Description: REVISED EZOIC - BLDG B -FIRE ALARM TI (SUITES 200,210,220,250)
Permit No: FPC2018-0362
Status: Closed - Finaled
Applied: 11/05/2018
Issued: 11/27/2018
Finaled Close Out: 02/11/2019
Inspector:
Final Inspection:
Applicant: FPContractor:
CVA SECURITY CHULA VISTA ALARM INC
JAMES RODRIGUEZ 6175 PROGRESSIVE AVE, # STE 400
6175 PROGRESSIVE DR. # STE 400 SAN DIEGO, CA 92154-6647-SAN DIEGO
SAN DIEGO, CA 92154-6648 (619) 585-9111
(619) 585-9111
FEE AMOUNT
FIRE Plan Resub (3rd&Subsequent Submittal/hr) $136.00
FIRE TI Fire Alarm System $620.00
Total Fees: $756.00 Total Payments To Date: $756.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1760-602-4665 1760-602-8561 f I www.carlsbadca.gov
FIRE ALARM SYSTEM ADDITION
SUBMITTAL
EZOIC I SPEC SUITES TENANT IMPROVEMENT
BLDG B - 6021 INNOVATION WAY
CARLSBAD, CA 92009
FPC20I8-0362
6021 INNOVATION WAY #200
REVISED EZOIC - BLDG B - FIRE ALARM TI (SUITES
200.210.220.250)
2132611400
11/1912018
FPC20I8-0362 . FUEGO ENGINEERING & DESIGN INC PREPARED FOR: CHULA VISTA ALARM INC
P.O. BOX 212731 6175 PROGRESSIVE AVE. SUITE 400
CHULA VISTA CA, 91921 SAN DIEGO, CA 92154
CELL: (619)610-8637 PHONE: 619-585-9111
OFFICE: (619)796-3360
PROJECT: EZOIC I SPEC SUITES TENANT IMPROVEMENT
BLDG B - 6021 INNOVATION WAY
CARLSBAD, CA 92009
Model Number Description CSFM#
ES-200X FIRE LITE FIRE CONTROL PANEL (EXISTING) 7165-0075:0500
FCPS-24F56 FIRE LITE NAC BOOSTER POWER SUPPLY 7135-0075:0206
MMF-301 FIRE LITE ADDRESSABLE MINI-MONITOR MODULE 7272-0075:0185
CRF-300 FIRE LITE ADDRESSABLE RELAY MODULE 7272-0075:0185
RTSI51 KEY SYSTEM SENSOR REMOTE TEST/RESET STATION 7300-1653:0212
P2WL SYSTEM SENSOR HORN-STROBE WALL 7300-1653:0503
SWL SYSTEM SENSOR STROBE WALL 7300-1653:0504
P2CWL SYSTEM SENSOR HORN-STROBE CEILING 7300-1653:0503
P2WK SYSTEM SENSOR HORN-STROBE WALL, WP 7125-1653:0188
SWK SYSTEM SENSOR STROBE WALL, WP 7300-1653:0187
PS-1270 I2VDC 7AMP BATTERY
. FUEGO ENGINEERING & DESIGN INC PREPARED FOR: CHULA VISTA ALARM INC
P.O. BOX 212731 6175 PROGRESSIVE AVE. SUITE 400
CHULA VISTA CA, 91921 SAN DIEGO, CA 92154
CELL: (619)610-8637 PHONE: 619-585-9111
OFFICE: (619)796-3360
FCPS-24FS6
24 Volt, 6 Amp Power Supply
General
The Fire-Lite FCPS-24FS6(C/E) is a compact, cost-effec-
tive, 6-amp remote power supplies with battery charger. The
FCPS-24FS6(C/E) may be connected to any 12 or 24 volt fire
alarm control panel (FACP) or may stand-alone. Primary appli-
cations include notification appliance (bell) circuit (NAG)
expansion (to support ADA requirements and NAG synchroni-
zation) or auxiliary power to support 24 volt system accesso-
ries. The FCPS provides regulated and filtered 24 VDC power
to four notification appliance circuits configured as either two
Glass B (Style Y) and Class A (Style Z, with ZNAG-4 option
module) or four class B only. Alternately, the four outputs may
be configured as any combination of resettable/non-resettable
power outputs (optimal for powering four-wire smoke detec-
tors. The FFCPS-24F56(G/E) also contains a battery charger
capable of charging up to 7.0 Amp hour batteries. FCPS-
24FS6(C/E) is ULC-listed.
NOTE: Unless otherwise specified, the term FCPS-24FS6 used in
this document refers to the standard FCPS-24FS6, FCPS-
24FS6C, FCPS-24FS6E
Form-C normally-closed trouble relay.
Fully supervised power supply, battery, and NAGs.
Selectable earth fault detection.
AG trouble report selectable for immediate 2-hour delay.
Works with virtually any UL 864 fire alarm control which uti-
lizes an industry-standard reverse-polarity notification cir-
cuit (including unfiltered and unregulated bell power).
Requires input trigger voltage of 9 - 32 VDC.
Self-contained in compact, locking cabinet - 15"H x 14.5"W
x 2.75"D (cm: 38.1H x 36.83W x 6985D).
DF-52301 :A2 • D-025
(a FureuTe'ALarms
by Honeywell
Includes integral battery charger capable of charging up to
18 AH batteries. Cabinet capable of housing 7.0 AH batter-
ies.
Battery charger may be disabled via DIP switch for applica-
tions requiring larger batteries.
Fixed, clamp-type terminal blocks accommodate up to 12
AWG (3.1mm2) wire.
Specifications
Primary (AC) Power:
FCPS-24FS6: 120 VAC, 60 Hz, 3.2A maximum.
FCPS-24F56/E: 240 VAC, 50 Hz, 1.6A maximum.
Wire Size: minimum #14 AWG (2.0mm) with 600 V insula-
tion.
Control Input Circuit:
Trigger input Voltage: 9 to 32 VDC.
Trigger Current: 2.0 mA (16-32 V); Per Input: 1.0 mA (9
-16V).
Trouble Contact Rating: 5 A at 24 VDC.
Auxiliary Power Output: Specific application power 500 mA
maximum.
Output Circuits:
+24 VDC filtered, regulated.
3.0 A maximum for any one circuit.
Total continuous current for all outputs (stand-alone mode):
- FGPS-24F: 4.0 A maximum.
Total short-term current for all outputs (NAG expander mode):
- FCPS-24F: 6.0 A maximum.
Features
UL-Listed Notification Appliance Circuit (NAG) synchroniza-
tion using System Sensor, Wheelock, or Gentex "Com-
mander2" appliances.
• Operates as a "sync-follower' or as a "sync-generator"
(default). See note on page 2.
Contains two fully-isolated input/control circuits - triggered
from FACP NAG (NAC expander mode) or jumped perma-
nently "ON" (stand-alone mode).
Two Glass B (Style Y) or Class A (Style Z, with ZNAG-4
module) NAGs (circuits 1 & 3)
6-amp full load output, with 3 amps maximum/circuit, in
NAC expander mode (UL 864).
4-amp continuous output in stand-alone mode (UL 1481).
Compatible with coded inputs; signals passed through.
Optional power-supervision relay (EOLR-1).
In stand-alone mode, output power circuits may be config-
ured as: resettabie, (reset line from FACP required),
non-resettable, or a mix of two and two.
Fully regulated and filtered power output - optimal for pow-
ering four-wire smoke detectors, annunciators, and other
system peripherals requiring regulated/filtered power.
Power-limiting technology meets UL power-limiting require-
ments.
DF-52301 P.2 • 5/17/13 - Page 1 of 4
Secondary Power (Battery) Charging Circuit:
Supports lead-acid batteries only.
Float-charge voltage: 27.6 VDC.
Maximum current charge: 250 mA.
Maximum battery capacity: 7.0 AH.
Applications
Example 1: Expand notification appliance power an additional
6.0 A. Use up to four Class B (Style Y) outputs or four Class A
(Style Z) outputs (using ZNAC-4). For example, the FACP noti-
fication appliance circuits will activate the FCPS when reverse-
polarity activation occurs. Trouble conditions on the FCPS are
sensed by the FACP through the notification appliance circuit.
Example 2: -Use the FCPS to expand auxiliary regulated 24-
volt system power up to 4.0 A. Both resettable and non-reset-
table power options are available. Resettable outputs are cre-
ated by connecting the resettable output from the FACP to one
or both of the FCPS inputs.
Example 3: Use addressable control modules to activate the
FCPS instead of activating it through the FACP notification
appliance circuits. This typically allows for mounting the FCPS
at greater distances" away from the FACP while expanding
system arôhitecturè in vaTrious applications.
For example, an addressable control module is used to acti-
vate the FCPS, and an addressable monitor module is used to
sense FCPS trouble conditions. Local auxiliary power output
from the FCPS provides iower to the addressable control
module.
*NOTE: Addressable FACP5 are capable of locating control and
monitor modules at distances of up to 10,000 feet (3,046 meters).
Agency Listings and Approvals
These listings and approvals apply to the modules specified in
this document. In some cases, certain modules or applications
may not be listed by certain approval agencies, or listing may
be in process. Consult factory for latest listing status.
UL Listed: S2424, S1287
ULC Listed: S2424
CSFM Approved: 7315-0076:176
MEA: 387-94E
Ordering Information
FCPS-24F56: 6.0 A, 120 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.59W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
FCPS-24FS6 is ULC-listed.
FCPS-24FS6E: 6.0 A, 240 VAC remote charger power supply.
Includes main printed circuit board, transformers, enclosure
(15"H x 14.5"W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and
installation instructions.
ZNAC-4: Glass A (Style Y) NAG option module.
EOLR-1: 12/24 VOG end-of-line relay for monitoring four-wire
smoke detector power.
BAT-1270: Battery, 12-volt, 7.0 AH (two required).
PS-1270: Battery, 12-volt, 7.0 AH (two required).
90286: Optional module mounting kit, is required to install an
addressable module on the power supply main circuit board.
S
Sync Follower/Generator Note
In some installations, it is necessary to synchronize the flash
timing of all strobes in the system for ADA compliance.
Strobes accomplish this by monitoring very short timing pulses
on the NAC power which are created by the FACP. When
installed at the end of a NAG wire run, the FCPS-24F56 can
track (i.e. "follow") the strobe synchronization timing pulses on
the existing NAG wire run. This maintains the overall system
flash timing of the additional strobes attaches to the FCPS.
When the FCPS-24FS6 is configured (via DIP switch settings)
as a "sync follower:' the FGPS's NAG outputs track the strobe
synchronization pulses present at the FCPS's sync input ter-
minal. The pulses originate from an upstream FACP or other
power supply.
When the FCPS-24FS6 is configured (via DIP switch settings)
as a "sync generator," the FCPS's sync input terminals are not
used. Rather, the FCPS is the originator of the strobe synchro-
nization pulses on the FCPS's NAG outputs. In "sync genera-
tor" mode, the sync type (System Sensor, Wheelock, or
Gentex) is selectable via DIP switch settings.
Standards and Codes
The FCPS-24FS6 complies with the following standards:
NFPA 72 National Fire Alarm Code.
UL 864 Standard for Control Units for Fire Alarm Systems
(NAG expander mode).
UL 1481 Power Supplies for Fire Alarm Systems.
Page 2 of 4— OF-52301:A2 • 5/17/13
..
S
. NOTE: All NAC outputs can
be converted to Style Z with
Style Y NAC or ZNAC-4 option module. FCPS Door Holder Trouble
Power Style Y NAC Style Y NAC Style Y NAC Contact
Output #4 Output #3 Output #2 Output #1 Output
AC
Power
INPUT/OUTPUT
FUNCTIONS
are programmable by
SWI DIP switch settings
24 VDC
Specific
Application
Power
NAG Control
Input #2
(from FACP)
NAC Control
Input #1
(from FACP)
Sync Input
FCPS
Battery Charger
Simplified Block Diagram
DF-52301:A2 • 5/17/13 - Page 3 of 4
Auxiliary Output: - -Aux. Common
500 mA Specific-
Application Power + Aux. 24 VDC
- - Control Input 2
- + Control Input 2
- + Out/Trouble Contact
- - Out Common
4 - - Control Input 1
3 - + Control input 1
2 - - Sync Input
Swi - + Sync Input Uuuut TB4 a *NOTE., Auxiliary Power
Output Is power-limited
but NOT supervised. SWI:
Programming
DIP Switches
(013 a
= 2
9
CL
Cr
FL
0,
0)
Sr
C
— 0)
CL 0) 03
CD.
.
a 0)
0)
C (0
I I I I
Non-Power-Limited
J2: To Transformer #2
JI: To Transformer #1 LEi 0 Oo
F1 Joe 0
Battery Fuse
15A. 30 V (:I
JP4 D [M 0
- Battery LEDs (L to R): L_ + Battery -AC Power (green)
- Ground Fault (yellow)
JP4: Supervised, - Battery Trouble (yellow)
Non-Power-Limited NAC Trouble (yellow)
18 All, 24 VDC Charger Trouble/AC Loss (yellow)
loraffllm
Normally Open
Normally Closed
Common
TB5: Trouble Relay
Form-C Fail-Safe
TB2
(shown energized)
K 8 7 6 5 4 3 2 1 III — 32
4- JP1:
4- 1 Lj
Ground Fault
Detection
[J2
J1
4
0
0
TB2: Power-Limited, . NAC/Out 1 + Supervised In NAC Mode NAC/Out 1 -
with Jumpers J5, JP6, NAC/Out 2
TBI: Supervised JP7, & JP8 In positions NAC/Out 2-
- Earth
shown below. NAC/Out 3 + NAC/Out 3- I —ACNeutrai
NACIOut4+-1 I ,— ACI- lot NAC/Out 4----,
Jp1 I,-'-' "
J3 - J3: ZNAC-4
JP2 Connector
I
JP2 & JP3:
Input Selection 0
0 0 0
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
S FIRE ENGINEERING BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7315-0075:0206 Page 1 of 1
CATEGORY: 7315 -- POWER UNITS
LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653
Contact: Vladimir Kireyev (203) 484-7161 Fax (203) 484-7309
Email: vladimir.kireyevHoneyweIl.com
DESIGN: Models FCPS-24F56 and FCPS-24F58 are power limited power supply/battery chargers
used for supervision and expanded power driving capability of up to four Notification
Appliance Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable
outputs. Model ZNAC-4 Class A converter. Refer to listee's data sheet for additional detailed
product description and operational considerations.
RATING: 120 VAC, 24 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, product designation, electrical rating and UL label.
APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm
control units.
NOTE:
11
*Rev. 05-06-05JW
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
5 Date Issued: July 01, 2017 Listing Expires June 30, 2018
Authorized By: DAVID CASTILLO, Program Coordinator
Fire Engineering Division
I HI HT H
MODEL PS-SZYO El
salwy
fir;~ :Avi
M00 al.
19
Absorbent Glass Mat (AGM) technology for superior
performance
Valve regulated, spill proof construction allows safe
operation in any position
Power/volume ratio yielding unrivaled energy density
Rugged impact resistant ABS case and cover (UL94-HB)
Approved for transport by air. D.0.T., l.A.T.A., F.A.A. and
C.A.B. certified
U.L. recognized under file number MH 20845
Nominal Voltage........................................................................12 volts (6 cells)
Nominal Capacity
20-hr. (350mA to 10.50 volts) ........................................................7.00 AH
10-hr. (650mA to 10.50 volts) .......................................................6.50 AH
5-hr. (1.2A to 10.20 volts) ............................................................6.00 AH
1-hr. (4.5A to 9.00 volts) ..............................................................4.50 AH
15-mm. (14A to 9.00 volts) .................................................................3.50 AH
Approximate Weight ...........................................................4.80 lbs. (2.18 kg)
Energy Density (20-hr. rate) ................................1.49 W-h/1n3 (90.95 W-h/1)
Specific Energy (20-hr. rate) ..............................17.50 W-h/lb (38.58 W-h/kg)
Internal Resistance (approx.) ......................................................23 milliohms
Max Discharge Current (7 Mm.) ...............................................21.0 amperes
Max Short-Duration Discharge Current (10 Sec.)..................70.0 amperes
Shelf Life (% of nominal capacity at 68°F (20°C))
1 Month ......................................................................................................97%
3 Months.....................................................................................................91%
6 Months ....................................................................................................83%
Operating Temperature Range
Charge .. ........................................................... -4"F(-20°C)to 122°F(50"C)
Discharge ....................................................... -40°F(-40°C)to 140°F(60°C)
case...................................................................................................... ABS Plastic
Power-Sonic Chargers ................................................ PSC-12800A, 12800A-C
Fl - Quick disconnect
tabs, 0.187" x 0.032"-
Mate with AMP. INC.
FASTON "187" series
—OR—
F2 - Quick disconnect
tabs, 0.250"x 0.032"
- Mate with AMP. INC
FASTON "250" series
Fl F2
1-324 -14-I
I4'5 EAI 6.35
1-6.35-I 1-7.95--I XO.8 '"''X0.8
L
is
L: 5.95 (151) W. 2.56 (65) H: 3.70 (94) HT: 3.86 (98)
Tolerances are +/-0.04 In. (1- 1mm) and +/- 0.08 in. (/- 2mm) for
height dimensions. All data subject to change without notice.
Z I-MIN11 ii 11:0 S.. a am, 1. 14 1 6101
MINES NOUN 10 UIIIIIII! UIIIIUP!1III :HUUIIIUI uUiEiiI•IIIRi Standing Period (Months) 8.0
00 is rd
° - - -nos08:y uros -
\ Is required.
80 ctrar,~ngtakrre N 5°C "
-(41-F) . USfleS0) (41 F) tohetprev& \. N MIcecIty.
40°C 3 C 20°C padty. Do -I
0 /\
0reerray
40 - - (104°F) _(86°F) - -(68°F) tOtbattatesloac
ft state.
(0
.2 S.
C 0
S. C 0)
0 10 0.
o 0 2 4 6 8 10 12 14 16 18 20
14.0
13.0
Discharge Time vs. Discharge Current
0.35 0.70 1.4 3.5 7.0 14
Discharge Current (A)
10
0) 5
I- 10.
2 03
(0 JC
. TI
a
30
E
.(68°9
-_ 20
._ 15
U..
U lll I. 'iUU I..u.
III I 10 (104°F) I.._ I• 1
(32°F)
100
120
IOC
80
Shelf Life & Storage Discharge Characteristics
Cycle Applications: Limit initial current to 2.1A. Charge until battery voltage
(under charge) reaches 14.4 to 14.7 volts at 68°F (20°C). Hold at 14.4 to 14.7
volts until current drops to under 70mA. Battery is fully charged under these
conditions, and charger should be disconnected or switched to "float" voltage.
"Roar or "Stand.By" Service: Hold battery across constant voltage source of
13.5 to 13.8 volts continuously. When held at this voltage, the battery will seek its
own current level and maintain itself in a fully charged condition.
Note: Due to the self-discharge characteristics of this type of battery, it is
imperative that they be charged within 6 months of storage, otherwise permanent
loss of capacity might occur as a result of sulfation.
1.2 2.4 6 12 24 36481 2 4 6810 20 40
h
Discharge Time
Life Characteristics in Stand-By Use
I I I Ambient Temperature 20°C (68°F) I
Float Charging Voltage
2.25 -2.30 V/Cell
0 1 2 3 4
Years
Life Characteristics in Cyclic Use
~X I
Me
Depth 100% Depth 501
-
Depth 30%
1. Discharge Current 0.2C (Final Voltage 1. Coll)
- 2. Charge Current: 0.11C I I I
3. Ambient Temperature: 20°C to 25°C (68°F to 77°F) I I I I
200 400 600 800 1000 1200
Number of Cycles
0 0
S
Power-Sonic offers a wide range of chargers suitable for batteries up to 100AH. Please refer to our website www.power.sonic.com for a complete range of useful
Please refer to the Charger Selection Guide in our specification sheets for "C-Series downloads, such as product catalogs, material safety data sheets (MSDS), ISO
Switch Mode Chargers" and "Transformer Type A and F Series". Please contact our certification, etc..
Technical department for advice if you have difficulty in locating suitable models.