HomeMy WebLinkAboutCT 94-09; CARLSBAD RANCH UNIT 1 PHASE I; FINAL SOILS REPORT; 1997-03-12THIS DOCUMENT WAS ISSUED PREVIOUSLY AND MAY NOT REFLECT CURRENT SITE CONDITIONS AND/OR STANDARDS OF GEOTECHNICAL PRACTICE. THE CONTENTS OF THE DOCUMENT SHOULD NOT BE USED OR RELIED UPON WITHOUT A REVIEW BY QUALIFIED PROFESSIONALS.LEIGHTON & ASSOCIATES, INC.I I 11 I 11 I I FINAL AS-GRADED REPORT 1• OF ROUGH GRADING, CARLSBAD RANCH PHASE II, CARLSBAD, CALIFORNIA 1• 1• March 12, 1997 I Project No. 4930489-011 I I I I I. Prepared For: I CARLTAS COMPANY 5600 Avenida Encinas, Suite 100 I Carlsbad, California 92008-4452 I. I I I I I I I I I I I I I I I I I I I I To: Attention: Subject: March 12, 1997 Carltas Company 5600 Avenida Encinas, Suite 100 Carlsbad, California 92008-4452 Mr. Christopher C. Calkins Project No. 4930489-01 I Final As-Graded Report of Rough Grading, Carlsbad Ranch Phase II, Carlsbad, California In accordance with your request and authorization, Leighton and Associates, Inc. (Leighton) has provided geotecbnical services during rough-grading operations for Carlsbad Ranch Phase Il. This incJudes Lots l through 3, 5 through 11, 14, and Lego Drive to Station 21+-00 and Armada Drive fi-om St.ation 18+72 to Station 54+20, of the Carlsbad Ranch project in Carlsbad, California The accompanying final as-graded report summarizes our observations, field and laboratory test results, and the geotechnical conditions encountered during rough grading of the subject site. If you have any questions regarding our report, please contact this office. We appreciate this opportunity to be of service. KBC/JGF/MRS/jss Distribution: (4) Addressee (2) Steve Harrison Company Respectfully submitted, . Franzone, . 'Y· of Engin Michael R. Stewan, G 1349 (Exp. 12/31/97) Director of Geology •' ( r:o. 1349 CEPTIFIEO Nc;1;; .:F.RW.., ' / I I I I I I I I I I I I I I I I I I I 4930489-011 TABLE OF CONTENTS Section Page 1.0 INTRODUCTION ................................................. -.. . 2.0 SUMMARY OF FINE-GRADING OPERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.1 Site Preparation and Removals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.2 Fill Slope Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.3 Stability Fill Slope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.4 Subdrains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2.5 Underground Storage Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2.6 Vertical Seepage Pits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2. 7 Fill Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.8 Field Density Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.9 Laboratory Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.1 O Graded Slopes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 3 .0 ENGINEERING GEOLOGIC SUMMARY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3. 1 As-graded Geologic Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.2 Geologic Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.2. 1 Undocumented Fill (Unmapped) . . . . . . . . . . . . . . . . . . . . • . . . . . . . . . . . 6 3.2.2 Topsoil/Colluvium (Unmapped) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . • . 6 3.2.3 Terrace Deposits (Map Symbol -Qt) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.2.4 Santiago Fonnation (Map Symbol -Ts) . . . . . . . . . . . . . . . . . . . . . . . . . . 6 3.3 Geologic Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.4 Landslides and Surficial Failures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3 .5 Faulting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.6 Ground Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4.0 CONCLUSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.2 Summary of Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 5.0 RECO1\11vfENDATIONS................................................. 9 5. I Earthwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 • I • I I I I I I I I I I I I I I I I I I I 5_1_1 5.1.2 5.1.3 5.1.4 4930489-01 l TABLE OF CONTENTS (Continued) Site Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Excavations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Fill Placement and Compaction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Cut/Fill Transition Lots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.2 Foundation Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5.3 Sulfate Testing of Finish Grade Soils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.4 Control of Surface Water and Drainage Control . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.5 Pavement Design Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.6 Graded Slopes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 5.7 Construction Observation and Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 List of Accompanying Figure. Plates and Appendices Figure 1 -Site Location Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Plates l through 12 -As-Graded Geotechnical Maps . . . . . . . . . . . . . . . . . . . . . . . . . . . In Pocket Appendices Appendix A -References Appendix B -Field Density Tests Appendix C -Laboratory Testing Procedures and Test Results Appendix D -General Earthwork and Grading Specifications for Rough Grading -ii - I I I I I I I I I I I I I I I I I I I 4930489-0] 1 1.0 INTRODUCTION Jo accordance with your request and authorization, Leighton has performed geotechnical observation and testing services during the rough-grading operations of Carlsbad Ranch Phase 2, located in Carlsbad, California (Figure 1). Phase 2 grading for the Carlsbad Ranch project included Lots l through 3, 5 through 11, 14, and a portion of Lego Drive from its intersection with Armada Drive to Station 21+00, as well as a portion of Annada Drive from Station 18+72 to Station 54+20. This final as-graded report of rough grading summarizes our geotechnical observations, geologic mapping, field and laboratory test results and the geologic conditions encountered during rough grading of the subject site. In addition, this report provides conclusions and preliminary recommendations for the proposed development of the site. As of this date, rough-grading operations for the previously mentioned lots and street sections are essentially complete. Prior to the issue of this report, comprehensive lot specific geotechnical recommendations have been provided for Lots 1 through 3 (Carlsbad Company Stores site), Lot 8 (NAMM site), and portions of Lego and Annada Drives under separate cover (see References, Appendix A). Since the remainder of the subject site has been sheet-graded and specific plans for the development of individual lots/units has not been completed, an updated geotechnicaJ report including specific foundation design considerations, retaining wall parameters, structural setbacks, etc., based on the actual design and location of the proposed structures and other site improvements is required by a qualified geotechnical consultant prior to site development. The 40-scale grading plans for Carlsbad Ranch Unit l, prepared by O'Day Consultants (O'Day, 1996), as well as the 40-scaJe grading plans prepared by Hunsaker and Associates (Hunsaker, 1996) were used as base maps to present the as-graded geotechoical conditions and approximate locations of the field density tests within the Jim its of the current phase of grading operations. The As-Graded Geotechnical Maps are presented as Plates 1 through 12 and are located at the rear of this report. -1 - I I I I I I I I I I I I :f:,. . - I I .. I ·1 I I Phase Ill -,-~- -1-i • -H '.· ... .;__, I I . ! -7 ~ ~ ·_ J .__......_............,_......_ I --. l '· ' BaseMap: ~~~.,:r~., - C"'RLSB.4.PllANCH ---·-r ~ ,,--~-~ ~. -04Li=ORN·. -RLSBAD A ' - 8LUl!PRQrT SOUflCE & y ,uoso SITE --LOCATION . MAP I I I ' , I ' I I ~ [> I ~-'-----r ----..!. \ I ... \;, ,, ,1 ii 11 II ..,. I t I -N- 1 ·1' -1· I . -0 I --200 g 4800-feet I I I I . t I : l I : Approximate Scale Project No. 4980489-011 Date 3/11/97 FIGURE 1 , I I I I I I I I I I I I I I I I I I I 4930489-011 2.0 SUMMARY OF FINE-GRADING OPERATIONS Rough grading of the subject lots began on May 29, 1996 and is essentially complete as of the date of this report. The grading operations were perfonned by Pahla Construction Company under the obsetvation and testing services of Leighton. Our field technician and geologist were on site on a full-time and as- needed basis, respectively, during grading operations. Rough-grading operations included the removal of potentially compressible soil to competent fonnational material and cuts and fills to achieve design grades. 2. I 2.2 2.3 Site Preparation and Removals Prior to grading, the areas of proposed development were stripped of surface vegetation and debris. These materials were disposed of offsite. Removals of unsuitable and potentially compressible soil, including undocumented fill, topsoil, colluvium, weathered terrace deposits and formational material, were made to competent material. Removals of the unsuitable and potentially compressible soil was made in accordance with the recommendations of the project geotechnical report {Leighton, 1993) and field recommendations made during the course of grading. The removal areas flatter than 5:1 (horizontal to vertical) exposing competent material were scarified a minimum of 6 inches, moisture-conditioned, as needed, to obtain a near-optimum moisture content and compacted to a minimum 90 percent relative compaction as determined by ASTM Test Method Dl557-91. The steeper natural hillsides were benched into competent material prior to fill placement. Representative bottom elevations in the removal areas are shown on the As-Graded Geotechnical Maps (Plates 1 through 12). Removals of the topsoil, coJluvium and weathered terrace deposits and formational material were on the order of approximately I to IO feet in thickness. The undocumented fill was removed where encountered. Fill Slope Keys Prior to the placement of fill slopes (including fill-over-cut slopes) that were placed above natural ground, a fill slope key was constructed. The keys were excavated at least 2 feet into competent formational material along the t~f-slope (with the exception of the fill-over-cut slope keys), a minimum of 15 feet wide and angled a minimum of 2 percent into-the-slope. The cut/fill contact in the fiJl-over-cut slopes was angled at least 2 percent into-the-slope prior to the fill placement. Stability Fill Slope A stability fill slope was constructed offsite, adjacent to Palomar Airport Road, east of Armada Drive. The purpose of this slope was to provide a stable, competent slope in an area of existing undocumented fill. A key was excavated a minimum of 2 feet into competent formational material at least 15 feet in width and a subdrain was installed. The location of this stability fill slope is shown on the Geotecbnical Maps at the rear of the text (Plates l through 12). This stability fill • 3 - I I I I I I I I 11 11 I I I I I I I I I 2.4 2.5 2.6 4930489-0 J l was constructed to provide a stable slope and did not include removaJ and recompaction of all undocumented fill soils. A large stability fill was also constructed along the eastern edge of Lots l through 3 (Carlsbad Company Store site). This stability fill included the excavation of a key through the Terrace Deposits and into the underlying Santiago Formation. A 6-inch diameter subdrain and backdrains consisting of m iradrain panels placed on 10 foot centers were also installed in accordance with our previous recommendations (see Appendix A). The stability fill backdrain discharges into a 24-inch RCP stonn drain and includes cleanouts constructed at ±300 feet intervals along the toe of slope. Subdrains During grading operations for a portion of Annada Drive, excessively wet conditions were encountered near the intersection of Annada Drive and Palomar Airport Road. In order to mitigate this condition, a subdrain was instaJled concurrently with, and adjacent to, the storm drain from Statfon 52+40 to Station 53+40 of Annada Drive as shown on the Geotecbnical Maps (Plates I through 12). Th.is subdrain along with those installed in the stability fills are shown on the geotechnical maps. In addition, a series of gravel filled trenches were installed within Lots 1 through 3 to provide additional drainage. Undergrowid Storage Tank On July 8, 1996 an underground storage tank {UST) was encountered during site grading and removed by the contractor, The Pahla Corporation. The location of the tank removal was along the eastern edge of the Armada Drive Alignment at Station 51 +o0. Soil samples were collected from beneath the tank and analyzed for TPH (as gasoline and diesel) and for benzene, toluene, ethylbenzene, and total xylenes (BTEX). Results indicate that TPH and BTEX were not present in the soil beneath the UST. The tank was disposed of off site according to pertinent regulations and a closure letter was issued by the County of San Diego (dated September 12, 1996). It is believed that the tank had been utilized for water storage as part of the previous agricultural fanning operations. Vertical Seepage Pits Several abandoned vertical seepage pits were encountered during rough-grading operations for Armada Drive between Stations 46+oO to 53+o0. The majority of these pits were removed during nonnal grading operations. The remaining seepage pits that extended below grade were filled with clean 3/4-inch grave) to a depth of a minimwn of 5 feet below rough grade and then filled to grade with clean filJ soils and compacted to at least 90 percent relative compaction. -4 - I I I I I I I I I I I I I I I I 2.7 2.8 4930489-011 Fill Placement After processing the areas to receive fill, native soil was generally spread in 4-to 8-inch lifts, moisture conditioned as needed to attain a near-optimum moisture content, and compacted to at least 90 percent of the maximum dry density in accordance with ASTM Test Method D1557-91. Compaction was achieved by use of heavy-duty construction equipment. Areas of fil) in which field density tests indicated less than 90 percent relative compaction, the soils exhibited nonuniforrnity, and/or showed an inadequate or excessive moisture content, were reworked, recompacted, and retested until a minimum 90 percent relative compaction and near-optimum moisture content was achieved. Field Density Testing Field density testing was performed using the Nuclear-Gauge Method (ASTM Test Methods D2922-91 and D3017-88). The approximate test locations are shown on the As-Graded Geotechnical Maps (Plates I through 12). The results of the field density tests are summarized in Appendix B. 2.9 Laboratory Testing Laboratory maximum dry density tests of representative onsite soils were performed in general accordance with ASTM Test Method D1557-91. The laboratory test results and a description of the laboratory test procedures are presented in Appendix C. 2.10 Graded Slopes Graded slopes within the tract were evaluated by the geotechnical consultant and considered grossly and surficially stable from a geotechnfoal standpoint (Leighton, 1993 ). All cut and fill slopes within the tract were constructed with slope inclinations of 2: I (horirontal to vertical) or flatter, during rough-grading operations under the observation of Leighton. A cut slope excavated north of Palomar Airport Road, west of Annada Drive and south of Lot 17 was overexcavated approximately 2 feet below design grades. This slope, which has a design gradient of 6 to 1 (horizontal to vertical), was then capped with 2 feet of topsoil material and will be utilized for agriculturaJ purposes. The topsoil horizon (upper 2 feet) is considered to be non-structural fill. -5 - I I I I I I I I I I I I I I 1· I I I I 3.1 3.2 4930489-011 3.0 ENGINEERING GEOLOGIC SUMMARY As-graded Geologic Conditions The as-graded conditions encountered during grading of the subject tract were essentially as anticipated. A summary of the geologic conditions including geologic units, geologic structure and faulting is presented below. The as-graded geologic conditions of the tract are presented on the As-graded Geotechnical Maps (Plates l through 12). Geologic Units The geologic units encountered during rough grading of the Phase II portion of Carlsbad Ranch project consisted of undocumented fill, previously placed compacted fill, topsoil, Quaternary Terrace Deposits, and the Eocene Santiago Fonnation. The approximate limits of the geologic units encountered during rough grading are presented on the As-graded Geotechnical Maps (Plates l through 12) and discussed below. 3.2. l Undocumented Fill (Unmapped) 3.2.2 Undocumented fill soils were encountered in localized areas-throughout the property. Where encountered within the limits of planned grading, these soils were removed to competent material. During grading of Lots l through 3, approximately 30,000 yards of wet material was removed and placed as a new stockpile of undocumented fill. The location of this stockpile is within the future Lot 12. Topsoil/Colluvium <Unmapped) Topsoil and colluvium consisting of dry to moist, loose, silty sand and slightly clayey sand generally on the order of 4 to S feet in thickness and locally to 10 feet in thickness was encountered covering the majority of the site. These soils were considered unsuitable and potentially compressible in their present condition and were removed to competent fonnational material during the rough-grading operations. 3.2.3 Terrace Deposits {Map Symbol -Qt) Quaternary-aged Terrace Deposits locally overlie the Santiago Formation in most areas of the site. As encountered during our investigation, these deposits generally consist of orange-red brown, dense, silty fine-to medium-grained sandstone. 3.2.4 Santiago Formation {Map Symbol -Ts} The Eocene-aged Santiago Formation appears to underlie the entire site. During our subsurface investigation, the Santiago Formation was encountered below the surficial soils -6- I I I I I I I I I I I I I I I I I I I 3.3 3.4 3.5 3.6 4930489-01 l on the west side of the site adjacent to Paseo del Norte and on the south side of the site adjacent to Palomar Airport Road. As encountered during our investigation, this unit generaJly consists of light gray to olive-green, moist, dense to very dense, silty sandstone with minor Lenses of stiff claystone. Geologic Structure Based on our geologic mapping during the rough-grading operations, literature review and our professional experience on nearby sites, bedding on site is flat lying to slightly dipping (5 to 10 degrees) to the west. Previous investigations and geologic mapping during site grading indicated the Terrace Deposits and the Santiago Formation are generally massive. Landslides and Surficial Failures Based on our review of the project geotechnical reports (Appendix A) and our geologic mapping during rough grading, there was no indication of landslides or other surficial failures within the subject property. Faulting No evidence of faulting was encountered nor anticipated during rough-grading operations at the site. Ground Water A perched ground-water condition was encountered during our subsurface investigation and during the rough-grading operations of Lots 1 through 3 at a depth ranging between S.S and 11 feet below the existing ground surface (at an approximate elevation of S3 to 61 feet msl). Toe perched ground-water condition is estimated to vary from approximately 1 to 6 feet thick (corresponding to a friable sand layer along the contact between the Terrace Deposits wtd the underlying Santiago Formation). This water is likely the result of heavy irrigation on the flower fields immediately upslope and past agricultural activities. Below the friable sand layer, the Santiago Formation consisted of a damp to moist, moderately cemented sandstone. Recommendations for ground water mitigation in this area has been provided under separate cover (see References, Appendix A). Ground water does not appear to be a significant constraint to future development on the remainder of the site. -7- I I I I I I I I I I I I I I I I I I I 4.1 4.2 4930489-011 4.0 CONCLUSIONS General Rough grading of Phase II including Lots I through 3, through 11, 14, and Portions of Lego Drive to Station 21 +00 and Annada Drive from Station 18+72 to Station 54+20 was perfonned in general accordance with the project geotecbnical reports (Appendix A), geotechnical recommendations made during course of the grading, and the City of Carlsbad requirements. It is our opinion that the subject tract is suitable for its intended use. The following is a summary of our conclusions concerning rough grading of the Carlsbad Ranch tract. Sommary of Conclusions • Geotechnical conditions encountered during rough grading were generally as anticipated. • Potentially compressible and/or desiccated undocumented fill, topsoil, colluvium and weathered terrace deposits were removed to competent material during rough grading. • Site preparation and removals were geotechnically observed. • The fill slopes and fill-over-cut slopes constructed above natural ground with gradients steeper than S to I (horizontal to vertical) were constructed with fill slope keys. The keys were excavated a minimum of 2 feet into competent material along the toe-of-slope (with the exception of the fill-over-cut slopes), approximately l S feet wide and angled a minimum of 2 percent into-the-slope. The cut/fill contact in the fill-over-cut slopes were angled at least 2 percent into-the-slope prior to the fill placement. • Fill soils were derived from onsite soils. Fill soils were tested to have at least 90 percent relative compaction (based on AS1M Test Method Dl557-91) and a near-optimum moisture content in accordance with the recommendations of the project geotechnical reports (Appendix A) and the requirements of the City of Carlsbad. • Landslides or surficial slope failures were not encountered during rough-grading operations. • No faults or evidence of faulting was encountered during rough grading. • Perched ground water was encountered on Lots 1, 2 and 3 during the rough-grading operations and mitigated by the construction of a stability fill with subdrains and additional subdrains within the lots. • Minor seepage was also noted in Annada Drive at approximately Station Nos. 52+40 to 53+40. A subdrain and cutoff wall was installed in this area as part of site grading. -8 - I I I I I I I I I I I I I I 11 I I I I 4930489-011 5.0 RECOMMENDATIONS Earthwork We anticipate that future earthwork on the lots will CQnsist of site preparation, possible minor regrading, and trench and retaining wall excavation and backfill. We recommend that earthwork on the site be perfonned in accordance with the fo1lowing recommendations, the City of Carlsbad grading requirements, and the General Earthwork and Grading Specifications of Rough Grading included in Appendix D. In case of conflict, the following recommendations shall supersede those in Appendix D. 5.1. 1 Site Preparation Due to the length of time anticipated between the construction and placement of fill soils on the graded pads and development of the lots, surficial soils of the graded pads may become desiccated. If the length of time between the completion of grading and the construction of the residences is longer than 6 to 12 months, or if the near-surface soils are disturbed or desiccated, we recommend that the areas of proposed development be scarified a minimum of 12 inches, moisture-conditioned to near-optimum moisture content and compacted to a minimum 90 percent relative compaction (based on AS1M Test Method D1557-91). If additional grading, such as fill placement, is planned on the site, the areas to receive structural fill or engineered structures should be cleared of subsurface obstructions, potentially compressible material (such as topsoil, colluvium, alluvium, weathered formation material, and desiccated fill soils) and stripped of vegetation prior to grading. Vegetation and debris should be removed and properly disposed of offsite. Holes resulting from removal of buried obstructions which extend below finish site grades should be replaced with suitable compacted fill material. Areas to receive fi ll and/or other surface improvements should be scarified to a minimum depth of 6 inches, brought to near-optimum moisture condition, and recompacted to at least 90 percent relative compaction (based on AS1M Test Method D1557-91). 5 .1.2 Excavations Excavations of the onsite materials for the installation of utilities and future site grading may generally be accomplished with conventional heavy-duty earthwork equipment. Doe to the relatively high-density characteristics and coarse nature of the o nsite soils, temporary excavations, such as utility trenches with vertical sides in the onsite soils, should remain stable for the period required to construct the utility provided they are free of adverse geologic conditions. However, in accordance with OSHA requirements, excavations between 5 and 15 feet in depth should be shored or laid back to inclinations -9 - I I I I I I I I I I I I I I I I I I 5.2 4930489-0 I I of I : l (horizontal to vertical) if workers are to enter such excavations. For excavations deeper than 15 feet, specific recommendations can be made on a case-by-case basis. 5.1.3 Fill Placement and Compaction The onsite soils are generally suitable for use as compacted fi ll provided they are free of organic material, debris, and rock fragments larger than 6 inches in maximum dimension. All fill soils should be brought to near-optimum moisture conditions and compacted in uniform lifts to at least 90 percent relative compaction based on the laboratory maximum dry density (AS™-Test Method D1557-91). The optimum lift thickness required to produce a uniformly compacted fill will depend on the type and size of compaction equipment used. In general, fill should be placed in lifts not exceeding 4 to 8 inches in compacted thickness. Placement and compaction of fill should be performed in general accordance with the current City of Carlsbad grading ordinances, sound construction practices, and the General Earthwork and Grading Specifications of Rough Grading presented in Appendix D. 5.1.4 Cut/Fill Transition Lots The cut/fill transition condition on the lots were not mitigated during the rough-grading operations, as lot specific design plans were not available at the time of this report. Foundation Design Considerations As previously noted the type of development proposed on each individual lot is unknown. Final development plans should be reviewed by the geotechnical consultant. In general, the proposed foundations and slabs of the anticipated structures should be designed in accordance with structural considerations provided by the structural engineer. Based on our current site knowledge, we anticipate alJ foundations can be designed for low expansive soils. Expansion index testing should be perfonned on the individual lot within the upper 5 feet of finish grade for verification. If import material is utilized as fill on the lots, the import material should consist of very low or low- expansive sandy material (with an expansion index less than 50 per UBC J 8-1-B). Additionally, the geotechnical consultant should provide, as a minimam, the following: • Foundation design to mitigate potentially expansive soil conditions if encountered. The finish grade soils typically have a very low to low expansion potential. If basement ex,cavations are proposed, conditions may vary somewhat. • Allowable soil bearing values and associated seltlement. • Design of other improvements to mitigate the anticipated settlement and/or the potentially expansive soil conditions, if encountered. I I I I I I I I I I I I I I I I I I I 5.3 5.4 5.5 5.6 4930489-011 • Recommendations to reduce the potential for moisture infiltration through concrete slabs-on- grade. • • Structural setbacks for buildings and other improvements . Retaining wall design parameters. • Pavement/flatwork recommendations. • Specific site/lot surface drainage recommendations. Sulfate Testing of Finish Grade Soils Soluble sulfate tests were perfonned on representative finish grade soils. The test results indicate that the finish grade soils have a negligible soluble sulfate content per the U.B.C. criteria (ICBO, 1994). The test results and procedures are presented in Appendix C. Control of Surface Water and Drainage Control Positive drainage of surface water away from structures is very important. No water should be allowed to pond adjacent to buildings. Positive drainage may be accomplished by providing drainage away from buildings at a gradient of at least 2 percent for a distance of at least 5 feet, and further maintained by a swale or drainage path at a gradient of at least 1 percent. Where necessary, drainage paths may be shortened by use of area drains and collector pipes. Planters with open bottoms adjacent to buildings should be avoided, if possible. Planters should not be design adjacent to buildings unless provisions for drainage, such as catch basins and pipe drains, are made. Overwatering should be avoided. Pavement Design Considerations Final pavement designs should be calculated utilizing R-value tests taken on the street/parking area subgrade soils upon completion of the street/parking area improvement operations. The upper 12 inches of subgrade soi Is should be scarified. moisture conditioned and compacted to a minimum of 95 percent relative compaction based on ASTM Test Method 01557-91. The aggregate base material should also be compacted to 95 percent relative compaction. Graded Slopes It is recommended that all graded slopes within the development be planted with drought-tolerant, ground-cover vegetation as soon as practical to protect against erosion by reducing runoff velocity. Deep-rooted vegetation should also be established to protect against surficial slumping. Oversteepening of existing slopes should be avoided during fine grading and construction unless -11 - I I I I I I I I I I I I I 5.7 4930489-0 I I supported by appropriately designed retaining structures. Retaining structures should be designed with structural considerations. Construction Observation and Testing Construction observation and testing should be performed by the geotechoical consultant during future grading, excavations and foundation or retaining wall construction at the site. Lot-specific recommendations should be provided by a qualified geotechnical consultant and should be based on actual site conditions. Grading and foundation design plans should also be reviewed by the geotechnical consultant prior to construction and a final report of geotechnicaJ services should be prepared to document geotechnical services upon completion of site development. -12 - 1 I I I I I I I I I I I I I I I I I I 4930489-011 APPENDIX A References International Conference of Building Officials (ICBO), 1994, Unifonn Building Code, Volume I - Administrative, Fire-and Life-Safety, and Field Inspection Provisions; Volume ll - Structural Engineering Design Provisions; and Volume Ill -Material, Testing and Installation Provisions: ICBO. Leighton and Associates, Inc., 1993, Preliminary Geotechnical Investigation Units I and 11 (Lots 1 through 7), Carlsbad Ranch Phase 1, Carlsbad, California, Project No. 4930489-01, dated July 22, t 993 . ----, 1994a, Preliminary Geotechnical Investigation, Carlsbad Ranch Phase II, Carlsbad, California, Project No. 4930489-03, dated March 23, 1994. ----, 1994b, Preliminary Geotechnical Evaluation for Tentative Map Purposes, Carlsbad Ranch, Carlsbad, California, Project No. 4930489-05, dated July 5, 1994. ----, 1995, Proposal for Geotechnical Observation and Testing Services during Rough-and Post- Grading, Carlsbad Ranch Phases l and 2, Carlsbad, California, Project No. 4930489-08, dated April 21, 1995. ----, 1996a, Soil Samplin,g for Underground Storage Tanlc (US1) Removal, Project No. 4930489-012, dated July 22, 1996 (Revised July 25, 1996). ----, 1996b, Geotechnical Investigation, Proposed Carlsbad Company Stores, Southeast Comer of Paseo del Norte and Car Country Drive, Carlsbad, California, Project No. 4960044-001, dated April 21, 1996. ----, 1996c, Revised Slope Recommendations, Proposed Carlsbad Company Stores, Southeast Comer of Paseo del Norte and Car Country Drive, Carlsbad, San Diego County, California, Project No. 4960044-002, dated September 27, 1996. ----, 1996d, Dewatering Provisions, Carlsbad Ranch, Carlsbad Company Store Site, Carlsbad, California, Project No. 4960044-002, dated October l l, J 996. ----, l 996e, Additional Subdrain Recommendations, Carlsbad Company Store Site, Carlsbad, California, Project No. 4960044-002, dated December 19, 1996. ----, l 996f, Geotechnical Investigation, Proposed Corporate Headquarters for National Association of Music Merchants, Phase Il, Lot 11, Carlsbad Ranch, Carlsbad, California, Project No. 4960091-001, dated April 10, 1996. A-1 I I I I I I I I I I I I I I I 4930489-01 I APPENDIX B EXPLANATION OF SUMMARY OF FIELD DENSITY TESTS Test No. Test of Test No. Test of Prefix Test of Abbreviations Prefix Test of Abbreviations (none) GRADING Natural Ground NG (SO) SUBGRADE Original Ground 0G (AB) AGGREGATE BASE Existing Fill I EF (CB) CEMENT TREATED BASE Compacted Fill CF (PB) PROCESSED BASE Slope Face SF (AC) ASPHALT CONCRETE Finish Grade FG (S) SEWER Curb C (SD) STORM DRAIN Gutter G (AD) AREA DRAIN Curb and Gutter CG (W) DOMESTIC WATER Cross Gutter XG (RC) RECLAIMED WATER Street ST (SB) SUBDRAIN Sidewalk: SW (G) GAS Driveway D (E) ELECTRICAL Driveway Approach DA (1) TELEPHONE Parking Lot PL (J) JOINT UTIL[TY Electric Box Pad EB (I) IRRIGATION Bedding Material B Shading Sand s Main Backfill M Lateral Backfill L Crossing X Manhole MH Hydrant Lateral HL Catch Basin CB Riser R lnvert I Check Valve CV Meter Box MB Junction Box JB (RW) RETAINING WALL (P) PRESA TURA TION (CW) CRIB WALL (LW) LOFFELL WALL Moisture Content M (SF) STRUCT FOOTING Footing Bottom F (I'D INTERIOR TRENCH Backfill B Wall Cell C Plumbing p Electrical E N represents nuclear gauge tests that were pe_rfonned in general accordance with most recent version of ASTM Test Methods D2922 and D3017. S represents sand cone tests that were perfonned in general accordance with most recent version of ASTM Test Method D1556. l SA represents first retest of Test No. l S l SB represents second retest of Test No. IS "O" in Test Elevation Column represents test was taken at the ground surface (e.g. finish grade or subgrade) "•l" in Test Elevation Column represents test was taken one foot below the ground surface B-1 ---- - -- - -- - --------02/12/97 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489-11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ------------LOCATION·-·······--·-· TEST SOIL DRY DENSITY(pcf) MOISTURE(¾) REL<¾> REMARKS NUMBER METH DATE OF ELEVCft) TYPE FJELD HAX FIELD OPT COMP ·--·-·---·---···-----------·--···--·--·-·-··---·-·-·---·--·----..................... -......... -......... -·-······· 1 N 05/31/96 CF N.E. OF LOT 9 142.0 4 120.9 133.0 10.1 9.0 91 2 N 05/31/96 CF N.E. OF LOT 9 144.0 4 122.0 133.0 9.7 9.0 92 3 N 05/31/96 CF N.E. OF LOT 9 143.0 4 121.5 133.0 9. 1 9.0 91 4 N 05/31/96 CF N.E. OF LOT 9 145.0 4 122.5 133.0 8.6 9.0 92 5 H 05/31/96 CF N.E. OF LOT 9 144.0 4 119.9 133.0 8.7 9.0 90 6 N 05/31/96 CF N.E. OF LOT 9 147.0 4 121.4 133.0 9.6 9.0 91 7 II 06/03/96 CF N.E. OF LOT 9 149.0 13 123.4 131.0 14. 1 9.0 94 8 N 06/03/96 CF N.E. OF LOT 9 150.0 13 124.8 131 .0 9.0 9.0 95 9 N 06/03/96 CF N.E. OF LOT 9 146.0 13 121.8 131 .0 10.7 9.0 93 10 N 06/03/96 CF N.E. OF LOT 9 147.5 13 122.1 131.0 11 .8 9.0 93 11 N 06/03/96 Cf S.E. OF LOT 9 153.0 13 119.4 131.0 13.9 9.0 91 12 N 06/03/96 CF E. OF LOT 9 155.0 4 122.4 133.0 10.7 9.0 92 13 N 06/03/96 CF S.E. OF LOT 9 144.0 13 119.3 131.0 14.4 9.0 91 14 N 06/03/96 CF S.E. OF LOT 9 146.0 4 121.4 133.0 12.8 9.0 91 15 N 06/03/96 CF E. OF LOT 9 144.0 4 122.8 133.0 11. 7 9.0 92 16 N 06/03/96 CF E. OF LOT 9 147.0 13 120. 1 131.0 12.7 9.0 92 17 N 06/03/96 CF N.E. OF LOT 10 158.0 4 123.7 133.0 10.8 9.0 93 18 N 06/03/96 CF N.E. OF LOT 10 160.0 13 118.0 131.0 12.5 9.0 90 19 N 06/03/96 CF N.E. OF LOT 10 159.0 13 120.2 131.0 14.9 9.0 92 20 N 06/03/96 CF N.E. OF LOT 10 161.0 4 123.2 133.0 12.4 9.0 93 21 N 06/03/96 CF N.E. OF LOT 9 148.0 13 119.8 131.0 14. 1 9.0 91 22 N 06/03/96 CF N.E. OF LOT 9 150.0 4 122.0 133.0 10.6 9.0 92 23 N 06/03/96 CF I:. OF LOT 9 148.0 4 122. 1 133.0 11 .6 9.0 92 24 N 06/03/96 CF E. Of LOT 9 149.0 4 122.9 133.0 10.5 9.0 92 2.5 N 06/04/96 CF E. OF LOT 9 151.0 3 122.0 135.0 11.t. 8.0 90 26 N 06/04/96 CF S.E. OF LOT 9 152.5 4 120.6 133.0 13.7 9.0 91 27 N 06/04/96 CF N.E. OF LOT 10 151.0 " 120.3 133.0 8.2 9.0 90 28 N 06/04/96 CF E. OF LOT 10 149.0 13 123.7 131.0 , 1.4 9.0 94 29 N 06/04/96 CF N. OF LOT 9 142.0 13 119.6 131.0 13.3 9.0 91 30 N 06/01,/96 CF N. OF LOT 9 1t.4.0 4 120.3 133.0 10.9 9.0 90 31 N 06/04/96 CF N. OF LOT 9 146.0 4 120.9 133.0 10.9 9.0 91 32 N 06/04/96 CF N. OF LOT 9 147 .0 4 122.6 133.0 10.9 9.0 92 33 N 06/0'-/96 CF CENTER OF LOT 9 145.0 4 121,2 133.0 10.6 9.0 91 34 N 06/04/96 CF S.E. OF LOT 10 152.0 4 120.2 133.0 10.0 9.0 90 35 N 06/04/96 CF S.E. OF LOT 10 149.0 13 120.3 131.0 11 .6 9.0 92 36 N 06/04/96 CF S.E. OF LOT 10 150.0 13 119.5 131.0 10.7 9.0 91 37 N 06/05/96 CF S.E. OF LOT 9 161.0 4 122.1 133.0 9.5 9.0 92 38 N 06/05/96 CF S.E. OF LOT 9 158.0 4 122.6 133.0 10. 1 9.0 92 39 N 06/05/96 CF N.E. OF LOT 10 156.0 10 114.9 128.0 11.6 9.0 90 40 N 06/05/96 CF S.E. OF LOT 10 158.0 12 120.4 127.0 12.5 8.5 95 41 N 06/05/96 CF S.E. OF LOT 10 160.0 13 122.3 131.0 12.7 9.0 93 42 N 06/05/96 CF S.E. OF LOT 10 1S6.0 10 115.1 12.8.0 13.3 9.0 90 43 H 06/05/96 CF S.E. OF LOT 10 158.0 3 121.2 135.0 12.5 8.0 90 44 N 06/05/96 CF LOT 9 SOUTH 143.0 4 121.2 133.0 10.6 9.0 91 45 N 06/05/96 CF N. OF LOT 10 143.0 13 118.9 131.0 11.6 9.0 91 46 N 06/05/96 FG LOT 8 (PAD AREA) 164.3 9 116.6 130.0 9.4 10.0 90 47 N 06/05/96 FG LOT 8 (PAD AREA) 164.3 1 •. 112.0 124 .0 10.5 8.5 90 - -- -- -- - - -- - - -- -- --02/12/97 Page No. 2 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489-11 NAME: CA.RLSBAO RANCH TEST TEST TEST TEST -------·····LOCATION·----··--·-·-· TEST SOIL DRY DENSITY(pcf) MOI STVRE("> REL(%) REMARKS NUMBER METH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT C014P -...... -.. --.. .. -# ...... ---·------····-········--·---·-·-·--·---·-···-·· ··-·--.. --.--.... -.... --. ·---.... -. -..... 48 N 06/05/96 fG LOT 8 (PAD AREA) 164.3 9 117.2 130.0 10.4 10.0 90 49 N 06/06/96 CF LOT 9 SOOTH 145.0 12 115.9 127.0 13.0 8.5 91 50 N 06/06/96 Cf LOT 10 NORTH 143.0 14 117.6 130.5 9.9 9.5 90 51 N 06/06/96 CF N. OF LOT 10 142.0 13 119.3 131.0 11.6 9.0 91 52 N 06/06/96 CF CENTER OF LOT 10 144.0 14 117.4 130.5 12.5 9.5 90 53 N 06/06/96 CF N. OF LOT 9 148.0 13 123.0 131.0 13.6 9.0 94 54 N 06/06/96 CF S. OF LOT 9 150.0 4 123.7 133.0 8.4 9.0 93 55 N 06/06/96 CF S, OF LOT 9 146.0 13 121.6 131.0 11.0 9.0 93 56 N 06/06/96 CF S. Of LOT 9 147.0 4 119.2 133.0 8.1 9.0 90 57 N 06/06/96 Cf E. Of LOT 9 163.0 13 120.0 131.0 12.7 9.0 92 58 N 06/06/96 Cf S.E. OF LOT 9 164.0 14 119.0 130.5 15.3 9.5 91 59 N 06/06/96 CF N.E. Of LOT 10 166.0 14 118. 1 130.5 13.9 9.5 90 60 N 06/06/96 CF E. Of LOT 10 164.0 14 119.2 130.5 13.7 9.5 91 61 N 06/06/96 CF N.E. OF LOT 11 151.0 4 123.6 133.0 9.8 9.0 93 62 N 06/07/96 CF N.E. OF LOT 11 148.0 4 122.6 133.0 11.5 9.0 92 63 N 06/07/96 CF S. OF LOT 10 136.5 14 119.0 130.5 12.1 9.5 91 64 N 06/07/96 CF S. OF LOT 10 138.5 14 119. 1 130.5 10.0 9.5 91 65 N 06/07/96 CF S. Of LOT 10 140.0 14 120.1 130.5 9.9 9.5 92 66 N 06/07/96 CF N. OF LOT 11 134.0 14 117.6 130.5 12.7 9.5 90 67 N 06/07/96 CF N. OF LOT 11 136.0 14 118.6 130.5 12.6 9.5 91 68 N 06/07/96 CF N. OF LOT 11 139.0 14 117.3 130.5 10.9 9.5 90 69 N 06/07/96 CF N. OF LOT 11 135.5 14 118.2 130.5 12. 1 9.5 91 70 N 06/07/96 CF N. OF LOT 11 138.0 14 118.2 130.5 12.9 9.5 91 71 N 06/07/96 CF N.E. OF LOT 10 166.0 4 122.5 133.0 12.6 9.0 92 n N 06/07/96 CF N.E. OF LOT 10 168.0 4 123.5 133.0 13.1 9.0 93 73 N 06/07/96 CF S.E. OF LOT 9 163.0 13 117.9 131.0 13.0 9.0 90 74 N 06/07/96 CF S.E. OF LOT 9 160.0 13 121.1 131.0 10.7 9.0 92 75 N 06/07/96 CF N. OF LOT 11 147.0 4 120.8 133.0 12.4 9.0 91 76 N 06/07/96 CF S. Of LOT 10 150.0 13 119. 1 131.0 11.5 9.0 91 77 N 06/07/96 CF S. OF LOT 10 145.0 13 120.2 131.0 11.4 9.0 92 78 N 06/10/96 CF LEGO OR IVE \JEST STATION 9+20 145.0 4 125.4 133.0 9.3 9.0 94 79 N 06/10/96 CF LEGO DRIVE \JEST STATION 10+00 147.0 4 126.2 133.0 11.5 9.0 95 80 N 06/10/96 CF LEGO DRIVE WEST STATION 11+00 149.0 4 124.2 133.0 11. 7 9.0 93 81 N 06/10/96 CF LEGO DRIVE \JEST STATION 8+60 143.0 12 116.0 127.0 8.6 8.5 91 82 N 06/10/96 Cf LEGO DRIVE WEST STATION 9+10 145.0 4 125.5 133.0 10.7 9_0 94 83 N 06/10/96 CF LEGO DRIVE EAST STATION 9+40 147.0 14 117.8 130.5 12.8 9.5 90 84 N 06/10/96 Cf lEGO DRIVE \JEST STAHON 7+95 143.0 4 125.6 133.0 12.9 9.0 94 85 N 06/10/96 CF LEGO DRIVE \IEST STATION 7+75 146.0 4 127.5 133.0 10.3 9.0 96 86 N 06/10/96 CF CONT<XJR EAST OF LEOO DRIVE 153.0 13 120.5 131.0 12.2 9.0 92 87 N 06/10/96 CF LEGO DRIVE EAST STATION 8+90 152.0 13 121.5 131.0 12. 1 9.0 93 88 N 06/10/96 CF N. OF LOT 11 142.0 4 122.0 133.0 10. 1 9.0 92 89 N 06/10/96 CF S. OF LOT 10 138.0 4 120.9 133.0 10.9 9.0 91 90 N 06/10/96 CF CENTER OF LOT 10 142.0 14 117.6 130.5 12.2 9.5 90 91 N 06/10/96 CF N. OF LOT 10 145.0 14 118. 1 130.5 11.5 9.5 90 92 N 06/10/96 CF LEGO DRIVE EAST STATION 9+00 150.0 14 119. 1 130.5 12.6 9.5 91 93 N 06/11/96 CF CONTOUR EAST OF LEGO DRIVE 157.0 14 117.5 130.5 9.2 9.5 90 94 N 06/11/96 CF CONT<XJR EAST OF LEGO DRIVE 156.0 14 .. 124.3 130.5 12.5 9.5 95 - - - - - - -- --- - - ---- - -02/12/97 Page No. 3 SUMMARY OF FIELD DENSIT~ TESTS PROJECT NtJHBER: 04 · 930489· 11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ··-···-····· LOCATION······-······-tEST SOIL ORY OENSITY(pcf) MOISTURE(%) RELCX) REMARKS NUMBER HETH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT COMP ·------·-----·. ---··-···---------·----------··--··----... ----....... -----····----·-------··----·------95 N 06/11/96 CF LEGO DRIVE EAST STATION 9+90 154.0 4 126.6 133.0 10.5 9.0 95 96 N 06/11/96 Cf LEGO DRIVE WEST STATION 8+70 147.0 14 117.6 130.5 12.8 9.5 90 97 N 06/11/96 CF LEGO ORIVE WEST STATION 8+40 149.0 4 126.8 \33.0 8.8 9.0 95 98 N 06/11/96 CF LEGO DRIVE WEST STATIOH 11+95 155.0 4 123.8 133.0 9. 1 9.0 93 99 N 06/11/96 CF LEGO DRIVE IIEST STAT ION 7+20 153.0 14 117 .5 130.5 11. 1 9.5 90 100 N 06/11/96 Cf LEGO DRIVE WEST STATION 11+50 157.0 14 118.4 130.5 10.4 9.5 91 101 N 06/11/96 CF CONTOUR AREA EAST OF LEGO DRIVE 160.0 12 114.5 127.0 12.9 8.5 90 102 N 06/11/96 CF CONTOUR AREA EAST OF LEGO DRIVE 157.0 13 118. 1 131.0 11 .2 9.0 90 103 N 06/11/96 CF LEGO DRIVE EAST STATION 7+00 155.0 13 119.2 131.0 9.7 9.0 91 104 N 06/11/96 CF LEGO DRIVE EAST STATION 7+80 156.0 13 120.6 131.0 9.8 9.0 92 105 N 06/11/96 CF LEGO DRIVE WEST STATION 9+75 155.0 13 126. 1 131.0 12. 1 9.0 96 106 .. 06/11 /96 CF LEGO DRIVE WEST STATION 10+60 157.0 13 123.5 131.0 11.0 9.0 94 107 N 06/11/96 CF S.11. OF LOT 10 139.0 13 118. 1 131.0 9.4 9.0 90 108 N 06/11/96 CF S.11. OF LOT 10 141.0 12 114.3 127.0 10.2 8.5 90 109 N 06/11/96 CF II. OF LOT 10 141.5 14 117.0 130.5 11. 9 9.5 90 110 N 06/11/96 CF II. OF LOT 10 143.5 14 118.9 130.5 12.3 9.5 91 111 N 06/12/96 CF LOT 9 SOUTHWEST 146.0 4 120.9 133.0 7.5 9.0 91 112 N 06/12/96 CF LOT 9 SWTHWEST 148.0 13 122.3 131.0 10.8 9.0 93 113 N 06/12/96 CF N. OF LOT 11 139.0 13 120.5 131.0 13.8 9.0 92 114 N 06/12/96 CF S. OF LOT 10 140.0 13 123.5 131.0 11.4 9.0 94 115 N 06/12/96 CF S. OF LOT 11 142.0 14 119.8 130.5 11.0 9.5 92 116 N 06/12/96 CF S. OF LOT 11 145.0 14 121.8 130.5 10.8 9.5 93 117 II 06/12/96 CF LOT 10 SOOTH 146.0 14 118.8 130.5 11.0 9,5 91 118 N 06/12/96 CF S.E. OF LOT 9 167.0 14 118.0 130.5 11.1 9.5 90 119 N 06/12/96 CF S.E. OF LOT 9 155.0 13 117.4 131.0 9.8 9.0 90 120 N 06/12/96 CF LOT 10 NO!I.THEAST 160.0 14 122.6 130.5 13.1 9.5 94 121 N 06/12/96 CF N.E. OF LOT 11 151.0 13 121.2 131.0 11.3 9.0 93 122 N 06/12/96 CF s.e. OF LOT 10 153.0 13 118.6 131.0 12.1 9.0 91 123 N 06/12/96 CF N.E. OF LOT 11 148.0 13 117.4 131.0 12.2 9.0 90 124 N 06/12/96 CF N.E. OF LOT 11 143.0 13 123.3 131.0 11.5 9.0 94 125 N 06/12/96 CF S.E. OF LOT 10 145.0 4 125.4 133.0 12.4 9.0 94 126 N 06/13/96 CF N.11. OF LOT 10 142.0 13 119.6 131.0 10.0 9.0 91 127 N 06/13/96 CF N.11. OF LOT 10 144.0 14 117 .3 130.5 11. 1 9.5 90 128 N 06/13/96 CF N,11. OF LOT 10 143.0 14 118.5 130.5 10.2 9.5 91 129 N 06/13/96 Cf S.IJ. OF LOT 10 142.0 14 118.8 130.5 12.2 9.5 91 130 N 06/13/96 CF S.11, OF LOT 9 144.0 14 117.7 130.5 12.8 9.5 90 131 N 06/13/96 CF S.11. OF LOT 9 143.0 13 117.4 131.0 13.6 9.0 90 132 N 06/13/96 CF N.IJ. OF LOT 9 145.0 4 123.3 133.0 9.0 9.0 93 133 N 06/13/96 CF M.IJ. OF LOT 9 142.0 13 120.2 131.0 13.4 9.0 92 134 N 06/13/96 CF N.11. OF LOT 9 147.0 13 118.3 131.0 10.0 9.0 90 135 N 06/13/96 CF CENTER OF LOT 9 154.0 4 120.9 133.0 9.7 9.0 91 136 N 06/13/96 CF CENTER OF LOT 9 153.0 12 116.6 127.0 9.8 8.5 92 137 N 06/13/96 CF CENTER OF LOT 10 142.0 4 125.7 133.0 11 .8 9.0 95 138 N 06/13/96 CF CENTER OF LOT 10 143.0 4 122.7 133.0 12.0 9.0 92 139 II 06/13/96 Cf S. OF LOT 10 145.Q 14 122.1 130.5 13.4 9.5 94 140 N 06/14/96 CF S. OF LOT 9 154.0 12 117 .8 127.0 11.1 8.5 93 141 N 06/14/96 CF N. OF LOT 10 155.0 12, 117 .3 127.0 10.0 8.5 92 - - - - -- -- - -- - --- - -- -02/12/97 Page No. 4 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ··········•• LOCATION ·•············ TEST SOIL ORY OENSITY(pcf) MOISTURE(X) REL(%) REMARKS NUMBER METH OATE OF ELEV(ft) TYPE FJELD MAX FIELD OPT COMP --·-·-----······· -····----··--·-········-·-···---------------·· ····-··------. --... -..... -··--·-··--142 N 06/14/96 CF N, OF LOT 10 152.0 13 118.2 131.0 11. 2 9.0 90 143 N 06/14/96 CF S.E. OF LOT 9 157.0 13 120.5 131.0 9.8 9.0 92 144 N 06/14/96 CF N.U. OF LOT 10 145.0 5 118.4 129.0 12.2 10,0 92 145 N 06/14/96 CF N.W, OF LOT 10 146.0 4 120.6 133.0 12.9 9.0 91 146 N 06/14/96 CF S.E. OF LOT 10 158.0 5 122.4 129.0 13.2 10.0 95 147 N 06/14/96 CF N.E. OF LOT 11 159.0 5 121.0 129.0 8.8 10.0 94 148 N 06/14/96 CF N. OF LOT 10 160.0 5 117.6 129.0 10.4 10.0 91 149 N 06/14/96 CF N. OF LOT 10 158.0 13 118.0 131.0 10,0 9.0 90 150 N 06/14/96 CF S.W. OF LOT 10 141.0 4 123.3 133.0 13.8 9.0 93 151 N 06/17/96 CF STABILITY FILL PAL()i!AR AIRPORT RD 84.0 15 110.0 122.5 10.8 12.0 90 152 N 06/17/96 CF STABILITY FILL PALOMAR AIRPORT RD 81.0 15 109.9 122.5 10.5 12.0 90 153 N 06/17/96 CF CENTER OF LOT 9 156.0 5 125.7 129.0 7.7 10.0 97 154 N 06/17/96 CF N. OF LOT 10 157.0 5 119. 1 129.0 9.5 10.0 92 155 N 06/17/96 CF N.E. OF LOT 11 158.0 13 119.8 131.0 13.2 9.0 91 156 N 06/17/96 CF N.E. OF LOT 11 156.0 13 120.0 131.0 14.0 9.0 92 157 N 06/17/96 CF s.E. OF LOT 9 163.0 4 129.9 133.0 12.1 9.0 98 158 N 06/17/96 CF N. OF LOT 9 152.0 5 115.6 129.0 10.0 10.0 90 159 N 06/17/96 CF N. OF LOT 10 147.0 5 121.2 129.0 1,. 1 10.0 94 160 N 06/17/96 Cf N. OF LOT 10 149.0 4 120.6 133.0 8.2 9.0 91 161 N 06/17/96 CF STABILITY FILL PAL()i!AR AIRPORT RD 90.0 5 117 .o 129.0 10.4 10.0 91 162 N 06/17/96 CF STABILITY FILL PALOMAR AIRPORT RO 85.0 5 117 .6 129.0 11.3 10.0 91 163 N 06/17/96 CF STABILITY FILL PALOMAR AIRPORT RD 87.0 5 116.4 129.0 11.9 10.0 90 164 N 06/18/96 CF N.E. OF LOT 10 162.0 4 126.4 133.0 11.4 9.0 95 165 N 06/18/96 CF N.E. OF LOT 10 164.0 13 119.5 131.0 11.5 9.0 91 166 N 06/18/96 CF E. OF LOT 10 160.0 5 118.0 129.0 9.9 10.0 91 167 N 06/18/96 CF CENTER OF LOT 10 151.0 5 119.0 129.0 9.9 10.0 92 168 N 06/18/96 CF N. OF LOT 10 149.0 5 124.2 129.0 8.4 10.0 96 169 N 06/18/96 CF N. OF LOT 10 148.0 5 119.5 129.0 10.2 10.0 93 170 N 06/18/96 CF N. OF LOT 10 151.0 5 120.7 129.0 10.7 10.0 94 171 N 06/18/96 CF N.E. OF LOT 11 157.0 13 119.3 131.0 10.6 9.0 91 172 N 06/18/96 CF STABILITY FILL PALOMAR AIRPORT RO 88.0 1l 120.5 131.0 10.8 9.0 92 173 N 06/18/96 CF STABILITY Fill PALOMAR AIRPORT RD 90.0 13 121.5 131.0 10.8 9.0 93 174 N 06/18/96 CF STABILITY Fill PALOMAR AIRPORT RO 92.0 12 113. 7 127.0 10. 1 8.5 90 175 N 06/19/96 CF CENTER OF LOT 10 153.0 4 123.9 133.0 13. 7 9.0 93 176 N 06/19/96 CF CENTER OF LOT 10 155.0 5 116.5 129.0 8.6 10.0 90 1n N 06/19/96 CF S. OF LOT 10 154.0 5 118.6 129.0 11 .6 10.0 92 178 N 06/19/96 CF S. OF LOT 10 153.0 5 124.2 129.0 13.0 10.0 96 179 N 06/19/96 CF S. OF LOT 10 154,0 4 127.3 133.0 11. 7 9.0 96 180 N 06/19/96 CF S. OF LOT 10 156.0 4 124.2 133.0 12.0 9.0 93 181 N 06/19/96 CF CENTER OF LOT 10 159.0 5 118.3 129.0 11.9 10.0 92 182 N 06/19/96 CF STABILITY FILL PALOMAR AIRPORT RD 95.0 5 117 .5 129.0 10.2 10.0 91 183 II 06/19/96 CF STABILITY FILL PALOMAR AIRPORT RD 96.0 5 119 .1 129.0 11 .6 10.0 92 184 N 06/19/96 CF STABILITY FILL PALOMAR AIRPORT RD 98.0 5 120.2 129.0 10.7 10.0 93 185 N 06/19/96 CF STABILITY FILL PALOMAR AIRPORT RD 102.0 5 116.7 129.0 8.5 10.0 90 186 N 06/19/96 CF STABILITY Fl LL PALOMAR AIRPORT RD 104.0 5 118.5 129.0 13.6 10.0 92 187 N 06/19/96 CF STABILITY Fill PALOMAR AIRPORT RD 100.0 5 119. 1 129.0 11 .a 10.0 92 188 N 06/19/96 CF STABILITY FILL PALOMAR AIRPORT RD 106.0 5 119.7 129.0 12. 1 10.0 93 - - - - -- - --- -- --- --- -02/12/97 Page No. 5 SUMMARY OF FIELO DENSITY TESTS PROJECT NUMBER: 04·930489-11 NAME: CARLSB.AO RAHCH TEST TEST TEST TEST ·······-···· LOCATION ······-······· TEST SOIL ORY OENSITY(pcf) HOI STUREC%) RELCX) REMARKS NUMBER HETH DATE OF ELEVCft) TYPE FIELD MAX FIELD OPT COMP -... ---... -.. -.. -. ------·-·--------------------·-·---·---· -----·--------·-·-·-·----------·· --.. ---... --189 N 06/19/96 CF STABILITY Fill PALOMAR AIRPORT RD 108.0 5 119.8 129.0 13.7 10.0 93 190 N 06/19/96 CF STABILITY Fill PALOMAR AIRPORT ~O 107.0 5 116. 1 129.0 12.8 10.0 90 191 N 06/20/96 CF STAB I LI TY FI LL PALOMAR AIRPORT RD 110.0 5 120.5 129.0 1,. 1 10.0 93 192 N 06/20/96 CF STABILITY FILL PALOMAR AIRPORT RO 109.0 5 119.8 129.0 10.9 10.0 93 193 N 06/20/96 CF STABILITY Fill PALOMAR AIRPORT RD 110.0 5 119.2 129.0 11.5 10.0 92 194 N 06/21/96 CF N.W. OF LOT 11 140.0 5 116.0 129.0 9.7 10.0 90 195 N 06/21/96 CF N.W. OF LOT 11 142.0 5 116.4 129.0 9.6 10.0 90 196 N 06/21/96 CF N.W. OF LOT 11 139.0 1 112.0 124.0 12.6 8.5 90 197 N 06/21/96 CF N.W. OF LOT 11 141.0 1 112.3 124.0 9.0 8.5 91 198 N 06/21/96 CF N.W. OF LOT 11 145.0 5 123.1 129.0 14.0 10.0 95 199 N 06/21/96 CF N.W. OF LOT 11 143.5 4 124.2 133.0 13.9 9.0 93 200 N 06/21/96 CF S.W. OF LOT 10 140.0 5 118.4 129.0 13.0 10.0 92 201 N 06/21/96 CF S.W. OF LOT 10 143.0 4 126.9 133.0 12.3 9.0 95 202 N 06/21/96 CF S,W. OF LOT 10 143.0 1 113.3 124.0 9.8 8.5 91 203 N 06/21/96 CF W. OF LOT 10 146.0 1 112.3 124.0 10.3 8.5 91 204 N 06/21/96 Cf 11.W. OF LOT 10 148.0 4 127.5 133.0 12.9 9.0 96 205 N 06/21/96 CF N.W. OF LOT 10 150.0 4 124.0 133.0 13.7 9.0 93 206 N 06/21/96 CF N.W. OF LOT 11 146.0 5 117.3 129.0 10.7 10.0 91 207 N 06/21/96 CF N.W. OF LOT 11 143.0 5 117.9 129.0 10.9 10.0 91 208 N 06/24/96 CF LOT 7 142.0 8 114.2 127.0 10.8 11 .o 90 209 N 06/24/96 CF LOT 7 148.0 8 117. 1 127.0 11.2 ,, .o 92 210 N 06/24/96 CF S. OF LOT 6 152.0 8 114.8 127.0 11.0 11.0 90 211 N 06/25/96 CF S. OF LOT 7 142.0 8 117.2 127.0 10.5 11.0 92 212 N 06/25/96 CF N. OF LOT 8 141.0 8 115.3 127.0 9.0 11.0 91 213 N 06/25/96 CF S. OF LOT 6 148.0 8 122.6 127.0 10.5 11.0 97 214 N 06/25/96 CF N. OF LOT 7 144.0 8 116.4 127.0 11.2 11.0 92 215 N 06/26/96 CF S. OF LOT 11 142.0 1 112.2 124.0 9.2 8.5 90 216 N 06/26/96 CF S.W. OF LOT 6 152.0 1 111.5 124.0 9. 1 8.5 90 217 N 06/26/96 CF S.W. OF LOT 6 152.0 1 117 .2 124.0 10.0 8.5 95 218 N 06/26/96 CF S.W. OF LOT 6 139.0 1 115.5 124.0 9.0 8.5 93 219 N 06/26/96 CF S.W. OF LOT 18 141.0 1 114.5 124.0 9.7 8.5 92 220 N 06/26/96 CF W. OF LOT 7 147.0 , 112.5 124.0 10.0 8.5 91 221 N 06/26/96 CF LOT 7 148.0 1 113.9 124.0 7.9 8.5 92 222 N 06/26/96 CF LOT 7 146.0 , 114.5 124.0 8.3 8.5 92 223 N 06/27/96 CF LOT 10 151.0 1 116.0 124.0 9. 1 8.5 94 224 N 06/27/96 CF LOT 10 162.0 , 113.8 124.0 8.7 8.5 92 225 N 06/27/96 CF LOT 10 160.0 1 112.3 124.0 9.5 8.5 91 226 N 06/27/96 CF LOT 10 162.0 1 116.8 124.0 8.3 8.5 94 227 II 06/27/96 CF LOT 10 163.0 1 112.3 124.0 7.9 8.5 91 228 N 06/27/96 CF LOT 10 165.0 2 118.4 129.0 9.6 10.0 92 229 ,. 06/27/96 CF LOT 10 165.0 2 120.0 129.0 10.4 10.0 93 230 N 06/27/96 CF LOT 7 152.0 2 117.5 129.0 11.0 10.0 91 231 N 06/27/96 CF LOT 6 SWTH 155.0 5 120.0 129.0 13.6 10.0 93 232 N 06/27/96 CF LOT 6 SWTH 155.0 5 119.9 129.0 11.4 10.0 93 233 N 06/27/96 CF LOT 6 SOOTH 161.0 5 116.9 129.0 10.8 10.0 91 234 N 06/27/96 Cf M. OF LOT 7 151.0 5 117.9 129.0 12.7 10.0 91 235 N 06/27/96 CF LOT 7 165.0 5 120.9 129.0 13. 1 10.0 94 - ---- - -- -- - -- -- --- -02/12/97 Page No. 6 SUMNARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489-11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ··••-·•·-··· LOCATION --------······ TEST SOIL ORY OE~SITY(pcf) M'OISTURECX) REL(¾) REMARKS NUMBER METH DATE OF ELEV( ft) TYPE FIELD MAX FIELO OPT COMP --------------·-· ·---------·-··-----·-------------------·---··------·-------------·--· ----------236 N 06/27/96 CF LOT 7 150.0 1 119.3 124.0 10. 1 8.5 96 237 N 06/27/96 CF LOT 7 155.0 1 112.3 124.0 9.6 8.5 91 238 N 06/27/96 CF S. OF LOT 7 157.0 1 115.0 124.0 8.8 8.5 93 239 N 06/27/96 CF S. OF LOT 7 149.0 1 116.0 124.0 9.5 8.5 94 240 N 06/27/96 CF LOT 8 159.0 1 118.6 124.0 8.8 8.5 96 241 N 06/27/96 CF LOT 8 144.0 14 117 .6 130.5 10.8 9,5 90 242 N 06/27/96 CF LOT 8 146.0 14 120.3 130.5 ,, .6 9.5 92 243 N 06/28/96 CF LOT 8 146.0 10 119.2 128.0 10.7 9.0 93 244 N 06/28/96 CF SLOPE E. OF LOT 8 144.0 10 114.9 128.0 11.8 9.0 90 245 N 06/28/96 CF SLOPE E. OF LOT 7 144.0 10 116.9 128.0 9.6 9.0 91 246 N 06/28/96 CF LOT 7 147.0 10 120.3 128.0 10.6 9.0 94 247 H 06/28/96 CF LOT 8 150.5 14 119.8 130.5 11.5 9.5 92 248 N 06/28/96 CF S. OF LOT 7 165.0 1 112.4 124.0 10.2 8.5 91 249 N 06/28/96 CF S. OF LOT 7 147.0 1 116.2 124.0 9.7 8.5 94 250 N 06/28/96 CF LOT 6 160.0 1 113.4 124.0 8.9 8.5 91 251 N 06/28/96 CF LOT 6 164.0 1 116.0 124.0 10.6 8.5 94 252 N 06/28/96 CF LOT 7 164.0 1 111. 7 124.0 8.9 8.5 90 253 N 06/28/96 CF LOT 6 157.0 1 112.4 124.0 9.2 8.5 91 254 N 06/28/96 CF LOT 7 168.0 1 113.7 124.0 10. 1 8.5 92 255 N 06/28/96 CF LOT 11 147.0 1 117.3 124.0 9.0 8.5 95 256 N 06/28/96 CF LOT 11 149.0 1 114.3 124.0 9.3 8.5 92 257 N 06/28/96 CF FILL SLOPE W. OF ARMADA DRIVE 153.0 , 119.9 124.0 10.4 8.5 97 258 N 06/28/96 CF FILL SLOPE W. OF ARMADA DRIVE 156.0 1 113. 7 124.0 10.1 8.5 92 259 N 06/28/96 CF Fill SLOPE W, OF ARMADA DRIVE 148.0 1 114.3 124.0 8.2 8.5 92 260 H 06/28/96 CF Fill SLOPE W. OF ARMADA DRIVE 150.0 1 112.9 124.0 8.8 8.5 91 261 N 06/28/96 CF 2:1 FILL SLOPE W. Of LOT 147.0 1 114.9 124.0 9. 1 8.5 93 262 H 06/28/96 CF 2: 1 FILL SLOPE W. OF LOT 144.0 1 113.3 124.0 9.8 8.5 91 263 H 06/28/96 CF 2:1 FILL SLOPE W. Of LOT 148.0 1 111.7 124.0 9.0 8.5 90 264 N 06/28/96 CF 2:1 FILL SLOPE II. OF LOT 151.0 1 112.4 124.0 8.0 8.5 91 265 N 07/01/96 CF W. OF ARMADA DRIVE 155.0 8 118.4 127.0 10.8 11.0 93 266 N 07/01/96 CF ARMADA DRIVE 153.0 8 115.8 127.0 12.7 11.0 91 267 N 07/01/96 CF W. OF ARMADA DRIVE 153.0 8 119.6 127.0 11.6 11.0 94 268 N 07/01/96 Cf W. OF ARMADA DRIVE 153.0 8 113.9 127.0 10.6 11.0 90 269 N 07/01/96 CF W. OF ARMADA DRIVE 152.0 8 116.6 127.0 10.4 11.0 92 270 N 07/01/96 CF W. OF ARMADA DRIVE 154.0 8 121.0 127.0 11.5 11. 0 95 271 N 07/01/96 CF LOT 11 148.0 8 117.3 127.0 11.8 11.0 92 272 H 07/01/96 CF LOT 11 149.5 14 124.2 130.5 10.6 9.5 95 2.73 N 07/01/96 CF W. OF ARMADA DRIVE 156.0 8 116.0 127.0 12.4 , 1.0 91 274 H 07/01/96 CF W. OF ARMADA DRIVE 156.0 8 114.8 127.0 11.6 11.0 90 275 N 07/01/96 CF ARMADA DRIVE 157.0 8 118.5 127.0 10.7 11.0 93 276 H 07/01/96 CF W. OF ARMADA DRIVE 157.0 8 117.2 127.0 11.2 11.0 92 2n N 07/01/96 CF ARMADA DRIVE 157.0 8 116.1 127.0 10.5 11.0 91 278 N 07/01/96 CF ARMADA DRIVE 155.0 8 118. 1 127.0 11.3 11.0 93 279 N 07/01/96 CF ARMADA DRIVE 154.0 8 114.6 127 .o 12.0 11.0 90 280 H 07/01/96 CF ARMADA DRIVE 155.5 8 117. 1 127.0 11.7 11.0 92 281 N 07/02/96 CF ARMADA DRIVE 150.0 1 113.9 124.0 9.7 8.5 92 282 N 07/02/96 CF LOT 14 151.5 4 120.7 133.0 11 .1 9.0 91 -- - - - -- -- - -- - --- ---02/12/97 Page No. 7 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST -····-···-·· LOCATION·-··········-· TEST SOIL ORY DENSITY(pcf) HDISTURE(X) REL(X) REMARKS NUMBER METH DATE Of ELEV(ft) TYPE FIELD MAX FIELD OPT Cc»4P ---------------·------·------·-·-----------·--------------------...... -....... ~ ------·-----------------283 N 07/02/96 CF AR"ADA DRIVE 148.0 5 119.4 129.0 9.9 10.0 93 284 N 07/02/96 CF II. OF LOT 12 ARMADA DRIVE 155.0 4 119.6 133.0 9.6 9.0 90 285 N 07/02/96 CF ARMADA DRIVE 157.0 5 117.3 129.0 12.5 10.0 91 286 N 07/02/96 CF ALONG 12 IIALL U/0 ARMADA 155.0 1 115.7 124.0 7.2 8.5 93 287 II 07/02/96 CF ALONG 12 IIALL 11/0 ARMADA 156.0 1 115.0 124.0 8.6 8.5 93 288 N 07/02/96 CF ALONG 12 IIALL 11/0 ARMADA 158.0 1 112.6 124.0 10.3 8.5 91 289 N 07/02/96 CF ALONG 12 IIALL 11/0 ARMADA 157.0 4 121.1 133.0 10.4 9.0 91 290 N 07/02/96 CF ARMADA DRIVE 158.0 5 117 .4 129.0 9.0 10.0 91 291 N 07/02/96 CF LOT 6 158.0 8 115.0 127.0 12.9 11. 0 91 292 N 07/02/96 CF LOT 6 166.0 8 113.7 127.0 9.8 11.0 90 293 N 07/02/96 CF ARHAOA DRIVE STATION 40+50 151.0 8 116,5 127.0 12. 1 11. 0 92 294 N 07/02/96 CF ARMADA DRIVE STATION 39+20 153.0 8 115.4 127.0 11.5 11.0 91 295 II 07/02/96 Cf LOT 14 152.0 8 116.8 127.0 11.2 11.0 92 296 II 07/03/96 CF N.E. OF LOT 6 164.0 9 121. 7 130.0 8.5 10.0 94 297 II 07/03/96 CF N.E. Of LOT 6 166.0 8 117 .9 127.0 11.5 , 1 .o 93 298 N 07/03/96 CF 11.E. OF LOT 6 157.0 8 114.0 127.0 10.7 11 .0 90 299 II 07/03/96 CF N.E. OF LOT 6 159.0 6 109.1 115.5 12.3 9.0 94 300 N 07/03/96 CF S.E. OF LOT 6 154.0 6 105.7 115.5 10.0 9.0 92 301 N 07/03/96 CF s.e. OF LOT 6 0.0 8 114.1 127.0 9.3 11.0 90 302 II 07/03/96 CF N.E. OPF LOT 6 o.o 8 115.3 127.0 10.8 11.0 91 303 N 07/03/96 CF N.E. OPF LOT 6 o.o 8 , 1r..r. 127.0 11.2 11.0 90 304 N 07/03/96 CF S.E. OF LOT 6 0.0 8 115.6 127.0 11.6 11 .0 91 305 N 07/03/96 CF ARMADA DRIVE STATION 21+75 o.o 6 109.9 115.5 11.2 9.0 95 306 N 07/03/96 CF ARMADA DRIVE STATION 21+90 0.0 6 106.9 115.5 11.5 9.0 93 307 N 07/03/96 CF ARMADA DRIVE STATION 22+30 0.0 1 112. 1 124.0 12.0 8.5 90 308 N 07/03/96 CF ARMADA DRIVE STATION 23+40 0.0 6 103.8 115.5 10.0 9.0 90 309 N 07/03/96 CF ARMADA DRIVE STATION 23+60 0.0 8 117.3 127 .o 12.0 11.0 92 310 II 07/03/96 CF ARMADA DRIVE STATION 23+45 0.0 8 117.5 127.0 11.0 11,0 93 311 N 07/03/96 Cf ARMADA DRIVE STATION 23+96 162.5 1 111.9 124.0 9.9 8.5 90 312 II 07/03/96 CF ARMADA DRIVE STATION 26-+55 159.0 8 117. 1 127.0 10.9 11.0 92 313 N 07/03/96 CF ARMADA DRIVE STATION 31+00 159.0 6 104.6 115.5 8.9 9.0 91 314 N 07/03/96 CF ARMADA DRIVE STATlON 31+10 155.0 8 115. 1 127.0 10.5 11.0 91 315 N 07/08/96 CF N.E. OF LOT 7 155.0 8 122.1 127.0 11. 1 11.0 96 316 N 07/08/96 CF II .E. OF LOT 7 156.0 8 123.4 127.0 1, .0 11 .o 97 317 N 07/08/96 CF E. OF LOT 7 153.0 8 116.2 127.0 11.4 11.0 91 318 II 07/08/96 CF E. OF LOT 7 154.0 8 119.2 127.0 12. 1 11.0 94 319 II 07/08/96 CF N.E. OF LOT 6 150.0 8 119.9 1l?.0 11.3 11 .0 94 320 N 07/08/96 CF N.E. OF LOT 6 151.0 8 120. 1 127.0 10.3 11.0 95 321 N 07/08/96 CF N. OF LOT 14 150.0 8 113.9 127.0 10.6 11.0 90 322 II 07/06/96 CF N. OF LOT 14 149.0 8 114.0 127.0 10.5 11.0 90 323 N 07/06/96 CF ARMADA DRJ VE STATION 41+40 148.0 8 116.3 127.0 10.2 11 .0 92 324 II 07/08/96 CF ARMADA DRIVE STATION 41+20 150.0 1 114.4 124.0 8.4 8.5 92 325 N 07/08/96 CF ARMADA DRIVE STATION 40+20 151.0 1 112.2 124.0 9.0 8.5 90 326 N 07/08/96 CF ARMADA DRIVE STATION 46+70 118.0 8 117 .6 127.0 11. 1 11.0 93 327 II 07/08/96 CF AR"AOA DRIVE STATION 46-+50 120.0 15 116.9 122.5 11.9 12.0 95 328 N 07/08/96 CF AR"ADA DRIVE STATION 48+00 116.0 8 116. 1 127.0 10.4 11.0 91 329 II 07/08/96 CF ARMADA DRIVE STATION 47+80 118.0 8 116.2 127.0 11.4 11. 0 91 - -- -- - -- -- - -- -- --- -02/12/97 Page No. 8 SUMMARY OF FIELO DENSITY TESTS PROJECT HUMBER: 04·930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST •••··•····•· LOCATION ·········•···· TEST SOIL DRY DENSITY(pcf) MOISTURE(X) REL(%) REMARKS NUMBER METH DATE OF ELEV(ft) TYPE FIELD MA)( F !ELD OPT C()fP ------------·-·-· --·---------------------------------..... --.... ------·-------·---... -...... --. ----------330 N 07/08/96 CF ARMADA DRIVE STATION 49+00 111.0 15 109.9 122.5 12.0 12.0 90 331 N 07/08/96 CF ARMADA DRIVE STATION 49+00 114.0 8 113.8 127.0 10. 1 11. 0 90 332 N 07/08/96 CF ARMADA DRIVE ST A Tl ON 46+50 126.0 16 112. 1 124.0 11.6 10.5 90 333 N 07/08/96 CF ARMADA DRIVE STATION 47+50 123.0 16 112.7 124.0 11.8 10.5 91 334 N 07/08/96 CF ARMADA DRIVE STATION 48+50 121.0 8 117.1 127.0 11 .8 11.0 92 335 N 07/09/96 CF ARMADA DRIVE STATION 47+00 129.0 16 114.5 124.0 12.6 10.5 92 336 H 07/09/96 CF ARMADA DRIVE STATION 47+70 127.0 16 113.0 124.0 12.7 10.5 91 337 N 07/09/96 CF ARMADA DRIVE STATION 48+10 125.0 16 114. 1 124.0 12.0 10.5 92 338 N 07/09/96 CF N.E. OF LOT 7 156.0 17 110.4 116.0 7.4 8.0 95 339 N 07/09/96 CF N.W. OF LOT 11 158.0 16 111.3 124.0 12.0 10.5 90 340 N 07/09/96 CF N.E. OF LOT 8 154.0 1 117.3 124.0 8.1 8.5 95 341 N 07/09/96 CF E. OF LOT 8 156.0 16 115.8 124.0 11.5 10.5 93 342 N 07/09/96 CF S.W. OF LOT 11 153.0 16 113. 1 124.0 10.2 10.5 91 343 H 07/09/96 CF N.W. OF LOT 18 154.0 16 111.5 124.0 10.8 10.5 90 344 N 07/09/96 Cf ARMADA DRIVE STATION 49+30 119.0 16 111.8 124.0 10.5 10.5 90 345 N 07/09/96 CF ARMADA DRIVE STATION 49+40 117.0 8 116.9 127.0 11 .6 11 .0 92 346 N 07/09/96 CF ARMADA ORIVE STATION 48+25 122.0 16 111.1 124.0 11.5 10.5 90 347 N 07/09/96 CF ARMADA DRIVE STATION 47+65 131.0 17 109.4 116.0 11. 1 8.0 94 348 N 07/09/96 CF ARMADA DRIVE STATION 46+40 133.0 16 113.2 124.0 10.6 10.5 91 349 N 07/09/96 CF ARMADA DRJVE STATJON 46+50 138.0 16 111.9 124.0 10.9 10.5 90 350 N 07/09/96 CF S.E. OF LOT 6 157.0 8 120.9 127.0 11.4 11.0 95 351 N 07/09/96 CF S.E. OF LOT 6 161.0 16 118.4 124.0 12. 1 10.5 95 352 N 07/09/96 CF N.E. OF LOT 7 155.0 17 112.0 116.0 8.6 8.0 97 353 N 07/09/96 CF !I.E. OF LOT 7 157.0 17 112.9 116.0 13.6 8.0 97 354 N 07/09/96 CF II. OF LOT 18 149.0 8 118.1 127.0 9.3 11.0 93 355 N 07/09/96 CF \I. OF LOT 18 152.0 1 116.8 124.0 8.2 8.5 94 356 N 07/10/96 CF CENTER OF LOT 6 164.0 8 120.5 127.0 10.9 11.0 95 357 N 07/10/96 CF CENTER OF LOT 6 165.0 17 104.3 116.0 8.5 8.0 90 358 N 07/10/96 CF N.E. OF LOT 7 156.0 16 117. 1 124.0 8.5 10.5 94 359 N 07/10/96 CF N.E. OF LOT 7 157.0 17 114.1 116.0 8.4 8.0 98 360 N 07/10/96 CF S.E. OF LOT 7 153.0 17 114.9 116.0 10.5 8.0 99 361 N 07/10/96 CF S.E. OF LOT 8 154.5 1 113.2 124.0 8.7 8.5 91 362 N 07/10/96 CF S.W. OF LOT 14 152.5 1 113.2 124.0 8.7 8.5 91 363 N 07/10/96 CF S.W. OF LOT 14 152.0 17 112.9 116.0 7.9 8.0 97 364 N 07/10/96 CF S.W. OF LOT 14 154.0 17 107.7 116.0 7.1 8.0 93 365 N 07/10/96 CF s.e. OF lOT 14 154,0 16 111.6 124.0 10.5 10.5 90 366 N 07/10/96 CF s.e. OF LOT 14 153.0 17 106.6 116,0 8.0 8.0 9Z 367 N 07/10/96 CF N.E. Of lOT 6 168.0 16 114.3 124.0 10.9 10.5 92 368 N 07/10/96 CF N.E, OF LOT 7 159.0 16 115.4 124.0 11.4 10.5 93 369 N 07/10/96 CF S. OF LOT 7 154.0 17 107 .s 116.0 8.1 8.0 93 370 N 07 /11/96 Cf E. OF LOT 6 165.5 9 121.3 130.0 11.6 10.0 93 371 N 07/11/96 Cf CENTER OF LOT 6 167.0 8 116.3 127.0 10.5 11. 0 92 372 N 07/11/96 CF S.E. OF LOT 7 156.0 1 118.2 124.0 11.5 8.5 95 373 N 07/11/96 Cf N.E. OF LOT 8 157.S 9 121.8 130.0 9.8 10.0 94 374 N 07/11/96 CF S.W. OF LOT 18 148.0 17 106.5 116.0 8.7 8.0 92 375 N 07 /11/96 CF S.E. OF LOT 8 151.0 16 118.5 124.0 13.4 10.5 96 376 N 07/11/96 CF S. OF LOT 6 165.0 9 121. 7 130.0 11.1 10.0 94 - -- - - --- - -- - - - ---- -02/12/97 Page No. 9 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489-11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ·•·········· LOCATION-····-········ TEST SOIL ORY DENSITY(pcf) MO!STURE(X) REL(r.) REMARKS NUMBER METH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT COMP -.. -.... -..... -. -.. -..... ·----·--·-··-------·-·-------·------............... ........... ---------··-·--··-.. ... --.......... 3n N 07/11/96 CF S,E. OF LOT 6 166.0 9 116.7 130.0 9.3 10.0 90 378 N 07/11/96 CF S.E. OF LOT 6 168.0 16 116. 7 124.0 11. 9 10.5 94 379 N 07/11/96 CF N. Of LOT 7 161.0 16 116.0 124.0 11. 1 10.5 94 380 N 07/11/96 CF N.E. OF LOT 7 162.0 9 120.4 130.0 10.0 10.0 93 381 N 07 /11/96 CF N.E. OF LOT 7 165.0 8 118.4 127.0 10.2 11.0 93 382 N 07/11/96 CF S.W. OF LOT 8 153.0 16 117 .1 124.0 9.6 10.5 94 383 H 07/11/96 CF S.W. OF LOT 18 154.0 16 116.2 124.0 10. 1 10.5 94 384 H 07/11/96 CF S.11. OF LOT 18 153.0 8 116. 1 127.0 11.2 11.0 91 385 N 07/11/96 FG S.11. OF LOT 18 164.5 1 112.0 124.0 8.4 8.5 90 386 H 07/11/96 FG S.W. Of LOT 18 165.0 5 116.9 129.0 8.1 10.0 91 387 N 07/11/96 FG S.11. OF LOT 18 165.0 1 112.8 124.0 8.0 8.5 91 388 H 07/12/96 CF N.E. Of LOT 6 168.0 2 123.2 129.0 10.3 10.0 96 389 N 07/12/96 CF N.E. Of LOT 6 149.0 2 116.8 129.0 11 .s 10.0 91 390 N 07/12/96 CF N.E. OF LOT 6 170.0 16 114.8 124.0 11. 7 10.5 93 391 N 07/12/96 CF lf,E. OF LOT 7 158.0 9 120.4 130.0 12.4 10.0 93 392 N 07/12/96 CF N.E. OF LOT 7 160.0 9 118.8 130.0 9.4 10.0 91 393 N 07/12/96 CF M.W. OF LOT 11 162.0 16 115. 1 124.0 11.0 10.5 93 394 N 07/12/96 CF S.E. OF LOT 8 152.5 17 107.5 116.0 10.4 8.0 93 395 N 07/12/96 CF S.11. Of LOT 18 153.S 16 118.7 124.0 12.2 10.5 96 396 N 07/12/96 CF S.W. OF LOT 18 157.0 16 118.4 124.0 11.4 10.5 95 397 N 07/12/96 CF E. Of LOT 14 151.0 1 111. 7 124.0 10.0 8.5 90 398 N 07/12/96 CF E. OF LOT 14 152.0 8 114.8 127.0 9.8 11.0 90 399 N 07/12/96 CF II.II. OF LOT 6 166.0 16 121.1 124.0 12.1 10.5 98 400 N 07/12/96 CF N.IJ. OF LOT 6 167.0 16 119. 1 124.0 11. 1 10.s 96 401 N 07/12/96 CF 11,\1. OF LOT 6 161.0 16 119.2 124.0 11.6 10.5 96 402 N 07/12/96 CF N.W. OF LOT 6 162.5 16 119.2 124.0 12.4 10.5 96 403 M 07/12/96 CF S.E. OF LOT 8 153.0 9 120.0 130.0 12.8 10.0 92 404 N 07/12/96 CF S.E. OF LOT 8 157.0 16 118.9 124.0 9.7 10.5 96 405 N 07/15/96 CF CENTER OF LOT 6 168.0 16 118. 1 124.0 13. 7 10.5 95 406 N 07/15/96 CF E. OF OT 6 168.0 16 120.1 124.0 10.3 10.5 97 407 N 07/15/96 CF E. OF OT 6 169.0 16 117 .0 124.0 10.5 10.S 94 408 N 07/15/96 CF S. CENTER OF LOT 7 163.5 16 114. 7 124.0 11.9 10.S 93 409 H 07/15/96 CF s.E. OF LOT 7 164.0 16 120.3 124.0 12.8 10.5 97 410 N 07/15/96 Cf s.e. OF LOT 7 165.0 16 116.2 124.0 13.S 10.5 94 411 H 07/15/96 CF N. CENTER OF LOT 8 159.0 16 115. 7 124.0 12.7 10.5 93 412 N 07/15/96 CF N.E. OF LOT 8 160.0 16 113.6 124.0 11.2 10.5 92 413 N 07/15/96 CF CENTER OF LOT 8 162.0 16 115.6 124.0 10. 1 10.5 93 414 H 07/15/96 CF N.E. OF LOT 6 169.0 16 115.6 124.0 11.8 10.5 93 415 H 07/15/96 CF S.E. OF LOT 7 164.0 16 115.8 124.0 13.5 10.5 93 416 H 07/15/96 CF N.E. OF LOT 8 163.0 16 114.3 124.0 10.6 10.5 92 417 N 07/16/96 CF S.E. OF LOT 6 169.0 16 116.5 124.0 13.6 10.5 94 418 N 07/16/96 CF S.E. OF LOT 6 170.0 16 118.7 124.0 10.5 10.5 96 419 N 07/16/96 CF S. OF LOT 6 169.0 16 114.5 124.0 11.2 10.5 92 420 N 07/16/96 CF N. OF LOT 7 167.0 16 118.9 124.0 12.5 10.5 96 421 N 07/16/96 CF !f.E. OF LOT 7 164.0 16 115.9 124.0 11.5 10.S 93 422 N 07/16/96 CF S.E. OF LOT 7 165.0 16 114.6 124.0 11.3 10.5 92 423 N 07/16/96 CF s.e. OF LOT 8 157.0 16 ' 113.5 124.0 10.8 10.5 92 - -- -- ------ - - --- -- -02/12/97 Page No. 10 SUMl'!ARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04 ·930489· 11 NAME: CARLSBAD RANCH TEST TEST TEST TEST •••••.•••... LOCATION ···•·····•···· TEST SOIL DRY DENSITY(pcf) MOISTURE(X) REL(X) REMARKS NUMBER METH DATE OF ELEV( ft) TYPE FIELD KAX f IELD OPT COMP ♦--·----------·----------·--------------•#·•-----~---------··--....................... ---.... ---.. -------·--·· 424 N 07 /16/96 CF s.e. OF LOT 8 158.5 16 119.8 124.0 10.7 10.5 97 425 N 07/16/96 CF S. OF LOT 8 161.0 16 116.5 124.0 11.0 10.5 94 426 N 07/16/96 CF N. OF LOT 7 167.0 16 120.4 124.0 12.2 10.5 97 427 N 07/16/96 CF N.E. OF LOT 7 168.0 16 112.6 124.0 15.2 10.5 91 428 N 07/16/96 CF N.E. OF LOT 7 168.0 5 119. 7 129.0 10.4 10.0 93 429 N 07/16/96 CF S. OF LOT 7 164.0 1 115. 7 124.0 7.9 8.5 93 430 N 07/16/96 CF S.E. OF LOT 7 165.0 16 116.6 124.0 12.7 10.5 94 431 H 07/16/96 CF S.E. OF LOT 7 164.0 16 115.0 124.0 12.9 10.5 93 432 N 07/16/96 CF S.E. OF LOT 8 158.0 9 118.5 130.0 11.5 10.0 91 433 N 07 /16/96 CF S.E. OF LOT 8 160.0 16 111, 5 124.0 13.6 10.5 90 434 N 07/16/96 Cf S.E. OF LOT 8 159.0 16 113.2 124.0 12. 1 10.5 91 435 N 07/17/96 Cf ARMADA ORIVE STATION 19+00 162.0 5 116. 1 129.0 10.6 10.0 90 436 N 07/17/96 CF ARMADA DRIVE STATION 19+40 163.5 1 116.9 124.0 8.8 8.5 94 437 N 07/17/96 CF ARMADA DRIVE STAT JON 19+50 164.0 16 113.8 124.0 9.4 10.5 92 438 N 07/17/96 CF ARMADA DRIVE STATION 26+90 164 .0 8 113.8 127.0 10.5 11.0 90 439 N 07/17/96 CF ARMADA DRIVE STATION 19+80 156.0 17 112.5 116.0 9.3 8.0 97 440 N 07/17/96 CF ARMADA DRIVE STATION 20+00 158.0 8 119. 7 127.0 13.2 11.0 94 441 N 07/18/96 Cf BELEVEOERE LOT 14 (\./EST) 148.0 8 114. 1 127.0 10.6 11. 0 90 442 N 07/18/96 CF BELEVEDERE LOT 14 (\./EST) 150.0 8 115.1 127.0 11.8 11.0 91 443 N 07/18/96 CF ARMARDA DRIVE 160.0 8 120.2 127.0 11.6 11.0 95 444 N 07/18/96 Cf ARMARDA DRIVE 162.0 8 117.8 127.0 9.8 11.0 93 445 N 07/18/96 CF BELVEDERE LOT 14 (WEST) 152.0 9 117 .3 130.0 9.6 10.0 90 446 N 07/18/96 Cf BELVEDERE 154.0 4 120.0 133.0 9.1 9.0 90 447 N 07/18/96 CF CENTER OF LOT 7 167.0 16 115.6 124.0 11.6 10.5 93 448 N 07/18/96 CF N.E. Of LOT 7 169.0 9 118.0 130.0 9.6 10.0 91 449 N 07/18/96 CF N.E. Of LOT 8 163.0 9 119.9 130.0 10.1 10.0 92 450 N 07/18/96 CF N.E. OF LOT 8 164.0 4 119.6 133.0 9.7 9.0 90 451 N 07/18/96 CF E. OF LOT 8 164.0 8 111.9 127.0 7. 1 11.0 88 RT 011 451A 451A N 07/18/96 CF E. OF LOT 8 164.0 8 115.2 127.0 10.6 11 .0 91 RT OF 451 452 N 07/19/96 CF BELVEDERE 155.0 4 120.4 133.0 8.6 9.0 91 453 N 07/19/96 CF BELVEDERE 157.0 4 123.4 133.0 8.9 9.0 93 454 N 07/19/96 FG E. OF LOT 14 153.0 1 111. 7 124.0 6.9 8.5 90 455 N 07/19/96 FG E. OF LOT 14 152.0 17 112. 1 116.0 10.0 8.0 97 456 N 07/19/96 CF ARMADA DRIVE STATION 19+75 166.0 1 109.8 124.0 9.6 8.5 89 RT ON 456A 456A N 07/31/96 CF ARMADA DRIVE 166.0 1 112.3 124.0 7.5 8.5 91 RT OF 456 457 N 07/19/96 CF ARMADA DRIVE STATION 19+95 165.0 9 108.5 130.0 6.8 10.0 83 RT ON 457A 457A N 07/31/96 CF ARMADA DRIVE 165.0 9 117 .3 130.0 9.3 10.0 90 RT OF 457 458 N 07/19/96 FG ARMADA DRIVE STATION 21+00 162.5 17 104.5 116.0 5.6 8.0 90 459 N 07/19/96 FG ARMADA DRIVE STATION 23+00 161.5 1 113.0 124.0 7.8 8.5 91 460 N 07/19/96 FG ARMADA PARK\IAY 165.0 17 109.9 116.0 6.2 8.0 95 461 N 07/19/96 FG ARMADA PARK\IAY 163.0 6 109.9 115.5 4.9 9.0 95 462 N 07/19/96 SF ARMADA PARK\IAY 159.0 8 113.8 127.0 5.1 11.0 90 463 N 07/19/96 FG ARMADA PARKWAY 161.5 17 108.4 116.0 7.6 8.o 93 464 N 07/19/96 Sf ARMADA PARK\IAY 156.5 17 110. 1 116.0 4.8 8.0 95 465 H 07/19/96 CF W. OF LOT 14 154.5 1 105.2 124.0 9.4 8.5 85 RT ON 465A 465A H 07/26/96 CF S.W. OF LOT 14 154.5 1 107.7 124.0 8.2 8.5 87 RT ON 4658 4658 N 08/16/96 CF ARMADA PARK\IAY 154.5 1 116. 9 124.0 9.0 8.5 94 RT OF 465 - - - - -- --- - - - ----- --02/12/97 Page No. 11 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04·930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ············LOCATION·············· TEST SOIL DRY DENStTYCpcf) HOISTURECX) REL(X) REMARKS NUMBER HETH DATE Of ELEV(ft) TYPE FIELD MAX FIELD OPT COMP ----... --. --·-···-·--·····---····---·---·--·-------------·-----· -..... -....... -..... ----······· ----------466 N 07/23/96 CF S. OF LOT 8 163.0 9 118.9 130.0 10.0 10.0 91 467 N 07/23/96 CF CENTER OF LOT 8 163.5 9 117.4 130.0 9.3 10.0 90 468 N 07/23/96 CF N. OF LOT 8 164.0 4 119.5 133.0 9.2 9.0 90 469 N 07/23/96 CF N. OF LOT 8 165.5 9 117. 1 130,0 9.6 10.0 90 470 N 07/23/96 CF S.E. OF LOT 8 157.5 9 120. 1 130.0 10.3 10.0 92 471 N 07/23/96 CF E. OF LOT 8 162.0 9 118.2 130.0 10.5 10.0 91 472 N 07/23/96 CF ARMADA PARKWAY STATION 26+80 165.0 17 104.3 116.0 7.6 8.0 90 473 N 07/23/96 Sf ARMADA PARKWAY STATION 21+50 158.5 1 110.1 124.0 8.6 8.5 89 RT ON 473A 473A N 08/16/96 SF ARMADA PARKWAY STATION 21+50 158.0 1 112.7 124.0 7.2 8.5 91 RT OF 473 474 N 07/23/96 SF ARMADA PARKWAY STATION 22 30 155.0 17 104.4 116.0 7.2 8.0 90 475 N 07/23/96 SF ARMADA PARKWAY STATION 23+25 157.0 17 101.6 116.0 7.1 8.0 88 RT ON 475A 475A N 08/16/96 SF ARMADA PARKWAY STATION 23+25 157.0 17 104.9 116.0 8.0 8.0 90 RT OF 475 476 N 07/23/96 CF S. OF LOT 8 164.0 8 119.6 127.0 12. 1 11.0 94 477 N 07/23/96 CF CENTER Of LOT 8 165.0 4 119.8 133.0 10.4 9.0 90 478 N 07/23/96 Cf CENTER Of LOT 8 165.0 16 117.2 124.0 11.8 10.5 95 479 N 07/24/96 CF ARMADA PARKWAY STATION 28+50 152.0 6 110. 1 115.5 14.8 9.0 95 480 N 07/24/96 CF ARMADA DRIVE STATION 28+50 154.0 1 111.5 124.0 11. 1 8.5 90 481 N 07/24/96 CF S.E. OF LOT 8 162.0 1 113. 1 124.0 8.7 8.5 91 482 N 07/24/96 CF S.E. OF LOT 8 160.0 9 117.5 130.0 10.2 10.0 90 483 N 07/24/96 CF S. OF LOT 8 163.0 9 117.5 130.0 12.4 10.0 90 484 N 07/24/96 FG CENTER OF LOT 8 163.0 9 116.5 130.0 7.3 10.0 90 485 N 07/24/96 FG ARMADA DRIVE 163.5 9 119.6 130.0 10.6 10.0 92 486 N 07/25/96 CF ARMADA DRIVE STATIOtl 42+50 140.0 9 118.4 130.0 11.8 10.0 91 487 N 07/25/96 CF ARMADA DRIVE STATION 43+00 142.0 9 120.0 130.0 12.6 10.0 92 488 N 07/25/96 CF ARMADA DRIVE STATION 44+00 141.0 4 12.3.4 133.0 10.9 9.0 93 489 H 07/25/96 CF ARMADA DRIVE STATION 43+80 142.5 9 117 .5 130.0 10.5 10.0 90 490 N 07/26/96 FG S.\I. OF LOT 14 153.5 17 113.2 116.0 6.2 8.0 98 491 N 07/26/96 FG S.\I. OF LOT 14 154.5 17 108.9 116.0 7.7 8.0 94 492 N 07/26/96 FG N.\I. OF LOT 14 157.5 1 113.2 124.0 6.4 8.5 91 493 N 07/26/96 FG N.\I. OF LOT 14 159.0 17 113.9 116.0 6. 1 8.0 98 494 N 07/26/96 CF ARMADA DRIVE STATION 46+50 125.5 1 111.8 124.0 8. 1 8.5 90 495 N 07/26/96 CF ARMADA DRIVE STATION 46+60 127.0 , 112.5 124.0 8. 1 8.5 91 496 N 07/26/96 CF ARMADA DRIVE STATION 46+65 128.5 1 113.2 124.0 8.9 8.5 91 497 N 07/29/96 CF S.E. OF LOT 14 144.0 9 117.2 130.0 10.6 10.0 90 498 N 07/29/96 CF S.E. OF LOT 14 145.0 9 118.2 130.0 11 .2 10.0 91 499 N 07/29/96 CF S.E. OF LOT 14 144.0 16 111.1 124.0 12.8 10.5 90 500 M 07/29/96 CF S.E. OF LOT 14 142.0 9 117.9 130.0 10.6 10.0 91 501 N 07/30/96 Cf S.E. OF LOT 14 148.0 1 114.4 124.0 12.5 8.5 92 502 N 07/30/96 CF S.E. OF LOT 14 150.0 16 111.2 124.0 10.4 10.5 90 503 N 07/30/96 CF ARMADA DRIVE STATION 42+10 147.0 17 110.3 116.0 11.0 8,0 95 504 N 07/30/96 CF ARMADA DRIVE STATION 47+10 129.0 4 119.6 133.0 9.6 9.0 90 505 N 07/30/96 CF ARMAOA DRIVE STATION 46+90 131.0 16 114.6 124.0 11.5 10.5 92 506 N 07/30/96 CF ARMADA DRIVE STATION 46+90 131.0 15 110.6 122.5 12. 1 12.0 90 507 N 07/30/96 CF ARMADA DRIVE STAT ION 48+50 122.0 9 118. 1 130.0 10., 10.0 91 508 N 07/30/96 CF ARMADA DRIVE STATION 48+00 125.0 9 120.3 130.0 9.9 10.0 93 509 N 07/30/96 CF ARMADA DRIVE 146.0 16 112.3 124.0 12.8 10.5 91 510 N 07/31/96 CF ARMADA DRIVE 113.0 16 112.4 124.0 10.8 10.5 91 - - - ---------- -- - ---02/12/97 Page No. 12 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04·930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ••••........ LOCATION ·············· TEST SOIL ORY DENSITY(pcf) MOISTURE(¾) REL(X) REMARKS NUMBER HETH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT COMP --·---··------·--· ·--·--·---···-·-·-··----·---··--··-· ................... --··--·--·-· ··--······· -·------·· 511 N 07/31/96 CF ARMADA DRIVE 112.0 16 112.4 124.0 11.9 10.5 91 512 N 07/31/96 FG ARMADA PARK\IAY 166.5 17 104.5 116.0 6.5 8.0 90 513 H 07/31/96 CF ARMADA DRIVE 164.0 17 106.9 116.0 7.3 8.0 92 514 N 07/31/96 SF ARMADA DRIVE 163.0 1 111.8 124.0 8.0 8.5 90 515 N 07/31/96 SF ARMADA DRIVE 159.0 17 104.8 116.0 7.2 8.0 90 516 N 07/31/96 SF ARMADA DRIVE 160.0 17 105.5 116.0 11.8 8.0 91 517 N 07/31/96 SF ARMADA DRIVE 164.0 17 104.3 116.0 7.7 8.0 90 518 N 07/31/96 FG ARMADA PARK\IAY 167.0 1 111.4 124.0 6.3 8.5 90 519 N 08/01/96 FG E. OF LOT 6 170.0 16 115.7 124.0 13.9 10.5 93 520 N 08/01/96 FG S.E. OF LOT 6 1n.o 16 112. 7 124.0 13.4 10.5 91 521 II 08/01/96 FG N.E. OF LOT 7 171.0 15 110.8 122.5 13. 1 12.0 90 522 N 08/01/96 FG E. OF LOT 7 ,n.5 9 120.2 130.0 10.8 10.0 92 523 N 08/01/96 FG S.E. OF LOT 7 167.0 9 118. 1 130.0 13.6 10.0 91 524 N 08/01/96 FG N.E. OF LOT 8 168.5 16 113.3 124.0 15.3 10.5 91 525 N 08/01/96 FG N.E. OF LOT 8 165.0 4 124.5 133.0 12.5 9.0 94 526 N 08/01/96 FG E. OF LOT 8 166.0 9 125.4 130.0 11.9 ,o.o 96 527 N 08/02/96 CF ARMADA DRIVE STATION 21+40 161.0 18 116.2 126.5 8.6 8.5 92 528 N 08/02/96 FG ARMADA PARK\IAY STATIOH 21+50 163,0 17 104.1 116.0 6.5 8.0 90 529 N 08/02/96 CF ARMADA DR I VE STATIOH 23+50 160.0 18 120.2 126.5 7.1 8.5 95 530 N 08/02/96 CF ARMADA DRIVE STATION 24+00 160.5 18 114. 1 126.5 7.3 8.5 90 531 N 08/02/96 FG ARMADA PARK\IAY STATION 24+50 163.5 16 113.4 124.0 10.8 10.5 91 532 N 08/02/96 CF LEGO DRIVE STATION 9+ r.; 156.0 16 111.4 124.0 10.0 10.5 90 533 N 08/02/96 CF LEGO DRIVE STATION 9+50 157.0 16 111 .8 124.0 12.6 10.5 90 534 N 08/05/96 CF 0 ST. & ARMADA DR. 150.5 1 115.4 124.0 8.2 8.5 93 535 N 08/05/96 CF 0 ST. & ARMADA DR. 152.0 , 118. 7 124.0 10.6 8.5 96 536 H 08/05/96 CF ARMADA DRIVE STATION 26+00 163.0 1 115.0 124.0 6. 1 8.5 93 537 N 08/05/96 FG ARMADA PARK\IAY STATION 26+00 163.5 17 107.5 116.0 5.2 8.0 93 538 N 08/05/96 CF ARMADA PARKWAY STATION 27+50 162.6 18 113.8 126.5 5.9 8.5 90 539 N 08/05/96 FG ARMADA PARK\IAY STATION 28+10 163.0 1 117.5 124.0 5.6 8.5 95 540 N 08/05/96 SF ARMADA PARKWAY STATION 27+00 161.0 17 104.4 116.0 5. 1 8.0 90 541 N 08/05/96 FG ARMADA PARK\IAY STATION 27+80 159.0 18 120.4 126.5 7.7 8.5 95 542 H 08/05/96 SF ARMADA PARK\IAY STATION 28+00 155.0 17 104.0 116.0 11.4 8.0 90 543 N 08/05/96 FG ARJilAOA PARIC\IAY STATION 29+00 153.0 9 117. 5 130.0 6.4 10.0 90 544 N 08/05/96 Cf ARMADA PARIC\IAY STATIOl4 30+50 159.0 18 118.5 126.5 5.5 8.5 94 545 H 08/05/96 FG ARMADA PARIC\IAY STATION 32+80 155.0 18 114.5 126.5 5.6 8.5 91 546 N 08/05/96 Cf ARMADA PARIC\IAY STATION 46+00 137.0 16 116.9 124.0 10.7 10.5 94 547 N 08/05/96 CF ARMADA PARIC\IAY STATION 46+70 134.0 16 116. 7 124.0 13.1 10. 5 94 54S N 08/05/96 CF ARMADA PARIC\IAY STATION 46+50 134.0 16 114.9 124.0 14.2 10.5 93 549 N 08/05/96 Cf ARMADA PARK\IAY STATION 48+00 127.0 16 114.4 124.0 10.0 10.5 92 550 M 08/05/96 CF ARMADA PARK\IAY STATION 48+35 123.0 16 115.2 124.0 13.4 10.5 93 551 N 08/06/96 Cf ARMADA PARIC\IAY STATION 32+50 159.0 16 ,, 1. 1 124.0 9.0 10.5 90 552 N 08/06/96 FG ARMADA PARK\IAY STATION 32+45 161.0 1 115.8 124.0 5.5 8.5 93 553 II 08/06/96 FG ARMADA PARK\IAY STATION 34+10 162.5 18 117.9 126.5 7.5 8.5 93 554 N 08/06/96 FG ARMADA PARK\IAY STATION 33+70 159.5 18 114.3 126.5 7.3 8.5 90 555 N 08/06/96 SF ARMADA PARK\IAY STATION 34+00 156.0 17 104.3 116.0 5.4 8.0 90 556 N 08/06/96 CF D ST./ARMADA PKWY. 156.0 18 116.7 126.5 9.2 8.5 92 557 N 08/07/96 CF ARMADA PARIC\IAY STATION 38+25 155,0 18 114. 9 126.5 8.9 8.5 91 - - - - - - -- - - -- --- -- --02/12/97 Page No. 13 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ···-·•···--· LOCATION ·······-······ TEST SOIL ORY OENSITY(pcf) MOISTURE C-X> REL(X) REMARKS NUMBER METH DATE Of ELEV(ft) TYPE FIELD MAX FIELD OPT COl'IP --·--------·---------------·-------------------------... --........ --... ----·---·--------------........ ---... -558 N 08/07/96 CF ARMADA PARK\IAY STATION 40+20 150.5 16 113. 1 124.0 9.5 10.5 91 559 N 08/07/96 FG ARMADA PARKIIAY STATION 40+40 156.0 18 113.7 126.5 7.1 8.5 90 560 N 08/07/96 CF ARMADA PARK\IAY STATION 52+90 85.0 9 117. 1 130.0 9.6 10.0 90 561 N 08/07/96 CF ARMADA PARK\IAY STATION 53+00 90.0 16 118.5 124.0 12.8 10.5 96 562 N 08/07/96 CF ARMADA PARK\IAY STATION 53+20 88.0 16 113.2 124.0 12.9 10.5 91 563 N 08/07/96 CF ARMADA PARK\IAY STATION 52+40 87.0 15 110.3 122.5 13.6 12.0 90 564 N 08/08/96 CF ARMADA PARK\IAY STATION 53+20 87.5 16 115.6 124.0 U.4 10.5 93 565 N 08/08/96 CF ARMADA PARKWAY STATION 53+40 89.0 16 122.2 124.0 11.5 10.5 99 566 N 08/08/96 Cf ARMADA PARK\IAY STATION 52+50 90.0 16 112 .o 124.0 11 .2 10.5 90 567 N 08/08/96 CF ARMADA PARKWAY 89.0 16 111.9 124.0 12.3 10.5 90 568 N 08/08/96 CF S.E. OF LOT 14 140.0 18 115.6 126.5 8.2 8.5 91 569 N 08/08/96 CF S.E. OF LOT 14 142.5 9 117.5 130.0 11 .3 10.0 90 570 N 08/08/96 CF S.E. OF LOT 14 144.5 16 112.7 124.0 10.3 10.5 91 571 N 08/08/96 CF S,E. OF LOT 14 146.5 16 113.5 124.0 12.4 10.5 92 5n N 08/08/96 FG S.E. OF LOT 8 165.0 16 113.8 124.0 10.9 10.5 92 573 N 08/08/96 FG E. OF LOT 8 167.0 16 113.3 124.0 11.4 10.5 91 574 N 08/08/96 FG N.E. OF LOT 8 167.0 9 120.9 130.0 13.4 10.0 93 575 N 08/08/96 FC s.e. OF LOT 8 164.0 9 119.3 130.0 7.5 10.0 92 576 N 08/08/96 FC S.E. OF LOT 7 170.0 16 115.0 124.0 10.3 10.5 93 577 N 08/08/96 FG E. OF LOT 7 ,n.o 16 113.8 124.0 10.8 10.5 92 578 N 08/08/96 FC N .E. OF LOT 7 173.0 9 116.9 130.0 10.4 10.0 90 580 H 08/08/96 FG CENTER OF LOT 7 169.0 16 114.3 124.0 8.8 10.5 92 581 N 08/08/96 FG S. OF LOT 7 167.0 16 111.9 124.0 9.5 10.5 90 582 N 08/08/96 FG S.11. Of LOT 7 166.5 16 120.6 124.0 11.8 10.5 97 583 N 08/08/96 FG N.11. OF LOT 7 167.0 16 114.9 124.0 12. 1 10.5 93 584 N 08/09/96 CF S,E. OF LOT 14 151.5 16 102.9 124.0 12. 1 10.5 83 RT ON 584A 584A N 08/09/96 CF s.e. OF LOT 14 151.5 16 114. 1 124.0 10.7 10.5 92 RT OF 584 585 N 08/09/96 CF S.E. OF LOT 14 149.0 9 114.5 130.0 13.0 10,0 88 RT ON 585A 585A N 08/09/96 CF S.E. OF LOT 14 149.0 9 117.4 130.0 11.6 10.0 90 RT OF 585 586 N 08/09/96 CF S.E. OF LOT 14 146.0 17 115.0 116.0 11.3 8.0 99 587 N 08/09/96 FG E. OF LOT 6 168.5 9 126.4 130.0 9.5 10.0 97 588 N 08/09/96 FG s.e. OF LOT 6 171.5 16 116.5 124.0 13.6 10.5 94 589 N 08/08/96 FG N. OF LOT 7 170.0 16 118.0 124.0 10.5 10.5 95 589 N 08/09/96 FG S. OF LOT 6 171.5 16 117. 2 124.0 10.8 10.5 95 590 N 08/09/96 FG CENTER OF LOT 6 170.0 5 120.2 129.0 9.8 10.0 93 591 N 08/09/96 FG N. OF LOT 6 168.5 5 122.3 129.0 9.4 10.0 95 592 N 08/12/96 FC N,\I, OF LOT 6 168.5 16 115.5 124.0 10.3 10.5 93 593 N 08/12/96 FG N.11. OF LOT 6 168.0 16 113. 7 124.0 9.1 10.5 92 594 N 08/12/96 FG S.E. OF LOT 14 155.0 16 113. 7 124.0 13.0 10.5 92 595 N 08/12/96 FG S.E. OF LOT 14 155.0 17 111.3 116.0 6.2 8.0 96 596 N 08/12/96 FG S.E. OF LOT 14 154.0 16 117 .9 124.0 10.5 10.5 95 597 N 08/12/96 FG S.E. OF LOT 14 154.0 17 113.0 116,0 5.8 8.0 97 598 N 08/12/96 FG S.E. OF LOT 14 152.5 1 112. 7 124.0 6.0 8.5 91 599 N 08/12/96 FG S.E. OF LOT 14 146.0 5 125.6 129.0 11.5 10.0 97 600 N 08/12/96 SF S.E. OF LOT 14 151.0 16 114.2 124.0 11 .6 10.5 92 601 N 08/12/96 SF S.E. OF LOT 14 153.0 18 113. 7 126.5 10.0 8.5 90 602 N 08/12/96 CF ARMADA PARKWAY STATION 41+7'5 148.0 16 113.5 124.0 9.9 10.5 92 ,. - - - - - - - -- - -- - - --- - -02/12/97 Page No. 14 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST •••••••••••. LOCATION·············· TEST SOIL ORY OENSITY(pcf) MOISTURE(?.) REL(¾) REMARKS NUMBER METH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT CONP ·------·· --------------··--·----·----·---------------.. -..... -.. ·--.. -------------·-·-----------·---·-603 N 08/12/96 FG ARMADA PARICWAY STATION 41+75 150.0 18 114.6 126.5 9.9 8.5 91 604 N 08/12/96 SF ARMADA PARKIIAY STATION 41+50 147.0 1 l11.5 124.0 6. 1 8.5 90 605 N 08/12/96 CF ARMADA PARK\IAY STATION 42+210 146.5 18 114.0 126.5 8.6 8.5 90 606 N 08/12/96 FG ARMADA PARICWAY STATION 42+00 148.5 18 116.4 126.5 7.0 8.5 92 607 N 08/12/96 FG E. OF LOT 14 147.5 18 121. 7 126.5 8.9 8.5 96 608 N 08/12/96 CF ARMADA PARKIIAY STATION 4i+50 146.0 18 118. 7 126.5 7.4 8.5 94 609 N 08/12/96 SF ARMADA PARKWAY STATION 43+00 144.0 16 112.5 124.0 10.8 10.5 91 610 N 08/12/96 FG ARMADA PARKIIAY STATION 43+20 146.5 18 117.4 126.S 7.6 8.5 93 611 N 08/12/96 CF ARMADA PARKIIAY STATION 45+80 145,0 18 122.7 126.5 11.8 8.5 97 612 N 08/12/96 CF ARMADA PARICWAY STATION 46+50 136.0 18 113.6 126.5 8.5 8.5 90 613 N 08/12/96 FG ARMADA PARKWAY STATION 46+50 137.5 18 119.9 126.5 7.3 8.5 95 614 N 08/12/96 SF ARMADA PARKIIAY STATION 46+75 131.0 16 112.2 124.0 9.0 10.5 90 616 N 08/12/96 FG ARMADA PARKIIAY STATION 47+00 135.0 16 111.4 124.0 8.8 10.5 90 617 N 08/12/96 SF ARMADA PARKWAY STATION 48+75 126.0 16 113.6 124.0 8.9 10.5 92 618 N 08/12/96 CF ARMADA PARICWAY STATION 47+50 130.0 18 123.6 126.5 8.5 8.5 98 619 N 08/12/96 FG ARMADA PARICWAY STATION 47+50 132.0 16 117. 7 124.0 10.5 10.5 95 620 N 08/12/96 CF ARMADA PARICWAY STATION 47+50 129.0 16 115.3 124.0 12.2 10.5 93 621 N 08/12/96 FG ARMADA PARK\IAY STATION 48+00 130.0 16 115.8 124.0 9.7 10.5 93 622 N 08/12/96 FG ARMADA PARICWAY STATION 49+00 122.0 16 115.6 124.0 11.6 1 o. 5 93 623 N 08/12/96 CF ARMADA PARKWAY STATION 49+00 120.0 16 113.7 124.0 12.3 10.5 92 624 N 08/12/96 CF ARMADA PARK\IAY STATION 49+00 120.0 16 118.6 124.0 9.9 10.5 96 625 N 08/12/96 FG ARMADA PMICWAY STATION 49+00 122.0 16 113. 7 124 .o 10.2 10.5 92 625 N 08/12/96 CF ARMADA PARK\IAY STATION 49+80 114.0 16 111.3 124.0 10.0 10.5 90 626 N 08/12/96 fG ARMADA PARICWAY STATION 50+10 114.5 16 120.0 124.0 10.2 10.5 97 627 N 08/12/96 CF ARMADA PARICWAY STATION 52+00 96.5 16 117.8 124.0 11.2 10.5 95 628 N 08/12/96 CF ARMADA PARICWAY STATIOM 52+50 93.0 16 112.4 124.0 10.3 10.5 91 629 N 08/12/96 CF ARMADA PARKIIAY STATION 53+20 90.0 16 118.2 124.0 10.9 10.5 95 630 N 08/12/96 FG ARMADA PARICWAY ST A Tl ON 53+00 92.0 16 114. 5 124.0 10.7 10.5 92 63\ N 08/12/96 FG ARMADA PARKWAY STATION 53+25 90.0 16 '13.9 124.0 14.0 10.5 92 632 N 08/12/96 CF ARMADA PARK\IAY STATIOM 44+40 141.5 5 119.3 129.0 8.9 10.0 92 633 N 08/12/96 CF ARMADA PARKWAY STATION 44+70 140.0 9 121.1 130.0 8.8 10.0 93 634 N 08/12/96 CF ARMADA PARK\IAY STATION 45+70 139.0 9 118.7 130.0 10.1 10.0 91 635 N 08/13/96 FG ARMADA PARICWAY STATION 44+70 143.0 16 1\6.2 124.0 9.0 10.5 94 !>36 N 08/13/96 CF ARMADA P,t.RK\IAY STATION 10+00 157 .o 16 114. 1 124.0 11.8 1 O. 5 92 637 N 08/13/96 CF ARMADA PARKWAY STATION 9+90 155.0 15 114.4 122.5 15.6 12.0 93 638 N 08/13/96 CF ARMADA PARICWAY STATION 9+00 156.0 16 119.8 124.0 13.7 10.5 97 639 N 08/13/96 Cf ARMADA PARICWAY STATIOH 8•60 156.0 16 117.3 124.0 14.7 10.5 95 640 N 08/13/96 CF ARMADA PARICWAY STATION 8+60 158.0 5 127.9 129.0 9.8 10.0 99 641 N 08/13/96 CF ARMADA PARK\IA Y STATION 8+90 158.0 16 122.4 124.0 13.5 10.5 99 642 N 08/13/96 CF LEGO DRIVE STATION 8+40 155.0 9 119.8 130.0 12.0 10.0 92 643 N 08/13/96 CF LEGO DRIVE STATION 8+50 156.5 9 118. 7 130.0 , 1.3 10.0 91 644 N 08/13/96 CF LEGO DRIVE STATION 8+00 158.0 9 117.5 130.0 8.5 10.0 90 645 N 08/13/96 CF LEGO DRIVE ST/\T!ON 9+50 156.0 9 117. 7 130.0 8.5 10.0 91 646 N 08/13/96 CF LEGO DRIVE STAT ION 9+70 157 .5 9 116.4 130.0 9.3 10.0 90 647 N 08/13/96 SF LEGO DRIVE STATION 8+90 154.0 16 111. 2 124.0 9.5 10.5 90 648 II 08/13/96 SF LEGO DRIVE STATION 9+60 154.0 16 112.2 124.0 10.7 10.5 90 649 N 08/14/96 SF S.W. OF LOT 18 155.0 9 117. 1 130.0 8.2 10.0 90 - - - - -- - -- - - -- -- -- --02/12/97 Page No. 15 SUMMARY OF FIELO DENSITY TESTS f>ROJECT NUMBER: 04·930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ············LOCATION·············· TEST SOIL ORY DENSITY(pcf) MOISTURE(%) RELCX) REMARKS NUMBER HETH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT COf4P -----•-"'· ·-·----------------------------·----------------·-----.. -.... ---.. -. ------------------·--650 N 08/14/96 SF S.\J, OF LOT 18 160.0 9 118.0 130.0 8.0 10.0 91 651 " 08/14/96 SF S,\J. OF LOT 18 149,0 16 112.4 124.0 10.0 10.5 91 652 N 08/14/96 SF N.\J. OF LOT 18 170.0 16 114.0 124.0 9.6 10.5 92 653 " 08/14/96 SF N .\I. OF LOT 18 163.0 16 111 .4 124.0 8.9 10.5 90 654 N 08/14/96 SF N.W. OF LOT 18 150.0 1 112.5 124.0 8. 1 8.5 91 655 N 08/15/96 CF E. OF LOT 10 167.0 115 114.5 126.5 11.8 8.5 91 656 N 08/15/96 CF S, OF LOT 10 162.0 17 106.4 116.0 6.9 8.0 92 657 N 08/15/96 CF S. OF LOT 10 158.0 1 111.9 124.0 7.7 8.5 90 658 N 08/15/96 CF CENTER OF LOT 10 159.0 16 111.8 124.0 10.1 10.5 90 659 N 08/15/96 SF S. OF LOT 8 162.0 18 114.3 126.5 7.4 8.5 90 660 N 08/15/96 SF S. OF LOT 8 158.0 16 112. 7 124.0 9.0 10.5 91 661 N 08/15/96 SF s.e. OF LOT 8 154.0 16 112.2 124.0 10.6 10.5 90 662 N 08/15/96 CF ARMADA PARIC\JAY STATION 43+20 144.0 18 118.5 126.5 7.3 8.5 94 663 N 08/15/96 CF ARMADA PARKWAY STATION 43+80 142.0 18 120.8 126.5 7.0 8.5 95 665 N 08/15/96 CF LEO DRIVE STATION 5+10 158.0 9 116.6 130.0 8.2 10.0 90 665 N 08/15/96 CF LEGO DRIVE STATION 6+00 156.5 17 105.9 116.0 6.9 8.0 91 666 N 08/15/96 CF W. OF LEGO DRIVE STATION 6+50 157.0 4 120. 1 133.0 11. 4 9.0 90 667 N 08/16/96 SF ARMADA PARKWAY STATION 24+50 154.0 17 104.7 116.0 7.8 8.0 90 668 N 08/16/96 SF ARAAOA PARIC\JAY STATION 25+40 150.0 17 105.3 116,0 7. 1 8.0 91 669 N 09/27/96 CF N. OF LOT 11 157.0 20 114.3 127.0 7.0 9.0 90 670 N 09/27/96 CF N.E. OF LOT 11 162.0 20 120.3 127.0 8.9 9.0 95 671 N 09/27/96 CF N.E. OF LO 10 169.0 20 114.2 127.0 13.7 9.0 90 672 N 09/27/96 CF N. OF LOT 10 161.0 20 125.0 127.0 '1.3 9.0 98 673 N 09/30/96 CF S. OF LOT 10 155.0 20 117.9 127 .o 9. 1 9.0 93 674 N 09/30/96 CF S, OF LOT 10 163.0 20 123.1 127.0 8.8 9.0 97 675 N 09/30/96 CF CENTER OF LOT 10 163.0 20 122. 1 127.0 11 .4 9.0 96 676 N 09/30/96 CF N.E. OF LOT 10 166.0 20 118.8 127 .0 12.5 9.0 94 6n N 09/30/96 CF S.E. OF LOT 9 170.0 20 125.4 127.0 9.1 9.0 99 678 " 09/30/96 CF S. OF LOT 9 163.0 4 126.2 133.0 , 0. 1 9,0 95 679 II 10/01/96 Cf N.E. OF LOT 10 172.0 4 123.2 133.0 8.2 9.0 93 680 N 10/01/96 Cf N.E. OF LOT 10 173.0 20 114.4 127.0 12.0 9.0 90 681 N 10/01/96 CF S.E OF LOT 10 167.0 20 115.9 127.0 11.8 9,0 91 682 N 10/01/96 CF S. OF LOT 10 165.0 20 114.5 127.0 11.4 9.0 90 683 N 10/01/96 CF N. OF LOT 10 163.0 14 117. 7 130.5 11. 9 9.5 90 684 N 10/01/96 CF s. OF LOT 10 163.0 16 111.7 124.0 11.5 10.5 90 685 N 10/01/96 CF N. OF LOT 11 162.0 15 110.0 122.5 14. 1 12.0 90 686 II 10/02/96 CF N. Of LOT 11 164.0 14 118.0 130,5 9.0 9.5 90 687 N 10/02/96 Cf CEHTER OF LOT 10 164.0 15 116.7 122.5 13.7 12.0 95 688 N 10/02/96 CF N. OF LOT 10 162.0 4 120.9 133.0 8.9 9.0 91 689 N 10/03/96 CF S. OF LOT 9 169.0 20 115 .2 127 .o 12. 1 9.0 91 690 N 10/03/96 Cf S.E. OF LOT 10 165.0 15 114.5 122.5 14.3 12.0 93 691 II 10/03/96 CF S, Of LOT 10 165.0 20 117.8 127.0 12.9 9.0 93 692 N 10/04/96 Cf CENTER Of LOT 10 170.0 16 111.8 124.0 14.6 10.5 90 693 N 10/04/96 Cf N. OF LOT 10 168.0 20 114.4 127.0 14.4 9.0 90 694 H 10/04/96 CF N. OF LOT 11 170.0 15 111.8 122.5 15.6 12.0 91 695 N 10/04/96 CF S.E. OF LOT 2 STATION 0+70 66.0 20 114.6 127.0 8.4 9.0 90 696 H 10/04/96 CF S.E. OF LOT 2 STATION 1+20 68.0 4 119. 7 133.0 8.8 9.0 90 - --- - - -- - -- - -- - --- -02/12/97 Page No. 16 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489·11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ••.•••••••.. LOCATION ······•······· TEST SOIL DRY DENSITY(pcf) MOISTURE(%) REL(%) REMARl,'.S NUMBER METH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT COMP ..... --·-·-·-----------·-·----------·-----·-·--·--·~----....... -.. -..... -....................... ----·-----· .. ................ 697 N 10/04/96 CF STABILITY FILL ST A Tl ON 2+20 66.0 4 121.0 133.0 7.3 9.0 91 698 N 10/04/96 CF S. OF LOT 2 STATION 0+00 72.0 4 120.9 133.0 9.6 9.0 91 699 H 10/04/96 CF S. OF LOT 2 70.0 4 122.7 133.0 9.2 9.0 92 700 N 10/04/96 CF S. OF LOT 2 68.0 20 1'6.7 127.0 10.7 9.0 92 701 N 10/07/96 CF S. OF LOT 2 153.0 20 121.4 127.0 9.7 9.0 96 702 N 10/07/96 CF S. OF LOT 2 150.0 20 115.9 127.0 9.8 9.0 91 703 N 10/07/96 CF S. OF LOT 2 147.0 20 115.4 127.0 6.1 9.0 91 704 N 10/07/96 CF S. OF LOT 2 148.0 20 124.9 127.0 8.6 9.0 98 705 N 10/07/96 CF E. OF LOT 2 STATION 4+25 64.0 20 118.0 127.0 10. 1 9.0 93 706 N 10/07/96 CF E. OF LOT 2 STATION 4+40 63.5 14 118.3 130.5 9.6 9.5 91 707 N 10/07/96 CF E. OF LOT 2 STATION 3+00 63.0 20 114.4 127.0 10.0 9.0 90 708 N 10/07/96 CF e. OF LOT 2 STATION 3+25 64.0 4 122.5 133.0 8.7 9.0 92 709 N 10/07/96 CF STABILITY FILL E. OF LOT 2 64.0 4 126.8 133.0 8.0 9.0 95 710 N 10/07/96 CF s.e. OF LOT 2 STATION 0+40 67.0 4 119. 7 133.0 11.6 9.0 90 711 N 10/07/96 CF s.e. OF LOT 2 STATION 1+00 70.0 4 120.9 133.0 8.6 9.0 91 712 N 10/07/96 CF s.e. OF LOT 2 STATION 0+80 72.0 4 119.6 133.0 8.3 9.0 90 713 N 10/07/96 CF STABILITY FILL E. OF LOT 2 67.0 4 120. 1 133.0 8.5 9.0 90 714 N 10/07/96 CF STABILITY FILL E. OF LOT 2 64.0 4 127.6 133.0 12.1 9.0 96 715 II 10/08/96 CF STABILITY FILL E. OF LOT 2 73.0 4 123. 1 133.0 7.8 9.0 93 716 N 10/08/96 CF STABILITY FILL E. OF LOT 2 75.0 4 121.0 133.0 7.7 9.0 91 717 N 10/08/96 CF STABILITY FILL E. OF LOT 2 68.0 20 113.8 127.0 10.2 9.0 90 718 N 10/08/96 CF STABILITY FILL E. OF LOT 2 70.0 20 114.6 127.0 7.5 9.0 90 719 N 10/19/96 CF E. OF LOT 2 STATION 6+30 63.5 4 122.2 133.0 8. 1 9.0 92 no N 10/19/96 CF E. OF LOT 2 STATION 6+60 65.0 20 119.2 127.0 8.8 9.0 94 721 N 10/19/96 CF E. OF LOT 2 STATION 8+00 64.0 16 111.5 124.0 13.9 10.5 90 722 N 10/19/96 Cf E. OF LOT 2 ST A Tl ON 9+40 63.0 16 112.4 124.0 10. 1 10.5 91 723 II 10/19/96 CF E. OF LOT 2 STATION 10+50 66.0 20 114.6 127.0 7.8 9.0 90 724 N 10/21/96 CF E. OF LOT 2 STATION 8+00 65.0 4 123.7 133.0 8. 1 9.0 93 725 N 10/21/96 CF E. OF LOT 2 STATION 7+00 67.0 20 117.9 127.0 10.1 9.0 93 726 II 10/21/96 CF E. OF LOT 2 STATION 6+50 69.0 20 119.6 127.0 10.1 9.0 94 727 N 10/21/96 CF E. OF LOT 2 STATION 6+00 75.0 4 127.4 133.0 8. 1 9.0 96 728 N 10/21/96 CF E. OF LOT 2 STATION 6+50 77.0 4 121.1 133.0 9.3 9.0 91 729 N 10/21/96 CF E. OF LOT 2 STATION 7+50 74.5 4 121.8 133.0 7.7 9.0 92 730 II 10/21/96 CF E. OF LOT 2 STATION 8+00 n.o 4 123. 7 133.0 8.2 9.0 93 731 N 10/22/96 CF E. OF LOT 2 STATION 6+25 80.0 20 123.0 127.0 9.8 9.0 97 732 N 10/22/96 CF E. OF LOT 2 STATION 8+00 82.5 20 120.9 127.0 9.4 9.0 95 733 N 10/22/96 CF E. OF LOT 2 STATION 9+00 82.0 4 120.2 133.0 10.5 9.0 90 734 N 10/22/96 CF E. OF LOT 2 STATION 10+00 77.0 4 121.8 133.0 9.9 9.0 92 735 N 10/22/96 CF E. OF LOT 2 STATION 10+40 75.0 20 116. 1 127.0 12.6 9.0 91 736 N 10/22/96 CF E. OF LOT 2 STATION 11+00 71.0 20 122.3 127.0 10.4 9.0 96 737 N 10/23/96 CF E. OF LOT 2 STATION 10+30 78.0 4 119.7 133.0 7.4 9.0 90 738 II 10/23/96 CF E. OF LOT 2 STATION 10+20 80.0 4 120.9 133.0 7.5 9.0 91 739 H 10/23/96 CF E. OF LOT 2 STATION 11+00 74.0 20 117.1 127.0 7.0 9.0 92 740 H 10/23/96 CF E. OF LOT 2 STATION 10+80 76.0 20 116.0 127.0 6.9 9.0 91 741 H 10/23/96 CF E. OF LOT 2 STATION 11+90 68.0 20 114. 7 127.0 6.4 9.0 90 742 N 10/23/96 Cf E. OF LOT 2 STATION 11+70 70.0 20 116.2 127.0 6.9 9.0 91 743 N 10/23/96 CF E. OF LOT 2 STATION 12+10 67.0 14 120.2 130.5 10.8 9.5 92 - - - -- - -- --- - --- -- --02/12/97 Page No. 17 SUM!1ARV OF FIELD DENSITl TESTS PROJECT NUMBER: 04-930489-11 NAME: CARLSBAD RANCH TEST TEST TEST TEST ------------LOCATION --------------TEST SOIL DRY DENSITY(pcf) MOISTURE CX) REL(%) REMARKS NUMBER HETH DATE OF ELEV(ft) TYPE FJELD MAX FIELD OPT COMP ---.............. ........ ---.... ··--·······--------·-·-····-4••····-------·-·-..... -.. -.. -... ·-······-·---............. -...... 744 N 10/23/96 CF E, Of LOT 2 STATIOM 12+40 64.5 20 117.3 127_0 8.2 9.0 92 745 N 10/24/96 CF E. OF LOT 2 STAT ION 12+00 75.0 20 116.8 127.0 9.4 9.0 92 746 N 10/24/96 CF E. OF LOT 2 STATION 12•40 70.0 20 115.8 127 .0 9.6 9.0 91 747 N 10/24/96 CF E. OF LOT 2 STATIOM 13+00 65.0 20 117.1 127 .0 10_3 9.0 92 748 N 10/24/96 CF E. OF LOT 2 STATION 12+60 78.0 20 115.6 127.0 13.2 9.0 91 749 N 10/24/96 CF STABILITY FILL STATION 12+50 80.0 20 116.6 127.0 11. 1 9.0 92 750 N 10/24/96 CF STABILITY FILL STATIOM 13+20 68.0 4 121.4 133.0 9.5 9.0 91 751 N 10/24/96 CF STABILITY FILL STATION 13+40 65.0 20 115.4 127.0 8.0 9.0 91 752 N 10/25/96 CF STABILITY FILL STATION 13+00 70.0 20 118.4 127 .0 9.1 9.0 93 753 N 10/25/96 CF STABIL !TY FIL! ST A Tl ON 13+50 68.0 20 116.6 127.0 8.6 9.0 92 754 N 10/25/96 CF STABILITY FILL STATION 12+75 73.0 4 120.2 133.0 8.4 9.0 90 755 N 10/25/96 CF STABILITY FILL STATION 14+00 66.0 4 123.6 133.0 9.2 9.0 93 756 N 10/25/96 CF STABILITY FILL STATIOM 13+75 70.0 20 114.7 127.0 13.0 9.0 90 757 N 10/28/96 CF S. 1/2 OF LOT 2 STATION 4+00 64_5 21 113.5 122.5 13.8 12.0 93 758 N 10/28/96 Cf S. 1/2 OF LOT 2 STATION 3+80 66.0 21 113.5 122.5 15.0 12.0 93 759 N 10/28/96 CF S. 1/2 OF LOT 2 STATION 4+00 64_5 20 116.8 127 .0 11.8 9.0 92 760 N 10/28/96 CF S. 1/2 OF LOT 2 STATION 3+90 66.0 20 118.3 127.0 12.4 9.0 93 761 N 10/28/96 CF S, OF LOT 2 STATION 2+90 65.0 20 115.0 127.0 14.8 9.0 91 762 N 10/28/96 CF S. OF LOT 2 ST A Tl ON 3+80 66.0 20 115.8 127.0 11.2 9.0 91 763 N 10/28/96 CF S. OF LOT 2 STATION 1+75 67.0 20 115.2 127.0 12.8 9.0 91 764 N 10/28/96 CF S, OF LOT 2 STATION 2+10 65.0 21 111.8 122.5 15.5 12.0 91 765 N 10/28/96 CF TRUCK ACCESS DRIVE S. Of LOT 2 73.0 21 111.8 122.5 13.1 12.0 91 766 N 10/28/96 CF TRUCK ACCESS DRIVE S. OF LOT 2 75.0 20 113.9 127.0 8. 1 9.0 90 767 N 10/28/96 CF TRUCK ACCESS DRIVE S. OF LOT 2 73.0 20 116.4 127.0 10.3 9.0 92 768 N 10/28/96 CF TRUCK ACCESS DRIVE S. OF LOT 2 75.0 20 114.7 127.0 9.0 9.0 90 769 N 10/29/96 FG S. 1/2 OF LOT 2 ST A Tl ON 0+50 70.0 4 122.5 133.0 8.0 9.0 92 770 N 10/29/96 FG S.W. OF LOT 2 STATION 0+60 70.0 20 113.7 127.0 11.2 9.0 90 771 N 10/29/96 FG S. OF LOT 2 STATION 0+15 72.5 20 117.4 127.0 8.6 9.0 92 772 N 10/29/96 FG TRUCK ACCESS DRIVE S. OF LOT 2 76.0 21 118.5 122.5 12.1 12.0 97 m N 10/29/96 FG S.11. OF LOT 2 STATION 2+95 63.0 20 118.8 127.0 9.5 9.0 94 774 N 10/29/96 FG S.W. OF LOT 2 STATION 3+60 65.0 20 122.0 127.0 8.4 9.0 96 775 N 10/29/96 FG CENTER OF LOT 2 STATION 7+75 63.5 21 117.4 122.5 11.3 12.0 96 776 N 10/29/96 FG CENTER OF LOT 2 STATION 7+05 65.0 21 115.7 122.5 12.9 12.0 94 m N 10/29/96 FG S. 1/2 OF LOT 2 STATION 6+00 63.0 20 121. 1 127.0 9.6 9.0 95 778 N 10/29/96 FG S. 1/2 OF LOT 2 STATION 5+10 65.0 20 115.3 127.0 8.9 9.0 91 779 N 10/29/96 Cf S.W. OF LOT 2 STATION 5+40 64.0 21 116.1 122.5 11.2 12.0 95 780 N 10/29/96 CF S.W. OF LOT 2 STATION 5+00 66.0 20 119.5 127.0 8.4 9.0 94 781 N 10/29/96 CF S.11. OF LOT 2 STATION 4+20 63.0 20 117.6 127.0 12.9 9.0 93 782 N 10/29/96 CF S.W. OF LOT 2 STATIOM 5+00 65.0 20 118. 1 127.0 8.2 9.0 93 783 N 10/29/96 Cf S.W. OF LOT 2 STATION 4+25 62.0 21 110.1 122.5 14.5 12.0 90 784 N 10/29/96 CF S.11. OF LOT 2 STATION 3+25 62.0 21 113.2 122.5 11.6 12.0 92 785 N 10/30/96 CF E. OF LOT 2 STATION 15+00 80.0 20 116. 1 127.0 7.6 9.0 91 786 N 10/30/96 Cf E. OF LOT 2 STATION 15+25 77.0 20 116.8 127.0 7 .9 9.0 92 787 N 10/30/96 CF E. OF LOT 2 STATION 16+00 71.0 20 117 .0 127.0 7.1 9.0 92 788 N 10/30/96 CF E. OF LOT 2 STATION 16+20 68.0 21 113. 1 122.5 10.9 12.0 92 789 N 10/30/96 CF E. OF LOT 2 STATION 14+70 82.0 20 114.2 127.0 8. 1 9.0 90 790 N 10/30/96 Cf E. OF LOT 2 STATIOM 16+40 65.0 21 111 .4 122.5 10. 1 12.0 91 ---- - - ---- -- - -- -- --02/12/97 Page No. 18 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489-11 NAME: CARLSBAD RANCH TEST TEST TEST TEST --------·-·-LOCATION ··-··-·-·····-TEST SOIL DRY DENSITY(pcf) MOISTURE(%) RELCX) REMARKS NUNBER METH DATE Of ELEV(ft) TYPE FIELD MAX FIELD OPT COMP -........... -... -. .. ----..... ---·-----··---·--·------------------. ---.......... --...... ---·------~-·--·---· .... ----....... -791 N 10/30/96 Cf N.IJ. OF LOT 10 151.0 4 120.9 133.0 8.8 9.0 91 792 N 10/30/96 CF N.IJ. OF LOT 10 153.0 21 110.6 122.5 13.3 12.0 90 793 N 10/30/96 CF S.IJ, OF LOT 10 153.0 20 118.8 127.0 8.5 9.0 94 794 N 10/30/96 CF S.IJ. OF LOT 10 149.0 20 115.7 127.0 8.7 9.0 91 795 N 10/30/96 CF N.W. OF LOT 10 152.0 20 114.2 127.0 11.9 9.0 90 796 N 10/30/96 CF N.IJ, OF LOT 10 157.0 4 120.0 133.0 11.0 9.0 90 797 N 10/30/96 CF IJ. OF LOT 10 155.0 20 114.9 127 .0 7.8 9.0 90 798 N 10/30/96 CF IJ. OF LOT 10 154.0 20 116.2 127.0 8.9 9.0 91 799 N 10/30/96 CF N.IJ. OF LOT 11 148,0 20 114.2 127.0 9.4 9.0 90 800 N 10/30/96 CF S.IJ. OF LOT 10 150.0 20 115.6 127.0 7,8 9.0 91 801 N 11/02/96 CF S.IJ. OF LOT 10 152.0 20 123.0 127.0 10.6 9.0 97 802 N 11/02/96 CF S.IJ. OF LOT 10 154.0 20 120.1 127.0 9.7 9.0 95 803 N 11/02/96 CF IJ. OF LOT 10 155.0 20 120. 1 127,0 8.7 9.0 95 804 N 11/02/96 CF N.IJ. OF LOT 10 157 .0 21 116.9 122.5 13.4 12.0 95 805 N 11/02/96 CF CENTER Of LOT 2 STATION 8+50 64.5 20 120. 7 127.0 9.3 9,0 95 806 N 11/02/96 CF S. 1/2 OF LOT 2 STATION 7+40 66.5 4 123. 1 133.0 , 1. 1 9.0 93 607 N 11/02/96 CF N. 1/2 OF LOT 2 STATION 9+90 64.5 4 128.5 133.0 8.6 9.0 97 808 N 11/02/96 CF N. 1/2 OF LOT 2 STATION 10+10 66.0 20 119.0 127.0 8.0 9.0 94 809 N 11/02/96 CF N. 1/2 OF LOT 2 STATION 10+30 64.5 20 117 .2 127.0 8.4 9.0 92 810 N 11/02/96 Cf N. 1/2 OF LOT 2 STATION 11+05 66.0 20 114.5 127.0 7.5 9.0 90 811 N 11/02/96 CF N. 1/2 OF LOT 2 STATION 11+10 64.0 4 123.6 133.0 9. 1 9.0 93 812 N 11/02/96 CF N. 1/2 OF LOT 2 STATION 10+25 65.0 4 120.0 133.0 9.1 9.0 90 813 N 11/02/96 CF N. 1/2 OF LOT 2 STAITON 9+40 66.0 20 116.0 127.0 8.4 9.0 91 814 M 11/02/96 CF N.W. OF LOT 3 STATION 11+70 60.U 20 123.8 127 .o 8.6 9.0 97 815 N 11/02/96 CF W. OF LOT 3 STATION 10+05 61.0 20 118.2 127.0 7.8 9.0 93 816 N 11/02/96 CF W. OF LOT 3 STATION 11+00 58.0 4 119,8 133.0 9.8 9.0 90 817 N 11/02/96 SF E. Of LOT 2 STATION 3+00 72.0 20 114.6 127.0 7.0 9.0 90 818 N 11/02/96 SF E. OF LOT 2 STATION 5+70 70.0 20 119.0 127,0 9.8 9.0 94 819 )I 11/02/96 SF E. OF LOT 2 STATION 6+00 76.0 20 119.5 127.0 9.9 9.0 94 820 N 11/02/96 SF E. OF LOT 2 STATION 9+75 71.0 4 126.3 133.0 8.5 9.0 95 821 N 11/02/96 Sf E. Of LOT 2 STATION 10+00 80.0 21 111. 7 122.5 10. 1 12.0 91 822 N 11/02/96 SF E. OF LOT 2 STATION 15+20 86.0 21 115.9 122.5 12.5 12.0 95 823 N 11/02/96 SF E. OF LOT 2 STATION 15+00 80.0 20 116.3 127.0 7.1 9.0 92 824 ti 11/02/96 CF E. OF LOT 2 STATION 15+00 88.0 20 120.7 127.0 9.0 9.0 95 825 N 11/02/96 CF E. OF LOT 2 STATION 17+00 89.5 4 122.1 133.0 9.6 9.0 92 826 II 11/02/96 SF E. OF LOT 2 STATION 12+80 92.0 20 117.5 127.0 7.6 9.0 93 827 N 11/04/95 CF N.W. OF LOT 11 153.0 20 119.6 127.0 10.6 9.0 94 828 N 11/04/95 Cf S.W. OF LOT 10 155.0 4 124.2 133.0 8. 1 9.0 93 829 N 11/04/96 CF N.W. OF LOT 10 160.0 4 122.4 133.0 11.2 9.0 92 830 N 11/04/96 Cf N.W. OF LOT 10 162.0 20 116. 7 127.0 10.0 9.0 92 831 N 11/04/96 FG CENTER OF LOT 3 STATION 11+20 66.8 20 121.7 127.0 9.2 9.0 96 832 N 11/04/96 FG CENTER OF LOT 3 STATION 11+00 66.8 20 119.3 127.0 8.4 9.0 94 833 N 11/04/96 FG S. 1/2 OF LOT 3 STATION 9+80 66.8 4 124. 1 133.0 8.5 9.0 93 834 N 11/04/96 FG S. 1/2 OF LOT 3 STATION 8+60 66.8 4 124.3 133.0 11.0 9.0 93 835 N 11/04/96 FG S. 1/2 OF LOT 3 STATION 6+10 66.8 20 115.4 127.0 8.3 9.0 91 836 N 11/04/96 FG S. 1/2 OF LOT 3 STATION 6+80 66.8 4 122.4 133.0 10.6 9.0 92 837 N 11/05/96 CF N.W. OF LOT 10 162.0 20, 117 .4 127.0 8.3 9.0 92 - - - -- - - -- - - - ------ -02/12/97 Page No. 19 SUMMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04·930489-11 NAME: CARLSBAD RANCK TEST TEST TEST TEST -·--·-------LOCATION-·-·····-····· TEST SOIL ORY OENSITY(pcf) MOISTURE();) RELCX) REMARKS HIMBER METH DATE OF ELEV(ft) TYPE FJELD MAX FIELD OPT CONP --.. -... --·------------·-·-·----------------------··---..... ------.. ----------·-...................... .. .... -..... --.. 838 N 11/05/96 CF t,1.IJ. OF LOT 10 164.0 20 116.9 127.0 8.8 9.0 92 839 N 11/05/96 CF N.U. OF LOT 10 166.0 21 112.5 122.5 10.0 12.0 92 840 N 11/05/96 CF N.U. OF LOT 10 157.0 4 122.4 133.0 7.8 9.0 92 841 H 11/05/96 CF N.U. OF LOT 10 159.0 4 119.3 133.0 9.7 9.0 90 842 N 11/05/96 FG S. 1/2 OF LOT 3 STATION 6+80 66.8 4 122.4 133.0 8.6 9.0 92 843 N 11/05/96 FG S. OF 1/2 LOT 2 STATION 6+00 66.8 4 128.2 133.0 7.8 9.0 96 844 N 11/05/96 FG S. OF 1/2 LOT 2 STATION 5+25 66.8 20 123.0 127.0 7.9 9.0 97 845 N 11/05/96 FG S. OF 1/2 LOT 2 STATION 6+50 66.8 20 121 .3 127.0 7.8 9.0 96 846 N 11/05/96 FG S. OF 1/2 LOT 3 STATION 7+95 66.8 4 120.8 133.0 8.2 9.0 91 847 N 11/05/96 FG CENT.ER OF LOT 3 STU!ON 9+95 66.8 20 124.4 127.0 8.1 9.0 98 848 N 11/05/96 FG N. 1/2 OF LOT 3 STATION 11+00 66.8 20 116.7 127.0 7.7 9.0 92 849 N 11/05/96 FG N. 1/2 OF LOT 3 STATION 13+90 668.0 4 121.9 133.0 9.0 9.0 92 850 N 11/05/96 FG N, 1/2 OF LOT 3 STATION 13+00 0.0 4 125. 1 133.0 8.8 9.0 94 851 N 11/05/96 FG N. 1/2 OF LOT 3 STATION 12+30 0.0 4 124.1 133.0 7.5 9.0 93 852 N 11/05/96 CF N .IJ. OF LOT 10 163.0 21 117.6 122.5 10.0 12.0 96 853 N 11/05/96 CF N.U. OF LOT 10 165.0 21 111.3 122.5 12.5 12.0 91 854 N 11/05/96 CF U. OF LOT 10 160.0 21 118.7 122.5 10.5 12.0 97 855 N 11/05/96 CF S.U. OF LOT 10 160.0 4 121.2 133.0 7.8 9.0 91 856 N 11/06/96 FG N. 1/2 OF LOT 2 STATION 13+50 66.8 20 116.1 127.0 8.5 9.0 91 857 N 11/06/96 FG N. 1 /2 OF LOT 2 STATION 13+00 66.8 4 124.9 133.0 8.4 9.0 94 858 N 11/06/96 FG N. 1/2 OF LOT 2 STATION 11+60 66.8 20 117.2 127.0 7.9 9.0 92 859 N 11/06/96 FG N. 1/2 OF LOT 2 STATION 11+60 668.0 20 117.2 127.0 7.5 9.0 92 860 N 11/06/96 FG N. 1/2 OF LOT 2 STATION 10+00 668.0 20 115.6 127.0 7.7 9.0 91 861 N 11/06/96 FG N. 1/2 OF LOT 2 STATION 10+15 668.0 20 119.4 127.0 8.0 9.0 94 862 N 11/06/96 FG N. 1/2 OF LOT 2 STATION 9+20 668.0 4 119.3 133.0 8.2 9.0 90 863 N 11/06/96 FG CENTER OF LOT 2 ST A Tl ON 8+60 668.0 4 123.S 133.0 7.9 9.0 93 864 N 11/06/96 FG CENTER OF LOT 2 STATION &+00 668.0 20 115.2 127.0 7.8 9.0 91 865 N 11/06/96 FG S. 1/2 OF LOT 2 STATION 7+00 668.0 22 114.7 118.5 8.3 11.0 97 866 N 11/07/96 FG N.U. OF LOT 10 170.0 4 128.2 133.0 8.4 9.0 96 867 N 11/07/96 FG N .\I. OF LOT 10 167.0 20 123.1 127.0 10.5 9.0 97 868 N 11/07/96 FG \I. OF LOT 10 168.0 20 117 .2 127.0 12.9 9.0 92 869 N 11/07/96 CF S.ll. OF LOT 10 163.0 14 120.3 130.5 8.4 9.5 92 870 N 11/07/96 CF S.ll. OF LOT 10 165.0 14 117.2 130.5 8.6 9.5 90 871 N 11/07/96 CF S.IJ. OF LOT 10 167.0 14 120.3 130.5 9.6 9.5 92 872 H 11/07/96 FG S.U. OF LOT 2 STATION 2+00 65.0 20 114.2 127.0 7.6 9.0 90 873 N 11/07 /96 FG S. 1/2 OF LOT 2 STATION 1+50 66.0 20 117.2 127.0 10.0 9,0 92 874 N 11/07 /96 FG S. 1/2 OF LOT 2 STATION 1+50 67.5 20 114.0 127.0 9.6 9.0 90 875 N 11/07/96 FG S. 1/2 OF LOT 2 STATION 2+40 65.0 4 127.8 133.0 8.0 9.0 96 876 N 11/07 /96 FG S, 1/2 OF LOT 2 STATION 2+90 66.0 20 120.4 127.0 9.7 9.0 95 an t,I 11/08/96 FG U. OF LOT 10 172.0 4 122.4 133.0 9.5 9.0 92 878 N 11/08/96 FG \I. OF LOT 10 174.0 4 121.0 133.0 8.2 9.0 91 879 N 11/08/96 CF S.\I. OF LOT 10 171.0 4 121.4 133.0 7.7 9.0 91 880 N 11/08/96 CF N,ll. OF LOT 11 167.0 14 121.1 130.5 10.4 9.5 93 881 N 11/08/96 CF N.\I. OF LOT 10 172.0 14 117 .8 130.5 9.8 9.5 90 882 N 11/12/96 FG S. 1/2 OF LOT 2 ST A Tl ON 3+60 66.8 20 116.9 127.0 11. 7 9.0 92 883 N 11/12/96 FG S. 1/2 OF LOT 2 STATION 4+00 66.8 20 119.8 127.0 11.4 9.0 94 884 N 11/12/96 FG S. 1/2 OF LOT 2 STATION 3+80 66.8 20 115.7 127.0 11.2 9.0 91 - -- - - --- -- - - -- --- --02/12/97 Page No. 20 SUHMARY OF FIELD DENSITY TESTS PROJECT NUMBER: 04-930489-U NAHE: CARLSBAD RAHCH TEST TEST TEST TEST ••••.•.....• LOCATION·············· TEST SOIL ORY OENSITY(pcf) MOISTURE(X) REL(~) REMARKS NUMBER METH DATE OF ELEV(ft) TYPE FIELD MAX FIELD OPT COMP -.... --... ----·--··--------···--··----·--·------------·-. -----... --.. .... -....... ---. ----..... -. ---. ----... -·. -.. 885 N 11/12/96 FG s. 1/2 OF LOT 2 STATION 5+80 66.8 21 115.9 122.5 10.4 12.0 95 886 N 11/12/96 FG s. 1/2 OF LOT 2 ST'-T ION 4+95 66.8 21 120.5 122.5 9.7 12.0 98 887 N 11/12/96 FG s. 1/2 OF LOT 2 STATION 4+95 66.8 20 119.2 127.0 8.7 9.0 94 888 N 11/12/96 FG s. 1/2 OF LOT 2 STATION 1+00 70.0 4 120.0 133.0 9.1 9.0 90 889 N 11/12/96 FG s. 1/2 OF LOT 2 STATION 1+00 72.0 4 122.2 133.0 8.0 9.0 92 890 N 11 /12/96 FG s. 1/2 OF LOT 2 STATlo+I 1+00 69.0 20 117.2 127.0 8.7 9.0 92 891 H 11/12/96 FG s. 1/2 OF LOT 2 STATION 1+90 66.5 20 123.3 127.0 7.8 9.0 97 892 N 11/12/96 FG s. 1/2 OF LOT 2 STATION 3+00 67.0 20 114 .3 127.0 7.3 9.0 90 893 N 11/12/96 FG s. 1/2 OF LOT 2 STATION 4+00 63.0 20 120. 1 127.0 7.6 9.0 95 894 N 11 /12/96 FG s. 1/2 OF LOT 2 STATION 5+10 64.0 20 121. 1 127.0 9.3 9.0 95 895 N 11/12/96 FG S. 1/2 OF LOT 2 STATION 4+20 63.0 4 121.6 133.0 7.9 9.0 91 896 N 11/13/96 CF N. OF LOT 10 162.0 s 116.6 129.0 10.4 10.0 90 897 N 11/13/96 CF N. OF LOT 10 164.0 s 118.2 129.0 8.2 10.0 92 898 N 11/13/96 CF CENTER OF LOT 10 170.0 4 125.5 133.0 10.0 9.0 94 899 N 11/13/96 CF CENTER OF LOT 10 172.0 4 129.4 133.0 10.7 9.0 97 900 H 11/13/96 CF S.E. OF LOT 10 174.0 4 125. 7 133.0 8.2 9.0 95 901 N 11/14/96 CF FUTURE LEGO DRIVE STATION 23+50 141.5 4 121.3 133.0 9.0 9.0 91 902 N 11/14/96 CF FUTURE LEGO DRIVE STATION 24+00 139.0 4 123.3 133.0 7,6 9.0 93 903 N 11/14/96 CF FUTURE LEGO DRIVE STATION 24+25 142.0 4 125.7 133.0 8.8 9.0 95 904 N 11/14/96 CF FUTURE LEGO DRIVE STATION 22+00 141.0 14 121.5 130.5 10.0 9.5 93 905 N 11/14/96 CF FUTURE LEGO DRIVE STATION 22+40 139.0 14 119.8 130.5 9.3 9.5 92 906 N 11/14/96 CF FUTURE LEGO DRIVE STATION 20+50 138.5 14 118.5 130.5 9.7 9.5 91 907 N 11/14/96 CF FUTURE LEGO DRIVE STATION 20+25 137.0 4 124 .4 133.0 8.5 9.0 94 908 N 11/14/96 CF FUTURE LEGO DRIVE STATION 19+00 136.0 14 118. 1 130.5 9.5 9.5 90 909 N 11/14/96 CF FUTURE LEGO DRIVE STATION 18+50 138.S 14 121.7 130.5 10.3 9.5 93 910 N 11/14/96 CF FUTURE LEGO DRIVE STATION 17+40 135.0 4 125.8 133.0 9.7 9.0 95 911 N 11/14/96 CF FUTURE LEGO DRIVE STATJON 17+00 137.5 14 117. 7 130.5 10.2 9.5 90 912 N 11/14/96 FG S.E. OF LOT 2 STATION 3+00 68.0 4 121. 7 133.0 9.3 9.0 92 913 N 11/14/96 FG S.E. OF LOT 2 STATION 5+00 66.8 4 121.6 133.0 7.7 9.0 91 914 N 11/14/96 FG E. OF LOT 2 STATION 7+00 66.8 20 118.9 127.0 8.9 9.0 94 915 N 11 /14/96 FG E. OF LOT 2 STATION 9+50 66.8 20 114.2 127.0 7.7 9.0 90 916 N 11/14/96 FG N.E. OF LOT 2 STATION 11+50 66.8 20 115.4 127.0 7.8 9.0 91 917 N 11/14/96 FG N.E. OF LOT 2 STATION 13+00 66.8 20 116.6 127.0 8.8 9.0 92 918 N 11 /14/96 CF FUTURE LEGO DRIVE STATION 29+50 143.5 14 119.4 130.5 10.0 9.5 91 919 N 11 /14/96 CF FUTURE LEGO DRIVE STATION 29+75 145.0 14 119. 1 130.5 9.8 9.5 91 920 N 11/14/96 CF FUTURE LEGO DRIVE ST A Tl OH 30+00 147.0 4 124.2 133.0 10.4 9.0 93 921 N 11/14/96 CF FUTURE LEGO DRIVE STATION 29+00 147.5 4 119.6 133.0 9.2 9.0 90 922 N 11/15/96 Cf FUTURE LEGO DRIVE STATION 14+50 137.0 14 118.6 130.5 11.7 9.5 91 923 N 11/15/96 CF FUTURE LEGO DRIVE STATION 15+00 135.0 14 118.9 130.5 10.2 9.5 91 924 N 11/15/96 CF FUTURE LEGO DRIVE STATION 13+30 134.0 20 114.2 127.0 9.7 9.0 90 925 N 02/10/96 FG LOT 14 SCAJINEST 153.5 18 115.9 126.5 9. 1 8.5 92 926 N 02/10/96 FG LOT 14 SOUHWEST 154.0 18 114. 1 126.5 7.8 8.5 90 927 N 02/10/96 FG LOT 14 WEST 156.0 18 116.2 126.5 7.0 8.5 92 928 N 02/10/96 FG LOT 14 WEST 157.0 18 116.5 126.5 7.7 8.5 92 929 N 02/10/96 FG LOT 14 NORTHWEST 158.0 18 115.0 126.5 9.0 8.5 91 930 N 02/10/96 FG LOT 14 NORTHWEST 160.0 17 114.2 116.0 6.7 8.0 98 931 N 02/10/96 FG LOT 14 SCAJTHEAST 153.0 1 115.7 124.0 5.5 8.5 93 - -- - -02/12/97 PROJECT NUMBER: 04·930489-11 NAME: CARLSBAD RANCH TEST TEST Nl/11BER HETH TEST DATE TEST OF 932 N 02/10/96 FG 933 N 02/10/96 FG - - - - - -SU/4MARY OF FIELD DENSITY TESTS --·-·-··----LOCATION -----·-·-·-··-TEST SOIL ELEV(ft) TYPE ------·---·--·-----·---------·--·---·-·-------LOT 14 SOUTHEAST 154.5 1 LOT 14 SOUTHEAST 154.0 18 - - - - - ---Page No. 21 DRY DE~SITY(pct) MOISTURE(%) REL(%) REMARKS FIELD MAX FIELD OPT COMP --·-·····--· -··--··----................. 112.2 124.0 5.3 8.5 90 126.5 126.5 6.1 8.5 100 I I I I I I I I 11 I I I I I I I I I I 4930489-011 APPEND[)( C Laboratory Testing Procedures and Test Results Maximum Density Tests: The maximum dry density and optimum moisture content of typical materials were detennined in accordance with ASTM Test Method Dl557. The results of these tests are presented in the table below. Maximum Dry Optimum Moisture Density Content Sample Number Sample Description (pcf) {%) 1 Orange-brown, silty sand (Terrace) 124.5 8.5 2 Dark brown, silty sand with clay 129.0 10.0 3 Topsoil, mixed with orange-brown silty 135.0 8.0 sand 4 Topsoil, brown silty sand 133.0 9.0 5 Orange-brown silty sand (Terrace) 129.0 10.0 6 Gray, clean sand 11 5.5 9.0 7 Brown. gray clayey sand 109.0 20 8 Brown-gray, oxidized sand, mix of 1,5 & 6 127.0 11.0 9 Red-brown, silty sand 130.0 10.0 10 Gray, silty to clayey sand 128.0 9.0 11 Dark brown clayey sand 125.0 9.5 12 Tan-brown topsoil, Lot 9 127,9 8.5 13 Orange-brown, sand w/clay (Terrace) 131.0 9.0 14 Orang«>-brown sandy siJt (alluvium) 130.5 9.5 15 Gray-tan silty sand (existing fill) 122.5 12.0 16 Gray coarse sand (cut south of Lot 14) 124.0 10.5 17 Gray sand/red-brown sand mix (cut south 116.0 8.0 of Lot 14) 18 Red-brown sand mix (20+00 Armada Dr) 126.S 8.5 19 Gray-brown DG sand (W/L import TC) 129.0 9.5 20 Gray-brown silty sand (Lot 2) 127.0 9.0 2 1 Gray-brown sand (Lot 2) 122.5 12.0 22 Gray fine sand (Lot 2) 118.S 11.0 I I I I I I I I I I I I I I I I I I I 4930489-01 I APPENDIX C (continued) Soluble Sulfates: The soluble sulfate contents of selected samples were detennined by standard geochemical methods. The test results are presented in the table below: Sample No. Results Classification* I Less than 50 ppm Negligible 2 Less than 50 ppm Negligible 3 Less than 50 ppm Negligible 4 Less than 50 ppm Negligible *Based on the 1994 edition of the Uniform Building Code (U.B.C.), Table 19-A-3 (ICBO, 1994). C-2 I I I I I I I I I I I I I I I I I I I LEIGIITON AND ASSOCIATES, INC. GENERAL EARTHWORK AND GRADING SPECIFICATIONS FOR ROUGH GRADING 1.0 General 1.2 1.3 )03Q.1~ Intent: These General Earthwork and Grading Specifications are for the grading and earthwork shown on the approved grading plan(s) and/or indicated in the geotechnical report(s). These Specifications are a part of the recommendations contained in the geotechnical report( s ). In case of conflict, the specific recommendations in the geotechnical report shall supersede these more general Specifications. Observations of the earthwork by the project Geotechnical Consultant during the course of grading may result in new or revised recommendations that could supersede these specifications or the recommendations in the geotechoical report(s). The Geotechnical Consultant of Record: Prior to commencement of work, the owner shall employ the Geotechnical Consultant of Record (Geotechnical Consultant). The Geotechnical Consultants shall be responsible for reviewing the approved geotechnical report(s) and accepting the adequacy of the preliminary geotechnical findings, conclusions, and recommendations prior to the commencement of the grading. Prior to commencement of grading, the Geotecbnical Consultant shall review the "work plan" prepared by the Earthwork Contractor (Contractor) and schedule sufficient personnel to perform the appropriate level of observation, mapping, and compaction testing. During the grading and earthwork operations, the Geotechnical Consultant shall observe, map, and document the subsurface exposures to verify the geotechnical design assumptions. If the observed conditions are found to be significantly different than the interpreted assumptions during the design phase, the Geotecbnical Consultant shall inform the owner, recommend appropriate changes in design to accommodate the observed conditions, and notify the review agency where required. Subsurface areas to be geotechnically observed, mapped, elevations recorded, and/or tested include natural ground afte r it has been cleared for receiving fill but before fill is placed, bottoms of all "remedial removal" areas, all key bottoms, and benches made on sloping ground to receive fill. The Geotechnical Consultant shall observe the moisture-conditioning and processing of the subgrade and fill materials and perform relative compaction testing of fill to determine the attained level of compaction. The Geotechnical Consultant shall provide the test results to the owner and the Contractor on a routine and frequent basjs. The Earthwork Contractor: The Earthwork Contractor (Contractor) shalJ be qualified, experienced, and knowledgeable in earthwork logistics, preparation and processing of ground to receive fill, moisture-conditioning and processing of fill, and compacting fill. The Contractor shall review and accept the plans, geotecbnical report(s), and these Specifications prior to commencement of grading. The I I I I I I I I I I I I I I Leighton and Associates, Inc. GENERAL EARTHWORK AND GRADING SPECIFICATIONS Page 2 of 6 2.0 JOJO. 1044 Contractor shall be solely responsible for performing the grading in accordance with the plans and specifications. The Contractor shall prepare and submit to the owner and the Geotechnical Consu1tant a work plan that indicates the sequence of earthwork grading, the number of "spreads" of work and the estimated quantities of daily earthwork contemplated for the site prior to commencement of grading. The Contractor shall inform the owner and the Geotechnical Consultant of changes in work schedules and updates to the work plan at least 24 hours in advance of such changes so that appropriate obse1Vations and tests can be planned and accomplished. The Contractor shall not assume that the Geotechnical Consultant is aware of all grading operations. The Contractor shall have the sole responsibility to provide adequate equipment and methods to l'ICCOmplish the earthwork in accordance with the applicable grading codes and agency ordinances, these Specifications, and the recommendations in the approved geotechnical report(s) and grading plan(s). If, in the opinion of the Geotechnical Consultant, unsatisfactory conditions, such as unsuitable soil, improper moisture condition, inadequate compaction, insufficient buttress key size, adverse weather, etc., are resulting in a quality of work less than required in these specifications, the Geotechnical Consultant shall reject the work and may recommend to the owner that construction be stopped until the conditions are rectified. Preparation of Areas to be Filled 2.1 Clearing and Grubbing: Vegetation, such as brush, grass, roots, and other deleterious material shall be sufficiently removed and properly disposed of in a method acceptable to the owner, governing agencies, and the Geotecbnical Consultant. The Geotecbnical Consultant shall evaluate the extent of these removals depe nding on specific site conditions. Earth fill material shall not contain more than l percent of organic materials (by volume). No fill lift shall contain more than 5 percent of organic matter. Nesting of the organic materials shall not be allowed. If potentially hazardous materials are encountered, the Contractor shall stop work in the affected area, and a hazardous material specialist shall be informed immediately for proper evaluation and handling of these materials prior to continuing to work in that area. As presently defined by the State of California, most refined petroleum products (gasoline, diesel fuel, motor oil, grease, coolant, etc.) have chemical constituents that are considered to be hazardous waste. As such, the indiscriminate dumping or spillage of these fluids onto the ground may constitute a misdemeanor, punishable by fines and/or imprisonment, and shall not be allowed. I I I I I I I I I I I I I I I I I I I Leighton and Associates, lnc. GENERAL EARTHWORK AND GRAOLNG SPECIFICATIONS Page 3 of 6 3.0 30:lll.tll'M 2.2 2.3 2.4 2.5 Processing: Existing ground that has been declared satisfactory for support of fill by the Geotecbnical Consultant shall be scarified to a minimum depth of 6 inches. Existing ground that is not satisfactory shall be overexcavated as specified in the following section. Scarification shall continue until soils are broken down and free of large clay lumps or clods and the working surface is reasonably uniform, tlat, and free of uneven features that would inhibit uniform compactio n. Overexcavation: In addition to removals and overexcavations recommended in the approved geotechnical report(s) and the grading plan, soft, loose, dry, saturated, spongy, organic-rich, highly fractured or otherwise unsuitable ground shall be overexcavated to competent ground as evaluated by the Geotechnical Consultant during grading. Benching: Where fills are to be placed on ground with slopes steeper than 5:1 (horizontal to vertical units), the ground shall be stepped or benched. Please see the Standard Details for a graphic illustration. The lowest bench or key shall be a minimum of 15 feet wide and at least 2 feet deep, into competent material as evaluated by the Geotechnical Consultant Other benches shall be excavated a minimum height of 4 feet into competent material or as otherwise recommended by the Geotechoical Consultant. Fill placed on ground sloping flatter than 5:1 shall also be benched or otherwise overexcavated to provide a flat subgrade for the 611. Evaluation/Acceptance of Fill Areas: All areas to receive fill, including r,emoval and processed areas, key bottoms, and benches, shall be observed, mapped, elevations recorded, and/or tested prior to being accepted by the Geotechnical Consultant as suitable to receive fill. The Contractor shall obtain a written acceptance from the Geotechnical Consultant prior to fill placement. A licensed surveyor shall provide the survey control for determining elevations of processed areas, keys, and benches. Ftll Material 3.1 3.2 General: Material to be used as fill shall be essentially free of organic matter and other deleterious substances evaluated and accepted by the Geotechnical Consultant prior to placement. Soils of poor quality, such as those with unacceptable gradation, high expansion potential, or low strength shaJI be placed in areas acceptable to the Geotechnical Consultant or mixed with other soils to achieve satisfactory fill material. Oversize: Oversize material defined as rock, or other irreducjble material with a maximum dimension greater than 8 inches, shall not be buried or placed in 611 unless location, materials, and placement methods are specifically accepted by the Geotechnical Consultant. Placement operations shall be such that nesting of oversized material does not occur and such that oversize material is completely surrounded by compacted or densified fill. Oversize material shall not be placed within 10 vertical feet of finish grade or within 2 feet of future utilities or underground construction. I I I I I I I I I I I I I I I I I I I Leighton and Associates, Joe. GENERAL EARTIIWORK AND GRADING SPEC[FICATIONS Page 4 of 6 4.0 JOJO. 109-I 3.3 Import: If importing of fill material is required for grading, proposed import material shall meet the requirements of Section 3.1. The potential import source shall be given to the Geotechnical Consultant at least 48 hours (2 working days) before importing begins so that its suitability can be determined and appropriate tests performed. Fill Placement and Compaction 4.1 4.2 4.3 4.4 4.5 Fill Layers: Approved fill material shall be placed in areas prepared to receive fill (per Section 3.0) in near-horizontal layers not exceeding 8 inches in loose thickness. The Geotechnical Consultant may accept thicker layers if testing indicates the grading procedures can adequately compact the thicker layers. Each layer shall be spread evenly and mixed thoroughly to attain relative uniformity of material and moisture throughout. Fi11 Moisture Conditioning: Fill soils shall be watered, dried back, blended, and/or mixed, as necessary to attain a relatively uniform moisture content at or slightly over optimum. Maximum density and optimum soil moisture content tests shaU be performed in accordance with the American Society of Testing and Materials (AS'IM Test Method D1557-91). Compaction of Fill: After each layer has been moisture-conditioned, mixed, and evenly spread, it shall be uniformly compacted to not less than 90 percent of maximum dry density (ASTM Test Method D1557-91). Compaction equipment shall be adequately sized and be either specifically designed for soil compaction or of proven reliability to efficiently achieve the specified level of compaction with uniformity. Compaction of Fill Slopes: In addition to normal compaction procedures specified above, compaction of slopes shall be accomplished by backrolJing of slopes with sheepsfoot rollers at increments of 3 to 4 feet in fill elevation, or by other methods producing satisfactory results acceptable to the Geotechnical ConsuJtaot. Upon completion of grading, relative compaction of the fill, out to the slope face, shall be at least 90 percent of maximum density per ASTM Test Method D1557-91. Compaction Testing: Field tests for moisture content and relative compaction of the fill soils shall be performed by the Geotechnical Consultant. Location and frequency of tests shall be at the Consultant's discretion based o n field conclitions encountered Compaction test locations will not necessarily be selected on a random basis. Test locations shaU be selected to verify adequacy of compaction levels in areas that are judged to be prone to inadequate compaction (such as close to slope faces and at the fill/bedrock benches). I I I I I I I I I I I I I I I I I I I Leighton and Associates, Inc. GENERAL EARTIIWORK AND GRADING SPECIFICATIONS Page 5 of 6 5.0 6.0 4.6 Frequency of Compaction Testing: Tests shall be taken at intervals not exceeding 2 feet in vertical rise and/or 1,000 cubic yards of compacted fill soils embankment. In addition, as a guideline, at least one test shall be taken on slope faces for each 5,000 square feet of slope face and/or each 10 feet of vertical height of slope. The Contractor shall assure that 611 construction is such that the testing schedule can be accomplished by the Geotechnical Consultant The Contractor shall stop or slow down the earthwork construction if these minimum standards are not met. 4. 7 Compaction Test Locations: The Geotechnical Consultant shall document the approximate elevation and horirontal coordinates of each test location. The Contractor shall coordinate with the project surveyor to assure that sufficient grade stakes are established so that the Geotechnical Consultant can determine the test locations with sufficient accuracy. At a minimum, two grade stakes within a horiwntal distance of 100 feet and vertically less than 5 feet apart from potential test locations shall be provided. Subdrain Installation Subdrain systems shalJ be installed in accordance with the approved geotechnical report(s), the grading plan, and the Standard Details. The Geotcchnical Consultant may recommend additional subdrains and/or changes in subdrain extent, location, grade, or material depending on conditions encountered during grading. All subdrains shall be suiveyed by a land surveyo~/civil engineer for line and grade after installation and prior to burial. Sufficient time should be allowed by the Contractor for these surveys. Excavation Excavations, as well as over-excavation for remedial purposes, shall be evaluated by the Geotechnical Consultant during grading. Remedial removal depths shown on geotecbnical plans are estimates only. The actual extent of removal shall be determined by the Geotechnical Consultant based on the field evaluation of exposed conditions during grading. Where fill-0ver-cut slopes are to be graded, the cut portion of the slope shall be made, evaluated, and accepted by the Geotechnical Consultant prior to placement of materials for construction of the fill portion of the slope, unless otherwise recommended by the Geotechnical Consultant. 7.0 Trench Backfills 7.1 The Contractor shall follow all OHSA and Cal/OSHA requirements for safety of trench excavations. I I I I I I I I I I I I I I I I I I I Leighton and Associates, lnc. GENERAL EARTHWORK AND GRADING SPECIFICATIONS Page 6 of 6 7.2 7.3 7.4 7.5 Jal0.1094 Ail bedding and backfill of utility trenches shall be done in accordance with the applicable provisions of Standard Specifications of Public Works Construction. Bedding material shall have a Sand Equivalent greater than 30 (SE> 30). The bedding shall be placed to 1 foot over the top of the conduit and densified by jetting. Backfill shall be placed and densified to a minimum of 90 percent of maximum from 1 foot above the top of tbe conduit to the surface. The jetting of the bedding around the conduits shall be observed by the Geotechnical Consultant. The Geotecbnical Consultant shall test the trench backfill for relative compaction. At least one test should be made for every 300 feet of trench and 2 feet of fill. Lift thickness of trench backfill shall not exceed those allowed in the Standard Specifications of Public Works Construction unless the Contractor can demonstrate to the Geotechnical Consultant that the fill lift can be compacted to the minimum relative compaction by his alternative equipment and method. I I I I I I I I I I I I I I I I I I I _t=.ETAINING WALL DRAINAGE DETAIL RETMNING WAL~ WALL. W ATEff PROOFING ;,ar ARcH1Tec-r-:-s· 8PECiFICATIC>N81--- FINISH GRAOEj ~i=::§t= --=t -__ --~===~~--=-===~==-~====== --..:-..:-.:--:..--=:~OMPACTED FILL :..-:..-::c-_-_-:_-.. -:..::~~~---... -· .. n•...--·---~~:::-::.:~ ----~ --------· ·NOT TO SCALE SPECIFICATIONS FOR CALTRANS CLASS 2 PERMEABLE MATERIAL SOIL BAC!(FILL, COMPACTED TO 89 PERCENT RELATIVE COMPACTION* .... (MIN.) DIAMETER PERFORATED liV~ P1:P( (SCHEblA.E 40 O~-- EQU)V~LE~T) yt~TH P.ERFOflATIONS ORIENTED,OOWN ·AS DEPICTED M1N1uuM 1 PERCENT o·RA01eNT TO 8UITA8LE OUTLET coMPE1ENf aebRoc·K oR MATERIAL AS EVALUATED ev 'THE ,ieoTeCHNICAL . CONSUL TANT . *BA8EO ON A8N 01&&.'i U.S. Standard Sieve Sfze i Passing ,, -. :-· ~ · l" 100 **IF CAL TRANS CLASS 2 PERMEABLE MATERIAL 3/411 90 100 (SEE GRADATION TO LEFT) 18 USED IN PLACE OF 3/8" 40:100 314•;...1.:112• GRAVEL, FILTER FABRIC M~Y BE ·. · 25 _40 DELETED. CAL TRAt4'tf CLA1i$ 2 PE&lMEABLE . No· 4 MATERIAL 8HOULO BE COMPACTED to 80 ~~: ;O 1tf~ PERCEN"fiAELATIVE COMPACTION* No. 50 0•7 NOTE:COMPOSITE DRAINAGE PRODUCTS SUCH AS MRAORAIN No. 200 0.3 :OR J-ORAIN MAY BE USED AS,AN ALTERNATIVE TO GRAVB. OR Sand Equ i valent>75 ~SS ~~AU.A~ 8HOUlD BE PERF0RM:D lN ACCORDANCE ._ ________ _. :wrTH MAN:i=AcnJRER'S SPEQflCATIONS. I I I I I I I I I I I I I I I I I I I PROJECTED 1 TO 1 -~1'\111_ .-JIM OF 8lOPE APPt~:n NAlUfW. GROUNO -- ----- CUfPAIZ LOWEST BENCH (KEY) 2' MIN. ICEYDEPTH 8fW.L BE OONll1IJCrED PflOR TO FU PI.ACEMENT TO ASSURE ADB:IMTE GEOl.OOIC C0NDIT10N9 PROJECTED PLANE . t TO t MAXIMUM FROM TOE a= 8L0PE TO APPACJYED OA0UN) KEYING AND BENCHING BENCH HEIGHT BENCH HEIGHT -------· ~CTED:..-..:: -~-----~ FILL SLOPE FILL-OVER-CUT SLOPE CUT-OVER-FILL SLOPE For SubdraJns See . Standard Detail C 8ENCHNG 8tWJ.. BE DONE WHEN 8L0PES ANCII.E ■ B:I.W. 'TOOR OfEATERTHAN 5:1 MINMJM BENCH HEIC!Hf 8fW.L ee 4 FEET MINMUM FU WID1M SHAU. BE 9 FEET GENERAL EARlliWORK AND GRADfNG [fill SPECIFICATIONS U STANDARD DETAILS A REV.4'1ft9' I I I I I I I I I I I I I I I I I I I FINISH GRADE --------------------------· -------------------~------------------------------------· -------------------------------=--=-=-----10· MIN ----coMPACTEO FILL·----SLOPE -=---==---------£·---· -------------- FACE -_ -:.. __ -:.._ =~-=~-:--=~-_:-_-_-_-_-:._-_-:,_-..=-_-_-_-:_-_-_-_:_-_-_:: ------~-:25-------------a------------n-------n----------· -----------------------------------------------------------------~----------.-: -------------------'3,,,-------------------------------------~-~~-=-~=~---~~ .... fi----:_7:~--: -------------------------------~~.;~~--=:?: __ -:_----~---~~-----~=-~--;~_--__ ._------~-------~-~--~-----------:..:-.4 MIN .. ---15 MIN. ------· --------~-~ -------~~--------------· ----------E--------------------------· ---------------------------------------------,---------------------------~ =::...--:..--=----~-~--:e--~~----~--_;--.,.:--_-...,:-:-_____________ --------------------------------------------------~------~-::.OVERSIZE • ---------------------· --JETIED OR FLOODED .:-_..;. /-.=-_-_-_-WINDROW :,:-_-_-_-_-_-_-_-:,_-_-_-_-_-. ----GRANULAR MATERIAL ..... --------------- • Ovenllze rock Is larger than B Inches In largest dimenmon. . • Excavate a trench In the compacted fil deep enough to tuy all the rock. • 8acldil with granular SOI felted or flooded In p&ace to fl all the VOlds. • Do not bury rock within 10 feet of finish grade. • Windrow of buried rock shal be parallel to lhe ...,118d slope fil ELEVATION A-A' PROFILE ALONG WINDROW _A--_-_-- - --- - - - -~r;-:-- - ---________ a_ _____ _ JETTED OR FLOODED GRANULAR MATERIAL OVERSIZE ROCK DISPOSAL GENERAL EARllfWORK AND GRADINO [][!] SPECIFICATIONS U STANDARD DETAILS e· I I I I I I I I I I I I I I I I I I I NATIJRAL ~GROUND ~ --™~=rm--=-~-----------------------------------------------------------------------------------------------------------------..,_._===--=-: --:._-_-_-:_-_-_-..:: COMPACTED FIU.-=-.-_-_--_-_-_-- BENCHING _ ___..~_ ------------------------~....,___ EMOVE ----------------------~~ UNSUITABLE -~--------~--MATERIAL ----=-------=----------------------------------------------------------------------1_;;;m=-=-=-=.li --------~~ ~ ~~....;_..-s \ \ CAL TRANS CLASS II PERMEABLE OR #2 ROCK (9FT.1/FT.) WRAPPED IN FILTER FABRIC FILTER FABRIC FROMTliETOP RY& FEET (MIRAFI 140 OR . APPROVED '-..coLLECTOR PIPE SHALL EQUIVALEN1) BE MINIMUM &-DIAMETER SCHEDULE 40 PVC PERFORATED CANYON SUBDRAIN OUTLET DETAIL PIPE. SEE STANDARD DETAIL D DESIGN FINISHED GRADE PERFORATED PIPE fi"♦ MIN. 20' MIN. NON-PERFORATED 5' MIN. 6"♦ MIN. CANYON SUBDRAINS FOR PIPE SPECIFICATION FILlER FABRIC (MIRAFJ 140 OR APPROVED EQUIVALENl) #2 ROCK WRAPPED IN FILTI:R FABRIC OR CALTRANS CLASS II PERMEABLE. GENERAL EARTHWORK AND GRADING Cfill SPECIFICATIONS I STANDARD DETAILS C 4,'M I I I I I I I I I ,1 I I I I I I I I I OUTLET PIPES 4•♦ NON-PERFORATED PIPE, 100' MAX. O.C. HORIZONTAU. Y, 30' MAX. O.C. VERTICALLY 15~ MIN, \ • SUBORAIN INSTAU.A110N -Subdraln collector pipe shall be Installed wtil perforadocas down or, tmless otherwise designated bi/ the geotechnical consulbn. Ot.set plpaS shall be l'lOl'\-pedoratecl pipe. The aubdraln pipe 8NII haYe • least 8 pecfonldons ldormly spaced par foOt. P8f1oratlon shall be ¼• to ~• I dr1led holes are used. M subdraln pipes shall have a gradient tit least 2" towards the oudet • SUBORAIN PIPE-SUbdraln pipe shall be ASTM 02751, SOR 23.5 or ASTM D1527, Schedule 40, or ASTM 03034, SOR 23;5, ~ 40 Potyyinyt Chlortde Plastic (PVC) pipe. • All oudat pipe shall be placed In a trench no wider than twtce the aubdraln pipe. Pipe shaft be In sell of SE>30 tatted or flooded in place a,ccept for the outside 5 feet which shall be native soil backfiU. BUTTRESS OR REPLACEMENT FILL SUBDRAINS . GENERAL EARTHWORK AND GRADING [fC] SPECIFICATIONS STANDARD DETAILS D I I I I I I I I I I I I I I I I I I I CUT AND CUT-FILL LOT ---- REMOVE UNSUITABLE GROUND -----.,,,..- -------------------------------~--.:.COMPACTED FILL-----~-~--------36" MIN.,.., ✓ OVEREXCAVATION AND RECOMPACT UNWEATHERED BEDROCK OR _s---- MATERIAL APPROVED BY __s-THE GEOTECHNICAL CONSULTANT t NAlURAL --_.- GROUND) .,..-_,..,. --SIDE HILL FILL FOR CUT PAD / ,/ .,,,,,,,, ,.,,.-_,,,, .,,.,,,,. OVEREXCAVATE / FINISHED CUT PAD AND RECOMPA ~_-~,:=-:_-==-_-=-_~-~~-----'-------- (REP• •CEMENT --------~ _-~-:_-_-_-_--. . . . . . . . . . . . . . . . . .. OVERBURDEN OR UNSUITABLE MATERIAL: ------~---PAD OVEREXCAVATION AND RECOMPACTION SHALL BE PERFORMED IF SPECIFIED BY THE GEOll:CHNICAL CONSULTANT '----SEE STANDARD DETAIL FOR SUBDRAIN ...,...,,---t:_,;~:.;.:a~ DETAIL WHEN REQUIRED BY GEOTECHNICAL 9 FEET MlN. CONSULTANT UNWEATHERED BEDROCK OR _s-MATERIAL APPROVED BY TliE ~ GEOTECHNICAL CONSULTANT TRANSITION LOT FILLS AND SIDE HILL FILLS GENERAL EARTHWORK AND GRADING [[!] SPECIFICATIONS STANDARD DETAILS E . r l)E'.\Sll"Y ·rFs·r L()(',\·1 I()'\" \1,\P C11rlsb11d R1111cl1 Carlsbad, Califo111ia l'roject: 4930489-011 Date: c Fn •lnecr/Grolu~i,.I: JGF/MRS \ . CD WUWIII lll'fl II V. ·1• I { ' ' ' . ; F ·,. .. Af l\j l I/ lo. • Qt T: 51 • • • • I ,., ._,,. • • • . " -- • ·• • / (' ,i I \ I •-, j '.I • • ' • l NOTE: GRADIN UNDER \ I • &3i • • N.A . .70 • - • • • • IS UNDER STRUCTION WMIT fOR 92-07. ® • • ·--·GFT • ~ •• --.< •• . '•. ,.• ' --.--(. ' .-· .. ;' • ,._ ..... .. Af . , / • \ \ ' • I I ' I \ I I \ \ Af 00 I 0Z l Cill t ' ... '• ' .' -•_\ , __ ' 0 I \ ./ ' • . .._, , k ·~ .. ~·" ~ ~'41~ ® 0 00 LOT 2 Qt 0 F GR~O/NG PER 5DP .9G-t7~ Pf!D £L "'tE.6. 83 00 Af 004• [ill •0./11 ll'J, 6 [HJ 0 • • \ t \ ' ! I I I GFT ,, ' 14 ( . ·Qt , I . ' --, , .. _~-~ , ,, '-...!◄. 1 f l . I , II ,-1, I EIIGINl'.l:lt .OF' ~ -, .. I ., I• 1 I j I I ~RW -, ~•-~ I I I \ l't I 1, I I 4 LJJ.-..;:....--r ' \ .. ' I 'x I., C. 1) ( ) 11 I 1 .tM. ~IUJI 1/f\ . 15.0 ' ~ I I \ • I I i I I I I • \ 3 ..... PH0M(O POIINCNT IIPOE$~ ' - LOT 1 GEOLOGIC UNITS. Af Qt Ts Artificial fill -documented by Leighton and Associates (circled where buried) Quaternary Terrace Deposits (circled where buried) Tertiary Santiago Formation (circled wtlera buried) SYMBOLS ,-· --0~ [ill ~ .q~~ 1--r' --r GfT Geologic contact, dashed where approximate, dotted where buried, queried where uncertain Approximate limits of fill F~Fill, C=Cut Approximate elevation of key and/or removal bottom Appro~imate location of stability fill slope key Approximate location of field density test Approximate location or subdrain with e.rrow showing direction ot now Approximate limits of grading during Phasa ti operations ·" Gravel fitted trench; capped with a minimum of two feet ot c ompacted soil Outletted \/ia short sect!on of perforated j pipe and cutoff wan into 24" storm drain '~•-·. _, .•. ,.,.,,.,.-',. ,.,,..,, .... ~··•'"'· ...... ___ -.,~ ' • NOT£: 18' ¥ ' 20' ----- 10' SECTION F-F GRASS CHANNELi 11G SClll£ • ST.&RM OR/1/JJ D£5/GN 8Y KRHR / !lSSOCIRTES f'ER REPORT D/11£0 /o-1-?G; /" .. • -- • • . . •-,. I ./4<::. ~ ~' .'· '" .,,, i<,,,;t '":.;-,..,~ ,,,,::i· ~,-'; ·~-• •;:,.t ' -~,:,:i :1 ,. 4r ~-:t ·.,--' :.1 .. -· ~~ .. . , . .=.: -.~?,C • \_¢, ,'!".' ,-' •• !of~':~ ~ . f ''0··;..·c .. ' ., , . ....,_ ; .... 'I, ,-~-- ' . ' ,; . ~ l s · }~,l~- ··-.. : .•, ' . ._,. --~ ' !: :;.;;~ '►_: ,.~- __ .:.(}!,_. , :,P :;,:tf -:. . .,, " . . ' ~ ii~>~_:,' ff~,\ ' . . t;~i;.(/ _-., . ·.ot: ~?;,:;,,,~ .• m ~Wll£t/ ~----~✓ :--+-llw.A:~ • w w VJ . . \ \ ·. , I r 57 P ate: .. J: • i \ LA 2 • • ' • • l(.f'~5i RCP[P U350·D ~ 2 4% ' I J6'RCP Af .. 1 l L :,;~ I fl : I I . I r I 1. I ' t I , I I ', Af \ \ I l fWIII-TYP( CAT£ ~:; SIIEClflCA I r ~~. l Fl,~\ ~·-.Q ' I I \ \ I I I \ ' ( \ \ • • Qt • ' I I SE£ SHEET NO. 1r ~~Af -~/8,?,t;'-24" R[ {P/l/VRT[,J[/35D·JJ)@(J.5Gf I Af I I I I I GFT SHEET NO. 13 . ' a \ Af LOT 2 ... ~,_.;·.,.,, .. --' -.~:i~~J~~.~-:)fY(~r;. :·•-:,\'--~"': ....... ...... ·--~-.. :.. .. GFT . , : [ill ...; 0 Qt ~'l.1--..,, ,,... ·"'·--~ .......... ... ' .. •.-~ ........ ,~,.,.,"•~-.... -""·-- \ \ I , \ ,. ,_ ···_.:-.,,--,.· -., . , ... r<a,,D, PROPOSa1 DIM t f'tlXS, .... ,-r,, \ \ - • - - ., I., ,,. -. . . ' ' O£$IGNfl) l!IV: !IN, °"~ n:a ,. 011 ••. II': _.,y,a,..._ ___ SCAl.& , § ,-"AS-BUILT " BENCHMARK: J I l'.tn IOI.; ,-0']). J09 IIQ.: ae--1014 c,,r" -t-------:~-~:-------~---{P E __ _ auifoc'_c,r -·. ( .. : .. \\ . : I REVIEWED BY. · E XP. ___ _ DAT( DATE • 0£SCRIPTOI· , (' 'Pl.dnc CJ#> I / (S.O. CO. C0NIIIOl P'T. '{-1 J07} tCGATION . r.G (I~ TTIIOIS II RMACW> llO.W. 500 fl 1U!H rK ~ illRf'ORI' 111W). . '*""· • \ \ \ \ i - 02 ' F Af .. ' '····" ,,,_ 11..---.. '<:,~-· -• ..,, .... _, ' - C 0 0 111 - / . ( ,:, . 'L '/""'-'.,a, 114 TdE O.F 5L 1//, /,. 1//-/// ,, .;-. . . .. / . ./ . ,, // 1/ // '.-'. /,> . 00 0 /./_,··1 / ,,;,_ .,.//.• /j ' / < . .. /, ~.~:·:_ ,,. /·~ .• / f ' co I ' I ' , I -i • I . r ,:~~t½·-;,'-~.~,,- I . , I . ' i ' I ,: I -? ; , ' .. t I I : I ..,.,c I ' I 1 124 I . T l'.l I' I I I t I I ·, I I I f+ I I t.,z5 I ~0 I I . . I :_,~13 I I . ' I I ' ' ) kvi$10N OESCRIP'l'ION I • , . cD 0 SHT t.J ',,. ,, ....... . : ' ' . '· 1-•.· .. , SEE BELOW LEFT 40' ----- NOT£: 5TDRK!DRl!!N Dl5/6N BY KRHR e IISSOC!//7F5 F£R R£?0£T DRTED /0-/-fG JO' P(O(STIMN PATH 6' , ., -;:.,.,,,. ' • . ...... :.' • j I)· 't. ,·,~ ~ .. I i i I ,: PCC SIO£MJ( ~-~8£ ™fll'<OllERS "' :\. • TYPICAL SECJIOt'.f H-H, LOOKING NORTH ',\-::: · ... :~,: · .. ,,,-, .. NO SCM£ ~-·. f ' ,1\ \~-- -< " ' ... f·:.-... , • . . ,;~<; .. \.- , .,, ., ,--~ .·"~· ~J.·<r-· '·. -'J ,; ' -• J • .. . ' . ·-. • .,. _ _;.; .. I I \ \ I \ .... ' \ / ,.\· I ' \ \ \ \ i \ i\ ! ' ' \ ...: ·. i ·' ' .. ~.~~---~ '-, ·.-:;r ·.,, ':·.•·• ,•..-,.'. ... ~ •. f"•'-.::.."""1..-"111~~-.::.;;,-,-...,.--.,-:::--~ \ I I I '· . \ ' . \. \. \ \ ' P .M. ,i'-Ji~B4 PAR, 2. .... ·, \ ' ( I ' / -.DESICHD B'r. N!P: ~TE , RI. !M DAMiN !IT: _r .. :a-· -~ .SCAl.!: c SHOW ""°4eT l,IQII~ 1ft. .1011 Nt.: •101+ I ' 1-____ _,,..._ _____ .,._ ___ .._..f P,E ___ _ ~-~·_/ .... >I.s_•·.;_~_ · ;:'.r 111, •• , .. , ,...., . , .. , k·:. ~ ~ ~ ;i, • ..; ... :.~ • ......... ,....._... •• .,,, ; .. ;~-~~-.,'·•>~tx;;,,. ;.. "''.._5<~•-·· ,~' I' • ~~;,e,.~-:-:,:;: e-.~~·-.. ~~•----d~,· . ~ ,~~;~::_·,._~1.t:.<~.---~,,~-~--·,. :~.~ ·.. --~-~-~-~_,._-., .~-... . / -\<\••!~~~--~~~:i~~~~.lfy~:.-~A,; ri'?i'"· ~. :;, ~·l·:tJ.·,:';~d;/::. , .. ~>N: ~·r.i~·.:~~.-ii:M ~-"'4,·· :~ -..: .. -. ., \: · ~~ .... ,.,,_~_,1;,~ ••. ,wr-*~"> t f'• ¼;.."':;·'!"~--" . ·· ,-~~~~0rt~.--.·,.·. .. "-. _ .. __ I EXP ___ _.__ DATE ' ' . ' ' I j ... 0 \ BENCHMARK: OCSCRIPTi(lN <FUSTICDI' ' \ ' I : . ' I i r {S.0. 00. allmQ. PT. T-1J07) _ LOU.TION: fAS1 <E INJl0ilO ~ II W I.O.& a f'f. IOrtli CJ' ~l!Wt • OM DID. RtCORO Ill!'.». 1191 ~f £1.£VA11)N; 4l.t1 It.le . . . . :'· ill] LOT rACRllOIN~ PER .5 W PRO£L =6 - -03 . \ I I 1 I 00 Qt 105 114-...______ \ 112. 1n1 V' I ' ' I I e7ffJ ,~ F ,, I.~ I I \ I I I I \1 \ ctSS ~,/(o6/:) ro NfRl'.ANf.llT" NO. 3 TH61,'-H EltSTINu/FLOIMI. --,"" lllk!N ti, L07'. I / 0 ,,. •-I -I" ,,,, •1s' f{,O-C-Jl!,() Pee wf,•••• 10/10 GMGE W>IF APAoAi I \ ' t ' \ JVJJ-\? -J 30 /8 i \ I ' \ ' ' \ 0 -1() CAANll~L. ;; 1)-11 C.,TOFF 'i/Au. PEft o• · J l<>ffol'I lo/ IOTII • ~' \ \ \ • \ ' I \ ' ' \ l ! ' I ' i • ., ; ' C ,. ~~,,.· ·· I <:"t'~-'~ -/ ,·-o:-. / .~>~/:~;.:-~.t '~:f-'~~·._ -•; ··;·:}·:;:,-,·· ... . ' ')\. :: ·ri,fq~ ,: .... r'!-,, • • • ' •• ,.. • ..., ' .• , ··•,' i ' ' l-'----+---+--1.c---_:.,__---+----+--~\ -+---I Lill GIWIIIC · fUIIS fUI: CARLSBAD RANCH ·-1~' t ' ':""'. ~·; . .. -\. . . PE ' OF"°"" REVISION DESCRIP'T19H ...... ·.' .J /"~i ·~ . ., ..... l :; 1"· ' I I ,' .... ~ _,. -t,-,:., .. _:: t·• <-< ,. ~<'-.. ·" ri-." ·:"" ' .,;. :-· ·. ;\,'' --~ .. I<·_'·•(·.'· . -··,, '. ! . ,~ :-· \<•: , .. ' ·.' -.. -'.!{.;-, ~ •• :c ~. ;~;}(':-: .,~--✓ • , .. :"c, .. r• • ~ ~:~'.r'i. ;.. .,. ( .. 't''. .. :•. --.~/:;;-r, f;:;-'•. m~:.,,;.;:1: ,·:· ' ... 1220-...- -204 ~-~920011 ,,-a--43,-1'00 ,01el_t.t-93l --.0 Pro ject 4930489•01 1 l n ineer/C rn lo .,t; JGF , MRS - ' ·. ' Dra ft in• lh K,'.M . . '. . . •· ·._ , · .. -. :'.--•·,., :•.~ -. :_:·,-.-.~~;_-~i ;, --~--~-~ , 40' , .-. ,: .· .:~ r ·.,· . .. ~---:.-, , "'"" , .. , .,· _-.0::•::w, ;_ :" ~ ·-.• ,;: ... :.'.,,.._· :-.. . -..... ... '-· .. __ ,. ____ _ -----___ ., ____ _ I i ' I I / . ' ------o· ..1.0' '"f 20' • . , . . -~ , ' · .. • ••• , ,. , .. · .)...... / /., ,, )> • • ' I-'. I/ Ii " // ,;1 ,t I f ,. / · II I 111.c:/ ., _/ ~ 11/ I I I - §,..~>.:;~:-,., :,:-'"::t _.,.••"$ .. ,,-;, .}_ ... ,.,·-1V/-, \,_:.,_'{. ,. J'-i:~ . .. ·• ''~ _ .. -;,..-. ., ; ;·•· .. ·:i);:,".J-f"· •. ,,, .. ,_, j"' ~ 0 ,;-,A~, -~-5:\':.-:: .. '" -· ··'.-• ·,., ·.•' ',Lo·f 5 ' . ~AAP -, ;13073 -~ -~ .--: ' ··•;,t,' ,_,/ /·' .. . ,,,. •. , , I a I • -.,_;. . ,. . , NOTE -RETNNING WAllS SHOWN HEH! · SHOI.Jl.O H4~ COi.OR AND J01l/R£ - . MATCHING THAT OF TH£ PROIENA/J£ WAl1S. "AS-BUILT " BENCHMARK;.-.· . ' , .. .,·. -.. , ,-·: ~~i- )<",\":\:\,;!}i, -', ~; --•. .,> ·. ,• ' i. ,. ,· \ . - • ----8' QtMtl .ltlll'. rocc-- PDI M .. ·---....; . •q~ -@···· it• .. \ SEE SHEET NO. -' (Dt$JW, \_~--~ ·------, oasr. SIO£WliUC EXIST. ___.,; .SIOBIIIU c-5 RETIIINI, wAli-- EXlSlJ«; ~ PV.TE _ llMOOIP,(iS • EXIST.mu 1.,,--.. g• Q-M UNK ma: PER 11-11 . ------·-----. lll'SIGHEO IW: 'IM OliMIN ~-t•-··---""°-li:cr .IIIGll: §PPi 0,..T[: fEI. 1991 SC:,,U:: Jlt2llllllL_ "°" ~•10"' OESCR!PllON: (' PlASIIC CM' (S.O. CO. COlmOi. l'I. T-1J07) ·_:f~ STATION SECTION J-J 3+66,00 Of L£GO DRIVE s CMt t.,y;.wf'itvo ' ~It...,. .. " Pret1U 1"1 ·· s....,, ... P.£. __ _ EXP. ___ .._ lNSPECTOR DATE· DATE,, lOCAT!ON: EAST Cf' ~ TIWCKS IN ~ R.o.w •. 500 fl NOlml Ci PM.CIMR WIJl1' ACW>.. · RE CORO FROM t 9Sl ACJ. ElfV,t,TION 46.67 11.S.1. .,~ SCN.£: HOHIZ N ,. ., 20' . lflPT. N ,• ~ r O,,TE ENGINEUI ,,,m•1. o, WO""-REVISION OESCRIPnON ( .. \ ;~.;. /:~t~-" .• ·,/11t·:, ' . . ' . -:--·,•--· \ \ ..if. ------------; ------~---·-- \ q_\_~\ ~'-,~ ·o .,. ·-'y~ . ~~~ !UT OIi 1/2 SECTlON \\_~ 36" CVP WITH MI !!.A MA'!' /(HJ() " \ OR IEIJIJAL FIL TElt 81..ANKE.T TO HOLD C/1.AVEL Ill PL.ACE PDlfOIWE 1!111 t °"-4Q£S AS OESCR!BEO 'dEUlll ~ El.EV. • 152.5 DEWl'WIING tn£S J,, f OM. H0L£S e fllV. 152.5. 153.5 & JM.5 ATTACII l)'r IOI SCREEN (C.C. IIOD.) I .. , 6' X Ir RIP-RAP NO. 2 BolC1<1NG· 1' THICK (MR H0J:S /4/Jll»fA"f lb()D M adUAL Fl.TEii aN«ET D-40 MQOffJEP TYPE 'f CATCH B.\51tf~'",; -•llll<-ll<-l~/Jr--~..I...LN01-lloSCM£-.L-...lll.l:J.ILJtU.J._.il::JIIWi.1{f <;-, . , ' -.;.._., I , , . 4' ,. • w l CITY OF CARLSBAD 11 SHEETS ENCIH££RtNG ~NmfENT 25 . . , > GPYI S l'UIIS FOi: -!- ' -.-. CARLSBAD . ' RANCH .. .. ... . . -UIIY1 c.t. '94-9 APP~#,f' ~ ., , ' . I L"'!l) A f-S--'1t. Pl 2 E:XP1RES 12-31-~ CHY ENGINE$R DATE . I OWN BY· I PROJECT NO. OAAWINC NO. O,,Tt INIT1AL O,.TE lfflTIM. -:=rv:~: C.T~-9-4-9 333-2K OTH[" WY >l'l'R()•IJ1l ,, .. ~~IOI~•-, :.-.r . •' ~ ·••"'\.,••-.. '-. -~-· .. ' . , , .:• . :, ... )..;, ,. . '• 1:, _ _.. \re:: .;,--· -~;., ,'!-• •;; • 0 z 1220 .....,,ido ~ Sult•:lO< Corl-Sttod. C:alitomia 92009 15tt,-9J,-7,no rcx:~19-t.Jt-SU,0 a : / I / - ,.,,_-.·_,', . \ , \ j \ ', ,, '_. /. I ' I I :z :,'-,· ,-; . ,' ·_ / l g f ~ \c I / I / I AA~r W~@1 ® I , fi J. • ; / ' \\ ... ' l ,\ Q F . . ' ~.:..: ... ·----.. ------- ------ tlESICtlEI) BY: . IYl,P. Mlt: •.. FEB. ttll llfWIN .ll'f: tG, .. SCALE( A StlM! " AS-BUILT" PRQJECT ~ JOtl NO.: 119::1014 i----:-----------==::'.:::::.J P.£ --- ENG!N£EII OF WORK: REVIEWED BY: INSPECTOR ' ' \ - I -- DATE I Af ..•..•. :>tii~t', ,(· _: .. ;\, . ; 1 Existtng' stockpile ·. -. i . ~ l I -,.;:.;./ ' ; ,' '' ,: ( --........ ' ' _,....,_ ... ,: •-/ .. ·.:: ·, ""'" '. :--- BENCHMARK; • O(SCRff'Tt(),; ~ P\AS1I: C#' . . . · , . (S.D. CO. CCHIIU Pr. T-1~ , LOCI\T!O!i £AST Of RM.Rtllll) T1IACICS If ~ R 500 fl Manli OF Pllll ,,...P . .0.1. . --=-· na ORT R<W>. RECORD FROII: 1980 Alli,. . ElfYATION: 46.67 ltSL..· I I '/ I , O' ..LO' ----,e; 5' '1J1 --= I I I I I I I I I I \,_ ~ air • £Pf/IMS' --- --------I --------. -------- r-:; .( -r ~j I j . OAT( INIT\AL ENGINEER or W()Pk. • \ . \ · .-· \ \ LOT 6 \ ' i I , ( I ! I ...______ '--.. -----~ ( ...______ '--.. ~ --------; / _/ I I I / I I I I I I , R£VISION DESCRIPTION \ \ \ \ t_ '. Af / I / I ./I . I I i i DATE INlilAL. [l&T[ fNfT""-. OTHER APPIIOl'Al crry APPA'O\l"L. .. • I I I I ,I . WI CITY OF_ CARISBAD IISHEE1S ENGIN£ERIHG O(?ARTMENT 25 ;I· GRADING PUMS mt: ,.v; ,,_ - CARLSBAD RANCH .UNIT I C.T. 94-9 AP~~~,i_. LlOY!l R H 'J..~-,, PE 2 EXPIRES 12-3H~~ CITY E:NG1NEER DATE DWN eJY· ~OJECT NO. CHKO BY· 1¥11 DRAWING NO RVWD BY : c.T. 9•-9 '333-2K