Loading...
HomeMy WebLinkAbout5791 VAN ALLEN WAY; ; AS100151; Permit9/15/2020 AS100151 Permit Data City of Carlsbad Sprinkler Permit Permit No: AS100151 Job Address:. 5791 VAN ALLEN WY Status: ISSUED Permit Type: SPRINK Applied 11/24/2010 Parcel No: 2121304500 Approved: 11/24/2010 Lot #: 0 Reference No.: Issued: 11/24/2010 PC #: Inspector: Project Title: LIFE TECHNOLOGIES THREE TI FIRE SPRINKLER INSPECTIONS @ $65/EA Applicant: Owner: MIKE L. HUANTE JR. MARARISK CARLSBAD L L C 16035 OLD VALLEY RD C/O LIFE TECHNOLOGIES CORP LAPUE.NTE, CA 5791 VAN ALLEN WAY CARLSBAD CA 626-336-0043 Fees ($). Add'I Fees ($) Total ($) Balance ($) 195 0 195 0 I 1/1 V's Fire Protection Plan Review & Code Consulting 9384 Suva Street Downey, CA 90240- (562) 833-3596 To: Mr. Michael Davis - Fire Marshal City of Carlsbad Fire Department 1635 Faraday Avenue Carlsbad, CA 92008 Project: Life Technologies CP-B 5791 Van Allen Way Carlsbad, CA Date: November 23, 2010 Scope of work: Provide sprinkler protection for 2-level addition to existing building. Design is .45/entire area w/ Ki 1.2 heads at the attic area, and .1/1500 using quick response extended coverage heads at the under ceiling area. Building area is +1- 6,000sqft. Structure has been reviewed by an Engineering Company. Total heads - 71 Plan Submittal: (3) set of plans consisting of (2) sheet each, (2) sets of calculations Plan Received: 11/22/10 Review Comments We have reviewed the submittal, and it is our opinion that it is in substantial conformance with the applicable codes and standards in force at this time, including local adopted ordinances. Acceptance of these plans is recommended subject to the following comments: 1. The extended coverage EC-1 1 sprinkler heads at 1550F are ULK listed quick response at a maximum 18 X 18 when using the style 30 semi recess escutcheon. When the spacing exceeds 18' apart (or 9' to a wall), the sprinklers shall not use the style 30 semi recess escutcheon. See marked plans Note I - Portable fire extinguishers shall be provided in accordance with the 2007 CFC Note 2 - The review is for the new overhead sprinkler system only. The underground fire mains shall be installed per the approved plans by the Carlsbad Fire Department Note 3 - This review did not include the analysis of any hazardous materials to be present. Note 4 -Any fire alarm system required by this system shall be approved by Carlsbad Fire Department and permitted Note 5 - The Building is not to be used for storage. Should high pile combustible storage be proposed, approval is required by Carlsbad Fire Department Note 6 - The roof structure shall be reviewed to verify it can adequately support the larger piping loads These plans are recommended for acceptance subject to the comments above incorporated onto the drawings, and contingent upon the City of Carlsbad Fire Department field inspection for compliance. 2Sicerell James S. arger, E. Fire Protection Plan Review & Code Consulting 9384 Suva Street Downey, CA 90240 (562) 833-3596 To: Mike L. Huarte Jr. Fire Protection 1432 17" St. Santa Monica, CA Project: Life Technologies CP-B 5791 Van Allen Way Carlsbad, CA Date: November 8, 2010 Scope of work: Provide sprinkler protection for 2-level addition to existing building. Design is .45/entire area wl Ki 1.2 heads at the attic area, and .1/1500 using quick response extended coverage heads at the under ceiling area. Building area is +1- 6,000sqft. Total heads - 71 Plan Submittal: (3) set of plans consisting of (2) sheet each, (2) sets of calculations Plan Received: 11/8/10 Review Comments Review of these plans indicate the following deficiencies requiring correction or additional information: i. The plans show the use of Ki 1.2 Tyco ELO-23 1 heads. Per the City of Carlsbad FD Standard FPB-039 #1, K8 1 17/32" heads are to be used. The use of other heads shall not be used without a meeting with the building owner and written approval from the Carlsbad Fire Department. a r"t Cio C. F D, Provide approval from the building's structural engineer that the light weight roof structure can handle the sprinkler piping and sway brace loads, based on NFPA 13. This is required per the City of Carlsbad FD Standard FPB-039 #4. A*9 ISM& UJ.F. !VAWS. G = Vio. 3. The Tyco EC- 11 semi-recess head is only listed as a quick response sprinkler with a 135°F temperature rating at 20 X 20 spacing. Reduce the spacing to a maximum 18 X 18, or change the heads to standard pendent type (not recessed) 6#C r. e* V. 1W&VAPJr >JI&.016 ja 0107- 29 $rw,, , Provide a copy of the hydrant flow test from the City of Carlsbad, off Faraday Ave, near the system point of connection. Provide a cushion in the water supply for the backflow prevention device. If the existing underground piping plan is available, design to the public water supply. 5sps, 5. Clearly indicate all revisions on the plans by clouding and delta. Provide a written description of the changes upon resubmittal. Provide a minimum 4-sets of plans and calculations upon resubmittal j997 CARLSBAD FIRE PREVENTION DIVISION Permit Application Form Check or fill in pertinent information for type of permit you are submitting. AS -Automatic Sprinklers (Check off type ofplans being submitted) New System - How many risers/levels? V Tenant Improvement Residential - How many systems and/or buildings? Underground for approval Underground included for reference only Total Fees FA - Fire Alarm 25 Devices or less Over 26 devices # of devices Monitoring System Total Fees FS - Fixed Systems (Circle One) Hood & Duct, Special Chemical Agent Suppression System, Standpipe, Spray Booth or Appliance. Total Fees Failed Inspection fee on new construction is $75.00. Name of Project: Address of job site: 1 (J.,1/1 / Suite # Building Permit # CB Contractor Contractor Information Name Address I+'2__ 3f City 6 M- C 04-p4- Phone 32,9?Fax Kind of License and Number (',_iLo Exp. Date 13.4 I Do you currently have a business license on file with the City of Carlsbad? Yes or No Signature Date /1/24/to . Please estimate at least 10 business days for plan review comments and/or approval. We will contact you by telephone when the plans are approved/disapproved. Thank you! HYDRAULIC CALCULATIONS FOR Life Technologies CP-B 5791 Van Allan Way Carlsbad, CA. DATE:. 11-22-2010 FILE NO: 1546A -DESIGN DATA- OCCUPANCY CLASSIFICATION: Ordinary Hazard Group 2 DENSITY: 0.45 gpm/sq. ft. AREA OF APPLICATION: 3000 sq. ft. COVERAGE PER SPRINKLER: Varies (100 sq. ft. max.) MINIMUM FLOW PER SPRINKLER: 38.0 gpm NUMBER OF SPRINKLERS CALCULATED: 37 TOTAL SPRINKLER WATER FLOW REQUIRED: 1572.7 gpm TOTAL WATER REQUIRED (Including hose): 2072.7 gpm FLOW & PRESSURE (@ BOR) : 1672.7 gpm @ 78.6 psi Items listed in bold print are automatically transfered from the ca1cu1ati6n report Mlnl5l... 0 0 0 0 0 N (N 0 0 (N 0 0 L1) 0 0 N 0 0 0 0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life 0 (N CO 00 c 00 OOCr104 U)U)Cr1 04U),-1_-_ SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) S 121.5 117.0 1920.0 116.3 2072.7 93.0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 2072.7 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 400.0 GPM OTHER HOSE STREAM ALLOWANCES 100.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 1572.7 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) S -3.0 SOURCE 93.0 1672.7 A -3.0 - - - - 92.4 - - - B -3.0 - - - - 87.4 C -3.0 - - - - 86.3 - - - D -3.0 - - - - 81.6 - - - BOR 0.5 HOSE STREAM 78.6 100.0 TOR 31.0 - - - - 57.3 POC 31.0 - - - - 34.5 1 33.0 K=10.60 15.7 42.0 2 33.0 K=10.10 15.8 40.2 3 33.0 K=10.10 16.4 40.9 4 33.0 K=10.60 14.0 39.7 5 33.0 K=10.10 14.2 38.0 6 33.0 K=10.10 14.6 38.6 7 330 K=10.60 16.1 42.5 8 33.0 K=10.60 14.2 39.9 9 33.0 K=10.10 14.3 38.2 10 33.0 K=10.10 14.8 38.8 11 33.0 K=10.60 16.3 42.8 12 33.0 K=10.60 14.5 40.4 13 33.0 K=10.10 14.7 38.7 14 33.0 K=10.10 15.1 39.3 15 33.0 K=10.60 16.7 43.3 16 33.0 K=10.60 15.1 41.2 17 33.0 K=10.10 15.3 39.5 18 33.0 K=10.10 15.8 40.1 19 33.0 K=10.60 17.6 44.4 20 33.0 K=10.10 15.2 39.4 21 33.0 K=10.10 15.4 39.6 22 33.0 K=10.10 15.9 40.2 23 33.0 K=10.10 16.7 41.3 24 33.0 K=10.60 16.4 42.9 25 33.0 K=10.10 16.7 41.2 26 33.0 K=10.10 16.8 41.4 NOTES r SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 H:\DATA\1546A.SDF DATE: 11/22/2010 JOB TITLE: Life NODE ANALYSIS DATA NODE TAG ELEVATION (FT) 27 33.0 28 33.0 29 33.0 30 33.0 31 33.0 32 33.0 33 33.0 34 33.0 35 33.0 36 33.0 37 33.0 38 32.0 39 32.0 40 32.0 41 32.0 42 32.0 43 32.0 44 320 45 32.0 46 32.0 47 31.0 48 31.0 49 31.0 50 31.0 51 31.0 52 31.0 53 31.0 54 31.0 55 31.0 NODE TYPE PRESSURE DISCHARGE (PSI) (GPM) K=10.10 17.3 42.1 K=10.10 18.2 43.1 K=10.60 17.9 44.8 K=10.10 19.9 45.1 K=10.10 20.1 45.3 K=10.10 20.7 45.9 K=10.60 22.6 50.4 K=10.60 22.6 50.4 K=10.10 22.8 48.2 K=10.10 23.5 49.0 K=10.60 25.8 53.8 - - - - 17.6 - - - - - - - 16.8 - - - - - - - 17.0 - - - - - - - 17.4 - - - - - - - 18.1 - - - - - - - 18.1 - - - - - - - 19.7 - - - - - - - 23.5 - - - - - - - 26.7 - - - - - - - 19.6 - - - - - - - 19.7 - - - - - - - 19.9 - - - - - - - 20.3 - - - - - - - 21.1 - - - - - - - 22.4 - - - - - - - 24.4 - - - - - - - 27.2 - - - - - - - 30.9 - - - NOTES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life NFPA PIPE DATA Pipe Tag K-fac Frm Node El (ft) PT To Node El (ft) PT Pipe: 1 10.60 2 33.0 15.8 1 33.0 15.7 Pipe: 2 10.10 3 33.0 16.4 2 33.0 15.8 Pipe: 3 10.10 38 32.0 17.6 3 33.0 16.4 Pipe: 4 10.60 5 33.0 14.2 4 33.0 14.0 Pipe: 5 10.10 6 33.0 14.6 5 33.0 14.2 Pipe: 6 10.10 39 32.0 16.8 6 33.0 14.6 Pipe: 7 10.60 39 32.0 16.8 7 33.0 16.1 Pipe: 8 10.60 9 33.0 14.3 8 33.0 14.2 Pipe: 9 10.10 10 33.0 14.8 9 33.0 14.3 Pipe: 10 10.10 40 32.0 17.0 10 33.0 14.8 Pipe: 11 10.60 40 32.0 17.0 11 33.0 16.3 Pipe: 12 10.60 13 33.0 14.7 12 33.0 14.5 Add Fl Add Fl To Fit: L C (Pt) (q) Node/ Nom ID Eq.Ln. F (Pe) Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) 42.0 Disch 8.00 120 0.2 0.0 2.000 ---- 0.00 0.0 42.0 2.067 8.00 0.019 0.2 40.2 Disch 8.00 120 0.5 42.0 1 2.000 ---- 0.00 0.0 82.2 2.067 8.00 0.065 0.5 40.9 Disch 1.00 120 1.3 82.2 2 2.000 E: 5.0 5.00 -0.4 123.0 2.067 6.00 0.138 0.8 39.7 Disch 8.00 120 0.1 0.0 2.000 ---- 0.00 0.0 39.7 2.067 8.00 0.017 0.1 38.0 Disch 8.00 120 0.5 39.7 4 2.000 ---- 0.00 0.0 77.7 2.067 8.00 0.059 0.5 38.6 Disch 4.00 120 2.2 77.7 5 2.000 T:10.0 10.00 -0.4 116.3 2.067 14.00 0.124 1.7 42.5 Disch 4.00 120 0.7 0.0 2.000 T:10.0 10.00 -0.4 42.5 2.067 14.00 0.019 0.3 39.9 Disch 8.00 120 0.1 0.0 2.000 ---- 0.00 0.0 39.9 2.067 8.00 0.017 0.1 38.2 Disch 8.00 120 0.5 39.9 8 2.000 ---- 0.00 0.0 78.1 2.067 8.00 0.059 0.5 38.8 Disch 4.00 120 2.2 78.1 9 2.000 T:10.0 10.00 -0.4 116.9 2.067 14.00 0.125 1.8 42.8 Disch 4.00 120 0.7 0.0 2.000 T:10.0 10.00 -0.4 42.8 2.067 14.00 0.020 0.3 40.4 Disch 8.00 120 0.1 0.0 2.000 ---- 0.00 0.0 40.4 2.067 8.00 0.018 0.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life Pipe Tag K-fac Frm Node El (ft) PT To Node El (ft) PT Pipe: 13 10.10 14 33.0 15.1 13 33.0 14.7 Pipe: 14 10.10 41 32.0 17.4 14 33.0 15.1 Pipe: 15 10.60 41 32.0 17.4 15 33.0 16.7 Pipe: 16 10.60 17 33.0 15.3 16 33.0 15.1 Pipe: 17 10.10 18 33.0 15.8 17 33.0 15.3 Pipe: 18 10.10 42 32.0 18.1 18 33.0 15.8 Pipe: 19 10.60 42 32.0 18.1 19 33.0 17.6 Pipe: 20 10.10 21 33.0 15.4 20 33.0 15.2 Pipe: 21 10.10 22 33.0 15.9 21 33.0 15.4 Pipe: 22 10.10 43 32.0 18.1 22 33.0 15.9 Pipe: 23 10.60 23 33.0 16.7 24 33.0 16.4 Pipe: 24 10.10 43 32.0 18.1 23 33.0 16.7 Pipe: 25 10.10 26 33.0 16.8 25 33.0 16.7 Add Fl Add Fl To Fit: L C (Pt) (q) Node/ Nom ID Eq.Ln. F (Pe) Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf) 38.7 Disch 8.00 120 0.5 40.4 12 2.000 ---- 0.00 0.0 79.1 2.067 8.00 0.061 0.5 39.3 Disch 4.00 120 2.2 79.1 13 2.000 T:10.0 10.00 -0.4 118.4 2.067 14.00 0.128 1.8 43.3 Disch 4.00 120 0.7 0.0 2.000 T:10.0 10.00 -0.4 43.3 2.067 14.00 0.020 0.3 41.2 Disch 8.00 120 0.1 0.0 2.000 ---- 0.00 0.0 41.2 2.067 8.00 0.018 0.1 39.5 Disch 8.00 120 0.5 41.2 16 2.000 ---- 0.00 0.0 80.7 2.067 8.00 0.063 0.5 40.1 Disch 4.00 120 2.3 80.7 17 2.000 T:10.0 10.00 -0.4 120.8 2.067 14.00 0.133 1.9 44.4 Disch 4.00 120 0.5 0.0 2.000 ---- 0.00 -0.4 44.4 2.067 4.00 0.021 0.1 39.4 Disch 8.00 120 0.1 0.0 2.000 ---- 0.00 0.0 39.4 2.067 8.00 0.017 0.1 39.6 Disch 8.00 120 0.5 39.4 20 2.000 ---- 0.00 0.0 79.0 2.067 8.00 0.061 0.5 40.2 Disch 4.00 120 2.3 79.0 21 2.000 T:10.0 10.00 -0.4 119.3 2.067 14.00 0.130 1.8 42.9 Disch 11.00 120 0.3 0.0 2.000 E: 5.0 5.00 0.0 42.9 2.067 16.00 0.020 0.3 41.3 Disch 4.67 120 1.4 42.9 24 2.000 T:10.0 10.00 -0.4 84.1 2.067 14.67 0.068 1.0 41.2 Disch 8.00 120 0.1 0.0 2.000 ---- 0.00 0.0 41.2 2.067 8.00 0.018 0.1 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe) 1' To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 26 10.10 41.4 Disch 8.00 120 0.5 27 33.0 17.3 41.2 25 2.000 ---- 0.00 0.0 26 33.0 16.8 82.6 2.067 8.00 0.066 0.5 Pipe: 27 10.10 42.1 Disch 4.00 120 2.4 44 32.0 19.7 82.6 26 2.000 T:10.0 10.00 -0.4 27 33.0. 17.3 124.7 2.067 14.00 0.141 2.0 Pipe: 28 10.60 44.8 Disch 11.00 120 0.3 28 33.0 18.2 0.0 2.000 E: 5.0 5.00 0.0 29 33.0 17.9 44.8 2.067 16.00 0.021 0.3 Pipe: 29 10.10 43.1 Disch 4.67 120 1.5 44 32.0 19.7 44.8 29 2.000 T:10.0 10.00 -0.4 28 33.0 18.2 87.9 2.067 14.67 0.074 1.1 Pipe: 30 10.10 45.1 Disch 8.00 120 0.2 31 33.0 20.1 0.0 2.000 ---- 0.00 0.0 30 33.0 19.9 45.1 2.067 8.00 0.021 0.2 Pipe: 31 10.10 45.3 Disch 8.00 120 0.6 32 33.0 20.7 45.1 30 2.000 ---- 0.00 0.0 31 33.0 20.1 90.3 2.067 8.00 0.078 0.6 Pipe: 32 10.10 45.9 Disch 4.00 120 2.8 45 32.0 23.5 90.3 31 2.000 T:10.0 10.00 -0.4 32 33.0 20.7 136.3 2.067 14.00 0.167 2.3 Pipe: 33 10.60 50.4 Disch 4.67 120 0.8 45 32.0 23.5 0.0 2.000 T:10.0 10.00 -0.4 33 33.0 22.6 50.4 2.067 14.67 0.026 0.4 Pipe: 34 10.60 50.4 Disch 8.00 120 0.2 35 33.0 22.8 0.0 2.000 ---- 0.00 0.0 34 33.0 22.6 50.4 2.067 8.00 0.026 0.2 Pipe: 35 10.10 48.2 Disch 8.00 120 0.7 36 33.0 23.5 50.4 34 2.000 ---- 0.00 0.0 35 33.0 22.8 98.6 2.067 8.00 0.092 0.7 10.10 49.0 Disch Pipe: 36 0.0 4.00 120 3.1 46 32.0 26.7 98.6 35 2.000 T:10.0 10.00 -0.4 36 33.0 23.5 147.6 2.067 14.00 0.193 2.7 Pipe: 37 10.60 53.8 Disch 4.67 120 0.9 46 32.0 26.7 0.0 2.000 T:10.0 10.00 -0.4 37 33.0 25.8 53.8 2.067 14.67 0.030 0.4 Pipe: 38 0.0 0.0 1.00 120 1.9 47 31.0 19.6 123.0 3 2.000 T:10.0 10.00 -0.4 38 32.0 17.6 123.0 2.067 11.00 0.138 1.5 - I J SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe) To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 39 0.0 116.3 6 1.00 120 2.9 48 31.0 19.7 42.5 7 2.000 T:10.0 10.00 -0.4 39 32.0 16.8 158.8 2.067 11.00 0.221 2.4 Pipe: 40 0.0 116.9 10 1.00 120 2.9 49 31.0 19.9 42.8 11 2.000 T:10.0 10.00 -0.4 40 32.0 17.0 159.7 2.067 11.00 0.223 2.5 Pipe: 41 0.0 118.4 14 1.00 120 2.9 50 31.0 20.3 43.3 15 2.000 T:10.0 10.00 -0.4 41 32.0 17.4 161.6 2.067 11.00 0.228 2.5 Pipe: 42 0.0 120.8 18 1.00 120 3.1 51 31.0 21.1 44.4 19 2.000 T:10.0 10.00 -0.4 42 32.0 18.1 165.2 2.067 11.00 0.238 2.6 Pipe: 43 0.0 84.1 23 1.00 120 4.3 52 31.0 22.4 119.3 22 2.000 T:10.0 10.00 -0.4 43 32.0 18.1 203.4 2.067 11.00 0.349 3.8 Pipe: 44 0.0 87.9 28 1.00 120 4.6 53 31.0 24.4 124.7 27 2.000 T:10.0 10.00 -0.4 44 32.0 19.7 212.6 2.067 11.00 0.379 4.2 Pipe: 45 0.0 136.3 32 1.00 120 3.7 54 31.0 27.2 50.4 33 2.000 T:10.0 10.00 -0.4 45 32.0 23.5 186.7 2.067 11.00 0.298 3.3 Pipe: 46 0.0 147.6 36 1.00 120 4.2 55 31.0 30.9 53.8 37 2.000 T:10.0 10.00 -0.4 46 32.0 26.7 201.4 2.067 11.00 0.343 3.8 Pipe: 47 0.0 0.0 9.50 120 0.1 48 31.0 19.7 123.0 38 B4.000 E:13.0 13.00 0.0 47 31.0 19.6 123.0 4.260 22.50 0.004 0.1 Pipe: 48 0.0 123.0 47 10.50 120 0.2 49 31.0 19.9 158.8 39 B4.000 ---- 0.00 0.0 48 31.0 19.7 281.9 4.260 10.50 0.019 0.2 Pipe: 49 0.0 281.9 48 10.50 120 0.5 50 31.0 20.3 159.7 40 B4.000 ---- 0.00 0.0 49 31.0 19.9 441.6 4.260 10.50 0.043 0.5 Pipe: 50 0.0 441.6 49 10.50 120 0.8 51 31.0 21.1 161.6 41 B4.000 ---- 0.00 0.0 50 31.0 20.3 603.2 4.260 10.50 0.077 0.8 Pipe: 51 0.0 603.2 50 10.50 120 1.3 52 31.0 22.4 165.2 42 B4.000 ---- 0.00 0.0 51 31.0 21.1 768.4 4.260 10.50 0.121 1.3 Fit: L C Eq.Ln. F (ft.) T Pf/ft. 10.50 120 0 ---- 0.00 0 10.50 0.186 10.50 120 0 ---- 0.00 0 10.50 0.269 10.50 120 0 ---- 0.00 0 10.50 0.352 8.00 120 0 ---- 0.00 0 8.00 0.454 258.00 .120 0 E:18.0 94.00 7 2T:76.0 352.00 0.065 ETGA 30.50 120 0 95.00 7 125.50 0.065 3.50 140 0 E:22.0 22.00 0 25.50 0.058 30.00 140 0 T:47.0 52.00 0 G: 5.0 82.00 0.058 220.00 140 ---- 0.00 0 220.00 0.005 assure Loss Device 5.0 psi, 1672.6 gpm (Pt) (Pe) (Pf) 2.0 0.0 2.0 3.7 0.0 3.7 3.6 0.0 3.6 22.8 0.0 22.8 21.3 -13.2 8.1 3.0 -1.5 1.5 4.7 0.0 4.7 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life Pipe Tag K-fac Frm Node El (ft) PT To Node El (ft) PT Pipe: 52 0.0 53 31.0 24.4 52 31.0 22.4 Pipe: 53 0.0 54 31.0 27.2 53 31.0 24.4 Pipe: 54 0.0 55 31.0 30.9 54 31.0 27.2 Pipe: 55 0.0 POC 31.0 34.5 55 31.0 30.9 Pipe: 56 0.0 TOR 31.0 57.3 POC 31.0 34.5 Pipe: 57 0.0 BOR 0.5 78.6 TOR 31.0 57.3 Pipe: 58 H.S. D -3.0 81.6 BOR 0.5 78.6 Pipe: 59 0.0 C -3.0 86.3 D -3.0 81.6 Pipe: 60 0.0 B -3.0 87.4 C -3.0 86.3 Pipe: 61 A -3.0 92.4 B -3.0 87.4 Pipe: 62 Source S -3.0 93.0 A -3.0 92.4 Add Fl Add Fl To (q) Node/ Nom ID Tot.(Q) Disch Act ID 768.4 51 203.4 43 B4.00 971.8 4.26 971.8 52 212.6 44 84.00 1184.5 4.26 1184.5 53 186.7 45 B4.00 1371.2 4.26 1371.2 54 201.4 46 84.00 1572.6 4.26 0.0 1572.6 55 B6.00 1572.6 6.35 0.0 1572.6 POC 86.00 1572.6 6.35 100.0 Disch 1572.6 TOR D6.00 1672.6 6.28 0.0 1672.6 BOR D6.00 1672.6 6.28 0.0 1672.6 D D10.0 1672.6 10.40' 0.0 Fixed Pr 1672.6 C 1672.6 0.0 1672.7 B D1O.01 1672.7 10.40 40.00 140 T:80.0 88.00 0 G: 8.0 128.00 0.005 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life NOTES (HASS): Calculations were performed by the HASS 8.1 computer program under license no. 38021611 granted by HRS Systems, Inc. 208 South Public Square Petersburg, TN 37144 (931) 659-9760 The system has been calculated to provide an average imbalance at each node of 0.003 gpm and a maximum imbalance at any node of 0.169 gpm. Total pressure at each node is used in balancing the system. Maximum water velocity is 35.4 ft/sec at pipe 55. SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11 DATE: 11/22/2010 H:\DATA\1546A.SDF JOB TITLE: Life Utility Report: Equivalent K-Factor Calculator Node Sprinkler Pres. Dia. Pipe Ftgs. Total H-W Equivalent Name K-Factor (psi) (in) Len. (ft) Len. (ft) coef. K-factor ------------------------------------------------------------------------ eqk-E 11.20 7.00 1.049 1.00 E 3.00 120.00 10.60 eqk-T 11.20 7.00 1.049 1.00 T 6.00 120.00 10.10 HYDRAULIC CALCULATIONS FOR Life Technologies CP-B 5791 Van Allan Way Carlsbad, CA. DATE: 11-22-2010 FILE NO: 15468 -DESIGN DATA- OCCUPANCY CLASSIFICATION: Light Hazard DENSITY: 0.10 gpm/sq. ft. AREA OF APPLICATION: 1500 sq. ft. COVERAGE PER SPRINKLER: 400 sq. ft. (20' x 20' max) MINIMUM FLOW PER SPRINKLER: 40.0 gpm NUMBER OF SPRINKLERS CALCULATED: 9 TOTAL SPRINKLER WATER FLOW REQUIRED: 416.3 gpm TOTAL WATER REQUIRED (including hose): 516.3 gpm FLOW AND PRESSURE (@ BOR): 416.3 gpm @ 67.6 psi Items listed in bold print are automatically transfered from the calculation report Aslool5k 0 0 CIO 0 0 0 c'J 0 0 H 0 0 ILl 0 0 c.\J H 0 0 H SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life N C. C. C. C. 0 0 00 0 H00 Lfl (N H H QU)•-1-- SPRINKLER SYSTEM HYDRAULIC ANALYSIS DATE: 11/22/2010 JOB TITLE: Life NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL NODE PRESS. PRESS. @ PRESS. @ DEMAND TAG (PSI) (PSI) (GPM) (PSI) (GPM) S 121.5 117.0 1920.0 121.1 516.3 Page 3 H:\DATA\1546B.SDF REQ'D PRESS. (PSI) 74.7 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 516.3 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 416.3 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE (FT) (PSI) (GPM) S -3.0 SOURCE 74.7 416.3 A -3.0 - - - - 74.6 - - - B -3.0 - - - - 69.6 - - - C -3.0 - - - - 69.6 D -3.0 - - - - 69.2 BOR 0.5 - - - - 67.6 TOR 31.0 - - - - 53.7 POC 31.0 - - - - 51.7 1 33.0 - - - - 49.9 - - - 2. 33.0 - - - - 49.9 - - - 3 33.0 - - - - 49.9 - - - 4 33.0 - - - - 49.9 - - - 5 .. 33.0 - - - - 49.9 - - - 6 33.0 - - - - 49.9 - - - 7 33.0 - - - - 49.9 - - - 8 33.0 - - - - 49.9' - - - 9 33.0 - - - - 49.9 - - - 10 33.0 - - - - 49.9 - - - 11 33.0 - - - - 49.9 - - - 12 33.0 - - - - 49.9 - - - 13 33.0 - - - - 49.9 - - - 14 33.0 - - - - 49.9 - - - 15 33.0 - - - - 49.9 - - - 16 33.0 - - - - 49.9 - - - 17 33.0 - - - - 49.9 - - - 18 33.0 - - - - 49.9 - - - 19 33.0 - - - - 49.9 - - - 20 33.0 - - - - 42.8 - - - 21 33.0 - - - - 44.2 - - - 22 33.0 -' - - - 45.6 - - - 23 33.0 - - - - 48.0 - - - 24 33.0 - - - - 48.0 - - - 25 33.0 - - - - 43.0 - - - 26 33.0 - - - - 44.3 - - - NOTES DATE: 11/22/2010 JOB TITLE: Life NODE ANALYSIS DATA NODE TAG ELEVATION (FT) 27 33.0 28 33.0 29 33.0 30 33.0 31 33.0 32 33.0 33 33.0 34 33.0 35 33.0 36 33.0 37 33.0 38 32.0 39 32.0 40 32.0 41 32.0 42 32.0 43 32.0 44 32.0 45 32.0 46 32.0 47 31.0 48 31.0 49 31.0 50 31.0 51 31.0 52 31.0 53 31.0 54 31.0 55 31.0 81 32.0 82 32.0 83 32.0 84 12.0 85 12.0 86 12.0 87 12.0 88 12.0 89 12.0 90 12.0 91 12.0 92 12.0 93 12.0 94 12.0 95 12.0 NODE TYPE PRESSURE DISCHARGE (PSI) (GPM) - - - - 45.7 - - - - - - - 48.1 - - - - - - - 48.1 - - - - - - - 43.0 - - - - - - - 44.4 - - - - - - - 45.8 - - - - - - - 48.2 - - - - - - - 50.5 - - - - - - - 50.5 - - - - - - - 50.5 - - - - - - - 50.5 - - - - - - - 50.3 - - - - - - - 50.3 - - - - - - - 50.3 - - - - - - - 50.3 - - - - - - - 50.3 - - - - - - - 48.4 - - - - - - - 48.5 - - - - - - - 48.6 - - - - - - - 51.0 - - - - - - - 50.8 - - - - - - - 50.8 - - - - - - - 50.8 - - - - - - - 50.8 - - - - - - - 50.8 - - - - - - - 50.8 - - - - - - - 50.8 - - - - - - - 51.0 - - - - - - - 51.4 - - - - - - - 41.3 - - - - - - - 41.4 - - - - - - - 36.9 - - - - - - - 35.8 - - - - - - - 36.2 - - - - - - - 31.6 - - - K= 9.94 26.4 51.1 K= 9.94 21.8 46.4 K=10.43 16.6 42.4 K= 9.94 25.9 50.6 K= 9.94 22.7 47.3 K=10.43 14.7 40.0 K= 9.94 26.3 51.0 K= 9.94 21.3 45.9 K=10.43 16.0 41.7 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 H:\DATA\1546B.SDF NOTES SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life NFPA PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe) 1' To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf!ft. (Pf) Pipe: 1 0.0 0.0 8.00 120 0.0 2 33.0 49.9 0.0 2.000 ---- 0.00 0.0 1 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 2 0.0 0.0 8.00 120 0.0 2 33.0 49.9 0.0 2.000 ---- 0.00 0.0 3 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 3 0.0 0.0 1.00 120 0.4 38 32.0 50.3 0.0 2.000 E: 5.0 5.00 -0.4 3 33.0 49.9 0.0 2.067 6.00 0.000 0.0 Pipe: 4 0.0 0.0 8.00 120 0.0 4 33.0 49.9 0.0 2.000 ---- 0.00 0.0 5 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 5 0.0 0.0 8.00 120 0.0 6 33.0 49.9 0.0 2.000 ---- 0.00 0.0 5 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 6 0.0 0.0 4.00 120 0.4 6 33.0 49.9 0.0 2.000 T:10.0 10.00 0.4 39 32.0 50.3 0.0 2.067 14.00 0.000 0.0 Pipe: 7 0.0 0.0 4.00 120 0.4 39 32.0 50.3 0.0 2.000 T:10.0 10.00 -0.4 7 33.0 49.9 0.0 2.067 14.00 0.000 0.0 Pipe: 8 0.0 0.0 8.00 120 0.0 8 33.0 49.9 0.0 2.000 ---- 0.00 0.0 9 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 9 0.0 0.0 8.00 120 0.0 9 33.0 49.9 0.0 2.000 ---- 0.00 0.0 10 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 10 0.0 0.0 4.00 120 0.4 40 32.0 50.3 0.0 2.000 T:10.0 10.00 -0.4 10 33.0 49.9 0.0 2.067 14.00 0.000 0.0 Pipe: 11 0.0 0.0 4.00 120 0.4 11 33.0 49.9 0.0 2.000 T:10.0 10.00 0.4 40 32.0 50.3 0.0 2.067 14.00 0.000 0.0 Pipe: 12 0.0 0.0 8.00 120 0.0 13 33.0 49.9 0.0 2.000 ---- 0.00 0.0 12 33.0 49.9 0.0 2.067 8.00 0.000 0.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe) 1' To Node El (ft) PT Tot. (Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 13 0.0 0.0 8.00 120 0.0 13 33.0 49.9 0.0 2.000 ---- 0.00 0.0 14 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 14 0.0 0.0 4.00 120 0.4 14 33.0 49.9 0.0 2.000 T:10.0 10.00 0.4 41 32.0 50.3 0.0 2.067 14.00 0.000 0.0 Pipe: 15 0.0 0.0 4.00 120 0.4 15 33.0 49.9 0.0 2.000 T:10.0 10.00 0.4 41 32.0 50.3 0.0 2.067 14.00 0.000 0.0 Pipe: 16 0.0 0.0 8.00 120 0.0 17 33.0 49.9 0.0 2.000 ---- 0.00 0.0 16 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 17 0.0 0.0 8.00 120 0.0 18 33.0 49.9 0.0 2.000 ---- 0.00 0.0 17 33.0 49.9 0.0 2.067 8.00 0.000 0.0 Pipe: 18 0.0 0.0 4.00 120 0.4 18 33.0 49.9 0.0 2.000 T:10.0 10.00 0.4 42 32.0 50.3 0.0 2.067 14.00 0.000 0.0 Pipe: 19 0.0 0.0 4.00 120 0.4 42 32.0 50.3 0.0 2.000 ---- 0.00 -0.4 19 33.0 49.9 0.0 2.067 4.00 0.000 0.0 Pipe: 20 0.0 0.0 8.00 120 1.4 21 33.0 44.2 138.6 83 2.000 ---- 0.00 0.0 20 33.0 42.8 138.6 2.067 8.00 0.172 1.4 Pipe: 21 0.0 0.0 8.00 120 1.4 22 33.0 45.6 138.6 20 2.000 ---- 0.00 0.0 21 33.0 44.2 138.6 2.067 8.00 0.172 1.4 Pipe: 22 0.0 0.0 4.00 120 2.8 43 32.0 48.4 138.6 21 2.000 T:10.0 10.00 -0.4 22 33.0 45.6 138.6 2.067 14.00 0.172 2.4 Pipe: 23 0.0 0.0 11.00 120 0.0 24 33.0 48.0 0.0 2.000 E: 5.0 5.00 0.0 23 33.0 48.0 0.0 2.067 16.00 0.000 0.0 Pipe: 24 0.0 0.0 4.67 120 0.4 23 33.0 48.0 0.0 2.000 T:10.0 10.00 0.4 43 32.0 48.4 0.0 2.067 14.67 0.000 0.0 Pipe: 25 0.0 0.0 8.00 120 1.4 26 33.0 44.3 137.9 82 2.000 ---- 0.00 0.0 25 33.0 43.0 137.9 2.067 8.00 0.170 1.4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) To Node El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 26 0.0 0.0 8.00 120 1.4 27 33.0 45.7 137.9 25 2.000 ---- 0.00 0.0 26 33.0 44.3 137.9 2.067 8.00 0.170 1.4 Pipe: 27 0.0 0.0 4.00 120 2.8 44 32.0 48.5 137.9 26 2.000 T:10.0 10.00 -0.4 27 33.0 45.7 137.9 2.067 14.00 0.170 2.4 Pipe: 28 0.0 0.0 11.00 120 0.0 29 33.0 48.1 0.0 2.000 E: 5.0 5.00 0.0 28 33.0 48.1 0.0 2.067 16.00 0.000 0.0 Pipe: 29 0.0 0.0 4.67 120 0.4 44 32.0 48.5 0.0 2.000 T:10.0 10.00 -0.4 28 33.0 48.1 0.0 2.067 14.67 0.000 0.0 Pipe: 30 0.0 0.0 8.00 120 1.4 31 33.0 44.4 139.9 81 2.000 ---- 0.00 0.0 30 33.0 43.0 139.9 2.067 8.00 0.175 1.4 Pipe: 31 0.0 0.0 8.00 120 1.4 32 33.0 45.8 139.9 30 2.000 ---- 0.00 0.0 31 33.0 44.4 139.9 2.067 8.00 0.175 1.4 Pipe: 32 0.0 0.0 4.00 120 2.9 45 32.0 48.6 139.9 31 2.000 T:10.0 10.00 -0.4 32 33.0 45.8 139.9 2.067 14.00 0.175 2.4 Pipe: 33 0.0 0.0 4.67 120 0.4 45 32.0 48.6 0.0 2.000 T:10.0 10.00 -0.4 33 33.0 48.2 0.0 2.067 14.67 0.000 0.0 Pipe: 34 0.0 0.0 8.00 120 0.0 35 33.0 50.5 0.0 2.000 ---- 0.00 0.0 34 33.0 50.5 0.0 2.067 8.00 0.000 0.0 Pipe: 35 0.0 0.0 8.00 120 0.0 35 33.0 50.5 0.0 2.000 ---- 0.00 0.0 36 33.0 50.5 0.0 2.067 8.00 0.000 0.0 Pipe: 36 0.0 0.0 4.00 120 0.4 46 32.0 51.0 0.0 2.000 T:10.0 10.00 -0.4 36 33.0 50.5 0.0 2.067 14.00 0.000 0.0 Pipe: 37 0.0 0.0 4.67 120 0.4 46 32.0 51.0 0.0 2.000 T:10.0 10.00 -0.4 37 33.0 50.5 0.0 2.067 14.67 0.000 0.0 Pipe: 38 0.0 0.0 1.00 120 0.4 38 32.0 50.3 0.0 2.000 T:10.0 10.00 0.4 47 31.0 50.8 0.0 2.067 11.00 0.000 0.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8 DATE: 11/22/2010 H\DATA\1546B.SDF JOB TITLE: Life Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node! Nom ID Eq.Ln. F (Pe) To Node. El (ft) PT Tot.(Q) Disch Act ID (ft.) T Pf/ft. (Pf) Pipe: 39 0.0 .0.0 1.00 120 0.4 39 32.0 50.3 0.0 2.000 T:10.0 10.00 0.4 48 31.0 50.8 0.0 2.067 11.00 0.000 0.0 Pipe: 40 0.0 0.0 1.00 120 0.4 40 32.0 50.3 0.0 2.000 T:10.0 10.00 0.4 49 31.0 50.8 0.0 2.067 11.00 0.000 0.0 Pipe: 41 0.0 0.0 1.00 120 0.4 50 31.0 50.8 0.0 2.000 T:10.0 10.00 -0.4 41 32.0 50.3 0.0 2.067 11.00 0.000 0.0 Pipe: 42 0.0 0.0 1.00 120 0.4 42 32.0 50.3 0.0 2.000 T:10.0 10.00 0.4 51 31.0 50.8 0.0 2.067 11.00 0.000 0.0 Pipe: 43 0.0 0.0 1.00 120 2.3 52 31.0 50.8 138.6 22 2.000 T:10.0 10.00 -0.4 43 32.0 48.4 138.6 2.067 11.00 0.172 1.9 Pipe: 44 0.0 0.0 28 1.00 120 2.3 53 31.0 50.8 137.9 27 2.000 T:10.0 10.00 -0.4 44 32.0 48.5 137.9 2.067 11.00 0.170 1.9 Pipe: 45 0.0 0.0 33 1.00 120 2.4 54 31.0 51.0 139.9 32 2.000 T:10.0 10.00 -0.4 45 32.0 48.6 139.9 2.067 11.00 0.175 1.9 Pipe: 46 0.0 0.0 . 1.00 120 0.4 46 32.0 51.0 0.0 2.000 T:10.0 10.00 0.4 55 31.0 51.4 0.0 2.067 11.00 0.000 0.0 Pipe: 47 0.0 0.0 . 9.50 120 0.0 47 31.0 50.8 0.0 B4.000 E:13.0 13.00 0.0 48 31.0 50.8 0.0 4.260 22.50 0.000 0.0 Pipe: 48 0.0 0.0 10.50 120 0.0 49 31.0 50.8 0.0 B4.000 ---- 0.00 0.0 48 31.0 50.8 0.0 4.260 10.50 0.000 0.0 Pipe: 49 0.0 0.0 10.50 120 0.0 50 31.0 50.8 0.0 B4.000 ---- 0.00 0.0 49 31.0 50.8 0.0 4.260 10.50 0.000 0.0 Pipe: 50 0.0 0.0 10.50 120 0.0 51 31.0 50.8 0.0 B4.000 ---- 0.00 0.0 50 31.0 50.8 0.0 4.260 10.50 0.000 0.0 Pipe: 51 0.0 0.0 10.50 120 0.0 52 31.0 50.8 0.0 B4.000 ---- 0.00 0.0 51 31.0 50.8 0.0 4.260 10.50 0.000 0.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life Pipe Tag K-fac Frm Node El (ft) PT To Node El (ft) PT Pipe: 52 0.0 53 31.0 50.8 52 31.0 50.8 Pipe: 53 0.0 54 31.0 51.0 53 31.0 50.8 Pipe: 54 0.0 55 31.0 51.4 54 31.0 51.0 Pipe: 55 0.0 POC 31.0 51.7 55 31.0 51.4 Pipe: 56 0.0 TOR 31.0 53.7 POC 31.0 51.7 Pipe: 57 0.0 BOR 0.5 67.6 TOR 31.0 53.7 Pipe: 58 0.0 D -3.0 69.2 BOR 0.5 67.6 Pipe: 59 0.0 C -3.0 69.6 D -3.0 69.2 Pipe: 60 0.0 B -3.0 69.6 C -3.0 69.6 Pipe: 61 A -3.0 74.6 B -3.0 69.6 Pipe: 62 Source S -3.0 74.7 A -3.0 74.6 Pipe: 63 0.0 30 33.0 43.0 81 32.0 41.3 Pipe: 64 0.0 25 33.0 43.0 82 32.0 41.4 Add Fl Add Fl To (q) Node/ Nom ID Tot. (Q) Disch Act ID 0.0 51 138.6 43 B4.000 138.6 4.260 138.6 52 137.9 44 B4.000 276.5 4.260 276.5 53 139.9 45 B4.000 416.4 4.260 0.0 416.4 54 B4.000 416.4 4.260 0.0 416.4 55 B6.000 416.4 6.357 0.0 416.4 POC B6.000 416.4 6.357 0.0 416.4 TOR D6.000 416.4 6.280 0.0 416.4 BOR D6.000 416.4 6.280 0.0 416.4 D D10.00 416.4 10.400 0.0 Fixed Pre 416.4 C 416.4 0.0 416.3 B D10.00 416.3 10.400 0.0 139.9 84 1.500 139.9 1.610 0.0 137.9 85 1.500 137.9 1.610 Fit: L C Eq.Ln. F (ft.) T Pf/ft. 10.50 120 0.00 10.50 0.005 10.50 120 0.00 10.50 0.018 10.50 120 0.00 10.50 0.039 8.00 120 ---- 0.00 8.00 0.039 258.00 120 E:18.0 94.00 2T:76.0 352.00 0.006 ETGA 30.50 120 95.00 125.50 0.006 3.50 140 E:22.0 22.00 25.50 0.004 30.00 140 T:47.0 52.00 G: 5.0 82.00 0.004 220.00 140 0.00 220.00 0.000 ssure Loss Device 5.0 psi, 416.4 gpm 40.00 140 88.00 128.00 0.000 3.50 120 0.00 3.50 0.590 3.50 120 0.00 3.50 0.575 (Pt) (Pe) (Pf) 0.1 0.0 0.1 0.2 0.0 0.2 0.4 0.0 0.4 0.3 0.0 0.3 1.9 0.0 1.9 13.9 -13.2 0.7 0.4 0.0 0.4 0.1 0.0 0.1 1.6 0.4 2.1 1.6 0.4 2.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life Pipe Tag K-fac Add Fl Add Fl To Fit:, L C (Pt) Frm Node El (ft) PT () Node! Nom ID Eq.Ln. F (Pe) To Node El (ft) PT Tt.(Q) Disch Act ID (ft.) T Pf!ft. (Pf) Pipe: 65 0.0 0.0 7.00 120 5.9 20 33.0 42.8 138.6 86 1.500 E: 4.0 4.00 0.4 83 32.0 36.9 138.6 1.610 11.00 0.580 6.4 Pipe: 66 0.0 0.0 20.00 120 5.5 81 32.0 41.3 139.9 87 1.500 E: 4.0 4.00 8.7 84 12.0 35.8 139.9 1.610 24.00 0.590 14.2 Pipe: 67 0.0 0.0 20.00 120 5.1 82 32.0 41.4 137.9 90 1.500 E: 4.0 4.00 8.7 85 12.0 36.2 137.9 1.610 24.00 0.575 13.8 Pipe: 68 0.0 0.0 20.00 120 5.3 83 32.0 36.9 138.6 93 1.500 E: 4.0 4.00 8.7 86 12.0 31.6 138.6 1.610 24.00 0.580 13.9 Pipe: 69 9.94 51.1 Disch 8.00 120 9.4 84 12.0 35.8 88.8 88 1.500 2E: 8.0 8.00 0.0 87 12.0 26.4 139.9 1.610 16.00 0.590 9.4 Pipe: 70 9.94 46.4 Disch 18.00 120 4.6 87 12.0 26.4 42.4 89 1.500 ---- 0.00 0.0 88 12.0 21.8 88.8 1.610 18.00 0.255 4.6 Pipe: 71 - :3.43 42.4 Disch 10.00 120 5.2 88 12.O 21.8 0.0 1.000 ---- 0.00 0.0 89 12.0 16.6 42.4 1.049 10.00 0.523 5.2 Pipe: 72 9.94 50.6 Disch 10.00 120 10.4 85 12.0 36.2 37.3 91 1.500 2E: 8.0 8.00 0.0 90 12.0 25.9 137.9 1.610 18.00 0.575 10.4 Pipe: 73 9.94 47.3 Disch 13.00 120 3.2 90 12.0 25.9 40.0 92 1.500 ---- 0.00 0.0 91 12.0 22.7 87.3 1.610 13.00 0.247 3.2 Pipe: 74 13.43 40.0 Disch 15.00 120 8.0 91 1.2.0 22.7 0.0 1.000 E: 2.0 2.00 0.0 92 12.0 14.7 40.0 1.049 17.00 0.469 8.0 Pipe: 75 9.94 51.0 Disch 5.25 120 5.4 86 12.0 31.6 87.6 94 1.500 E: 4.0 4.00 0.0 93 12.0 26.3 138.6 1.610 9.25 0.580 5.4 Pipe: 76 9.94 45.9 Disch 20.00 120 5.0 93 12.0 26.3 41.7 95 1.500 ---- 0.00 0.0 94 12.0 21.3 87.6 1.610 20.00 0.248 5.0 Pipe: 77 10.43 41.7 Disch 10.50 120 5.3 94 12.0 21.3 0.0 1.000 0.00 0.0 95 12.0 16.0 41.7 1.049 10.50 0.507 5.3 - SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life NOTES (HASS) Calculations were performed by the HASS 8.1 computer program under license no. 38021611 granted by HRS Systems, Inc. 208 South Public Square Petersburg, TN 37144 (931) 659-9760 The system has been calculated to provide an average imbalance at each node of 0.002 gpm and a maximum imbalance at any node of 0.176 gpm. Total pressure at each node is used in balancing the system. Maximum water velocity is 22.0 ft/sec at pipe 63. U 4 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12 DATE: 11/22/2010 H:\DATA\1546B.SDF JOB TITLE: Life Utility Report: Equivalent K-Factor Calculator Node Sprinkler Pres. Dia. Pipe Ftgs. Total H-W Equivalent Name K-Factor (psi) (in) Len. (ft) Len. (ft) coef. K-factor ----------------------------------------------------------------------- eqk-E 11.20 7.00 1.049 2.00 E 4.00 120.00 10.43 eqk-T 11.20 7.00 1.049 2.00 T 7.00 120.00 9.94 Seismic Bracing Calculations Sheet ( of / Project: 14 FE TEUf 4o £_c'cr M Contractor: tfrtCE es4N'7 ,Pc t_L44 W( Address: Address: cA Telephone: Fax: Brace Information Seismic Brace Attachments Length of brace: Structure attachment fitting o.r.tension-only bracing system: Make: Model: ZS _______ Diameter of brace: Type 4.-o Listed load rating ' Adjusted load rating per 9.3.5.10.3: of brace: Angle of brace: 6 Sway 7 brace (pipe attachment) fitting: 1 0 0 Least radius of gyration:* Make: Model: 1k (LvMQ Listed load rating:' Adjusted load rating per 9.3.5.10.3: L/R value:* 2-00 Seismic Brace Assembly Detail Maximum horizontal load: +t'5 /h. (Provide detail on plans) Fastener Information -. Orientation of connecting surface: Fastener: ..ToLtc 1.' Type: I4T Diameter: 1%/A Length (in wood): K/A Maximum load: Zb(S fk Brace identification no. I (to be used on plans) I Lateral brace D Longitudinal brace Sprinkler System Load Calculation [F =!W (default is 0.5)] Diameter Type Length (ft) Total (ft) Weight per ft Total Weight 54 10 ________________ 4c' to?_$ lb/ft 2$3.7 lb ~4 +0 i3o' 130 1 . a-2_ )t lb/ft 0 lb " tA o LtZ.eSlb/ft lb lb/ft lb. lb/ft lb Total weight lb Fx1.15 Conterminous 48 States 2003 NEHRP Seismic Design Provisions Latitude = 33.1412124 Longitude = -117.3205123 Spectral Response Accelerations Ss and SI Ss and SI = Mapped Spectral Acceleration Values SiteClassB - Fa1.0Fv=1.O Data are based on a 0.009999999776482582 deg grid spacing Period Sa (sec) (g) 0.2 1.266 (Ss, Site Class B) poN tc7to4 F og- 1 <~2-r P-. 0 ~ ~ 02 tqCJ7 /Fire & Building / Products Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500 Series ELO-231 Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description The 11.2 K-factor, Series ELO-231, Standard Response, Standard Cover- age, Upright and Pendent Sprinklers (Ref. Figure 1) are automatic sprin- klers of the fusible solder type. They are "standard response - spray sprin- klers" that produce a hemispherical water distribution pattern below the deflector. The 11.2 K-factor, ELO-231 Sprinklers were subjected to full scale, high-piled storage, fire tests to qualify their use in lieu of 5.6 or 8.0 K-factor standard spray sprinklers for the protection of high-piled storage. Higher flow rates can be achieved at much lower pressures with the 11.2 K-factor, ELO-231 Sprinklers - mak- ing their use highly advantageous in high density applications, such as the protection of high-piled storage. Wax or lead coatings can be used to extend the life of the copper alloy com- ponents used in Series ELO-231 sprin- klers beyond that which would other- wise be obtained when exposed to corrosive atmospheres. Although wax and lead coated sprinklers have passed the standard corrosion tests of the applicable approval agencies, the testing is not representative of all pos- IMPORTANT Always refer to Technical Data Sheet TFP 700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 6 sible corrosive atmospheres. Conse- quently, it is recommended that the end user be consulted with respect to the suitability of these corrosion resis- tant coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemi- cals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An upright intermediate level version of the Series ELO-231 Sprinklers for in-rack applications can be obtained by utilizing the Series ELO-231 Up- right Sprinkler with the WSG-2 Guard & Shield, and a pendent intermediate level version of the Series ELO-231 Sprinklers can be obtained by utiliz- ing the Series ELO-231 Pendent Sprinkler with the WS-2 Shield. If there is a possibility of the pendent interme- diate level version being exposed to mechanical damage, a G-2 Guard can be added. WARNINGS The 11.2 K-factor, Series ELO-231 Upright and Pendent Sprinklers de- scribed herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or manufac- turer should be contacted with any questions. Installation of Series ELO-231 Pen- dent Sprinklers in recessed escutch- eons will void all sprinkler warranties, as well as possibly void the sprinkler's Approvals and/or Listings. MARCH, 2007 LJ TFP34O Astool'5 Page 2 of 6 TFP34O SPRINKLER FINISH TYPE TEMPERATURE FRAME COLOR NATURAL BRASS I CHROME PLATED LEAD COATED I WAX COATED I WAX J OVER LEAD UPRIGHT (TY5III TY5811) 165FI74°C Unpainted 1, 2, 3,4 1, 2, 3,4 212°F/100°C White 1 286°F/141°C Blue 1,2, 3,4 1(a) 2(a), 3(a), 4(a) 165F/74C Unpainted 3,4 1, 2, 4 (TY5211 212°F/100°C PENDENT 1,2, White 286F/141C Blue 1, 2, 4 Val, 2(a), 4(a) NOTES: Listed by Underwriters Laboratories, Inc. (UL Listed). Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL Listed). Approved by Factory Mutual Research Corporation (FM Approved). Approved by the City of New York under MEA 291-04-E. (a). Listed/Approved for a maximum ceiling temperature of 150°F166°C. TABLE A LABORATORY LISTINGS AND APPROVALS FOR 11.2 K-FACTOR SERIES ELO-231 UPRIGHT AND PENDENT SPRINKLERS (Refer to the Design Criteria Section) Model/Sprinkler Identification Numbers TY5111 - Upright 11.2K, 3/4"NPT TY5211 - Pendent 11.2K, 3/4"NPT TY5811 - Upright 11.21K, 1/2'NPT 15111 is a redesignation for C51 11 TY5211 is a redesignation for C521 1 TY5811 is a redesignation for C581 1 Technical Data Approvals UL and C-UL Listed. FM and NYC Ap- proved.(Refer to Table A for complete approval information including corro- sion resistant status. The approvals apply to the service conditions indi- cated in the Design Criteria section.) Maximum Working Pressure 175 psi (12,1 bar) Discharge Coefficient K = 11.2 GPM/psi112 (161,4 LPM/barll2) Temperature Ratings Refer to Table A Finishes Refer to Table A Physical Characteristics Frame .............Bronze Seal Disc ..........Copper Cap ..............Bronze Strut Assembly . . . Solder, Bronze, Stainless Steel Compression Screw .....Bronze Deflector ............Bronze Helper Spring . . . . Stainless Steel Ejector Spring .........Nickel Strut Clip ......Stainless Steel Design Criteria UL and C-UL Listing Requirements The 11.2 K-factor, Model ELO-231 (1Y5111, 1Y5211 & 1Y5811) Sprin- klers are to be installed in accordance with NFPA 13 standard sprinkler posi- tion and area/density flow calculation requirements for light, ordinary, or ex- tra hazard occupancies, as well as high piled storage occupancies (solid piled, palletized, rack storage, bin box, and shelf storage including but not lim- ited to Class -IV and Group A plastics) with a minimum residual (flowing) pressure of 7 psi (0,5 bar) for wet or dry pipe systems. FM Approval Requirements The 11.2 K-factor, Model ELO-231 (1Y5111, TY5211 & TY5811) Sprin- klers are to be installed in accordance with the applicable control mode den- sity/area" guidelines provided by Fac- tory Mutual. (FM guidelines may differ from UL and C-UL Listing criteria.) TFP34O * Temperature rating is indicated on deflector. ** Pipe thread connections per ISO 7/1 can be provided on 1/2 (12,7 mm) special request. NOMINAL MAKE-IN 2-13/16' (71,4 mm) FLATS I WRENCH TYP. 1 - 1/20** NPT 7/16" (11,1 mm) NOMINAL MAKE-IN UPRIGHT TY5811 Page 3 of 6 Components: - Frame Seal Disc Cap 4 - Strut Assembly 5 - Compression Screw 6 - Deflector* Helper Spring Ejector Spring Strut Clip -il--1 _________ w 4 , 'I/ill II - i44ti NPT NPT !Ar MAKE-IN UPRIGHT PENDENT CROSS FIGURE 1 11.2 K-FACTOR SERIES ELO-231 UPRIGHT - 3/4" NPT (TY5III), UPRIGHT - 1/2" NPT (TY5811), AND PENDENT - 3/4" NPT(TY5211) SPRINKLERS Operation A fusible alloy is sealed into a bronze actuating rod (center strut) by a stain- less steel ball. When the alloy melts at its rated temperature, the ball is forced upward into the center strut, releasing the two ejectors and operating the sprinkler. Installation The Series ELO-231 Sprinklers must be installed in accordance with the fol- lowing instructions: NOTES A leak tight 3/4 inch NPT sprinkler joint should be obtained with a torque of 10 to 20 ft.Ibs. (13,4 to 26,8 Nm). A maxi- mum of 30 ft.lbs. (40,7 Nm) of torque is to be used to install sprinklers with 3/4 NPT connections. A leak tight 1/2 inch NPT sprinkler joint should be ob- tained with a torque of 7 to 14 ft.lbs. (9,5 to 19,0 Nm). A maximum of 21 ft. lbs. (28,5 Nm) of torque may be used to install sprinklers with 1/2 NPT con- nections. Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler. Do not attempt to make-up for insuffi- cient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit. The Series ELO-231 Upright and Pendent Sprinklers must be installed in accordance with the following in- structions. Step 1. Pendent sprinklers are to be installed in the pendent position, and upright sprinklers are to be installed in the upright position. Step 2. With pipe thread sealant ap- plied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting. Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type "FITTING SIDE" TOWARDS SPRINKLER FITTING / WRENCH RECESS (END 'A") FIGURE 2 W-TYPE 3 SPRINKLER WRENCH 3 Sprinkler Wrench (Ref. Figure 2), except that an 8 or 10 inch adjustable Crescent wrench is to be used for wax coated sprinklers. With reference to Figure 1, the W-Type 3 Sprinkler Wrench or the adjustable Crescent wrench, as applicable is to be applied to the wrench flats. When installing wax coated sprinklers with the adjustable Crescent wrench, additional care needs to be exercised to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequently, exposure of bare metal to the corrosive environ- ment. The jaws of the wrench should be opened sufficiently wide to pass over the wrench flats without damag- ing the wax coating. Before wrench tightening the sprinkler, the jaws of the wrench are to be adjusted to just con- tact the sprinkler wrench flats. After wrench tightening the sprinkler, loosen Page 4 of 6 TFP34O the wrench jaws before removing the wrench. After installation, the sprinkler wrench flats and frame arms must be in- spected and the wax coating re- touched (repaired) whenever the coat- ing has been damaged and bare metal is exposed. The wax coating on the wrench flats can be retouched by gen- tly applying a heated 1/8 inch diameter steel rod to the areas of wax that have been damaged, to smooth it back over areas where bare metal is exposed. NOTES Only retouching of the wax coating ap- plied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation. The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precautions need to be taken, when handling the heated rod, in order to prevent the installer from being burned. If attempts to retouch the wax coating with complete coverage are unsuc- cessful, additional wax can be ordered in the form of a wax stick (the end of which is color coded). Only the correct color coded wax is to be used, and retouching of wrench flats and frame arms is only permitted at the time of initial sprinkler installation. With the steel rod heated as previously de- scribed, touch the rod to the area re- quiring additional wax with the rod an- gled downward, and then touch the wax stick to the rod approximately one-half inch away from the area re- quiring retouching. The wax will melt and run down onto the sprinkler. Care and Maintenance Series ELO-231 Sprinklers must be maintained and serviced in accord- ance with the following instructions: NOTES Before closing a fire protection system control valve for maintenance work on the fire protection system that it con- trols, permission to shut down the af- fected fire protection system must be obtained from the proper authorities and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be be painted, plated, coated or otherwise altered after leaving the factory. Modi- fied or over-heated sprinklers must be replaced. Care must be exercised to avoid dam- age to the sprinklers - before, during, and after installation. Sprinklers dam- aged by dropping, striking, wrench twist/slippage, or the like, must be re- placed. Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant sprinklers, after the installation has been completed, to verify the long term potential integrity of the sprinkler coatings. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of in- specting from the floor level, a random sampling of close-up visual inspec- tions should be made, so as to better determine the exact sprinkler condi- tion and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in- stalling contractor or sprinkler manu- facturer should be contacted relative to any questions. It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national code. Limited Warranty Products manufactured by Tyco Fire & Building Products (TFBP) are war- ranted solely to the original Buyer for ten (10) years against defects in mate- rial and workmanship when paid for and properly installed and maintained under normal use and service. This warranty will expire ten (10) years from date of shipment by TFBP. No warranty is given for products or com- ponents manufactured by companies not affiliated by ownership with TFBP or for products and components which have been subject to misuse, improper installation, corrosion, or which have not been installed, maintained, modi- fied or repaired in accordance with ap- plicable Standards of the National Fire Protection Association, and/or the standards of any other Authorities Having Jurisdiction. Materials found by TFBP to be defective shall be either repaired or replaced, at TFBP's sole option. TFBP neither assumes, nor authorizes any person to assume for it, any other obligation in connection with the sale of products or parts of prod- ucts. TFBP shall not be responsible for sprinkler system design errors or inac- curate or incomplete information sup- plied by Buyer or Buyer's repre- sentatives. In no event shall TFBP be liable, in contract, tort, strict liability or under any other legal theory, for incidental, indirect, special or consequential dam- ages, including but not limited to labor charges, regardless of whether TFBP was informed about the possibility of such damages, and in no event shall TFBP's liability exceed an amount equal to the sales price. This limited warranty sets forth the ex- clusive remedy for claims based on failure of or defect in products, materi- als or components, whether the claim is made in contract, tort, strict liability or any other legal theory. P/N 50-XXX-X-- XXX I TEMPERATURE RATING 165 165°F174°C 212 212°F/100°C 286 1 286°F1141°C TABLE B PRODUCT SYMBOL NUMBER SELECTION 11.2 K-FACTOR SERIES ELO-231 STANDARD RESPONSE UPRIGHT AND PENDENT SPRINKLERS 110 UPRIGHT 3/4" NPT (1Y5111) 112 PENDENT 3/4" NPT (1Y5211) 210 UPRIGHT 1/2" NPT (1Y5811) 4.. TFP34O Ordering Procedure A Part Number (P/N) is not specified when ordering sprinklers with thread connections per ISO 7/1. Contact your local distributor for avail- ability. Sprinkler Assemblies with NPT Thread Connection: Specify: (specify SIN), 11.2 K-factor, (specify temperature rating), Series ELO-231 Standard Response (specify Pendent or Upright) Sprinkler with (specify finish), P/N (specify from Ta- ble B). Sprinkler Wrench: Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001. Wax Sticks: (for retouching wrench damaged wax coating) Specify: (Specify color) color coded Wax Stick for retouching (specify tem- perature rating) temperature rated Se- ries ELO-231 Sprinklers, P/N (spec- ify). Red for 165'F .............P/N 56-065-1-155 Blue for 212'F and 286'F.................P/N 56-065-1-286 NOTES Each wax stick is suitable for retouch- ing up to twenty-five sprinklers. The wax used for 286°F sprinklers is the same as for 212°F sprinklers, and, therefore, the 286°Fsprinkler is limited to the same maximum ceiling tempera- ture as the 212°F sprinkler (i.e., 150°F). Page 5 of 6 tqCJ7 Fire & Building 1,Pro du c ts Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500 Series EC-1 I & EC. 14 - 112 and 14,0 K-factor Extended Coverage (Light and Ordinary Hazard) Upright, Pendent, and Rec. Pendent Sprinklers General Description The Series EC-11 and EC-14 Ex- tended Coverage Upright and Pendent Sprinklers are decorative glass bulb sprinklers designed for use in light or ordinary hazard occupancies. They are intended for use in automatic sprinkler systems designed in accord- ance with standard installation rules (e.g., NFPA 13) fora maximum cover- age area of 400 ft2 (37,2 m2), as com- pared to the maximum coverage area of 130 ft2 (12,1 M2) for standard cover- age sprinklers used in ordinary haz- ard occupancies or 225 ft2 (20,6 m2) for standard coverage sprinklers used in light hazard occupancies. The Series EC-li and EC-14 Sprin- klers feature a UL and C-UL Listing that permits their use with unob- structed or non-combustible ob- structed ceiling construction as de- fined and permitted by NFPA 13, as well as a specific application listing for use under concrete tees. The Series EC-11 and EC-14 Ex- tended Coverage Sprinklers have been fire tested to compare their per- formance to that of standard coverage spray sprinklers. These tests have shown that the protection provided is equal to or more effective than stand- ard coverage spray sprinklers. IMPORTANT Always refer to Technical Data Sheet TFP 700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Page 1 of 8 Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be ob- tained when exposed to corrosive at- mospheres. Although corrosion resis- tant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suitability of these corrosion resistant coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be con- sidered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. WARNINGS The Series EC-11 and EC-14 Ex- tended Coverage Sprinklers described herein must be installed and main- tained in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. SEPTEMBER, 2004 Model/S ikler Identifi- Numbe; TY513 -U1 ri TY5Ee tUprig 1Y6237 - Pende TY5137 is a red for C5137, G1894, and S25 TY5237 is a redc' cr 'nr C5237, G1893, and S25 TY6137 is a rede io, r C6137, G1896, and S26 TY6237 is a red' 76237, G1895, and S26 7113220 Asttiot5it WRENCH FLAT Page 2 of 8 P22O 3/4" ** NPT 2-7/16" (61,9 mm) UPRIGHT & PENDENT 1/2"(12,7mm) J NOMINAL MAKE-IN UPRIGHT ESCUTCHEON PLATE SEATING SURFACE 1 ) 1-11/16 4 / \ (42,7 mm) -. -------- 5 - 6* 2 PENDENT 1 - Frame 2 - Button 3 - Sealing Assembly 4- Bulb 5 - Compression Screw 6- Deflector* * Temperature rating is indicated on deflector ** Pipe thread connections per ISO 7/1 can be provided on special request. FIGURE 1 SERIES EC-li AND EC-14 EXTENDED COVERAGE SPRINKLERS 11.2 K-FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT 14.0 K-FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT HAZARD TYPE TEMP. BULB LIQUID 135°F/57"C Orange LIGHT UPRIGHT K=11.2 (TY5137) 1, 2, 3", 4 155°F/68"C Red 175°F/79°C Yellow PENDENT Refer to Table B for K=11.2 (TY5237) K14.0 (TY6237) 1,2,4 200°F/93°C Green 286°F/141°C Blue UL and C-UL 135°F/57°C Orange Sensitivity Rating and Refer to Table C for REC. PENDENT K=1 1.2 (TY5237) 1,2, 3,4 155°F/68"C Red 175°F/79°C Yellow FM K=14.0 (TY6237) Sensitivity Rating With Style 30 Escutcheon 1, 2, 4 200°F/93"C Green 286°F/141"C Blue UPRIGHT 135°F/57"C Orange ORDINARY K=11.2 (TY5137) K=14.0(TY6137) and 1,2,3,4 1550F/68°C Red 175°F/79"C Yellow Refer to Table B for UL and C-UL Sensitivity Rating PENDENT K11.2 (TY5237) K14.0 (TY6237) 200"F/93°C Green 286°F/141°C Blue REC. PENDENT 135°F157°C Orange and Refer to Table C for FM Sensitivity Rating K=1 1.2 (TY5237) K=14.0 (TY6237) With Style 40 1,2,4 155°F/68"C Red 175°F179°C Yellow Escutcheon 200°F/93°C Green NOTES: 1.Listed by Underwriters Laboratories, Inc. (UL). 2.Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL). Approved by Factory Mutual Research Corporation (FM). Approved by the City of New York under MEA 177-03-E. Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL a' Corrosion Resistant Sprinklers. "Frame and Deflector only. Listings and approvals apply to color (Special Order). ** Pendent Only. N/A: Not Available TABLE A, LABORATORY LISTINGS AND APPROVALS 1,2,4 N/A 2,4 N/A as SPRINKLER FINISH' NATURAL CHROME 't - - AD BRASS PLATED POL. DTED TFP22O P P 3of8 LIGHT HAZARD ORDINARY H 135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 36°F AREA STYLE 14x14 Up. orPend. - - - - - SR SR SR 'R 14 x 14 Style 30 Recessed - - - - - SR SR SR 14 x 14 Style 40 Recessed - - - - - SR SR SR 16x16 Up. orPend. QR* QR* QR* OR' QR* SR SR SR SR 16x16 Style 3ORecessed QR- QR* QR* OR OR* SR SR SR f 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR 18x18 Up. orPend. QR* QR* QR OR' QR* SR SR SR 18x18 Style 30 Recessed QR* QR* QR* OR' QR* SR SR SR 18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR 20x20 Up. orPend. OR* QR* QR* SR' SR* SR SR SR 20 x 20 Style 30 Recessed QR* SR* QR* SR' SR* SR SR SR 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR OR: Quick Response SR: Standard Response N/A: Not Applicable ° Does not apply to Upright K = 14.0 TABLE B SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-1 I OR EC-14 SPRII (SEE TABLED FOR PERMITTED K-FACTOR/AREA COMBINATIONS) SR NA N/A SR SR N/A 'A SR 'A LIGHT HAZARD 135°F 155°F 175°F 200°F 286°F AREA STYLE 14 x 14 Up. or Pend. - - - - - 14 x 14 Style 30 Recessed - - - - - 14 x 14 Style 40 Recessed - - - - - 16 x 16 Up. or Pend. QR* QR* N/A N/A N/A 16 x 16 Style 30 Recessed OR OR N/A N/A N/A 16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A 18 x 18 Up. or Pend. QR* OR* N/A N/A N/A 18 x 18 Style 30 Recessed OR OR N/A N/A N/A 18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A 20 x 20 Up. or Fend. OR OR* N/A N/A N/A 20 x 20 Style 30 Recessed OR OR N/A N/A N/A 20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A OR: Quick Response SR: Standard Response N/A: Not Applicable * Pendent Only ORDINARY H, 135°F 155°F 175°F SR SR SR N/A N/A N/A N/A N/A N/A VA SR SR SR F 'R N/A N/A N/A ' 'A N/A N/A N/A A SR SR SR N/A N/A N/A N/A N/A N/A 'A SR SR SR N/A N/A N/A A N/A N/A N/A A TABLE C SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-1 I OR EC-14 SPRIIJKI (SEE FM LOSS PREVENTION DATA SHEET 2-8N FOR PERMITTED K-FACTOR/AREA CO/ cation 'e S 4 Ex- edent 7,137 - Spe- cinder is fol- C COfl- r1an more .r. The st not The e tee ever, i ex- 'ills- he so tees '11) in n be or :ie are tal he 15, S- of p- E x- on gs 'he ry am- on n- 0, a' - e. UL ie- - n. Page 4 of 8 220 Technical Data Approvals UL and C-UL Listed. FM Approved. (Refer to Table A for complete approval information including corrosion resis- tant status. The approvals apply to the service conditions indicated in the De- sign Criteria section.) Maximum Working Pressure 175 psi (12,1 bar) Pipe Thread Connection 3/4 inch NPT Discharge Coefficients K = 11.2 GPM/psi1/2 (161,3 LPM/bar112) K = 14.0 GPM/psi112 (201,6 LPM/barl'2) Temperature Ratings 135°F1570C to 286°F/141°C Finish Sprinkler: Refer to Table A Recessed Escutcheon: White Coated, Chrome Plated, and Brass Plated Physical Characteristics Frame .............Bronze Button .............Bronze Sealing Assembly .......... Beryllium Nickel w/Teflonf Bulb ........Glass (3 mm dia.) Compression Screw ......... ......Bronze Deflector ............Brass Patents U.S.A. Patent Numbers 5,366,022; 5,579,846; 5,584,344; 5,609,211; 5,862,994; and 5,865,256. Operation The glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, which then allows the sprin- kler to activate and flow water. Design Criteria The Series EC-11 and EC-14 Ex- tended Coverage Sprinklers must only be installed in accordance with the ap- plicable UL and C-UL Listing or FM Approval requirements as indicated below. Only the Style 30 or 40 Re- cessed Escutcheon is to be used for recessed installation, as applicable (Ref. Table A, B, and C). UL and C-UL Listing Requirements The Series EC-1 1 and EC-1 4 Sprin- klers may be used for the coverage areas shown in Table D, based on maintaining the minimum specified flow rate as a function of coverage area and hazard group for all of the sprinklers in the design area. The Series EC-li and EC-1 4 Sprin- klers are permitted to be used with unobstructed or non-combustible obstructed ceiling construction as defined and permitted by NFPA 13. For example: Unobstructed, combustible or non-- combustible, ceiling construction with a deflector to ceiling/roof deck distance of 1 to 12 inches (25 to 300 mm. Obstructed, nor -combuje. cei1 ing construction with a deflector lo- cation below structural members of 1 t 6 inches (25 to 150 mm) and a maximum deflector to ceiling/roof deck distance of 22 inches (550 mm). The Series EC-1 1 and EC-14 Sprin- klers having been specifically tested and listed for non-combustible ob- structed construction are permitted to be used within trusses or bar joists having non-combustible web mem- bers greater than .4 mm) when applying th 4 time obstrLic- tion criteria rule d under "Ob- structions to Sprinkler Discharge Ptt,,,D;c.'epmnt". he minimum allowable spacing be- tween the Series EC-1 1 and EC- Sprinklers, to prevent cold solder- ing, is 8 feet (2,4 m) for uibLspdn- klers and-Wet (2,7 m) for pendent sprinklers. The Series EC-1 1 and EC-14 Sprin- klers are to be installed in accord- ance with all other requirements of NFPA 13 for extended coverage up- right and pendent sprinklers. For cx- ample: ohtrt' ., er dis- charge, ons' cl rinkler pattern d've or ictions to prevent si 1, e from reaching h:2, i, o stor- age, etc. UL and C-UL Listinq Req ri lnstai:ation The June" tended Coy Sprinklers (T. & TY6237) I: cific Applical concrete tec lows: The stern" o' striCtiOn 'I 7.5 leet (, i tl. i 3 Ic' C nIh of U e ed 2 e hi' C uth of • II it lie dc us n(• li'rigth 2. TI- snr' " k '.. 3. 1 FM t "rov• Req. irne The tenC inst cab Dat of s prc ha.' rnn cic Los but coil mui ing. The and sigi mil' MCI TFP22O 1/2±1/8 (12,7±3,2 mm) 2-7/8 DIA. (73,0 mm) 2-1/4 DIA. 1/2 (12,7 mm) 1/4" (6,4 mm) FACE OF (57,2 mm) SPRINKLER 1/8" FITTING (3,2 mm) 8 'ICH 0) MOUNTING SURFACE MOUNTING PLATE CLOSURE 1-3/8" (34,9 mm)! 1-1/8" (28,6 mm) FIGURE 2 SERIES EC-li AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 30 RECESSED ESCUTCHEON 2-7/8" DIA. 5/8±1/4' (73,0 mm) 3/4(19,1 mm) (15,9±6,4 mm) 2-1/4" DIA. 1/4" (6,4 mm) FACE OF (57,2 mm) SPRINKLER 1/8" FITTING (3,2 mm) / OUNTING MOUNTING SURFACE /PLATE CLOSURE 1-3/8" (34,9 mm) 7/8" (22,2 mm) FIGURE 3 SERIES EC-il AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 40 RECESSED ESCUTCHEON LIGHT HAZARD 0.10 GPM/FT2 GPM PSI 30 7.2 33 8.7 40 12.8 30 7.2 33 8.7 40 12.8 N/A N/A N/A N/A N/A N/A N/A N/A 37 7.0 37 7.0 40 8.2 GROUP I ORDINARY fi 7 ' 0.15 GPM/F" GPM 30 39 49 60 30 7. 39 49 60 33 49 60 39 49 63 'ID I Page 6 of 8 DESCRIPTION AREA TY5137 (K=11.2) UPRIGHT 14 x 14 16 x 16 18 x 18 20 x 20 TY5237 (K=11.2) PENDENT 14 x 14 16 x 16 18 x 18 20 x 20 TV6137 (K=14.0) UPRIGHT 14 x 14 16 x 16 18x 18 20 x 20 TV6237 (K=14.0) PENDENT 14 x 14 16 x 16 18 x 18 20 x 20 1 ft. = 0.3048 m 1 ft2 = 0.093 m2 1 gpm = 3.785 1pm 1 psi = 0.06895 bar 1 gpmlft2 = 40.74 mm/mm TABLE 0 FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-1 1 ANr. -1.: Step 1. The sprinkler must be installed Installation with the deflector parallel to the mounl- ing surface. Pendent sprinklers must The Series EC-11 and EC-14 Sprin- be installed in the pendent position. klers must be installed in accordance and upright sprinklers must be in- with the following instructions: stalled in the upright position. NOTES Step 2. After installing the Style 30 or Do not install any bulb type sprinkler if 40 mounting plate (or other escutch- the bulb is cracked or there isaloss of eon, as applicable) over the sprinkler liquid from the bulb. With the sprinkler pipe threads and with pipe thread held horizontally, a, small air bubble sealant applied to the pipe threads. should be present. The diameter of the hand tighten the sprinkler into the air bubble is approximately 1/16 inch sprinkler fitting. (1,6 mm) for the 135°F/570C to 3/32 Step 3. Wrench tighten upright or pen- inch (2,4 mm) for the 286°F/141°C dent sprinklers using only the W-Type temperature ratings. 3 (End A) Sprinkler Wrench. Wrench A leak tight 3/4 inch NPTsprinkler joint tighten the recessed pendent sprin- should be obtained with a torque of 10 klers using only the W-Type 22 Sprin- to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi- kler Wrench. The wrench recess of the mum of 30 ft.lbs. (40.7 Nm) of torque applicable sprinkler wrench (Ref. Fig- /s to be used to install sprinklers. ure 4 and 5) is to be applied to the Higher levels of torque may distort the sprinkler wrench flats (Ref. Figure 1). sprinkler inlet with consequent leak- age or impairment of the sprinkler. Do not attempt to compensate for in- sufficient adjustment in an Escutcheon Plate by under- or over-tightening the Sprinkler. Readjust the position of the sprinkler fitting to suit. V TFP22O of 8 Care and Maintenance The Series EC-11 and EC-14 Sprin- klers must be maintained and serviced in accordance with the following in- structions: NOTE Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection systems must be obtained from the proper authori- ties and all personnel who may be affected by this action must be notified. Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi- fied sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid dam- age to the sprinklers - before, during, and after installation. Sprinklers dam- aged by dropping, striking, wrench twist/slippage, or the like, must be re- placed. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section). Frequent visual inspections are rec- ommended to be initially performed for corrosion resistant coated sprinklers, after the installation has been com- pleted, to verify the integrity of the cor- rosion resistant coating. Thereafter, annual inspections per NFPA 25 should suffice; however, instead of in- specting from the floor level, a random sampling of close-up visual inspec- tions should be made, so as to better determine the exact sprinkler condi- tion and the long term integrity of the corrosion resistant coating, as it may be affected by the corrosive conditions present. The owner is responsible for the in- spection, testing, and maintenance of their fire protection system and de- vices in compliance with this docu- ment, as well as with the applicable standards of the National Fire Protec- tion Association (e.g., NFPA 25), in addition to the standards of any other authorities having jurisdiction. The in- stalling contractor or sprinkler manu- facturer should be contacted relative any questions. It is recommended that automatr sprinkler systems be inspected. tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. n -o Fire othe 01 ye -'ears a' t work- erly ' -rmal LI' I ex- .var- nn or npa- hat with and w hject 'orro- -lIed, ac- -S of Ja- ;er he- be C or - 1e to in it. - ;or • U cts or by RE '1- R 1, L 1 0 D H IT IT T- Page 8 of 8 Ordering Procedure When placing an order, indicate the full product name. Please specify the Sprinkler Identification Number (SIN), quantity, and temperature rating. Refer to the Price List fpr complete listing of Part Numbers. Contact your local distributor for avail- ability. Sprinkler Assemblies with NPT Thread Connections: Specify: (specify SIN), (specify K-Fac- tor), (specify temperature rating), (specify Pendent or Upright) Extended Coverage Sprinkler with (specify fin- ish), P/N (specify - from Table E, where applicable). Recessed Escutcheon: Specify: Style (specify 30 or 40) Re- cessed Escutcheon with (specify fin- ish), P/N (specify). Style 30 Recessed Escutcheon Chrome Plated ............PSN 56.705-9.011 White Color Coated ........PSN 56-705-4.011 White (RAL9010)*PSN 56-705-3-011 Brass Plated ..............PSN 56-705-2-011 Style 40 Recessed Escutcheon Chrome Plated ............PSN 56-700.9-010 White Color Coated ........PSN 56-700-4-010 White (RAL9O1O). ......... PSN 56-700-3-010 Brass Plated ..............PSN 56-700-2-010 Eastern Hemisphere sales only. Sprinkler Wrench: Specify: W-Type 3 Sprinkler Wrench, P/N 56-895-1-001 Specify: W-Type 22 Recessed Sprin- kler Wrench, P/N 56-665-7-001 P/N 51 - AAA - B -CCC AAA = 893 (for TY5237 K1 1.2 Pendent) AAA = 894 (for TY5137 Ki 1.2 Upright) AAA = 895 (for 1Y6237 K14.0 Pendent) AAA = 896 (for TY6137 K14.0 Upright) B = 1 (for Natural Brass) B = 3 (for White [RAL9010])* B = 4 (for White Polyester) B = 7 (for Lead Coated B = 9 (for Chrome Plated) CCC = 135 (for 135°F/57°C) CCC = 155 (for 155°F/681C) CCC = 175 (for 175°F/790C) CCC = 200 (for 200°F1930C) *Eastern Hemisphere sales only. TABLE PART NUMBERS FOR EC- 11 AND EC-14 SPRINKLERS TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale. P'' Carlsbad' Municipal Water District Potable Water Discharge Event Report Date: 1142 Z I I C" Location: 15 341 I v-k'N ki-1-gN Reason for Discharge Event: c . . Type of Event: Initial Dewatering Water Mains iiA Estimated Discharge Flow: J?Z7 eM Note: Includes flow testing and flushing • Dewatering Reservoirs Jf Start Time I{)3 IL' Unscheduled Water Discharge A- End Time ' tO Pre*-Dechlorination Residual: OiL4 Clear flow path of debris, surface contaminants and/or hazardous Post-Dechlorination Residual: S materials. Do not remove native (less than 0.1 mg/L) vegetation. pH within limits of 6.0 and 9.0 Erosion control, i.e. sandbags, silt fencing, hay bales, gravel bags, decreasing the velocity of discharge water. Upon completion of dewatering, ensure that the flow path is free of all temporary erosion prevention materials. Upon completion of dewaterihg, ensure that any sediment or silted areas are cleared. • Water Sampling Performed by: Comments: Submitted by: Reviewd by: (Name & (Name & Da FIRE FLOW TEST DATA Project Address: 'S- 7ct 1 JA: t-\ At14 4p'j' Test Date: if- 7_2-( Test Time:fo3,kM Test Outlet Size:—.. Flowing Hydrant Elevation: Gauged Hydrant Elevation Static Pressure = __ psi Residual Pressure = psi Pitot Tube Pressure = psi Observed Flow = gpm* Calculated Flow @ 20 psi = (t43, gpm** Test Performed By:5- Telephone Number:(3v ') Test Witnessed By: _7...L-I* kD4cLf ?LecA./_rt.. /C ( Telephone Number: 02-- Observed Flow = 29.83 x C x d2 x Where C is the coefficient of discharge d is the diameter of the test outlet in inches P is the velocity (pitot) pressure in psi ** Flow @ 20 Psi = o( I Zo Where Q is the observed flow in gpm S is the static pressure in psi R is the residual pressure in psi