HomeMy WebLinkAbout2535 GLASGOW DR; ; AS160115; Permit10/20/21 11:26 AM AS160115 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 2535 GLASGOW DR
Permit Type: SPRINK
Parcel No: 2081911500
Lot #: 0
Reference No.:
Permit No: AS160115
Status: ISSUED
Applied 5/2/2016
Approved: 6/9/2016
Issued: 6/9/2016
PC #: Inspector:
Project Title: 2535 GLASGOW DR SFR: 4,994 SF LIV / 648 SF GAR / 248 SF
PATIO THIS SUBMITTAL TO CONSIST OF THE BLUFFS PA 5
LOTS 25-60 36 SFR
Applicant:
INNOVATIVE FIRE PROTECTION INC
STE 101
8779 COTTONWOOD AV
SANTEECA
(619) 593-8200 (619)593-9133
Owner:
Fees ($) Add'I Fees ($) Total ($) Balance ($)
798 0 798 0
1/1
AS160115
2535 GLASGOW DR
2539 GLASGOW DR, 2543 GLASGOW DR
2547 GLASGOW DR, 2551 GLASGOW DR
2555 GLASGOW DR, 2559 GLASGOW DR
2563 GLASGOW DR, 2567 GLASGOW DR
2571 GLASGOW DR, 2575 GLASGOW DR
2579 GLASGOW DR, 2583 GLASGOW DR
2587 GLASGOW DR, 2591 GLASGOW DR
2595 GLASGOW DR, 2599 GLASGOW DR
2526 GLASGOW DR, 2530 GLASGOW DR
2534 GLASGOW DR, 2538 GLASGOW DR
2542 GLASGOW DR, 2546 GLASGOW DR
2550 GLASGOW DR, 2554 GLASGOW DR
2558 GLASGOW DR, 2562 GLASGOW DR
2566 GLASGOW DR, 2570 GLASGOW DR
2574 GLASGOW DR, 2578 GLASGOW DR
2582 GLASGOW DR, 2586 GLASGOW DR
2590 GLASGOW DR, 2594 GLASGOW DR
2598 GLASGOW DR
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 1 (LOT 51) (1HD)
2571 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 315 sq. ft.
COVERAGE PER SPRINKLER: 20x20-400 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 1 sprinkler
TOTAL SPRINKLER WATER FLOW REQUIRED: 21.0 gpm
TOTALS WATER REQUIRED (including hose): 26.0 gpm
FLOW AND PRESSURE (@ BOR): 21.0 gpm @ 28.7 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
AS 160115
2535 GLASGOW DR
E
0
0 0 LU
0
(I)
0 0
LU
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016R5 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV)-LOT 51(1HD).SDF
JOB TITLE: THE BLUFFS
0 0 0 0
0 ••• 0
0 0 0• 0 0 0 I
0
C
N
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016R5 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV)-LOT 51(1HD).SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 9 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.6 26.0 52.2
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE - 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES , 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 202.0 SOURCE 52.2 26.0
2 202.0 - - - - 42.8 - - -
2A 202.0 - - - - 41.8 - - -
D 202.0 - - - - 41.5 - - -
C 202.0 - - - - 35.5 - - -
2B 202.0 HOSE STREAM 34.2 5.0
2C 202.0 - - - - , 34.0 - - -
3A 206.0 - - - - 30.8 - - -
3B 208.0 - - - - 29.8 - - -
3 210.0 - - - - 28.7 - - -
4 212.0 - - - - 26.9 - - -
5 216.0 - - - - 23.6 - - -
6 218.0 - - - - 21.2 - - -
7 218.0 - - - - 21.2 - - -
8, 218.0 - - - - 20.1 - - -
101 218.0 - - - - 21.2 - - -
102 218.0 - - - - 21.2 ' - - -
103 218.0 K= 4.90 18.4 21.0
NOTES
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016R5 SYSTEMS\JP CALCS\THEBLUFFS-PLAN 1(REV)-LOT 51(1HD).SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 9.4
1 202.0 52.2 26.0 2A K1.000 T: 6.0 7.00 0.0
2 202.0 42.8 26.0 0.995 G: 1.0 52.00 0.181 9.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 42.8 26.0 D 1.0 psi; 26.0 gpm
2A 202.0 41.8 26.0
Pipe: 3 0.0 0.0 2.00 150 0.3
2A 202.0 41.8 26.0 C L1.000 ---- 0.00 0.0
D 202.0 '•41.5 26.0 1.025 2.00 0.157 0.3
Pipe: 4 0.0 Fixed Pressure Loss Device
D 202.0 41.5 26.0 28 6.0 psi, 26.0 gpm
C 202.0 35.5 26.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 1.3
C 202.0 35.5 21.0 2C L1.000 T: 7.0 7.00 0.0
2B 202.0 34.2 26.0 1.025 8.00 0.157 1.3
Pipe: 6 0.0 0.0 2.00 150 0.2
2B 202.0 34.2 21.0 3A L1.000 ---- 0.00 0.0
2C 202.0 34.0 21.0 1.025 2.00 0.105 0.2
Pipe: 7 0.0 0.0 36.00 150 3.2
2C 202.0 34.0 21.0 38 1.250 ---- 0.00 -1.7
3A 206.0 30.8 21.0 1.244 36.00 0.041 1.5
Pipe: 8 0.0 0.0 3.00 150 1.0
3A 206.0 30.8 21.0 3 1.250 ---- 0.00 -0.9
38 208.0 29.8 21.0 1.244 3.00 0.041 0.1
Pipe: 9 0.0 0.0 3.00 150 1.1
38 208.0 29.8 21.0 4 F1.000 ---- 0.00 -0.9
3 210.0 28.7 21.0 1.101 3.00 0.074 0.2
Pipe: 10 0.0 0.0 2.00 120 1.9
3 210.0 28.7 21.0 5 A1.000 C: 5.0 5.00 -0.9
4 212.0 26.9 21.0 1.049 7.00 0.142 1.0
Pipe: 12 0.0 10.4 8 9.00 150 3.3
4 212.0 26.9 10.6 6 F1.000 E: 7.0 12.00 -1.7
5 216.0 23.6 21.0 1.101 B: 5.0 21.00 0.074 1.6
Pipe: 13 0.0 0.0 54.00 150 2.4
5 216.0 23.6 10.6 8 F1.000 2E:14.0 19.00 -0.9
6 218.0 21.2 10.6 1.101 B: 5.0 73.00 0.021 1.5
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/2016RS SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV)-LOT 51(1HD).SDF
JOB TITLE: THE BLUFFS -
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: .13A 0.0 21.0 103 84.00 150 3.5
5 216.0 23.6 -10.6 103 F1.000 5E:35.0 45.00 -0.9
8 218.0 20.1 10.4 1.101 2B:10.0 129.00 0.020 2.6
Pipe: 14 0.0 0.0 11.00 150 0.0
7 218.0 21.2 0.0 F1.000 B: 5.0 5.00 0.0
6 218.0 21.2 0.0 1.101 16.00 0.000 0.0
Pipe: 15 0.0 0.0 12.00 150 0.0
101 218.0 21.2 0.0 F1.000 E: 7.0 7.00 0.0
7 218.0 21.2 0.0 1.101 19.00 0.000 0.0
Pipe: 16 0.0 0.0 1.50 150 0.0
102 218.0 21.2 0.0 F1.000 E: 7.0 7.00 0.0
7 218.0 21.2 0.0 1.101 8.50 0.000 0.0
Pipe: 18 4.90 21.0 Disch 11.00 150 1.7
8 218.0 20.1 0.0 F1.000 E: 7.0 12.00 0.0
103 218.0 18.4 21.0 1.101 B: 5.0 23.00 0.074 1.7
Pipe: 19 0.0 21.0 103 48.00 150 1.1
6 218.0 21.2 -10.4 5 F1.000 B: 5.0 5.00 0.0
8 218.0 20.1 10.6 1.101 53.00 0.021 1.1
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.006 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Note
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 1 (LOT 51) (2HD)
2571 GLASGOW' DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 233 sq. ft.
COVERAGE PER SPRINKLER: 18'X18'-324 sq. ft.
NUMBER OF SPRINKLERS' CALCULATED: 2 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 34.4 gpm
TOTAL WATER REQUIRED (including hose): 39.4 gpm
FLOW AND PRESSURE (@ BOR) : 34.4 gpm @ 31.4 psi
SPRINKLER ORIFICE SIZE: ' 1/2" inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV2)LOT 51(2HD).SDF
JOB TITLE: THE BLUFFS
w-1
0 0 0 0
0 • • • • 0
0 0 0 0 0 0•
ci' (N I
0
(N
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV2)LOT 51(2HD) .SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID, FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.5 39.4 73.6
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 39.4 GPM
TOTALHOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 34.4 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 202.0 SOURCE 73.6 39.4
2 202.0 - - - - - 53.3 - - -
2A 202.0 - - - - 50.3 - - -
D 202.0 - - - - 49.6 - - -
C 202.0 - - - - 42.6 - - -
2B 202.0 HOSE STREAM 39.9 5.0
2C 202.0 - - - - 39.4 - - -
3A 206.0 - - - - 34.0 - - -
3B 208.0 - - - - 32.8 - - -
3 210.0 - - - - 31.4 - - -
4 212.0 - - - - 28.0 - - -
5 216.0 - - - - 22.4 - - -
6 218.0 - - - - 16.0 - - -
7 218.0 - - - - 13.0 - - -
8 218.0 - - - - 17.6 - - -
101 218.0 K= 4.90 12.0 17.0
102 218.0 K= 4.90 12.6 17.4
103 218.0 - - - - 17.6 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV2)-LOT 51(2HD) .SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 20.3
1 202.0 73.6 39.4 2A K1.000 T: 6.0 7.00 0.0
2 202.0 53.3 39.4 0.995 G: 1.0 52.00 0.390 20.3
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 53.3 39.4 D 3.0 psi, 39.4 gpm
2A 202.0 50.3 39.4
Pipe: 3 0.0 0.0 2.00 150 0.7
2A 202.0 50.3 39.4 C L1.000 ---- 0.00 0.0
D 202.0 49.6 39.4 1.025 2.00 0.337 0.7
Pipe: 4 0.0 Fixed Pressure Loss Device
D 202.0 49.6 39.4 2B 7.0 psi, 39.4 gpm
C 202.0 42.6 39.4
Pipe: 5 H.S. 5.0 Disch 1.00 150 2.7
C 202.0 42.6 34.4 2C L1.000 T: 7.0 7.00 0.0
2B 202.0 39.9 39.4 1.025 8.00 0.337 2.7
Pipe: 6 0.0 .0.0 2.00 150 0.5
2B 202.0 39.9 34.4 3A L1.000 ---- 0.00 0.0
2C 202.0 39.4 34.4 1.025 2.00 0.262 0.5
Pipe: 7 0.0 0.0 . 36.00 150 5.4
2C 202.0 39.4 34.4 3B 1.250 ---- 0.00 -1.7
3A 206.0 34.0 34.4 1.244 36.00 0.102 3.7
Pipe: 8 0.0 0.0 3.00 150 1.2
3A 206.0 34.0 34.4 3 1.250 ---- 0.00 -0.9
3B 208.0 32.8 34.4 1.244 3.00 0.102 0.3
Pipe: 9 0.0 0.0 3.00 150 1.4
3B 208.0 32.8 34.4 4 F1.000 ---- 0.00 -0.9
3 210.0 31.4 34.4 1.101 3.00 0.185 0.6
Pipe:-10 0.0 0.0 2.00 120 3.3
3 210.0 31.4 34.4 5 A1.000 C: 5.0 5.00 -0.9
4 212.0 28.0 34.4 1.049 7.00 0.354 2.5
Pipe: 12 0.0 13.0 8 9.00 150 5.6
4 212.0 28.0 21.3 6 F1.000 E: 7.0 12.00 -1.7
5 216.0 22.4 34.4 1.101 B: 5.0 21.00 0.185 3.9
Pipe: 13 0.0 34.4 7 54.00 150 6.5
5 216.0 22.4 -13.0 8 F1.000 2E:14.0 19.00 -0.9
6 218.0 16.0 21.3 1.101 3: 5.0 73.00 0.077 5.6
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 1(REV2)-LOT 51(2HD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 13A 0.0 0.0 84.00 150 4.8
5 216.0 22.4 13.0 6 F1.000 5E:35.0 45.00 -0.9
8 218.0 17.6 13.0 1.101 23:10.0 129.00 0.031 4.0
Pipe: 14 0.0 17.4 102 11.00 150 3.0
6 218.0 16.0 17.0 101 F1.000 B: 5.0 5.00 0.0
7. 218.0 13.0 34.4 1.101 16.00 0.185 3.0
Pipe: 15 4.90 17.0 Disch 12.00 150 1.0
7 218.0 13.0 0.0 F1.000 E: 7.0 7.00 0.0
101 218.0 12.0 17.0 1.101 19.00 0.050 1.0
Pipe: 16 4.90 17.4 Disch 1.50 150 0.4
7 218.0 13.0 0.0 F1.000 E: 7.0 7.00 0.0
102 218.0 12.6 17.4 1.101 8.50 0.052 0.4
Pipe: 18 0.0 0.0 11.00 150 0.0
103 218.0 17.6 0.0 F1.000 K: 7.0 12.00 0.0
8 218.0 17.6 0.0 1.101 B: 50 23.00 0.000 0.0
Pipe: 19 0.0 34.4 7 48.00 150 1.6
8 218.0 17.6 -21.3 5 F1000 B: 5.0 5.00 0.0
6 218.0 16.0 13.0 : 1.101 53.00 0.031 1.6
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The: system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.004 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.2 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Note
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 2 (LOT 52) (1HD)
2567 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 176 sq. ft.
COVERAGE PER SPRINKLER: 20X20'-400 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 1 sprinkler
TOTAL SPRINKLER WATER FLOW REQUIRED: 21.0 gpm
TOTAL WATER REQUIRED (including hose): 26.0 gpm
FLOW AND PRESSURE (@ BOR) : 21.0 gpm @ 34.3 psi
SPRINKLER ORIFICE SIZE: 1/2' inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
Q
Q
0 LU
0
(I)
0.
0
LU
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV)-LOT 52(1HD).SDF
JOB TITLE: THE BLUFFS
0 0 0 0
0 • 0
0 0 0• 0• 0 •
-1 00 110 (N 0 I
C)
0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV)-LOT 52(1HD) .SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.6 26.0 57.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 202.0 SOURCE 57.8 26.0
2 202.0 - - - - 48.4 - - -
2A 202.0 - - - - 47.4 - - -
D 202.0 - - - - 47.1 - - -
C 202.0 - - - - 41.1 - -
2B 202.0 HOSE STREAM 39.8 5.0
2C 202.0 - - - - 39.6 - - -
3A 206.0 - - - - 36.5 - - -
3B 208.0 - - - - 35.4 - - -
3 210.0 - - - - 34.3 - - -
4 212.0 - - - - 32.5 - - -
5 216.0 - - - - 25.6 - - -
6 216.0 - - - - 24.6 - - -
7 216.0 - - - - 24.2 - - -
8 216.0 - - - - 23.8 - - -
9 226.0 - - - - 19.2 - - -
10 226.0 - - - - 18.9 - - -
11 226.0 - - - - 18.6 - - -
12 226.0 - - - - 18.6 - - -
13 226.0 - - - - 18.9 - - -
14 226.0 - - - - 19.3 - - -
101 226.0 - - - - 18.6 - - -
102 226.0 - - - - 18.6 - - -
103 226.0 K= 4.90 18.4 21.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS -PLAN 2 (REV)-LOT 52(1HD) .SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 9.4
1 202.0 57.8 26.0 2A K1.000 T: 6.0 7.00 0.0
2 202.0 48.4 26.0 0.995 G: 1.0 52.00 0.181 9.4
Pipe: 2 0.0 Fixed Pressure Loss Device -
2 202.0 - 48.4. .26.0 D 1.0 psi, 26.0 gpm
2A 202.0 47.4 26.0
Pipe: 3 0.0 . 0.0 2.00 150 0.3
2A 202.0 47.4 26.0 C L1.000 ---- 0.00 0.0
D 202.0 47.1 26.0 1.025 2.00 0.157 0.3
Pipe: 4 0.0 Fixed Piessure Loss Device
D 202.0 47.1 26.0 2B 6.0 psi, 26.0 gpm
C 202.0 41.1 26.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 1.3
C 202.0 41.1 21.0 2C L1.000 T: 7.0 7.00 0.0
2B 202.0 39.8 26.0 . 1.025 8.00 0.157 1.3
Pipe: 6 0.0 0.0 2.00 150 0.2
2B 202.0 39.8 21.0 3A L1.000 ---- 0.00 0.0
2C 202.0 39.6 21.0 1.025 2.00 0.105 0.2
Pipe: 7 0.0 0.0 34.00 150 3.1
2C 202.0 39.6 21.0 3B 1.250 ---- 0.00 -1.7
3A 206.0 36.5 21.0 1.244 34.00 0.041 1.4
Pipe: 8 0.0 0.0 5.00 150 1.1
3A 206.0 36.5 21.0 3 1.250 ---- 0.00 -0.9
3B 208.0 35.4 21.0 1.244 5.00 0.041 0.2
Pipe: 9 0.0 0.0 3.00 150 1.1
3B 208.0 35.4 21.0 4 . F1.000 ---- 0.00 -0.9
3 210.0 34.3 21.0 1.101 3.00 0.074 0.2
Pipe: 10 0.0 0.0 2.00 120 1.9
3 210.0 34.3 21.0 5 A1.000 C: 5.0 .5.00 . -0.9
4 212.0 32.5 21.0.. 1.049 7.00 0.142 1.0
Pipe: 12 0.0 0.0 44.50 150 6.8
4 212.0 32.5 21.0 6 F1.000 2E:14.0 24.00 -1.7
5 216.0 25.6 21.0 1.101 2B:10.0 68.50 0.074 5.1
Pipe: 13 0.0 14.2 9 8.50 150 1.0
5 216.0 25.6 6.8 7 F1.000 B: 5.0 5.00 0.0
6 216.0 24.6 21.0 1.101 13.50 0.074 1.0
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV)-LOT 52(1HD).SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
F±m Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 14 0.0 0.0 38.00 150 0.4
6 216.0 24.6 6.8 8 F1.000 B: 5.0 5.00 . 0.0
7 216.0 24.2 6.8 1.101 43.00 0.009 0.4
Pipe: 15 0.0 0.0 34.00 150 0.5
7 216.0 24.2 6.8 14 F1.000 2E:14.0 19.00 0.0
8 216.0 23.8 6.8 1.101 B: 5.0 53.00 0.009 0.5
Pipe: 16 0.0 0.0 10.00 150 4.5
8 216.0 23.8 6.8 13 F1.000 E: 7.0 7.00 -4.3
14 226.0 19.3 6.8 1.101 17.00 0.009 0.2
Pipe: 17 0.0 0.0 . 11.00 150 5.4
6 216.0 24.6 14.2 10 F1.000 2E:1.0 19.00 -4.3
9 226.0 19.2 14.2 1.101 B: 5.0 30.00 0.036 1.1
Pipe: 18 0.0 15.4 103 5.00 150 0.4
9 226.0 19.2 -1.2 103 F1.000 B: 5.0 5.00 0.0
10 226.0 18.9 14.2 1.101 10.00 0.036 0.4
Pipe: 19 4.90 21.0 Disch 7.00 150 0.5
10 226.0 18.9 -5.6 11 F1.000 B: 5.0 5.00 0.0
103 226.0 18.4 15.4 1.101 12.00 0.042 0.5
Pipe: 20 4.90 21.0 Disch 24.50 150 0.2
11 226.0 18.6 -15.4 10 F1.000 E: 7.0 12.00 0.0
103 226.0 18.4 5.6 1.101 B: 5.0 36.50 0.006 0.2
Pipe: 21 0.0 0.0 7.00 150 0.0
11 226.0 18.6 0.0 F1.000 B: 5.0 5.00 0.0
12 226.0 18.6 0.0 1.101 12.00 0.000 0.0
Pipe: 22 0.0 0.0 6.00 150 0.0
101 226.0 18.6 0.0 F1.000 E: 7.0 7.00 0.0
12 226.0 18.6 0.0 1.101 13.00 0.000 0.0
Pipe: 23 0.0 0.0 4.00 150 0.0
102 226.0 18.6 0.0 FLOOD E: 7.0 7.00 0.0
12 226.0 18.6 0.0 1.101 11.00 0.000 0.0
Pipe: 24 . 0.0 0.0 .12 41.00 150 0.3
13 226.0 18.9 5.6 103 F1.000 B: 5.0 5.00 0.0
11 226.0 18.6 5.6 1.101 46.00 0.006 0.3
Pipe: 25 0.0 1.2 10 . 23.00 150 0.4
14 226.0 19.3 5.6 11 F1.000 E: 7.0 17.00 0.0
13 226.0 18.9 6.8 1.101 2B:10.0 40.00 0.009 0.4
Pipe: 26 0.0 15.4 103 54.00 150 0.0
13 226.0 18.9 -14.2 9 F1.000 2B:10.0 10.00 0.0
10 226.0 18.9 1.2 1.101 64.00 0.000 0.0
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV)-LOT 52(1HD).SDF
JOB TITLE: THE BLUFFS
NOTES (HASS)
(1) Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.006 gpm and a maximum
imbalance at any node of 0.135 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPV1v NPTee
1.244 1.81 3.62 1.21 4.22 3.62 0.60 6.03 6.03 3.62
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngE11 ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) L E B R K C G
45 El Tee RunT Kpig ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 2.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Eli Tee 45-Eli TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 2 (LOT 52) (2HD)
2567 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: APRIL 21, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSJTY: .05 gpm/sq. ft.
AREA OF APPLICATION: 394 sq. ft.
COVERAGE PER SPRINKLER: 18'X18-324 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 34.1 gpm
TOTAL WATER REQUIRED (including hose): 39.1 gpm
FLOW AND PRESSURE (@ BOR) : 34.1 gpm @ 43.4 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV2)LOT 52(2HD).SDF
JOB TITLE: THE BLUFFS
0 0 0 c
0 0
0 0 0 0 0 0 I
0
0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV2)-LOT 52(2HD).SDF
JOB TITLE: THE BLUFFS
NFPA MATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. S PRESS. S DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.5 39.1 85.2
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 391 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 34.1 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
• (FT) (PSI) (GPM)
1 202.0 SOURCE 85.2 39.1
2 202.0 - - - - 65.2 - - -
2A 202.0 - - - - 62.2 - - -
D 202.0 - - - - 61.5 - - -
C 202.0 - - - - 54.5 - - -
2B 202.0 HOSE STREAM 51.9 5.0
2C 202.0 - - - - 51.3 - - -
3A 206.0 - - - - 46.2 - - -
3B 208.0 - - - - 44.8 - - -
3 210.0 - - - - 43.4 - - -
4 212.0 - - - - 41.8 - - -
5 216.0 - - - - 27.6 - - -
6 216.0 - - - - 25.2 - - -
7 216.0 - - - - 24.1 - - -
8 216.0 - - - - 22.8 - - -
9 226.0 - - - - 18.3 - - -
10 226.0 - - - 17.4 - - -
11 226.0 - - - - 14.9 - - -
12 226.0 - - - - 12.7 - - -
13 226.0 - - - - 17.1 - - -
14 226.0 - - - - 18.1 - - -
101 226.0 K= 4.90 12.0 17.0
102 226.0 K= 4.90 • 12.1 17.1
103 226.0 - - - - 16.8 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV2)-LOT 52(2HD).SDF
JOB TITLE: THE BLUFFS
Ila JS)1W
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 S 45.00 150 20.0
1 202.0 85.2 39.1 2A K1.000 T: 6.0 7.00 0.0
2 202.0 65.2 39.1 0.995 G: 1.0 52.00 0.385 20.0
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 65.2 39.1 D 3.0 psi, 39.0 gpm
2A 202.0 62.2 39.0
Pipe: 3 0.0 0.0 2.00 150 0.7
2A 202.0 62.2 39.1 C L1.000 ---- 0.00 0.0
D 202.0 61.5 39.1 1.025 2.00 0.333 0.7
Pipe: 4 0.0 Fixed Pressure Loss Device
D 202.0 61.5 39.1 2B 7.0 psi, 39.0 gpm
C 202.0 54.5 39.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 2.7
C 202.0 54.5 34.1 2C L1.000 T: 7.0 7.00 0.0
2B 202.0 51.9 39.1 1.025 8.00 0.333 2.7
Pipe: 6 0.0 0.0 2.00 150 0.5
2B 202.0 51.9 34.1 3A L1.000 ---- 0.00 0.0
2C .202.0 51.3 34.1 1.025 2.00 0.258 0.5
Pipe: 7 0.0 0.0 34.00 150 5.2
2C 202.0 51.3 34.1 3B 1.250 ---- 0.00 -1.7
3A 206.0 46.2 34.1 1.244 34.00 0.101 3.4
Pipe: 8 0.0 0.0 5.00 150 1.4
3A 206.0 46.2 34.1 3 1.250 ---- 0.00 -0.9
3B 208.0 44.8 34.1 1.244 5.00 0.101 0.5
Pipe: 9 0.0 0.0 3.00 150 1.4
3B 208.0 44.8 34.1 4 F1.000 ---- 0.00 -0.9
3 210.0 43.4 34.1 1.101 3.00 0.182 0.5
Pipe: 10 0.0 0.0 2.00 120 1.6
3 210.0 43.4 34.1 5 A1.000 ---- 0.00 -0.9
4 212.0 41.8 34.1 1.049 2.00 0.348 0.7
Pipe: 12 0.0 0.0 44.50 150 14.2
4 212.0 41.8 34.1 6 F1.000 2E:14.0 24.00 -1.7
5 216.0 27.6 34.1 1.101 2B:10.0 68.50 0.182 12.5
Pipe: 13 0.0 22.6 9 8.50 150 2.5
5 216.0 27.6 11.5 7 F1.000 B: 5.0 5.00 0.0
6 216.0 25.2 34.1 1.101 13.50 0.182 2.5
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV2)-LOT 52(2HD).SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 14 0.0 0.0 38.00 150 1.1
6 216.0 25.2 11.5 8 F1.000 B: 5.0 5.00 0.0
7 216.0 24.1 11.5 1.101 43.00 0.024 1.1
Pipe: 15 0.0 0.0 34.00 150 1.3
7 216.0 24.1 11.5 14 F1.000 2E:14.0 19.00 0.0
8 216.0 22.8 11.5 1.101 B: 5.0 5'3.00 0.024 1.3
Pipe: 16 0.0 0.0 10.00 150 4.7
8 216.0 22.8 11.5 13 F1.000 E: 7.0 7.00 -4.3
14 226.0 18.1 11.5 1.101 17.00 0.024 0.4
Pipe: 17 0.0 0.0 11.00 150 6.9
6 216.0 25.2 22.6 10 F1.000 2E:14.0 19.00 -4.3
9 226.0 18.3 22.6 1.101 B: 5.0 30.00 0.085 2.5
Pipe: 18 0.0 5.1 13 5.00 150 0.8
9 226.0 18.3 17.5 103 F1.000 B: 5.0 5.00 0.0
10 226.0 17.4 22.6 1.101 10.00 0.085 0.8
Pipe: 19 0.0 0.0 7.00 150 0.6
10 226.0 17.4 17.5 11 F1.000 B: 5.0 5.00 0.0
103 226.0 16.8 17.5 1.101 12.00 0.053 0.6
Pipe: 20 0.0 34.1 12 24.50 150 1.9
103 226.0 16.8 -16.6 13 F1.000 E: 7.0 12.00 0.0
11 226.0 14.9 17.5 1.101 B: 5.0 36.50 0.053 1.9
Pipe: 21 0.0 17.1 102 7.00 150 2.2
11 226.0 14.9 17.0 101 F1.000 B: 5.0 5.00 0.0
12 226.0 12.7 34.1 1.101 12.00 0.182 2.2
Pipe: 22 4.90 17.0 Disch 6.00 150 0.7
12 226.0 12.7 0.0 F1.000 E: 7.0 7.00 0.0
101 226.0 12.0 17.0 1.101 13.00 0.050 0.7
Pipe: 23 4.90 17.1 Disch 4.00 150 0.6
12 226.0 12.7 0.0 F1.000 5: 7.0 7.00 0.0
102 226.0 12.1 17.1 1.101 11.00 0.051 0.6
Pipe: 24 0.0 34.1 12 41.00 150 2.2
13 226.0 17.1 -17.5 103 F1.000 B: 5.0 5.00 0.0
11 226.0 14.9 16.6 1.101 46.00 0.048 2.2
Pipe: 25 0.0 16.6 11 23.00 150 1.0
14 226.0 18.1 -5.1 10 F1.000 E: 7.0 17.00 0.0
13 226.0 17.1 11.5 1:101 2B:10.0 40.00 0.024 1.0
Pipe: 26 0.0 16.6 11 54.00 150 0.3
10 226.0 17.4 -11.5 14 F1.000 2B:10.0 10.00 0.0
13 226.0 17.1 5.1 1.101 64.00 0.005 0.3
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 2 (REV2)-LOT.52(2HD).SDF
JOB TITLE: THE BLUFFS
NOTES (HASS)
(1) Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
(2.) The system has been calculated to provide an average
imbalance at each node of 0.007 gpm and a maximum
imbalance at any node of 0.162 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.1 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: * MATERIAL: S40 HNC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.244 1.81 3.62 1.21 4.22 3.62 0.60 6.03 6.03 3.62
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet (
(in) E .T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) L E B R K C G
45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 2.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Eli Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
t
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 3 (LOT 32) (1HD)
2570 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION:
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
TOTAL, SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose)
FLOW AND PRESSURE (@ BOR)
SPRINKLER ORIFICE SIZE:
NAME OF CONTRACTOR:
DESIGN/LAYOUT BY:
AUTHORITY HAVING JURISDICTION:
CONTRACTOR CERTIFICATION NUMBER:
RESIDENTIAL/LIGHT
.05 gpm/sq. ft.
250 sq. ft.
20X20'-400 sq. ft.
1 sprinkler
2,1.0 gpm
26.0 gpm
21.0 gpm @ 32.8 psi
1/21, inch
INNOVATIVE FIRE PROTECTION, INC.
JOE PLASSMEYER
CARLSBAD FIRE DEPARTMENT
C-16 711148
CALCULATIONS BY HAS'S COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT 32(1HD) .SDF
JOB TITLE: THE BLUFFS
EW
- -
0 0 0 0
0 0
0 0 0 0 0 CD (N 0
—QCI) -H - ---
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT 32(1HD).SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REO'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.6 26.0 56.4
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 202.0 SOURCE 56.4 26.0
2 202.0 - - - - 46.9 - - -
2A 202.0 - - - - 45.9 - - -
D 202.0 - - - - 45.6 - - -
C 202.0 - - - - 39.6 - - -
2B 202.0 HOSE STREAM 38.4 5.0
2C 202.0 - - - - 38.2 - - -
3A 206.0 - - - - 34.9 - - -
33 208.0 - - - - 33.9 - - -
3 210.0 - - - - 32.8 - - -
4 212.0 - - - - 30.9 - - -
5 216.0 - - - - 25.6 - - -
5A 216.0 - - - - 25.2 - - -
6 216.0 - - - - 25.2 - - -
7 216.0 - - - - 24.6 - - -
8 226.0 - - - - 20.0 - - -
9 226.0 - - - - 20.0 - - -
9A 226.0 - - - - 20.0 - - -
10 226.0 - - - - 19.3 - - -
11 226.0 - - - - 20.0 - - -
101 226.0 - - - - 20.0 - - -
102 226.0 - - - - 20.0 - - -
103 226.0 K= 4.90 18.4 21.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT 32(1HD) .SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fàc Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 9.4
1 202.0 56.4 26.0 2A K1.000 T: 6.0 7.00 0.0
2 202.0 46.9 26.0 0.995 G: 1.0' 52.00 0.181 9.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 46.9 26.0 D 1.0 psi, 26.0 gpm
2A 202.0 45.9 26.0
Pipe: 3 0.0 0.0 2.00 150 0.3
2A 202.0 45.9 ' 26.0 C L1.000. ---- 0.00 0.0
D 202.0 45.6 26.0 1.025 2.00 0.157 0.3
Pipe: 4 0.0 Fixed Pressure Loss Device
D 202.0 45.6 26.0 2B 6.0 psi, 26.0 gprn
C 202.0 39.6 26.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 1.3
C 202.0 39.6 21.0 2C L1.000 T: 7.0 7.00 0.0
2B 202.0 38.4 26.0 1.025 8.00 0.157 1.3
Pipe: 6 0:0 0.0 2.00 150 0.2
2B 202.0 38.4 21.0 3A L1.000 ---- 0.00 0.0
2C 202.0 38.2 21.0 1.025 2.00 '0.105 0.2
Pipe: 7 0.0 0.0 36.00 150 3.2
2C 202.0 38.2 21.0 3B 1.250 ---- 0.00 -1.7
3A 206.0 34.9 21.0 1.244 36.00 0.041 1.5
Pipe: 8 0.0 0.0 5.00 150 1.1
3A 206.0 34.9 21.0 3 1.250 ---- 0.00 -0.9
3B 208.0 33.9 21.0 1.244 5.00 0.041 0.2
Pipe: 9 0.0 0.0 3.00 150 1.1
3B 208.0 33.9 21.0 4 F1.000 ---- 0.00 -0.9
3 210.0 32.8 21.0 1.101 3.00 0.074 0.2
Pipe: 10 0.0 0.0 2.00 120 1.9
3 210.0 32.8 21.0 5 A1.000 C: 5.0 5.00 -0.9
4 212.0 30.9 21.0 1.049 7.00 0.142 1.0
Pipe: 12 0.0 13.7 5A 21.50 150 5.3
4 212.0 30.9 7.3 6 F1.000 3E:21.0 26.00 -1.7
5 216.0 25.6 21.0 1.101 B: 5.0 47.50 0.074 3.5
Pipe: 13 0.0 6.8 7 36.00 150 0.5
5 216.0 25.6 0.5 5A F1.000 2B:10.0 10.00 0.0
6 216.0 25.2 7.3 1.101 46.00 0.011 0.5
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT 32(1HD).SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 14 0.0 14.2 8 9.50 150 0.5
5 216.0 25.6 -0.5 6 F1.000 B: 5.0 5.00 0.0
5A 216.0 25.2 13.7 1.101 14.50 0.034 0.5
Pipe: 15 0.0 14.2 8 67.50 150 0.0
6 216.0 25.2 -13.7 5 F1.000 E: 7.0 17.00 0.0
5A 216.0 25.2 0.5 1.101 2B:10.0 84.50 0.000 0.0
Pipe: 16 0.0 0.0 43.50 150 0.6
6 216.0 25.2 6.8 9 F1.000 E: 7.0 17.00 0.0
7 216.0 24.6 6.8 1.101 2B:10.0 60.50 0.009 0.6
Pipe: 17 0.0 6.9 10 19.00 150 4.6
7 216.0 24.6 -0.1 9A F1.000 E: 7.0 12.00
9. 226.0 20.0 6.8 1.101 B: 5.0 31.00 0.009 0.3
Pipe: 18 0.0 14.1 10 11.00 150 5.2
5A 216.0 25.2 0.1 9A F1.000 E: 7.0 12.00 -4.3
8 226.0 20.0 14.2 1.101 B: 5.0 23.00 0.036 0.8
Pipe: 19 0.0 0.0 92.00 150 0.0
8 226.0 20.0 0.1 9 F1.000 E: 7.0 22.00 0.0
9A 226.0 20.0 0.1 1.101 3B:15.0 114.00 0.000 0.0
Pipe: 20 0.0 6.9 10 0.50 150 0.0
9A 226.0 20.0 -6.8 7 F1.000 B: 5.0 5.00 0.0
9 226.0 20.0 0.1 1.101 5.50 0.000 0.0
Pipe: 21 0.0 0.1 9 5.00 150 0.0
11 226.0 20.0 -0.1 8 F1.000 B: 5.0 5.00 : 0.0
9A 226.0 20.0 0.0 1.101 10.00 0.000 0.0
Pipe: 22 0.0 0:0 4.00 150 0.0
102 226.0 20.0 0.0 F1.000 E: 7.0 7.00 0.0
11 226.0 20.0 0.0 1.101 11.00 0.000 0.0
Pipe: 23 0.0 0.0 4.00 150 0.0
101 226.0 20.0 0.0 F1.000 E: 7.0 7.00 0.0
11 226.0 20.0 0.0 1.101 11.00 0.000 0.0
Pipe: 24 0.0 21.0 103 : 14.50 150 0.7
8 226.0 20.0 -6.9 103 F1.000 B: 5.0 5.00 0.0
10 226.0 19.3 14.1 1.101 19.50 0.036 0.7
Pipe: 25 4.90 21.0 Disch 5.50 150 0:9
10 226.0 19.3 0.0 F1.000 E: 7.0 7.00 0.0
103 226.0 18.4 21.0 1.101 12.50 0.074 0.9
Pipe: 26 0.0 21.0 103 65.50 150 0.7
9 226.0 20.0 -14.1 8 F1.000 E: 7.0 7.00 0.0
10 226.0 19.3 6.9 1.101 72.50 0.010 0.7
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT32(1HD).SDF
JOB TITLE: THE BLUFFS
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.079 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEil ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.244 1.81 3.62 1.21 4.22 3.62 0.60 6.03 6.03 3.62
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatViv AlmChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 , 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) L K B R K C G
45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 2.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E' T F R K C G N
Eli Tee 45-Eli TeeRun Kouplg ChkVlv GatViv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
INNOVATIVE FIRE PROTECTION! INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
V
FOR
THE BLUFFS PLAN 3 (LOT 32) (2HD)
2570 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION:
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose)
FLOW AND PRESSURE (@ BOR) :
V
SPRINKLER ORIFICE SIZE:
NAME OF CONTRACTOR:
DESIGN/LAYOUT BY:
AUTHORITY HAVING JURISDICTION:
CONTRACTOR CERTIFICATION NUMBER:
RESIDENTIAL/LIGHT
.05 gpm/sq. ft.
244 sq. ft.
18X18-324 sq. ft.
2 sprinklers
V
34.0 gpm
39.0 gpm
34.0 gpm @ 37.3 psi
1/2" inch
V
INNOVATIVE FIRE PROTECTION, INC.
JOE PLASSMEYER
CARLSBAD FIRE DEPARTMENT
C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
V HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)LOT 32(2HD).SDF
JOB TITLE: THE BLUFFS
Q Q Q Q
0 • • • • 0
0 0 0 0 0 •
(N 0 I
04 U)-r1--
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT 32(2HD) .SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 9 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.5 39.0 79.2
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 39.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 34.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 202.0 SOURCE 79.2 39.0
2 202.0 - - - - 59.3 - - -
2A 202.0 -. -, - - 56.3 - - -.
D 202.0 - - - - 55.6 - - -
C 202.0 - - - - 48.6 - - -
2B 202.0 HOSE STREAM 46.0 5.0
2C 202.0 - - - - 45.5 - - -
3A 206.0 - - - - 40.1 - - -
38 208.0 - - - - 38.8 - - -
3 210.0 - -. - - 37.3 - - -
4 212.0 - - - - 34.0 - - -
5 216.0 - - - - 23.7 - - -
5A 216.0 - - - 22.5 - - -
6 216.0 - - - 22.5 - - -
7 216.0 - - - - 20.3 - - -
8 226.0 - - - - 16.6 - - -
9 226.0 - - - - 14.9 - - -
9A 226.0 - - - - 14.4 - - -
10 226.0 - - - - 16.3 - - -
11 226.0 - - - - 12.6 - - -
101 226.0 K= 4.90 12.0 17.0
102 226.0 K= 4.90 12.0 17.0
103 226.0 - - - - 16.3 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)LOT 32(2HD).SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 19.9
1 202.0 79.2 39.0 2A K1.000 T: 6.0 7.00 0.0
2 202.0 59.3 39.0 0.995 G: 1.0 52.00 0.383 19.9
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 59.3 39.0 D 3.0 psi, 39.0 gpm
2A 202.0 56.3 39.0
Pipe: 3 0.0 0.0 2.00 150 0.7
2A 202.0 56.3 39.0 C L1.000 ---- 0.00 0.0
D 202.0 55.6 39.0 1.025 2.00 0.332 0.7
Pipe: 4 0.0 Fixed Pressure Loss Device
D 292.0 55.6 39.0 2B 7.0 psi, 39.0 gpm
C 202.0 48.6 39.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 2.7
C 202.0 48.6 34.0 2C L1.000 T: 7.0 7.00 0.0
2B 202.0 46.0 39.0 1.025 8.00 0.332 2.7
Pipe: 6 0.0 0.0 2.00 150 0.5
2B 202.0 46.0 34.0 3A L1.000 -.--- 0.00 0.0
2C 202.0 45.5 34.0 1.025 2.00 0.257 .0.5
Pipe: 7 0.0 0.0 36.00 150 5.3
2C 202.0 45.5 34.0 38 1.250 ---- 0.00 -1.7
3A 206.0 40.1 34.0 1.244 36.00 0.100 3.6
Pipe: 8 0.0 0.0 5.00 150 1.4
3A 206.0 40.1 34.0 3 1.250 ---- 0.00 -0.9
33 208.0 38.8 34.0 1.244 5.00 0.100 0.5
Pipe: 9 0.0 0.0 3.00 150 1.4
3B 208.0 38.8 34.0 4 F1.000 ---- 0.00 -0.9
3 210.0 37.3 34.0 1.101 3.00 0.182 0.5
Pipe: 10 0.0 0.0 2.00 120 3.3
3 210.0 37.3 34.0 5 A1.000 C: 5.0 5.00 -0.9
4 212.0 34.0 34.0 1.049 7.00 0.347 2.4
Pipe: 12 0.0 21.9 5A 21.50 150 10.4
4 212.0 34.0 12.1 6 F1.000 3E:21.0 26.00 -1.7
5 216.0 23.7 34.0 1.101 B: 5.0 47.50 0.182 8.6
Pipe: 13 0.0 14.0 7 36.00 150 1.2
5 216.0 23.7 -1.8 5A F1.000 2B:10.0 10.00 0.0
6 216.0 22.5 12.1 1.101 46.00 0.027 1.2
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/20165 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)-LOT 32(2HD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 14 0.0 20.0 8 9.50 150 1.2
5 216.0 23.7 1.8 6 F1.000 B: 5.0 5.00 0.0
5A 216.0 22.5 21.9 1.101 14.50 0.080., 1.2
Pipe: 15 0.0 14.0 7 67.50 150 0.1
5A 216.0 22.5 -12.1 5 F1.000 E: 7.0 17.00 0.0
6 216.0 22.5 1.8 1.101 2B:10.0 84.50 0.001 0.1,
Pipe: 16 0.0 0.0 43.50 150 2.1
6 216.0 22.5 14.0 9 F1.000 E: 7.0 17.00 0.0
7 216.0 20.3 14.0 1.101 2B:10.0 60.50 0.035 2.1
Pipe: 17 0.0 23.8 9A 19.00 150 5.4
7 216.0 20.3 -9.9 10 F1.000 E: 7.0 12.00 -4.3
9 226.0 14.9 14.0 1.101 B: 5.0 31.00 0.035 1.1
Pipe: 18 0.0 9.9 10 . 11.00 150 5.9
5A 216.0 22.5 10.2 9A F1.000 E: 7.0 12.00 -4.3
8 226.0 16.6 20.0 1.101 B: 5.0 23.00 0.068 1.6
Pipe: 19 0.0 34.0 11 92.00 150 2.2
8 226.0 16.6 -23.8 9 F1.000 E: 7.0 22.00 0.0
9A 226.0 14.4 10.2 1.101 3B:15.0 114.00 0.019 2.2
Pipe: 20 0.0 34.0 11 . 0.50 150 0.5
9 226.0 14.9 -10.2 8 F1.000 B: 5.0 5.00 0.0
9A 226.0 14.4 23.8 1.101 5.50 0.094 0.5
Pipe: 21 0.0 17.0 101 5.00 150 1.8
9A 226.0 14.4 17.0 102 F1.000 B: 5.0 5.00 0.0
11 226.0 12.6 34.0 1.101 10.00 0.182 1.8
Pipe: 22 4.90 17.0 Disch 4.00 150 0.6
11 226.0 12.6 0.0 F1.000 E: 7.0 7.00 0.0
102 226.0 12.0 17.0 1.101 11.00 0.050 0.6
Pipe: 23 4.90 17.0 Disch 4.00 150 0.6
11 226.0 12.6 0.0 F1.000 E: 7.0 7.00 0.0
101 226.0 12.0 17.0 1.101 11.00 0.050 0.6
Pipe: 24 0.0 0.0 . 14.50 150 0.4
8 226.0 16.6 9.9 9 F1.000 B: 5.0 5.00 0.0
10 226.0 16.3 9.9 1.101 . 19.50 0.018 0.4
Pipe: 25 0.0 0.0 . 5.50 150 0.0
103 226.0 16.3 0.0 F1.000 E: 7.0 7.00 0.0
10 226.0 16.3 0.0 1.101 12.50 0.000 0.0
Pipe: 26 0.0 23.8 9A 65.50 150 1.3
10 226.0 16.3 -14.0 .7 F1.000 E: 7.0 7.00 0.0
9 226.0 14.9 9.9 1.101 72.50 0.018 1.3
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 5/17/2016S SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV)LOT 32(2HD).SDF
JOB TITLE: THE BLUFFS
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
(-IRS Systems, Inc.
208 Southside Square
Petersburg, TN: 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.012 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.1 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B .G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.244 1.81 3.62 1.21 4.22 3.62 0.60 6.03 6.03 3.62
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) L E B R K C G
45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 2.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T ,F R K C G N
Ell Tee 45-Eli TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 3 (LOT 43) (1Hb)
526 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION:
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose)
FLOW AND PRESSURE (@ BOR)
SPRINKLER ORIFICE SIZE:
NAME OF CONTRACTOR:
DESIGN/LAYOUT BY:
AUTHORITY HAVING JURISDICTION:
CONTRACTOR CERTIFICATION NUMBER:
RESIDENTIAL/LIGHT
.05 gpm/sq. ft.
250 sq. ft.
20'X20'-400 sq. ft.
1 sprinkler
21.0 gpm
26.0 gpm
21.0 gpm @ 32.8 psi
1/2' inch
INNOVATIVE FIRE PROTECTION, INC
JOE PLASSMEYER
CARLSBAD FIRE DEPARTMENT
C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(1HD) .SDF
JOB TITLE: THE BLUFFS
f 0 • 0 0 0 0 IN 0
co 0 10 (N 0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)LOT 43(1HD) .SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 119.5 105.0 500.0 119.4 26.0 61.9
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 170.0 SOURCE 61.9 26.0
2 170.0 - - - - 52.5 - - -
2A 170.0 - - - - 51.5 - - -
D 170.0 - - - - 51.2 .- - -
C 170.0 - - - - 45.2 - - -
2B 170.0 HOSE STREAM 43.9 5.0
2C 170.0 - - - - 43.7 - - -
3A 176.0 - - - - 34.9 - - -
3B 178.0 - - - - 33.9 - - -
3 180.0 - - - - 32.8 - - -
4 182.0 - - - - 30.9 - - -
5 186.0 - - - - 25.6 - - -
5A 186.0 - - - - 25.2 - - -
6 186.0 - - - - 25.2 - - -
7 186.0 - - - - 24.6 - - -
8 196.0 - - - - 20.0 - - -
9 196.0 - - - - 20.0 - - -
9A 196.0 - - - - 20.0 - - -
10 196.0 - - - - 19.3 - - -
11 196.0 - - - - 20.0 - - -
101 196.0 - - - - 20.0 - - -
102 196.0 - - - - 20.0 - - -
103 196.0 K= 4.90 18.4 21.0
NOTES
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTENS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(1HD) .SDF
JOB TITLE: THE BLUFFS -
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frrn Node El (ft) PT (q) Node! Worn ID Eq.Ln. F (Pe) NotE
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 9.4
1 170.0 61.9 26.0 2A K1.000 T: 6.0 7.00 0.0
2 170.0 52.5 26.0 0.995 G: 1.0 52.00 0.181 9.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 170.0 52.5 26.0 D 1.0 psi, 26.0 gprn
2A 170.0 51.5 26.0
Pipe: 3 0.0 0.0 2.00 150 0.3
2A 170.0 51.5 26.0 C L1.000 ---- 0.00 0.0
D 170.0 51.2 26.0 1.025 2.00 0.157 0.3
Pipe: 4 0.0 Fixed Pressure Loss Device
D 170.0 51.2 26.0 23 6.0 psi, .26.0 gprn
C 170.0 45.2 26.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 1.3
C 170.0 45.2 21.0 2C L1.000 T: 7.0 7.00 0.0
23 170.0 43.9 26.0 1.025 8.00 0.157 1.3
Pipe: 6 0.0 .0.0 2.00 150 0.2
2B 170.0 43.9 21.0 3A L1.000 ---- 0.00 0.0
2C 170.0 43.7 21.0 . 1.025 2.00 0.105 0.2
Pipe: 7 0.0 0.0 . 150.00 150 8.8
2C 170.0 43.7 21.0 3B 1.250 ---- 0.00 -2.6
3A 176.0 34.9 21.0 1.244 150.00 0.041 6.2
Pipe: 8 0.0 0.0 5.00 150 1.1
3A 176.0 34.9 21.0 3 1.250 ---- 0.00 -0.9
33 178.0 33.9 21.0 1.244 5.00 0.041 0.2
Pipe: 9 . 0.0 0.0 3.00 150 1.1
33 178.0 33.9 21.0 4 F1.000 ---- 0.00 -0.9
3 180.0 32.8 21.0 1.101 3.00 0.074 0.2
Pipe: 10 0.0 0.0 2.00 120 1.9
3 180.0 32.8 21.0 5 A1.000 C: 5.0 5.00 -0.9
4 182.0
- . 30.9 21.0 1.049 7.00 0.142 1.0
Pipe: 12 0.0 13.7 5A 21.50 150 5.3
4 182.0 30.9 7.3 6 F1.000 3E:21.0 26.00 -1:7
5 186.0 25.6 21.0 1.101 B: 5.0 47.50 0.074 3.5
Pipe: 13 0.0 6.8 7 36.00 150 0.5
5 186.0 25.6 0.5 5A F1.000 23:10.0 10.00 0.0
6 186.0 25.2 7.3 1.101 46.00 0.011 0.5
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(1HD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frrn Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 14 0.0 14.2 8 9.50 150 0.5
5 186.0 25.6 -0.5 6 F1.000 B: 5.0 5.00 0.0
5A 186.0 25.2 13.7 1.101 14.50 0.034 0.5
Pipe: 15 0.0 14.2 8 67.50 150 0.0
6 186.0 25.2 -13.7 5 F1.000 E:• 7.0 17.00 0.0
5A 186.0 25.2 0.5 1.101 2B:10.0 84.50 0.000 0.0
Pipe: 16 0.0 0.0 43.50 150 0.6
6 186.0 25.2 6.8 9 F1.000 E: 7.0 17.00 0.0.
7 186.0 24.6 6.8 1.101 2B:10.0 60.50 0.009 0.6
Pipe: 17 0.0 6.9 10 19.00 150 4.6
7 186.0 24.6 -0.1 9A F1.000 E: 7.0 12.00 -4.3
9 196.0 20.0 6.8 1.101 B: 5.0 31.00 0.009 0.3
Pipe: 18 0.0 14.1 10 11.00 150 5.2
5A 186.0. 25.2 0.1 9A F1.000 E: 7.0 12.00 -4.3
8 196.0 20.0 14.2 - 1.101 B: 5.0 23.00 0.036 0.8
Pipe: 19 0.0 0.0 92.00 150 . 0.0
8 196.0 20.0 0.1 9 F1.000 E: 7.0 22.00 0.0
9A 196.0 20.0 0.1 1.101 3B:15.0 114.00 0.000 0.0
Pipe: 20 . 0.0 6.9 10 . 0.50 150 0.0
9A 196.0 20.0 -6.8 7 F1.000 B: 5.0 5.00 0.0
9 196.0 20.0 0.1 1.101 5.50 0.000 0.0
Pipe: 21 0.0 0.1 9 5.00 150 0.0
11 196.0 20.0 -0.1 8 F1.000 B: 5.0 5.00 0.0
9A t96.0 20.0 0.0 1.101 10.00 0.000 . 0.0
Pipe: 22 0.0 0.0 4.00 150 0.0
102 196.0 20.0 0.0 F1.000 E: 7.0 7.00 0.0
11 196.0 20.0 0.0 1.101 11.00 0.000 0.0
Pipe: 23 0.0 0.0 4.00 150 0.0
101 196.0 20.0 0.0 F1.000 E: 7.0 7.00 0.0
11 196.0 20.0 0.0 1.101 11.00 0.000 0.0
Pipe: 24 0.0 . .21.0 103 14.50 150 0.7
8 196.0 20.0 -6.9 103 F1.000 B: 5.0 5.00 0.0
10 196.0 19.3 14.1 1.101 19.50 0.036 0.7
Pipe: 25 4.90 21.0 Disch 5.50 150 0.9
10 196.0 19.3 0.0 F1.000 E: 7.0 7.00 0.0
103 196.0 18.4 21.0 1.101 12.50 0.074 0.9
Pipe: 26 0.0 21.0 103 65.50 150 0.7
9 196.0 20.0 -14.1 8 F1.000 E: 7.0 7.00 0.0
10 196.0 19.3 6.9 1.101 72.50 0.010 0.7
NotE
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(1HD).SDF
JOB TITLE: THE BLUFFS
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
Under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.076 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation, report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: * MATERIAL: S40 HNC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D ,N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.244 1.81 3.62 1.21 4.22 3.62 0.60 6.03 6.03 3.62
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HNC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) L E B R K C G
45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 2.00
PAGE: K MATERIAL: CT-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Ell Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 3 (LOT 43) (2HD)
2526 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSJTY: .05 gpm/sq. ft.
AREA OF APPLICATION: 244 sq. ft.
COVERAGE PER SPRINKLER: 18X18'-324 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 34.0 gpm
TOTAL WATER REQUIRED (including hose): 39.0 gpm
FLOW AND PRESSURE (@ BOR) : 34.0 gpm @ 37.3 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
E
0
0
0
LC)
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(2HD).SDF
JOB TITLE: THE BLUFFS
0 N
0 0 0
0 (N 0 H 00 H
H H (N 0 I
W&)J01x1 -0U)H---
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(2HD).SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 119.5 105.0 500.0 119.4 39.0 91.5
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 39.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 34.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 170.0 SOURCE 91.5 39.0
2 170.0 - - - - 71.6 - - -
2A 170.0 - - - - 68.6 - - -
D 170.0 - - - - 67.9 - - -
C 170.0 - - - - 60.9 - - -
2B 170.0 HOSE STREAM 58.3 5.0
2C 170.0 - - - - 57.8 - - -
3A 176.0 - - - - 40.1 - - -
33 178.0 - - - - 38.8 - - -
3 180.0 - - - - 37.3 - - -
4 182.0 - - - - 34.1 - - -
5 186.0 - - - - 23.7 - - -
5A 186.0 - - - - 22.5 - - -
6 186.0 - - - - 22.5 - -,-
7 186.0 - - - - 20.3 - - -
8 196.0 - - - - 16.6 - - -
9 196.0 - - - - 14.9 - - -
9A 196.0 - - - - 14.4 - - -
10 196.0 - - - - 16.3 - - -
11 196.0 - - - - 12.6 - - -
101 196.0 K= 4.90 12.0 17.0
102 196.0 K= 4.90 12.0 17.0
103 .196.0 - - - - 16.3 - - -
NOTES
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(2HD).SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 'l ' Source 0.0 45.00 150 19.9
1 170.0 91.5 39.0 2A K1.000 T: 6.0 7.00 0.0
2 170.0 71.6 39.0 0.995 G: 1.0 52.00 0.383 19.9
Pipe: 2 0.0 Fixed Pressure Loss Device
2 170.0 71.6 39.0 D 3.0 psi, 39.0 gpm
2A 170.0 68.6 39.0
Pipe: 3 0.0 0.0 2.00 150 0.7
2A 170.0 68.6 39.0 C 'Ll.00O ---- 0.00 0.0
D 170.0 67.9 39.0 1.025 2.00 0.332 0.7
Pipe: 4 0.0 Fixed Pressure Loss Device
D 170.0 67.9 39.0 2B 7.0 psi, 39.0 gpm
C 170.0 60.9 39.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 2.7
C 170.0 60.9 34.0 2C L1.000 T: 7.0 7.00 0.0
2B 170.0 58.3 39.0 1.025 8.00 0.332 2.7
Pipe: 6 0.0 0.0 2.00 150 0.5
2B 170.0 58.3 34.0 3A L1.000 ---- 0.00 0.0
2C 170.0 57.8 34.0 1.025 2.00 0.257 0.5
Pipe: 7 0.0 0.0 150.00 150 17.6
2C 170.0 57.8 34.0 3B 1.250 ---- 0.00 -2.6
3A 176.0 40.1 34.0 1.244 150.00 0.100 15.0
Pipe: 8 0.0 0.0 5.00 150 1.4
3A 176.0 40.1 34.0 3 1.250 ---- 0.00 -0.9
3B 178.0 38.8 34.0 1.244 5.00 0.100 0.5
Pipe: 9 0.0 0.0 3.00 150 1.4
3B 178.0 38.8 34.0 4 F1.000 ---- 0.00 -0.9
3 180.0 37.3 34.0 1.101 3.00 0.182 0.5
Pipe: 10 0.0 0.0 2.00 120 3.3
3 180.0 37.3 34.0 5 A1.000 C: 5.0 5.00 -0.9
4 182.0 34.1 34.0 1.049 7.00 0.347 2.4
Pipe: 12 0.0 21.9 5A 21.50 150 10.4
4 182.0 34.1 12.1 6 F1.000 3E:21.0 26.00 -1.7
5 186.0 23.7 34.0 1.101 B: 5.0 47.50 0.182 8.6
Pipe: 13 0.0 14.0 7 36.00 150 1.2
5 186.0 23.7 -1.8 5A F1.000 2B:10.0 10.00 0.0
6 186.0 22.5 12.1 1.101 46.00 0.027 1.2
NotE
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN-3 (REV2)-LOT 43(2HD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 14 0.0 20.0 8 9.50 150 1.2
5 186.0 23.7 1.8 6 F1.000 B: 5.0 5.00 0.0
5A 186.0 22.5 21.9 1.101 14.50 0.080 1.2
Pipe: 15 0.0 14.0 7 67.50 150 0.1
5A 186.0 22.5 -12.1 5 F1.000 E: 7.0 17.00 0.0
6 186.0 22.5 1.8 1.101 25:10.0 84.50 0.001 0.1
Pipe: 16 0.0 0.0 43.50 150 2.1
6 186.0 22.5 14.0 9 F1.000 E: 7.0 17.00 0.0
7 186.0 20.3 14.0 1.101 2B:10.0 60.50 0.035 2.1
Pipe: 17 0.0 23.8 9A 19.00 150 5.4
7 186.0 20.3 -9.9 10 F1.000 E: 7.0 12.00 -4.3
9 196.0 14.9 14.0 1.101 B: 5.0 31.00 0.035 1.1
Pipe: 18 0.0 9.9 10 11.00 150 5.9
5A 186.0 22.5 10.2 9A F1.000 E: 7.0 12.00 -4.3
8 196.0 16.6 20.0 1.101 B: 5.0 23.00 0.068 1.6
Pipe: 19 0.0 34.0 11 92.00 150 2.2
8 196.0 16.6 -23.8 9 F1.000 E: 7.0 22.00 0.0
9A 196.0 14.4 10.2 1.101 3B:15.0 114.00 0.019 2.2
Pipe: 20 0.0 34.0 11 0.50 150 0.5
9 196.0 14.9 -10.2 8 F1.000 B: 5.0 5.00 0.0
9A 196.0 14.4 23.8 1.101 5.50 0.094 0.5
Pipe: 21 0.0 17.0 101 5.00 150 1.8
9A 196.0 14.4 17.0 102 F1.000 B: 5.0 5.00 0.0
11 196.0 12.6 34.0 1.101 10.00 0.182 1.8
Pipe: 22 4.90 17.0 Disch 4.00 150 0.6
11 196.0 12.6 0.0 F1.000 E: 7.0 7.00 0.0
102 196.0 12.0 17.0 1.101 11.00 0.050 0.6
Pipe: 23 4.90 17.0 Disch 4.00 150 0.6
11 196.0 12.6 0.0 F1.000 E: 7.0 7.00 0.0
101 196.0 12.0 17.0 1.101 11.00 0.050 0.6
Pipe: 24 0.0 .0.0 14.50 150 0.4
8 196.0 16.6 9.9 9 P1.000 B: 5.0 5.00 0.0
10 196.0 16.3 9.9 1.101 19.50 0.018 0.4
Pipe: 25 0.0 0.0 5.50 150 0.0
103 196.0 16.3 0.0 P1.000 E: 7.0 7.00 0.0
10 196.0 16.3 0.0 1.101 12.50 0.000 0.0
Pipe: 26 0.0 23.8 9A 65.50 150 1.3
10 196.0 16.3 -14.0 7 F1.000 E: 7.0 7.00 0.0
9 196.0 14.9 9.9 1.101 72.50 0.018 1.3
NotE
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 3 (REV2)-LOT 43(2HD).SDF
JOB TITLE: THE BLUFFS
NOTES (HASS)
Calculations were performed by the I-lASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.007 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.1 ft/sec at pipe 1.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD1.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell Tee LngEli ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1.244 1.81 3.62 1.21 4.22 3.62 0.60 6.03 6.03 3.62
PAGE: A MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A P N
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
1:049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 2.00 5.00
PAGE: F MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) L E B R K C G
45 El Tee RunT Kplg ChkVlv Gate
1.101 1.00 7.00 5.00 1.00 1.00 8.00 2.00
PAGE: K MATERIAL: CT-K HWC: 150.
Diameter Equivalent Fitting Lengths in Feet
(in) E T F R K C G N
Eli Tee 45-Ell TeeRun Kouplg ChkVlv GatVlv NPTee
0.995 2.00 6.00 1.00 2.00 0.00 6.00 0.00 6.00
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 4 (LOT 42) (1HD)
2530 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 194 sq. ft.
COVERAGE PER SPRINKLER: 20X20-400 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 1 sprinkler
TOTAL SPRINKLER WATER FLOW.REQUIRED: 21.0 gpm
TOTAL WATER REQUIRED (including hose): 26.0 gpm
FLOW AND PRESSURE (@ BOR) : 21.0 gpm @ 32.0 psi
SPRINKLER ORIFICE SIZE: 1/2' inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: 0 JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
E
(D
0
0
Ln
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS—PLAN 4 (REV2)LOT 42(1HD) .SDF
JOB TITLE: THE BLUFFS
0 0 )14 r- 0 0 0 0 0
00
00 10 c'J C I
/DcnDc) —0uJH--
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016 SYSTEMS\JP CALC5\THE BLUFFS-PLAN 4 (REV2)LOT 42(1HD) .SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 119.5 105.0 500.0 119.4 26.0 59.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 170.0 SOURCE 59.8 26.0
2 170.0 - - - - 50.4 - .- -
2A 170.0 - - - - 49.4. - - -
D 170.0 - - - - 49.1
C 170.0 - - - - 43.1 - - -
2B 170.0 HOSE STREAM 41.9 5.0
2C. 170.0 - - - - 41.7 - - -
3A 176.0 - - - - 34.1 - - -
3B 178.0 - - - - 33.1 - - -
3 180.0 - - - - 32.0 - - -
4 182.0 - - - - 30.1 - - -
5 186.0 - - - - 25.1 - - -
6 186.0 - - - - 23.9 - - -
7 196.0 - - - - . 19.8 - - -
8 196.0 - - - - 19.5 - - -
9 196.0 - - - - 19.4 - - -
10 196.0 - - - - 19.0 - - -
101 196.0 - - - - 19.0 - - -
102 196.0 - - - - 19.0 - - -
103 196.0 K= 4.90 18.4 21.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 42(1HD) .SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe) NotE
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 1 Source 0.0 . 45.00 150 9.4
1 170.0 59.8 26.0 2A K1.000 T: 6.0 7.00 0.0
2 170.0 50.4 26.0 0.995 G: 1.0 52.00 0.181 9.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 170.0 50.4 26.0 D 1.0 psi, 26.0 gprn
2A 170.0 49.4 26.0
Pipe: 3 0.0 0.0 . 2.00 150 0.3
2A 170.0 49.4 26.0 C L1..000 ---- 0.00 0.0
D 170.0 49.1 26.0 1.025 2.00 0.157 0.3
Pipe: 4 0.0 Fixed Pressure Loss Device
D 170.0 49.1 26.0 2B 6.0 psi, 26.0 gpm
C 170.0 43.1 26.0
Pipe: 5 H.S. 5.0 Disch 1.00 150 1.3
C 170.0 43.1 21.0 2C L1.000 T: 7.0 7.00 0.0
2B 170.0 41.9 26.0 1.025 8.00 0.157 1.3
Pipe: 6 0.0 0.0 2.00 150 0.2
2B 170.0 41.9 21.0 3A L1.000 ---- 0.00 0.0
2C 17.0.0 41.7 21.0 1.025 . 2.00 0.105 0.2
Pipe: 7 0.0 0.0 120.00 150 7.5
2C 170.0 41.7 21.0 3B 1.250 ---- 0.00 -2.6
3A 176.0 34.1 21.0 1.244 120.00 0.041 4.9
Pipe: 8 0.0 0.0 5.00 150 1.1
3A 176.0 34.1 21.0 3 1.250 ---- 0.00 -0.9
38 178.0 33.1 21.0 1.244 5.00 0.041 0.2
Pipe: 9 0.0 0.0 3.00 150 1.1
38 178.0 33.1 21.0 4 F1.000 ---- 0.00 -0.9
3 180.0 32.0 21.0 1.101 3.00 0.074 0.2
Pipe: 10 0.0 0.0 2.00 120 1.9
3 180.0 32.0 21.0 5 A1.000 C: 5.0 5.00 -0.9
4 182.0 30.1' 21.0 1.049 7.00 0.142 1.0
Pipe: 12 0.0 14.2 7 27.00 150 5.0
4 182.0 30.1 6.8 6 F1.000 E: 7.0 17.00 -1.7
5 186.0 25.1 21.0 1.101 2B:10.0 44.00 0.074 3.3
Pipe: 13 0.0 0.0 107.00 150 1.2
5 186.0 25.1 6.8 9 F1.000 E: 7.0 22.00 0.0
6 186.0 23.9 6.8 1.101 3B:15.0 129.00 0.009 1.2
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS -PLAN 4 (REV2)-LOT 42(lHD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T. Pf/ft. (Pf)
Pipe: 14 0.0 0.0 . 11.00 150 5.3
5 186.0 25.1 14.2 8 F1.000 E: 7.0 17.00 -4.3
7 196.0 19.8 14.2 1.101 2B:10.0 28.00 0.036 1.0
Pipe: 15 0.0 9.0 10 10.00 150 4.5
6 186.0 23.9 -2:2 8 F1.000 B: 5.0 5.00 -4.3
9 196.0 19.4 6.8 1.101 15.00 0.009 0.1
Pipe: 15A 0.0 2.2 9 2.00 150 0.3
7 196.0 19.8 12.0 103 F1.000 B: 5.0 5.00 0.0
8 196.0 19.5 14.2 1.101 7.00 0.036 0.3
Pipe: 17 4.90 21.0 Disch 31.00 150 1.1
8 196.0 19.5 -9.0 F1.000 E: 7.0 12.00 0.0
103 196.0 18.4 12.0 1.101 B: 5.0 43.00 0.026 1.1
Pipe: 18 0.0 . 9.0 10 . 46.00 150 0.1
8 196.0 19.5 -6.8 6 F1.000 E: 7.0 12.00 0.0.
9 196.0 19.4 2.2 1.101 B: 5.0 58.00 0.001 0.1
Pipe: 19 0.0 0.0 6.00 150 0.0
102 196.0 19.0 0.0 F1.000 E: 7.0 12.00 0.0
10 196.0 19.0 0.0 1.101 B: 5.0 18.00 0.000 0.0
Pipe: 20 .0.0 0.0 8.50 150 0.0
101 196.0 19.0 0.0 F1.000 E: 7.0 7.00 0.0
102 196.0 19.0 0.0 1.101 15.50 0.000 0.0
Pipe: 21 4.90 21.0 Disch 37.00 150 0.7
10 196.0 19.0 -12.0 8 F1.000 B: 5.0 5.00 0.0
103 196.0 184 9.0 1.101 42.00 0.016 0.7
Pipe: 22 0.0 0.0 22.00 150 0.4
9 196.0 19.4 9.0 103 F1.000 B: 5.0 5.00 0.0
10 196.0 19.0 9.0 1.101 27.00 0.016 0.4
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.003 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Not€
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 4 (LOT 42) (2HD)
2530 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 233 sq. ft.
COVERAGE PER SPRINKLER: 18'X18'-324 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 2 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 34.6 gpm
TOTAL WATER REQUIRED (including hose) : 39.6 gpm
FLOW AND PRESSURE (@ BOR) : 34.6 gpm @ 39.7 psi
SPRINKLER ORIFICE SIZE: 1/2' inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: • JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
E
ia
0
0
LO
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 42(2HD).SDF
JOB TITLE: THE BLUFFS
0
0 0 0 0 (N 0
ci, 0 0 (N 0 I
0(5N (14 W -Q4 U)-H--
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 42(2HD).SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 119.5 105.0 500.0 119.4 39.5 91.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 39.5 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 34.5 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES
(FT) (PSI) (GPM)
1 170.0 SOURCE 91.8 39.5
2 170.0 - - - - 71.4 - - -
2A 170.0 - - - -. 68.4 - - -
D 170.0 - - - - 67.7 - - -
C 170.0 - - - - 60.7 - - -
2B 170.0 HOSE STREAM 58.0 5.0
2C 170.0 - - - - 57.5. - - -
3A 176.0 - - - - 42.5 - - -
3B 178.0 - - - - 41.1 - - -
3 180.0 - - - - 39.7 - - -
4 182.0 - - - - 36.3 - - -
5 186.0 - - - - 26.3 - - -
6 186.0 - - - - 22.9 - - -
7 196.0 - - - - 19.6 - - -
8 196.0 - - - - 19.0 - - -
9 196.0 - - - - 18.2 - - -
10 196.0 - - - - 16.2 - - -
101 196.0 K= 4.90 12.0 17.0
102 196.0 K= 4.90 12.8 17.5
103 196.0 - - - - 17.6 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTENS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 42(2HD).SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Note
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 20.4
1 170.0 91.8 39.5 2A K1.000 T: 6.0 7.00 0.0
2 170.0 71.4 39.5 0.995 G: 1.0 52.00 0.393 20.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 170.0 71.4 39.5 D 3.0 psi, 39.5 gpm
2A 170.0 68.4 39.5
Pipe: 3 0.0 0.0 . 2.00 150 0.7
2A 170.0 68.4 39.5 C L1.000 ---- 0.00 0.0
D 170.0 67.7 39.5 1.025 2.00 0.340 0.7
Pipe: 4 0.0 Fixed Pressure Loss Device
D 170.0 67.7. 39.5 2B 7.0 psi, 39.5 gpm
C 170.0 60.7 39.5
Pipe: 5 H.S. 5.0 Disch 1.00 150 2.7
C 170.0 60.7 34.5 2C L1.000 T: 7.0 7.00 0.0
2B 170.0 58.0 39.5 . 1.025 8.00 0.340 2.7
Pipe: 6 0.0 0.0 2.00 150 0.5
2B 170.0 58.0 34.5 3A L1.000 ---- 0.00 0.0
2C . 170.0 57.5 34.5 1.025 . . 2.00 0.265 0.5
Pipe: 7 0.0 0.0 . . .120.00 150 15.0
2C 170.0 57.5 34.5 33 1.250 ---- 0.00 -2.6
3A 176.0 42.5 34.5 1.244 120.00 0.103 12.4
Pipe: 8 0.0 0.0 5.00 150 1.4
3A 176.0 42.5 34.5 3 1.250 ---- 0.00 -0.9
3B 178.0 41.1 34.5 1.244 5.00 0.103 0.5
Pipe: 9 0.0 0.0 3.00 150 1.4
3B 178.0 41.1 34.5 4 F1.000 ---- 0.00 -0.9
3 180.0 39.7 34.5 1.101 3.00 0.187 0.6
Pipe: 10 0.0 0.0 2.00 120 3.4
3 180.0 39.7 34.5 5 A1.000 C: 5.0 5.00 -0.9
4 182.0 36.3 34.5 1.049 7.00 0.358 2.5
Pipe: 12 0.0 22.5 7 27.00 150 10.0
4 182.0 36.3 12.0 6 F1.000 E: 7.0 17.00 -1.7
5 186.0 26.3 34.5 1.101 23:10.0 44.00 0.187 8.2
Pipe: 13 0.0 0.0 107.00 150 3.4
5 186.0 26.3 12.0 9 F1.000 E: 7.0 22.00 0.0
6 186.0 22.9 12.0 1.101 3B:15.0 129.00 0.027 3.4
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 42(2HD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F. (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf).
Pipe: 14 0.0 0.0 , 11.00 150 6.7
5 186.0 26.3 22.5 8 F1.000 E: 7.0 17.00 -4.3
7 196.0 19.6 22.5 1.101 2B:10.0 28.00 0.085 2.4
Pipe: 15 0.0 20.9 10 10.00 150 4.7
6 186.0 22.9 -8.8 8 F1.000 B: 5.0 5.00 4.3
9 196.0 18.2 12.0 1.101 . 15.00 0.027 0.4
Pipe: 15A 0.0 8.8 9 2.00 150 0.6
7 196.0 19.6 13.7 103 F1.000 B: 5.0 5.00 0.0
8 196.0 19.0 22.5 1.101 7.00 0.085 0.6
Pipe: 17 0.0 0.0 31.00 150 1.4
8 196.0 19.0 13.7 10 F1.000 E: 7.0 12.00 0.0
103 196.0 17.6 13.7 1.101 B: 5.0 43.00 0.034 1.4
Pipe: 18 0.0 20.9 10 46.00 150 0.9
8 196.0 19.0 712.0 6 F1.0.00 E:.7.0 12.00 0.0
9 196.0 18.2 8.8 1.101 B: 5.0 58.00 0.015 0.9
Pipe: 19 4.90 17.5 Disch 6.00 150 3.4
10 . 196.0 16.2 17.0 101 F1.000 E: 7.0 12.00 0.0
102 196.0 12.8 34.5 1.101 .B: 5.0 18.00 0.187 3.4
Pipe: 20 4.90 17.0 Disch .8.50 150 0.8
102 196.0 12.8 0.0 F1.000 E: 7.0 7.00. 0.0
101 196.0 12.0 17.0 1.101 15.50 0.050 0.8
Pipe: 21 0.0 34.5 102 37.00 150 1.4
103 196.0 17.6. -20.9 9 . F1.000 B: 5.0 5.00 0.0
10 196.0 16.2 13.7 1.101 42.00 0.034 1.4
Pipe: 22 0.0 34.5 102 22.00 150 2.0
9 196.0 18.2 -13.7 103 F1.000 B: 5.0 5.00 0.0
10 196.0 16.2 20.9 ' 1.101 27.00 0.074 2.0
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.007 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.3 ft/sec at pipe 1.
Not€
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEE,CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 4 (LOT 50) (1HD)
2575 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL/LIGHT
DENSITY: .05 gpm/sq. ft.
AREA OF APPLICATION: 194 sq. ft.
COVERAGE PER SPRINKLER: 20X20-400 sq. ft.
NUMBER OF SPRINKLERS CALCULATED: 1 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 210 gpm
TOTAL WATER REQUIRED (including hose): 26.0 gpm
FLOW AND PRESSURE (@ BOR): 21.0 gpm @ 32.0 psi
SPRINKLER ORIFICE SIZE: 1/2 inch
NAME OF CONTRACTOR: INNOVATIVE FIRE PROTECTION, INC.
DESIGN/LAYOUT BY: JOE PLASSMEYER
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C-16 711148
CALCULATIONS BY MASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC..
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 50(1HD) .SDF
JOB TITLE: THE BLUFFS
E la
0
0
In
0
44
-H
U)
04
(D
In
Cl)
cl)
U)
CD
04
E-4
0
0
III
0 0 0 0 0 • • • • 0
0 0 0 0 0 •
r—i 00 10 (N 0
-QU) -H- ---
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 50(1HD).SDF
JOB TITLE: THE BLUFFS
NFPA MATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.6 26.0 54.7
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 202.0 SOURCE 54.7 26.0
2 202.0 - - - - 45.3 - - -
2A 202.0 - - - - 44.3 - - -
D 202.0 - - - - 44.0 - - -
C 202.0 - - - - 38.0 - - -
2B 202.0 HOSE STREAM 36.7 5.0
2C 202.0 - - - - 36.5 - - -
3A 206.0 - - - - 34.1 - - -
3B 208.0 - - - - 33.1 - - -
3 210.0 - - - - 32.0 - - -
4 212.0 - - - - 30.1 - - -
5 216.0 - - - - 25.1 - - -
6 216.0 - - - - 23.9 - - -
7 226.0 - - - - 19.8 - - -
8 226.0 - - - - 19.5 - - -
9 226.0 - - - - 19.4 - - -
10 226.0 - - - - 19.0 - - -
101 226.0 - - - - 19.0 - - -
102 226.0 - - - - 19.0 - - -
103 226.0 K= 4.90 18.4 21.0
NOTES
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 50(1HD).SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q.) Node! Nom ID Eq.Ln. F (Pe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 9.4
1 202.0 54.7 26.0 2A K1.000 T: 6.0 7.00 0.0
2 202.0 45.3 26.0 0.995 G: 1.0 52.00 0.181 9.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 45.3 26.0 D 1.0 psi, 26.0 gpm
2A 202.0 44.3 26.0
Pipe: 3 0.0 0.0 2.00 150 0.3
2A 202.0 44.3 26.0 C L1.000 ---- 0.00 0.0
D 202.0 44.0 26.0 1.025 2.00 0.157 0.3
Pipe: 4. 0.0 Fixed Pressure Loss Device
D 202.0 44.0 26.0 2B 6.0 psi, 26.0 gpm
C 202.0 38.0 26.0
Pipe: 5 H.S. 5.0 Disch S
1.00 150 1.3
C 202.0 38.0 21.0 2C L1.000 T: 7.0 7.00 0.0
28 202.0 36.7 26.0 1.025 8.00 0.157 1.3
Pipe: 6 0.0 0.0 2.00 150 0.2
28 202.0 36.7 21.0 3A L1.000 ---- 0.00 0.0
2C 202.0 36.5 21.0 1.025 2.00 0.105 0.2
Pipe: 7 0.0 0.0 16.00 150 2.4
2C 202.0 36.5 21.0 3B 1.250 ---- 0.00 -1.7
3A 206.0 34.1 21.0 1.244 16.00 0.041 0.7
Pipe: 8 0.0 0.0 5.00 150 1.1
3A 206.0 34.1 21.0 3 1.250 ---- 0.00 -0.9
3B 208.0 33.1 21.0 1.244 5.00 0.041 0.2
Pipe: 9 0.0 0.0 3.00 150 1.1
3B 208.0 33.1 21.0 4 F1.000 ---- 0.00 -0.9
3 210.0 32.0 21.0 1.101 3.00 0.074 .0.2
Pipe: 10 0.0 0.0 2.00 120 1.9
3 210.0 32.0 21.0 5 A1.000 C: 5.0 5.00 -0.9
4 212.0 30.1 21.0 1.049 7.00. 0.142 1.0
Pipe: 12 0.0 14.2 7 27.00 150 5.0
4 212.0 30.1 6.8 6 F1.000 E: 7.0 17.00 -1.7
5 216.0 25.1 21.0 1.101 28:10.0 44.00 0.074 3.3
Pipe: 13 0.0 0.0 107.00 150 1.2
5 216.0 25.1 6.8 9 F1.000 E: 7.0 22.00 0.0
6 216.0 23.9 6.8 1.101 38:15.0 129.00 0.009 1.2
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 50(1HD) .SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: - L C (Pt)
Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Fe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 14 0.0 0.0 11.00 150 5.3
5 216.0 25.1 14.2 8 Fl.000 E: 7.0 1.00 -4.3
7 226.0 19.8 14.2 1.101 2B:10.0 28.00 0.036 1.0
Pipe: 15 0.0 9.0 10 10.00 150 4.5
6 216.0 23.9 -2.2 8 F1.000 B: 5.0 5.00 -4.3
9 226.0 19.4 6.8 1.101 15.00 0.009 0.1
Pipe: 15A 0.0 2.2 9 2.00 150 0.3
7 226.0 19.8 12.0 103 F1.000 B: 5.0 5.00 0.0
8 226.0 19.5 14.2 1.101 7.00 0.036 0.3
Pipe: 17 4.90 21.0 Disch 31.00 150 1.1
8 226.0 19.5 -9.0 F1.000 E: 7.0 12.00 0.0
103 226.0 18.4 12.0 1.101 B: 5.0 43.00 0.026 1.1
Pipe: 18 0.0 9.0 10 46.00 150 0.1
8 226.0 19.5 -6.8 6 F1.000 E: 7.0 12.00 0.0
9 226.0 19.4 2.2 1.101 B: 5.0 58.00 0.001 0.1
Pipe.: 19 0.0 0.0 6.00 150 0.0
102 226.0 19.0 0.0 F1.000 E: 7.0 12.00 0.0
10 226.0 19.0 0.0 1.101 B: 5.0 18.00 0.000 0.0
Pipe: 20 0.0 0.0 8.50 150 0.0
101 226.0 19.0 0.0 F1.000 E: 7.0 7.00 0.0
102 226.0 19.0 0.0 1.101 15.50 0.000 0.0
Pipe: 21 4.90 21.0 Disch 37.00 150 0.7
10 226.0 19.0 -12.0 8 F1.000 B: 5.0 5.00 0.0
103 226.0 18.4 9.0 1.101 42.00 0.016 0.7
Pipe: 22 0.0 0.0 22.00 150 0.4
9 226.0 19.4 9.0 103 F1.000 B: 5.0 5.00 0.0
10 226.0 19.0 9.0 1.101 27.00 0.016 0.4
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080.621 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.072 gprn.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 10.7 ft/sec at pipe 1.
Note
INNOVATIVE FIRE PROTECTION, INC.
8779 COTTONWOOD AVENUE SUITE 101
SANTEEI CA 92071
HYDRAULIC CALCULATIONS
FOR
THE BLUFFS PLAN 4 (LOT 50) (2HD)
2575 GLASGOW DRIVE
CARLSBAD, CA 92010
FILE NUMBER: C6207
DATE: MAY 17, 2016
-DESIGN DATA-
OCCUPANCY CLASSIFICATION:
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS CALCULATED:
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose)
FLOW AND PRESSURE (@ BOR)
SPRINKLER ORIFICE SIZE:
NAME OF CONTRACTOR:
DESIGN/LAYOUT BY:
AUTHORITY HAVING JURISDICTION:
CONTRACTOR CERTIFICATION NUMBER:
RESIDENTIAL/LIGHT
.05 gpm/sq. ft.
233 sq. ft.
18'X18-324 sq. ft.
2 sprinklers
34.6 gpm
39.6 gpm
34.5 gpm @ 37.9 psi
1/2" inch
INNOVATIVE FIRE PROTECTION, INC.
JOE PLASSMEYER
CARLSBAD FIRE DEPARTMENT
C-16 711148
CALCULATIONS BY BASS COMPUTER PROGRAM (LICENSE # 16080621
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 50(2HD) .SDF
JOB TITLE: THE BLUFFS
a
0
0
0
IC)
0
In a
0
C
LC)
0 0 0 0
0 0
0 0 0 0 0
(N 0 I
—acn•H----
SPRINKLER SYSTEM HYDRAULIC ANALYSIS. Page 2
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)LOT 50(2HD) .SDF
JOB TITLE: THE BLUFFS
NFPA WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. S DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 105.6 95.0 500.0 105.5 39.5 78.4
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 39.5 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 34.5 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 202.0 SOURCE 78.4 39.5
2 202.0 - - - - 58.0 - - -
2A 202.0 - - - - . 55.0 - - -
D 202.0 - - - - 54.3 - - -
C 202.0 - - - - 47.3 - - -
2B 202.0 HOSE STREAM 44.6 5.0
2C 202.0 - - -, - 44.1
3A 206.0 - - - - 40.7 - - -
3B 208.0 - - - - 39.3 - - -
3 210.0 - - - - 37.9 - - -
4 212.0 - - - - 36.3 - - -
5 216.0 - - - - 26.3 - - -
6 216.0 . - - - - 22.9 - - -
7 226.0 . - - - - 19.6 - - -
8 . .226.0 - - - - 19.0 - - -
9 226.0 - - - - 18.2 - - -
10 . 226.0 - - - - 16.2 - - -
101 226.0 K= 4.90 12.0 17.0
102 226.0 K= 4.90 12.8 . 17.5
103 226.0 - - - - 17.6 - - -
NOTES
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS-PLAN 4 (REV2)-LOT 50(2HD) .SDF
JOB TITLE: THE BLUFFS
NFPA PIPE DATA
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft). PT (q) Node/ Nom ID Eq.Ln. F (Fe)
To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 1 Source 0.0 45.00 150 20.4
1 202.0 78.4 39.5 2A 1<1.000 T: 6.0 7.00 0.,0
2 202.0 58.0 39.5 0.995 G: 1.0 52.00 0:393 20.4
Pipe: 2 0.0 Fixed Pressure Loss Device
2 202.0 58.0 39.5 D 3.0 psi, 39.5 gpm
2A 202.0 55.0 39.5
Pipe: 3 0.0 0.0 2.00 150 0.7
2A 202.0 55.0 39.5 C L1.000 ---- 0.00 0.0
D 202.0 54.3 39.5 1.025 2.00 0.340 0.7
Pipe: 4 0.0 Fixed Pressure Loss Device
D 202.0 54.3 39.5 2B 7.0 psi, 39.5 gpm
C 202.0 47.3 39.5
Pipe: 5 H.S. 5.0 Disch 1.00 150 2.7
C 202.0 47.3 34.5 2C L1.000 T: 7.0 7.00 0.0
28 202.0 44.6 39.5 1.025 8.00 0.340 2.7
Pipe: 6 0.0 0.0 2.00 150 0.5
2B 202.0 44.6 34.5 3A L1.000 ---- 0.00 0.0
2C 202.0 44.1 34.5 1.025 2.00 0.265 0.5
Pipe: 7 0.0 0.0 . 16.00 150 3.4
2C 202.0 44.1 34.5 3B 1.250 ---- 0.00 -1.7
3A 206.0 40.7 34.5 1.244 16.00 0.103 1.7
Pipe: 8, 0.0 0.0 5.00 150 1.4
3A 206.0 40.7 34.5 3 1.250 ---- 0.00 -0.9
3B 208.0 39.3 34.5 1.244 5.00 0.103 0.5
Pipe: 9 0.0 0.0 3.00 150 1.4
3B 208.0 39.3 34.5 4 F1.000 ---- 0.00 -0.9
3 210.0 37.9 34.5 1.101 3.00 0.187 0.6
Pipe: 10 0.0 0.0 2.00 120 1.6
3 210.0 37.9 34.5 5 A1.000 ---- 0.00 -0.9
4 212.0 36.3. 34.5 1.049 2.00 0.358 0.7
Pipe: 12 0.0 22.5 7 27.00 150 10.0
4 212.0 36.3 12.0 6 F1.000 E: 7.0 17.00 -1.7
5 216.0 26.3 34.5 1.101 28:10.0 44.00 0.187 8.2
Pipe: 13 0.0 0.0 . 107.00 150 3.4
5 216.0 26.3 12.0 9 F1.000 E: 7.0 22.00 0.0
6 216.0 22.9 12.0 1.101 3B:15.0 ' 129.00 0.027 3.4
Note
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page.4
DATE: 5/17/2016 SYSTEMS\JP CALCS\THE BLUFFS -PLAN 4 (REV2)LOT 50(2HD).SDF
JOB TITLE: THE BLUFFS
Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt)
Frm Node El (ft) PT (q$ Node/ Nom ID Eq.Ln. F (Pe)
To Node . El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf)
Pipe: 14 0.0 0.0 11.00 150 6.7
5 216.0 26.3 22.5 8 F1.000 5: 7.0 17.00. -4.3
7 226.0 19.6 22.5 1.101 2B:10.0 28.00 0.085 2.4
Pipe: 15 0.0 20.9 10 10.00 150 4.7
6 216.0 22.9 -8.8 8 F1.000 8: 5.0 5.00 4.3
9 226.0 . 18.2 12.0 1.101 15.00 0.027 0.4
Pipe: iSA 0.0 8.8 9 2.00 150 0.6
7 226.0 19.6 13.7 103 F1.000 8: 5.0 5.00 0.0
8 226.0 19.0 22.5 1.101 7.00 0.085 0.6
Pipe: 17 0.0 0.0 . 31.00 150 1.4
8 226.0 19.0 13.7 10 F1.000 E: 7.0 12.00 0.0
103 226.0 17.6 13.7 1.101 B: 5.0 43.00 0.034 1.4
Pipe: 18 0.0 20.9 10 . 46.00 150 0.9
8 226.0 19.0 -12.0 6 F1.000 5: 7.0 12.00 0.0
9 226.0 18.2 8.8 1.101 B: 5.0 58.00 0.015 0.9
Pipe: 19 4.90 17.5 Disch . 6.00 150 3.4
10 226.0 16.2 17.0 101 F1.000 5: 7.0 12.00 0.0
102 226.0 12.8 34.5 1.101 B: 5.0 18.00 0.187 3.4
Pipe: 20 4.90. 17.0 Disch 8.50 150 0.8
102 226.0 12.8 0.0 F1.000 E: 7.0 7.00 0.0
101 226.0 12.0 17.0 1.101 15.50 0.050 0.8
Pipe: 21 0.0 34.5 102 37.00 150 1.4
103 226.0 17.6 -20.9 9 F1.000 B: 5.0 5.00 0.0
10 226.0 16.2 13.7 . 1.101 42.00 0.034 1.4
Pipe: 22 0.0 34.5 102 . 22.00 150 2.0
9 226.0 18.2 -13.7 103 F1.000 B: 5.0 5.00 0.0
10 226.0 16.2 20.9 1.101 27.00 0.074 2.0
NOTES (HASS)
Calculations were performed by the HASS 8.5 computer program
under license no. 16080621 . granted by
HRS Systems, Inc. -
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.001 gpm and a maximum
imbalance at any node of 0.015 gpm. .
Total pressure at each node is used in balancing the system.
Maximum water velocity is 16.3 ft/sec at pipe 1.
Not €
'-C-.
P.
.jPage 1 of 8
SENJU SPRINKLER CO.,LTD.
Residential Lead Free Flat Concealed Sprinkler,
Pendent,
Model: RC-RES, K-Factor: 4.9, SIN: SS8464 I-u
GENERAL DESCRIPTION
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. These
are decorative and fast response. The Cover Plate Assembly hides the Deflector, Heat Responsive Element etc., which is in turn
concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 inch, 68mm). The
push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows easy installation of the cover plate.
Therefore, the Model RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and
unbeatable performance is desired. The Model RC-RES is designed for the residential occupancies and it is perfect for use in
homes, hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13.
The Model RC-RES has a 4.9 (70.6 LPM/bar12) K-factor that meets the required residential flow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements.
For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of
pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents' escape or
evacuation in case of fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety
construction required by building codes.
"Lead Free" is defined in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and
California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of pipes,
plumbing fittings and fixtures.
WARNINGS
The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of
any other authorities having jurisdiction.
In the event of this condition, consult the authorities having jurisdiction for guidance and approval.
Failure to do so may impair the integrity of these devices.
It is the responsibility of the installing contractor to provide a copy of this document to the owner or his representative,
and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner is
responsible for maintaining their fire protection system and devices in proper operating condition. The installing
contractor or sprinkler manufacturer should be contacted with any related questions.
AS 160115
2535 GLASGOW DR
Document No. U085160 Date Feb/09/2015
OPERATION
Page 2 of 8
2- 46 (0 52mm)
NPT1/2 Marking
No.
Year of Manufacture
SIN SS8464
K-factor <4.9
1/—Lot
Roling : 162F/72C
UL Mark or75F/79C
Temperature
r Control No. : 6P37
ji
NSF Mark: Nsr- sl --G
RES SPKR
® Body (Copper Alley)
Deflector (Phosphorus Bronze)
CD Gasket (PTFE)
_________________ ® Fusible Metal (Solder)
t Heat Collector (Copper)
2- °/e" (0 68mm) 6 Cover Plate Assembly
or 3-Y4" (83mm)
or 2- °/8"square (068mm)
FIGURE 1. Model RC-RES K4.9
Color Code Color
-SIN SS8464
K-toclor: e4.9
Temperature Rating:
6zrfl2c or 175F/79C
COVER PLATE SPRINKLER
(Top view) (Bottom view)
FIGURE 1-1. Marking (Color Code)
TECHNICAL DATA
Approvals:,UL,,, Listed, NSF-61 -G
Sprinkler Identification Number (SIN): SS8464
Maximum Working Pressure: 175psi (112.1 bar)
Discharge Coefficient (Nominal K-Factor):
K4.9 GPM/psi112 (70.6 LPM/bar112)
Temperature Rating:
162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate
1751 (79°C) Sprinkler with 1621 (72°C) Cover Plate
Color Code (Sprinkler)
1621 (72°C): Uncolored
1751 (790C): White
Color Code (Cover Plate)
140°F (600C): No Mark
1621 (720C): White-Colored Mark
Vertical Adjustment: 1/2 inch (12.8 mm)
Cover Plate Finishes:
Standard Finishes-
White, Ivory, Beige, Brown, Black, Nickel,
Wood Grain
Custom Finishes-
Custom color and custom pattern cover plates are
available on special order. Contact a Senju
Sprinkler representative with any custom orders.
Please see chart on Page 8 for more detail.
Physical Characteristics: Ref. Figure 1
In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then, the C
o
v
e
r
P
l
a
t
e
i
s
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire
,
a
n
d
when sufficient heat from the fire is recorded, internal components of the sprinkler to fall apart. This leads to allow the
w
a
t
e
r
f
l
o
w
to be distributed on the affected by fire area. (Ref. Figure 2)
Normal Condition Cover Plate Operation =# Sprinkler Operation Water Discharge
FIGURE 2. OPERATION PROCESS (The figure is for illustrative purpose only)
Document No. U085160 Date Feb/09/2015
Page 3 of 8
DESIGN CRITERIA
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
NOTES
Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar
with automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the
sprinkler system designer review and develop a working understanding of the complete list of criteria prior to initiating
the design of the sprinkler system.
Questions concerning sprinkler installation and usage criteria, which are not coverage by the following instructions,
should be submitted to Contact Company. Include sketches and technical details as appropriate.
In some instances, the requirements of this document may concern specifications which are more stringent and which
take precedence over those specified in NFPA 13, 130, 13R, or by the authority having jurisdiction.
The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below.
Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the
cup are open and free from any air flow impediment.
The spray from the sprinkler is distributed radically outward and downward from the sprinkler deflector. Consequently,
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers,
overhangs or other parts of the dwelling structure.
The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R) must be kept as small as
possible. Do NOT use more sprinklers than necessary to cover a particular space.
Use only the Cover Plate provided with the Model RC-RES. The sprinkler must be secured in place by firmly fastening
the sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces
resulting from sprinkler operation could alter its orientation and its water distribution pattern.
Obstruction to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13 for Residential Sprinklers.
General Service Conditions
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Heat Source Criteria
Refer to NFPA 13D or 13R for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to exposure to a heat sources other than an actual fire.
Precautionary Warnings for Corrosive Environments
The Model RC-RES should not be installed where they may be subjected to a corrosive environment including the following:
Chlorine ion and Chloride environment.
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire.
Sprinkler system piping with Copper.
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for the copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA
(Copper Development Association) - Solder Joint)
All residual flux must be removed from the interior and exterior of copper piping by thoroughly flushing before installation of
the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and leakage in the sprinkler system.
Hydraulic Design Criteria
The minimum required sprinkler flow rates for system designed to NFPA 130 or 13R are given in Table A as a function of
temperature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge
from the most hydraulically demanding sprinkler from each of the total number of 'design sprinklers" as specified in NFPA 13D
or 13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the followings;
The flow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area.
Document No. U085160 Date Feb/09/2015
Page 4 of 8
A minimum discharge 0.1GPM/sq.ft. [4.07LPM/sq.m] over the design area' comprised of the four most hyd
r
a
u
l
i
c
a
l
l
y
demanding sprinklers for the actual coverage areas being protected by the four sprinklers.
TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464
Maximum Ordinary Intermediate
Covera ge Maximum Temperature Rating Temperature Rating Deflector Minimum
Spacing 162'F (72°C) 175F (79°C) Installation Spacing
Area 1
Ft. x Ft. Ft.
to
Ceiling Type Ft. Flow Pressure (b) Flow
xm) (m) GPM GPM
(m PSI
(LPM) (bar)
Fer)e
(LPM)
Smooth
12x12 12 13 7.0 13 Ceilings
(3.7x3.7) (3.7) (49.2) (0.48) (49.2) 3/8 to 7/8
Inches.
14x14 14 13 7.0 13 7.0 Beamed
(4.3x4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Ceilings
per NFPA
16x16 16 13 7.0 14 8.2 13D,13R Concealed 8
(4.9x4.9) (4.9) . (49.2) (0.48) (53.0) (0.57) or 13 (2.4)
Installed
in beam
18X18 18 17 12.0 18 13.5 . 3/8 to
(5.5x5.5) (5.5) (64.3) (0.83) (68.1) (0.93) 7/8
inches
20x20 20 21 18.4 below
(6.1x6.1) (6.1) (79.5) (1.27) -
- bottom of
beam.
For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for th
e
Next Higher Coverage Area listed.
Requirement is based on minimum flow in GPM/LPM from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with the 2013 E
d
i
t
i
o
n
o
f
NFPA 13D, 13R or 13 as applicable.
Sprinkler Spacing Criteria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go bey
o
n
d
t
h
e
coverage area calculated by using the specific hydraulic factors. (Ref. Table A)
INSTALLATION
The Model RC-RES must be installed in accordance with the following instructions.
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprink
l
e
r
s
w
h
i
c
h
show deformation or cracking in either the Sprinkler or the Protective Cap.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minim
i
z
e
t
h
e
potential for damage to sprinklers that would cause improper operation or non-operation.
The Protective Cap must remain on the sprinkler during installation and until the ceiling installation is co
m
p
l
e
t
e
d
.
T
h
e
Protective Cap must be removed to place the sprinkler in service.
Document No. U085160 Date Feb/09/2015
Page 5 of 8
Use a torque of 7 to 14 ft.lbs (9.5 to 19.ONm) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended
maximum torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
In case of insufficient adjustment in. Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely
or make any modification to the cover plate assembly. Readjust the sprinkler fitting for a better fit.
Installina Procedure
Step I
The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway
perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface
will be nominally 2 inch (50.8mm) as shown in Figure 3.
Step 2
With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the
Sprinkler Socket or Wrench & Socket Combination (Ref. Figure 4). The grooves of the Socket must fit perfectly with the
grooves on the Sprinkler for proper installation (Ref. Figure 4).
Step 3
If desired the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling material
against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be started with
the 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Tolerance Limit of Ceiling Level" indicator on the
Protective Cap to check for proper installation height (Ref. Figure 3).
Make o Space Here Do NOT
/we. ) (6.4mm) I Over-Tighten Groove on the Sprinkler
Mn )' (3.2mm)
Tolerance Limit Protective Cop
of
Mountino Surface
_____ ___
Groove of the Socket
fCeiling
Mounting Surface/
(6Omm)
Ceiling Hole Diameter
Socket
I CORRj IINCORRECT1
FIGURE 3. INSTALLATION FIGURE 4
Step 4
Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on
the Cup of the Sprinkler by hand until its flange just comes in contact with the ceiling (Ref. Figure 6 and Figure 7). Stop
tightening the Cover Plate Assembly once the flange has come in contact with the ceiling. If the ceiling has been lifted from its
normal position in the process of tightening of the Cover Plate Assembly, readjust the cover plate assembly as necessary. If
the flange of the Cover Plate Assembly cannot come in contact with the ceiling sufficiently, readjust the sprinkler fitting as
necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and the
ceiling, as shown in Figure 6
Document No. U085160 Date Feb/09/2015
Page .• 6 of
Sprinkler :Head: M
Prote ctive
Step I
Remover RC
Step 2
Hook by turning
Step 3 4
Pull down
FIGURE 5. PROTECTIVE CAP REMOVAL
Document No. U085160 Date Feb/09/2015
CARE AND MAINTENANCE Page :7of 8
The following instructions must be implemented for the maintenance and service of the Model.RC-RES.
NOTES
Wet pipe sprinkler systems must be maintained at a minimum temperature of 40 F/4 t to prevent freezing and bursting
of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result.
Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of fire.
Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may
cause improper operation or non-operation.
If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint
does not seal off any of the air gap.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover
plates. Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire.
Do not pull the Cover Plate. Separation may result.
In preparation for maintenance of the fire protection system, permission to close the main control valve mustbe
obtained from the proper authorities and all affected by this action parties must be informed before the maintenance
session can commence.
Do NOT enclose any,sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and water, detergents, ammonia, cleaning fluids, or other chemicals. Remove
dust, lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (i.e., dusting) brush attachment.
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of fire
development and spread of these materials can reduce the ability of the sprinkler systems to aid in the control of a fire
involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must never be shipped or stored where the temperature exceeds 100'F/38°C.
Automatic sprinkler must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the
sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged
units, as a result of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service and
which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated under Table A
'Hydraulic Design Criteria").
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first verity that
the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction
and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing, its compliance with this
documents, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any other
authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the installing
contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested, and
maintained by a qualified Inspection Service in accordance with NFPA 25.
Document No. U085160 Date . Feb/09/2015
Page 8 of 8
ORDER PROCEDURE
When placing an order, please contact a local distributor with the'following information (Model Name, Specify, Temp. and Finish).
Sprinkler:
Model: RC-RES
(SIN: SS8464, Residential Flat Concealed Sprinkler, Pendent, K4.9, Temperature: 162°F (72°C) or 175°F '(79°C))
Cover Plate Assembly:
2-5/8 inch (q5 68mm) or 3-1/4 inch (0 83mm) or 2-5/8 inch square (08mm), Order Separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and finishes.
Standard Finishes Custom Finishes
White Ivory Beige Brown Black Nickel Wood grain Custom Color Custom Pattern
2-5/8" Round, 140°F 0 0 - - - 0 - 0 0
3-1/4" Round, 140°F 0 0 0 0 0 0 0 0 0
2-5/8" Square, 140°F 0 '- - - - - - 0 0
2-5/8" Round, 162°F 0 - - - - - - 0 0
3-1/4" Round, 162°F 0 - - - - - - 0 0
Tools for Installation of Model: RC-RES
Socket for Model RC-RES
Wrench & Socket for Model RC-RES
Cap Remover RC
Document No. U085160 Date Feb/09/2015
Conventional
Recessed
Pendent/Fl/F2
Recessed
PendentjFP
Bulletin 014 Rev. N
liable Model Fl FR Series
Quick Response
Glass Bulb Sprinklers
C
CD
0
CD
PIA
Model F1FR56 Sprinkler Types
Standard Spray Upright
Standard Spray Pendent
Conventional Upright/Pendent
Vertical Sidewall
Horizontal Sidewall
Model Fl FR56 Recessed Sprinkler Types
Standard Spray Pendent
Horizontal Sidewall
Model F1FR56 Concealed Sprinkler Types
Standard Spray Pendent
Model F1FR42, F1FRXLH & F1FR28 Sprinkler
Types
Standard Spray Upright
Standard Spray Pendent
Model Fl FR40 Sprinkler Types
Standard Spray Pendent
Model F1FR42, F1FR40, F1FRXLH & F1FR28
Recessed Sprinkler Types
Standard Spray Pendent
Model Fl FR56LL & Fl FR42LL NSF Certified Low
Lead Sprinkler Types
Standard Spray Pendent with less than 0.25% Lead
Content
Listing & Approvals
The following organizations provide Listings or Approvals
for various Model Fl FR series sprinklers. See the Design
and Installation table in this Bulletin for information on
specific listings and approvals applicable to each sprin-
kler.
Underwriters Laboratories Inc. and Certified for
Canada (cULus).
FM Approvals (FM)
Loss Prevention Certification Board (LPCB)
VdS Schadenverhutung GmbH (VdS)
NSF Certified to NSF/ANSi Standard 61 Annex G
(NSF)
EC Certificate: 0786-CPD-40239 (RA1414), 0786-
CPD-4025 1 (RA 1425) 0786-CPD-40252 (RA 1475)
(EC)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Upright Pendent
Vertical Sidewall Horizontal Sidewall
Recessed
Horizontal Sidewall
XLH Upright XLH Pendent
Pendent Fl/F2
Product Description
Reliable Model F1FR series sprinklers
are quick-response automatic sprin-
klers with a glass bulb thermal element.
Model F1FR series sprinklers are Stan-
dard Spray sprinklers, with the excep-
tion of the Model F1FR56 Conventional XLH Recessed
sprinkler which is an Old-style/Conven- Pendent FP
tional sprinkler.
The Model F1FR Series automatic sprinklers utilize a 3.0
mm frangible glass bulb. These sprinklers have demonstrat-
ed response times in laboratory tests which are five to ten
times faster than standard response sprinklers. This quick
response enables the Model Fl FR Series sprinklers to apply
water to a fire faster than standard-response sprinklers of the
same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
-
..-
:-_
;;-
:.•:-
Concealed
Pendent
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Model F1FR Series sprinklers provide a wide range of op-
tions where quick-response, glass bulb sprinklers are used:
Pendent, recessed pendent, upright, horizontal side-
wall, and vertical sidewall deflectors
K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60
metric), and 5.6 (80 metric)
Flush, recessed, and concealed installations
See the Design and Installation Information table in this
Bulletin for information on the approvals and availability of
specific Model F1FR series sprinkler configurations.
Model F1FR Recessed Pendent and Recessed Horizon-
tal Sidewall sprinklers are required to be used with Reliable
Model Fl, F2, or FP recessed escutcheons. See the Re-
cessed Escutcheon Data table in this Bulletin for listing and
approval information with each specific Model F1FR series
sprinkler. Model Fl and F2 recessed escutcheons, shown in
Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch
(19mm) and 1/2-inch (12.7mm) of adjustment, respectively.
Model FP recessed escutcheons, shown in Fig. 2, provide a
1/2-inch (12.7mm) threaded adjustment.
Model F1FR56 Concealed Pendent and Model F1FR56LL
Concealed Pendent sprinklers are required to be used with
Model CCP cover plates. A standard profile Model CCP cov-
er plate is available that provides up to 1/2-inch (12,7mm) of
cover plate adjustment. In addition, a low profile Model CCP
cover plate is also available that provides up to 5/16-inch
(8.0mm) of cover plate adjustment. See the Design and In-
stallation Information and Listed and Approved Temperature
Ratings tables in this Bulletin for further information on ap-
proved cover plate options.
Application
Model F1FR Series sprinklers are intended for use in
accordance with NFPA 13, FM Property Loss Prevention
Data Sheets, and the requirements of the Authority Hav-
ing Jurisdiction. Care must be exercised that the k-factor,
temperature rating, deflector style, and sprinkler type are
in accordance with the requirements of the applicable
design and installation standards. In addition, Model
F1FR Series sprinklers must be used in accordance with
their listings and approvals, as well as the information
provided in this Bulletin.
Installation
Glass bulb sprinklers have orange bulb protectors or pro-
tective caps to minimize bulb damage during shipping, han-
dling and installation. Reliable sprinkler installation wrench-
es are designed to install sprinklers with bulb protectors in
place. Remove the bulb protector at the time when the sprin-
kler system is placed in service for fire protection. Removal
of the bulb protector before this time may leave the bulb vul-
nerable to damage. Remove bulb protectors by undoing the
clasp by hand. Do not use tools to remove bulb protectors.
2.
Model F1FR Series sprinklers must be installed with the
Reliable sprinkler installation wrench identified in the Design
and Installation Information table in this Bulletin. Any other
wrench may damage the sprinkler. A leak tight sprinkler joint
can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m).
Do not tighten sprinklers over the maximum recommended
installation torque. Exceeding the maximum recommended
installation torque may cause leakage or impairment of the
sprinkler.
Recessed Sprinklers
Model Fl FR Series Recessed sprinklers are to be installed
as shown in Fig. 1 Fig. 2, or Fig. 3, as applicable to the spe-
cific model being installed. The Recessed Escutcheon Data
table in the Bulletin identifies the only recessed escutcheons
that are permitted to be used with each Model F1FR Series
Recessed sprinkler. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
Concealed Sprinklers
Model F1FR Series Concealed Pendent sprinklers are to
be installed as shown in Fig. 4 or Fig. 5, as applicable to the
selected cover plate. Model F1FR56 Concealed Pendent
and Model Fl FR56LL Concealed Pendent sprinklers have
a factory-installed Model CCP cup. A protective cap is in-
stalled at the factory that should remain on the sprinkler until
the sprinkler is installed and should then be reinstalled on
the sprinkler until the cover plate is installed. The concealed
sprinkler assemblies are completed by the installation of a
Model CCP push-on/thread-off cover plate assembly. The
cover plate and sprinkler cup assemblies are joined using
a cover plate skirt with flexible tabs'for threaded engage-
ment. A choice of two Model CCP cover plate assemblies
provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover
adjustment. Do not install Model F1FR Series Concealed
Pendent sprinklers in ceilings which have positive pressure
in the space above.
Model F1FR Series Concealed Pendent sprinklers require a
2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
Model RC1 wrench is used to engage the sprinkler wrenching
surfaces and to install the sprinkler in the fitting. Remove the
protective cap to install the sprinkler, then reinstall the protective
cap until the cover plate is installed. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should be
taken to prevent damage to the sprinkler. Do not wrench any
other part of the sprinkler/cup assembly. Installation is com-
pleted by removing the protective cap from the sprinkler and
pushing the cover plate onto the cup. Final adjustment is made
by hand turning the cover plate until the skirt flange makes full
contact with the ceiling. Cover plate removal requires turning the
cover plate in the counter clockwise direction. After installation,
inspect all sprinklers to ensure that there is a gap between the
cover plate and ceiling and that the four cup slots are open and
free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any concealed cover
plate/cup assembly other than the Reliable Model CCP with
Model Fl FR56 Concealed Pendent and Model Fl FRS6LL
Concealed Pendent sprinklers or the use of the Model CCP
Concealed cover plate assembly on any sprinkler with which
it is not specifically listed my prevent good fire protection and
will void all guarantees, warranties, listings and approvals.
Technical Data:
Sensitivity: Quick-response
Thread Size: 1/2-inch NFl standard; ISO 7-R1/2 optional
Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar)
SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar)
Design and Installation Information
Model
Nominal
K-factor
Nominal
Orifice
Diameter
Deflector/
Orientation
Nominal
Sprinkler
Height
Installation
Wrench
mm
SIN
List in gs
and
Approvals
Approval
Notes
US Metric inches mm inches
Fl FR28 2.8 40 3/8 10
Pendent 2.25 57 0 RA1411 cULus 2
Recessed Pendent 2.25 57 GFR2 RA141 1 cULus 2
Upright 2.25 57 0 RA1421 cULus 1,2
F1FR40 4.0 57 3/8 10 Pendent 2.25 57 0 RA1418 VdS
Recessed Pendent 2.25 57 GFR2 RA14181 VdS
F1FR42 4.2 60 7/16 10
Pendent 2.25 57 D RA1413 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 D RA1423 cULus 1,2
F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 D RA1410 cULus, NSF
Recessed Pendent 2.25 57 GFR2 RA1410 cULus, NSF
F1FRXLH
(Fl FR42
with Pintle)
4.2 60 7/16 10
Pendent 2.25 57 D RA1413 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 D. RA1423 us cULus 1,2
F1FR56 5.6 80
______
1/2 15
Pendent 2,25 57 0 RA1414 FM,
LPCB, VdS, EC 1,2,3,4
Recessed Pendent
_______________
2.25
_____
57 GFR2
_________
RA1414
______
cULus, FM,
LPCB, VdS, EC
1,2,3,4
Concealed Pendent 2.25 57 RC1 RA1414 cULus,VdS,EC 5,6
Upright 2.25 57 D RA1425 cULus, FM,
LPCB, VdS, EC 1,2,3,4
"Conventional 2.25 57 (Pendent or Upright)"
D RA1475 LPCB, VdS, EC 4
F1FR56LL 5.6 80 1/2 15
Pendent 2.25 57 0 RA1415 cULus, NSF 1
Recessed Pendent 2.25 57 GFR2 RA1415 cULus, NSF
Concealed Pendent 2.25 1 57 RC1 RA14141 cULus, NSF 6
F1FR56 5.6 80 1/2 15
Horizontal Sidewall 2.63 67 D RA1435 cULus, FM 1,2,3,7
Recessed Horizontal
Sidewall
2.63 67 GFR2 RA1435 cULus, FM 8
F1FR56 5.6 80 1/2 15 Vertical Sidewall
(Pendent or Upright) 2.25 57 D RA1485
_______
cULus, FM,
LPCB 1,2,3,9
cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
0 cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PTFE plating.
3) Available with FM approved Polyester coating in black or white.
'" Available with LPCB and VdS approved Polyester coating.
VdS and EC approvals of the F1FR56 Concealed Pendent sprinkler are for 155°F (680c) temperature rated sprinklers only. VdS approved sprin-
klers must use Norbuib brand glass bulbs with the 1/2-inch (12.7mm) adjustment Model CCP cover plate only.
°) Model Fl F856 Concealed Pendent and Model Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
available as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment.
(7) cULus Listing of the F1FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. FM Approval of the F1FR56 Hori-
zontal Sidewall sprinkler is for Light Hazard occupancies only.
° cULus Listing and FM Approval of the Fl FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
0 The F1FR56 Vertical Si dewall sprinkler is listed and approved for use only in Light Hazard occupancies. Minimum to maximum deflector to ceil-
ing distance shall be 4 inches to 12 inches (102mm to 305mm). LPCB approval of the F1FR56 Vertical Sidewall sprinkler is for installation in the
Pendent position only.
3.
Listed and Approved Temperature Ratings
Model Deflector!
Orientation
Ordinary Temp.
Classification
100°F (38°C) Max. Ambient
Temp.
Intermediate Temp.
Classification
150°F (65°C) Max. Ambient
Temp.
High Temp.
Classification
225°F (107°C) Max.
Ambient Temp.
1350F(57°C)
Temp. Rating
155°F(680C)
Temp. Rating
1750F(79°C)
Temp. Rating
200°F(93°C)
Temp. Rating
286°F (141°C) Temp.
Rating
Orange Bulb Red Bulb I Yellow Bulb Green Bulb Blue Bulb
Pendent cULus
F1FR28 Recessed Pendent cULus --
_________ Upright cULus
Pendent VdS F1FR40
Recessed Pendent VdS --
Pendent cULus
F1FR42 Recessed Pendent cULus I --
__________ Upright cULus
Pendent -- cULus, NSF -- F1FR42LL
_________ Recessed Pendent -- cULus, NSF --
Pendent cULus
F1FRXLH Recessed Pendent cULus I --
__________ Upright cULus
Pendent cULus, FM, LPCB, VdS, EC
Recessed Pendent cULus, FM, LPCB, VdS, EC --
F1FR56 Concealed Pendent* cULus cULus,VdS,EC I cULus --
Upright cULus, FM, LPCB, VdS, EC
"Conventional
(Pendent or Upright) LPCB VdS EC
Pendent -- cULus, NSF --
F1FR56LL Recessed Pendent -- cULus, NSF --
_________ Concealed Pendent" -- cULus, NSF --
Horizontal Sidewall cULus, FM
Fl FR56 Recessed Horizontal
Sidewall cULus, FM --
F1FR56 I
Vertical Sidewall (Pen-
dent or Upright) cULus, FM, LPCB
* Model Fl FR56 Concealed Pendent and Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model
CCP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover
plate. For Intermediate Temperature Classification sprinklers use a 165°F (74°C) temperature rated cover plate.
Recessed Escutcheon Data
Listed and Approved Recessed Escutcheons
Model Fl Model F2 Model FP
Model Deflector/ (Fig. 1 & 3) (Fig. 1 & 3) (Fig. 2) SIN Orientation 3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-inch (12.7mm)
adjustment adjustment adjustment
F1FR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA 1410
F1FR42XLH Recessed Pendent cULus cULus cULus RA1413
F1FR56 Recessed Pendent cULus, LPCB, VdS, cULus, FM, LPCB, cULus, VdS, EC RA1414 EC VdS,EC _
F1FR56LL Recessed Pendent cULus, NSF cULus, NSF cULus, NSF RA1415
FIFR56 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435
4.
1" X 1/2" REDUCER
FACE OF FITTING
TO FACE OF CEILING DIMENSION
F? ESCUTCHEON
AT MAXIMUM RECESS = 1[25.4mm]
AT MINIMUM RECESS = 3/8[9.5mm]
/ F2 ESCUTCHEON
AT MAX/MUM RECESS = 3/4[19mm]
AT MINIMUM RECESS = 3/8[9.5mm]
Fl ESCUTCHEON
AT MAXIMUM RECESS = 7/8"(22.2mm]
[32mm] I / AT MINIMUM RECESS = I - 5/8 '[41.3mm]
r F2 ESCUTCHEON
AT MAXIMUM RECESS = 1-l/8"[28.6mm]
AT MINIMUM RECESS = 1-5/8[41.3mm]
2 1/4' HOLE 01,4.
[57.2mm]
I 15/16" 0/A
[49.2mm] '
1
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER
WRENCH Boss
Fl ESCUTCHEON j_
.314't 19mm]
ADJUSTMENT
F2 ESCUTCHEON
7/2[12.7mm]
ADJUSTMENT
2 27/32" 0/A.
(72.2mm]
Fig.1
Model F1FR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH & F1FR28
Recessed Pendent sprinkler with Model Fl or F2 escutcheon
T
2 5/8" 0/A. [66,7mm]
HOLE IN CEILING
/
2 5/16" DIA. [58.7mm] -
CUP
CEILING
1" X 1/2" REDUCER
FACE OF FI177NG
TO FACE OF CEILING
DIMENSION
AT MAXIMUM RECESS = 1-1/2 "[38mm]
AT MINIMUM RECESS = 1 "[25.4mm]
Y2"[12. 7mm]
47 MAXIMUM RECESS = 9/16"[14,3mm]
AT MINIMUM RECESS = / "[25.4mm]
ADJUSTMENT
3 1/4" DIA.
[82.6mm]
Fig.2
Model F1FR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH & F1FR28
Recessed Pendent sprinkler with Model FP escutcheon
5.
1 1/2" MAX.
FACE OF FITTING
_HTO FACE OF CEILING
DIMENSION
Fl ESCUTCHEON
T AAAV!AAIIAA p,"ç 1_ AIR "T4 Q,,,,-,,7
AT MINIMUM RECESS = 2- 16"[52.4mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 1-5/8."[4 1.3mm]
1/8" AT MINIMUM RECESS = 2-1/16 "[52.4mm]
2mm]
I (j)
4"-12"
[101.6mm-304.8mm]
32 DIA CEILING TO
[72.1mm] DEFLECTOR
F! ESCUTCHEON
3/4"[19mm] ADJUSTMENT
F2 ESCUTCHEON
1/2'[12. 7mm] ADJUSTMENT
FACE OF FITTING
TO FACE OF CEILING DIMENSION
Fl ESCUTCHEON
AT MAXIMUM RECESS = 1 "[25.4mm]
AT MINIMUM RECESS = 3/8 "[9.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 3/4"[19mm]
AT MINIMUM RECESS = 3/8"[9.5mm]
2 1/4" HOLE 0/A.
[5 7.2mm]
1" X 1/2" REDUCER
I
-
I I
15/16"
[49.2mm] Ii
I I -
TURN COLLAR UNTIL ---
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
Ol/VOJE
RECESSED HSW w/F1 OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" - 6" [101.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY
Fig.3
Model Fl FR56 Recessed Horizontal Sidewall sprinkler with Model Fl or F2 escutcheon
1" x 1/2" REDUCING
TEE OR ELBOW
Ef1 +Ih1 }
2 5/8" DIA.
2 5/16" 0/A -
7
17OLE IN CEILING
CUP
CEILING -"
1/2" MAX. I
COVER ADJUSTMENT
COVER PLATE -7
ASSEMBLY 5/16 0/A
SPRINKLER
CONCEALED, 1/2" ADJUSTMENT
Fig. 4
Model Fl FR56/1`1 FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch (12.7mm) adjustment - Model CCP cover plate
Ll-
1" x
TEE
1/2" REDUCING
OR ELBOW
T1If1r
2
/8" 0/A.
IN CEILING
1 1/2' MAX.
FACE OF FITTING
. TO FACE OF CEILING
,
DIMENSION
CEILING
5/16"
COVER ADJ
COVER
AS.
3/4"
-r
SPRINKLER
.CONCEALED, "f 6" ADJUSTMENT 017F502A
Fig. 5- Model Fl FR56IF1 FR56LL Concealed Pendent sprinkler with low profile
5/16-inch (8.0mm) adjustment - Model CCP cover plate
Maintenance
The Model Fl FR Series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or
any other cleaning fluids. Remove dust by using a soft brush
or gentle vacuuming. Replace any sprinkler which has been
painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow
quick replacement of damaged or operated sprinklers.
Finishes (1)
Standard Finishes
Sprinkler Escutcheon Cover platet"
Bronze Brass Chrome
Chrome Plated Chrome White
Polyester Plated
Coated )4))5X6i White Painted
Special Application Finishes
Sprinkler Escutcheon Cover platet
Electrofess Nickel
PTFE 7t
Electroless Nickel
PTFE Bright Brass rig
Bright Brass(') Bright Brass Black Plating
Black Plated Black Plated Black Paint
Black Paint(20) Black Paint Off White
Off White (2X6) Off White Satin Chrome
Chrome Dull Chrome Dull
Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
cULus Listed only.
200°F (93°C) maximum.
(1) cULus listed 'corrosion resistance" applies to SIN Numbers RA1435
(HSW), RA1485(vsw), RA1425 (upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
(5) FM Approvals finish as "Polyester coated" applies to SIN Number
RA1414, RA1435 and RA1425 in standard black or white.
LPCB and VdS Approved finish applies only to RA1425, RA1414, RA1418
(VdS) and RA1475.
cULus listed Corrosion Resistant 7
Material Data
Frame: DZR Brass, OM Brass, or Low Lead Brass
Deflector: CDA Alloy 220, 260, or 510
Load Screw\Pintle: CDA Alloy 360 or 544
Cup: CDA Alloy 651 or 693
Washer: Nickel Alloy 440 or 360, coated with PTFE
Adhesive Tape
Bulb: Glass
Ordering Information
Specify:
Sprinkler Model: [Fl FR28][F1 FR4O][F1 FR42]
[Fl FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL]
Sprinkler Deflector/Orientation: [Pendent] [Recessed
Pendent][ Upright] [Conventional][Horizontal Sidewall]
[Recessed Horizontal Sidewall][Vertical Sidewall]
Sprinkler threads: [1/2-inch NPT][lSO 7-Rl/2]
Sprinkler Temperature Rating: [135°F (57°C)][155°F
(68°C)][175°F (79°C)][200°F (93°C)][286°F (141°C)]
Sprinkler Finish
Escutcheon Model: [F1][F2][FP]
Escutcheon Finish (where applicable)
Cover plate Model: [standard profile CCP 1/2-inch
(12.7mm) adjustment][low profile CCP 5/16-inch
(8.0mm) adjustment]
Cover plate Temperature Rating: [135°F(57°C)for use
with Ordinary Temperature sprinklers][165°F (74°C)
for use with Intermediate Temperature sprinklers]
Cover plate Finish
Note: When Model F1FR Series Recessed sprinklers are ordered, the
sprinklers and escutcheons are packaged separately.
Reliable ... For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges
Identification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
Rr'll a b I (800) 431-1588 Sales Offices Pape
(800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices
- www.reliablesprinkler.com Internet Address EG. Printed inU.S.A. 12/15 P/N9999970300
Fl Res 30, 49, 58 & 76 Fl Res 30,49,58&76
Recessed Pendent I Fl Recessed Pendent! FP
Bulletin 135 Rev. M
Model Fl
Residential Sprinklers for
Design Density of .05 gpm1ft2
ED C
(11
c) 01
(0
CR
Model Fl Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpm1ft2
Types:
Fl Res 30Pendent
Fl Res 30 Recessed Pendent/F2
Fl Res 30 Recessed Pendent/FP
Fl Res 49 Pendent
Fl Res 49 Recessed Pendent/Fl
Fl Res 49 Recessed Pendent/FP
Fl Res 58 Pendent
Fl Res 58 Recessed Pendent/Fl
Fl Res 58 Recessed Pendent/FP
Fl Res 76 Pendent
Fl Res 76 Recessed. Pendent/Fl
Fl Res 76 Recessed Pendent/FP
Fl Res 30 CCP Pendent
Fl Res 49 CCP Pendent
Fl Res 58 CCP Pendent
Fl Res 76 CCP Pendent
Fl Res 44HSW
Fl Res 44 Recessed HSW/F2
Fl Res 58 HSW
Fl Res 58 HSWX
KRes58 HSWX
Fl Res 58 HSW Recessed HSW/F2
Fl Res 44 SWC
Listings & Approvals
1. Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6516,893 applies to the Model Fl Res 49
& 58 Pendent Sprinklers
US Patent No. 7,353882 applies to Model Fl Res 44 & 58
HSW Sprinklers
US Patent No. 7,784,555 applies to Model Fl Res 44 SWC
Sprinklers
Product Description
Model Fl Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are fast
response sprinklers combining excellent durability, high sensitiv-
ity glass-bulb and low profile decorative design. The Fl Res
Fl Res 44 & 58 Fl Res 44 SWC
Recessed HSW/F2
Horizontal Sidewall sprinklers (Figs. 5, 6 & 7) are equally attrac-
tive when above ceiling piping cannot be used.
The 3mm glass-bulb pendent sprinklers permit the efficient use
of residential water supplies for sprinkler coverage in residential
fire protection design.
The low flow Fl Res sprinklers are specially engineered for fast
thermal response to meet the sensitive fire protection applica-
tion needs of the latest residential market standards (UL 1626
Standard). Upon fire conditions, rising heat causes a sprinkler's
heat-sensitive element, glass bulb or link to actuate, releasing the
waterway for water flow onto the deflector, evenly distributing the
discharged water to control a fire.
Technical Data:
Thermal Sensor: Soldered Element (Link) or Nominal
3mm glass-bulb
Sprinkler Frame: Brass Casting
Sprinklers' Pressure Rating: 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size: 1/2' NPT (R'/2)
K-Factor: 3.0 (432) (Actual) - Fl Res 30 Pendent Sprinkler
4.9 (70.6) (Actual) - Fl Res 49 Pendent Sprinkler
5.8 (83.5) (Actual) - Fl Res 58 Pendent & HSW Sprinkler
7.6 (109)(Actual) - Fl Res 76 Pendent Sprinkler
4.4(63) (Actual) - Fl Res 44 HSW Sprinkler
Density: Minimum 0.05 gpm/ft2
Fl Res 30, 49, 58 & 76
CCP Pendent
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Model Fl Res Sprinklers are used for Residential Fire Pro-
tection according to UL 1626 Standard*. For ceiling types:
Smooth Flat Horizontal, or beamed, or sloped, in accordance
with NFPA 13D, 13R, or 132013 editions. Be sure that orifice
size, temperature rating, deflector style and sprinkler type are
in accordance with the latest published standards of The Na-
tional Fire Protection Association or the approving authority
having jurisdiction.
Installation
Models Fl Res sprinklers are to be installed as shown.
Model Fl, F2 and FP Escutcheons, illustrated herewith, are
Escutcheon*, Fl or F2, Data:
the only recessed escutcheons to be used with ModelF1 Res
sprinklers. Use of any other recessed escutcheon will void all
approvals and warranties. For installing Model Fl Res Pen-
dent sprinklers use only the Model D sprinkler Wrench; for
installing Models Fl Res Recessed Pendent, CCP & SWC
sprinklers use only the Model GFR2 sprinkler wrench; for in-
stalling Model Fl Res Recessed HSW sprinklers use only the
Model GFR2 Sprinkler Wrench. Use of wrenches other than
those specified may damage these sprinklers. Install Fl Res
44 with a ceiling to deflector distance of 4" - 12". Flow arrow
on deflector must point away from near wall and "Top" mark-
ing must face ceiling.
Type Adjustment
Inch (mm)
"A"
Inch (mm)
Face of fitting to ceiling
Inch (mm)
B
Deflector Distance below bottom of beam
Inch (mm)
Fl (19.0) Mm. Recessed = 1/8 (41.3) /8 (9.5) 13/,(44.4)
Max. Recessed = /8 (22.2) 11/8 (28.6) 1(25.4)
1/2 (12.7) Min. Recessed = 1/8 (41.3) (9.5) 13/-(44.4)
Max. Recessed = 1/8(28.6) /a (22.2) 11A(31.7)
'Note: Escutcheons El or F2 may be used with Model Fl Res 49, 58 & 76 Recessed Pendent Sprinkler
Model Fl Res 30 Recessed Pendent / F2
Model El Res 30, 49. 58 & 76 Pende
P --I-i
nt • Mod I i-i iies 4. bu & i'ti iiecessea i-'en lent /Fi
IJ5F'COJ
1-1 escutcheon, /4 (19mm) adjustment
[57.2mn)-..
I I5/I6 01.4.
II [492 m] —
TICHT AGAINST SPRINKLER
21/4' HOLE 0/A
- REDUCER 2
FACE OF FITUNG TO
TURN COLLAR UNTIL
WRENCH BOSS. CEILING DIMENSION:
K 1/
3/8W-I 1/8" (Fl ESCUTCHEON)
318"-718" (P2 ESCUTCHEON)
ADJUSTMENT
W.
2 27/32' 0/A.
[722
Hg. 1 Fig. 2
Technical Data: Fl Res 30 Pendent and Recessed Pendent (SIN R351 1)
I Thread
Size
I Nominal Orifice
Inch (mm)
Max. Pressure
psi (bar)
I Sprinkler Temp. Rating I Max. Arn ientTemp.1 Actual K
Factor
I Sprinkler Length
Inch (mm) I OF I °C I OF °C
Y2"NPT
I (R½)
21/" (8.2) 175 (12) I I 155
175
68
I 79 I 100 38 3.0(43.2) 2.25 (57)
Max. Ordinary Temp. Rating Intermediate Temp. Rating Minimum Max. Coverage area Spacing (1550 80c) (175°F/790 ) Top of Deflector to Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (tlmin) PSI (bar) GPM (Llmin) PSI (bar)
12 x 12 (3,6 x 3,6) 12(3.6) 8(30,3) 7.0 (0,48) 8(30,3) 7.0(0,48) Smooth Ceilings 1¼104(31.7t0 102) using F2 escutcheon.
14 x 14 (4,3 x 4,3) 14(4,3) 10(37,8) 11(0,76) 10(37,8) 11(0,76) Beamed Ceilings per NFPA 13D, 13R
or 13 installed in beams 1/4 to 1/4
(31.710 44.4) using F2 escutcheon
8(2,4)
16 X 16(4,9 X 4,9) 16(4,9) 13(49) 18.8(1,3) 13(49) 18.8(1,3)
I-or Uefflng types reter to NI-I-/A 13, 13H or 13U
2.
Technical Data: Fl Res 49 Pendent and Recessed Pendent (SIN R3516)
I Thread FNominal Orifice Max. Sprinkler Max. I Actual I Sprinkler 1
Size Inch (mm) Pressure Temp. Rating Ambient Temp. K Length cc I OF °C I psi (bar) Factor I Inch (mm)
½"NPT
(R½)
I
/16" (11) 175 (12) I 155
I 175
68
79 J 100
150 I
I 38
66
I
I 4.9(70.6) 2.25 (57)
Ordinary Temp. Rating Intermediate Temp. Rating
Max. Coverage area Max. Spacing (1550Fi8°C) (175°F/790C) Top of Deflector Minimum
Ft x Ft (m x m) Ft (m) to Ceiling Spacing Flow Pressure Flow Pressure
GPM (L/min) PSI (barL GPM (L/min) PSI (bar) Inch (mm) Ft (m)
12 x 12 (3,6 x 3,6) 12(3,6) 13 (49) 7.0 (0,48) 13(49) 7.0(0,48) Smooth Ceilings 11/4 to 4(31.7 to
102) using F2 escutcheon.
14 x 14 (4,3 x 4,3) 14(4,3) 13(49) 7.0 (0,48) 13(49) 7.0(0,48) 1 to 4(25.4 to 102) using Fl
escutcheon.
16 x 16(4,9 x 4,9) 16(4,9) 13(49) 7.0 (0,48) 13(49) 7.0(0,48) Beamed Ceilings per NFPA
13D, 13R or 13 installed in 8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 17 (64,3) 12(0,83) 17(64,3) 12 (0,83) beams 11/4 to 13A (31.7 to
14.4) using F2 escutcheon, 1
20 x 20(6,1 x 6,1) 20(6,1) 20(75,7) 16.7 (1,14) 20(75,7) 16,7(1,14) to 1/4 (25.4 t044.4) using Fl
_____ escutcheon
For Ceiling types refer to NFPA 13, 13R or 130
Ordinary Temp. Rating Intermediate Temp. Rating
Max. Coverage area Max. Spacing (l55°F,8°C) (175°F'790C) Top of Deflector Minimum
FtxFt(mxm) . Ft(m) to Ceiling Spacing Flow Pressure Flow Pressure
GPM (11mm) PSI (bar) GPM (Llhiin) PSI (bar)
Inch (mm) Ft (m)
12 x 12(3,6 x 3,6) 12(3,6) 15(57) 9.4 (0,65) 15(57) 9.4 (0,65) Smooth Ceilings 4 to 8(100 to
203) using F2 escutcheon. 14 X 14 (4,3 x 4,3) 14(4,3) 16(60.5) 10.6(0,73) 16(60,5) 10.6 (0,73) 4 to 8(100 to 203) using Fl
escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 17(64,3) 12.0 (0,83) 17(64,3) 1 12.0(0,83) Beamed Ceilings per NFPA 13D,
13R or 13 installed in beams
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 19(72) 15.0(1,0) 19(72) 15.0(1,0) 41/4 to 8(108 to 203) using F2
escutcheon, 4 to 8(100 to 203) 20 x 20(6,1 x 6,1) 20(6,1) 22(83,2) 20.2 (1,4) 22(83,2) 20.2 (1,4) using Fl escutcheon
Technical Data: F1 Res 58 Pendent and Recessed Pendent (SIN R3513)
Thread I Nominal Orifice I Max.p I Sprinkler S I Max. I I Actual Sprinkler
Size Inch (mm) Pressure pTemp. Rating i Ambient Temp. K Factor Length
OF °C OF I psi (bar) Inch (mm)
½" NPT
(R'/2) I ½" (13) 1 175 (12)
j
155
175
68
79 I 100
I 150
38
66 5.8 (83.5) I
2.25 (57)
Ordinary Temp. Rating Intermediate Temp. Rating
Max. Coverage area Max. Spacing (155°Fit8) (175°F179°C) Top of Deflector Minimum
Ft Ft (m x m) Ft(rn) to Ceiling Spacing Flow Pressure Flow Pressure
GPM (Llmin) PSI (bar) GPM (Llmin) PSI (bar) Inch (mm) Ft(m)
12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6 (0,53) 16(61) 7.6 (0,53) Smooth Ceilings 1114 to 4(31.7 to
102) using F2 escutcheon. 14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6 (0,53) 16(61) 7.6 (0,53) 1 t 4(25.4 to 102) using Fl
escutcheon. 16 x 16(4,9 x 4,9) 16(4,9) 16 (61) 7.6 (0,53) 16(61) 7.6 (0,53) Beamed Ceilings per NFPA 130,
I3A or 13 installed in beams
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8 (0,75) 19(72) 10.8 (0,75) 11/4 to 1/4 (31.7 to 44.4) using
F2 escutcheon, 1 t 13/4 (25.4 to 20 x 20 (6,1 x 6,1) 20(6.1) 22( 83,3) 14.4(1,0) 22 (83,3) 14.4 (1,0) 44.4) using Fl escutcheon
For Ceiling types refer to NFPA 13, 13R or 13D
3.
Technical Data: Fl Res 76 Pendent and Recessed Pendent (SIN R7618)
Thread Nominal Orifice Max. I Sprinkler I Max. K Sprinkler
Size Inch (mm) I Pressure Temp. Rating Ambient Temp. Factor Length
I °C I OF I °C psi (bar) I Inch (mm)
NPT "/32" (13.5) 175(12) I 155 68 100 I 38
I 7.6(109) J 2.25 (57) 175 I I 150 66
Ordinary Temp. Rating Intermediate Temp. Rating Minimum Max. Coverage area Max. Spacing (1 55°F/8°C) (11750 90C) Top of Deflector to Ceiling
Flow Pressure Flow GPM Pressure Ft x Ft (mx m) Ft (m) Inch (mm) Spacing
Ft GPM (Llmin) PSI (bar) (L/min) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 21(79,5) 7.6 (0,53) 21(79,5) 7.6 (0,53) Smooth Ceilings 41/4 to 8(108
to 203) using F2 escutcheon.
14 X 14 (4,3 X 4,3) 14(4,3) 21(79,5) 7.6 (0,53) 21(79,5) 7.6 (0,53) 4 to 8(100 to 203) using Fl
escutcheon.
16 x 16(4,9 x 4,9) 16(4,9) 21(79,5) 7.6 (0,53) 21(79,5) 7.6 (053) Beamed Ceilings per NFPA
130, 13R or 13 installed in
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 21(79,5) 7,6 (0,53) 21(79,5) 7.6 (0,53) beams 414 to 8(108 to 203) us-
ing F2 escutcheon, 4 to 8(100
20 x 20(6,1 x 6,1) j 20(6,1) 23(87,1) 9.2 (0,63) 23(87,1) 1 9.2 (0,63) to 203) using Fl escutcheon
For Ceiling types refer to NFPA 13, 13R or 130
Model Fl Res 30, 49, 58 & 76 CCP Pendent*
* Not listed for corrosion resistance.
CEILING
CUP
1".112" REDUCER
CUP
MAX. FACE OF FITTINGJ TO FACE OF CEILING
DIMENSION
COVER ADJUSTMENT HEIGHT
3 5/16 0/A.
135FG04E [84. 1mm]
Fl RES 30, 49. 58 & 76 CCP PEND.
Fig. 3
Note: The Fl Res 76 will use a 1" x 3/4" reducer.
CCP Cover Plate Data:
"A"
Cover Adjustment
"B"
CCP Height
"C"
Deflector Distance below bottom
Inch (mm) Inch (mm) of beam
Inch (mm)
1/2(12.7) '/16 (24) 112 (13) - 1(25.4)
/16 (7.9) 3/4 (19) 1 1/2 (13) - 1 (25.4)
' Model Fl Res 30, 49, 58 & 76
FP push-on/thread-off escutcheon
2 5/8" 0/A. [66.7mm]
-HOLE IN CEILING -
2 5/16" 0/A.
- [58.7mm] -
CUP
- i' X 1/2' REDUCER
CEILING
I
1/2" [38 1mm] MAX
01, FACE OF FITTING
TO
/
FACE OF CEILING
"a"
El RES 49 PENDENT/FP
Fig. 4
FP Escutcheon Data:
"B"
"A" Deflector Distance below bottom FP Position Inch (mm) of beam
Inch (mm)
Max. Recessed /6(11) Y2(12.7)
Mm. Recessed '5/16(24) 1 1 (25.4)
Note: Sprinklers shown in Fig. 3 and Fig. 4 are not suitable for installation in ceilings which have positive pressure in
the space above.
4
Technical Data: Fl Res 30 CCP Pendent and Recessed Pendent/FP (SIN R351 1)
Nominal Max. CCP Assembly Max. K Sprinkler I Orifice j Pressure
I Temp. Rating i Ambient Temp. Factor Length
°F I °C °F I °C
LThread
Inch (mm) psi (bar) Inch (mm) I
I 21//' (82) 175(12) 135 57 100 38 3.0(43.2) 2.25(57)
Ordinary Temp. Rating
Max. Coverage area Max. Spacing (155°F/68°C) lop of Deflector to Ceiling Minimum
Ft x Ft (m x m) Ft (m) Inch (mm) Spacing Flow Pressure
GPM (lJmin) PSI (bar) Ft (m)
12 X 12 (3,6 X 3,6) 12(3,6) 8(30,3) 7.0 (0,48) Smooth Ceilings ½ to 1(13 to 25.4) using COP.
'/2 to 1(13 to 25.4) using FP escutcheon.
Beamed Ceilings per NFPA 13D, 13R or 13 installed in 8(2,4)
14 x 14(4,3 x 4,3) 14(4,3) 11(37,8) 13.4(0,92) beams 1/2 to 1(13 to 25.4) using COP.
½ to 1(13 to 25.4) using FP escutcheon.
For Ceilino Woes refer to NFPA 13. 13R or inn
Technical Data: F1 Res 49 CCP Pendent and Recessed Pendent/FP (SIN 3516)
Nominal CCP Max. I
Thread Orifice Max. Assembly Ambient K Sprinkler
Size Inch Pressure Temp. Temp . Fact or Length
(mm) psi (bar) Rating Inch (mm)
OF oC OF IOC
½' NPT
(R½)
/6" (11) 175 (12) 135 57 100 38 4.9 (70.6) 2.25 (57)
Max. Coverage Ordinary Temp. Rating Minimum Max. Spacing (155' 80C) lop of Deflector to Ceiling area
Ft x Ft (m x m) Ft (m) Inch (mm) Spacing
Ft (m) Flow Pressure
GPM (Llmin) PSI (bar)
12 x 12(3,6 x 3,6) 12(3.6) 13(49) 7.0 (0,48)
Smooth Ceilings ½ to 1(131025.4) using
14 x 14 (4,3 x 4,3) 14(4.3) 13(49) 7.0 (0,48) COP.
½ to 1(13 1025.4) using FP escutcheon.
16 x 16(4,9 x 4,9) 16(4,9) 14 (53) 8.2(0,56) Beamed Ceilings per NFPA 13D, 13R or 13
installed in beams ½ to 1(131025.4) using
8(2.4)
18 x 18(5,5 x 5,5) 18(5,5) 18(68,1) 13.5 (0,93) COP.
1/2 to 1(131025.4) using FP escutcheon.
20 x 20(6,1 x 6,1)
f
20(6,1) 20(75,7) 16.7 (1,14)
For Ceiling types refer to NFPA 13, 13R or 130
Technical Data: F1 Res 58 CCP Pendent and Recessed Pendent/FP (SIN R3513)
Thread Nominal Max. I I CCP Assembly I Max. I K Sprinkler
Size Orifice Pressure I Temp. Rating I Ambient Temp. Length I Inch (mm) I psi (bar) , I OF , I °C i
I OF , I °C I Factor I I Inch (mm)
(R½) I /2" (13) I 175 (12) I 135 I I 57 100 38 I 5.8 (83.5) 2.25 (57)
Max. Coverage Ordinary Temp. Rating Minimum Max. Spacing (155' 80C) Top of Deflector to Ceiling area
Ft x Ft (m x m) Ft (m) Inch (mm) Spacing Flow Pressure
GPM (L/min) PSI (barL Ft (m)
12 x 12(3,6 x 3,6) 12(3,6) 16(61) 7.6 (0,53)
Smooth Ceilings ½ to 1(131025.4) using OCR
112 to 1(13 to 25.4) using FR escutcheon.
14 x 14(4,3 x 4,3) 14(4,3) 16(61) 7.6 (0,53)
16 x 16(4,9 x 4,9) 16(4,9) 16(61) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to
1(13 to 25.4) using COP.
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 19(72) 10.8 (0,75) ½ to 1(13 to 25.4) using FP escutcheon.
20 x 20 (6,1 x 6, 1) 20(6,1) 22(83,3) 14.4(1,0)
For Ceiling types refer to NFPA 13, 13R or 130
5,
Escutcheon, F2, Data:
Face of Fitting
Type Adjustment to wall Inch (mm) I Inch (mm)
F2
______
1/2 (13) /16 -
(4.7-17.4)
Technical Data: F1 Res 76 CCP Pendent and Recessed Pendent/FP (SIN R7618)
Thread Nominal I I CCP Assembly I Max. Sprinkler
Size I Pr KOrifice Temp. Rating Ambient Temp. Length
(mm) p
A(12)
°F IInch °C I °F °C Inch Factor (mm)
3/4W NPI /32" (13.5) 1 135 57 I
100
150
38
66 7.6(109) 2.25 (57)
Max. Coverage Ordinary Temp. Rating Minimum
area Max. Spacing (155°F/68°C) lop of Deflector to Ceiling Spacing Flow Pressure Ft x Ft (m x m) Ft (m) Inch (mm) Ft (m) GPM (L/min) PSI (bar)
12 x 12 (3,6 x 3,6) 12(3,6) 21(795) 7.6 (0,53)
Smooth Ceilings 1/2 to 1(13 to 25.4) using OCR
1/2 to 1(13 to 25.4) using FP escutcheon.
14 x 14 (4,3 x 4,3) 14(4,3) 21 (79,5) 7.6 (0,53)
16 x 16(4,9 x 4,9) 16(4,9) 21 (79,5) 7.6 (0,53) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½
to 1(13 to 25.4) using COP.
8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 22(83,3) 8.4 (0,58) ½ to 1(13 to 25.4) using FP escutcheon.
20x 20(6,1 x 6,1) 20(6,1) 25(94,6) 1 10.8 (0,74)
-or Ceding types reter to NFPA 13, 13R or 13D
Model Fl Res 44 & 58 HSW
35/006-0
I
I 15/16" 0/A. 1,1 Ii
(49.2mm]
2 1/4' HOLE OIA.
[57.2mm)
I" X 1/2" REDUCER
TURN COLLAR UNTIL -
TIGHT AGAINST SPRINKLER
WRENCH SOSS.
F02_7~"~2
FACE OF FITTING To - WALL DIMENSION I
7-
Fl RES 58 & 44 HSW/F2
1/8
[3 2mmJ
I
H 1/2" [13mm]
ADJUSTMENT
1 1/4" MIN.
[31.8mm] I
4'.
CEILING TO
DEFLECTOR
IMENSION
2 27/32" 0/A.
[72.2mm]
Fig. 5
F2 escutcheon,
1/2" (13mm) adjustment
Model Fl Res 44 & 58 Recessed HSW/F2
Technical Data: F1 Res 44 HSW & HSW/F2 (SIN R3531)
Thread Nominal I Max. Sprinkler I
Max.
I Ambient K I Sprinkler
Size I Orifice I Pressure I Temp. Rating
I i I Temp. Factor I Length
Inch (mm) psi (bar) I Inch (mm) 1°F I 0FI0C
Y2' NPT
I (R½) /e" (10) 175 (12) I 155 100
1175 150166 E79
38 4.4(63) 2.45 (62)
on
m ,.....-,
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C)
Intermediate Temp. Rating
(175°F179°C) Top of Deflector to
Ceiling
Inch (mm) PSI (bar)
Minimum
Ft (m)
Flow
GPM (1/mm)
Pressure
PSI (bar)
Flow
GPM (1/mm)
Pressure
12 x 12 (3,6 x 3,6) 12(3.6) 12 (45,4) 7.5(0,52) 12(45,4) 7.5 (0,52)
4 to 6(100 to 152):
Y2(13) recessed
using F2 escutcheon
8(2,4)
14 x 14 (4,3 x 4,3) 14(4,3) 14(53,0) 10.2 (0,71) 14(53,0) 10.2 (0,71)
16 x 16(4,9 x 4,9) 16(4,9) 16(60,6) 13.3(0,92) 16(60,6) 13.3 (0,92)
16 X 18(4,9 x 5,5) 16(4,9) 18(68,1) 16.8 (1,16) 18(68,1) 16.8(1,16)
18 x 18(5,5 x 5,5) 18(5,5) 19(72,0) 18.7 (1,29) 19(72,0) 18.7(l.29)
16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89) 23(87,1) 27.4(1,89)
12 x 12 (3,6 x 3,6) 12(3,6) 14 (53,0) 10.2(0,71) 14(53,0) 10.2 (0,71)
6t0 12 (152 to 305):
1/2 (13)recessed
using F2 escutcheon
14 x 14 (4,3 x 4,3) 14(4,3) 16(60,6) 13.3 (0,92) , 16(60,6) 13.3 (0,92)
16 x 16(4,9 x 4,9) 16(4.9) 17(64,4) 15.0(1,04) 17 (64,4) 15.0(1,04)
16 x 18(4,9 x 5,5) 16(4,9) 20(75,7) 20.7(1,43) 20(75,7) 20.7(1,43)
16 x 20(4,9 x 6,1) 16(4,9) 23(87,1) 27,4 (1,89) 23(87,1) 27.4 (1,89)
For Ceiling types refer to NFPA 13, 13R or 130
Technical Data: Fl Res 58 HSW & HSW/F(SIN R3533)
Escutcheon, F2, Data:
Nominal Max. Sprinkler Max. Sprinkler Face of Fitting Adjustment Thread Orifice to wall Pressure Temp. Rating Ambient K Length Type Inch (mm) Size Inch psi (bar) Temp. Factor Inch Inch (mm) (mm) OF I °C OF I °C (mm) ______
/16 - 11/16 /2' NPT 155 68 100 38 F2 V2(13) 1/2"(13) 175 (12) 5.8 (83.5) 2:45 (62) (4.7 17.4) (R/2) 175 79 150 66
Ordinary Temp. Rating Intermediate Temp. Rating Top of Deflector to Minimum Max. Coverage area Max. Spacing (1550F/68°C) (175°F179°C) Ceiling Spacing Flow Pressure Flow Pressure Ft x Ft (m x m) Ft (m)
Inch (mm) Ft (m) GPM (Llmin) PSI (bar GPM (L/min) PSI (bar)
12 x 12 (3,6 x 3,6) 12(3.6) 16(60,6) 7.6(0,53) 16 (60,6) 7.6(0,53)
4 to 6(100 to 152):
14 x 14(4,3 x 4,3) 14(4.3) 18(68,2) 9.7(0,69) 18 (68,2) 9.7(0,69)
16 x 16(4,9 x 4,9) 16(4,9) 21(79,5) 13.2(0,91) 21(79,5) 13.2 (0,91) ½ (13) recessed
using F2 escutcheon 16 x 18(4,9 x 5,5) 16(4,9) 25(94,7) 18.6(1,28) 25(94,7) 18.6(l.28)
8(2,4) 16 x 20(4,9 x 6,1) 16(4,9) 29(109,8) 25.0 (1,73) 29(109,8) 25.0(1,73)
12 x 12(3,6 x 3,6) 12(3,6) 22(83,3) 14.4(1,0) 22(83,3) 14.4(1,0)
6 to 12 (152 to 305):
1/2 (13)recessed
14 x 14(4,3 x 4,3) 14(4,3) 22(83,3) 14.4 (1,0) 22(83,3) 14.4(1,0)
16 x 16(4,9 x 4,9) ' 16(4,9) 26(98,4) 20.1 (1,39) 26(98,4) 20.1 (1,39) using F2 escutcheon
16 x 18(4,9 x 5,5) 16(4,9) 31(117,4) 1 28.6 (1,97) 1 31(117,4) 1 28.6 (1,97)
:or Ceiling types refer to NFPA 13, 13R or 13D
7.
Model Fl Res 44 SWC*
* Not listed for corrosion resistance. --7
4' 4" to 12'
(l01.60rno To
1/4" (3I.75rn,,,J M04,rn,m - 304.
P* Of Fltt,ng
To Wo6 OH,ons,on PUSH ON COVER. 114tH I TURN TO ADJUST UNTIL
R 1 flGHI AGAINST WALL.
IX I/2 Rod0000 -
Roo,noodod I
We//HOI
2 5/8
2 5/I6
[66.68mm) Ojo.
-
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER
WRENCH ROSS.
trr .s 5/I6 I (84.4mm]
0,0.
I -
/2" (12.70mm) A8jo0tm.flt
Ft RES 44 swc
Fig. 6
Tprhnir"il floits 1:1 Poe 1101 cwc IQIKI
Nominal Max. Cover Max. I i Sprinkler Thread Orifice I I Pressure Temp. Ambient K Length Size
Inch (mm)
I I psi (bar) Rating Temp. Factor Inch (mm) °F I 0C OF
'/"NPT
I (R½) 3/8" (10) 175 (12) 135 57 100L38 4.4 (63) 2.45 (62)
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/68°C) Top of Deflector to
Ceiling
Inch (mm) PSI (bar)
Minimum
Spacing
Ft (m) Flow
GPM (1/mm)
Pressure
12 x 12(3,6 x 3,6) 12(3,6) 13 (49,2) 8.7(0,60)
4 to 6(100 to 152):
1/2 (13)recessed
using F2 escutcheon
8(2,4)
14 x 14(4,3 x 4,3) 14(4.3) 14(53,0) 10.2(0,71)
16 x 16(4,9 x 49) 16(4,9) 17(64,3) 15.0(1,1)
16 x 18 (4,9 x 5,5) 16(4,9) 19(71,8) 18.7(1,13)
16 x 20 (4,9 x 6,1) 16(4,9) 23(87,1) 27.4(1,89)
12 x 12(3,6 x 3,6) 12(3,6) 14(52,9) 10.2 (0,71)
6 to 12 (152 to 305);
72 (13) recessed
using F2 escutcheon
14 x 14(4,3 x 4,3) 14(4,3) 15(56,7) 11.7(0,81)
16 x 16(4,9 x 4,9) 16(4,9) 18(68,1) 16.8(1,16)
16 x 18(4,9 x 5,5) 16(4,9) 20(75,6) 20.7(1,43)
For Ceiling types refer to NFPA 13, 13R or 13D
Mr'idgI WccR I.IQWV (I inirl
Technical Data: F1 Res 58 HSWX (SIN RA3533)
Thread Nominal Max. Sprinkler I
I Max.
Ambient K Sprinkler Sprinkler
Size
Orifice Pressure Temp. Rating
________________________ Temp. Factor Length Identification
Inch (mm) psi (bar) Inch (mm) I °F
Number (SIN) I °C
Bulb Y2"NPT 1/2 (13) 175 (12) 155
175 79
68
I
100
150 66
38 5.8 (83.5) 2.45 (62) RA3533
Max. Coverage area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(155°F/680C)
Intermediate Temp. Rating
(1750F/79°C) Top of Deflector to
Ceiling
Inch (mm)
Spacing
I Minimum
Ft( m) Flow
GPM (L/min)
Pressure
PSI (bar)
Flow
GPM (11mm)
Pressure
PSI (bar)
18x20(5,5x 6,1) 18(5,5) 30(114) 26.8(1,85) 30(114) 26,8(1,85)
4t06(100to 152);
½ (13) recessed
using F2 escutcheon
8(2.4)
20 x 20 (6,1 x 6, 1) 20(6,1) 30(114) 26.8(1,85) 30(114) 26.8(1,85)
16 x 22(4,9 x 6,7) 16(4.9) 33(125) 32.4 (2,23) 33(125) 32.4 (2,23)
16 x 24 (4,9 x 7,3) 16(4,9) 38(144) 42.9 (2,96) 38(144) 42.9 (2,96)
14 x 26(4,3 x 7,9) 14(4,3) 42(160) 52.4 (3,75) 42(160) 52.4 (3,75)
18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4 (2,5) 35(133) 36.4 (2,5)
6 to 12 (152 to 305);
112 (13) recessed
using F2 escutcheon
16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9 (2,96) 38(144) 42.9 (2,96)
16 x 24(4,9 x 7,3) 16(4,9) 42(160) 52.4 (3,6) 42(160) 52.4 (3,6)
14 x 26(4,3 x 7,9) 14(4,3) 46(174) 62.9 (4,34) 46(174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Mnrfr.I Fl R I4WY (Ri,Ih
FACE OF F/ri/NC To
WALL DIMENSION
2 1/4" HOLE 0/A.
[57.2mm]
I" X 1/2" REDUCER
TURN COLLAR UNTIL -
TIGHT AGAINST SPRINKLER
WRENCH ROSS.
JSFGO8
L2m
I 11/16" U/N.
(31 8mm] '
CElL/NC TO
DEFLECTOR
OwENSION
2 27/32" 0/A.
[72.2mm]
1/2" [/3mm]
ADJUSTMENT
Fl RES 58 HSWX
Fig. 7
I
Technical Data: KRes58 HSWX (RA3593)
Thread Nominal Max. Max.
Ambient K Sprinkler Sprinkler
Size Orifice Pressure Temp. Factor
Length Identification
Inch (mm) psi (bar) Inch (mm) Number (SIN) OF I0C
Link ½" NPT /2" (13) 175(12) 100 (R 112)
38 5,8 (83.5) 2.45 (62) RA3593
Ordinary Temp. Rating
Max. Coverage area Max. Spacing (165- VC) Top of Deflector to Minimum
Ft x Ft (m x m) Ft (m) Ceiling Spacing Flow Pressure
GPM (1/mm) PSI (bar)
Inch (mm) Ft (m)
18 x 20 (5,5 x 6, 1) 18(5,5) 29(109) 25(1,72)
4 to 6(100 to 152):
20 x 20(6,1 x 6,1) 20(6,1) 30(114) 26.8(l.85)
16 x 22 (4,9 x 7,3) 16(4,9) 33(125) 32.4 (2,23) ½ (13) recessed
using F2 escutcheon
16 x 24 (4,9 x 7,3) 16(4.9) 38(144) 42.9(2,96)
8(2,4) 14 x 26 (4,3 x 7,9) 14(4,3) 42(160) 52.4(3,75)
18 x 20(5,5 x 6,1) 18(5,5) 35(133) 36.4 (2,5)
6 to 12 (152 to 305);
½ (13) Recessed
16 x 22(4,9 x 6,7) 16(4,9) 38(144) 42.9 (2,96)
16 x 24 (4,9 x 7,3) 16(4,9) 42(160) 52.4 (3,6) using F2 escutcheon
14 x 26(4,3 x 7,9) 14(4.3) 46(174) 62.9 (4,34)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model Fl Res 30, 49, Fl Res 58, Fl Res 76 and Fl Res
44 Sprinklers should be inspected and the sprinkler sys-
tem maintained in accordance with NFPA 25, 13, 13D,
and 13R. Do not clean sprinkler with soap and water, Am-
monia or any other cleaning fluids. Remove dust by using
a soft brush or gentle vacuuming. Remove any sprinkler
which has been painted (other than factory applied) or
damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should
remain in the original cartons and packaging until used.
This will minimize the potential for damage to sprinklers
that could cause improper operation or non-operation.
Model Fl Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-F)] low flow residential pendent sprin-
klers engineered to provide a minimum design density of
0.05 gpm/ft2 over the listed coverage area. Listed flows
as specified by the manufacturer's technical data sheets
are to be used. Residential sprinklers shall be installed
in conformance with the manufacturer's installation guide-
lines and the applicable installation standard. Deflector-
to-ceiling distance listing shall be 1" to 8" maximum, only
for FiRes 49. Sprinkler frame and deflector shall be of
bronze frame construction having a ½" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)]
[175°F (79°C)]. Sprinklers shall have a nominal K-factor
of 3.0, 4.9 and 5.8. Standard finish: [Bronze] [Chrome-
plated] [White Polyester] [Special finish- specify]. Resi-
dential pendent sprinklers shall be Reliable Model Fl Res
30,49 & 58, SIN R351 1, R3516 & R3513 (Bulletin 135).
Model Fl Res 49 & 58 Recessed Pendent/171,
Model Fl Res 30, 49 & 58 Recessed Pendent/
F2, Model Fl Res 30,49 & 58 Recessed Pendent(
FP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed pen-
dent sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's in-
stallation guidelines and the applicable installation stan-
dard. Deflector-to-ceiling distance listing shall be 1" to 8"
maximum, only for F1 Res 49. Sprinkler frame and deflec-
tor shall be of bronze frame construction having a ½" NPT
thread. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer with top-loaded extruded
"DuPont Registered Trademark
10.
or cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (790C)]. Sprinklers shall have a nomi-
nal K-factor of 3.0, 4.9 & 5.8. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish— spec-
ify]. Recessed escutcheon assembly shall be a steel,
two-piece escutcheon [with 1/2" adjustment (Model F2)]
[with 3/4" adjustment (Model Fl)] [of push-on and thread
off design with ½' adjustment (Model FP)]. Standard fin-
ish shall be [brass][bright chrome] [white painted]. Resi-
dential recessed pendent sprinklers shall be Reliable
[Model Fl Res 30, 49 & 58 Recessed Pendent/Fi] [Model
El Res 30, 49 & 58 Recessed Pendent/F2] [Model Fl Res
30,49 & 58 Recessed Pendent/FP] SIN R3511, R3516 &
R3513 (Bulletin 135).
Model Fl Res 30, 49 & 58 CCP Pendent
(Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-F)] low flow residential concealed
sprinklers engineered to provide a minimum design den-
sity of 0.05 gpm/ft2 over the listed coverage area. Listed
flows as specified by the manufacturer's technical data
sheets are to be used. Residential sprinklers shall be in-
stalled in conformance with the manufacturer's installa-
tion guidelines and the applicable installation standard.
Sprinkler frame and deflector shall be of bronze frame
construction having a ½' NPT thread. Water seal as-
sembly shall consist of a Teflon* coated Belleville spring
washer with top-loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of 155°F (68°C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a ½" cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color— specify]. ]. Concealed pendent sprinklers shall
be Reliable Model Fl Res 30,49 & 58 CCP, SIN R3511,
R3516 & R3513 (Bulletin 135).
Model Fl Res 44, Fl Res 58 Horizontal
Sidewall, Fl Res 58 HSWX & KRes58 HSWX
Residential Sprinkler Specifications
Sprinklers shall be [cULus Listed] low flow residential
horizontal sidewall sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a ½" NPT thread.
Water seal assembly shall consist of a Teflon" coated Bel-
leville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)]
[175°F (79°C)]. The solder element (Link) version, the
water seal consist of a cap with a bellville spring washer
and a temperature rating of 165°F (74°C). The recessed
assembly forthe HSWX (Bulb & Link) should be a steel
two pieces escutcheon with 1/2" adjustment (Model F2)
standard finish should be Bright Chrome and white paint-
ed. The Fl Res 58 HSW is also available with low lead
frame. Fl Res 58 HSW and HSWX sprinklers shall have a
nominal K Factor of 5.8 and Fl Res 44 a nominal K factor
of 4.4. Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish— specify]. Residential horizontal
sidewall sprinklers shall be Reliable Model El Res 44, Fl
Res 58, Fl Res 58 HSWX & Model KRes58 HSWX, SIN
R3531, RA3533 & RA3593 (Bulletin 135).
Model Fl Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 44 horizontal side-
wall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½" adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish— specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 44/F2, SIN R3531 (Bulletin 135).
Model Fl Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 34" NPT thread. Wa-
ter seal assembly shall consist of a Teflon" coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
a temperature rating of [155°F (680C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish— specify]. Residential pendent sprinklers shall
be Reliable Model Fl Res 76, SIN R7618 (Bulletin 135).
p
*DuPont Registered Trademark
,., .-.
Model Fl Res 76 Recessed Pendent/Fl,
Model Fl Res 76 Recessed Pendent/F2,
Model Fl Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineered to provide a
minimum design density of 0.05 gpm/ft2 over the listed
coverage area. Listed flows as specified by the manu-
facturer's technical data sheets are to be used. Residen-
tial sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall
be of bronze frame construction having a 3/4" NFl thread.
Water seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and hav-
ing a temperature rating of [155°F (680C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 7.6. Standard
finish: [Bronze] [Chrome-plated] [White Polyester] [Spe-
cial finish- specify]. Recessed escutcheon assembly
shall be a steel, two-piece escutcheon [with ½" adjust-
ment (Model F2)] [with 3/4" adjustment (Model Fl)] [of
push-on and thread off design with ½" adjustment (Mod-
el FP)]. Standard finish shall be [brass][bright chrome]
[white painted]. Residential recessed pendent sprinklers
shall be Reliable [Model Fl Res 76 Recessed Pendent/
Fl] [Model Fl Res 76 Recessed Pendent/F2] [Model Fl
Res 76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model Fl Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/1t2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprin-
klers shall be installed in conformance with the manufac-
turer's installation guidelines and the applicable installa-
tion standard. Sprinkler frame and deflector shall be of
bronze frame construction having a 3/4" NPT thread. Wa-
ter seal assembly shall consist of a Teflon* coated Bel-
leville spring washer with machined or cold head cup with
3 mm glass bulb containing no plastic parts, and having
-;.- ....
a temperature rating of 155°F (680C). Cover plate assem-
bly shall consist of a brass cover plate and copper alloy
retainer flange. Method of attaching the cover plate to the
sprinkler cup shall be a push-on and thread-off design
allowing a ½" cover plate adjustment. Cover plate tem-
perature rating shall be 135°F (57°C). A plastic protec-
tive cap shall be provided and factory installed inside the
sprinkler cup to protect the sprinkler from damage, which
could occur during construction before the cover plate
is installed. Standard cover plate finish: [White] [Custom
Color- specify]. ]. Concealed pendent sprinklers shall be
Reliable Model Fl Res 76 CCP, SIN R7618 (Bulletin 135).
Finishes (1)
Standard Finishes
Sprinkler F1 F2 FP Cover Plates Escutcheons
Bronze Brass White Painted
Chrome Plated Bright chrome Plated chrome
White and Black White Painted
Polyester(l) coated
Special Application Finishes
Sprinkler Fl, F2, FP
Escutcheons
Electroless Nickel PTFE(Teflon 2' Electroless Nickel PTFE (Tellon®)
Bright Brass Bright Brass
Black Plated Black Plated
Black Paint Black Paint
Off White Off White
Chrome Dull chrome Dull
Other finishes and colors are available on special order.
Consult factory for details.
cULus listed corrosion Resistant
Note: Paint or any other coating applied over the factory finish will void
all approvals and warranties.
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish
Cover Plate Finish
*DuPont Registered Trademark
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and properly for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United Slates, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
(800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data. Reliable (914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 06/15 P/N 9999970235
ZURN Model. 950XL
JLKINS Double Check Valve Assem
AS 160115
2535 GLASGOW DR
Application
Designed for installation on water lines to protect against
both backsiphonage and backpressure of polluted water into
the potable water supply. Assembly shall provide protection
where a potential health hazard does not exist.
Standards Compliance
(All sizes approved horizontal. Vertical approvals as listed
below.)
ASSE® Listed 1015 (vertical 3/4", 1 1/4", 1 1/2" & 2")
IAPMO® Listed (vertical 1 1/4-2")
CSA® Listed (vertical 3/4", 1 1/4", 1 1/2" & 2")
AWWA Compliant C510 (vertical 3/4")
UL® Classified (less shut-off valves only)
o C-UL® Classified (less shut-off valves only)
Approved by the Foundation for Cross Connection Control
and Hydraulic Research at the University of Southern Cali-
fornia (vertical 3/4")
City of Los Angeles Approved (vertical 1-1/4-2)
NYC MEA 426-89-M VOL 3
Materials
Main valve body Cast Bronze ASTM B 584
Access covers Cast Bronze ASTM B 584
Internals Stainless Steel, 300 Series
Elastomers Silicone (FDA approved)
Buna Nitrile (FDA approved)
Polymers NoryITM, NSF Listed
Springs Stainless steel, 300 series
Options
(Suffixes can be combined)
- with full port QT ball valves (standard)
Li L - less ball valves
F1 U - with union ball valves
S - with bronze "Y" type strainer
fl TCU - with test cocks "vertical up E] V - with union swivel elbows (3/4" & 1")
Li OSY - with OS & V gate valves
fl FDC - with fire hydrant connection (2" only)
fl FT - with integral male 45° flare SAE test fitting
PF - with Z-BiteTM push fit connections* (1/2-1 "only)
I PR - with ZPressTM press fit connections"
*Fittings ship in box with valve and must be threaded into
valve by hand on site.
Accessories
Repair kit (rubber only)
Features El Thermal expansion tank (Model XT)
Sizes: 3/4", 1", 1 1/2", 2 F1 QT-SET Quick Test Fitting Set
Maximum working water pressure 175 PSI
Maximum working water temperature 180°F
Hydrostatic test pressure 350 PSI
End connections Threaded ANSI 131 .20.1
tC E 13-
DH__
G -
Dimensions & Weights (do not include pkg.)
DIM ENSIONS_(aoproximate) WEIGHT
MODEL A UNION B LESS BALL LESS WITH
SIZE A BALL VALVES C D E F G BALL BALL
VALVES VALVES VALVES
in. mm in. 'mm in. I mm in. imm in. imm in. Imm in. mm in. Imm in. mm Us jg
3/4 20 111/4 286 121/2 1318 7 178 11/2 38 1/2 89 3 76 15 381 5 2.3 7 3.2
1 25 121/4 311 137/8 353 7 178 11/2 38 31/2 89 3 76 173/4 451 8 3.6 12 5A
11/4° 32 151/2 419 18 1/2 470 109/16 268 2 51
3J94
31/1/2 114 41/2 114 211/2 546 16 7.3 22 10
11/2 40 171/8 435 191/8 486 109/16 268 2 51 31/0
2 50 181/4 4601 20 5081 109/16 2681 2 51 31//2 114 41/2 114 25 1/8 638
*Size 1-1/4" Discontinued
Zurn Industries, LLC I Wilkins Rev. 0
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 Date: 4/15
In Canada Zurn Industries Limited Document No. BF-950XL
3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292 Product No. Model 950XL
.1-._X-,n I Page 1 of 2
Flow Characteristics 0 Raid Flow (esablishcd by approval agcncic0
MODEL 950XL 3/4", 1", 11/4", 11/2" & 2" (STANDARD & METRIC)
FLOW RATES (us)
1.26 2.52 3.8 5.0
—
25mrn
0 10
cc 5—__
U) ________ U) ________
cc W _________
0 0 120 40 60 80
3.2 6.3 9.5 12.6 15.8 15 :11/4" (32mm)1 1/2'_(40mm)4 103 .
50mm) 0 —J
LU
5 35 Q
Ci) LU 0
0 50 100 150 200 250 °
FLOW RATES (GPM)
Typical Installation
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturer's instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a mini-
mum of 12" (305mm) and a maximum of 30" (762mf1) above
adequate drains with sufficient side clearance for testing and
maintenance. The installation shall be made so that no part of
the unit can be submerged.
Capacity 4hruSchedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
1/8" 1 1 2 3 -
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2 5 7 9 14
3/4" 8 12 17 25
13 20 27 40 -
11/4" 23 35 47 70
1 1/2" 1 32 48 1 63 95
1 52 1 78 1 105 1 167
OUTDOOR INSTALLATION
DIRECTION OF FLOW
INDOOR INSTALLATION
Specifications
The Double Check Valve Backflow Preventer shall beASSE® Listed 1015 approved, and supplied with full port ball valves.
The main body and access covers shall be bronze (ASTM B 584), the seat rings and all internal polymers shall be NSF® Listed
NorylTM and the seat disc elastomers shall be silicone. The first and second checks shall be accessible for maintenance with-
out removing the device from the line. The Double Check Valve Backflow Preventer shall be a ZURN WILKINS Model 950XL.
Zurn industries, LLC 1 Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada I Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292
Page 2 of 2
Model LP-5/8 5/8" x 3/4" Model 25-5/8, 5/8'x 3/4" Model 35-3/4"
Model 55-1 Model 70—i"
2535 GLASGOW DR
Recordall® Disc.... -
Badger Meter Lead-Free Bronze Alloy, Sizes 5/8 5/8" x 3/4", 3/41i & 1!!
NSF/ANSI Standards 61 and 372 Certified
DESCRIPTION
The Recordall Disc Series meters meet or exceed the most recent revision
of AWWA Standard C700 and are available in a lead-free bronze alloy. The
meters comply with the lead-free provisions of the Safe Drinking Water Act,
are certified to NSF/ANSI Standards 61 and 372 (Trade Designations: MLP-LL
M25-LL, M35-LL, M55-LL, M70-LL) and carry the NSF-61 mark on the housing
All components of the lead-free bronze alloy meter (housing, measuring
element, seals, and so on) comprise the certified system.
Applications: For use in measurement of potable cold water in residential,
commercial and industrial services where flow is in one direction only.
Operation: Water flows through the meter's strainer and into the measuring
chamber where it causes the disc to nutate. The disc, which moves freely,
nutates on its own ball, guided by a thrust roller. A drive magnet transmits
the motion of the disc to a follower magnet located within the permanently
sealed register. The follower magnet is connected to the register gear train.
The gear train reduces the disc nutations into volume totalization units
displayed on the register or encoder face.
Operating Performance: The Recordall Disc Series meters meet or exceed
registration accuracy for the low flow rates (95%), normal operating flow
rates 000 ± 1.5%), and maximum continuous operation flow rates as
specifically stated in AWWA Standard C700.
Construction: Recordall Disc meter construction, which complies with
ANSI/AWWA standard C700, consists of three basic components: meter
housing, measuring chamber and permanently sealed register or encoder
The meter is available in a lead-free bronze alloy with externally-threaded
spuds. A corrosion-resistant engineered polymer material is used for the
measuring chamber.
Magnetic Drive: Direct magnetic drive, through the use of high-strength
magnets, provides positive, reliable and dependable register coupling for
straight-reading or AMR/AM[ meter reading options.
Tamper-Proof Features: Unauthorized removal of the register or encoder
is inhibited by the option of a tamper detection seal wire screw, TORX
tamper-resistant seal screw or the proprietary tamper-resistant keyed seal
screw. Each can be installed at the meter site or at the factory.
Maintenance: Badger Meter Recordall Disc Series meters are designed and
manufactured to provide long-term service with minimal maintenance.
When maintenance is required, it can be performed easily either at the meter
installation or at any other convenient location.
To simplify maintenance, the register, measuring chamber, and strainer can
be replaced without removing the meter housing from the installation. No
change gears are required for accuracy calibration. Interchangeability of
parts among like-sized meters and meter models alo minimizes spare parts
inventory investment, The built-in strainer has an effective straining area of
twice the inlet size.
Connections: Tailpieces/Unions for installations of meters on various pipe
types and sizes, including misaligned pipes, are available as an option.
Meter Spud and Connection Sizes
Model
I Size < Designation Length
,, ,, B
B Dia. ore
Coupling
Nut and
Spud Thread
Tailpiece
Pipe
Thread
LP 5/8" x 7-1/2" 5/8" 3/4(5/8') 1/2"
5/8"x3/4" x 7-1/2" 5/8'3/4" 1(3/4') 3/4"
25 5/8" x 7-1/2" 5/8" 3/4 (5/8") 1/2"
5/8"x3/4" x 7-1/2" 5/8'3/4" 1(3/4") 3/4"
3/4" x 7-1/2" 3/4" 1(3/4") 3/4"
35 3/4" x 9" 3/4" 1' (3/4") 3/4"
3/4"x 1" x 9" 3/4" 1-1/4(1") 1"
55 V. x 10-3/4" 1" 1-1/4(1") 1"
70 1 x 10-3/4" 1"
RDM-DS-00464-EN-03 AWWA (October 2015) Product Data Sh eet
Recordall® Disc Meters, Lead-Free Bronze Alloy, Sizes 5/8','5/8"x314'1'314"& 1"
SPECIFICATIONS
Model LP Model 25 Model 35 Model 55 Model 70
(5/8" & 5/8' x 3/4°) (5/8' & 5/8' x 3/4") (3/4') (111) (1)
Typical Operating 0.5 ... 20gpm 0.5 ... 25gpm 0.75 ... 35gpm 1 ... 55gpm 1.25 ... 70gpm Range (0.11.4.5 m3/hr) (0.11.5.7 m3/hr) (0.17.7.9 m3/hr) (0.23 ... 1 2.5 m3/hr) (0.28 ... 16 m3/hr) (100%±1.5%)
0.25 gpm 0.25 gpm 0.375 gpm 0.5 gpm 0.75 gpm
Low Flow (0.057 m3/hr) (0.057 m3/hr) (0.085 m'/hr) (0.11 m3/hr) (0.17 m3/hr)
Mm. 95% Mm. 98.5% Mm. 97% Mm. 95% Mm. 95%
Maximum logpm 15 gpm 25 gpm 40 gpm 50 gpm Continuous (2.3 m3/hr) (3.4 m3/hr) (5.7 m3/hr) (9.1 m3/hr) (11.3 m'/hr) Operation
5/8" size: 5/8' size:
Pressure Loss 2 psi @ 10 gpm 3.5 psi @ 15 gpm
at Maximum (0.14 bar @2.3 m3/hr) (0.24 bar @3.4 m3/hr) 5 psi @25 gpm 3.4 psi @40 gpm 6.5 psi @50 gpm
Continuous 5/8" x 3/4" size: 5/8" x 3/4' size: (0.37 bar @5.7 m3/hr) (0.23 bar @9.1 m3/hr) (0.45 bar @ 11.3 m3/hr)
Operation 1.5 psi @10 gpm 2.8 psi @ 15 gpm
(0.10 bar @2.3 m3/hr) (0.19 bar @3.4 m3/hr)
Maximum
Operating 80° F (26° C)
Temperature
Maximum
Operating 150 psi (10 bar)
Pressure
Measuring Nutating disc, positive displacement Element
Available in NL bronze and engineered polymer to fit spud thread bore diameter sizes:
Meter I 5/8" size: I I I
Connections 5/8" or 5/8' (DN 15 mm) 3/4" (DN 20 mm) 1 (DN 25 mm) 1" (DN 25 mm) 3/4" (DN 15 mm) I 5/8" x 3/4" size: I
3/4" (DN 15 mm)
MATERIALS
Model LP
(5/8°&5/8"x3/4')
Model 25
1 (5/8"&5/8"x3/4")
Model 35
(3/4")
Model 55 Model 70
Meter Housing Lead-free bronze alloy
Housing Bottom Plates Lead-free bronze alloy, cast iron,
engineered polymer Cast iron, lead-free bronze alloy
Measuring Chamber Engineered polymer
Disc Engineered polymer
Trim Stainless steel
Strainer Engineered polymer
Disc Spindle Engineered polymer Stainless steel Stainless steel Engineered polymer Stainless steel
Magnet Ceramic Ceramic Ceramic Polymer bonded Ceramic
Magnet Spindle Engineered polymer Stainless steel Stainless steel Engineered polymer Stainless steel
Register Lid and Shroud Engineered polymer, bronze
Page 2 RDM-DS-00464-EN-03 AWWA October 2015
25 i'- RecordoiC -
0 .
_7 Gallons 3-
f
' 25
40%
2
-.7 CubIc Feet .3
iooi:oio:
0
0,09 111, 0925
Recorda0 .:-o,00 .:92
o
pa
_0,O7 '
m3 0,03
D.Oj1.00iO 'off
0,06 0,04
0,05 "\,\
Product Data Sheet
DIMENSIONS
Meter Size Model -
A
Laying Length
B
Height Reg.
C
Centerline Base Width Approx. Shipping
Weight
5/8"and 5/8"x 3/4" (15 mm) LP 7-1/2" (190 mm) 3.70" (94 mm) 1.26" (32 mm) 3.75(95mm) 3 lb (1.4 kg)
5/8"(15mm) 25 7-1/2(190 mm) 4-15/16" (125 mm) 1-11/16" (42 mm) 4-1/4" (108 mm) 4-1/2 lb (2 kg)
5/8" x 3/4"(15mm) 7-1/2" (190 mm) 4-15/16" (125 mm). 1-11/16" (42 mm) 4-1/4(108 mm) 4-1/2 lb (2 kg)
3/4" (20 mm)
35
7-1/2" (190 mm) 5-1/4" (133 mm) 1-5/8(41 mm) 5" (127'rnm) 5-1/2 lb (2.5 kg)
3/4" (20 mm) 9(229mm) 5-1/4" (133 mm) 1-5/8(41 mm) 5" (127 mm) 5-3/4 lb (2.6 kg)
3/4" x 1" (20 mm) 9(229mm) 5-1/4" (133 mm) 1-5/8" (41 mm) 5(127mm) 6 lb (2.7 kg)
1(25mm) 55 10-3/4" (273 mm) 6(152mm) 2-1/32" (52 mm) 6-1/4(159mm) 8-3/4 lb (3.9 kg)
1(25mm) 70 10-3/4" (273 mm) 1 6-1/2" (165 mm) 2-5/16" (59 mm) 1 7-3/4" (197 mm) 1 11-1/2 lb (5.2 kg)
REGISTERS / ENCODERS
Standard—Sweep-Hand Registration
The standard register is a straight-reading, permanently sealed magnetic drive register. Dirt, moisture, tampering and lens fogging problems are eliminated.
The register has a six-odometer wheel totalization display, 360° test circle with center sweep hand, and flow finder to detect leaks. Register gearing is made of
self-lubricating engineered polymer, which minimizes friction and provides long life.The multi-position register simplifies meter installation and reading. The
register capacity is 10,000,000 gallons (1,000,000 ft3, 100,000 m3).
A Model 25 register is used in the following example:
Model Gallon Cubic
Feet
I Cubic
Meter
LP 10 1 0.1
25(5/8") 10 1 0.1/0.01
25(5/8" x 3/4") 10 1 0.1/0.01
35 10 1 0.1
55 10 1 0.1
70 10 L 1 0.1
Optional—Encoders for AMR/AMI Reading Solutions
AMR/AMI solutions are available for all Recordall Disc Series meters. All reading options can be removed from the meter without disrupting water service.
Badger Meter encoders provide years of reliable, accurate readings for a variety of applications and are also available pre-wired to Badger Meter approved
AMR/AMI solutions. See details at www.badgernietev.com.
October2015 RDM-DS-00464-EN-03 AWWA Page 3
Recordalle Disc Meters, Lead-Free Bronze Alloy, Sizes 5/8','518"x314','314"& 1"
PRESSURE LOSS CHARTS
Rate of Flow in Gallons per Minute
Model LP 5/8"
25
20
15
vi
10
a-
5
0
Model LP 5/8' x 3/4"
1 10 ion
-(I 40 60 80
—
______• — ______. __ __. ____. ______. _____ . — _ _ ____. - _______. — _____.. - ______. _____..
MIM
— ______. - ______.
0.
— ______. - ______.
WIN ME
— -
Model 255/8"
1 10 100 4 a a 0 40 an an
25
20
15
0
10
0
Page 4 RDM-DS-00464-EN-03 AWWA October2015
Product Data Sheet
PRESSURE LOSS CHARTS (CONTINUED)
Rate of Flow in Gallons per Minute
Model 25 5/8 x 3/4
Model 35 3/4
1 1 0 100 2 4 6 8 20 40 60 80
25
20
15
vi
10
0
5
0
Model 55 1'
1 10 100 In n on
25
20
0 -J 15
aj 10
5
0
October2015 RDM-DS-00464-EN-03 AWWA Pages
Recordall® Disc Meters, Lead-Free Bronze Alloy, Sizes 518','518"x 3/4', 3/4" & 1"
PRESSURE LOSS CHARTS (CONTINUED)
Rate of Flow in Gallons per Minute
Model 701"
1 10 nn an cn 100
25
20
0 -J 15
10
0-
5
0
ACCURACY CHARTS
Model LP 5/8'
1 1.0 10 100
Model LP 5/8" x 3/4"
1 1.0 10 100
Page 6 RDM-DS-00464-EN-03 AWWA October2015
Product Data Sheet
ACCURACY CHARTS (CONTINUED)
Model 25 5/8
.1 A 1.0 010 100
Model 25 5/8 x 3/40
1 1.0 10 100
.1 C 0 fl .4 C 0 in nfl CA
Model 353/4"
I I
MIN
MEW 0
no 00 ___.u.. mmmomm --------------..--------...
. ______..u.______...I_______•. ...._____..Ogg..___mommimmommms___•••• •
_
MEN ME owns
MEMO____.._i______...._____••... OEM
momms
------....-----.....------.... mommomm MEEM
October2015 RDM-DS-00464-EN-03 AWWA Page 7
0
-: — ---- -
Recordall Disc Meters, Lead-Free Bronze Alloy, Sizes 5/8,' 518"x314"' 3/4" & 1"
ACCURACY CHARTS (CONTINUED)
Model 55 1"
1 1.0 10 100
mom NEE= mmmmmon
------....------....------...I
------...l------....------....
------....------...I-----..... __... .I—_—___....
1MR11100 mom IM ZERO El MIM mmommm moons MIMMINEM ------....------...I------....
Model 70 1"
1 1.0 10 DO 100
MEMOS
WMNN -----.—..------...U------.—.
__.....______...0 • __....__ ME"
MEMO ME immmirpmemm
-------.l------....------.... -----....------.$..------a..I —
(U ~MMMMMMOMOM so • C&10— on ..______...._____....I
NEW ME MOM ME
Making Water Visible'
MAKING WaTER VISIELE arcl PECURDALL are acli';t7red irdernai ks o Badyor Meter, Inc. Other trademarks appearmq this document are the property ol tl sir respective sastites
Due tu continuous tpsojrch, pi .sudus'' ii ipruvan ent,s raid enhsiscntnents Sedi' Metar reserves the riyht to 5lir njv product or system spaiilicvtlns without notice. ensept to ha
'etsrit tn csastsndi'cj contractual cl71iq.7tiou cuists, L 2015 8a,Iqcr Mor Inc. All riqht; rou2l'ved.
www.badgermeter.com
TheAnericas I61rei .a.7'ltlrav, p 5C Mil.,,kc'c 5-Vl 53774v;551 0.00376J3.17 .-iI'l-555-u430
Masico I Catlger Meter de las A,nek. S.A.de c.j. Swim Lair 0s2ri lr72j Erq.Aa.iclina 4 Gskuiu Guadalupe inn cprjrvsc Myra-v OF Mcnirc
Europe, Middir, East and Africa I Cadger M,we Eurapa Gr,bH I 1`4mli.viv. SIrS'S I Nui "'w I
Europe, Middle Cost ttronih (StOre Cd6erf,Se1,r Europe I roitnr3ni-142 L ic•13,lirau 0-us, thud Quul'sr Lrs-ldi,. Wiu 2,ulCry tQvu Dub,s SiSAL 9?l 4.37 7503
Czech Republic I Sudijer Meter Czech Rapublit sr.o. l:i.,t,l.ov,2l5212, 21 -.51 tSr, 0, l:scl, Eep'.Lle -l27-7-0l42('4t I
Stovakla BadijerMete'Slovalda err. I Eirisaslsi 109/i' - t$l 12 Orrir-lava. 51w-aSia I 44212-44u 11331
Asia Padlir Bdt;srMaler IQ Marl-v Pacrtr 5(1 21-06 PLw,is Paude I Laewre3492uS J -i65-n5464b5o
China I Cadger Meter I 7-1207 99 Haal,c-v Iliad I Minlvinq 0,121 5isincIlrai I Ch7s 2,1101 e86-21-9763 1412 cc'qucy Dcuec'it iluwbars: I1ISM-O3-c10IM2. 63, Sd, as. cc. :577
ZURN Model 950XL
WILKiNS Double Check Valve Assembly
Application
Designed for installation on water lines to protect against
both backsiphonage and backpressure of polluted water into
the potable water supply. Assembly shall provide protection
where a potential health hazard does not exist.
Standards Compliance
(All sizes approved horizontal. Vertical approvals as listed
below.)
ASSE® Listed 1015 (vertical 3/4", 11/4", 11/2" & 2")
IAPMO® Listed (vertical 1 1/4"-2")
CSA® Listed (vertical 3/4", 1 1/4", 1 1/2" & 2")
AWWA Compliant C510 (vertical 3/4")
UL® Classified (less shut-off valves only)
C-UL® Classified (less shut-off valves only)
Approved by the Foundation for Cross Connection Control
and Hydraulic Research at the University of Southern Cali-
fornia (vertical 3/4")
City of Los Angeles Approved (vertical 1-1/4-2')
NYC MEA 426-89-M VOL 3
Materials
Main valve body Cast Bronze ASTM B 584
Access covers Cast Bronze ASTM B 584
Internals Stainless Steel, 300 Series
Elastomers Silicone (FDA approved)
Buna Nitrile (FDA approved)
Polymers NorylTM, NSF Listed
Springs Stainless steel, 300 series
Features
Sizes: 3/4", 1", 11/2", 2'
Options
(Suffixes can be combined)
El - with full port QT ball valves (standard)
L - less ball valves
E U - with union ball valves
fl S - with bronze "V type strainer
TCU - with test cocks "vertical" up
Ej V - with union swivel elbows (3/4" & 1")
OSY - with OS & V gate valves
E FDC - with fire hydrant connection (2" only)
LI FT - with integral male 45° flare SAE test fitting
fl PF - with Z-BiteTM push fit connections* (1/2-1 "only)
LI PR - with ZPressTM press fit connections*
*Fittings ship in box with valve and must be threaded into
valve by hand on site.
Accessories
fl Repair kit (rubber only)
E] Thermal expansion tank (Model XT)
Ej QT-SET Quick Test Fitting Set
Maximum working water pressure 175 PSI
Maximum working water temperature 180°F
Hydrostatic test pressure 350 PSI
End connections Threaded ANSI B1.20.1
Dimensions & Weights (do not include pkg.)
DIME NSIONS_(a )proximate) WEIGHT
MODEL A UNION LESS WITH
SIZE A BALL B LESS BALL C D E F G BALL BALL
VALVES VALVES VALVES VALVES
mm in. mm in. mm in. Imm in. I mmm. mm in. I mm in. I mm
3/4 20 111/4 286 121/2 318 7 178 11/2 38 3 76 31/2 89 3 76 15 381 5 2.3 7 3.2
1 25 112 1/4 311 137/8 353 7 178 11/2 38 3 76 31/2 89 3 76 173/4 12 5.4
11/4* 32 151/2 419 181/2 470 109/16 268 2 51 31/2 89 41/2 114 41/2 114 211/2
%6338 W167.3
22 10
11/2 40 171/8435 191/8 486 109/16 268 2
Im
89 41/2 114 41/2
M11425
22 10
2 50 181/4460 20 508 109/16 268 2 89 41/2 114 41/2 28 12.7
*Size 1-1/4" Discontinued
Zurn Industries, LLC I Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada I Zurn Industries Limited
3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292
Rev. D
Date: 4/15
Document No. BF-950XL
Product No. Model 950XL
wwwurncom I Page 1 of 2
Flow Characteristics 0 Rated Flow (established by approval agencies)
MODEL 950XL 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC)
FLOW RATES (us)
C,
Cl) a-
U, Cl) 0 —J
W cc
(I, Cl) Lu cc a- .•
3.2 6.3 9.5 12.6 15.8 15 CX 11/4 (32 m) (40mm) 103
_____ _____ Cl) 10 7 69 0 —J
w
35 5 —
C') uJ Cc 0 0 50 100 150 200 250 °
FLOW RATES (GPM)
Typical Installation
Local codes shall govern installation requirements. To be
installed in accordance with the manufacturer's instructions
and the latest edition of the Uniform Plumbing Code. Unless
otherwise specified, the assembly shall be mounted at a mini-
mum of 12" (305mm) and a maximum of 30" (762mm) above
adequate drains with sufficient side clearance for testing and
maintenance. The installation shall be made so that no part of
the unit can be submerged.
Capacity thruSchedule 40 Pipe
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 Wsec
1/8" 1 1 2 3
1/4" 2 2 3 5
3/8" 3 4 6 9
1/2 5 7 9 14
3/4" 8 12 17 25
13 20 27 40
1 1/4" 23 35 47 70
1 1/2" 32 48 63 95
52 78 105 167
DIRECTION OF FLOW
OUTDOOR INSTALLATION INDOOR INSTALLATION
Specifications
The Double Check Valve Backflow Preventer shall be ASSE® Listed 1015 approved, and supplied with full port ball valves.
The main body and access covers shall be bronze (ASTM B 584), the seat rings and all internal polymers shall be NSF® Listed
NorylTM and the seat disc elastomers shall be silicone. The first and second checks shall be accessible for maintenance with-
out removing the device from the line. The Double Check Valve Backflow Preventer shall be a ZURN WILKINS Model 950XL.
Zurn Industries, LLC l Wilkins
1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766
In Canada ( Zurn Industries Limited 3544 Nashua Drive, Mississauga, Ontario L4V 1L2 Ph. 905-405-8272, Fax 905-405-1292
wwww.zurn.com Page 2 of 2
DOMESTIC
WATER -
LINE
i
10 4
'ffi+ 16 D 12
IIIIIHIII
1••
SEE DETAIL BRASS OR
COPPER 10
PRIVATE
PUBLIC
8
NOTES:
REFER TO DRAWING W-3 FOR SPECIFICATIONS OF 17.5 INSTALLATION OF SERVICE LINE AND APPURTENANCES.
DISTRICT;TO SET METER AND BALL VALVE, ALL OTHERS
TO BE INSTALLED BY CONTRACTOR.
DOMESTIC WATER LINE MATERIAL WILL BE IN 6
CONFORMANCE TO CODE.
ALL 2" OR SMALLER COPPER JOINTS SHALL BE
PRESS-CONNECT IN CONFORMANCE WITH SPECIFICATIONS.
/ - SIDEWALK
SEE W-3, W-8,
7
ITEM DESCRIPTION SPEC/DWG - COPPER, [TYPE 'K' , SOFT] 15057
2 30; LB. ZINC ANODE LEAD WIRE W-25
3 2" T-7-COPPER TEE (PRESS-CONNLCT)
4 1"90_ COPPER -CONNECT) _BEND _(PRESS
5 NOT USED
6 1" ANGLE METER STOP
7 #37 ARMORCAST METER BOX (OR EQUIVALENT)
8 1" BALL VALVE.
WATER METER BY DISTRICT
BRASS UNION
FIRE APPROVED FIRE _SYSTEM _WATER _LINE _(SIZE _TO_BE_ _BY_ _MARSHAL)
1" DOUBLE CHECK VALVE WITH SHUT OFF VALVES (LEAD FREE)
REV. APPROVED DATE CARLSBAD MUNICIPAL WATER DISTRICT . /h - 02 /1 6
1 02/16 I' DOMESTIC WATER SERVICE CONNECTION DISTfCT ENGINEER DATE WITH FIRE SPRINKLER SYSTEM
STANDARD DWG. NO. -