HomeMy WebLinkAbout6005 HIDDEN VALLEY RD; 200; FPC2021-0151; PermitPERMIT REPORT
Fire Permit
Print Date: 10/13/2021
Job Address: 6005 HIDDEN VALLEY RD, # 200, CARLSBAD, CA 92011-4225
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #:
Valuation:
Occupancy Group:
#of Dwelling Units:
2120406600 Track#:
$288,362.00 Lot#:
Project#:
Plan#:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check#:
Plan Check#:
Project Title:
Description: PARTNERS ADMIN -SPRINKLER Tl (29 HEADS)
Applicant:
TOTAL FIRE PROTECTION INC
JOHN CAPUTO
1611A S MELROSE DR
VISTA, CA 92081-5407
(760) 525-4329
FEE
FIRE NFPA 13 or 13R System 7-100 heads
Total Fees: $553.00
Fire Department
Total Payments To Date: $553.00
{city of
Carlsbad
Permit No: FPC2021-0151
Status: Closed -Finaled
Applied: 08/12/2021
Issued: 09/21/2021
Finaled Close Out: 10/13/2021
Inspector:
Final Inspection:
FPContractor:
TOTAL FIRE PROTECTION INC
1611 S MELROSE PL, # 244
VISTA, CA 92081-5471
(760) 525-4329
Balance Due:
AMOUNT
$553.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
· Bulletin 014 Rev. L
Reliabld Model F1 FR Series
Quick Response
Standard Spray
Model F1 FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model F1 FR56 Recessed Sprinkler Types
Standard Pendent/F1/F2/FP
Horizontal Sidewall
Model F1 FR56 Concealed Sprinkler Types
Standard Pendent
Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler
Types
Standard Upright
Standard Pendent
Model F1 FR42, F1 FRXLH & F1 FR28 Recessed
Sprinkler Types
Standard Pendent
Model F1 FR56LL & F1 FR42LL Low Lead Sprinkler
Types*
Standard Pendent
Less than 0.25% Lead Content
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada (cULus).
2. Factory Mutual Approvals (FM)
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverhutung GmbH
5. *NSF Certified to NSF/ANSi Standard 61 Annex G
6. EC Certificate: 0786-CPD-40239 (RA 1414 }, 0786-
CPD-40251 (RA 1425), 0786-CPD-40252 (RA 1475)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1 FRXLH & F1 FR28 Series Sprinklers are quick response
sprinklers which combine the durability of a standard sprin-
kler with the attractive low profile of a decorative sprinkler.
The Models F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1 FRXLH & F1 FR28 Series Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers.
This quick response enables the Model F1 FR56, F1 FR56LL,
Upright Pendent
Vertical Sidewall Horizontal Sidewall
y
~
• f ..
Conventional
Recessed
Pendentif 1/F2
'---------' :{;.~i~:._ ·. :., ~ .. ~. ·:.> J ;':
Recessed Concealed .___R_ec_e_ss_e_d _ _,
Horizontal Sidewall Pendent PendentifP
XLH Upright XLH Pendent
F1FR42, F1FR42LL, F1FRXLH &
F1 FR28 Series sprinklers to apply wa-
ter to a fire much faster than standard
sprinklers of the same temperature rat-
ing.
The glass bulb consists of an accu-
XLH Recessed
Pendent F 1 /F2
.__ ____ ___,
rately controlled amount of special fluid XLH Recessed
hermetically sealed inside a precisely Pendent FP
manufactured glass capsule. This glass bulb is specially
constructed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford , New York 10523
co C
i. ::,
0 .J.
~
:0 (D :<
r
Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-
sponse sprinklers should not be intermixed.
*Pin tie
(XLH Onry)
Deflector
Washer
Frame
014FG06A
Load Screw
Bulb
Cup
Model F1 FR42, F1 FRXLH Upright
Technical data:
Thread Max. Min. Temperature
Models Discharge Coefficient Response Working Working Finish Size Pressure Pressure Rating
F1FR56 K 5.6 **F1 FR56LL<1>
F1FR42 Quick 1/2" NPT See See
**F1 FR42LL<1> K 4.2 Response (R1/2) 175 PSI 7 PSI "Temperature "Finish Table"
F1FRXLH Ratings" Table.
F1FR28 K 2.8
c,1 Low Lead Sprinklers available only with Temperature Rating 200°F/93°C
Material Data:
Frame Deflector Load Screw *Pintle Cup Washer Bulb
DZR Brass CDA Alloy 260, CDA Alloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360
QM Brass CDA Alloy 220 or or or coated with PTFE Adhesive Glass
**Low Lead Brass or CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape CDA Alloy510
2.
Model F1 FR56, Upright, Pendent & Conventional Sprinklers
Model F1 FR42, F1 FRXLH & F1 FR28 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal Thread Nominal K Factor Sprinkler Approval
Orifice Size us Metric Height Organization
Sprinkler Identification Number
(SIN)
Upright Pendent
Standard-Upright (SSU) and Pendent Deflectors Marked to Indicate Position
1/2" (15mm) P) 1/2" NPT (R1/2) 5.6 80 2.25" (57mm) 1, 2, 3, 4, 6
7/16" (10mm) 1 /2" NPT (R 1 /2) 4.2 60 2.25" (57mm) 1
3/8" (10mm) 1/2" NPT (R1/2) 2.8 40 2.25" (57mm) 1
Conventlonal-lnstall In Upright or Pendent Position
15mm<1) 1/2" NPT (R1/2) 5.6 80
11> cULus listed corrosion resistant (Polyester coated) sprinkler.
<2> Polyester coated FM approved sprinkler.
57mm
<3> Polyester coated LPCB & VdS approved sprinkler RA 1425, RA 1414 & RA 1475.
1•> Electroless Nickel PTFE (Teflon_.)* Plated -cULus listed Corrosion Resistant
Upright Pendent
Model F1 FR56LL & F1 FR42LL Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal Thread Nominal K Factor Sprlnkler
Orifice Size us Metric Height
3,4, 6
Approval
Organization
Standard-Pendent Deflectors Marked to Indicate Position
1/2" (15mm) 11> 1/2" NPT (R1/2) 5,6 80 2.25" (57mm) 1, 5
7/16" (11mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) 1, 5
<1> cULus listed corrosion resistant (Polyester coated) sprinkler.
*DuPont Registered Trademark
3.
RA 1425PX2X3X4) RA 1414PX2X3X4)
RA1423PX4) RA 141 31•>
RA 1421(1X4) RA1411I•>
RA1475<3>
Conventional
Sprinkler Identification Number
(SIN)
Pendent
RA1415
RA1410
Model F1 FR56, F1 FR42, F1 FRXLH & F1 FR28 Quick Response Recessed Pendent Sprinkler<1>
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor Sprinkler Sprinkler Identification Number
Orifice Size us Metric Height (SIN)
1/2" (15mm) 1/2" NPT(R½) 5.6 80 2.25" (57mm) RA1414
7/16" (10mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) RA141 3
3/8" (10mm) 1/2" NPT (R1/2) 2.8 40 2.25" (57mm) RA 141 1
11> Refer to escutcheon data table for approvals & dimensions
Model F1 FR56LL & F1 FR42LL Quick Response Recessed Pendent Sprinkler<1>
Installation Wrench: Model GFR2 Sprinkler Wrench
Installation Data:
Nominal Thread K Factor
Orifice Size us Metric
1/2" (15mm) 1/2" NPT(R½) 5.6 80
7/16" (10mm) 1 /2" NPT (R 1 /2) 4.2 60
11> Refer to escutcheon data table for approvals & dimensions
ModelF1FR56,F1FR56LL,F1FR42, F1FR42LL, F1FRXLH&
F1FR28 F1 or F2
Sprinkler
Height
2.25" (57mm)
2.25" (57mm)
Sprlnkler Identification Number
(SIN)
RA1415
RA1410
t • X , /2• REIJUClR
rACE or FrrTWG 7D TN:£ or CDUNQ OIMDISION
AT -R£tfS$ -t-t/2T»mm] AT lilNIUfl RfC£SS • t f15.4mm}
T ...:,ss -1/t1T,.,"'""'1 AT JIINMM llfttSS' • f 115..f.mni}
J t/4"'(¥,t. [U,,-,J
ModelF1FR56,F1FR56LL,F1FR42,F1FR42LL,F1FRXLH&
F1FR28 FP
Model F1 FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
Installation Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Nominal K Factor Sprinkler Approval Sprinkler
Thread Size Identification
Orifice us Metric Height Organizations Numbers (SIN)
½" (15mm) ½" NPT (R1/2l 5.6 80 2.25" (57mm) 1, 2, 3 RA 1485l2X3>
15mm ½" NPT (R1/2) 5.6 80 2.25" /57mml 3(1)
l1> LPC Approval is for pendent position only.
l2> cULus Listed corrosion resistant (Polyester coated) sprinkler.
<3> Electroless Nickel PTFE (Teflon~)* Plated -cULus listed Corrosion Resistant
Vertical Sidewall
*DuPont Registered Trademark 4.
Sprinkler Type
Uoriaht
Pendent
Deflector to Celling Distance
{Min. -Max.)
4" 1102mm) -12" (305mm)
4" /102mm)-12" (305mm)
Model F1 FR56 Quick Response Horizontal Sidewall Sprinkler
Deflector: HSW
Installation Wrench: Model D Sprinkler Wrench
Installation Data: Horizontal Si dewall
Nominal K Factor
Nominal Orifice Thread Size
Sprinkler
Height
Approval Organizations
and Type of Approval
us Metric Light Hazard Ordinary
Hazard
½" (15mm) ½" NPT (R1/2) 5.6 80
P> cULus Listed corrosion resistant (Polyester coated) sprinkler.
<2> Polyester coated FM approved sprinkler.
2.63" (67mm)
(3> Electroless Nickel PTFE (Teflon•)* Plated -cULus listed Corrosion Resistant
1, 2 1
Sprinkler
Identification
Numbers (SIN)
RA 1435(1X2~3J
~-----------------------------,
Horizontal Sidewall
FACE OF FlmNG
TO FACE OF Cf /LING 0I/JfNSION
Ft ESCUTCHEON
AT /JAXI/JU/J RECESS • I 125.4mm]
AT /JINI/JU/J RECESS • J/B19.5mm}
f2 [SCUTCHEON
AT /JAXI/JU/J RECESS • J/41l9mm}
AT /JINI/JU/J RECESS • J/819,Smm}
2 I/•" HOLE DIA.
{57.2mm]
TURN COLI.AR UNnL
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
WWW7/21 @ fl £SCtJTCHEON
AT /JAXI/JU/J RECESS • I-J/B1J4.9mm]
AT /JINI/JU/J RECESS • 2-1/I6"{52.•mm]
f2 ESCUTCHEON
AT WJ<//JUIJ RECESS • 1-5/81• I.Jmm]
AT /JINI/JU/J RECESS • 2-l/l6"{52.4mm}
2 27/J2" DIA
{72.2mm]
j
I fl ESCtJTCHEON 1--J/•1l9mm] ADJUST/.lfNT
F2 ESCUTCHEON
1/21I2.lmm} ADJUST/.lfNT
(I)
4"-12"
{l0I.6mm-J04.8mm]
Cf/UNG TO
DEFLECTOR
RECESSED HSW W/FJ OR F2 ESCUTCHEON
(I} F/J APPROVED FOR •• -6" {I0I.6/J/J -I52.4/J/J] Cf/LING TD DEFLECTOR WITH F2 ONLY.
Note: For Recessed HSW Sprinklers use installation wrench GFR2.
cULus permits use with F1, F2 or FP escutc heons for "Lig ht Hazard"
only. While FM limits use for the same hazard with the F2 escutcheon
only.
Model F1 FR56 Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC 1 Sprinkler Wrench
Technlcai Data:
Nominal "K" Factor Thread Temp. Rating Max. Bulb
Orifice Size Model Ambient Color us Metric Sprinkler Cover Temp
½" (15mm) 5.6 80 ½"NPT F1FR 135°F/57°C 135°F/57°c 100°F/38°C Orange
½" (15mm) 5.6 80 ½"NPT F1 FR 1ss°F/68°c 135°F/57°C 100°Ft38°c Red
½" (15mm) 5.6 80 ½" NPT F1FR 11s°F/79°C 165°F/74°C 100°F/38°c Yellow
½" (15mm) 5.6 80 ½" NPT F1FR 200°F/93°C 165°F/74°C 150°F/6s0 c Green
('> For VdS only = 155°F/68°C Norbulb and 1/2" [12,7mm) adjustment.
Model F1 FR56LL Quick Response Concealed Pendent Sprinklers
Installation Wrench: Model RC1 Sprinkler Wrench
Technlcal Data:
Nominal "K" Factor Thread Temp. Rating Max. Bulb Model Ambient Orifice us Metric Size Sprinkler Cover Temp Color
1/2" (15mm) 5.6 80 ½" NPT F1 FR56LL 200°F/93°C 165°F/74°C 150°F/65°c Green
'DuPont Registered Trademark
5.
Sprinkler
Approvals Identification
Number(SIN)
1 RA1414
1,411', 6 RA1414
1 RA1414
1 RA1414
Sprinkler
Approvals Identification
Number(SIN)
1, 5 RA141 4
1 1/2" MAX.
FACE OF FITTING
1-.. -··-·mTO FACE OF CEILING C~~~G MAX . .r·~1 ~=~li1~b~,=~ ~i'['.:i' :~~
COVER ADJUSTMENT j
COVER PLATE ------~
ASSEMBLY J 5/l6 .. DIA.
SPRINKLER ____J
CONCEALED J /2" ADJUSTMENT 017F"001A
Figure 1
Installation Aid
A protective cap is included for use during installation.
Important: The F1 FR56 Sprinkler with Model CCP cover
plate is not an FM Approved combination.
Installation
Quick response sprinklers are intended for installation as
specified in NFPA 13. Quick response sprinklers and stan-
dard response sprinklers should not be intermixed.
The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1 FRXLH & F1 FR28 Recessed Quick Response Sprin-
klers are to be installed as shown. The Model F1 or F2 Es-
cutcheons illustrated are the only recessed escutcheons
to be used with the Model F1FR56, F1FR56LL, F1FR42,
F1 FR42LL, F1 FRXLH & F1 FR28 Sprinklers. The use of any
other recessed escutcheon will void all approvals and ne-
gate all warranties.
When installing Model F1 FR56, F1 FR56LL, F1 FR42,
F1 FR42LL, F1 FRXLH & F1 FR28 Sprinklers, use the Model
D Sprinkler Wrench. Use the Model GFR2 Wrench for install-
ing F1FR56, F1FR56LL, F1FR42, F1FR42LL, F1FRXLH &
F1 FR28 Recessed Pendent Sprinklers. Any other type of
wrench may damage these sprinklers.
NOTE: A leak tight ½" NPT (R1/2) sprinkler joint can be
obtained with a torque of 8-18 ft-lbs (10,8 -24,4 N-m). Do
not tighten sprinklers over maximum recommended torque.
It may cause leakage or impairment of the sprinklers.
The Models F1FR56/CCP & F1FR56LUCCP Concealed
Sprinkler use the ½" orifice,½" NPT (R1/2), Model F1FR56
& F1FR56LL Pendent Sprinkler with a threaded Model CCP
cup which is factory attached to the sprinklers. The Model
F1 FR56 Pndent is available in temperature rating of 135°F
(57°C), 155°F (68°C), 175°F (79°C) or 200°F (93°C). The
Model F1 FR56LL Pendent is available only in a rating of
200°F (93°C). The concealed sprinkler assemblies are com-
pleted by the installation of the attractive low profile Model
CCP push on cover plate assembly, rated 135°F (57°C) or
165°F (74°C) for the F1FR56 and 165°F (74°C) for the FIFR56
LL. The cover plate and sprinkler cup assemblies are joined
using a cover plate skirt with flexible tabs for threaded en-
*D uPont Registered Trade Mark
6.
1 " • 1/2" REDUCING
Tff OR ELBOW '-.... ··-··-··-----· -k=~=:" --------,--------,, :=~~~~ -
--2 5/8" DIA.
2 5/16" 0 HOLE IN CEILING
CUP
3/4"
CONCEALED, 5/JS" ADJUSTMENT 011,00:rA
Figure 2
gagement. A choice of two cover plate assemblies provide
either 1/2" (13mm) or 5/8" (8mm) of cover adjustment,
Do not install these sprinklers in ceiling which have positive
pressure in the space above.
After a 25/s" (67mm) diameter hole is cut in the ceiling, the
sprinkler is easily installed with the Model RC1 Wrench. A
Teflon* based thread sealant should be applied to the sprin-
kler threads only. The Model RC1 Wrench is then used to
engage the sprinkler wrenching surfaces and to install
the sprinkler in the fitting. When inserting or removing the
wrench from the sprinkler/cup assembly, care should be tak-
en to prevent damage to the sprinkler. DO NOT WRENCH
ON ANY OTHER PART OF THE SPRINKI ER The cover
plate is then pushed onto the cup. Final adjustment is made
by hand turning the cover plate until the skirt flange makes
full contact with the ceiling. Cover plate removal requires
turning in the counter clockwise direction.
After installation, inspect all sprinklers to ensure that there
is a gap between the cover plate and ceiling and that the
four cup slots are open and free from any air flow impedi-
ment to the space above.
Concealed cover plate/cup assemblies are listed only for
use with specific sprinklers. The use of any other concealed
cover plate/cup assembly with the Model F1 FR56 Pendent
Sprinkler or the use of the Model CCP Concealed cover
plate assembly on any sprinkler with which it is not specifi-
cally listed my prevent good fire protection and will void all
guarantees, warranties, listings and approvals.
Glass bulb sprinklers have orange bulb protectors to
minimize bulb damage during shipping, handling and in-
stallation. REMOVE THIS PROTECTION AT THE TIME THE
SPRINKLER SYSTEM IS PLACED IN SERVICE FOR FIRE
PROTECTION. Removal of the protectors before this time
may leave the bulb vulnerable to damage. RASCO wrench-
es are designed to install sprinklers when covers are in
place. REMOVE PROTECTORS BY UNDOING THE CLASP
BY HAND. DO NOT USE TOOLS TO REMOVE THE PRO-
TECTORS.
Temperature Ratings
Sprinkler Max. Ambient Classification Temoerature Bulb Color oc OF Temp.
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
Hiah <1> 141 286 225°F /107°C\ Blue
<1> Not available for recessed sprinklers.
Escutcheon Data <1>
<1> SIN RA1435 -cULus permits use with F1, F2 or FP escutcheons for "light
hazard" only, while FM limits use for same hazard with F2 escutcheon only.
Maintenance
The Model F1 FR56, F1 FR56LL, F1 FR42, F1 FR42LL,
F1 FRXLH and Model F1 FR56, F1 FR56LL, F1 FR42,
F1FR42LL, F1FRXLH & F1FR28 Recessed Sprinklers should
be inspected and the sprinkler system maintained in accor-
dance with NFPA 25. Do not clean sprinklers with soap and
water, ammonia or any other cleaning fluids. Remove dust
by using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of dam-
aged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging
to minimize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
•DuPont Registered Trademark
7.
Finishes <1>
Standard Finishes
Sorin kier Escutcheon Cover olate<1>
Bronze Brass Chrome
Chrome Plated Chrome White
Polvester Plated
Coated <4x5xe) White Painted
Soec ial Aoolicatlon Finishes
Sorinkler Escutcheon Cover olate<1>
Electroless Nickel Electroless Nickel Bright Brass PTFE/Teflon<11>)•<7> PTFE (Teflon<11>l'
Briaht Brass<3l Briaht Brass Black Platinn
Black Plated Black Plated Black Paint
Black Paint<2xe, Black Paint Off White
Off White<2X6l Off White Satin Chrome
Chrome Dull Chrome Dull
c1> Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
c2> cULus Listed only.
<3> 200°F (93°C) maximum.
c•> cULus listed "corrosion resistance" applies to SIN Numbers RA 1435
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
cs> FM Approvals finish as "Polyester coated" applies to SIN Number
RA 1414, RA 1435 and RA 1425 in standard black or white.
cs1 LPCB and VdSApprovedfinish applies only to RA 1425, RA 1414 and RA 1475.
C1> cULus listed Corrosion Resistant
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
9. Cover plate Model
10. Cover plate Thread size
11 . Cover plate Temperature
12. Cover plate Adjustment
13. Cover plate Finish
Note: When Model F1 FR56 Recessed sprinklers are ordered, the sprinklers
and escutcheons are packaged separately.
Reliable!
Product Description
Model J11 2 and JL 112 series sprinklers are cULus Listed
extended coverage spray sprinklers intended for installation
in accordance with NFPA 13. The sprinklers also have cU-
Lus Listed Specific Application Criteria for installation under
concrete tee construction in accordance with the require-
ments documented in this bulletin. Coverage areas up to
400 ft2 (37 m2) per sprinkler with a maximum spacing of up
to 20 ft by 20 ft (6.1 m by 6.1 m) are permitted for both Light
Hazard and Ordinary Hazard occupancies. Listed flows and
pressures for each hazard classification and sprinkler spac-
ing are provided in this bulletin. Model J112 and JL 112 se-
ries sprinkler are cULus Listed as quick-response sprinklers
for Light Hazard occupancies. When used in the Ordinary
Hazard occupancies, Model J 112 and JL 112 series sprin-
klers are cULus Listed as quick-response for spacings up
to 14 ft by 14 ft ( 4.3 m by 4.3 m) and standard-response for
other listed spacings up to 20 ft by 20 ft (6.1 m by 6.1 m).
Model J112 Pendent and J1 12 Upright sprinklers use a
glass bulb operating element and are cULus Listed as
Corrosion Resistant Sprinklers when ordered with White
Polyester, Black Polyester, or Electroless Nickel PTFE (ENT)
finish. Model JL 112 Pendent and JL 112 Upright sprinklers
use a fusible link operating element. Model J112 Pendent
and Model JL 112 Pendent sprinklers are cULus Listed for
use with the Model F2 and Model FP recessed escutch-
eons, which provide up to½ inch (13 mm) of adjustment. In
addition, for Ordinary Hazard occupancies, the Model J112
Pendent and Model JL 112 Pendent sprinklers are cULus
Listed for use with the Model F1 recessed escutcheon that
provides up to ¾ inch (19 mm) of adjustment.
Application
Model J 112 and JL 112 series sprinklers are intended for
installation in Light Hazard and Ordinary Hazard occupan-
cies in accordance with NFPA 13. The sprinklers must be
installed in accordance with the requirements of NFPA 13
for extended coverage spray sprinklers and the require-
ments identified in this bulletin. In addition to the installation
requirements of NFPA 13, cULus Listed Specific Application
Criteria for installation under concrete tee construction is
provided in this bulletin.
Model J112 and JL 112 Series Sprinkler Summary
Model Orientation
J112 Pendent
JL112 Pendent
J112 Upright
JL11 2 Upright
Bulletin 172 May 2019
Model J112 and JL 112 Sprinklers
Extended Coverage Sprinklers for
Light Hazard and Ordinary Hazard
Model JL 112 Upright
Model JL 112 Pendent
F1/F2 Recessed Escutcheon
Operating Element
Glass Bulb
Fusible Link
Glass Bulb
Fusible Link
cULus Listed
K11 .2 (160 metric)
Model J 112 Upright
Model J 112 Pendent
FP Recessed Escutcheon
Table A
Sprinkler Identification Number
(SIN)
RA7216
R7216
RA7326
R7326
www.reliablesprinkler.com
Model J112 Pendent Sprinkler SIN RA7216
Technical Specifications
Style: Extended Coverage Pendent
Threads: 3/4" NPT or ISO 7-1 R3/4
Nominal K-Factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Glass Bulb
Cup: Bronze Alloy
Frame: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Kick Spring: Steel Alloy
Deflector: Brass Alloy
Sprinkler Wrench
Model J1
Model RJ (recessed)
Finishes
(See Table G)
Sensitivity
(See Table B)
Temperature Ratings
155°F (68°C)
200°F (93°C)
286°F (141°C)
Recessed Escutcheons
F1 -3/4" (19mm) adjustment (Ordinary Hazard only)
F2-1/2" (13mm) adjustment
FP-1/2" (13mm) adjustment
Listings and Approvals
cULus Listed
cULus Listed as Corrosion Resistant
with White Polyester, Black Polyester,
and ENT finish only
_M_o_d_e_l_J_1_1_2_P_e_n_d_e_n_t_S_p_r_in_k_le_r_C_o_m_p_o_n_e_n_t_s _______________________ .§j.jijij-
Wrench Flat
Bulb
Listed Design Criteria and Sensitivity
Max. Spacing Light Hazard Ordinary Hazard
Group 1 ft. X ft.
(mxm)
12 X 12
(3.7 X 3.7)
14 X 14
(4.3 X 4.3)
16 X 16
(4.9 X 4.9)
18 X 18
(5.5 X 5.5)
20x 20
(6.1 X 6.1)
QR = Quick-response
SR = Standard-response
Bulletin 172
May 2019
Flow
gpm (Vm)
30 (114)
QR
30 (114)
QR
30 (114)
QR
33 (125)
QR
40 (152)
QR
Pressure Flow Pressure
psi (bar) gpm (1/m) psi (bar)
7.2 (0.50) 30 (114) 7.2 (0.50)
QR QR QR
7.2 (0.50) 30 (1 14) 7.2 (0.50)
QR QR QR
7.2 (0.50) 39 (148) 12.1 (0.8)
QR SR SR
8.7 (0.60) 49 (186) 19.1 (1.3)
QR SR SR
12.8 (0.88) 60 (227) 28.7 (2.0)
QR SR SR
3" (76mm)
Table B
Ordinary Hazard
Group 2
Flow Pressure
gpm (1/m) psi (bar)
39 (148) 12.1 (0.8)
QR QR
39 (148) 12.1 (0.8)
QR QR
51 (193) 20.7(1.4)
SR SR
65 (246) 33.7 (2.3)
SR SR
80 (303) 51 .0 (3.5)
SR SR
Page 2 of 7
www.reliablesprinkler.com
Model JL 112 Pendent Sprinkler SIN R7216
Technical Specifications
Style: Extended Coverage Pendent
Threads: 3/4" NPT or ISO 7-1 R3/4
Nominal K-Factor: 11 .2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 fl. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Frame: Brass Alloy
Levers: Brass Alloy
Cap: Bronze Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Brass Alloy
Strut: Copper Alloy
Sprinkler Wrench
Model J1
Model RJ (recessed)
Finishes
(See Table G)
Sensitivity
(See Table C)
Temperature Rating*
165°F (74°C)
212°F (100°c)
Recessed Escutcheons
F1-3/4" (19mm) adjustment (Ordinary Hazard only)
F2-1/2" (13mm) adjustment
FP-1/2" (1 3mm) adjustment
Listings and Approvals
cULus Listed
•c hrome and white polyester finish is supplied
with white link regardless of temperature rating
__ Mo_d_e_l_J_1_1_2_P_e_n_d_e_n_t_S_p_r_in_k_le_r_C_o_m....;p_o_n_e_n_t_s _______________________ .. ii•Mif.-lll
Link
Listed Design Criteria and Sensitivity
Max. Spacing
ft. X ft.
(mxm)
12 X 12
(3.7 X 3.7)
14 X 14
(4.3 X 4.3)
16 X 16
(4.9 X 4.9)
18 X 18
(5.5 X 5.5)
20 x20
(6.1 X 6.1)
QR = Quick-response
SR = Standard-response
Bulletin 172
May 2019
Light Hazard
Flow Pressure
gpm (Vm) psi (bar)
30 (114) 7.2 (0.50)
QR QR
30 (114) 7.2 (0.50)
QR QR
30 (114) 7.2 (0.50)
QR QR
33 (125) 8.7 (0.60)
QR QR
40 (152) 12.8 (0.88)
QR QR
L1-5/8" (42mm)J
Ordinary Hazard
Group 1
Flow Pressure
gpm (1/m) psi (bar)
30(114) 7.2 (0.50)
QR QR
30 (1 14) 7.2 (0.50)
QR QR
39 (148) 12.1 (0.8)
SR SR
49 (186) 19.1 (1.3)
SR SR
60 (227) 28.7 (2.0)
SR SR
3' (76mm)
Table C
Ordinary Hazard
Group2
Flow Pressure
gpm (Vm) psi (bar)
39 (148) 12.1 (0.8)
QR QR
39 (148) 12.1 (0.8)
QR QR
51 (193) 20.7 (1.4)
SR SR
65 (246) 33.7 (2.3)
SR SR
80 (303) 51.0 (3.5)
SR SR
Page 3 of 7
www.reliablesprinkler.com
Model J112 Upright Sprinkler SIN RA7326
Technical Specifications
Style: Extended Coverage Upright
Threads: 3/4" NPT or ISO 7-1 R3/4
Nominal K-factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Glass Bulb
Cup: Bronze Alloy
Frame: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Kick Spring: Steel Alloy
Deflector: Brass Alloy
Finishes
(See Table G)
Sensitivity
(See Table D)
Temperature Rating
155°F (6a0 c)
200°F (93°G)
2as°F (141 °C)
Sprinkler Wrench
Model J1
Listings and Approvals
cULus Listed
cULus Listed as Corrosion Resistant
with White Polyester, Black Polyester,
and ENT finish only
_M_o_d_e_l_J_1_1_2_U_p_r_ig'-h_t_S_p_r_in_k_l_e_r_C_o_m __ p_o_n_e_n_ts ________________________ i/-/iiif-
Wrench Flat
Bulb
1-5/8' (41mm)
Listed Design Criteria and Sensitivity
Max. Spacing Light Hazard Ordinary Hazard
Group 1 ft. X ft.
(mxm)
12 X 12
(3.7 X 3.7)
14 X 14
(4.3 X 4.3)
16 X 16
(4.9 X 4.9)
18 X 18
(5.5 X 5.5)
20x 20
(6.1 X 6.1)
QR = Quick-response
SR = Standard-response
Bulletin 172
May 2019
Flow
gpm (Vm)
30 (114)
QR
30 (114)
QR
30 (114)
QR
33 (125)
QR
40 {152)
QR
Pressure Flow Pressure
psi (bar) gpm (Vm) psi (bar)
7.2 (0.50) 30 (114) 7.2 (0.50)
QR QR QR
7.2 (0.50) 30 (114) 7.2 (0.50)
QR QR QR
7.2 (0.50) 39 (148) 12.1 (0.8)
QR SR SR
8.7 (0.60) 49 (186) 19.1 (1.3)
QR SR SR
12.8 (0.88) 60 (227) 28.7 (2.0)
QR SR SR
iTirF'Frr:
2-13/16' (71mm)
Table D
Ordinary Hazard
Group2
Flow Pressure
gpm (1/m) psi (bar)
39 (148) 12.1 (0.8)
QR QR
39 (148) 12.1 (0.8)
QR QR
51 (193) 20.7(1.4)
SR SR
65 (246) 33.7 (2.3)
SR SR
80 (303) 51.0 (3.5)
SR SR
Page 4 of 7
www.reliablesprinkler.com
Model JL 112 Upright Sprinkler SIN R7326
Technical Specifications
Style: Extended Coverage Upright
Threads: 3/4" NPT or ISO 7-1 R3/4
Nominal K-factor: 11.2 (160 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Frame: Brass Alloy
Levers: Brass Alloy
Strut: Brass Alloy
Cap: Bronze Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Deflector: Brass Alloy
Finishes
(See Table G)
Sensitivity
(See Table E)
Temperature Rating•
165°F (74°C)
212°F (100°C)
Sprinkler Wrench
Model J1
Listings and Approvals
cULus Listed
*Chrome and white polyester finish is supplied
with white link regardless of temperature rating
_M_o_d_e_l_J_L_1_12_U_p_r_ig_h_t_S_p_r_in_k_l_e_r_C_o_m_p_o_ne_n_t_s ______________________ ~-i/-jijji-
Wrench Flat
Link
--1-5/8' (41mm)
Listed Design Criteria and Sensitivity
Max. Spacing Light Hazard Ordinary Hazard
Group 1 ft. X ft.
(mxm)
12 X 12
(3.7 X 3.7)
14 X 14
(4.3 X 4.3)
16 X 16
(4.9 X 4.9)
18 X 18
(5.5 X 5.5)
20x 20
(6.1 X 6.1)
QR = Quick-response
SR = Standard-response
Bulletin 172
May 2019
Flow
gpm (Vm)
30(114)
QR
30 (114)
QR
30 (114)
QR
33 (125)
QR
40 (152)
OR
Pressure Flow Pressure
psi (bar) gpm (1/m) psi (bar)
7.2 (0.50) 30 (114) 7.2 (0.50)
QR QR QR
7.2 (0.50) 30(114) 7.2 (0.50)
QR QR QR
7.2 (0.50) 39 (148) 12.1 (0.8)
QR SR SR
8.7 (0.60) 49 (1 86) 19.1 (1.3)
QR SR SR
12.8 (0.88) 60 (227) 28.7 (2.0)
OR SR SR
i . . • .
2-13/16' (71mm)
Table E
Ordinary Hazard
Group2
Flow Pressure
gpm (1/m) psi (bar)
39 (148) 12.1 (0.8)
QR QR
39 (148) 12.1 (0.8)
QR OR
51 (193) 20.7 (1.4)
SR SR
65 (246) 33.7 (2.3)
SR SR
80 (303) 51.0 (3.5)
SR SR
Page 5 of 7
www.reliablesprinkler.com
Model J112 and JL 112 Specific Application Criteria for Use Under Concrete Tee Construction cULus Listed
The Model J112 and JL 11 2 pendent and upright sprinklers are cULus Listed for installation under concrete tee construction in ac-
cordance with the following specific application criteria:
• Max. Tee Depth: 2'-6" (0.8m)
• Max. Tee Stem Spacing: 7'-6" (2.3m)
• Min. Tee Stem Spacing: 3'-O" (0.9m)
• Max. Tee Length: 32'-O" (9.8m) or baffles not less than the depth of the tees must be installed so that the longitudinal space
between baffles does not exceed 32ft (9.8m) in length.
• Max. Deflector distance below Tee: 1" (25mm)
• Comply with obstructions to the Sprinkler Discharge Pattern Development requirements of the NFPA13 where deflector is lo-
cated above bottom of tee.
Application and Installation for Use Under Concrete Tee Figure 5
Model FP Escutcheon
Installation Dimensions
2-5/8' DIA. (67mm) -t--+------+-<
Hole In Celllng
2.S/16' DIA. --t,J--t
(59mm)Cup
--3-3/16' (81mm)
v t::~=~:v lL..Y
!• ·····················T······················~ 1" (25mm) max. J
! 7'-6" (2.3m) max. !
3'-0' (0.9m) min.
Figure 6
1' (25mm) +/-1/4' (6mm)
1-3/8' (35mm) +/-1/4' (6mm)
Model F1/F2 Escutcheon
Installation Dimensions
1-15/16"DIA.
(491ml)
2-318' (60mm) DIA .
Hole In Celling
2-13/16"(71mm)
Figure 7
Fl: 1/Z' (12mm) +/-3/8' (10mm)
t--+,"'T'Tm-,, F2: 3/8' (10mm) +/. 1/4' (6mm)
F1:2'(51mm) •/-3/8'(10mm)
F2: 2· 1/8' (54mm) +/· 1/4' (6mm)
Note: The Model FP, F1 , or F2 may be used for ordinary hazard occupancies. For light hazard occupancies, the Model FP or F2
recessed escutcheon must be used. Model J112 and JL 112 sprinklers with Model F1 recessed escutcheon are not listed for use
in light hazard occupancies.
Bulletin 172
May 2019
Page 6 of 7