HomeMy WebLinkAbout1911 CALLE BARCELONA; 157; AS110080; Permit10/27/2020 AS110080 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: ASII0080
1911 CALLE 4H5 1
Job Address:
BARCELONA
Permit Type: SPRINK
Parcel No: 2550120400
Lot #: 0
Status: ISSUED
Applied 5/19/2011
Approved; 5/19/2011
Reference No.: Issued: 5/19/2011
PC #: Inspector:
Project Title WHITE HOUSE/BLACK MARKET T.I. FIRE SPRINKLER PLAN CHECK
& INSPECTIONS
Applicant:
A & D FIRE SPRINKLERS, INC.
2ND FLOOR
11465 WOODSIDE AVE
SANTEE, CA 92071
619-448-1962
Owner:
FOURTH QUARTER PROPERTIES XXX L L C
C/O THOMAS TROPEA
45 ANSLEY DR
NEWNANGA
Fees ($) .Add'I Fees ($) Total ($) Balance ($)
130 0 - .130 0
1/1
A51(oc)SO
FIRE SPRINKLERS INC.
rTE HOUSE BLACK MARKET
1911 CALLE BARCELONA
F3
: BLDG
SAN DIEGO, CA
Install Fire Service
FIRE .SPRINKLER SUBMITTAL
••. I'
MANUFACTURE'S DATA SHEETS
Materials of equal design: utility, and performance may be substituted for submitted materials so as to avoid delays in the
qonstrudtion schedule and shall be deemed accepted by the Purchaser.
r
:
I tqt0/
Fire & Building
Products
. I j
Technical Sery lies: Tel (800) 381-931? Fax (800) 791-5500
A®
Customer Service/Sales:
Tel: (414) 570-5000 / (800) 558-5236
Fax: (414) 570-5010/(800) 877-1295
Series flFlI — 56 K-factor
"Royal Flus -1 kh If " Pendent Concealed Sprinklers
Quick & Stafldard Response, Standard Coverage
a
General
Description
The )Series RFII Quick Response
(3 nm bU!b) & Staçdard Resp9nef(5
thmbulb) 5.6 K-F4ctor, "Royal Flush
II" Concealed Pehdent Sprinklers are
decôratiye sprinkle-s featuiing a flat
cover plate designed to conceal the
spnnkler. It lithe best choice for archi-
tecturaHji sensitive areas such ashotel
lobbies office buildings, churthes,
and reaurants.
,' \
Each uhit inqludesia Cover Plate As-
sernblthat d.onceáls.the sprinkler op-
.eratingomponents above the ceiling.
The separable two-piece design Of the
Cove! Plateiand Sipport Cup Assem-
blies állóws. instalItionof the sprin-
klèrs ind,prbssurb testing of the fire
piotedtion system prior jo installation
of ia stispended cçiling or appiicakioh
of the finish. coating ito a11xed ceiling.
They also permif erpoval of us-
perided ceiling panels :o access to
building service. e'uipmèjit iitiout
having to first shut dowri the pro-
tection system and r2 've sprinklers.
Also, the separable-..two-ike design
of the the Sprinkler provides for .1/2
inch (12,7 mm) of vèrtialadjustment,
to reduce the accu'racy to. which .'the
length of fixed pipedrop to The sp'rin-
klers rnust.be cut.
The Series RFll; Sprinklers' are
shipped with a Disposable Protective
IMPORTANT. IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or; its compo-
nents and cause the sprinkler to fall
:to operate in a fire situation oica use
it to operate prematurely,
%Page
Cap. The Protective Cap is temporarily
removed for installation, and then it
can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against the
Protective Cap. When the ceiling in-
stallation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
As an option, the Series RFll Standard
Response (5 mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers may be
fitted with a silicone Air and Dust Seal
(Ref. Fig. 5). The Air and Dust Seal is
intended for sensitive areas where it is
desirable to stop air and dust travel
through the cover plate from the area
above the ceiling.
WARNINGS
The Series RFll Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3551 (5mm bulb) & TY3531 (3 mm
bulb): maximum 175 psi (12,1 bar) by
UL, C-UL, FM, LPCB and NYC.
TY3504 (5 mm bulb)& TY3505 (3 mm
bulb): maximum 250 psi (17,3 bar) by
JULY, 2004
UL, C-UL, and NYC Maximum 175
psi (12,1 bar) by -FM.
Technical
Data
Approvals for Series RFll
UL and C-UL Listed. FM Approved.
NYC under MEA 353-01-E. LPCB (Ref.
No. 094a/09 for TY3551 & 094a/10 for
TY3531) Approved.
The approvals apply only to the serv-
ice conditions indicated in the Design
Criteria section and maximum pres-
sure ratings indicated in the
Model/Sprinkler Identification Num-
bers section.
Approvals for Air & Dust Seal
(Part #10908100)
UL and C-UL Listed for use with the
RFIl (TY3551 & TY3504) Standard Re-
sponse Concealed Sprinkler.
Temperature Ratings
155F/68C Sprinkler - 135F/57C Plate
200F/93C Sprinkler - 165F/74C Plate
Discharge Coefiient
K = 5.6GPM/psi / (80,6 LPM/bar1"2)
Adjustment
1/2 inch (12,7 mm)
Finishes
Cover Plate: Chrome Plated, Brass
Plated, or White Painted (Custom paint
matches and colors other than white
are available on request.)
TFPI8I
Page 2 of 4 TFPIBI
fl
1/2 NPT SEALING
ASSEMBLY
FRAME
CAP
SUPPORT
CUP WITH BULB
ROLL FORMED
THREADS
COMPRESSION
SCREW
GUIDE
PINS (2)
= DEFLECTOR I (DROPPED
DEFLECTOR POSITION)
SPRINKLER/SUPPORT CUP
I
ASSEMBLY
I
THREAD INTO JJ TAINER
SUPPORTCUP WITH THREAD
UNTIL MOUNTING MPLES
SURFACE IS
FLUSH WITH LEJECTION
CEILING RING
SOLDER 1
'-,
COVER
TABS (3) COVER PLATE/RETAINER PLATE ASSEMBLY
FIGURE 1
SERIES RFII CONCEALED SPRINKLER
ASSEMBLY
PhysicalCharaçteristics
Frame .............Bronze
Support Cup . Chrome Plated Steel
Guide Pins. . . Stainless Steel
Deflector : ..........Bronze
Compressioh . Brass
Bulb . . . '. . . ; . '. Glass
Cap .....'Bronze or Copper
Sealing Assembly: . .... . . •i.
Beryiltuth NickelW1T&lon*
Cover Jate.,......... h. Brass
Retainer .. .. .... . .. . Brass
EjectIopSpçIng Stainless Steel
PatentS,
, u.S.A..34'014,388
''••. Operation
Whenposed to Heat from a fire; the
CovetPJate, which, is nomally s01-
deedthe'Retaine at three points,
falls, aiay to expose the Sprinkler M-
sembAt this point the Deflector sup-
portöØ;y the Guide Pins dropsdOwn
to,itsqp'erational position.:
The t'as Bulb contains: a fluid that
expands when exposed to heat. When
the, rafed -temperature is reached, the
flu! d,Wcparids 'sufficiently to shatter the
glass Bulb, activating the sprinkler and
allowing watei to flow.
Design I Criteria
The 9F11 (TY3551 & TY504), 5 mm
B'ulb Type, Concealed Pendent Sprin-
klersare UL and C-UL Listed as stand-
ard response - standardspray sprin-
klers for use in accordance with the
current NFPAstandard. They are FM
Approved as standard: response -
standard spray sprinklers for use in
aoàordanpe with the current FM Loss
Prevention Data Sheets.
The RFII (TY3531 & TY3505) 3 mm
Bulb Type, Concealed Pendent Sprin-
klers are UL and C-UL Listed as quick
response - standard spray Sprinklers
for vse in accordance with the current
NFPA standard. They are: FM Ap-
proved as standard response - stand-
ard spray sprinklers for use in accord-
ance with the current FM Loss
Rrevention Data Sheets.
The Series • RFII Concealed Pendent
Sprinklers are only listed and ap-
proved with the Series RFll Concealed
Cover Plates having a metallic or white
painted finish.
The Series RFII must not be used in
applications where the air pressure
- above the ceiling is greater than that
below. Down drafts through the Sup-
port Cup could delay sprinkler opera-
tion in a fire situation. -'
Installation
The Series RFII must be installed in
accordance with the following instruc-
tions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 155°F/680C and 3/32
inch (2,4 mm) for The 200°F/930C tem-
perature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in the Sprinkler
Assembly by under- or over-tightening
the Sprinkler/Support Cup Assembly.
Readjust the position of the sprinkler
fitting to suit.
Step 1. The sprinkler must only be
installed in the pendent position and
with the centerline of the sprinkler per-
pendicular to the mounting surface.
Step 2. Remove the Protective Cap.
Step 3. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 4. Wrench tighten the sprinkler
using only the RFII Sprinkler Wrench
(Ref. Figure 3). The RFII Sprinkler
Wrench is to be applied to the Sprin-
kler as shown in Figure 3.
Step 5. Replace the Protective Cap
(Ref. Figure 4) by pushing it upwards
until it bottoms out against the Support
Cup. The Protective Cap helps prevent
damage to the Deflector and Arms dur-
ing ceiling installation and/or during
application of the finish coating of the
ceiling. It may also be used to locate
the center of the clearance hole by
gently pushing the ceiling material up
against the center point of the Protec-
tive Cap.
NOTE
As long as the Protective Cap remains
in place, the system is considered to
be "Out of Service'
* Registered Trademark of DuPont
TFPI8I . FACE OF - SPRINKLER
\ FITTING
SPRINKLER
SUPPORT CUP
ASSEMBLY
1/2" (12,7 mm)
THREADED D ADJUSTMENT:
FACE OF CEILINGj
RETAINING RING
MOUNTING
SURFACE
Page 3 of 4
CLEARANCE
HOLE
FIGURE 4
DISPOSABLE PROTECTIVE CAP
S
P
Step 6. After the ceiling has been com-
pleted with the 2-1/2 inch (63,5 mm)
diameter clearance hole and in prepa-
ration for installing the Cover Plate As-
sembly, remove and discard the Pro-
tective Cap, and verify that the
Deflector moves up and down freely. If
the Sprinkler has been damaged and
the Deflector does not move up and
down freely, replace the entire Sprin-
kler assembly. Do not attempt to mod-
ify or repair a damaged sprinkler.
Step 7. When installing an Air and
Dust Seal, refer to Figure 5, otherwise
proceed to Step 8. To attach the Air and
Dust Seal, verify the angle of the out-
side edge of the seal is oriented ac-
cording to Figure 5. Start the edge of
the Retainer in the grooved slot of the
Air and Dust Seal and continue around
the retainer until the entire Air and
Dust Seal is engaged.
NOTE
The Air and Dust Seal is only to be
installed on the periphery of the Re-
tainer.
Step 8. Screw on the Cover Plate/Re-
tainer Assembly until the Retainer -
Figure 2 (or Air and Dust Seal - Figure
5) contacts with the ceiling: Do not
continue to screw on the Cover
Plate/Retainer Assembly such that it
lifts a ceiling panel out-of its normal
position. If the Cover Plate/Retainer
Assembly cannot be engaged with the
Support Cup or the Cover Plate/Re-
tainer Assembly cannot be engaged
sufficiently to contact the ceiling, the
Sprinkler Fitting must be repositioned.
Care and
Maintenance
The Series RFII must be maintained
and serviced in accordance with the
following instructions:
NOTES
Absence of the Cover Plate Assembly
may delay sprinkler operation in a fire
situation.
H H
3/16" to 11/16" tMANUFACTURER DEFLECTOR COVER PLATE
(4,8 to 17,5 mm) - nnnrll e nrnrLJ
PRESET GAP IN DROPPED RETAINER
REFERENCE 3/32" (2,4 mm) POSITION ASSEMBLY
COVER PLATE: COVER PLATE
— nln.arren - IJIpIvI I fl
DIMENSION B. DIMENSION A
3-1/4" (82,6 mm) C: 2-3/8" to 2-5/8" (60,3 to 66,7 mm)
3/16" (48 mm) 0: 1-3/4" to 2-1/4" (44,5 to 57,2 mm)
FIGURE 2
SERIES RFII CONCEALED SPRINKLER
INSTALLATION DIMENSIONS
EiriIIiiT1
•,
: i Ii •: :
-
7/8" (23 mm)
SQUARE
ALIGN
ARROWS WITH
. FRAMEARMS
ACCEPTS o 2-- sockET
DRIVE
)
1' FIGURE
'RFII SPRINKLER WRENCH
•
Page 4 of 4 TFPIBI
0
When properly installed,' there. is a
nominal 3/32 inch (2,4 mm) Th:gap
between the lip of the Cover Platthnd
the ceiling, as shown in Figure 2his
air gap is necessary for prdpertopeLra
tion of the sprinkler. If the ceiling Is to
be repainted after the installation of
the Sprinkler, care must be ?xe()sed
to ensure that the new paint doesdvbT
seal off any of the air gap.
Factory painted Cover Platesi MUST
IOT be repaiñtid. They should b,re-
'.placed, if necessary, by factory
i: -painted units.
Do not pull the Cover Plate relative to
the Enclosure. Separation rnay result.
Before closing a fire protection sytem
main control valve for maifltehance
- work on the fire protection systethat
it controls, permission to shut down. the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced. .1
Automatic sprinklers must neveribe
painted, plated, coated or otheiw)se
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustio but
have not operated, should be replaced
if they cannot be bompletely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle br,ush.
Care must be exercised to avoid dam-
age to the sprinklers - beforejduring,
and after installation. Sprinklers:.dam-
aged by dropping, striking,: Wrench
twist/slippage, or the like, must be' re-
placed. Also, replace any sprinklr that
has a cracked bulb or that hà& lost
liquid from its bulb. (Ref. Installation
Section).
If a sprinkler must be removed; do not
reinstall it or a replacement Without
reinstalling the Cover Plate Assembly.
If a Cover Plate Assembly becomes
dislodged during service, replace it im-
mediately. ; A.
The owner is :.esponsible for the In-
spection, testin', and maintenance of
their fire protëtion system afld de-
vices in compliance with this\docu-
ment, as well s with the applicable
standards of,thé National Fire Protec-
tion Associaflôh (e.g., NFPA 5), in
addition to. the standards of any other
authorities hviñg jurisdiction. The in,
stalling contradtbr or sprinkler manii-
facturer should becontacted rela,tive to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested,, and ma!intained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
c9rdance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
!IJ:W JWl1
Ordering
Procedure
When placing an order, indicate the full
product name. Contact your local dis-
tributor for availability.
Sprinkler Assembly:
Specify: (SIN), (specify temperature
rating) Series RFII Concealed Pen-
dent Sprinkler, P/N (specify).
155F168C 200F/93C
1V3551 51-790-1-155 51-790-1-200
TY3504 51-796-1-155 51-796-1-200
TY3531 51-792-1-155 51-792-1-200
TY3505 51-797-1-155 51-797-1-200
Separately Ordered Cover Plate:
Specify: (specify temperature rating)
Series RFII Concealed Cover Plate
with (specify finish), P/N (specify).
135F/57C(a) 165F174C(b)
Brass 56-792-1-135 56-792-1-165
Bright Brass 56-792-2-135 56-792-2-165
Chrome 56-792-9-135 56-792-9-165
Brushed Chrome 56-792-8-135 56-792-8-165
White 56-792-0-135 56-792-0-165
White (RAL9010) 56-792-3-135 56-792-3-165
Bright White 56-792-4-135 56-792-4-165
Off White 56-792-5-135 56-792-5-165
Black 56-792-6-135 56-792-6-165
Custom 56-792-X-135 56-792-X-165
For use with 155F/68C sprinklers.
For use with 200F/93C sprinklers.
* Eastern Hemisphere sales Only.
Sprinkler Wrench:
Specify: RFII Sprinkler Wrench,
P/N 56-000-1-075.
Air and Dust Seal:
Specify: Air and Dust Seal,
P/N 56-908-1-001.
- TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446