HomeMy WebLinkAbout3457 VIA MONTEBELLO; 156 | 158; FPC2018-0368; PermitPERMIT REPORT
Fire Permit
Print Date: 03/16/2022
Job Address: 3457 VIA MONTEBELLO, # 158 & 156, CARLSBAD, CA 92009-8491
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
2230530900 Track#:
$86,276.05 Lot#:
Project#:
Plan#:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check#:
Plan Check#:
Project Title:
Description: EAST HOLLISTIC MASSAGE -SPRINKLER Tl (21 HEADS 1 RISER)
FEE
FIRE NFPA 13 or 13R System 7 -100 heads
Total Fees: $553.00 Total Payments To Date: $553.00
Fire Department
(city of
Carlsbad
Permit No: FPC2018-0368
Status: Closed -Finaled
Applied: 11/14/2018
Issued: 11/28/2018
Finaled Close Out: 03/16/2022
Inspector:
Final Inspection:
FPContractor:
BRIAN SULLIVAN
1975 SPANISH OAK WAY
VISTA, CA 92081-7383
(760) 716-9226
Balance Due:
AMOUNT
$553.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
1:qca Worldwide Contacts www.tyco-fire.com
Series TY-FRB, 5.6 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
• A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 inch (15,9 mm) from
the flush pendent position.
• A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 inch (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must b'e cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
lt11•1i@I
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification
Number (SIN}
TY313 •..... Upright 5.6K, 1/2"NPT
TY323 ...... Pendent 5.6K, 1/2" NPT
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
• The maximum working pressure of 250 psi {17.2 bar)
only applies to the listing by Underwriters Laborato-
ries. Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi½ (80,6 LPM/bar½)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................ Bronze
Button ...................... Brass/Copper
Sealing Assembly ... Stainless Steel w/TEFLON
Bulb ............................... Glass
Compression Screw ................. Bronze
Deflector .......................... Bronze
FEBRUARY 2018
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
TFP172
TFP172
Page 2 of4
Components:
1 -Frame
2 -Button
3 -Sealing
4 -Bulb
5 -Compression
Screw
* Temperature rating is
indicated on Deflector.
** Pipe thread connections per ISO 7-1
can be provided on special request.
Assembly 6 -Deflector* DEFLECTOR *
1/2' 7/16" (11,1 mm)
NPT** NOMINAL MAKE-IN
STYLE 15 or 20
RECESSED
ESCUTCHEON
7/16'
(1 1,1 mm)
NOMINAL
MAKE-IN
2'
(50,8 mm)
j
CROSS SECTION
1/2' NPT**
UPRIGHT
_J_ t
PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
WRENCH RECESS
(USE ONLY
END 'A")
FIGURE2
W-TYPE6
SPRINKLER WRENCH
WRENCH
RECESS
t
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprinkler
if the bulb is cracked or there is a loss
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F (57°C) and 3/32
inch (2,4 mm) for the 286°F (141 °C) tem-
perature ratings.
A leak-tight 1/2 inch NPT sprinkler
joint should be obtained by applying a
minimum to maximum torque of 7 to 14
ft.-lbs. (9,5 to 19,0 Nm). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under-or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 ft.-lbs. (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 ft.-lbs. (9,5 to 19,0
Nm).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
TFP172
Page 3 of 4
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA.
(57,2 mm)
3/8±5/16" '71~
I I
MOUNTING
5/8" (15,9 mm)
FLUSH
__l (9,5±7,9 mm) VZ,
SURFACE ~ia::::&!b
CLOSURE SERIES
TY-FRB
MOUNTING
PLATE
1-3/8" (34,9 mm)
3/4" (19,1 mm)
FIGURE4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER
FITTING
2-1/4" DIA.
(57,2 mm)
5/16±1/4'
(7,9±6,4 mm)
MouNTING
SURFACE
1/2' (12,7 mm)
FLUSH
l-\J.:!=7'.:::
=L_l
1/8'
(3,2 mm)
I I ~Z-
er:::==::,
CLOSURE SERIES
TY-FRB
MOUNTING
PLATE
1-3/8' (34,9 mm)
7/8" (22,2 mm)
FIGURE5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 112 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(PIN).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specifyj finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, PI N (specify*)
• Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
TFP172
Page 4 of4
SPRINKLER FINISH (See Note 7)
K TYPE TEMPERATURE BULB LIQUID NATURAL I CHROME I POLYESTERc FACTOR COLOR BRASS PLATED
135°F (57°C) Orange
UPRIGHT 155°F (68°C) Red (TY313)
and 175°F (79°C) Yellow 1,2,3,4, 5,6
PENDENT 2oo·F (93°C) Green (TY323)
5.6 286°F (141°C) Blue 1/2" NPT
135°F (57°C) Orange
RECESSED 155"F (68°C) Red PENDENT
(TY323) 175°F (79°C} Yellow 1, 2, 3, 4
Figures 4• and Sb
2oo·F (93°C) Green
Notes:
1. Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the City of New York under MEA 354-01-E.
5. VdS Approved (For details, contact TYCO Fire Protective Products, Enschede, Nethe~ands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
6. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 0948/06) as Quick Response Sprinklers.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
a. Installed with Style 15 (1/2" NPTI 5/8" Total Adjustment Recessed Escutcheon. as applicable.
b. Installed with Style 20 (1/2" NPTI 1/2" Total Adjustment Recessed Escutcheon, as applicable.
c. Frame and Oeflector only. Listings and approvals apply to color (Special Ord•~-
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na 77 -XXX -X -XXX I ·1
I I SIN SPRINKLER
FINISH
370 5.6K UPRIGHT (1/2" NPT) TY313 1 NATURAL BRASS 135
371 5.6K PENDENT (1/2" NPT) TY323 3 PURE WHITE (RAL9010)8
POLYESTER 155
Notes: SIGNAL WHITE (RAL9003) a Use suffix ·1• for ISO 7-1 connection; for example, 4 175
77-370-4-175-1 POLYESTER
5 JET BLACK iRAL9005)
POLYE TER 200
9 CHROME PLATED 286
Notes:
a. Eastern Hemisphere safes only
TABLES
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway, Lansdale, PA 19446 I Telephone +1-215-362-0700
02011 JohMon Controlt. Al rioht• ~-Al •PK-iftcetions end other lnl~ •hown were c~nt •• of document rfflaion d■t• and.,. Mlbject to change without notice,,
NATIONAl ARE PROTECTION ASSOCIATION and NfPA •• ~ 1,ademaftui of NehoNil F-~lion~ TITLON la 1 .-.oiti.t.i t,IM,Mlilark of DuPont
TEMPERATURE
RATINGS
135°F (57°C)
155°F (68°C)
175°F (79°C)
200°F (93°C)
286°F (141 °C)
Johnson f JJ,
Controls
FPC2018-0368
3457 VIA MONTEBELLO #158 &
EAST HOLLISTIC MASSAGE -SPRINKLER Tl (21 HEADS 1 ......
RISER)
2230530900
11/14/2018
F PC2018-0368