HomeMy WebLinkAboutCDP 2017-0064; SLOWIK ADU; GEOTECHNICAL REPORT UPDATE; 2017-08-08EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC. 10925 HARTLEY ROAD, SUITE "I" SANTEE, CALIFORNIA 92071 619 258-7901 FAX 619 258-7902 Sharon Slowik 3960 Sunnyhill Drive Carlsbad, California 92008 Subject: Geotechnical Report Update Proposed New Primary Residence 3960 Sunnyhill Drive City of Carlsbad, California 92008 August 8, 2017 Project No. 03-1106H6(A) Reference: "Limited Site Investigation, Proposed New Primary Residence, 3960 Sunnyhill Drive, City of Carlsbad, California", Project No. 03-l 106H6(A), Prepared by East County Soil Consultation and Engineering, Inc., Dated April 21, 2003. Dear Mr. & Mrs. Slowik: In accordance with your request, we have reviewed the referenced geotechnical report and visited the site on August 7, 2017. The proposed building pad was found as described in the referenced geotechnical report. Therefore, the recommendations provided in the referenced geotechnical report are still valid for the proposed development. However, to be in accordance with the present guidelines for geotechnical reports, the following additional recommendations may be incorporated into the project design and construction. SEISMICITY Regional Seismicity Generally, Seismicity within California can be attributed to the regional tectonic movement taking place along the San Andreas Fault Zone, which includes the San Andreas Fault and most parallel and subparallel faults within the state. The portion of southern California where the subject site is located is considered seismically active. Seismic hazards are attributed to groundshaking from earthquake events along nearby or more distant Quaternary faults. The primary factors in evaluating the effect an earthquake has on a site are the magnitude of the event, the distance from the epicenter to the site and the near surface soil profile. According to the Fault-Rupture Hazard Zones Act of 1994 (revised Alquist-Priolo Special Studies Zones Act), quaternary faults have been classified as "active" faults, which show apparent surface rupture during the last 11,000 years (i.e., Holocene time). "Potentially-active" faults are those faults with evidence of displacing Quaternary sediments between 11,000 and 1.6 million years old. PAUL & SHARON SLOWIK/ 3960SUNNYHILL DRIVE ROJECT NO. 03-l 106H6(A) Seismic Analysis Based on our evaluation, the closest known "active" fault is the Rose Canyon Fault located approximately 4.4 kilometers (2.74 miles) to the west. The Rose Canyon Fault is the design fault of the project due to the predicted credible fault magnitude and ground acceleration. The Seismicity of the site was evaluated utilizing the 2008 National Hazard Maps from the USGS website and Seed and Idriss methods for active Quaternary faults within a 50-mile radius of the subject site. The site may be subjected to a Maximum Probable Earthquake of 6.9 Magnitude along the Rose Canyon Fault, with a corresponding Peak Ground Acceleration of 0.46g. The maximum Probable Earthquake is defined as the maximum earthquake that is considered likely to occur within a I 00-year time period. The effective ground acceleration at the site is associated with the part of significant ground motion, which contains repetitive strong-energy shaking, and which may produce structural deformation. As such, the effective or "free field" ground acceleration is referred to as the Repeatable High Ground Acceleration (RHGA). It has been determined by Ploessel and Slosson (1974) that the RHGA is approximately equal to 65 percent of the Peak Ground Acceleration for earthquakes occurring within 20 miles of a site. Based on the above, the calculated Credible RHGA at the site is 0.30g. 2016 CBC Seismic Design Criteria A review of the active fault maps pertaining to the site indicates the location of the Rose Canyon Fault Zone approximately 9.4 km (5.9 miles) to the west. Ground shaking from this fault or one of the major active faults in the region is the most likely happening to affect the site. With respect to this hazard, the site is comparable to others in the general area. The proposed single- family residence should be designed in accordance with seismic design requirements of the 2016 California Building Code or the Structural Engineers Association of California using the following seismic design parameters: P~TER VALUE 2016 CBC & ASCE 7 REFERENCES Site Class D Table 20.3-1/ ASCE 7, Chapter 20 Mapped Spectral Acceleration For Short Periods, 1.113g Figure 1613.3.1(1) s. Mapped Spectral Acceleration For a I-Second 0.428g Figure 1613.3.1(2) Period, S1 Site Coefficient, Fa 1.055 Table 1613.3.3(1) Site Coefficient, F v 1.572 Table 1613.3.3(2) Adjusted Max. Considered Earthquake Spectral 1.174g Equation 16-3 7 Response Acceleration for Short Periods, SMs Adjusted Max. Considered Earthquake Spectral 0.673g Equation l 6-3 8 Response Acceleration for I -Second Period, SM 1 5 Percent Damped Design Spectral Response 0.783g Equation 16-39 Acceleration for Short Periods, Sos 5 Percent Damped Design Spectral Response 0.448g Equation 16-40 Acceleration for I-Second Period, S01 2 PAUL & SHARON SLOWIK/ 3960SUNNYH/LL DRIVE ROJECT NO. 03-1106H6(A) Geologic Hazard Assessment Ground Rupture Ground rupture due to active faulting is not considered likely due to the absence of known fault traces within the vicinity of the project; however, this possibility cannot be completely ruled out. The unlikely hazard of ground rupture should not preclude consideration of "flexible" design for on-site utility lines and connections. Liquefaction Liquefaction involves the substantial loss of shear strength in saturated soils, usually sandy soils with a loose consistency when subjected to earthquake shaking. Based on the absence of shallow groundwater and consistency of the bedrock material, it is our opinion that the potential for liquefaction is very low. Landsliding There is no indication that landslides or unstable slope conditions exist on or adjacent to the project site. There are no obvious geologic hazards related to landsliding to the proposed development or adjacent properties. Tsunamis and Seiches The site is not subject to inundation by tsunamis due to its elevation and distance to the ocean. The site is also not subject to seiches (waves in confined bodies of water). PERMANENT SLOPES Permanent cut and fill slopes are anticipated to be less than 10 feet in height and may be constructed no steeper than 2: 1 (horizontal to vertical). These slopes are anticipated to be grossly stable. It is recommended that drought resistant vegetation be planted as soon as practical to enhance the stability of the slope surfaces. TEMPORARY SLOPES For the excavation of foundations and utility trenches, temporary vertical cuts to a maximum height of 4 feet may be constructed in fill or natural soil. Any temporary cuts beyond the above height constraints should be shored or further laid back following a I: I (horizontal to vertical) slope ratio. OSHA guidelines for trench excavation safety should be implemented during construction. PRESATURATION OF SLAB SUBGRADE Due to the granular characteristics of the subgrade soils, presoaking of subgrade prior to concrete pour is not required. However, subgrade soils in areas receiving concrete should be watered prior to concrete placement to mitigate any drying shrinkage, which may occur following site preparation and foundation excavation. 3 PAUL & SHARON SLOWIK/ 3960SUNNYHILL DRIVE ROJECT NO.03-1106H6(A) DRAINAGE Adequate measures should be undertaken to finish grade the site after the structure and other improvements are in place, such that the drainage water within the site and adjacent properties is directed away from the foundations, footings, floor slabs and the tops of slopes via rain gutters, downspouts, surface swales and subsurface drains towards the natural drainage for this area. In accordance with the 2016 California Building Code, a minimum gradient of 2 percent is recommended in hardscape areas adjacent to the structure. In earth areas, a minimum gradient of 5 percent away from the structure for a distance of at least 10 feet should be provided. If this requirement cannot be met due to site limitations, drainage can be done through a swale in accordance with Section 1804.4 of the 2016 California Building Code. Earth swales should have a minimum gradient of 2 percent. Drainage should be directed to approved drainage facilities. Proper surface and subsurface drainage will be required to minimize the potential of water seeking the level of the bearing soils under the foundations, footings and floor slabs, which may otherwise result in undermining and differential settlement of the structure and other improvements. If we can be of any further assistance, please do not hesitate to contact our office. Respectfully submitted, Mamadou Saliou Diallo, P.E. RCE 54071, GE 2704 MSD/md 4 EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC. 10925 HARTLEY ROAD, SUITE "I" SANTEE, CALIFORNIA 92071 (619) 258-7901 Fax (619) 258-7902 Mr. & Mrs. Paul Slowik 3960 Sunnyhill Drive Carlsbad, California 92008 Subject: Soil Bearing Value Recommendation Proposed Second Story Addition 3960 Sunnyhill Drive City of Carlsbad, California Dear Mr. & Mrs. Slowik: July 16, 2003 Project No. 03-1106H6 In accordance with your request, we have performed laboratory testing on a representative sample of the foundation soils to provide a soil bearing value for the design of a second story addition over the south side of the existing residence located at 3960 Sunnyhill Drive, in the City of Carlsbad, California. The foundation soils associated with the Terrace deposits Formation (Qt2 ) consist of brown, silty fine-grained sand (SM) exhibiting a very low potential for expansion (Expansion Index = zero). The footing of the original house was 12 inches wide and 12 inches deep, while the footing of the previous single story addition to the east was 12 inches wide and 18 inches deep. SOIL BEARING VALUE An allowable soils bearing value of 1500 pounds per square foot may be used for the design of continuous and spread footings at least 12 inches wide and founded a minimum of 12 inches into the dense native soils. This value may be increased by 20 percent for each additional foot of depth or width to a maximum value of 4500 lb/ft2, as set forth in the 1997 Edition of the Uniform Building Code, Table No. 18-1-A. SLOWIK PROJECT NO 03-1106H6 GEOLOGIC HAZARDS A review of the available geological literature pertaining to the site indicates the existence of the Rose Canyon Fault Zone approximately 9. 0 Km to the west. Ground shaking from this fault or one of the major active faults in the region is the most likely happening to affect the site. With respect to this hazard, the site is comparable to others in the general area. The proposed second story addition should be designed in accordance with seismic design requirements of the 1997 Uniform Building Code or the Structural Engineers Association of California using the following seismic design parameters: PARAMETER VALUE UBC REFERENCE Seismic Zone Factor, Z 0.40 Table 16-I Seismic Source B Table 16-U Soil Profile Type So Table 16-J Near-Source Factor, Na 1.0 Table 16-S Near-Source Factor, Nv 1.1 Table 16-T Seismic Coefficient, Ca 0.44 Table 16-Q Seismic Coefficient, Cv 0.70 Table 16-R Based on the absence of shallow groundwater and consistency of the Terrace Deposits, it is our opinion that the potential for liquefaction is very low. If we can be of any further assistance, please do not hesitate to contact our office. Laboratory test results and references are parts of this report. Respectfully submitted, ~ '/,-, ~\ .~ -'rft /~ <'\()'u ~'-I)/,. ~ ;::._'>J ~'\I ~ No.C054071 L ~ ·,J., ' Mamadou Saliou Diallo, P.E. RCE 54071 MSD/md 2 SLOWIK PROJECT NO 03-1106H6 PAGE L-1 LABO RA TORY TEST RESULTS RES UL TS OF EXP ANSI ON INDEX TEST An expansion test in conformance with ASTM D4829 was performed on a representative sample of on-site soils to determine volumetric change characteristics with change in moisture content. The recorded expansion of the sample is presented as follows: INITIAL MOISTURE CONTENT% 8.4 SATURATED MOISTURE CONTENT% 16.5 INITIAL DRY DENSITY LB.ICU. FT. 115.5 EXPANSION INDEX 0 RESULTS OF PARTICLE SIZE ANALYSIS . ;. U.S. Standard Sieve Size . ASTM D-422) l" 1/2" 3/8" #4 #8 #16 #30 #60 #100 #200 uses 3 100 99 97 94 85 41 26 21 SM SLOWIK PROJECT NO 03-1106H6 REFERENCES 1. "1997 Edition, Uniform Building Code, Volume 2, Structural Engineering and Design Provisions". 2. "Maps of Known Active Fault Near-Source Zones in California and Adjacent Portions of Nevada", Page 0-37, used with the 1997 Edition of the Uniform Building Code, Published by International Conference of Building Officials. 3. "Geologic Maps of the Northwestern Part of San Diego County, California. Plate No. 1, Geologic Maps of the Oceanside, San Luis Rey and San Marcos 7.5' Quadrangles", by Siang S. Tan and Michael P. Kennedy, 1996. 4 EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC. 10925 HARTLEY ROAD, SUITE "I" SANTEE, CALIFORNIA 92071 (619) 258-7901 Fax 258-7902 Mr. & Mrs. Paul Slowik 3960 Sunnyhill Drive Carlsbad, California 92008 April 21, 2004 Project No. 03-1106H6(A) Subject: Limited Site Investigation Proposed New Primary Residence 3960 Sunnyhill Drive City of Carlsbad, California Dear Mr. & Mrs. Slowik: In accordance with your request, we have performed a limited investigation of the soil conditions at the subject site. The investigation was undertaken to provide the soil engineering criteria for site grading and recommend an appropriate foundation system for the proposed residence. Our investigation has found that the proposed building pad is underlain by undocumented fill soils, topsoil and colluvium to a maximum depth of approximately 5.0 feet. Below the colluvium, medium dense to dense sandstone of the Terrace Deposits Formation was encountered to the maximum explored depth of 5.5 feet. It is our provided opinion that the the recommendations construction. Respectfully submitted, Mamadou Saliou Diallo, P.E RCE 54071 proposed herein development is are implemented feasible during SLOWIK PROJECT NO.03-1106H6(A) INTRODUCTION This is to present the findings and conclusions investigation for a proposed two-story, single-family be located on the east side of Sunnyhill Drive, in Carlsbad, California. of a soil residence to the City of The objectives of the investigation were to evaluate the existing soils conditions and provide recommendations for the proposed construction. In order to accomplish these objectives, borings were drilled to a maximum depth of and loose bag samples were obtained, and performed. SITE DESCRIPTION AND PROPOSED CONSTRUCTION two (2) 5.5 feet; laboratory exploratory undisturbed tests were The subject site is located on the east side of Sunnyhill Drive, in the City of Carlsbad, California. It is a previously graded cut and fill lot that was developed with a single-story house. This residence will remain as a granny flat. The area of the proposed second dwelling unit was an elevated pad approximately 15 feet above existing grade. Vegetation consisted of trees, shrubs and grass. It is our understanding the proposed construction will consist of a two-story, wood-framed structure to be utilized as a primary residence. The plot plan, Plate No. 1 provides a layout of the proposed development. FIELD INVESTIGATION On March 5, 2004, two (2) exploratory borings were drilled to a maximum depth of 5.5 feet below existing grade with a hand auger. The approximate locations of the borings are shown on the attached Plate No. 1, entitled "Location of Exploratory Borings". A continuous log of the soils encountered was recorded at the time of excavation and is shown on Plate No. 2 entitled "Summary Sheet". The soils were visually and texturally classified according to the filed identification procedures set forth on the attached Plate No. 3 entitled "Uniform Soil Classification Systemu. 2 SLOWIK PROJECT NO. 03-l 106H6(A) SUBGRADE CONDITIONS -Undocumented fill soils, topsoil and colluvium underlie the proposed pad to a maximum depth of approximately five feet. These soils generally consist of silty sand with a trace of clay and a loose consistency. Dense sandstone of the Terrace Deposits Formation was underlying the colluvium. EXPANSIVE SOILS An expansion index test was performed on a select sample of the undocumented fill soils to determine volumetric change characteristics with change in moisture content. An expansion index of 14 indicates a very low expansion potential of the fill soils. GROUNDWATER Groundwater was not investigation. Static greater than 100 feet. proposed development. GEOLOGIC HAZARDS encountered during the course of our groundwater is anticipated at a depth We do not expect groundwater to affect the A review of the available geological literature pertaining to the site indicates the existence of the Rose Canyon Fault Zone approximately 9.0 Km to the west. Ground shaking from this fault or one of the major active faults in the region is the most likely happening to affect the site. With respect to this hazard, the site is comparable to others in the general area. The proposed accordance with Building Code California using residential structure should be designed in seismic design requirements of the 1997 Uniform or the Structural Engineers Association of the following seismic design parameters: PARAMETER VALUE UBC REFERENCE Seismic Zone Factor, Z 0.40 Table 16-I Seismic Source B Table 16-U Soil Profile Type So Table 16-J Near-Source Factor, Na 1.0 Table 16-S Near-Source Factor, Nv I.I Table 16-T Seismic Coefficient, Ca 0.44 Table 16-Q Seismic Coefficient, Cv 0.70 Table 16-R ,., .) SLOWIK PROJECT NO.03-1106H6(A) Based on the absence of shallow groundwater and consistency of the Terrace Depostts Formation, it is our opinion that the potential for liquefaction is very low. CONCLUSIONS AND RECOMMENDATIONS The following conclusions and recommendations are based upon the analysis of the data and information obtained from our soil investigation. .This includes visual inspection; field investigation; laboratory testing and our general knowledge of the soils native to the site. The site is suitable for the proposed residential development provided the recommendations set forth are implemented during construction. GRADING AND EARTHWORK Site grading should begin with clearing and grubbing, e.g. the removal of vegetation and deleterious materials. Subgrade soils extending to the Terrace Deposits Formation in the proposed building pad should be overexcavated, moisture conditioned within 2 percent over optimum and compacted to a minimum of 90 percent relative compaction. Proper keying and benching of the subgrade along the adjacent slopes should be observed during the grading operation, should the proposed footings be built on those slopes. The actual depth and extent of removal should be evaluated in the field at the time of excavation by a representative of this firm. Grading should be performed in accordance with the attached appendix A. FOUNDATION AND SLAB a. Continuous footings are suitable for use and should extend a minimum of 18 inches for the two-story residence into the compacted fill soils. These footings should be at least 15 inches in width and reinforced with two #5 steel bars; one bar placed near the top of the footings and the other bar placed near the bottom of the footings. b. Concrete floor slabs should be a minimum of 4 inches thick. Reinforcement should consist of #3 bars placed at 16 inches on center each way. Slab reinforcement should be placed within the middle third of the slab by supporting the steel on chairs or concrete blocks "dobies". The slab should be underlain by 2 inches of clean sand over a 10-mil visqueen moisture barrier. 4 SLOWIK PROJECT NO. 03-1106H6(A) The effect of concrete shrinkage will result in virtually all concrete slabs. To reduce the extent of the concrete should be placed at a maximum of 4 inch minimum steel recommended is not intended to prevent cracks. cracks in shrinkage, slump. The shrinkage c. Where moisture sensitive floor coverings are anticipated over the slab, the 10-mil plastic moisture barrier should be underlain by a capillary break at least 2 inches thick, consisting of coarse sand, gravel or crushed rock not exceeding 3/4 inch in size with no more than 5 percent passing the #200 sieve. d. An allowable soil bearing value of 1500 pounds per square foot may be used for the design of continuous and spread footings founded a minimum of 12 inches into the compacted fill soils. This value may be increased by 20 percent for each additional foot of width or depth to a maximum value of 4500 lb/ft2, as set forth in the 1997 Edition of the Uniform Building Code, Table No. 18-1-A. e. Lateral resistance to horizontal movement may be provided by the soil passive pressure and the friction of concrete to soil. An allowable passive pressure of 200 pounds per square foot per foot of depth may be used. A coefficient of friction of 0.35 is recommended. The soils passive pressure as well as the bearing value may be increased by 1/3 for wind and seismic loading. FOUNDATION SETBACK Compacted fill soils that occur within 8 feet of the face of slope possess poor lateral stability, even though they have been certified with a relative compaction of 90 percent or better. Proposed structures and other improvements that are located within 8 feet of the face of compacted fill slopes could suffer differential moveme~t as a result of the poor lateral stability of these soils. Therefore, foundations and footings for the proposed structures or other improvements should be placed at least 8 feet back from the top of these slopes. Foundations placed closer to the top of slope than 8 feet should be deepened such that the bottom of the foundation is at least 8 feet back from the face of the slope. 5 SLOWIK PROJECT NO. 03-1106H6(A) SETTLEMENT Settlement of compacted fill soils is normal and should be anticipated. Because of the type and thickness of the fill soil and the light building load, the settlement should be within acceptable limits. UTILITY TRENCH EXCAVATIONS Excavations for on-site utility trenches may be made vertically for shallow depths and must be either shored or sloped at lH: lV for depths greater than 4 feet. Utilities should be bedded and backfilled with clean sand or approved granular soil to a depth of at least one foot over the pipe. This backfill should be uniformly watered and compacted to a firm condition for pipe support. The remainder of the backfill should be on-site soils or non-expansive imported soils, which should be placed in thin lifts, moisture conditioned and compacted to at least 90 % relative compaction. DRAINAGE Adequate measures should be undertaken to properly finish grade the site after the structures and other improvements are in place, such that the drainage water within the site and adjacent properties is directed away from the foundations, footings, floor slabs and the tops of slopes via surface swales and subsurface drains towards the natural drainage for this area. Proper surface and subsurface drainage will be required to minimize the potential of water seeking the level of the bearing soils under the foundations, footings and floor slabs, which may otherwise result in undermining and differential settlement of the structures and other improvements. 6 SLOWIK PROJECT NO.03-1106H6(A) LIMITS OF INVESTIGATION The recommendations provided in this report pertain only to the site investigated and based upon the assumption that the soil conditions do not deviate from those disclosed in the borings. If any variations or undesirable conditions are encountered during construction, or if the proposed construction will significantly differ from that planned at the present time, East County Soil Consultation and Engineering, Inc. should be notified so that supplemental recommendations can be provided. Plates No. 1 through 3, Pages L-1 & L-2, References and Appendix A are parts of this report. Respectfully submitted, ' ~·---. ~ ~ No.C054071 Exp. \ t.-3,\ - Mamadou Saliou Diallo RCE 54071 MSD/md ,L 7 1J ( ~ ~ I 1~ ~ ~ EAST COUNTY SOIL CONSULTATION & ENGINEERING, INC. I 0925 HARTI..EY RD . SUITE I. SANTEE. CA 9207 I (6 I 9) 258-790 I Fax (6 I 9) 258-7902 .. \l fJ~tJ/} ti! r· 1;.f. DEPTH Surface 1. 5' 3. 0' 4. 0' 5. 0' SLOWIK PROJECT NO 03-l 106H6(A) PLATE NO. 2 SUMMARY SHEET NO. 1 BORING NO. 1 SOIL DESCRIPTION UNDOCUMENTED FILL (Quf) tan, moist to wet, loose, silty, sand with a trace of clay " " " " " TOPSOIL brown, damp, loose, silty sand with rootlets COLLUVIUM (Qal) brown, moist, loose, fine-grained silty sand (SM) TERRACE DEPOSITS (Qt4 ) tan, damp to moist, medium dense to dense, silty sand (SM) 5.5' bottom of boring, no caving, no groundwater boring backfilled 3/5/04 DEPTH Surface 2 • 0 I 3.5' BORING NO. 2 SOIL DESCRIPTION UNDOCUMENTED FILL (Quf) tan, moist to wet, loose, silty, sand with a trace of clay COLLUVIUM (Qal) brown, moist, loose, fine-grained silty sand (SM) TERRACE DEPOSITS (Qt") tan, damp to moist, medium dense to dense, silty sand (SM) 4.0' bottom of boring, no caving, no groundwater boring backfilled 3/5/04 8 y M 98.9 16.1 y M 103.0 10.5 ! MAJOR DIVISIONS SYMBOL DESCRIPTION GW WELL GRADED GR.A VELS OR GR.A VEL· SAND MIXTURES. LITTLE OR NO FINES GRAVELS GP (MORE THAN½ POORLY GRADED GR.A VELS OR GR.A VEL·SAND OF COARSE MIXTURES, LITTLE OR NO FINES FRACTION GM SILTY GR.A VELS, GRAVEL-SAND-SILT MIXTURES >NO. 4SIEVE SIZE) COARSE GC GRAINED SOILS CLAYEY GR.A VELS, GRA VEL·SA.i'ID-CLA Y MIXTURES (MORE THAN ½ OF SOIL > S"\V NO. 200 SIEVE SIZE) WELL GRADED SANDS OR GRA YELL Y SANDS, LITTLE OR NO FINES SANDS SP (MORE THAN½ POORLY GRADED SANDS OR GRA YELL Y SANDS, OF COARSE LITTLE OR NO FINES FRACTION SM <NO. 4SIEVE SILTY SA.i'IDS, SIL T-SA.i'ID MIXTURES SIZE) SC CLAYEY SANDS, SAND-CU. Y MIXTURES ML INORGANIC SIL TS A.'ID YER Y FINE SA.i'IDS, ROCK SILTS & FLOUR, SIL TY OR CLAYEY FINE SANDS OR CLAYEY SIL TS WITH SLIGHT PLASTICITY CLAYS CL INORGA.i'IIC CLAYS OF LOW TO MEDIUM LIQUID LIMIT PLASTICITY, GRA YELL Y CLAYS, SANDY CLAYS, < 50 SIL TY CLAYS. LEAN CLAYS FINE GRAINED OL SOILS ORGANIC SILTS AND ORGA."'-IIC SILTY CLAYS OF LOW PLASTICITY (MORE THAN ½ OF SOIL < MH NO. 200 SIEVE SIZE) INORGA.'lIC SILTS, MICACEOUS OR DIATOMACEOUS SILTS & FINE SA.i'lDY OR SIL TY SOILS, ELASTIC SIL TS CLAYS CH INORGA.'lIC CLAYS OF HIGH PL\STICITY, FAT LIQUID LIM!, ~50 CLAYS OH ORGA.i'lIC CLAYS OF MEDIUM TO HIGH PLASTICITY, ORGANIC SIL TY CLAYS. ORGANIC SIL TS HIGHLY ORGANIC SOILS I Pt PEAT AND OTHER HIGHLY ORGA.i'IIC SOILS CLASSIFICATION CHART (lJNIFIED SOIL CLASSIFICATION SYSTEM) 70 ,-----------,----..--------, CL..\.SSIFICA TION R.\.NGE OF GR.\.IN SIZES I 50 1--.,..--...,...------t--,,,_ _______ _,. U.S. STANDARD I GR.\.IN SIZE IN I SIEVE SIZE :'<IILLIMETERS _: 10 BOCLDERS I Above 12 Inches Above 305 ~ 1-----:--....,....--,-...c.--+----'--_;.__,,,.:::.....____, COBBLES ! 1: Inches To 3 Inches I 305 To 76.2 ~ ,.c l--'-----'-----:1"-+--_;._-,,c. ___ ____, GR.\ YEL I 3 Inches to No. 4 i i6.2 to 4. :'6 I "' Coarse i 3 Inches to'~ Inch 1· 76.2 to 19. l ! § io Fin.: \ ~1• [nch to No. 4 19 i to 4.76 I ;; SA.\iD '.'Jo 4 to No. 200 4.76 to 0 0i'.l ~ :o l----'---,t:.--"----A----------1 Coarse No. 4 to No. l 0 4. i6 to 2.00 Medium No. l Oto No. 40 2.00 to 0.420 Fine No. 40 to No. 200 0.420 to IJ.0-:-4 SILT AND CL..\ Y I Bdow '.'Jo. 200 I Bdow () :T 4 GRAIN SIZE CHART EAST COuNTY SOIL CONSlL T...\ TION AND ENGINEERING, INC. 10925 HARTLEY RO . ..\D. SlITE "I'" SANTEE. C...\LIFOR.'IL..\ no-:1 C.S.C.S. SOIL CLASSIFICATIO:'-i '0 r~:::::::===;;,"-----t-----:------:--J 0 IO l!l !O 40 !O ;c 7'0 JO lC 1 CO ''Ct.,;•:J 'Mli '' -PL..\STIC-ITY-CHA°RT SLOWIK PROJECT NO. 03-1106H6(A) PLATE NO. 3 APRIL 21, 2004 SLOWIK PROJECT NO 03-1106H6(A) PAGE L-1 LABORATORY TEST RESULTS RESULTS OF MAXIMUM DENSITY AND OPTIMUM MOISTURE The maximum dry densities and optimum moisture contents of the fill materials as determined by ASTM D1557-91, Procedure A which uses 25 blows of a 10 pound slide hammer falling from a height of 18 inches on each of 5 equal layers in a 4 inch diameter 1/30 cubic foot compaction cylinder and Procedure C which uses 56 blows of a 10 pound slide hammer falling from a height of 18 inches on each of 5 equal layers in a 6 inch diameter 1/13.3 cubic foot compaction cylinder are presented as follows: SOIL TYPE/ PROCEDURE 1/A DESCRIPTION TAN TO GRAY SILTY FINE SAND WITH A TRACE OF CLAY (SM) MAXIMUM DRY DENSITY LB/ CU. FT. 126.5 OPTIMUM MOISTURE CONTENT %DRYWT. LOCATION 9.8 B-1 @2.0' RESULTS OF PARTICLE SIZE ANALYSIS U.S. Standard Percent Passing Percent Passing Sieve Size B-1 @2.0' B-2@2.5' (ASTM D-422) Undocumented Fill Colluviurn 2" - l" -- 1/2" -- 3/8" 100 100 #4 97 99 #8 88 99 #16 67 97 #30 49 94 #40 43 85 #60 31 41 #100 24 26 #200 20 21 I ' uses SM SM 9 SLOWIK PROJECT NO.03-1106H6(A) PAGE L-2 LABORATORY TEST RESULTS RESULTS OF EXPANSION INDEX TEST An expansion test in conformance with ASTM D4829 was performed on a representative sample of on-site soils to determine volumetric change characteristics with change in moisture content. The recorded expansion of the sample is presented as follows: INITIAL MOISTURE CONTENT% 9.6 SATURATED MOISTURE CONTENT% 18.7 INITIAL DRY DENSITY LB.ICU. FT. 108.7 EXPANSION INDEX 0 LOCATION B-2@2.0' SLOWIK PROJECT NO.03-1106H6(A) REFERENCES 1. "1997 Edition, Uniform Building Code, Volume 2, Structural Engineering and Design Provisions". 2. "Maps of Known Active Fault Near-Source Zones in California and Adjacent Portions of Nevada", Page 0-36, used with the 1997 Edition of the Uniform Building Code, Published by International Conference of Building Officials. 3. "Geologic Maps of the Northwestern Part of San Diego County, California. Plate No. 1, Geologic Maps of the Oceanside, San Luis Rey and San Marcos 7.5' Quadrangles", by Siang S. Tan and Michael P. Kennedy, 1996. 10 EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC. 10925 HARTLEY ROAD, SUITE I SANTEE, CALIFORNIA 92071 (619) 258-7901 APPENDIX A RECOMMENDED EARTHWORK SPECIFICATIONS l. General Description The intent of these specifications is to obtain uniformity and adequate strength in filled ground so that the proposed structures may be safely supported. The procedures include the clearing and preparation of the land to be filled, processing the fill soils, the spreading, and compaction of the filled areas to conform with the lines and grades as shown on the approved plans. The owner shall retain a Civil Engineer qualified in soil mechanics (herein referred to as engineer) to inspect and test earthwork in accordance with these specifications. The engineer shall advise the owner and grading contractor immediately if any unsatisfactory conditions are observed to exist and shall have the authority to reject the compacted filled ground until such time that corrective measures are taken, necessary to comply with the specifications. It shall be the sole responsibility of the grading contractor to achieve the specified degree of compaction. 2. Preparing Areas to be Filled (a) All brush, vegetation and any biodegradable refuse shall be removed or otherwise disposed of so as to leave the areas to be filled free of vegetation and debris. Any uncompacted filled ground or loose compressible natural ground shall be removed unless the report recommends otherwise. Any buried tanks or other structures shall be removed and the depression backfilled to the satisfaction of the engineer. (b) The natural ground which is determined to be satisfactory for the support of the filled ground shall then be plowed or scarified to a depth of at least 12 inches (12"). ( c) After the natural ground has been prepared, it shall then be brought to the proper moisture content and compacted to not less than 90 percent of maximum dry density in accordance with ASTM D1557-91. ( d) Where fills are made on slopes greater than 20 percent, horizontal benches shall be cut into the firm natural ground. The initial bench at the toe of the fill shall be at least 15 feet in width on firm undisturbed natural ground. The width of all succeeding benches shall be at least 6 feet. APPENDIX A 2 3. Fill Materials All material shall be approved by the engineer and shall consist of materials free from vegetable matter, and other lumps greater than 6 inches in diameter. If, during grading operations, soils are found which were not encountered and tested in the preliminary investigation, tests on these soils shall be performed to determine their physical characteristics. Any special treatment recommended in the preliminary or subsequent soils reports not covered herein shall become an addendum to these specifications. 4. Placing and Compacting Fill Materials (a) When the moisture content of the fill material is below that specified, water shall be added until the moisture content is near optimum to assure uniform mixing and effective compaction. (b) When the moisture content of the fill materials is above that specified, the fill material shall be aerated by blading and scarifying or other satisfactory methods until the moisture content is near optimum as specified. ( c) After processing, the suitable fill materials shall be placed in layers which, when compacted, shall ~ot exceed six inches (6"). Each layer shall be spread evenly and shall be thoroughly mixed during the spreading insure uniformity of materials and moisture in each layer. · (d) After each layer has been placed, mixed and spread evenly, it shall be thoroughly compacted to not less than the density set forth in paragraph 2 (c) above. Compaction shall be accomplished with approval types of compaction equipment. Rolling shall be accomplished while the fill material is at the specified moisture content. In place density tests shall be performed in accordance with ASTM D1556-90. ( e) The surfaces of the fill slopes shall be compacted by means of sheepsfoot rollers or other suitable equipment. Compacting operations shall be continued until the slopes are stable and until there is no appreciable amount of loose soil on the slopes. 5. Inspection Sufficient inspection by our firm or the Soil's Engineer of record and/or his/her representative shall be maintained during the filling and compacting operations so that he/she can verify that the fill was constructed in accordance with the accepted specifications. 6. Seasonal Limits No fill material shall be placed, spread, or rolled if weather conditions increase the moisture content above permissible limits. When the work is interrupted by rain, fill operations shall not be resumed until the moisture content and density of fill are as previously specified. All recommendations presented in the attached report are a part of these specifications. 2