HomeMy WebLinkAboutDWG 471-7A; CT 06-27; MUROYA SUBDIVISION; 01-17GRADING NOTES (IN ADDITION TO THE REQUIREMENTS OF CHAPTER 15.16 OF THE CARLSBAD MUNICIPAL CODE.) 1. THIS PLAN SUPERSEDES ALL OTHER PLANS PREVIOUSLY APPROVED BY THE CITY OF CARLSBAD REGARDING GRADING SHOWN ON THIS SET OF PLANS. 2. APPROVAL OF THIS PLAN DOES NOT LESSEN OR WAIVE ANY PORTION OF THE CARLSBAD MUNICIPAL CODE, RESOLUTION OF CONDITIONAL APPROVAL, CITY STANDARDS OR OTHER ADD/DONAL DOCUMENTS OF LISTED HEREON AS THEY MAY PERTAIN TO THIS PROJECT. THE ENGINEER RESPONSIBLE CHARGE SHALL REVISE THESE PLANS WHEN NON-CONFORMANCE IS DISCOVERED. 29. THE OWNER/APPLICANT SHALL INSURE THAT ALL CONTRACTORS SHALL COORDINATE THE WORK OF THESE GRADING PLANS WITH THAT SHOWN ON BOTH THE LANDSCAPE AND /RR/GA T/ON PLANS AND THE IMPROVEMENT PLANS AS REQUIRED FOR THIS WORK IN ACCORDANCE WITH THE LANDSCAPE MANUAL TIME REQUIREMENTS. 30. WHERE AN EXISTING PIPE LINE JS TO BE ABANDONED AS A RESULT OF THE GRADING OPERATION, IT SHALL BE REMOVED WITHIN TWENTY FEET OF BUILDING OR STREET AREAS AND REPLACED WITH PROPERLY COMPACTED SOILS. IN OTHER AREAS THE PIPE WILL BE PLUGGED WITH CONCRETE OR REMOVED AS APPROVED BY THE CITY ENGINEER. 31. THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL EXISTING FACILITIES CARLSBAD TRACT NO. MUROYA GRADING, AND PRIVATE EROSION CONTROL NOTES 3. CITY APPROVAL OF PLANS DOES NOT REL/EVE THE DEVELOPER OR ENGINEER-OF- WORK FROM RESPONSIBILITY FOR THE CORRECTION OF ERRORS AND OMISSIONS DISCOVERED DURING CONSTRUCTION. ALL PLAN REVISIONS SHALL BE PROMPTLY SUBMITTED TO THE CITY ENGINEER FOR APPROVAL. 4. A RIGHT-OF-WAY PERMIT FROM THE CITY ENGINEER WILL BE REQUIRED FOR ANY WORK IN THE PUBLIC RIGHT -OF -WAY. PRIOR TO PERMIT ISSUANCE, A CERT/FICA TE OF INSURANCE AS WELL AS ADD/7/0NAL INSURED ENDORSEMENT MUST BE FILED NAMING THE CITY OF CARLSBAD AS AN ADD/7/0NAL INSURED ON THE PERMITTEE'S POL/CY IN THE MINIMUM AMOUNT OF $1,000,000.00 FOR EACH OCCURRANCE OF LIABILITY. THE INSURANCE COMPANY WR/11NG THE POLICY MUST HAVE A RATING OF "A-" OR BETTER AND A SIZE CATEGORY OF CLASS V OR BETTER AS ESTABLISHED BY "BESTS" KEY RA TING GU/OE. ( ABOVE GROUND AND UNDER GROUND ) WITHIN THE PROJECT SITE SUFFICIENTLY AHEAD OF GRADING TO PERMIT THE REVISION OF THE GRADING PLANS IF IT IS FOUND THAT THE ACTUAL LOCA T/ONS ARE IN CONFLICT WITH THE PROF'OSED WORK. 1. IN CASE EMERGENCY WORK IS REQUIRED, CONTACT ---'-A~P~Rl=L_T-'-O~RN-'-l=LL~O ____ AT 949-341-12B9 (PHONE NUMBER) 5. UNLESS EXEMPTED BY SECTION J01.(b)5 OF THE UNIFORM BUILDING CODE, RETAINING WALLS OUTSIDE OF PUBLIC RIGHT -OF -WAY REQUIRE SEPARATE PERM/TS FROM THE BUILD/NG DEPARTMENT. 6. NO WORK SHALL BE COMMENCED UNTIL ALL PERMITS HAVE BEEN OBTAINED FROM THE CITY AND OTHER APPROPRIATE AGENCIES. 7. APPROVAL OF THESE PLANS BY THE CITY ENG/NEER DOES NOT AUTHORIZE ANY WORK OR GRADING TO BE PERFORMED UNTIL THE PROPERTY OWNER'S PERMISSION HAS BEEN OBTAINED AND A VALID GRADING PERMIT HAS BEEN ISSUED. 8. NO REVISIONS WILL BE MADE TO THESE PLANS WITHOUT THE WRITTEN APPROVAL OF THE CITY ENGINEER, NOTED WITHIN THE REVISION BLOCK, ON THE APPROPRIATE SHEET OF THE PLANS AND THE TITLE SHEET. 9. ORIGINAL DRAWINGS SHALL BECOME THE PROPERTY OF THE CITY UPON BEING SIGNED BY THE CITY ENGINEER. 10. THE ORIGINAL DRAWING SHALL BE REVISED TO REFLECT AS-BUILT CONDITIONS BY THE ENGINEER-OF-WORK PRIOR TO FINAL ACCEPTANCE OF THE WORK BY THE CITY. 11. ACCESS FOR FIRE AND OTHER EMERGENCY VEHICLES SHALL BE MAINTAINED TO THE PROJECT S/Tf AT ALL TIMES DURING CONSTRUCTION. 12. WHERE TRENCHES ARE WITHIN CITY EASEMENTS, A SOILS REPORT COMPRISED OF: (A) SUMMARY SHEET, (B) LABORATORY WORK SHEETS AND (C) COMPACTION CURVES, SHALL BE SUBMITTED BY A PROFESSIONAL ENGINEER OF THE STA TE OF CALIFORNIA, PR/NC/PALLY DOING BUSINESS IN THE FIELD OF APPLIED SOIL MECHANICS. THE SOILS REPORT WILL BE SUBMITTED TO THE CITY ENGINEERING INSPECTOR WITHIN TWO WORKING DAYS OF THE COMPLETION OF FIELD TESTS. 13. A SOILS COMPACTION REPORT AND COMPLIANCE VERIFICATION REGARDING ADHERENCE TO RECOMMENDATIONS OUTLINED IN THE SOILS REPORT IS REQUIRED PR/OR TO THE ISSUANCE OF A BUILDING PERMIT. ALL CONTROLLED GRADING SHALL BE DONE UNDER THE DIRECTION OF A PROFESSIONAL ENGINEER OF THE STATE OF CALIFORNIA PRINCIPALLY DOING BUSINESS IN THE FIELD OF APPLIED SOIL MECHANICS. ALL FILL OR FUTURE FILL AREAS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CITY OF CARLSBAD STANDARD SPECIF/CATIONS AND THE " EARTHWORK SPECIF/CATIONS " ATTACHED TO THE PRELIMINARY SOILS INVEST/GA 710N. DAILY FIELD COMPACT/ON REPORTS WILL BE SUBMITTED TO THE PROJECT INSPECTOR. 14. A PRECONSIBUCTION MEETING SHALL Bf HFI D AT THF SIT[ PRIOR TO THE BFG/NNING Of WORK AND SHAl L Bf A [T[NQED BY All RFPRFSENTA 7/VFS RESPONSIBLE FOR CONSTRUC110N, INSPECTION, SUPERVISION, TESTING AND ALL OTHER ASPITTS Of THE WORK. THE CONTRACTOR SHALL REQUEST A PRECONSTRUCTION MEETING BY CALLING THE INSPECTION LINE AT (760) 438-3891 AT LEAST FIVE(5) WORKING DAYS PRIOR TO STAR71NG CONSTRUC110N. THE CONTRACTOR WILL THEN BE CONTACTED BY THE PROJECT INSPECTOR TO COORDINATE A DA TE AND TIME FOR THE PRECONSTRUCTION MEETING. APPROVED DRAWINGS MUST BE AVAILABLE PRIOR TO SCHEDULING. THE GRADING PERMIT WILL BE PROVIDED BY THE PROJECT INSPECTOR AT THE MEETING. 15. All INSPECTION RfQl/fSIS OTHER THAN FOR PRFC0Nsm11c110N MFFTING W7/ l Bf MADE RY CAI UNG THF ENGJNFFR/NG 24 HOUR /NSPECllQN RFQIIEST llNF AT (760) 438-3891, INSPECTION REQUEST MUST BE RIT[fVEO PRIOR TO 2: 00 P,M, ON THE DAY BEFORE THE INSPECTION IS NEEDED. INSPECTIONS WILL BE MADE THE NEXT WORK DAY UNLESS YOU REQUEST OTHERWISE. REQUESTS MADE AFTER 2: 00 P.M. WILL BE SCHEDULED FOR TWO FULL WORK DAYS LATER. 16. THE OWNER AND/OR APPLICANT THROUGH THE DEVELOPER AND/OR CONTRACTOR SHALL DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES, INCLUDING SHORING, ANO SHALL BE SOLELY RESPONSIBLE FOR CONFORMING TO ALL LOCAL, STATE AND FEOERIL SAFETY AND HEALTH STANDARDS, LAWS AND REGULATIONS. 32. THE CONTRACTOR SHALL NOTIFY AFFECTED UTILITY COMPANIES (SEE BELOW) AT LEAST 2 FULL WORKING DAYS PRIOR TO STAR11NG GRADING NEAR THEIR FACILITIES AND SHALL COORDINATE THE WORK WITH A COMPANY REPRESENTATIVE. UNDERGROUND SERVICE ALERT SDG&E PACIFIC BELL TIME WARNER CABLE COX COMMUN/CATIONS CITY OF CARLSBAD(STREETS & STORM DRAIN) CITY OF CARLSBAD(SEWER, WATER & RECLAIMED WATER) DIG ALERT 33. PERMIT COMPLIANCE REQUIREMENTS: (800)422-4133 (800)660-7343 (800)892-0123 (760)438-7741 (760)806-9809 (760)434-2980 (760)438-2722 1-800-227-2600 A. FOR CONTROLLED GRADING -THE APPLICANT HIRES A CIVIL ENGINEER, SOILS ENGINEER, AND/OR GEOLOGIST TO GIVE TECHNICAL ADVICE. OBSERVE AND CONTROL THE WORK IN PROGRESS /15.16.120 A.B/ CARLSBAD MUNICIPAL CODE. 8. PRIOR TO FINAL APPROVAL OF A GRADING PERMIT -THE FOLLOWING REPORTS MUST BE SUBMITTED TO THE CITY ENGINEER VIA THE PROJECT INSPECTOR /15.16.120 A.10/ CARLSBAD MUNICIPAL CODE: (1) FINAL REPORT BY SUPERVISING GRADING ENGINEER STATING ALL GRAD/NG IS COMPLETE. ALL EROSION CONTROL, SLOPE PLANTING AND IRRIGATION ARE INSTALLED IN CONFORMANCE WITH CITY CODE AND THE APPROVED PLANS ( OBTAIN SAMPLE OF COMPLIANCE LETTER FROM CITY ENGINEERING DEPARTMENT). (2) AS-BU/LT GRADING PLAN. (J) REPORT FROM THE SOILS ENG/NEER, WHICH INCLUDES RECOMMENDED SOIL BEARING CAPACITIES, A STATEMENT AS TO THE EXPANSIVE QUALITY OF THE SOIL, AND SUMMARIES OF FIELD AND LABORATORY TESTS. THE REPORT SHALL ALSO INCLUDE A STATEMENT BY THE SOILS ENGINEER THAT THE GRADING WAS DONE IN ACCORDANCE WITH THE REQUIREMENTS AND RECOMMENDATIONS OUTLINED IN THE PRELIMINARY SOILS REPORT AND ANY SUPPLEMENTS THERETO. (4) REPORT WITH AS-BU/LT GEOLOGIC PLAN, IF REQUIRED BY THE CITY. J4. UNLESS A GRADING PERMIT FOR THIS PROJECT IS ISSUED WITHIN ONE (1) YEAR AFTER THE CITY ENGINEER'S APPROVAL, THESE PLANS MAY BE REQUIRED TO BE RESUBMITTED FOR PLANCHECK. PLANCHECK FEES WILL BE REQUIRED FOR ANY SUCH RECHECK. 35. THE SOILS REPORT TITLED: GEO TECHNICAL /NVESTIGA TION -MURO YA PROPERTY CARLSBAD CALIFORNIA DA TED JULY 14, 2009. AND THE FOLLOWING UPOA TES: 1) SEPTEMBER 30, 2009 -UPOA TED GEOLOGIC MAP 2) JULY 10, 2009 -RESPONSE TO REVIEW COMMENTS LETTER 3) NOVEMBER 3, 2009 -DRAINAGE SWALES 4) JANUARY 11, 2010 -RESPONSE TO GEOTECHNICAL REVIEW COMMENTS 5) MARCH 2, 2011 REVISED MAY 18, 2011 -STORM WATER MANAGEMENT CONSULTATION. 6) JULY 15, 2011 -RETAINING WALL REVIEW AND RESPONSE TO COMMENTS SHALL BE CONSIDERED AS A PART OF THIS GRADING PLAN. ALL GRADING SHALL BE DONE IN ACCORDANCE WITH THE RECOMMENDA 710NS AND SPECIF/CATIONS CONTAINED IN SAID SOILS REPORT AND UPDATE LETTERS. "DECLARATION OF RESPONSIBLE CHARGE" 2. EQUIPMENT AND WORKERS FOR EMERGENCY WORK SHALL BE MADE AVAILABLE AT ALL TIMES DURING THE RAINY SEASON. ALL NECESSARY MATERIALS SHALL BE STOCKPILED ON SITE AT CONVENIENT LOCATIONS TO FACILITATE RAPID CONSTRUCTION OF TEMPORARY DEVICES WHEN RAIN IS IMMINENT. 3. DEVICES SHOWN ON PLANS SHALL NOT BE MOVED OR MODIFIED WITHOUT THE APPROVAL OF THE ENGINEERING INSPECTOR. 4. THE CONTRACTOR SHALL RESTORE ALL EROSION CONTROL DEVICES TO WORKING ORDER TO THE SATISFACTION OF THE CITY ENGINEER AFTER EACH RUN-OFF PRODUCING RAINFALL. 5. THE CONTRACTOR SHALL INSTALL ADDITIONAL EROSION CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY ENGINEER DUE TO UNCOMPLETED GRADING OPERATIONS OR UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE. 6. THE CONTRACTOR SHALL BE RESPONSIBLE AND SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT PUBLIC TRESPASS ONTO AREAS WHERE IMPOUNDED WATERS CREA TE A HAZARDOUS CONDITION. 7. ALL EROSION CONTROL MEASURES PROVIDED PER THE APPROVED GRADING PLAN SHALL BE INCORPORATED HEREON. 8. GRADED AREAS AROUND THE PROJECT PERIMETER MUST DRAIN AWAY FROM THE FACE OF SLOPE AT THE CONCLUSION OF EACH WORKING DAY. 9. ALL REMOVABLE PROTECTIVE DEVICES SHOWN SHALL BE IN PLACE AT THE END OF EACH WORKING DAY WHEN THE FIVE (5) DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PERCENT ( 40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER EACH RAINFALL. 10. ALL GRAVEL BAGS SHALL BE BURLAP TYPE WITH 3/4 INCH MINIMUM AGGREGRATE. 11. SHOULD GERMINATION OF HYDROSEEDED SLOPES FAIL TO PROVIDE EFFECTIVE COVERAGE OF GRADED SLOPES (90% COVERAGE) PRIOR TO NOVEMBER 15, THE SLOPES SHALL BE STABILIZED BY PUNCH STRAW INSTALLED IN ACCORDANCE WITH SECTION 35.023 OF THE EROSION AND SEDIMENT CONTROL HANDBOOK OF THE DEPARTMENT OF CONSERVATION, STA TE OF CALIFORNIA. SEE THE STORM WATER POLLUTION PROTECTION PLAN (SWPPP) DOCUMENT AND EXHIBITS INCLUDING THE TEMPORARY HYDROSEED NOTES A-E. BASIS OF BERARINGS THIS BASIS OF BEARINGS FOR THE SURVEY IS THE CALIFORNIA COOROINA TE SYSTEM ZONE 6 EPOCH 1991.35 GRID BEARING BETWEEN CITY OF CARLSBAD SURVEY CONTROL STA T/ONS DESIGNATED 'CLSB-046' AND 'CLSB-044' PER RECORD OF SURVEY NO. 17271. I.E N15"15'04"E QUOTED BEARINGS FROM REFERANCE MAPS/DEEDS MAY OR MAY NOT BE IN TERMS OF SAID SYSTEMS. THE COMBINED SCALE FACTOR AT STATION 'CLSB-046' IS 0.999950310. 17. THE CONTRACTOR SHALL CONFORM TO LABOR CODE SECTION 6705 BY SUBMITTING A DETAIL PLAN TO THE CITY ENGINEER AND/OR CONCERNED AGENCY SHOWING FOR DESIGN OF SHORING, BRACING, SLOPING OR OTHER PROVISIONS TO BE MADE OF WORKER PROTECTION FROM THE HAZARD OF CA V/NG GROUND DURING THE EXCAVATION OF SUCH TRENCH OR TRENCHES OR DURING THE PIPE INSTALLATION THEREIN. THIS PLAN MUST BE PREPARED FOR ALL TRENCHES FIVE FEET (5') OR MORE IN DEPTH AND APPROVED BY THE CITY ENG/NEER AND/OR CONCERNED AGENCY PRIOR TO EXCAVATION. If THE Pl AN VARIFS FROM THE SHORING SYSJFM I HEREBY DECLARE THAT I AM THE ENGINEER OF WORK FOR THIS PROJECT, THAT I HA VE EXERCISED RESPONSIBLE CHARGE OVER THE DESIGN OF THE PROJECT AS DEFINED IN SECTION 6703 OF THE BUSINESS AND PROFESSIONS CODE, AND THAT THE DESIGN IS CONSISTENT WITH CURRENT STANDARDS. 0/STANCE=GROUND DISTANCE X COMBINED SCALE FACTOR. BENCH MARK STANDARDS ESTABLISHED BY THE CONSTRUCTION SAFETY ORDERS TITLE 8 CALIFORNIA ADMINISTRATIVE CODE, THE PLAN SHALL BE PREPARED BY A RFG/STFRFD FNG/NITR AT THE CONTRACTOR'S FXPFNSE. A COPY OF THE OSHA EXCAVATION PERMIT MUST BE SUBMITTED TO THE INSPECTOR PR/OR TO EXCAVATION. 18. NO BLASTING SHALL BE PERFORMED UNTIL A VALID BLASTING PERMIT HAS BEEN OBTAINED FROM THE CITY OF CARLSBAD. SUBMIT APPL/CAT/ON FOR BLASTING PERMIT WELL IN ADVANCE OF THE SCHEDULING OF BLASTING OPERATIONS. 19. IF ANY ARCHAEOLOGICAL RESOURCES ARE DISCOVERED WITHIN ANY WORK AREA DURING CONSTRUCT/ON, OPERATIONS WILL CEASE IMMEDIATELY. AND THE PERMITTEE WILL NOTIFY THE CITY ENGINEER. OPERA T/ONS WILL NOT RESTART UNTIL THE PERMITTEE HAS RECEIVED WRITTEN AUTHORITY FROM THE CITY ENGINEER TO DO SO. I UNDERSTAND THAT THE CHECK OF PROJECT DRAWINGS AND SPECIFICATIONS BY CITY OF CARLSBAD DOES NOT REL/EVE ME, AS ENGINEER OF WORK, OF RESPONSIBILITIES FOR PROJECT DESIGN. FIRM: PANGAEA LAND CONSUL TAN TS, INC. ADDRESS: 2834 LA MIRADA DR/VF SUITF H CITY, STATE: VISTA CALIFORNIA 92081 TELEP~~~: #32 BY: 7'"_ t __, 1 mCHARD C. BRASHER DA TE· ID . {) i• 2011 R.C.E. NO.:---'C"-'4"'3"-8'-'19:.._ ___________ _ REGISTRATION EXPIRATION DATE:-=6/~3=0~/~13~----?PANGAEA LAND CONSULTANTS. iNC. 20. ALL OPERATIONS CONDUCTED ON THE SITE OR ADJACENT THERETO, INCLUDING WARMING UP, REPAIR, ARRIVAL, DEPARTURE OR OPERATION OF TRUCKS, EARTHMOVING EQUIPMENT, CONSTRUCTION EQUIPMENT AND ANY OTHER ASSOC/A TED GRADING EQUIPMENT SHALL BE LIMITED TO THE PERIOD BETWEEN 7: 00 A.M. AND SUNSET EACH DAY, MONDAY THRU FRIDAY AND NO EARTHMOVING OR GRADING OPERATIONS SHALL BE CONDUCTED ON WEEKENDS OR HOLIDAYS. (A UST OF CITY SOILS ENGINEER'S CERTIFICATE HOL/DA YS IS AVAILABLE AT THE ENGINEERING DEPARTMENT COUNTER.) f, 6 UM,JJ L 'f'f;:r d , A REGISTERED (CIVIL/ 21. ALL OFF-SITE HAUL ROUTES SHALL BE SUBMITTED BY THE CONTRACTOR TO THE GEDTECHNICAL) ENGINEER OF THE STA TE OF CALIFORNIA, PR/NC/PALLY DOING CITY ENGINEER FOR APPROVAL TWO FULL WORKING DAYS PRIOR TO BEGINNING OF WORK. BUSINESS IN THE FIELD OF APPLIED SOIL MECHANICS, HEREBY CERTIFY THAT 22. IMPORT MATERIAL SHALL BE OBTAINED FROM, AND WASTE MATERIAL SHALL BE A SAMPLING ANO STUDY OF THE SOIL CONDITIONS PREVALENT WITHIN THIS DEPOSITED AT, A SITE APPROVED BY THE CITY ENGINEER. THE CONTRACTOR SITE WAS MADE BY ME OR UNDER MY DIRECTION BETWEEN THE DATES OF SHALL BE RESPONSIBLE FOR ANY DEBRIS OR DAMAGE OCCURRING ALONG THE HAUL .)Ui-'\' l~ , 20 0 9 AND SEPTENl8E.f', 30 , 20~. TWO ROUTES OR ADJACENT STREETS AS A RESULT OF THE GRADING OPERATION. COPIES OF THE SOILS REPORT COMPILED FROM THIS STUDY, WITH MY 23. BRUSH SHALL BE REMOVED ONLY WITHIN THE AREA TO SE GRADED. NO TREES ARE RECOMMENDATIONS, HAS BEEN ~U D TO THE OFFICE OF THE CITY TO BE REMOVED UNLESS SPECIF/CALLY NOTED ON THE PLAN. ENG/NEER. 24. ALL AREAS SHALL BE GRADED TO DRAIN. GRADING RESULTING IN THE PONDING OF S/GNEO: __ ~~--------------- WATER IS NOT PERMITTED. ALL EARTHEN SWALES AND DITCHES SHALL HAVE A CALIFORNIA REGISTRATION NO.: G3e Z,7/1' MINIMUM ONE PERCENT SLOPE. ~ 25. THESE PLANS ARE SUBJECT TO A SIGNED AND APPROVED SET OF EROSION DA TE: ___.xr='---"C,,+1--"~=/-'-/ ___ 1~-.1------- CONTROL PLANS. EROSION CONTROL SHALL BE AS SHOWN AND AS APPROVED BY LICENSE EXP/RATION DA TE: <, .._ /~ THE CITY ENGINEER OR AS DIRECTED BY THE PROJECT INSPECTOR. C"'J 26. ALL SLOPES SHALL BE TRIMMED TO A FINISH GRADE TO PRODUCE A UNIFORM SURFACE AND CROSS SECTION. THE SITE SHALL BE LEFT IN A NEAT AND ORDERLY CONDITION. ALL STONES, ROOTS DR OTHER DEBRIS SHALL BE REMOVED AND DISPOSED OF AT A SITE APPROVED OF BY THE CITY ENG/NEER. 27. ALL SLOPES SHALL BE /RR/GA TED, STABILIZED, PLANTED AND/OR HYDROSEEDED WITHIN TEN (10) DAYS OF THE TIME WHEN EACH SLOPE IS BROUGHT TO GRADE AS SHOWN ON THE APPROVED GRADING PLANS. 28. LANDSCAPING SHALL BE ACCOMPLISHED ON ALL SLOPES AND PADS AS REQUIRED BY TH£ CITY OF CARLSBAD LANDSCAPE MANUAL, TH£ LANDSCAPING PLANS FOR THIS PROJECT, DRAWING NO. 471-7C , AND/OR AS DIRECTED BY THE CITY ENGINEER OR PLANNING DIRECTOR. OWNER'S CERTIFICATE I ( WE ) HEREBY CERTIFY THAT A REGISTERED SO/LS ENG/NEER OR GEOLOGIST HAS BEEN OR WILL BE RETA/NED TO SUPERVISE OVER-ALL GRADING ACTIVITY ANO ADVISE ON THE COMPACTION AND STABILITY OF THIS SITE. ~ ~~-----I , 1.--.-,"'-(Jc--r ,.11,,;,1111 DATE ' SURVEY CONTROL STAT/ON PT. NO. 46 NAMED: CLSB-046 PER RECORD OF SURVEY NO. 17271. WELL MONUMENT MARKED LS 5667 AT THE INTERSECTION BLACK RAIL RD. AND MARTINGALE CT. NGVD 29 ELEV = 342. 747' SOURCE OF TOPOGRAPHY TOPOGRAPHY SHOWN ON THESE PLANS WAS GENERA TED BY AERIAL PHOTOMETRIC METHODS FROM INFORMATION GATHERED ON NOV, 24 2004 BY SAN-IO AFR/AL SIJRVFY5 TOPOGRAPHY SHOWN HEREON CONFORMS TO NATIONAL MAP ACCURACY STANDARDS. PROJECT LOCATION THIS PROJECT IS LOCATED WITHIN ASSESSORS PARCEL NUMBER($) 215-040-03 THE CALIFORNIA COORDINATE INDEX OF THIS PROJECT IS: N 1986 E 6246 ASSESSOR PARCEL NUMBER 215-040-03 TITLE COMPANY FIRST AMERICAN TITLE COMPANY CT 06-27 STORM DRAIN VICINITY MAP NO SCALE OWNER AK/RA MUROYA AND TOSHIKO MUROYA TRUSTEES OF THE MUROYA FAMILY TRUST DATED MAY 18, 1998 P.O. BOX 131016 CARLSBAD, CA 92013 PHONE: (760) 438-7691 FAX: (760) 438-7691 DEVELOPER TAYLOR MORR/SON OF CALIFORNIA, LLC 8105 /RVIN[ CENTER DRIVE, SUITE 1450 /RV/NE, CALIFORNIA 92618 PHONE: (949) 341-1289 FAX: (949) 341-1400 CONTACT: APRIL TORNILLO LEGAL DESCRIPTION THE EAST ONE-HALF OF THE NORTHEAST QUARTER OF THE NORTHWEST QUARTER, SECTION 27, TOWNSHIP 12 SOUTH, RANGE 4 WEST, SAN BERNARDINO BASE ANO MERIDIAN, IN THE Cl TY OF CARLSBAD, COUNTY OF SAN DIEGO, STATE OF CALIFORNIA, ACCORDING TO UNITED STA TES GOVERNMENT SURVEY REFERENCE DRAWINGS 397-4 TABATA 322-7 AV/ARA PA 24 387-1 CARNATION 335-5 BLACK RAIL ROAD 322-2A NIGHT SHADE ROAD (STORM DRAIN OFFS/TE) EARTHWORK QUANTITIES CUT: ______ 21,897 CY FILL: 20,691 CY IMPORT: 0 CY EXPORT: 1,206 CY REMEDIAL:----36,000 CY DEBRIS TO BE REMOVED 3,120 CY WORK TO BE DONE THE GRADING WORK SHALL CONSIST OF THE CONSTRUCTION OF ALL CUTS AND FILLS, REMEDIAL GRADING, DRAINAGE: FACILITIES, EROSION CONTROL FACILITIES, AND PLANTING OF PERMANENT LANDSCAPING AND PREPARATION OF AS-BUILT GRADING PLANS, AS-BUILT GEOLOGIC MAPS AND REPORTS, ALL AS SHOWN OR REQUIRED ON THIS SET OF PLANS AND THE CITY STANDARDS, SPECIF/CA T/ONS, REQUIREMENTS, RESOLUTIONS AND ORDINANCES CITED ON THESE PLANS. THE GRAD/NG WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE FOLLOWING DOCUMENTS, CURRENT AT THE TIME OF CONSTRUCTION, AS DIRECTED BY THE CITY ENGINEER. 1. CARLSBAD MUNICIPAL CODE: 2. CITY OF CARLSBAD ENGINEERING STANDARDS 3. THIS SET OF PLANS 4. PLANNING COMMISSION RESOLUTION NO. 6686 DATED APRIL 7 2010 5. THE STANDARD SPECIF/CA T/ONS FOR PUBLIC WORKS CONSTRUCTION (GREEN BOOK). 6. SOILS REPORT AND RECOMMENDATIONS BY GEOCON /NCORPORA TED _____ DATED JULY 14, 2009 7. THE SAN DIEGO REGIONAL STANDARD DRAWINGS AND AS MAY BE MODIFIED BY THE CITY OF CARLSBAD STANDARDS. 8. S,\UFORIIM G0,6,51'.\L COASTAL DEVELOPMENT PERMIT CONDITIONS RESOLUTION 6688 DA TED APRIL 7 2010 9. ENVIRONMENTAL APPROVAL DOCUMENTS DATED APRIi Z ?Q1Q 10. STORM WATER POLLUTION PREVENTION PLAN PREPARED BY CHANG CONSULTANTS DA TED MARCH 1, 2011 WDID NO. ----'9'-"-3-'7C'-'3-'-6-'10'-'-7-'-0 ______ _ 11. STORM WATER MANAGEMENT PLAN PREPARED BY CHANG CONSULTANTS DATED JULY 14, 2011 12. CALIFORNIA STORM WATER QUALITY ASSOC/A TION BMP CONSTRUCT/ON HANDBOOK AND CAL TRANS CONSTRUCTION SITE BMP MANUAL. LEGEND DESCRIPTION DWG.NO. 12" PVC (PR/VA TE STORM DRAIN) ...........•................................... 18" RCP (1350-0) ....................................................................... . 24 • RCP (1350-0 ) ...................................................................... . STORM DRAIN CLEANOUT TYPE "A-4" .................................... '*0-9 CURB INLET TYPE "B" (SIZE: PER PLAN) ................................ '*D-2 TYPE 'F' CATCH BASIN (BIO-BASIN OUTLET STRUCTURE) ......... D-7 TYPE 'G' CATCH BASIN ............................................................ 0-8 CONCRETE CUTOFF WALL. ........................................................... S-10 CONCRETE HEADWALL (18" & 24" PIPE) .................................. 0-34 RIP RAP ENERGY DISS/PA TOR (SIZE AND LOCA T/ON PER PLAN) ............................................ **D-40 GROUTED RIP RAP EMERGENCY SPILLWAY .............................. **0-40 DRAINAGE DITCH TYPE "B" ....................................................... ••D-75 BIO-RETENTION BASIN ............................ (SEE DETAIL SHEET 3) BIO-SWALE .............................................. (SEE DETAIL SH[[T 3) MODIFIED D-41 ENERGY DISS/PA TOR .. (SEE DETAIL SHEET 15-17) 0-41 6" CANYON SUBDRAIN .. (PER FIGURE 8, 9 AND 10 IN THE SO/LS REPORT) RETAINING WALLS MASONRY RETAINING WALL (WALLS 1-7, 9-13 AND 15-17 SEE SHT 14) PLANTABLE GEO-GRID RETAINING WALL (WALL 8 & 14) SEE SHT 10-13 CABLE RAIL FENCE (TOP RETAINING WALL 14) CALTRANS STD 811-47 SYMBOL QUANTITY --------------248 LF -------254 LF ------- --------------145 LF !§I] 3 EA [Q_] 3 EA I@] 2 EA □ 2 EA --=Q:--------1 EA Q 3 EA ~ 6 EA ~ 688 SF < /43LF > --~ ,~, ~~-~~ : I· · · · · · · I 6,655 SF --·. .. 4,566 SF ~ EiC I 1 EA < <( 218 LF -------5,370 SF FACE ~ 4,440 SF FACE 162 lF ALL STANDARD DRAWINGS ARE SAN DIEGO REGIONAL STANDARD DRAWINGS (SDRSD) UNLESS NOTED OTHERWISE " -(SOR SD )AS MODIFIED PER CITY OF CARLSBAD BMP NOTE: I. ALL BMP'S FOR THIS PROJECT ARE TO BE MAINTAINED BY THE DEVELOPER AND /OR FUTURE HOA. 2. THIS IS A PRIORITY PROJECT, TIER 3 THREAT ASSESSMENT. REQUIRED TREATMENT CONTROL BMP TABLE TYPE DESCRIPTION OWNERSHIP BIO-RETENTION HOA TC-32 BASIN TC-30 BID-SWALE HOA SUSMP PROJECT PRIORITY ---~H=I=G=H __ _ PWfNING1 DEPARTMENT APPROVAL ~ 2 {w DATE:/0/IJ/// (SIGNED) ,()o,v llle°U > PLANNING DIRECTOR w {JJ DATE: /0/1:> /1\ (SIGNED) RECOIIMENDED ev. J)Ar,..) Be-\v 11'{s"'ON (PRINT NAME) MAINTENANCE SHEET NO. IIAINTENANCE AGREEMENT FREQUENCY BMP AGREEMENT 3,4,5,6 MONTHLY & AF'!ER AND CC&R'S STORMS BMP AGREEMENT MONTHLY & AF'!ER AND CC&R'S 3,4 STORMS ''AS BUILT" ,qp~d~ {;; -tZ-t7-(J RCF @t-' EXP. G·JQ·tO DATE REVIE'-'ED BY, a: v aJ.~_ :s-,-11 raT □R. ~ DATE 1-----t-· ------,1-------------+-----+----t----i-----al SHlEET I CITY OF CARLSBAD fsREilll ~::::::::~.'::::::::==:::E=NG:::I::::N::::E::::ER::'l::::N::::G=D:::E::::P::':A::'R::':TM::'E::::N::'T==:::'..::LJ'.U==7==: 1---+---+------------------+----+--+----t---t GRADING PLANS FOR: MUROYA TITLE SHEET APPROVED~.•~-../. ,.,fA_/}, .,I_ GLEN K. VAN PESKI ~, LC,!_~ ~ ;Oljil)lj/ ENGINEERINGMANAGER PE 41204 EXPIRES 3/31 /13 =,c~·A"'fE~--, 1--~--,-+-cc=-+-,,--.,----=.,....-c-c----------+---t----+---t-----1 IZ·lC.-IJ ff:/5 /1\ AC.-G(,/(l"{" DWN BY: JG PROJECT MO. DRAWING NO. DATE INl"TIAL DATE INITIAL DATE INl11AL CHKD BY OM ,,, : CT 06-27 471-7A ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL RVWD BY: RB 110111 LEGEND ORANGE PLASTIC HABITAT/ HMP FENCE ■■■■■■■ CONSTRUCT A CONTINUOUS ORANGE PLASTIC HABITAT/ HMP FENCE ON THE LOT 4 (OPEN SPACE) LOT LINE (AT THE LOCATION SHOW ABOVE) PRIOR TO THE START OF ANY GRADING OR CONSTRUCTION. THE ENGINEER OF RECORD SHALL PREPARE A CERT/FICA TION LETTER TO THE CITY (PLANNING, ENGINEERING AND FIELD INSPECTION) STA TING THE LOCA T/ON OF THE ORANGE FENCE ON THE LOT 4 LOTL/NE WAS FIELD SURVEYED AND THE ORANGE FENCE WAS CONSTRUCTED BASED ON THE FIELD SURVEYED LOCATION. THE LETTER SHOULD BE PREPARED AND PRESENTED AT THE CITY PRE-CONSTRUCTION MEETING. THE PROJECT BIOLOGIST WILL REWIEW THE EXISTING HABITAT IN LOT 3 AND MAY REQUIRE ADDITIONAL HMP FENCING IN LOT 3 TO PROTECT EXISTING HABITAT IN AREAS NOT SHOWN TO BE GRADED PER THIS GRADING PLAN. THESE AREAS WILL BE DETERMINED BY THE BIOLOGIST AND FENCED PRIOR TO THE START OF ANY GRADING AND CONSTRUCT/ON. By: /2tJ213.e .. Luk ,047 ,;ao11 Name: Richard C. Brasher SAN DI EGO GAS & ELECTRIC COMPANY REVIEWED BY~i2:1acR DATE/~~/ R.C.E.: 43819 exp: 6-30-2013 9PANGAEA FRED CLARK / LAND MANAGEMENT REPRESENTATIVE LANU CONSULTANTS. I NC VALID FOR 18 MONTHS FROM SIGNATURE NOTE: THE SITE DISTANCE SETBACK AREAS SHALL NOT HAVE ANY OBSTRUCTIONS INCLUDING, STRUCTURES, GRADING, WALLS, FENCES, ETC. LANDSCAPING SHALL NOT THAT EXCEED 30" IN HEIGHT SHEET INDEX SHEET 1 -TITLE SHEET AND NOTES SHEET 2 -KEY MAP SHEET 3 -TYPICAL UNDERCUT SECTIONS AND DETAILS SHEET 4 -ROUGH GRADING SHEET 5 -PR/VA TE STORM DRAIN SHEET 6 -PR/VA TE STORM DRAIN SHEET 7 -RETAINING WALL PROFILES SHEET 8 -RETAINING WAU PROFILES SHEET 9 -RETAINING WAU PROFILES SHEET 10 -VERDURA RETAINING WALL DETAILS SHEET 11 -VERDURA RETAINING WALL DETAILS SHEET 12 -VERDURA RETAINING WALL DETAILS SHEET 1J -VE.ROURA RETAINING WALL DETAILS SHEET 14 -MASONRY RETAINING WALL DETAILS SHEET 15 -MODIFIED D-41 OUTLET STRUCTURAL DETAILS SHEET 16 -MODIFIED D-41 OUTLET STRUCTURAL DETAILS SHEET 17 -MODIFIED 0-41 OUTLET STRUCTURAL DETAILS I 60 1:1 PERMISSION IS HEREBY GRANTED TO GRADE AND CONSTRUCT IMPROVEMENTS AS SHOWN ON THESE PLANS IMTHIN SAN DIEGO GAS & ELECTRIC COMPANY'S EASEMENT(S) SUBJECT TO THE FOLLOWING CONDITIONS: 1. SUBMITTALS: 1.1. PERM/TT££ AGREES TO SUPPLY SDG&E WITH 'AS BU/Lr GRADING, IMPROVEMENT AND PROFILE PLANS TO SDG&E SPECIF/CATIONS, IF REQUESTED. 1.2. PERMITTEE AGREES TO SUBMIT FOR RE\!1EW AND APPROVAL A BLASTING PLAN PRIOR TO BLASTING , IF BLASTING IS REQUIRED. PRE-CONSTRUCTION MEETINGS: SDG&E LAND MANAGEMENT REPRESENTATIVE (LMR) MUST BE INVITED WITH AT LEAST THREE (3) WORKING DAYS PRIOR NOTICE. GRADING: 3.1. AT LEAST TWENTY FOUR (24) HOURS NOTICE MUST BE GIVEN TO SDG&E'S LMR BEFORE START OF WORK. 3.2. FIELD CHANGES TO PLANS IMTHIN SAID EASEMENT SHALL BE APPROVED IN WRITING BY SDG&E LMR. 3.3. PERMITTEE IS RESPONSIBLE TO CALL DIG ALERT AT 1-800-227-2600 FOR ALL UNDERGROUND MARK-OUT LOCATIONS. 3.4. CLEARANCE OF (35) FEET MINIMUM BETWEEN THE SDG&E ELECTRIC TRANSMISSION WIRES AND THE NATURAL GROUND SHALL BE MAINTAINED ON ANY GIVEN DAY, NOTING LINE SAGS VARY DEPENDING ON AMBIENT TEMPERATURE AND LINE CURRENT. ALL CAL-OSHA REQUIREMENTS FOR CLEARANCES BETWEEN WHEN WORKING AROUND ENERGIZED ELECTRICAL FACILITIES MUST BE MAINTAINED. 3.5. NO GRADING SHALL BE ALLOWED WITHIN TEN (10) FEET OF A SINGLE WOOD POLE STRUCTURE OR ANCHOR, WITHIN FIFTEEN (15) FEET OF MULTI-WOOD POLES, WITHIN TWENTY (20) FEET OF STEEL LA TT/CE TOWERS OR WITHIN THIRTY (30) FEET OF STEEL POLES. 3.6. SDG&E RESERVES THE RIGHT TO INSPECT AND PERFORM QUALITY CONTROL WORK DURING CONSTRUCTION., 4. SPECIAL CONDITIONS: NONE · :· GRAPHIC SCALE 0 ,0 60 120 l!!I ~ j t j ei ( IN FEET ) 1 inch = 60 ft. 11 AS BUILT" tf4:P/4L RCE 436/;) EXP. G-::,0-1$ DATE·, KEY MAP 3-S:·l'f DATE 1----+--+-----------+-----f---+---t-------tl SH2EET I CITY OF CARLSBAD ~7 ENGINEERING DEPARTMENT l__1l__j ~G::;R=AD:;l;:N~G,.':;::P:;LA~N~S~F:;OR~::::=:::====:::::::::===:::'.-'===~ ENGINEERIN AS-t&acr DWN BY: DA TE INl11AL ENGINEER OF WORK REVISION DESCRIPTION DA TE INITIAL DATE IN171AL OTHER APPROVAL Cl TY APPROVAL CHKD BY: RVWD BY: MUROYA KEY MAP GLEN K. MANAGER PE 41204 EXPIRES 3 31 13 JG PROJECT NO. ~~ <, CT 06-27 VAN PESKI /~LtfP' DAT DRAWING NO. 471-7A 110111 ! 38' UNDERCUT 36' TOP OF LINER TO BE 6' MIN. ABOVE EMERGENCY SPILLWAY ELEVATION L.---SILT / DEBRIS DEPTH GAUGE BOTTOM OF BASIN PER PLAN "/---TOP OF LINER TO BE 6" MIN. ABOVE 6" 2.0% ,, 6" CURB 18' 2.0% 1.5' UNDERCUT 18' 2.0% ' ---~ ,~ '""' 6" CURB & GUTTER WHITE SAGE WAY UNDERCUT SECTION NOT TO SCALE 26' UNDERCUT 24' 12' 12' HOLL YLEAF COURT AND SWEETCLOVER LANE UNDERCUT SECTION NOT TO SCALE ' I ! I I STA. 18+20 -21+60 34' OR 44' UNDERCUT 6" 2.0% ~ ,.if TYPICAL H(i)LL YLEAF COURT AND SWEETCLOVER LANE PARKING SPACE UNDERCUT SECTION NOT TO SCALE I' 1/ /J -~~ ~ ~ • TOP oF lx1sT. EMERGENCY SPILLWAY ELEVATION 3" SCHEDULE 40 PVC PERFORATED PIPE WRAPPED WITH FILTER FABRIC PER CALTRANS SECTION 68-1.028 AND INSTALLED PER CALTRANS SECTION 68-1.03 THE J" DRAIN SHALL SLOPE 0.5% TOWARD THE BASIN TYPE 'F' OUTLET STRUCTURE ~-24' MIN. THICKNESS -CLASS 2 PERMEABLE MATERIAL PER CALITTANS SECTION 68-1.025 SECTION A-A BIO-RETENTION BASIN (SEE SHT 4) NOT TO SCALE EMERGENCY SPILLWAY BASIN 1 ELEV = 323.50, BASIN 2 ELEV = 327.00 (SEE SPILLWAY DETAIL AT RIGHT) ~-MODIFIED' TYPE 'F' BASIN OUTLET WITH NOTCH SILT / DEBRIS GAUGE TO BE LOCATED NEAR THE CLEANOUT 3" PVC CLEANOUT AT THE END 18" RCP BASIN OUTLET PIPE SEE PROFILE ON SHEET 5 DOWN STREAM HEADWALL DEEPENED CUTOFF WALL AND RIP RAP WITH CUTOFF WALL AND NO TOP (SEE DETAILS BELOW) 18" PLANTING MIX PER LANDSCAPE ARCHITECT SPECIFICATION BOTTOM OF BASIN PER PLAN OF THE 3" PVC DRAINS ~-2' WIDE X 1' HIGH RIP RAP FOREBAY BERM ALONG EDGE OF RIP RAP ALL SIDES FOREBAY «:f'_::------RIP RAP (SIZE PER PLAN) /v---HEADWALL WITH DEEPENED CUTOFF WALL f f "':t:!i~or~·;::====-,---24" RCP BASIN 1 -18" BASIN 2 l-1; INLET PIPE ,,, : , , 45 DEGREE ELBOW 24" MIN. THICKNESS -CLASS 2 PERMEABLE MATERIAL PER CALITTANS SECTION 68-1.025 . 0 THE BASIN SHALL BE LINED WITH AN IMPERMEABLE LINER OF HIGH-DENSITY POLYETHYLENE, HOPE, WITH A MIN. THICKNESS OF 12 MIL. OR EQUIVALENT POLYVINYL CHLORIDE, PVC LINER. All PIPES THROUGH THE LINER SHALL BE MADE WATER PROOF (TYPICAL) '--------J" SCHEDULE 40 PVC PERFORATED PIPE WRAPPED WITH FILTER FABRIC PER CALTRANS SECTION 68-1.028 AND INSTALLED PER CALTRANS SECTION 68-1.03 THE 3" DRAIN SHALL SLOPE 0.5% TOWARD THE BASIN TYPE 'F' OUTLET STRUCTURE 3" X 3" X 4" TEE ~-4" SCHEDULE 40 SOLID PVC FROM THE TEE INTO THE TYPE 'F' BASIN (4" ORIFICE PER DRAINAGE REPORT) SECTION B-B BIO-RETENTION BASIN (SEE SHT 4) NOT TO SCALE 18" PLANTING MIX PER LANDSCAPE ARCHITECT SPECIFICATION ~ Q 1/ HEADWALL ' VJ ~ II 3r/7.61 / W/ / J...,.. Q 7 EXIST. 24" RCP/ ;/: fJ: I 304.40 /FL ~ fl EXIST CONCRt1-E DITCH. c;;;; SWALE 305.60 FL 305.40 FL 5'-5" 305. DRAINAGE NOTCHES FL 'S IN THE CUTOFF WALL TO MATCH THE EXISTING CONCRETE SWALE ELEVATION RIP RAP PER 0-41 (18" PIPE) SAWCUT THE EXIST CONCRETE SWALE AND ONLY REMOVE ENOUGH TO CONSITTUCT THE STRUCTURE. 307.60 TW J06.60 TCW EXISTING 24" RCP EXISTING HEADWALL 305.60 EG & FLOW ---...:---..._ ET£ sWALE EXIST coNCR 3.75' THE SWALE SHALL BE LINED WITH AN IMPERMEABLE LINER OF HIGH-DENSITY POLYETHYLENE, HOPE, WITH A MIN. THICKNESS OF 12 MIL. OR EQUIVALENT POLYVINYL CHLORIDE, PVC LINER. All PIPES THROUGH THE LINER SHALL BE MADE WATER PROOF (TYPICAL) J" SCHEDULE 40 PVC PERFORATED PIPE WRAPPED WITH FILTER FABRIC PER CALTRANS SECTION 68-1.028 AND INSTALLED PER CALTRANS SECTION 68-1.03 THE J" DRAIN SHALL SLOPE 0.5% TOWARD THE BASIN OUTLET STRUCTURE ( CURB INLET) i'./;./.;,. :1::;1!1! . )' ' > ' ' .~ •. 1/ 24" MIN. THICKNESS -CLASS 2 PERMEABLE MATERIAL PER CALTRANS SECTION 68-1.025 12' WIDE BIO-SWALE NOT TO SCALE SEE SHEET 6 FOR PLAN VIEW NOT TO SCALE 2: 1 2: 1 7.0' 'U' SHAPED WALL ADDED TO THE TOP OF 0-41 17.0' 'Ir------~~-----------{. 312.23 TW 'U' SHAPED WALL l 5'-11" ,.,.._ __ BOTTOM 6' WIDE X 1' DEEP EMERGENCY BASIN OVERFLOW SPILLWAY WHICH IS LINED WITH GROUTED RIP RAP (SEE DETAIL @ RIGHT) 309.63 BW ~6.76 [? LJ 1.0% a 5% -;::'==:~9 J06 ~=:'.~·".'.".'.======~I"-"'\.. -,:FL"""t 8,g,..,R=c=p ~o:_ INLET BOX PER D-41 NOTE: CONSTRUCT A CONCRETE CUTOFF WAU PER D-40 AT THE END OF THE BASIN 2 SPILLWAY 6' 2' I 2' I 2' ELEVATION PER PLAN 1.0' '/Y'mTirr/.'4...._GROUTED FACING CLASS 3.0' THICK RIP RAP OVER 3/8" GRAVEL FILTER BLANKET 1 FOOT THICK BASIN 1 & 2 EMERGENCY BASIN OVERFLOW SPILLWAY NOT TO SCALE 304.40 FL Cu'O"F "''LL_/"-------+----8_.0_' __ -'k-_2._0_,,_' 83005TT.808M ~--------~ " " ,,,, ~ SEE SHEET 15, 16 AND 17 FOR i---· ---~17~.o~·----------'1-smUCTURAL DETAILS SECTION C-C MODIFIED D-41 CONCRETE ENERGY DISSIPATOR NOT TO SCALE y ;\ END 0-75 WITH CUTOFF WALL SHAPE THE GROUTED FACING CLASS RIP RAP TO MATCH AND JOIN THE [ND OF THE CONCR[TE 0-75 DRAINAGE DITCH WITH A SMOOTH TRANSITION DIRECTING THE DRAINAGE DOWN STREAM SEE SHEET 4 FOR PLAN VIEW CABLE RAIL FENCE PER CALTRANS 811-47 UN[ VEROURA WALL 8 4.0' .5' .5' 2' WIDE CONCRETE DITCH PER 0-75 TYPE B GEOGRIO RETAINING WALL FABRIC THREE. RETAINING WALL BLOCK DOWN POST HOLE TO BE B" DIA MAX BORED THROUGH THE FIRST LA YER OF GEOGRIO FABRIC SEE SHEETS 10 THROUGH 13 FOR VERDURA WALL NOTES AND DETAILS WALL 8 -TOP OF WALL FENCE AND DITCH DETAIL NTS TOP OF WALL ELEVATION PER PLAN RETAINING WALL SEE SHT 14 4" A TR/UM GRATE tl\i;~~ MODIFIED D-75 TYPE 'B' CONCRETE CONCRETE DITCH 12" WIDE x 12" MAX DEPTH AT THE ATRIUM GRATE 4" PVC DRAIN TOP OF WALL ELEVA T/ON PER PLAN H"l.,.___ MODIFIED 0-75 TYPE 'B' CONCRETE CONCRETE DITCH 12" WIDE x 8" DEEP RETAINING WALL TYPICAL DITCH @ TOP OF WALL NTS SWALE. SYMBOL ON PLAN -- Jf----4'---i( ,i'-0.9'.,i' 323.50 TOP ~-~ --·· --,-~=~~- 321.90 l\1ER 321. 00 BASIN BOTTOM 6" ~ TYPICAL I I ,I' o. 9'.i' NOTCH Jf----4'---i( OPEN TOP N.T.S. T J'-5.5" MODIFIED TYPE 'F INLET OUTLET BASIN 1 N.T.S. NOTE. 4" PVC ELBOW PIPE FLOW EQUALS PAO ELEVA T/ON PAD ELEVA T/ON PER PLAN , ~-BACK OF WALL DRAIN SEE. DE.TAIL ON SHT 14 __ WALL FRENCH DRAIN PIPE (NOT TO BE CONNECTED SURFACE SWALE DRAIN) CORE HOLE THROUGH THE WALL FOR 4" PVC OUTLET PIPE. ~.J..--WALL FOOTING TYPICAL DRAIN @ TOP OF WALL NTS DRAIN SYMBOL ON PLAN --0 ,__ __ 4' -~-,- ~}----3,0'.____,j-c-C__,3=2~7.=00~TO~P_ 326.00 mER 325. 00 BASIN BOTTOM ! 6" H TYPICAL I If------, jJ<-' --3.0::c-,I' NOTCH ,----4'--,/' OPEN TOP N.T.S. T J'-5.5" MODIFIED TYPE 'F INLET OUTLET BASIN 2 N.T.S. NOTE TYPE 'F' (D-7) CATCH BASIN MOD!FICA T/ON INCLUDES NOTCH DETAIL AND EL/MINA T!ON OF STRUCTURE TOP WHICH WILL REMAIN OPEN. TYPE 'F' (D-7) CATCH BASIN MODl,"!CA TION f/\JCLUDES NOTCH DETAIL AND [LIM/NAT/ON OF STRUCTURE TOP f½'-/iCH WILL REMAIN OPEN By. t?tm«~ate, 1O·01-'lDII Name, Richard C. Brasher R.C.E.: 43819 exp: 6-30-2013 , s,PANGAEA LAND 0 ... H-.SliLIANl5, lNC I TREATMENT CONTROL BMP TABLE DESCRIPTION QUANTITY BIO-RETENTION BASIN 2 EACH BIO-SWALE 4,566 SF "AS BLJIL T" 41/t,&/ RCE 436/,!j EXP. (,-.30•1$ DATE DATE l---+--+------------+---+--t----+----1 I SH3EET I CITY OF CARLSBAD ~7 ~:::;:~..':::;:;=.:;;E=NG;::I::=N:;EE=R=I=N=G=D=E=P=A=R=TM=E::::N=T==::"::L.11_j==~ GRADING PLANS FOR l-----+--+---------------+---t---+-~-1-----1 MUROYA TYPICAL UNDERCUT SECTIONS AND DETAILS APPROVED: GLEN K. VAN PESKI ENGINEERING 13 ~~l DA TE INITIAL ENGINEER OF WORK REVISION DESCRIPTION DWN BY: JG PROJECT NO. DRAWING NO. DATE INITIAL DATE INlllAL CHKD BY: DM /J~ RVWD BY: RB CT 06-27 471-7A OTHER APPROVAL CITY APPROVAL 110111 ~,, PA1'1GAE.l"':. .. ·,r:-~·-' . -- lANl)CUN5GiTAr...:Ts.. lr-.;c SEE SHEET 3 FOR TOP OF WALL SWALE AND DRAIN DETAILS IN FEET ) 1 inch = 40 ft. 1 Ai:,· (31.t(t. r DATE INITIAL REVISION DESCRIPTION DATE INITIAL INITIAL ENGINEER OF WORK OTHER APPROVAL CITY APPROVAL --------------- MUROYA ROUGH GRADING PLAN GLEN K. ENGINEERING MANAGER PE 41204 EXPIRES 3 31 13 OWN BY: CHKD BY: RVWD BY: JG DM l, RB PROJECT NO. CT 06-27 lZ-t?·/3 DATE DATE DRAWING NO. 471-7A -.- - - i I ' ' ' I ' ' ! ! ! ' ' I ' ' ' i ' ' ' i ' ' ' I ' ' I >-. ~ ! i I lli ½:Ji ' ! -- ' 0:, "' t5 ~I ! . . o:i -"' " ~ cl'. ,1J Vi ~ ~ I ~ ' ' Sc-' ' . I ~1 , !'ii ...., ~" ~ i::: -- ' ...., • ,. >-. '8 c:, . h :a: i.;:; u " <5 -::::i "' " ~ ...., ' -_, .;, --• -<el ' c::, -- I ' -"< --· ~ "' f ~~ t ::-~ ~ 5' ::s h , a ~-I u -...., ' ' "' ,,. "' = ' "' -!li .... ~ "' . "'flf I ! <c ;, re -!--!-"" ' le'I ---+->------------1-+--+--+--,+-+---t---t--t-+-+--t--+-----t-t-+-+-+--+-t-+-<'tt----fltt---;;;Fi.-;!~rlr)-"t-t--lf----tc±i"'!' nn'"=-l"''?,.c.e7ic'"ci-,.,=t-+-+--+-+--i-+--+-+-+---t---+B1t!"'ih"i3it-~--+-'-'---t-+-+--+-+--i-t-+-+-+---t-t-+--F+"l"-"'+-t-+-+--+-+--i-t-+-+-+---t-t-"'-lt--'9'-'4--t~r ~ .:t-8~ f-~"'j -----t-t-+-+-+-----t-t-+-+---t---t--t-t-+--+-+-----t-t,,,;i=;c;c;.l,--;ct-,.;;ler-b.h¼.,--t---t--tf's--+-j-1"-f'lcf~il\--jtill-r--lllll-lTillfEF,fY-~:=l.-c--l-+--ll;al--\f----t-,c-l-·c+---cf,-cc-----hc-;p ~-5,-~2 _;-; iir---~ --e-"---t='='a7c-t---t---t--t--J-J--t--J--t--t-,, ~a ,o 6 111 E 1 Dt cP -1 \ ' "'" ~r----~ ,. 1-JGL n~ IT ,n,. re; .,, ry. @ 0. % -H L c::, ;:, -r ~ t j~ -. IN D WT, G OUC/ED RI/ R P \ / 7 , "A IN I / f3A IN 1 -1-, ' Ci -:i ~, --' JJ.2 ' 8" ~c: ( 47 R /GH' J IN S) ~ I 00' r-~ HI L.f " v, . 7_-1 v, ' ~ , "" D 1 Ire ' '--.. -I ' ' . 2i ,Ei D, TAI c Sl,!Et 3 , , ,_ '-__ ::-,,., __ '--"-, 21. '" r"-8, -,2 , c "zJi,,,,, PK v"' £---- -----t-t-+-+-+-t-t-+-+-+-+--t-+~-~ V--t--t--+-----t-t-+-++'--+~t-t-+-+','t-1+itt--t-'r~k::t--+.::;-tc:::!-::::t-+-+-+-+-t--+-+.~ ' _,,~~~1 .+-+-f--tt_'ll---'¥-f-+-fic\l-H;ff,\1?.\1--IJfiW,\l--l-+---+1 -+-t-+-++-+-t-t-+-+-+-+-t--+-+-t--+-t-t-+-t---t--t-t-t--t--+-----t-t-+-++--+-t-t---t-).. / ,' ..'. '-..___ FL 321 90 -I\'::./ ~ ~ "' ~: I ~ ~ ~ _<.J ._, If 'll ~fr-+--+--t-,k-+-+----il'llr+-··J <.,J,·vv -.v L,r --l-l--+-+-+-f-l--+-+ +-+--l-+-+-+-+--l-l--+-+-+-+-f-+-lm-+-+1-1A'hi\0J-'~~-z"';t1t';:;!-s:cl-l--+-$--c..jl~VL-icnl'Jf"S//.jllj.;'4--j-+-*-'4;,,'-/j"+¾-l VJc'+Jt-·F.4i;wj~/+v-+-~ +.:-i..:;"'~'+-+-+-+-'4'.l---l-+-~-+~t+-t-t--'E,-!--.6cl:"'l-t-+-+-+---t-t-+-+-+-+-t-+---H"'~-~':"~·Hcc:-Tt,jj;~s:-i--lCf""""'t=---t"'"'4"'~,,,.---j--t--+-+--+--+--+-+-+--+--+--+-t--+--+--+-+-t--+--t--+--+---t-t-+--+----t----t-t-+--+--+-+-t--+--t--+--+-~! / ,J'"C@ ...... ,....d.11 ,_.. -r, ..,, CL, ss RIF Rt D VEJ . s .:t ..) i::::i_ l•~ - -+--j-t--+-+--+---+--+-+--j-t--+-+--+--+ -+--+-+vo,io;i;Ot:==-FJ.-,'.J'rn,C:,,FS\c-,-,-'l!--ic;::lt---i-lf~~&,~~-/}''c,+/fi§l"l-----t#lul--fm-=-'+'.:.41--".:coi-cl_::_F/fc--+-f--t-+-++-+--ltiJ/<" RA 'tL FIL tR V 00 -1. I FPr::_ -, b NK: , -· r ~ ,/ '"& c PEID4' -- 0/.61 L , ' 1 / , : -+-+-f--+-+-+-+--j-+-+-+-+----lf'&f-fQl'')Hi~,n4.'J.b,4H'~l~/4-+~"~'ol--4(i-_l.-,"f--+-+-+-J--+-+-+-+-f--l--++-+---JCf!l_~~::j_el"Ujr'·(}E 1ui.11J I 1/ 6 ) I '---+-+-+--+-i--+-+-+-+---4-+--+-+-+---t-l--+-+--+--+-t-+--t-+-+-----t-t-+--t--+--t,-t-+-+-+--+-,t-+--+---i -+-+--+--ii--+-+---11 ; -1--1---l----j-t-+--+--+---j-t--+--+--+-+'-t--+-+--+----+-+-+--+--+--+-t--+--+--+-+·-· -t--+--+--+-+'-- ! 6 r 1 ~ fY" ..._ 2J.O ' ! 1 ) ~=={;:\~ '\:i:;:(';"ci-,+-r.C~Qf,,c:'§:"'ri::J-:c,--ir,=o::!1=--+ l:,\L:--:Lf--t--t-+-+-++++-+-+-+-+--t-l-l-t--t-+-+-+-++++-+-+-+-+--+-l-1-f--t--t-+-+-++++-+-+-+-+---t ' 'AL I t. ,,; , II --+-+--+-+-+-t-+--+-+-+--+-----i-t-.::' "';1tJ'f--t-+-+-+---t'-T1-'"-+-diP~'+++.c:,s:' +t-H-+t--t--t'i"-,71"'v1"'of,-'"::i--"..,_ir5·-"-J+'i...cP++-+-t-+-+-+-+---t-1--t-.l'Uli , l;i --'" 1/0 /Ff fJ -4 D SI AliR -- ---t-t--t--+---J---t----- * .r ' -J9--~ '-,/ N GRAPHIC SCALE 40 0 20 40 ,o &; t j t j ( IN FEET ) 1 inch = 40 It. ' !<J . Vi "'~ [;: i '< _, ,;;: f>E__I St E 3 0, ~t CAI ~ '' o, ,,_ ~ ',TRIIC I JR L 'ET. /LS ; 9., PR/VA TE STORM DRAIN DA TA TABLE BEARING/DEL TA RADIUS LENGTH TANGENT 589"48"40'E -37.12' 2 17'13"44' • 60.JJ' • 18.14' 9.14' 3 S89'59"5I 'E -75.38' 4 11'53"59' *' 100.00' •• 20.77' 10.42' 5 N78'06"01'E -30.22' 6 SI 7'22"52'E -33.26' 7 N55'20"35'W -85.84' 8 02'43'20" JOO.DO' 14.25' 7.13' 9 S52'37"1S'E -56.09' 10 05'04'42" 630.00' 55.84' 27.94' 11 N47'32"JJ'W -30.06' 12 N42"J0"06'E -38.71' 13 N15'49"50'E -42.22' 14 NOO'J4 "29'E -121.93' • USE 4' PIPE LENGHTS 111TH 5 DEGREE BEVEL ON ONE END ** USE 8' PIPE LENGHTS WITH 5 DEGREE BEVEL ON ONE END REMARKS 18" RCP (1350-0) 24" RCP WA TER TIGHT JOIN TS {1350-D) 24" RCP WATER TIGHT JOINTS 0350-0 24" RCP WATER TIGHT JOINTS '1350-D 24" RCP WAC/ER TIGHT JOINTS 1350-D 18" RCP WATER TIGHT JOINTS 1350-0 12" PVC SOR 35 12" PVC SOR 35 12" PVC SOR 35 12" PVC SOR 35 12" PVC SOR 35 10" PVC (SDR 35 IO" PVC (SOR 35 10" PVC (SDR 35 NOTE: SEE DRA »1NG 471-7 FOR WATER, SEWER, PR/VA TE STREET IMPROVEMENTS AND THE PROFILE FOR THE 12" PVC PRIVATE STORM DRAIN IN WHIC/E SAGE WAY - - i ' ' 1 ' ' ' I : ' I --1-+-+--+--+--+-+-+--+--+--+-t--+--+--+-+-t--+--t--t---t---i-t-+--+----t---+-i---t--t---r---+- I · -4irl-Ftl1,H1tt1H1·r-t-fm-1r----t-ti11i11111 ''-r .... I • - ' ' PROFILE SCALE': I ' I HOR/l: VERT: NOTE: THE SIC/E DISTANCE SETBACK AREAS SHALL NOT HA VE ANY OBSTRUCTIONS INCLUDING, STRUCTURES, GRADING, WALLS, FENCES, ETC. LANDSCAPING SHALL NOT THAT EXCEED JO" IN HEIGHT. TREATMENT CONTROL BMP TABLE /"=40' 1'=8' DESCRIPTION QUANTITY BIO-RETENTION BASIN 1 EACH "AS BUil T" /!.U~L> 1z-t7-t.5 P. E. 4.?6/~ EXP. G, ·:JO· /o DA TE REVIEWED BY: ~1) ~ ~-5-l'f IN DATE l------!----+-----------+----+--+---+------1 I SH5EET I CITY OF CARLS BAD ~7 ENGINEERING DEPARTMENT l___!_2'__j ~===-=========~=:'....'::::::==: GRADING PLANS FOR: MUROYA PRIVATE STORM DRAIN APPROVED:///. , /.., L -/],J, GLEN K. VAN, fESKI ~'4/r=-=~i=.....,_ ___ (o/111/fl ENGINEERING MANAGER PE 41204 EXPIRES 3/31/13 DATE /1\ AS-/3lllt..r DATE INITIAL ENGINEER OF WORK REVISION DESCRIPTION DATE INITIAL DATE INITIAL OTHER APPROVAL CITY APPROVAL DWN BY: JG I PROJECT NO. I DRAWING NO. CHKD BY: n" '" CT 06--27 471-7A RVWD BY: RB 110111 I : -~ 3 --+--+----+---+---+---t,-t---+-+--+----t---+--+---t-t---+---l---+--+---+--+-----t-t---+----l---+--t---+--+-+-l--+--+-+--+--+--+-+--l-+-+-+--+--+---+--+--l-t---+----l--+--+--+-+---+-l--+--+-+--+--+--+-+--l--+--+-+--+--+-~-+--+--+-+-l--+--+-+--+--+--+-+--l-+-+-+--+--+---+--+---+-t----J--c--Ct+--+--+---+--+--+--+---f-t--t-+-+--+-+--+---f-t--t-+-+o:i1-l---1~t--+-+--+----+---+---+---+-+--+-+--+--+---+--+--+ ~ ~ SC --., ' e:i ' I ' i c:, r;-' ,_, kl i --+--+--!--+-+---ti--+--+-----t-t-t--t-+--+-+-+---t-f-----t-+-+--+-+--+---t--t-t-+-+--+--+-+--+---f-t--t--+-+--+-+--+---f-1--t-+--+--+-+-+---t---fl--t-+--+~~~-~-+-++-+-+-+-l--+-+-++-+-+"-'-~t:i~L_+-+-+++-+-+--t-+-+-+-++-+-+--t-l--t-+---t!,t;;ltt--;:;f' ~3--' --+--+---+-t--+-+--+--+--t----+ ---t--+-+---H~4---t---fc-3t- !>:: -~ ;:-~ ~' ~ i I ~ -SC ~ kl --., ½ ~ "' ' i t,J ' l--t-++-+--+--t-l--t--t-++-+--+--l-l--t-+--t-+-+-+--l-l-+-~~'!f-+-+-2:'¾i'i~~~~+-+-+--t-+-+-+-+--l--+-+--t-l--l-+-++-+-+--l-l--l-+-+:~~"'~-+--l-l--+-+-+-+-+-+-+--t+:::i!.<-i--+--l-i_°'~~-+-l---l--t1--l--l-+-++-+-+--l-l--l-+-++-+--+--t-fS~"l-F-~ -H;l~-c-'iH--t-++-+--r1---t -+--+-t---t-1 -t-+--+----t---+c-tt!:--1-, t-~f-'l'--t-t-+--+--+--+-+---t-t-+-+--t--+-t--t------i----- C3 ~ (3 ~ ~ 3 ~ lt) S) -~ 1·--+-+--l---l--l-l---l-+-++-+--l--l-l---l---+-+--t--l--l---lu".jt"~'f-+~ Gklt,:,~G~--+-+--l-~+-,+-+++-+-+---1-+-+-+;i;Ht-+-+-+~~t-+--t--++-+-+--l-f----t-+-++~Hi'--f-f-l '-.. :l c:, ~ 1 I Cc ,_, t,, " K ¢rl 0 --------t.3'#{, S ;i C cS ~ ~ t f--f----j-----t--J----j---j'--t-+--f--t-ti;P-5--li'--,sr---j-j---f--t---t--+---t----f---J~! ~ ~ C'\J ;j ~ ,.-d-1 c-l~'<l~v,~::'Jc-f'-.;~"f-+-t---+--Jl-f--t--t---f--++-+--t-f--r.=c~+-+-f.:jf--'l\l}! --., • • kl • ~ 15 \ ,;; /< C ' - V) "' ' ~ ' ; ~ ~ \ .. ,,: <! ~ . ~ ~ ~ ~ ~ ;,-.: 11 .-.1 ::.c f>-~f--l-+-+++-+---+--1-l-+--1~0--/fE'-~'l+f/N--l';w,jlcJ.~4+--+--1i~ffi,t-,~, cH~~+-g~sJ6-g!--"'"fl--+--+--+--+--+---+-t---+-----· --+--+----t--t----+---t-t-+-+--+--+--t---+---+-t-+--+-Jw,,,cs,l,c~c,-·,"-,""c-,",,,"""•t-tl-+-o,::i:' l--+-+-+----t--+-+-----t-f-----t-iiroJc-i,,/--t--+---t--tt-+-+-+--+--+--<,<bh1't--.,::l-1-"<-h-""' V l'-. ~ ~ O:i -" I -= ,.. "°' . Q1;:!; 9 $?1~ SE. D TA C 'HE.i T I "-... , JI ' "' s:: I ' c:, c:, ( - CJ;) c::i 0 • -_)__ 'At ~-a; ill cl-:.. 'i( /, -· ,,_ -! . " CT '" nl . ' I c:,"' .:'; c'; ~ f 010 ;; r1, ii:"-:,,J _ ~ "-~ 0 ;.. I::' ~ "<o °' I 000= .JCF: ;:: 6'JICC ~ -- ,.,., ,.:~ ~ 2 C::0 J 02 / - V VU= ~ ~ i5 I I-• ,-?S BO 'TO i ?5,' 0 .::.a, V / T)1 E ,· A r, H A-N ' . , o" n 0 -,--_, \'.:'. . --,_ . - C P W17 ' 2 ' C >/Fl E __ ~ -,, £> ' 'C. ' --'Ji.,i;;!~ ~ I 4 PE, F:: A D ~VI AD ~ '-'= ,. .., lil' RI' RP 0~ R ./8' G. Al L ~ "~I? "'i ~ --,-t--t---t---t--t--+--t--t-t-+--t_-.. + .. ~1!,or'?i ..,Df''9/ll~~+t:t:'.tt7,,#-,-f-t'Nf}~ .. cN .. 11ffl.Hi"-t'R1 ffl'f-l-f--f--~-+++-f---j-f--f--+-+++-+J.4E-j~~+J---j/-o,~---1-f--+-+-+-+c'_,M;~'-c:;~ .,,. ~ -~'• ' I I vv -7 /TC,,..f-+-+-+--t---f-f---+-+--+--+--t--+--9/-:,,_;H--"'+1 ;:\--"f--t---f-t-t-+ ---+--+-+--+--t----t--t--+-t----t---t----t-l--t--t-+-+-+-+-+,,"'1"--t-/~frt-f1 -f',i;;-;t-1<:,H--str~-+-+-+--t--t-l-f--t--t-+--t-+-+-++---t--+-+-+--t--l-l-l--l--~l~~,jf .. c--f--t-l-l--1--1--l::"--l!>,;:/----f----i\ , , ;.,., \ , , Ki . '-.. "' ~ _, ::, -"'i l'1 ~ I / Q ,.,., ;.:!.ill es-o \ -, ~ a -'-.. ',)\ " ~ • I I I , , I ON 'RE E UT, FF WA LI "'" c:, "'i ; .., j-}! o:, w 1, ON ~RE 'E UT, FF WA L -~~:-t<-9----+-t--+--+-+ +-+-+--+---+---+-+-lt---+-+-+--+--+-+--+---t-t--+-+-f--+--+--+--+--+-+-+---tr-+-+-+--+--+-+-+---+-+-+-+--+----+--t----+---+-+-+--+--+--+----t---+--+-t---+--~+--+--+-+--+--- ,_:., ! 6' x Po' 1 0·1 \ I I';\ F,C/N~ 1 A,, t P 'AP µ .,_. " 7 I OOT7•/C, ' " ~-.J::,. --., I I i ' I I I --+--+----t--t----+---t-t-+-+--+--+----t---+-----t-+-+-+--+--+----t---+--+-t---+-+-+--+----t--+--+~r-+-+-+--+---+--+-+-l-t--+-+--+--+-+--+-l-t--+--+--+--+---+-+-+-t---+----l---+--+---+--+-+-t--+---J-+--+--+--+--+--+-+---l-l--t--+--+--+--+-+--+-l--+-+--+--+--+---f---+-+-+-1--+--+-+--+---+--+--+-l-t--+-+--+--+-+--+---+-+-+--+--+--+-+--+--+-+-+-+--+--+--t--+---- i ,, f/ I I ,-- ' I I j I . -, j • I LI I .... _.,Ill 'AJ • •~/ 1--IJ --+--+--+---+---+---t-+-+-+-+--+---+--+--+-t---+-+--+--+----t---+-+-t---+-+-+--+---+--+-+-1'--+-+-+--+--+-+-+--l-t--+-+--+--+--+-+--f-t---+----l--+--+--+-+---+-l--+--+-+--+--+--+-+-l--+--+-+--+---+---+-+-~-+--+--l,-J-+-+--+-~--+--+---+-t---+-+--+-+--+--+--+-+-+-f--+-+--+--+--+-+-+--l-t-+-+--+--+-+-l+--+--+--+--+-l-t--+-~-+--+--t---+--t-t--+--+--+--1--+-+l--+_f---+-+-- ! I i ' i i ' .-+-+--+-+-+--l-t---+-+--+--+--+-+--+-+--+--+--+--+--+-+---+-f--+--+-+--+--+-+-+---tf--+--+-+--+--+-+-+--l-+-+-+--+--+--+--+-1-+--+--+--+---l--+-+---l-l--+--+-+--+--+-+---l-f--+--+--+--+--+-+---l--lf--+-+--+--+--+-+--+--I-+-+-+--+--+-+---+-+--+--+-+' -+-l--+-+-+--+--+--+--+-l-+t--+-7 --+----t--t--+---+--+-+-+--+--+-t---+---t-+-+--:-,--+----t--,--+-t---+-+--+--+--H'PROF/LE SCALE: i i I HORIZ: 1"=40' • ":&i-~ ' ~ N GRAPHIC SCALE 40 0 BO bi•.; t j ( IN FEET ) 1 inch = 40 ft. PR/VA TE STORM DRAIN DA TA TABLE BEARING/DEL TA RADIUS LENGTH TANGENT REMARKS (it, 1 69'29"45' ** 100.00' '* 121.29' 69.37' 18" RCP (1350-0) I 2 S2Ji7"55'E -1.26' -18" RCP (1350-0 2 J 577i0"45'E -30.15' -78" RCP WATER TIGHT JOINTS (1350-0) J 4 N67'05"55'E -9.68' -18" RCP 1350-0 4 5 N67'09"00'E -ID.BJ' -/8" RCP 1350-0 5 6 N67'05"55'E -2.50' -12" PVC (SDR 35 6 7 N67'09"00'E -2.50' -12" PVC (SDR 35} 7 8 508'52'49"W 9 /5'25'2J" -10.84' -10" PVC {SOR 35) 300.00' 80.75' 40.62' 10• PVC (SOR 35 8 9 10 506'J2J4"E -67.41' -10" PVC SOR 35 11 20·59'13• 12 250.00' 91.58' 46.31' 10" PVC SOR J5l -71.42' -10" PVC, 'SDR 35• 5273422E=---+-----+-"""'"'=---1-=~---1---~~~ •• USE 8' PIPE LENCHTS mm 5 DECREE BEVEL ON ONE END CENTERUNE DA TA TABLE BEARING/DEL TA RAO/US LENGTH TANGENT S08"52'49"W -82.71' - 15'25'23" JOO.OD' 80.75' 40.62' S0632'J4"E -95.23' - 21'01'48" 100.00· 36.70' 18.56' S2734'22"E -97.46' - 14'34"52" 100.00· 25.45' 12.79' SI 2 ·59 'JO "E -129.06' - 77'03'08" 25.00' JJ.62' 19. 90' N89"57'22"E -J/.61' - NOTE: SEE ORA WING 471-7 FOR WATER, SEW1=R, PR/VA TE STREET IMPROVEMENTS AND THE PROFILE FOR THE 10" PVC PR/VA TE STORM DRAIN IN SWEET CLOVER LANE REMARKS - - - - - - - - - STORM DRAIN SEE SDG&E PERMISSION NOTES ON SHEET 2 SAN DIEGO GAS & ELECTRIC COMPANY REVIEWED BY:''( §<?:z9,v FRED CLARK DATE~~ LAND MANAGEMENT REPRESENTATIVE VALID FOR 18 MONTHS FROM SIGNATURE +--+--+-+--+--+--+---+--+--+--+---+--t-1--+-+-+-+---+--+--t--+--t----t----t----+-+--t--t-l+-t-] VERT: /"=8' 10+00 11+00 NOTE: THE SITE DISTANCE SETBACK AREAS SHALL NOT HA VE ANY OBSTRUCTIONS INCLUOING, STRUCTURES, GRADING, WALLS, FENCES, ETC. LANDSCAPING SHALL NOT 71/A T EXCEED JO" IN HEIGHT. TREATMENT CONTROL BMP TABLE DESCRIPTION QUANTITY BIO-RETENTION BASIN 1 EACH BIO-SWALE 4,566 SF P.F 4::,6/::> EXP. i,·3'0·/8 DATE REVIEWED BY: ~fa).~ IN TOR DATE i-------<---1------------+-------l----+----+------I I SH6EET I CITY OF CAR LS BAD ~7 ENGINEERING DEPARTMENT lJ2._J ~====--==========='--'===: 1----+---+-----------------+---t-----t---,----------i GRADING PLANS FOR: MUROYA PRIVATE STORM DRAIN APPROVED:/# ~I ./}, ./. GL£N K. VANJ'ESKI ~=?u:~r~./4=-KLK4=::,_· __ ($f/ll 1-=~~f----c~---t--,,----c--~---,---,---------------t---+------t------i ENGINEERINt:' MANAGER PE 41204 EXPIRES 3/31 /13 DATE IZ·{G,.(3 tff.3 /1\ Ao-(&./(le DATE INlllAL DATE INITIAL DA TE INlllAL ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL OWN BY: -~JG~,, I CHKD BY: PM qr RVWD BY: RB _ PROJECT NO. CT 06--27 I DRAWING NO. _ 471-7A 110111 345f-----t----1------I---!---+-'---t----:J:--:-::-:±.---+--+---.--+--+---+--+--+--+---1----, 4.0 ' __, NO TE. TOP OF W, LL E, EVA 7i NS __, DO N T IN LUDE THE " CA WHI H ~ SHAL BE DDED TO A L WA LS ,.__ -·-..._J __, ~ ~ Lc.i 335r--t-----l----+--+--+--+--+--+---+--+--+-l----1-----1----1-------l---1---L-_J__ 6'(1-. 00 EE SH TS 14 FO W, LL 330 E Al IN AL L ID E U! DI G 3) I C L L 1 ,, 2 J VE Tl A 1 ' 4' - ' 325 105. 4' 350!--t------l---t---+--+--+-+-+--+--+-+--+---1----1-------1----ll----l---1--_j_ _ _j__J_ _ _j_ 335 330 50 341. 0 - 341. 0 - 45 340. 0 340. 0 - 39. 0 - 40 12. 2.6 2.6 2.6 2.0 .00' 00' ~ ~ h. < a Q_ lJ..J G < -SC E I IN CALE: 7' ' ' ' 2 .67' 2 .00' h. < a Q_ lJ..J G < -SC 05. 4' EE HE. TS 14 FO W, LL ET /LS AL ORZO 30. 7' (, L D s U/ DI G 1) 1" = 20' J 164. 0 9.3 ' OF WALL EL£ OT CLV £ TH 2" L AD D Ti ALL 0.0 9.5 .0 8.5 Tl AL .00 -4.00 I,_ 00' .oo' .00 .00 4 32. 7' __, c.:i 351--t-------1---t---+-----J0::i~--+-+--r+-----+--+-+--+---l---l-----l---+---l---,-+----+----l-----+--l---l-- 3oi-----i----,---r----t---J---+-+-+-+-+--+--+--t----l------l--+--+--+--l----l-----'---I--+- G A L 1 BU LD N 3, 1 & 32 0 IZ N AL 7 TICA 7" ' ' 25f----------l----+---+---+--+--_,__ -~----t--+-+-+-+--+--t---t-----1----\-----+--+--+--+---I---- __, __, ~ ~ ~ 7 .61', RETAINING 8 .00' 6. o· I 30 .oo' OT£: TOP F WA L ELqvA TIO S 0 NO INCL DE £ 2'1 CAP WHIG >----,--£. D TAI ING WAL 6 'ND B GIN RET. /NIN WA L 7 ALL BE A OED O AL4 WAL S 1--l-----l---+--+--+--+--+--+---+--+--+--+--~+---l-----l---l--+---+--+--+--+------jJ40 160 33' 71.33' 13.3 4.00' h. ~ Q_ BUI I ING 14 --++---+---1-- lw lw G G < < -SC -SC BUil ING 13 c::, c::, 320 5?33' 7. 34 4.3 ' BUI DIN S 14 15 AND 16 05_0 , 3.3 ' LL 7 (BUILD/ GS 14, SCALE: 15, A D 16 HORI ONTAL 7" = o' ' RETAIN NG WALL VER T!CAL 1" = 4' D NO INCL DE T, £ 2" CAP 'HIGH S ALL £ AD ED ALL WALL 88. O' 6 ( UILD!NGS 7 3) J50r--t-----l----t--+--'s_t--.-+--.+---+---+--+--+.--+--++--l-----j---+--+-----+---+-/ .oo' 2.00' 32 oo' 20 oo' 345 342. 4 2. 342. 4 2. 341. 4 -2. 340f-----t----l------l---+~;;;,- ~ 8 ~ Q_ NO : TO OF 'ALL LEVA DO OT I GLUD THE 2" C SH L BE ADD£ TO LL W, NS WHCH LS 340 15 sn s 0.5 ' VE T. 'HORIZ 40. 0 __, ~ < G ~ 34 .50 OP S 1.3 ' ~~P#:~m \®'1~\;J__j__J.~:_+--~12-_l'.]~R'!_l_:_T.+-_j__L __ _ :irait Jf,_·; i ;1r.~~'i'-r,~~'fiFi~ , ~-.:Ji -~~;:·~~\ ~ii~f~ ,·.</"'·...,_--; ,'j;_G, -. ':'.J: ?s:":::"-P'..:t-" -'~-1 >,.1;>-c:, ~ 41.5 -.33' ,- h. 8 Q_ lw 335r--t------l----t----t---+.;=--.!;/-f---l----t---l-----il""4--+--+--+---l-l---+---l----+----l-----1----1-335 lw __, 18. 7' 8.0 ' 37. 3' 6 67' 8.00' 330r--t-----l----t--+--+-4---t---+--+-_L_+--+--+--++--1-----jL----+--+-----+---+-3301----1------1----+---+---r--+--+-+-+-+-+-+---+--F,.,bh----1----l-----+--+---l----1---+-- 8 .00' S £ HE i TS 14 OR WA L L 1' J SEE SHEET 4 FOR WALL LOCA T/ONS NOTE: ALL WALLS TO BE 6" TALL SLUMP BLOCK WITH 2" CAPS THE 2" WALL CAPS SHALL HAVE A 1" OVERHANG ON TH£ FRONT AND ENDS. WALL COLOR PER LANDSCAPE PLAN 471-7L -SHT 7 By: ~ti.bate f().Q7-fti/l{ Name: Richard C. Brasher R_C,E.: 43819 exp: 6-30-2013 ·9PANGAEA LANO CONSULTANTS, INC. HE. TS 14 WALL ET /LS UI DI ) 11 AS BUIL T 11 /lUdlu,L lZ-l7-lo RCE 4q0/~ EXP. G'30-(S DATE REVIEw'ED BY, DATE I SH,EET I CITY OF CARLSBAD ~7 t====1====t============================t====t===:1====1====: ENGINEERING DEPARTMENT l___l'?'_J t-----+--+----------------+---t----1-----!-----I GRADING PLANS FOR: MUROYA DATE INITIAL f--D_AT-=-E-'-l-'-Nl-'-TIA-=L-1-D:.:.A___:TE:____,__::_IN::...ITlccAL=-i g:o B;~ ~~,; PROJECT NO. DRAWING NO. ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL RVWD BY:---"R'"'-BJLC CT 06-27 471-7A 110111 340 335 330 325 33 33 331 33. 122. oo· NO £: 7i P OF WALL ELEV TION " SH LL B ADD D TO ALL ALLS 9. 3' 13. 3' 99. 4' .00 - 1. 1. 332 00 1. 331. 50 1. 331. 00 1.3 330. 50 1. -.J -.J ~ 13. 1 8.6 c::i CJ 12 .00' G WALL 70 ( EH ND B IL IN 3) I I ' a' " s 0 1zpN TA 1 2 Vi RTi CA ' 335r----t---t----t---t--:-.J,t---t----t---;l;-;;--;;-=l,----t----i-r---t---t---j--------t-----t---r----t-----J -.J ;!= ,____,_ _ _,___, _ _,_ _ _,___ = NOT, · TOP OF W, LL EL VA 77 NS < DO OT IN LUOE THE " CAP WHIG G SHA BE f ODED TO A L WA S p D 9. 5 ~ 3 .83 330 1---r---r--,----i==::::'.:m ---+--+----+--+--+----+--+-----+ SE OR A L ETA LS 6 .67' J20f------+--+----+--+--+----+--+-----,---+--+----+-'---+--+----+--+----+--+--+----+ T INN 9 ( ID BUil I G 0 SCA £: H T L 1 " 0 ERT!C L 1" SEE SHEET 4 FOR WALL LOCA T/ONS NOTE: ALL WALLS TO BE 6" TALL SLUMP BLOCK WITH 2" CAPS THE 2" WALL CAPS SHALL HA VE A 1" OVERHANG ON THE FRONT AND ENDS. WALL COLOR PER LANDSCAPE PLAN 471-lL SHT 7 NOTE: WALL 8 IS A PLANTABLE VERDURA WALL SEE WALL PROFILE ON SHEET 12 3' 3 ' ' 335 ' 330 325 320 i J RiT, IN/ S A [: I OTE: TOP WAL ELE A TION 0 NO INCL DE E 2" CAP 'HIGH HALL BE A ED ALL WALL - 2. 6 ' 3 ' 3 2. 3 2. 3 7. -.J -.J ~ 1-.._ ~ -.J < -.J ~ G Q_ il5 lu c::i G CJ < <:( <:::) 14.0 ' 14 00' 0) 14. O' 1 .00' 9 . 3' 9.3~' 3 . 33' 37.3 ' s E H£ TS 14 OR WA L ETA/LS ID OF G w, LL 7 7 ( Ti [ U/ DI G 24 VfRt!c H RI 0 1 TA~ " o' L 1 ,, 4' - ' 110111 11 AS BUIL T11 ~.L.. IZ-l7-l3 RCE 4.!,e,(~ EXP, G,.zo.,s DATE REVIE\JED BY, DATE I s8HEET I CITY OF CARLSBAD ~7 1---+--+---------------t-----t-----t-----t------J ENGINEERING DEPARTMENT l___!2_j 1---+--+---------------t-----t-----t-----t------J ~G==RAD::::==IN:::'..G'.::::::P::;:LAN:::;;:;:S :::;F:;:;OR;::: =========::::::'....':=~ MUROYA B, P~♦ R"ec+e· (0-"l•'ldf Nome: Richard C. Brasher R.C.E.: 43819 exp: 6-30-2013 yiPANGAEA 1 /'I&-OOll.7." DATE INITIAL LAND CONSUL TANIS, INC ENGINEER OF WORK REVISION DESCRIPTION 4.67' 5.3 ' 337 50Ti 33 .50 ~ -.J 1-... ~ 1-... -.J ~ 1'.3 ~ ~ C) ~ C) Q lu Q < lJJ ~ lJJ G l---+-+----+--+---ee+-;;;~+,i.-!-+h?--1----¾f-----l-+----l----l--+-------+-+-----1---l---1--+----l--.-----1f---G G l...J "!; 'I' "<: c::, c::, 0:, 0:, 8 oo' 5.3 , 4.67 12.6 SE OR WA L £TA LS R T, IN! G W, LL 1 S A £: H RI O TA S R T SI E OF B IL o', Rtic L 1" = 4' NO TE. TOP OF W, LL EL VA TIO S DO N T IN UDE E 2 CAP WHIC SHAL BE DDED TO AL WAL S .67' 3 .33 6. 7' -.J -.J -.J -.J ~ ~ 3351-----1----+---I-----I--- 330 325 320 3 3.0 TF 331 00 F (.!) <'. ,• 00' 6 67' '<: a 2.00 0) E HE TS 14 OR WAL TA IN/ G W, LL 7 B IL IN 2 AL N AL £: H 0 TA ' " 0: Vi R 1C L 7" = 4' SEE SHEET 4 FOR WALL LOCA T!ONS NOTE: ALL WALLS TO BE 6" TALL SLUMP BLOCK WITH 2" CAPS TH£ 2 11 WALL CAPS SHALL HAVE A 1" OVERHANG ON TH£ FRONT AND ENDS. WALL COLOR PER LANDSCAPE PLAN 41-7L SHT 7 IN 17) ET, /LS TR E) 90 (FOR SDG NO £: TO OF 'ALL LEVA ONS 37. 'AL D TAI S G WALL 1 L B SCAL!f-C--Fl-l~-fiPi'c/-/-rffiH!Lf-Jr-hl-l-+---'"f---Af-+-+-+H='IN~-,A-IJ---+~"~----4+-1-+-- 33 5 {FOR SD SCALE: I I I 1;'&1 clOf NOT, ':· TOI OF Pl LL E, EVATI )NS DO •10T IP 'CLUDE THE 0 " CA, WHIC 1-i SHA L BE 4DDEI TO A L WA LS 1. J,"' 14.l· 1 vi. 3,: 1.: 9.5 , ,,; ~1.33" 33. V 336. w 335 83 w "--.. ~ I/ 335. .3 T 'I 335. [33 I w-------' v >35.-3 Tl ,, . . , ·-f--·-~,; ,, r----r---, 33.8 13 TF T~ v t---OA 1GLE POii f'---.._ 90. NGL-PO NT V 4_nn .~ 114.! 3' ["--.. 4.00 , 6.B~ ,/ Si E 5 HEE TS 4 I OR WA1 L D [TA LS Kt IA (NII i1G WI !LL lb +-. 42n . RA s ,_Of nMt R SY BL '-I /Z1 DN-~AL 7 ' 2 D' V£ RT! t7AL -- ' OTE.· TO WAL ELE :4 TIO) 0 ND IN 2• CAP 'HICH 0 A GLE Po11r 4.oor 6.8 ' 90 NGL PONT 4.0 ' SE S EE S 14 F R I 'AL, R T, IN/NG W, LL 7 ' DC 2t r) 7 t,, 4 ' -~I {FOR SD ,l;,-'(t'-r--j------'J-'2j~-+--f-lr-tt--f\j---"-.Hf-H-r'ib'l--f--ft-r'--f++-llf-+f--ftc/-f,-J--,l----',--j/---+--+--- SCALE: R z TfL 1" = 20', YE4TI AL 7' NOT£: WALL 14 IS A PLANTABLE VERDURA WALL SEE WALL PROFILE ON SHEET 11 4 LOT LINE AND BACK YARD FENCE STRATA GRID 200 WILL 6.5' ENCROACH 2.5' MAX. INTO i---i~f----1 BUILDING 1 ____ ...!..F.!'..'.IN1::::Sl'.'..!:.HE.':..':D'.....:P'=.'.A~D+-----"s--=~~'::Lll..l-_j:2'.:::5~L::_::O::::_G'.::'.:GIA'..'.....__ ___ _ 3401-. FINAL jLA YER OF STRATA GRID 200 lP BE 5.0' BELOW FINISH'fD PAD I PROPOSED LOPE LOT 4 LOT 3 5.0' _ PAQ_ 51/iALLPIR THE -'---f----,,.-9 / PRECISE GRADING PLAN /' ~ EXISTING GROUND ~I STRATA GRID 200 OR I I I J. O' I II TYP. J....-,,:.........., EQUIVALENT TO BE SPACED J. O' VERT/CALLY THE ENTIRE HEIGHT OF THE SLOPE 3201---1-----------+---l--,----,L------+--------' , , I ENTIRE SLOPE TO BE LANDSCAPE ~ l(l.0 ~ (TYP.) FOR SURFACE STABILITY ,_._'--.I NO GRADING OR CONSTRUCTION EQUIPMENT ALLOWED WITHIN LOT 4 11 11 ______-1.5: 1 BUTTRESS FILL BACKCUT I 1~ MINIMUM ,__~ I I , 9 1,'0;1 STRATA GRID 00 OR EQUIVALENT <-S· 1-----c/.J.-..';._. TYP. ,. I I I -I 10.0' J00l---,---------f-,--+-f--+----------1------------1 HABITAT/ HMP FENCE SET ON THE LOT LINE EXISTING GROUND ------ I I I I EXTEND STRATA GRID 200 OR EQUIVALENT TO BACK CUT 1: I BUTTRESS KEY BACK UT -VERTICAL BUTTRESS i BUTTRESS FILL KEY (DEPTH OF BUTRESS CUT MAX. 4' HIGH ,,. _,,. 1 KEY TO BE DETERMINED BY THE SOILS -1: 1 BUTTRESS COT---+<~ 1.:,. I ENGINEER DURING THE GRADING OPERA T/ON) OVER 4' DEEP 280Hc::::::--t=~~=±:---t----------r-----------j I .~~'I BUTTRESS RAIN PER SOILS REPORT TO ~-OUTLET AT THE LOWEST POINT (TOE OF SLOPE DA Yi IGHT WITH NATURAL GROUND {ELEV 281. 0) SECTION ·c-c' STRATA GRID 200 REINFORCED BUTTRESS FILL NOT TO SCALE SEE SHEET 4 FOR SECTION 'c-c' LOCA T!ON AND LIMITS OF THE BUTTRESS FILL REINFORCED BUTTRESS FILL IS REQUIRED FOR ALL SLOPES STEEPER THAT 2: 1 By ~4;/""te·IQ•tfT-'Ja/ Name: Richard C. Brasher R.C.E.: 43819 exp: 6-30-2013 .. 9PANGAEA 11 AS BUIL T 11 ~- RCE ~/:, EXP, C,·oCJ·/5 DATE REVIEl,IED BY1 ~ 1,). # J,,4, 3-5 ·1~ I DATE i-?H9EET I CITY OF CARLSBAD ~7 ~-+---+-------------+---+---+---+---I ENGINEERING DEPARTMENT U2.__j ~-+---+-------------+---+---+---+---I ~-+---+-------------+---+---+---+---I GRADING PLANS FOR: MUROYA RETAINING WALL PROFILES 110111 1.01 DESCRIPTION A. WORK SHALL CONSIST OF FURNISHING AND CONSTRUCTING A VERDURA SEGMENTAL RETAINING WALL SYSTEM IN ACCORDANCE WITH THESE SPECIFICATIONS AND IN REASONABLY CLOSE CONFORMITY WITH THE LINES, GRADES, DESIGN AND DIMENSIONS SHOWN ON THESE PLANS. B. WORK INCLUDES PREPARING FOUNDATION SOIL, FURNISHING AND INSTALLING LEVELING PAO (IF REQUIRED), PLANTABLE SOIL UNIT FILL, AND BACKFILL TO THE LINES AND GRADES SHOWN ON THE CONSTRUCTION DRAWINGS. C. WORK INCLUDES FURNISHING AND INSTALLING GEOSYNTHETIC SOIL REINFORCEMENT OF THE TYPE, SIZE, LOCATION, STRENGTH AND LENGTHS DESIGNATED ON THE CONSTRUCTION DRAWINGS. D. WORK INCLUDES FURNISHING AND INSTALLING FOUNDATION DRAIN, SUBDRAIN AND OTHER WALL-RELATED DRAINAGE SYSTEMS THAT MAY BE SHOWN ON THE CONSTRUCTION DRAWINGS. E. CALCULATIONS ADDRESSING INTERNAL AND EXTERNAL STABILITY PROVIDED IN DOCUMENTATION AS NOTED IN TABLE 1. 1 .02 REFERENCE DOCUMENTS A. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) 1) ASTM C 1372-SPECIFICATION FOR SEGMENTAL RETAINING WALL UNITS 2) ASTM D-3080-DIRECT SHEAR TEST OF SOILS UNDER CONSOLIDATED DRAINED CONDITIONS 3) ASTM D-1557-LABORATORY COMPACTION CHARACTERISTICS OF SOIL MODIFIED PROCTOR 4) ASTM D-4318-LIQUID LIMIT, PLASTIC LIMIT AND PLASTICITY INDEX OF SOILS 5) ASTM D-4595-TENSILE PRIORITIES OF GEOTEXTILES -WIDE WIDTH STRIP 6) ASTM D-5262-UNCONFINED TENSION CREEP BEHAVIOR OF GEOSYNTHETICS 7) ASTM D-3034-POLYVINYL CHLORIDE PIPE (PVC) B) ASTM D-4829-EXPANSION INDEX OF SOILS 9) ASTM C-140-STD. SPEC. FOR SAMPLING ANO TESTING CONCRETE MASONRY UNITS 10) ASTM C-145-STD. SPEC. FOR SOLID LOAD BEARING CONCRETE MASONRY UNITS B. GEOSYNTHETIC RESEARCH INSTITUTE (GRI) 1) GRI-GG4-DETERMINATION OF LONG TERM DESIGN STRENGTH OF GEOGRIDS 2) GRI-GT7-DETERMINATION OF LONG TERM DESIGN STRENGTH OF GEOTEXTILES 3) GRI-GG5-DETERMINATION OF GEOGRID (SOIL) PULLOUT C. NATIONAL CONCRETE MASONRY ASSOCIATION (NCMA) 1) NCMA SRWU-1-TEST METHOD FOR DETERMINING CONNECTION STRENGTH OF SRW UNITS 2) NCMA SRWU-2-TEST METHOD FOR DETERMINING SHEAR STRENGTH OF SRW UNITS 3) "DESIGN MANUAL FOR SEGMENTAL RETAINING WALLS, 2ND EDITION." (1997) D. ICC EVALUATION SERVICES, INC. (FORMERLY INTERNATIONAL CONFERENCE OF BUILDING OFFICIALS (ICBO)) ICC ES ER-5515-VERDURA AND CANDURA SEGMENTAL RETAINING WALL SYSTEMS 1.03 SUBMITTALS/CERTIFICATION A. CONTRACTOR SHALL SUBMIT A MANUFACTURER'S CERTIFICATION PRIOR TO START OF WORK THAT THE RETAINING WALL SYSTEM COMPONENTS MEET THE REQUIREMENTS OF THESE SPECIFICATION AND STRUCTURE DESIGN PLANS. B. CONTRACTOR SHALL SUBMIT A TEST REPORT DOCUMENTING STRENGTH OF SPECIFIC MODULAR CONCRETE UNIT AND GEOSYNTHETIC REINFORCEMENT CONNECTION TO VERDURA BLOCKS. THE MAXIMUM DESIGN TENSILE LOAD OF THE GEOSYNTHETIC-FACING UNIT CONNECTION AT A MAXIMUM NORMAL FORCE AS IS APPROPRIATE FOR THE VERTICAL LOCATION OF REINFORCEMENT UNDER CONSIDERATION. THE CONNECTION STRENGTH EVALUATION SHALL BE PERFORMED IN ACCORDANCE WITH NCMA TEST METHOD SRWU-1. 1.04 QUALITY ASSURANCE A. CONTRACTOR SHALL SUBMIT CERTIFICATION, PRIOR TO START OF WORK, THAT THE RETAINING WALL SYSTEM (MODULAR CONCRETE UNITS AND SPECIFIC GEOSYNTHETIC): 1) HAS BEEN SUCCESSFULLY UTILIZED ON A MINIMUM OF FIVE (5) SIMILAR PROJECTS, I.E., HEIGHT, SOIL FILL TYPES, ERECTION TOLERANCES, ETC.; AND ... 2) HAS BEEN SUCCESSFULLY INSTALLED ON A MINIMUM OF 1 MILLION SQUARE FEET (93,000 M~2) OF RETAINING WALLS. B. CONTRACTOR SHALL SUBMIT A LIST OF FIVE (5) PREVIOUSLY CONSTRUCTED PROJECTS OF SIMILAR SIZE AND MAGNITUDE BY THE WALL INSTALLER WHERE THE SPECIFIC RETAINING WALL SYSTEM HAS BEEN CONSTRUCTED SUCCESSFULLY. CONTACT NAMES AND TELEPHONE NUMBERS SHALL BE LISTED FOR EACH PROJECT. C. CONTRACTOR SHALL PROVIDE EVIDENCE THAT THE DESIGN ENGINEER HAS A MINIMUM OF FIVE YEARS OF DOCUMENTABLE EXPERIENCE IN THE DESIGN OF REINFORCED SOIL STRUCTURES. D. OWNER SHALL PROVIDE SOIL TESTING AND QUALITY ASSURANCE DURING EARTHWORK AND WALL CONSTRUCTION OPERATION. OWNER'S QUALITY ASSURANCE PROGRAM DOES NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY FOR WALL PERFORMANCE. 1.05 DELIVERY, STORAGE AND HANDLING A. CONTRACTOR SHALL CHECK ALL MATERIALS UPON DELIVERY TO ASSURE THAT THE PROPER TYPE, GRADE, AND CERTIFICATION HAVE BEEN RECEIVED. B. CONTRACTOR SHALL PROTECT ALL MATERIALS FROM DAMAGE DUE TO JOBSITE CONDITIONS AND IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. DAMAGED MATERIALS SHALL NOT BE INCORPORATED INTO THE WORK. PART 2: PRODUCTS 2.01 MODULAR CONCRETE RETAINING WALL UNITS A. MODULAR CONCRETE UNITS SHALL BE VERDURA, AS INDICATED IN TABLE 2. B. MODULAR CONCRETE MATERIALS SHALL CONFORM TO THE REQUIREMENTS OF ASTM C-1372 -STANDARD SPECIFICATIONS FOR SRW UNITS. C. MODULAR CONCRETE UNITS SHALL CONFORM TO THE FOLLOWING STRUCTURAL AND GEOMETRIC REQUIREMENTS MEASURED IN ACCORDANCE WITH SECTION 1.03 AND OTHER APPROPRIATE REFERENCES: * COMPRESSIBLE STRENGTH = 4000 PSI (27,000 KPA) · MINIMUM AT 28 DAYS; * MOISTURE ABSORPTION = 8% MAXIMUM FOR STANDARD WEIGHT AGGREGATES; * BATTER = AS INDICATED IN TABLE 2. * DIMENSIONAL TOLERANCES = ± 1 /8" (3MM) FROM NOMINAL UNIT DIMENSIONS (NOT INCLUDING EXPOSED AGGREGATE FACE TEXTURE), ±1/8" (3 MM) UNIT HEIGHT -TOP AND BOTTOM PLANES. 2.02 GEOSYNTHETIC-CONCRETE BLOCK CONNECTORS A. CONNECTORS SHALL BE 1 INCH (2.5 CM) DIAMETER OR GREATER SCHEDULE 80 PIPE OR EQUIVALENT AND MUST BE CAPABLE OF PROVIDING POSITIVE MECHANICAL INTERLOCK BETWEEN GEOSYNTHETIC SOIL REINFORCEMENT MATERIAL (GEOTEXTILE OR GEOGRID) AND BLOCK. B. CONNECTORS SHALL BE CAPABLE OF HOLDING THE GEOSYNTHETIC SOIL REINFORCEMENT IN THE PROPER DESIGN POSITION DURING GEOSYNTHETIC PRE-TENSIONING AND BACKFILLING PROCEDURES 2.03 UNIT FILL A. UNIT FILL SHALL CONSIST OF SOILS USf FOR WALL BACKFILL OR AS SPECIFIED BY THE PROJECT LANDSCAPE ARCHITECT. 2.04 SOIL FILL NOTE: A. SELECT ENGINEERED FILL FOR THE REl~1FORCED/INFILL SOIL AND RETAINED/BACKFILL SOIL. SOIL ZONES SHALL BE ON-SITE OR IMPORTED SOILS ACCEPTEI BY THE GEOTECHNICAL ENGINEER OF RECORD AND HAVING THE SOIL STRENGTH PROPERTIES AS NOTED TABL 3 WHEN COMPACTED TO 90% RELATIVE COMPACTION PER ASTM D-1557. B. ENGINEERED FILL MATERIALS FOR THE -t'PER ONE (1) FOOT IMMEDIATELY BEHIND THE TOPMOST BLOCK AND ABOVE THE ZONE OF SELECTED SOIL MATERIAi ' AS SHOWN ON THE TYPICAL SECTION SHALL BE COMPROMISED OF MORE IMPERVIOUS ON-SITE SOILS. C. MATERIALS CAN BE SITE-EXCAVATED SI · .S WHERE THE ABOVE REQUIREMENTS CAN BE MET. UNSUITABLE SOILS (HIGH PLASTIC CLAYS OR ORGANIC SOie:..) SHALL NOT BE USED. D. SOIL WITHIN 6 INCHES OF A GEOGRID LAYER SHALL NOT CONTAIN PARTICLES LARGER THAN 6 INCHES. E. GEOTECHNICAL-ENGINEER-OF-RECORD ~ HALL PERFORM LABORATORY TESTS ON THE SOIL MATERIAL PROPOSED FOR USE TO ENSURE COMPLIANCE WITH Rf~ ,JIREMENTS STATED IN SECTION 2.05, ITEM A AS OUTLINED ABOVE PRIOR TO THE PLACEMENT OF THE MATERIALS F ., , THE SELECT BACKFILL/REINFORCED SOIL ZONE. WORK CONTAINED WITHIN THESE PLANS SHALL NC . COMMENCE UNTIL AN ENCROACHMENT PERMIT ANI I OR GRADING PERMIT HAS BEEN ISSUED. THE PRIVATE ENGINEER SIGNING THESE PLANS IS RESPONSIBLI FOR ASSURING THE ACCURACY AND ACCEPTIBILITY OF THE S1 CTIJRAL DESIGN HEREON. IN THE EVENT OF DISCREPANCIES AFTER JUF JICTIONAL APPROVAL OR DURING CONSTRUCTION, THE PRIVATE ENGINEEF ;HALL BE RESPONSIBLE FOR DETERMINING AN ACCEPTABLE SOLUTION At~ REVISING THE PLANS FOR APPROVAL BY THE CITY. ... --------------~ VERDURA®SEGMENTAL WALL PLANS 2.05 GEOGRID SOIL REINFORCEMENT A. GEOSYNTHETIC REINFORCEMENT SHALL BE OF THE TYPE SHOWN ON THESE DESIGN PLANS. THE CONTRACTOR, OR THE SUPPLIER AS HIS AGENT, SHALL FURNISH THE GEOTECHNICAL ENGINEER OF RECORD WITH A CERTIFICATE OF COMPLIANCE CERTIFYING THAT THE GEOSYNTHETIC REINFORCEMENT COMPLIES WITH THIS SECTION OF THE SPECIFICATIONS, THE DRAWINGS AND THE DESIGN CALCULATIONS. 2.06 DRAINAGE PIPE A. PROVIDE A PERFORATED AND SOLID PIPING SYSTEM CONSISTING OF 4-INCH-DIAMETER SCHEDULE 40 PVC PIPE AS SHOWN ON THESE PLANS. 2.07 FILTER FABRIC A. PROVIDE FILTER FABRIC CONSISTING OF MIRAFI 140N OR EQUIVALENT AS SPECIFIED BY THE GEOTECHNICAL ENGINEER OF RECORD. PART 3: EXECUTION 3.01 SURFACE CONDITIONS A. PRIOR TO WORK, CAREFULLY INSPECT PREVIOUS GRADING WORK. VERIFY THAT ALL SUCH WORK IS COMPLETE TO THE POINT WHERE THIS INSTALLATION MAY PROPERLY COMMENCE. B. VERIFY THAT WORK OF THIS SECTION MAY BE INSTALLED IN STRICT ACCORDANCE WITH THE ORIGINAL DESIGN, ALL PERTINENT CODES AND REGULATIONS. C. VERIFY WALL DRAINAGE SYSTEM IS COORDINATED WITH POINTS OF CONNECTION TO STORM DRAINAGE SYSTEM OR OTHER PROPER DRAINAGE DEVICE. D. IN THE EVENT OF DISCREPANCY, IMMEDIATELY NOTIFY THE PROJECT COORDINATOR. DO NOT PROCEED WITH INSTALLATION UNTIL ALL SUCH DISCREPANCIES HAVE BEEN RESOLVED. 3.02 LAYOUT A. VERIFY ALL STAKING AND FIELD ENGINEERING REQUIRED TO IMPLEMENT THE WORK AS SHOWN ON THE DRAWINGS. B. PROTECT ALL STAKES AND BENCHMARKS. REPLACE ALL STAKES AND BENCHMARKS DAMAGED DURING THE COURSE OF CONSTRUCTION AT NO COST TO OWNER. C. SET GRADE STAKES USING INSTRUMENT TECHNOLOGY, AT 50-FOOT GRID INTERVALS AT AREAS WHERE GRADIENTS ARE LESS THAN 2 PERCENT. SET GRADE STAKES USING INSTRUMENT TECHNOLOGY, 25-FOOT-INTERVALS AT AREAS WHERE GRADES ARE GREATER THAN 2 PERCENT. D. HAND TRIM EXCAVATIONS TO REQUIRED ELEVATIONS. CORRECT OVER-EXCAVATION WITH FILL MATERIALS APPROVED BY THE GEOTECHNICAL ENGINEER OF RECORD. E. REMOVE LARGE STONES OR OTHER HARD MATTER WHICH WOULD DAMAGE PIPES OR IMPEDE CONSISTENT BACKFILLING OR COMPACTION. F. PROVIDE ALL EQUIPMENT OF SUCH TYPE, FUNCTION, AND DESIGN AS REQUIRED TO ACHIEVE SPECIFIC VALUES. WHERE NECESSARY, PROVIDE RUBBER-TIRED AND VIBRATORY SHEEPSFOOT COMPACTION EQUIPMENT. 3.03 SUBSURFACE DRAINAGE SYSTEM INSTALLATION A. EXCAVATE TRENCHES FOR DRAINAGE PIPING SHOWN ON DRAWINGS. B. LAY FILTER FABRIC IN BOTTOM OF EXCAVATION PRIOR TO PLACING PERMEABLE FILL. PLACE MINIMUM 4-INCH-THICK BED OF PERMEABLE FILL OVER FABRIC C. INSTALL AND JOIN PIPE AND PIPE FITTINGS IN ACCORDANCE WITH MANUFACTURERS INSTRUCTIONS. INSTALL DRAINAGE PIPING WITH PERFORATIONS DOWN. JOIN PIPE ENDS AND SOLVENT ENDS. D. LAY PIPE TO SLOPE GRADIENTS NOTED ON DRAWINGS, WITH MAXIMUM VARIATION FROM TRUE SLOPE OF 1/8 INCH IN 10 FEET. E. BACKFILL PIPE USING FILTER AGGREGATE. F. WRAP FILTER FABRIC AROUND AGGREGATE COVER AND TUCK LOOSE EDGE BETWEEN AGGREGATE COVER AND TUCK LOOSE EDGE BETWEEN AGGREGATE AND SOIL. G. INSTALL BACKFILL IN ACCORDANCE WITH THE PROVISIONS OF THIS SECTION. DO NOT DISPLACE OR DAMAGE PIPE WHEN COMPACTING. H. EXTEND NON-PERFORATED PIPING TO DRAINAGE PIPING AS SHOWN ON DRAWINGS. PROVIDE TRENCHING, BEDDING, AND BACKFILL AS REQUIRED. 3.04 EXCAVATION A. CONTRACTOR SHALL EXCAVATE TO THE LINES AND GRADES SHOWN ON THE CONSTRUCTION DRAWINGS. OWNER'S REPRESENTATIVE SHALL INSPECT THE EXCAVATION AND APPROVE PRIOR TO PLACEMENT OF LEVELING MATERIAL OR FILL SOILS. PROOF ROLL FOUNDATION AREA AS DIRECTED BY THE GEOTECHNICAL ENGINEER OF RECORD TO DETERMINE IF REMEDIAL WORK IS REQUIRED. B. OVER-EXCAVATION AND REPLACEMENT OF UNSUITABLE FOUNDATION SOILS AND REPLACEMENT WITH APPROVED COMPACTED FILL WILL BE COMPENSATED AS AGREED UPON WITH THE OWNER. 3.05 MODULAR UNIT INSTALLATION A. FIRST COURSE OF UNITS SHALL BE PLACED ON THE FOUNDATION SOILS OR LEVELING PAD, AS DIRECTED BY THE WALL DESIGNER, AT THE APPROPRIATE LINES AND GRADES. MOLDED SURFACE OF MODULAR UNITS SHALL BE USED FOR ALIGNMENT. ALIGNMENT AND LEVEL SHALL BE CHECKED IN ALL DIRECTIONS AND ENSURE THAT ALL UNITS ARE IN FULL CONTACT WITH THE BASE AND PROPERLY SEATED. 8. UNITS SHALL BE PLACED ON THE FOUNDATION SOILS WITH A MAXIMUM DISTANCE OF 9 INCHES (23 CM) BETWEEN ADJACENT UNITS. THE SPACING BETWEEN UNITS INSTALLED IN CURVED REGIONS (CONCAVE OR CONVEX) MUST BE ADJUSTED ACCORDINGLY AND SUCH THAT THE RUNNING BOND LAYOUT IS MAINTAINED. VERTICALLY ADJACENT UNITS SHALL BE CENTERED ON UNITS ABOVE AND BELOW. ALL BLOCK LAYOUT AND PLACEMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. C. MODULAR UNITS MAY BE INSTALLED HORIZONTALLY WITH RESPECT TO THE PROFILE WALL ALIGNMENT OR MAY BE MADE TO FOLLOW THE BOTTOM OF WALL CONTOURS ("RUN WITH THE GRADE"). WHERE BOTTOM OF WALL CONTOURS ARE USED TO SET THE FIRST ROW OF MODULAR BLOCKS, GRADES MAY NOT SLOPE MORE THAN 15% WITH RESPECT TO THE WALL PROFILE BASE. D. PLACE AND COMPACT FILL BEHIND WALL UNITS. AFTER UNIT FILL IS COMPACTED EXCESS UNIT FILL MUST BE SCREEDED (ROD-BOARDED) OFF TO DEVELOP A FLAT BASE UPON WHICH SUBSEQUENT UNITS CAN BE POSITIONED. PLACE AND COMPACT BACKFILL SOIL BEHIND UNITS. FOLLOW WALL ERECTION AND UNIT FILL CLOSELY WITH STRUCTURE BACKFILL. E. MAXIMUM STACKED VERTICAL HEIGHT OF WALL UNITS PRIOR TO UNIT FILL AND BACKFILL PLACEMENT AND COMPACTION SHALL NOT EXCEED ONE COURSE. 3.06 GEOSYNTHETIC SOIL Rli:INFORCEMENT INSTALLATION A. GEOSYNTHETIC SOIL REINFORCEMENT SHALL BE ORIENTED WITH THE HIGHEST STRENGTH AXIS PERPENDICULAR TO THE WALL ALIGNMENT. 8. GEOSYNTHETIC SOIL REINFORCEMENT SHALL BE PLACED AT THE STRENGTHS, LENGTHS, AND ELEVATIONS SHOWN ON THESE DRAWINGS. WHERE GEOSYNTHETIC PLACEMENT ELEVATIONS VARY FROM FACING UNIT INCREMENTS, GEOSYNTHETIC ELEVATIONS MAY BE ADJUSTED UP OR DOWN BY 4 INCHES MAXIMUM. C. THE GEOSYNTHETIC SOIL REINFORCEMENT SHALL BE LAID HORIZONTALLY ON COMPACTED BACKFILL AND ATTACHED TO THE MODULAR WALL UNITS IN ACCORDANCE WITH THE DETAILS OF THESE PLANS AND SPECIFICATIONS. A TOLERANCE FROM FACE TO TAIL OF REINFORCEMENT OF 6" IN 1 O' IS ACCEPTABLE RELATIVE TO HORIZONTAL GEOSYNTHETIC ORIENTATION. PLACE THE NEXT COURSE OF MODULAR CONCRETE UNITS OVER THE GEOSYNTHETIC SOIL REINFORCEMENT. THE GEOSYNTHETIC SOIL REINFORCEMENT SHALL BE LAID FLAT PRIOR TO BACKFILL PLACEMENT ON THE GEOSYNTHETIC SOIL REINFORCEMENT. D. GEOSYNTHETIC SOIL REINFORCEMENT SHALL BE CONTINUOUS THROUGHOUT THE LENGTH OF EMBEDMENT. SPLICED CONNECTIONS BETWEEN SHORTER PIECES OF GEOSYNTHETIC SOIL REINFORCEMENT WILL NOT BE PERMITTED. I HEREBY CERTIFY THAT THESE PLANS HAVE BEEN UNDER MY SUPERVISION. -t~~~ SOIL RETENTION v<A~ DESIGNS INC. 2501 STA,ISTi CARLSBAD, CA 92008 800-346-7995 ;);J"nvt////,// IO!f<il/ PREPARED -=:-:-::-::-==--:-:-~~~ft,}c~~~~-(._,-----::-::--=:-:-::::=-:--:--~:'.:f:!~~ ENGINEER NIKLAV JANSSON R.C.E. 67744 DATE 3.07 REINFORCED BACKFILL PLACEMENT A. REINFORCED BACKFILL SHALL BE PLACED, SPREAD AND COMPACTED IN SUCH A MANNER THAT MINIMIZES THE DEVELOPMENT OF SLACK IN THE GEOSYNTHETIC SOIL REINFORCEMENT AND INSTALLATION DAMAGE. 8. REINFORCED SOIL BACKFILL SHALL BE PLACED AND COMPACTED IN LIFTS NOT TO EXCEED THE "RAIL HEIGHT" OF THE UNITS BEING PLACED. LIFT THICKNESSES SHALL BE DECREASED TO ACHIEVE THE REQUIRED DENSITY AS REQUIRED. C. REINFORCED BACKFILL SHALL BE COMPACTED TO 90% RELATIVE COMPACTION AS DETERMINED BY ASTM D-1557. THE MOISTURE CONTENT OF THE BACKFILL MATERIAL PRIOR TO AND DURING COMPACTION SHALL BE UNIFORMLY DISTRIBUTED THROUGHOUT EACH LAYER. D. ONLY LIGHTWEIGHT HAND-OPERATED EQUIPMENT SHALL BE ALLOWED WITHIN 1 FOOT (0.3 METERS) FROM THE BACK OF THE MODULAR CONCRETE UNIT. E. TRACKED CONSTRUCTION EQUIPMENT SHALL NOT BE OPERATED DIRECTLY UPON THE GEOSYNTHETIC SOIL REINFORCEMENT. A MINIMUM FILL THICKNESS OF 6 INCHES (15 CM) IS REQUIRED PRIOR TO OPERATION OF TRACKED VEHICLES OVER THE GEOSYNTHETIC SOIL REINFORCEMENT. TRACKED VEHICLE TURNING SHOULD BE KEPT TO A MINIMUM TO PREVENT TRACKS FORM DISPLACING THE FILL AND DAMAGING THE GEOSYNTHETIC SOIL REINFORCEMENT. F. RUBBER TIRED EQUIPMENT SHALL PASS OVER GEOSYNTHETIC SOIL REINFORCEMENT AT SLOW SPEEDS, LESS THAN 10 MPH (16 KPH). SUDDEN BRAKING AND SHARP TURNING SHALL BE AVOIDED. G. AT THE END OF EACH DAY'S OPERATION, THE CONTRACTOR SHALL SLOPE THE LAST LIFT OF REINFORCED BACKFILL AWAY FROM THE WALL UNITS TO DIRECT RUNOFF AWAY FROM THE WALL FACE. THE CONTRACTOR SHALL NOT ALLOW SURFACE RUN-OFF FROM ADJACENT AREAS TO ENTER THE WALL CONSTRUCTION SITE. H. CARE SHOULD BE TAKEN DURING EXCAVATION FOR AND CONSTRUCTION OF THE V-DITCH AND ALL OTHER TYPE OF WALL STRUCTURE NOT TO DAMAGE THE UPPER GEOGRID LAYER. IF THE GEOGRID LAYERS ARE DAMAGED, THEY NEED TO BE PROPERLY REPLACED. 3.08 EROSION CONTROL A. PROVIDE DUST AND EROSION CONTROL PROTECTION PLAN IN ACCORDANCE WITH CONTACT DOCUMENTS. 3.09 AS-BUILT CONSTRUCTION TOLERANCES A. VERTICAL ALIGNMENT: ±1.5 INCHES (37 MM) OVER ANY 10 FT (3 M) DISTANCE. 8. WALL BATTER: WITHIN 2 DEGREES OF DESIGN BATTER. C. HORIZONTAL ALIGNMENT: ±1.5 INCHES (37 MM) OVER ANY 10 FT (3 M) DISTANCE. D. CORNERS, BENDS, CURVES: ±1 FT (0.3 M) TO DESIGN LOCATIONS. E. MAXIMUM HORIZONTAL GAP BETWEEN ERECTED UNITS SHALL BE 9 INCHES (23 CM). 3.10 FIELD QUALITY CONTROL A. THE OWNER SHALL ENGAGE INSPECTION AND TESTING SERVICES, INCLUDING INDEPENDENT LABORATORIES, TO PROVIDE QUALITY ASSURANCE AND TESTING SERVICES DURING CONSTRUCTION. THIS DOES NOT RELIEVE THE CONTRACTOR FROM SECURING THE NECESSARY CONSTRUCTION CONTROL TESTING DURING CONSTRUCTION. B. QUALIFIED AND EXPERIENCED TECHNICIANS AND ENGINEERS SHALL PERFORM TESTING AND INSPECTION SERVICES. C. AS A MINIMUM, QUALITY ASSURANCE TESTING SHOULD INCLUDE FOUNDATION SOIL INSPECTION, SOIL AND BACKFILL TESTING, VERIFICATION OF DESIGN PARAMETERS, AND OBSERVATION OF CONSTRUCTION FOR GENERAL COMPLIANCE WITH DESIGN DRAWINGS AND SPECIFICATIONS. D. FIELD INSPECTION AND TESTING SHALL BE PERFORMED BY THE GEOTECHNICAL ENGINEER OF RECORD. 3.11 SPECIAL INSPECTIONS A. PER ICC-ES REPORT ER-5515, SPECIAL INSPECTIONS DURING INSTALLATION MUST BE PERFORMED IN ACCORDANCE WITH SECTION 1704 OF THE 2011 CBC. THE SPECIAL INSPECTOR MUST BE QUAUFIED BY THE CONSTRUCTION INSPECTOR / CITY ENGINEER IN ACCORDANCE WITH SECTION 1704 OF THE CBC. THE INSPECTOR'S RESPONSIBILITIES INCLUDE VERIFYING THE FOLLOWING AS DESCRIBED PREVIOUSLY: 1. FOUNDATION PREPARATION. 2. UNIT PLACEMENT, INCLUDING ALIGNMENT AND INCLINATION. 3. GEOSYNTHETIC REINFORCEMENT LENGTH, STRENGTH, AND PLACEMENT WITH RESPECT TO ELEVATION AND ORIENTATION. 4. BACKFILL SOIL STRUCTURAL PROPERTIES 5. BACKFILL PLACEMENT AND COMPACTION TABLE 1 -REFERENCED DOCUMENTATION: TABLE 2 -VERDURA BLOCK PROPERTIES I.) GRADING PLAN AND lvALL PROFILE, CT06-27 MUROYA, CARLSBAD CA. PREPARED BY PANGAEA LAND CONSULATNTS, INC. RECEIVED ON• 02/25/2011 2.) VERDURA 40 MSE w'ALL DESIGN, CT06-27 MUR□YA CARLSBAD, CA, PROJECT !11 1007-004 PREPARED BY SOIL RETENTION DESIGN, DATED 07/15/2011 3.) VERDURA lvALL DESIGN PARAMETERS, MUROYA PROPERTY CARLSBAD CA., DATED 07/14/2009 PREPARED BY GEOSOILS CONSULTANTS 4,) RESPONSE TO PLAN CHECK COMMENTS ON THE VERDURA RETAINING w'ALL FDR MUR□YA, CARLSBAD CA. PREPARED BY SOIL RETENTION DESIGNS INC. DATED, 8/25/2011 TABLE 3 -SOIL STRENGTH REQUIREMENTS MATERIAL t,::--,.....,....S_H_E..,..A_R-,--T'S_T_R....,,E...,N_G_T.,...H.....,.........,..,-tuN IT \./EI GH Friction Angle Coheslon(psf) (pcf) iReinforceci/lnfill Soil 30 0 130 Reto.ineci/Bo.ckflll Soll 30 0 130 F ouncio. tion Soil 30 300 130 SEISMICITY 0.17 g (50% OF .33g) Unit 1ype, Verdura Unit Size, Rail Heillht, in. (mm) Unit Size, Crown Heil ht, in. (mm) Unit Size, Width, in. mm Unit Size, Denth, in. mm Wei•ht, (tvne.l, lbs. 1 ra1 Batter = (degrees from vertical) \ V30 / 1M 163.Y 9]~ 181~0 1 20 \ V40 , V50 V60 , 8 200) l.5(161 \e/201 11 280) 918 111.l:IIU 18 450 18 50 181&50 12(300 0 121~1iii: 82138 / 119• acft'",inli,2;r,(6;t,~cl 14 1 20 I 14 ' SPECIAL INSPECTION REQUIRED PROVIDE VERIFICATION AND INSPECTION OF SOILS PER CBC TABLE 1704,7 PROVIDE LEVEL I VERIFICATION AND INSPECTION OF THE VERDURA RETAINING w'ALL SYSTEM PER CBC TABLE 1704.5.1 SECTION 5 A, B B. C □NL Y. ALL OTHER SECTIONS DO NOT APPLY TO THE VERDURA RETAINING w'ALL SYSTEM. * REINFORCED/INFILL SOIL SHALL HAVE MAXIMUM FINE SOIL FRACTION (% PASSING #200 SIEVE) NOTE• SECTION 5A REFERS TD THE BLOCK UNIT SIZE, AND ALIGNMENT OF 30%. THE MAXIMUM PLASTICITY INDEX (Pl) OF THE FINE SOIL FRACTION SHALL BE 20. TABLE 4 -GEOSYNTHETIC REINFORCEMENT PROPERTIES Miragrid Test Method Unit Tensile strength ASTII kN/m (at ultimate) D6637 (lbs/ft) Tensile strength ASTII kN/m (at 5,: strain) D6637 (lbs/fl) Creep reduced ASTII kN/m stre•"'h D5262 (lbs/fl) Long Term Allowable kN/m 5XT 8XT 62.7 102.1 (4300) (7000) 25.4 36.8 (1740) (2520) 37.6 61.3 (2580) (4200) 32.6 53.1 (3636) \ Ox~ \i. BX~ 20X" 21. 31':i1 181.2 ( l~O ) 93 ) (12420) (::%'oJ (:I!,) 77.9 (5340) ~~) 'i~1 105.4 ~9 j561 (7221) / 82.9 ,\ / 67.7 87.1 SECTION 5B REFER TO THE GEOSYNTHETIC REINFORCEMENT LENGTH, STRENGTH, AND PLACEMENTw'ITH RESPECTTO ELEVATION AND ORIENTATION 11 AS BUILT" &4{J(!&u,,f'_~-!2-(?-t.3 RCE 408/;J EXP, C,,-30-tS DATE REVIEw'ED BY• Design Load GR! GC-, (lbs/fl) (2234) (4312) (4641 (5966) PLAN DATE•OB/24/2011 IN~~-~• DATE ~ CITY OF CARLSBAD ENGINEERING DEPARTMENT 1---+----+----------------+-----l---1----1----1 GRADING PLANS FOR: MUROYA VERDURA<l!JSEGMENTAL RETAINING WALIB APPROVED~.M )I~~ GLEN K. V~ ::&SKI 1----+--+---------------1----+-----t---+----1 ENGINEERING°"MANAGER PE 41204 EXPIRES 03/31/13 □1TF. l?.·(G·l,3 ~ta 11\ A&·toUIC..7" DATE INITIAL ENGINEER OF WORK REVISION DESCRIPTION OA TE INITIAL DA TE INITIAL 01HER APPROVAL CITY APPROVAL DWN BY: ES I PROJECT NO. I DRA'MNG NO. CHKD BY: NNJJ fl~ RVWD BY: CT 06-27 471-7A ~-------~ 110111 0 Joi. :e 0 C) 0.i:a, .... ...., fol, fol, ...., . i:! / 340 7 I 335-+-j -- 315 305 0 0 0 'a, + 0 ( L NOT£: THIS PLAN IS INTENDED TO ILLUSTRATE THE PROPOSED VERDURA WALLS, AND IS NOT INTENDED TO SERVE />S A GRADING PLAN. NOTE: WORK CONTAINED WITHIN THESE PLANS SHALL NOT COMMENCE UNTIL AN ENCROACHMENT PERMIT AND/OR GRADING PERMIT HAS BEEN ISSUED, THE PRIVATE ENGINEER SIGNING THESE PLANS IS RESPONSIBLE FOR ASSURING THE ACCURACY AND ACCEPTIBILITY OF THE STRUCTURAL DESIGN HEREON. IN THE EVENT OF DISCREPANCIES AFTER JURISDICTIONAL APPROVAL OR DURING CONSTRUCTION, THE PRIVATE ENGINEER SHALL BE RESPONSIBLE FOR DETERMINING AN ACCEPTABLE SOLUTION AND REV1SING THE PLANS FOR APPROVAL BY THE CITY- _ __,__ -- 0 0 0 0 + ~ --- 0 0 0 LO + ~ 20 H=22.0' MIRAFI 20XT BOTTOM LAYER ONLY MIRAFI BXT ALL OTHER LAYERS L= 23' ALL LAYERS ' i ---L J --__ I 0 0 0 0 + N PLAN VIEW 0 20 SCALE 1" = 20' 40 PROFILE LEGEND -FG FINISH GRADE -TW TOP OF WALL -------------,----------. 340 i --+-I ! ---1 __ ,__335 i -----~-~--· ----·-----------. +-330 0 0 0 LO + N -1 ~325 ----!-320 COMPETENT MA$IAL PER GEOTECHNICAL ENGINEER ~315 I I 1310 L305 0 0 0 0 + f") . - I I __ §_____ rlr'-----'--m---" l \~ I --I --' 339. 0 ·-1- -BW -MG -#XT- ---<lb -L EB / 'VI-+-'\ SOIL RETENTION DESIGNS INC. 2501 STATE STREET, CARLSBAD, CA 92008 800-346-7995 BOTTOM OF MSE STRUCTURE MIRAGRID GEOSYNTHETIC REINFORCING DENOTES TYPE OF MIRAGRID REINFORCING REQ'D DENOTES THE NO OF BLOCKS BET. THE MIRAGRID LA YER LENGTH OF GEOSYNTHETIC REINFORCING (FEET) GEOGRID TRANSITION (LENGTH OR TYPE) DENOTES SUBDRAIN OUTLET LOCATION NOTE: INFRASTURCTURE IMPROVEMENTS SHALL NOT BE INSTALLED DEEPER THAN 1.5' FROM THE TOP OF WALL IN ORDER TO AVOID CONFLICT WITH THE GEOSYNTHETHIC REINFORCEMENT PROPOSED RESIDENCE GEDGRID FREE ZONE CTDP LAYER OF GE□GRID ND CLOSER THAN 3 BLOCKS AND ND FURTHER THAN 5 BLOCKS FROM 'v/ALL CREST) 23' + MIRAFI BXT L = 23' ( 1.05 • H) SLOPE DESIGN BY OTHERS SEE CIVIL PLANS FOR ALL DRAINAGE (TYP.) V-40 BLOCK TEMPORARY BACKCUT XT ------8XT ------'rfi'ill / (TYP) ENGINEER MIRAFI 8XT L = 23' (1.05 * H) PER GEOTECHNICAL ~ CLASS 2 PERMEABLE MATERIAL ---TO FILL BLOCK AND 6" MIN. REINFORCED SOIL -y=130 pct <1>=30" C=O psf -------8XT ------8XT ------'ffi'il' MIRAFI BXT L = 23' ( 1.05 • H) \-------8XT ------8XT ------'mi~, MIRAFI 8XT L = 23' ( 1.05 * H) "l's;::------8XT ------8XT -----+-w.11 MIRAFI 8XT L = 23' ( 1.05 * H) WIDTH BEHIND BLOCKS (~ * H) RETAINED SOIL :;g1f~fft(;lli\-. -------BXTMIRA--Fl-8_XT_L_=_2_3'-(~.:: -.-H-)-----1--'rli"rl\ EXISTING GRADE -y=130 pct ___fifiETAINED t 8XT ------8XT -----+w.n C <1>=30' ' $QI!.-:!:f C=O p5f ''•\:($\!'.(ft MIRAFI 8XT L = 23' (1.05 • H) '-PROPOSED BENCH 1--------8XT ------8XT -----+--.!I TEMPORARY CONSTRUCTION ,,.--WEDGE TO BE BACKFILLED MIRAFI BXT L = 23' (1.05 * H) DURING WALL CONSTRUCTION \-------BXT ------8XT ------+-ilrJUi<v7Jf7:77;~ MIRAFI BXT L = 23' (1.05 • H) / /. / // // ~ 1--------8XT ------8XT -----+-''ffilillvj y<::, J ~ TOTAL HEIGHT NOT TO EXCEED H=22' 4" PERFORATED PVC DRAIN (TYP.) ENCAPSULATED IN 1 CF DRAIN ROCK AND WRAPPED W/GEOTEXTILE DRAINAGE FABRIC. 4" DIA. SOLID PVC OUTLET PIPE PER PROFILE OR AS DIRECTED BY GEOTECHNICAL ENGINEER. ///// ~ }!J~~~~~~~~~~~~~~:::~:::J:::~:::TFl~":::_-:=_-:~XT-k~~--?-':::'-:~~•--:~,-,,~;-:~'1-::::,~-,1:::,:-_=L==~==gx==;==_==H-'-)==_==_==_==_==_==_==_==_==+~..J~'#t;=/f ... ~u""~-/-;:::-~-~-::~-~,~:-:-i>l:-?i'_,-+.;;..,,:-~--~-1-.:---'-I 1-..:::-------'---- , •' 7'-0" TO '.';FOUNDATION SOIL2 ~'.~\~Et~'Yf&f::fJ'f,t;}iJ(i\~{W DAYLIGHT MIN. FOUNDATION SOIL -y=130 pct <1>=30' C=300 psf LEGEND -Xl-GEOSYNTHETIC REINFORCMENT H OVERALL WALL HEIGHT H' EXPOSED WALL HEIGHT HEIi! WALL EMBEDMENT FG FINISHED GRADE TW TOP OF WALL BW BOTTOM OF WALL COMPETENT FORMATIONAL MATERIAL PER GEOTECHNICAL ENGINEER 4" DIA. SOLID PVC OUTLET PIPE. DRAINS TO LOW POINT SEE PLAN 4" PERFORATED PVC DRAIN PIPE WRAPPED W/GEOTEXTILE DRAINAGE FABRIC. 4" DIA. SOLID PVC OUTLET PIPE TO BE CONNECTED TO BACKDRAIN OUTLET PIPE MAXIMUM CROSS SECTION SCALE: 1" = 4' "AS BUILT" ~ tZ ·l7·!o RCE 438(::) EXP, G,·&J·/5 DATE REVIE'v/ED BY, cl 'l l t1J. 3·S ·1~ PLAN DATE:08 24 2011 U~CTIJ~ efv ,. DATE 1----t----t--------------+----t----t--t-------t CTr] CIJNINE~!NG ~b~~~~AD ~ l-----l--+-----------------11------t---t-----t------t ;:;G~R;:AD~I;:N~G,..::;:PLAN:=:;::;:;:S=FO~R~:========:::::..:=== DA TE INITIAL DA TE INITIAL DATE INITIAL ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL MUROYA VERDURA®SEGMENTAL RETAINING WALLS APPROV~~ zlh,,h{;-GLEN K. VAN PESKI . ~4 1 ENGINEERINMANAGER PE 41204 EXPIRES 03 31 13 & OWN BY: -=ES'-- CHKD BY: NJ t,-.l RVWD BY: NJ PROJECT NO. CT 06-27 DRAWING NO. 471-7A 1101'1: 0 0 g ... ~ -0 330 "' i:!: ~ (/J 325 ,.._ g ~ .; ~ ~ (J) 320 &l !;l c!i ~ ~ " ~ ~ .,. ... ... 0 -0 " ~ ~ (/J 5X 5XT SXT \\_ 5X 5XT 5XT H=11.3' MIRAFI SXT ALL LAYERS L= 9' ALL LAYERS (.) !;l IXI 0 ~ <o ...; ~ <o ~ co 0) ... ... -0 -0 ~ " .. ~ i:!: (/J OPE --tQ) I '@ 5Xl! 5XT OF f!ASIN ELEV: 32).00 5Xl NO GRID ZONE ---+----+---+-5X '---. Q) ' ---~--+-' . HORIZONTAL SCALE: 1"=20' VERTICAL SCALE: 1 "=4' ~ -~ 0 ~ ~ " <o 0 " 0 330 " "' N ~ ~ ~ 1 (/J (/J PROFILE LEGEND -FG -TW -BW -MG -#XT- -<J/) -L FINISH GRADE TOP OF WALL BOTTOM OF MSE STRUCTURE MIRAGRID GEOSYNTHETIC REINFORCING DENOTES TYPE OF MIRAGRID REINFORCING REQ'D DENOTES THE NO OF BLOCKS BET. THE MIRAGRID LAYER LENGTH OF GEOSYNTHETIC REINFORCING (FEET) GEOGRID TRANSITION (LENGTH OR TYPE) PROPOSED RESIDENCE~ * REINFORCED SOIL ')'=130 pcf <1>=30" C=O psf NOT£· INFRASTURCTURE IMPROVEMENTS SHALL NOT BE INSTALLED DEEPER THAN 1 .5' FROM THE TOP OF WALL IN ORDER TO AVOID CONFLICT WITH THE GEOSYNTHETHIC REINFORCEMENT 6' HIGH METAL RAIL FENCE / FOUNDATION PER CIVIL PLANS REFER TO TYPICAL DEATAILS (SHEET #14) FOR FOUNDATION LIMITATIONS 5.5' + 5.0' SLOPE 2% GEOGRID FREE ZONE (TOP LAYER OF GEOGRID NO CLOSER THAN 3 BLOCKS AND NO FURTHER THAN 5 BLOCKS FROM ~ALL CREST) V-40 BLOCK '1,_-------U ~ =_9'---r--'rlnl' / (TYP) MIRAFI 5XT L = 9' EXPOSED HEIGHT H'=3.5' ,----5XT --1---\-"IJil\!1!..':. 310_;__--~---_l_---l--_____ ______']i!!!!l!l!!!!I '------+--_l_-~--'------t-310 RETAINED SOIL )i ')'=130 pcf _/ RETAINED MIRAFI 5XT L = 9' 1----5XT ---1-"'ll; BOTTOM OF BASIN' NOTE: THIS PLAN IS INTENDED TO ILLUSTRATE THE PROPOSED VERDURA WALLS, AND IS NOT INTENDED TO SERVE AS A GRADING PLAN. NOTE: WORK CONTAINED WITHIN THESE PLANS SHALL NOT COMMENCE UNTIL AN ENCROACHMENT PERMIT AND/OR GRADING PERMIT HAS BEEN ISSUED. THE PRIVATE ENGINEER SIGNING THESE PLANS IS RESPONSIBLE FOR ASSURING THE ACCURACY AND ACCEPTIBILITY OF THE S1RUCTURAL DESIGN HEREON. IN THE EVENT OF DISCREPANCIES AFTER JURISDICTIONAL APPROVAL OR DURING CONS1RUCTION, THE PRIVATE ENGINEER SHALL 6E RESPONSIBLE FOR DETERMINING AN ACCEPTABLE SOLUTION AND REVISING THE PLANS FOR APPROVAL BY THE CITY. I I 0 0 + I 0 t,[) + 0 0 + N 0 t,[) + N 0 0 + n WALL 8 PROFILE VIEW PLAN VIEW 20 0 20 SCALE 1" = 20' 40 ==L ~ 1--1 Vl-r-'1 SOIL RETENTION DESIGNS INC. 2501 STATE STREET, CARLSBAD, CA 92008 800-346-7995 I HEREBY CERTIFY THAT Ai~ /oJ<Ju/ THESE PLANS HAVE BEEN PREPARED -=c-::c:-=:=---=:~~;;t!,~~~~:e::__J. __ -;:;-:::-;::c--;:::;:;c;--;-~!.<:t.=~~ UNDER MY SUPERVISION. ENGINEER NIKL E. JANSSON R.C.E. 67744 DATE ?'i<-orEss;0 E. "< " -0 M w 67744 ["""] CL c,, i< EXP. 06/13 >t <1>=30' SOIL C=O psf MIRAFI 5XT L = 9' TOTAL HEIGHT NOT TO EXCEED H=11.3' 1----5XT ---1-'lli"i HEMB=7.8'MAX. -•\---------~ 4" PERFORATED PVC DRAIN O ----5XT --+,,,!:ff Y MIRAFI 5XT L = 9' IMPERMEABLE BASIN LINER (TYP.) ENCAPSULATED IN CF PER FOOT OF f' DRAIN ROCK AND WRAPPED W/GEOTIEXTILE DRAINAGE FABRIC. 4" DIA. SOLID PVC ATTACH TO STORM DRAIN PIPE AT SOUTH END OF WALL LEGEND -XT-GEOSYNTHETIC REINFORCMENT H OVERALL WALL HEIGHT H' EXPOSED WALL HEIGHT HEMB WALL EMBEDMENT FG FINISHED GRADE TW TOP OF WALL BW BOTTOM OF WALL FOUNDATION SOIL FOUNDATION SOIL ')'=130 pcf ~=30' C=300 psf --. __ CLASS 2 PERMEABLE MATERIAL TO FILL BLOCK AND 6" MIN. WIDTH BEHIND BLOCKS 4" PERFORA TIED PVC DRAIN WRAPPED W/GEOTIEXTILE DRAINAGE FABRIC. 4" DIA. SOLID PVC ATTACH TO STORM DRAIN PIPE AT SOUTH END OF WALL MAXIMUM CROSS SECTION SCALIE: 1" = 4' NOTE: SEE CIVIL PLANS FOR BASIN CONSTRUCTION AND LINER TYPE 11 AS BUILT" &&,~ RCE 4:M:;I~ EXP, (p,c()-/5 REVIE~ED BY, l2-l7-l3 DATE 1-----+----+---------------+-----t-----t--r------. ~ c 1rN1rnE~!NG ~b~~~J?AD ~ 1---+--+-----------------J---t---t-----t-----J ~G:;:RAD::;::l;:N;,G..':P;:LAN;:::;:;::::S=F;:O;:;R:;::· ========~==:::::; lZ·l~-13 tel5 t A$·{oUlL7" DATE INITIAL DA TE INITIAL DA TE INITIAL ENGINEER OF WORK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL MUROYA VERDURA®SEGMENTAL RETAINING WAIJB DWN BY: -=ES,____ CHKD BY: mu? RVWD BY: NJ GLEN K. VAN P SKI PROJECT NO. CT 06-27 ///! z 13 DATE DRAWING NO. 471-7A 110111 I I L _ _J 9• MAXIMUM SPACING I L_ 9• MAXIMUM SPACING I LL _ _J_J BLOCK SPACING DETAIL l=1s•--1 TOP VIEW I I I _J_J I f--18' ----j FRONT VIEW I 12· 11 ~- ' I - 1 1 ~• - I f--12· ----j SIDE VIEW VERDURA 40 BLOCK DETAIL FRONT WALL PROFILE NOTE: WORK CONTAINED WITHIN THESE PLANS SHALL NOT COMMENCE UNTIL AN ENCROACHMENT PERMIT AND/OR GRADING PERMIT HAS BEEN ISSUED. THE PRIVATE ENGINEER SIGNING THESE PLANS IS RESPONSIBLE FOR ASSURING THE ACCURACY ANO ACCEPTIBIUTY OF THE STRUCTURAL DESIGN HEREON. IN THE EVENT OF DISCREPANCIES AFTER JURISDICTIONAL APPROVAL OR OURING CONSTRUCTION, THE PRIVATE ENGINEER SHALL SE RESPONSIBLE FOR DETERMINING AN ACCEPTABLE SOLUTION AND REVISING THE PLANS FOR APPROVAL BY THE CITY. I 7.75 • I PLAN VIEW CABLE RAILING/ FOOTING PER CAL TRANS STANDARD DRA'v/lNGS Bll-47 CABLE RAILING BY OTHERS ~ SLOPE PER CIVIL~ ENGINEER'S ),;' V-DITCH SIZE 2 ~0 GE□SYNTHETIC REINFORCEMENT l' DIAMETER SCHEDULE 80 PVC (CONTINUOUS) SIDE VIEW 12' MIN □VERLAPi-----1 GEOGRID CONNECTION DETAIL OPTIONAL NOTCH AT N□N-C□NNCECTI□N INTERFACE <TYP,) MU lv'ALL CMU lv'ALL Iv'/ RETURN /VERDURA lv'ALL Iv'/ BATTER VERDURA lv'ALL Iv'/ BATTER CASE A PLAN VIEW CASE A PLAN VIEW CASE B (/) r D "t) CMU lv'ALL A CASE C A END OF WALL TRANSITION DETAILS 3' OF GRANULAR FILL REQUIRED BETlv'EEN OVERLAPPING GE □SYNTHETJC REINFORCEMENT FDR PROPER ANCHORAGE CMU lv'-\LL VERDURA lv'ALL RETURN CMU lv'ALL ~ ;,~YC\\y~•( SECTION A-A CASED VERTICALLY ALTERNATE GE □SYNTHETJC REINFORCEMENT PLACEMENT TD AVOID CONTINUOUS UNREINFORCED SECTIONS NOTES: CHECK 'v/lTH MANUFACTURER'S SPECIFICATIONS FDR THE CORRECT ORIENTATION OF THE GE□SYNTHETIC REINFORCEMENT TD OBTAIN PROPER STRENGTH. FACE OF VERDURA lv'ALL GEOGRID PLACEMENT ON CURVES SOIL RETENTION DESIGNS INC. 2501 STA;jE ST E T, CARLSBAD, CA 92008 800-346-7995 ' I HEREBY CERTIFY THAT • /(?~ ~/ THESE PLANS HAVE BEEN PREPARED -=:-:-::-::c=:--~~~ UNDER MY SUPERVISION. ENGINEER R.C.E. 67744 DATE VERDURA Iv' ALL DA TE INITIAL ENGINEER OF WORK N□IE 1 PER CIVIL ~ <>»/:0 /,' ENGINEER'S 1 1 A«"<«0-< / REQUIREMENT ~)$,>"' '-,<, «0· 18' MAXIMUM 6'CLEAR GE □GRID DEPTH UPPER MOST GE □GRID LAYER DRILLED FOOTING EXCAVATION NOT TD EXCEED 24' DIA. AT 8' □N CENTER RAILING/ FENCE CONTRACTOR SHALL NOT TRENCH EXCAVATE THROUGH UPPER GRID LAYER, FOOTINGS TD BE DRILL EXCAVATED TYPICAL V DITCH AND CABLE RAILING DETAIL TOP OF WALL DETAILS PAD ELEVATION VARIES SEE PLAN ~ TOP □F \./ALL DETAILS (\./HEN APPLICABLE) GE □GRID FREE ZONE (TOP LAYER □ F GE□GRID ND CLOSER THAN 3 BLOCKS AND ND FURTHER THAN 5 BLOCKS FROM \./ALL CREST) T\./ 14• MIN, H' H FG B\./ t AS·t&ltt..r REVISION DESCRIPTION COHESIVE SOIL CAP AREA TD BE PLANTED DR COVERED \./ / :.. IMPERVIOUS MATERIAL h'li!'r'-JE---lE--l<---+-+----lf--J<-----)f-----f_,Y,?<,;;; 1/,. 1/ ;f5j .fP--lE--l<---+-+----lf--J<-----)f-----J(----/:c~/ lh'l.11" REINFORCED SOIL MASS RETAINED SOIL MASS LEGEND _,,____,s--GE□SYNTHETIC REINFORCEMENT FOUNDATION SOIL MASS BACK DRAIN PER SOILS ENGINEER'S RECOMMENDATIONS TYPICAL DETAIL DWN BY: DA TE INITIAL DA TE INITIAL CHKD BY: OTHER APPROVAL CITY APPROVAL RVWD BY: H OVERALL \./ALL HEIGHT H' EXPOSED \./ALL HEIGHT HEMB \./ALL EMBEDMENT FG FINISHED GRADE T\./ TOP OF \./ALL B\./ BOTTOM □F \./ALL 11 AS BUIL T 11 ~ t2-t7-(,3 RCE 4361.B EXP, (p-;J0-{5 DATE DATE MUROYA VERDURA®SEGMENTAL RETAINING WALIS ES e,il NJ NJ GLEN K. VAN PESKI 10/2~/2) ' DATE PROJECT NO. CT 06-27 DRAWING NO. 471-7A 110111 NOTfS: TESTS AND INSPECT/Ol\/5: fm"' 1500 PSI WITH La,e. l SPECW. INSPECTION· IJ.N.o. Nt.)1'($$; CQNCRPTF. MCX SHAU CtJ(yFQRM ro 4S'rM C 9()/( USE 08P f'm ., !SW PSI WITH UNa. J SPE'CML 1NSPEC1'10N • ll.N,0, ''TYPES" MORT.AR PS<ASTM C JJtJ. CONCReTE Bi.OCK SH'll.l. CONFOAA ra ASTM C90 & USE' 08P USE A57M t.615 GRADE 60 S1'e=t. MJ1'. DESIGN CRITBIUA: '1YPE5" MORTAR PcRASTM C )JO. SPECIAL INSPECTIONS SHALL BE DONE INACCORDANCE WITH THE STATEMENT OF C-ROIJT S'TRBKiTH TO 8E 200lJ PS1 MIN P!R ASli~ C ,ms. AUOWAB!..t' SOii. BEAIUA'G "'2000 PSF + U.'lf' ASTM AolS {j/l,Al)E 00 S1m NIN. FOOT1.NG COffCRETf: 2500 PSI l'41N. ~ 18 OAl-S. VSE Tfl'E 11/V 3CO PSF UJCR, FOR. WIDTH PER SOIJ.$ G/Wiff STRENGTH TO BE 2000 PSI Ml'N, PER ASrM C 475, OESIGN f:Mf'EflJA: CEMENT. ROORr FOOTING CONcRETE; 25fJtJ P51 MIN. @ 28 DA nL tJSe n'Pf' II/V SPECIAL INSPECTIONS PER 1704 AND 1705. FOUNDATIONS AND WALLS AR[ SUBJECT AU.OWAeLE SOlL BEARING "' 2000 PSF + PROV!OE r MIN. CONCRETE REJJAR COVER FOf.l. IWY POO'F;NG C4S' AllOVJABLE LATERAL PASSIVE"' ]S(J /:'CF. CEMEMT. 31}() PSF fflCR. f()fl WlOrH PER SOI£S AGAINST NATURAL SOIL, l!!QllU.lllA!.z!lfr fLWD P/l.ESS!JR€ FDR.;; i'O PROV/OE 3~ Mfr(, OONCRF.1E ~eMR COVER FOR A/!IYF00f/NG015'. TO INSPECTION BY TH[ GRADING INSPECTOR IN ACCORDANCE WITH CBC 109.3. REPOR.f l iJACKf'!LL "' so PSr' ~ sans AGA!Mir IVATVRAL SO!l.. AU.OWA&'.E" I.ATE/ML PASSI!>="' JSO PCF. FDR RETA!Nffil(; WAI.I.$, REl'O/ff CONTRACTOR SHALL COORD!NA T£ ALL REQUIRED INSPECTIONS WITH TH£ GRADING l!Qi)llJVAlENT FWlfJ PRESSVRF. FOR. I.Ml U5E saecr<JRAM/lAR SACKRJ.1, PER sous EJV(,,'k, FlJR RETAli'llNG WAUS: BACKFIU. ,,. 35 PSP PER .soI!.S PROVIOE A DRAINSTAR SV801WN AS S.I-IOWN, e USE 5E!..iCT GFANUIAR BAO,r]ll. t>f.'R sorts rJN(JII, REFORr WA reRPJWfF SACKFILJ. !!De Ol' WALL WI 'WATCHOOS HD• OR ,1 ffl:JVIDE A CJRAlNSTArl. SVSDRAfN AS $H0!+'/V, INSPECTOR. L<V£L BAC7 ,c;<JAL 1_111 11 I""" WATERNI.Off' f.11,CJ(f'l!./, S'IiJe OF WALJ. WI ''t-1,;tlTCHVO-&' HD' OR PROVIDE PROP/fll. SHORING Di/RING CONSTRJJCl"JfJN, EQUAL . .PROVIDE PROKR SHORING OORING cormRIJCTIOi'I . SPECIAL INSPECTORS SHALL B£ EMPLOYED BY THE OWNER TO PlfOVIO[ SPECIAL . ' 111 111:--MOTE: PROIIIoE lEVf/,. ON~S"E'Ct<\l. Wm--INSPECTIONS FOR THE PROJECT. SPECIAL INSPECTORS SHALL BE QUALIFIED lNSPECTION PER COC TABLE J 704-. S, 1 OF NOTE: PRDll.!OE lEltl'l ONE SPeCJAL THE MASONRY STEM PIUOP. TO G!tOf.JT.lNG IMSPECTKJN PER CJJC TABLE 1704,5,l OF P£RSONS WHO ARE REGISTERED BY THE CITY OF CARLSBAD. ,-.:111-TO VERJF'l GRADE, 5m AND PROPER ' #4 HCJ~Z. CONJ, THE MASONRY STtM PRIOR TO GRlJUTING 1--#4 HURZ. CONJ, PLACEMENT OF REINFr)RCEMENf AND TO !:"1 .----! 24" !JIC 8816 CHU Sllt.I.D ro VERIFIGRADE, S!ZfliNDPROP~ ' --e .:1.4" a;c 8816 CMU SD/..I11 ENSURf THE GROUT SPACE 15 711£ PROPER GRJ11Jr£D Iii/ NtJ SPCI-P!.ACl=MENT OF Ri!INFORCEMENT AND TO ft\ e~ ,.,, , iNSPE.'t:TllJN Rtt1JJ, ~UrF:IJ W NIJ SPC'l.., SIZE w.rmour (JfJS1'P..UCTION OTHER THAN -'G' BAR I f:DGE. Cir ENS//RE ~ GROUT SPACE JS THE PROPER SCHEDULE OF SPECIAL INSPECTIONS 2~ CL' INSP£CT!IJN R£QD, NORM.4l MORtAR F11-JS. ..... SlZf WITHOUT O&TRIJCTION OTHER THAN -'G' DAR i ElltiE Dr B' CMU FULL HE:IGHT ..... v NOll.MAl MORTAR HA'S . s~ CMU FULL. f!DCif/T ' ' <[ (E> I 4 HDRZ, Cr:JNT, ' . ., l 24' DIC ~ -a!) fl 4 HtJR.Z. WNT. 2-l/~ CL. LEVEL 1 SPECTAL INSPECTION PER TABLE 1704.5.1 . 2' e•" G/C -~l../2• CL f.,-'F' DfJWfl.S e £1JGr 'F'' IJD\lir1.S f EDGE' ~ 1 .... 1.,....,--[IF 1~ OR S" CMIJ , v-!1F' 12' DR 8" Cf,IJJ ' 12'8J6 CNU SfJLlJJ u FREQUENCY OF INSPEC770N ' ;a: 1eru6 CMU st:1L.1IJ ' uROUr£.O W/ N/J SPCL, u >" GROUT£]) w'/ NG SPCJ..., ' . , 1NSP£CTICJN RE&tD, I/1/SPEctPJN RE()D, "' ?,·,•('•· •. INSPECTION TASK CONTINUOUS ' ~~-· :•: t, 4' PIA S])R 35 PERF" PIP£ W/ J C:r', PERIODIC "' ~;::•~/~-·:-. -4" lJIA. SJJR 35 nu PIP£: w'/ J CF, ~11 40•· !" 3/4~ GRAVt:L VRAPPF:D W/ MlRAFI J40N ' '"'' ... DURING TASK DURING TASK ;•:,.e·h: ._I I ·•Jj·:., C 3/,fl GRl"tVfL WRM'Pf:.li WI MIRAFI HON . Fl!. T~ rAIJRIC -SLOP( ro tmAJM ;; .. /· •.. :~. fJL TER FA.i.RIC -SJ.DP£ TO M41# " WATERPRDCJF .B-ACKS'lli£' OF WALL. \v'ATfifi!PROOr BACJ(SJI£.' UF WALL, ' i [ __ r_ ---~ 1. AS MASONRY 1.."0NSTRUTION BEGINS, THE ' • 'I '11 I ~ (\j f'.. FOUOWING SHALL BE VARIFIED TO ENSURE (\j -~ .. ,. -'H' !IAR COMPLIANCE: ..., ~ -" r ' f::: V 'II' BAR d si,TJ-~ ' I '--:: w ;::,.. #4 HflRZ ctJNT. TtJP AN1J PROPORTIONS OF SITE-PREPARED MORTAR. X w "' -Jj/Jff(JH I! 12' 11/C ,i.s ..J 1 ~ #4 ~Z, CONT, T!]P AND ' ' j SHOWN -"k (.) 8fJTTfJJ4 i Jt" a/C AS ' Sf/D\IN • Cl CONSTRUCTION OF MORTAR JOINTS, X 1-, 'D'~12't ,j<12' ~ Nt:Jn::i AL TE:RNA T ,,.,f'Jft'' JJIRE:CTIDN e S' VAL GNU 'D' 2. THE INSPECTION PROGRAM SHALL VARIFY.· [!oR WALLS 1, 2, 4, 5, AND 61 SIZE AND LOCATION OF STRUCTURAL ELEMENTS. X I I FOR WALLS 3, 7, 9, AND 10 SPEC'D SIZE, GRADE AND TYPE OF REINFORCEMENT. X IA/ . 'B' DOWF. VERT 'H' BA,'2 'A I 'B' 1c, ID/ 'E' Fl Dow£dG 1 VERT IH/ BAR 'T' HOT OR COLO WEATHER CONSTRUCTTON REQ'M. X 'C' ID/ /El Fl GI #4€32' D/C 33' ~4€32' G/C 15' #4f!3i:' 0/C f' 2'-0' 2'-0' N/A 1'-9' 4' 12-L N/A 6'r-6' 3. PRIOR TO GROUTING, THE FOLLOWING SHALL BE 2'-0' e,.-oA N/A jJ'-6' N/A N/• N/A ' 12' 2✓-al e'-B" N/A 2'-3'-' 6' #41!32' 0/C LJ' 4@32' D/C ,.§.t_ VERIFIED TV ENSURE COMPJANCE: #4@32' 0/C l41' •4€3/:' G/C 18' 12' N/A 6'' 6' 2'-8' .?.'-8' N/A 2'~0" N/A N/A ,,,r-Ji!"'·-3'-4' 3'-4,t N/A 2 1-9;,, 9' 1/4@32' 0/C r.9· #4€/32' D/C '" GROUT SPACE IS CLEAN X '#4€/32' 0/C 21' N/A 6'r-6' 3"-4" 3'-4.,,. N/A 2 1-3' N/A #4@38' D/C r.9 Jf!,I' N/A 6'r-CONSTRUCTION OF MORTAR JOINTS X 12' 4"-0" 4'-0/t N/A 3 1-3" 15' #4@!6' D/C i.::7 #4/1!32' 0/C r'7 #4€!32' 0/C l.:7 #41!32' 0/C c:, ! 12' N/A 6" Ct,.. 6' 4'-0p 4'-0"' N/A 2 1-9"' N/A N/11 4. GROUT PLACEMENT SHALL BE VERIFIED 1V ENSURE 12.. · 6' 4'-8' 41-8"' N/A 3'-9' 18' #51116' 0/C t_:5 #41!!16' 0/C I 39•1 COMPUANCE WfTH CODE AND CONSTRUCTION X #4€/15' 0/C ~,, N/A 6' 4"-8' 4J-8"' N/A 31-31 6' #41116' D/C l:.5 N/A 12' 6' e4"' DOCUMENT PROVISIONS. 12" i 6' 5'"-4,:, 3'-4& f!1·-0' 4'-3"' 21"' #41!16' D/C l:'.3 115/1!16' 0/C '7 #4@16' D/C t'1 ~ .. #5€16' 0/C ;,y' #41116' 0/C 9' 6. COMPUANCE WfTH THE APPROVED 5UBMITTALS 5"-4' 5'-4' N/A 3'-9' 6' ·; N/14 12' 6' er X 12' i 6' 6'-0'/3'-4' 2 1-8"' 4'-9" 24' #51116' D/C tl' 1151/16' 0/C "' 'l SHAU: 8£ VERIFIED. #41116' 0/C I 334 #5/1!16' D/C r-#41116' 0/C 9' 6'-0' 4'-0' 2'-0' 4 1-0" 9' #4@16' 0/C 12' 6' 30' . 12"1-! ... ,, 6' 3"-4" #6€!8' /J/C j 65 #5@8' D/C 1 6z I 8 1-01 4 1-8,tl,6 1-31 39' IH/116' D/C 12.1 i 18' 6" 4E .. , , RETAINING WALL NOTES: 110111 MA TERJALS: 8, 14''ALLS SHOVI.D BE GROl.lTED AT 4' H£!JGHT IN."ERVALS. CONTP.ETE: ft: "" 2500 PSI@ 28 DA Y.S. CtRQUTING Si-lOULO SE PERFORMED AS SOON AS POSS.lBLE REINR'JRCJNG STEEL: ASTM li."615 GRADE 60. AFTfR THE CONCRETE MASONRY UNITS ARE PlACED. CONCRET'E MASONRY UNITS; ASTM C 90 MORTAR: USE OBP TYPES PER ASTM C 270 9. t'R.OVlDE CONTROL JOJNTS Ar 4()' 0/C MAX, GROUT: IJSE 2000 PSl@2f:i WIY5 ff.R A5TM C 476. CEMENT: PORTLAND CEMENT PER ASTM C·150 7YPE lf/V. tO. BfJJWlNG DEPARTMENT INSPECTIDJV SHAll BE OF THE FOlf..OWJNG STEPS: 1st. FOUNDATION TRENCH WITH SECURED REINFORCING S!ffi.. GENERAL NOTES: 2nd. BWCK WAU W!TH RElNFORONG STEEL BEFORE GROUT. 3rd, M/D·HElGf/T GROUTING FOR WALI.S OVER 4' HIGH. 1, AU MATERIAlS, PROOUCTS1 WORKMENSHIP, TESTING AND 4th GR.OUTED W.All AND DIML~~ 5'/STEM, !NSPl:CTION SHALL a:JMPLY WITH THE 2-0i'JJ CBC. St!r. BACKFILL AND-F!NAL 2, All FOOTINGS SHALL Bf POURED ON UNDIS11JRBl!D NIIWPAl. 11. OMIT HEAD JOINTS AT FIRST COURSE AT EVERY 32~ 0/C WITH GROUND OR ON /JNDJSWRIJED ENGINEERED FILL 1 Qi FT. OF' ,i; GRAVEL FOR WfN'IIOLE WI/EN rHf WALL IS l£5S THAN 'l' GH. J. ~l.4U SHAU BE LAID 7RUE AND PLUMB, AND All. CELLS 12. PROVlOE 4~ fif SOR 35 PERFORATED PIPE WITH PERl'OPA110NS fl ESSI SHALL BE GP.OUTED SOUD. "( DOWN AT 1 % MIN, Sl..OPE WITH 1 Cf, OF 3/4" GRAVEL ~' 4. All SPUCES SHALL 8£ 4B B4R OWJETERS, Wl'APPEO WI1H MIRAFl J,//JN Ft/. T£R FABRIC OR cQ/IAI., BA<X " Dl(AINAGE SYSTEM SHAU HAVE 'TH: CONNECrION AND NON• 1' vv ~ 5. All VERT!CALANDHORJZONTA! 8AR5SHAU 8E71ED PERPORATel> 2"f9 DUnEi P!FE AT EVERY 10' QIC THROI.JGH -1:IJ I TOGETHfJl THE WALL AT 2 % St.OPE ABOYE THI: FI/il/SHED SURFACE. ., "' ex,. 1 /I01 "' 6, DO NOT USE HEAVY COMPACTION EQillPM!1Ni ADJACflNT TO • • THE WAlL. rHE CONTRACTOR 'SHAi1. BE RESPONSIBLE FOR. ANY DAM4&"ES ro THE WAl.L RESJJL11NG FllOM INAPPIWPRIATE ~¥ CIV\\. ~~ Cl:JMPACTlON TECNIQtJES AND EQUIPMENTS. OFc,-1.lf-- J, THE RETAINING WALLS SHALL NOT BE 8ACKFI1.LED UNTll AT l.EAST 14 DAYS· UNLESS f>R.OPER SWORING LS PROVIDED. , \ CONT/lat. .JDINT II AS BUIL T11 -' BLDCf< WALL 'rl/ RnHF'ORCJNG &ft&.~/1 \ ~ P£R lJEi'll!LS. (2-t7-!.:!J I ------RCE ~(~ EXP, Ce·,22·($ DATE t.f MJRZ. cam. ! TOP 4S' REIJUN€JJ - -PRD\/JJJ£ 24" HIN. LAP AND HAJNT NH S-.....,,,, v----.... CC.tAR FROM SUII,.., REVIEIJED BY• <;; ~ I" ~~RJJ~ 3· 5-1'1 .. " . • • " . " DATE . . • . . . • • ~ ~ . ' . . • . . " I CITY OF CARLSBAD . • . • • 0 ~ .. " " . .. ' . .. . ' " I-" .. 4 ENGINEERING DEPARTMENT . 7 " . .. ~~ .. .. • ... • ~ ' . . . ~ . . .. • • Q wi11 -• \, k GRADING PLANS FOR: . . .. •. • • " • -ili . .. . •._:m . ~ !i1 " • • • MUROYA • 0 .'. .. .-... m-, ~ii! MASONRY RETAINING WALL DETAILS 71.'._'.IJ I I I I \ i~ 111~' \_ __ \,, ,I Irr IU HlJRZ. CONT, t JJIJTT!JM .. PNl.'JV1]}E 24~ ' APPROVE~ j 7, ~, GLEN K. ~ 3' flfJ.N. LAP AMJ HAJNTAJN 3" CU'Ale nmH SO).L, ~ TllRAL SDIL ENGINEERIN MANAGER PE 41204 EXPIRES 03/31/13 AT ~ ct/NNJCTF:0 f'IlL ,,.., /2-(t"--13 /f.'13 11\ A&-C&.tl( .. :, DWNBY:~ I DATE INITIAL DAIT INITIAL DAIT INITIAL CHKD 8Y: M PROJECT NO. DRAWING NO. FOOTING STEP DETAIL ENGINEER OF WORK REVISION DESCRIPTION . OTHER APPROVAL CITY APPROVAi. RVWD BY: Ba CT 06-27 4',"-7A 2 -#4 HOR AND VERTICAL FENCE POS ::I ~ w ei • 00 I <D IZONTAL \ AROUND T TYP • r-- • N I'-. . ~ ~ st- -1---- - N I '-. ~ ~ • <D st- I -1---- - L{) • N I '-. ~ ~ st- ---- • N I '-. ~ ~ st- • r-- 7' -OH 1 '-0" 6' -0" '\ '-( - FL 305.60 / -/ FL 305.40 -/ / FL 305.60 -/ V -.. .. .. ., V .. I SEE NOTE_) 17' -0" OVERALL 8' -0" .. 8" 3' -5" .n ' .n -- • N I '-. ~ 6 .. TYP ~ _r st- ----r- 7 11 " N I'-. . ~ ~ st- ----r- • N I'-. . ~ ~ st- -r---- -r- • N 6" I '-. ~ ~ st- .. .. -. . .n - F T N . NOTE. FIVE 00 HIGH CHAIN LINK FENCi G EMBED POSTS 18" DEEP IN WALLS AND ENCASE WITH CLASS B MORTAR. PLAN 3/4" = 1 '-0" #4 @ 8 --------c TW 310.63 #5 -SEE NOTE 1 #4[@ 7 7" n - -( 3' -4" 2' -0" . . .n - ' ' ' I I ,-1 ' I ' ' I ' ' I ' I ' -' • <D I -:..- / / I / / l I / / I / I I '~ / ' ' , I -l ' - 2' -2" i-1 '-2" TW 313.63 #5 n -SEE NOTE 1 #4 n TYP -'--...I I ~ '--- r- ~ 2:1 ------------- • 0 I N 2: 1 w -0 ~ • 0 I <D ---------------.. ----- • 0 I st- BOTTOM OF EMERGENCY SPILLWAY ~ ,-------, 8" TW 308.51 -TOTAL 3 #5 -TOTAL 4 BW 309.63 Cl. <( 0:: >-I <( Cl. ~ 0:: ..J ..J 0 Cl. w (/JI-::, >-0 u 0:: zc., w 0:r: 0:: I-w-::;;~ Wo w z ::J #5 J TYP #5 L@ 8 TYP -- (CENTERED) 7" H _.--#51 TYP 7" 5' -6" #5 n TYP #4•@ 8 TYP 1----""' ...__ #4 TYP #4 @ 7 TYP #4 LJ @ 8 BOTH WAYS 3" CLR #4 @ 18 BOTH WAYS 7" 1 FINISH GRADE ----"THOROSEAL" (OR EQUIVALENT) TYP 1 _.,v--DRAINAGE PANEL V MIRADRAIN 6000 · (OR EQUIVALENT) TYP NOTE: CHAIN LINK FENCING NOT SHOWN FOR CLARITY. SECTION A-A 3/ 4" = 1 · -0" 8 n H #4 TYP .,..--#4] TYP #4[ -- #5 J 1 '-8" #5 -SEE NOTE 1 ~ #5 r@ 12 I ,..--q_ 18"¢ RCP PER CIVIL PLANS #8 -TOTAL 2 (FULL HEIGHT) ...___ #4 L TYP .___ #5 TW 307.60 (~~F:::::::::L~:=::~~~t:::===:,.,~---~;;;,~~: = 2" CLR TYP ,.,,.,,., (CENTERED) #5 TYP 7" t TW 306.60 OG AND FL 305.60 BW 302.84 08-2.s-11 Job No.: 548-002 ,.,,., EL 306.76 #5[@ 7 FL 306.80 / / / / / ,.-,.-#5 (CENTERED) I RIP-RAP PER CIVIL PLANS 3" CLR -0.5% #4 TYP BW 302.84 2" CLR #4 TYP SIMON WONG ENGINEERING 9968 Hibert Street, Second Floor Son Diego, California 92131 #4 u TYP NOTES: 1. EXTERIOR WALL TRIM REINFORCEMENT SHOWN. FOR ADDITIONAL EXTERIOR WALL REINFORCEMENT, SEE SECTIONS A-A, B-B, C-C, AND D-D. 2. CHAIN LINK FENCING NOT SHOWN FOR CLARITY. ELEVATION 3/ 4" = 1 '-0" #5 - TOTAL 4 EL 305.88 #4] BW 304.87 INLET BOX PER SAN DIEGO REGIONAL STANDARD DRAWING D-41 A FL 306.84 (858) 566-3113 NOTE: FOR SECTIONS D-D, E-E, F-F, G-G, AND H-H, SEE SHEET 16 OF 17. SECTION 8-8 3/ 4" = 1 '-0" #4r- (CENTERED) SECTION C-C 3/4" = 1 '-0" "AS BUILT" ;Z@~ RCE 42,6(,3 EXP. u·J0-(5 REVIEWED BY: LZ-t?-(3 DATE DATE ~ CITY OF CARLSBAD ~7 i-----+---+-------------+---+------t---i--------t ~ ENGINEERING DEPARTMENT L...!1J 1----+--+-------------+---+--+--t----t ;;;G;;R.:;:;U>~ING~~PLANS~;;;:=;;l'O;;R:~========~==; MUROYA DRAINAGE STRUCTURE DETAILS NO. 1 GLEN K. VAN PF;SKI , 1¢1,111 1-=-:-::-=+-=-+,r--,,-,;----;:;;;--;-;::-=----------+----t---+--t----t ENG. MANAG R PE 41204 EXPIRES 03 31 13 DATE tl-tG,·t-3 ~63 t A~·@lf.tlr oWN BY: PROJECT No. I DRA\\1NG No. DATE INITIAL . REVISION DESCRIPTION DATE INITIAL DATE INITIAL CHKD BY: ESN CT 06-27 471-7A ENGINEER OF I\ORK OlHER APPROVAL CITY APPROVAL RVWD BY: CS 110111 7" 5' -6" 7" 7" 5' -6" 7" 7" 5' -6" 7" #5 TYP 1 ' - 1 ' -1 ' -1 ' --1 '-1 ' - 1 ' - 1 ' -.~ t 1 /2" 4 4 1 /2" 4 1 /2" 4 1 /2" 4 1 /2" 4 1 /2" 4 1 /2" 4 1 /2" FINISH ' ' ' • I GRADE I I I · ..•• ·>::, .. '• I I I ' ,-; : / ,?>;}'. I I ' ··'.:'•::,·-,.:-.· ~ #4 @ 7 TYP • I I I I . . . I 0 Q. I I I #5L@ 8 TYP ~ I ~ #5 TYP 7 r 6 .. 1P #5 TYP -~ L,-- I I L--' (CENTERED) • I I I i..-I I LI • 1 I I t I" 1~ DRAINAGE PANEL MIRADRAIN I 6000 I • j (OR EQUIVALENT) TYP I I "THOROSEAL" ~- • I I I I I (OR EQUIVALENT) 7 I r 6 .. 1P I • ·J TYP ( #4 LJ @ 8 BOTH WAYS • •' I ~ FILTER FABRIC ENVELOPE ~ ~---I I - ----~--, - r 1 MIRAFI 140N (OR EQUIVALENT) TYP I I I 1 '-0" 1. • t ~ I I" 1'-0"-' #5 -TOTAL 3 TYP #5 -TOTAL 4 TYP M-"1 ~ 2" CLR v / r J • 'J ~ -- [' ___ J il ---,, - --I-~--------,-----I-~ ._ ___ -~---- ........... • l"'"""":1 • -. .,. ----J --' 1""'""'" 3/4" CRUSHED '"""'~ 0 :::::::::::'r. f, ',f•:-:,:,:-:,:::: :I ROCK #4 I 1::::::::::: . ...... or . ~ t' • "" ...... I/ -I"""' .. flo:::::::::::::i c 1 cu FT /FT) ..... ...•.•. !'I ..l... / /" • l • .:.'.,... • , -~----+----. -,_ ----~ i---------. - ---• . ..:.:,:.:.:.:.:J TYP I-1-----t-- - -~-,_ ---I-I-1-----I-• --'" ((#4 t L-4"¢ SCH 40 PERFORATED ' I"-// 3" CLR -@ 18 BOTH WAYS I'--... #4 -TOTAL 3 (_ #5 -TOTAL 3 TYP PVC PIPE (OR EQUIVALENT) v L-- EXTEND TO APPROVED OUTLET V -SEE CIVIL PLANS TYP ' // NOTE: CHAIN LINK FENCING NOT SHOWN FOR CLARITY. NOTE: CHAIN LINK FENCING NOT SHOWN FOR CLARITY. #5 -TOTAL 3 TYP SECTION D-D SECTION F-F 3/ 4" = 1 '-0" NOTE: CHAIN LINK FENCING NOT SHOWN FOR CLARITY. 3/ 4" = 1 '-0" SECTION E-E 3/4" = 1 '-0" #4[ TYP A A V V - ~ • #4]@ 7 #4 TYP (TRIM AROUND ,_ . -. C PIPE OPENING I AS REQUIRED) --· L--.... 1----· L--I-, L I---· L--~ ~ . I II 7. I le ' ,, • I/ ,\ J-., I " PIPE OPENING #5 TYP-/ ;<:, I / le / • 11011'1 I l/ I/ ' ' I IA, ,/ ' . ,_.., ,I I #5, TYP (TRIM -~--J ADDITIONAL #5 HORIZONTAL I •L .... -. L L-·-r-....., -+-I AROUND OPENING REINFORCEMENT -TOTAL 8 ' • I/ ·/ ( 4 EACH FACE) I I AS REQUIRED) "' / I'\. / / I I • K I\ I ;x / L--#5 TYP , / -~ I~ ~ • • I " st :J 1 I i--~~3" CLR TYP ' -~ ~ --~ ~ ~ ~,,... #4 J@ 8 -r--- 1/2" TYP \ 1 #4 TYP • (TRIM AROUND ..... I ~ le ->-5 • -~ I/' ~ - PIPE OPENING '-' AS REQUIRED) ~ Ill _., • • ---\ --• """ --#5J TYP ADDITIONAL #5 VERTICAL • • • ' • REINFORCEMENT -TOTAL 8 '\ ( 4 EACH FACE) NOTE: CHAIN LINK FENCING NOT SHOWN FOR CLARITY. #4LJTYP #5 \._/ #4 TYP "AS BUILT" NOTE: ALL REINFORCEMENT TO BE 2" MIN CLEAR FROM PIPE OPENING. f2@tnut£ tZ-t7-t.3 SECTION G-G SECTION H-H RCE 4~61:J EXP G-30-15 DATE £,_...,...,!"< REVIEWED BY: :~ ~~ ~"-°'' r o "' 3/ 4" = 1 '-0" 3/ 4" = 1 '-0" ~-~J4-< 3.5. Jt.f I -• I'-• ·. 1 lt;i,f IN R lJ DATE ~ No \, 699B • CML 2 ~ CITY ~ OF CARI.SBAD .,. .,,it;.• ~ 0, CM-'' ........ os-2.5-11 6 ENGINEERING DEPARTMENT 7 GRADING PLANS roR: MUROYA DRAINAGE STRUCTURE DETAIIB NO. 2 I/ ' SIMON WONG V /\ \/0 ~\ ENGINEERING APPROVE~ ;/ J. ~ GLEN K. VAN PJ;KI J · 10/2 9968 Hibert Street, Second Floor (2-t~·l:?, ~0 It\ A& ·toll(l.c ENG. MANAGrn PE 41204 EXPIRES 03 31 /13 DAiE ~ San Diego, California 92131 DWN BY:--::::::ll!:::: I Job No.: 548-002 (858) 566-3113 DATE INITIAL DATE INITIAL DATE INITIAL PROJECT NO. I DRAv.lNG NO. ENGINEER OF v«lRK REVISION DESCRIPTION OTHER APPROVAL CITY APPROVAL CHKD BY: ESN" CT 06-27 RVWD BY: cs 471-7A GENERAL NOTES: 1. THE PROJECT SPECIFICATIONS SHALL CONFORM TO THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION, 2009 EDITION, UNLESS OTHERWISE NOTED. 2. THE STRUCTURAL DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE CIVIL DRAWINGS. 3. THE CONTRACTOR SHALL REVIEW EXISTING CONDITIONS ON THE SITE DURING THE BIDDING. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO STARTING WORK. THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES OR INCONSISTENCIES PRIOR TO PROCEEDING. 4. UNLESS NOTED OR SHOWN OTHERWISE, ALL PHASES OF WORK ARE TO CONFORM TO THE MINIMUM STANDARDS OF THE CALIFORNIA BUILDING CODE (2010 EDITION), AND ANY A.S.T.M. SPECIFICATIONS ON WHICH THESE STANDARDS ARE BASED. WHERE CONFLICT BETWEEN BUILDING CODES AND SPECIFICATIONS OCCUR, THE MOST STRINGENT REQUIREMENTS SHALL GOVERN. 5. ALL A.S.T.M. DESIGNATIONS REFERRED TO ON THESE DRAWINGS SHALL BE THE LATEST ADOPTED OR REVISED SPECIFICATION, AS OF THE DATE OF THESE DRAWINGS. 6. ALL DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS, SECTIONS AND DETAILS. DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. 7. NOTES AND DETAILS ON THE DRAWINGS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. 8. THE STRUCTURAL DRAWINGS SHOW ONLY THE BASIC STRUCTURAL REQUIREMENTS. REFER TO THE CIVIL DRAWINGS FOR NON-STRUCTURAL ITEMS, SUCH AS: A. DIMENSIONS AND ELEVATIONS NOT SHOWN ON STRUCTURAL DRAWINGS. B. EMERGENCY SPILLWAY. C. RCP DIMENSION AND ALIGNMENT. D. RIP-RAP. E. DRAINAGE OUTLET CONNECTIONS. 9. THE STRUCTURAL CONTRACT DOCUMENTS AND SPECIFICATIONS REPRESENT THE FINISHED STRUCTURE. UNLESS NOTED OTHERWISE, THEY DO NOT INDICATE THE METHOD OF CONSTRUCTION. 10. NEITHER THE OWNER NOR THE ENGINEER WILL ENFORCE SAFETY MEASURES OR REGULATIONS. THE CONTRACTOR SHALL, AT HIS OWN EXPENSE, DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES, INCLUDING SHORING AND BRACING AND SHALL BE SOLELY RESPONSIBLE FOR CONFORMING TO ALL LOCAL, STATE AND FEDERAL SAFETY AND HEALTH STANDARDS, LAWS AND REGULATIONS. SITE OBSERVATION VISITS BY THE STRUCTURAL ENGINEER SHALL NOT INCLUDE INSPECTION OF THE ABOVE SAFETY ITEMS. 11. SATISFACTORY EXECUTION OF CONSTRUCTION IS DEPENDENT UPON CONFORMANCE WITH THE INTENT OF THESE DRAWINGS. THE OWNER OR CONTRACTOR SHALL RETAIN A CALIFORNIA LICENSED CIVIL OR STRUCTURAL ENGINEER DURING CONSTRUCTION TO OBSERVE THE CONSTRUCTION AND STATE THAT THE STRUCTURE HAS BEEN BUILT IN GENERAL CONFORMANCE WITH THE INTENT OF THESE DRAWINGS. 12. WHERE NO CONSTRUCTION DETAILS ARE SHOWN OR NOTED FOR ANY PART OF THE WORK. THE DETAILS SHALL BE THE SAME AS FOR OTHER SIMILAR WORK. DESIGN BASIS: CODE: 2010 CBC (CALIFORNIA BUILDING CODE), CCR, TITLE 24, PART 2 SOIL: ACTIVE EFP = 35 pcf SLIDING COEFFICIENT = 0.35 WATER PRESSURE = 62.4 pcf -·~ ,~ s1io,, ~ . n,:;, "{. , C) "o.., \~ f\. • r--~ V5592 CML ,,. ,. °' ""''~ of-z.S-11 Job No.: 548 002 SIMON WONG ENGINEERING 9968 Hibert Street, Second Floor San Diego, California 92131 (858) 566 3113 FOUNDATION: 1. ATTACH ONE COPY OF SOILS REPORT TO THE APPROVED SET OF CONSTRUCTION DOCUMENTS. SOILS REPORT SHALL BE PART OF THESE NOTES. PRIOR TO THE POURING OF CONCRETE AND PRIOR TO THE CONTRACTOR REQUESTING A BUILDING DEPARTMENT FOUNDATION INSPECTION, THE GEOTECHNICAL ENGINEER SHALL INSPECT AND APPROVE THE FOOTING EXCAVATIONS. HE SHALL POST NOTICE ON THE JOB SITE AND ADVISE THE BUILDING INSPECTOR IN WRITING THAT THE WORK SO INSPECTED MEETS THE CONDITIONS OF THE REPORT. A WRITTEN CERTIFICATION TO VERIFY THAT: A. THE PAD FOR THE STRUCTURE WAS PREPARED IN ACCORDANCE WITH THE SOILS REPORT. B. THE UTILITY TRENCHES HAVE BEEN PROPERLY BACKFILLED AND COMPACTED, AND C. THE FOUNDATION EXCAVATIONS COMPLY WITH THE INTENT OF THE SOILS REPORT. 2. SOILS REPORT PREPARED BY: GEOCON INCORPORATED, "MUROYA PROPERTY, CARLSBAD, CALIFORNIA", DATED JULY 14, 2009. 3. SOIL REMOVAL AND RECOMPACTION SHALL BE DONE PER SOILS REPORT RECOMMENDATIONS UNDER GEOTECHNICAL ENGINEER'S SUPERVISION AND INSPECTION. 4. FOOTING: DESIGN SOIL PRESSURE: FOOTING TYPE STATIC BEARING PRESSURE CONTINUOUS FOOTING 2000 P.S.F. ON COMPACTED ENGINEERED FILL 5. SLAB BASE AND COMPACTION TO BE IN ACCORDANCE WITH SOILS REPORT. 6. NO PIPES OR DUCTS SHALL BE PLACED IN SLABS OR WALLS UNLESS SPECIFICALLY DETAILED OR APPROVED BY THE ENGINEER. 7. ALL WALLS RETAINING EARTH SHALL DRAIN TO DAYLIGHT OR OTHER DRAINAGE. 8. ALL ABANDONED FOOTINGS, UTILITIES, ETC., THAT INTERFERE WITH NEW CONSTRUCTION SHALL BE REMOVED. 9. THE CONTRACTOR SHALL DETERMINE THE LOCATION OF UTILITY SERVICES IN AREAS TO BE EXCAVATED BEFORE BEGINNING EXCAVATION. EXERCISE EXTREME CAUTION IN EXCAVATING AND TRENCHING. DAMAGE CAUSED AS A RESULT OF FAILING TO EXACTLY LOCATE AND PRESERVE ALL EXISTING UNDERGROUND UTILITIES ARE THE RESPONSIBILITY OF THE CONTRACTOR. 10. THE CONTRACTOR SHALL PROVIDE FOR THE DESIGN, APPROVALS, PERMITS, INSTALLATION AND MONITORING OF ALL CRIBBING, SHEATHING AND SHORING REQUIRED TO SAFELY RETAIN TEMPORARY EXCAVATIONS. 11. ALL PLANTERS IN CLOSE PROXIMITY TO THE STRUCTURE SHALL HAVE ADEQUATE DRAINAGE OF SURFACE WATER TO PREVENT SATURATION OF SOIL UNDER FOUNDATION. ABBREVIATIONS: BW C.J. CLR FL OG RCP SDRSD TW TYP LEGEND: 0 )( )( 0 BOTTOM OF WALL CONSTRUCTION JOINT CLEAR FLOW LINE ORIGINAL GRADE REINFORCED CONCRETE PIPE SAN DIEGO COUNTY REGIONAL STANDARD DRAWINGS TOP OF WALL TYPICAL FIVE FOOT HIGH CHAIN LINK FENCE CONCRETE: 1. ALL CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF A.C.I. 318-LATEST EDITION "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS", EXCEPT AS MODIFIED BY THE SUPPLEMENTAL REQUIREMENTS CONTAINED HEREIN OR SHOWN ON THE DRAWINGS. 2. ALL CONCRETE SHALL BE 150 P.C.F. HARDROCK, MIXED PER A.S.T.M. C-94, AND SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3,600 P.S.I. AT 28 DAYS AND A MAXIMUM WATER TO CEMENT RATIO NOT EXCEEDING 0.40. 3. THE MAXIMUM SIZE AGGREGATE IN FOUNDATION AND MASS CONCRETE WORK SHALL BE 1 INCH. THE MAXIMUM SIZE AGGREGATE IN SLABS ON GRADE, WALLS, AND ALL OTHER CONCRETE SHALL BE 3/4 INCH. 4. CEMENT SHALL CONFORM TO A.S.T.M, C-150, TYPE II, LOW ALKALI. AGGREGATES FOR NORMAL WEIGHT SHALL CONFORM TO A.S.T.M. C-33. 5. ADMIXTURES AND COLORS (EXCEPT AS NOTED HEREIN) SHALL NOT BE USED UNLESS SUBSTANTIATING DATA IS SUBMITTED TO AND REVIEWED BY THE ENGINEER OF RECORD. 6. CONCRETE MIXES SHALL BE DESIGNED BY A QUALIFIED TESTING LABORATORY. THE MIX DESIGNS SHALL CONFORM TO C.B.C. SEC. 1905 UNLESS OTHERWISE NOTED. 7. NON-STRUCTURAL STEEL EMBEDDED IN CONCRETE SHALL BE GALVANIZED OR PAINTED. ALL DAMAGED GALVANIZED AREAS SHALL BE REPAIRED PRIOR TO EMBEDMENT. 8. PROVIDE 2-#5 DIAGONAL BARS AT CORNERS OF WALL, FLOOR, AND ROOF OPENINGS AND INSIDE CORNERS OF FLOORS, UNLESS OTHERWISE NOTED. 9. READY MIXED CONCRETE SHALL CONFORM TO (A.S.T.M. C-94). 10. PLACEMENT OF CONCRETE SHALL CONFORM TO A.C.I. 304. CLEAN AND ROUGHEN TO 1/4" AMPLITUDE FOR ALL CONCRETE SURFACES AGAINST WHICH CONCRETE IS TO BE PLACED. 11. ALL EXPOSED CONCRETE SHALL HAVE A SMOOTH FORM FINISH USING B-B PLYFORM, CLASS I, EXT-A.P.A. PLYWOOD. 12. ALL SLABS SHALL HAVE A TROWELED FINISH EXCEPT AS NOTED ON THE DRAWINGS. 13. ALL REINFORCING STEEL, ANCHOR BOLTS, DOWELS AND INSERTS SHALL BE WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE. 14. IF THE CONTRACTOR DESIRES TO MAKE ANY CONSTRUCTION JOINTS OTHER THAN THOSE SHOWN ON THESE DRAWINGS, HE SHALL SUBMIT DETAILS OF CHANGES TO THE ENGINEER OF RECORD FOR REVIEW BEFORE STARTING WORK. 15. NO BRICK OR POROUS MATERIAL SHALL BE USED TO SUPPORT FOUNDATION STEEL OFF THE GROUND. 16. PROVIDE 3/4 INCH CHAMFER ON ALL EXPOSED CONCRETE CORNERS, U.0.N. 17. ALL REINFORCING BARS SHALL BE PROVIDED WITH THE FOLLOWING CONCRETE MINIMUM COVER: FOOTINGS CAST AGAINST EARTH FORMED CONCRETE EXPOSED TO EARTH, WEATHER OR LIQUID REINFORCING: 3" 2" 1. ALL REINFORCING STEEL SHALL BE PLACED IN CONFORMANCE WITH THE C.B.C., AND THE "MANUAL OF STANDARD PRACTICE" BY THE C.R.S.I. OR AS MODIFIED BY THE CONSTRUCTION DOCUMENTS. 2. REINFORCING BARS SHALL CONFORM TO A.S.T.M. A-615, DEFORMED GRADE 60, EXCEPT #3 BARS MAY BE GRADE 40. REINFORCING BARS THAT ARE TO BE WELDED SHALL COJ:JFORM TO A.S.T.M. A-706, DEFORMED GRADE 60. 3. WELDING OF REINFORCEMENT SHALL BE IN ACCORDANCE WITH A.S.T.M. A-706 WITH LOW HYDROGEN ELECTRODES AND STRUCTURAL WELDING CODE REINFORCING STEEL SHALL CONFORM TO A.N.S.I. / A.W.S. 01 .4. MINIMUM TENSILE STRENGTH OF WELD METAL SHALL BE 90 K.S.I. ALL WELDING SHALL BE PERFORMED BY CERTIFIED WELDERS. 4. ALL REINFORCING BAR BENDS SHALL BE MADE COLD, UNLESS OTHERWISE PERMITTED BY THE BUILDING OFFICIAL. 5. WELDED WIRE FABRIC SHALL CONFORM TO A.S.T.M. A-185, AND SHALL BE LAPPED 1 SPACE AND 12" MINIMUM. 6. DOWELS BETWEEN FOOTINGS AND WALLS OR COLUMNS SHALL BE LAPPED WITH THE SAME GRADE, SIZE, SPACING AND NUMBER AS THE VERTICAL REINFORCEMENT. 7. REINFORCING SPLICES SHALL HAVE A MINIMUM LAP LENGTH OF 40 TIMES THE BAR DIAMETER. 8. SPACING OF REINFORCING BARS ARE IN INCHES. SUMMARY OF SPECIAL INSPECTION REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION VERIFICATION AND INSPECTION 1. INSPECTION OF REINFORCING STEEL, INCLUDING PRESTRESSING TENDONS, AND PLACEMENT. 2. INSPECTION OF REINFORCING STEEL WELDING IN ACCORDANCE WITH REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION TABLE, ITEM 5b. 3. INSPECT BOLTS TO BE INSTALLED IN CONCRETE PRIOR TO AND DURING PLACEMENT OF CONCRETE WHERE ALLOWABLE LOADS HAVE BEEN INCREASED. 4. VERIFYING USE OF REQUIRED DESIGN MIX. 5. AT THE TIME FRESH CONCRETE IS SAMPLED TO FAIBRICATE SPECIMENS FOR STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE OF THE CONCRETE. 6. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES. 7. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES. 8. INSPECTION OF PRESTRESSED CONCRETE: a. APPLICATION OF PRESTRESSING FORCES. b. GROUTING OF BONDED PRESTRESSING TENDONS IN THE SEISMIC-FORCE-RESISTING SYSTEM. 9. ERECTION OF PRECAST CONCRETE MEMBERS. 10. VERIFICATION OF IN-SITU CONCRETE STRENGTH, PRIOR TO STRESSING OF TENDONS IN POSTTENSIONED CONCRETE AND PRIOR TO REMOVAL OF SHORES AND FORMS FROM BEAMS AND STRUCTURAL SLABS. 11. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE CONCRETE MEMBER BEING FORMED. 12. EXPANSION ANCHORS CONTINUOUS PERIODIC INSPECTION INSPECTION X X X X X X SUMMARY OF SPECIAL INSPECTION REQUIRED VERIFICATION AND INSPECTION OF SOILS VERIFICATION AND INSPECTION 1. VERIFY MATERIALS BELOW FOOTINGS ARE ADEQUATE TO ACHIEVE THE DESIGN BEARING CAPACITY. 2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED PROPER MATERIALS. 3. PERFORM CLASSIFICATION AND TESTING OF CONTROLLED FILL MATERIALS. 4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES DURING PLACEMENT AND COMPACTION OF CONTROLLED FILL. 5. PRIOR TO PLACEMENT OF CONTROLLED FILL, OBSERVE SUBGRADE AND VERIFY THAT SITE HAS BEEN PREPARED PROPERLY. CONTINUOUS PERIODIC INSPECTION INSPECTION X X X X X "AS BUILT" ~ tZ-t7·t.3 RCE 4ofj(~ EXP 0-:xJ ·lo DATE REVIEWED BY: t2. '1. , t 7 I · ~-5·1~ ~~,OR (, . DATE 9. HOOK LENGTH FOR REINFORCING BAR SHALL CONFORM TO STANDARD HOOK LENGTH SPECIFIED IN ACI 318, UNLESS OTHERWISE NOTED. ~ CITY OF CARLSBAD ~ 1-----+--+-------------+---+---t---t---, L.!!J ENGINEERING DEPARTMENT LJZ._j l--+--+-------------+----+---+-~1--; !:;;G:;;:RAD:;::;;;;;IN~G~PLANS;:::;:;;;;::;;;ro;;R:~::::::::::::::::::::::::::::::::::::::=:::=-=::=~ MUROYA DRAINAGE STRUCTURE NOTES APPROVEDM -./7/,, ~ ,7 GLEN K. VA~:~SKI ----4=..,, j( ~~~-. qiA_/11 1----l----+-------------+---+---+--1----t ENG. MANAGER PE 41204 EXPIRES 03/31/13 DATE DWN BY: I PRo.ECT NO. I DRAWING NO. ~DA.;.;;lE::.....i..:.IN:..;.ITI;;,;;AL;.+-.:.;DA.;;.;lE::.....i..:.IN;;.;;111.;.;:AL'-I CHKD BY: Eg: ,, CT 06-27 471-7 A OTHER APPROVAL CITY APPROVAL RVWO BY: . DAlE INITIAL ENGINEER OF WORK REVISION DESCRIPTION 110111 C 1-1-:E ...., C) O_,::. -...., 1-1-1-1-...., I ~