HomeMy WebLinkAbout1822 ASTON AVE; ; FPC2021-0100; PermitPERMIT REPORT
Fire Permit
Print Date: 10/13/2021
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
1822 ASTON AVE, CARLSBAD, CA 92008-7306
FIRE-Construction Commercial Work Class:
2121202100 Track#:
$0.00 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Fire Sprinklers
(city of
Carlsbad
Permit No: FPC2021-0100
St atus: Closed -Finaled
Applied: 06/07/2021
Issued: 06/22/2021
Finaled Close Out: 10/13/2021
Inspector:
Final Inspection:
Description: HAYES -SPRINKLER Tl FOR NEW OFFICE AND SHIPPING/RECEIVING ROOM (20 HEADS)
Applicant:
INDUSTRIAL FIRE SPRINKLER CO INC
JAKE SANDAGE
3845 IMPERIAL AVE
SAN DIEGO, CA 92113-1702-SAN DIEGO
(619) 266-6030 x109
FEE
FIRE NFPA 13 or 13R System 7 -100 heads
Total Fees: $553.00
Fire Department
Total Payments To Date: $553.00
FPContractor:
INDUSTRIAL FIRE SPRINKLER CO INC
3845 IMPERIAL AVE
SAN DIEGO, CA 92113-1702
(619) 266-6030
Balance Due:
AMOUNT
$553.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
INDUSTRIAL
FIRE SPRINKLER CO., INC.
CA LIC .C-16 558084 HI LIC. C-20351 COLIC. 11-1058
UT LIC. 7336958-5501 VA LIC. 2705 125390A
HAYES T.I.
1822 ASTON AVE
CARLSBAD, CA 92108
MATERIAL SUBMITTAL
3845 Imperial Ave., San Diego, CA., 9211 3 • Phone (619) 266-6030 • Fax (619) 266-6035
'\IIKINCG® TECHNICAL DATA
Page 1 of 6
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1. DESCRIPTION
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is a small
thermosensitive glass bulb spray sprinkler available with various finishes and tem-
perature ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors
are desired. In addition, these coatings have been investigated for installation in
corrosive environments and are Listed and Approved as indicated in the Approval
Charts.
2. LISTINGS AND APPROVALS
,@. cULus Listed: Category VNIV
<8> FM Approved: Class Series 2000
~ VdS Approved: Certificates G414009, G414010, 84040095, and 4880045
tLl'CB) LPCB Approved: Certificate 096e/06
~ WARNING: Cancer and Reproductive Harm•
l_D www.P65Wamings.ca.gov
( E CE: Standard EN 12259-1,Declaration of Performance DOP _ Sprinklers_LPCB _5-2-19, DOP _ VK302ENT _29-1-20 & DOP _ VK302-
57C _30-9-20
China Approval: Approved according to China GB standard
0 MED Certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003
Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for
FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to 175 psi (12 bar) water working pressure
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" NPT, 15 mm BSP
Nominal K-factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-1/4" (58 mm)
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500
Bulb: Glass, nominal 3 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap -ENT plated.
Ordering Information: (Also refer to the current Viking price list.)
Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Form No. F_033314 20.07.14 Rev20.1 Replaces Form No. F _033314 Rev 19.3
(Added ENT to CE Approval.)
Page 2 of 6
\IIKINai® TECHNICAL DATA
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for.the latest edition of this technical data page: www.vikinggroupinc.com
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G
For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the current Viking price list.)
Sprinkler Wrenches:
A. Standard Wrench: Part No. 21475M/B.
B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006)
C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010)
**A½" ratchet is required (not available from Viking).
***Allows use from the floor by attaching a length of 1" diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F _051808.
Sprinkler Cabinets:
A. Six-head capacity: Part No. 01724A (available since 1971)
B. Twelve-head capacity: Part No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
5. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
The Viking Microfast® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Wrench Flat
Figure 1:
Standard Sprinkler Wrench 21475M/B
Form No. F _033314 20.07.14 Rev 20.1
Page 3 of 6
'JIKINCG® TECHNICAL DATA
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (KS.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Ordinary 135 °F (57 °C) 100 °F (38 °C) Orange
Ordinary 155 °F (68 °C) 100 °F (38 °C) Red
Intermediate 175 °F (79 °C) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 °C) 225 °F (107 °C) Blue
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings3: White Polyester, and Black Polyester. ENT in all temperature ratings except 135 °F (57 °C)
Footnotes
1 The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
For ENT coated automatic sprinklers, the waterway is coated. only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings.
Sprinkler wrench 13655W/B""
for recessed pendent
sprinklers
** A 1/2" ratchet is required
(not available from Viking)
... ... Carefully slide the wrench sideways around
the protective cap, ensuring engagement with
the sprinkler wrench flats
Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers
FormNo.F_033314 20.07.14 Rev20.1
I
I
Page 4 of6
"IKINCG® TECHNICAL DATA
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@viklngcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggrouplnc.com
Approval Chart 1 (UL)
The VUdng llk:lolast9 Quick ilNPonN
Pendent 8prlnlder VK302
lllulmum 171 PII (12 a., WNP
Base
Part
Number'
SIN
Thread Size Sprlnkler Style 1----.----ll----r----+---.--+-------,---,-----,.--------.----.--C-h-ln-a--i
NPT BSP U.S. metric' Inches mm cULus• VdS LPCB CE' MED" Approval
Nomlnal
K-factor
overall
length
Listings and Approvals'
(Refer also to Design Criteria.)
12979 VK302 Pendent 1/2" 15 mm 5.6 80.6 2-1/4 58 A1Z, 61Y, 02, C2X A1 A1Z, 61V O1Z.C1Y,O2,
A1Z, 61Y
21354' VK302 Pendent 15 mm 5.6 80.6 2-1/4 58 03
Approved Temperature Ratings
A-135 °F (57 'C), 155 'F (68 'C), 175 'F
(79 °C), 200 "F (93 'C), 286 "F (141 °C)
5.6 80.6 2-1/4
Approved Finishes
58 A1Z, 61Y O1Z, C1Y, 02
Approved Escutcheons
X • Standard surface-mounted escutcheon or the
Viking MlcromatiC-Model E-1 Recessed Escutcheon
0 1
03
B -135 "F (57 'C), 155 'F (68 'C), 175 'F
(79 'C), and 200 'F (93 'C)
1 -Brass, Chrome, White
Polyester", Black Polyes-
ter4•
2-ENP
Y • Standard surface-mounted escutcheon or recessed with the Viking Micromati~
Model E-1, E-2, or E-3 Recessed Escutcheon
C -155 'F (68 'C). 175 'F (79 'C). and
200 'F (93 'C)
0 -155 'F (68 'C), 175 'F (79 'C), 200 'F
(93 'C), 286 'F (141 'C)
3-Chrome Z -Standard surface-mounted escutcheon
Footnotes
' Base part number shown. For complete part number, refer to Viking's current price schedule.
• Metric K-factor measurement shown Is when pressure Is measured In Bar. When pressure Is measured In kPa, divide the metric K-factor shown by 10.0.
• This table shows the listings and approvals available at the time of printing. Other approvals may be In process.
• Listed by Underwriters Laboratories Inc. for use In the U.S. and Canada.
5 cULus Listed as corrosion-resistant.
• Other colors are available on request with the same Listings and Approvals as the standard colors.
1 CE: Standard EN 12259-1,Declaration of Performance OOP _Sprinklers_LPCB_S-2-19, OOP _VK302ENT_29-1-20 & OOP _VK302-57C_30-9-20.
1 MED Certified, Standard EN 12~59-1, EC-0832-MED-1003.
• Approved accordi to China GB Standard.
DESIGN CRITERIA -UL (Also refer 10 Approval 018111 above.)
cULys Ll1Stoa Requlceroents:
The Viking Microfas~ Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in
accordance with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F _091699 • Care and Handling of Sprinklers. Also refer to Form No. F _080614
for general care, Installation, and maintenance Information. Viking sprinklers are to be Installed In accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F _033314 20.07.14 Rev 20.1
"
TECHNICAL DATA
Page 5 of6
MICROFASTe QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877--384-5464 Fax: 269-818-1680 Email: techsvcs@vik.ingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vlklnggrouplnc.co!!'
Approval Chart 2 (FM)
The Viking llk:n)faet9 Quick Rnponu
Pendent Sprtnlder VK302
llulmum 175 PSI (12 a., WWP
Base Part Sprinkler Thread Size Nominal K-factor Overall Length SIN Number' Style NPT BSP U.S. metric' Inches mm
12979 VK302 Pendenl 112· 15mm 5.6 80.6 2-1/4 58
2-1/4 58
2-1/4 58
2-1/4 58
Approved Temperature Rating•
FM Approval•'
(Refer allo to Design Criteria.)
A1Z,B1Y,O2X,C2
C3
A1Z,B1Y,D2X,C2
A1Z,B1Y
Approved Escutcheons
A. 135 •f (57 °C). 155 "F (68 °C), 175 °F (79 "C), 200 °F Approved Finishes
(93 •c), 286 "F (141 •c) 1-Brass, Chrome, White Polyester',
B -135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and d Bl k p I t r'
200 •F (93 "C) an ac o yes e
C • 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 2 • ENT5 "F (141 •q 3 -Chrome
X -Standard surface-mounted escutcheon or the
Viking MicromatiC-Model E-1 Recessed Escutcheon
Y -Standard surface-mounted escutcheon or recessed
with the Viking MicromatiC-Model E-1 or E-2
Recessed Escutcheon
D • 155 "F (68 °C), 175 °F (79 "C}, 200 "F (93 "C)
Z -Stand~rd surface-mounted escutcheon
Footnotes
1 Base part number shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by
10.0.
1 This table shows the FM Approvals available at the time of printing. Other approvals may be in process.
• Other colors are available on request with the same Approvals as the standard colors.
5 FM approved as corrosion resistant.
8 Approved accordin to China GB Standard.
DESIGN CRITERIA -EN (Alto r.r.r 10 Approval Chart 2 above.)
EM AIUICDitll B1gulc11W1D1I;
The Viking Microfast-Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage pendent sprinklers
as Indicated in the FM Approval Guide. For specific application and Installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM ln1tallatlon guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F _091699 -Care and Handling of Sprinklers. Also refer to Form No. F _080614
for general care, Installation, and maintenance Information. Viking sprinklers are to be Installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organlza-
tlons, and also with the provisions of governmental codes, ordinances, and standards, whenever appllcable.
FormNo.F_033314 20.07.14 Rev20.1
Page 6 of 6
'\IIKINGi® TECHNICAL DATA
I
MICROFAST® QUICK
RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
1/2"
1-3/4"
(45 mm)
Installed with a standard
1/8" surface-mounted
escutcheon
Ceiling Opening Size:
2-5/16" (59 mm) minimum
2-1/2" (64 mm) maximum
Figure 3: Sprinkler Dimensions with a Standard Escutcheon
2-1/8"~ (54 mm) .... , ,?J':, --.,,.. • t #,
"" .. ,. I • •
1-1/8" 2""
Ceiling Opening Size:
2-5/16" (59 mm) minimum
2-1/2" (64 mm) maximum
2-1/8"~ (54 mm) ,, ., /JJ
• Ji ., .. .
1-3/4"
(45 mm)
Max.
(29 mm)
Min. (51 mm)
Max.
1-1/8"
(29 mm)
Min.
♦ n:•
Installed with a
Model E-1 Recessed
Escutcheon
♦
Installed with a Model
E-2 Thread-on Recessed
Escutcheon
Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons
FormNo.F_033314 20.07.14 Rev20.1 Replaces Form No. F _033314 Rev 19.3
(Added ENT to CE Approval.)
' al
0
GENBW. INFORMATION
GENERALINFORMA'IION
HANGERMATE®
Rod Hanging Anchors
PRODUCT DESCRIPTIDrl
Hangermate is an all steel threaded fastening system for suspending steel threaded rod vertically
overhead in pipe hanging, fire protection, electrical conduit and cable-tray applications. They are
available in versions which can be installed in a variety of base materials including steel pur1ins, bar
joists and beams, wood frame columns and beams, as well as concrete ceilings, beams and columns.
Steel threaded rods in 1/4" and 3/8" diameters can be vertically suspended with Hangermate
{a 1 /2" diameter size is also available for wood). They are also offered in a side mount style for
lateral installation of 1/4" and 3/8" diameter steel threaded rods onto joists, columns and overhead
members. For all steel and wood hangers, a Hangennate Socket Driver is recommended to provide
proper Installation with a drill ocrf!NI gun. For concrete hangers, a powered impoct tool with a clutch
is recommended.
A pivot head version is also available for flexible connection angle and positioning of rod hangers.
AA acoustical ceiling eyelet version is also available for hanging wire or cable attachments.
GHIERAL APPLICATIO!lS ArlO USES
• Hanging Pipe and Sprinkler Systems • 1-NAC Ductwork and Strut Channels
• Suspending Conduit and Gable Trays • Suspended Ceilings
• Lighting Systems and Overhead Utilities • Mounting Security Equipment
FEATURES AUD BErlEHTS
+ ~ and speed of overhead installation
+ Lower in-place cost, when compared to beam clamps, lag bolts and dropins
+ Steel and wood Hangermate can be installed with a drill scrf!NI gun
+ Side mount versions available for steel and wood Hangermate
+ Socket drivers, pole tool and accesrories to optimize ease of installation
APPROVALS AND LISTINGS
• FM Approvals {FM) -see listing for applicable sizes and types
Pipe Hangers components for automatic sprinkler systems -File No. JI 3015153
• Underwriters Laboratory (U..) -see listing for applicable sizes and types
Pipe Hangers -File No. EX 1289
GUIDE SPECIFICATIOUS
CSI Divisions: 03 16 00 -Concrete Anchors, 05 05 23 -Metal Fastenings and 06 05 23 -Wood,
Plastic, and Composite Fastenings. Rod Hangers shall be Hangermate ancmrs as supplied by
DEWALT, Towson, MD. Anchors shall be installed in accordance with published instruction and the
Authority Having Jurisdiction.
DEWALi -·-
SECTION CONTENTS
General lnformadol L ........................ 1
Malertal Speciflcalions ................... 2
lnstallallon Specifications .............. 2
Plllfonnllice Data ............................ 3
Orderq lnformallon ....................... 5
STEEL HANOERMATE
WOOD HANOERMATE
~
CONCRETE HANOERMATE
ANCHOR MA1BIIALS
• Zinc Plated Carbon Steel
ANCHOR SIZE RANGE (lYP,)
• 1/4" to 3/8" for Steel
• 1/4" to 1/2" for Wood
• 1/4" to 3/8" for Concrete
(Threaded Coupler Heads)
1IIREAD VERSION
• Unified Coarse Thread (Lt-JC)
SUll'IBlE BASE MATERIALS
• Steel Pur1ins and Beams
• Wood and Timber
• Concrete Members
www.DEWALT.com
DEWALi MATERIAL SPECIFICATIONS
MATERIAL SPECIFICA110NS
C I I 111111111
Screw Boo; Case hardened carboo steel
C',oopllng (LtlC thread) / Eyelet Case hardened carboo steel
ZilcPlatilg A.5TM B633, SC1, Type Ill (Fe/Zn5)
INSTAI.LA110N SPECIFICAllONS
Steel ==---■■--Wood ---.......... 11'· Ill" .......... 1,,. Ill" 111"
Coupling Thread Sile (LtlC) 1/4-20 3/8-16 Crupllng Thread Sile (LtlC) 1/4-20 3/8-16 1/2-13
r.oi..>ling Thread Depth (11.) 3/8 3/8 Crupling Thread Depth (i1,) 3/8 3/8 3/8
Coupling Height (111.) 3/4 3/4 Coupling Height Qn.) 13/16 13/16 13/16
Sock.et Driver Sile (i1.) 1/2 1/2 Sock.et Driver Sae Qn.) 518 518 518
Nole: the side ITlOl.flt co.C)lngs hM U tined delXh (tlYwJh head). l«lal: the side mollll cn4)lings hM U tined delXh (tlYwJh head).
Concnllll .. .......... 11'■
ANSI DrUI Bit (In.) 1/4
Overall Screw Sl1lllk l..eng1h 1-1/4
/wm Thread l..eng1h (111.) 1-1/8
Coopler / W~lng ~ (11.) 27/64
rrtegral Was'tf!I O.D. (i1.) 31/64
Coupling Thread Sile (LtlC) 1/4-20
Coopllng Thread Depth Qn.) 3/8
Sock.et Driver Sile (i1.) 3/8
lnltallallon Guldellnes
1. If ~oillng Is required (certain types of wood
truss/wood j(jsl and all concrete base materlals),
select the recommended am bit type end dameter.
For Coocrete Hangermale, ~II a hole to the appropnate embedment depth, addng at least 1/4"
to the ~Nlng depth to preyeot the tip at the fastener
from nmlng Into the back at the anchor hole <iJmg
lnstallatkln.
Ill"
1/4
1-1/2
1-3/8
8116
39/64
3/8-16
1/2
1/2
2. Select the appropnate socket o1ver for the anchor
size end type to be Installed end mount Into chuck of
ristallatXlll lool. klsert the tm;iermate coupling Into
the socket d1ver, end Install perpendcular ID the base
mater1al surface. Drne the fa<ltener with a smooth
steady motkln until the o1ver end coupling Is seated
against the surface of the base materfal. ·
When lr6talilg Hangermate, eye prolectioo shoud be worn as a safety p.'8C8Ution.
3. Thread the appropnate diameter steel threaded
rod or threaded bolt Into the coupllng. Toe threaded
rod or bolt should fulty engage the thread length
of the coupling on a vertical mount fastener. The
threaded rod or threaded portion of the bolt can pass
through coupling of a side mount fastener.
For UL Md/or FM llstlngs for twigers S1eel Hir,germate shoukl be ristaled with a relalnlng nut for parts that are padQlged wllh a nut (see performance da1a and lslings as applk:able).
SUggested Id speed for S1eel Hlrlgemlate lnstallatl0ns Is 1200 to 1800 rJJll.
Steel Wood Concrete
Install with appropriate sized steel socket driver. Install with appropriate sized wood socket ~r. Install with appropriate sized concrete socket driver.
(side and variable mount direction versions not pictured) (side and var1able mount direction versions not pictured) t,,arlable mount direction version not pictured)
1-800-4DEWALt
Q
i;;
1
DEWALi
PERFORMANCE DATA
PERFORMANCE DATA
::__ .• _:_ far SINI -.._.. ... ... --.. .. .... .... ... ..... .... 1111111. 1111111. lmfll ...... --II. --.. .. ... ... .... 1111& .... 1111111.
IL~-Ftrlllll•Vwllcll
PFM2231000 1/4-201' #3 Vert 1/4' PFM2201200 (Silver) 0.060 0.210 ----
PFM2231100 1/H0x1'#3 Vert 318" PR.12201200 (SilYer) 0.060 0.210 4' 0.060' --
PFM223110N 1/4-20 X 1' #31nut Vert. 318' PR.12201200 (SilYer) 0.060 0.210 4' 0.125' 4" 0.105"
PFM2231150 1/4'-20 X 1-1/2' #5 Vert. 318" PFM2201200 (Silver) 0.125 0.500 4• 0.060' 4' 0.060'
PFM223115N 1/4-20 X 1-1/2' #5/nut Vert 318' PR.12201200 (Sliver) 0.125 0.500 4' 0.125" 4• 0.105'
PFM2231200 1/4-20 X 1-1/2' #3 Vert 318" PFM2201200 (Sliver) 0.060 0.210 4' 0.060" --
PFM223120N 1/4-20x 1-1/2" #3/nut Vert 318" PR.12201200 (SIIYer) 0.060 0.210 4• 0.060' --
PFM2231250 1/4-20 X 2" #3 Vert 318" PFM2201200 (Sllvel) 0.060 0.210 4" 0.125"
11_._ ..................
PFM2241100 1/4-20 X 1' #3 Side 318' PR.12201200 (Sliver) 0.060 0.210 ----
PFM224110N 1/4-20 X 1 • #31nul Side 318" PFM2201200 (Sliver) 0.060 0.210 4" 0.060' 4' 0.060"
PFM2241150 1/4-20 X 1-1/2" #3 Side 318" PFM2201200 (Silvel) 0.060 0.210 ----
PFM224115N 1/4-20 X 1-1/2" #3/nut Side 318" PR.12201200 (SIIYer) 0.060 0.210 4" 0.060' 4• 0.060'
PFM2241200 1/4-20 X 1-1/2" #5 Side 318" PFM2201200 (SilYer) 0.125 0.500 ----
PFM224120N 1/4-20 X 1-1/2' #5lnut Side 318' PR.12201200 (Sliver) 0.125 0.500 4• 0.060' 4• 0.060' . _. ........................ ". II I
PFM2281150 1/4-20 X 1" #3 VcV1able 318' PFM2201250 0.060 0.188 ----
PFM2281200 12-20x 1-314' #5 Variable 318" PFM2201250 0.125 0.500 ----
PFM2281250 1/4-14 X 1" #3 Variable 318' PFM2201250 0.060 0.188 ----• ................... C.-.. .... 1!11111
PFM2231500 1/4-14 X 7/8' #2 (3116' eyeleQ Variable -PFM2201350 0.060 0.105 ----
PR.12231550 1/4-14 X 2 #2 {3116' eyeleQ Variable -PFM2201350 0.060 0.105 ----
--far SINI -Ultlmala Load ----when lnstaled In SINI' ... ... ....... I ..... .... ---■] . I '-' 0 ..... 111 ... 141&171 1111.1• 11111.18 lllllt.117 1/41 .... 1111 ... ... ... ... ... ... ... ... . . .................
PFM2231000 1/4-201· #3 Vertical 1/4 785 1,140 1,740 2,375 2,820 --
PFM2231100 1/4-20 X 1' #3 Vertical 318 785 1,140 1,740 2,375 4,695 --
PFM223110N 1 /4-20 X 1' #3/nut Vertical 318 3,435 4,025 4,280 4,690 5,810 --
PFM2231 150 1/4 -20 X 1-1/2' #5 Vertical 318 ----3,675 5,205 5,205
PFM223115N 1/4-20 X 1-1/2' #5/nut Vertical 318 3,435 4,025 4,280 4,690 5,810 5,810 5,810
PFM2231200 1/4-20 X 1-1/2' #3 Vertical 318 785 1,140 1,740 2,375 4,695 --
PFM223120N 1/4-20 X 1-1/2' #3/nut Vertical 318 3,435 4,025 4,280 4,690 4,695 --
PFM2231250 1/4-20 X 2' #3 Vertical 318 785 1,140 1,740 2,375 4,695 --,., ...................
PFM2241100 1/4-20 X 1' #3 Side 318 1,740 1,945 2.420 2,570 2,810 --
PFM224110N 1/4·20 X 1' #31nul Side 318 2,755 2,810 2,570 2,810 2,810 --
PFM2241150 1/4-20 X 1-1/2" #3 Side 318 1,740 1,945 2,420 2,570 2,810 --
PFM224115N 1/4-20 X 1-1/2' #3/nut Side 318 2,755 2,810 2,570 2,810 2,810 --
PFM2241200 1/4-20 X 1-1/2' #5 Side 318 ----2,205 2,810 2,810
PFM224120N 1/4-20 X 1-1/2" #5/nut Side 318 2,755 2,810 2,570 2,810 2,810 2,810 2,810
N I ........................ 11•. I
PFM2281150 1/4-20 X 1' #3 Variable 3/8 635-Vert. 635-Vert. 1,130 -Vert. 1,130 -Vert. 1,640 -Vert. --(875@45°) (875@45°) (875@45°) (875@45°) (875@45°)
PFM2281200 12-20 X 1-3/4' #5 Variable 318 635 -Vert. 635 -Vert. 1,130 -Vert. 1,130-Vert. 1,640 -Vert. 1,640 -Vert. 1,640 -Vert.
(875@ 45°) (875@45°) (875@45°) (875@45°) (875@45°) (875@45°) (875@45°)
PFM2281250 1/4-14 X 1' #3 Variable 3/8 590 -Vert. 590-Vert. 970 -Vert. 970-Vert. 1,640 -Vert. --(875@45°) (875@45°) (875@45°) (875@45°) (875@45°)
II I ■-II Ftr 111111 • "-lall C.-.. IClw 1!,-111
PFM2231500 3116 X 2' #2 Variable -800 800 1,245 ----
PFM2231550 3116 X 3-1/4 #2 Variable -800 800 1,245 ----
1. Tre values listed above are ultlmate load capootles which should be reduced by a mlnlmi.rn safety factor of 3.0 or greater to determine lhe allowable IW!1<!ng load.
2. Tre strength of lhe lhreaded rod used with lhe Hangermate anchors must be considered wheo determining lhe controlling load capacity of the assembly.
www.DEWALT.com
PmFORMANCE DATA
-far Wood • Ulllnllle Load -wllen l111taled In Wood1.2
Cll.le. .... .... ... --...... ........ .. ..
I lfll ....... -__ .,.._ __ .,.. _ ....... ,. ..... .,...._
PFM2251000 1/4" X 2" Vert. 1/4" PFM2201150 (Red) 1,510 . .
PFM2251050 1/4" X 1" Vert. 318" PFM2201150 (Red) 650 . .
PFM2251100 1/4" X 2" Vert. 3/8' PFM2201150 (Red) 1,510 3" .
PFM2251150 5116" X 2-1/2" Vert. 318" PFM2201150 (Red) 2,670 4• 4•
PFM2251200 1/4" X 3" Vert. 3/8" PFM2201150 (Red) 2,075 3• .
PFM2251250 1/4" X 4" Vert. 3/8" PFM2201150 (Red) 2,075 3• .
PFM2251~ 5116" x2-1/2" Vert. 1/2" PFM2201150 (Red) 2,670 . .
• ..... ,. .............
PFM2261000 1/4" X 1" Side 1/4" PFM2201150 (Red) 650 . .
PFM2261050 1/4" X 1" Side 3/8" PFM2201150 (Red) 650 . .
PFM2261100 1/4" X 2" Side 318" PFM2201150 (Red) 1,800 3• .
PFM2261150 5116" X 2-1/2" Side 318" PFM2201150 (Red) 1,450 3• . . . ........ ,. ............... • 1,470 (Vert.) . . PFM2281100 1/4" X 2" ~ 3/8" PFM2201250 1,155 (45°) . .
• I .... ,. ............ C--. .... ltllll
PFM2251500 3/16" X 3-1/4" Varialle . PFM2201350 880 . .
Ulmate Llals In Douglas Ar, Pile Md Spruce
1. T~ rnarua::llnrs ITl8'f recµre pre-drlled holes wtlh Y«IOO depencilg oo the locatioo of the ardu' ilslalalkn. Const.« wl1h the trussl]oist lllellufacturer for detils.
2. The Yalues lisllld aboYe n Ll'limlle load capadties 1hal must be nw:ed by a minlm11TI safely fa:u of 3.0 or grealllf lo determine the allowable v.ooq load.
Cena• .. -Ulllllllle Load -wllen lnstaled In Normal-Weight Cencle191.2"
............ c , ..... .._,.., ........ .... .... ...... ...... a.-11111 ...... .... ... Cllle. -...... ~ 1111. II F\lt ....... 1111. T■-IN -T■-IN .... T■-IN .... ------PFM2217171 1/4 1/4" X 1-1/4" Vertical 1/4 1-1/4 1,390 1,810 1,950 2,440 2,070 2,570
PFM2217173 3/8 1/4" X 1-1/2" Vertical 1/4 1-1/2 1,760 2,580 2,595 2,640 2,no 2,700
1. The Yalues llsled aboYe n ullinale load capadties for n:hors lnslalled In uncracked rmnaJ weig1I an:sete.
2. The values llsl8d aboYe n lAtinate load capadties ~ roost be nw:ed by a millmum safely lador of 4.0 or greater to determine the ~ v.ooq load.
3. Li1ea.' ntsrpolalk,n ITl8'f be used to detemn load capadties for imnediale eooliresst,,, streoglhs.
Concnte .. -Ulllmlt8 Load ca wllenlnstaled-. Metal Deck Into I . . -. Concnte1,2,3,4
11111 .................... ,,:t,... ... ....... _ .... ht C I .... .... ... 1/P ..... Cllle. -In fll ....... ..... ■-1111. 1111. 1111. T■-IN ........ -...
PFM2217171 1/4 1/4" X 1-1/4" Vertical 1/4 1-1/4 800 1,140
PFM2217173 3/8 1/4" X 1-1/2" Vertical 1/4 1-1/2 1,780 1,500
1. The values HsteC1 alxll'e are uttmate load capacHl8s for anchors lns1alled In uncracked Slrld-llltltwelght concrete.
2. The metal deck shall rd eJal8d 18 gauge (0.048-n;ti base metal llickness} Md conform lo ASTM A 653.
3. The vak.oes llsled above n lAtimate load ~ies ~ roost be ll!duclKI by a millmum safely lador of 4.0 or greater to detarmlne the alowable v.u1dng load.
4. The 11Kuated load values are for anchors Installed with a miroom kJwer nute edge dlstMce ol 1-1/8-lnch; or In the upper f\Jte wl1h coostoerallon for Integral washer dearaoo!.
Concnte . -Ullllllate Load ca when lataled In Hollow Con Concn18 Plank1.2 ... _.._ ...... I 1 I 2 lllplll c~ c~ Cllle. .... ,mr,• .......... ...... 1111. 1111. 1111. ... -PFM2217171 1/4 1/4" X 1-1/4' Vertical 1/4 1-1/4 2,775 1,920
PFM2217173 3/8 1/4" X 1-1/2" Vertlcal 1/4 1-1/2 3,700 2,570
1. TabtAated load values are for an:hors Installed In 8-n;h-1hick uncrack8d holkJw core an:sete with mlninum compressive strength of 5,000 psi at the time of Installation. The normal-weight
coocrete must have 1-112· [XJ(I')( above Md below cores and a mlnilnllTI web 1hickness of 1-112·.
2. The values listed above are ultimate lood capadties which must be reduced by a minimum safety lador of 4.0 or greater to determine the alklwable W0001Q load .
ell.le.
PFM2217173
1-800-4D1\VALI
... _.._
ILL
3/8
... t.lllOllpl L
1/4" X 1-1/2"
..........
Vertical
...... .....
1111.
1/4
CIC Slllplll
ILL
1-1/2 4"
DEWALi
ORDERING INFORMATION -·-
ORDERING INFORMATION
'-StNl·Vertlcal
CII. ... . ...... ...-,ca-, .... ... -.. ., . Clrlllll.,,
PFM2231000 1/4-20 X 1" #3 PFM2201200 Vertk:al 1/4" 25 125
PFM2231100 1/4-20 X 1" #3 PFM2201200 Vertk:al 318" 25 125
PFM22311 <J,l 1/4-20 X 1 • #3/nut PFM2201200 Vertk:al 318" 25 125
PFM2231150 1/4"-20 X 1-1/2" #5 PFM2201200 Vertk:al 318' 25 125
PFM2231 15N 1/4-20 X 1-112' #5/nut PFM2201200 Vertk:al 318" 25 125
PFM2231200 1/4-20x1-1/2"#3 PFM2201200 Vertk:al 318' 25 125
PFM22312(J,l 1/4-20X1 -112• #3/nut PFM2201200 Vertk:al 318" 25 125
PFM2231250 1/4-20 X 2' #3 PFM2201200 Vertk:al 318" 25 125
==----=-.. Steel -Hortmltal
CII. ... I . I II .... ,(allt .... ... _ .. .,. Clrlllll.,,
PFM2241 100 1/4-20 X 1' #3 PFM2201200 Side 318' 25 125
PFM22411 <J,l 1/4-20 X 1" #3lnut PFM2201200 Side 318' 25 125
PFM2241150 1/4-20 X 1-1/'2" #3 PFM2201200 Side 318' 25 125
PFM224115N 1/4-20 X 1-1/2' #3lnut PFM2201200 Side 318" 25 125
PFM2241200 1/4-20 X 1-112" #5 PFM2201200 Side 318" 25 125
PFM22412(J,l 1/4-20 X 1-1/2' #5/nut PFM2201200 Side 318" 25 125
::_ ___ :.. PINI'-51111 -la .._. ----
CII. ... I . I II ......... , .... ... -.. .,. Clrlllll.,,
PFM2281150 1/4-20 X 1' #3 PFM2201250 Vlliable 318" 25 125
PFM2281200 12-20 X 1 -3/4" #5 PFM2201250 VMable 318' 25 125
PFM2281250 1/4-14 X 1' #3 PFM2201250 Vlliable 318" 25 125
--Acoultlcal Cellna EYllet for StNI
CII. ... lmflill lfllllllllllll'I .... ,:: ..... Clrlllll ...
PFM2231500 ~6·x2· PFM2201350 Virilmle 3/16' 25 125 1/4-14 X 7/8" #2 screw
PFM2231550 3/16' X 3-1/4' PFM2201350 Vlliable 3/16" 25 125 1/4-14 X 2' #2 screw
.. '-Wood -Vatlcal
CII. ... Ill Ill .... ,~ .... ... _ .. ., . Clrlllll.,,
PFM2251000 1/4' X 2" PFM2201150 Vertical 1/4" 25 125
PFM2251050 1/4' X 1" PFM2201150 Vertical 318' 25 125
PFM2251100 1/4' X 2" PFM2201150 Vertical 318" 25 125
PFM2251150 5116' X 2-1/2" PFM2201150 Vertical 318" 25 125
PFM2251200 1/4" X 3" PFM2201150 Vertical 318' 25 125
PFM2251250 1/4' X 4' PFM2201150 Vertical 318' 25 125
PFM2251300 5116'x 2-1/2' PFM2201150 Vertical 1/2" 25 125
--'-Wood • Hortzontal
CII. ... I 7 I ' 11111111'1(1111 .... ... -.. .,. Clrlllll.,,
PFM2261000 1/4" X 1" PFM2201150 Side 1/4" 25 125
PFM2261050 1/4" X 1" PFM2201150 Side 318" 25 125
PFM2261100 1/4" X 2" PFM2201150 Side 318" 25 125
PFM2261150 5116" X 2-1/2" PFM2201150 Side 318" 25 125
PIiot for Woad -llcatlonl
CII. ... l1111flil1 .... ... -..... Clrlllll ...
PFM2281100 1/4" X 2" Variable 318" 25 125
Acoultlcal Celll for Woad
I ........ .... E,111111111 ...,. Clrlllll ...
i!l 3/16" X 3-1/4" Var1able 3/16" 25 125
0
www.DEWALT.com
DEWALi
: ____ :_ tor Conclete -Vert1ca11
CILIL ....... .... ....., .... ---..... Clrllll-
PFM2217171 1/4' X 1-1/4' PfM1491050 Vertical 1/4' 100 600
PFM2217173 1/4" X 1-1/2' PFM1491100 Vertical 3/8' 100 600
1. Caicrele Hangennate reqlke a pre-aled hole using a 1/4' ANSI caiWe <ti bit (e.g. OW5517).
1,2
CILIL
PFM2281300 .... ---■--Clrllll ... Vnble 3/8' 25 125
1. The l&lgermate Pt.d for cax:rete requie a pre-ctlled hole using a 3116" ANSI cartlide ail bit je.g. DW5402).
2. U1inale loed capacity for the tmgennate PiYot for coocrete Is 875 b . The ij1jmale loed C8j8:ities must be reduced by a ml'limllll
safety fact()' of 4.0 or greater to deternine Ille allowlEle wooing load.
Conclele lnltallatlon AcceslOl'lel • Tool Gulde
CIL ■-.
PFM2217171
PFM2217173
Stllel and Wood
CILIL
PFM2201100
.....
II . I " ....,._.
..::3, .. ··-----_., --
1 /4' Vertical Hanger
1/4' X 1-1/4" DCH273P2DH
3/8" Vertical Hanger
1/4' X 1-1/2' DCH273P20H
PoleTool
l■r \I
Hangermate Pole Tool (Kil)
... -T..-...,
! ....
DW5416
DW5517 150
(1/4j
DW5416
DW5517 150
(1/4j
1117. 1'111111 ... Clrllll-
5
The Hangermate pc-, tooi kit ls desl!Jled for LB8 with striderd 1/2" steel conduit tliling (coocUt not lnctuded) and ar1 be custon'ized kl
Wl1rus lengths and C8illJ heights. ~!Ible with sllmlr'd steel and wood ltwlgermale.
Steel and Wood ::__ .. _::_ Pole Tool
CIIL■-. Ill \I ... ,.. ... Clrllll-.
PFM2201200 1/4' & 3/8" Steel Hangermate Driver -
Vertical Md Hor1zonlal Mounts (Sllwr) 5 25
PFM2201150 1/4" & 3/8" Wood Hangermate Driver -
Vertk:al and Hor1zonlal Mo..rlts (Red) 5 25
PFM1491050 1 /4" Concrete Hangennate Driver -Vertical Mount (Black) 5 25
PFM1491100 3/8" Concrete Hangermate Driver -Vertical Mount (Black) 5 25
PFM2201250 Hangermate Pivot Driver -Angled Mounts 5 25
PFM2201350 Hangermate Eyelet Driver -Angled Mounts 5 25
All Hangetmate drMllS have a 1 /4-lnch hex for connection to tools.
nslal latlon Accesso."1es Unlnnal I
CIL ■-. D■ll\111 1117.l'IIIIIQlr. ClrllllQlr.
PFM2201050 3/8" to 1/2" Adapter 25 125
The 3/8" to 1/2' adaptor has a 3/8-16 external thread and a 1/2-13 lntemal thread.
1-BOCMDIWALT
ORDBllNG INFORMATION
I 111 ............ ..... 1,111: ..... , ....
J --DCF887 PFM1491050 or
(1/4' Impact Or1Yel) DWMT17311
DCF890 DW2284 (3/Bj (3/8" Impact Wrendl)
DCF887 PFM1491100 or
(1/4' Impact Or1Yel) DWMT17311
DCF890 DW2286 (1/2j (3/8" Impact Wrendl)
I
i
i
RING HANGERS ~ANVIL:
~I NT ... N-.TIO NAI..
Fig. 69 (Formerly Afcon Fig. 300) Adjustable Swivel Ring, Tapped Per NFPA Standards
Size Range: 1/i" through 8"
Material: Carbon steel
Finish: Strap is Pre-Galvanized Zinc Material. Nut is Zinc Plated.
Service: Recommended for suspension of non-insulated stationary pipe line.
Maximum Temperature: 450° F
Approvals: Complies with Federal Specification A-A-1192A (Type 10), WW-H-171-E {Type 10),
and ANSI/MSS SP-58 (Type 10). UL Listed and FM Approved (Sizes 3//-8").
Features:
• 1/i" -2" sizes designed for use with steel and CPVC piping and manufactured with
FBC System Compatible oil.
• Threads are countersunk so that they cannot become burred or damaged.
• Knurled swivel nut provides vertical adjustment after piping is in place.
• Captured swivel nut in the 1/i" through 6" sizes. The capture is permanent in the bottom
portion of the band, allowing the hanger to be opened during installation if desired, but
not allowing the nut to fall completely out.
Ordering: Specify size, figure number and name.
Non-captured nut also available upon request.
1 Ai
1/i" through l" pipe l ¼" through 2" pipe
G
i1/i" through 8" pipe
FIG. 69: DIMENSIONS (IN) • LOADS (LBS) • WEIGHT (LBS)
Pipe Size Max Load Weight Rod Size B C F G
A Width
½ 0.10 2¼ 2 1%
¾ 0.10 2¾ Fis 1%
1 300 0.10 29/16 111/ie 1 5/a 1¼ 0.10 2% 1¾
1½ 0.10 ¾ 2¾ 111a 1fa
2 0.11 3¼ 2¾ 1¼
2½ 525 0.20 4 2¾ 1%
3 0.20 31% 213/ts 1%
4 650 0.30 411/ie 313/ie 1% ¾ 5 0.54 53/ts 4¾
6 1,000 0.65 ½ 611/is 5o/1s 2¼
8 1.00 89As 7% 3¼
PROJECT INFORMATION
Project: □Approved
½" through 2" Size
Rounded Edge Design
c@us <S> USTED APPROVED
21/i" through 8" Size
APPROVAL STAMP
Address: □Approved as noted
Contractor: D Not approved
Engineer: Remarks:
Submittal Date:
Notes 1:
Notes 2:
PH-1.18
' .
A Fcon., SEISMIC RESTRAINTS
Fig. AF310 (Formerly Afcon Fig. 310) Surge Restrainer
Size Range: 1" thru 2" Figure 69, Swivel Ring Hanger
Material: Carbon steel
Finish: Pre-Galvanized per ASTM A653
Restrainer Service: Prevents vertical movement of ho rizontal sprinkler piping from thrust loads due to
sprinkler activation. The surge restrainer is intended to be installed with Anvil's Figure 69 Swivel Ring Hanger.
Restraint Service: May be installed as part of a branch line seismic restraint assembly per the requirements
of NFPA 13. The surge restrainer is intended to be installed wit h Anvil's Figure 69 Swivel Ring Hanger.
Approvals: cULus Listed (UL 203 and UL 203a). Complies w ith the hanging and restraint requirements
listed in NFPA 13.
Features:
• One universal size accommodates Fig. 69 sizes 1" through 2''.
• Simple design allows for quick installation on existing sprinkler systems.
Installation Instructions:
• Snap surge restrainer onto the Fig. 69 knurl nut.
• The gap between the surge restrainer and service pipe shall not exceed 1/a''.
• Fire Protection applications shall also be installed per the requirements of NFPA 13.
Ordering: Specify figure number and description.
3/a'' Rod
Fig. AF310
Fig. 69
FIG. AF310:
Fig. 69 Knurl Nut
Branch Pipe
LOADS (LBS) • DIMENSIONS (IN) • WEIGHT (LBS)
Service Rod UL Max Seismic Restraint Load Approx.
Pipe Size Size (UL 203a) Weight/100
1 thru 2 31a 300 4
PROJECT INFORMATION
Project:
Address:
Contractor:
Engineer:
Submittal Date:
Notes 1:
Notes 2:
PH-1.18
Surge Restraint
Assembly
Seismic Restraint
Assembly
Notes: Anvil International• brand bracing components are designed to be
compatible ONLY with other Anvil lnternational•brand bracing components,
resulting in a Listed seismic bracing assembly. Updated UL listing information
may be viewed at www.ul.com
Disclaimer. Anvil International ("Anvil") does not provide any warranties and
specifically disclaims any liability whatsoever with respect to Anvil bracing
products and components that are used in combination with products, parts
or systems not manufactured or sold by Anvil. In no event shall Anvil be liable
for any incidental, direct, consequential, special or indirect damages or lost
profits where non-An vi I bracing components have been, or are used.
APPROVAL STAMP
□Approved
D Approved as noted
D Not approved
Remarks: