HomeMy WebLinkAbout2641 GATEWAY RD; 101; FPC2020-0211; PermitCL7city of
PERMIT REPORT
S Carlsbad
Print Date: 04/08/2021 Permit No: FPC2020-0211
Job Address: 2641 GATEWAY RD, # 101, CARLSBAD, CA 92009-1754 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2131912500 Track #: Applied: 12/17/2020
Valuation: $95,008.96 Lot #: Issued: 12/29/2020
Occupancy Group: Project #: Finaled Close Out: 04/08/2021
#f Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: PANDA EXPRESS -SPRINKLER TI (28 HEADS)
Applicant: FPContractor:
WESTERN FIRE PROTECTION INC WESTERN FIRE PROTECTION INC
MARIO MACK 13630 DANIELSON ST
13630 DANIELSON ST P0 WAY, CA 92064-6830
POWAY, CA 92064-6830 (858) 513-4949
(858) 513-4949
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads S $553.00
TotaF Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
QUICK RESPONSE
GL mum a BE
FIRE SPRINKLER CORPORATION
DESCRIPTION AND OPERATION
AUTOMATIC SPRINKLERS GL
SERIES RECESSED PENDENT
TO MEET IBC-ASCE/SEI 7 CODES
FOR SEISMIC AREAS C, D & E
The Globe Quick Response GL Series Sprinkler is a low profile yet durable design which utilizes
a 3mm frangible glass ampule as the thermosensitive element. This provides sprinkler operation
approximately six times faster than ordinary sprinklers. While the Quick Response Sprinkler
provides an aesthetically pleasing appearance, it can be installed wherever standard spray
sprinklers are specified but offers the additional feature of greatly increased safety to life. Quick
Response Sprinklers should be used advisedly and under the direction of approving authorities
having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating assembly is a hermetically sealed
frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed,
the liquid within the bulb expands increasing the internal pressure. At the prescribed temperature,
the internal pressure within the ampule exceeds the strength of the glass causing the glass to
shatter. This results in water discharge which is distributed in an approved pattern depending upon
the deflector style used.
The use of the 4112" diameter recessed escutcheon allows for 1" of clearance around
the sprinkler body, and meets the IBC-ASCEISEI 7 requirements for use in seismic design
categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of
installation.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
'Temperature Ratings - 135°F (570C), 155°F (68°C), 175°F f
(790C), 200°F (930C), 286°F (141°C) ; )
Water Working Pressure Rating - 175 psi (12 Bars) /
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze • Deflector - brass • Screw - brass QUICK RESPONSE
Bulb seat - copper • Spring - nickel alloy • Seal - teflon RECESSED PENDENT
Bulb - glass with alcohol based solution, 3mm size WITH OPTIONAL 41/2" SEISMIC
Escutcheon Assembly - steel RECESSED ESCUTCHEON
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER BULB N.F.P.A. MAXIMUM CLASSIFICATION TEMPERATURES COLOR CEILING TEMPERATURE
ORDINARY 1350F/155°F 570C1680C ORANGE/RED 100°F 38°C
INTERMEDIATE 175°F1200°F 79°C193°C YELLOW/GREEN 150°F 66°C
HIGH 286°F 141°C BLUE 225°F 107°C
4O77AIRPARKDRIVE, STANDISH, MICHIGAN 48658 989-846-4583 9 FAX989-846-9231
APRIL 2009 A-24E0 BULLETIN GL2801-EQ
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES RECESSED PENDENT
TO MEET IBC-ASCE/SEI 7 CODES
FOR SEISMIC AREAS C, D & E
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES
2.8 (39 metric) 1/2' NPT 2 1/4" (5.7 cm)
4.2 (59 metric) 1/2' NPT 2 1/4' (5.7 cm) Chrome
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) White Polyester'
7.8 (111 metric) 1/2' NPT 2 1/4" (5.7 cm)
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'cULus LISTED CORROSION RESISTANT -
POLYESTER MUST BE SPECIFIED ON ORDER.
APPROVALS
STYLE SIN K 135°F 155°F 175°F 200°F **286F cULus LPC CE NYC - DOB
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C FM MEA101-92-E
GL2801 2.8 X X X X X X - - - x
GL4201 4.2 X X X X X X - - - X PENDENT GL5601 5.6t X X X X X X X X X X RECESSED
GL8101 7.8t X X X X X X X - - X
GI-8106, 8.1t X X I X I X X X I X I X I X X
t5.6K ORIFICE, 7.8K ORIFICE AND 8.11< ORIFICE LISTED FOR ALL HAZARDS.
°286°F cULus LISTED ONLY.
t 1/2' RECESSED ESCUTCHEONS ARE REQUIRED FOR FM APPROVED SPRINKLERS.
ORDERING INFORMATION
SPECIFY
Quantity • Model Number . Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Recessed Wrenches - P/N 325391 (1/2");
1/8'MIN. P/N 325401, Rev. F (L.O.) 5/8° MAX. - 1/2' AD). 7/8' MAX. -3/4'ADJ. • Quantity - Protective Caps - P/N 327109-CAP
(Friction Fit Recessed)
GLOBES PRODUCT WARRANTY
Globe agrees to repair or replace any of its own
manufactured products found to be defective in material
or workmanship for a period of one year from date of
shipment.
For specific details of our warranty, please refer to
Price List Terms and Conditions of Sale (Our Price List).
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX989-846-9231
1-800-248-0278 www.globespnnkIer.com
CROSS SECTIONS
—4 112' DIA.-
7/8'-4'DIA.MIN.
1° x 1/2' HOLE IN cElUNG
REDUCER —129/32' DIA.-
1' MIN.
13/4' MAX.
PENDENT WITH OPTIONAL IBC
SEISMIC RECESSED ESCUTCHEON
GLb)13E
FIRE SPRINKLER CORPORATION
APRIL 2009 PRINTEDU.S.A. BULLETIN GL2801-EQ
GLbRE
FIRE SPRINKLER CORPORATION
DESCRIPTION AND OPERATION
QUICK RESPONSE
"THE INCH"
MODEL GL5606 ONE INCH
ADJUSTABLE CONCEALED
PENDENT WITH COVER PLATE
TO MEET lB C-A SCE/SEI 7 CODES
FOR SEISMIC AREAS C, D & E
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile,
aesthetically pleasing design. It provides sprinkler operation approximately six times faster than
ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are
specified, when allowed by the applicable standards. It offers the additional feature of greatly
increased safety to life and should be used advisedly and under the direction of approving
authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low
profile cover plate assembly. The 4 1/2" diameter cover plate allows for 1" clearance around
the sprinkler body, and meets the IBC-ASCE/SEI 7 requirements for the use in seismic
design categories C, D & E. The GL Series Concealed Sprinkler may be virtually invisible, as it
does not interrupt the "smooth flow" of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm
frangible glass ampule which is located above the ceiling and concealed from view by the ceiling
plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper
wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be
installed. The "push on - screw off' designed cover plate is easilyinstalled and with a nominal I"
inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build-up causes the solder holding the cover plate
to the support shell to melt, allowing the cover plate to fall clear. Continued heat build-up causes
the 3mm glass bulb to burst, allowing the deflectorto drop down and distribute water in an approved
pattern to extinguish or control the fire.
TECHNICAL DATA
See reverse side for Approval and Specifications.
Temperature Ratings-
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
Water Working Pressure Rating - 175 psi 112 Bars)
Factory tested hydrostatically to 500 psi (34 Bars) -
Maximum low temperature glass bulb rating is -67°F (-55°C) QUICK RESPONSE
Frame - bronze. Deflector - brass. Screw - brass 4 1/2" diameter plate
Bulb Seat - brass • Spring - nickel alloy • Seal - teflon WHITE
Bulb - glass with alcohol based solution, 3mm size ADJUSTABLE
Drop Pin - stainless steel • Cover Plate - brass CONCEALED PENDENT
Upper Escutcheon Assembly - plated steel
NOTE: Globe's wrench P/N 332765 must be used to install this sprinkler.
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION BULB COLOR TEMPERATURES CEILING TEMPERATURE
ORDINARY 1350F/ 1550F 57°C /680C ORANGE/RED 100°F 38°C
INTERMEDIATE 175°F / 200°F 79°C /93'C YELLOW/GREEN 150°F 66°C
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 (989) 846-4583 • FAX 989-846-9231
APRIL 2009 A-38-EQ BULLETIN GL5606-EQ REV#2
QUICK RESPONSE
MODEL GL5606 ONE INCH
ADJUSTABLE CONCEALED PENDENT
WITH COVER PLATE TO MEET
IBC-ASCE/SEI 7 CODES FOR
SEISMIC AREAS C. D & E
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES
Chrome 5.6 (80 metric) 1/2" NPT 2 1/2" (6.4 cm) White
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
APPROVALS
SIN K 135°F (57°C) 155°F (68°C) 155°F (68°C) 175°F (79°C) 200°F (93°C)
STYLE MODEL FACTOR with plate with plate with plate with plate with plate c1JLus
135°F (57°C) 135°F (57°C) 155°F (68°C) 155°F (68°C) 155°F (68°C)
Adjustable
Concealed GL5606 5.6 X X X X X X
Pendent
CROSS SECTION
7/8" -4" DIX. MIN.
HOLE IN CEILING
DIV.
DROP PIN 2 3/4" MAX.
I 7/8" MIN. SUPPORT SHELL
CEILING COVER PLATE 41/2"
CEILING
PLATES
WHITE 135°F
PART#
WHITE 155°F
PART#
CHROME 135°F
PART#
CHROME 155°F
PART#
332822 332828 332821 332827
ORDERING INFORMATION
SPECIFY
Quantity • Model Number Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Adjustable Concealed Wrenches -
P/N 332765
GLt)BE
FIRE SPRINKLER CORPORATION
APRIL 2009
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for
a period of one year from date of shipment.
For specific details of our warranty, please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.gIobesprinkler.com
PRINTED U.S.A. BULLETIN GL5606-EQ REV#2
.rc
QUICK RESPONSE
SERIES GL-QR SERIES GL-QRJCNV
UPRIGHT CONVENTIONAL
D
QUICK RESPONSE
SERIES GL-QR SERIES GL-QRISW
PENDENT VERTICAL
SIDEWALL
00012
IVNIQ VIP" gliiR3
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A U TO MA TI C SPRINKLERS
GL SERIES
UPRIGHT ° PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response Series GL-QR Sprinklers are
a low profile yet durable design which utilizes a 3mm frangible
glass ampule as the thermosensitive element. This provides
sprinkler operation approximately six times faster than ordinary
sprinklers. While the Quick Response Sprinkler provides an
aesthetically pleasing appearance, it can be installed wherever
standard spray sprinklers are specified when allowed by the ap-
plicable standards. It offers the additional feature of greatly in-
creased safety to life and is available in various styles, orifices,
temperature ratings and finishes to meet many varying design
requirements. Quick Response Sprinklers should be used ad-
visedly and under the direction of approving authorities having
jurisdiction.
The heart of Globe's Series GL-QR sprinkler proven ac-
tuating assembly is a hermetically sealed frangible glass ampule
that contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the inter-
nal pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern depending upon the deflector style
used.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
C9
Temperature Ratings - 135°F (570C), 155°F (680C),
175°F (79°C), 200°F (93°C), 286°F (141°C) 0 a,
Water Working Pressure Rating - 175 psi (12 Bars) QUICK RESPONSE Factory tested hydrostatically to 500 psi (34 Bars) HORIZONTAL LPCB/CE Maximum low temperature glass bulb rating is -67°F (-55°C) SIDEWALL HORIZONTAL Frame - bronze • Deflector - brass • Screw - brass SERIES GL-QRISW SIDEWALL
Lodgement Wire - stainless steel • Bulb seat - copper SERIES GL-QRISW
Spring - nickel alloy • Seal - teflon
Bulb - glass with alcohol based solution, 3mm size
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION BULB COLOR TEMPERATURES CEILING TEMPERATURE
ORDINARY F H 1oi F 57 G bd C ORANGE/RED 38 C
INTERMEDIATE 700F 7cyc93c YELLOW/GREEN 150 F 66C
HIGH 141 C BLUE 725 F 107C
MAR 2018 GFS-100a (Formerly A-20)
QUICK RESPONSE
A U TO MA TIC SPRINKLERS
UPRIGHT PENDENT VERTICAL SIDEWALL
HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL. "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (40 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm)
4.2 (60 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Factory Bronze
5.6 (80 metric) 1/2"NPT (15mm) 2 1/4 (5.7cm) Chrome
White Polyester'
8.0 (115 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Black Polyester 2.3
8.0 (115 metric) I 3/4'NPT (20mm) 27/16" (6.2cm)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 29/16".
°FINISHES AVAILABLE ON SPECIAL ORDER.
3AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
LISTINGS/APPROVALS
K TEMPERATURE NYC - DOB
_____
135°F 155°F 175°F 200°F 286°F STYLE SIN FACTOR HAZARD' cULus FM LPCB2 CE MEA
(57°C) (68°C) (79°C) (93°C) (141°C) 101-92-E
GL2815 2.8 LH X X X X X X -- X
GL4215 4.2 LH X X X X X X --- -- --- X
UPRIGHT GL5615 5.6 LH/OH X X X X X X X X X X
GL8115° 8.0°(WNPT) LH/OH X X X X X -' X --- -- -- X
GL8118 8.0 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X X
GL4201 4.2 LH X X X X X X - X
PENDENT GL5601 5.6 LH/OH X X X X X X X X X X
GL8101° 8.0° (W NPT) LH/OH X X X X X X - - . .X - -
GL8106 8.0 LH/OH X X X X X X X X ( X
VERTICAL GL5632 5.6 LH X X X X X X X --
SIDEWALLt GL8133 8.0 .LH X X X X X X --
GL2826 2.8 LH X X X X X X - -- - X
HORIZONTAL GL4226 4.2 LH X X X X X X --- ---
SIDEWALL GL5626 5.6 LH/OH X X X X X X X - X
GL5627a 5.6 LH/OH X X X X X --- --- X X
GL8127 8.0 LH/OH X X X X X X -
CONVENTIONAL GL5624 5.6 LH/OH X X X X X --- --- X X -
(OLD STYLE) GL8125 8.0 LH/OH
I
X X X
I
X X --- -- --- X --
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA1 3 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
BINSTALL IN ACCORDANCE TO B55306 AND ANY OTHER RELATED DOCUMENTS.
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
fUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
"1/2" NPT, FOR RETROFIT ONLY
2LPCB REF. NO. 147c/05
ORDERING INFORMATION GLOBE® PRODUCT WARRANTY
SPECIFY Globe agrees to repair or replace any of its own manufactured
Quantity • SIN • Style • Orifice products found to be defective in material or workmanship for a
Thread Size • Temperature Finishes desired period of one year from date of shipment.
Quantity - Wrenches - PIN 325390 (1/2"); For specific details of our warranty please refer to Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
GLBE
FIRE SPRINKLER CORPORATION
MAR 2018
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.gIobesprinkler.com
PRINTED U .S.A. GFS-1 00a (Formerly A-20)
QUICK RESPONSE
A U TOMA TI C SPRINKLERS Bonn
NIFFA
6 L ___
GL SERIES DRY TYPE
FIRE SPRINKLER CORPORATION RECESSED PENDENT TO MEET
IBC-ASCE/SEI 7 CODES FOR
SEISMIC AREAS C. D & E
DESCRIPTION AND OPERATION
The Globe Quick Response Series GL-QR/DRY Pendent Sprinkler is designed for use in special
applications such as freezing environments and conditions where sediment or foreign materials might
accumulate in ordinary drop nipples.
The Globe Quick Response Series GL-QRIDRY Pendent Sprinkler utilizes a 3mm frangible glass
ampule as the thermosensitive element. This provides sprinkler operation approximately six times faster
than ordinary sprinklers. At the ampule's rated temperature, the sprinkler opens releasing the bulb seat,
causing the inner tube assembly to move, allowing the spring assembly to pivot alongside the inner tube.
At this time, water flows through the sprinkler and is distributed by the deflector in an approved discharge
pattern. It can be installed wherever standard spray sprinklers are specified but offers the additional
feature of greatly increased safety to life. Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction.
The heart of Globe's Series GL-QR/DRY sprinkler proven actuating assembly is a hermetically sealed
frangible glass ampule that contains a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At the prescribed temperature the internal
pressure within the ampule exceeds the strength of the glass causing the glass to shatter. This results in
water discharge which is distributed in an approved pattern.
The use of the 41/2" diameter recessed escutcheon allows for 1" of clearance around the sprinkler
body, and meets the IBC-ASCE/SEI 7 requirements for use in seismic design categories C, D & E.
The sprinkler and escutcheon are not factory assembled. Assembly is done at the time of installation.
TECHNICAL DATA
See reverse side for Approvals and Specifications.
Temperature Ratings -
135°F (57°C) 155°F (68°C), 175°F (79°C)
200°F (93°C), 286°F (141°C)
Water Working Pressure Rating -175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze • Deflector - brass• Screw - brass
Bulb Seat - brass• Spring - nickel alloy' Seal - teflon
Retainer - brass • Pin - stainless steel
Torsion Spring - stainless steel• Orifice Insert - brass
Bulb - glass with alcohol based solution, 3mm size
3/4"NPT or 1"NPT • Outer Tube - galvanized steel pipe
Inner Tube - stainless steel
SERIES GL-QRJDRY
RECESSED PENDENT
WITH OPTIONAL 41/2" SEISMIC
RECESSED ESCUTCHEON
NOTE: Globe's wrench P/N 337014 must be used to install this sprinkler.
0 SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM CEILING
TEMPERATURES TEMPERATURE
ORDINARY 135°F/155°F 57°C/68°C ORANGE/RED 100°F 38°C
INTERMEDIATE 175°F/200°F 79°C193°C YELLOW/GREEN 150°F 66°C
HIGH 286°F 141°C BLUE 225°F 107°C
DEC 2017 GFS-505a-EQ (Formerly A-55EQ)
CROSS SECTION
.. , . - . ' ...,.-TEEFIT11NG I I,.. ANSI 616.3 CLASS 150 OR r ANSI 616.4 CLASS 125
PENDENT WITH OPTIONAL IBC
SEISMIC RECESSED ESCUTCHEON
QUICK RESPONSE
AUTOMATIC SPRINKLERS GL SERIES
DRY TYPE RECESSED PENDENT TO MEET
lB C-AS CE/SEI 7 CODES FOR SEISMIC AREAS C, D & E
SPECIFICATIONS
NOMINAL
"K" FACTOR THREAD SIZE LENGTH FINISHES
5.6 (80 metric) 3/4' or 1"NPT
cULus Variable to 48"
FM Variable to 36'
Chrome
White Polyester2 8.0 (115 metric) 1"NPT
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
2cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
APPROVALS
K THREAD 135°F 155°F 175°F 200°F 286°F NYC-DOB
STYLE SIN FACTOR SIZE HAZARD' (57°C) (68°C) (79°C) (93°C) (141°C) *FM cULus MEA
101-92-E
GL5635 5.6 1'NPT LH/OH X X X X X X X X
RECESSED GL5636 5.6 3/4"NPT LH/OH X X X X X -- X X PENDENT
GL8135 8.0 1"NPT LHIOH X X X X X --- X X
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA1 3 AND ANY OTHER RELATED DOCUMENTS.
"FM APPROVED FOR 155°F (68°C) AND 200°F (93°C) ONLY.
LH: LIGHT HAZARD; OH: ORDINARY HAZARD
IMPORTANT INSTALLATION DATA
Globe GL Series Dry Pendent Sprinklers should be installed in
accordance with the requirements set forth in NFPA 13. These
sprinklers are to be installed using a pipe wrench applied to
the outer tube. When this is not possible, the proper sprinkler
head wrench may be used with extreme care for lengths up to
approximately 18". Excessive force may distort the frame thus
destroying the unit.
When installed in a wet system extending into a freezing
area see chart on Dry Caution Sheet for minimum exposed
barrel length to prevent ice plugs. Please refer to our Dry
Caution Sheet for further important installation data.
ORDERING INFORMATION
SPECIFY MPr Quantity ° SIN• Style" Orifice Temperature
Finishes desired• Quantity - Recessed Wrenches - PIN 337014
° Quantity - Protective Caps - P/N 327109-cap (Friction Fit Recessed)
"A" Dimension - Distance from face of fitting to the finished ceiling line
regardless of escutcheon used.
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
I ;
FIRE SPRINKLER CORPORATION
DEC 2017
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.gIobesprinkler.com
PRINTED U.S.A. GFS-505a-EQ (Formerly A-55EQ)