HomeMy WebLinkAbout2653 GATEWAY RD; ; AS090088; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS090088
Job Address: 2653 GATEWAY RD
Permit Type: SPRINK
Parcel No: 2131911900
Lot #: 0
Reference No.:
PC #:
Status: ISSUED
Applied 7/31/2009
Approved: 7/31/2009
Issued: 7/31/2009
Inspector:
Project Title: TWIG HAIR LOUNGE T.I. FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant: Owner:
Fees ($) Add'l Fees ($) Total ($) Balance ($)
130 0 130 0
AS OO'OU
Material Data Submittal
Twig Hair Lounge
2653 Gateway Road, Suite 104
Carlsbad, CA 92008
Jul -30 09 10:49a AAR Fire Sprinklers 16194454052 p-S
tqcal F/re & Building
Products
Technical Services: Tel: (800) 381-93121 Fax: (800) 791-5500
Series TY-FRB— 2.8, 4.2, 5,6, and 8,0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the 'INSTALLER
WARNING' that provides cautions
with respect to handling and instal-
lation of sprinkler systems and corn-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a tire situation or cause
it to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tänt coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their tire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers•
1Y1131 - Upright 2.8K, 1/2"NPT TY1231 - Pendent 2.8K, 1/2"NPT
Ff2131 - Upright 41K, 1/2"NPT
TY2231 - Pendent 4.2K, 1/2"NPT
TY3131 - Upright 5.6K, 1/2"NPT
TY3231 - Pendent 5.6K, 1/2"NPT
Ff4131 - Upright 8.01K, 3/4'NPT
Ff4231 - Pendent 8.01K, 3/4"NPT
TY4831- Upright 8.0K, 1/2"NPT
TY4931- Pendent 8.0K, 1/2"NPT
Page 1 of 10 AUGUST, 2007 TFPI7I
I ESCUTCHEON I PLATE SEATING
SURFACE 112 NPT
I I (57,2 mm)
7116(11,1 mm)
NOMINAL
MAKE-IN
Jul-30 09 10:50a AAA Fire Sprinklers 16194454052 p.7
Page 2 of 10 TFPI7I
STYLE 10 or 20
RECESSED SSU*
ESCUTCHEON DEFLECTOR
(11 1,11 mm) I
FRATS
NOMINAL
I
7/16
MAKE-IN
H (55.6 mm)
2-3/16
1/2' NPT SSP DEFLECTOR * H— 2-7/8"(73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly 5-Compression 7-Bushing orifice seat on frame. Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TVI13I) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16' (11,1 mm)
PLATE SEATING NOMINAL
SURFACE MAKE-IN NPT
2-3/16'
(55,6 mm) f
1-lIT
(38,1 mm) W
STYLE 10 or 20
RECESSED
ESCUTCHEON
NOMINAL 4
MAKE-IN
2-3116"
WRENCH
FLATS
(55,6 mm) 3
SSP DEFLECTOR* h — 2-7/8"(73,0 mm) DIA
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
- Frame 3-Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly 5 - Compression orifice seat on frame. Screw
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
2-7/8" (73,0 mm) DIA.
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
2-1/4"
(57,2 mm)
CROSS SECTION
Jul •30 09 10:50a ARA Fire Sprinklers 16194454052 p.8
TFPI7I Page 3 of 10
1/2"
NPT
7/16"(11,1 mm)
NOMINAL
MAKE-IN
ESCUTCHEON
PLATE SEATING
SURFACE
7
2-3/16_
(55,6 mm)
1-1/2"
(36.1 mm)
SSP DEFLECTOR*
STYLE 10 or 20
RECESSED s* ESCUTCHEON JR'1L'I.
FLATS 3
112* NPT
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3-Sealing 4- Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly 5-Compression orifice seat on frame.
Screw
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT(TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2" (12,7 mm)
PLATE SEATING 3/4. NOMINAL
SURFACE MAKE-IN
F_
— 1
2-5/16"
_JJ
NPT
(58,7 mm)
W
(39.7mm)
1-9/16
STYLE 30 0r40
RECESSED SSU*
ESCUTCHEON DEFLECTOR
WRENCH
FLATS
SSP DEFLECTOR* - 2-7/8" (73,0 mm) DIA. 3/4" NPT
PENDENT RECESSED PENDENT UPRIGHT
- Frame 3-Sealing 4- Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to
2- Button Assembly 5-Compression orifice seat on frame. Screw
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (Y4131) AND PENDENT (7Y4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
Ju130 09 10:51a RAR Fire Sprinklers 16194454052 p.9
Page 4of 10 TFP171
7/16' (11,1 mm)
1/2" NOMINAL SSU'
NPT MAKE-IN DEFLECTOR
t'AlIENCHIt
6
2-3/16
5
(57,2 mm)1-9/16"
3 (39,7mm)FLATS
SsP *
DEFLECTOR CROSS
PENDENT UPRIGHT SECTION
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector * Temperature rating is indicated on deflector or adjacent to
2 - Button Assembly 5-Compression orifice seat on frame. Screw
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT (Y4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
1< = 2.8 GPM/psi112 (40,3 LPM/barl'2)
K = 4.2 GPM/psi112 (60,5 LPM/bar112)
K = 5.6 GPM/psi112 (80,6 LPM/barl'2)
K = 8.0 GPM/psi112 (115,2 LPM/bar12)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K=2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Jul.30 09 10:51a AAA Fire Sprinklers 16194454052 p.lo
Page 5 of 10 TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE
IPOLYESTER
2.8
1/2'
PENDENT
(TY1231)
and
UPRIGHT
(TYII3I)
135°F157*C Orange
123,5 155°F/68"C Red
175"F179°C Yellow
200"FI93°C Green
286"F1141°C Blue
NPT RECESSED
PENDENT
crviair
Figure 6
135"F/57"C Orange
1, 2, 5
155'F/68"C Red
175°F/79°C Yellow
200"F193"C Green
135F/57"C Orange
RECESSED
PENDENT
(TY1231)
Figure 7
155"F/68°C Red
175F/79°C Yellow
200"F/93°C Green
4.2
1/2"
NPT
PENDENT
(TY2231)
and
UPRIGHT
(n'2131)
135°F/57°C Orange
1,2
155°F/68"C Red
175"F179"C Yellow
200"F/93C Green
286°F/141°C Blue
135'F/57"C Orange
RECESSED
PENDENT
(TY2231)*
Figure 8
155°F168°C Red
175"F/79C Yellow
200"F/93°C Green
RECESSED
PENDENT
(TY2231)"
Figure 9
135"F/57C Orange
155"F/68C Red
175F/79"C Yellow
200°F/93°C Green
NOTES:
1Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (314" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Jul -30 09 10:51a AAA Fire Sprinklers 16194454052 p.11
Page 6 of 10 TFPI7I
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB
LIQUID
NATURAL
BRASS
I CHROME
PLATED
I WHITE
POLYESTER
LEAD'
COATED
-
5.6
PENDENT
(TY3231)
and
UPRIGHT
(1'Y3131)
135°F/57'C Orange
1, 2, 3, 4, 5, 6, 7
Blue
1,2,3, 5
155°F168'C Red
175'F179°C Yellow
200'F193°C Green
286'F1141'C 1/2'
NPT 135'F/57'C Orange
' 1,2,4.5
Green
' N/A
RECESSED
PENDENT
(1V3231)
Figure 10
155°F168°C Red
175°F179'C Yellow
200'F/93'C
135'F/57'C Orange
1, 2, 3,4, 5
Green
N/A
RECESSED
PENDENT
(rY3231)'
Figure 11
155'F168'C Red
175°F/79'C Yellow
200'F193'C
-
8.0
PENDENT
(TY4231)
and
UPRIGHT
(TY4131)
135'F/57'C I Orange
1,2, 3,4,5, 6,7
Blue
1,2.5 155'F/68°C Red
175°F/79°C Yellow
200'F/93°C Green
286'F/141'C 3/4,
NPT RECESSED
PENDENT
(1Y4231)*
Figure 12
135°171571C Green
1,2,4,5
Yellow
N/A 155'F/68°C Orange
175'F179'C Red
20OFI93°C
RECESSED
PENDENT
(TY4231)"
Figure 13
135'F/57°C Orange
1,2.3,4. 5
Green
N/A 155'F168°C Red
175'F179°C Yellow
200'1`193'C
-
8.0
1/2'
NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
135'F157'C Orange
1,2,4,5, 6
Blue
1, 2, 5 155°F168'C Red
175'F/79'C Yellow
200°F/93'C Green
286°F/141°C
NOTES:
Listed by Underwriters Laboratones,'Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31.53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a106) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2' NPT) or Style 40 (3/4' NPT) 3/4' Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2' NPT) or Style 30 (314' NPT) 1/2' Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Jul -30 09 10:52a RAR Fire Sprinklers 16194454052 p.12
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL I CHROME I WHITE LEAD
BRASS PLATED IPOLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/20 RECESSED PENDENT
NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/40 RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (YY3131) OR
1/2" 175 PSI (12.1 BAR)
RECESSED PENDENT NPT (TY3231) (SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
3/4,, RECESSED PENDENT NPT (TY4231) N/A
8.0 PENDENT (TY4931)
1/2' and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL): and, the Approval by the City of New York.
TABLE C, MAX/MUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the '2860F/141°C
temperature ratings.
A leak tight 1/2 inch NPrsprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak fight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40.7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Jul-30 09 10:52a AAA Fire Sprinklers 16194454052 p.13
Page 8 of 10
- 2-718'DIA.
(73,0 mm) I (19,1 mm)
(15,9±6,4 mm) 2-1/4 01k I ii (6,4 mm)
FACE OF (57.2 mm) 7- MOUNTING
PLATE' FITTING
__ ___________
118
SPRINKLER
I
MOUNTING
CLOSURE SERIES 1-5/16'
SURFACE ________________
TY-FRB 13116"(20,6 mm)
FIGURE 6
SERIES TY.FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7)8' 01k -
5/6t1/4 ______________
(73.0 mm) 3/4' (19,1 mm) r (15,9±6,4 mm) 2-1/4- DIA. 1/4' (6.4 mm) I
I SPRINKLER
FITTING
PLATE I
_
2 rnJ
FACE OF
mm
MOUNTING
MOUNTING
I
SURFACE
CLOSURE SERIES 1-1/4'(31,8 mm) TYFRB 3/4"(19,1 mm)
FIGURE
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFPI7I
- 2.718' OLA. -
(73,0mm) 1/2±1/8' 112"(12,7 mm) r (12.7±3,2 mm) 2-1/4' DIA. 114"(6,4 mm) I
I FACE OF 17-57,2 mm) MOUNTING
SPRINKLER PLATE
I
I FITTING
1/&
(3,2 mm)
MOUNTING / SURFACE//I
(33.3 mm)l CLOSURE SERIES
TY-FRB 1-1/16'(27.0 mm)
FIGURE 7
SERIES TYFRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL. ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
2-7/8' DIA.
(73.0 mm) 1/2±1/8' I 112'(12,7 mm) r (12,7±3.2 mm) 2-1/4' DIA. 114"(6,4 mm) I
FACE OF .2 MM) MOUNTING I SPRINKLER PLATE FrrTING
1(8'
\
MOUNTING
SURFACE
SERIES 1-114"(31,8 mm) CLOSURE TYFRB 1"(25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and al/personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been corn-
Ju130 09 10:53a AAA Fire Sprinklers 16194454052 p.14
TFPI7I
- 2-7/8" CIA.
5/8±1/4' (73,0 mm) - (191 mm) -
(15.9±6,4 mm) 2-1/4' CIA. 1/4' (6,4 mm)
FACE OF MOUNTING
SPRINKLER PLATE
57.2
FITTING
1/8'
MOUNTING
SURFACE
SERIES 1-1/4'L31,8 mm CLOSURE 'rY-FRB 3/4" (19.1 rnnl)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" CIA.
5/8±1/4" (73,0 mm) '•'""'l 314"(19.1 mm)
(15,916,4 mm) 2.1/4" DIX J 1/4" (6,4 mm)
FACE OF (57,2 MOUNTING
SPRINKLER PLATE
FITTING 1/8]
MOUNTING
SURFACE/
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 13/16"(20.6 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 9 of 10
2-7/8'DIA.
112±118"
(73,0 mm) 1/2" (12,7 mm)
r (12.7±3.2 mm) 2-1/4' CIA. I 1/4!'(6,4 mm)
FACE OF MM MOUNTING I
SPRINKLER PLATE I
I FITTING
57,2
/71
/
i /=
MOUNTING
SURFACE
CLOSURE
/J
I \
SERIES 1-1/4" (31,8 mm
TY.FRB 1' (25,4 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8' CIA.
112±118' (73,0 mm) 117 (12,7 mm)
[(12.7±3.2 mm) .,_. 2-1(4" CIA 1/4' (6,4
SPRINKLER PLATE I
FITTING 1 m
m)
I
- (3.2
,
j
,
1 FACE OF ;.2mml NTING MOUNTING I
t \
MOUNTING
_
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm)
Ty-FRO 1-1/16"(27,0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
pleted, to verity the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END 'A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B' USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
- WRENCH
RECESS
PUSH WRENCH
IN TO 'ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
Jul-30 09 10:53a AAA Fire Sprinklers 16194454052 P.15
Page 10 of 10 TFPI7I
PIN 57-XXX-X-XXX
I L
MODEL/SIN
330 2.8K UPRIGHT (112"NPT) TY1131
331 2.8K PENDENT (112'NPT) TY1231
340 4.2K UPRIGHT (1/2"NPT) TY2131
341 4.2K PENDENT (1/2NPT) TY2231
370 5.6K UPRIGHT (1/2"NPT) TY3131
371 5.6K PENDENT (1/2"NPT) TY3231
390 8.0K UPRIGHT (3I4NPT) 1Y4131
391 8.0K PENDENT (3/4"NPT) TY4231
360 8.0K UPRIGHT (1/2"NPT) TY4831*
361 8.0K PENDENT (1/2'NPT) TY493
I
I t 135
SPRINKLER
155
175
200
286
RATING
1 NATURAL BRASS 155'F/68C
4 WHITE POLYESTER 175F/79C
3 WHITE (RAL9O1O)' 200°F/93C
9 CHROME PLATED 286F/141'C
7 LEAD COATED
Eastern Hemisphere sales only.
TABLED
PART NUMBER SELECTION
SERIES TV-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation. corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBPs sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor). (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish. P/N (specify).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Jul-30 09 10:48a AAA Fire Sprinklers 16194454052 p.3
Dyna-Flow®
High Strength Steel Pipe
The original high-strength lightwall sprinkler pipe with hydraulics superior to Schedule-10.
Dyna-Flow pipe is the "original" high-
strength lightwall sprinkler pipe. Dyna-
Flow has outstanding hydraulic
capabilities and is recognized as the
most popular alternative to Schedule- 10
pipe. Lightweight, easy to cut and easy
to handle for installation. Dyna-Flow is a
valuable addition to any fire protection
system.
With an inside diameter of up to 11%
larger than Schedule-40 and up to 7%
larger than Schedule- 10, Dyna-Flow
pipe hydraulics are exceptional. Larger
I.D.s enable Dyna-Flow, and related
components, to be down-sized within the
system, thus increasing the potential for
job Cost savings. For complete Hazen-
Williams charts, refer to "Dyna-Flow
Hydraulic Data Tables."
Specifications
NPS Nominal 1.0. W. WI. (H20 Filled) Pal WtIl.ift (21') Wt,t.ilt (24') Wtjljlt (25')
In; mm In; mm Lbsrn; Kg/rn Lbs/Ft; Kg/rn Lift Lbs; Kg Lbs; Kg Lbs; Kg
1.191 0.830 1.31 91 1,586 1,812 1,888
25 30.3 1.2 1.95 91 719 822 856
11/4' 1.536 1.059 1.87 61 1,356 1,550 1,615
32 39.0 1.6 2.78 61 615 703 733
11% 1.728 1.667 2.71 61 2,135 2,440 2,542
40 43.9 2.5 4.03 61 968 1107 1153
2.203 2.104 3.79 37 1.634 1,868 1,946
50 56.0 3.1 5,64 37 741 847 883
2W 2.703 2.564 5.10 30 1,615 1,846 1,923
65 68.7 3.8 7.59 30 733 837 872
3.314 3.387 7.18 19 1,351 1,544 1,608
80 64.2 5.0 10.69 19 613 700 729
4.310 4.473 10.86 19 1,784 2,039 2,124
90 109.5 6.7 1616 19 809 925 963
Dyna-Flow products are coated with
an environmentally approved and
specially formulated modified-acrylic or
water-based coating. This durable coating
is paintable. The black coating acts as
an excellent primer and is resistant to
weathering and UN. degradation from
outdoor storage.
Metallurgical properties provide excellent
fabrication characteristics for end prep
finishes, welding and roll grooving.
There is no special process or equipment
needed for fabrication and installation.
The internal surface of all black Allied
Tube & Conduit Fire Sprinkler pipe
products up to 4.5000" in diameter is
coated with our new Antibacterial
Formula, "ABF". In scientific laboratory
test, ABS proved to have superior
resistance to microbial colonization of
pipe walls, thereby delaying or possibly
preventing the onset of Microbiologically
Influenced corrosion (MIC) when the
First Sprinkler System is first installed.
Dyna-Flow/Super Flo pipe is manufac-
tured to meet ASTM A-795 Type E,
Grade A and is in compliance with
NFPA- 13 and NFPA- 14. All sizes of
Dyna Flow/Super Flo are UL Listed, FM
Approved and ULC Listed.
0 <~> 9
Listed Approved Listed
Dyna-Flow/Super Flo is UL/ULC Listed
for use with roll grooved, plain-end
couplings, and welded joints for wet, dry,
preaction and deluge systems. It is FM
Approved for roll grooved, plain-end, and
welded joints for wet systems. Refer to
appropriate documentation for up-to-date
listing and approval information. Dyna-
Flow/Super Flo is now available "hot-
dip" galvanized and has been specifically
approved by FM for dry systems uses.
Additional Benefits
Lightweight and easy to install,
resulting in more efficient use of your
freight and labor dollars.
Provides stability needed to comply
with standard hanger spacing
(15 ft O.C.) per NFPA.
Available in Standard lengths for your
convenience, or can be ordered in
custom lengths upon approval.
Fast cutting and welding, as well as
easy roll grooving and end preparation.
Available in Factory roll grooved form
for quicker shop turnaround.
Clean, durable mill coating provides
longer "shelf life" and acts as an
excellent primer for custom paint
applications.
16100 S. Lathrop• Harvey, IL 60426 Customer Service:
tqco/F/owcor?tro/ allied 11350 Norcom Rd. • Philadelphia, PA 19154 (800)882-5543
TUBE & CONDUIT 2525 N. 27 th Ave. 'Phoenix, AZ 85009 Fax 708-339-1806
S2-3
Jul-30 09 10:49a AAA Fire Sprinklers 16194454052 P.4
c® US US1ID Fig. 25 - Surge Restrainer
Size Range - One size fits 3/4 thru 2 pipe.
Material - Pre-Galvanized Steel
Function - Designed to be used in conjunction with TOLCO® Band Hangers to
restrict the upward movement of piping as it occurs during sprinkler head
activation or earthquake type activity. The surge restrainer is easily and efficient-
ly installed by snapping into a locking position on the band hanger. This product
is intended to satisfy the requirements as indicated in the National Fire Protection
Association (NFPA 13, 1999 Edition), 6-2.3.3, 6-2.3.4 and A-6i-2.3.3 Can be
used to restrain either steel pipe or CPVC plastic Pipe.
Approvals - Underwriters' Laboratories Listed pn1y when used with TOLCO
band hangers Fig. 2, 2NFPA and 200, in the USA (UL) and
Canada (cUL).
Finish - Pre-Galvanized
Order By - Figure number and TOLCO band hanger, size from 3/4
thru 2.
Patent #5,344,108
OFFICE/MANUFACTURING FACIUTY • 375 SAMPSON AVE. • CORONA. CA 92870 • P1-I: 951.7375509 • FAX: 951.737.8030
CUSTOMER SERVICE • 8007855255
www.Wko.com
IMPERIAL MAX REC.
LOAD LBS.
METRIC*
PIPE ROD PIPE ROD
112 3/8 400 10
314 318 400 20 10
1 3/8 400 25 10
1 1/4 3/8 400 32 11)
11/2 3/8 400 40 10
2 318 400 5D 10
21/2 3/8 600 65 to
3 3/8 600 80 II)
31/2 3/8 600 10
4 3/8 1000 100 10
5 1/2 1250 125 12
6 1/2 1250
8 1250 200 12
Order Part #300m
Note: 1/2 Ring Hanger not <FM> approved
1/2 and 3/4 inch pipe
5 thru 8 Inch pipe
Jul-30 09 10:49a AAA Fire Sprinklers 16194454052 p.5
H
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
300
RING HANGER
1 thru 4 mcli pipe
LISTED FOR STEELICPVC
SIZE - 1/2 thru 8 inch pipe.
MATERIAL - Carbon Steel, Mu. Galvanized to G-90 spec.
LISTING/APPROVAL -
c® 203-EX 2551
. Approval guide - Pipe Hangers
OSHPD OPA-060 I See Website.
CONFORMS WITH: Federal Specification WW-H-171 (Type 10,
Manufacturers Standardization Society ANSI/MSS-SP-58 (Type 10).
MAXIMUM TEMPERATURE - 650°F.
FUNCTION - Pipe hanger component for use on steel, CPVC or
copper piping.
INSTALLATION - Per NFPA13, 13R, I3D and
CPVC manufacturers instructions.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FEATURES -
' Sized and listed exclusively for use with #310 Surge Restrainer.
* Band edge is offset for EASY pipe insertion.
* Custom fit swivel nut for better retention in ring body.
* Full length knurl on swivel nut for better grip.
ORDERING - Part #, pipe size.
pipe A 0
T
, LOM 2.5250
'14 2.1392 2.M50
T i 112 72673 2.9110
_2_ 2.lO4C 3.2516
2112 3.492C 4-1159
+ LI
A 60268 5202
o 1.5768
1/08