. Workilg Pressure: 1 0 psi (0.7 taj Hyctostatic Test Pres.ue: 350 psi (24.1 tal Hyctostatic Safety Presst.re: 700 psi (48.3 tal Temperature Range: 33"F -140"F (o.s·c-60"C) eontroous Dimensions & Weights Below are the r10111ilal dimensions and physical weigrts for the Model LF856 size 21h' 1tlroug11 o·. Alkmances rrust be made for normal nmtiacturing tolercn:es. Please visit our website to download a OOfJi of this product's installatioo instructions, or contact your local FEBCO Representative for more information. B A ------------------------------~ Model LF866 Assemblies SIZE A ill Ill. mm 2'h 4~ 1035 3 41 7/o 1064 4 46~ 1175 6 56 1422 8 65 1651 10 72% 1845 B 1n. 25'h 25% 28 34% 417'• 46% DIMENSIONS c E .. mm in mm it mm 648 10 254 16% 416 651 10 254 22'h 565 711 10% 257 23~ 591 883 12% 324 30'/o 765 1061 15% 397 37% 959 1178 15% 397 48 1219 " Indicates nominal dimensions with OSY Gate Valves (Full Open Position) ... Indicates weight of complete Backflow Assemblies with specified Gate Valves F G H 1n. mm in. mm Ill mm 41h 114 7% 181 133/o 340 4'h 114 7% 187 133/o 340 5'h 140 8% 206 14 356 6'h 165 97/o 251 15 381 7 178 11'/o 283 15% 400 9 229 12"/o 314 15% 400 OSY bs. kg. 245 111 271 123 338 153 515 234 826 375 1234 560 Performance Flow capacity chart identifies valve perfoonance based upon rated water Velocity up to 2Clps. • Maximum service flow rate is delermiled by maximum rated Velocity of 7.5fps. • AWNA ManJal M-22 (AppErdx C) recanmends that the maxrm.m water Velocity in the services be not more than 1 Clps. • UL ftow rate is detemined by typicaly rated Velocity of 15 feeVsec. 22 31 18 16 114 112 ·~ I B 4 2 0 II I I I I I I I I I I I I I I I I I I I I I I I I I I ____... I I I I I I 0 25 !Ill J5 100 125 15l) 1J5 2110 225 2lill 2J5 300 325 31111 Gl'lll 22 31 18 I'a ~ :: f. 10 f I "1.8 4 2 0 18 18 14 }12 ~10 I 8 ... 8 0 2 0 0 284 568 852 1136 tm a• (LF856} ...-- 5l) 100 319 4" (LF856) ~ w ~ • SlnlceRow I I I I I I I I I I I 151 311 757 u SeniceAow I I I I I I I 250 I I I I I I 'llll*dRow I I I I I I A I ~ I ~ I I I I I I I 300 31111 400 4!10 !1111 &PM 1136 1514 trn 14.7 ~ lpl Rial Row "'JJ.IIIIId Row I I I I I I I I I / I __..,.. I .....JI' I I I 100 310 300 400 5l)O 800 1111 _, GPIII 319 1136 1893 2650 tm 7.5 12.8 19.1 • 18 16 14 }12 ( 10 I • ... 6 4 2 0 18 18 14 J12 I'D I • ... & 4 2 0 0 0 11 18 14 J12 ( 10 t 8 ... 6 • 2 0 0 6" (LF856) 310 757 8" (LF856} Gl 1514 108 (lf856) 800 2271 • 2271 I I I I I I I 7.5 .. I I I I I I 10111 3785 11A 1211 I I : _l_ I ____,.... 1400 s:m I I 17.0 Slnlce Row ,..... Flow 'll.lllllldfluw I • m 1310 4543 I I I T T I I I I 1310 4543 7.5 Slnlceflow I I I I I I I 1800 6814 7.5 I I I I T I I I I I I I I I 1100 --GPIII 6057 7571 Q5 trn 11.5 153 • Ratlld Flaw "'ll.llatad Flow I I I I I . I A I / I .J--l I 2400 ~ u 3000 11356 I I t -&PM 13627 pn 14.1 lpl A Watts Water Technologies Company ES-F-LF856 1515 USA: Tel: (800) 767-1234 • Fax: (BOO) 788-4491 • FEBCOonllne.com c-da: Tel: (905) 332-4090 • Fax: (905) 332-7068 • FEBCOQnllne.ca Latin America: (52) 81-1001-6600 • Fax: (52) 81-8000-7091 • FEBCOonRne.com C 2015 FEBCO I J I ~ ~~ PARCEL A 4.i8AC 2600 GAGE DRIVE BLDG 1 FF=36.00 PA0=34.75 · 2600 GAGE DRIVE BLDG 1 fF=36.00 PA0=34.75 --~----- (( D ~tt () lA R A. I-\ c1-t S ~V\ t'ov--f-t cusi~ R--~v~ fir-e-S7~~ II -u -2-Qis-" ~fy ~ ~ I I I I I I I I I I I I I I