HomeMy WebLinkAboutCT 03-12; PROMONTORY BUS. PARK LOT 21; PRELIMINAY STORM WATER MANAGEMENT PLAN; 2003-08-29B RICK ENGINEERING ®COMPANY PRELIMINARY STORM WATER MANAGEMENT PLAN FOR LOT 21, CARLSBAD TRACT 74-21 JOB NO. 14437 AUGUST 29, 2003 ------------------------- I I I I I I I I I I I I, 'I I I I I I I I PRELIMINARY STORM'WATER MANAGEMENT PLAN FOR LOT 21, CARLSBAD TRACT 74-21 Job Number 14437 August 29, 2003 Roger L. Ball RCE27678 Prepared by: Rick Engineering Company 5620 Friars Road San Diego, California 92110-2596 (619) 291-0707 I 'I I I I I I I I I I I I I I , I I I I TABLE OF CONTENTS 1.0 Introduction ............................................................. : ................................................................. 1 2.0 Vicinity Map ............................................................................................................................. 2 . . 3.0 Water Quality Requirements Post-Construction ................................................................•...... .3 4.0 Pollutants and Conditions of Concern ...................................................................................... 5 5.0 Permanent Storm Water Best Management Practices (BMPs) ................................................. 6 6.0 Anticipated Maintenance Condition(s) ................................................................................... 10 7.0 Summary ................................................................................................................................. 13 APPENDICES A. AES 2000 Ratior .. al Method Analysis: 100-Year, 6-Hour Rational Method Analysis for On-site Hydrology B. Calculations for Water Quality Treatment Flow Requirements C. KriStar Enterprises, Inc.: Water Quality Treatment Capacities, Details, and Costs D. Suntree Technologies: Water Quality Treatment Capacities, Details, and Costs E. CDS Technologies In-line Treatment Units: Water Quality Treatment Capacities, Details, and Costs F. Summary of Approximate Costs for Treatment Control BMPs MAP POCKET 1. Preliminary Drainage Map for Proposed On-site Condition Prepared By: Rick Engineering Company August 29,2003 ST:rh\R:\d:..14437\Report\S\VMP (OOl).doc I I I I I 'I I I I I I I I I I I I I I' I I 1.0 INTRODUCTION This preliminary technical report summarizes stonn water quality treatment based on exisitmg conditions on Lot 21, of Carlsbad Tract 74-21 located in the City of Carlsbad. The project , entails subdividing an existing 5.38 acre site consisting of6 buildings andparkingJot around its perimeter. Access exists from Loker Avenue via a driveway in the Northbound direction. 'Please refer to the Vicinity Map (next page) for the approximate project location. The scope of this project is to detennine the flow rates contributing to each of the three existing catch basins / inlets on site and the appropriate water quality devices to be selected based on the calculated Qs. There will be no construction activities taking place on the project. National Pollutant Discharge Elimination System NPDES requirements are contained in Section 402(P) of the federal Clean Water Act. These requirements are implemented through permits issued by the State Water Resources Control Board (SWRCB) or the local California Regional Water Quality Control B..)ard (CRWQCB) in which the project is located. These requirements are discussed in further detail within Section 3.0 of this report. This project is exempt from permanent storm water requirements as defined by the Municipal Storm Water Permit. Section F.l.b.(2)(a) Qfthy Municipal Pennit states that projects adding or creating at least 5,000 square feet of impervious surfaces on an already developed site are subject to SUSMP requirements. This project proposes no improvements and thus no new impervious surfaces. This preliminary technical report is intended to comply with the City of Carlsbad requirement to provide a Stonn Water Management Plan with application submittals. BMP options, flow calculation and maintenance requirements are provided, however it is emphasized that per the California Regional Water Quality Control Board Municipal Permit this project should not be subject to the requirement for these water quality treatment devices. 'Prepared By: Rick Engineering Company 1 August 29,2003 ST:th\R:\d_14437\Report\SWMP (OOl).doc I I I I I I I 'I I I I 'I I I I I I I I 2.0 VICINITY MAP Prepared By: Rick Engineering Company 2 August 29, 2003 ST:rh\R:\d _14437\Report\SWMP (001 ).doc ·1 I I I I I I I I I I I I I il I I I I 3.0 WATER QUALITY REQUIREMENTS FOR POST-CONSTRUCTION The California Regional Water Quality Control. Board, San Diego Region is the State Agency· tasked with regulating storm water discharges in the City of San Di<;:go, the County of San biego, the Port of San Diego, and 17 other cities in the region (hereafter referred to as . Copermittees). On February 21,2001 the Regional Board adopted a new Municipal Storm Water Permit, Order No. 2001-01 (Municipal Permit). This Municipal Permit coupled with the existing Statewide General Construction Permit, Order No. 99-08-DWQ, places greater requirements on new development. The Municipal Permit requires municipalities to develop and implement Jurisdictional Urban Runoff Management Programs (JURMP). The JURMp contains several components. These components include: • Land-Use Planning for New Development and Redevelopment • Construction • Existing Development • Education • Illicit Discharge Detection and Elimination • Public Participation • Assessment of Jurisdictional URMP Effectiveness • Fiscal Analysis The Land Use Planning for New Development and Redevelopment Component requires each Copermittee to modify their development project approval processes. Prior to project approval, Copermittees are tasked with conditioning each proposed project to implement measures that ensure pollutants and runoff from the development will be reduced. This reduction of pollutants is accomplished through the development ofproject requirements in local permits. These conditions include specific requirements for project proponents, such as: • Implementing source control B<;:st Management Practices (BMPs) for all applicable development projects; Prepared By: Rick Engineering Company 3 August 29,2003 ST:rh\R:\d_14437\Report\SWMP (001 ).doc I I I I I I I I I I I I I I I I I I I • Implementing site design/landscape characteristics which maximize infiltration, provide . retention, slow runoff ~d minimize impervious land coverage. for all development:projects; and • Providing proof of a mechanism which will ensure on going long-term maintenance of all structural Post-Construction BMPs Another constituent of the Land Use Planning for New Development and Redevelopmem.t Component of the Municipal Permit requires Copermittees to provide SUSMPs to reduce pollutants from all new c1evelopment and significant redevelopment projects falling under specific priority project categories or locations. The SUSMP includes the use of structural treatment BMPs. These BMPs should be located to infiltrate, filter or treat a required volume or flow prior to its discharge to any receiving water body supporting beneficial uses. This volume or flow based BMP treatment is known as Numeric Sizing Criteria. The San Diego Final Model Standard Urban Storm Water Mitigation Plan (San Diego SUSMP) developed by the Copermittees and approved by the SDRWQCB on June 12,2002 provides an implementation guide for compliance with the Municipal Permit. Prepared By: Rick Engineering Company 4 August 29,2003 ST:rh\R:\d_14437\RllPort\sWMP(001 ).doc I I I I I I I I I I I I I I I I I I II 4.0 POLLUTANTS AND CONDITIONS OF CONCERN Pollutants from the Project Area Typical storm water pollutants that may be anticipated from a commercial development such as this property include trash and debris that are contributed by humans and landscaping, as well as oil and grease that may result from leaking vehicles. Pesticides may pose problems when. excessive applications containing toxic levels of its active component result in runoff While the site is not expected to generate a large volume of sediment since no construction activities will take place, some sediment will be tracked in by cars and a small amount may be generated on site. This sediment is defined as a pollutant, and may also contain attached polhltants such as heavy metals. The majo:i.ty of these typical pollutants will be transported by low flows occurring during the initial stage of a storm event. Pollutants of Concern in Receiving Waters According to the "Water Quality Control Plan for the San Diego Basin (9Y', dated September 8, 1994, the Lot 21 property is within the Agua Hedionda Hydrologic Subarea of the San Marcos Hydrologic Area within the Carlsbad Hydrologic Unit. The corresponding number designation is 904.51 (Region '9', Hydrologic Unit '04', Hydrologic An~a '5', Hydrologic Subarea '1 '). Existing condition collects runoff in a drain network that will discharge into Agua Hedionda Creek. Agua Hedionda Creek drains west into Agua Hedionda Lagoon and ultimatelY:drains into the Pacific Ocean. Lot 21 does not discharge directly into any impaired water bodies and the property is therefore not subject to the requirements of a 303(d) listings. Prepared By: Rick Engineering Company 5 August 29, 2003 ST:rh\R.:\d_14437\Report\SWMP (OOl).doc I I I I I I I I I I I I I I I I I I I 5.0 PERMANENT STORM WATER BEST MANAGEMENT PRACTICES (BMPs) In order to meet the requirements for termination of coverage under the Municipal Pennit,and the San Diego SUSMP requirements, a proj ect such as this would incorporate a treatment train of non-structural and structural BMPs to the maximum extent practicable (MEP). The Stom Water Standards manual indicates projects shall incorporate the following BMPs into the project design: Site Design BMPs Source Control BMPs BMPs for Individual Priority Project Categories (these are site design and source control) Treatment Control BMPs In general, site design, source control, and category specific BMPs are non-structural; and treatment control BMPs are structural. A more detailed description of each type ofBMP is discussed below. Site Design Site design BMPs are designed to maintain or reduce pre-development erosion and protect stream habitat. Since the proposed subdivision will not result in any disturbance of the native vegetation, site design BMPs are not required for this project. However, the discharge within an existing storm drain network would be treated by structural treatment control facilities, which are discussed below. Source Control Source control BMPs are generally non-structural and are intended to reduce the quantity of pollutants entering the storm drain system. This can be accomplished by employing integrated pest management (IPM) principles that includes minimizing the use of pesticides on site, Prepared By: Rick Engineering Company 6 . August 29, 2003 ST:rh\R:\d_14437\Report\sWMP (OOl).doc I I I I I I I I I I I I I I I II I I I utilizing efficient irrigation systems to prevent runoff from landscaping, through public education (e.g., storm water conveyance system stenciling and signage, pollution prevention literature), as well as street sweeping. Public education is a preventative measure to reduce potential storm waterpollution at its source. Public education typically includes literature describing storm water pollution prevention, resources for reduction, and proper disposal techniques for potential storm water pollutants. Stenciled inlets are another form of public education that informs the general public that the storm drain system discharges directly into downstream water bodies~ The owner of a property subject to source control BMP's would be responsible for removal and disposal of waste material from the project site and maintaining landscaping on the project site in 'a manner that would prevent soil erosion and minimize sediment transport. Street sweeping physically removes sediment and trash from the roadways and parking areas to prevent it from entering the storm drain system. Site specific source control BMPs would be described in greater detail within the PCSWOMP as required for termination of coverage when under the General Construction Permit. Treatment Control Treatment control BMPs will treat, infiltrate, or filter a specified amo1,l11t of runoff from the project based on the numeric sizing criteria described in the Storm Water Standards manual (and the Municipal Permit Order No. 2001-01). The amount ofrunoffthat must be ,treated maybe calculated using either the volume-based criteria or flow-based criteria, depending on the type of BMP selected to meet this requirement. The Storm Water Standards manual provides several criteria for calculating treatment volume of runoff for volume-based BMPs' or treatment flow for flow-based BMPs. The following discussion of structural BMPs describes the treatment control BMPs which could be used to address the pollutants of concern associated with a project such as this. Prepared By: Rick Engineering Company 7 August 29,2003 ST:rh\R:\d_14437\Report\sWMP (OOl).doc I I I I I I I I I- I I I I I I I I I I Structural BMPs For Treatment Control Structural BMPs on this type of project may include in-line storm water treatment units andlor catch basin/inlet filter inserts. Following are descriptions of Structural BMP options that could be used on a site such as Lot 21. In-line storm water treatment units (with absorbent booms added) are mechanical separatots that physically reduce sediment, trash, debris, and oil and grease from the flow and pesticides that attach to sediment. In-line storm water treatment units are installed after the last inlet to the storm water conveyance system and before the system connects to the existing off-site: storm drain system. In-line storm water treatm~nt units are flow-based BMPs. These BMPs would be incorporated to meet the requirements of the Storm Water Standards manual and would be sized using a flow-based numeric sizing criteria. Catch basin/inlet filter inserts (with absorbent booms added) are flow-based BMPs. Catch basin/inlet filter inserts reduce sediment, trash, debris, oil and grease from the flow and pesticides that attach to sediment. The catch basin/inlet filter inserts must be capable of treating the required treatment flow for the area of the project site draining to the catch basin or inlet. These BMPs would-be incorporated to meet the requirements of the Storm Water Standards manual and would be sized using a flow-based numeric sizing criteria. The required treatment flow for in-line storm water treatment units andlor catch basinlit).let filter inserts is calculated using the flow-based numeric sizing criteria provided in Table 3 of the Storm Water Standards manual, Table 3 -Numeric Sizing Treatment Standards (Section III of Storm Water Standards). Appendix C provides calculations fo~ water quality treatment flow requirements for the project based on the following numeric sizing criteria: "the maxImum flow rate of runoff produced from a rainfall intensity of 0.2 inch of rainfall per hour for each hour of a storm event". For the purposes of this water quality technical report, Suntree Technologies filter inserts and KriStar-Enterprises, Inc. filter inserts (named FloGard+PLUS) have been sized according to Prepared By: Rick Engineering Company 8 August 29, 2003 ST:rh\R:\d..) 4437\Report\SWMP (001 )_doc r-----------------------------------------------------------------------~------~---- I I I I I I I I I I I. I I I I. I I I I water quality treatment requirements for the development area covered by the project site. The specific structural BMPs that have been selected for installation throughout the development area are listed in the tables provided in Appendices D and E ofthis report. Approximate costs for both manufacturers have been provided in Appendix G of this report. CDS Technologies in-line treatment units have been sized according to water quality treatment requirements for lot 21 and approximate costs have been provided. Additional approved manufacturers ofin-line treatment facilities exist and maybe substituted if the appropriate calculations are performed to size each facility according to its own unique water quality treatment capacities. Refer to Appendix F for water quality treatment capacities, details, and costs associated with CDS Technologies in-line treatment units. These water quality treatment capacities, details, and costs provided in Appendix F are tmique to the CDS Technologies in-line treatment facility and shall not be used for sizing in-line treatment facilities by additional manufacturers: Depending on the overall design capacity ofthe storm drain system, the CDS Technologies in- line treatment units may require diversion boxes in order to provide for the locallQO-year design storm event. Preliminary rational method analyses have been performed for the 100-year peak storm event and are provided for reference in Appendix B. The size and slope of pipe and amount of discharge passing through the unit are the parameters, which detenn~ne if ~ diversion box is required. Prepared By: Rick Engineering Company 9 August 29,.2003 ST:rh\R:\d_14437\Report'iSWMP (OOt).doc .... ----------------------------------------------- I I I I I I I I I I I I I I I I I I I 6.0 ANTICIPATED MAINTENANCE CONDITION(S) Typical Maintenance Procedures for Treatment Control BMPs The maintenance procedure for servicing in-line treatment units or curb inlet filter inserts typically includes contracting the maintenance cleaning/waste removal through a provjder of those services. Manufacturers often offer servicing for their own facilities, however, maintenance services are also offered through a variety of other manufacturers and cleaners as well. Th~ frequency of maintenance required is site and drainage area specific. The units should be inspected periodically to assure its condition is adequate to handle anticipated runoff. Initially following the installation of new treatment BMPs, it is important to check that the unit is functioning properly and measure the amount of deposition occurring from specific storm events. At a minimum, inspections should be made on a monthly basis and after every storm event to check that the unit is functioning properly and whether the unit requit~s servicing at 'that time. Based on these inspections, it may be necessary to adjust the frequency of schedule<l in~pections and maintenance cleanings. It is important to note that for the purpose of this water quality technical report, anticipated maintenance costs and the frequency of servicing (as discussed below for "Anticipated Maintenance Cost of Post-Construction Structural BMPs") are approximated and do not reflect the periodic inspections that are necessary to determine the actual frequency that site specific units will require. Specific to the curb inlet filter inserts provided by KriStar Enterprises, mc., serv.ice procedures include the removal of the manhole cover, vacuuming the collected debris,. replacing the hydrocarbon pouches as necessary (sorbent material), inspecting for needed repairs andlor replacement ofthe filter medium, closing the manhole cover, properly disposing of the waste, and recording the maintenance service for future reference. Specific to the curb inlet filter inserts provided by Suntree Technologies, service procedures include the removal of the manhole cover, removing the curb inlet basket, properly disposing of Prepared By: Rick Engineering Company 10 August 29, 2003 ST:rti\R:\d _ i 4437\Report\SWMP (001 ).doc ··1 I I I I I I I I I I I I I I II I I I the waste, replacing the hydrocarbon absorption boom (sorbent material), returning the filter to its secure position and closing the manhole cover, and reporting on debris and condition of filters . for the maintenance service. Specific to the CDS Technologies units, "a unit can be cleaned using a vacuum truck or a small clamshell bucket, or a basket can be provided to fit a standard sump," as specified in the "CDS Technologies Storm Water Pollution Control Technical Manual," date:d July 2002. If a basket is desired, CDS Technologies should be advised so that the material and installation costs can be adjusted accordingly. Anticipated Maintenance Cost of Post-Construction Structural BMPs Please refer to Appendix G of this water quality technical report for a summary of the . approximate maintenance costs associated with the proposed post-construetion BMPs. ~he annual maintenance cost; provided within Appendix G assume that the catch basin inlet filters will be serviced four times a year, and the CDS units twice a year. However, periodic inspections should be made to ensure the unit is functioning properly and that the frequency of maintenance does not need to be increased (as described above in· "Typical Maintenance Procedures for Treatment Control BMPs"). It is important to realize the annual maintenance costs provided within this report are preliminary and are approximations, which do notteflect the actual frequency that installed units may require servicing. Pursuant to information provided to Rick Engineering Company on May 20, 2002 from Bio Clean En~ironmental Services (a provider/vendor of Suntree Technologies Curb Inlet Baskets), maintenance costs for filter inserts are $316.00 per inlet per year, which assumes four $79.00 cleanings per year per inlet. It is recommended that maintenance requirements are monitored for any necessary increase in frequency. Pursuant to a phone conversation made on April 23, 2003 with Bob Griese of Downstream Services (a local distributor of KriStar Enterprises' FloGard+PLUS units), maintenance costs associated with the filter inserts range from approximately $150.00 to $450.00 per inlet per year . Prepared By: . Rick Engineering Company 11 August 29, 2003 ST:rh\R:\d_14437\Report\SWMP (OOl).doc r--------------------------------~~-~--~--~~- I I I I I I I, I I I I I I I I I I I I (depending on the number of filter insert components for each inlet), which includes four cleanings per year per inlet. It is recommended that maintenance requirements be monitored for any necessary increase in frequency. Pursuant to a phone conversation with Gordon Wilson of CDS Technologies, mc. on June 3, 2003, maintenance costs associated with the PMSU20 _15_ 4 treatment unit proposed for this project is approximately $1,470 per unit per year, based on two cleanings a year. The number of cleanings a year is based on soil and site conditions and may range from one to four cleanings a year. It is important to note that a variety of vendors distribute, install, and maintain these types of treatment facilities:and may offer significantly different costs associated with each unit than those provided within this technical report. Responsible Party for Maintenance and Funding of Structural BMPs The owners of the subject property would be responsible for maintenance and funding of structural BMP's. Prepared By: Rick Engineering Company 12 August 29, 2003 ST:rb\R:\d _14437\Report\SWMP (001 ),doc ....------------------------------------ I I I I I I I I I I I I I I I I I I I 7.0 SUMMARY The application to the City of Carlsbad consists of a non residential Tentative Map and Planned Unit Development for an existing light industrial site. No improvements or creation of impervious surfaces are proposed. Based on these conditions, this project would be exempt from requirements for permanent BMP's and water quality treatment, pursuant to the provisions of the Municipal Storm Water Permit adopted by the Regional Water Quality Control Board. Prepared By: Rick Engineering Company 13 August 29, 2003 ST:rh\R:\d_14437\Report\SWMP (001 ).doc I I -I :1 I I I I I I :1 'I I I :1,-, , ',1 I :1 ' , I, APPENDIX A AES 2000 Rational Method Analysis 100-Year Rational Method Analysis for Lot 21, Carlsbad Tract 74-21 ~I ., -i ;1 I ·1 I fl I· I I· ·'1 I I I I I I. I' 'I. I:. *************************.*************************************************** RATIONAL METHOD HYDROLOGY COMPUTER PROGRAM PACKAGE Reference: SAN DIEGO COUNTY FLOOD' CONTROL DISTRICT 1985,1981 ·HYDROLOGY MANUAL (c) Copyright 1982-20'00 Advanced Engineering Software (aes) Ver. 1.5A Release Date: 01/01/2000 License lIT 1261 Analysis prepared by: Rick Engineering.Company 5620 Friars Road San Diego, CA 92110 (619) 291-0707 ************************** DESCRIPTION OF STUDY **********~*************** * Drainage Study for Lot 21 * 07/24/03 * ************.************************************************************** FILE NAME: C:\SCRATCH\LOT21.DAT· TIME/DATE OF' STUDY: 14:48 07/24/2003 * * * ----------------~-------------------------------------------------~~---~---~ USER SPECIFIED HYDROLOGY AND HYDRAULIC MODEL INFORMATION: 1985 SAN'DIEGO MANUAL CRITERIA USER SPECIFIED STORM EVENT (YEAR) = 100.00 6-HOUR DURATION PRECIPITATION (INCHES) = 2.600 SPECIFIED MINIMUM PIPE SIZE(INCH) = 18.00 SPECIFIED PERCENT OF GRADIENTS (DECIMAL) TO USE FOR FRICTION SLOPE SAN DIEGO HYDROLOGY MANUAL "C"-VALUES USED FOR RATIONAL METHOD NOTE: ONLY PEAK CONFLUENCE VALUES CONSIPERED *USER-DEFINED STREET-SECTIONS FOR COUPLED PIPEFLOW AND STREET FLOW HALF-CROWN TO STREET-CROSSFALL: CURB GUTTER-GEOMETRIES: WIDTH CROSS FALL IN-/ OUT-/PARK-HEIGHT WIDTH LIP HIKE NO. (FT) (FT) SiDE / SIDE/ WA:£ (FT) (ET) (FT) (FT) ========= ================= ====== ====== 0.95 MQDEL* MANNING FACTOR (n) 1 30.0 20.0 0.018/0.018/0.020 0.67 2.00 0.0313 0.167 0.0150 GLOBAL STREET FLOW-DEPTH CONSTRAINTS': 1. Relative Flow-Depth = 0.00 FEET 'as (Maximum Allowable Street Flow Depth) -(Top-of-Curb) 2. (Depth) * (Velocity) Constraint =: 6.0 (FT*FT/S) *SIZE PIPE WITH A FLOW CAPACITY GREATER THAN OR EQUAL TO THE UPSTREAM'TRIBUTARY PIPE.* '* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *-* * * * *:1< * * * * * * * * * *-* * * FLOW PROCESS FROM NODE. 100.00 TO NODE 101.00 IS CODE = 21 , . ---------------------------------------------------------~~----------------~ »»>RATIONAL METHOD INITIAL SUBAREA;ANALYSIS««< ========================7=============================~=====~=====~====~=p== USER-SPECIFIED RUNOFF COEFFICIENT ='.9500 S.C.S. CURVE NUMBER (AMC II) = 92 INITIAL SUBAREA FLOW-LENGTH 140.00 1. I ·1 '1 I I I I I I I I I I I I I I I I UPSTREAM ELEVATION = DOWNSTREAM ELEVATION ELEVATION DIFFERENCE 395.00 383.60 11. 40 URBAN SUBAREA OVERLAND TIME OF FLOW (MINUTES) 1.588 *CAUTION: SUBAREA SLOPE EXCEEDS COUNTY NOMOGRAPH DEFINITION. EXTRAPOLATION OF NOMOGRAPH USED. TIME OF CONCENTRATION ASSUMED AS 6-MINUTES 100 YEAR RAINFALL INTENSITY (INCH/HOUR) = 6.090 SUBAREA RUNOFF(CFS) 1.10 . TOTAL AREA (ACRES) = 0.19 TOTAL RUNOFF (CFS) i.10 ****************************************************************t****~****** FLOW PROCESS FROM NODE 101. 00 TO NODE 102.00 IS CODE = 62 ------~---------~----------------------------------------------------------- »»>COMPUTE STREET FLOW TRAVEL TIME THRU SUBAREA««< »»>(STREET TABLE SECTION # 1 USED)««< =================================================================~========== UPSTREAM ELEVATION(FEET) = 383.pO DOWNSTREAM ELEVATION (FEET) = . 380.50 STREET LENGTH (FEET) = 490.00 CURB HEIGHT (INCHES) = 8.0 STREET HALFWIDTH(FEET) = 30.00 DISTANCE FROM CROWN TO CROSSFALL GRADEBREAK(FEET) 20.00 INSIDE STREET CROSS FALL (DECIMAL) 0.018 OUTSIDE STREET CROSSFALL(DEClMAL) 0.018 SRECIFIED NUMBER OF HALFSTREETS CARRYING RUNOFF 1 STREET PARKWAY CROSS FALL (DECIMAL) 0.020 Manning's FRICTION FACTOR for Street flow Section (curb-to-curb) 0.0150 Manning's FRICTION FACTOR for Back-of-Walk Flow Section -0.0200 **TRAVEL TIME COMPUTED USING ESTIMATED FLOW(CFS, STREETFLOW MODEL RESULTS USING ESTIMATED FLOW: 15.51 STREET FLOW DEPTH (FEET) = 0.44 HALFSTREET FLOOD WIDTH (FEET) = AVERAGE FLOW VELOCITY(FEET/SEC.) PRODUCT OF DEPTH&VELOCITY(FT*FT/SEC .. ) 2.19 STREET FLOW TRAVEL TIME(MIN.) = 3.72 100 YEAR RAINFALL INTENSITY (INCH/HOUR) USER-SPECIFIED RUNOFF COEFFICIENT = .9500 S.C.S. CURVE NUMBER (AMC II) = 92 0.96 Tc(MIN.) 4.461 9.72 SUBAREA AREA(ACRES) 1.88 TOTAL AREA(ACRES) = 2.07 SUBAREA RUNOFF (CFS) '= PEAK FLOW RATE(CFS) = END OF SUBAREA STREET FLOW HYDRAULICS: DEPTH (FEET) = 0.51 HALFSTREET FLOOD WIDTH(FEET) 19.57 9.14 7.97 9 • .0'7 FLOW VELOCITY(FEET/SEC.) =' 2.51 DEPTH*VELOCITY(FT*FT/SEC.) '1.28 LONGEST FLOWPATH FROM NODE 100.00 TO NODE 102.00 = 630.00' FEET. *********************************************************************.******* FLOW PROCESS FROM NODE 200.00 TO NODE 201.00 IS CODE ~ 21 ----------------------------------------------~----------------------;------ »»>RATIONAL METHOD INITIAL SUBAREA A~ALYSIS««< ===================================================================:======== . : . USER-SPECIFIED RUNOFF COEFfICIENT = .9500 S.C.S. CURVE NUMBER (AMC II) = 92 INITIAL SUBAREA FLOW-LENGTH = 115.00 UPSTREAM ELEVATION 395.00 2 I I I ,I 'I I I I I 'I I I I I I I ,I I I DOWNSTREAM ELEVATION 384.50 ELEVATION DIFFERENCE 10.50 URBAN SUBAREA OVERLAND TIME OF FLOW (MINUTES) -1'.385 *CAUTION: SUBAREA SLOPE EXCEEDS COUNTY NOMOGRAPH DEFINITION. EXTRAPOLATION OF NOMOGRAPH USED. TIME OF CONCENTRATION ASSUMED AS 6-MINUTES 100 YEAR ~INFALL INTENSITY (INCH/HOUR) = 6.090 SUBAREA RUNOFF (CFS) 1.04 TOTAL AREA (ACRES) = 0.18 TOTAL RUNOFF (CFS) 1..04 ************************************************************~***********~*** FLOW PROCESS FROM NODE 201.00 TO NODE 202.00 IS CODE = 62 -------------~----------------------------------------------~-~------------- »»>COMPUTE STREET FLOW TRAVEL TIME THRU SUBAREA««< »»>(STREET TABLE SECTION # 1 USED)««< ===================================================================~======== UPSTREAM ELEVATION (FEET) = 384.50 DOWNSTREAM ELEVATION(FEET) STREET LENGTH (FEET) = 255.00 CURB HEIGHT (INCHES) = 8.0 STREET HALFWIDTH(FEET) = 30.00 DISTANCE FROM CROWN TO CROSSFALL GRADEBREAK(FEET) 20.00 INSIDE STREET CROSS FALL (DECIMAL) 0.018 OUTSIDE STREET CROSS FALL (DECIMAL) 0.018 SPECIFIED NUMBER Of HALFSTREETS CARRYING RUNOFF -, 1 STREET PARKWAY CROSSFALL(DEClMAL) 0.020 381. 50 Manning's FRICTION FACTOR for Street flow Section(c~rb-to-curb) 0.0150 Manning's FRICTION FACTOR for Back~of-Walk Flow Section ~ 0.0200 **TRAVEL TIME COMPUTED USING ESTIMATED FLOW (CFS) STREETFLOW MODEL RESULTS USING ESTIMATED FLQW: STREET FLOW DEPTH (FEET) = 0.37 HALFSTREET FLOOD WIDTH(FEET) =, 11.84 AVERAGE FLOW VELOCITY(FEET/SEC.) 2.58 PRODUCT OF DEPTH&VELOCITY(FT*FT/SEC.) 0.96 STREET FLOW TRAVEL TIME(MIN.) = 1.65 Tc(MIN.) 7.65 100 YEAR RAINFALL INTENSITY (INCH/HOUR) 5.207 USER-SPECIFIED RUNOFF COEFFICIENT = .9500 S.C.S. CURVE NUMBER (AMC II) = 92 SUBAREA AREA(ACRES) 1.08 SUBAREA RUNOFF(CFSj TOTAL AREA (ACRES) = 1.26 PEAK FLOW RATE(CFS) END OF SUBAREA STREET FLOW HYDRAULICS: DEPTH (FEET) = 0.43 HALFSTREET FLOOD WIDTH(FEET) 14.96 3.72 5.34 6.38 FLOW VELOCITY(FEET/SEC.) = 2:91 DEPTH*VELOCITY(FT*FT/SEC.) 1.25 LONGEST FLOWPATH FROM NODE 200.00 TO NODE 202.00 =' 370;00 FEET. **********************************************t***************************** FLOW PROCESS FROM NODE 300.00 TO NODE 301.00 IS CODE = 21 ---------------------------~------------------------------------------------ »»>RATIONAL METHOD INITIAL SUBAREA ANALYSI'S««< =======================================~=========================~========== USER-SPECIFIED RUNOFF COEFFICIENT ='.9500 S.C.S. CURVE NUMBER (AMC II) = 92 INITIAL SUBAREA FLOW-LENGTH = 100.00 UPSTREAM ELEVATION = 395.00 DOWNSTREAM ELEVATION = 384.50 3 I I •• 'I /1 ·1 I I I I I I I I I I I I I ELEVATION DIFFERENCE 10.50 URBAN SUBAREA OVERLAND TIME OF FLOW (MINUTES) 1.233 . *CAUTION: SUBAREA SLOPE EXCEEDS COUNTY NOMOGRAPH ·DEFINITION. EXTRAPOLATION O~ NOMOGRAPH USED. TIME OF CONCENTRATION ASSUMED AS 6-MINUTES 100 YEAR RAINFALL INTENSITY (INCH/HOUR) = 6.090 SUBAREA RUNOFF(CFS) 0.81 TOTAL AREA(ACRES) = 0.14. TOTAL RUNOFF (CFS) 0.81 **************************************************************************** . . FLOW PROCESS FROM NODE 301.00 TO NODE 302.00 IS CODE = 62 -------------------------------------------------~-------------------------- »»>COMPUTE STREET FLOW TRAVEL TIME THRU SUBAREA««< »»>(STREET TABLE SECTION # 1 USED)««< ============================================================================ UPSTREAM ELEVATION(FEET) = 384.50 DOWNSTREAM ELEVATION(FE~T) STREET LENGTH(FEET) = 585.00 CURB HEIGHT (INCHES) = 8.0 STREET HALFWIDTH(FEET) = 30.00 DISTANCE FROM CROWN TO CROSSFALL GRADEBREAK(FEET) 20.00 INSIDE STREET CROSSFALL(DECIM~L) 0.018 OUTSIDE STREET CROSS FALL (DECI,MAL) 0.018 SPECIFIED NUMBER OF HALFSTREETS CARRYING RUNOFF 1 STREET PARKWAY CROSSFALL(DECIMAL) 0.020 380.80 Manning's FRICTION FACTOR for Streetflow Section(curb-to~curb) 0.0150 Manning's FRICTION'FACTOR for Back-of-Walk Flow Section = 0.0200 **TRAVEL TIME COMPUTED USING ~STIMATED FLOW (CFS) 3.89 STREETFLOW MODEL RESULTS USING ESTIMATED FLOW: STREET FLOW DEPTH (FEET) = 0.41 HALFSTREET FLOOD WIDTH(FEET) = 13.79 AVERAGE FLOW VELOCITY(FEET/SEC.) 2.06 PRODUCT OF DEPTH&VELOCITY(FT*FT/SEC.) 8.,84 STREET FLOW TRAVEL TIME(MIN.) = 4.74 Tc(MIN.) 10.74 100 YEAR RAINFALL INTENSITY (INCH/HOUR) 4.183 USER-SPECIFIED RUNOFF' COEFFICIENT = .9500 S·.C.S. CURVE NUMBER (AMC II) = 92 SUBAREA AREA(ACRES) 1.52 SUBAREA RUNOFF{CFS) 6.04 TOTAL AREA(ACRES) = ,1.66 PEAK FLOW RATE(CFS) 6.85 END OF SUBAREA STREET FLOW HYDRAULICS: DEPTH (FEET) = 0.47 HALFSTREET FLOOD WIDTH (FEET) 17.46 FLOW VELOCITY (FEET /SEC.) = 2.35 DEPTH'*VELOCITY (FT*FT /SEC. ) i.11 LONGEST FLOWPATH FROM NODE 300. 00 TO NODE 302. 00 = 685.00 'F,EET. ======~======================================================~============== END OF STUDY SUMMARY: TOTAL AREA(ACRES) PEAK FLOW RATE (CFS) 1.66 TC(MIN.) = 6. '8 5 10.74 ===~========7============================================~=============~==== ============================================================================ END OF RATIONAL METHOD ANALYSIS 1 4· . -~j ._ ... _,,, .. i - -~ -.. --T"N -U·· .. - --= - - - -._,.-.. . .. rNTENSITY!"D MrJ.yl~ DESIGN· CHART 'Directions for Application: 1) From precipitation maps detennine·6 hr. anf 24 hr. amounts for the selected frequency. These maps are·printed in the County Hydrolog~ Manual (10, 50 and 100 yr. maps tncluded in tt Des i gn and Ptocedure Nanua 1 ) • . 2) Adjust 6 hr. precipitati'on (if necessary) so that it is within the range of 45% to 65% of the 24 hr. precipitation. (Not nrrlicable to Desert) , Plot 6 hr. precipitation on the rinht side of the chart. Draw a line through the point parallel to the plotted lines. . \00 yr. * ---:;:;;--' P 6 = O-b~%*· ~4 . *P6=-·;2.-f. .. . . :,.. I 2) Adjusted . : .... : . , : . : , · ~ --... ---. -'. .. ... . .. " ~: .... : .. • ~.2 _-_CCC_:_:: ....... :.:; :; · x. _ _ _ . .. I ., .... :. · ~ . IH-·I~I-I-I-I··I-:I-I.I :1: • ..... ,1 .. 1,1 ... ...;..I-f- • ... I .. ,.r.t1~ ..... t ... ,. · t~_fRfFrfffmlll1tmwmllll~ffiJ~mlmllll· --. 15 20 1lIlJl!1111H t H:ttlttttttHliHIl II III 40 50' 1 30 2 Hours 3 4 5 6 Mi,nlltp.!; 3) t = c 4) I = r .. .' J', ',':. \-1.::> : .... :: ,', ,,::;;.,.~' , . mi n. i n/h.r. *N~t Applicable to Desert Region ., . APPENDIX XI IV-A-14 Revised 1/85 ---~---------------------------..... ------------------------... . ~ , . .' • '. I --. -_._~_: _J._ ..... _, __ ,I. .... .... I, » , ~ .---.. C.OU1ITV OF SAN 0 lEGO DEPARTMENT OF SANITATION·& FLOOD CONTROL 45'" I ' \ /l1~TI~} S-. " ... , ! t I 15' ; I ,. '" 33 0 s ---'.,,-.... --, .. , ... ,--45 t 'r. /. , II'LCAJot n" __ .{;(;,..iJiJJ.il ..... Ptel'.n ld by, U.S. DEPARTi\·tEN r OF COMMERCE NATrO~AL OCItANIC AND AT, OSPIIE~IC ADMI~ISTRA:rIO~ 'J:'£CIAL STUDIES I3RANCH~ OFFICE OF' ", UROLOGY. NATIONAL, WEATHER SERVl.CE 30 t I . I' . I ' I. LV--:-l~ta.luJ~ 118' 45.1 30' lS" , J17° f .., . -----'_., j::.' _ :' l.S' 30' J 5·' 116°~ ... --..-~. _:'-=--_:._: _1 _: _: ~_~ ~ -=~. ~.~.~.~ ... .1: COUNTY OF SAN DIEGO DEPARTM'ENT OF SANITATION & FLOOD CONTR0L 45 ' 30' 15' 100~VEAR 24~Bm~H PfU~CIPITATION '-20.../ ISOPLUVIALS' Of 1 00 -YEAR 24-HOUR PflEGlPlTATION IN hrnHS OF At~ mel-! .330 -1 -1 --. \\~ ,-1- 45' Pre,."t·'.I by . u.s. DEPARTMENlrOF COMMERCE , I NATION.\L OC~i\="IC AND AT:'\OSI'IIERIC' A'D~IINlS'rRATION SPECIAL ,STl.IDIES SRA:-lCII. Ofl'ICJ:: Of' nlD'~OLOQY •. NA·rioNAL IVEATUER SERVICE . 30 ,~. ~ I I . . r ,. H .... ~~ 1 tnU 1,5' 30' . Pi I t .W 1170 "'!i • JO' 1~ I ·1 Hj" I I I I I I. I I I I I ,I I I I II I I 'I -APPENDIXB Calculations f()r Water Quality Treatment Flow Requirements ~~~~~~-'-~~~~~~~--.--- d; WATER QUA.L1TY TREATMENT FLOW REQUIREMENTS FOR FILTER INSERTS Post Construction BMP's for Lot 21 Project Required Treatment Flow (cfs) = 'C' x 'A" x 0.2 in/hr (pursuant to Numeric Sizing Criteria within Storm Water Standard manual) Drainage Map Type of Inlet Tributary Rational Method Required Treatment Node # Area (Ac) Coefficient 'C' Flow (cfs) 102 C 2.07 0.95 0.39 202 G-3 1.26 0.95 0.24 302 B 1.66 0.95 0.32 :1 I I I ,1 I I, I -I I I I I II I I I I I APPENDIXC KriStar Enterprises, Inc. Water Quality Treatment CapaCities, Details, and Costs II I I: I I II, " I I I '1' ' 1 \ I' 'I I il I, :1', .1 ;1 I 07/23/2003 :15: 55 <., 707:'::52:4-8186 , KRISTAR.ENTERPRISES·' Flo.Ga-d+PIus Riter Installed -+--..... '-"I!:If:lI 1"'otIO GmteOD Model No. Cln x In) (lox in) FGP·i2F Ux12 14x14 ·FGP·1530F 15x30 16x36 FGP-1I!F 16x 16 18;Jt16 FGP·18F 18X·18 20x20 ItGP-1822F 20 x: 24 18x~2 fGI'-1824F ~6 x: 22 20)(24 f(;P-1836F 18x36 18x40 f'(;P-2024F ~Ox24 22:;:24 FGP·21F 22x22 • 24x24 IIQTES: ffiP.i142F 21 x42 FGP·24F, 24'lt24 fGP·2436F 24x36 FGP-244SF 24:x 45 FGP-2448F 24x48 FGP-28F V3x28 i=GP40F 3(h;:3Q FGP-36F 36x36 FGP·364SF 36xMJ FGP-48F (2 PGl MJ,l(MJ ,. ~a:p.dtyrdl«i:saO!lOO( ~11'IJm/lQllde • _caIIonprtQ"ta'fI1)et!lrolltl!dnq~~. , 2. R~flOWt'-1t",lrQIUQ""""d¥i'<>cIa cf~ ~ ,,*GlrdtfllJs~ BlIj<In RII"'I~....,;.; .... II.cle • j,,1I)Io1(llnd ... ClSI-t" .... -IQ';n QlIIQm"-' 26;x;42 26x26 24x40' 2tlx47 ts X41! 30x30· 3{)x34 36x~ 40x.a 48x52 II. FIo-GlrdfoRu:sru~~~b<:u=::Iih«>l\)tl\dlon • wth"H~r rmlnlIIIl8f'Qapragmn. Rof"rto " • 'fl1I~::;_mcniJ!!d m!!Infl!l1en;QGUlo.Jl,",,~ IJ$ PATeN" p t;IIIlJNO Solids Storage- Cap. (cu1t) 0.3 2.3 o.a 0.8 2.1 1.5 2.3 1.2 2.2 U 2.2 3.4 4.4 4.4 2.2 3.6 4.6 6.8 9.5 - Inltll\l Tatal' Filtered Sypas$ S&col'lclary, l3y'p~ Flow cap. SYl'OUS Cal'. , lefs) (ds) C~p-,.{Gfsl J~1. 0.4 ".r n.1 2.8 1.6 6.5 0.4-6.9 0.7 4.4 0,2 .4.7 (J.t 4.4 0.2 4.7 1.4 5.6 0.3 S.! U 4..8 0.2 5;0 1.6 6.5 0.4 6.9, 1'.0 5.6 0.3 5.9 1.5 5.8 U 6.1 2.4 8.7 0.4-9.1 1.5 ~.8 0.3 6.1 2.0 7.5 0.4 8.1i 2.4 8.9 0.4-9.3 2.4-8.9 0.4 9.3 1.5 5.8 : 0.5 6.~ ,2.U 7.S 0.5 8.1 2.4 8.6 O.S 9.1 32 '10.8 O.li 11.5 3.9 12.5 0.7 13.2 .FLO..GAREfli +P.LUS .CATCH BASIN FILTER INSERT (j::'~ Iv1ount) FLPiTGRPlTEOfliurr .Sl-EET 1 OF 2 Wister Ellterprlsos.lnc •• Studt! RO:1«. CA (SOO)57S-lI819 PAGE 02/07 ~I I I- . ' I I :1 I ~I I I' I '1 , ,I, ,. ; I, I I ~I :1 ' \ .' t . 11' . ' . 07/23/2003. :'.15: 55··· .. · 707-:524":8186 KRISTAR ENTERPR1SES' . OeIJda 'Imp Uoer Qit\:ll aatlln (Flal Gtala S~9) -----.----·---r----~-....J.~OullQlPipo U.S. PATI:NT PENDING NOTES: 1. AoGali:l+PLUS'" (\'mms mount) high t;:BpacIty catch btlai!l~ts lW av'a/ljlble In sizes to 'fit most industry- standal'd catch basin $iie$ ~ $lyle$ (see epeclfier~rl). RefBrto,ihe f'loG~rU+PLLlSTM (wall mO,urd) in~ert lqr ~oeslO tit non-standard or eomblnathlrl ~11 C$:h basins, 2. Almr iMmt shtltt hn~e !)Qlh s;m 'lnltlsl" filtering ~~al'l(l '\ll1I~' high- How b)'pas:; fCa/tU'Q, . 3: FU!ar IIBSGIlIbly shall 00 eo/1StrlI~ from stalnleaa stool (T}1JIl' 304). DabrisTI'aI' 4, Allow 1\ mfnIrTl\4fII Qf2'.O',Q1 cfaslBf1C¢ between Iha l»ttom of grate an(llOp oj Inlet or oU1lGt plpe($) •. ReI'ilr 10 SUpport SIlskat lhe FlQl3ar(11'11.in$aitfor"5haIidn'" InS1allalions. Liner 5. Ff~r ~d1um shall be PI18SY RrXi?" lriataHed and maintalned.in =n;kmc;o . with manufacturer re~on,'l., . FLOGAROtPLtj$1M . CATCH BASIN' FILTER INSERT (F~Me MOUNT) FLAT GRATEO INLET SHEET20F2 KriSttlr IlnIO~fi$1l$, !@.,$8ntaRosa"CA(OOO),5ro-a6i9 ·PAG~ :0'3/07 I I I I ,I I I. '1 I· I· I I I ,I· I I I";, ·1 '1' \. . 07/23/2009' 15:·55 : 701~524-8185 ! POlE:;.: Ro-Gard+Ptus installed Inl~t Mod4;d No. width tin} FGP-24CI 24 FQP-.3DCI 30 FGP~6C1 36 FGP-42CI 42 FGP-4SCI 4$ ·FGP-6CI 60 FGP-6CI T2 FGP-7CI Bot FGP.(ICI 96 . FGP-10CI 120 FGP~12CI 144 ,"GP~14CI 168 ~GP-16C1 192 FGP~18CI 216 FGP·21CI 252 FGP·~C/ 336 .1. ~~tyrQ'I~~oIf n1'ONftl,jm~lld~ • oaIIlJ<flanpr/ortql~lrQ1~tlil'll1llb}p-' :z. PltcndflaymtAfnoll.iQ\l;IIA"Qllt'~r<.1~ ;it. FJo.OIotd+f\1.a< c.toI;I ~n FlI cr;~ '"' """'doIe: • In lhUill'ldIl'dSlz"'C-"""""lcr In cuoloin of __ • c.IJ ford.hil""" o.ofDm d..,fn....u. Grate 00 (In x in) iliA NA NA NA NA NA NA filA NA NA NA NA NA NA NA NA I. FIo-GWtl'lw1IH.-11lRrt5 roould be wmln ;orWnClion • Wlh :ar~ ... ,.q;nI~'"'III prOGI"lm. R4I fil'1Ii • llWIUI''IIOttmIflll'r_mMlndIld IMitUn:ll'l<:eOlld<!l""""_ ,lJG PATENT PSHO.ING Solids Storaga Can.(cum 0.9 1.1 1.4 1.6 1.9 2.3 . 2.8 3,:2 3.1 4.6 5.6 6.S 7.S 8.3 9.1 13.0 KRI'STAR ENTERPRISES :', . Initial Total Fllt9I'Gd Bypasf; S~coodary Sypass FIQW ~:l Bypass Cap. rcf!;l . Cao.(m\ (cfs\ 0.8 5.5 0.1 5.6 1.0 6:.5 0.2 6.7 1.~ 7.S 0.2 1.7 1.4 a.6 0.2 . 8.8 1.S 9.6 0.3 9.9 1.B 11.3 0.3 f1.6 2.2 13.4-0..4' 13.8 2.5 15.5 0.4. 1U 2.9 17.5 0.5 18.0 3.5 21.3 M 21.9 4.2 25.4 0.3 26.2 4.9 29.2 0.9 30.1 s.6 33.4 .1.0 34.4 6.:2 37.2 1.1 SS.3 7.2 43.0 1.3 44.3 9;5 56.8 1.8 58.5 fLO..GAROM +PLUS ~ATCH BASIN FILTER INSERT {CUrb Mount} FLAT GRATSHNJ.,ET .s~1OF2 I{rlStor Ei11Brpl'lS8 8,' 00" :;l1lfl\1!I R mI i C' A ceOO) 51$-6813 ',1 I I I I I I I I I I I I I I I·' I I I , .. :-1 , 07/23/2003' 15: 55 '707-524-8185 KRISTAR ENTERPRISES . PAGE :05/07 Attach to.catch basin wall or waif mount bracket assembly Debrisrrap (16 Ga. stainless steel) ~-------------------------V~es-------------------------- Initial (frttering) BYP<isS Stainless Steel Support Sasket TOP VIEW Liner FRONT VIEW Stainless Steel Debris Trap (is Ga.) Filter I.lner . (optional) St:ainle~ Steel Support Basket (0.08) FLOGARO+PlUS'W CATCH BASIN FILTER INSERT (CURB OPENING STYLE) SHEE't20F2 KrlStar Enterpri~s, Inc., SMta ROSa, CA (BOO) 579·~1!l Gasket -I I 'I I, I I I I I I I -I· I I I 'I 1_-- , ' I I' ,07/23/2003 15': 55 '701.'-:524-8185 KRISTAR ENTERPRISES Scope: GENERAL SPECIFICATIONS FOR FLO-GARD AND FLO-GARD "PLUS" (HIGH CAPACITy) CATCH BASIN INSERTS ' This specification desc;ttDes a Catch Basin Filtration Device that removes sediment, debcis~ trash and petroleum hydrocarbons (oil and grease) from water flow.illg into the drainage inlets during low flows (first flush) without impeding the inlet's xnaxitnwn design flow. Hydraulic bypass calculations shall be supplied upon request. The nitration devioe shall incorporate a silicate adsorbent filt~ medium capable of collecting and containing non-soluble pollutants inclu.ding, but not limited to, petroleum hydrocarbons (oil and grease). Filter medium shall be contained -in separate removable containers that can easily be replaced without removing the filter line:r. Filtration device shall not rely on collected sediment, debrist trash 01' filter liner as the medimn for hydrocarbon collection. High cap.acity filtration devices shall incorporate a debris trap, designed to retain , ;float,able pollutants during high flow periods and both an initial filtering bypass for moderate flows and an ultimate bypass for peak design 'flows. The installed device '~shall not"' impede drainage inlet's peak design flow prior to or after the device has reacned its pollutant storage capacity. Material Properties: Filtration device support frame and hardware shall be manufactured from Type 304 stainless steel It shall be designed to support maximum anticipated loads from the collected pollutants and water. Structural calculations or laboratory tests shall be supplied upon request. ,Field modifications, welding or pairiting of the device shall not be allowed. ' Device shall incorporate a removable :filter liner made from a woven polyptopolene monofilament geotextile with a cleap. flow rate of 140 gallons per minute (gpro) per square foot. The use of a non-woven geotextile filter liner shall not be allo-wed. Filter medium shall be hydrophobic silicate adsorbent material treated to attract and ~etain petroleum hydrocarboD§ ,(Jlld other non-soluble pollutants. It shall be non- biodegradable and non-leach~ and contain no hazardous ingredients as defined by the I I I I I' :1 I I I I .1 I, II I I I .1 I I . 07/23/2003 l5:55' ·707~524~8185 KRISTAR ENTERPRISES, U.S. Environmeotall'rotection Agency (EPA), U.S. -LUPational Sal\>ty and Health Administration (OSHA), and the .World Health orgadzation (WHO). Installation: I Installation of filtration device shall not require ext~ns~e modification of the cat~ ~in and shall be performed by a manufacturer-approved installation contractor. Installation ~ontractor shall be licensed and insured in accordance With agf:ncy requirements. Filtration devices installed into gra.te~ or combination grate with curb openmg. inlets shall be either supported by resting the' support brackets on the grate beating ledge . (installed without the use bolts or other anchoring devices) or mounted to the Catch basin wall with easily removable separate wall mount brackets to allow for quick access to the piping. System in the event of an emergency. . Devices fur curb opening style inlets (no grate) shall be installed across the entire width .ofthe curb opening and shall be seoured to inlet wall, across aud berteath the curb opening, using corrosion-resistant anchors (Type 304 stainless steel). The use of chains or cable to secure the device shall not be allowed. . Filtration devices shall be installed in such a manner as to direct aU flows into the devige. Distance (gaps) between the inlet wan and th~ device sba11 not exceed linch. Gaps of less than -1 inch shall be sealed with a flexible weatherproof sealant~ as appro-vedby . agency. IDStallation ¢ont:rMtor shall supply agency (engineer) with an installation record, . denoting the date of installatiOn, drainage inlet location, type of drainage inlet and type and/or size of filtration device. . '.-7 . PAGE. 07/07 Ir 1 1 _······ , " " : 'i . / I i I ,. , I ~I • I , , I . ./ . I~· I k I 1 I· ~ I 1 I i I j I· .J I····'········ '. , ...1 I DRAINAGE PROTECTION SYSTEMS .. -P.O. Box 7352" .----... .A KrIStar Enterprises, Inc. In.tall"lIon/Maintenance Department DRAINAGE PROTECTION SYSTElVIS Santa Rosa, CA 95407 Phone: 888-950-8826 . fax: 707 524 8·186 www.kristar.com General Specifications For JY1aintenance of Catch Basin Filtration. Systems SCOPE: Federal, State an~ Local Clean Water Act regulations and those of insurance carriers require that stonnwater filtration systems be maintained and serviced on a recurring basis. The intent of the regulations is to ensure't4at the systems efficiently r~move petroleum hydrocarbons, chemicals, sedinient and other harmful pollutants from stoi-mwa~er runoff. . RECOI\1l\1END.ED FREQUENCY OF SERVICE: Drainage Protection Systems (DPS) re90mmends that catch basin filtration systems be serviced on a recurring basis. The ,frequency depends on the amount of runoff, 'pollutant loading and interference from debris (Ieaves~ vegetation, cans, paper, etc.). As ~ minimum., it is. tecon:uTI.ende~ that each installation be serviced' a minimum of three times per y~ar, wj~h a change of filter . nie~ium once per year. SERVICE PROCEDURES 1. The catch basin shall be visuaily inspected f~r defects and. possible illegal dumping. if defects that affect the efficiency of the catch basin are found, the 9ustomer repreSentative will.be SO notified and a note made on the catch basin. service log; If illegal dumping has occurred, the proper authorities and prop~rty owner repr~sentatiye should be notified as . soon as possible. Debris around the. catch basin shall be collected and placed in a DOT approved container for later di~pos~1. . . 2. Depending on the type of system, the catch basin grate or manhole cover will be removed ··and the cond,ition of the 'filter and filte~ me4ium visually inspected. Serviceability' of the gaskets, silicone sealant and stainleSs steel concrete anchors should be determined a~d a check made to insure proper P9sitioning of the filter within t~e·catch basin. Problems found with the filter will be corrected and noted on t~e catch pasin service log. The filter medium pouches will be inspected for remaining useful life and rep~aced as ne~ed. 3. The collected debris will be vacu:umed'from tfie filter and placed in. a DOT approved storage tank .. Materials in the filter that are questionable in tetms of polhltloq po~ential will be placed: in a separate DOT approved con~ainer. Once th~ debris has b.ren removed, the filter liner and liner connections will be inspected fot damage. Damage to the liner or liner connections .will be corrected ~nd an appropriate notation made on the catch basin. s,ervice' log. . . 4. After the filter is cleaned, and :necess~ry repairs or adjustments made, the grate or . manhole cover will be replaced. The amount and typ.e of debris removed from the filter will be'fecord~' on the catch basin.service log. Recommendations' orpotentlill problem.s will also be noted on the catch basin serv.ice log. . :-d l-r ... ·····,. '. .' l.r I~ I' I' ,1, I I l.. ~~ I ~ I 1 I. ; .. I j I .1. I J I j " . EXCHANGE AND DISPOSAL OF EXPOSED FILTER :MEDTIJM The. frequency of filter medium pouch exchange will be in accordance with the maintenance agreement. DPS recommends that the medium be changed at least once per year. During the appropriate service call, or if so determined by the service techniCian, the'filter'medium pouches will be replaced. with new pouches and the exposed pouches placed in Ii. separa~-e DOT approved container. Once the filter !1ledium is removed, DPS takes possession of the waste and becomes responsible ror proper handling and disposal. The exposed mediufil and the debris removed from .. the filter and catch basin will be kept in separate DOT approved coritainers. Because the task-of the filter medium is to remove petrole~m'hydrocarbons, some heavy met'als and other harmful pollutants from stormwater runoff, the pouches must be treated. as' an EPA Class 2 Hazardous Waste and disposed of in accordance with local, state and federal agency-regulations .. DISPOSAL OF REMOVED DEBRIS Debris removed from the catch basin will be placed in a DOT approved container. Once'~he , " debris is removed from the catch basin" DPS takes possession and becomes responsible for proper disposal. The debris removed from the catch basins will be transported off site, tested arid profiled to'determine the proper method of disposaL After the debris is profiled, it will be .- mani(ested and transported to an appropriate waste facility. All manifests and. test results will be retained by DPS. Copies of the manifests and test results. can be supp1i~ upon request of the customer. . CATCH BASIN SERVICE LOGS , . Every catch basil? that contains a filter will be assigned an identifying tracking number. A catch basin',ser.:vice log folder will be assembled for-each specific site. The catch basin se,rvice log will be used to track the' debris removed and any potential problems for each individual catch basin for each service call. After each service call, copies of the catch basin service log will be forwarded to the customer and these should be placed in the/older:·provided to the customer by .DPS. DPS . will send copies ofthe service logs to the appropr~ate government agency upon requ~s~ of the customer. . . . ADDITIONAL SERVICES, IF REQUIRED Services not mcIuded'in the foregoing service agreement, but may be necessary, are removal and disposal of debris, sediment,. etc. at the bottom of the catch basins or more frequent .filter services. DPS also has the capability of servic~g catch basins without filters, underground oil/water . separators, stormwater iriterceptors, and other devices. Call us at (800) 950-8826 for further information. . I~~~--·· ."".~'~~.-... -' .. -~~~~-~.~.~~:." ~", .. ,. , , .. '" .... j .: I .~ I" , I> i, . Ir' , . I; I, I, •• :1· . I .1 . I I k I I 1 I II .. 1, I' i . J I'. I I ! i II. RICK . . ENGINEERING COMPANY 5620 Friars Road· San Diego, California 92110-2596' (619) 291-3588 • www.rickengineering.com o.tt/~ ~~-~ -. ·f~r·fA.o1e C41vt:·rso..ho/l LN,-fi, 1506 ~ 4'B ') ~ F·G-f-'-\-~c..J:' 30 11 t t50 FG-f -~oc:c .2-iflt' ~ 35' CJ ~"'f --z..q c-:r:. Rc:v;~J ~ osloi' /O~ :r .. ~ ~ 1 ~ ~'. G-.. i e S e o;~)) ~~ rtcc":'?r-IV ~ L()c~/ D,~<§t(/~f of k (1"\ <; t-~r pro&u '--l~ Ie -r I t.ee Flo &-o-rd t fLu') Cotto-I, }kr,,, Fi It, r .. IMif+, G~ .c . .1/ L.I s" G.uoTe p(\c e . I fI~-ro.lI11,,~~ h, 't) ) IT u se.· L.f g Ii . ~ 6'2. $" f $" '3 I , ~ z· .. S' 0 . ~ 3 7 ~ ~ o ~-~ lAse 4-SI/ ~ ~o . flO.?? t '7\Y. ~1\"tSO t 75" ~ .. B-2 ij.se ,+8'") 4 (2). 30/) '~.?:<S-.~ I~~b t\l.s"o· fIIZ,~ J 51o-H.J..Uo.~~ V\~(. 'l..4\"' 'I =t:3 50 t 2.j1. 5 a t 't.1.SO. ~ '31 .. ~ * Q::e:;~ °1r ic.e i'5 IS '1'. v'sc "",.-t-'i'Cl>':' 1..-1 ST .J' ; ce AS Z.,. f--.:!d b 7 D06 &\esc ·of 1>ow~s~M S'er,,\c~s -t~(-North C lv.Ste, r IC\~+o..\ I price ~;, ~ ~ '2 ,.50) ~ ~·c..ft')e. To\'. €.O\ch \(\\e+ .~ype ); 'l(\deptf\~(Mt of haw f-A(~\J'l ri \+u-\l\S~r+-CClMP0t'u.(\ts.· c..C'"t l.t fY1~~~~o..C\(" e. ft·; ('.'~. : s .$ 37, <;: O· pe,r f[ I tee-'j n ').~ (+ (og p~/ f file· 1'k~e-toct.) tYf~ 13--I cAl\OL "B ... 1.. ~.t\.I.trs w~,ch ko.ve. ·+t....I6 "'~J. tN-ee t~ \~ ,(\$ e r -K. e Q(.. h)' rC' ~~ cf-I'''~ 11 J Cos + . ,(y\ 0 (~ +-0' 0:'~ ,:y\ \- ~5e· fv\o..\l\teAlA(\C'e· c.as+:, ""e pI! r de",-";,,,) -f\Pf<1l>(i",,"'~ Iy fov-( e-I eC\0.i0-~S· rae j'eo...\ MfA.t be , (\~C~ ~Q\.(y... ; Nvte.-~ ,.1Lst 'f('~ct'~ ~\e r£l)~ ~ '<oc~\ Jit7tribt4fc7r for Kr; S~~(' 6('\~(X',ses : ·prodtA-c+S •. n.e ty\O(()'(,JfQ,"+~~l 0J,o~tJ i'f .• ~ L ~_ l4_ ___ _ .... _If" I I I I :1 I I I I :1 I I .1 'I ' i 'I j • i I ·1' II I' APPENDIXD Suntree Technologies Water Quality Treatment Capacities, Details and Costs . , I~ .~ I , , , ,R G\/~SGd> 'TA~rt(€1Jr T:1J)w CA'f1ALt,T'1 C.AL..UJt..A.r ,'orAl 1 p()~: <,:" ,,' ' - , c...v,ft/3, ':;i (tJ/.;.,E:-T" 'a. A-SWlE,' , " -n-\-'\S:. ~l.C..ULPi'to~ ,W~~S W~ 0-U:-~LA-TrDf'.f D~D 1-012..4\01. f8rtFo~,M@ '~'i R\c..~ ,G~,IN~rt.!tvG C-aM~klV-'1 i3A;S€:1) ON tVeW ItJFo«..MATlaN ~f<,. GGo !Y\~1'p.."i Or=: ~''IR' ~---_,:",Zy,IJ __ ---:-~ -=-----".---.-,.-j.: " :7' : i I-"'=, 23 1/ '" , II ------. lNfO~"TIDIJ ?~vr~ ~"-/ H-" ~'</: fIl PtNlJfAc:rv 12.eR. . ~,~T-r\. -= ~iS II , ~~' J g ~~PF I C...{ ~tJ~ Cw ~ 2, ~ {s e£ A'TTA~t?D ') H ' . AI H /' 3,G'" SQ\A6 F~ovJ tY)P)'1 Sl.{f/t5S 8AS kE-f t: ~6r?BGNT' , ffiP-.""'\Be.\ kL : . H-;: '2 ,t;;" , / \ $ N.. AY: 'H' F oIJ.. . ; " . tl50 %, lK..~,A 'T'\V\e-iVT • j • POOR QUALITY ORIGINAL S 5-22 I4NDBO<?K OF IfYDRAUL.ICS ... creSt is likely to become dulled or.rtl&ted, or it may be damaged by floating ice and debris. Under 'sueh eonditions 'it may be ad-visable to use a weir with a thleker crest. It is often con- venient to use an' existi)"lg weir or overflow dam' for mep.suring discharges. Weirs of various dlmensions and sha.pes are used in hydraulic structures. When designing 'such'struetures it is important to be able to estimate approximately the dis~h;rges OV& these w~irs (p. 2-15). The amount of water which will pass over a weir, not sharp- crested., depends tq a large extent upon. its' sectional form and the shape ·of its crest, and it is necessary to resort to experiment . to determine the discharge over any particular shape. Inas- 'much as the number cif shapes of weirs is uiilimited, it is not to be expected that experimental data are or ever will be available fo; them all. There are available, however, the results of several series of experiments on :weirs of different crosS sections which furnish much. valuable information for detei:m.ini:ng discharges over weirs of the same or similar shapes. The available experiments are not extensive enough for a comprehensive study of the effect of velocity of Ilopproach on weirl3 not sharP-crested. The coefficients given in this chapter probably apply more accurately where the velocity of approach . is not .high. From a consideration of s.harp-crested weirs ~t . appears that· discharges, . for high. yelociti~s. of app!.~fl:c1i" will be somewhat greater tl;tan is given by formula (5-10). Since exp~llnental conditions will'seldom be duplicated in practice, it is probable th!J-t errors inay resUlt from th~ general use of the coefficients' given in this chapter. Extreme accuracy, however, is not always necessary in design, where uncertain~r as to the exact quantity of water to be provided for may exist. The problem of establi~hing a fixed relation qetween head and dischargel for weirs not sharp-crested, is complic\Lted Py' the ..fact that the nappe may assume a variety. of forms in passing over. the weir. For each modification of nappe form, . there is a, corresponding change m the relation between head and Qjscharge. The effect of this co~dition ~ more nof.iceable /..-... for low heads. The nappe mll-Y undergo.~Beveral of these mddifications in succession as the head is varied.. T~e I succe~sive forms that appear ,with an increasing stage may differ from those p'er-., taining to similar stages v6th a decreasing head. . The head at . which the changes of nippe.form·occur'·varies with the rate of, . WEIRS 5-23 change of head, whether increasing or decre!lsing, and with other' conditions. Among weirs of irregular section there is a. large cla:ss for which, from· the nature of their section, the napp~ can assume only one form unless drowned. Such weirs, it is suggested, may, if properly calibrated, equal or exceed the usefuJ.D.ess of the thin-edged weir for purposes of stream gaging, b~cause of their stability of section and because the thin-edged weir is, not free from modifi.ca~ion of nappe form for low heads. 'Broad-crested Weirs. A weir approximately rectangular in cross section is. termed a broad-crested weir. Unless otherwise noted, it will be assumed to have vertical fac'es, a pJane level b FIG. 5-6. Broad-crested' weir. crest, and sharp right-angled corners. Figure 5-6'represents a: broad-crest'ed weir of breadth b. The h~ad H should be measured at least 2.SH upstream from the weir. ~ecause of the sharp upstream ed~e, contraction of the nappe occurs. Surface contraetion begins at. a point slightly upstream from .the weir. . The disc4arge over broad-crested weirs is usually expressed l.:!y the equation Q = 'CLHH. '. (5,..10) Experiments on broad-crested weirs have been performed by Blackwell:, Bazin, Woodburn, the U.S. Deep Waterways Board, ll.nd, th~ "0:9" Geo.logical Survey. These exper:iments cover' a wide range of conditions as to head, breadth, and height pf weir. Considerable discrepancy e~ists Pl ~he results ot" the different experimenters, especialJy for ~ads below 0.5 ft. For heads from 0.5 tq about 1.5 it the coefficient becomes more uniform, ~nd for' heads from i.5 ft to tb,at at whi.ch,the nappe becomes detached from the crest, the coeffici~nt as given by·the .different experiments is nearly constant and equals approximately 2.63. '" _.:'.:.".:::::::='-::d -. . '-----' .1. :;" .... 5-40 HAND;B.OOK OF HYDRAULICS Table 5-3. Values of C in the Formula Q = CLH% for l3road- . crested Werrs M"""llI"iod \ :Breadth of crest of weir in fe .. t :~~ 0.5~.l0.7511;0011.5012.001~·~013.~+.~01:··ooI1O:00115.£X 0.2' ~'80r'752'6~2'622'542'4 ~M2'3!l~'M ~A9 ·2.6E 0.4 2.9.1 2.802.72 2.M 2.61 2.11'Q 2.§8 E.54 2.50 2.56 2.7C 0.6 . B2.892.752.642:612.6Q2.682.692.70 2'.70 2.7C O.~ . 3.303.042.852.682.602.60. 2.682.68 2.69 2.M 1.0 . 3.323.142.982.752.66.2.64 2.66 2.67 2.68 2.68 2:63 1.2 1.4 1.6 '1.8 2.0 '2.5 3.0 3.5 4.0 4.5 5.0 . 5,5 - 3.323.203.08 2.8!3 2.70 2.65 2.64 2.672.66 2.69 2.54 3:323.263.202.922.712...,68 2.¥. 2,65 2.65 2.67 2.81 3.323.293.283.012.892.752.682.662.65 2.64 2.m 3.3~3.323.313.072.882.742.1l82.662.65 2.64 2.61 3.3~ a..31 3.303.032.85 2.76 2.722.682.65 2.64 2.~' ! 3.323.323.31\3.283 .. 07 2.89 2 •. 81\~.72 2.67 2.64 2.61 3.323.323.323.323.'203.052.922.732.66 2.64 2.63 3.323.323.32 1 3:323.323.192.972.762.68 2-:64 2.63~ 3:323:323.323.323.323.323.07'\2.792.70 2.64 2.63 3.323.323.323.323.323.323 • .322.882.74 2.64 2.6 .-13.323.323.32\3,.328.323.323.323.072.79 2.64 2.63,. 3.32 S.32 3.323.323.323.323.323.322.88 2.64.2.6 Table 5-4. Values of C in the Formula Q = CLH¥l.for Models of Broad-crested Weirs with Rounded Upstieam porner "il ",:. ~ Head in feet. H Name of 'O~ ;] '0] \ '. \ \ \ .\ '\ \ \ \ experimenter' IQ.-~ p ~ I:l • • '. :B~ --g.;: f.';:. 0'.4 0.6 0.8 1.0 1.5 2.0 ~.5 3.0 4.0 5.0 m "" f~iil ~Ql·41 p:lZ¢lit\!:jt . .. l' . . I I 1 1 r Bazin. •••• , •.••• 0.332.622.462.932.972.983.013.04 Bazin. •••• , ••••• 0.336.562.462,702.82 2.S7 2.89 2.92 U. S. Deep . Waterways ... 0.332.624.51 ..... 2.772.802.832.925.003.083.173.343.50 U. S. Deep . . 'Waterway •.•. 0.33 6.564.56 ........ 2.832.83 2.8s12.8212.8212.s212.s2Lsl WEIRS 5-41 Table 5-5. Values of C in the Formula Q = CLHH for Broa~~ crested Weirs with Crests Inclined Slightly Downward (ay' Energy head -Hf Crest 0.510.610'.710.810.9'11.011.211.4.11.5 -----------1--,--,--,-.-,--,--,--.--,-- Level. .. " ..........•... 12.7812.1912.8012.8112.8212:83/2.8512.8512.85 Slope = 0.004 ........... 2.95 2.94ll. 932.922.912.902.882,8712.87 Slope = 0.026 ........... 3.073.063.05 3.04l}.03 3.02 3.002.99 (b) Length Head in feet, H Slope of of weir 0.1 I 0.210.310.410.510.6.1 0.7 crest in feet 12 to' 1. ........... :_ . . 3.0 .. 2.58 2.81 2.51 2.60 2.54 2.81 2.10 18 to 1 .... : ... · .... 3.0 2.91 2.92 2.53 2.60 2.80 2.74 2.62 18 to 1 ............ 10.0 2.52 2.68 2.13 2.80 2.90 . 2:80 2.68 Table' 5-6. Values of C in. the Formula Q = CLHH for Weirs of . Triangular Cross Section with Vertical Upstream Face. . and Sloping Downstream Face . . Slope of Height Head in feet. H down-of weir streAm. in.feet, 9·2 lo.a 10.41°.510.6.10.71°.81°.9/1.0 11.211.5 fAce P Hor. Vert. a.8s1a.85 a:85/a.85 3.85/a.85 3:~JI,.85 1 to 1 . 2.46. 3.88 a.85 3.85 2 to 1 2.46 3.48 3.483.49 3.493.50 3.50 3.50 a.50 3.50 3.513.51 2~1 1.64 3.56 3.47 3.47 3:51 11:54 3.57 a.58 3.58 3.58 3.59 3.57 3. to 1 1.M ~ ... 2.90 3.11 3.22 3.26 3.33 3.37 3.40 3.40 3.4l. 3.41 5 to 1 2.46 .... S.08 3'.06 3.05 a.05 3.01 3.09 3.12 3.13 3.13 3.13 10 to 1 2.46 2.82 ~.81;l 2.!l4 2.86 2.89 2.90 2 .. 91 2.91 2.92 2.93 _--I'!~--.... -'.:/.' ... Curb InletBasket " Heavy an,d Expensive quipment Is,Not eq,uired To (J Service Work Multi-stage Filtration Captures Everything From Hyd~ocarbons, To Sediment, To Grass Clippings, To Litter ... Everything! NiJ Nee,d To Enter' The. CQnjined ,Space If e C(ltchbasin To Service To Service: , + Remove the .. manhole Ijd + Reach in with by hand or with a ' manhole hook and rem<;>ve the basket . + EID:pty the contents of the basket and' repla'ce·the Storm Boom + Replace the bask~t and manhole lid Techno~f/)gies lric~ 720 Mullet RQad, Suite "H'! , , 'Cape Can:;tveral; FL 32920 " ,Phone (321) 799"(){)Of; Fax (32i) 799·1245 . www.suntrei!tech.com~appel@suntreetech.com ... -. ,. ' .. Curb Inlet Basket (CIB). Curb Inlet Basket Maintenance The Curb' Inlet Basket i~ easily cleaned 'withoutentering' the mahhole and avoids the complexity of having to deal wi.th Safe Entry Laws. Simply reniove the manhole lid, . reach in with a manhole hook to retrieve the b.asket,· erripty the contents of.the basket into a container for disposal, and then replace' the basket and manhole lid. Because the maintenance of the' ern is so simple and quick, one man and a 'small truck can service up to 80 eIBs in one day, removing hundreds of pounds. of debris, and helping' to meet Clean Water Standards. Cleaning the ems. can also be done by the local county/city trash colleb·~ion.services. Installation Square Catch basin:' . For inst?-l1~tion into a square catchbasin, there is a left half and a right half that telescope together to adjust for size, which ri1ak~ up the main body of the ern and mounts solid' to the catchbasin .wall with either· drive pins ,or Tap-Cons.' The non- . removable portion, consi.sts of a tray 'area ~hat . directs the flo;w toward the weir, and a weir . that channels the flow into the removable basket: The basket is placed on .last, and is simply dropped in place and hangs from the top of the weir. (See the schematic on the other side of this page) Ro und Catchbasin: To install the eIB ioto a round catchbasin there are 3 main pieces; the weir,. which attaches to' the catch basin wall, the ·tray which attaches to the' catchbasin wall and weir, and the removable basket. The weir and tray attach to the catchbasin wall with either Tap-Cons or drive pins .. The basket is placed on last, and is just dropped in place. and hangs from the top of the weir. Technologies InCa 720 Mullet Road, Suite "H" . Cape Canaveral, FL 32920 Phone (321) 799-{)001 Fax (321) 799-1245 www.suntreetech.comhappel@suntreetech.com After each storm 'event, the CIB drains completely of all .water and the captured debris dries out and loses its nufrient pollutant load to the air. .~ Technologies. In Co 720 Mullet Road, Suite "H" Cape Canaveral, FL 32920 Phone (321) 799-0001 Fax (321) 799-1245 www.sl.mtreetech.comhappel@suntreetech.com Curb Inlet Basket (CIB) G),Stormwater runoff carrying d'ebris and . poI;tutants enters curb inlet. ~'Adjustable throat ,,:,idth funnels water to weir. The immediate drop in the thro·at elevation prevents head. losses .through the inlet. Sediment wilt" collect along the incoming side of the weir. @ Water ·.flows over weir and into 'removable basket, filtering trash, leaves, yard clippings, sediment, etc.~. If desired,' a hydro~arbon absorption boom .can be fitted along the incoming edge of the baske't. . @ CleaD:er . water leaves basket and enters catchbasin, then flows' d·own. stream. The position of the CIB,high in the. catch hasin, avoids . any restriction of up-stream .pipes flowing through the catchbasin. . The em telescopes to change size so that it can fit almost any catchbasin, : In ,addition, eIBs that fit a round c'atchbasin are also available', licensed under: US Patemt NQ. 5,405,539 e Techno$ogies lnc@ , 720 Mullet Road, Suite ftH" , , Cal?e Canaveral, F,L 32920 Phone (321) 799-0001 Fax (321) 799-j245 ' www.suntreetech.com happel@Sunireetech.c0f!1 Storm Boom Hydrocarbon Absorbtion Booms , ' Designed For Stormwater Applications , . The Storm Boom, has been specifically ,Absorbs lfydrocarbons On Contact designed for stormwater applications to remove hydrocarbons. The outside covering will not ' clog' with s'ediment, all9wing indefmite stormwater penetration, all' the' w~y to the' center of the hoom. The absorbent filler is Absorbent W, and: is made from reClaimed paper mill by-products. It ,is certifieq,by Green Cross ,'as 100% recycled material. ,Ab,sorbed liquid'is draV(ll into ,t~e cellulose fibers through , capillary action and ,locked into the, boom. This, ' process prevents leaching arid draining which is a common proble,m with p.olypropylene ?ooms:: Absorbent W FactsoG , , , @Absorbs 2-3 times more volume than polypropylene ,0 A,bsorbs up to 14 times "tore volume than clay, . o Absorbs immediately on contact ~ Absorbs and retains up to 7 times its weight' ' @Retain,s absorbed hydrocarb.ons; prevents' leaching @It is hydrophobic -'will not absorb water @ Works in a,l temperl1:tures, s~b-freeiing to hot @1 00% organic -environmentally friendly ; @It is not toxic to hUltlans or -the environment ,: @It wilthiodegrade naturally, if lost in tlte envir~'n1!lent @No dangerousfurnes when burned 'oIncinerate at.low temperatur~ Jvith less than 1% ash ·f· • ·.PRIJiqEI'IO:: :. ·761214333176 May!: .2121 2ia02 06: 12PM P2 .' :8"0 CLEAN ENVIRONMENTAL SERVICES' ST·o.RMwATER F1L TRATIOH. SYSTEMS . .... '. . . Pric.e List Effective June ;W02 Gr.ate Inlet Skimmer Box Flange Dimensions . Pri~e Per-Unit Up'to '247' x 14" $ 826.00 2.,5" :1';' 25~ up to 28" x 36" . $' 945.00 .. . 2.9S ) x 3r.' up to 361> X 4g~" ,. $ l064.QO 3T.~X:49!'upto48·,'~54~'· . "'$ 11&3.00 . For l¥ger sizes -pleas,e call for quote.~ '. Curb Inlet Basket Product D~cr;ip#on Crub Inl\:t Units·with Basket 30" to 52" Curb Inld Units with-Basket 54" to 120" Curb Inlet Units with ~~kets i20~'to 180" 180" an,~1 above call for Quote .. P'nce Per Unit . $ 82.~.O.0 ~ $'1000.00' $ 1200.00 . -If'3 1/ ~'G\)~e+' fvf ~ll ?'\1., ~ . i~ 1e.+S· 'Wing I{i :tensions' up to S; iong $ . 1. OO;Op Deflector Shields viI piimo hinge up 36" $ 1.JS.09. . .:nef1e~tor·~bield~ w/'pi(}no hinge up 4W·' $ ·~50 .. 00 .' . JC~b InJ~t ~ts;. c:O~sisfoffiberg1ass ~lfbolted .actos~;t:Q~. width of opel'l~g Wi~h b~ket,r6cAt~:~er .. ~ole. Fron~ tQ.~f~·dep.t.p.:9f~elfdepends OD. depth. . :. ()f lrianlfole . from t.tce c::1f <?~b. . -. . ;. .:. ~ ... ' . Baffle. Box . l?rodl!ct D~ription Price ~er Unit Nu:t,rient :f;)ep·~ating:Bat;Ue.Box toncret~ BQx $25~:O00.00 + Insta.llittion . Bas;ic ur.iit s~e 1~':lijn~fx'8'!"taRx 5'· Wide .. :. All oth~ ~iZes·at.e:p.& ~Ulote only. Ma.ny larger unit~J~,v:e tp·.be p¢lt. "cast·in place.'.~ " ,': .:,,:,,\', .: . ~"':-. .t:" ,,' .. .' '. "':'~" . . . ; ~ .. '.:,~ ... ' ':" .:':".;~:': :' :,: ... ,.::.. :': .: . .. ' ... :.:: .... :;: .. ::~ .. " .. · .. i:' ..... :.'. t .. Storm ·so.oms ... ':.:"::..' .... . ' " " ',:'! .. " :":: "';' ". . . '. . ..'.. .":!': '.,:, . ..... I. :":t{oo~ D~~ii~to~s: . 'Price';Per BO:QIn ... Pa~~gbig \" . : .:,,:':'. ' j~:J?'~ait1~1ier ~y 4~~:;t~ng:' . $ 15.00 : '36 *.OQrns!B·o?,.· .. 3~' Diameter by 9Q"·.LoD.g $ 24.00 . 1& Haains/Box, 5" Di..<Unerei' by'-4~:"~-4~ . .. . 12J?powstB.Gx S-~.~ 9·~!'~Iig:.· "'-$-"$9.:00-" r'" ...... " '~!~?~~~O~ :. ,,' : 0,00 .. , .... I 0 .~: I • , .' • I : .~I .' ' I ... • ", ", ,'I '0 t • . ' .' . . . ~ ~ " .. ~ :;' ',' " .. " . , •• ':': :'.' 0 " '0': .: .... . ".. :,' :' 1 .:" '. .... , • r,' .. , .: .' :', ; . " ,.i "",,,:.,' ,",v' • , , , " • . '. , .' PHONE NO. : 760433317~ Mat,j. 20 2002 06: 13PM P~ 810 CLEAN .' . ENVIRO'NMENTAL SERVIceS . '. STORrJlWATER FILTRATION' SYSTEMS' Installation Cost EJI'ectiYc J'I1UC 2002 Grate Ip.let Skimmer Box Up to 24" x 24" 25" x 25" up to 28" X 36" 291 ' X 37" up to 36"·x 48" 3(' X 49" up to 48" x 54" OYer 48'" x 54" Up.to.10 Units $ 75.00·ea. $ 75.00 ea. $ 75.00 ea. $ 75.00 ea., Per Quote Curb Inlet Basket 10 or Mote'UnHg $ 55.00 ea." $ '55.00' ea.· $ 55.00 ea. $ 65.00 ea. Fer Quote' Unit Size 30" up to 52": Installation includes installing a fiberglass shelf mounted. '0 the concrete vault. Installation of the back basket, located under manhole. Unit caulked. in. place. . $155.00 , U~t Sizes 52" up to 120": Installation includes installi~g a fiberglass shelf mounted, to the COncrete vault Installadon of the, back basket located under Inanb.ole:Unit caulked in place. $200.00 ~ach Unit Sizes 120" ,~p to 180": lnstallatjon inc1U;des installing a fiberglaSs'shelf' ; modnted to the concrete vault. InstallatJon of the baek bas1s:et'located und~ manhole. Unit caulked in p1.a.ce. $250.00 each Curb Wet Units ~th' Custom Work:' Exau+ple -Wing Bxten~ions and Front Deflector' Shields on Grate Curb Inlet Units: Wrng Extensions up ~ 8) long . De~eCt;~r Shi~ld.s up.to 8' loag $100.00 ~h includes in~tall, $150.09 ~h in.eludes lp¥tall ! \ BIO··.CLEAN ENVIRONMENTAL Si3W.VICES P O.'·SO:X SS9, OCEANSIDE CA '~2049' .'. (760) 4.~·3--7640 FAX (760) 433~176 ".1 I I ~ . i ',FROM: .-" .. BID-CLEAN' ENUIRDNMENTAL . PHONE NO. : 7604333176. .Ma~. 20 2002 06: 13PM P4,' ! I~·-···~· . . --.----------------------~--------------------~--~--~----------~--~--~ I? ~ I; If I· l' 1 I .. I , I 1 I J I· .' , 1> .. 1 ,I J. ·1 • , 1 , • i -r 'J I J I J , T :1 } :1 r ···BIO· eLIS·AN. E·NVIRONMENTAL. SERVicES . STORMWATER FILTER SERVI·CE PROGRAM ~. Effo-ctlv. Ytlrch 2.002' Grate Inlet Skimmer 'Box ·LfP.to 28".x 36" ... 29" x 37 up to 48" x·54" Curb Inlet Basket 30)) to 84'·' Shelf & Ba,sket 84" to 144'" Shelf & BaSket 144" to 180" Shelf & Basket . $79.00 per Unit . $89.00 per Unit $79.00 per Unit , $99.00 per Unit' ' . $110.00 per Unit Service Inch~des: Dispo'sal of d~bris c~ptured by filtrati~n device. Replae,ement .of HY9rocarbon Absorption Boom. Report on debris and: coniiltion 9f filters along with . ·recommendatioD.s, sug~estions and 'changes for each mter:' Service ?-greement does n9t .. include any water sampling or testing. . . '. . Bio Clean EnYi,ronmental Service rnaint6nance program is based uPOI,l riormal wear and removal of noroia,l deb$..s ap.d hydrocarbon boo~ from stormwat,er fllters. . -'. '. ;' Ii. . . .. ' A ~um of 10 units. per day 41 needed ioi serv:ice_ Units can be E!. co~bination of . Grate Inlet Skimmer B6xes and Cui'b Inlet Baskets~ . " . . f . . . Bio Clean Eo.Y;ironmental Services' reserves the right to service :fi1~er ,systems that hay~ misused., vandaliied., illegaUy durilped into or not used for intended pUrposes . " Please' s~e Bio Cl~ Service Agreement for specifio details. . ,'. BIO'CLEAN ENVIRONMENTAL SeRVICES, POBOX 869, OC~~N~IDE CA 9i049 (760) 433-·7640 FAX (76Uf433 .. S'1'76 I I I I -I I ·1: I I I- I I I I I I I I I APPENDIXE CDS Technologies Water Quality Treatment Capacities, Details and Costs ... ! .. -... I .. Ir: .. -.. ·· ......... ~_....." ........... : __ ...... : ........ _. ..',,' .... __ .. _ .. 1 _____ .. __ . . -'. "...,. " .. . . J~ .. ' ~ .... >I . •• .., • , '" ...... -~"""'.'... ". \ . . . . ." ., .... ....... ....... " --. . ~ -,; · . APPROXI.MATE·CDS MAINTENANCE COSTS . . .. ·.··:j~~i~: <:·.sUMF«· ~I~~'tt~\f~~: .... '." ··.O.lsP-osAL ~Y.AC·tOR ·:VACTOR .. ; ·t.~t~~· ;'. '. . . :: '.:~: ~ 'Q~~T . .' M.~DEP:.:< : .:(S~SJ' j~C~E£;)': ·:~b,~~ME :. , :MA7ER]~·.!· '; ;:;~e05TSF~' '<: YI.¥~: .;::-! ··.:g,~~~~W;· ·.:.::~S?~T:·:·:~ ... j,,-,., ." ::w£: {iQ'~sf .•.. ·.i ':. +~-' •• :.:.: . . .. ' .: . ~. -: :". - -.... :. ;,-, r' ,:: .. -~; .. .. (CU YD$). $4:OffON ... .,.: .. ()-tfiSY· ,-' .. $-17:$.'1;1 R , PMIU 20 15 0.7 4 1 1 $35 4 $700 . $735 ~ PMSU 20' '15 4 D.7. 4 1 1 $35 4 $700 $735 PMSU 2D 15 D.7 4 1 · . 1 $50 4 $700 $750 . PMSU 20-20 1.1 6 1 1 $50 4 $700 $750 PMSU 2D 25' 1.6 8 1 1 . $5D .4 $700 $750 PMSU 30 20 2.0 10 2 2 $100 4 $700 $800 PMSU 30 30 3 .. 0 20 2 '2 $100 4 $700 $800 PSW 30 30 3.0 20 1 2 $65 4 $700 $765 PMSU 40 30 4.5 25 '6 6 $250 4 $700 $950 PMSU 40 40 6.0 30 6 6 $250 4 $700 $950 PSWC40 30 4.5 80 6 6' $250 4 $700 $950 PSWC4040 . 6.0 8.0 6 . 6 $250' 4 $700 $950 PSW5042 9.0 50 2 2 $.85 4 $700 $785 PSW 50 50 11 60 2 2 $85 4 $700 $785 PSWC 56 53 14 110 6 6 $250 5 $875 $1,125 PSWC 56 68 19 . 110 6 · . 6 $250 5 $875 $1,125 . PSW'70 70 26 150 4 '4 $180 6 $1,050 $1,230 PSW 100 60 30 210 14 16 . . $635 7' $1,225 $1,860 PSW 100 80 50 280 14 16 . $635 7 $1,225 $-1,860 PSW.100 100 64 350 . , 14 . 16 $635 7 $1,225 $1.-860 Assu mptlons: 1. Sump material weighs 85 Ibs per cubic foot , 2. Cleanout tnterval~ are based on the amount and types of fio;;ltables am! sediment car:tured by each CDS unit. . CDS instatlations'jn Southern California typically require 1-2 clea1outS' per year. 3. This ~stimate does not include hazardous waste di~posal fees, if required. 4. Liquids may be deCanted baCk into the CDS unit or discharged Into the sanitay sewerwitho~t fees. E·, Minimum vactor charge of 4 hours ap.pie$. Actual maintenance time is h~s$. Therefore, cleaning IT)ultiple CDS ·l.Ihits in one day is recommended to reduce cost. ... (S). en \; w "-N CSJ CSJ W CSJ to N N 'm en N -I"-N -I"-m w w en o t::;J (j) ~ :r: z' o r o Gl H [Tj (J) -u ~ CSJ W ----CSl W ';r .... ' .. lor-... _I..-... ' .. ;."." .... ___ .... _ ...... ___ . __ _ .' --. ~ ... .' ..... .. '" ":-1'" ", . '. ,.. . _. -.. -............. -l1li-, ... . . ,. . . . '-/ b~\j.." -_....,.~D!, t~" J: " APPROXIMATE CDS COSTS 1 • ", ',_ • ; Q'lffiatme'nt-':" ':::ArlBA'-::C~:~, ?~ ;,,~Q~i,~M~~j'i':~ '. ',iN§]~(tA:iJQ.~:/ <,' ',:': ,',i6+~'l;"~''-:''>':' , :": MODEL: '" ",--: " ,_::; :.(~Sr ~!;;il--:(~ -'n: ~~;'l':::~¢9s:tSt:*~·· :-:-, -', .• ~. • ,. ~.:J. ~ ;:.: ~~~:.-: ' •. ; ~:' {,: ~¢J5"es" :~--:.~ ;'; . ", : :~Q~X$r:,:;;''-i'::~;: ... ' .;:. ..... . ... .::.. ::~,. ... "'., ~; .. : ,-. ',. ~"'" Y':',"::-' •.• PMU20 15 0.7 4 $4,600 $2,400 $7,000 PMSU 20 15 4 0.7 4 $6,900 $2.400 $9,300 pMsu 20 15 0.7 4 $8,200 $3,400 $11,f:lOO PMSU2020 1.1 6 ' $10,500 $3,800 $14,300 PMSU2025 1.6 9 $14,700 $3,800 $18,500 J?M~U 30 20 ,. ... 2 . .0 ..... ii, $19,200 $3.800 $23,{)00 PMSU 30 30 ' 3.0 17 -. $24.500 $4.500 $29,OOO PSW30 30 3.0 " 17 $19.700 $9.300 $29,000 PMSU 40 30 4.5 . 25 $28,000 $6.000 $34,000 PMSU 40 40 6.0 33 $32.700 $7,000 $39,700 .. PSWC4030 4.5 25 $23:900 $13.000 $36.900 PSWC40,40 6.0 . 33 $28;000 $13,000 $41,000 .. PSW5042 9.0 50 . $35,500 $18,000 $53,500 PSW5050 11 61 $36,200 $20,000 $56.200 PSWC5653 14 -: 78 $42,000 $26,0'00 $68,000 PSWC5668 19 106 $5'1.600 $33,000 .$84,600 PSWtO'10 26-'144 $64,900 $4(,000 $104-,900 PSW 100 6.0 3.8 211 $115,300 $60,000 $175,300 . PSW 100 80' 50 " 278 ·$12t600 $7C,OOO $191,600 ~$Y(jO<L1~Q 64 356 $127,900 $8C,OOO $207)900 -----------_ .. _-- ~ = ·Qler (I = 0.2 INlHR, C = n:9) (Based ·on Regional W2ter quality Cqntrol Board Requirements .(SUSMP»). ... Equipment cQsts include delivery to joosite (FOB). Prices are based' on finished gr~da to invert depth~ of 5 ft. -Prices are'subject to change. . . 'H: Installation CCists may va.ry depending, on site, condiUpns. Cost incfudes the cast-in-place weir box (if requrred)_ " , . , ",-,,' '\'. iCS) !~ . . cs) W -.:.." I',) CS). CS), w' CS) LO .1',) 'I',) I tJ1 CIl I',) .P>-I',) .P>-ro w w (fl o d tn --l fTI o :c z o 5 G'J H Gl \J 1> G'J f1l CS) I'-) "-CS) w 1>--,----·· __ · "-..,.-"-' ~---___ --'------:-_-----, , . I~ l Ii' ·I~· I~ I' I: ~ If Ir I·.·. .I). I 1 ~ ,I ~ . ~ I ~ I J PLAN VIEW FIBERGLASS INLET &: SEPARATION CYLINDER INLET PIPE -FLOW~ ELEV. VIEW SEE SHEET 3 , I . ~---' 30"1ll MH COVER &: FRAME 1YP., OTHER HATCH' SYSTEMS READILY AVAILASLE THE INTERNAL COMPONENTS ARE SHOWN IN tHE RIGHT-HAND CONFIGURATION-THESE COMPONENTS MAY.BE FURNISHED IN THE MIRROR IMAGE TO THAT SHOWN (LEFT-HAND CONFIGURATION). 'CDS MODEL PMSU20_~5_4 0.7 CFS CAPACITY FIBERGLASS OIL BAFFLE OUTLET PIPE t. MH ELEV. VIEW SEE SHEEr 3. , I -_..:-l 48" ID MH. 4'-10" 00 I- 1 '~--------------~------------~--------------~D-A-TE----------~---'---S-CA~L~t~ I 12/3/01 "=-2~ FOR USE ON PIPES ~ 18"~ ™ , PRO JE C.T NAME DRAIJN JSF . SHEET 1~~~ ___ ~:P __ R_O __ JE __ C_T ___ L_O_CA_T_I~O~N~ __ APp_RDv_,~ ____ ~l_'~ I,·· --.. i .---------------------------------------~~------~~----------~ I~ I· I I I I .. I . I I· t I 11 I I ~ I j, I· 1 I i I ~ JI ·1\ 1 . I. J, I. .. SECTION CUT NOTES: 48" 10 MH, 4'-10" 00 FIBERGLASS INLET & SEPARATION CYLINDER CENTER OF 25"¢ SCREEN ANP SUMP ACCESS HOLE CENTER 48" 10 MH 1. THE INTERNAL COMPONENTS ARE SHOWN IN "(HE RIGHT-HAND CQNFIGURATION-THESE COMPONENTS MAY BE FURNISHED IN THE MIRROR iMAGE TO THAT SHOWN (LEFT-HAND CONFIGURATION). . 2. ALL STAINLESS STEEL· FAST~NING HARDWARE SUPPLIED BY CDS TECHNOLOGIES, INC. (888) 535.,...7559. . . .CDS MODEL PMSU~O_15..-4 0.7. CFS CAPACITY FOR US·E ON PIPES· ~ 18"¢ DATE ·48" 10 MH, 4'-10" 00 -+-<t. MH ~ OUTLE)'· PIPE ·FASTEN OIL BAFFLE OVER OUTLET USING CONCREfE ANCHORS· .12/3/01· TM DRAW'N JSF PROJECT NAME PROJECT LOCATION APPROV. SCAlE "=2·' . SHEET· 2 : . .. ELEVATION VIEW 30" ¢ MH COVER OTHER HATCH "TYPES L AND FRAME "TYPICAL;7 C CDS SEPARATION CHAMBER READILY AVAILABLE. t MH RISER' -r---,..--__ --,----,-,-__ --c-rr;====R~=::;J1 ---------:---~""II,,}.. FINISHED GRADE ~.J----r-+---4-.;t..,'~I": '" EL .. XX.XX . VARIES . < : ..... : I ' ....... ' ' . ' .. : ,. VARIES' q', 3'_6" lYP .. SECT. CUT ::. SEE SHEET 2 .:> .. '22" !l'. OIL . FIBER'GLASS BAFFLE SEPARATION CYLINDER & INLET . 25" ¢ SEPARATION SCREEN 4 ... . • (SEE NOTE) -. . ... 1.---I...,.."L------i:-rI----.1 '4'-. .. ;d· I l/ . ... SUMP 14" "TYP. '.' I~: ··~.l ." .~ .: .. ;. ! .. '. '~II ' ....... : .. ' .' . '. '. ~ .: .... 6 "TYP. v .... '. • 'II '" .[4"" _ -'--1 I , SECT. CUT SEE SHEET 2 ,...----/A$ ...... INVERT' EL. XX .XX ..,-----/A"" ....... SUMP INVERT '" EL. XX.XX CDS MODEL I. :PMSU20 15_4 NOTE: . TM FOR PROPER INSTALLATION, GREEN FLANGE ON SCREEN FACES' UP FOR RIGHT-HAND L)NIT .CONFiGURATIONS; 'RED FLANGE FASTENS TO FIBERGLASS' SUMP INSERT. . DATE 12/3/01 SCALE PROJECT NAME 1"=2' DRPiVlN SHEET PROJECT LOCATION JSF '3 APPRDV, :4 I- t 11 , If. i I~ I I, I ;. .1 ;. ~. I· ~ I f I. I Ji I r ... I k I I: M . I i I I • i II . j I 1 :1 VARIES 3'-6" (TYPICAL) t. CDS SEPARATION. CHAMBER t. MH RISER FIBERGLASS SEPARATION CYLINDER & ir---h 'INLET I "r-- t..:::::.=..~r~ --.J - - - SCREEN. ~ . . ,.Ir--r'i'c------~--_,! .~.:. . '~<I. SUMP . ~ (BASE) : .. <I .1 L-4'-0" ~I' ·1 L===4'-10"~ .. ' . CO NSTR'UCTION NOTES: 1. APPLY BUTYL MASTIC AND/OR GROUT TO SEAL JOINTS OF MANHOLE STRUCTURE. APPLY LOAD TO MASTlC SEAL IN· JOINTS OF MH. SECTIONS TO Cq'MPRI;SS SEALANT IF NECE;SSARY. UNIT MUST BE. WATER TIGHT, HOLPlh-IG WATER UP TO FLOWLINE INVERT (MINIMUM). . 2. BEFORE PLACING MORE PRECAST COMPONENTS OR BACKFILLING, ENSURE FIBERGLASS INLET AND PIPE INLET INVERT ELEVATIONS MATCH. . . 3. GROUT PIPE CONNECTIONS TO $EAL. JOINT. 4. USE . GRADE RINGS. BLOCKS AND/OR GROUT TO. ENSURE COVER RIM MATCHES FINISHED GRADE. SEAL AS REQ'D. GENERAL NOTES: 1. CDS UNIT COMES COMPLETE· WITH FIBERGLASS INLET/DIVERSION STRUCTURE. OIL BAFFLE AND SCREEN CYLINDER .. PRE-INSTALLED. 1. IN.STALL CDS UNIT PER CDS IN$TALLATION SPECIFICATIONS. 3. CONTRACTOR TO BE EQUIPPED 'TO HANDLE THE HEAVIEST PICK SECTION (6.200 lBS. TYPICAL) . ™ CONSTRUCTION NOTES MODEL PMSU20_15_4 DATE DRA'w'N APPROY. 12/3/01 J.S.F. :', SCALE N.T.S. SHEET 4 I , t CDS SEPARATION 'CHAMBER It MH RISER I 1<-- ; INTERNAL COMPONENT ASSEMBLY ~----r-:;.---n-~ "~L , BAFFLE .1'. AND· I}[STALLATIO}[ }[OTES: .3. POSITiON FIBERGlASS OIL BAFFLE INSIDE BASE BARREL FIBERGLASS S'EPARAllON CYLINDER &: @,Q) AT THE 2S" ABOVE THE'SECllON FLOOR INVERT AND .' " MARK LOCATION BEFORE PLACING NEXT PRECAST 'MH RISER SECTION. TRIM THE BOTTOM OF ll-fE BAFFLE· AS NECESsARY TO ACHIEVE' .2S" HEIGHT WHILE ENSURING INLET , THE TOP FLANGE OF OIL BAFFLE FITS INSIDE THE MH .1 STRUCTURE. MARK ANCHOR BOLT POSITIONS AND PRE:- DRILL HOLES IN' THE PRECAST BASE THE SECTION FOR .. , """ THE CONCRETE EXPANSION ANCHORS. DO NOT fASTEN r . .~ OIL BAFFLE AT THIS TIME -.INSTALLAllON OF THE SEP 14" ® .. ~. @ :I"~ ARATION ASSEMBLY MUST BE COMPLETED FlRST. 3'-6" CD;: @(SCREEN)'.::. 4. 'FIRST CENTER SCREEN OVER FIBERGlASS SUMP HOLE, . TYPL· .). , I >: MATCH DRILL HOLES IN FIBERGLASS SUMP AND INSERT : '. @ 14" TYP. ,,' 1< FOUR (4) SETS OF 1/2" x' 1 1/2" SS BOLT W/ NUT :. ': , (MP), , ... AND WASHERS TO FASTEN SCREEN ASSEMBLY TO FIBER ::'~ :" .~. '~'.'" .:.-:-:6" TYP.;':, : ... . Il: lMPO:::: :~:N FLANGE FA::;TEN~ TO I.;YLINDRII.;AL INLET LANGE FUR " I~ 4:-~~ ~f. ", I 5 i ). RIGHT HAND UNIT;;, RED FLANGE FA::;TEN;; TO ::;UM ; REVER;;E '-===4'-10"==-.,j ::;t.;REEN URIENTATIUN FUR LEFT HAND t.;UNFIGURE UNIT::;. ~--------------------------~----------~ NEXT, CENTER THE FlBERGLASS INLET CYLINDER OVER THE !?CREEN CYLINDER AND MATCH DRILL HOLES'IN 1)-fE FlBERGlASS FlANGE; FASTEN THE FlBERGLASS INLET TO ll-fE SCREEN CYLINDER FLANGE WITH FOUR (4) SETS, OF 1)2" x 1 1/2" SS HEX HEAD BOLTS W/ NUTS &: WASHE~S, (HARDWARESUPPUED BY,.CDS TECHNOLOGIES). PRE-DRILL A MINIMUM OF FOUR' (4) 9/16" HOLES IN THE INLET FLANGES AND PLACE ll-fE. SEPARATlON ASSEMBLY INTO THE PRECAST BASE; MARK THE POSITIONS OF THE INLET FlANGE HOLES ON THE RISER· WALL AND REMOVE .THE SEPARATION ASSEMBLY FROM THE MANHOLE; PRE-DRILL HOLES FOR THE CONCRETE EXPANSION ANCHORS USED TO SECURE THE INLET/SEPARATION ASSEMBLY; REPOSITION THE SEPARATION ASSEMBLY AND FASTEN THE INLET FLANGE TO ll-fE MANHOLE WALL USING A MIMINUM OF FOUR (4) 3/S" x 2 .3/4" SS EXPANSION· ANCHORS. SEAL ANY, ~APS BETWEEN THE INLET AND BARREL SECTION WITH GROUT OR AN APPROPRIATE SEALANT MATERIAL . PLACE OIL BAFFLE WITHIN MANHOLE STRUCTURE ALIGNED WITH THE PRE-DRILLED HOLES AND FASTEN TO MANHOLE· WITH A MINIMUM OF (10) 3/8" x 2 3/4" SS EXPANSION ANCHORS •. SEAL ANY GAPS BETWEEN THE BAFFLE AND THE 'MANHOLE RISER WITH AN APPROPRIATE SEALANT MATERIAL. i ; I 7. I MANHOLE CONSTRUCTION NOTES: I 1. APPLY BtJTYL MASTIC AND/OR GROUT TO SEAL JOINTS OF MANHOLE STRUCTURE. APPLY LOAD TO MASTIC SEAL IN JOINTS :11 , :: 9. OF MH SECTIONS TO COMPRESS SEALANT IF NEESSARY, UNIT MUST 8E WATER TfGHT, HOLDING WATER UP TO FLOWLINE INVERT (MINIMUM).· . IMMEDIATELY AFTER PLACING BASE COMPONENT, ENSURE FIBERGlASS INLET AND PIPE INLET INVERTS MATCH BEFORE PLACING MORE PRECAST COMPONENTS OR BACKFILLING. GROUT PIPE CONNECTIONS TO SEAL JOINT. USE, GRADE RINGS, BLOCKS AND/OR GROUT TO ENSURE COVER RIM MATCHES FINISHED GRADE. SEAL AS REQ'D. :I! . GENERAL NOTES: . 1. INSTALL CDS UNIT PER CDS INSTALLATION SPECIFICATIONS. , 2. CONTRACTOR TO BE EQUIPPED TO HANDLE THE HEAVIEST PICK SECTlONS. I 11 SCALE 11/24/01 NTS' CON STR U CTI 0 N NOTE S . I-DR-A'W-N----------,.-;.-I--"--S·-H~-ET·-' --I MODEL PMSU20_15 __ 4 JSF / WGS APPRDV,, , DATE :1 I I I I I I I I I, I I ,I I I I -I I I APPENDIXF Summary of Approximate Cost$ fQr Treatment Control BMPs ,.,.. ... ~.I...:'Ji. I ~-~.~ ....... iiiIIIt ...... .. -.. .. ...... ~- J~' DRAINAGE OPTION # LOCATIO[\! AREA (AC) Area 1 2 OPTION 1 Area 2 2 Area 3 2.- OPTION 2 EntrreSite 6 COMMON LOT 21 CARLSBAD,CA SUSMP TREATMENT FLOW CALCULATION JULY 28, 2003 .. SUSMP. . SU~MP' RUNOFF TRJ;ATMENT RECOMMJ;:NDED f:;OEfFICIEN"F IN.TEN~.TY . FI.,~W CDS MOI;)El, . (IN/flR) ICF'~U 0.95 0.2 0.36 PMSU20 15 0.95 0.2 0.38· PMSU2015 0.95 0.2 0.38· PMSU2015 0.95 0.2 1.14 PMSU20-.25 .. Depending upon site conditions, 1 ar 2 cleanouts·per year are typically required. 1 w/.,pC( Cf'I-\'.:. \/(/. ... ; 4··e or-fl()~~ tft.4;vt"-t 7 eDS TREATMENT ~49W ·(~FSl 0.7 0.7 0.7 1.6 .. --" .. - TOTAl:. Etr~IMAft:D ESTIMATED MAINTENANCE IN·PLACE COST PER COST CLEANOtJT'"' $ 30,000 $ 750.00 $ 18.000 $ 7/iOOn - CSl -..J ...... 1'0 CD ...... 1'0 CSl CSl w tSi· LD W co (JJ en 1'0 .p.. 1'0 .p.. CD W w en () t:1 ~ :'-l fTl· e) :c "U ~ CSl 1'0 ...... cSl 1'0 . IiiIIIJ ........... ~ _~ '_r ._~ _: ____ : __ . ___ _ SUMMARY OF APPROXIMATE COSTS FOR TREATMENT CONTROL BMPs ._ t'qst Construction BMP's for Lot 21 Project Manufacturer 1 (Suntree Technologies Filter Insert Products) Drainage Map Type of Inlet Equipment Material Cost Installation Cost Annual Maintenance Node# Cost -102 C Curb Inlet Basket $826 $155 $316 202 G-3 Curb Inlet Basket $1,200 $200 $316 302 B Curb Inlet Basket $826 $155 $316 Total: $2,852 $510 $948 Note 1: Treatment Flow Capa.cities for B-1 Inlets is 0.85 cfs (see Appendix C). All Required Treatment flows have been Provided with the 'units specified ablove. Note 2: For locations of basins, node numbers, and inlets, refer to "Via de la Valle Preliminary Drainage Map for Proposed On-Site Condition", Located in Map Pocket 2 Note 3: Ann~al maintenance cost is based on an estimated 4 cleanings per year. Refer to section 7.0 of the water quality technical report for additional information on required frequency of maintenance. .. . . .... . . k ~"" • ~ '. - __ J: -_:---... : -'---~crlF .. SUMMARY OF APPROXIMATE COSTS FOR TREATMENT CONTROL BMPs ,,, Pbst Construction BMP's for Lot 21 Project Manufacturer 2 (Kristar Enterprises Filter Insert Products) .iiIiiIiIii. . ~.;...-~~~ ~-.. .. ~"1 "«--79 ""--'''''!'!!I Equipment Material Cost I Installation Cost I Annual Maintenance -$531 $42.50 $893 $42.50 $531 $42.50 " Fio-Gard Plus Catch Basin Filter Insert (Curb Opening Style) II;a Fio-Gard Plus Catch Basin Filter Insert (Curb Opening Style) .:; Fio-Gard Plus Catch Basin Filter Insert (Curti Opening Style) Total: $1,424 $85.00 Note 1: Treatment Flow Capacities for Flo-Grd Plus in J Inlets is 1.76 cf~ and b-1 inlets is 2.76 cfs (see Appendix D). All required treatment flows have been provided with the units specified above. Note 2: For locations of basins, node numbers, and inlets, refer to "Via de la Valle Preliminary Drainage Map for . Proposed On-Site Condition", Located in Map Pocket 2 Note 3: Annual maintenance cost is based on an estimated 4 cleanings per year. Refer to section 7.0 of the water quality technical report for additional information. on required frequency of maintenance. Cost $150 $150 $150 $300 =-'''~''( """ ' .. --~ , i· i , , I I .' Ii I R' \d_14431\4431oTr1, cIQn \ I 1 .; j l .-"-i ' i \\ " \ I , \ i" ~, ;. , . \ "i ,.' -l \ \III"Y _I'"I bl \R l(:kSt<:l"\dOl"'<lIl\ I D I oWl O_SE\SO\Pen\ool Gorrp. pen ze·JUL-lO(ll I~'I& i J i ·1 , , , \ , i -....... i--, j - 'Z7 8 ~, ~)!.~t5< i. X !J:.. i~r j..~ . s~·· " . . I , l~ . f\' ' I \ , \ I, \ I t1';\ i \ ! f ! I , \ .' i V;102 ' 376.54 @) .", .. \ \\ " • . , -:. - \. , /' \ '\\\ \ , '-\\ \\ ' " \. \ \ \\ ,~.. '\ P"\\" , \ 'lo , ">. \ r PARCEL 2 " \ \ C-' \ \ \ L I'. ,~-.? ., . -..... ,. '---'---~--" --.---" '," .... -.-' .-" "'_.uoo. __ ~ _. r<II .\ , , I 'X ~f11 7 ." ~)...;". , ~ (}0 Ot.:~ .. I , PARCEL 3 ; ; -r'-r;;;t;;~~~s ~;;;;~~;;;;~;--\\~..p,;~~j.s -20~--!hf-"---'-----:7'"~-S -----".----!i~,'+c\_,;__J"T___++---cc/ S ----,-t,. . \~, I I , I I I I I t , , I I' i! ---··t:; I: ( , ; , 1 \' i I ~ )( , ----_._--------)C. X 3E ,t:;p Hi A ... / , ----.. " l~.Q,) ~. ,-- ........ ...--~.' ------..... --................ -.... "'-;-====-"'============='===c"==""""'.,.-o=========~~"""' .. ~.==.-____ -~========:::::..-~';:~; ....... i . (t.OBAC) I , . I .; ~ : 'I: 1 • I ., , . -.. PROPERTY LINE r • 'r I I , I ' . . , II I: I r 1 r--=-r.;~T61 1 .;, 1 ,J 1 1 . (P;-i , , --1--/ . ·· .. r .. -c'! ~-, .. i ! I i I, I ' ) 1 I ~ I i , X I 387.4 K· ~ol·r .' , ~~. , }, 0", -i Ii : i (I j . -----:--_:,,""=~-_o-:---" I i.'=-'. \\ _. ~~\. ~l x / '--, .;-.. ,'J "' .. '-~'" L.EGEND: • . (O.OOAc) Ixxxxx I. LOCATION OF POTENTIAL COS TECHNOLOGIES IN-LINE STORM WATER UNIT . LOCA TION OF POTENTIAL CURB INLET FILTER INSERT DRAINAGE BASIN ACREAGE (ACRE) NODE NUMBER DRAINAGE BASIN BOUNDARY . - - -INITIAL BASIN BOUNDARY LOT 21 -o r<l " = ~ w -' « u Vl PRELIMINAR,Y DRAINAGE MAP FOR PROPO:SED ONSITE CONDITION MAP #1 I ! i I ~ ~ ) . ,