HomeMy WebLinkAbout2656 GATEWAY RD; 140; FPC2018-0403; Permit(
PERMIT REPORT
ity of
Carlsbad
Print Date: 10/18/2021 Permit No: FPC2018-0403
Job Address: 2656 GATEWAY RD, # 140, CARLSBAD, CA 92009 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2132622100 Track #: Applied: 12/12/2018
Valuation: $113,260.00 Lot #: Issued: 12/20/2018
Occupancy Group: Project #: Finaled Close Out: 05/26/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: RICHARD WALKER'S PANCAKE HOUSE -REVISED PLANS FOR SPRINKLER TI (32 HEADS)
FPContractor:
BRIAN SULLIVAN
1975 SPANISH OAK WAY
VISTA, CA 92081-7383
(760) 716-9226
FEE AMOUNT
FIRE NFPA 13 or 13R System 7- 100 heads $553.00
FIRE Plan Resub (3rd&Subsequent Submittal/hr) $136.00
Total Fees: $689.00 Total Payments To Date: $689.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Sully Fire Protection
1975 Spanish Oak Way
Vista, California
C16 701590
HYDRAULIC CALCULATIONS
FOR
New Horizontal Sidewall Sprinklers for
Tenant Improvement of Exterior Dining Area
Richard Walker's Pancake House
The Square @ Bresi Ranch
Carlsbad, California 92009
0 ( iIoP.i€.."
ogJ P4%1IS7 4ij4,ç
FILE NAME: Pancake-HSW-REVI.sdf
DATE: 22,2019
-Design Data-
OCCUPANCY CLASSIFICATION: Light Hazard
DENSITY:
AREA OF APPLICATION:
COVERAGE PER SPRINKLER:
NUMBER OF SPRINKLERS FLOWING:
TOTAL SPRINKLER WATER FLOW REQUIRED:
TOTAL WATER REQUIRED (including hose):
FLOW AND PRESSURE REQUIRED AT SOURCE:
PRESSURE AVAILABLE AT SOURCE:
SPRINKLER ORIFICE SIZE:
0.10 gpm/1'2
Exterior Dining Area
± 786 ft'
290 ft2 maximum coverage for Sidewalls
5 Horizontal Sidewall Sprinklers
146.7 gpm
246.7 gpm
146.7 gpm @ 44.0 psi
73.4 psi
5.6
Notes: Hydraulic design label for existing system indicated 81.588 psi required at a flow of 479.75
gpm at the base of the riser. These calculations were performed with a source point at the base of the
riser, and those values reduced by 10%.
91
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 2/22/2019 C:\HASS FILES\PANCAKE-HSW-REV1.SDF
JOB TITLE: Pancake - Sidewalls
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 73.4 73.3 479.8 73.4 247.0 44.0
Available pressure is 29.4 psi (40%) greater than required pressure.
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 247.0 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 147.0 GPM
DENSITY
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE AREA REQ. ACT.
(FT) (PSI) (GPM) (FT2) (GPM/FT2)
1 13.0 K= 5.60 27.4 29.3 290.0 0.100 0.101
1A 13.0 - - - - 32.4 ---
2 13.0 K= 5.60 26.8 29.0 290.0 0.100 0.100
2A 11.5 - - - - 32.4 ---
3 13.0 K= 5.60 27.6 29.4 290.0 0.100 0.101
4 13.0 K= 5.60 27.2 29.2 290.0 0.100 0.101
4A 13.0 - - - - 29.2 ---
5 13.0 - - - - 27.2 ---
6 13.0 K= 5.60 28.8 30.1 290.0 0.100 0.104
A 11.5 - - - - 37.0 - - -
B 11.5 - - - - 37.1 - - -
C 11.5 - - - - 32.4 - - -
D 11.5 - - - - 32.2 - - -
E 11.5 - - - - 32.3 - - -
F 11.5 - - - - 33.1 - - -
G 11.5 - - - - 33.2 - - -
H 11.5 - - - - 37.7 - - -
TOR 11.5 - - - - 38.3 - - -
SOURCE 0.0 SOURCE 44.0 147.0
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 2/22/2019 C:\HASS FILES\PANCAKE-HSW-REV1.SDF
JOB TITLE: Pancake - Sidewalls
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -29.3 1.049 PL 10.00 PF 5.0
1 13.0 5.6 27.4 29.3 10.9 120 FTG 2ET PE 0.0
1A 13.0 0.0 32.4 0.0 0.264 TL 19.00 PV
Pipe: 2 -29.0 1.049 PL 10.00 PF 4.9
2 13.0 5.6 26.8 29.0 10.8 120 FTG 2ET PE 0.6
2A 11.5 0.0 32.4 0.0 0.259 TL 19.00 PV
Pipe: 3 -29.4 1.049 PL 6.00 PF 4.0
3 13.0 5.6 27.6 29.4 10.9 120 FTG 2ET PE 0.6
D 11.5 0.0 32.2 0.0 0.265 TL 15.00 PV
Pipe: 4 -29.2 1.049 PL 0.50 PF 2.0
4 13.0 5.6 27.2 29.2 10.8 120 FTG ET PE 0.0
4A 13.0 0.0 29.2 0.0 0.262 TL 7.50 PV
Pipe: 5 0.0 1.049 PL 13.00 PF 0.0
5 13.0 0.0 27.2 0.0 0.0 120 FTG ---- PE 0.0
4 13.0 5.6 27.2 29.2 0.000 TL 13.00 PV
Pipe: 5A -29.2 1.049 PL 2.50 PF 2.5
4A 13.0 0.0 29.2 0.0 10.8 120 FTG ET PE 0.6
E 11.5 0.0 32.3 0.0 0.262 TL 9.50 PV
Pipe: 6 -30.1 1.049 PL 4.00 PF 3.6
6 13.0 5.6 28.8 30.1 11.2 120 FTG 2ET PE 0.6
F 11.5 0.0 33.1 0.0 0.277 TL 13.00 PV
Pipe: 7 69.6 1.610 PL 16.00 PF 3.9
A 11.5 0.0 37.0 0.0 11.0 120 FTG T PE -0.6
1A 13.0 0.0 32.4 0.0 0.162 TL 24.00 PV
Pipe: 8 40.3 1.610 FL 11.50 PF 0.7
1A 13.0 0.0 32.4 0.0 6.4 120 FTG ---- PE 0.6
2A 11.5 0.0 32.4 0.0 0.059 TL 11.50 PV
Pipe: 8A 11.3 1.610 PL 4.40 PF 0.0
2A 11.5 0.0 32.4 0.0 1.8 120 FTG ---- PE 0.0
C 11.5 0.0 32.4 0.0 0.006 TL 4.40 PV
Pipe: 8B 11.3 1.610 FL 15.00 PF 0.2
C 11.5 0.0 32.4 0.0 1.8 120 FTG ET FE 0.0
D 11.5 0.0 32.2 0.0 0.006 TL 27.00 PV
Pipe: 9 -18.1 1.610 FL 8.00 PF 0.1
D 11.5 0.0 32.2 0.0 2.9 120 FTG ---- PE 0.0
E 11.5 0.0 32.3 0.0 0.013 TL 8.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 2/22/2019 C:\HASS FILES\PANCAKE-HSM-REV1.SDF
JOB TITLE: Pancake - Sidewalls
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 10 -47.3 1.610 PL 5.50 PF 0.8
E 11.5 0.0 32.3 0.0 7.5 120 FTG E PE 0.0
F 11.5 0.0 33.1 0.0 0.079 TL 9.50 PV
Pipe: 11 -77.4 1.610 PL 0.75 PF 0.1
F 11.5 0.0 33.1 0.0 12.2 120 FTG ---- PE 0.0
G 11.5 0.0 33.2 0.0 0.197 TL 0.75 PV
Pipe: 12 -77.4 1.610 PL 14.50 PF 4.4
G 11.5 0.0 33.2 0.0 12.2 120 FTG T PE 0.0
H 11.5 0.0 37.7 0.0 0.197 TL 22.50 PV
Pipe: 13 -69.6 3.068 PL 11.50 PF 0.2
A 11.5 0.0 37.0 0.0 3.0 120 FTG T PE 0.0
B 11.5 0.0 37.1 0.0 0.007 TL 26.50 PV
Pipe: 14 -69.6 3.068 PL 58.00 PF 0.5
B 11.5 0.0 37.1 0.0 3.0 120 FTG T PE 0.0
H 11.5 0.0 37.7 0.0 0.007 TL 73.00 PV
Pipe: 14A -147.0 3.068 PL 9.00 PF 0.6
H 11.5 0.0 37.7 0.0 6.4 120 FTG 2E PE 0.0
TOR 11.5 0.0 38.3 0.0 0.028 TL 23.00 PV
Pipe: 15 -147.0 3.260 PL 11.50 PF 0.7
TOR 11.5 0.0 38.3 0.0 5.7 120 FTG CG PE 5.0
SOURCE 0.0 SRCE 44.0 (N/A) 0.021 TL 34.50 PV
NOTES (HASS)
Calculations were performed by the HASS 8.8 D computer program
in accordance with NFPA13 (2016)
under license no. 50110279 granted by
HRS Systems, Inc.
208 Southside Square
Petersburg, TN 37144
(931) 659-9760
The system has been calculated to provide an average
imbalance at each node of 0.006 gpm and a maximum
imbalance at any node of 0.100 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.2 ft/sec at pipe 11.
Items listed in bold print on the cover sheet
are automatically transferred from the calculation report.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 2/22/2019 C:\HASS FILES\PANCAKE-HSW-REV1.SDF
JOB TITLE: Pancake - Sidewalls
Available pressure at source node SOURCE under full flow conditions is
73.36 psi with a flow of 296.48 gpm.
PIPE FITTINGS TABLE
User Pipe Table Name: KEN CUSTOM.PIP
PAGE: A MATERIAL: 40 HMC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Ell T LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv BlHdTe
R K
--------------------------------------------------------
TeeRun TeeRun
1.049 2.00 5.00 2.00 5.00 6.00 1.00 10.00 10.00 5.00
2.00 2.00
1.610 4.00 8.00 1.00 9.00 6.00 1.00 10.00 10.00 8.00
3.00 3.00
3.068 7.00 15.00 3.00 16.00 10.00 1.00 13.00 10.00 15.00
0.00 0.00
PAGE: B MATERIAL: THNWL HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D R
Ell Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv TeeRn
3.260 6.70 17.50 7.00 22.00 13.00 1.00 18.00 13.00 0.00
E
Co
N
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 2/22/2019 C:\HASS FILES\PANCAKE-HSM-REV1.SDF
JOB TITLE: Pancake - Sidewalls
a)
0
0
U)
U) a)
4JC
U)4J
a)ra
4J0 U) ..-a)4)
E-0
0(D
44
ro
a)a)
_)
eU)
a)
0U)
a)0
zoo
'cz
-a)
4) U)
a)
Q) Q)
0
U)
.a)
U)
U) U)
a) a) c
0..
a)
.04J
a) •H
OU) U)
0 0
a)
0
z
III N 0 0 0 0 0 0 0
0 0 0 0 0 0 0
N (0 1fl N ,-4 0
-0U)-1--
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 2/22/2019 C:\HASS FILES\PANCAKE-HSW-REV1.SDF
JOB TITLE: Pancake - Sidewalls
WATER SUPPLY CURVE
84+
77+
*\\\\Q\\\\\\\\\\\* <-73.3 psi 8 480 gpm
Flow Test Point
70+
63+
P 56+
R I
E I
S
S 49+
U I
R I
E I X
42+
P I
S I
I 35+
28+
21+
14+ LEGEND
I X = Required Water Supply
I 44.00 psi 0 247.0 gpm
7+
I 0 = Available Water Supply
I 73.37 psi 0 247.0 gpm
0++-+---+----+-----+ ------+ --------+ --------+ ---------+ -----------+
200 300 400 500 600 700 800 900 1000
FLOW (GPM)
it, '
tqca Worldwide www.tyco-fire.com Contacts
Series TYFRB - 5,6 and 8,0 K-factor
Extended Coverage Horizontal Sidewall Sprinklers
Quick and Standard Response (Light Hazard)
General
Description
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Hori-
zontal Sidewall Sprinklers Quick and
Standard Response (Light Hazard) are
decorative 3 mm glass bulb type spray
sprinklers designed for use in hydrau-
lically calculated sprinkler systems in
light hazard, commercial occupancies
such as churches, restaurant seating
areas, hotels, educational facilities,
offices, etc. With their coverage up
to 16 ft (4,9 m) wide by 24 ft (7,3 m)
long, they are designed for installation
along a wall or the side of a beam and
just beneath a smooth ceiling. Hori-
zontal sidewall (HSW) sprinklers are
commonly used instead of pendent or
upright sprinklers due to aesthetics or
building construction considerations,
where piping across the ceiling is not
desirable.
The fast response thermal sensitivity
rating of the Series TY-FRB, 3 mm bulb
type sprinklers provides for a quick
response extended coverage (QREC)
rating for many of the coverage areas
detailed in Tables B and C.
The recessed version of the Series
TY-FRB Extended Coverage Horizontal
Sidewall Sprinkler utilizes either a two-
piece Style 10 (1/2 in. NPT) or Style
40 (3/4 in. NPT) Recessed Escutch-
eon with 1/2 in. (12,7 mm) of recessed
adjustment or up to 3/4 in. (19,1 mm)
of total adjustment from the flush side-
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
wall position, or a two-piece Style 20
(1/2 in. NPT) or Style 30 (3/4 in. NPT)
Recessed Escutcheon with 1/4 in. (6,4
mm) of recessed adjustment or up to
1/2 in. (12,7 mm) of total adjustment
from the flush sidewall position. The
adjustment provided by the Recessed
Escutcheon reduces the accuracy to
which the fixed pipe lengths to the
sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the life
of copper alloy sprinklers beyond that
which would otherwise be obtained
when exposed to corrosive atmo-
spheres. Although corrosion resistant
coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently,
it is recommended that the end user
be consulted with respect to the suit-
ability of these coatings for any given
corrosive environment. The effects of
ambient temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
EMM
The Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association (NFPA), in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
AUGUST 2018
Sprinkler
Identification
Numbers (SINs)
TY333 .EC HSW, 5.6K, 1/2 in. NPT
TY4332 ... EC HSW, 8.0K, 3/4 in. NPT
TFP296
TFP296
Page 2 of 8
Components DEFLECT( 1 - Frame HAT 2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector*
7 - Ejection Spring
6*
* Temperature rating is indicated
on Deflector or adjacent to orifice WRENCH
seat on Frame. 7 FLATS 1/20**
NPT
7/16" (11,1 mm)
4/
CENTERLINE
7/16
(39,7 mm) OF SPRINKLER
I
WATERWAY (11,1 mm)
NOMINAL
MAKE-IN
1-1/2
I
** Pipe thread connections per
i
ISO 7-1 can be provided on (38,1 mmiH special request.
7/16 2-3/16
(55,6 mm) (11,1 mm)
FIGURE 1
SERIES TV-FRB (TY3332)
EXTENDED COVERAGE
HORIZONTAL SIDEWALL SPRINKLER
5.6K-FACTOR, 1/2 INCH NPT
6*
* Temperature rating is Indicated
on Deflector or adjacent to orifice WRENCH
cant ,n Frame 7 FLATS 3/4" **
NPT ......iI 7/16" (11,1 mm) ri
1-1/2° CENTERLINE I
Th38,1 mm) OF SPRINKLER ( WATERWAY 12,7 mm)
NOMINAL
**
MAKE-IN
Pipe thread connections per
I
1-1/2' ISO 7-1 can be provided on (381 mm) special request.
9/16" • 2-1/4"
(14,3 mmi (57,2 mm)
FIGURE 2
SERIES TY-FRB (TV4332)
EXTENDED COVERAGE
HORIZONTAL SIDEWALL SPRINKLER
8.0 K-FACTOR, 314 INCH NPT
Components DEFLECT( 1 - Frame HAT 2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector*
7 - Ejection Spring
Technical
Data
Approvals
UL and C-UL Listed
FM and NYC Approved
(Refer to Table A for complete approval infor-
mation including corrosion resistant status,
as well as the Design Criteria section per-
taining to special design considerations.)
Maximum Working Pressure
Refer to Table B.
Discharge Coefficient
K=5.6 gpm/psi"2 (80,6 Ipm/barl/2)
K=8.0 gpm/psi112 (115,2 1pm/barll2)
Temperature Ratings
Refer to Table A.
Finishes
Sprinkler: Refer to Table E.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Button ......................Brass/Copper
Sealing Assembly.. Beryllium Nickel w/TEFLON
Bulb...............................Glass
Compression Screw .................Bronze
Deflector .........................Copper
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Horizon-
tal Sidewall Sprinklers Quick and Stan-
dard Response (Light Hazard) must be
installed and utilized in Light Hazard
Occupancies, under smooth ceilings
as outlined in the appliable installation
standard recognized by the Approval
Agency (e.g., UL recognizes NFPA 13,
and FM recognize the FM Loss Preven-
tion Data Sheets). Only the Style 10,
20, 30, or 40 Recessed Escutcheon, as
applicable, is to be used for recessed
installations.
TFP296
Page 3 of 8
BULB _____________________ K-FACTOR SPRINKLER TEMPERATURE LIQUID
SPRINKLER FINISH(5)__
T—CHROME TYPE RATING COLOR NATURAL POLYESTERC BRASS PLATED
135°F (57°C) Orange 56
1/2 in EC HSW
(TY3332) 1, 2, 3, 4 155°F (68°C) Red
175°F (79°C) Yellow NPT
135°F (57°C) Orange 5.6
1/2 in. RECESSED EC HSW 1, 2,4 155°F (68°C) Red
NPT (TY3332)
175°F (79°C) Yellow
135°F (57°C) Orange 5.6
1/2 in. RECESSED EC HSWb 1,2,3,4 155°F(68°C) Red
NPT (TY3332)
175°F (79°C) Yellow
135°F (57°C) Orange 8.0
3/4 in. EC HSW
(TY4332) 1, 2, 3, 4 155°F (68°C) Red
175°F (79°C) Yellow NPT
135°F (57°C) Orange 8.0
3/4 in. RECESSED EC HSW8 1, 2, 4 155°F (68°C) Red
NPT (TY4332)
175°F (79°C) Yellow 1, 2, 3, 4
135°F (57°C) Orange 8.0
3/4 in.
RECESSED EC HSWb 1, 2, 3, 4 155°F (68°C) Red
NPT (TY4332)
175°F (79°C) Yellow
Notes:
Listed by Underwriters Laboratories, Inc. (UL) per Table C
Listed by Underwriters Laboratories, Inc. for use in Canada per Table C
Approved by Factory Mutual Research Corporation (FM) per Table D
Approved by the City of New York under MEA 354-01-E
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed corrosion-resistant sprinklers.
Installed with Style 10 (1/2 in. NPT) or Style 40 (3/4 in. NPT) 3/4 in. Total Adjustment Recessed Escutcheon, as applicable
Installed with Style 20(1/2 in. NPT) or Style 30 (3/4 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable
Frame and deflector only
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
SPRINKLER FINISH
K-FACTOR SPRINKLER
TYPE NATURAL I CHROME POLYESTER BRASS PLATED
EC HSW 5.6 (TY3332) 1/2 in. 250 PSI (17,2 BAR) NPT RECESSED EC HSW OR (TY3332) 175 PSI (12,1 BAR) EC HSW
8.0
3/4 in. (1Y4332) (SEE NOTE 1)
RECESSED EC HSW NPT (TY4332)
Notes:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories, Inc. (UL); the Listing by Underwriters Laboratories, Inc. for use in
Canada (C-Ui.); and, the Approval by the City of New York.
TABLE B
MAXIMUM WORKING PRESSURE
TFP296
Page 4 of 8
5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY3332)
R Coverage Minimum Minimum Deflector-to-Ceiling Sprinkler Minimum
eRating sPonse Area(11, Flow(2), Pressure(2), Distance(3), Temperature Spacing(4),
ft x ft (m x m) gpm (1pm) psi (bar) Inches (mm) °F Rating, ft (m)
Quick 16 x 16(4,9 x 4,9) 26(98) 21.6(1,48) 4 to 12 (100 to 300) 135, 155, 175 10(3,1)
Quick 16 x 18(4,9 x 5,5) 29 (110) 26.8(1,85) 4 to 12 (100 to 300) 135, 155, 175 10(3,1)
Quick 16 x 20 (4.9 x 6,1) 32 (121) 32.7 (2,25) 4 to 6(100 to 150) 135 10(3,1)
Quick 16 x 22 (4,9 x 6,7) 35 (133) 39.1 (2,70) 4 to 6(100 to 150) 135 10(3,1)
Standard 16 x 20(4,9 x 6,1) 32 (121) 32.7 (2,25) 4 to 6(100 to 150) 155 10(3,1)
Standard 16 x 22 (4,9 x 6,7) 35 (133) 39.1 (2,70) 4 to 6 (100 to 150) 155,175 10(3,1)
8.0K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)
Response Coverage Minimum Minimum Deflector-to-Ceiling Sprinkler Minimum
Rating Area(1JT, Flow(2), Pressure(2), Distance(3), Temperature Spacing(4),
ft x ft (m x m) gpm (1pm) psi (bar) Inches (mm) °F Rating, ft (m)
Quick 16 x 16 (4,9 x 4,9) 26 (98) 10.6 (0,73) 4 to 12 (100 to 300) 135, 155, 175 10 (3,1)/13 (4,0)(5)
Quick 16 x 18(4,9 x 5,5) 29(110) 13.1 (0,90) 4 to 12 (100 to 300) 135, 155, 175 10(3,1)/13 (4,0)(5)
Quick 16 x 20 (4.9 x 6,1) 32 (121) 16.0(1,10) 4 to 6(100 to 150) 135 10 (3,1)/13 (4,0)(5)
Quick : 16 X 20(4.9 X 6,1) 33(125) 17.0 (1,17) 4 to 12 (100 to 300) 135 10 (3,1)/13 (4,0)(5)
Quick 16 x 22 (4,9 x 6,7) 35 (133) 19.1 (1,32) 4 to 6(100 to 150) 135 10 (3,1)/13 (4,0)(5)
Quick 16 x 22(4,9 x 6,7) 36(136) 20.3(1,59) 4 to 12 (100 to 300) 135 10 (3,1)/13 (4,0)()
Quick 16 x 24(4,9 x 7,3) 39 (148) 23.8(1,64) 4 to 6(100 to 150) 135 10 (3,1)/13 (4,0)(5)
Quick 16 x 24(4,9 x 7,3) 40 (151) 25.0 (1,72) 4 to 12 (100 to 300) 135 10 (3,1)/13 (4,0)(5)
Standard 16 x 20 (4.9 x 6,1) 32 (121) 16.0 (1,10) 4 to 6 (100 to 150) 155 - 10 (3,1)/13 (4,0)(5)
Standard 16 x 20 (4.9 x 6,1) 33 (125) 17.0 (1,17) 4 to 12 (100 to 300) 155 10 (3,1)/13 (4,0)(5)
Standard 16 x 22 (4,9 x 6,7) 35 (133) 19.1 (1,32) 4 to 6(100 to 150) 155,175 10 (3,1)/13 (4,0)(5)
Standard 16 x 22 (4,9 x 6,7) 36(136) 20.3 (1,59) 4 to 12 (100 to 300) 155,175 10 (3,1)/13 (4,0)(5)
Standard 16 x 24 (4,9 x 7,3) 39 (148) 23.8 (1,64) 4 to 6 (100 to 150) 155,175 10 (3,1)/13 (4,0)(5)
Standard 16 x 24(4,9 x 7,3) 40(151) 25.0 (1,72) 4 to 12 (100 to 300) 155,175 10(3,1)/13 (4,0)(5)
Notes:
Backwall (where sprinkler is located) by sidewall (length of throw)
Requirement is based on minimum flow in gpm from each sprinkler. The indicted residual pressures are based on the nominal K-factor.
The centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deflector (Ref. Figures 1 and 2).
Minimum spacing is for lateral distance between sprinklers located along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-
site wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
Minimum spacing is 13 ft (4,0 m) when design pressure exceeds 175 psi (12,1 bar), otherwise the minimum spacing is 10 ft (3 m).
TABLE C
UL AND C-UL LISTING COVERAGE AND FLOW RATE CRITERIA
TFP296
Page 5 of 8
5.6K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (1Y3332)
Coverage Minimum Minimum Deflector-to-Ceiling Sprinkler Minimum
ReRs1onse ating Area('( Flow(2), Pressure(2), Distance(3), Temperature Spacing(4),
fix ft (m x m) gpm (1pm) psi (bar) Inches (mm) Rating, F ft (m)
Quick 16 x 16(4,9 x 4,9) 26(98) 22(1,51) 4 to 12 (100 to 300) 135,155 10(3,1)
Quick 16 x 18(4,9 x 5,5) 30(114) 29(2,00) 4 to 12 (100 to 300) 135,155 10(3,1)
Quick 16 x 20 (4.9 x 6,1) 33 (125) 35 (2,41) 4 to 12 (100 to 300) 135,155 10(3,1)
Standard 16 x 16(4,9 x 4,9) 26 (98) 22 (1,51) 4 to 12 (100 to 300) 175 10(3,1)
Standard 16 x 20 (4,9 x 6,1) 30 (114) 29 (2,00) 4 to 12 (100 to 300) 175 10(3,1)
Standard 16 x 22 (4,9 x 6,7) 33 (125) 35 (2,41) 4 to 12 (100 to 300)) 175 10(3,1)
8.0K EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLER (TY4332)
Response
Coveraqe Minimum Minimum Deflector-to-Ceiling Sprinkler Minimum
Rating Area(11 Flow(2), Pressure(2), Distance(3), Temperature Spacing(4),
fix ft (m x m) gpm (1pm) psi (bar) Inches (mm) °F Rating, ft (m)
Quick 16 x 16(4,9 x 4,9) 32(121) 16(1,10) 4 to 12 (100 to 300) 135,155 10(3,1)
Quick 16 x 18(4,9 x 5,5) 36(136) 20(1,38) 4 to 12 (100 to 300) 135,155 10(3,1)
Quick 16 x 20(4.9 x 6,1) 40(151) 25 (1,72) 4 to 12 (100 to 300) 135,155 10(3,1)
Quick 16 x 22 (4,9 x 6,7) 44(167) 30 (2,06) 4 to 12 (100 to 300) 135,155 10(3,1)
Quick 16 x 24(4,9 x 6,7) '48(182) 36(2,48) 4 to 12 (100 to 300) 135,155 10(3,1)
Standard 16 x 16(4,9 x 4,9) 32(121) 16 (1,10) 4 to 12 (100 to 300)) 175 10(3,1)
Standard " 16 x 18(4,9 x 5,5) 36(136) 20 (1,38) 4 to 12 (100 to 300) 175 10(3,1)
Standard 16 x 20(4.9 x 6,1) 40(151) 25 (1,72) 4 to 12 (100 to 300)) 175 10(3,1)
Standard 16 x 22 (4,9 x 6,7) 44(167) 30 (2,06) 4 to 12 (100 to 300) 175 10(3,1)
Standard 16 x 24(4,9 x 6,7) 48 (182) 36 (2,48) 4 to 12 (100 to 300) 175 10(3,1)
Notes:
Backwall (where sprinkler is located) by sidewall (length of throw)
Requirement is based on maintaining both minimum flow and minimum residual pressure.
The centerline of the sprinkler waterway is located 7/16 in. (11,1 mm) below the deflector (Ref. Figures 1 and 2).
Minimum spacing is for lateral distance between sprinklers located along a single wall, otherwise adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an oppo-
site wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.
TABLED
FM COVERAGE AND FLOW RATE CRITERIA
TFP296
Page 6 of 8
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END 'B" USED FOR
3/4" NPT MODELS)
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Horizon-
tal Sidewall Sprinklers Quick and Stan-
dard Response (Light Hazard) must
be installed in accordance with this
section.
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm).
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of
7 to 14 lb-ft (9,5 to 19,0 N.m). A leak
tight 3/4 in. NPT sprinkler joint should
be obtained with a torque of 10 to
20 lb-ft (13,4 to 26,8 Nm). Higher levels
of torque may distort the sprinkler inlet
and cause leakage or impairment of the
sprinkler.
Do not attempt to make-up for insuf-
ficient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
Series TY-FRB EC
Sidewall Sprinkler
The Series TY-FRB EC Sidewall Sprin-
klers must be installed in accordance
with the following instructions:
Step 1. Horizontal sidewall sprinklers
are to be installed with their center-
line perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the deflector is to face towards the
ceiling.
Step 2. With pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 3).
With reference to Figures 1 and 2, the
W-Type 6 Sprinkler Wrench is to be
applied to the sprinkler wrench flats.
Series TY-FRB Recessed EC
Sidewall Sprinkler
The Series TY-FRB Recessed EC
Sidewall Sprinklers must be installed
in accordance with the following
instructions:
Step 1. Horizontal sidewall sprinklers
are to be installed with their center-
line perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the deflector is to face towards the
ceiling.
Step 2. After installing the Style 10, 20,
30, or 40 Mounting Plate, as applica-
ble, over the sprinkler threads and with
pipe thread sealant applied to the pipe
threads, hand tighten the sprinkler into
the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1
or 2, the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step 4. After the wall has been installed
or the finish coat has been applied,
slide on the Style 10, 20, 30, or 40.
Closure over the Series TY-FRB Sprin-
kler and push the Closure over the
Mounting Plate until its flange comes
in contact with the wall.
Care and
Maintenance
TYCO Series TY-FRB 5.6 and 8.0
K-factor Extended Coverage Horizon-
tal Sidewall Sprinklers Quick and Stan-
dard Response (Light Hazard) must be
maintained and serviced in accordance
with this section. Before closing a fire
protection system main control valve
for maintenance work on the fire pro-
tection system that it controls, per-
mission to shut down the affected fire
protection system must be obtained
from the proper authorities and all per-
sonnel who may be affected by this
action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent oper-
ation may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Refer to Installa-
tion Section.)
Frequent visual inspections are rec-
ommended to be initially performed
for corrosion resistant coated sprin-
klers, after the installation has been
completed, to verify the integrity of the
corrosion resistant coating. Thereafter,
annual inspections per NFPA 25 should
suffice; however, instead of inspecting
from the floor level, a random sampling
of close-up visual inspections should
be made, so as to better determine the
exact sprinkler condition and the long
term integrity of the corrosion resistant
coating, as it may be affected by the
corrosive conditions present.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions. It is recommended
that automatic sprinkler systems be
inspected, tested, and maintained by
a qualified Inspection Service in accor-
dance with local requirements and/or
national codes.
TFP296
Page 7 of 8
5/8±1/4"
(15,9±6,4 mm)
MOUNTING - FACE OF
SURFACE SPRINKLER
FITTING
CLOSURE
2-7/8" DIA.
SERIES
(73,0 mm)
2-1/4" DIA. TY-FRB EC
MOUNTING
-
(57,2mm)
PLATE
(3,2 mm)
1-1/4" (31,8 mm) 3/4" (19,1 mm)
3/4" (19,1 mm) 1/4 (6,4 mm)
FIGURE 5
SERIES TY-FRB RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON 5.6 K-FACOTR, 1/2 INCH NPT
5/8±1/4"
- (15,9±6,4 mm)
MOUNTING FACE OF
SURFACE SPRINKLER
FITTING
MOUNTIN
CLOSURE
1 2-7/8 DIA.
SERIES
(73,0 mm)
TY-FRB EC 2-1/4 01k
(57,2 mm)
PLATE
1
4
1/8"
(3,2 mm)
1-1/4" (31,8 mm) 3/4" (19,1 mm)
3/4" (19,1 mm) 1/4" (6,4 mm)
FIGURE 7
SERIES TY-FRB RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
1/2±1/8'
- (12,7±3,2 mm)
MOUNTING
FACE OF
SURFACE . SPRINKLER
FITTING
CLOSURE
1 2-7/8 DIA.
SERIES
(73,0 mm)
TY-FRB EC 2-1/4" 01k
2mm)
MOUNTING
PLATE
(57,
(3,2 mm)
1-1/4" (31,8 mm) 1/2" (12,7 mm)
1" (25,4 mm) - 1/4 (6,4 mm)
FIGURE 6
SERIES TY-FRB RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
1/2±1/8
(12,7±3,2 mm)
MOUNTING FACE OF
SURFACE SPRINKLER
FITTING
f
CLOSURE
1 2-7/8 DIA.
SERIES
(73,0 mm)
2 1/4" DIA. TV-FRB EC
2 mm)
MOUNTING
PLATE
1/8
(3,2 mm)
1-1/4" (31,8 mm) 1/2" (12,7 mm)
1(25,4mm) 1/4(6,4mm)
FIGURE 8
SERIES TY-FRB RECESSED EC SIDEWALL
SPRINKLER ASSEMBLY WITH TWO-PIECE
1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
TFP296
Page 8 of 8
57-XXX-X-XXX
II I SPRINKLER FINISH
I 1 NATURAL BRASS I TEMPERATURE
I I SIN I - 3 PURE WHITE (RAL9010) RATING
I
I I POLYESTER I 135 135°F (57°C) 376 I 5.6K EC HSW TY3332 - I 4 SIGNAL WHITE (RAL9003) I 155 155°F (68°C) 396 8.0K EC HSW 1Y4332 POLYESTER I
- 1 175 175°F(79°C) 5 JET BLACK (RAL9005)
POLYESTER
9 1 CHROME PLATED
TABLE
SERIES TY-FRB EXTENDED COVERAGE HORIZONTAL SIDEWALL SPRINKLERS
PART NUMBER SELECTION
Limited
Warranty
For warrany terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assembly with
NPT Thread Connections
Specify: Series TY-FRB, (specify SIN),
Extended Coverage Horizontal Side-
wall Sprinkler, K=(specify), (specify)
temperature rating, (specify) finish, P/N
(specify from Table F)
Recessed Escutcheon
Specify: Style (10, 20, 30, or 40)
Recessed Escutcheon with (specify*)
finish, P/N (specify*)
Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
1400 Pennbrook Parkway, Lansdale, PA 194401 Telephone +1-215-302-0700
Alto e2olaJoft.,00n Controfo. AD ,ihto noonrood. AD specifications ond other inton,,otion ohownwn,e current no of document ronlnIo. dodo ondo,. nobjootto ohonaowlthooi notion. Johnson
NATIONAL FIRE PROTECTION ASSOCIATION nod NFPA n,e ,ogIotond trodonobo Of National Fan P,Otoot,on Aa,ociotia Controls TEflON i o,00loto,nd nodoandt of EnRoot