HomeMy WebLinkAbout3677 GARFIELD ST; ; FPR2021-0001; PermitPERMIT REPORT ILbty of
Carlsbad
Print Date: 08/31/2021 Permit No: FPR2021-0001
Job Address: 3677 GARFIELD ST, CARLSBAD, CA 92008-8219 Status: Closed - Finaled
Permit Type: FIRE-Construction Residential Work Class:
Parcel #: 2042320400 Track #:
Valuation: $419,210.40 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: S Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:.
Project Title: H ERNANDEZ RESIDENCE
Description: HERNANDEZ - NEW 13D SPRINKLERS FOR NEW SFR (30 HEADS)
Single Family Fire Sprinkl
Applied: 01/05/2021
Issued: 02/04/2021
DEV2019-0158 Finaled Close Out: 08/31/2021
Inspector:
Final Inspection:
Applicant: S FPContractor:
SYMONS FIRE PROTECTION SYMONS FIRE PROTECTION INC
ANGELAZUMAYA S 12155 PAINE PL
12155 PAINE PL POWAY, CA 92064-7154
POWAY, CA 92064-7154 5 (619) 588-6364
(619) 588-6364
FEE S AMOUNT
FIRE NFPA 13D Single Family System (lnsp/Bldg) S $125.00
FIRE NFPA 13D Single Family System (Plan Review) S $246.00
Total Fees: $371.00 Total Payments To Date: $371.00 Balance Due: $0.00
Fire Department S S Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
• IILI..lLC
12155 PAINE PLACE
P0 WAY, CA 92064
HYDRAULIC CALCULATIONS
FOR
HERNANDEZ GARAGE
FILE NUMBER: 20-0694-GARAGE.SDF
DATE: DECEMBER 18, 2020
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL
DENSITY: .05 gpm/ 512 sq.ft.
AREA OF APLICATION: GARAGE
COVERAGE PER SPRINKLER: 256 sq.ft.
NUMBER OF SPRINKLERS: 2 SPRINKLERS
TOTAL SPRINKLER WATER FLOW REQUIRED: 33.2 gpm
TOTAL WATER REQUIRED (including hose): 38.2 gpm
FLOW AND PRESSURE (@ BOR): 23.2 gpm @ 44.3 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: SYMONS FIRE PROTECTION, INC.
DESIGN! LAYOUT: FRANCISCO IBARRA
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C16-682025
WATER DEPARTMENT: CARLSBAD WATER DEPARTMENT
CONTACT: KAREN
WATER PRESSURE INFORMATION: 83.0 psi STATIC
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE #38071930)
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATi: 12.20/2020RAM FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329-GARAGE.SDF
JOB TITLE: HERNANDEZ GARAGE TWO HEAD CALC
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQD
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 74.4 73.0 500.0 74.4 38.2 73.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 38.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 33.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 -2.0 SOURCE 73.8 38.2
2 0.0 - - - - 60.4 - - -
3 0.0 - - - - 56.4 - - -
4A 3.0 - - - - 51.0 - - -
4B 0.0 - - - - 48.3 - - -
5 2.0 HOSE STREAM 44.3 5.0
6 9.5 - - - - 37.0 - - -
7 9.5 - - - - 17.8 - - -
7A 9.0 K= 4.90 17.0 20.2
8A 9.0 K= 4.90 7.0 13.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATy. 12/20/2020RAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329-GARAGE.SDF
JOE TITLE: HERNANDEZ GARAGE TWO HEAD CALC
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 38.2 0.995 PL 25.00 PF 12.5
1 -2.0 SRCE 73.8 (N/A) 15.8 150 FTG TG PE -0.9
2 0.0 0.0 60.4 0.0 0.369 TL 34.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 60.4 0.0 4.0 psi, 38.2 gpm
3 0.0 0.0 56.4 0.0
Pipe: 3 38.2 1.590 PL 85.00 PF 4.1
3 0.0 0.0 56.4 0.0 6.2 150 FTG 2E4L PE -1.3
4A 3.0 0.0 51.0 0.0 0.038 TL 109.00 PV
Pipe: 4 38.2 1.590 PL 75.00 PF 4.0
4A 3.0 0.0 51.0 0.0 6.2 150 FTG ET4L PE 1.3
4B 0.0 0.0 48.3 0.0 0.038 TL 105.00 PV
Pipe: 5 38.2 1.025 PL 5.00 PF 3.2
4B 0.0 0.0 48.3 0.0 14.9 150 FTG EL PE -0.9
5 2.0 H.S. 44.3 5.0 0.319 TL 10.00 PV
Pipe: 6 33.2 1.101 PL 7.00 PF 4.0
5 2.0 H.S. 44.3 5.0 11.2 150 FTG ET3RC PE -3.2
6 9.5 0.0 37.0 0.0 0.174 TL 23.00 PV
Pipe: .7 33.2 0.874 PL 18.00 PF 19.3
6 9.5 0.0 37.0 0.0 17.8 150 FTG 3E3R PE 0.0
7 9.5 0.0 17.8 0.0 0.535 TL 36.00 PV
Pipe: 8 20.2 0.874 PL 0.50 PF 1.0
7 9.5 0.0 17.8 0.0 10.8 150 FTG TR PE 0.2
7A 9.0 4.9 17.0 20.2 0.214TL 4.50 PV
Pipe: 9 13.0 0.874 PL 112.00 PF 10.9
7 9.5 0.0 17.8 0.0 7.0 150 FTG TR PE 0.2
8A 9.0 4.9 7.0 13.0 0.094 TL 116.00 PV
NOTES (HASS):
Calculations were performed by the HASS 8.8 D computer program
in accordance with NFPA13 (2019)
under license no. 38071930 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.009 gpm and a maximum
imbalance at any node of 0.077 gpm.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE,: 12420/2020RAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329-GARAGE.SDF
JOB TITLE: HERNANDEZ GARAGE TWO HEAD CALC
Total pressure at each node is used in balancing the system.
Maximum water velocity is 17.8 ft/sec at pipe 7.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Available pressure at source node 1 under full flow conditions is
74.39 psi with a flow of 38.38 gpm.
PIPE FITTINGS TABLE
User Pipe Table Name: FSS.PIP
PAGE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
0.874 5.00 3.00 1.00 0.00 1.00 1.00 0.00 1.00
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Lii Tee
1.025 3.00 8.00 2.00 8.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter . Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Ell Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 12120/2020RAM FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329-GARAGE.SDF
JOB TITLE: HERNANDEZ GARAGE TWO HEAD CALC
WATER SUPPLY ANALYSIS
Static: 74.40 psi Resid: 73.00 psi Flow: 500.0 gpm
[:LIWI]
2
70.0
60.0
G
A
U 50.0
G
E
40.0
P
R
E 30.0
S
S
U 20.0
R
E
10.0
LEGEND
1 Available pressure
74.39 psi 8 38.2 gpm
2 1 Required pressure
73.80 psi 8 38.2 gpm
Source Supply Curve
System Demand Curve
p
5 0.0
i
-14.7
100150 200 250 300 350 400 450 500
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DARE: 1?/20/2020RA1'1 FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329-GARAGE.SDF
JOB TITLE: HERNANDEZ GARAGE TWO HEAD CALC
WATER SUPPLY CURVE
84+
77+
0\\\\\\\\\\\\\\\\\
X * <-73.0 psi @ 500 gpm
I Flow Test Point
70+
63+
P56+
R I
S I
S I
5 49+
U I
R I
E I
42+
P I
S I
I 35+
28+
21+
14+ LEGEND
I,
I X = Required Water Supply
I 73.80 psi 8 38.2 gpm
7+
I 0 = Available Water Supply
74.39 psi 8 38.2 gpm
+------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
ff
neSeOf..oI'..'E • UCOOLJ flOC PIJL • flE L$.fl.O LE
12155 PAINE PLACE
P0 WAY, CA 92064
HYDRAULIC CALCULATIONS
FOR
HERNANDEZ RESIDENCE
FILE NUMBER: 20-0329.SDF
DATE: DECEMBER 18, 2020
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL
DENSITY: .05 gpm/ 400 sq.ft.
AREA OF APLICATION: BEDROOM
COVERAGE PER SPRINKLER: 400 sq.ft.
NUMBER OF SPRINKLERS: I SPRINKLER
TOTAL SPRINKLER WATER FLOW REQUIRED: 21.0 gpm
TOTAL WATER REQUIRED (including hose): 26.0 gpm
FLOW AND PRESSURE (@ BOR): 21.0 gpm @36.4 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: SYMONS FIRE PROTECTION, INC.
DESIGN! LAYOUT: FRANCISCO IBARRA
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C16-682025
WATER DEPARTMENT: CARLSBAD WATER DEPARTMENT
CONTACT: KAREN
WATER PRESSURE INFORMATION: 83.0 psi STATIC
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE #38071930)
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: I2/20/2020 C:\PROGPJ-\M FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE ONE HEAD CALC
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW
NODE PRESS. PRESS. @
TAG (PSI) (PSI) (GPM)
1 74.4 73.0 500.0
AVAIL. TOTAL REQ'D
PRESS. @ DEMAND PRESS.
(PSI) (GPM) (PSI)
74.4 26.0 54.0
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 26.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 21.0 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 -2.0 SOURCE 54.0 26.0
2 0.0 - - - - 47.0 - - -
3 0.0 - - - - 43.0 - - -
4A 3.0 - - - - 39.7 - - -
5 5.0 HOSE STREAM 36.4 5.0
6 14.5 - - - - 30.5
7 15.5 - - - - 21.3
8 25.5 - - - - 16.9 - - -
9 25.5 - - - - 16.8 - - -
9A 27.0 - - - - 16.2 - - -
10 25.5 - - - - 16.8 - - -
10A 27.0 - - - - 16.2 - - -
11 25.0 - - - - 17.0
12 15.5 - - - - 21.1
13 15.5 - - - - 20.9
13A 15.0 K= 4.90 18.4 21.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DP4JE: 172/20/2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE ONE HEAD CALC
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 26.0 0.995 PL 25.00 PF 6.2
1 -2.0 SRCE 54.0 (N/A) 10.7 150 FTG TG PE -0.9
2 0.0 0.0 47.0 0.0 0.181 TL 34.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 47.0 0.0 4.0 psi, 26.0 gpm
3 0.0 0.0 43.0 0.0
Pipe: 3 26.0 1.590 PL 85.00 PF 2.0
3 0.0 0.0 43.0 0.0 4.2 150 FTG 2E4L PE -1.3
4A 3.0 0.0 39.7 0.0 0.018 TL 109.00 PV
Pipe: 4 26.0 1.025 PL 5.00 PF 2.3
4A 3.0 0.0 39.7 0.0 10.1 150 FTG TL PE -0.9
5 5.0 H.S. 36.4 5.0 0.157 TL 15.00 PV
Pipe: 5 21.0 1.101 PL 8.00 PF 1.8
5 5.0 H.S. 36.4 5.0 7.1 150 FTG ET3RC PE -4.1
6 14.5 0.0 30.5 0.0 0.074 TL 24.00 PV
Pipe: 6 21.0 0.874 PL 16.50 PF 8.8
6 14.5 0.0 30.5 0.0 11.2 150 FTG 4E2R PE -0.4
7 15.5 0.0 21.3 0.0 0.229 TL 38.50 PV
Pipe: 7 1.9 0.874 PL 12.00 PF 0.1
7 15.5 0.0 21.3 0.0 1.0 150 FTG ET2R FE -4.3
8 25.5 0.0 16.9 0.0 0.003 TL 22.00 FV
Pipe: 8 0.8 0.874 FL 38.00 PF 0.1
8 25.5 0.0 16.9 0.0 0.4 150 FTG 9E8T FE 0.0
9 25.5 0.0 16.8 0.0 0.000 TL 107.00 PV
Pipe: 9 0.0 0.874 FL 11.50 PF 0.0
9 25.5 0.0 16.8 0.0 0.0 150 FTG 4ETR FE -0.6
9A 27.0 0.0 16.2 0.0 0.000 TL 35.50 PV
Pipe: 10 0.8 0.874 FL 7.00 PF 0.0
9 25.5 0.0 16.8 0.0 0.4 150 FTG ---- FE 0.0
10 25.5 0.0 16.8 0.0 0.000 TL 7.00 PV
Pipe: 11 0.0 0.874 FL 13.50 PF 0.0
10 25.5 0.0 16.8 0.0 0.0 150 FTG 4ETR PE -0.6
10A 27.0 0.0 16.2 0.0 0.000 TL 37.50 PV
Pipe: 12 0.8 0.874 PL 17.50 PF 0.0
10 25.5 0.0 16.8 0.0 0.4 15.0 FTG 6E4T PE 0.2
11 25.0 0.0 17.0 0.0 0.000 TL 59.50 PV
Pipe: 13 -1.1 0.874 PL 33.00 PF 0.1
11 25.0 0.0 17.0 0.0 0.6 150 FTG 9E2T FE -0.2
8 25.5 0.0 16.9 0.0 0.001 TL 84.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: l2/20/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE ONE HEAD CALC
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 14 1.9 0.874 PL 10.00 PF 0.0
11 25.0 0.0 17.0 0.0 1.0 150 FTG 2R PE 4.1
12 15.5 0.0 21.1 0.0 0.003 TL 12.00 PV
Pipe: 15 1.9 0.874 PL 60.50 PF 0.2
12 15.5 0.0 21.1 0.0 1.0 150 FTG 2E3T PE 0.0
13 15.5 0.0 20.9 0.0 0.003 TL 79.50 PV
Pipe: 16 21.0 0.874 PL 3.00 PF 2.8
13 15.5 0.0 20.9 0.0 11.2 150 FTG ETR PE 0.2
13A 15.0 4.9 18.4 21.0 0.229 TL 12.00 PV
Pipe: 17 -19.1 0.874 PL 1.00 PF 0.4
13 15.5 0.0 20.9 0.0 10.2 150 FTG R PE 0.0
7 15.5 0.0 21.3 0.0 0.193 TL 2.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.8 D computer program
in accordance with NFPA13 (2019)
under license no. 38071930 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.031 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 11.2 ft/sec at pipe 16.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Available pressure at source node 1 under full flow conditions is
74.39 psi with a flow of 30.98 gpm.
PIPE FITTINGS TABLE
User Pipe Table Name: FSS.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 12/20/2020 C:\PROGRAM FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE ONE HEAD CALC
PAGE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
0.874 5.00 3.00 1.00 0.00 1.00 1.00 0.00 1.00
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.025 3.00 8.00 2.00 8.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 12/20/2020 C:\PROGRAI4 FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE ONE HEAD CALC
WATER SUPPLY ANALYSIS
Static: 74.40 psi Resid: 73.00 psi Flow: 500.0 gpm
1
70.0
60.0
G
A
2 U 50.0
G
E
40.0
P
R
E 30.0
S
S
U 20.0
R
E
10.0
LEGEND
1 A Available pressure
74.39 psi @ 26.0 gpm
2 M Required pressure
54.00 psi @ 26.0 gpm
Source Supply Curve
System Demand Curve
-14.7
100150 200 250 300 350 400 450 500
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
EATE: 12/20/2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE ONE HEAD CALC
WATER SUPPLY CURVE
84+
77+
0\\\\\\\\\\\\\\\\\
I * <-73.0 psi @ 500 gpm
Flow Test Point
70+
63+
P56+
R X
E I
S I
S 49+
U I
R I
E I
42+
P I
S I
I 35+
28+
21+
14+ LEGEND
I X = Required Water Supply
I 54.00 psi @ 26.0 gpm
7+
0 = Available Water Supply
l 74.39 psi @ 26.0 gpm
0++-+---+----+-----+------+--------+--------+---------+-----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
;. .
12155 PAINE PLACE
P0 WAY, CA 92064
HYDRAULIC CALCULATIONS
FOR
HERNANDEZ RESIDENCE
FILE NUMBER: 20-0329.SDF
DATE: DECEMBER 18,2020
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: RESIDENTIAL
DENSITY: .05 gpm/ 512 sq.ft.
AREA OF APLICATION: EXERCISE
COVERAGE PER SPRINKLER: 256 sq.fi.
NUMBER OF SPRINKLERS: 2 SPRINKLERS
TOTAL SPRINKLER WATER FLOW REQUIRED: 26.1 gpm
TOTAL WATER REQUIRED (including hose): 31.1 gpm
FLOW AND PRESSURE (@ BOR): 26.1 gpm @ 47.6 psi
SPRINKLER ORIFICE SIZE: 1/2" inch
NAME OF CONTRACTOR: SYMONS FIRE PROTECTION, INC.
DESIGN! LAYOUT: FRANCISCO IBARRA
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE DEPARTMENT
CONTRACTOR CERTIFICATION NUMBER: C16-682025
WATER DEPARTMENT: CARLSBAD WATER DEPARTMENT
CONTACT: KAREN
WATER PRESSURE INFORMATION: 83.0 psi STATIC
CALCULATIONS BY HASS COMPUTER PROGRAM (LICENSE #38071930)
HRS SYSTEMS, INC.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE:12/2 /2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE TWO HEAD CALC
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
1 74.4 73.0 500.0 74.4 31.1 69.3
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 31.1 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM
OTHER HOSE STREAM ALLOWANCES 5.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 26.1 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 -2.0 SOURCE 69.3 31.1
2 0.0 - - - - 59.8 - - -
3 0.0 - - - - 55.8 - - -
4A 3.0 - - - - 51.7 - - -
5 5.0 HOSE STREAM 47.6 5.0
6 14.5 - - - - 40.8
7 15.5 - - - - 27.1
8 25.5 - - - - 19.5 - - -
9 25.5 - - - - 11.2 - - -
9A 27.0 K= 4.90 7.2 13.1
10 25.5 - - - - 11.2 - - -
bA 27.0 K= 4.90 7.0 13.0
11 25.0. - - - - 18.3 - - -
12 15.5 - - - - 23.0
13 15.5 - - - - 27.0
13A 15.0 - - - - 27.3
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE 12//2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE TWO HEAD CALC
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 31.1 0.995 PL 25.00 PF 8.6
1 -2.0 SRCE 69.3 (N/A) 12.8 150 FTG TG PE -0.9
2 0.0 0.0 59.8 0.0 0.253 TL 34.00 PV
Pipe: 2 FIXED PRESSURE LOSS DEVICE
2 0.0 0.0 59.8 0.0 4.0 psi, 31.1 gpm
3 0.0 0.0 55.8 0.0
Pipe: 3 31.1 1.590 PL 85.00 PF 2.8
3 0.0 0.0 55.8 0.0 5.0 150 FTG 2E4L PE -1.3
4A 3.0 0.0 51.7 0.0 0.026 TL 109.00 PV
Pipe: 4 31.1 1.025 PL 5.00 PF 3.3
4A 3.0 0.0 51.7 0.0 12.1 150 FTG TL PE -0.9
5 5.0 H.S. 47.6 5.0 0.218 TL 15.00 PV
Pipe: 5 26.1 1.101 PL 8.00 PF 2.7
5 5.0 H.S. 47.6 5.0 8.8 150 FTG ET3RC PE -4.1
6 14.5 0.0 40.8 0.0 0.111 TL 24.00 PV
Pipe: 6 26.1 0.874 PL 16.50 PF 13.2
6 14.5 0.0 40.8 0.0 14.0 150 FTG 4E2R PE -0.4
7 15.5 0.0 27.1 0.0 0.343 TL 38.50 PV
Pipe: 7 16.8 0.874 PL 12.00 PF 3.3
7 15.5 0.0 27.1 0.0 9.0 150 FTG ET2R PE -4.3
8 25.5 0.0 19.5 0.0 0.152 TL 22.00 PV
Pipe: 8 11.7 0.874 PL 38.00 PF 8.3
8 25.5 0.0 19.5 0.0 6.2 150 FTG 9E8T PE 0.0
9 25.5 0.0 11.2 0.0 0.077 TL 107.00 PV
Pipe: 9 13.1 0.874 PL 11.50 PF 3.4
9 25.5 0.0 11.2 0.0 7.0 150 FTG 4ETR PE -0.6
9A 27.0 4.9 7.2 13.1 0.096 TL 35.50 PV
Pipe: 10 -1.4 0.874 PL 7.00 PF 0.0
9 25.5 0.0 11.2 0.0 0.8 150 FTG ---- PE 0.0
10 25.5 0.0 11.2 0.0 0.002 TL 7.00 PV
Pipe: 11 13.0 0.874 PL 13.50 PF 3.5
10 25.5 0.0 11.2 0.0 7.0 150 FTG 4ETR PE -0.6
bA 27.0 4.9 7.0 13.0 0.094 TL 37.50 PV
Pipe: 12 -14.4 0.874 PL 17.50 PF 6.8
10 25.5 0.0 11.2 0.0 7.7 150 FTG 6E4T PE 0.2
11 25.0 0.0 18.3 0.0 0.115 TL 59.50 PV
Pipe: 13 -5.1 0.874 PL 33.00 PF 1.4
11 25.0 0.0 18.3 0.0 2.7 150 FTG 9E2T PE -0.2
8 25.5 0.0 19.5 0.0 0.017 TL 84.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE 12/2)0/2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE TWO HEAD CALC
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 14 -9.3 0.874 PL 10.00 PF 0.6
11 25.0 0.0 18.3 0.0 5.0 150 FTG 2R PE 4.1
12 15.5 0.0 23.0 0.0 0.051 TL 12.00 PV
Pipe: 15 -9.3 0.874 PL 60.50 PF 4.0
12 15.5 0.0 23.0 0.0 5.0 150 FTG 2E3T PE 0.0
13 15.5 0.0 27.0 0.0 0.051 TL 79.50 PV
Pipe: 16 0.0 0.874 PL 3.00 PF 0.0
13 15.5 0.0 27.0 0.0 0.0 150 FTG ETR PE 0.2
13A 15.0 0.0 27.3 0.0 0.000 TL 12.00 PV
Pipe: 17 -9.3 0.874 PL 1.00 PF 0.1
13 15.5 0.0 27.0 0.0 5.0 150 FTG R PE 0.0
7 15.5 0.0 27.1 0.0 0.051 TL 2.00 PV
NOTES (HASS)
Calculations were performed by the HASS 8.8 D computer program
in accordance with NFPA13 (2019)
under license no. 38071930 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.006 gpm and a maximum
imbalance at any node of 0.088 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 14.0 ft/sec at pipe 6.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
Available pressure at source node 1 under full flow conditions is
74.39 psi with a flow of 32.50 gpm.
PIPE FITTINGS TABLE
User Pipe Table Name: FSS.PIP
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE 12/?)0/2020 C:\PROGRA14 FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE TWO HEAD CALC
PAGE: H MATERIAL: CPVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T R K C L B L
Eli Tee TEERUN COUPLG EL45
0.874 5.00 3.00 1.00 0.00 1.00 1.00 0.00 1.00
1.101 7.00 5.00 1.00 0.00 1.00 1.00 0.00 1.00
PAGE: I MATERIAL: CPPR-L HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Ell Tee
1.025 3.00 8.00 2.00 8.00 2.00 2.00 0.00 0.00
PAGE: J MATERIAL: S40PVC HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee
1.590 6.00 12.00 3.00 14.00 8.00 2.00 0.00 0.00
PAGE: K MATERIAL: CPPR-K HWC: 150
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D
Eli Tee L
0.995 2.00 6.00 1.50 0.00 0.00 3.00 0.00 0.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE 12/2 /2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE TWO HEAD CALC
WATER SUPPLY ANALYSIS
Static: 74.40 psi Resid: 73.00 psi Flow: 500.0 gpm
80.0
1
70.0
60.0
G
A
U 50.0
G
E
40.0
P
R
E 30.0
S
S
U 20.0
R
E
10.0
LEGEND
1 Available pressure
74.39 psi 8 31.1 gpm
2 1 Required pressure
69.28 psi 8 31.1 gpm
Source Supply Curve
System Demand Curve
P
0.0
i
-14.7
100150 200 250 300 350 400 450 500
FLOW (GPM)
Note: (1) Dashed Lines indicate extrapolated values from Test Results
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE. 12/2a0/2020 C:\PROGRAN FILES\HRS SYSTEMS\HASS87\HASS DATA\20-0329.SDF
JOB TITLE: HERNANDEZ RESIDENCE TWO HEAD CALC
WATER SUPPLY CURVE
84+
77+
0\\\\\\\\\\\\\\\\\
I * <-73.0 psi @ 500 gpm
I Flow Test Point
70X
63+
P 56+
R I
E I
S I
5 49+
U I
R I
E I
42+
P I
S I
I 35+
28+
21+
14+ LEGEND
I
I X = Required Water Supply
'I
I 69.28 psi @ 31.1 gpm
7+
I 0 = Available Water Supply
I 74.39 psi @ 31.1 gpm
I,
+------+--------+-----
200 300 400 500 600 700
FLOW (GPM)
+-----------+
800 900 1000
Model RFC30 & RFC30LL Model RFC43 & RFC43LL
Model RFC49 & RFC49LL Model RFC58
r - -
Bulletin 006 January 2020
Model RFC Series Residential Sprinklers
Flat Concealed Pendent
cULus Listed
Features
cULus Listed as Residential Sprinklers
Push-On cover plate installation
Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in ac-
cordance with UL 1626. In addition, Model RFCLL Series
sprinklers are cULus Certified for Health Effects to NSF/ANSI
standard 61 Annex G (LL) and Australian WaterMark Certified
(WMCS).
Model RFC30 sprinklers have a 165°F (74°C) temperature
rated fusible-link operating element. Model RFC43, RFC49,
RFC58, and RFC76 sprinklers are offered with either a 165°F
(74°C) or 212°F (100°C) temperature rated fusible-link oper-
ating element. Sprinklers with a 165°F (74°C) temperature
rating are ordinary temperature classification and are listed
for use with a 135°F (57°C) temperature rated cover plate.
Sprinklers with a 212°F (100°C) temperature rating are inter-
mediate temperature classification and are listed for use with
a 165°F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
or Model G5 Cover Plate. Model G5 Cover Plates may be
installed by either pushing or threading the cover plate into
the sprinkler cup. Model RFC30, RFC30LL, RFC43, RFC43LL,
RFC49 and RFC49LL sprinklers allow 1/2' (13 mm) of cover
plate adjustment. Model RFC58 and RFC76 sprinklers allow
3/4' (19 mm) of cover plate adjustment. Model RFC and G5
Cover Plates are available in a variety of finishes as listed in
Table H.
Model RFC76 Model RFC & G5 Cover Plate
Sprinkler Model Nominal K-Factor
gpm/psi'/2 (I/mm/bar112)
Max. Coverage Area
ft x ft (m x m)
Sprinkler Identification
Listings &
Approvals Number (SIN)
RFC30 3.0(43) 14x 14(4.3x4.3) cULus RA0611
RFC30LL 3.0(43) 14 x 14 (4.3 x 4.3) cULus, LL, WMCS RA3211
RFC43 4.3(62) 20x20(6.1 x6.1) cULus RA0612
RFC43LL 4.3(62) 20 x 20(6.1 x 6.1) cULus, LL, WMCS RA3212
RFC49 4.9(71) 20x20(6.1 x6.1) cULus RA0616
RFC49LL 4.9(71) 20x20(6.1 x6.1) cULus, LL, WMCS RA3216
RFC58 5.8(84) 20x20(6.1 x6.1) cULus RA0613
RFC76 7.6(109) 20x20(6.1 x6.1) cULus RA0618
cULus: cULus Listed to UL1626, Residential Sprinklers for Fire Protection Service.
LL: cULus Certified for Health Effects to NSF/ANSI Standard 61 Annex G (Less than 0.25% Lead content).
WMCS: Australian WaterMark Certified.
www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1R1/2
Nominal K-Factor: 3.0 (43 metric)
Max. Working Pressure: 175 psi (12 bar)
Mm. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC Cover Plate
Model G5 Cover Plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed to UL 1626
cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC30LL only)
Watermark Certified (RFC30LL only)
Bottom View I
Model RFC30 & RFC30LL Sprinkler Components and Dimensions
I 2-5/16! (58 mm)
Threads Dia.
Body
Cup
Tower 1-3/4"(44 mm) +1- 1/4"(6
Fusible Link Nominal face of fitting to ceiling
Deflector (retracted)
Pin (extended) II I III 4I II Deflector (extended) OKI
Model G4/G5 Cover Plate 3-5/16" 84 mm) Dia
7 13/16" (5 mm)
Ceiling
Model RFC30 and RFC30LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure
Max. Coverage Area (2) Flow Pressure
ft. x ft. gpm psi
(m x m) (I/mm) (bar)
12x12 9 9.0
(3.6 x 3.6) (34) (0.62)
14x14 10 11.0
(4.3 x 4.3) (38) (0.76)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the ex1 larger max. coverage area listed.
Bulletin 006 Page 2 of 8
January 2020 . www.reliablesprinkler.com
Bottom View
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2" NPT or ISO 7-1R1/2
Nominal K-Factor: 4.3 (62 metric)
Max. Working Pressure: 175 psi (12 bar)
Mm. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Listings and Approvals Cover Plate Finishes cULus Listed to UL 1626 (See Table H) cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC43LL only)
Watermark Certified (RFC43LL only)
Sensitivity
Fast-response
Temperature Rating
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Model G5 Cover Plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Model RFC43 & RFC43LL Sprinkler Components and Dimensions
Threads -
Body
Cup -
Tower -.-.
Fusible Link -
Deflector (retracted)
Pin (extended)
Deflector (extended) —
L..... 2-5/16' (58 mm)
Dia.
1-3/4" (44 mm) +/- 1/4" (6 mm)
Nominal face of fitting to ceiling
Model G4/G5 Cover Plate -' - 3-5/16" (84 mm) Dia.
3/16(5 mm)
Ceiling
Model RFC43 & RFC43LL Sprinkler Hydraulic Design Criteria Table C
Minimum Flow and Residual Pressure (I)
Max. Coverage Area 2 Ordinary Temperature Intermediate Temperature
Flow Pressure Flow Pressure ft. x ft.
(m x m) gpm psi gpm psi
(I/mm) (bar) (I/mm) (bar)
15x15 12 7.8 12 7.8
(4.6 x 4.6) (45) (0.54) (45) (0.54)
16x16 13 9.1 13 9.1
(4.9 x 4.9) (49) (0.63) (49) (0.63)
18x18 18 17.5
(5.5x5.5) (68) (1.21) -- --
20x20 21 23.8
(6.1 x6.1) (79) (1.64) -- --
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Ai.Iiiiig Page 3 of 8
January 2020 _______ www reliablesprinklercom
r'., 4-1 ff H Bottom View
- /
Technical Specifications Sensitivity
Style: Flat Concealed Pendent Fast-response
Threads: 1/2" NPT or ISO 7-1R1/2
Nominal K-Factor: 4.9 (71 metric) Temperature Rating
Max. Working Pressure: 175 psi (12 bar) Ordinary:
Mm. Spacing: 8 ft. (2.4 m) 165°F (74°C) sprinkler
135°F (57°C) cover plate
Material Specifications Intermediate:
Thermal Sensor: Nickel Alloy Solder Link 212°F (100°C) sprinkler
Sprinkler Body: Brass Alloy 165°F (74°C) cover plate
Levers: Bronze Alloy
Yoke: Brass Alloy Cover Plate
Sealing Assembly: Nickel Alloy with PTFE Model G5 Cover Plate
Load Screw: Bronze Alloy
Towers: Copper Alloy Sprinkler Wrench
Pins: Stainless Steel Model FC (without wrench-able cap)
Deflector: Bronze Alloy Model W3 (with wrench-able cap)
Cup: Steel
Listings and Approvals Cover Plate Finishes cULus Listed to UL 1626
(See Table H) cULus Certified for Health Effects to NSF/ANSI
Standard 61 Annex G (RFC49LL only)
Watermark Certified (RFC49LL only)
Model RFC49 & RFC49LL Sprinkler Components and Dimensions I 9MW I
Body
Cup
Towe
Fusible Li
Deflector (retri
Pin (exter
Deflector (extenc
2-5/16'(58 mm)
Dia.
1-3/4' (44 mm) +1- 1/4"(6 mm)
Nominal face of fitting to ceiling
Model G4/G5 Cover Plate -' I 3-5/16" (84 mm) Dia.
3/16(5mm)
Ceiling
Model RFC49 & RFC49LL Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure"
Max. Coverage Area
Ordinary Temperature
__________________
Intermediate Temperature
Flow Pressure Flow Pressure ft. x ft.
(m x m) gpm psi gpm psi
(I/mm) (bar) (I/mm) (bar)
16x16 13 7.0 13 7.0
(4.9 x 4.9) (49.0) (0.48) (49.0) (0.48)
18x18 17 12.0 17 12.0
(5.5 x 5.5) (64.3) (0.83) (64.3) (0.83)
20x20 20 16.7 21 18.4
(6.1 x 6.1) (75.7) (1.15) (79.5) (1.27)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Page 4 of 8
January 2020 www.reliablesprinkler.com
Bottom View
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2' NPT or ISO 7-1R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Mm. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Chrome Plated Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model G5 Cover Plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Listings and Approvals
cULus Listed
Model RFC58 Sprinkler Components and Dimensions
2-5/16 (58 mm)
Dia.
Threads
Body
Cup
Tower
Fusible Link 1-7/8 (48 mm) L- 3/8"(9 mm)
Deflector (retracted) _______
Nominal face of fitting to ceiling
Pin (extended)
Deflector (extended)
—-5/16"84rnmDia. Model G4/G5 Cover Plate
._3/16°(5mm)
Ceiling
Model RFC58 Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressuret1
Max. Coverage Area ' Flow Pressure
ft. x ft. gpm psi
(m x m) (I/mm) (bar)
16x16 16 7.6
(4.9 x 4.9) (60.6) (0.53)
18x18 18 9.6
(5.5x5.5) (68.1) (0.66)
20x20 20 11.9
(6.1 x 6.1) (75.7) (0.82)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1)the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Page 5 of 8 January 2020 www.reliablesprinkler.com
Technical Specifications
Style: Flat Concealed Pendent
Threads: 3/4° NPT or ISO 7-1 R3/4
Nominal K-Factor: 7.6 (109 metric)
Max. Working Pressure: 175 psi (12 bar)
Mm. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model G5 Cover Plate
Sprinkler Wrench
Model FC (without wrench-able cap)
Model W3 (with wrench-able cap)
Bottom View
Listings and Approvals
cULus Listed
Model RFC76 Sprinkler Components and Dimensions
2-5/16"(58 mm)
I Dia.
Threads
Body
Cup
Tower
Fusible Link 1-7/8" (48 mm) +/- 3/8" (9 mm)
Nominal face of fitting to ceiling
Deflector (retracted)
II _
Pin (extended)
H Deflector (extended)
-5/16"84mm Model G4/G5 Cover Plate Dia.
.l 3/16"(5 mm) A 1
/ / / /4_L
Ceiling
Model RFC76 Flat Concealed Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressuret1t
Max. Coverage Area (2) Flow Pressure
ft. x ft. gpm psi
(m x m) (I/mm) (bar)
16x16 21 7.6
(4.9 x 4.9) (79.5) (0.52)
18x18 24 9.9
(5.5 x 5.5) (90.8) (0.68)
20x20 34 20
(6.1 x6.1) (128.7) (1.4)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Page Sot 8
January 2020 - - www.reliablesprinkler.com
Cover Plate Finishes'1
Standard Finishes Special Application Finishes
White Polyester Off White Paint Black Paint Raw Brass
Chrome Plated Bright Brass Finished Bronze Black Plated
Satin Chrome Stainless Steel Clad(3) Custom Color Paint(2)
Notes:
Paint or any other coating applied over the factory finish will void all approvals and warranties.
Custom color paint is semi-gloss, unless specified otherwise.
Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the backside. Cover plates
are not listed or approved as corrosion resistant.
Installation Dimensions Table
Recommended Min. to Min. to Max.
Sprinkler Cover Cover Plate Hole Diameter Cover Plate Max. Face Dropped Deflector Cover Plate
Model Plate Diameter in Ceiling Adjustment of Fitting to Distance below Temperature
Model inch (mm) inch (mm) inch (mm) CeiIingt1 Ceiling Rating
inch (mm) inch (mm)
RFC30, RFC or 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 135°F
RFC30LL G5 (84) (67) (13) (38 to 51) (13 to 25) (57°C)
RFC43, 135°F2 RFC43LL, RFC or 3-5/16 2-5/8 1/2 1-1/2 to 2 1/2 to 1 (57°C)
RFC49, G5 (84) (67) (13) (38 to 51) (13 to 25) or 1650F3)
RFC49LL (74°C)
135°F2
RFC58, RFC or 3-5/16 2-5/8 3/4 1-1/2 to 2-1/4 1/4 to 1 (57°C)
RFC76 G5 (84) (67) (1 g) (38 to 57) (6 to 25) or 165°F3
(74°C)
Notes:
Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method
prior to installation. A 1/2" x /2" brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing
sprinklers.
For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C).
For use with 212°F (100°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 150°F (660C).
Installation
Model RFC series sprinklers are intended to be installed in
accordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as
the requirements of applicable authorities having jurisdiction.
Model RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in
the cup are open and unobstructed following installation. Model
RFC series sprinklers are shipped with a wrench-able protective
cap that should remain on the sprinkler until the sprinkler system
is placed in service following construction.
Model RFC series sprinklers can be installed without removing
the wrench-able protective cap using the Model W3 wrench.
Alternatively, Model RFC series sprinklers can be installed using
the Model FC wrench by temporarily removing the protective cap
during installation of the sprinkler. The use of any other wrench to
installed Model RFC series sprinklers is not permitted and may
damage the sprinkler. Fully insert the Model W3 wrench over
the cap until it reaches the bottom of the cup, or the Model FC
wrench over the sprinkler until the wrench engages the body.
Do not wrench any other part of the sprinkler/cup assembly. The
Model W3 and FC wrenches are designed to be turned with a
standard 1/2" square drive. Tighten the sprinkler into the fitting
after applying a PTFE based thread sealant to the sprinkler's
threads. Recommended installation torque is 8 to 18 ft-lbs (11
to 24 N-m) for 1/2" thread sprinklers and 14 to 20 ft-lbs (19 to 27
N-m) for 3/4° thread sprinklers.
Bulletin 006
January 2020
Do not exceed the maximum recommended torque. Exceeding
the maximum recommended torque may cause leakage or
impairment of the sprinkler. Use care when inserting or removing
the wrench from the sprinkler to avoid damage to the sprinkler.
Install the cover plate by hand by pushing the cover plate into the
cup and turning the cover in the clockwise direction until it is tight
against the ceiling.
Application
Model RFC series sprinklers are intended for installation where
residential sprinklers are permitted or required by NFPA 13,
NFPA 13R, and NFPA 130. The sprinklers are concealed
pendent residential sprinklers.
Model RFC 30 and RFC30LL sprinklers are available in
ordinary temperature classification for installation where
the Maximum Ceiling Temperature does not exceed 100°F
(380C). Model RFC43, RFC43LL, RFC49, RFC49LL, RFC58,
and RFC76 sprinklers are available in either ordinary or
intermediate temperature classification for installation where
the Maximum Ceiling Temperature does not exceed 100°F
(38°C) or 150°F (660C), respectively.
Page 7 of 8
www.reliablesprinkler.com
n
Model FC
For use with Model RFC Series sprinklers
without wrench-able cap installed
Model W3
For use with Model RFC Series sprinklers
with wrench-able cap installed
Maintenance
Model RFC series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace
any sprinkler cover plate assembly which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non-oper-
ation.
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada to UL1626, Residential Sprinklers for Fire-protection
Service (cULus).
Certified by Underwriters Laboratories, Inc. and Underwrit-
ers Laboratories of Canada for Health Effects to NSF/ANSI
Standard 61 Annex G (LL) (RFC30LL, RFC43LL, and RFC49LL
only).
Australian WaterMark Certified (RFC30LL, RFC43LL, and
RFC49LL only).
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms
and conditions, visit www.reliablesprinkler.com.
Patents
Model RFC30, RFC30LL, RFC43, RFC43LL, RFC49, RFC49LL,
RFC58, and RFC76 sprinklers are covered by U.S. Patent No.
9,248,327 and U.S. Patent No. 7,275,603.
Model RFC30, RFC30LL, RFC43 and RFC43LL sprinklers are
additionally covered by U.S. Patent No. 8,776,903.
Ordering Information
Specify the following when ordering.
Sprinkler
Model (RFC30, RFC30LL, RFC43, RFC43LL,
RFC49, RFC49LL, RFC58, RFC76)
Temperature Rating
Cover Plate
Model RFC or G5
Temperature Rating
Finish (See Table H)
Sprinkler Wrench
Model FC
Model W3
Bulletin 006 ONPage 8 of 8
January 2020 www.reIiablesprinkler.com
Bulletin 135 October 2019
Relmlabld
Features
cULus Listed Residential Sprinklers
Available in pendent and horizontal sidewall orientations
Decorative finishes available, including recessed escutch-
eons and conical concealed cover plates
Product Description
Model F1 Res Series sprinklers are residential sprinklers with a
3 mm glass bulb operating element. A variety of K-Factors as
well as recessed and conical concealed options are available
as detailed in this Bulletin.
The Fl Res Series sprinklers are specially engineered for fast
thermal response to meet the requirements of UL 1626. They
are intended for installation in accordance with NFPA 13, 13R,
and 13D.
Application
The Model FiRes Series sprinklers cULus Listed Residential
sprinklers are intended for use in accordance with NFPA 13,
NFPA 13R, or NFPA 13D. The Model FiRes residential sprin-
klers are cULus Listed for use in residential occupancies and
residential portions of any occupancy, where per by
NFPA 13, NFPA 13R, or NFPA 13D. For NFPA 13R and NFPA
13D applications, the design flow and pressure shall not be
less than the minimum flow and pressure specified in the Listed
Model Fl Res Series Glass Bulb
Residential Sprinklers
cULus Listed
Design Criteria tables in this Bulletin. For NFPA 13 applications,
the design density shall be a minimum of 0.1 gpm/sf (4.1 mml
mm), but in no case shall the flow and pressure be less than
the minimum flow and pressure specified in the Listed Design
Criteria tables in this bulletin. Model Fl Res Series sprinklers are
listed for use in wet systems only.
Residential Sprinkler Summary
Sprinkler Sprinkler K-Factor Thread Size Max. Coverage Area
Model Identification Orientation gpm/psi112 NPTorISO7-1 Installation Options ftxft(mxm) Number (SIN) (lpm/bar1 )
F1Res30 R3511 Pendent 3.0(43) 1/2 Pendent or Recessed 16 x 16 (4.9 x 4.9)
F1Res49 R3516 Pendent 4.9(71) 1/2 Pendent or Recessed 20x20(6.1 x6.1)
F1Res58 R3513 Pendent 5.8(84) 1/2 Pendent or Recessed 20x20(6.1 x6.1)
FiRes76 R7618 Pendent 7.6(109) 3/4 Pendent or Recessed 20 x 20(6.1 x 6.1)
F1Res30CCP R3511 Pendent 3.0(43) 1/2 Conical Concealed or 14 x 14(4.3 x 4.3) Recessed
F1Res49CCP R3516 Pendent 4.9(71) 1/2 Conical Concealed or 20x20(6.1 x6.1) Recessed
F1Res58CCP R3513 Pendent 5.8(84) 1/2 Conical Concealed or 20x20(6.1 x6.1) Recessed
F1Res76 CCP R7618 Pendent 7.6(109) 3'4 Conical Concealed or 20x20(6.1 x6.1) Recessed
F1Res44 HSW R3531 Horizontal Sidewall 4.4(63) 1/2 Recessed 16 x 20(4.9 x 6.1)
F1Res44 SWC R3531 Horizontal Sidewall 4.4(63) 1/2 Conical Concealed 16 x 20(4.9 x 6.1)
F1Res58 HSW R3533 Horizontal Sidewall 5.8(84) 1/2 Recessed 16 x 20(4.9 x 6.1)
F1 Res 58
HSWX RA3533 Horizontal Sidewall 5.8(84) 1/2 Recessed 14 x 26 (4.3 x 7.9)
www.reliablespririkler.com
')1M" 17rr,n.
Face of titling
to finished
ceiling
1/2 (13mm)
+1- 1/4 (6mm)
Technical Specifications Finishes
Style: Pendent and Recessed Pendent (See Table N)
Threads: 1/2' NPTor 1507-1R1/2
Nominal K-Factor: 3.0 (43 metric) Temperature Ratings
Max. Working Pressure: 175 psi (12 bar) 155°F(68°C)
175°F (79°C)
Material Specifications
Thermal Sensor: 3 mm glass bulb Recessed Escutcheons
Sprinkler Frame: Brass Alloy F2 Recessed
Button: Copper Alloy FV Recessed* 4
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy Sprinkler Wrenches 40
Deflector: Bronze Alloy Model W2 I
Model GFR2_(Recessed)
* Model FV escutcheons are not for use in positively pressurized ceiling plenums.
Model F1Res30 Residential Pendent Sprinkler Components and Installation Dimensions
Threads
Wrench Flat
Sealing Assembly 2-1/4'
Glass Bulb (57mm)1 I II I I
Load Screw
Deflector ....1° .
k32rnm)
Components Dimensions F2 & FV Recessed Escutcheon Installation
Model F1Res30 Residential Pendent Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems")
Maximum
Coverage Area ) Flow
gpm (I/mm)
ft. x ft.(m x m)
Pressure
psi (bar)
Deflector to
Ceiling Distance
12 x 12(3.7 x 3.7) 8(30) 7.0(0.48)
1104 inches
(2510100mm)
14 x 14(4.3 x 4.3) 10(38) 11.0(0.76)
15 x 15 (4.6 x 4.6) 12(45) 16.0(1.1)
16x16 (4.9x4.9) 13(49) 18.8(1.3)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 Page 2 of 15
October 2019 - www.reliablesprinkler.com
Technical Specifications Finishes
(See Table N) Style: Pendent and Recessed Pendent
Threads: 1/2 NPTor lS07-1R1/2 Temperature Ratings Nominal K-Factor: 4.9 (71 metric) 155°F (68°C) Max. Working Pressure: 175 psi (12 bar) 175°F (79°C)
Material Specifications Recessed Escutcheons Thermal Sensor: 3 mm glass-bulb Fl Recessed Sprinkler Frame: Brass Alloy F2 Recessed Button: Copper Alloy FV Recessed* Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy Sprinkler Wrenches Deflector: Bronze Alloy Model W2
Model GFR2 (Recessed)
* Model FV escutcheons are not for use in positively pressurized ceiling plenums.
Model Fl Res49 Residential Pendent Sprinkler Components and Installation Dimensions 11TT'
2-1/4" (57mm) 2-1/4" (57mm)
4 —(49
Face of fitting DIA. r Face of fitting
1-15/16" to finished
ceiling
to finishe
d(49mm) DIA. ceiting
1/2" (13mm) 5/8"(l6mml3/8"(9mm) +/- 1/4"(6mm)
NONE
'I 03M 2-1/4
(57)
1-3/4" (44mm)i 5/8 (41mm) ~1- 6mm1 "(9mm)
(32mm) 2718 (72mm) DlA. -
3/8
L2718 (72mm) DIA.
1/4"
Dimensions Fl Recessed Escutcheon Installation F2 & FV Recessed Escutcheon Installation
Model Fl Res49 Residential Pendent Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systemstht
Maximum Coverage Area(2)
ft. x ft. (m x m)
Flow
gpm (I/mm)
Pressure
psi (bar)
Deflector to
Ceiling Distance
12 x 12(3.7 x 3.7) 13(49) 7.0(0.48)
1 t 4 inches
(25 to 100 mm)
14 x 14(4.3 x 4.3) 13(49) 7.0(0.48)
16 x 16(4.9 x 4.9) 13(49) 7.0(0.48)
18 x 18(5.5 x 5.5) 17(64) 12.0(0.83)
20 x 20 (6.1 x 6. 1) 20(76) 16.7(1.15)
12 x 12(3.7 x 3.7) 15(57) 9.4(0.65)
4 to 8 inches
(100 to 200 mm)
14 x 14(4.3 x 4.3) 16(61) 10.7 (0.74)
16 x 16(4.9 x 4.9) 17(64) 12.0(0.83)
18 x 18(5.5 x 5.5) 19(72) 15.0(1.03)
20 x 20(6.1 x 6.1) 22(83) 20.2(1.39)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 lRellabld Page 3 of 15
October 2019 www.reliablesprinkler.com
to finished
ceiling
5/8° (16mm)
+1- 3/8(9mm)
Fl Recessed Escutcheon Installation Dimensions
Technical Specifications
Style: Pendent and Recessed Pendent
Threads: 1/2 NPTor 1507-1R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
175°F (79°C)
Recessed Escutcheons
Fl Recessed
F2 Recessed
FV Recessed*
Sprinkler Wrenches
Model W2
Model GFR2 (Recessed)
* Model FV escutcheons are not for use in positively pressurized ceiling plenums.
Model Fl Res58 Residential Pendent Sprinkler Components and Installation Dimensions
2-1/4° (57mm) 2-1/4° (57mm) hr DIA. -ii F'.p of fitting hT- DIA. -ii FP of fittinn
1-15/16° to finished
(49mm) DIA. ceiling
1/2°(l3mm)
I +1- 1/4° (6mm)
L_
.._J 1-3/4"(44rnrn)
2-7/8° (72mm) DIA.
F2 & FV Recessed Escutcheon Installation
Model Fl Res58 Residential Pendent Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems0t
Maximum Coverage Area(2)
ft. x ft. (m x m)
Flow
gpm (I/mm)
Pressure
psi (bar)
Deflector to
Ceiling Distance
16 x 16(4.9 x 4.9) 16(61) 7.6(0.52)
1 to 4 inches
(25 to 100 mm) 18 x 18(5.5 x 5.5) 19(72) 10.8 (0.75)
20x20(6.1 x6.1) 22(83) 14.4(1.0)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin Bulletin 135 Page 4 of 15
October 2019 Heliabidd -. www.reliablesprinkler.com
Finishes Technical Specifications (See Table N) Style: Pendent and Recessed Pendent
Threads 3/4 NPT or 1S07 1 R3/4 Temperature Ratings Nominal K-Factor: 7.6(109 metric) 155°F (68°C) 0
Max. Working Pressure: 175 psi (12 bar) 175°F (79°c)
Material Specifications
. jC
Recessed Escutcheons :, Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy Fl Recessed 51
F2 Recessed Button: Copper Alloy FV Recessed*
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy Sprinkler Wrenches Deflector: Bronze Alloy Model W2
Model GFR2 (Recessed)
* Model FV escutcheons are not for use in positively pressurized ceiling plenums
Model Fl Res76 Residential Pendent Sprinkler Components and Installation Dimensions
Face of fitting
to finished
ceiling
5I8 (16mm)
+1- 3I8 (9mm)
2-1/4 (57mm)
DIA,
1-15/16
(49mm) DIA.
Face of fitting
to finished
ceiling
1/2 (13mm)
+1- 1/4(6mm)
1-5/8
(44mm)
1-518°(4lmm) 4-/-
3/8 (9mm) Qk
2-7/8 (72mm)
1-3/4 (44mm) +1-
1/4(6mm)
Dimensions Fl Recessed Escutcheon Installation F2 & FV Recessed Escutcheon Installation
Model Fl Res76 Residential Pendent Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems1"
Maximum Coverage Aream Flow Pressure Deflector to
ft. x ft. (m x m) gpm (I/mm) - psi (bar) Ceiling Distance
18 x 18(5.5 x 5.5) 21 (80) 7.6(0.52)
1 to 4 inches
(25 to 100 mm) 20x20(6.1 x6.1) 23(87) 9.2 (0.63)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 Beliabl!Page Sot 15
October 2019 - - 0 - www.reliablesprinkter.com
Technical Spécifióations
Style: Conical Concealed Pendent and
Recessed Pendent
Threads: 1/2 NPTor 1S07-1R1/2
Nominal K-Factor: 3.0 (43 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
rInusnes
(See Table N)
Temperature Ratings
155°F (68°C)
Recessed Escutcheons/Cover Plates
CCP Conical Concealed Plate 135°F (570C)°
FP Recessed*
Sprinkler Wrenches
Model GFR2
*Note: Model FP escutcheons and COP cover plates are not listed for use in positively pressurized ceiling plenums.
Model F1Res30 CCP and FP Recessed Pendent Sprinkler Installation Dimensions TIT71.
2-5/8° (67mm) 2-5/8° (67mm)
DIA. DIA.
25/160 2-5/16"
T
(59mm)DIA.j (59mm)DIA.
ace of filling
to finished
ceiling
1/4° (32mm)
- 1/4° (6mm)
15/16"
24mm)
L3-3/16"(78mm)
Face of fitting
to finished
ceiling
1-1/4° (32mm)
+1- 1/4°(6mm)
1°(25mm)
+1- 1/4" (6mm)
CCP Recessed Escutcheon Installation FP Recessed Escutcheon Installation
Modal F1Rasfl incip Panriant & FP Ra,ad Pndnt Anriniciar I.1urIri,Ii, flnn Critri
Minimum Flow and Residual Pressure in Wet Pipe SystemsOl
Maximum Coverage Area Flow Pressure I Deflector to Ceiling Distance ft. x ft. (m x m) gpm (I/mm) psi (bar)
12 x 12 (3.7 x 3.7) 8 (30) 7.0(0.48) 1/2 to 1 inch
(13 to 25 mm) 14 x 14(4.3 x 4.3) 11(38) 13.4(0.92)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1)the flow listed in the table above or (2)the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
The sprinkler must be installed into a ceiling with the listed cover plate installed.
Bulletin 135 iiai Page 6 of 15
October 2019 www.reliablesprinkler.com
CCP Recessed Escutcheon Installation
Technical Specifications
Style: Conical Concealed Pendent and
Recessed Pendent
Threads: 1/2 NPTor 1S07-1R1/2
Nominal K-Factor: 4.9 (71 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 m glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
Recessed Escutcheons/Cover Plates
CCP Conical Concealed Plate 135°F (570C)*
FP Recessed*
Sprinkler Wrenches
Model GFR2
*Note: Model FP escutcheons and COP cover plates are not for use in positively pressurized ceiling plenums.
Model Fl Res49 CCP & FP Recessed Pendent Sprinkler Installation Dimensions 05105TT
2-5/8° (67mm)
DIA.
2-5/16°
(59mm)DIA.
ace of fitting
to finished
ceiling
I it I ______________________________ ______________________________
Faceof fitting
to finished I ceiling I
-1/4° (32mm) 1-1 /4°(32mm)
I- 1/4°(6mm) i-,- 1/4° (6mm)
(24mm) - .
L3-3/16"(78mm) DIA.
FP Recessed Escutcheon Installation
Model Fl Res49 CCP Pendent and FP Recessed Pendent Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems"
Maximum Coverage Aream
ft. x ft. (m x m)
Flow
gpm (Vmin)
Pressure
psi (bar) Deflector to Ceiling Distance
14 x 14 (4.3 x 4.3) 13 (49) 7.0 (0.48)
1/2 to 1 inch
(13 to 25 mm)
16.7(1.15)
16 X 16(4.9 X 4.9) 14(53) 8.2(0.57)
18 x 18(5.5 x 5.5) 18(68) 13.5(0.93)
20 x 20 (6.1 x 6. 1) 20(76)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
The sprinkler must be installed into a ceiling with the listed cover plate installed.
Bulletin 135 Page 7 of 15
October 2019 . - www.reliablesprinkler.com
CCP Recessed Escutcheon Installation
Technical Specifications
Style: Conical Concealed Pendant and
Recessed Pendent
Threads: 1/2' NPTor lS07-1R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PIFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
Recessed Escutcheons/Cover Plates
CCP Conical Concealed Plate 135°F (57°C)°
FP Recessed*
Sprinkler Wrenches
Model GFR2 (Recessed)
*Note: Model FP escutcheons and COP cover plates are not for use in positively pressurized ceiling plenums.
Model Fl Res58 CCP and FP Recessed Pendent Sprinkler Installation Dimensions 1l1T7'
2-5/16"
(59mm)DIA.
ace of fitting
to finished
ceiling
I ____________________________________
Face of fitting
to finished
ceiling I
-1I4(32mm)
(-1/4°(6mm) , [
I 1-1/4(32mm)
__________ 1/4 (6mm)
(24mm) ... .+/-1/4(6rnrn)
L3-3/16"(78mm) DIA.
FP Recessed Escutcheon Installation
Model Fl Res58 CCP Pendent & FP Recessed Pendent Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems()
Maximum Coverage AreaR
ft. x ft. (m x m)
Flow gpm
(I/mm)
Pressure psi
(bar) Deflector to Ceiling
Distance
16 x 16(4.9 x 4.9) 16(61) 7.6(0.52)
1/2 to 1 inch
(13 to 25 mm) 18 x 18(5.5 x 5.5) 19(72) 10.8 (0.75)
20 x 20(6.1 x 6.1) 22(83) 14.4(1.0)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
The sprinkler must be installed into a ceiling with the listed cover plate installed.
Bulletin 135 Page B of 15
October 2019 -. www.reiiablesprinkler.com
CCP Recessed Escutcheon Installation
Technical Specifications
Style: Conical Concealed Pendent and
Recessed Pendent
Threads: 3/4" NPT or 1S07-1 R3/4
Nominal K-Factor: 7.6(109 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
Recessed Escutcheons/Cover Plates
CCP Conical Concealed Plate 135°F (57°C)°
FP Recessed*
Sprinkler Wrenches
Model GFR2 (Recessed)
*Note: Model FP escutcheons and COP cover plates are not for use in positively pressurized ceiling plenums.
Model Fl Res76 CCP and FP Recessed Pendent Sprinkler Installation Dimensions
2-5/8° (67mm)
DIA.
2-5/16°
(59mm)DIA.
ceof fitting
0 finished
ceiling
-- 1 ' I _______________________________
Face of fitting
to finished
ceiling IIIi ..I
/4° (32mm) I I 1-1/4°(32mm)
1/4°(6mm) 1/4° (6mm) ,
24mm) - .
-
\rV +/1/4°(6rnm)
L3-3/18"(78mm) DIA. -
FPRecessedEscutcheonInstallation
Model Fl Res76 CCP Pendent & FP Recessed Pendent Hydraulic Design Criteria
Minimum Flow and Residual Pressure In Wet Pipe Systems")
Maximum Coverage Aream Flow Pressure Deflector to Ceiling Distance ft. x ft. (mx m) gpm (1/mm) psi (bar)
16 x 16(4.9 x 4.9) 21(80) 7.6(0.52)
1/2 to 1 inch
(13 to 25 mm)
10.8 (0.75)
18 x 18(5.5 x 5.5) 22(83) 8.4(0.58)
20 x 20(6.1 x 6.1) 25(95)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
The sprinkler must be installed into a ceiling with the listed cover plate installed.
Bulletin 135 Page 9 of 15
October 2019 - - www.reliablesprinkler.com
Technical Specifications
Style: Sidewall and Recessed Sidewall
Threads: 1/2' NPT or 1507-1R1/2
Nominal K-Factor: 4.4 (63 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
175°F (79°C)
Recessed Escutcheons
F2 Recessed
FV Recessed
Sprinkler Wrenches
Model W2
Model GFR2 (Recessed)
Model Fl Res44 Horizontal Sidewall Sprinkler Installation Dimensions
Face of fitting
to finished wall 1-5/8" (41 mm)
3/8" (10mm) +1- 1/4" (6mm)
+1- 1/4° (6mm)
- 2-7/16" (62mm)- -
1? 5;16J
(8mm)
21/40 1-15/16°
(57mm) (49mm) -
DIA. DIA.
Top of Deflector Down from
- Ceiling to be Either 4" to 6"
(100 to 150 mm) or 6" to 12"
(150 to 300 mm) Based on
Hydraulic Calculations
Dimensions F2 & FV RecessedEscutcheon Installation
Model FlRes44 Horizontal Sidewall Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems")
Maximum Coverage Aream
ft. x ft. (m x m)
Flow
gpm (1/mm)
Pressure
psi (bar)
Deflector to
Ceiling Distance
12 x 12(3.7 x 3.7) 12(45) 7.5(0.52)
4 to 6 inches
(100 to 150 mm)
18.7(1.29)
14 x 14(4.3 x 4.3) 14 (53) 10.2(0.70)
15 x 15(4.6 x 4.6) 15(57) 11.6(0.80)
16 x 16(4.9 x 4.9) 16(61) 13.3 (0.92)
16 x 18 (4.9 x 5.5) 18(68) 16.8(1.16)
16 x 20(4.9 x 6.1) 23(87) 27.4(l.89)
18 x 18(5.5 x 5.5) 19(72)
12 x 12(3.7 x 3.7) 14 (53) 10.2 (0.7)
6 to 12 inches
(150 to 300 mm)
27.4(l.89)
14 x 14(4.3 x 4.3) 16(61) 13.2(0.91)
15 X 15(4.6 x 4.6) 16(61) 13.2(0.91)
16 x 16(4.9 x 4.9) 17(64) 15.0(1.03)
16 x 18(4.9 x 5.5) 20(76) 20.7(l.43)
16 x 20(4.9 x 6.1) 23(87)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 Page 100115
October 2019 - www.reliablesprinkler.com
Technical Specifications
Style: Conical Concealed Sidewall
Threads: 1/2 NPTor ISO 7-1 R1/2
Nominal K-Factor: 4.4 (63 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass-bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PIFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
175°F (79°C) (1)
Cover Plates
SWC Conical Concealed Plate(2)
SWC-2 (Slotted) Conical Concealed Plate131
Sprinkler Wrenches
Model GFR2
Note:
"Not for installation where the maximum ceiling temperature exceeds 100°F due to cover plate temperature rating.
21135°F SWC Conical Concealed Plate for 155°F (68°C) sprinklers
131135°F SWC-2 (Slotted) Conical Concealed Plate for 175°F (79°C) sprinklers
Model F1Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler and Installation Dimensions
1'(25mm) 1"25mm
+1- 1/4 (6mm) +1- 1I4 (6mm)
Face of fitting
to finished wait I
- -2-7/16 )62mm)--.
5Il6 J (8mm)
Dimensions
- --
!1
il
- 15/8,
(41mm)
swc & SWC-2 Concealed Cover Plate Installation
Top of Deflector Down
from Ceiling lobe Either
4 to 6 (100mm to (84mm)
150mm) or 6to 12 DIA.
(150mm to 300mm) I
Based on Hydraulic I
Calculations I
Model F1Res44 SWC Conical Concealed Horizontal Sidewall Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systemst')
Maximum Coverage Area(2)
ft. x ft. (m x ni)
Ordinary Temperature Rating
155°F (68°C)
Intermediate Temperature Rating
175°F (79°C) Deflector to Ceiling
Distance
psi (bar)
Flow
gpm (I/mm)
Pressure
psi (bar)
Flow
gpni (I/mm)
Pressure
12 x 12(3.7 x 3.7) 13(49) 8.7 (0.60) 14(53) 10.2 (0.7)
14 x 14 (4,3 x 4.3) 14(53) 10.2(0.7) 14(53) 10.2 (0.7)
15 x 15(4.6 x 4.6) 16(61) 13.2(0.91) - - - - 4 to 6 inches
16 x 16 (4.9 x 4.9) 17(64) 15.0(1.03) -- -- (100 to 150 mm)
16 x 18(5.5 x 5.5) 19(72) 18.7(1.31) -- --
16 x 20(4.9x 6.1) 23(87) 27.4(l.89) -- --
12 x 12(3.7 x 3.7) 14(53) 10.2 (0.7) - - --
14 x 14(4.3 x 4.3) 15(57) 11.7(0.81) - -
15 x 15 (4.6 x 4.6) 17 (64) ' 15.0(1.03) - -
- -
6 t 12 inches
(150 to 300 mm)
16 x 16 (4.9 x 4.9) 18(68) 16.8(1.16) --
16x 18 (4.9x5.5) 20(76) 20.7(1.43) -- --
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger niax. coverage area listed.
Bulletin 135 Page 11 of 15
October 2019 Rellabld www.reliablesprinkler.com
Technical Specifications
Style: Sidewall and Recessed Sidewall
Threads: 1/2 NPTor IS07-1R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Material Specifications
Thermal Sensor: 3 mm glass bulb
Sprinkler Frame: Brass Alloy
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Bronze Alloy
Finishes
(See Table N)
Temperature Ratings
155°F (68°C)
175°F (79°C)
Recessed Escutcheons
F2 Recessed
FV Recessed
Sprinkler Wrenches
Model W2
Model GFR2 (Recessed)
Model F1Res58 Residential Horizontal Sidewall Sprinkler Installation Dimensions
Face of fitting
to finished wall 1-5/8° (41mm)
3/8°(lomm) +1- 1/4° (6mm)
+/- 1/4° (6mm)
—2-7/16 (62mm)---.-J
5/16°
(8mm)
Dimensions
1-15/16° i 1 Jk
F2 & FV Recessed Escutcheon Installation
Top of Deflector Down from
Ceiling to be Either 4° to 6°
(100 to 150 mm) or 6 to 12°
(150 to 300 mm) Based on
Hydraulic Calculations
Model Fl Res58 Horizontal Sidewall Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems(1)
Maximum Coverage ArearA
ft. x ft. (m x m)
Flow
gpm (I/mm)
Pressure
psi (bar)
Deflector to
Ceiling Distance
12 x 12(3.7 x 3.7) 16(61) 7.6(0.52)
4 to 6 inches
(100 to 150 mm)
25.0 (1.72)
14 x 14 (4.3 x 4.3) 18(68) 9.7 (0.66)
15 x 15(4.6 X 4.6) 19(72) 10.7 (0.74)
16 x 16(4.9 x 4.9) 21(80) 13.2(0.91)
16 x 18(5.5 x 5.5) 25(95) 18.6(l.28)
16 x 20(4.9 x 6.1) 29(110)
12 x 12(3.7 x 3.7) 22(83) 14.4(l.0)
6 to 12 inches
(150to300mm)
28.6(l.97)
14 x 14(4.3 x 4.3) 22(83) 14.4(1.0)
15 x 15 (4.6 x 4.6) 24(91) 17.1 (1.18)
16x 16(4.9x4,9) 26(98) 20.1 (1.39)
16 x 18 (4.9 x 5.5) 31(117)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 Page 12 of 15
October 2019 - www.reliablesprinkler.com
Finishes
Technical Specifications (See Table N)
Style: Sidewall and Recessed Sidewall
Threads: 1/2 NPT or 1507-1R1/2 Temperature Ratings
Nominal K-Factor: 5.8 (84 metric) 155°F (68°C)
Max. Working Pressure: 175 psi (12 bar) 175°F(79°C)
Material Specifications Recessed Escutcheons
Thermal Sensor: 3 mm glass bulb F2 Recessed
Sprinkler Frame: Brass Alloy FV Recessed
Button: Copper Alloy
Sealing Assembly: Nickel Alloy with PTFE Sprinkler Wrenches
Load Screw: Bronze Alloy Model W2
Deflector: Bronze Alloy Model GFR2 (Recessed)
Model Fl Res58 HSWX Residential Horizontal Sidewall Sprinkler Installation Dimensions
2-7/8°(73mm) -
5/16
(8mm)
Dimensions
Face of titling
to finished wall 1-7/8° (48mm)
3/8°(10mm) +1- 1/4"(6mm)
+/- 1/4° (6mm)
2-1/4° 1-15/16° jj I jJ (5f
F2&FV Recessed Escutcheon Installation
Top of Deflector Down From
Ceiling to be Either 4° 106°
(100 to 150 mm) or 6 to 12
(15010300mm) Based on
Hydraulic Calculations
Model F1Res58 HSWX Horizontal Sidewall Sprinkler Hydraulic Design Criteria
Minimum Flow and Residual Pressure in Wet Pipe Systems11
Maximum Coverage Area2
ft. x ft. (m x m)
Flow
gpm (I/mm)
Pressure
psi (bar)
Deflector to
Ceiling Distance
18x20(5.5x6,1) 30(114) 26.8(1.85)
4 to 6 inches
(100 150rn)
52.4(3.63)
20 x 20(6.1 x 6.1) 30(114) 26.8(1.85)
16 x 22(4.9 x 6.7) 33(125) 32.4(2.23)
16 x 24(4.9 x 7.3) 38(144) 42.9(2.96)
14 x 26(4.3 x 7.9) 42(160)
18 x 20 (5.5 x 6.1) 35(133) 36.4(2.51)
610 12 inches
(15010300mm)
62.9(4.34)
16 x 22 (4.9 x 6.7) 38(144) 42.9 (2.96)
16 x 24(4.9 x 7.3) 42(160) 52.4 (3.61)
14 x 26(4.3 x 7.9) 46(174)
Notes:
For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in the table above or (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 135 Page 13 of 15
October 2019 www.reliablesprinkler.com
Finishes
Standard Finishes Special Application Finishes
Sprinkler'" Fl, F2. FV, FP'3t, CCP, SWC (Conical) Sprinkler (1) Fl, F2. FV, FP'', CCP, SWC (Conical)
Escutcheons Cover Plates (1) Escutcheons Cover Plates (1)
Bronze Brass -- Bright Brass Bright Brass Bright Brass
Chrome Plated Chrome Plated Chrome Plated Dull Chrome Dull Chrome Dull Chrome
White
Polyester(2)
White
Polyester White Paint Black
Polyester (2)
Black
Polyester Black Paint
-- -- --
Custom Color Custom Color Custom Color Paint Polyester Polyester
Electroless Nickel -- --
-- PTFE'2' -- --
Notes:
Paint or any other coating applied over the factory finish will void all approvals and warranties.
cULus Listed Corrosion Resistant.
The Model FP escutcheon assembly consists of an unfinished galvanized cup with a finished escutcheon ring.
Installation
Models Fl Res sprinklers are to be installed as shown in this
bulletin. Model Fl F2, FV, and FP recessed escutcheons
are the only recessed escutcheons to be used with Model
Fl Res sprinklers. Not all Fl Res sprinklers may be used with
all recessed escutcheons offered. Confirm listing of escutch-
eon type for use with individual sprinklers. Use of any other
recessed escutcheon will void all approvals and warranties.
For installing Model Fl Res sprinklers, use only the Model
W2 sprinkler Wrench; for installing Models Fl Res Recessed
Pendent, Sidewall, Conical Concealed Pendent (CCP), and
Sidewall Concealed (SWC and SWC-2) sprinklers use only
the Model GFR2 sprinkler wrench. Use of wrenches other than
those specified may damage these sprinklers.
Model W2
Model GFR2
Installation of Fl Res sprinklers in a wall or ceiling will require
a hole diameter of 2-1/4" (57 mm) for Fl or F2 recessed
escutcheons; or 2-5/8" (67 mm) for FP recessed escutcheons,
CCP, SWC, and SWC-2 cover plates.
Install Fl Res HSW sprinklers with a ceiling to deflector dis-
tance that complies with the hydraulic design criteria tables in
this bulletin. The flow arrow on deflector must point away from
near wall and "Top" marking must face the ceiling.
A 'leak tight" sprinkler joint can be obtained with the following
torque:
1/2" NPT and 1S07-1R1/2: 8-18 ft-lbs (11 —24 N-m)
3/4" NPT and 1507-1R3/4: 14-20 ft-lbs (19-27 N-m)
Do not tighten sprinklers over maximum recommended torque.
This may cause leakage or impairment of the sprinklers.
Do not install any glass bulb sprinklers where the bulb is
cracked or there is a loss of liquid from the bulb.
Glass bulb sprinklers have orange bulb protectors to mini-
mize bulb damage during shipping, handling and installation.
Remove this protection at the time the sprinkler system is
placed in service. Removal of the protectors before this time
may leave the bulb vulnerable to damage. RASCO wrenches
are designed to install sprinklers when protectors are in place.
Remove protectors by undoing the clasp by hand. Do not use
tools to remove the protectors.
Maintenance
Reliable Model Fl Res Sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25, 13,
13D, and 13R, as well as the requirements of any Authorities
Having Jurisdiction.
Prior to installation, sprinklers should remain in the original
cartons and packaging until used. This will minimize the
potential for damage to sprinklers that could cause improper
operation or non-operation.
Do not clean sprinklers with soap and water, ammonia liquid
or any other cleaning fluids. Remove dust by gentle vacuum-
ing without touching the sprinkler.
Replace any sprinkler which has been painted (other than
factory applied). Properly installed CCP, SWC, and SWC-2
cover plates will have an air gap that is required for proper
operation, do not seal the gap or paint the cover plates.
Bulletin 135 Page 14 of 15
October 2019 www.reliablesprinkler.com
Replace any sprinkler which has been damaged, where
cracks are observed in the glass bulb, or when liquid has
been lost from the glass bulb.
A stock of spare sprinklers should be maintained to allow
quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadver-
tent operation or non-operation during a fire event.
Listings & Approvals
Listed by Underwriters Laboratories Inc. and UL Certified for
Canada (cULus)
Guarantee s
For Reliable Automatic Sprinkler Company guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Patents
For patents applicable to products contained in this technical
bulletin, please visit www.r-s.co
Ordering Information
Specify the following when ordering:
Sprinkler
Model (See Table A)
Temperature Rating
Threads (NPT or 507-1)
Finish (See Table N)
Escutcheon or Cover Plate
Model
Finish (See Table N)
Sprinkler Wrench
Model W2 (Pendent and HSW)
GFR2 (Recessed and Concealed)
z
Bulletin 135 Page 15 of 15
October 2019 www.reliabIesprinkler.com
Pendent
I
Horizontal Sidewall
Model Fl FR Series
Quick Response
Glass Bulb Sprinklers
Recessed
Pendent/FP
It
I
XLH Recessed
Pendent F1 /F2
XLH Upright XLH Pendent
Bulletin 014 March 2019
Re.1 a,bk
Model Fl FR56 Sprinkler Types
Standard Spray Upright
Standard Spray Pendent
Conventional Upright/Pendent
Vertical Sidewall
Horizontal Sidewall
Model Fl FR56 Recessed Sprinkler Types
Standard Spray Pendent
Horizontal Sidewall
Model Fl FR56 Concealed Sprinkler Types
Standard Spray Pendent
Model F1FR42, F1FRXLH & F1FR28 Sprinkler
Types
Standard Spray Upright
Standard Spray Pendent
Model Fl FR40 Sprinkler Types
Standard Spray Pendent
Model Fl FR42, Fl FR40, Fl FRXLH & Fl FR28
Recessed Sprinkler Types
Standard Spray Pendent
Model Fl FR56LL & Fl FR42LL Low Lead Sprinkler
Types
Standard Spray Pendent with less than 0.25% Lead
Content
Listing & Approvals
The following organizations provide Listings or Approvals
for various Model El FR series sprinklers. See the Design
and Installation table in this Bulletin for information on
specific listings and approvals applicable to each sprin-
kler.
Underwriters Laboratories Inc. and Certified for
Canada (cULus) in accordance with ANSI/UL199.
FM Approvals (FM)
Loss Prevention Certification Board (LPCB)
VdS SchadenverhUtung GmbH (VdS)
Underwriters Laboratories Inc. and Underwriters
Laboratories of Canada Certified for Health Effects
to NSF/ANSI Standard 61 Annex G (ULH)
EC Certificate: 0786-CPD-40239 (RA1414), 0786-
CPD-40251 (RA1 425), 0786-CPD-40252 (RA1 475)
(EC)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Model Fl FR series sprinklers
are quick-response automatic sprin-
klers with a glass bulb thermal element. 40 Model El FR series sprinklers are Stan-
dard Spray sprinklers, with the excep-
tion of the Model Fl FR56 Conventional XLH Recessed
sprinkler which is an Old-style/Conven- Pendent FP
tional sprinkler.
The Model Fl FR Series automatic sprinklers utilize a 3.0
mm frangible glass bulb. These sprinklers have demonstrat-
ed response times in laboratory tests which are five to ten
times faster than standard response sprinklers. This quick
response enables the Model Fl FR Series sprinklers to apply
water to a fire faster than standard-response sprinklers of the
same temperature rating.
The glass bulb consists of an accurately controlled amount
of special fluid hermetically sealed inside a precisely man-
ufactured glass capsule. This glass bulb is specially con-
structed to provide fast thermal response.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Model Fl FR Series sprinklers provide a wide range of op-
tions where quick-response, glass bulb sprinklers are used:
Pendent, recessed pendent, upright, horizontal
sidewall, and vertical sidewall deflectors
K-factors of 2.8 (40 metric), 4.0 (57 metric), 4.2 (60
metric), and 5.6 (80 metric)
Flush, recessed, and concealed installations
See the Design and Installation Information table in this
Bulletin for information on the approvals and availability of
specific Model Fl FR series sprinkler configurations.
Model Fl FR Recessed Pendent and Recessed Horizon-
tal Sidewall sprinklers are required to be used with Reliable
Model Fl, F2, or FP recessed escutcheons. See the Re-
cessed Escutcheon Data table in this Bulletin for listing and
approval information with each specific Model El FR series
sprinkler. Model Fl and F2 recessed escutcheons, shown in
Fig. 1 and 3, are a friction fit assembly allowing for 3/4-inch
(19mm) and 1/2-inch (12.7mm) of adjustment, respectively.
Model FP recessed escutcheons, shown in Fig. 2, provide a
1/2-inch (12.7mm) threaded adjustment.
Model Fl FR56 Concealed Pendent and Model El FR56LL
Concealed Pendent sprinklers are required to be used with
Model CCP cover plates. A standard profile Model CCP cov-
er plate is available that provides up to 1/2-inch (12.7mm) of
cover plate adjustment. In addition, a low profile Model CCP
cover plate is also available that provides up to 5/16-inch
(8.0mm) of cover plate adjustment. See the Design and In-
stallation Information and Listed and Approved Temperature
Ratings tables in this Bulletin for further information on ap-
proved cover plate options.
Application
Model F1ER Series sprinklers are intended for use in
accordance with NFPA 13, FM Property Loss Prevention
Data Sheets, and the requirements of the Authority Hav-
ing Jurisdiction. Care must be exercised that the k-factor,
temperature rating, deflector style, and sprinkler type are
in accordance with the requirements of the applicable
design and installation standards. In addition, Model
El ER Series sprinklers must be used in accordance with
their listings and approvals, as well as the information
provided in this Bulletin.
Installation
Glass bulb sprinklers have orange bulb protectors or pro-
tective caps to minimize bulb damage during shipping, han-
dling and installation. Reliable sprinkler installation wrench-
es are designed to install sprinklers with bulb protectors in
place. Remove the bulb protector at the time when the sprin-
kler system is placed in service for fire protection. Removal
of the bulb protector before this time may leave the bulb vul-
nerable to damage. Remove bulb protectors by undoing the
clasp by hand. Do not use tools to remove bulb protectors.
2.
Model F1 FIR Series sprinklers must be installed with the
Reliable sprinkler installation wrench identified in the Design
and Installation Information table in this Bulletin. Any other
wrench may damage the sprinkler. A leak tight sprinkler joint
can be obtained with a torque of 8 to 18 lb-ft (11 to 24 N-m).
Do not tighten sprinklers over the maximum recommended
installation torque. Exceeding the maximum recommended
installation torque may cause leakage or impairment of the
sprinkler.
Recessed Sprinklers
Model El ER Series Recessed sprinklers are to be installed
as shown in Fig. 1 Fig. 2, or Fig. 3, as applicable to the spe-
cific model being installed. The Recessed Escutcheon Data
table in the Bulletin identifies the only recessed escutcheons
that are permitted to be used with each Model El FR Series
Recessed sprinkler. The use of any other recessed escutch-
eon will void all approvals and negate all warranties.
Concealed Sprinklers
Model El ER Series Concealed Pendent sprinklers are to
be installed as shown in Fig. 4 or Fig. 5, as applicable to the
selected cover plate. Model E1FR56 Concealed Pendent
and Model Fl FR56LL Concealed Pendent sprinklers have
a factory-installed Model CCP cup. A protective cap is in-
stalled at the factory that should remain on the sprinkler until
the sprinkler is installed and should then be reinstalled on
the sprinkler until the cover plate is installed, The concealed
sprinkler assemblies are completed by the installation of a
Model CCP push-on/thread-off cover plate assembly. The
cover plate and sprinkler cup assemblies are joined using
a cover plate skirt with flexible tabs for threaded engage-
ment. A choice of two Model CCP cover plate assemblies
provides either 1/2-inch (13mm) or 5/8-inch (8mm) of cover
adjustment. Do not install Model FlEA Series Concealed
Pendent sprinklers in ceilings which have positive pressure
in the space above.
Model El FR Series Concealed Pendent sprinklers require a
2-5/8-inch (67mm) diameter hole to be cut in the ceiling. The
Model GF1R2 wrench is used to engage the sprinkler wrench-
ing surfaces and to install the sprinkler in the fitting. Remove the
protective cap to install the sprinkler, then reinstall the protective
cap until the cover plate is installed. When inserting or remov-
ing the wrench from the sprinkler/cup assembly, care should be
taken to prevent damage to the sprinkler. Do not wrench any
other part of the sprinkler/cup assembly. Installation is com-
pleted by removing the protective cap from the sprinkler and
pushing the cover plate onto the cup. Final adjustment is made
by hand turning the cover plate until the skirt flange makes full
contact with the ceiling. Cover plate removal requires turning the
cover plate in the counter clockwise direction. After installation,
inspect all sprinklers to ensure that there is a gap between the
cover plate and ceiling and that the four cup slots are open and
free from any air flow impediment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any concealed cover
plate/cup assembly other than the Reliable Model CCP with
Model F1FR56 Concealed Pendent and Model E1FR56LL
Concealed Pendent sprinklers or the use of the Model CCP
Concealed cover plate assembly on any sprinkler with
which it is not specifically listed my prevent good fire pro-
tection and will void all guarantees, warranties, listings and
approvals.
Technical Data:
Sensitivity: Quick-response
Thread Size: 1/2-inch NPT standard; ISO 7-R1/2 optional
Maximum Working Pressure: 175 psi (12 bar) - 100% Factory tested hydrostatically to 500 psi (34.5 bar)
SIN RA1425, RA1414 & RA1435 cULus listed for 250 psi (17 bar)
Design and Installation Information
Model
Nominal
K-f actor
Nominal
Orifice
Diameter Deflector/
Orientation
Nominal
Sprinkler
Height _____
Installation
Wrench SIN
Approvals
Listings
and Approval
Notes
US Metric inches mm inches mm
F1FR28 2.8 40 3/8 10
Pendent 2.25 57 W2 RA1411 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1411 cULus 2
Upright 2.25 57 W2 RA1421 cULus 1,2
F1FR40 4.0 57 3/8 10 Pendent 2.25 57 W2 RA 1418 VdS
Recessed Pendent 2.25 57 GFR2 RA1418 VdS
F1FR42 4.2 60 7/16 10
Pendent 2.25 57 W2 RA1413 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 W2 RA1423 cULus 1,2
F1FR42LL 4.2 60 7/16 10 Pendent 2.25 57 W2 RA1410 cULus, ULH
Recessed Pendent 2.25 57 GFR2 RA1410 cULus, ULH
F1FRXLH
(F1FR42
with Pintle)
4.2 60 7/16 10
Pendent 2.25 57 W2 RA1413 cULus 2
Recessed Pendent 2.25 57 GFR2 RA1413 cULus 2
Upright 2.25 57 W2 RA1423 cULus 1,2
F1FR56 5.6 80 1/2 15
Pendent 2.25 57 W2 RA1414 cULus FM, ,
LPCB, VdS, EC
1,2,3,4
Recessed Pendent 2.25 57 GFR2 RA1414 cULus, FM,
LPCB, VdS, EC
12,3,4
Concealed Pendent 2.25 57 GFR2 RA14141 cULus,VdS,EC 5,6
Upright 2.25 57 W2 RA1425 cULus, FM,
LPCB, VdS, EC
1,2,3,4
"Conventional
(Pendent or Upright)" 2.25 57 W2 RA1475 LPCB, VdS, EC 4
F1FR56LL 5.6 80 1/2 15
Pendent 2.25 57 W2 RA1415 cULus, ULH 1
Recessed Pendent 2.25 57 GFR2 RA14151 cULus, ULH
Concealed Pendent 2.25 57 GFR2 RA14151 cULus, ULH 6
F1FR56 5.6 80 1/2 15
Horizontal Sidewall 2.63 67 W2 RA1435 cULus, FM 1,2,3,7
Recessed Horizontal 2.63 67 Sidewall
GFR2 RA1435 cULus, FM 8
F1FRS6 5.6 80 1/2 15 Vertical Sidewall
(Pendent or Upright) 2.25 57 W2 RA1485 cULus, FM,
LPCB
1,2,3,9
cULus Listed Corrosion Resistant sprinkler when ordered with available Polyester coating.
cULus Listed Corrosion Resistant sprinkler when ordered with available Electroless Nickel PIFE plating.
(31 Available with FM approved Polyester coating in black or white.
Available with LPCB and VdS approved Polyester coating.
VdS and EC approvals of the Fl FR56 concealed Pendent sprinkler are for 155°F (68°C) temperature rated sprinklers only. VdS approved sprin-
klers must use Norbulb brand glass bulbs with the 1/2-inch (12.7mm) adjustment Model CCP cover plate only.
Model Fl FR56 Concealed Pendent and Model Fl FR56LL concealed Pendent sprinklers must be used with Reliable Model CCP cover plates,
available as either standard depth with 1/2-inch (12.7mm) of adjustment or low profile with 5/16-inch (8.0 mm) of adjustment.
cULus Listing of the F1 FR56 Horizontal Sidewall sprinkler is for Light and Ordinary Hazard occupancies only. Minimum to maximum deflector to
ceiling distance shall be 4 inches to 12 inches (102mm to 305mm). FM Approval of the Fl FR56 Horizontal Sidewall sprinkler is for Light Hazard
occupancies Only.
cULus Listing and FM Approval of the Fl FR56 Recessed Horizontal Sidewall sprinkler is for Light Hazard occupancies only.
The Fl FR56 Vertical Sidewall sprinkler is listed and approved for use only in Light Hazard occupancies. LPCB approval of the Fl FR56 Vertical
Sidewall sprinkler is for installation in the Pendent position only.
3.
Listed and Approved Temperature Ratings
Model Deflector!
Orientation
Ordinary Temp.
Classification
100°F (38°C) Max.Ambient
Temp.
Intermediate Temp.
Classification
150°F (65°C) Max. Ambient
Temp.
High Temp.
Classification
225°F (1070C) Max.
Ambient Temp.
135°F (57°C)
Temp. Rating
I 155°F (68°C) I Temp. Rating
175°F (79°C)
1 Temp. Rating
I 200°F (93°C)
I Temp. Rating
286°F (141°C) Temp.
Rating
Orange Bulb Red Bulb I Yellow Bulb Green Bulb Blue Bulb
Pendent cULus
F1FR28 Recessed Pendent cULus I
Upright cULus
FIFR4O Pendent VdS
Recessed Pendent VdS I
Pendent cULus
Fl FR42 Recessed Pendent cULus I
Upright cULus
F1FR42LL Pendent I cULus, ULH I Recessed Pendent I cULus, ULH
Pendent cULus
Fl FRXLH Recessed Pendent cULus I Upright cULus
Pendent cULus, FM, LPCB, VdS, EC
Recessed Pendent cULus, FM, LPCB, VdS, EC I
FIFRS6 Concealed Pendent* cULus cULus,VdS,EC I cULus
Upright cULus, FM, LPCB, VdS, EC
"Conventional
(Pendent or Upright)" LPCB, VdS, EC
Pendent I cULus, ULH I
F1FR56LL Recessed Pendent I cULus, ULH
Concealed Pendent* I cULus, ULH I
Horizontal Sidewall cULus, FM
Fl FR56 Recessed Horizontal
Sidewall cULus, FM I I
F1FRS6 Vertical Sidewall (Pen-
dent _or_Upright) cULus, FM, LPCB
* Model Fl FR56 Concealed Pendent and Fl FR56LL Concealed Pendent sprinklers must be used with Reliable Model
COP cover plates. For Ordinary Temperature Classification sprinklers use a 135°F (57°C) temperature rated cover
plate. For Intermediate Temperature Classification sprinklers use a 1650F (740C) temperature rated cover plate.
Recessed Escutcheon Data
Listed and Approved Recessed Escutcheons
Deflector! Model Fl Model F2 Model FP
Model Orientation (Fig. 1 & 3) (Fig. I & 3) (Fig. 2) SIN
3/4-inch (19mm) 1/2-inch (12.7mm) 1/2-inch (12.7mm)
adjustment adjustment adjustment
FIFR28 Recessed Pendent cULus cULus cULus RA1411
F1FR40 Recessed Pendent VdS VdS VdS RA1418
F1FR42 Recessed Pendent cULus cULus cULus RA1413
F1FR42LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1410
F1FR42XLH Recessed Pendent cULus cULus cULus RA1413
F1FR56 Recessed Pendent cULus, LPCB, VdS, cULus FM LPCB, cULus, VdS, EC RA1414
F1FR56LL Recessed Pendent cULus, ULH cULus, ULH cULus, ULH RA1415
F1FRS6 Recessed Horizontal Sidewall cULus cULus, FM cULus RA1435
4.
J T AT MAXIMUM RECESS = 7/8"[22.2mm]
(3.2mm] I / AT MINIMUM RECESS = 1-5/8 "[41.3mm]
F2 ESCUTCHEON I AT MAXIMUM RECESS = 1- 1/8"[28. 6mm]
AT MINIMUM RECESS
A A Ft ESCUTCHEON
2 1/4" HOLE 014.
(57.2mm]
I 75/16" 014
[49.2mm]
11 --------
-
Ii (
\ /
/—o
TURN COLLAR
UNTIL TIGHT
AGAINST SPRINKLER
WRENCH BOSS __\\\\
Fl ESCUTCHEON_L. 3/4719mm]
ADJUSTMENT
F2 ESCUTCHEON
1/2"[12.7mm]
ADJUSTMENT f
1 X 1/2" REDUCER
FACE OF FITTING
TO FACE OF CEILING DIMENSION
F! ESCUTCHEON
AT MAXIMUM RECESS = 1 "[25.4mm]
____ AT MINIMUM RECESS = 3/8"[9.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 3/4"[l9mm]
-7777771 I AT MINIMUM RECESS = 3/8"[9.5mm]
2 27/32" 014.
[72.2mm]
Model F1F1R56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH & F1FR28
Recessed Pendent sprinkler with Model Fl or F2 escutcheon
2 5/8' DI 66.7mm
1" X 1/2" REDUCER
HOLE IN CEILING
2 5/16" DIA. [58.7mm]
CUP
EMJ
CEILING
AT MINIMUM RECESS
FACE OF FITTING
- TO FACE OF CEILING
DIMENSION
L I I
AT MAXIMUM RECESS = 1-1/2738mm]
AT MAXIMUM RECESS = 9/16"[14.3mm]
Y2 "[12.7mm] AT MINIMUM RECESS = 1 "[25.4mm]
ADJUSTMENT __________
31/4"DIA.
[82.6mm]
Model F1FOR56, F1FR56LL, F1FR42, F1FR40, F1FR42LL, F1FRXLH & F1FR28
Recessed Pendent sprinkler with Model FP escutcheon
5.
Fl ESCUTCHEON L.4 AT & IA %/iIIII&I nerrer - 4 7 Jo "r. n__ IiI IWPtAIIW(JM C&.C..) = I .'/O L..)?.mmJ
AT MINIMUM RECESS = 2-1/16 r52. 4mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 1-5/8"[4 1.3mm]
'-1/8" AT MINIMUM RECESS = 2- 1/16"[52.4mm]
[3.2mm]
V (j)
4"-12"
32" DIA. CEILING TO
[72.2mm] DEFLECTOR
Fl ESCUTCHEON
-H 3/4"[19mm] ADJUSTMENT
F2 ESCUTCHEON
1/2"[12. 7mm] ADJUSTMENT
FACE OF FITTING
TO FACE OF CEILING DIMENSION
Fl ESCUTCHEON
AT MAXIMUM RECESS = 1 [25.4mm]
AT MINIMUM RECESS = 3/89.5mm]
F2 ESCUTCHEON
AT MAXIMUM RECESS = 3/4 "[19mm]
AT MINIMUM RECESS = 3/8"[9.5mm]
2 1/4" HOLE 0/A.
[57.2mm]
1" X 1/2" REDUCER
I ilIIlI
1 15/16" DIA. 4jJ4
[49.2mm] lull
11111
I --
TURN COLLAR UNTIL -,
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
RECESSED HSW W/F1 OR F2 ESCUTCHEON
(1) FM APPROVED FOR 4" - 6" [10 1.6MM - 152.4MM] CEILING TO DEFLECTOR WITH F2 ONLY.
Fig.3
Model Fl FR56 Recessed Horizontal Sidewall sprinkler Wth Model Fl or F2 escutcheon
1" x 1/2" REDUCING TEE OR ELBOW
TT
l
- 25/8 DIA.
.1 HOLE IN CEILING
1 1/2" MAX.
FACE OF FITTING
TO FACE OF CEILING DIMENSION
1/2" MAX. .. COVER ADJUSTMENT
COVER PLATE ASSEMBLY _____/ 5/16" DIA.
SPRINKLER
CONCEALED, 1/2" ADJUSTMENT
Ftg.4
Model Fl FR56/F1 FR56LL Concealed Pendent sprinkler with standard depth
1/2-inch (12.7mm) adjustment- Model COP cover plate
2 5/16" DIA - u
CUP
CEILING
15/16"
017FG01A
1" x 1/2" REDUCING
TEE OR ELBOW
—FE__
____
25/8 0/A.
2 5/16" 0/A - 1' .'PHOLE IN CEILING
CUP —.
M vu 1 1/2k' MAX.
TT
—4tJH--- FACE OF FITTING
II [ To FACE OF CEILING
kktt )I FT DIMENSION
CEILING—" MY -F-- '- I
5/16" MAX. J 3/4"
COVER ADJUSTMENT
COVER PLATE— I
ASSEMBLY • 3 5/16" 0/A
SPRINKLER
CONCEALED, 5Z16" ADJUSTMENT 017FG0
Hg. 5- Model Fl FR56IF1 FR56LL Concealed Pendent spnnkler with low profile
5/16-inch (8.0mm) adjustment - Model CCP cover plate
Maintenance
The Model Fl FR Series sprinklers should be inspected and
the sprinkler system maintained in accordance with NFPA
25. Do not clean sprinklers with soap and water, ammonia or
any other cleaning fluids. Remove dust by using a soft brush
or gentle vacuuming. Replace any sprinkler which has been
painted (other than factory applied) or damaged in any way.
A stock of spare sprinklers should be maintained to allow
quick replacement of damaged or operated sprinklers.
Finishes (1)
Standard Finishes
Sprinkler Escutcheon Cover pIate1
Bronze Brass Chrome
Chrome Plated Chrome Plated White
Polyester Coated (X5X) White Painted
Specpl Application Finishes
Sprinkler Escutcheon Cover plate111
Electroless Nickel
PTFEI7I
Electroless Nickel
PTFE Bright Brass
Bright Brass(3) Bright Brass Black Plating
Black Plated Black Plated Black Paint
Black Paint121161 Black Paint Off White
Off White 21161 Off White Satin Chrome
Chrome Dull I Chrome Dull I
Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
2) cULus Listed only.
(3) 200°F (93°C) maximum.
cULus listed "corrosion resistance" applies to SIN Numbers RA1435
(HSW), RA1485(vSw), RA1425 (Upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
FM Approvals finish as "Polyester coated" applies to SIN Number
RA1414, RA1435 and RA1425 in standard black or white.
LPCB and VdS Approved finish applies only to RA1425, RA1414, RA1418
(VdS) and RA1475.
cULus listed Corrosion Resistant
Material Data
Frame: DZR Brass, OM Brass, or Low Lead Brass
Deflector: CDA Alloy 220, 260, or 510
Load Screw\Pintle: CDA Alloy 360 or 544
Cup: CDA Alloy 651 or 693
Washer: Nickel Alloy 440 or 360, coated with PTFE
Adhesive Tape
Bulb: Glass
Ordering Information
Specify:
Sprinkler Model: [Fl FR28][F1 FR40][F1 FR421
[Fl FR42LL][F1 FRXLH][F1 FR56][F1 FR56LL]
Sprinkler Deflector/Orientation: [Pendent][Recessed
Pendent][Upright] [Conventional][Horizontal Sidewall]
[Recessed Horizontal Sidewall][Vertical Sidewall]
Sprinkler threads: [1/2-inch NPT][ISO 7-R112]
Sprinkler Temperature Rating: [135°F (570C)][155°F
(680C)][175°F (790C)][200°F (930C)][286°F (1410C)]
Sprinkler Finish
Escutcheon Model: [F1][F2][FP]
Escutcheon Finish (where applicable)
Cover plate Model: [standard profile CCP 1/2-inch
(12.7mm) adjustment] [low profile COP 5/16-inch
(8.0mm) adjustment]
Cover plate Temperature Rating: [135°F (57°C) for use
with Ordinary Temperature sprinklers][165°F (74°C)
for use with Intermediate Temperature sprinklers]
Cover plate Finish
Note: When Model Fl FR Series Recessed sprinklers are ordered, the
sprinklers and escutcheons are packaged separately.
Reliable ... For Complete Protection
Reliable offers a wide selection of sprinkler components. Following are some of the many
precision-made Reliable products that guard life and property from fire around the clock.
Automatic sprinklers
Flush automatic sprinklers
Recessed automatic sprinklers
Concealed automatic sprinklers
Adjustable automatic sprinklers
Dry automatic sprinklers
Intermediate level sprinklers
Open sprinklers
Spray nozzles
Alarm valves
Retarding chambers
Dry pipe valves
Accelerators for dry pipe valves
Mechanical sprinkler alarms
Electrical sprinkler alarm switches
Water flow detectors
Deluge valves
Detector check valves
Check valves
Electrical system
Sprinkler emergency cabinets
Sprinkler wrenches
Sprinkler escutcheons and guards
Inspectors test connections
Sight drains
Ball drips and drum drips
Control valve seals
Air maintenance devices
Air compressors
Pressure gauges
Identification signs
Fire department connection
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
® (800) 431-1588 Sales Offices Paper Reliabid
(800) 848-6051 Sales Fax Revision lines indicate updated or new data. (914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 03/19 P/N 9999970300