HomeMy WebLinkAbout1969 PALOMAR OAKS WAY; ; AS120050; Permit11/12/2020 . AS120050 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS120050
1969. PALOMAR OAKS
Job Address.: . . Status: APPROVED
.wY
Permit Type: SPRINK . . Applied 5/17/2012
Parcel No: 2130922000
.
. Approved: 5/21/2012
Lot #: 0
Reference No.: . Issued: 5/21/2012
PC #: • . Inspector:
Project Title: AIR PRODUCTS GLASS SHOP T.I.
Applicant:
SCHMIDT FIRE PROTECTION CO INC
4760 MURPHY CANYON RD
SAN DIEGO, CA 92123
858-279-6122
Owner:
AIR PRODUCTS&CHEMICALS INC
C/O J C SCHUMACHER CO
1969 PALOMAR OAKS WAY
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($).
262 .0 262 .. 0
1/1
AS 12- ooso
9
AIR PRODUCTS
GLASS SHOP
FIRE PROTECTION
WET SPRINKLER SYSTEMS
SUBMITTAL PACKAGE
1IKe phii ha' biI 1vicWcd for ipp.iflflt compliance
wiibi currn appi hb codi and Mandard in iorCi
in ih u: ndicIioIl Thc ovfl,r or contracu .r may un%lli'
un' Ii' h'i% Hi uP1I1 ii JO abIiIicmuion for a hiuiIdifl
r'iiui oh hr irs' uundrrswulLtun ubuui ihis rr'
III cc ir c ihr owilel or conhiiucior or
nab ruigiulrrr or aichiiccl lor obc rcspou1sil1b0Y
liii liii I comnpb I ancc with said codrs and suauidard.
induibung the huiIdin code or for auu rcspoiusihibtY for
ikticieulcics. errors. 0Ifli5SII'fl 01 iicuIiriiCC in these
pbaii hether or nol noied in ihis review.
Cl sIMINl) API'k()VAI.
\ .\I '•'
n
- - - Fire Protection by Computer Design
Schmidt Fire Protection
4760 Murphy Canyon Rd.
San Diego, Ca. 92123
858-279-6122
Job Name : AIR PRODUCTS GLASS SHOP
Building :
Location : 1969 PALOMAR OAKS WAY CARLSBAD.CA. 92011
System : 100
Contract Ml 2-7559
Data File : 100.WXF
-0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Schmidt Fire Protection Page
AIR PRODUCTS GLASS SHOP Date
Hydraulic Design Information Sheet
Name - AIR PRODUCTS - GLASS SHOP Date - 4/24/12
Location - 1969 PALOMAR OAKS WAY CARLSBAD.CA. 92011
Building - System No. - 100
Contractor - SCHMIDT FIRE PROTECTION Contract No. - M12-7559
Calculated By - COSTAS PAFAILAKIS Drawing No. - FP-4
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height - VARIES
Occupancy - GLASS SHOP
S (X) NFPA 13 ( ) Lt. Haz. Ord.Haz.Gp. ( ) 1 (X) 2 C ) 3 C ) Ex.Haz.
Y ( ) NFPA 231 ( ) NFPA 231C ( ) Figure Curve
S Other
T Specific Ruling Made By Date
E
M Area of Sprinkler Operation - 1172 System Type Sprinkler/Nozzle
Density - .2 (X) Wet Make RELIABLE
D Area Per Sprinkler - VARIES ( ) Dry Model F1FR 56
E Elevation at Highest Outlet - 10-0" ( ) Deluge Size 1/2"
S Hose Allowance - Inside - 0 C ) Preaction K-Factor 5.6
I Rack Sprinkler Allowance - N/A C ) Other Temp.Rat.VARIES
G Hose Allowance - Outside - 250
N
Note
Calculation Flow Required - 422 Press Required - 57 BOR
Summary C-Factor Used: 120 Overhead 150 Underground
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - 4/16/12 Cap. -
T Time of Test - 8:25 AM Rated Cap.- Elev. -
E Static Press - 81.9 @ Press -
R Residual Press - 67.5 Elev. - Well
Flow - 1300 Proof Flow
S Elevation - 3
U
P Location - HYDRANTS ALONG PALOMAR OAKS WAY
P
L Source of Information - SCHMIDT FIRE PROTECTION CONDUCTED TEST WITH CARLSBAD
Y WATER DEPARTMET AS WITNESS
C Commodity Class Location
O Storage Ht. Area Aisle W.
M Storage Method: Solid Piled % Palletized Rack
M
Single Row ( ) Conven. Pallet ( ) Auto. Storage ( ) Encap.
S R C ) Double Row C ) Slave Pallet C ) Solid Shelf ( ) Non
T A ( ) Mult. Row ( ) Open Shelf
O C
R K Flue Spacing Clearance:Storage to Ceiling
A Longitudinal Transverse
G
E Horizontal Barriers Provided:
p
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
S
Water SuppIyCurve (C)
Schmidt Fire Protection Page 2
AIR PRODUCTS GLASS SHOP Date
City Water Supply: . Demand:
Cl - Static Pressure : 81.9 Dl - Elevation : 3.032
C2 - Residual Pressure: 67.5 D2 - System Flow : 421.761
C2 - Residual Flow : 1300 . D2 - System Pressure : .53.262
Hose (Adj City)
Hose (Demand) : 250
D3 - System Demand : 671.761
Safety Margin : 24.392
150
140
130
p120
10
j
1
oo
90 ci
S 80
C2
U 70
R 60 -
E 50
133 40
30
20
10
.
206-400 600 800 1000 1200 1400 1600 1800
FLOW (NA 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fillings Used Summary
Schmidt Fire Protection Page 3
AIR PRODUCTS GLASS SHOP Date
Fitting Legend
Abbrev. Name '/2 % 1 VA 1'/2 2 2.4 3 3'A 4 5 6 8 10 12 14 16 18 20 24
A Alarm Ret El & E3 7.7 21.5 17 27 29
E NFPA1390' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
T NFPA139O' Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units
Length Units
Flow Units
Pressure Units
Inches
Feet
US Gallons per Minute
Pounds per Square Inch
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
0
Pressure / Flow Summary - STANDARD
Schmidt Fire Protection Page 4
AIR PRODUCTS GLASS SHOP Date
Node Elevation K-Fact Pt . Pn Flow Density Area Press
o.
Actual Actual Req.
01 10.0 5.6 25.68 na 28.38 0.2 40 7.0
03 10.0 5.6 23.36 na 27.07 0.2 87 7.0
05 10.0 5.6 23.51 na 27.15 0.2 87 7.0
07 10.0 5.6 26.3 na 28.72 0.2 46 7.0
02 19.0 26.14 na
04 19.0 26.17 na
06 19.0 26.35 na
08 19.0 26.86 na
09 19.0 30.51 na
11 10.0 5.6 20.52 na 25.37 0.2 120 7.0
13 10.0 5.6 20.44 na 25.32 0.2 120 7.0
15 10.0 5.6 20.25 na 25.2 0.2 126 7.0
17 10.0 5.6 14.05 na 20.99 0.2 58 7.0
18 10.0 5.6 14.06 na 21.0 0.2 62 7.0
19 10.0 5.6 15.15 na 21.8 0.2 107 7.0
20 10.0 16.35 na
21 10.0 5.6 17.17 na 23.2 0.2 85 7.0
22 10.0 18.11 na
23 10.0 19.72 na
12 19.0 21.36 na
14 19.0 21.4 na
16 19.0 21.56 na
24 19.0 21.98 na
25 19.0 28.09 na
27 10.0 5.6 21.72 na 26.1 0.2 120 7.0
29 10.0 5.6 21.63 na 26.04 0.2 120 7.0
31 10.0 5.6 21.42 na 25.92 0.2 100 7.0
33 10.0 5.6 14.74 na 21.5 0.2 46 7.0
34 10.0 5.6 16.53 na 22.77 0.2 78 7.0
17.45 na
46 10.0
10.0 5.6 20.34 na 25.26 0.2 104 7.0
10.0 23.58 na
28 19.0 22.78 na
30 19.0 22.83 na
32 19.0 22.99 na
38 19.0 23.26 na
39 19.0 28.91 na
10 18.0 33.32 na
26 18.0 33.33 na
40 18.0 33.35 na
41 18.0 33.39 na
42 18.0 33.69 na
43 18.0 34.11 na
TOR 18.0 34.12 na
BOR 0.5 41.79 na
UGI -3.0 43.41 na 250.0
BKFL -3.0 44.25 na
UG3 -3.0 55.6 na
SRC 3.0 53.26 na
The maximum velocity is 13.71 and it occurs in the pipe between nodes 22 and 23
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Schmidt Fire Protection Page 5
AIR PRODUCTS GLASS SHOP Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
01 28.38 1.049 1E 2.0 10.540 25.680 K Factor = 5.60
to 120.0 IT 5.0 7.000 -3.898
02 28.38 0.2486 0.0 17.540 4.360 Vel = 10.54
0.0
28.38 26.142 K Factor= 5.55
03 27.07 1.049 3E 6.0 13.420 23.363 K Factor = 5.60
to 120.0 2T 10.0 16.000 -3.898
04 27.07 0.2278 0.0 29.420 6.701 Vel = 10.05
0.0
27.07 26.166 K Factor= 5.29
05 27.15 1.049 3E 6.0 13.420 23.506 K Factor = 5.60
to 120.0 2T 10.0 16.000 -3.898
06 27.15 0.2291 0.0 29.420 6.739 Vel = 10.08
0.0
27.15 26.347 K Factor= 5.29
07 28.72 1.049 1E 2.0 10.540 26.299 K Factor = 5.60
to 120.0 IT 5.0 7.000 -3.898
08 28.72 0.2542 0.0 17.540 4.458 Vel = 10.66
- 0.0
28.72 . 26.859 K Factor= 5.54
02 28.38 2.203 0.0 3.580 26.142
to 120.0 0.0 0.0 0.0
04 28.38 0.0067 0.0 3.580 0.024 Vel = 2.39
04 27.07 2.203 0.0 7.830 26.166
to 120.0 0.0 0.0 0.0
06 55.45 0.0231 0.0 7.830 0.181 Vel = 4.67
06 27.15 2.203 0.0 10.580 26.347
to 120.0 0.0 0.0 0.0
08 82.6 0.0484 0.0 10.580 0.512 Vet = 6.95
08 28.71 2.203 0.0 43.500 26.859
to 120.0 0.0 0.0 0.0
09 111.31 0.0840 0.0 43.500 3.654 Vel = 9.37
09 0.0 2.203 2T 27.277 1.000 30.513
to 120.0 0.0 27.277 0.433
10 111.31 0.0840 0.0 28.277 2.376 Vel = 9.37
0.0
111.31 33.322 KFactor= 19.28
11 25.37 1.049 1E 2.0 11.460 20.519 K Factor = 5.60
to 120.0 2T 10.0 12.000 -3.898
12 25.37 0.2020 0.0 23.460 4.739 Vel = 9.42
0.0
25.37 21.360 K Factor= 5.49
13 25.32 1.049 1E 2.0 12.170 20.437 K Factor = 5.60
to 120.0 2T 10.0 12.000 -3.898
14 25.32 0.2012 0.0 24.170 4.864 Vel = 9.40
0.0
25.32 21.403 K Factor= 5.47
15 25.20 1.049 1E 2.0 14.080 20.250 K Factor =5.60
to 120.0 2T 10.0 12.000 -3.898
16 25.2 0.1996 0.0 26.080 5.205 Vel = 9.35
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Schmidt Fire Protection Page 6
AIR PRODUCTS GLASS SHOP Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. lice, or Ftngs Pe Pv ******* Notes
oint Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
25.20 21.557 K Factor= 5.43
17 20.99 1.049 1E 2.0 9.210 14.048 K Factor = 5.60
to 120.0 iT 5.0 7.000 0.0
20 20.99 0.1423 0.0 16.210 2.306 Vel = 7.79
0.0
20.99 16.354 K Factor = 5.19
18 21.00 1.049 0.0 7.670 14.056 K Factor = 5.60
to 120.0 0.0 0.0 0.0
19 21.0 0.1424 0.0 7.670 1.092 Vet = 7.80
19 21.79 1.38 1E 3.0 5.625 15.148 K Factor = 5.60
to 120.0 0.0 3.000 0.0
20 42.79 0.1398 0.0 8.625 1.206 Vel = 9.18
20 20.99 1.61 1E 4.0 8.710 16.354
to . 120.0 0.0 4.000 0.0
22 63.78 0.1381 0.0 12.710 1.755 Vel = 10.05
0.0
63.78 18.109 KFactor= 14.99
21 23.20 1.049 IT 5.0 0.500 17.167 K Factor = 5.60
to 120.0 0.0 5.000 0.0
22 23.2 0.1713 0.0 5.500 0.942 Vel = 8.61
2 63.78 1.61 IE 4.0 2.580 18.109
to 120.0 0.0 4.000 0.0
23 86.98 0.2451 0.0 6.580 1.613 Vel = 13.71
23 0.0 1.61 IE 4.0 13.125 19.722
to 120.0 iT 8.0 12.000 -3.898
24 86.98 0.2451 0.0 25.125 6.158 Vet = 13.71
0.0
86.98 21.982 K Factor= 18.55
12 25.37 2.203 0.0 7.830 21.360
to 120.0 0.0 0.0 0.0
14 25.37 0.0055 0.0 7.830 0.043, Vet = 2.14
14 25.31 2.203 0.0 7.830 21.403
to 120.0 0.0 0.0 0.0
16 50.68 0.0197 0.0 7.830 0.154 Vel = 4.27
16 25.20 2.203 0.0 10.290 21.557
to 120.0 0.0 0.0 0.0
24 75.88 0.0413 0.0 10.290 0.425 Vel = 6.39
24 86.98 2.203 0.0 35.960 21.982
to 120.0 0.0 0.0 0.0
25 162.86 0.1699 0.0 35.960 6.108 Vel = 13.71
25 0.0 2.203 2T 27.277 1.000 28.090
to 120.0 0.0 27.277 0.433
26 162.86 0.1699 0.0 28.277 4.803 Vel = 13.71
0.0
33.326 K Factor = 28.21 S 162.86
7 . 26.10 1.049 1E 2.0 11.290 21.721 K Factor =5.60
to 120.0 2T 10.0 12.000 -3.898
28 26.1 0.2129 0.0 23.290 4.959 Vel = 9.69
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Schmidt Fire Protection Page 7
AIR PRODUCTS GLASS SHOP Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "CI' or Ftng's Pe Pv ******* Notes ******
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
26.10 22.782 KFactor= 5.47
29 26.04 1.049 1 2.0 12.040 21.627 K Factor= 5.60
to 120.0 2T 10.0 12.000 -3.898
30 26.04 0.2121 0.0 24.040 5.098 Vel = 9.67
0.0
26.04 22.827 K Factor= 5.45
31 25.92 1.049 1 2.0 14.000 21.421 K Factor= 5.60
to 120.0 2T 10.0 12.000 -3.898
32 25.92 0.2102 0.0 26.000 5.466 Vel = 9.62
0.0
25.92 22.989 K Factor= 5.41
33 21.50 1.049 3E 6.0 12.210 14.737 K Factor = 5.60
to 120.0 0.0 6.000 0.0
35 21.5 0.1487 0.0 18.210 2.708 Vel = 7.98
0.0
21.50 17.445 K Factor= 5.15
34 22.77 1.049 IT 5.0 0.540 16.529 K Factor =5.60
to 120.0 0.0 5.000 0.0
35 22.77 0.1653 0.0 5.540 0.916 Vet = 8.45
35
to
21.49 1.38
120.0
2E 6.0
0.0
13.460
6.000
17.445
0.0
36 44.26 0.1488 0.0 19.460 2.896 Vel = 9.49
36 25.26 1.61 3E 12.0 8.000 20.341 K Factor = 5.60
to 120.0 0.0 12.000 0.0
37 69.52 0.1619 0.0 20.000 3.239 Vet = 10.96
37" 0.0 1.61 1 4.0 10.125 23.580
to 120.0 IT 8.0 12.000 -3.898
38 69.52 0.1619 0.0 22.125 3.583 VeI= 10.96
0.0
69.52 23.265 K Factor= 14.41
28 26.10 2.203 . 0.0 7.830 22.782
to 120.0 0.0 0.0 0.0
30 26.1 0.0057 0.0 7.830 0.045 Vet = 2.20
30 26.04 2.203 0.0 7.830 22.827
to 120.0 0.0 0.0 0.0
32 52.14 0.0207 0.0 7.830 0.162 Vel = 4.39
32 25.92 2.203 0.0 6.330 22.989
to 120.0 0.0 0.0 0.0
38 78.06 0.0436 0.0 6.330 0.276 Vel = 6.57
38 69.52 2.203 0.0 39.920 23.265
to 120.0 0.0 0.0 0.0
39 147.58 0.1415 0.0 39.920 5.650 Vel = 12.42
39 0.0 2.203 2T 27.277 1.000 28.915
to 120.0 0.0 27.277 0.433
40 147.58 0.1415 0.0 28.277 4.002 VeI= 12.42
0.0
147.58 33.350 K Factor = 25.56
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
Schmidt Fire Protection Page 8
AIR PRODUCTS GLASS SHOP Date
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
oint Qt Pf/Ft Eqv. Ln. Total Pf Pn
10 111.31 6.357 0.0 8.330 33.322
to 120.0 0.0 0.0 0.0
26 111.31 0.0005 0.0- 8.330 0.004 Vel = 1.13
26 162.87 6.357 0.0 9.750 33.326
to 120.0 0.0 0.0 . 0.0
40 274.18 0.0025 0.0 9.750 0.024 Vel = 2.77
40 147.58 6.357 0.0 7.000 33.350
to 120.0 0.0 0.0 0.0
41 421.76 0.0057 0.0 7.000 0.040 Vel = 4.26
41 0.0 6.357 0.0 52.830 33.390
to 120.0 0.0 0.0 0.0
42 421.76 0.0057 0.0 52.830 0.299 Vet = 4.26
42 0.0 6.357 0.0 73.830 33.689
to 120.0 0.0 0.0 0.0
43 421.76 0.0057 0.0 73.830 0.419 Vel = 4.26
43 0.0 8.249 0.0 10.500 34.108
to 120.0 0.0 0.0 0.0
TOR 421.76 0.0015 0.0 10.500 0.016 Vet = 2.53
TOR 0.0 8.249 IG 4.698 17.500 34.124
to 120.0 1A 34.061 38.759 7.579
BOR 421.76 0.0016 0.0 56.259 0.090 Vet = 2.53
OR
ro
0.0 8.27 2E 56.936 27.000 41.793
140.0 0.0 56.936 1.516
UG1 421.76 0.0012 0.0 83.936 0.099 Vet = 2.52.
UG1 250.00 7.98 3E 81.548 205.000 43.408 Qa = 250
to 150.0 0.0 81.548 0.0
BKFL 671.76 0.0029 0.0 286.548 0.840 Vet = 4.31
BKFL 0.0 8.27 4E 113.872 12.000 44.248
to 140.0 0.0 113.872 11.000 * Fixed loss = 11
UG3 671.76 0.0028 0.0 125.872 0.352 Vel = 4.01
UG3 0.0 7.68 IT 43.857 30.000 55.600
to 150.0 0.0 43.857 -2.599
SRC 671.76 0.0035 0.0 73.857 0.261 Vet = 4.65
0.0
671.76 53.262 K Factor = 92.05
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Vertical Sidewall Conventional
Horizontal Sidewall Recessed
Pendent/Fl/F2
iiecessea Recessed
Horizontal Sidewall Pendent/FP
Application
Quick response sprinklers are used in fixed fire protec-
tion systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflec-
tor style and sprinkler type are in accordance with the lat-
est published standards of the National Fire Protection As-
sociation or the approving Authority Having Jurisdiction.
Quick response sprinklers are intended for installation
specified in NFPA 13. Quick response sprinklers and stale
dard response sprinklers should not be intermixed.
Bulletin 014 Rev. F
R I la bl Model Fl FR56 Series
Quick Response
Standard Spray
w
CD
Q
Model Fl FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model Fl FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types
Standard Pendent
Listing & Approvals
Underwriters Laboratories Inc. and Certified for
Canada (cULus).
Factory Mutual Approvals (FM)
Loss Prevention Council (LPCB, UK)
VdS Schadenverhutung GmbH
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56 Series Sprinklers are quick re-
sponse sprinklers which combine the durability of a stan-
dard sprinkler with the attractive low profile of a decorative
sprinkler.
The Models F1FR56 Series Recessed automatic sprin-
klers utilize a 3.0 mm frangible glass bulb. These sprin-
klers have demonstrated response times in laboratory tests
which are five to ten times faster than standard response
sprinklers. This quick response enables the Model Fl FR56
Series sprinklers to apply water to a fire much faster than
standard sprinklers of the same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely manu-
factured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Upright Pendent
The Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
(I)
ADJUSTMENT -
2 5/8 0.14. (66.7mm)
HOLE IN CEILING
2 5/16 014. (58.7mm)
CUP
L--=-4
r
[L
1X 1/2 REDUCER
FACE OF F1TI7NG 70 FACE OF CEILING
OIMENSION(,)
Ea i
(I)
1
(I) REFER 70 FP ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONS.
Model F1FR56/FP
Model Fl FR56 Quick Response Upright, Pendent & Conventional Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
Nominal K Factor Sprinkler
Height
I
Approval
I Organization I
I Sprinkler Identification Number
I (SIN)
US Metric Upright Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
1/2"(15mm) ½" NPT(R½) 5.6 1 80 1 2.25" (57mm) 1 1,2,3,4 RA1425111 RA1414('X2)
Conventional-Install in Upright or Pendent Position
15mm11 1/2" NPT(R½) 5.6 1 80 1 57mm 1 3,4 RA1475
" cULus listed corrosion resistant (Polyester coated) sprinkler.
(2) Polyester coated FM approved sprinkler.
Upright Pendent Conventional
Model Fl FR56 Quick Response Recessed Pendent Sprinkler
nstallation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor Sprinkler
Height
Sprinkler Identification Number
(SIN) us Metric
½" (15mm) ½" NPT(R½) 5.6 80 2.25" (57mm) RA1414
(') Refer to escutcheon data table for approvals and dimensions.
2 I/4 HOLE DIA I
(57.2,nn,j
I 15116-014 (49.2mm)
TURN COLLAR
r
I
I'x 112' REDUCER
UNIX LiGHT AGAINST SPRINKLER WRENCH BOSS
ji-LL777771 FACE OF f
l CEXI'? AOJUSTMENT' IVN
I/a-I
(2mmJ
2 27/32 OR I 0147601
[72.2-1
(I) REFER TO FL & 72 ESCUTCHEON DATA TABLE FOR APPROVALS AND DIMENSIONE
Model F1FRS6/F1 or F2
2.
After installation, inspect all sprinklers to ensure that
there is a gap between the cover plate and ceiling and
that the four cup slots are open and free from any air flow
impediment to the space above.
Concealed cover plate/cup assemblies are listed only
for use with specific sprinklers. The use of any other con-
cealed cover plate/cup assembly with the Model Fl FR56
Pendent Sprinkler or the use of the Model CCP Concealed
cover plate assembly on any sprinkler with which it is not
specifically listed my prevent good fire protection and will
void all guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and
installation. REMOVE THIS PROTECTION AT THE TIME
THE SPRINKLER SYSTEM IS PLACED IN SERVICE FOR
FIRE PROTECTION. Removal of the protectors before this
time may leave the bulb vulnerable to damage. RASCO
wrenches are designed to install sprinklers when covers
are in place. REMOVE PROTECTORS BY UNDOING THE
CLASP BY HAND. DO NOT USE TOOLS TO REMOVE
THE PROTECTORS.
Temperature Ratings
Classification
Sprinkler
Temperature Max. Ambient
Temp. Bulb Color OC OF
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
High (" 141 1 286 1 225°F (107°C) Blue
' available for recessed sprinklers.
Escutcheon Data (1)
Escutcheon "A" Face of Fitting to
Model Approvals Adjustment Dimension Ceilingor Wall
Dimension
Fl 1.3,4 Max Recess 11W (38.lm) 311e - 15/1a"
Mn Recess 3/4" (19.ln'r,) (5nn - 24nrn)
F2 1,2 3,4 Max Recess 1 ½" (38.lnin) 3/"
-
Mn Recess I 1" (25rrn1) (5rrrn - 17rmi)
FP Push-cry 1,4 Max Recessed 7/,a" (llrrni) 1W' (38.lm)
raci.ott Mk, Recessed i5/ (24mi) 1" (25.4mm)
11) SIN: RA1435 - cULus and FM permits use with Fl or F2 escutcheons for light
hazard only.
Maintenance
The Models F1 FR56 and F1 FR56 Recessed Sprinklers
should be inspected quarterly and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler which has
been painted (other than factory applied) or damaged
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or oper-
ated sprinklers. Prior to installation, sprinklers should be
maintained in the original cartons and packaging to mini-
mize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
Finishes (1)
Standard Finishes
Sprinkler Escutcheon Cover plate
Bronze Brass
Chrome Plated Chrome Chrome
White Polyester Plated White
Coated White Painted
Special Application Finishes
Sprinkler Escutcheon Cover plate
Bright Brass ' Bright Brass Bright Brass
Black Plated Black Plated Satin
Black Paint (2) Black Paint Off White
Off White (2) Off White Black Paint
Satin Chrome I Satin Chrome Black Plated
(" Other finishes and colors are available on special order.
Consult the factory for details.
t2l cULus Listed only.
200°F (93°C) maximum.
cULus listed "corrosion resistance" applies to SIN Numbers
RA1425 (Upright) and RA1414 (Pendent) in standard black or white.
FM Approvals finish as 'Polyester coated" applies to SIN Number
RA1414 (Pendent) in standard black or white.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Orifice Size
Deflector Type
Temperature Rating
Sprinkler Finish
Escutcheon Type
Escutcheon Finish (where applicable)
Cover plate Model
Cover plate Thread size
Cover plate Temperature
Cover plate Adjustment
Cover plate Finish
Note: When Model Fl FR56 Recessed sprinklers are ordered, the sprin-
klers and escutcheons are packaged separately.
61
?
ATM
\With AUF \
)Protectioi,J
I I yI'I
0 <~> @
Listed Approved Listed
0
16100 S. Lathrop Harvey, IL 60426 Customer Service:
11350 Norcom Rd. • Philadelphia, PA 19154 (800) 882-5543
2525 N. 27th Ave. • Phoenix, AZ 85009 Fax 708-339-1806
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
Vibration Test
111CC/F/ow Control Qv, allied
TUBE & CONDUIT
Schedule-1O®/Schedule-40®
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-10/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although theses
products do not require separate approvals, Schedule- 10/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (V/4"- 8") pipe and Sch-40 (1"- 21411) pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Schedule-i 0/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A- 123.
' !0 Specifications
NPS Nominal I.D. WI. WI. (H20 Filled) Pc Wt/1.ift (21') WI/Uft (24') WI/Lift (25')
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.049 1.680 2.05 70 2,470 2,822 2,940
25 26.6 2.5 3.05 70 1,120 1,280 1,334
11/4" 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
1½" 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2.067 3.650 5.13 30 2,300 2,628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
21/2" 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 1,048 1,197 1,247
3I0I.1yEttTh.r.
NPS Nominal I.D. WI. Wt. (H20 Filled) Pcs/ WI/Lift (21') WI/lift (24') WI/Lift (25')
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.097 1.400 1.81 91 2,675 3,053 3,185
25 27.9 2.1 2.70 91 1,213 1,385 1,445
1%" 1.442 1.810 2.52 61 2,319 2,664 2,760
32 36.6 2.7 3.75 61 1,052 1,208 1,252
1½" 1.682 2.080 3.04 61 2,664 3,045 3,172
40 42.7 3.1 4.52 61 1,208 1,381 1,439
2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
2½" 2.635 3.530 5.89 30 2,224 2,542 2,648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3.260 4.330 7.94 19 1,728 1,975 2,057
80 82.8 6.4 11.82 19 784 896 933
4.260 5.610 11.78 19 2,238 2,558 2,665
90 108.2 8.3 17.53 19 1,015 1,160 1,209
5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6.357 9.290 23.03 10 1,951 2,230 2,322
150 161.5 13.8 34.27 10 885 1,012 1,053
8" 8.249 16.490 40.15 7 2,424 2,770 2,885
200 209.5 24.5 59.75 7 1,100 1,256 1,309
Our advanced formula mill coating of-
fers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
American U'1FIi [
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
Schedule-i 0/Schedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
C
S5-3
NOMINAL
SIZE
(INCH)
ITEM
CODE
4
MAX.
WORKING
P.S.I.
DIMENSIONS WEIGHT
-
A
-
B
EACH
PIECE
1 CB90033 300 1.50 1.50 0.95
11/4 CB90044 300 175 175 1.34
11/2 CB90055 300 1.94 1.94 1 1.80
2 CB90066
1
300 2.25 2.25 2.90
21/2 CB90077 300 2.70 2.70 1 4.75
:0ll
NOMINAL
SIZE
(INCH)
ITEM
CODE
4
MAX.
WORKING
P.S.I.
DIMENSION WEIGHT
EACH
PIECE A
1X1/2 CRC031 300 1.70 0.62
1X3/4 CRC032 300 1.70 0.80
NOMINAL
SIZE
(INCH)
ITEM
CODE
4
MAX.
WORKING
P.S.I.
DIMENSIONS WEIGHT
EACH
PIECE
-
A
-
B
1 CT333 300 1.50 1.50 1.21
11/4 CT444 300 1.75 175 1.87
11/2 CT555 300 1.94 1.94 2.51
2 CT666 300 2.25 2.25 3.96
21/2 CT777 300 2.70 2.70 6.45
4
NOMINAL
SIZE
(INCH)
ITEM
CODE
4
MAX.
WORKING
P.S.I.
DIMENSIONS WEIGHT
EACH
PIECE A B
1 CB45033 300 1.12 1.12 0.84
11/4 CB45044 300 1.29 1.29 1.40
11/2 1 CB450551 300 1.43 1.43 1.80
2 1 CB450661 300 1.68 1.68 2.79
S
FITTINGS
~50 A I ,
LISTED LISTED APPROVED
For fire protection services request submittal GRS 1.3
CAST IRON THREADED FITTINGS ARE UL, ULC LISTED AND FACTORY MUTUAL
APPROVED FOR 300 PSI SERVICE. GRAY IRON PER ASTM A126 CLASS B. DIMEN-
SIONS CONFORM TO ANSI 1316.4 CLASS 125 EXCEPT PLUGS CONFORM TOASME
1316.14. THREADS ARE NPT PERANSI/ASME 13I.20.1.
Aj
C
A -
NOMINAL
SIZE
(INCH)
ITEM
CODE
4
MAX.
WORKING
P.S.I.
DIMENSIONS WEIGHT
EACH
PIECE
-
A
-
B
1X1/2 CB90031 300 1.26 1.36 0.64
1X3/4 CB90032 300 1.37 1.45 0.87
1 1/4X1/2 CB90041 300 1.34 1.53 0.96
1 1/4X3/4 CB90042 300 1.45 1.62 1.13
1 1/4X1 CB90043 300 1.58 1.67 1.16
1 1/2x1 1/2 C590051 300 1.41 1.66 1.17
1 1/2x3/4 CB90052 300 1.52 1.75 1.28
1 1/2X1 CB90053 300 1.65 1.80 1.51
1 1/2X1 1/4 CB90054 300 1.82 1.88 1.62
2X1/2 CB90061 300 1.49 1.88 2.00
2X3/4 CB90062 300 1.60 1.97 1 2.05
2X1 CB90063 300 1.73 2.02 2.10
2X1 1/4 CB90064 300 .90
!2.002
2.10 2.30
2X1 1/2 CB90065 300 2.16 2.60
Page 38
NOMINAL
SIZE
(INCH)
ITEM
CODE
4
MAX.
WORKING
P.S.I.
DIMENSION WEIGHT
EACH
PIECE A
1/2 CPL001 300 0.94 0.10
3/4 CPLOO2 300 1.07 0.17
1 CPL003 300 1.25 0.28
11/4 CPLOO4 300 1.36 0.44
11/2 CPL005 300 1.45
j
0.62
2 CPL006 300 1.56 0.91
(9 (~~ <~>
LISTED LISTED APPROVED
protection services request submittal GRS 1.3
4SIONS WBGI4I
EACH
PIECE B
I 1.50 1.54
i 1.75 2.40
I 1.94 3.10
2.25 4.00
1 1.67 2.05
1.80 2.40
1 2.02 1 2.75
KiW
NOMINAL
SIZE
(INCH)
ITEM
CODE
#
MAX.
WORKING
P.S.I.
DIM B1SIONS WEIGHT
EACH
PIECE A I B C
1X1X1I2 t 300 1.26 1.26 1.36 0.95
1X1X314 300 1.37 1.37 1.45 1.10
1X1/2X1 C 315 300 1.50 1.36 1.50 1.08
1X3/4X1 C 323 300 1.50 1.45 1.50 1.18
1X1X1 1/4 C1334 300 1.67 1.67 1.58 1.52
1X1XI 1/2 CT335 300 1.80 1.80 1.65 1.73
1 1/4X1 X1/2 CT431 300 1.34 1.26 1.53 1.17 14
1 114X1 X314 CT432 300 1.45 1.37 1.62 1.38
1 1/4X1X1 CT433 300 1.58 1.50 1.57 1.47
1 1/4X1 Xl 1/4 CT434 300 1.75 1.67 1.75 1.80
1 1I4X1X1 1/2 G 43 300 1.88 1.80 1.82 2.05
1 1/4X1 1/4X1/2 CT441 300 1.34 1.34 1.53 1.37
1 1/4X1 1/4X314 CT442 300 1.45 1.45 1.62 1.54
1 1/4X1 114X1 CT443 300 1.58 1.58 1.67 1.65
1 1/4X1 1/4X1 1/2 CT445 300 1.88 1.88 1.82 2.21
1 1/4X1 114X2 CT446 300 2.10 2.10 1.90 2.55
1 1/2X1XI/2 CT531 300 1.41 1 1.34 1.66 1.41
1 1/2X1 X3/4 CT532 300 1.52 1.37 1.75 1.65
1 1/2X1X1 CT533 300 1.65 1.50 1.80 TO
1 1/2X1X1 1/4 CT534 300 1.82 1.67 1.88 2.00
1 1I2X1X1 1/2 CT535 300 1.94 1.80 1.94 73u--
1 1/2X1 1/4X1/2 CT541 300 1.41 1.34 1.66 --f.-59--
1 1/2X1 1/4X314 CT542 300 1.52 1.45 1.75 1.72
1 1/2X1 114X1 CT543 300 1.65 1.58 1.80 1.85
1 1/2x1 114x1 1/4 C1544 300 1.82 1.75 1.88 2.22
1 112x1 1/4x1 1/2 CT545 300 1.94 1.88 1.94 2.45
1 1/2X1 1/4X2 C1546 300 2.16 2.10 2.02 2.80
1 1/2X1 1/2X1/2 CT551 300 1.41 1.41 1.66 1.76
1 1/2X1 1/2X3/4 CT552 300 1.52 1.52 1.75 1.87
1 1/2X1 1/2X1 CT 53 300 1.65 1.65 1.80 1 1.94
1 1/2X1 1/2X1 1/4 CT554 300 1.82 1.82 1.88 1 2.29
1 1/2X1 1/2X2 CT556 300 2.16 2.16 2.02 3.28
2X1X2 CT636 300 2.25 2.02 2.25 3.40
2X1 1/4X2 CT646 300 2.25 2.10 2.25 2.80
2X1 1/2X1/2 CT651 300 1.49 1.41 1.88 2.09
2X1 1/2X3/4 CT652 300 1.60 1.52 1.97 2.40
2X1 1/2X1 CT 53 300 1.73 1.65 2.02 2.54
2X1 1/2X1 1/4 C1654 1 300 1.90 1.82 2.10 2.85
2X1 1/2X1 1/2 CT 55 300 1.49 1.41 1.88 2.24
2X1 1/2X2 CT656 300 2.25 2.16 1 2.25 3.75
2X2X1/2 CT661 300 1.49 1.49 1 1.88 2.60
2X2X3/4 CT662 300 1.60 1.60 1.97 2.71
2X2X1 CT663 300 1.73 1.73 1 2.02 2.97
2X2X1 1/4 CT664 300 1.90 1.90 2.10 3.32
2X2X1 1/2 CT665 300 2.02 2.02 2.16 3.72
2x2x2 1/2 CT667 300 2.60 2.60 2.39 5.10
Page 39
I
p
AwtBtar' FIG. 7045 Clamp-T®, FPT Branch Fire Products Division of Anvil International
The Gruvlok® Clamp-I provides a quick and easy outlet is at any location along the pipe. A hole drilled or cut in
the pipe to receive the locating collar of the Clamp-I is
all that is required. The full, smooth outlet area provides
For optimum flow characteristics.
The Clamp-I housing is specially engineered to conform
to the pipe O.D. and the Clamp-I gasket providing a leak
tight reliable seal in both positive pressure and vacuum
conditions. Working pressure ratings shown are for
reference only and are based on Schedule 40 pipe. For
the latest UL/ULC listed and FM approved pressure ratings
versus pipe schedule, see www.anvilstar.com or contact
your local AnvilStar Representative.
The Gruvlok Clamp-I provides for a branch or cross
connection in light wall or standard wall steel pipe.
The Fig. 7045 Clamp-I female pipe thread branch is
available with NPT or ISO 7/1 connection and the Fig.
7046 Clamp-I has grooved-end branch connection.
Clamp-I cross connections are available in various sizes
allowing greater versatility in piping design.
NOTE: Variable End Configurations are Possible -
Thd x Thd and Gr. x Thd. Sizes - 2"X 1/2" through 8" x 4"
CLAMP-T FLOW DATA
(FRICTIONAL RESISTANCE)
Fig. 7045 Threaded Branch Branch Size CV. Value Equiv. Pipe Length
In./0(mm) ___________ Alm
1/2 22 1.0
15 0.3
1/4 25 2.0
20 0.6
1 44 2.0
25 _____________ 0.6
11/4 76 2.5
32 0.8
89 4.0
40 - 1.2
2 164 3.5
50 - 1.1
2/2 152 12.5
65 - 3.8
3 318 8.5
80 . 2.6
4 536 8.0
100 - 2.4
-Available galvanized.
HOUSING:
Ductile Iron conforming to ASTM A-536, Grade 65-45-12 or
Malleable Iron conforming to ASTM A-47, Grade 32510
ANSI BOLTS & HEAVY HEX NUTS:
Heat treated, oval neck track head bolts conforming to ASTM A- 183 Grade
2 with a minimum tensile strength of 110,000 Psi and heavy hex nuts of
carbon steel conforming to ASTM A-563 Grade A or Grade B, or J995
Grade 2. Bolts and nuts are provided zinc electroplated as standard.
U-BOLT:
Cold drawn steel and zinc plated.
COATINGS:
Rust inhibiting paint Color: ORANGE (standard)
Hot Dipped Zinc Galvanized (optional)
Other available options: Example: RAL3000 or RAL9000 Series
For other coating requirements contact an AnvilStar Representative.
LUBRICATION:
Standard Gruvlok
Gruvlok XtremeTM required for dry pipe systems and freezer applications.
GASKETS: Materials
Properties as designated in accordance with ASTM D-2000.
Grade "E" EPDM (Green color cede)
-40°F to 230°F (Service Temperature Range)(-40°C to 110°C)
Recommended for water service, diluted acids, alkalies solutions, oil-free
air and many chemical services.
NOT FOR USE IN PETROLEUM APPLICATIONS.
FM
III I. UC APPROVED
For Listing/Approval Details and Limitations,
vjtll our website at www.anvilsiar.com or contaci
on A iIe/A,r.iIStorvu Sales Representative.
PROJECT INFORMATI ON A PPROVAL ISTAMP tI
Project: U Approved
Address: Approved as noted
ontractor: J Not approved
gineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
5/09
ILt FIG. 7045 Clamp-T®, FPT Branch Fire Products Division of Anvil International
Fig. 7045 Fig. 7045 (U-Bolt)
345 FPT RPANCH fT11FF corJTIrdiiFc TC
. WARNING
For dry pipe systems and freezer applications
lubrication of the gasket is required,
Gruvlok° XtremeTM Lubricant is required.
Nominal Hole Dimensions V Max. Clomp-T Dimensions Bolt Specified Torque § Approx.
Size Pressure Size Wt. En. O.D.Working
Mm . Diameter Max. Diameter T U Threaded w ' z Mm. Max.
In-1011(mm) In1mm In./mm In1mm PSI/bar In Am In1mm In ./mm In1mm In./mm In./mm In ./mm FL-lbslll-m LbsjKg
2x½ 2.375x0.840 1½ 1½ 500 21A s/is 2% ½ 51h 3 ½UBolt 30 40 2.3
50:75 60.3:21.3 38 41 34.5 56 1 74 61 12 140 16 - 7.0
2 x Y4 2.375 x 1.050 16 1½ 500 2!As 1/1s 2% 1½ 51h 3 ½ V-Bolt 30 40 2.3
50:20 60.3:26.1 38 41 345 52 74 61 38 140 16 - 1.0
2 x 2.375x1.315 1½ 1% 500 l/io !,s 21h 1½ 51h 3 ½ V-Bolt 30 40 2.6
50:25 60.3:33.7 38 41 34.5 51 74 61 38 140 16 - 7.2
2x 1¼ 2375x 1.660 2 21/a 500 21A6 !Iis 2% 1½ 51h 31h ½ U-Bolt 30 40 2.7
50:32 60.3:42.4 57 54 34.5 55 14 73 38 140 89 - 7.2
2x 116 2.375:1.900 2 21A 500 21A6 /i 2¼ 1½ 7 31h ½ U-Bolt 30 40 2.5
50: 40 60.3x48.3 57 54 34.5 1 55 14 73 38 778 89 . - - 71
2½x½ 2.875x0.840 116 1% 500 2!,i6 2% 1% 51h 3 ½V-Bolt 30 40 3.0
65:15 1 73.0:21.3 38 41 345 62 14 1 73 44 1 140 16 - 1.4
21hxV4 2.815x1.050 1½ 1% 500 2% 'ro 2% 1% 5½ 3 ½U-Bolt 30 40 2.9
65:20 73.0:26.7 38 41 34.5 59 14 13 44 740 16 - - 1.3
2½ x 2.875, 1.315 1½ 15/s 500 2% '/18 2¼ 1'/i 6¼ 3 ½ U-Bolt 30 40 2.9
65: 25 73.0:33.7 38 41 34.5 55 14 13 44 756 16 - 1.3
21h 01¼ 2.875 01.660 2 214 500 27Ao /I6 3¼ 1% 61A 3% ½ U-Bolt 30 40 3.4
65:32 73.0:42.4 51 54 34.5 62 14 79 44 156 86 - 1.5
2½x1½ 2.875x1.900 2 214 500 2¼ 'u 3¼ 1% 614 3% ½U-Bolt 30 40 3.4
65: 40 1 73.0:48.3 51 54 34.5 62 74 1 79 44 1 156 86 1 - 1.5
3x½ 3.500x0.840 16 1% 500 21s /io 3 21A 7 3% ½U-Bolt 30 40 2.8
80175 88.9:21.3 38 41 34.5 65 14 76 54 118 95 - 7.2
3 xY4 3.500x1.050 1½ 1% 500 2A 6 '/16 3 21A 7 3% YoU-Bolt 30 40 2.7
80%20 88.9:26.7 38 47 34.5 62 14 76 54 778 95 - - - 1.2
3:1 3.500x 1.315 1½ 1% 500 21A6 9/1 3 2¼ 7 3% ½ V-Bolt 30 40 2.7
80:25 1 88.9:33.7 38 41 34.5 1 59 74 76 54 178 95 - 1.2
3x1¼ 3.500x1660 2 214 500 21/is 1½ 3% 2¼ 6% 3% ½x2% 80 100 3.4
80:32 88.9%42.4 57 54 34.5 68 38 1 86 54 715 95 - 1.5
3x1½ 3.50001.900 2 2½ 500 WAs 1½ 3% 2¼ 6% 3% ½ x2YA 80 100 4.4
80:40 88.9:48.3 57 54 34.5 68 38 86 54 175 95 - 2.0
3x2 3500x2.375 216 2½ 500 2% 1½ 3% 214 6¼ 41A ½x2% 80 100 4.6
80:50 88.9:60.3 64 67 34.5 68 38 86 54 175 705 - 2.7
4x½ 4300x0.840 116 15A 500 3½o /i6 31h 25A 7% 33A ½U-Bolt 30 40 2.9
100:15 114.3:21.3 38 41 34.5 16 74 89 61 1 791 95 - 1.3
4x% 4.500 x 1.050 1½ 1% 500 3¼s 9/is 3½ 2% 7V4 3Y4 YoU-Bolt 30 40 2.8
700:20 714.3:26.7 38 41 34.5 18 14 1 89 61 791 95 . 73
4:1 4.500, 1.315 1½ 1½ 500 2% 'ts 31 2% 7% 3% ½ li-Bolt 30 40 2.7
700:25 114.3:33.7 38 41 34.5 1 13 14 89 61 791 95 1 - 1.2
401¼ 4300x1.660 2 21A 500 3%s 1% 31/a 2% 71h 3% ½ x 2'A 80 100 4.5
100:32 1743:42.4 51 54 34.5 81 48 98 1 61 191 95 . 2.0
401½ 4.50001.900 2 21h 500 33/16 1¼ 3¼ 21A 71h 3% ½ 02% 80 100 4.6
700:40 114.3:48.3 57 54 345 87 48 98 61 1 791 95 - 2.1
4,2 4.500x2375 216 2% 500 3%6 11/8 4 21A 71h 414 ½x2% 80 100 7.7
100:50 774.3:60.3 64 61 34.5 1 84 48 702 61 797 705 1 - - 3.5
4x2½ 4.500x2.875 2% 2¼ 500 3'¼6 11/6 4 21A 791 4% ½x2°h 80 100 5.2
700:65 774.3:13.0 70 73 34.5 18 48 102 61 191 111 - 2.4
4:30.1). 4.500:2.996 2114 26 500 3 1% 4 21i 1½ 44 ½x2 80 700 5.2
100x80 114.3:76.1 70 73 345 76 1 48 102 67 191 111 . 24
4:3 4.500x3.500 391 3% 500 31/4 1¼ 64 2% 7½ 51/4 ½x3½ 80 100 6.5
700:80 1 714.3: 88.9 1 89 1 92 34.5 1 83 1 48 708 67 1 797 1 733 1 - 2.9
NOTE: 21h", 5° and 6° Nominal size run pipe maybe used on 3" 0.0., 51h" O.D. and 6½" 0.D. pipe. § - For additional Bolt Torque information, see Technical Data Section.
V Based an use with standard wall pipe. (Additional larger sizes on next page)
Not for use in copper systems.
5/09
Fig. 7045
Atr FD. 745 Clamp-P, FPT Branch Firs Products Division of Anvil International `tv,&WIL
Fig. 7045 (U-Bolt)
I A WARNING
For dry pipe systems and freezer applications
lubrication of the gasket is required.
Gruvlok6 XtremeTM Lubricant is required.
FIGURE L.L4 II ffI : :1i 1.4: .i.iiiotiiisiT FROM j..iaavicsiui PAGE)
Nominal Hole Dimensions Max. Clamp-I Dimensions Bolt Specified Torque § Approx.
Size O.D.Working Mm . Diameter Max. Diameter Pressure T U Threaded W '' z Size Mm. Max. Wt. Ea.
InjDN(mm) In Ant InJmm In./mm PSI/bar InImni In1mm injmm !njmnt In./mm In./mm In Am Ft.-Lbs/N-m LbsjKg
5:1% 5.563 x 1.660 2 2¼ 500 V/4 1% 4% 3¼ 9¼ 334 t/tx 31/4 100 130 5.4
125:32 141.3: 42.4 51 54 34.5 1 94 48 III 83 232 95 1 - 2.4
5: 1½ 5.563 :1.900 2 2¼ 500 3'%s V/a 43's 31/4 9¼ 3Y4 %X3'/4 100 130 5.5
125:40 747.3:48.3 57 54 34.5 94 48 1 III 83 1 232 95 - 2.5
5:2 5.563:2.375 2½ 21/a 500 31316 V/a 416 31/4 91A 41A 34:3% 100 130 5.7
725:50 141.3:60.3 64 61 34.5 91 48 774 83 232 705 - 2.6
5x2½ 5.563:2.875 234 2% 500 3911 1/a 434 31/4 9¼ 4% %x3% 100 130 7.0
725:65 741.3:13.0 10 13 34.5 91 48 727 83 232 717 - 3.2
5:30.0. 5.563:2.996 2 24 500 33 1'. 4% 31,4 9% 4 x414 130 780 1.0
125:80 141.3:76.1 70 73 34.5 1 95 48 121 83 232 111 - 3.2
5:3 5.563:3.500 31/2 354 500 4 1/a 5 31/4 9¼ 5¼ %x3¼ 100 130 8.7
125:80 741.3:88.9 89 92 34.5 702 48 721 83 232 733 . 39
6:1 ¼ 6.625:1.660 2 21/a 500 4346 2 41/a 3% 10¼ 3% 34:4% 100 130 7.8
150:32 768.3:42.4 51 54 34.5 706 51 724 98 251 95 - 3.5
6:134 6.625x1.900 2 2¼ 500 4/4 2 4½ 31A 10½ 3Y4 ½x434 100 130 7.8
150: 40 768.3:48.3 57 54 34.5 106 1 57 124 98 251 95 - 3.5
6:2 6.625:2.375 2½ 2% 500 434a 2 4% 3% 10¼ 4¼ 34:4% 100 130 7.8
150:50 768.3:60.3 64 67 34.5 706 51 1 724 98 251 705 . 35
6:234 6.625:2.875 234 2% 500 04 2 51A 3% 1014 4% 54:4% 100 130 8.4
750:65 168.3:13.0 10 13 34.5 106 57 130 98 251 III - 3.8
6:30.0. 6.625:2.996 26 2a 500 4% 2 5% Xi 7014 4!'i %x4% 100 130 8.4
150:80 168.3:76.1 70 73 1 34.5 105 51 130 1 98 257 1 111 - 3.8
6:3 6.625:3.500 31/2 35's 500 4% 2 5% 31h I 01 5V4 54:4% 100 130 9.6
750:80 768.3:88.9 89 92 34.5 1 III 57 137 98 251 133 1 - 4.4
6:4 6.625:4.500 46 45A 500 4% 2 5½ 3% 101/8 61h 34:4% 100 130 10.5
150:700 168.3:114.3 114 II? 34.5 III 51 140 98 257 765 . 4.8
8:2 8.625:2.750 25's 214 500 5314 21/4 5% 5 12% 4¼ 34:4% 130 180 11.3
200:50 219.1:10.0 64 67 34.5 132 57 749 721 324 105 . 5
8:234 8.625:2.875 2Y4 2% 500 55A6 2¼ 6¼ 5 12,4 4% 34:434 130 180 11.1
200:65 279.1:13.0 70 73 1 34.5 134 1 51 759 121 324 1 111 - 5.0
8:30.0. 8.6 25:2.996 23i 2% 500 511-4 2% 6¼ S 72% 46 %x4' 130 180 17.1
200:80 219.1:76.1 70 73 34.5 133 57 159 127 324 111 . 50
8 x 3 8.625:3.500 3½ 3% 500 5% 2¼ 6% 5 12Y4 5¼ Y4: 41h. 130 180 13.0
200:80 279.1:88.9 89 92 34.5 131 57 762 127 324 733 59
8:4 8.625:4.500 41/2 41A 500 5% 21/4 65's 5 12% 61h 34:434 130 180 16.2
200: 700 1 219.1:714.3 774 II? 34.5 731 57 165 121 1 324 765 1 - 7.3
NOTE: 2½", 5" and 6" Nominal size run pipe may be used on 3" O.D., 51h" O.D. and 61h" O.D. pipe. § - For additional Bolt Torque information, see Technical Data Section.
V Based on use with standard wall pipe. (Additional larger sizes on next page)
Not For use in copper systems.
S
5109
Fig. 105 - Coach Screw Hanger Rod
Size Range - 3/8" thru 1/2" rod
Material - Carbon Steel
Function - Typically used to suspend pipe from wood joists.
Machine threaded on one end and lag threaded on the other
end. It is recommended that pilot holes be pre-drilled to pre-
vent beam from splitting and to aid in starting lag threads.
Finish - Plain
Note - Available in Electro-Galvanized and HOG finish or
Stainless Steel materials.
Order By - Figure number, rod size, length and finish
Dimensions Weights
Machine
Rod Size Rod Thread Lag
A Length Length Length
3/8 3 1/2 21/2
3/8or1/2 4 1'/2 21/2
3/8 5 2V2 21/2
3/8 or 1/2 6 21/2 21/2
3/8 7 21/2 21/2
3/8 or 1/2 8 21/2 21/2
3/8 9 21/2 21/2
3/8 10 21/2 21/2
3/8 11 21/2 21/2
3/8 12 2'/2 21/2
106 -Tie Bolt
Material -Carbon Steel
Function - Rmended for securing the
connection of steel pi to ductile pipe by
attaching tie bolts to pipéf1arges then
connect tie rods. May be use ertical or
horizontal applications.
Approvals - Conforms to NFPA Pampiil&
24, Installation of Private Fire Service
Maintenance 4" - 12" pipe size.
Finish - Plain
Note - Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, size and finish.
Custom lengths for thicker flange avaiIaDI '
SIZE SPECIFY 4-
OR
4-112 1
.STEEL PIPE RISER
ADAPTER
.4 1I1L1{
1HRADROD
PL OW RISER
Main Office/Manufacturing Facility 1375 Sampson Ave. Corona, CA 92879 • Ph: 909.737.5599 • Fax 909.731.0330
Customer Service • 800.186.5266
INIR!Ift! tnlrn tflni
Dimensions
Rod Max. Rec. Load Lbs.
Size For Service Temp
650°F
3/8 730
1/2 1350
5/8 2160
3/4 3230
7/8 4480
Component of State of
California OSHPO Approved
Seismic Restraints Syst -•.
4DF@-.M - Rod Stiffener
Fig. 981pd Stiffener w/Break-off Bolt Head
Size Range - Secures a"thru 7/8" hanger rod
Material - Carbon Steel
Function - Secures channel to for vertical seismic bracing.
Approvals - Included in our
Seismic Restraint Systems Guidelines
Finish - Electro Galvanized
Note - Available in HOG finei'tainless Steel materials.
Order By - Figure nube(
FIG. 98
FIG. 98B
Fig. 99 - All Thread Rod Cut to Length
Size Range - Secures 3/8" thru 7/8" rod in
1" increments
SMaterial - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain
Note - Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, rod diameter, rod
length and finish
Fig. 100 - All Thread Rod Full Length
Size Range - Secures 3/8" thru 11/2" rod in
10' lengths
Material - Carbon Steel
Maximum Temperature - 750°F
Finish - Plain
Note - Available in Electro-Galvanized and
HDG finish or Stainless Steel materials.
Order By - Figure number, rod diameter
and finish
S
Dimensions • Weights
Max Rec. Load Lbs.
Rod For Service Temps Approx.
Size 650°F Wt./100
1/4 240 12
3/8 730 29
1/2 1350 53
5/8 2160 84
3/4 3230 123
7/8 4480 169
1 5900 222
11/4 9500 360
1½ 13800 510
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
aflaflfl#flht.fl nm
Fig. 200 - "Trimline"
Fig. 200R (Import) -
Adjustable Band Hanger
"Trimline" Adjustable Band Hanger
w/Retainer Ring
C®US LISTED
Size Range - 1/2" thru 8" pipe
Material - Carbon Steel, Mil. Galvanized to G90
specifications
Function - For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features -
(1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe
from abrasion. Captured design keeps adjusting
nut from separating with hanger. Hanger is eas-
ily installed around pipe.
(21/2" thru 8") Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals - Underwriters' Laboratories listed
(1/2" thru 8") in the USA (UL) and Canada (cUL)
for steel and CPVC plastic pipe and Factory Mutual
Engineering Approved (3/4" thru 8"). Conforms to
Federal Specifications WW-H-1 71 E, Type 10 and
Manufacturers Standardization Society SP-69, Type
10.
Maximum Temperature - 650°F
Finish - Mu. Galvanized. Stainless Steel materials will
be supplied with (2) hex nuts in place of a knurl nub.
Order By - Figure number and pipe size
Note - Figure 200R (import) with retainer ring and
non-captured knurl nut.
Fig. 200R 21h" - 8"
Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. WtJ100
1/2 3/8 8mm or 10mm 31/8 25/8 400 11
3/4 3/8 8mm or10mm 31/8 21h 400 11
1 3/8 8mm or 10mm 33A 2% 400 12
11/4 3/8 8mm or 10mm 33/4 2% 400 13
1½ 3/8 8mm or 10mm 3½ 2/8 400 14
2 3/8 8mm or 10mm 41h 3 400 15
21h 3/8 10mm 5% 41,b 600 27
3 3/8 10mm 5½ 4 600 29
3½ 3/8 10mm 73A 51/4 600 34
4 3/8 10mm 7% 5 1000 35
5 1/2 12mm 91A 61/4 1250 66
6 1/2 12mm 101/8 63/4 1250 73
8 1/2 12mm 131/s 83/4 1250 136
OFFICE/MANUFACTURING FACIUTY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
Fig. 200R 1/2" - 2"
P44.2 Angle Bracket
Material - Car Steel
Function - Recomme d for supporting pipe at various
distances from wall or colum
Finish - Plain
Note - Available in Electro-Galvanized an DG finish or
Stainless Steel materials.
Order By - Figure number, size and finish
Dimensions 'Weights
Pipe Hole x. Rec. Approx.
Size A B Si Load Lbs. Wt./100
1 3 2 7/16 180 46
2 4 7/16 180 65
3 3 2 9/16 390 85
4 3 9/16 390 115
Fig. 50 - Side Beam Bracket
•
Size Range - 3/8" thru 7/8" rod
Material - Carbon Steel
Function - Recommended for attaching hanger rod to side
of beams or walls.
Approvals - 3/8", Underwriters' Laboratories Listed in the
USA (UL) and Canada (cUL), and Factory Mutual
Engineering approved.
Finish - Plain
Note - Available in Electro-Galvanized and HDG finish or
Stainless Steel materials.
Order By - Figure number, rod size and finish
Dimensions- Weights
Pipe Hole Max. Rec. Approx.
Size A B C Size Load Lbs. Wt./100
3/8 2 3/4 2 7/16 700 35
1/2 2 3/4 2 9/16 700 35
5/8 2 3/4 2 11/16 700 32
3/4 2V 3/4 21/2 13/16 1250 110
7/8 2'/2 3/4 2V2 15/16 1250 100
ses
Office/Manufacturing Facility. 1375 Sampson Ave. . Corona, CA 92819 • Ph: 909.737.5599 • Fax: 909.137.0330
Customer Service • 800.786.5266
,,m,.,,MI.n anm
(D TOLCO'
a biand of NIBCO Revision 5/24/2001
Fig. 25
Surge Restrainer
fl
Size Range - One size fits 3/4 thru 2 inch pipe.
Material - Steel.
Function - Designed to be used in conjunction with TOLCOTM Band
Hangers to restrict the upward movement of piping as it occurs during
sprinkler head activation or earthquake type activity. The surge restrainer
is easily and efficiently installed by snapping into a locking position on the
band hanger. This product is intended to satisfy the requirement as
indicated in the National Fire Protection Association (NFPA #13, 1999
Edition), 6-2.3.3, 6-2.3.4, and A-6-2.3.3. Can be used to restrain either
steel pipe or CPVC plastic pipe.
Approvals - Underwriters' Laboratories Listed Qjiy when used with
TOLCO band hangers Fig. 2, 2 NFPA, and 200, in the USA (UL) and
Canada (cUL).
Finish - Pre-Galvanized.
Note—Available in Electro-galvanized and HDG finish.
Order By - Figure number and TOLCO band hanger, size from 3/4 thru 2.
Patent #5,344,108
Main Office/Manufacturing Facility • 1375 Sampson Ave. • Corona, CA 92870 • Ph: 909.737.5599 • Fax: 909.737.0330
Distribution Center • 8790 Fruitridge Road • Sacramento, CA 95826 • Ph: 916.388.7800 • Fax: 916.388.1401
Manufacturing Facility • 4851 Homestead Road. Bldg. 118 • Houston, TX 77028 • Ph: 713.672.0058 • Fax: 713.672.0074
www.folco.com
6~Affffyg j
i- #14 SW Red
Nut Driver
Part # 8114910
114' 8047957 SWD 100 1/4-14x1" TEKS 3 1477 (169a.) .060%16 ga 3/16" 25 125
[I1__114' 8049957 SWDR 100' 1/4-20 x 1' TEKS 3 1900 (ga. .036%20 ga 3/18' 25
3/8' 8050957 SWD 10 114-14x 1° TEKS 3 1477 (16ga.) .060"-16 go 3/16' 25 125
- 3/8° 8080925 SWD 10-SS 114-14x1'TEKS3 1477 (L6ga.L - .060°46ga 3/16' 25 125
3/8' 8051957 SWD 15 114-14 x 1-1/2" TEKS 3 1477 (169a.) .060°-16 ga 3/16" 25 125
3/8° 8052957 SWD 20 1/4-14x2'TEKS3 14j1g .060"-16 as 3116" 25 iii]
3/8" 8053957 SWD 516 5/16-18 x 1-1/4" TEKS 3 2480 (20 ga.) .036'-20 ga 3/16" 25 125
r >3/8' 8055957 SWDR 1' 114-20 x l" TEKS 3 1900 (20 ga.) 15001475 - 036°-20ga - 3/18' 25 ij
/.<> 3/8' 8054957 SWDR 1-1/2 12-24 x 1-112"TEKS 5 2375 (3/16') 1500 1475 .188"-3116' 1/2' 25 125
3/8" 8056957 SWDR 516' 5116-18x 1-1!4"TEKS 3 2480 ga 1500 1475 .036"-20_9a 3/16°
3/8'
*Includes retaining nut
8057957 SWT 15 12-24 x 1-112' TEKS 5 2375(3/16') .188"-3/16" 1/2' 25 125
Eliminates distortion of threaded rod in sloped too LaPlications,
Accommodates 3-1/2 x 12 pitch.
Installs into angled z.purlinjpwi&eaded rod to hang plumb.
'Allows 17° deflecJqdIn "ertical.
Made in
th 8*O*JflCIOt'd1Oflail Wwwmitwbuildexxom
#14 Black 3/8" 81 SH-DSTR 1' 1/4.20 X? 3220(3/16') Nut Driver TEKS 3 Part # 811391 0
2368(1/2° steel Vertical)
3/8" 8268957 SH-TEK 50
jnlar~rg,r1— Nut
1/2 8270957 SH TEK 50
1585(3/16" HSS 45° off Vertical)
12-24 x 1.3/4° 1306(45" off Vertical) 1500 (Vertical)
TEKS 5 2281 (3/16' HSS) 850(45° off Vertical)
2368(1/2°steel Vertical)
12-24 x 1-3/4' 1306(45' off Vertical) -TEKS 5 2281 (3(16'I1SS)
1585(3/16'HSS 45" off Vertical)
rver Part #8273910 DOOS not comply with ROHS ,equirementsllncfudes retaining nut
1475 .038' 3/16' 25 1251
—
Product description
Intumescent (expands when exposed to fire) firestop sealant that
helps protect combustible and non-combustible penetrations for
up to 4 hours fire rating
Technical Data FS-ONE Intumescent Firestop
(at 73°F (23°C) and 50% relative humidity)
Chemical basis: Water-based intumescent acrylic dispersion
Density: Approx. 1.5 g/cm3
Color: Red
Working time: Approx. 20-30 mm
Curing time: Approx. 14-21 days
Shore A Hardness: Approx. 35
Movement capability: Approx. 5%
Intumescent Activation: Approx 250°F (121°C)
Expansion rate (unrestricted): Up to 3-5 times original volume
Temperature resistance (cured): -40°F (-40°C) to 212°F (100°C)
Application temperature: 35°F (2°C) to 100°F (38°C)
Surface burning characteristics:
(ASTM E 84-96)
Flame Spread: 0
Smoke Development: 5
Sound transmission classification: 50
ASTM E 90-97
System advantage/Customer benefits
Protects most typical firestop penetration applications
Easy to work with and fast cleanup
-1-m-.Z011~2 expertise. in every Case.
Can be repenetrated when laying new cables
Can be painted
Approvals
ICBO Evaluation Service, Inc. Report No. 5071 CLASSJREDBY I I FM
® TE!S LBORA1ORES. INC. I California State Fire Marshal Listing No. 1200:108 UNDE
M 4e
RWR1
R USE IN JO:NTSNSTEMS AIMMM
City of New York MEA 326-96-M vol. II SULRRERcoISTANCEDREG1OnY I
I °'°'
Installation instructions for FS-ONE
Cable installation
Aft
1. Clean opening. 2. Pack mineral wool. 3. Apply FS-ONE. 4. Smooth FS-ONE. 5. Leave completed seal 6. Fasten identification (If required) undisturbed for 48hours. plate (if required).
Pipe installation
I. Clean opening. 2. Pack mineral wool. 3. Apply FS-ONE. 4. Smooth FS-ONE. 5. Leave completed seal 6. Fasten identification
(If required) undisturbed f0r48 hours. plate (if required).
Opening
Clean the opening. Surfaces to which FS-ONE will be applied should be
cleaned of loose debris, dirt, oil, moisture, frost and wax. Structures
supporting penetrating items must be installed in compliance with
local building and electrical standards.
Application of firestop sealant
Install the prescribed backfilling material type and depth to obtain the
desired rating (if required). Leave sufficient depth for applying FS-ONE.
Application of firestop sealant: Apply FS-ONE to the required depth in
order to obtain the desired fire rating. Make sure FS-ONE contacts all
surfaces to provide maximum adhesion. For application of FS-ONE use a
standard caulking gun, foil pack gun, bulk loader and bulk gun. With
FS-ONE buckets, Graco type sealant pumps may be used. (Contact pump
manufacturer for proper selection).
Smoothing of firestop sealant: To complete the seal, tool immediately to
give a smooth appearance. Excess sealant, prior to curing, can be cleaned
away from adjacent surfaces and tools with water.
Leave completed seal undisturbed for 48 hours.
For maintenance reasons, a penetration seal should be permanently
marked with an identification plate and fastened in a visible position next
to the seal.
Notice about approvals
Check that the penetration has been sealed according to the specified
drawing in the UL Fire Resistance Directory or the Hilti Firestop Manual.
For further advice, please contact Hilti customer service. Refer to Hilti
product literature and UL Fire Resistance Directory for specific application
details.
Not for use...
High movement expansion joints
Underwater
On materials where oil, plasticizers or solvents may bleed i.e. impregnated
wood, oil based seals, green or partially vulcanized rubber
In any penetration other than those specifically described in this manual
or the test reports
Safety precautions
Before handling, read the product and Material Safety Data Sheet for
detailed use and health information
Keep out of reach of children
Wear suitable gloves and eye protection
Storage
Store only in the original packaging in a location protected from moisture
at temperatures between 40°F (5°C) and 86°F (30°C)
Observe expiration date on the packaging
Saving Lives & Propertythrough innovation & education° Hilti U.S.: 1-800-879-8000 / www.us.hilti.com
%.
Carlsbad Municipal Water District
Potable Water Discharge
Event Report AS 12,00c3o
T . Date: Alt 611
Location: :1964
Reason for Discharge Event: 4?E M'°.tlL.
Type of Event: Initial
Dewatering Water Mains tJA Estimated Discharge Flow: 1500 &fM
Note: Includes flow testing and flushing
Dewatering Reservoirs t4JA 021C
Start Time o
Unscheduled Water Discharge . k End Time
Pre-Dechiorinatlon Residual:
Clear flow path of debris, surface 0. contaminants and/or hazardous Post-Dechlorination Residual:
materials. Do not remove native
vegetation.
(less than. 0.1 mg/L)
pH within limits of 6.0 and 9.0
Erosion control, I.e.
sandbags, slit fencing, hay bales,
gravel bags, decreasing the velocity .
. of discharge water.
Upon completion of dewatering, ensure
that the flow path is free of all
temporary erosion prevention materials.
Upon completion completion of dewateririg, ensure
that any sediment or silted areas are
cleared.
Water Sampling Performed by
Comments;
Submitted by: Reviewd by:
(Name & Date) (Name & Date
Flow Test Record
Test Hydrant
Location Il
Hydrant ID No. Size Main_____________
Static ...... ........._'1
Residual .......... 115
Pressure Drop. (, (PDX 1).....K factor for PDI 1 _4 .4'
Flow Hydrant(s)
Hydrant I location tCt ( ? At0&çL. OA-S kf
Hydrant 2 location
Hydrant 3 location
Hydrant I Pitot PSI GPM: ('boo Size of Orifice 2.
Hydrant 2 Pitdt PSI GPM: Size of Orifice__________
Hydrant 3 Pitót PSI GPM: Size of Orifice.__________
Total:__________
.(Q1)
Calculated test and flow data.. 0 x PD2 k =Q2
PDI*k
Static........................
Desired Residual ........ 20
Pressure Drop (PD 2). 1 K factor PD 2:
x divided by 4.4, equals 2I' GPM at 20 psi residual.
Q PD2k POlk .Q2
Comments:
Test conducted for:
cbccM L-i-t0c
Conducted by: iwtik . '€ c1.,ot-
Date: *jt,Ji#z. Time:_________
—