North Coas Calvary Chapel - Multi-Purpose Building Alarm System Review Comments. Page 2
Review Comments
/ North Coas Calvary Chapel - Multi-Purpose Building Alarm System, 1340 Poinsettia, Carlsbad,
California
A manual pull station should be added at the double exit doors to the exterior of the upper right
hand corner of the gymnasium. (Field Verify)
No scale or north arrow on floor plan sheets.
Site plan has building labeled "Auditorium", verify this is the same building.
15 cd strobe at end of corridor near office 202 should be relocated to the opposite wall to the
right for better visibility throughout the corridor.
MIX-3 100 alarm current is shown as 4 mA in the catalog data sheets, while the calculations
show only 0.34 mA. Results in minor increase in alarm current, and total current. No revision
required.
MIX- 1O1P alarm current is shown as 4 mA in the catalog data sheets, while the calculations
show 0.6 mA. Results in minor increase in alarm current, and total current. No revision required.
EMCOM
ELECTRONIC SYSTEMS, INC. CALIC.820216 SEC. L1C ACID 3838
256 WITHERSPOON WAY, SUITE H • EL CAJON, CA 92020 • PH. (619) 667-1200 • FAX (619) 667-1222
I
I
I
Fire Alarm System
Equipment Submittal
I
I
I for
I
I
North Coast Calvry Chapel
I Multi Purpose Building
1340 Poinsettia
I Carlsbad, CA APPROVEASLJBMITTED
I CARLSBA5F1bEPARTMENT
iliesc plaits ha c No, revswctl t'i llpiin1 otitipltaitce
Iwillt theei lirelit ap 111thl soiLs alld standards iii liitL'C
itt tlti no s,liititt. 1ltciVsi1Ct r V.01111,K101 May titilirt
this is so" it sltpptrt ol nit :ippltcittitit 'i t htnldttie
nt vnttt 't ith the tprsss titrts-rstttirlt;lg that this rits'tsw
ii itt o to rel cvi' the owner oi con tractor or t kit
j,tt,fesstitnal citt!lilccr or architect for sole icspisitsihilily
for full coinpliattce with said codes and standards.
including the building ctie or for any responsihibty For
deticieneics. errors. omissions or negligence in these
plaits whether or not noted in this review.
Dale: eviewer:
cl RECOMMEND APPROVAL
RECOMMEND APPROVAL. AS NOTED
INTELLIGENT FIRE ALARM CONTROL PANELS FX-350 SERIES
I The FX-350 Series Intelligent Fire Alarm Control Panels
are single loop addressable panels with support for up to
60 or 126 addressable points. The FX-350 Series panels
are equipped with a two line by 20 character backlit LCD
display, numerical keypad and an integrated UDACT/
Digital Communicator. The FX-350 Series family also
includes remote LED and LCD annunciators.'
The FX-350 Series panels are ideal for both new and
retrofit applications. Designed for small to medium
commercial, institutional and industrial occupancies,
these panels are powerful enough to meet today's
in demands. The FX-350 Series panels are
configurable by the keypad for onsite programming or by
a PC for both onsite and remote programming. Easy to
install and simple to operate and configure, the FX-350
Series panels enable the installer to configure the system
to meet their specific requirements.
The F-350 Series panels are equipped with a 5.5
Amp power supply, auxiliary resettable smoke power
supply (300mA max.), an interface for a Remote Trouble
Indicator (RTI- 1) and an RS-485 interface for remote LCD
and LED annunciators.
All FX-350 Series panels come complete with a red door,
black enclosure, durable CAT-30 lock and key and space
to mount up to 12 AH batteries. Optional trim rings are
available for semi-flush mounting.
Features
Single Addressable SLC Loop that supports 60 or
126 addressable points
Points can be any combination of Addressable
Sensors or Modules
Supports Ionization Sensors, Photoelectric Sensors,
Variable Heat Sensors and Multi—Sensor (Heat/Photo)
Equipped with a 2 line by 20 character backlit LCD
display, numerical keypad and an integrated UDACT/
Digital Communicator
Digital Communicator can be configured for DACT
or UDACT mode of operation
Configurable via the front panel, PC Configurator, or
remote dial up through the built-in modem
Sensors can be configured as Alarm, VerifiedAlarm,
Latching or Non-Latching Supervisory, Monitor and
Trouble-Only
,• Modules can be configured as Alarm, Latching
Supervisory, Non-Latching Supervisory, Water Flow,
Monitor, Trouble, Fire Drill Switch, Signal Silence
Switch, Aux Disconnect Switch and Buzzer Silence
Switch
Base panel is equipped with Four Class "B" (Style "B')
indicating circuits which may be configured as Class "A"
(Style 'Z") using a Class "A" signal converter module
Indicating Circuits may be configured as Silenceable
or Non-Silenceable for both signals and strobes
Built-in sync protocols for the following strobe
manufacturers: Mircom, Amseco, System Sensor,
Gentex, Faraday and Wheelock
Relay contacts for Common Alarm, Auxiliary/Alarm
(Disconnectable), Common Supervisory and
Common Trouble
Configurable Signal Silence Inhibit, Auto Signal
Silence and One-Man Walk Test
Subsequent,Jarm, Supervisory, and Trouble operation
RS-485 Interface for Remote LED and LCD
Annunciators,
Interface for a Remote Trouble Indicator (RTI-1)
Two event history logs comprised of a 200 event
alarm log for alarm related events and a 200 event
general log for all other events
5.5 Amp Power Supply
Optional modules for additional internal relay circuits
and City Tie/Polarity Reversal
Complies with UL 864 9th Edition requirements
Optional trim rings for semi-flush mounting
X&
7165-1477:156 S7010
CATALOG NUMBER
I
U
U
I
I
u, y NOT TO BE USED FOR INSTALLATION PURPOSES.
Mtrcom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models. I
111111ii, MIRcQM'
Canada U.S.A.
25 interchange Way 60 Industrial Parkway, PMB 278
Vaughan, Ontario L4K 5W3 Cheektowaga, New York 14227
Telephone: (905) 660-4655 Toil Free: (888) 660-4655
Fax: (905) 660-4113 Fax Toll Free: (886) 660-4113
Web page: http:llwww.mjrcom,com Email: maii@mircom.com
Distributed by:
ISO 90012000
REGISTERED ;fr
U
I
I
CAT. 5670
Rev. 0
Optional Adder Mod uJes
:r., 4±
—
-
OCAC-304 Four Indicating Circuit Class "A" Converter Module
The OCAC-304 converts four Class "B" (Style "Y") output
circuits on the FX-350 to Class 'A" (Style "Z") circuits. The
OCAC-304 is equipped with wire leads to connect to the FX-
350 main board.
Remote Annunciators
;t fVii 1
T
-
PR-300 Polarity Reversal/City Tie Module
The PR-300 provides outputs for city box and polarity reversal
applications. As a city tie module the PR-300 provides an interface
between the control panel indicating circuits and a master box.
As a polarity reversal module the PR-300 provides an interlace
between the control panel and a reverse polarity receiver.
RAM-300LCDR Remote LCD Annunciator
The RAM-300LCDR provides LCD remote annunciation through
a 2 line by 20 character LCD display. The RAM-300LCDR
provides control switches for System Reset, Signal Silence, Fire
Drill and Acknowledge as well as a numeric keypad to access
the menu functions. The common control functions can be
disabled on a per function basis. The RAM-300LCDR has LED
indicators forA.C. On, Alarm, Supervisory, Trouble and CPU Fail.
The RAM-300LCD comes complete with a red enclosure and a
CAT-30 Lock and key.
RAM-1 016/RAM-I 032 Remote LED Annunciators
The RAM-1016 and RAM-1032 Remote LED Annunciator provide
16 or 32 points respectively of LED annunciation. Both models
come standard with bi-coloured LEDs which are automatically
configured for either Alarm (Red) or Supervisory (Amber). The
annunciators have indicators forA.C. On, Common Trouble and
Signal Silence and controls for System Reset, Lamp Test, Fire
Drill, Buzzer Silence and Signal Silence. In addition both models
allow for the control switches to be disabled on a per function
basis. Both models mount in a BB-1001R enclosure.
RAM-208R/RAM-216R Remote LED Annunciators
The RAM-208R and RAM-216R provide 8 or 16 points respectively of LED annunciation.
Both models feature bi-coloured LEDs which are auto-configurable for either Alarm (red) or
Supervisory (amber). The LED annunciators have indicators forA.C. On, Common Trouble
and Signal Silence and control switches for System Reset, Signal Silence, Lamp Test and
Buzzer Silence. The RAM-208R and RAM-216R are equipped with a keyswitch which allows
for enabling and disabling of the Common Control functions. Both models are available in a
red finish and mount in a 4-gang electrical box.
Ordering Information
Model Description
FX-360 Series Intelligent Fire Alarm Control Panels
FX-350-60-DR Single Loop 60 Point Intelligent Fire Alarm Control Panel with built-in UDACT/Digital Communicator
FX-350-126-DR Single Loop 126 Point Intelligent Fire Alarm Control Panel with built-in UDACT/Digital Communicator
FA-300TRB Black semi-flush trim ring for FX-350 Series enclosures
Optional Adder Modules
OCAC-304 Four Indicating Circuit Class 'A' Converter Module PR-300 Polarity Reversal/City Tie Module Remote Annunciators
RAM-300LCDR Remote LCD Annunciator
RAM-1016 16 Zone Remote LED Annunciator
RAM-1032 32 Zone Remote LED Annunciator
BB-1001R Enclosure for RAM-1016 & RAM-1032 Annunciators RAM-208R 8 Zone Remote LED Annunciator
RAM-216R 16 Zone Remote LED Annunciator
NOT TO BE USED FOR INSTALLATION PURPOSES.
I ..
Appendix D: Power Supply and Battery Calculations
Appendix D: Power Supply and Battery Calculations
POWER REQUIREMENTS (ALL CURRENTS ARE IN AMPERES)
Model Number Description I Qty STANDBY TOTAL II ALARM TOTAL
STANDBY ALARM
FX-350-60-R/ Main Panel X 0.200 0.370 =
FX-350-1 26-R
FX-350-60-DR/ Main Panel c/w Dialer X 0.220 = 0.380 =
FX-350-126-DR 11 1
FX-351-LW Main Panel c/wi RAX- x 0.210 = 0.390 (Note 1)
332 LED Displays
Main Panel, c/wi RAX-
FX-351-LDW 332 LED Displays and X 0.230 = 0.400 (Note 1) =
Dialer
RAX-332 32 LED Display
-
X 0.005 = 0.010 =
PR-300 Polarity Reversal and 0.050 = 0.300
City Tie Module
- -
RAM-300- Remote LCD X 0.016 = 0.040 =
LCDW/R Annunciator
RAM-208/216 Remote Annunciator, 8 x 0.0350 = 0.090 = Zone LED 11
Rh-i Remote Trouble x 0.035 = 0.035 = Indicator
MIX-3000 Ionization Detector X 0.00028 = 0.00028 =
MIX-3100 Photoelectric Detector X 0.00034 = 0.00034 =
MIX-3200 Multi-sensor Detector X 0.00047 = 0.00047 =
MIX-3300 Heat Detector X 0.00025 0.00025 =
MIX-lOOP Priority Monitor Module X 0.00060 = 0.00060
MIX-1O1P Mini Priority Monitor X 0.00060 = 0.00060 = Module
Apollo 55000-820 Relay Output Module X 0.00085 = 0.00085
MIX-100S Supervised Control X 0.00100 = 0.00100 = Module
MIX-i OOX (Kit)
100XH (Isolator) Isolator c/w Mounting X 0.000035 0.000035 = Base
100XB (Base)
MIX-2001R Relay Base X 0.000002 = 0.000040
Device LEDs (Maximum 15) - X I
x
I 0.0040 =
Signal Load (bells, horns, strobes, and etc.)
- =
Auxiliary Power Supply for Annunciators, etc. (See Note 2)
Total currents (Add above currents) STANDBY(A) ALARM (B)
continued on next page
MS-71 oiou
Intelligent Addressable
Dual Action Manual Station
ALPHA INTELLIGENT ADDRESSABLE MANUAL STATIONS MS-700IDU SERIES
MS-701 lDU
Intelligent Addressable
Single Action Manual Station
Description
Mircom's MS-7001DU Series provide manual
fire reporting. These high quality, die-cast metal
Intelligent Fire Alarm Manual Stations are available
in either single or dual action configurations with a
permanently attached addressable module.
The MS-7001DU Series stations are available as
single or dual-action devices with key resets and
a permanently attached addressable module . The
addressable manual station has DIP switches which
allow for address setting. Pulling the handle initiates
the operation of the addressable module.
All models are available with CAT-30 keys and mount
on a standard single gang backbox, Mircom model
BB-700 interior surface metal backbox, or BB-700WP
weather proof backbox.
Operation
The MS-7011DU Single Action Intelligent Manual
Station is operated by pulling down the handle marked
"PULL HANDLE" on the front of the station. The
MS-7101DU Dual Action Intelligent Manual Station is
operated by pushing the bar labelled "PUSH BAR"
and then pulling down the handle marked "PULL
HANDLE", The MS-70ClDU Series Manual Stations
are reset by opening the station with the key, placing
the handle in the normal upright position and re-
locking the station.
Features
Single or Dual Action
• Key resettable
Permanently Attached Intelligent Addressable
Module
High-gloss red enamel finish
Plastic breakrod
Meets ADA 5 lb. maximum manual-force
Mounts on standard single gang box, Mircom's
BB-700 surface metal backbox or BB-700WP
weather proof backbox
Specifications
The manual station shall be Mircom's MS-700IDU
Series. Operating instructions shall be in raised
English lettering and the unit shall be constructed
of high quality die-cast metal and finished in red
enamel paint to provide quick identification. Pulling
the handle shall initiate immediate operation of the
intelligent addressable module.
All manual fire alarm stations shall be installed as per
the specific requirements outlined in the UL codes,
as well as all other applicable national or local codes.
Final acceptance is subject to the local authority
having jurisdiction.
X@@
7150-1477:128 S7005 S7005
I
I
I
I
I
I
I
I
I
I
I
I
I
I
CATALOG NUMBER SPA w W U W NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any lime without notice in prices, colours, materials. components, equipment. specifications and models and also to discontinue models.
I
Specifications
Switch Rating: 1 Amp @ 30 VDC
0.1 Amp @ 125 VAC
Manual Station Dimensions: 4.9 H x 3.5" W x 2.0 D
Color: Red with raised white letters, white Manual bar with raised red letters.
Surface Mount Backboxes
BB-700 Surface Mount
Backbox
Dimensions:
5" H x 3.6W x 2.0 D
BB-700WP Weatherproof
Surface Mount Backbox
Dimensions:
5" H x 3.6" W x 2.2" D
Typical Wiring Diagram
MS-7011DU and MS-7101DU
I
I
1
I
I U
Ordering Information
MS-701 IOU Alpha Intelligent Addressable Key Resettable Single Action Manual Station
MS-71010U Alpha Intelligent Addressable Key Resettable Dual Action Manual Station
BB-700 Series 700 Interior Surface Mount Backbox, Red Finish
BB-700WP Series 700 Weatherproof Surface Mount Backbox, Red Finish
I NOT TO BE USED FOR INSTALLATION PURPOSES.
- MIRcQ
I Canada U.S.A.
25 Interchange Way 60 Industrial Parkway Vaughan, Ontario 1.4K 5W3 Cheektowaga, New York 14227
Telephone: (905) 660-4655 Toll Free: (888) 660-4655
I Fax: (905) 660-4113 Fax Toll Free: (888) 660-4113
Web nen •. uIIlI(I(IIII.U(fl.cUUl . CAT. 5679 ISO 9OO120O0 (2t Rev 0 REGISTERED
I
ALPHA INTELLIGENT ADDRESSABLE DETECTORS MIX-3000 SERIES
MIX-3000 MIX-3100
Ionization Smoke Detector Photoelectric Smoke Detector
MIX-3200 MIX-3300
Multi-Sensor Detector Thermal Detector
Description
Mircom's Alpha Series Intelligent Addressable
Detectors are designed to meet a wide range
of applications. The detectors address is set in
its base providing a convenient and trouble free
maintenance procedure. The detectors mount into a
selection of base styles to accommodate installation
requirements.
Intelligent Ionization Smoke Detector (MIX-3000)
The Ionization smoke detector incorporates a
unique dual chamber design to respond quickly and
dependably to a broad range of fires. The ionization
detector is equipped with a red LED which flashes
when the detector is polled and turns on steady when
the detector goes into alarm. (UL Listed)
Intelligent Photoelectric Smoke Detector (MIX-3100)
The Intelligent photoelectric smoke sensor utilizes
a unique optical sensing chamber that is designed
to sense smoke produced by a wide range of
combustion sources. The photoelectric detector
is equipped with a clear LED which flashes when
the detector is polled and turns on steady when the
detector goes into alarm.
Features
Low profile design
For use with the FX-350 Series Fire Alarm Control
Panels
Fast response time
Automatic addressing with the MIX-ADD card
Variety of mounting bases
Ease of installation
Elegant, unobtrusive design
Digital communications
Intelligent Multi-Sensor Detector (MIX-3200)
The Intelligent Multi-Sensor Detector is a photoelectric
smoke detector with a supplementary thermal sensor.
The Multi-Sensor detector combines photoelectric smoke
and thermal sensor values to provide enhanced detection
performance and reduction of false alarms. Information
from each sensing element is processed and conditioned
by an on-board advanced technology ASIC and digitally
transmitted to the FACP as a single analog value
comprised of the combined responses from both the
photoelectric smoke and thermal detection elements.
Intelligent Thermal Detector (MIX-3300)
The Intelligent Thermal Detector utilizes state of the art
electronic temperature sense to provide fast and accurate
temperature monitoring. The thermal detector features
an adjustable termperature range that is configured from
the FX-350 Series fire alarm control panel.
0 & @
S6295 S6965 7271.1477:138 (MIX-3000, MIX-3100 (MIX-3100 (MIX-3000) 4 MIX-3200) & MIX-3200) 7272-1477:131
(MIX.3 100) S6299 S7498
7272-1477:142 (MIX-3300) (MlX.3300
727
0,
1477:139 CATALOG NUMBER
t..
w i NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models,
I
MIX-ADD Address Card
A unique, patented addressing method provides simple, user friendly and accurate
identification of the detector location. AcodedMlX-ADD card is inserted in the base. This
can then be read by any Alpha Series detector once it is plugged in. Using this method,
all the electronic components are in the detector but the location information is held in
the base. The MIX-ADD card simplifies and speeds up installation and commissioning.
Addressing errors during maintenance and service are eliminated.
Specifications
General Specifications
16-28 VDC
fbn Class A (Style D) or Class B (Style B)
switch selectable
0% to 95% (No condensation or icing)
MIX-3000 Ionization Detector
280 pA
4 mA
MIX-3100 Photoelectic Detector
340 pA
4 mA
Ordering Information
0°F to +155°F (-20°C to +70°C) mperre. ' ,
?H{ i°Cr dUg White Polycarbonate
MIX-3200 Multi-Sensor Detector
470 pA
Jo 4 mA
MIX-3300 Thermal Detector
d 250 pA
4 mA
*F *C 131'F to 194 (55 to 90 C)
NMI
MIX-3000 Intelligent Addressable Ionization Smoke Detector (UL Listed)
MIX-3100 Intelligent Addressable Photoelectric Smoke Detector
MIX-3200 Intelligent Addressable Multi-Sensor Detector
MIX-3300 Intelligent Addressable Thermal Detector
MIX -ADD Address Card for MIX-3000 Series Intelligent Detectors
NOT TO BE USED FOR INSTALLATION OURPOSES.
- 4h MRCOM
I Canada U.S.A. 25 Interchange Way -60 Industrial Parkway, PMB 278 Vaughan, Ontario L4i< 5W3 Cheektowaga New York 14227 Telephone: (905) 660-4655 Toll Free: (888) 6604655
I Fax: (905) 660-4113 Fax Toll Free: (888) 660-4113
Web page: http://www.rnircorn.corn Email: mail@mircom.com
ISO9001,2000 CAT. 5676
REGISTERED Rev. 0
AL PHA iINTELLIGENT A.1') *1: UE MODULES 'i I P6 LsI'ISERIES
.' . -• ' '
EU-11 711
n *11
.-.------
MIX-lOOP
MIX-100S
Features
Designed to meet a wide range of applications
For use with the FX-350 Series Fire Alarm Control
Panels
Fast response time
Priority Interrupt feature on monitor modules
Monitor modules can be wired as a Class A (Style
D) or Class B (Style B)
Each module can be addressed from I to 126
Eight position dip switch for address setting
Red light indicator
Modules mount in standard 4" junction box
I
I
I
MIX-1O1P
I
I
I
I Description
Mircom's Alpha Series Intelligent Addressable
Modules are designed to meet a wide range of
applications. The monitor and control modules can
be used to supervise and activate sounders, strobes,
door closers, pull stations, waterfiow switches,
conventional smoke detectors and more. An eight
position dip switch allows for the address setting of the
device and the wiring class/style of the devices that
are connected to the module. All modules mount in
a standard 4" x 4" x 2 1/8" junction box.
Intelligent Addressable Priority Monitor Module
(MIX-1 OOP)
The Intelligent Addressable Priority Monitor Module
(MIX-loop) provides an address for a group of UL/
ULC Listed normally open (NO.) initiating devices,
such as heat detectors, beam smoke detectors, 4-
wire smoke detectors, waterflow switches, manual
pull stations, etc. wired in a Class A (Style D) or
Class B (Style B) initiating circuit. The MIX-100P
is equipped with a priority interrupt to provide a fast
response to emergency conditions. The MIX-100P
has an activated red LED.
Intelligent Addressable Priority Mini-Monitor
Module (MIX-101P)
The Intelligent Addressable Priority Mini Monitor Module
provides an address for a group of UL/ULC Listed
Normally Open (NO.) initiating devices, such as heat
detectors, projected beam smoke detectors, 4-wire
smoke detectors, waterfiow switches, manual pull
stations, etc. wired in a Class A (Style D) or Class B
(Style B) initiating circuit. The MIX-101P is equipped
with a priority interrupt to provide a fast response
to emergency conditions. The MIX-101P has an
activated red LED.
Intelligent Addressable Single Relay Output
Module (55000-820)
The Intelligent Addressable Single Relay Output
Module connects to the same loop as the initiating
devices and provides one Form-C contact to control
a variety of normally open or normally closed
contact applications cuch as fan operation and door
closures.
14@@
7150-1477:156 S5434 S5434
I
I
1
I
I
I
I
CATALOG NUMBER 4979
NOT TO BE USED FOR INSTALLATION PURPOSES,
Mircom reserves the right to make changes at any time Without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
I
MiRCOM
I Canada U.S.A.
25 Interchange Way 60 Industrial Parkway, PMB 278
Vaughan, Ontario L4K 5W3 Cheektowaga, New York 14227
Telephone: (905) 660-4655 Toll Free: (888) 660-4655 I Fax: (905) 660-4113 Fax Toll Free: (888) 660-4113
Web page: http:/tw'ww.mircom.com
I
Email: mail@mircom.com
Distributed by:
1509001:2000 CAT. 5675
REGISTERED -GM Rev. 0
Intelligent Addressable Supervised Control
Module (MIX-100S)
The MIX-100S Control module provides supervised
monitoring of wiring to signal devices that require
an external power supply to operate, such as horns,
strobes, bells or speaker isolators. Conventional
signals will require a 24 VDC power source and
speakers will require an audio input. The red LED will
illuminate when the module is activated. The module
is capable of Class A (Style Z) or Class B (Style Y)
supervision.
Specifications
General Specifications
16-28 VDC
Zt Class A (Style 0) or Class B (Style B)
switch selectable
0% to 95% (No condensation or icing)
MIX-1 OOP and MIX-101P
i •'.ga°.-4-°.•,'rr . -. . 600 pA
larCurit " 4 mA (LED on)
Djmenslons' . -.
"
MIX lOOP 40 Wx40 Hx13 D
MIX -101P 30 Wx20 Hx075 D
Welght ,,, I
MIX -100P
MIX 101P
3.0 oz. (858g)
1.5 oz (42.6g.)
Fault Isolator Module (MIX-bOX)
The MIX-bOX Fault Isolator Module is used to
protect the system against wire-to-wire short circuits
on the analog loop. The modules should be spaced
between groups of sensors or modules in a loop to
protect the rest of the loop. In the event of a short
circuit between any two fault isolator modules,
both modules immediately switch to an open circuit
condition and isolate any group of sensors between
them. The remaining units on the circuit will continue
to operate in a normal fashion (must be wired in Class
A or Style 6).
0°F to +155°F (-20°C to +70°C)
ernptuSe i
is 47
White Potycarbonate
MIX-100X
35pA at 24V
LlnoCu,rent 1 Amp
tjR 0.2 ohm
40 Wx4 0 H xl 3 D
3.0 oz (85.8g)
MIX-100S
1 mA
-. Signals 24 VDC regulated Source,Power
xll l Speakers 70.7 V RMS M N
tins ' 2A c 3OVDC 0.6A @ 125VAC
Dmenslons -,!. 40 Wx40 Hx1 3 0
3.0 oz. (858g)
Ordering Information
MIX-lOOP Intelligent Addressable Priority Monitor Module
MIX-101P Intelligent Addressable Priority Mini Monitor Module
MIX-100S Intelligent Addressable Supervised Control Module
MIX-100x Fault Isolator Module
55000-820 Intelligent Addressable Single Relay Output Module
- NOT TO BE USED FOR INSTALLATION PURPOSES.
ZNH-R Red 0300 ZNH-W White 0301
Wall Mount Horn Strobe
ZNS-MCW-FR Red 0304
ZNS-MCW-FW White 0305
ZNS-MCWH-FR Red 0306
ZNS-MCWH-FW White 0307
Ceiling Mount Horn Strobe
ZNS-MCC-FW White 0311
ZNS-MCC-FR Red 0310
ZNS-MCCH-FW White 0313
ZNS-MCCH-FR Red 0312
UL Max. Current 15cd 30cd 75cd llOcd
High (95) dBA 24 VDC. 0 0.244
Low (90) dBA 24 VDC 0.066 0.101 0.177 0.232
UL Max. Current 15cd 30cd 75cd 95cd
High (95) dBA 24 VDC 0.082 0.124 0.209 0.275
Low(90)dBA 24 VOC 0.071 0.114 0.201 0.261
UL Max. Current UL Max. Current Audible
ll5cd 177cd
------------
24 VDC 12 VDC
High (95) dBA 0.350 0.477 High (95) dBA 0.044 0.021 Low (90) dBA 0.306 0.429 Low (90) dBA 0.018 0.012
(800) 631-2148 www.cooperwheelock.com
I
1
I
p
I 1-2 09/06
Features,ane.asy: snaponbase designed 1, Strobes to simlifytri&Snstallàtion and testing of strobes, horns and horn strobes.
Available features and options:
Color: Red or white
Mounting: Wall or ceiling
EZ mount SNAP design
Universal mounting plate - single
plate for wall and ceiling mount in-
stallations
Disposable cover to protect base
plate
Strobes produce 1 flash per sec-
ond over the Regulated Voltage
Range
[I
Wall Mount Strobes
ZRS-MCW-FR Red
ZRS-MCW-FW White
ZRS-MCWH-FR Red
ZRS-MCWH-FW White
Ceiling Mount Strobes
ZRS-MCC-FW White
ZRS-MCC-FR Red
ZRS-MCCH-FW White
ZRS-MCCH-FR Red
UL Max. Current l5cd 30cd 75cd 110cd 4085 ..
24 VDC 0.060 0.092 0.165 0.220
5242 ................................
0303 UL Max. Current 135cd 185cd
-.
24 VDC 0.300 0.420
0309
0308 UL Max. Current 15cd 30cd 75cd 95cd
0314 .
:yp.c.. 0.249 5240
UL Max. Current 115cd 177cd
24 VDC 0.300 0.420
Horns and Horn Strobes
Wall or Ceiling Mount Horn
DH( )GC1
Electromagnetic
Fire Door Holders
OH Series
DH( jFPC
IPowdercoated)
RSG
3300 E. 59th St.
Long Beach, CA 90805
P: (562) 529 5,100
F: (562) 529 5102
www. rsgsecurity.corn
Description: OH series fire door holders are constructed of the finest materials and workmanship available. The door holder is
made of durable die-cast metal and offered in a high luster plated or powdercoated finish.
Other features include standard dual voltg ac ur dc inputs of 12 & 24V, 24 & 120V and 24 & 220V models, While reducing
stocking requi(ements, model 24120 draws a rnern 020 ma @24V00 lowering overall job costs in large installations the cost
savings can be substantial).
Other features: single or double coil floor mourning, surface mounting and direct wall mounting. No brackets are required. The
OH series door holder offers a new installation technique using an adhesive template assuring alignment without secondary
adjustments.
Accessories include extension and misalignment rods (various lengths) enabling parallelism between door and wall at distances
greater than 12 inches and misalignment over 4 inches.
I Aiding in installation is the aircraft quality OH drill that reduces installation time and provides a near perfect alignment of
catch-plate and armature - again, lowering overall installation costs.
I Basic units offer supetior holding force and low residual magnetism, Models 1224 arid 24120 can operate at higher listed
voltages producing hotding forces in excess of 10bs. (45.3kg.) For special applications.
Extension Rod . ' I Dual Voltage
Applications ' (re.aiw riw) hi\
I IL
4
.
,... / •'\"\
V 2.
MADE r Tj I ( 1)) \ AMLKA
U - .--------- - - - -
OPTLOf'IALFEATURES TANDARD FEAiuRES
PLATEDORPOWDERCOATEO rINISH VERY LOW CURRENT DRAW
Db DUAL VOLTAGE lrpuT$.
EXTENSION AND MISALIGNMENT RODS TERMINAL BLOCK CONNECTlONSf SURFCE1MOUNT BACKtBOX HIGH HOLDtNGFpRCE 1"
TIME 'DRILL FIXTURE. LOWRESIDUAL.'MAGNETlSM I (FOR MOUNTING CATCH PLA'rC) DOUBLE CHROMEPLATING
- . ..' . MOUNTING ARDWARE&INSTRJGoSJL4
---------
Surface Mounting:
DHBB (back box)
0
3I.
PERFORMANCE DATA:
MODEL VOLTAGE DC/mA AClmA Terminals LB. KG.
1224 12V 40 38 C&L 30 13.6
24V 40 36 C&H 30 13.6
24V 20 19 C&L 40 16.1 24120 120V -- 20 C&H 35 15.8
24420 24V 20 19 C&L 40 181
220V ---- 15 C&H j 25 1 11.3
NOTE: Holding forces listed in above table Correspond WIfl shaded
values, non shaded values are slightly less.
MODEL VOLTAGE DClmA AC/ijiA Terminals LB. KG.
1,224 24V 85 5' C&L 75 34.0
24120 120V .100 110 49.8
HIGH HOLDING FORCESPECLAL ,APPLICKHOI'IS.
To obtain pei'formance values in table above apply hgh listed voltage to low
voltage terminals (C & Li
NOTE: This configuration can only be applied to models 1224 & 24,120
ACCESSORIES
ORDERING INFORMATION:
DH = 0o(* Holder
F = Flush Mount
S = Surface Mount
R Recessed
G Ground Mount
P Powdercoated
C = Chrome Plating
B 7= Brass Plating
1 = Single Coil
2 = Double Coll
NOTE: #2 indicates double Coil ground
mount model,
Example DH 24120) (S) (P) (C) (1)
Door holder
Mode.liVoltaqe
12-24,24120.24220
Mount Style
Surface. Flush. Ground, Recessed
Powc$ercoated
Brass
I
I
I
I
I
I
I
I
I
I
I
I
I
I
Extensions:
Extension rods
:
I I
i4
Extension :---
Wre'rtches
Installation Tools:
DHDF (drill,fixture)
I
•
-4~
U
I
1,2
ACCESSORIES:
Extensions:
DHE1C 1 inch extension chrome.
DHE1B 1 inch extension brass.
DHE15C 1-1/2 inch extension chrome.
DHE158 1-1/2 inch extension brass.
DHE2C 2 inch extension chrome.
DHE28 2 inch extension brass.
DHE3C 3 inch extension chrome,
DHE3B 3 inch extension brass.
DHEAC 4 inch adjustable extension
chrome.
DHEAB 4 Inch adjustable extension
brass.
Hardware:
OHCPC Catch plate asseb1y'
DHGPB
chrome,
Catch plate asseipjt)4y brass
DHDC Catch disc
DHDB Catch
DHBBC
DHBBB
DHW
DHDF ' tJpitlg ture'r
MD-815 FX-350/FX-351 Mainboard - with Dialer
MD-837 FX-350/FX-351 Mainboard - No Dialer
MD-749 DSP Core Board
MD-819 Power Supply Board
PR-300 City Tie/Polarity Reversal
TR-061 120/240 VAC Transformer
CH-613 FX-350 Backbox
CH-641 FX-350 Door
CH-642 FX-350 Deadfront
CH-643 FX-351 Deadfront
CH-644 FX-351 Door
CH-645 FX-351 Backbox
MD-825 RAX 232
RAM-300-LCD Remote LCD Annunciator
MIX-3000 Addressable Ion Smoke Detector (CSFM# 7271-1477:138)
MIX-3100 Addressable Photoelectric Smoke Detector (CSFM# 7272-1477:131)
MIX-3200 Addressable Photo/Heat Detector (CSFM# 7272-1477:142)
MIX-3300 Addressable Heat Detector (CSFM# 7270-1477:139)
MIX-2000-2001 Standard Base (CSFM# 7300-1477:145)
MIX-2001 R Standard Base with Relay (CSFM# 7300-1477:145)
MIX-lOOP Priority Monitor Module
MIX-1O1P Mini Priority Monitory Module
MIX-loos Supervised Control Module
MIX-bOX Isolator Kit
120 VAC, 60Hz
240 VAC, 50 Hz
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7165-1477:156 Page 1 of 2
CATEGORY: Control Unit (Non High-Rise)
LISTEE: Mircom Technologies Ltd., 25 Interchange Way, Vaughan, Ontario, Canada L4K 5W3
Contact: Mara Cherubin (888) 660-4655 FAX (888) 660-4113
DESIGN: Models FX-350-60-R, FX-350-60-DR, FX-350-1 26-R, FX-350-1 26-DR, FX-351 -LW and
FX-351-LDW fire alarm control units. Local, auxiliary, remote station (PPU), central
station (PPU), waterflow and sprinkler supervisory services. Refer to the listee's data
sheet for detailed product description and operational considerations. System components:
I
I
I
I
I
I
I
I
I
I
I
I
I
RATING
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as fire alarm control units for use with listee's separately listed electrically and
functionally compatible initiating and indicating devices as indicated in design. Refer to
listee's Installation Instructions Manual for details. These control units can generate a
distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in
accordance with NFPA 72, 2002 Edition.
I
I
I
L
111
I
I
I
Page 2 of 2
7165-1477:156
NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
This control panel meets the requirements of UL-864, 9 Edition.
05-23-2007 iw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JULY 17, 2007 Listing Expires June 30, 2008
Authorized By: MIKE TANAKA, Senior Deputy State Fire Marshal
Program Manager
I LISTING No.
I CATEGORY:
LISTEE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7150-1477:128 Page 1 of 1
Boxes/Pull Stations
Mircom Technologies Ltd, 25 Interchange Way, Vaughan, Ontario, Canada L4K 5W3
Contact: Mara Cherubin (888) 660-4655 FAX (888) 660-4113
DESIGN: Models MS-701U,-703U, 704U,-710U. -713U, -714U, 7O1ADU, -71 OADU, -702U, -7O2ADU,
-701UP, -710UP, -703U(C), -704U(C), •713U(C), -714U(C), -705U, -715U,-706U(C), -
716U(C), -707U(C), -717U(C) and *..708 fire alarm boxes. These devices are manually
actuated, single or dual action non-coded, fire alarm boxes. Units are to be mounted on
standard outlet boxes or listee's Model BB-700 backbox for indoor use only and BB-700WP
backbox for indoor and outdoor use.
*Models MS- 7011D(U), -7021D(U) and -71010(U) non-coded, indoor use only, fire alarm
boxes. To be mounted on three-inch deep outlet boxes.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING: 30VDC, 1A, 125 VAC, 1A
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, rating, and UL label.
APPROVAL: Listed as fire alarm manual pull stations for use with separately listed compatible fire alarm
control units. Refer to listee's Installation Instruction Manual for details.
*Rev. 04-22-2007 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 27, 2007 Listing Expires June 30, 2008
Authorized By.. MIKE TANAKA, Senior Deputy State Fire Marshal
I
Program Manager
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
I
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7272-1477:142 Page 1 of 1
CATEGORY: Photoelectric Smoke Detector
LISTEE: Mircom Technologies Ltd 25 Interchange Way, Vaughan, Ontario Canada L4K 5W3
Contact: Mara Cherubin (888) 660-4655 FAX (888) 660-4113
DESIGN: Model MIX-3200 photoelectric type smoke detector. Unit employs an integral
supplemental heat sensor and is not intended for use as a required heat detector. Refer to
listee's data sheet for detailed product description and operational considerations.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm
control units and listed Models MIX-2000 Series detector bases (CSFM Listing No. 7300-
1477:145). Refer to listee's Installation Instruction Manual for details.
NOTE: The photoelectric type detectors are generally more effective at detecting slow,
smoldering fires that smolder for hours before bursting into flames. Sources of these fires
may include cigarettes burning in couches or bedding. The ionization type detectors are
generally more effective at detecting fast, flaming fires that consume combustible
materials rapidly and spread quickly. Sources of these fires may include paper burning in
a waste container or a grease fire in the kitchen.
XLF 7272-1394:113
04-06-2005
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 27, 2007 Listing Expires June 30, 2008
Authorized By: MIKE TANAKA, Senior Deputy State Fire Marshal
Program Manager
I LISTING No.
I CATEGORY
LISTEE:
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
7300-1394:108 Page 1 of 1
Misc. Devices/Control Unit Accessories
*Apollo Fire Detectors Ltd, 36 Brookside Road, Havant, Hampshire, P09 1JR, England
*Contact: Gordon Ash +44(0)23 9249 2412 FAX +44(0)23 9249 2754
DESIGN: *XP95A analog addressable signaling/contact monitoring modules. Model 55000-805
switch monitor module, Model 55000-806 priority switch monitor module, Model 55000-
820 switch monitor input-output module. Model 55000-825 sounder control module, Model
55000-830 mini priority switch monitor module and Model 55000-831 mini switch monitor
module. Refer to listee's data sheet for additional detailed product description and
operational considerations.
RATING: *Electrical: 17 to 28 VDC, 5 to 9 V protocol
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as monitoring modules for use with separately listed compatible fire alarm control
units. Refer to listee's Installation Instruction Manual for details.
Rev. 06-20-03KK
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:, JUNE 8, 2007 Listing Expires June 30, 2008
I Authorized By: MIKE TANAKA, Senior Deputy State Fire Marshal
Program Manager
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
I OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
I
LISTING SERVICE
LISTING No. 7135-0785:150 . Page 1 of 1
CATEGORY: Audible Devices
I LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Luy Nguyen (732) 433-6005 Fax (732) 222-5607
I DESIGN: Models MIZ-TC12, MIZ-TC24, *M1Z12S and *MIZ 24S electronic horns. Refer to listee's
data sheet for additional detailed product description and operational considerations.
RATING: MlZ-TC12, *M1Z12S = 12V Nominal, 8-17.5V DC, 17mA max.
MlZ-TC24, *Mlz24S = 24V Nominal, 16-33V DC, 24mA max.
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
I APPROVAL: Listed as audible devices for use with separately listed compatible fire alarm control units.
*For indoor use only. Models MIZ-1 2S and MIZ-24S are suitable for synchronization when
used in conjunction with Models SM-12/23, SMX-12/24, DSM-12/24, DSMX-12/24 (CSFM
I Listing No. 7300-0785:132) Sync Control Modules. Refer to listee's Installation Instruction
Manual for details.
These units can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation
I Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
I Rev 06-13-06
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 4, 2007 Listing Expires June 30, 2008
Authorized By: MIKE TANAKA, Senior Deputy State Fire Marsha/
Program Manager
I
I
I
I
I
I
I
I
I
I
I
I
I
1
I
I
I
I
I
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:142 Page 1 of 1
CATEGORY: Fire Alarm Devices for the Hearing Impaired
LISTEE: Wheelock Inc. 273 Branchport Ave., Long Branch NJ 07740
Contact: Luy Nguyen (732) 433-6005 Fax (732) 222-5607
DESIGN: Models NH-12/24, NH-12/24R, and *ZNH horns and Models NS-1215W, NS-121575W,
NS-2415W, NS-241575W, NS-2430W, NS-2475W and NS-24110W; NS4-1215W, NS4-
121575W, NS4-241 5W, NS4-241 575W, NS4-2430W, NS4-2475W and NS4-241 lOW,
NS-24MCW, NS4-24MCW, NS-24MCC, NS-24MCCH, *ZNSMCW *ZNSMCC *zNs
MCWH and *ZNSMCCH horn strobes. Model number may be followed by any two-
alpha/numeric characters indicating lens, lettering and color. Units are synchronized or
non-synchronized strobes. Models NH-12/24R, NS-24MCC, NS-24MCCH, *ZNS MOO
and 'ZNS MCCH are ceiling mount only. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: Electrical-Strobe Horn: 8-17.5 VDC/FWR and 16-33 VDC/FWR
Horn: 8-17.5 VDC/FWR and 16-33 VDC/FWR
Candela: 15=15cd, 1575=15/75cd on axis, 30=30cd, 75=75cd, 110110cd (Wall)
NS-24MCW, NS4-24MCW, *ZNS..MCW: Selectable 15cd, 30cd, 75cd, 110cd *NS24MCC *ZNSMOO: Selectable 15cd, 30cd, 75cd, 95cd
*NS24MCCH *ZNS.MOOH: Selectable 115cd, 177cd
*ZNSMCWH: Selectable 135cd, 185cd
Flash rate: 60 Flashes/minute
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction. *All units are for wall mount only.
MARKING: Listee's name, model number, electrical/candela rating and UL label.
APPROVAL: Listed as audible and audible/visual signaling devices for use with separately listed
electrically compatible fire alarm control units. Models with strobe lights are suitable for
the hearing impaired. For indoor use only except for model NH-12/24 horn. All
synchronization strobes shall be used with Models SM-12124, SMX-12/24, DSM-12/24 or
DSMX-12/24 Sync Control Module (CSFM Listing No. 7300-0785:132). Refer to
manufacturer's installation manual for details.
NOTE: These appliances can produce a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
Rev. 12-13-2006 jw
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or / recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 4, 2007 Listing Expires June 30, 2008
Authorized By.. MIKE TANAKA, Senior Deputy State Fire Marsha/
Program Manager
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:141 Page 1 of 1
CATEGORY: Fire Alarm Devices for the Hearing Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Luy Nguyen (732) 433-6005 Fax (732) 222-5607
DESIGN: Synchronized or non-synchronized Strobe Lights. Models are as follows:
RSS-##W RSSP4#W RSS-##C RSSP-##C RSS-##CR RSSP-##CR
2415 2415 2415 2415 2415 2415
2475 2475 2430 2430 2430 2430
241575 241575 2475 2475 2475 2475
2430 2430 *2495 *2495 *2495 *2495
24110 24110
1215 1215
121575 121575
Also, Models RSS-24M0W and RSSP-24MCW, RSS-24MCC, RSS-24MCCR, RSSP-
24MCC, RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, RSS-24MCCH, RSS-
24MCCHR, RSSP-24MCCH, *ZRSMCC *ZRSMCW *ZRS.MCCH and *ZRS..MCWH
Model numbers may be followed by any two alpha/numeric character indicating lens
orientation, lettering and color. Refer to listee's data sheet for additional detailed product
description and operational considerations.
RATING: Electrical 12 = 8-17.5VDC/FWR OR 24 =16-33VDC1FWR
Candela 15=5cd, 1575=15/75cd on axis, 30=30cd, 75=75cd, 110=110cd (Wall)
RSS-24MCW, RSSP-24MCW, *ZRS MOW: Selectable 15cd, 30cd, 75cd
or ll0cd
RSS-24MCC, RSS-24MCCR, RSSP-24MCC, *ZRSMCC: Selectable
15cd, 30cd, 75cd and 95cd
RSS-24MCWH, RSS-24MCWHR, RSSP-24MCWH, *ZRSMCWH:
Selectable 135cd, 185cd
RSS-24MCCH, RSS-24MCCHR, RSSP-24MCCH, *ZRSMCCH:
Selectable 115cd, 177cd
Flash rate 60 flashes/minute
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction. Models with
suffix -W, wall mount only. Models with suffix -C, ceiling mount only. All models are for
indoor use only.
MARKING: Listees name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as strobe light suitable for the hearing impaired when used with separately listed
electrically compatible fire alarm control units. For synchronization strobes, Models SM-
12/24, SMX-12/24, DSM-12/24 or DSMX-12/24 Sync Control Module (CSFM Listing No.
7300-0785:132) must be used. Refer to listee's Installation Instruction Manual for details.
*Rev. 12-13-20061w
11 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued:
Authorized By
JUNE 4, 2007 Listing Expires June 30, 2008
MIKE TANAKA, Senior Deputy State Fire Marshal
Program Manager
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7125-0785:131 Page 1 of 2
CATEGORY: Fire Alarm Devices for the Hearing-Impaired
LISTEE: Wheelock Inc., 273 Branchport Ave., Long Branch NJ 07740
Contact: Luy Nguyen (732) 433-6005 Fax (732) 222-5607
DESIGN: Models AS-1215, -2415, -1230, -2430, -121575, -241575, -2475 and -24110 audible/strobes for
the hearing impaired followed by any three alpha/numeric characters indicating lens
orientation, lettering and color.
Models AS-1215W, -2415W, -1230W, -2430W, -121575W, -241575W, -2475W and -24110W
audible/strobes for the hearing impaired followed by any three alpha/numeric characters
indicating lens orientation, lettering and color. These units with suffix -W are for wall mount
only.
Models AS-2415C, -2430C, -2475C and -24100C audible/strobes for the hearing impaired
followed by two alpha/numeric characters indicating lens lettering, orientation and color. These
units are intended for ceiling mount only.
Model AH-12, -24, AH-12WP, -24WP audible appliances (no strobe), followed by an alpha or
numeric character indicating product color.
Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric
character indicating lettering and product color.
Model ASWP-2475W audible/strobe with integral private mode fire/emergency visual signaling
for non-hearing impaired applications. Model ASWP-2475W is also suitable for outdoor use
when mounted to Model WPBB back box.
Models AS-24MCWH and AS-24MCCH audible/strobes for the hearing impaired followed
by two alpha/numeric characters indicating lens lettering and product color. Units with
suffix C are for ceiling mount only. Units with suffix W are for wall mount only.
Refer to the listees data sheet for detailed product description and operational considerations
RATING: Electrical: 8-17.5/16-33 VDCNFR
Candela: 15:15cd, 1575:15/75cd, 30:30cd, 75:75cd, 95:95cd, 100:100cd, 110:110cd
MCW: Selectable 15cd, 30cd, 75cd, 110cd
MCC: Selectable 15cd, 30cd, 75cd, 95cd
MCWH: Selectable 135cd, 185cd
MCCH: Selectable 115cd, 177cd
INSTALLATION: In accordance with listees printed installation instructions, applicable codes and ordinances and
in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W and AS-
24MCW are for wall mount only. Models with suffix -W are for wall mount only. Models with
suffix -C are for ceiling mount only.
I Rev. 06.13-06
I
I
I
I
I
I
I
I
I
I
Listing No. 7125-0785:131
Page 2 of 2
I MARKING: Listee's name, model number, electrical/candela rating, and UL label.
I
APPROVAL: Listed as audible and audible/visual signaling devices suitable for the hearing impaired when used
in conjunction with separately listed electrically compatible fire alarm control units. For indoor use
only except Models AH-1 2WP and AH-24WP audible appliances are suitable for indoor/outdoor.
For synchronization, Models AS Series must be used with Model SM-12/24, SMX-12/24, DSM-
U
12/24 or DSMX-12/24 sync control module (CSFM Listing No. 7300-0785:132). Refer to listees
Installation Instruction Manual for details.
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE: Models ASWP-2475W, AH-12, AH-24, -12WP and -24WP audible devices are not suitable for
the hearing impaired applications.
I
I
I
I
Ii
I
I
I
1
*Rev. 06-13-06
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
'+ recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 4, 2007 Listing Expires June 30, 2008
Authorized By: MIKE TANAKA, Senior Deputy State Fire Marshal
Program Manager
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 3550-1039:100 Page 1 of 1
CATEGORY: Door Closer/Holders/Releasing Devices
LISTEE: RSG, 3300 E. 59th St. Long Beach CA 90805
Contact: Louis Finkle *(562) 630-4684 FAX (562) 529-5100
DESIGN: Models DH-1 2, -24, -120, -1224,-24120, and -24220 door closer/holders. Refer to listee's data
sheet for additional detailed product description and operational considerations.
RATING: 12V, 24V, 120V, and 220V
INSTALLATION: In accordance with listees printed installation instructions and applicable codes and ordinances.
The system is intended to be mounted in a horizontal position only.
MARKING: Listee's name, model number, rating and UL label.
APPROVAL: Listed as door closer/holders for use with separately listed compatible detectors and fire alarm
control units.
Rev. 06-13-2003
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listees data sheet, installation instructions and/or other suitable information sources.
Date Issued: JUNE 1, 2007 Listing Expires June 30, 2008
Authorized By: MIKE TANAKA, Senior Deputy State Fire Marshal
Program Manager