HomeMy WebLinkAbout1905 CALLE BARCELONA; ; AS090085; PermitCity of Carlsbad.
Sprinkler Permit
Permit No: AS090085
1905 CALLE
Job Address: Status: ISSUED
BARCELONA •
Permit Type: SPRINK Applied 7/22/2009
Parcel No: 2550120400 Approved: 7/22/2009
Lot #: 0 • • •
Reference No.:
• • • Issued: 7/22/2009
PC #: Inspector:
Project-Title: ULTA 01 FIRE SPRINKLER PLAN REVIEW & INSPECTION ULTA
Cosmetics
Applicant: •
•
• Owner:
A & D FIRE SPRINKLERS, INC..' • BORDERS INC FOURTH QUARTER
2ND FLOOR
11465 WOODSIDE AVE •
C/O DELOITTE TAX LLP
SANTEE, CA 92071 P 0 BOX 131071
CARLSBAD CA. • 619-448-1962
Fees ($) Add'I Fees ($). • Total ($) Balance ($)
•• 235 .0 235 • 0
lit
'4
___
FIRE SPRINKLERS INC.
UL TA CARLSBAD TI
1905 CALLE BARCELONA SUITE 110
CARLSBAD, CA 92,009
FIRE SPRINKLER SUBMITTAL
MANUFACTURER DATA SHEETS
** Materials of equal design, utility, and performance may be substituted for submitted materials so as to avoid delays in the
construction schedule and shall be deemed accepted by the Purchaser.
AS 0100t57 FILE COPY
4
tilco/F/re & Building
Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series TY-FRB - 2.8, 4.2, 5,6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
S
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
114 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.8K, 1/2"NPT
TY1231 - Pendent 2.81K, 1/2"NPT
TY2131 - Upright 4.21K, 1/2"NPT
TY2231 - Pendent 4.2K, 1/2"NPT
TY3131 - Upright 5.61K, 1/2"NPT
TY3231 - Pendent 5.61K, 1/2"NPT
TY4131 - Upright 8.0K, 3I4'NPT
1Y4231 - Pendent 8.0K, 3/4'NPT
Page 1 of 10 APRIL, 2006 TFPI7I
ESCUTCHEON
PLATE SEATING
SURFACE
7/16 (11,1 mm)
1/2° ** NOMINAL
MAKE-IN
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16°
(55,6 mm)
1-1/2"
(38,1 mm)
=
S
Page 2 of 10 TFPI7I
7 FLATS
STYLE 10 or 20
RECESSED SSU* ESCUTCHEON DEFLECTOR
7/16"
(11.1 mm)
NOMINAL I
11/
—
1 _ 1
MAKE-IN
2-3/16"
'WRENCH (55,6 mm)
1/2" NPT** SSP DEFLECTOR* h — 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly 5- Compression 7 - Bushing orifice seat on frame. Screw **pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYI 131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
7/16" (11,1 mm) STYLE 10 or 20
** NOMINAL RECESSED 1/2 MAKE-IN ESCUTCHEON NPT
SSP DEFLECTOR* 2-7/8" (73,0 mm) DIA
SSU *
DEFLECTOR
;r(N
mm) 1
L
'
-IN
2-3/16"
NAL I
WRENCH (55,6 mm)
FLATS
1/2" NPT** I
6*
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3-Sealing 4-Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
S
6*
ESCUTCHEON 1/2"(12,7mm)
PLATE SEATING ** NOMINAL
SURFACE NPT MAKE-IN
25!16" \TJ (58,7 mm)
1-9/16" I (39,7 mm)
SSP DEFLECTOR*
PENDENT
STYLE 30 or 40
RECESSED
ESCUTCHEON
WRENCH
FLATS
I - 2-7/8" (73,0 mm) DIA. -
RECESSED PENDENT
SSU *
DEFLECTOR
1/2" 1
(12,7 mm) I NOMINAL I MAKE-IN I 2-1/4"
(57,2 mm)
3/4 NPT**
6*
TFPI7I Page 3 of 10
T_
2-3/16"
(55,6 mm) T
STYLE 10 or 20
RECESSED SSU* ESCUTCHEON DEFLECTOR
I
7/16"
(11.1 mm) 1
Ill I I II NOMINAL I
E-IN
RENCH
J,j__ 2-3/16"
FLATS
(55,6 mm
1/2NPT**
ESCUTCHEON
PLATE SEATING
SURFACE
7/16(11,1 mm)
1/2" ** NOMINAL
MAKE-IN NPT
SSP DEFLECTOR* h"— 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5 - Compression orifice seat on frame. Screw **Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
11
UPRIGHT
1-
Page 4 of 10
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE***
IPOLVESTER
2.8
1/2'
PENDENT
(TY1231)
and
UPRIGHT
(TYII3I)
135°F/57°C Orange
1,2,3,5 155°F/68°C Red
175°F179°C Yellow.
200°F/93°C Green
286°F1141°C Blue
NPT 135°F/57°C Orange
1, 2, 5
RECESSED
PENDENT
(TY1231)
Figure 5
155°F/68°C Red
175°F179°C Yellow
200°F/93°C Green
135°F157°C Orange
RECESSED
PENDENT
(TY1231)°°
Figure 6
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
4.2
1/2"
NPT
PENDENT
(1Y2231)
and
UPRIGHT
(T''2131)
135°F157°C Orange
1,2
155°F/68°C Red
175°F/79°C Yellow
200°F/93°C Green
28&F/141°C Blue
135°F/57°C Orange
RECESSED
PENDENT
(TY2231)°
Figure 7
155°F/68°C Red
175°F179°C Yellow
200°F/93°C Green
135°F157°C Orange
RECESSED
PENDENT
(TY2231)°
Figure 8
155°F/68°C Red
175°F179°C Yellow
200°F193°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2° NPT) or Style 40 (3/4' NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
TFPI7I
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/ps1112 (40,3 LPM/bar112)
K = 4.2 GPM/psi1l2 (60,5 LPM/barl'2)
K = 5.6 GPM/p5i112 (80,6 LPM/bar112)
K = 8.0 GPM/psi112 (115,2 LPM/barl'2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame ............Bronze
Button ........ Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ..............Glass
Compression Screw' .....Bronze
Deflector .......Copper/Bronze
Bushing (K2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
S
S
S
TFPI7I Page 5 of 10
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
WHITE
POLYESTER
I LEAD
COATED
5.6
1/2"
PENDENT
(TY3231)
and
UPRIGHT
(TY3131)
135°F/57°C Orange
1,2,3,4,5,6,7 1,2,3,5
155°F/68"C Red
175°F/79°C Yellow
200"F/93°C Green
286"F/141"C Blue
NPT 135°F/57°C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)*
Figure 9
155°F/68°C Red
175"F/79°C Yellow
200"F/93"C Green
135°F/57°C Orange
1,2, 3, 4,5
I I I I 1,2,4,5 I
Green
N/A
RECESSED
PENDENT
(TY3231)
Figure 10
155°F/68"C Red
175°F/79"C Yellow
200°F/93"C
8.0
3/4',
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135"F/57"C Orange
1,2,3,4,5,6, 7
1,2,5 155°F/68°C Red
175°F/79°C Yellow
200"F/93"C Green
286°F/141"C Blue
NPT RECESSED
PENDENT
(TY4231)"
Figure 11
135"F/57"C Green
1,2,4,5 N/A
155"F/68"C Orange
175°F/79°C Red
200°F/93°C Yellow
RECESSED
PENDENT
(TY4231)**
Figure 12
135"F/57°C Orange
1,2, 3,4,5 N/A 155°F/68°C Red
175°F/79°C Yellow
200°F/93"C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-4284444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 10 TFPI7I
SPRINKLER FINISH
K TYPE NATURAL I CHROME WHITE LEAD
BRASS PLATED
I
POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2' RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/40
RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2" 175 PSI (12,1 BAR) RECESSED PENDENT NPT (TY323) (SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (1Y4131)
3/4,, RECESSED PENDENT NPT (TY4231) N/A
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
174
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 1350F/570C to 3/32
inch (2,4 mm) for the 2860F/141°C
temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TFPI7I
2-7/8' DIA.
5/8±1/4' (73,0 mm) 3/4(19,1 mm)
- (15,9±6,4 mm) - 2-1/4' DIA. 1/4' (6,4 mm)
PLATE SPRINKLE4R*1
FITTING
1/8'
FACE OF MOUNTING
(3,2 mm)
MOUNTN
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)I
TY-FRB 13/16"(20,6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8' DIA. -
5/8±1/4'
(73,0 mm) I 3/4(19,1 mm)
(15,916,4 mm)
.,_...... 2-1/4 DIA. I 1/4(6,4 mm) I
FACE OF MOUNTING
I PLATE I FITTING
118' I
SPRINKLER I
/
(3,2 mm)
MOUNTING/ f
f
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 3/4(19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Page 7 of 10
- 2-7/8' DIA.
(73,0 mm) 1/2±1/8' I 1/2" (12,7 mm)
1 (12,7±3,2 mm) 2-1/4' DIA. 1/4"(6,4 mm) I
SPRINKLEqR PLATE I FACE OF
572
mm) MOUNTING I
FITTING / 1/8
(32mm)
SURFAC
6'(33,3 mm)
MOUNTIN
CLOSURE SERIES
TY-FRB 1-1/16"(27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. -
1/2±1/8' I (73,0 mm) 1/2"(12,7 mm) r (12,7±3,2 mm) 2-1/4" DIA. I 1/4" (6,4 mm) I
I FACE OF (572 mm) MOUNTING I SPRINKLEqR PLATE I FITTING
1/8"
±
32mm)
MOUNTIN
SURFACESERIES
1-1/4" (31.8 mm) I CLOSURE TYFRB 1" (25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
0
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
El
Page 8 of 10
- 2-7/8' DIA. -
5/8±1/4" (73,0 mm) I 3/4"(19,1 mm)
- (15.9±6.4 mm) 2-1/4" DIA. 1/4" (6,4 mm) I
I FACE OF mm) MOUNTING SPRINKLER PLATE
I
FITTING
(3,2mm)
-1/8"
MOUNTING,,,////
I I
f SURFACE
SERIES 1-1/4"(31,8 mm) I CLOSURE TYFRB 3/4"(19,1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8"DIA.
5/8±1/4" (73.0 mm) 3/4"(19,1 mm)
(15.9±6,4 mm) 2-1/4" DIA. .__.I 1/4" (6,4 mm)
FACE OF (57,2 mm)
FITTING
M
SR
I
MO
PLATE PLAI
UNTING
MOUNTING I
SURFACE
CLOSURE SERIES 1.5/16" (33,3 mm)
TY-FRB 13/16"(20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
TFPI7I
2-7/8' DIA. -
1/2±1/8" I (73.0 mm) 1/2(12.7 mm) r (12,7±3,2 mm) 2.1/4" DIA. 1/4" (6,4 mm)
I SPRINKLER PLATE
FACE OF 57.2 mm)
]
MOUNTING I
I FITTING
1/8"
(/#mm) I \ MOUNTING
SURFACE
SERIES 1-1/4" (31.8 mm) CLOSURE TY-FRB 1"(25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. -
1/2±1/8" (73.0 mm) 1/2"(12,7 mm)
r (12,7±3,2 mm) 2.1/4" DIA. 1/4" (6.4 mm)
FACE OF
I
(57,2 mm) MOUNTING
I SPRINKLER PLATE
I FITTING 1/8" / L32 m)
I \
MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm
TYFRB 1-1/16"(27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
I
0
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI7I Page 9 of 10
EI
P/N 57-XXX-X-XXX
MODEL/SIN
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2"NPT) TY2131
341 4.2K PENDENT (1/2"NPT) TY2231
370 5.6K UPRIGHT (1/2"NPT) TY3131
371 5.6K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (3/4°NPT) TY4131
391 8.0K PENDENT (3/4°NPT) TY4231
I I L 135
SPRINKLER I
155
175
200
286
RATING
1 NATURAL BRASS 155F/68°C
4 WHITE POLYESTER 175°F179°C
3 WHITE (RAL9010)* 200°F/93°C
9 CHROME PLATED 286F/141*C
7 LEAD COATED
* Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001. . In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
Page 10 of 10 TFPI 71
I
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
IIUUI.LU / cI1UUIU
Fully Listed and FM Approved Sprinkler Pipe
When you specify Schedule-1O/Schedule-40 sprinkler pipe you get a UL listed and FM approved product. Although these
products do not require separate approvals, Schedule-1O/Schedule-40 gives you the extra quality assurance you demand.
Our Sch-10 (l"- 8") pipe and Sch-40 (1"- 2k") pipe have passed the same thorough lab testing as our other listed pipe
products, and receive periodic mill inspections from both UL and FM agents to ensure consistent quality.
Meets "Buy American" requirement
and is available through distributors in
the USA, Canada and Mexico.
Sch-40 Specifications
NPS Nominal I.D. Wt. Wt. (H20 Filled) Pcsl WI/Lilt (21') WI/Lift (24') WI/lift (25')
In; mm In; mm Lbs/Ft; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
ill 1.049 1.680 2.05 70 2,470 2,822 2,940
25 26.6 2.5 3.05 70 1,120 1,280 1,334
1V4 1.380 2.270 2.93 51 2,431 2,778 2,894
32 35.1 4.36 4.36 51 1,103 1,260 1,313
1½' 1.610 2.720 3.61 44 2,513 2,872 2,992
40 40.9 4.0 5.37 44 1,140 1,303 1,357
2' 2.067 3.650 5.13 30 2,300 2,628 2,738
50 52.5 5.4 7.63 30 1,043 1,192 1,242
21/2" 2.469 5.790 7.86 19 2,310 2,640 2,750
65 62.7 8.6 11.73 19 1,048 1,197 1,247
Sch40 Specifications
NPS Nominal I.D. WI. WI. (H20 Filled) Pcs/ WI/Lilt (21') WI/Lift (24') WI/Lilt (251)
In; mm in; mm Lbs/Ft; Kg/rn Lbs/Fl; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1' 1.097 1.400 1.81 91 2,675 3,053 3,185
25 279 2.1 2.70 91 1,213 1,385 1,445
11/4' 1.442 1.810 2.52 61 2,319 2,664 2,760
32 36.6 2.7 3.75 61 1,052 1,208 1,252
11/2" 1.682 2.080 3.04 61 2,664 3,045 3,172
40 42.7 3.1 4.52 61 1,208 1,381 1,439
2° 2.157 2.640 4.22 37 2,051 2,344 2,442
50 54.8 3.9 6.28 37 930 1,063 1,108
21/2' 2.635 3.530 5.89 30 2,224 2,542 2,648
65 66.9 5.3 8.77 30 1,009 1,153 1,201
3.260 4.330 7.94 19 1,728 1,975 2,057
80 82.8 6.4 11.82 19 784 896 933
4.260 5.610 11.78 19 2,238 2,558 2,665
90 108.2 8.3 17.53 19 1,015 1,160 1,209
5.295 7.77 17.33 10 1,632 1,865 1,943
125 134.5 11.56 25.80 10 740 846 881
6.357 9.290 23.03 10 1,951 2,230 2,322
150 161.5 13.8 34.27 10 885 1,012 1,053
8' 8.249 16.490 40.15 7 2,424 2,770 2,885
200 209.5 24.5 59.75 7 1,100 1,256 1,309
Schedule- lO/Schedule-40 product can be
"hot-dip" galvanized to meet FM
requirements for dry systems in
accordance with the zinc coating
specifications of ASTM A-123.
Superior Coating
Our advanced formula mill coating of-
fers a clean, durable surface. It is also
paint-ready for custom color applications
without special preparation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial For-
mula, "ABF". In scientific laboratory
•
test, ABS proved to have superior resis-
tance to microbial colonization of pipe
walls, thereby delaying or possibly pre-
venting the onset of Microbio logically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
Schedule- 10/S chedule-40 pipe are in
compliance with the following:
ASTM A-135, and NFPA 13. Both pipe
products have a working pressure rating
of 300 psi maximum and also meet the
stringent requirement for the following
tests:
Welded Outlets
Hydrostatic Pressure
Side Wall Rupture
Vibration Test
tLICQ/Flow Control
@ <~> 9
Listed Approved Listed
16100 S. Lathrop • Harvey, IL 60426 '11350 Norcom Rd. • Philadelphia, PA 19154 llied TUBE & CONDUIT 2525 N. 27 th Ave. • Phoenix, AZ 85009
Customer Service:
(800) 882-5543
Fax 708-339-1806
S5 -3
1 .
v; B
EJA
Outside Head
II
AiLBtar Flu Preduds Olvivinu uS Anvi' ternntIant
I
Ductile Iron Submittal Sheet
Nominal Anvil Item Universal Dimensions Style Approx.
Size Number Dumber wt. Each
A B C
In (tam) ,. '' '/ i (iñn) In (ninj ' 'In (m) 5.. . ct6s Ikg)
1 x ½ 840600001 DBUSH31 0.15 0.25 1.42 Outside 0.22
25 15 . 7903 .35 34.O
1 x 840600019 DBUSH32 0.75 0.25 1.42 Outside 0.11
25 .0 20 !9.0 63 36.06
11/4 a I . 840600027 DBUSH43 0.80 0.28 1.16 Outside 0.28
7.11 0.13
1%x I 840600035 DBLISH53 0.83 0.31 2.00 Outside 0.45
,W25 . 21.08 7.814 50fl0
1½x 1% 840600043 DBUSH54 0.83 0.31 2.00 Outside 0.30
4032. 2105 1574
2 x 840600050 DBUSII63 0.88 0.41 1.95 Inside 0.67
70414 49.53 0.30
2x 11,14 840600068 DBUSU64 . 0.88 0.34 2.48 Outside 0.73
5799 033
2x 11h 840600016 DBUSH65 0.88 0.34 2.48 Outside 0.61
SO:s 40 22.15 429
B
t A
Inside Head
Ductile iron threaded fittings are UL & ULC listed & Dimensions conform to ASME 816.3 Class 150.
Factory Mutual Approved For 500 psi service. Threads are NPT per ANSI/ASME 131.20.1.
Ductile iron per ASTM A536 Class 65-4512.. APPROVED
ForListing/Approval
NOTICE: Ductile iron listings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile
iron listings should be tightened three turns beyond hand tight, but no more than Four turns.
details contact your
AflulIStarTu Representative.
Project:
[Date: I Phone:
[Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
SPF Cost & Ductile Iron Fittings For the latest UL/IJLC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06.0020 go to www.anvilstar.com or contact your local AnvilStar representative
AiLtr
- Fire Products Division at Anmi' ivtniniianui
RNVIL Ductile Iron Submittal Sheet
I Al"s I
Anvil Item Universal tau M k' or tag In (mm) Approx. Size Number (lumbar .Pressure Mt. Eoch
A B
11n 4mm),. ' t?51(kP&h im) In(m Lbs ?k)
1 840000004 DB90033 500 1.50 1.50 0.62
3450 38W 33.10 0.28
1% 840000012 0890044 500 . 1.75 1.75 0.90
1½ 840000020 0890055 500 1.94 1.94 . 1.20
3450 49.216 0S6
2 840000038 1 0890066 500 2.25 2.25 1.85
50 3650 5:tJ5 51)5 034
Ductile iron threaded fittings are UL & ULC listed & Dimensions conform to.ASME B16.3 Class 150.
Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B1.20. 1. APPROVED Ductile iron per ASIM A536 Class 65-45-12. For Listing /Approval
details contact your NOTICE: Ductile iron Fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile 'AnvilStar'14 Representative iron fittingi should be tightened three turns beyond band tight, but no more than four turns.
_
Project: . .
Date: Phone:
Architect! Engineer:
Contractor: .
Address:
Notes 1: . .
4NWotes 2:
-
SPF Cast & Ductile Iron Fittings For the latest UIJULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06.0010 go to www.anvilstar.com or contact your local AnvilStar representative ,, .................
91
VIL Ductile Iron Submittal Sheet
Nominal Anvil Item Universal Max. Dimensions
Working
Approx.
Size Number Number ____ ________ __________ 'Pressure w. Each
A B C _______________
PSUkPoi1 In(mj ih(m'2i 1nim) Lbsc(kg)ks
1 x I z 1% 840004238 01334 500 1.61 1.67 1.58 0.98
25x25;'32 5450 42M 441 40.13 0A4
1 x 1 x 1½ 840001246 01335 500 1.80 1.80 1.65 1.16
1'Axlxl½ 840004295 DT435 500 1.88 1.80 1.82 1.42
2.5 340 4i.7S 4S.1 4a.2
1114 1114x11h 840004337 01445 500 1.88 1.88 1.82 1.45
____ 3430 41•75 4175
1',4x1'ix2 840004345 01446 500 2.10 2.10 1.90 1.15
____ 3450 . 5334 53.34 43.2d 019
1½x1½z2 840004436 01546 500 2.16 2.10 2.02 1.90 4o3?if co ____ 345n 54ju 53.34 51.30 083
1½ x 1½x 2 840004485 D1556 500 2.16 2.16 2.02 1.98
413x48';SO 34c0 S.I.S. 54.86 31.30 010
A 1 B
-.
Ductile iron threaded Fittings are UL & ULC listed & Dimensions conform to ASME B16.3 Class 150.
Factory Mutual Approved For 500 psi service. Threads are NPT per ANSI/ASME B1.20.1. Ductile iron per ASTM A536 Class 654 APPROVED512. For Linting/Approval
details Contact your NOTICE: Ductile iron livings have higher tensile strength than that oi steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile AnvilStarlm Representative. iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
Project:
Date: Phone:
Architect / Engineer: . . . .
Contractor: .
Address:
Notes 1:
Notes 2:
SPF Cast & Ductile Iron Fittings For the latest UL'ULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.060015 go to www.anvilstar.com or contact your local AnvilStar representative .
Nominal Anvil Item Universal Max. Working Dimensions Approx.
Size Number Number Pressure WI. Each
A B
'In(miiiP'4 jJ3 jPSIikPo)J tn (mA) F*In(ntrn) *1 040
840003164 01333 500 1.50 1.50 0.85
5 . - 3450 3&!0 18.I0 0.39
11,14 840003172 01444 500 1.75 1.75 1.22
44.45 0.55
1½ 840003180 01555 500 1.94 . 1.94 1.55
41) 3430 49.21 4 f. 21 0.70
2 840003198 01666 500 2.25 2.25 2.45
B
A -'-h-- A
ALBtr
Fire Prnducls Diinan d jwIr Inleniatbuvi
Ductile Iron Submittal sheet
Ductile iron threaded fittings are UL & UIC Listed & Dimensions conform to ASME B 16.3 Class 150. ® (j
Factory Mutual Approved For 500 psi service. Threads are NPT per ANSI/ASME B1.20.1. APPROVED Ductile iron per ASTM A536 Class 65-45.12. . For Listing /Approval
details contact your NOTICE: Ductile iron Fittings have higher terssile.strength 1hon that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile AnvilStarTm Representative. iron Fittings should be tightened three turns beyond hand tight, but no more than tour turns.
Project: .
Date: Phone:
Architect I Engineer: .
Contractor:
Address:
Notes 1:
Notes 2:
SPF Cast & Ductile Iron Fittings For, the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.06-0013 go to www.anvilstar.com or contact your local AnvilStar representative
Ductile Iron Submittal Sheet
. Nominal Nominal Anvil Item 0nivecsel ft . ° Dimensions lsetktng _______________________
A PP lOX.
WI.
. Anvil lies . Untversol titus. n
Working
tniun.tons Approx.
Size Number tivinber Each Size Wombat Number Pressure - Each B A I
In. (itim) ) In. (mm)In. (min) L6s.(kg) In. (mm) In.PSI PSI
() In. (mm) (mm) In. (aim) Lbs.(kg)
84000i°6 UTT T Tö T I I' 1 T7
84O0O1O4
80004428 Db4 500 165 153 lEO
kpl
$;96
ii T
lxi
17 1 xl 4 40flO443o Y6 k
- 84000121i 0131 T& 011 i7lkxt 84000d444 t 5i 500 141 141 I lô 115
1 xl X/i 840004226 01332 TT T 11W 1½e 1½x ¼ 840004451 b1W 500 1.52 1.52 1.15 1.24
It. Ix l'i 840004236 01.334 iir iii TT TF T1 I v la I 840004469 11 500 103 105 ISO T.30
1 a It 11 ' 840004246 ir -r TF 11 TW fIA,TT51xI4 840004477 01554 500 182 TT 'TT
______
Tsax1 t''z 840004253 1$T1T -'!iiö TW T3r 012 1'u1"x2 840004485 01556 3iii r1r ir -ir iii
1¼x 1 x¼ 840004261 01432 5 T13 11T 1T1 T 2x 1 :e2 840004495 11 3 500 2.25 2.02 2.25 2.15
1'/vxiul 840004219 1W 500 TW• 'TF 11W T 2x1¼x2 840004501 500 11W 2.25 2.30 .5 1 ,l I I 50 _5_1 '471__...._:_ i__ lViuixl% 840004287 0144' 500 1.75 1.67 1.75 1.08 2x1½u½ 840004519 116 T 11W 1.41 1.88 1.50 3 a ___ 'v3 4 _________.___ it, ul u lth 840004295 01435 500 1.88 1.80 11T iTT 2u1'.x¼ 840004527 i'2 500 1.60 1.52 1.91 -F6-2-
IN;lt/4x½ P ( IS . 55 10 11
840004303 111T 1U Tt lIT 131 ir 2x1½x1 ________ 840004535 iöi' 1.73 1.65 2.02 1.64
- .a4 3111.04 s - 3450 IL..! ___ 1'/4x P/va ¼ 840004311 01442 500 1.45 1.45 1.62 02' 2x l 'ill u 11/ 040004543 01654 500 1.90 1.82 2.10 1.80
i'A x11/ix1 !!!__.L_.P' _450.Iji_L_!L..4L... 1 840004329 01443 500 1.58 1.58 1.61 03 2x1½x1112 840004550 D1655 500 2.02. 1.94 2.16 2.00 t I '. 0 L 5 4 r I 4' .122... L _8_ ..ii..... 1¼x11/4 x1½ 840004331 D1445. 500 1.88 111 lIT i1' 2x1½u2 _________ 840004568 01656 500 2.25 2.16 2.35 2.35 c) c 3 16-22 A 05 0 !_t._ L2 i .!z. Q.__ li/i x 1114 x 2 840004345 - D1446 500 2.10 2.10 1I iT7 2 /2 2 x x 840004576 TT 500 1.49 1.88 1.60
5
"J"
_________ _•_•,j_ I ) .15 f r5 Jj ....L........... ....LL i_ 840004352 Y-531 500 1.41 Tt TT I3 2x2x¼ .i L1½x1x½ 840004584 1T 500 1.60 1.97 1.68 11 L 0 x 1 a ¼ 840004360 01532 500 1.52 1.37 T7 11W 2 a 2 xl 840004592 D1663 500
r14
1.13 2.02 1.85
____JL J. iL a 101 840004376 01533 500 1.65 1.50 111 1117 2!L114 2e2 x P/i 840004600 1T1 500 1.90 2.10 2.04
1 A.. - 1½ xl xl ½ 440004386 01534 500 1.82 1.61 1.88 '1I4 2 x 2 x ½ 840004618 01665 500 2.02 2.02 2.16 2.18
42L, 'C__'s j,.._ 412 Z_ ..- .....i 1½ a 1 a 1½ 840004394 01535 500 1.94 11 11T TT 2 a 2 a . 01667 500 2.60 2.60 2.39 3.61
- ;'s 9 11P Js 1.' £r. 50__I__ e ....sa41 ......2.. ..1_.2.. .............2. .......!.. 1½ x1114 a ½ 840004402 01541 500 1.41 lIT 1.66 T' 2½x 2x ¼ . 11Th 500 1.14 1.60 2.32 2.28
4-0,13".1 _C
__ - ,z za t -fl-- 1½x1'/,x¼ 840004410 01542 3ö 1.52 115 1.75 1 1.15
________ _______ •Q_iR1 _jj _________________________________
J;i
A-N-01L.Starl-
Fire Pcodur.ts 0iv1aisn ul .Anvil' tnlu;national
Ductile iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B 16.3 Class 150. UL
Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME 81.20.1. APPROVED Ductile iron per ASTM A536 Class 65-45-1 2. For Listing /Approval
NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile details contact your
AnviIStar 4 Representative. iron Fittings should be tightened three turns beyond hand tight, but no more than Four turns.
Project:
Date: Phone:
Architect / Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
.
SPF Cast & Ductile Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule, .g REV. 03.03.060014 go to www.anvilstar.com or contact your local AnviiStar represntative
A -riv- 11, L Btr"
Fire Products Di in ni Anvil' !eterimuurgl
ENVIL Ductile Iron Submittal Sheet
T41 -•"
Nominal Anvil Item Universal Max. Working Dimensions Approx.
Size Number Number Pressure A WI. Each
1 x•½ 840010155 D8C031 500 1.69 0.39
3450 482 0.18
1 x 840010163 08(032 500 1.69 0.53
3458 12.92 8.24
Ductile iron threaded fittings are UL & UIC Listed & Dimensions conform to ASME B1 6.3 Class 150. ® Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B1.20-1.
Ductile iron per ASTM A536 Class 6545i 2. APPROVED
ForListing/Approva
NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile details contact your
AnviIStarTM Representative.
iron fittings should be tightened three turns beyond hand tight, but no more than four turns.
SPF Cast & Ductile Iron Fittings For the latest UL/ULC Listed and FM Approved pressure ratings, versus pipe schedule,
xcv. 03.03.06.0017 • go to www.anvilstar.com or contact your local AnvilStar representative
AtLStr Fire Fdiicts Di,-Aeon at Asi'Al' lflternatjesal
Submittal Sheet Ductile Iron
tiominal Anvil Item Universal Max.
Working Dimensions Approx.
Sire tiumber (lumber Pressure _________ WI. Each
lit (flint) PSI (kPa) In (mat) In (mm) Lb.s (kg)
1x½ 840001036 0890031 500 1.26 1.36 0.44
:1St 15 34C 53.30 36.56 020
1x164 840001044 0890032 500 1.37 1.45 0.52
3.153 34.i 55.83 01 4
11Ax½ 840001051 D890041 500 1.34 1.53 0.64
3450 5403 11
1'/ix.'u 840001069 0890042 500 1.45 1.62 0.72
4S0 3353 Li4 333
1x1 840001017 0890043 500 1.58 1.61 0.75
.0 X 75 .5650 ;013.
1½x1 840001085 D890053 500 1.65 . 1.80 0.92
40x25 . 3650 4191 45.13 062
1'hx .840001093 0890054 500 1.82 1.88 1.08
40 X V, 3450 46.2.7 43.15 0.69
2x½ - 840001101 0890061 500 1.49 1.88 . 1.08
5815 .1.611 3U4 6?]!i 8.10
2x~A 840001119 0890062 500 1.60 1.91 1.24
50 20 6064 5003 1156
2x1 840001127 D890063 500 1.73 2.02 1.40
3450 6:194 SUC 0.61
2x1',4 840001135 0090064 500 1.90 2.10 1.52
53.34 0.10
2x1½ 840001143 0890065 500 1 2.02 2.16 1.65
Ductile iron threaded fittings are UL & ULC Listed & Dimensions conform to ASME B16.3 Class 150. UL -Ougq
Factory Mutual Approved for 500 psi service. Threads are NPT per ANSI/ASME B 1.20. 1.
Ductile iron per ASTM A536 Class 65.45.12. APPROVED
For Listing /Approval
details contact your NOTICE: Ductile iron fittings have higher tensile strength than that of steel pipe. Therefore, over tightening can cause damage to pipe threads which may cause leakage. Ductile AnvilstarrnP.epresontative. iron Fittings should be tightened three turns beyond hand tight, but no more than Four turns.
31
Project:
Date: Phone:
Architect.! Engineer:
Contractor:
Address:
Notes 1:
Notes 2:
SPF Cast & Ductile Iron Fittings For the latest IJLIULC Listed and FM Approved pressure ratings, versus pipe schedule,
REV. 03.03.060012 go to www.anvilstar.com or contact your local AnvilStar representative . ' J
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
310
RING RESTRAINER
Restraint
SIZE - One size fits 3/4 thi-u 2 inch .4FCON#300 Ring Hanger.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTINGS -
C 203-EX 2551
Listed only for use with AFON #300 Ring Hanger.
FUNCTION - To restrain movement of sprinkler pipe toward the knurl nut of the
ring hanger. To prevent upward movement of pipe that supplies a pendent
sprinkler below the ceiling.
INSTALLATION - Per NFPA 13 and CPVC manufacturers instructions
on steel. CPVC. or copper pipe.
Snap into locking position on swivel nut of AFCON 4300 Ring Hanger.
SPECIAL NOTE: When installing on CPVC sprinkler ssten1 pipe:
'erily that all assembly colnpoiients are. cleaned of any surface oil.
FEATURES -
°' Listed only for use with .4FCON #300 Ring Hanger.
ORDERING - Part # and size.
Specific APCOfs products are eselusinelv designed to be compatible ONLY with other AFCOtVproducts including parts and ftstetiers. resulting in a listed sway bract, retraitInr or hanger assembly.
lIe advised the following warrant) restriction will apply. DlSCL% IMII( . ,IPCI)N will NOT warrant against sire lilurc of its products wlsun uscd tit contbinautort with ctbce products, parts or systems
stot mrnufaclurcd or sold by AttOV. YCON shall NOT be liable under my circuatsaraces wltniaor for attn direct at indirect. ntcidetttal or consequential dnfltndcs Ol any kind. titcltidtti bet not
limited in loss uI business or pruflt, when nati.AFCOM products Im a been. or are used.
IMPERIAL MAX REC.
LOAD LBS.
METRIC
PIPE I ROD PIPE RO2
1/2 318 400 I to
3/4 318 400 20f 10
1 318 400 25 l.....J!...
1114 318 400 32 10
1 1/2 318 400 40 In
2 318 400 50 ii)
2112 318 600 65 itl
3 3/8 600 so to
31/2 318 600
- 10
4 318 1000 100 in
5 1/2 1 125 12
6 112 250 ISO 12
8 112 1250 200 12
Order Port 1300m
Note: 1/2 Ring Hanger nOL <FM' approved
A Inch pipe
5 thru 8 Inch pipe
I 1
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
300
RING HANGER
Ll
314 thru 4 Inch pipe
LISTED FOR STEELICPVC
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mit. Galvanized to G-90 spec.
LISTING/APPROVAL -
c®IJs 203-EX 2551
Approval guide - Pipe Hangers
OSHPD OPA-0601 See Website.
CONFORMS WITH: Federal Specification WW-H-17l (Type 10,
Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10).
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - Pipe hanger component for use on steel.. CPVC or
copper piping.
INSTALLATION.- Per NFPA 13. 13R. 130 and
CPVC manufacturers instructions.
SPECt,LNOTI: When installing an CPVC sprinkler system
:cl.ify that all assembly components are cleaned of any surface oil.
FEATURES -
Sired and listed exclusively for use with 9310 Surge Restrainer
Band edge is offset for EASY pipe insertion.
Custom fit swivel nut for better retention in ring body.
Full length knurl on swivel nut for better Qrip.
ORDERING - Part #. pipe size.
5/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www.Afcon.org
ALL THREADED ROD 10' -0' LENGTHS
ROD
SIZE
MAX. REC. LOAD LBS.
FOR SERVICE TEMP.
650F 75OF
.1/4
3/8
240
610
215
540
1/2 1130 ioib
5/6 1810 1610
3/4 2710 2420
718 3770 . 3360
4960 4420
11/4 8000 7140
11/2 11630 10370
NOTE; maximum Temperature: 750F
SIZE - 1/4 thru I 1/2 inch rod in .1.0'- 0" lengths.
MATERIAL - Carbon Steel.
FINISH - Plain, E.G., H.D.G. and S.S.
ORDERING - Part l!. rod. diameter and finish.
3/00