HomeMy WebLinkAbout1630 FARADAY AVE; ; FPC2021-0102; PermitPERMIT REPORT
Fire Permit
Print Date: 01/12/2022
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
1630 FARADAY AVE, CARLSBAD, CA 92008-7313
FIRE-Construction Commercial Work Class:
2121302200 Track#:
$1,224,143.20 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Description: ELAGO -SPRINKLER Tl (86 HEADS)
FEE
FIRE NFPA 13 or 13R System 7 -100 heads
Fire Sprinklers
Total Fees: $553.00 Total Payments To Date: $553.00
Fire Department
C cityof
Carlsbad
Permit No: FPC2021-0102
Status: Closed -Finaled
Applied: 06/09/2021
Issued: 07/08/2021
Finaled Close Out: 01/12/2022
Inspector:
Final Inspection:
Balance Due:
AMOUNT
$553.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
tqca. Worldwide I Contacts www.tyco-fire.com
Series TY-B, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
General
Description
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers described in this data sheet
are standard response, standard cov-
erage, decorative 5 mm glass bulb
type spray sprinklers designed for use
in light, ordinary, or extra hazard, com-
mercial occupancies such as banks,
hotels, shopping malls, factories, refin-
eries, and chemical plants.
The recessed version of the Series
TY-B Pendent Sprinkler, where applica-
ble, is intended for use in areas with a
finished ceiling. This recessed pendent
sprinkler uses one of the following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from the
flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from the
flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-B Sprinklers are described in Tech-
nical Data Sheet TFP352. Sprinkler
guards and shields are described in
Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
IIJ-iAA◄ The Series TY-B Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the stan-
dards of any other authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Numbers (SINsJ
TY315 .... Upright 5.6K, 1/2 in. NPT
.... Pendent 5.6K, 1/2 in. NPT
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
• The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato•
ries, Inc. (UL).
Discharge Coefficient
K = 5.6 GPM/psi¼ (80,6 LPM/bar¼)
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................ Bronze
Button ...................... Brass/Copper
Sealing Assembly ... Stainless Steel w/TEFLON
Bulb ............................... Glass
Compression Screw ................. Bronze
Deflector .................•........ Bronze
AUGUST 2018
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing
or Approval agency (e.g., UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of the FM Loss Preven-
tion Data Sheets). Only the Style 15
or Style 20 Recessed Escutcheon, as
applicable, is to be used for recessed
pendent installations.
TFP152
TFP152
Page 2 of4
Components:
1 -Frame
2 -Button
4 -Bulb
5 -Compression
Screw
* Temperature rating is
indicated on Deflector.
** Pipe thread connections per ISO 7-1
can be provided on special request.
3 -Sealing
Assembly 6 -Deflector* DEFLECTOR*
ESCUTCHEON PLATE
SEATING SURFACE
1/2' 7/16" (11,1 mm)
NPT** NOMINAL MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
7/16'
(11,1 mm)
NOMINAL
MAKE-IN
2"
(50,8mm)
j
CROSS SECTION
1/2' NPT**
UPRIGHT
I
2·
(50,8 mm)
I f
1-3/8" I J (34,9mm)
WRENCH
FLATS
DEFLECTOR* I-2-7/8' (73,0 mm) DIA.
PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-B UPRIGHT {TY315) AND PENDENT (TY325) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, STANDARD RESPONSE
WRENCH RECESS
(USE ONLY
END 'A')
FIGURE2
W-TYPE6
SPRINKLER WRENCH
WRENCH
RECESS
t
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-B, 5.6 K-factor,
Upright (TY315) and Pendent (TY325)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 in.
(1,6 mm) for the 135°F (57°C) to 3/32 in.
(2,4 mm) for the 360°F (182°G) tempera-
ture ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a min-
imum-to-maximum torque of 7 to 14
lb-ft (9,5 to 19,0 N•m). Higher levels of
torque may distort the sprinkler inlet
and cause leakage or impairment of
the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the escutch-
eon plate by under-or over-tightening
the sprinkler. Readjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-B Upright and Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in the
pendent position; install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 N•m).
Recessed Pendent Sprinklers
The Series TY-B Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15 or
Style 20 Mounting Plate, as applica-
ble, over the sprinkler threads and with
pipe-thread sealant applied to the pipe
threads, hand-tighten the sprinkler into
the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 N•m).
Step C. After the ceiling is installed or
the finish coat is applied, slide on the
Style 15 or Style 20 Closure over the
Series TY-8 Sprinkler and push the
Closure over the Mounting Plate until
its flange contacts the ceiling.
Care and
Maintenance
The TYCO Series TY-8, 5.6 K-factor,
Upright (fY315) and Pendent (fY325)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
system from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
Thereafter, annual inspections per
NFPA 25 are required; however, instead
of inspecting from the floor level, a
random sampling of close-up visual
inspections should be made.
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
TFP152
Page 3 of4
2-7/8' DIA.
(73,0 mm)
FACE OF
SPRINKLER
FITTING
2-1/4' DIA.
(57,2 mm)
3/8±5/16' ,?I~
I I
MOUNTING
5/8" (15,9 mm)
FLUSH
{9,5±7,9mm) v~
SURFACE c:r;=!:z::i;:~
CLOSURE SERIES
TY-8
MOUNTING
PLATE
1-3/8" (34,9 mm)
3/4" (19,1 mm)
FIGURE4
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
WITH TWO-PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8' DIA.
(73,0 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA
(57,2 mm)
5/16±1/4'
(7,9±6,4 mm) 1/2" (12,7 mm)
FLUSH
I /~~&JI:::;:;;;;;;;~
MOUNTING
SURFACE
=l_J
1/8"
(3,2mm)
-+--------+
CLOSURE SERIES MOUNTING 1-3/8' (34,9 mm)
7/8" (22,2 mm) TY-8 PLATE
FIGURES
SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY (TY325)
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
Automatic sprinklers are recommended
to be inspected, tested, and maintained
by a qualified Inspection Service in
accordance with local requirements
and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-8 Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=S.6, Standard Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table B)
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify•) finish, PIN (specify•)
Specify: Style 20 Recessed Escutch-
eon with (specify•) finish, P/N (specify•)
• Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
TFP152
Page4 of 4
BULB SPRINKLER RNISH !71
K SPRINKLER TEMPERATURE LIQUID
I I POLYESTER0 TYPE RATING COLOR NATURAL CHROME
BRASS PLATED
135°F (57°C) Orange
UPRIGHT 1 ss°F (68°C) Red (TY315)
and 175°F (79°C) Yellow
PENDENT 200°F (93°C) Green 1, 2, 3, 4, 5, 6,
(TY325) 2a6°F (141 ·q 5.6 Figure 1 Blue
1/2 in. 360°F (182°C) Mauve
NPT 13s•F (S7°C) Orange
RECESSED 1ss°F (6a0c) Red
PENDENT 175°F (79°C) Yellow
1, 2, 3, 4,
(TY325)*
Figures 4 and 5 200°F (93°C) Green
2a6°F (141°C) Blue 1, 2
Notea:
1, Ust&d by Underwriters Laboratories, Inc. (UL}
2. Listed by Underwriters Laborato,lo,;, Inc. fo, use In Canada (C-UL)
3. Approved by FIIA Global (FI\A Approvals)
4. Approved by the Loss Prevention Certification Soard (LPC8 Rel, No. 007k/03)
5. VdS Approved (For details contact Johnson Controls, Ensch&de, Netherlands, Tel. 31-53-428-4444 / Fax 31-53-428-3377)
6. Approved by the Loss Prevention Certlficallon Board (LPCB Ref. No. 094a/05)
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, tho sprinklers are UL and C-UL Listed as CorToalon-Ro,;lstant Sprinklers.
• Installed with Style 15 (1/2 In. NPT) 5/8 In. Total Adjustment Recessed Escutcheon, as applicable
•• Frame and deflector only
N/A -Not AppPcablo
TABLE A
SERIES TY-B UPRIGHT AND PENDENT SPRINKLERS
LABORATORY LISTINGS AND APPROVALS
P/N* 77 -XXX -X -XXX
I I
SIN SPRINKLER
FINISH
570 5.6K UPRIGHT (1/2 in. NPn TY315 1 NATURAL BRASS
571 5.6K PENDENT (1/2 in. NPn TY325 3 PURE WHITE (RAL9010) ..
POLYESTER
4 SIGNAL WHITE (RAL9003)
POLYESTER
5 JET BLACK (RAL9005)
POLYSTER
9 CHROME PLATED
' Use suffix "I" for ISO 7·1 connection; for example, 77-570-4-175-1
0 Eastern Hemisphere sales onty
••• OPEN indicates aprinkler assembly without Glass Bulb, Button. and Sealing Assembly
TABLES
SERIES TY-8 UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway, lanadale, PA 19448 I Telephone +1-215-382-0700
MA..TIONAi. ~ PfW1T!CTION ASSOCIATtON ~d NFPA ■,• ,.i•.ct tt■d.-natk• of NMtoml '""• Ptot<Ktkin AaAoc.l■tkin, f'lllOtr,ll••• .. .t:ter.db~O,OUPont
135
155
175
200
286
360
000
TEMPERATURE
RATINGS
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
2a6°F (141°C)
360°F (182"C)
OPEN ...
Johnson ~Jg,
Controls