Loading...
HomeMy WebLinkAbout5451 AVENIDA ENCINAS; ; FA080040; Permit9/22/21 4:07 PM FA080040 Permit Data City of Carlsbad Fire Alarm Permit Permit No: FA080040 5451 AVENIDA Job Address: Status: ISSUED ENCINAS Permit Type: FALARM Applied 7/1/2008 Parcel No: 2100904500 Approved: 7/1/2008 Lot #: 0 Reference No.: Issued: 7/1/2008 PC #: Inspector: Project Title: ICI PAINTS TI FIRE ALARM PLAN CHECK & INSPECTIONS Applicant: CENTRAL SECURITY SERVICES, INC. 43174 BUSINESS PARK DRIVE 951-676-7121 Owner: SAN-GAL TRUST THE C/O PHILIP L GILDRED JR 550 WEST C ST #1820 SAN DIEGO CA Fees ($) Add'I Fees ($) Total ($) Balance ($) 125 0 125 0 1/1 FIRE SYSTEM ICI PAINTS CARLSBAD, CA SUBMITTAL PREPARED BY: MICHAEL J. MAHONEY 407-475-1110 EXT 1103 NICET IV : ... ..• . Applicant ID No: 544986-001 Service Center No 1 S S Expires: 31-MAR-2009 CERTIFICATE OF COMPLIANCE THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with Certificated Alarm Systems.. The only evidence of compliance with UL's requirements is the issuance of a UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service Listed Service From: PITTSBURGH, PA Alarm Service Company: (544986-001) . Service Center: (544986-001) VECTOR SECURITY INC VECTOR SECURITY INC 3400 MCKNIGHT E OR: . .. . 3400 MCKNIGHT E DR PITTSBURGH PA 15237 .' . . PITTSBURGH PA 15237 The. Alarm Service Company is Listed in the following Certificate Service Categories: FIle Vol No CCN Listing Cateqry BP4558 - 1 CPVX [Burglar Alarm Systems] Central Station BP8466 - 1 •CVSG [Burglar Alarm Systems] Mercantile .BP5046 - I . I CVSU [Burglar Alarm Systems] Monitoring Station, Residential :BP41 11 - 1. : CVWY [Burglar Alarm Systems] Residential Alarm Systems S2535 - 1 UUFX [Signal and Fire Alarm Equipment and Services] (Protective •: :.. Signaling Services) Central Station .***THIS CERTIFICATE EXPIRES ON 31-MAR-2009 'LOOK FOR THE UL ALARM SYSTEM CERTIFICATE' mrp,/__ S si: 02008 UL Form CS-CC Intrusion Systems I D7412G Control Panel O BOSCH Invented for life D7412G Control Panel (_60-sa-, The D7412G Control Panel provides an integrated solution for Access Control, Security, and Fire Alarm system applications. The control panel is capable of monitoring alarm points for intruder or fire alarms while operating user command centers and other outputs. The control panel includes a communicator that reports events to selected PSTN or IP network destinations through four programmable route groups. Programming and accessory modules offer flexibility and beneficial features rarely found in other security control systems. The 07412G Control Panel provides eight on-board points, up to 67 off-board points, 64 relays, and two access control doors. Grant access from a Wiegand style card reader connected to: a D92 108 Access Control Module, a request- to-enter or request-to-exit input, or a keypad. Functions Programmable Outputs 2 A alarm power at 12 VDC 1.4 A auxiliary power at 12 VDC Four alarm output patterns Automatic bell test Programmable bell shut-off timer The 07412G Control Panel provides up to 75 individually identified points. Each point accommodates normally open Digital communicator with phone line monitor (loop or ground start) Multiple telephone numbers, primary and duplicate paths with main and alternate destinations All reports within each of four route groups are programmable Optional dual phone line switcher monitors two phone lines Optional network interface module for two-way communication over Ethernet networks Automatic test and status reports Time windows for arming and open and close report suppression Programmable answering machine solution for remote programming on shared phone lines (No) and or normally closed (NC) devices with end-of-line (EOL) resistor supervision. Each point is programmable for fire, fire supervisory, or burglary applications. System Response 31 custom point indexes, including fire supervisory Selectable point response time Cross point compatibility Fire alarm verification Fire inspector's local test Watch mode Scheduled events (skeds) arm, disarm, bypass and unbypass points, control relays, control authority levels, and control door access User Interface Supervises up to eight command centers or keypads (up to 32 non-supervised command centers or keypads can be used) Custom command center text Full function command menu including custom functions Each user has authority by area and 16-character name 14 custom authority levels control user's authority to change, add, delete passcodes or access control tokens/cards, disarm, bypass points, and initiate system tests www.boschsecurity.com I Adjustable brightness or volume for keypad display or sounder Note At least one keypad per system is recommended. Area Configurations Area programming offers a wide selection of different system configurations. Each area is assigned an account number to define annunciation, control, and reporting functions. Multiple areas can be linked to a shared area which is automatically controlled (hallway or lobby). Area arming can be conditional on other areas (master or associate). User Passcodes User passcodes contain three to six digits. Each user is assigned one of 14 customized authority levels in each area. Passcodes can be restricted to operate only during certain times. User names can contain up to 16 characters. The user name can be viewed, printed, reported to a central station in Modem lila2 Communications format or retrieved with Remote Programming (RPS) software. Security and Fire Detection The D7412G Control Panel provides eight on-board points, and up to 67 additional off-board points (depending on model and expansion interfaces). Program individual points to monitor all types of burglar alarm, fire alarm, and supervision devices. Communications The D7412G has four route groups. It can sort reports by priority and transmit reports to four route groups each of which has a programmable primary and backup destination. The 074120 is compatible with the 06600 NetCom Communications System using a DX4020 Network Interface Module. It has programmable anti-replay anti-substitution when using a DX4020. The Modem Ilia Communications Format, available with Bosch receivers, adds reporting capabilities such as: Individual point numbers and text Opening or closing reports by area number, user number, and user text Remote programming attempts Diagnostic reports Event Log Storage, Viewing and Printing All local and transmitted events (up to 1,000 total events) are stored in a log. The event log includes time, date and event, with area, point and user number. You can view the event log from select keypads or remotely retrieve event information using RPS. With the printer interface module installed, the 074120 Control Panel allows the use of one on-site parallel printers. The Event Log and a local printer provide a record of openings and closings without extra communications costs. RPS operators can retrieve events periodically using one phone call, rather than receiving several calls each day. When the control panel's event log reaches the storage limit, it can send a report to a receiver. Access events that you can store, view or print include: Access granted No entry Request-to-enter Request-to-exit Access Control Custom door strike, point shunt and auto disarming response by area Logging options for: Access Granted, No Entry, Request-to-exit, and Request-to-enter 14 panel-wide access levels with both manual and scheduled control Scheduled Events (Skeds) The D7412G Control Panel's internal clock and calendar helps to operate individually scheduled events (skeds). Skeds perform a specific function such as arm/disarm, relay control, or point bypassing. The 07412G Control Panel offers: 40 scheduled events with up to 26 different functions 16 open or closing windows Eight user windows Day-of-week, date-of-year, or holiday only schedules Four holiday schedules of 366 days each (leap year) Fire Test When a user activates Fire Test Mode, the control panel suppresses all reports to the central station. Use a passcode at the keypad to activate Fire Test Mode. The keypad and annunciator show all testing data. An automatic sensor reset feature saves time; you do not need to reset the sensors manually. At the end of test, the keypad shows the number of untested points. Programming, Diagnostics and Controls Users can program all system functions on-site with a 05200 Programmer, or remotely through RPS. A programmable system passcode prevents unauthorized remote programming. The control panel accommodates up to four separate telephone numbers for primary, alternate and backup receivers for automatic test reports. When resetting alarms, arming or disarming a combination fire/burglary and/or access control system, the user is identified by name and number. Certifications and Approvals . Keypads D1260Series Keypads (D1260 D1260W D1260R - D1260BLK,D1260B) UL Standards UL365, Police Station Burglar Alarm Units and Systems MB-G10-24-R Bell 24 V, 25.4 cm (10 in.) UL609, Local Burglar Alarm Units and Systems Modules C900V2 Dialer Capture Module UL864, Control Units for Fire-protective Signaling Sys- tems DI 25B Dual Class B Initiating Module UL985, Household Fire Warning System Units 0127 Reversing Relay Module UL1023, Household Burglar-alarm System Units D129 Class A Initiating Module UL1076, Proprietary Burglar Alarm Units and Systems UL1610, Central-station Burglar-alarm Units D130 Auxiliary Relay Module UL1635, Digital Alarm Communicator System Units D136 Plug-in Relay Approvals FCC: AJ9MLU-46532-AL-E D185 Reverse Polarity Signaling Module Factory Mutual D192C Notification Appliance Circuit Module CSFM: D192G Notification Appliance Circuit Module 7165-0801:123, Control Units - Non-high Rise 08121A Derived Channel S.T.U. Five Zone (Non-UL) 7170-0801:175, Control Units - High Rise D8122 Derived Channel S.T.U. Five Zone (UL) D8125MUX Multiplex Bus Interface nstalIation/Configuration Notes - I 08125 POPEX Point Expander 081280 OctoPOPIT Eight Point Expander Compatible Products 08129 Octo-relay Module Keypads 01260 Series Keypads (01260,01260W, 01260R, 09127 Series POPIT Modules D1260BLK, D1260B) 09131A Printer and Parallel Interface Module 0720 Series Keypads (0720,0720W, D720R, D720B) D9210BLC Access Control Interface Module 01255 Series Keypads (D1255, 01255W, 01255R, DS7432 Eight-input Remote Module D1255B, 01255RB) DS7457i Series Single Zone Multiplex Input Modules 01256 and 01256RB Fire Keypads DS74601 Two-input Module D1257 and 01257RB Remote Fire Alarm Annunciators DS7461i Single-input Multiplex Module W 0279A Independent Zone Control DS7465i Input and Output Module Detectors 0D850 Series Outdoor TriTech Detectors DX4010i RS-232 Serial Interface Module MX250 Series Smoke Detectors 0X4020 Network Interface Module MX775i Addressable PIR Detector Peripheral Hard- rvm4c Remote Video Module MX794i Long Range Multiplex PIR Detector ware MX934i Addressable PIR Detector Programming D5200 Series Programmers MX938i Addressable PIR Detector RPS or APS-Lite Remote Programming Software ZX776Z PIR Detector Readers ARD-R10 iCLASS Mullion Reader ZX794Z Long Range PIR Detector ARD-1140 iCLASS Switchplate Reader ZX835 Trilech Microwave/PIR Detector ARD-RK40-09 iCLASS PIN Reader ZX935Z PIR Detector ARD-VSMART iCLASS Reader ZX938Z PIR Detector D8201/W Series Low-profile Readers ZX970 PIR/Microwave Detector 08203/W Series Mullion Proximity Readers Bosch conventional detectors include Blue Line, seis- D8223 Prox Pro Reader mic, PIR, Trilech PIR Microwave, photoelectric, and D8224 Mullion Reader heat, and smoke. D8224-SP Switch Plate Reader Enclosures 08103 Universal Enclosure D8225 Mini Mullion Reader 08108A Attack-Resistant Enclosure 08227 Insert Card Reader D8109 Fire Enclosure 08301/W Series Low-profile Proximity Readers Magnetic Contacts All Bosch magnetic contacts, including recessed, termi- nal connection, miniature, overhead door, and surface 08302 Vandal-resistant Reader mount. 083031W Series Mullion Proximity Readers Bells 0440 Bell 12 V, 15 cm (6 in.) 08304/W Series Extended Range Proximity Readers 0441 Bell 24 V, 15 cm (6 in.) WP644 Series Waterproof Pass-through Readers MB-G10-12-R Bell 12 V, 25.4 cm (10 in.) www.boschsecurity.com Is Keypads D1260 Series Keypads (01260, D1260W, 01260R, D12608LK, D12608) SAFECOM Radio SC2 104 Series Slave Communicators Communicators SC3 100 Series Data Transfer Radio Communicators SC4000 Series Full Data Transfer Radio Communicator Wireless Products D8125lNV Wireless Interface FA113 Keychain Remote Control FA116 Executive Programmer FA202 Wireless Smoke Detector and Transmitter FA203S Necklace Pendant Transmitter (Single-button) FA203D Necklace Pendantlransmitter(Double-button) FA204 Necklace Pendant Transmitter FA205S Belt Clip/Loop Transmitter (Single-button) FA205D Belt Clip/Loop Transmitter (Double-button) FA206DS PIR Transmitter FA206i PlR Transmitter FA209 Billtrap Transmitter FA210 Universal Transmitter (Off-white) FA2 1O-BN Universal Transmitter (Brown) FA2 lOW Universal Wide Gap Transmitter (Off-white) FA21OW-BN Universal Wide Gap Transmitter (Brown) FA2 16L Low Temperature Transmitter FA2 16H High Temperature Transmitter FA2235 Water-resistant Pendant (White Single-button) FA223D Water-resistant Pendant (Black Double-but- ton) FA250 High-power Universal Transmitter FA400 Remote Receiver FA404R Transmitter Receiver FA41611 Transmitter Receiver FA570 High Power Indoor Repeater FA575 High Power Indoor/Outdoor Repeater Parts Included D7412G Components Quantity D7412G Board 1 Mounting Skirt 1 Faceplate with 07412G Label 1 • r4:D7412G Control Panel Technical Specifications Communications SDI Bus A(+): 9VDC 4572 m (15,000 it) SDI Bus B (-): 9 VDC 4572 m (15,000 it) Telephone Connection: • Two TelCo lines 0928 Dual Phone Line module required for 2 phone lines Environmental Considerations Relative Humidity: 5%to85%at+30°C(+86°F), non-con- densing Temperature (Operating): 0°C to +50°C (+32°F to +122°F) Number of... Areas: 8 Card Readers (Doors): 2 Credentials (Tokens): 396 Custom Functions: 4 Events: Store up to 1,000 Hardware Addresses: 75 Parallel Printers: 1 Passcode Users: 99, plus 1 service passcode Points: 75 (8 on-board, up to 67 off-board) Programmable Relay Outputs: 67 RFPoints: 67 SKEDs: 40 Power Requirements Current Draw (Minimum): 200 mA Current Draw (Maximum): 500 mA Output (Alarm): 2 A at 12 VDC Output (Auxiliary, Continuous Pow- 1.4 A at 10.2 VDC to 13.9 VDC er, and Switched Auxiliary com- bined): Voltage (Operating): 12 VDC Voltage (AC): 16.5 VAC 40 VA plug-in transformer (01640) Voltage (DC): Upto 212 VDC, 7 Ah sealed lead acid rechargeable batteries Upto2 12 VDC, 18Ahsealed lead acid rechargeable batteries S Ordering Information D7412G Control Panel D7412G Includes one printed circuit board (PCB). D7412G Attack-Resistant Kit 07412G-A Includes one PCB, one D8108A Attack-Re- sistant Enclosure, and one D1640 Trans- former. 07412G Fire and Burglar Kit D7412G-B Includes one PCB, one D8109 Fire Enclo- sure, one D928 Dual Phone Line Switcher, and two D161 Dual Modular Phone Cords. D7412G Commercial Burglar Kit D7412G-C Includes one PCB, one D8103 Enclosure, and one D1640 Transformer. D7412G Commercial Burglar Kit D7412G-D Includes one PCB, one D6103 Enclosure, and one 01640 Transformer. Accessories lCP-EZTS Dual Tamper Switch ICP-EZTS Combination tamper switch with a wire loop for additional tamper outputs. [D7412G Kit Ordeg information T _______________ - Components Kili D7412A D7412CB D74120-C 074120 Board 01640 Transformer 1 1 1 1 08103 Enclosure with 0101 Lock and Key Set 08108A Attack-Resistant Enclosure with 0101 Lock and Key Set 1 08109 Fire Enclosure with 0101F Lock and Key Set 1 06103 Enclosure with 0101 Lock and Key Set 1 0122 Dual Battery Harness 1 0928 Dual Phone Line Switcher 1 0161 2.1 nn (7 It) Dual Modular Phone Cords 2 D101 Lock and Key Set Standard lock set with one key supplied. Uses the D102 (1358) replacement key. D122 Dual Battery Harness Harness with circuit breaker. Connects two batteries to a compatible control panel. D122L Dual Battery Harness with Long Leads Color-coded harness with circuit breaker and leads measuring 89 cm (35 in.). Con- nects 12 V batteries to compatible control panels. D126 Standby Battery (12 V, 7 Ah) Sealed lead-acid standby and auxiliary re- chargeable power supply. D137 Mounting Bracket Used to mount accessory modules in D8103, 08108A, and D8109 enclosures. 0122 D122L D1O1 D138 Mounting Bracket, Right Angle 0138 Used to mount accessory modules in 08103, D8108A, and 08109 enclosures. Ordering Information - D168A Telephone Remote Arming Module D168A A remote control module that arms or dis- arms a security system remotely or locally through a telephone. D928 Dual Phone Line Switcher D928 Allows the control panel to operate over and supervise two separate phone lines. Only one D162 phone cord is supplied. Two ad- ditional D161 or D162 phone cords are required. D1218 Battery (12 V. 18Ah) D1218 A 12 V sealed lead-acid battery for standby and auxiliary power with two bolt-fastened terminals. Includes hardware for attaching battery leads or spade connectors D1224 Battery (12 V, 24Ah) D1224 A 12 V seated lead-acid battery for standby and auxiliary power with two bolt-fastened terminals. Includes hardware for attaching battery leads or spade connectors. D1238 Battery (12V,38Ah) 01238 A 12 V sealed lead-acid battery for standby and auxiliary power with two bolt-fastened terminals. Includes hardware for attaching battery leads or spade connectors. 01640 Transformer 01640 System transformer rated at 16.5 VAC, 40 VA. D8103 Enclosure D8103 Grey steel enclosure measuring 41 cm 41 cm x 9 c (16 in. x 16 in. x 3.5 in.). D8109 Fire Enclosure 08109 Red steel enclosure measuring 40.6 cm 40.6 cm 8.9 cm (16 in. x 16 in. x 3.5 in). UL Listed. Includes a lock and key set. D9002-5 Mounting Skirt 09002-5 Mountsinside D8103, 08108A, and D8109 enclosures. Can accept up to six standard 7.62 cm 12.7 cm (3 in. x 5 in.) cards. 08108A Attack Resistant Enclosure D8108A 0126 Grey steel enclosure measuring 41 cm x 41 cm x 9 c (16 in. x 16 in. x 3.5 in.). UL Listed. Includes lock and key set. Requires D137 the D2402 Mounting Plate. www.boschsecurity.com 6 1 D7412G Control Panel S I .Ordering- Information D136 Plug-In Relay D136 Maximum rating is 1 A at 24 VDC or 2 A at 12 VOC. Available individually (D136) or in a package of 25 (D136-25). Software Options RPS Kit (LPT) D5500C-LPT Account management and control panel- programming software with LPlconnection. RPS Kit (USB) D5500C-USB Account management and control panel- programming software with IJSB connec- tion. Europe. Middle East. Afrlc& Americas Bosch Security Systems B.V. Bosch Security Systems, Inc. P.O. Box 80002 130 Perinton Parkway 5600 JO Eindhoxen, The Netherlands Fairport, Now York, 14450, USA Phone: + 3140 2577 284 Phone: -1800 289 0096 Fax.: 2577 330 Fax: +15852239180 emea.securitysyxtems@bosch.com secxrity.satex@us.bosch.com www.boschsecunty.com www.hoschsecurity.us Asla'Paclflc, Bosch Security Systems Pte Ltd 38C Joian Pestimpin Singapore 577180 Phone: +65 6319 3450 Fax: +65 6.319 3499 apr.securitysystems@bosch.com www.boschsecurity.com Represented by © Bosch Security Systems 2006 I Data subject to change without notice F1699480203 I Cur: en-US, V4, 27 Sep 2006 o moscm Invented for life D1255 Series VFD Keypads bccm hii i2 Each D1255 Series VFD Keypad model is an SDI bus compatible device that works with the G Series Control Panels and the D9124 Addressable Fire Alarm Panel. Each keypad model has an illuminated keypad, 16- character English language vacuum fluorescent display (VFD), and a sounder that emits eight tones. Functions Display Every D1255 Series Keypad model uses words, numbers, and symbols to show the status of the security system. When several events occur, each model shows each event in order of priority. Keys Each D1255 Series Keypad model has 10 numeric keys and five function keys. Use the [COMMAND] key with the numeric keys to perform a function. Use the [ENT] key or [YES] key to enter your passcode. When pressed, each key emits light and a muted beep. Audible Tones The sounder emits eight distinct warning tones. You can adjust the volume or use a passcode to silence the tone. The tones include: Easy to read vacuum fluorescent display (VFD) Easy system control with menu keys User controlled brightness and volume Installer configured menus, text, and custom functions Multiple or single area configurations Burglary Signal: Steady high-pitched bell tone during alarm. Fire Signal: Pulsed high-pitched bell tone during fire alarm. Entrance Warning: Intermittent beep tones during entry delay periods. Exit Warning: Intermittent beep tones during exit delay periods. Invalid Key Buzz: Buzz tone when an invalid key is pressed. Keypad Encoding Tone: Muted beep tone as each key is pressed. Trouble Buzzer: Two-tone warble during a trouble event. Watch Tone: Intermittent beep tone when a watch point is faulted. System Overview Use D1255 Series Keypad models in applications for system controllers and annunciators: For commercial use, install the keypad in building entrances and areas with unrestricted access. Mounting a keypad near exterior doors in hotel or business lobbies allows people to identify the type and location of the emergency. S www.boschsecurity.com For residential use, install the keypad near the front Technical Specifications • and rear entrances to the home. Install additional keypads in a kitchen or in a bedroom. Connections Use multiple keypads in a large building with many Connections: 4-wire flying lead for data and power separate areas of security. Program multiple keypads - to control multiple areas. Resistance: 25 () maximum Install the keypad in locations that are hidden from Environmental Considerations view. Audible tones from the keypad sounder alert personnel to fire events and assist fire fighters in Temperature (Operating): 0°C to +50°C (+32°F to +122°F) - '- - locating the keypad. Relative Humidity: 5%to85%at+30°C(+86°F) Keypad Certifications and Approvals Dimensions for D1255. 11.7cmx21cmx2cm D1255W. and 01255R: (4.6 in. x 8.2 in. x 0.8 in.) Keypad Model Certifications and Approvals Dimensions for 012559: 12.6 cm 20 cm x 3.2 cm All Models U1365, Police Station BurgiarAlarm Units and Systems (Sin. x 7.9 in. x 1.3 in.) UL609. Local Burglar Alarm Units and Systems Weight for All Models: 439 g (15.5 oz) UL864, Control Units for Fire-protective Signaling Sys- Material for All Models: CHI MEl POLYLAC° PA757 ABS with UV Sta- tems bilizer. UL94-HB Fire Rated UL985, Household Fire Warning System Units Display Window: • 16-character vacuum fluorescent dis- UL1023, Household Burglar Alarm System Units play UL1076. Proprietary Alarm Units Each character is a 14-segment unit UL1610, Central-station Burglar-alarm Units Indicators: • Illuminated keys UL1635, Digital Alarm Communicator System Units Warning and indicating tones D1255,01255R. CSFM Number of... and 01255W 01255 Only FM. MEA 01255 Series Keypad Models Eight supervised 32 unsupervised per Control Panel: Installation/Configuration Notes Power Requirements Voltage: Nominal 12 VDC Compatibility Information Current: Idle 104 mA, armed or disarmed Maximum Control Panels with 09412G. 07412G, D9412, D7412, D7212, D9112, and 206 mA. with keypad lit and warning tone on SDI Bus 09124 Trademarks 072 12G with firmware version 6.41 or higher POLYLAC° is a registered trademark of CHI MEl Industrial Corporation, LTD. Mounting Considerations Plexiglas' is a registered trademark of Arkema. Do not mount any of the D1255 Series Keypad models in a location exposed to direct sunlight. Direct sunlight can interfere with screen visibility and Ordering Information damage internal components. 01255 VFD Keypad 01255 Do not mount any of the D1255 Series Keypad models Off-white classic case. in damp locations. 01255W VFD Keypad 01255W White classic case. Power Supplies 01255R VFD Keypad 01255R Red classic case. A compatible control panel supplies the power and data D1255B VFD Keypad 01255B requirements to a D1255 Series Keypad model through White and gray modern case. a four-wire connection. Hardware Accessories Wiring Considerations 0548 Brass Flush Mount Kit 0548 Back box and polished brass faceplate. Use 0.8 mm (22 AWG) or 1.2 mm (18 AWG) wire. D54C Stainless Steel Flush Mount Kit 054C Resistance cannot exceed 25 U. Each D1255 Series Back box and stainless steel faceplate. Keypad model includes a wiring assembly of four color- 055 Keypad Desk Stand 055 coded flying leads and one female four-pin connector. Portable desk stand in smoke colored Plexiglas°. - D1255 Series VFD Keypads 13 . Ordering Information D56 Surface Mount-Conduit Box D56 White surface mount box. 056R Red Surface Mount Conduit Box D56R Red surface mount box. Americas: Europe. Middle East, Africa. Bosch Security Systems Bosch Security Systems B.V. 130 Perinton Parkway P.O. Boo 80002 Fairport, New York. 14450, USA 5600 JS Eindhoven, The Netherlands Phone: +1585 223 4060 Phone: +3140 27 83955 Fax: -1800 289 0096 Fax: +3140 27 86668 security.sales@us.bosch.com emea.securitysystems@bosch.com www.boschsecurity.us www.boschsecurity.com © Bosch Security Systems 2006 I Data subject to change without notice F1157913099 I Cur: en-US, VS. 7 Feb 2006 Aala'Pacmc Bosch Security Systems Pte Ltd 38C Jalan Pernimpir, Singapore 577180 Phone: *65 6319 3450 Fan: +65 6319 3499 apr.securitysystems@bosch.com www.boschsecority.com Represented by Intrusion Systems I D8125 Addressable Expansion Module O BOSCH Invented for life D8125 Addressable Expansion Module Provides point identification of initiating devices Supervises wiring to devices for circuit integrity Expands the number of points in the system Compact size Terminal connections for reliability Multiplex technology Low installation costs The D8125 Addressable Expansion Module works with the D9127U or D9127T POPIT Modules to provide multiplex technology that combines zone or point supervision with individual device addressing on one pair of wires. Use the D8125 to provide expansion beyond the standard number of control panel zones, up to a total of 240 points. Each D8125 module can fully supervise 120 D9127U or D91271 POPIT Modules. System Overview Each D8125 installs in the control panel enclosure or in an adjacent approved enclosure. Future system expansion is very economical as D9127U or 09127T POPITs can be spliced in anywhere along the two-wire data expansion loop from the D8125 module. The D9127 is a compact, addressable device that is suitable for applications where specifications call for point identification from each initiating device or series of devices. The units are small, and easily installed in standard outlet boxes, above false ceilings, closets, or other accessible locations. The D8125 includes a 33 kc) end-of-line (EOL) resistor. Install the resistor at the farthest point on the loop for proper supervision. www.boschsecurity.com Technical Specifications Properties Dimensions: 13cm x 8cm x 2cm (5 in. x 3 in. x0.75 in.) Power Requirements Current Draw: 50 mA for each 08125 module Voltage (Operating): 12 VDC Certifications and Approvals Region Certification USA UL AMCX: Central Station Alarm Units (UL1610, UL1635), AMCX7: Central Station Alarm Units Certified for Canada (cULus), AOTX: Local Alarm Units (UL464, UL609), AOTX7: Local Alarm Units Certified for Canada (cULus), APAW: Police Station Alarm Units (UL365, UL464), APAW7: Police Station Alarm Units Certified for Canada (cULus), APOU: Proprietary Alarm Units (UL1076), APOU7: Proprietary Alarm Units Certified for Canada (cULus), NBSX: Household Burglar Alarm System Units (UL1023), NBSX7: Household Burglar Alarm System Units Certified for Canada (cULus), UOJZ: Control Units. System (UL864. 9th edition), UTOU: Control Units and Accessories - Household System Type (UL985), UTOU7: Control Units and Accessories - Household System Type Certified for Canada (cULus) FM CSFM 7167-1615: 100,7165-1615: 113, 7165-1615: 119, 7170-1615: 144, and NYC-MEA 7170-1615:145 12-92-E, Vol. 11 12-92-E, Vol. 11 12-92-E, Vol. 12 12-92-E, Vol. 12 12-92-E, Vol. 15 12-92-E, Vol. 15 Australia C-Tick Ordering Information D8125 Addressable Expansion Module Provides expansion up to 240 points. Accessories D9127U POPIT Module No tamper switch. D91271 POPIT Module Includes a magnetic tamper switch. D8125 D9127U D91271 Installation/Configuration Notes Compatibility Information Control Panels D9412GV2, D7412GV2, D72 12GV2, D9412G, D7412G, D7212G, D9412, D7412, 07212, 07212B1,09112, D9112B1, D8112G1,D8112G2, and D9124 Parts Included Quantity Component 1 Expansion board 1 Hardware pack 1 Literature pack Represented by Americas: Europe, Middle East, Africa: Bosch Security Systems, Inc. Bosch Security Systems B.V. 130 Perinton Parkway P.O. Boo 80002 Fairport, New York, 14450, USA S 5600 JS Eindhoven, The Netherlands Phone: +1800 289 0096 Phone:, 3140 2577 284 Fan: 41 585 223 9180 Fax: -+31 40 2577 330 security.sales@us.bosch.com emea.securitysystems@bnsch.com www.boschsecority.us www.boschsecurity.com Asia-Pacific, Bosch Security Systems Pte Ltd 38C Jalan Pemirnpin Singapore 577180 Phone: +65 6319 3450 Fax: +65 6319 3499 apr.securitysystemsQbosch.com www.boscksecurity.com Bosch Security Systems Inc. 20081 Data subject to change without notice 71158865031 I Cur: en-US, V4, 7 Feb 2008 UL NBSX: Household Burglar Alarm System Units (UL 1023) UL UOJZ: System Control Units (UL864) UL UTOU: Control Units and Accessories - Household System Type (UL985) Installation/Configuration Notes Compatibility Information Control Panels D9412GV2, 07412GV2. D7212GV2, D94126, D7412G, D7212G, D9412, D7412, 07212, 07212B1, 09112, 09112B1, D8112G1, 08112G2, and D9124 Module 08125 The D8125 Multiplex Zone Expander is required. The D9127 modules are wired in parallel on the D8125 data loop. Number of POPIT Modules per Control Panel D7212G, D7212GV2 3209127 POPITs 07212B1 40 09127 POPITs D7212, D7412, D7412G, D7412GV2 67 D9127 POPITs D9124 119 D9127 POPITs D9112B1 126D9127POPITs D9112, D9412, D9412G, D9412GV2 23809127 POPITs Intrusion Systems I D9127 Series POPIT Modules 0 BOSCH 0 Invented for life D9127 Series POPIT Modules The D9127 Series POPIT Modules includes the D91271 (with magnetic tamper switch) and the D91271J (without tamper). They are used with a D8125 Addressable Expansion Module when there is a need to expand a compatible control panel beyond its standard number of on- board initiating zones or points. Future system expansion is very economical as D9127 Series POPITs can be added anywhere along the two-wire data expansion loop from the D8125 module. Both modules include proven technology that combines zone and point supervision with individual device addressing on one pair of wires. Screw terminals provide reliable connections for the data expansion loop and supervised sensor loop wiring. Install a 33 kID end-of-line resistor at the farthest point on the loop for proper supervision. The units are small and easily installed in standard outlet boxes, above false ceilings, closets, or other accessible locations. Certifications and Approvals Listings and Ap- UL AMCX: Central Station Alarm Units (UL1610) provals: UL AOTX: Local Alarm Units (UL464) UL APAW: Police Station Alarm Units (UL365) ULAPOU: Proprietary Alarm Units (UL 1076) S Provides point identification of initiating devices Supervises wiring to devices for circuit integrity Expands the number of points in the system Compact size Terminal connections for reliability Multiplex technology Low installation costs www.boschsecurity.com Wiring Considerations Wire Size Maximum Length D8125 to POPIT Loops Use one two-wire data expansion loop, or distribute the POPlTs on up to three loops. The maximum lengths shown in the following table are for all data expansion loops combined connected to the same D8125 module. Setting DIP switches on the POPIT modules assigns them to point numbers. The switch setting on each POPIT assigns it a point number, regardless of its physical location. of all Data Expansion Loops Combined 0.8 mm (22 AWG) 549m (1800 ft) 1.0 mm (20AWG) 881 m (2890 ft) 1.2mrn(18AWG) 1402m(4600it) 1.5 mm (16AWG) 2231 m(7320ft) 1.8 mm (14AWG) 3551 m (11650 ft) Technical Specifications - Environmental Considerations Relative Humidity: Up to 93% non-condensing Temperature (operating): 0°C to +50°C (+32°F to +122°F) Properties Color: Off white Dimensions: 8.1 cm 3.8 cm 2.4 cm (3.2 in. x 1.5 in. x 0.9 in.) Material: UL Listed fire-resistant Power Requirements Current Draw 0.8 mA maximum Resistance: Maximum increase in resistance on the POPIT loop is 10000. Maximum resistance between the 08125 module and each POPIT is 900. Voltage (operating): 12V DC nominal Sensor Loop POPIT to Sensor Loops The number of detection devices each sensor loop can Resistance: Maximum resistance on the sensor loop is 1000. supervise is limited only by the resistance on the loop. Response Time: 1 sec approximately Resistance on each sensor loop must be less than 100 C) not including the end-of-line (EOL) resistor. . .. . . - Certain UL and National Fire Protection Association (NFPA) Ordering Information applications can limit the number of detection devices. 09127T POPIT Module 09127T Consult the appropriate UL or NFPA standards. Includes a magnetic tamper switch. Terminate each POPIT sensor loop with the 33 kc) EOL D9127U POPIT Module 09127U resistor included with each POPIT. No tamper switch. Use a twisted-pair wire (six twists per foot) in all POPIT installations for both the data expansion loop wiring and the POPIT sensor loops. Run wires away from AC sources to prevent AC induction. Parts Included - - - Quantity Component 1 POPIT module 1 33 kf) EOL resistor 1 Magnet (09127T only) 1 Hardware pack 1 Literature pack Europe. Middle East, AJdcw Anronlcas, Asia-Pacific Bosch Security Systems B.V. Bosch Security Systems, Inc. Bosch Security Systems Pte Ltd P.O. Boo 80002 130 Porinton Parkway 38C Jalan Pernimnpin JB Eindhoven. The Netherlands Fairport, New York, 14450. USA Singapore 577180 ' 5600 Phone: • 3140 2577 284 Phone: xl 800 289 0096 Phone: +65 6319 3450 Fax: 3140 2577 330 Fax: +1585 223 9180 Fax: +65 6319 3499 emea.securitysystems@bosch.com securicy.salesus.boxch.com apr.securitysystems@bosch.com www.boschsecurlty.com www.boschsecurity.us www.boschsecurity.com © Bosch Security Systems 20061 Data subject to change without notice F5648218895 I Cur: on-US, V3,19 Sep 2006 Represented by Fire Alarm Systems I D273 Series Photoelectric Smoke and Smoke and Heat Detectors -IBOSCHJ i nvented for If t D273 Series Photoelectric Smoke and Smoke and Heat Detectors The D273 Series includes the following detector models: Model Description D273 Four-wire D273ES° Four-wire with sounder and end-of-line (EOL) relay D2731S' Four-wire with an isolated 135°F (57°C) heat sensor and sounder D2731H Four-wire with 135°F (57°C) heat sensor D273THC Four-wire with 135°F (57°C) heat sensor and auxiliary relay D273THCS° Four-wire with 135°F (57°C) heat sensor, auxiliary relay, and sounder cI!HII7 Four-wire with 135°F (57°C) heat sensor and EOL relay D273THR Four-wire with 135°F (57°C) heat sensor and trouble relay D273THS Four-wire with 135°F (57°C) heat sensor and sounder D273THES° Four-wire with 135°F (57°C) heat sensor, sounder, and EOL relay D273THSR° Four-wirewith 135°F (57°C) heatsensor, sounder, andtrouble relay * Sounders produce 85 dB at 10 ft (3 m). Each of the 0273 Series Detector models is UL Listed and works with commercial fire protective signaling and household fire warning systems. Each model detects smoke particles produced during wood, paper, and fabric combustion. 12 VDC or 24 VDC input Designed for commercial or residential use Four-wire application Light-emitting diodes (LEDs) indicate the status of the chamber, power, and alarm Removable terminal block to simplify wiring connections ' Cable connection point for voltmeter sensitivity test Trim Plate TP280 for retrofit and remodeling purposes Functions - - Chamber Calibration Tests Check the sensitivity and calibration of any 0273 Series Detector model using a visual check, a magnet test, or a voltage measurement test. Visual check: When the detector's calibration is within the factory-listed range, the red alarm LED flashes once every 35 sec. If the detector's calibration is out of range for more than 24 h, the red alarm LED flashes once a second. Magnet test: Hold a magnet horizontally against the detector for about 10 sec and observe the LED. If the detector is within the factory-listed calibration range, it goes into alarm and the Alarm LED latches on. If the detector is too sensitive, the LED rapidly flashes six times (once every half second) and the detector goes into alarm. If the detector is not sensitive enough, the LED slowly flashes four times, once every 6 seconds, and the detector goes into alarm. If the detector does not operate, it does not signal an alarm. Voltage measurement test: 0, www.boschsecurity.com • Use a 01005 Test Cable and a digital voltmeter to measure the voltage and compare the results with the factory-listed sensitivity range. System Overview The 0273 Series Detector models use an infrared (IR) LED light source and a silicon photodiode to measure light in a chamber. A fine screen covers the chamber to deter insects and reduce dust accumulation and nuisance alarms. During a fire, smoke particles reflect light onto the photodiode. When the photodiode measurements exceed the alarm threshold, the detector signals an alarm condition. After the alarm condition clears, interrupt power at the control panel to reset the detector. When a D132B Reversing Relay Module is used, the LED does not latch on alarm. Certifications and Approvals Listings and UROX: Smoke Automatic Fire Detectors (UL268) Approvals: UROX7: Smoke -Automatic Fire Detectors certified for Canada (S529) c-UL-us . CSFM: 72721615: 134 NYC/MEA: 274-93-E, Vol. VII Installation/Configuration Notes Use smoke detectors for detection circuits that protect people. Use heat detectors for circuits that protect property. Compatible Products The following products are compatible with the 0273 Series detectors: Category Product ID Product Description Control Pan- The D273 Series Detector models are compatible with UL Listed els four-wire control panels. Refer to the manufacturers installation instructions to select the correct EOL resistor. Modules D132B Reversing relay module Loop Supervision For loop supervision, install a Bosch Security Systems D275 Power Supervision Module and an EOL resistor after the last device on the loop. Mounting The detector has a mounting plate that attaches to a standard four-inch back box. For commercial and industrial installations in accordance with NFPA 72, space each detector 30 ft (9.2 m) apart. Wiring The terminal block accepts up to 12 AWG (2.3 mm) wire. You can remove the terminal block from the detector for easier wiring. The terminal block snaps in and out of the detector. Parts Included Quant. Component 1 Detector 1 Literature pack Ordering Information D273THES Four-Wire Smoke/Heat Detectorwith EOL D273THES Relay and Sounder D2 73THR Four-Wire Smoke/Heat Detector with Trou- D273THR ble Relay D273THS Four-Wire Smoke/Heat Detector with D273THS Sounder D273THSR Four-Wire Smoke/Heat Detector with D273THSR Sounder and Trouble Relay Hardware Accessories D275 Power Supervision Module D275 01005 Test Cable D1005 DT-2 Detector Removal Tool DT-2 TP280 Trim Plate TP280 • Technical Specifications Environmental Considerations Relative Humidity: Up to 93%, non-condensing Operating and Storage +32°F to +120°F (0°C to +40°C) Temperature: Radio Frequency No alarm or setup on critical frequencies in the Interference (RFI) range of 26 MHz to 950 MHz. Immunity Mechanical Properties Dimensions (Diameterx H): 5 in. x 2 in. (12.7 cm 5.1 cm) Material: High impact, fire retardant ABS plastic Power Requirements Power-up Time: RMS Ripple: Voltage (stand-by): Current Draw (alarm) at 30 VDC 0273, D2731H: 18 mA maximum D273THC: 33 mA maximum D273THE. D273THR: 36 mA maximum D273THS: 78 mA maximum D273THCS: 90 mA maximum D273ES, D273THES, D273THSR: 96 mA maximum 02731S: 100 mA maximum Current Draw (standby) D273. D273TH, D27THC, D273THCS, 0.1 mA maximum D273THS: 02731S: 0.14 mA maximum D273E5, D273THE, D273THES, 15 mA D273THSR D273THR: 18 mA maximum Ordering Information 0273 Four-Wire Smoke Detector D273 D273E5 Four-Wire Smoke Detector with EOL Relay D273ES and Sounder D273I5 Four-Wire Smoke Detector with Isolated Heat 0273 IS Sensor and Sounder D2731H Four-Wire Smoke/Heat Detector 0273TH D273THC Four-Wire Smoke/Heat Detector with Aux- D273THC iliary Relay D27311-ICS Four-Wire Smoke/Heat Detector with D273THCS Auxiliary Relay and Sounder D273THE Four-Wire Smoke/Heat Detector with EOL D273THE Relay 22 sec maximum 25% of DC input maximum 10 VDC to 30 VDC Americas: Europe, Middle East, Afrtc& Bosch Security Systems Bosch Security Systems B.V. 130 Perinton Parkway P.O. Box 80002 Fairport, New York. 14450. USA 5600.18 Eindhoven, The Netherlands Phone: -1585 223 4060 Phone: +3140 21 83955 Fax: +1 800 289 0096 Fax: +3140 27 86668 security.5a1e51955.bxxch.cxm emea.securitysystems@bosch.com www.bosctsecurity.us www.boschsecurity.com Asia-Pacific: Bosch Security Systems Pte Ltd 38C Jxlan Pemnimnpin Singapore 577180 Phone: c65 6319 3450 Fax: *65 6319 3499 apr.securitysystemstxosch.com www.boschxecurity.com Represented by © Bosch Security Systems 2006 I Data subject to change without notice F1341903627 I Cur: en-US, V2, 25 Jan 2006 0BOSCH www.tucanobrasil.com.br Invented for life FMM-100 Series Die-cast Metal Fire Alarm Manual Stations Single or dual action Terminal connections Gold-plated alarm contacts for corrosion resistance Surface or weatherproof back boxes The FMM-100 Series is a family of versatile, high-quality, metal fire alarm manual stations. Single-action or dual- action models are available. All models come with a key lock and contain gold-plated contacts to resist corrosion. Functions Operation Single-action When the bar on the front of the manual station is pulled, it latches open and is easily visible from 50 ft (15 m). Reset the activation bar by opening the manual station with the key and placing the activation bar in its normal upright position. An optional scored acrylic break rod is available. Dual-action With the dual-action configuration the upper bar on the front of the manual station rotates inward allowing the activation bar to be grasped and operated by a single hand. Certifications and Approvals Listings and UL UNIU: Boxes, Non-coded (UL38) Approvals: UL UNIU7: Boxes, Non-coded Certified for Canada (CAN/ ULCS528M91) CSFM 71501615:224 NYC/MEA (382-94-E, Vol. 3) Installation/Configuration Notes Compatibility Information Compatible with all Bosch Security Systems Fire Alarm Control Panels. Mounting Considerations The FMM Series manual stations can be surface mounted on either the FMM-100BB-R Surface-mount Back Box or the FMM-100WPBB-R Weatherproof Back Box. They can also be flush mounted on a standard single-gang back box. Note When properly mounted on the FMM-100WPBB-R Weatherproof Back Box, these manual stations meet UL requirements for outdoor use. To comply with ADA standards, the manual station must be less than 48 in. (1.2 m) above the floor for front www.tucanobrasil.com.br .wheelchair access and less than 54 in. (1.3 m) above the floor for side wheelchair access. Parts Included Quant. Component 1 Manual station 1 D102 Key (1358 key) 1 FMM-100GR Acrylic Break Rod 1 Hardware pack 1 Literature pack Technical Specifications Environmental Considerations Relative Humidity: 90% at +100°F (+38°C) Temperature (operating): -40°F to +150°F (-40°C to +66°C) Mechanical Properties Color: Red Dimensions (H x W x D): 4.75 in. x3.25 in. xl.l in. (12cmx8.3cmx2.8cm) Material: die-cast metal Inputs Switch Rating: 1 A at 30 VDC or 125 VAC • Distribuiçao: Alarmes Tucano Ltda R. Des. AntOnio de Paula, 3577 - Boqueirao - Curitiba - Pr Fone/fax: (41) 3286-2867 - Cep: 81720-280 tucano@tucanobrasil.com.br www.tucanobrasil.com.br 0 Ordering Information FMM-100SATK Single-action Manual Station (red) FMM-100SATK FMM-100SATK-NYC Single-action Manual Station for FMM-100SATK-NYC New York City FMM-100DATK Dual-action Manual Station (red) FMM-100DATK Hardware Accessories D102 Replacement Key 0102 FMM-100BB-R Surface-mount Back Box (red) FMM-100BB-R FMM-100WPBB-R Weatherproof Back Box (red) FMM-100WPBB-R FMM-1006R Scored Acrylic Breakrods FMM-100GR COOPER Notification Series AS Audible Strobe Appliances and Series AH Audibles SERIES AS SERIES AH Description The Wheelock patented 2-wire Series AS Audible Strobe Appliances and Series AH Audibles offer more features with low current draw. Strobe options for wall mount models include 1575cd or the Wheelock patented MCW multi-candela wall strobes with field selectable candela settings of 15/30175/110cd, or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models incorporate Wheelock's patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30175/95cd or the high intensity MCCH strobe with field selectable 115/177cd. The audible provides a selectable choice of either a continuous horn or temporal pattern (Code 3) when constant voltage from a Fire Alarm Panel (FACP) is applied. Each tone has 3 dBA settings to choose from. When used with the Wheelock Series SM,DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol, synchronization of the continuous horn tone provides the temporal (code 3) tone (mandated by NFPA72) simultaneously for all audible appliances. This ensures a distinct temporal (code 3) pattern when 2 or more audibles are within hearing distance. If not synchronized the temporal sound could overlap and not be distinctive. At the same time the strobes will be synchronized. This provides the ability to comply with ADA guidelines concerning photosensitive epilepsy and the NFPA standards when installing 2 or more visual appliances within the field of view all of this plus the ability to silence the audible is achieved by using only 2 wire. Features Approvals include: UL Standard 1971, UL Standard 464 New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information ADA/NFPAIUFC/ANSI Compliant Wall mount models are available with Field Selectable Candela Settings of 151301751110cd or 1351185cd (Multi- Candela models) or 1575cd (single candela model) Ceiling mount models are available with field selectable candela settings of 15/30/75195cd or 115/177cd (multi-candela ceiling models) Selectable Continuous Horn or Temporal (Code 3). 3 Selectable dBA settings (99, 95 and 90 dBA) in both tones Patented 2-Wire Audible Strobe Appliance. Patented Universal Mounting Plate Weatherproof models are available for outdoor use Strobes produce 1 flash per second over the regulated voltage range 12 and 24 VDC models with wide UL "Regulated Voltage Range" using filtered DC or unfiltered FWR input voltage Synchronize using the Wheelock Sync Modules or panels with built-in Wheelock Patented Sync Protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires For Weatherproof Series AS, See Datasheet S9004 (D ~:-,; Ik <g> MEA APPROVED E5946 151-92-E 7125-0785:131 S5391 Table 4: Average Current* (AMPS) For Series ASWP Voltage High dBA Setting (99) dBA Medium dBA Setting (95) dBA Low dBA Setting (90) dBA 24.0 VDC 0.128 0.105 0.098 UL Max* 0.168 0.155 0.150 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. NOTE: All CAUTIONS and WARNINGS are identified by the symbol a. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR PERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU 0/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their "Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of I to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range". Table 1: Ratings Per UL 1971 Model Number Input Voltage VDC Regulated Voltage Range VDC/FWR Strobe Candela (cd) AS-24MCW 24 16.0-33.0 15/30/75/110 AS-24MCCH 24 16.0-33.0 115/177 AS-241575W 24 16.0-33.0 15(75onAxis) AS-121575W 12 8.0-17.5 15 (75 on Axis) AS-24MCC 24 16.0 -33.0 15/30/75/95 AS-24MCWH 24 16.0-33.0 135/185 ASWP-2475W 24 16.0-33.0 75 @ -31°F Table 2: dBA Ratings for 12 VDC and 24 VDC Series AS/ AH 12 and 24 VDC Audible Reverberant Anechoic Description Volume dBA Per t464 dBA @10 ft. @10 ft. High 91 99 Continuous Medium 88 95 Horn Low 83 90 High 87 99 Medium 84 95 Code 3 Horn Low 79 90 Table 3: Average RMS Current 24 VDC Models Audible AH-24 AS-241575V' 1575cd High (99) dBA 24 vdc 0.062 0.100 UL max* 0.080 0.121 Med (95) dBA 24 vdc 0.033 0.080 UL max* 0.043 0.107 Low (90) dBA 24 vdc 0.017 0.072 UL max* 0.021 0.100 12 VDC Models Audible Wall Mount Audible Strobe AH-12 AS-121575W Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models AS-24MCW AS-24MCWH AS-24MCC AS.24MCCH 15cd 30cd 75cd llocd 135cd 185cd 15cd 30cd 75cd 95cd 11 5c 177cd 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 High (99) 12 vdc __ 0.163 0.260 _______ UL max" 0.192 0.320 dBA Med (95) 12 vdc 0.076 0.195 ULmax° 0.108 0.275 dBA Low (90) 12 vdc 0.039 0.175 UL max* 0.058 0.265 dBA Wiring Diagrams" 'SERIES AS APPLIANCES NON-SYNCHRONIZED I FROMD I I PRECEDING TO NEXTO I APPLIANCED - _PPLIANCED I OR EOLRD OR FACPD SERIES AS & RSS APPLIANCES SYNCHRONIZED WITH PS-121244CP and PS-12/24-8MP OUTPUTSD ::C eOLRQ FD 1-40 - 4-CLASSO AD PSJ Bll ASO RSSO CLi 2-CLASSO P 11 ASO P950 Sri P5-12/24-8 PD or PS-12/24-8MP SERIES AS APPLIANCES SYNCHRONIZED WITH DSM MODULE CLASS"A" NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE Specifications and Ordering Information 10 nSTROBEO Strobol -DsTROBEO LI co Circuit[ uSudib *0 AudibleD udib *0 NACO CircuitO Strobe NAC Cir 2 1 FL] Audible NAC IlE A —Strobe NAC .yncO co Audible PD N yncU Strobe NAC C -t~ F DSM Interconnecting wiring shown. Maximum twenty (20)0 For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring informationon the power supplies refer to Installation Instructions P84662 for PS-24-8MC. SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SIN- GLE CLASS "B" NAC CIRCUIT WITH AUDIBLESILENCE FEATURE SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES - .........DSM #10 Model Number Order Code Strobe Candela N Sync DSM Sync w/SM, or 24 VDC 12 VDC Wall Mount Ceiling Mount Mounting Options* Agency Approvals AS-24MCW-FR 9024 15/30/75/110 X X X - X - ABD,EF,G,H,JNO,R,X X X X X X AS-24MCW-FW 9025 15/30/75/110 X X X - X - AB,D,EF,G,HJNOR,X X X X X X AS-24MCWH-FR 3468 135/185 X X X - X - A,BD,EFG,HJ,NOR,X X X X X * AS-24MCWH-FW 3469 135/185 X X X - X - AB,D,EFG,HJN,O,R,X X X X X * AS-241575W-FR 7405 115(75onAxis) X X X - X - A,6,DE,F,GH,J,N,OR,X X X X X X AS-121575W-FR 7410 15 (75 on Axis) X X - X X - AB,DE,F,G,H,J,N,O,R,X X X X X X) AS 24MCC FR 3161 15/30/75/95 X X X - X A B D E FG H J N OR X X X X X * AS-24MCC-FW 3162 15/30/75/95 X X X - - X A,BD,E,FG,H,J,NOR,X X X X X * AS-24MCCH-FW 3467 115/177 X X X - - X A,B,D,E,GHJN,O,R,X X X X X * ASWP2475WFR** 9012 75 @ -31°F X X X - X - I(see Data Sheet S9004) X X X X X AH-24-R 7892 - X X X - X X A,BDE,FG,H,JN,O,R,X X X X X X AH-24-W 7893 - X X X - X X A,BD,E,G,HJN,OR,X X X X X X AH-12-R 7891 - X X - X X X A,B,D,E,F,GHJ,N,OR,X X X X X X AH-12-W 7894 - X X - X I X I X AB,D,E,FGH,JN,O,R,X X X X X X AH24WPR** 7416 - X X X - X X K X X X - X \H12WPR** 7415 - X X - X I X I X K X X X I X **For Weatherproof Series AS/AH specifications see data sheet S9004. *PENDING ***Refer to Data Sheet S7000 for Mounting Options. Note: Models are available in either Red or White. Contact Customer Service for Order Code and Delivery. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice In accordance with Wheelock Inc. standard terms and conditions. S8100 AS/AH 10/07 Notification Architects and Engineers Specifications The notification appliances shall be Wheelock Series AS Audible Strobe appliances and Series AH Audible appliances or approved equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling). Both shall meet the requirements '1 FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm ..ontrol Panel (FACP). The audible portion of the appliance shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal (Code 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series AS shall be of low current design. Where Multi- Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110 or 135/185 candela for wall mount and 15/30/75/95 or 115/177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e. contacts remain closed), the strobe shall revert to a non-synchronized flash-rate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock synchronization. The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single-gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. [Member - WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA Series RSS and RSSP Strobes and Strobe Plates Series RSS Series RSS Series RSSWP RSS Round Description The Wheelock patented Series RSS Strobe Appliances and Series RSSP Strobe Plates have lower current draw while maintaining outstanding performance, reliability and cost effectiveness. These versatile appliances will satisfy virtually all requirements for indoor, wall or ceiling mount applications. Strobe options for wall mount models include 1575 or the Wheelock Patented MCW multi-candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models include the patented MCC multi-candela ceiling strobe with field selectable intensities of 15130/75195cd or the high intensity MCCH strobe with field selectable 115/177cd. All models may be synchronized using the Wheelock SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels incorporating the Wheelock Patented Sync Protocol. Synchronized strobes can eliminate possible restrictions on the number of strobes in the field of view. Wheelock's synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy as well as meeting the requirements of NFPA 72. The Wheelock Series RSS Strobes employ a Patented Integral Strobe Mounting Plate that can be mounted to a single gang, double gang, 4" square, 100mm European backboxes or the SHBB surface backbox. If the flush backbox has side or top space between it and the finished wall, the NATP (Notification Appliance Tnmplate) may be used. It provides an additional .65" of trim for the Appliance. An attractive cover plate is provided for a dean, finished appearance on all models. The Series RSSP Multi-Candela Strobe Plates are a cost effective way to retrofit required wall strobe appliances to bells, horns, chimes, multitones or speakers and easily mounts to standard 4" backboxes or for surface mount use with the Wheelock SBL2 surface backbox. 0 (D 0 <g> MEA APPROVED S5391 151-92-E 7125-0785:141 7300-0765:154 Features Approvals include: UL Standard 1971, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADAJNFPAJUFC/ANSI compliant. Meets OSHA 29 Part 1910. 165 Wall mount Multi-Candela models are available with Field Selectable Candela Settings of 15/30/ 75/110cd or 1351185cd. Single Candela models are available in 1575cd Ceiling mount Multi-Candela models are available with field selectable candela settings of 15/30/75195cd or 115/177cd. (Round or Square) Strobes produce I flash per second over the regulated voltage range 12 and 24 VOC models with wide UL "Regulated Voltage" us- ing filtered (DC) or unfiltered VRMS input voltage Synchronize using the Wheelock sync modules or panels with built-in Wheelock Patented Sync Protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wire For Weatherproof Series RSS See Datatsheet S9004 SERIES RSSIRSSP APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM #1 DSM Interconnecting wiring shown. Maximum of twenty (20) NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters. A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING This PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR °ERAT1ON OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU D/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range". Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 t 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). "Regulated Voltage Range" is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology "Listed Voltage Range". Table 1: Average RMS Current* RSS/RSSP -Wall Mount I Ceiling Mount RSS/RSSP 241575W 24MCW 24MCWH 24MCC 24MCCH 24V0C I I I Models I I ' I I I i I 1575cd l5cd 30cd 75cd ll0cd 135cd I 185cd I l5cd 30cd 75cd i 95cd I 115cd 177cd UL max* I 0.090 I 0.060 1 0.092 1 0.165 I 0.220 1 0.300 1 0.420 1 0.065 I 0.105 I 0.189 1 0.249 I 0.300 I 0.420 I RSS/RSSP RSS/RSSP Wall Mount 24VDC * RMS current ratings are per UL average RMS method. UL max current ____________ Models rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum 12 vdc 0.152 listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, UL max* 0.255 see installation instructions. V Table 2: Audibles/Speakers for RSSP Strobe Plate Product Series Multitorte Appliances AMT, MT Horns AH, NH, HS Motor Bells MB-G6/G1O Speakers ET-1010/1080, E70, ET70 Chimes CH70 Wiring Diagrams SERIES RSS/RSSP APPLIANCE FROM + TO NEXT PRECEDING - APPLIANCE APPLIANCE, SYNC OR EOLR MODULE, POWER SUPPLY OR FACP SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT DSM STROBE 0 NAC SYNC 0 CIRCUIT UTI OUTiE NUS RSS RSS RSS I AUDIBLE ]ROBE N1 0+ MINUS 2 0 * IN 2 RSS SRSS OUT 2 NAC CIRCUIT RETURN SERIES RSS/RSSP APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT SM F 0 ~ STROBE 0 - STROBE Strobe A NAG Circuit Au d ble le EOLR P D+I Audible SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH PS-12124-8CP or PS-12124-8MP Series PS-12/24BMP OUTPUTS EOLR 1-4 F - 4-CLASS A B OR A RSS C 2-CLASS P AS RSS Series PS-12/24-8MP l STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON TO NEXT FROM _____ ______________ + APPLIANCE PRECEDING I II - OR EOLR APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP + - STROBE AUDIBLE STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY FROM + + TO NEXT PRECEDING APPLIANCE APPLIANCE OR - OREOLR FACP FROM +--1r----- +TONEXT PRECEDING STROBE OR STROBE. SYNC - - - Fl 1 r - - COLE - - MODULE. POWER SUPPLY OR FACP STROBE APPLIANCE 11 For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer PS-24-8MC. Specifications and Ordering Information . Model Order Code Wall Mount Ceiling Mount Non- Sync Strobe Candela - 24 VDC - 12 VDC Color RED Color WHITE Mounting Options Square Ro or und Agency Approvals - UL - MEA CSFM - FM - BFP RSS-24MCW-FR 940 X - X 15/30/75/110 X - X - BD,EF,G,HJ,NO,R,X Square X X X X X RSS-24MCW-FW 9401 X - X 15/30/75/110 X - - X B,DE,F,G,H,J,N,O,R,X Square X X X X X RSS-241575W-FR 7471 X - X 15(75onAxis) X - X - B,DE,F,G,H,J,N,O,R,X Square X X I X I X X RSS-241575W-FW 7788 X - X 15 (75 on Axis) X - - X BAEG,H,JN,O,R,X Square -X- —X— —X-_. X X I RSS121575W-FR 747X - X 15(75onAxis) B,D,E,G,HJ.N,OR,X Square X X X X j RSSi21575W-FW 7468 - X 15 (75 on Axis) - X - X B,D,E,F,G,H,J,NO,R,X Square X X X X X RSS-24MCC-FW 3158 - X X 15/30/75/95 X - - X B,D,E,F,G,HJ,N,OR,X Square X X X X * RSS-24MCC-FR 3157 - X X 15/30/75/95 X - X - B,D,E,F,G,H,J,NO,R,X Square X X X X * RSS-24MCCR-FW 3160 - X X 15/30/75/95 X - - X B,D,E,F,G,H,JN,O,R,X Round X X X X * RSS-24MCCH-FW 3461 - X X 115/177 X - - X BD,EF,G,H,J,N,OR,X Square X X X X * RSS-24MCCHR-FW 3463 - X X 115/177 X - - X B,D,E,F,GH,J,N,O,R,X Round X X X X * RSS-24MCWH-FR 3465 X X 135/185 X X B,D,E,F,GH,J,NO,R,X Square X X X X * RSS-24MCWH-FW 3464 X X 135/185 X X BD,E,F,G,H,J,N,OR,X Square X X X X * RSSWP2475WFR** 9013 X - X 180@ 77-F X X X - B,D,EF,G,H,J,N,O,R,X Square X X X X * RSSWP2475WFW** 3034 X - X 180@ 77-F X X - X BD,E,F,G,F-I,J,NO,R,X Square X X X X * RSSP-121575W-FR 7798 X - X 15(75onAxis) - X X - D,E,Z Square X X X X X RSSP-24MCW-FR 9402 X - X 15/30/75/110 X - X - D,E,Z Square X X X X X RSSP-241575W-FR 7793 X - X 15(75onAxis) - - X - D,E,Z Square X X X X X *PENDING All models sync with Wheelock SM, DSM or PS-12/24-8CP or PS-12/24-8MP. # Models are available in either Red or White. Call Customer Service for Order Code & Delivery. **For Weatherproof Series RSS Strobe specifications see data sheet S9004. ***Refer to data sheet S7000 for mounting options. S0410 RSS/RSSP 02/08 Notification Architects and Specifications The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The strobe shall 1'e listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of I ne (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry as the Wheelock Series RSS. The Series RSS Strobe shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/11ocd or 135/185cd for wall mount and 15130175195cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock's SM, DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to single- gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The Appliance shall not have any mounting holes or screw heads visible when the installation is completed. The Series RSSP Multi-Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting, or the Wheelock SBL2 backbox for surface mounting. All notification appliances shall be backward compatible. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice In accordance with Wheelock, Inc. standard terms and conditions. F!EM4 I,'r1.i4 WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S Rechargeable Sealed Lead-Acid Battery PS-1 2180 12 Volt 18.0 Amp. Hrs. Features: Absorbent Glass Mat (AGM) technology for superior i / performance. / • Valve regulated, spill proof construction allows safe pa operation in any position. ps.121° NB ..• MO'' .:.. Power/volume ratio yielding unrivaled energy density. J" Rugged plastic case and cover A • Approved for transport by air. D.O.T., I.A.T.A., F.A.A. and C.A.B. certified. U.L. recognized under file number MH 20845. . 0% PERFORMANCE SPECIFICATIONS NominalVoltage ................................................................................................................................................................12 volts (6 cells in series) Nominal Capacity 20 hour rate (900mAto 10.50 volts) .....................................................................................................................................................18.OA.H. 10 hour rate (1.7A to 10.50 volts)..........................................................................................................................................................17.0 A.H. 5 hour rate (3.2A to 10.20 volts)..........................................................................................................................................................16.OA.H. 1 hour rate (11.lAto 9.00 volts).........................................................................................................................................................11.1 A.H. 15 min rate (34,3A to 9.00 volts) ........................................................................................................................................................... 8.6A.H. ApproximateWeight...............................................................................................................................................................12.6 pounds (5.73 kg) Energy Density (20 hour rate) .......................................................................................................1.53 Watt-hours/cubic inch (93.51 Watt-hours/I) Specific Energy (20 hour rate)........................................................................................................17.14 Watt-hours/pound (37.71 Watt-hours/kg) Internal Resistance (Fully Charged Battery)..............................................................................................................12 milliohms (approximately) MaximumDischarge Current (S7 Mm.) ............................................................................................................................................... 54 amperes Maximum Short-Duration Discharge Current( S 10 Sec.).................................................................................................................180 amperes Terminal configuration NB ....................................................................................................................Tin plated brass post with 5mm nut & bolt connectors F2 ...............................................................................Quick disconnect tabs, 0.250"x 0.032', mate with AMP. INC. FASTON '250' Shelf Life - % of nominal capacity at 68' F (20° C) 1 Month .................................................................................................................................................................................................97% 3 Months .................................................................................................................................................................................................91% 6 Months .................................................................................................................................................................................................83% Operating Temperature Range Charge...........................................................................................................................................................-4°F (-20°C) to 122°F (50°C) Discharge...........................................................................................................................................................-4°F(20°C)t0140°F(60°C) W Case ......................................................................................................................................................................................ABS Plastic To ensure safe and efficient operation always refer to the latest edition of our Technical Manual, as published on our website. 100 not unless adty Z; 80 before 2 g60 fail not z 40 each (0 a. 0 0 2 4 6 8 10 12 14 16 18 20 Standing Period (Months) Life Characteristics in Stand-By Use L I 14.0 20°C 13.0 ci ci 12.0 (5 11.0 (5 10.0 :r: 36A 1.2 2.4 6 12 24 36481 2 4 6 810 20 40 mm. . .. hrs. Discharge Time -cnargings nessary 10O%fca charging is req~lred. bE5C necessary us&s-(4if)tohel'reco fullcaadty chalemay 0.(104°F)_(86F)--(68°F)__._-_letbatterieSl ths 40*C 36.c to restore full state. Discharge Time vs. Discharge 'urrent IEUU 111 NEW 0.90 1.8 3.6 9.0 18 36 Discharge Current (A) (104°F) (68°F) (32°F) 20 15 10 5 .5e 30 Physical Dimensions: in. (mm) T El 539 (137) 71311811 2 100 :: 40 20 0 0 1 2 3 4 Years Life Characteristics in Cyclic Use AmbientTemperature 20C(68°F) 7r717! Float Charging 2.25 - 2.30 fit Voltage V/Cell -, II_H 1111 12C ) bC 8C 6C C .2 4C 20 0200 400 600 800 1000 1200 Number of Cycles CHARGING Cycle Applications: Limit initial current to 5.4A. Charge until battery voltage (under charge) reaches 14.40 to 14.70 volts at 68°F (20°C). Hold at 14.40 to 14.70 volts until current drops to approximately 180mA. Battery is fully charged under these conditions, and charger should either be disconnected or switched to "float" voltage. *EE D(sciarge Depth 100% Discharge 1Depth 501 Discharge Depth 30% Discharge Current 0.2C (Final Voltage 1.7V/Cell) Charge Current: 0.IC 1 . I I Ambient Temperature: 20°C to 25°C (68°F to 77°F) I I I I TECHNICAL DATA: PS-12180 Shelf Ljfe & Storage Discharge Characteristics "Float" or "Stand-By" Service: Hold battery across constant voltage source of 13.50 to 13.80 volts continuously. When held at this voltage, the battery will seek its own current level and maintain itself in a fully charged condition. NOTE: Due to the self-discharge characteristics of this type of battery, it is imperative that they be charged after 6-9 months of storage, otherwise permanent loss of capacity might occur as a result of sulfation. Ar s MODEL PS.128ONO Tolerances are n7.0.04 in. (-II.I ,rno) and +1. 0.08 in. (.7. 2rrnn) to, height din,ennlonn. All data nobject to change willroot notice. CORPORATE OFFICE 7550 Panasonic Way San Diego, CA 92154 USA Tel: +1-619-661-2020 Fax: +1-619461-3650 national-sales@power.sonic.com PRINTED IN U.S.A. CUSTOMER SERVICE SALES / INTERNATIONAL Tel: +1-619-661-2030 Tel: +1450-364-5001 Fax: +1-619-661-3648 Fax: +1-650-366-3662 customer-service@power-sonic.com battery©power-sonic.com www.power.sonic.com 0107 1M LEV The scope of this article covers the installation of wiring and equipment of fire alarm systems including all circuits controlled and powered by the fire alarm system including fire detection and alarm notification, guard's tour, sprinkler waterflow, and sprinkler supervisory systems; circuits controlled and powered by the fire alarm system include circuits for the control of building systems safety functions, elevator capture, elevator shutdown, door release, smoke doors and damper control, fire doors and damper control and fan shutdown, but only where these circuits are powered by and controlled by the fire alarm system. Fire Power Limited Cable: Type FPL, FPLR, FPLP NEC DEFINITIONS FOR ARTICLE 760 Fire Alarm Circuit: The portion of the wiring system between .\ the load side of the overcurrent device or the power-limited supply and the connected equipment of all circuits powered and controlled by the fire alarm system. Fire alarm circuits are classified as either nonpower limited or power limited. Non-Power-Limited: A fire alarm circuit powered by a source - that complies with NEC Sections 760-21 and 760-23. ?, by a 19 Jacketed Unshielded LL5 ' Applications: Fire Protective Signaling Circuits installed in the City of New York. Code Restrictions: Meets the requirements of New York City Local Law 5, and New York State Toxicity. Features: Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Construction: Copper Conductors, Fluoropolymer Insulation and Jacket. - Standard Jacket Color: Red. Color Code Chart 4. JACKETED UNSHIELDED LL5 15O C NOM. NOM. CAP. AVG. WT. AWG #/COND. SOL O.D. PF/FT . LISTINGS PER MFT PART# i 1 H 18 1 SQL. .198 45 UL, FPLP, NYC LL5 - 26 (LBS.) 5500 18 2 SQL. .312 45 . UL, FPLP, NYC LL5 47 (LBS.) 5501 16 1 SQL. .214 55 UL, FPLP, NYC LL5 . 36 (LBS.) 5502 16 2 SOL. .345 55 UL, FPLP, NYC LL5 62 (LBS.) 5503 14 1 SQL. .244 60 UL, FPLP NYC LL5 47 (LBS.) 5504 14 2 SQL. .374 60 UL, FPLP, NYC LL5 87 (LBS.) 5506 12 1 SQL. .272 65 UL, FPLP, NYC LL5 67 (LBS.) 5505 Jacketed Shielded LL5 (Overall Shield) Applications: Fire Protective Signaling Circuits installed in the City of New York. Code Restrictions: Meets the requirements of New York City Local Law 5, and New York State Toxicity. Features: Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Construction: Copper Conductors, Fluoropolymer Insulation, Aluminum/Mylar Shield and Fluoropolymer Jacket. Standard Jacket Color: Red. Color Code Chart 4. JACKETED SHIELDED LL5 (OVERALL SHIELD) 150'C AWG #/COND. SOL NOM. O.D. NOM. CAR PF/FT LISTINGS AVG. Wt PER Mfl PART# 18 1 SQL. .202 80 UL, FPLP, NYC LL5 28 (LBS.) 5550 18 2 SQL. .316 . 80 UL, FPLP, NYC LL5 51 (LBS.) 5551 16 1 SQL. .215 100 UL, FPLP, NYC LL5 42 (LBS.) 5552 16 2 SQL., .343 100 UL, FPLP, NYC LL5 71 (LBS.) 5553 14 1 SQL. .243 110. UL, FPLP, NYC LL5 51 (LBS.) 5554 14 2 SQL. .398 110 UL, FPLP, NYC LL5 93 (LBS.) 5555 12 1 SQL. .276 130 UL, FPLP, NYC LL5 75 (LBS.) 5556 I 28 Genesis Series Cable toll free 800.222.0060 phone 262.947.0720 fax 262.947.0724 Fire Alarm Jacketed Unshielded Applications: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums. . Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. - Standard Jacket Color: Red or White. Conductor Color Code Chart 4. FIRE ALARM JACKETED UNSHIELDED 75' C . AWG #/COND. SOL NOM. O.D. NOM. CAP. PF/FT - LISTINGS AVG. WT. PER MFT PART# 22 4 SQL. .122 15 UL, FPL 15 (LBS.) 4101* 22 6 SQL. .144 15 UL, FPL 19 (LBS.) 4102 22 8 SOL. .156 15 UL, FPL 24 (LBS.) 4103 22 10 SOL. .182 15 UL, FPL 31 (LBS.) 4104 22 12 SQL. .188 15 UL, FPL 37 (LBS.) 4105 • 18 2 SQL. .134 20 UL, FPL 17 (LBS.) 4106 18 4 SQL. .170 20 UL, FPL 29 (LBS.) 4107* 18 6 SQL. .192 20 UL, FPL 41 (LBS.) 4108+ 18 8 SQL. .208 20 UL, FPL 52 (LBS.) 4109+ 18 10 SQL. .244 20 UL, FPL 68 (LBS.) 4110+ 16 2 SQL. .154 20 UL, FPL 24 (LBS.) 4111 16 4 SOL. .180 20 UL, FPL 43 (LBS.) 4112+ 14 2 SQL. .182 22 UL, FPL 35 (LBS.) 4113+ 4 SQL. .214 22 UL, FPL 64 (LBS.) 4114+ .14 ) 12 2 SQL. .214 22 UL, FPL 52 (LBS.) 4115+ 'Not Twisted +Spools Only Fire Alarm Jacketed Unshielded, Direct Burial Applications: Wiring for Outdoor or Underground. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums, but intended for Outdoor or Underground Use. Features: Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Construction: Stranded Copper Conductors, PVC Insulation, High Molecular Weight PVC Jacket Color: Black. Conductor Color Code Chart 4. FIRE ALARM JACKETED UNSHIELDED, DIRECT BURIAL 75 C NOM. NOM. CAR AVG. WE AWG #/COND. STR O.D. PF/FT LISTINGS PER MFT PART# 18 2 SIR. .260 19 FPL, CL2 19 (LBS.) 4156 18 4 STR. .295 19 FPL, CL2 15 (LBS.) 4157* 18 6 STR. .345 19 FPL, CL2 24 (LBS.) 4158 16 2 STA. .282 21 FPL, CL2 31 (LBS.) 4151 14 2 SIR. .310 23 FPL, CL2 37 (LBS.) 4153 14 4 STR. .355 23 FPL, CL2 17 (LBS.) 4154 S 'Not Twisted 20 Genesis Series Cable toll free 800.222.0060 phone 262.947.0720 fax 262.947.0724 Fire Alarm Jacketed Shielded (Overall Shield) Applications: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Twisted Copper Conductors, Polypropylene Insulation, Aluminum/Mylar Shield with Drain Wire applied overall the assembled conductors. Flexible Polyvinyl-Chloride Jacket. Standard Jacket Color: Red or White, Conductor Color Code Chart 4. FIRE ALARM JACKETED SHIELDED (OVERALL SHIELD) 75 C - NOM. NOM. CAR AVG. WT. AWG #IC0ND. SOL O.D. PF/FT LISTINGS PER MFT PART# 22 4 SQL. .124 31 UL, FPL 17 (LBS.) 4201 18 2 SQL. .138 42 UL, FPL 20 (LBS.) 4202 18 4 SQL. .160 42 UL, FPL 31 (LBS.) 4203 18 6 SQL. .196 42 UL, FPL 50 (LBS.) 4204 18 8 SQL. .212 42 UL, FPL 57 (LBS.) 4205+ 16 2 SQL. .158 46 UL, FPL 29 (LBS.) 4206 16 4 SQL. .186 46 UL, FPL 49 (LBS.) 4207+ 14 2 SQL. .186 52 UL, FPL 40 (LBS.) 4208+ 14 4 SQL. .218 52 UL, FPL 67 (LBS.) 4209+ 12 2 SQL. .218 56 UL, FPL 59 (LBS.) 4210+ +Spools Only Fire Alarm Zipcord Applications: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. One Conductor Ribbed for Polarity. Sequential Footage Markings. Construction: Copper Conductors Laid Parallel in a Zipcord Style. Integral Polyvinyl-Chloride Insulation. Standard Colors: Red, White, Black. FIRE ALARM ZIPCORD 75 C NOM. NOM. CAR AVG. WT. AWG #/COND. SOL O.D. PF/FT LISTINGS PER MFT PART# 18 2 SQL. .105 x .217 17 UL, FPL, C(UL) CMG 18 (LBS.) 4002 16 2 SQL. .116 x .247 17 UL, FPL, C(UL) CMG 39 (LBS.) 4003 14 2 SQL. .129 x .273 17 UL, FPL, C(UL) CMG 39 (LBS.) 4004 12 2 SQL. .146 x .307 17 UL, FPL, C(UL) CMG 55 (LBS.) 4005o consult factory for availability S Honeywell 21 Fire Alarm Mid Cap Unshielded Applications: Wiring of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Sunlight Resistant. LR Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Twisted Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM MID CAP UNSHIELDED 75 C NOM. NOM. CAR AVG. WE AWG #/COND. SOL O.D. PF/FT LISTINGS PER Mfl PAF# 18 2 SOL. .150 15 UL, FPL 17 (LBS.) 4050 16 2 SQL. .170 17 UL, FPL 25 (LBS.) 4051+ 14 2 SOL. .208 19 UL, FPL 36 (LBS.) 4052+ +Spools Only Fire Alarm Mid Cap Shielded (Overall Shield) Applications: Wiring Of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums. Features: Available in 500 Ft. or 1000 Ft. Spools or Reel-in-the-Box. Sequential Footage Markings. Construction: Twisted Copper Conductors, Polypropylene Insulation, Aluminum/Mylar Shield with Drain Wire, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM MID CAP SHIELDED (OVERALL SHIELD) 75' C NOM. NOM. CAR AVG. WE AWG #/COND. STR O.D. PF/FT LISTINGS PER MFT PART# 18 2 SQL. .150 32 UL, FPL 20 (LBS.) 4070 16 2 SQL. .170 36 UL, FPL 28 (LBS.) 4071+ 14 2 SQL. .210 37 UL, FPL 42 (LBS.) 4072+ .i-Spools Only 22 Genesis Series Cable toll free 800.222.0060 phone 262.947.0720 fax 262.947.0724 0 Fire Alarm Jacketed Unshielded, . Riser Rated Applications: Wiring of Fire-Protective Signaling Circuits. Sunlight Resisistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red or White, Conductor Color Code Chart 4. FIRE ALARM JACKETED UNSHIELDED, RISER RATED 75C NOM. NOM. CAP. AVG. W. AWG #ICOND. SOL O.D. PF/FT LISTINGS PER MFT PART# 22 4 SQL. .122 15 UL, FPLR/CL2R, C(UL), FT4 15 (LBS.) 4301 22 6 SQL. .144 15 UL, FPLR/CL2R, C(UL), FT4 19 (LBS.) 4302' 22 8 SQL. .156 15 UL, FPLR/CL2R, C(UL), FT4 25 (LBS.) 4303' 22 10 SQL. .182 15 UL, FPLR/CL2R, C(UL), FT4 30 (LBS.) 4304- 22 12 SQL. .188 15 UL, FPLR/CL2R, C(UL), 74 36 (LBS.) 4305- 18 2 SOL. .138 19 UL, FPLR/CL2R, C(UL), FT4 17 (LBS.) 4306 18 4 SQL. .174 19 UL, FPLR/CL2R, C(UL), FT4 34 (LBS.) 4307 18 6 SQL. .187 19 UL, FPLR/CL2R, C(UL), FT4 44 (LBS.) 4308+ 18 8 SQL. .208 19 UL, FPLR/CL2R, C(UL), FT4 54 (LBS.) 4309+ 18 10 SQL. .244 19 UL, FPLR/CL2R, C(UL), FT4 67 (LBS.) 4310+ 16 2 SQL. .160 20 UL, FPLR/CL2R, C(UL), FT4 24 (LBS.) 4311 16 4 SQL. .184 20 UL, FPLR/CL2R, C(UL), FT4 43 (LBS.) 4312+ 14 2 SQL. .184 22 UL, FPLR/CL2R, C(UL), FT4 37 (LBS.) 4313+ 14 4 SQL. .214 22 UL, FPLR/CL2R, C(UL), FT4 65 (LBS.) 4314+ 12 2 SQL. .214 22 UL, FPLR/CL2R, C(UL), FT4 55 (LBS.) 4315+ 0I +Spools Only consult factory for availability. Fire Alarm Jacketed (Overall Shield), Riser Rated Applications: Wiring Of Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Plenums. Features: Available In 500 Ft. Or 1000 Ft. Tangle-free Boxes, or Spools. Sequential Footage Markings. Construction: Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red Or White, Conductor Color Code Chart 4. FIRE ALARM JACKETED (OVERALL SHIELD), RISER RATED 75 C NOM. NOM. CAR AVG. WT. AWG #/COND. SOL O.D. PF/FT LISTINGS PER Mfl PART# 22 4 SQL. .126 31 UL, FPLR/CL2R, C(UL), FT4 16 (LBS.) 4401 18 2 SQL. .138 42 UL, FPLR/CL2R, C(UL), FT4 21 (LBS.) 4402 18 4 SQL. .163 42 UL, FPLR/CL2R, C(UL), FT4 32 (LBS.) 4403 18 6 SQL. .196 42 UL, FPLR/CL2R, C(UL), F1-4 46 (LBS.) 4404 18 8 SQL. .212 42 UL, FPLR/CL2R, C(UL), FT4 56 (LBS.) 4405+ 16 2 SQL. .158 46 UL, FPLR/CL2R, C(UL), FT4 31 (LBS.) 4406 16 4 SQL. .190 46 UL, FPLR/CL2R, C(UL), FT4 49 (LBS.) 4407+ 14 2 SQL. .192 52 UL, FPLR/CL2R, C(UL), FT4 42 (LBS.) 4408+ 14 I 4 SQL. .218 52 UL, FPLR/CL2R, C(UL), FT4 72 (LBS.) 4409+ 12 2 SQL. .218 56 UL, FPLR/CL2R, C(UL), FT4 60 (LBS.) 4410+ +Spools Only Honeywell 23 C Fire Alarm Zipcord, Riser Rated Applications: Wiring Of Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. One Conductor Ribbed for Polarity. Sequential Footage Markings. Construction: Copper Conductors, Polyvinyl-Chloride Insulation. Standard Colors: White, Black, Blue, Red. FIRE ALARM ZIPCORD, RISER RATED 75C NOM. NOM. CAR AVG. Wt AWG #/COND. SOL O.D. PF/FT LISTINGS PER MFT PART# 18 2 SQL. .088 x .196 17 UL, FPLR/CL2R, C(UL), FT4 18 (LBS.) 4422 16 2 SQL. .094 x.200 17 UL, FPLR/CL2R, C(UL), FT4 26 (LBS.) 4423 14 2 SQL. .107 x.220 17 UL, FPLR/CL2R, C(UL), FT4 37 (LBS.) 4424+ 12 2 SOL. .124 x .250 17 UL, FPLR/CL2R, C(UL), FT4 52 (LBS.) 4425+ +Spools Only 0) Fire Alarm Mid Riser Rated- Cap Unshielded, Applications: Wiring Of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Copper Conductors, Polypropylene Insulation, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM MID CAP UNSHIELDED, RISER RATED 75 C NOM. NOM. CAR AVG. Wt AWG #/COND. SOL O.D. PF/FT LISTINGS PER MFT PART# 18 2 SQL. .144 15 UL, FPLR/CL2R, C(UL), FT4 19 (LBS.) 4431 16 2 SQL. .170 17 UL, FPLR/CL2R, C(UL), FT4 26 (LBS.) 4432+ 14 2 SQL. .208 19 UL, FPLR/CL2R, C(UL), FT4 38 (LBS.) 4433+ 12 2 SQL. .256 22 UL, FPLR/CL2R, C(UL), FT4 60 (LBS.) 4434+. +Spools Only Consult factory for availability 24 Genesis Series Cable toll free 800.222.0060 phone 262.947.0720 fax 262.947.0724 Fire Alarm Mid Cap Overall Shield, 1 Riser Rated Applications: Wiring Of Mid-Capacitance Fire-Protective Signaling Circuits. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Plenums. Features: Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Construction: Twisted Copper Conductors, Polypropylene Insulation, Aluminum/Mylar Shield with Drain Wire, Polyvinyl-Chloride Jacket. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM MID,CAP SHIELDED (OVERALL SHIELD) RISER RATED 75 C NOM. NOM. CAR AVG. WE AWG #/COND. SOL O.D. PFIFT LISTINGS PER MFT PART# 18 2 SOL. .148 34 UL, FPLR/CL2R, C(UL), FT4 21 (LBS.) 4441 U 16 2 SOL. .187 38 UL, FPLR/CL2R, C(UL), FT4 32 (LBS.) 4442 14 2 SOL. .212 41 UL, FPLR/CL2R, C(UL), FT4 43 (LBS.) 4443- 12 2 SOL. .260 48 UL, FPLR/CL2R, C(UL), FT4 48 (LBS.) 4444 Consult factory for availability. 10) Honeywell 25 Fire Alarm Jacketed Unshielded, . Plenum Rated Applications: Wiring Of Fire-Protective Signaling Circuits. Code Restrictions: OK for use with all Power-Limited Circuits. U Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Copper Conductors, Low Smoke PVC Insulation, Low Smoke PVC Jacket And Ripcord. - Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM JACKETED UNSHIELDED, PLENUM RATED 75 C AWG #/COND. SOL NOM. O.D. NOM. CAR PF/FT LISTINGS AVG. WT. PER MFT PART# 22 4 SQL. .122 22 UL, FPLP/CL2P C(UL), F16 15 LBS. 4501 22 6 SQL. .144 22 UL, FPLP/CL2P C(UL), FT6 21 (LBS.) 4502 228 SOL. .15622 UL, FPLP/CL2PC(UL), FT6 28 LBS.) 4503 22 10 SQL. .182 22 UL, FPLP/CL2P C(UL, FT6 33 LBS.)4504. 2212SQL..18822UL,FPLP/CL2PC(UL,FT638 LBS.) 4505 18 2 SQL. .134 24 UL, FPLP/CL2P C(UL,, FT6 19 (LBS.) 4506 184 SOL. .15624 UL, FPLP/CL2PC(UL), FT6 32 (LBS.) 4507 18 6 SQL. .192 24 UL, FPLP/CL2P C(UL), FT6 45 (_BS.) 4508+ 18 8 SQL. .208 24 UL, FPLP/CL2P C(UL), FT6 58 (LBS.) 4509+ 18 10 SQL. .244 24 UL, FPLP/CL2P C(UL), FT6 74 (LBS.) 4510+ 16 2 SQL. .154 27 UL, FPLP/CL2P C(UL), FF6 26 (LBS.) 4511 16 4 SOL. .180 27 UL, FPLP/CL2P C(UL), FF6 47 (LBS.) 4512+ 14 2 SQL. .182 27 UL, FPLP/CL2P C(UL), FT6 38 (LBS.) 4513+ 14 4 SQL. .214 27 UL, FPLP/CL2P C(UL), FT6 68 (LBS.) 4514+ 12 2 SQL. .214 30 UL, FPLP/CL2P C(UL), FT6 55 (LBS.) 4515+ +Spools Only consuft factory for availabilfty. Fire Alarm Jacketed Overall Shield, Plenum Rated Applications: Wiring Of Fire-Protective Signaling Circuits. Code Restrictions: OK for use with all Power-Limited Circuits. Features: Available In 500 Ft. Or 1000 Ft. Tangle-free Boxes, or Spools. Sequential Footage Markings. ! ' Construction: Twisted Copper Conductors, Low Smoke PVC Insulation, .Juminum/MyIar Shield With Drain Wire Low Smoke PVC Jacket and Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM JACKETED SHIELDED (OVERALL SHIELD) PLENUM RATED 75°C AWG #/COND. SOL NOM. O.D. NOM. CAP. PF/FT LISTINGS AVG. WI PER MFT PART# 22 4 SQL. .126 53 UL, FPLP/CL2P C(UL), FT6 18 (LBS.) 4601 18 2 SQL. .140 68 UL, FPLP/CL2P C(UL), FT6 22 (LBS.) 4602 18 4 SQL. .168 68 UL, FPLP/CL2P C(UL), FT6 35 (LBS.) 4603 18 6 SQL. .196 68 UL, FPLP/CL2P C(UL), FT6 50 (LBS.) 4604+ 18 8 SQL. .212 68 UL, FPLP/CL2P C(UL), FT6 62 (LBS.) 4605+ 16 2 SQL. .158 77 UL, FPLP/CL2P C(UL), FT6 35 (LBS.) 4606 16 4 SQL. .186 77 UL, FPLP/CL2P C(UL), 76 52 (LBS.) 4607+ 14 2 SQL. .186 86 UL, FPLP/CL2P C(UL), 1`176 44 (LBS.) 4608+ 14 4 SQL. .218 86 UL, FPLP/CL2P C(UL), FF6 75 (LBS.) 4609+ S 12 2 SQL. .218 96 UL, FPLP/CL2P C(UL), FT6 63 (LBS.) 4610+ i-Spools Only 26 Genesis Series Cable toll free 800.222.0060 phone 262.947.0720 fax 262.947.0724 Fire Alarm Midcap Unshielded, Plenum Rated Applications: Wiring Of Mid-Capacitance Addressable Fire-Protective Signaling Circuits. Code Restrictions: OK for use with all Power-Limited Circuits. Features: Available In 500 Ft. Or 1000 Ft. Spools. Sequential Footage Markings. Construction: Copper Conductors, Fluoropolymer Insulation, Low Smoke PVC Jacket and Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM MIOCAP UNSHIELDED, PLENUM RATED 75 C NOM. NOM. CAR AVG. Wt AWG #/COND. SOL O.D. PF/FT LISTINGS PER Mfl PART# 18 2 SQL. .146 16 UL, FPLP/CL2P C(UL), FT6 21 (LBS.) 4631- 16 2 SQL. .182 16 UL, FPLP/CL2P C(UL), FT6 29 (LBS.) 4632- 14 2 SQL. .210 16 UL, FPLP/CL2P C(UL), FT6 42 (LBS.) 4633' Consult factory for availability. • Fire Alarm Midcap Overall Shield, Plenum Rated Applications: Wiring Of Mid-Capacitance Fire-Protective Signaling Circuits. Code Restrictions: OK for use with all Power-Limited Circuits. Features: Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Construction: Copper Conductors, Fluoropolymer Insulation, Aluminum/Mylar Shield with Drain Wire, Low Smoke PVC Jacket and Ripcord. Standard Jacket Color: Red, Conductor Color Code Chart 4. FIRE ALARM MIDCAP SHIELDED (OVERALL SHIELD) PLENUM RATED 75 NOM. NOM. CAR AVG. W1. AWG #ICOND. SOL O.D. PF/FT LISTINGS - - PER MFT PART# 18 2 SQL. .150 32 UL, FPLP/CL2P C(UL), FT6 25 (LBS.) 4641 16 2 SQL. .187 32 UL, FPLP/CL2P C(UL), FT6 39 (LBS.) 4642 14 2 SQL. .214 32 UL, FPLP/CL2P C(UL), FT6 52 (LBS.) 4643. Consult factory for availability. S Honeywell 27 HNIR.E175 105 - Power-limited Fire Alarm Cable (J Underwriters L L.aboratories lnc HNIR.E175105 Power-limited Fire Alarm Cable Page Bottom Print-friendly version Questions? Power-limited Fire Alarm Cable See General Information for Power-limited Fire Alarm Cable GENESIS CABLE SYSTEMS L L C 7701 95TH ST WEASANT PRAIRIE, WI 53158 USA E175105 Types FPL , FPLP, FPLR. Type FPLP also classified for use as fire alarm cable in New York City. Last Updated on 1998-04-09 Page Top Notice of Disclaimer Questions? I eI1 UL Listed and Classified UL Recognized Products Certified Products Components for Canada This page and all contents are Copyright © 2005 by Underwriters Laboratories Inc.® The appearance of a company's name or product in this database does not in itself assure that products so Wntified have been manufactured under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up Service. Always look for the Mark on the file:///GI/Steve%20Camahan/HNIR_E 175 105%20-%20Power-limited%20Fire%20Alarm%20Cable.htm (1 of 2)4/18/2005 10:23:45 AM HNIR.E175 105 - Power-limited Fire Alarm Cable product permits the reproduction of the material contained in the Online Certification Directory subject to the Aullowing conditions: 1. The Guide Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc."must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright © 2005 Underwriters Laboratories Inc.®" file://IGIISteve%2oCamahanlHNlR_E175 105%20-%20Power-limited%20Fire%20Alarm%20Cable.htm (2 of 2)4/18/2005 10:23:45 AM FROM :CENTRAL SECURITY, INC. FAX NO. :1e009747369 NFPA RECORD OF COMPLETION Aug. 27 2008 11:44AM P2 Name of protected property: Address: 5451 AN' Rep. of protected property (i Authority having jurisdiction: Address/telephone number; San Diego Fire S Installer: Central Security Services (951) 676-7121 James Kreischer Supplier: Bosch - Service organization: Central Security Services, 43174 Business Park Drive, Temec u l a , CA. 92590 Location of record (as-built) drawings: _Central Security Services Location of operation and maintenance manuals, Central Security Services Location of test reports: Central Security Services -- A contract for test and inspection in accordance with NFPA st a n d a r d ( s ) : Contract No(s): Effective Date: Expiration Date: - System Software Operating system (executive) software revision level(s)_— Site-specific software revision date;_ Revision completed by: - -. - (name) (firm) 1. Type(s) of System or Service: NFPA 72, Chapter 6- Local If alarm is transmitted to location(s) off premise, list where receiv e d : NFPA 72, Chapter 8- Remote Station Telephone numbers of the organization receiving alarm: Alarm: Supervisory: Trouble: If alarm is retransmitted to public fire service communications c e n t e r s o r o t h e r s , i n d i c a t e l o c a t i o n a n d t e l e p h o n e numbers of the organization receiving alarm: - Indicate how alarm is retransmitted: NFPA 72, Chapter 8 - Proprietary Telephone numbers of the organization receiving alarm; Alarm: Supervisory: Trouble: If alarms are retransmitted to public fire service communications ce n t e r s o r o t h e r s , i n d i c a t e l o c a t i o n a n d telephone number of the organization receiving alarm: - Indicate how alarm is retransmitted: - NFPA 72, Chapter 8 - Central Station; Prime contractor: Central station location; Page 1 of 4 FROM :CENTRAL SECURITY, IN C . FAX NO. :180097473613 Aug. 27 208 11:44AM P3 Means of transmission of signals from the protected premises to the central station: McCulloh Multiplex - One-way radio - Digital alarm communicator - ,Two-way radio -_______ Others Means of transmission of alarms to the public fire service communicat i o n s center. La') Phone Lines System location:. Location of telephone number for receipt o f s i g n a l s : NFPA 72, Chapter 9 .._ Auxiliary Indicate type of connection Local energy - —__Shunt _Parallel telephone Z. Record of System Installation (1i11 out after installation is complete and wiring is checked for opens, shorts, g r o u n d f a u l t s , a n d i m p r o p e r b r a n c h i n g , b u t p r i o r t o conducting operational acceptance tests.) This system has been installed in accordance with the NFPA standards a s shown below, was inspected by Central Security on - 08114/08 includes the devices shown -. in 5 and B, and has been in service since NFPA 72, Chapters 1 (2) (3) 4 (5) (6) (7) 8 9 10 11 (circle all that apply) NFPA 70. National Electrical Code, Article 760 Manufacturers instructions Other (specify):- Signed: Date: 811412008 Organization: Central Security Services, Inc. 3. Record of System Operation Documentation in accordance with Inspection Testing Form, Figur e 1 0 . 6 . 2 . 3 , i s attached ,All operational features and functions of this sytem were tested by date and found to be operating properly in accordance with the requirements o f : -. NFPA 72,1Chapters 1 (2) (3) 4 (5) (6) (7) 89 10 11 (circle all that apply) NFPA 70, National Electrical Code, Article 760 Manufacturers instructions Other (specify): Signed. - - Date. 8114/08 Organization: Central Security Services, Inc. 4, Signaling Line Circuits Quantity and class of signaling line circuits connected to System (see NFPA 72, table 6.6.1): Quanitity, 3 B Class: B Page 2 of 4 FROM :CENTRAL SECURITY, INC. FAX NO. :18009747369 Aug. 27 2008 11:45AM P4 5 Alarm-initiating Devices and Circuits Quantity and class of initiating device circuits (see NFPA 72, table 65): Quantity: 3 MANUAL Manual stations Noncoded Transmitters Coded Addressable X Combination manual fire alarm and guards tour coded stations AUTOMATIC Coverage: Complete .- Partial Selective _. Nonrequired Smoke Detectors Ion Duct Detectors . Ion Heat Detectors FT RR E Sprinkler waterfiow indicators: Transmitt The alarm verification feature is disabled Other (list): Photo Addressable ) Photo X Addressable RC Addressable X Noncoded Coded . seconds. 6. Supervisory Signal-Initiating Devices and Circuits (use blanks to indicate quantity of devices) GUARD'S TOUR Coded stations Noncoded stations (C) Compulsory guards tour system comprised of transmitter situations and intermediate stations Note: Combination devices are recorded under 5(b). Manuel, and 6(a), Guards Tour. SPRINJE SYjM1 cheCproded x yIve supervisory switches ?-'Building temperature points Site water temperature points Site water supply level points Electric fire pump: (e)Fire pump power ______Fire pump running Phase reversal Engine-driven fire pump: (h)Selector in auto position (I) Engine or control panel trouble (j) Fire pump running ENGINE-DRIVEN GENERATOR: Selector in auto position Control panel trouble Transfer switches _Engine running Other supervisory function(s) (specify): Page 3 of 4 FROM :CENTRAL SECURITY, INC. FAX NO. :18009747369 Aug. 27 2008 11:45AM P5 7.. Annunciator(s) Number: I Type: 1255R Location: Front Door S. Alarm Notification Appliances NFPA 72, Chapter 6.. Emergency Voice/Alarm Service Quantity of voice/alarm channels: Single:____ Multiple: Quantity of speakers installed:_ Quantity of speaker zones: Quantity of telephones or telephone jacks included i n s y s t e m : Quantity and the class of notification appliance circuits connected to system (see NFPA 72, Table 6.7): Quantity: 1 Style: B Class: B Types and quantities of notification appliances installed: Bells With visible Speakers With visible Horns 2 With visible . X -. Chimes With visible Other - With visible (1) Visible appliances without audible: 1 Strobe Only 9. System Power Supplies Q Fire Alarm Control Panel: - Nominal voltage: 24VLTS Current rating: Overcurrent protection: Type: -. Current rating: .. - Location; Warehouse Secondary (standby): - Storage battery: 24VLTS Amp-hour rating: Calculated capacity to drive system, in hours: .. .. - Engine-driven generator dedicated to fire alarm system: Location of fuel storage: Emergency system used as backup to primary power supply: .-. Emergency system described in NFPA 70, Article 700: - 10. Comments Frequency of routine tests and inspections, if other than in. accordance with the referenced NFPA standard: System deviations from the referenced NFPA standard(s) are:____________________________________________ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ I I IVIC.. (signed) for central station . (title) (date) Upon completion of the system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction): (signed) representative of the authority having jurisdiction (title) (date) - Page 4 of 4