HomeMy WebLinkAbout5927 LANDAU CT; ; FPC2020-0204; PermitPERMIT REPORT
Fire Permit
Print Date: 11/03/2021
Job Address: 5927 LANDAU CT, CARLSBAD, CA 92008-8803
Permit Type: FIRE-Construction Commercial Work Class:
Parcel#: 2120611900 Track#:
Valuation: $485,796.95 Lot#:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
Project#:
Plan#:
Construction Type:
Orig. Plan Check #:
Plan Check#:
Description: ATLAS INVESTMENT -SPRINKLER Tl (31 HEADS)
Applicant:
TOTAL FIRE PROTECTION INC
JOHN CAPUTO
1611A S MELROSE DR
VISTA, CA 92081-5407
(760) 525-4329
FEE
FIRE NFPA 13 or 13R System 7 -100 heads
Fire Sprinklers
Total Fees: $553.00 Total Payments To Date: $553.00
Fire Department
{City of
Carlsbad
Permit No: FPC2020-0204
Status: Closed -Finaled
Applied: 12/03/2020
Issued: 01/07/2021
Finaled Close Out: 11/03/2021
Inspector:
Final Inspection:
Balance Due:
AMOUNT
$553.00
$0.00
Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
.... Bulletin 014 Rev. L
Relialll~ Model F1 FR Series
Quick Response
Standard Spray
Model F1 FR56 Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Vertical Sidewall
Horizontal Sidewall
Model F1 FR56 Recessed Sprinkler Types
Standard Pendent/F 1 /F2/FP
Horizontal Sidewall
Model F1 FR56 Concealed Sprinkler Types
Standard Pendent
Model F1 FR42, F1 FRXLH & F1 FR28 Sprinkler
Types
Standard Upright
Standard Pendent
Model F1 FR42, F1 FRXLH & F1 FR28 Recessed
Sprinkler Types
Standard Pendent
Model F1 FR56LL & F1 FR42LL Low Lead Sprinkler
Types*
Standard Pendent
Less than 0.25% Lead Content
Listing & Approvals
1. Underwriters Laboratories Inc. and Certified for
Canada (cULus).
2. Factory Mutual Approvals (FM)
3. Loss Prevention Council (LPCB, UK)
4. VdS Schadenverh0tung GmbH
5. *NSF Certified to NSF/ANSi Standard 61 Annex G
6. EC Certificate: 0786-CPD-40239 (RA 1414 ), 0786-
CPD-40251 (RA 1425), 0786-CPD-40252 (RA 1475)
UL Listing Category
Sprinklers, Automatic & Open (VNIV)
Quick Response Sprinkler
Product Description
Reliable Models F1 FR56, F1FR56LL, F1 FR42, F1FR42LL,
F1 FRXLH & F1 FR28 Series Sprinklers are quick response
sprinklers which combine the durability of a standard sprin-
kler with the attractive low profile of a decorative sprinkler.
The Models F1FR56, F1 FR56LL, F1FR42, F1FR42LL,
F1 FRXLH & F1 FR28 Series Recessed automatic sprinklers
utilize a 3.0 mm frangible glass bulb. These sprinklers have
demonstrated response times in laboratory tests which are
five to ten times faster than standard response sprinklers.
This quick response enables the Model F1FR56, F1FR56LL,
Upright Pendent
Vertical Sidewall Horizontal Sidewall
Recessed
Horizontal Sidewall
XLH Upright
Concealed
Pendent
XLH Pendent
F1FR42, F1FR42LL, F1FRXLH &
F1 FR28 Series sprinklers to apply wa-
ter to a fire much faster than standard
sprinklers of the same temperature rat-
ing.
The glass bulb consists of an accu-
Conventional
Recessed
Pendent/F1tf2
Recessed
PendenttfP
XLH Recessed
Pendent F 1 /F2
.....__ ____ -----1
rately controlled amount of special fluid XLH Recessed
hermetically sealed inside a precisely Pendent FP
manufactured glass capsule. This glass bulb is specially
constructed to provide fast thermal response.
At normal temperatures, the glass bulb contains the fluid
in both the liquid and vapor phases. The vapor phase can
be seen as a small bubble. As heat is applied, the liquid
expands, forcing the bubble smaller and smaller as the liq-
uid pressure increases. Continued heating forces the liquid
to push out against the bulb, causing the glass to shatter,
opening the waterway and allowing the deflector to distrib-
ute the discharging water.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application
Quick response sprinklers are used in fixed fire protection systems: Wet, Dry, Deluge or Preaction. Care must· be
exercised that the orifice size, temperature rating, deflector style and sprinkler type are in accordance with the latest
published standards of the National Fire Protection Association or the approving Authority Having Jurisdiction. Quick
response sprinklers are intended for installation as specified in NFPA 13. Quick response sprinklers and standard re-
sponse sprinklers should not be intermixed.
*Pin tie
(XLH On~)
Deflector
Washer
Frame
014FG06A
Load Screw
Bulb
Cup
Model F1 FR42, F1 FRXLH Upright
Technical data:
Thread Max. Min. Temperature Models Discharge Coefficient Response Working Working Finish Size Pressure Pressure Rating
F1FR56 K 5.6 **F1 FR56LL<1>
F1FR42 Quick 1/2" NPT See See
**F1 FR42LL<1> K4.2 Response (R1/2) 175 PSI 7 PSI "Temperature "Finish Table"
F1FRXLH Ratings" Table.
F1FR28 K2.8
<1> Low Lead Sprinklers available only with Temperature Rating 200°F/93°C
Material Data:
Frame Deflector Load Screw *Plntle Cup Washer Bulb
DZR Brass CDA Alloy 260, CDAAlloy 360 CDA Alloy 360 CDA Alloy 651 Nickel Alloy 440 or Alloy 360
QM Brass CDA Alloy 220 or or or coated with PTFE Adhesive Glass
**Low Lead Brass or CDA Alloy 544 CDA Alloy 544 CDA Alloy 693 Tape CDA Alloy510
2.
Model F1 FR56, Upright, Pendent & Conventional Sprinklers
Model F1 FR42, F1 FRXLH & F1 FR28 Upright & Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal Thread Nominal K Factor Sprinkler Approval
Orifice
Size us Metric Height Organization
Sprinkler Identification Number
(SIN)
Upright Pendent
Standard-Upright (SSU) and Pendent Deflectors Marked to Indicate Position
1/2" (15mm) (1) 1/2" NPT (R1/2) 5.6 80 2.25" (57mm) 1,2,3,4, 6
7/16" (10mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) 1
3/8" (10mm) 1/2" NPT (R1/2) 2.8 40 2.25" (57mm) 1
Conventional-Install In Upright or Pendent Position
15mm(1l 1/2" NPT (R1/2) 5.6 80
<1J cULus listed corrosion resistant (Polyester coated) sprinkler.
<2J Polyester coated FM approved sprinkler.
57mm
<3J Polyester coated LPCB & VdS approved sprinkler RA 1425, RA 1414 & RA 1475.
<4J Electroless Nickel PTFE (Teflon®)* Plated -cULus listed Corrosion Resistant
Upright Pendent
Model F1 FR56LL & F1 FR42LL Pendent Sprinklers
Installation Wrench: Model D Sprinkler Wrench
Installation Data:
Nominal Thread Nominal K Factor Sprinkler
Orifice
Size us Metric Height
3,4,6
Approval
Organization
Standard-Pendent Deflectors Marked to Indicate Position
1/2" (15mm) <1J 1/2" NPT (R1/2) 5.6 80 2.25" (57mm) 1, 5
7/16" (11mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) 1, 5
<1J cULus listed corrosion resistant (Polyester coated) sprinkler.
*DuPont Registered Trademark
3.
RA 1425(1l(2l<3l(4l RA 1414(1X2H3l(4l
RA 1423<1)(4) RA1413(4l
RA 1421(1)(4) RA1411(4l
RA1475(3l
Conventional
Sprinkler Identification Number
(SIN)
Pendent
RA1415
RA1410
-Model F1 FR56, F1 FR42, F1 FRXLH & F1 FR28 Quick Response Recessed Pendent Sprinkler<1>
lnstallatlon Wrench: Model GFR2 Sprinkler Wrench
lnstallatlon Data:
Nominal Thread K Factor Sprinkler Sprinkler Identification Number
Orifice Size us Metric Height (SIN)
1/2" (15mm) 1/2" NPT(R½) 5.6 80 2.25" (57mm) RA1414
7/16" (10mm) 1/2" NPT (R1/2) 4.2 60 2.25" (57mm) RA1413
3/8" (10mm) 1/2" NPT (R1/2) 2.8 40 2.25" (57mm) RA1411
<1> Refer to escutcheon data table for approvals & dimensions
Model F1 FR56LL & F1 FR42LL Quick Response Recessed Pendent Sprinkler<1>
lnstallatlon Wrench: Model GFR2 Sprinkler Wrench
lnstallatlon Data:
Nominal Thread K Factor
Orifice Size us Metric
1/2" (15mm) 1/2" NPT(R½) 5.6 80
7/16" (10mm) 1/2" NPT (R1/2) 4.2 60
<1> Refer to escutcheon data table for approvals & dimensions
1• X 1/2' R£DUCER
r,.........L......111B---1J~ll-------l---4----~
AT W.Xllllltl R£CESS -7/8f22.2mm]
AT --R£CESS -1-5/Bf•U.Jmm] ~
Sprinkler Sprinkler Identification Number
Height (SIN)
2.25" (57mm) RA1415
2.25" (57mm) RA1410
2 .5/lf" lM [tl&7mm] ---I,,-.+--------,,..~ HOtE IN CEIUNG
2 .5/16" lM [!J8.7mm} -.&.J.-----..J.__ ___ ~-CUP
C£1UNG
I" X 1/2" REDUCER
FACE OF F1TTING ro FACE OF CDUNG
DIIIENSION
AT IIAX1lllM REr;£SS • l-l/2'[»nm] AT "1NMHtl REr;£SS • I 'f25.4mm]
T REr;£SS -9/16'f14.::smmJ
AT MAX/MUii RCCCSS -1-1/8128.flmm} AT lrllNIMM RCCESS -1-5/Bf•fl . .Jmm]
~ _j 'MM REr;£SS • 1'[2.5.fmm]
:J 1/4"£114. [112.6mm]
ModelF1FR56,F1FR56LL,F1FR42, F1FR42LL,F1FRXLH&
F1 FR28 F1 or F2
ModelF1FR56,F1FR56LL,F1FR42, F1FR42LL, F1FRXLH&
F1FR28 FP
Model F1 FR56 Quick Response Vertical Sidewall Sprinkler
Installation Wrench: Model D Sprinkler Wrench
lnstallatlon Position: Upright or Pendent
Approval Type: Light Hazard Occupancy
Installation Data:
Nominal Nominal K Factor Sprinkler Approval Sprinkler
Thread Size Identification Orifice us Metric Height Organizations Numbers (SIN)
½" (15mm) ½" NPT (R1/2) 5.6 80 2.25" (57mm) 1, 2, 3 RA 1485<2><3> 15mm ½" NPT (R1/2) 5.6 80 2.25" (57mm) 3(1)
<1> LPG Approval is for pendent position only.
<2> cULus Listed corrosion resistant (Polyester coated) sprinkler.
<3> Electroless Nickel PTFE (Teflon®)* Plated -cULus listed Corrosion Resistant
Vertical Sidewall
*DuPont Registered Trademark 4.
Sprinkler Type
U ri ht
Pendent
Deflector to Celling Distance
Min. -Max.
4" 102mm -12" 305mm
4" 102mm -12" 305mm
Temperature Ratings
Sprinkler Max. Ambient Classlflcatlon Temm ~rature Bulb Color oc Of Temp.
Ordinary 57 135 100°F (38°C) Orange
Ordinary 68 155 100°F (38°C) Red
Intermediate 79 175 150°F (66°C) Yellow
Intermediate 93 200 150°F (66°C) Green
Hiah (1l 141 286 225°F (107°C) Blue
<1l Not available for recessed sprinklers.
Escutcheon Data <1>
<1> SIN RA 1435 -cULus permits use with F1, F2 or FP escutcheons for "light
hazard" only, while FM lim~s use for same hazard with F2 escutcheon only.
Maintenance
The Model F1FR56, F1FR56LL, F1FR42, F1FR42LL,
F1 FRXLH and Model F1FR56, F1 FR56LL, F1 FR42,
F1 FR42LL, F1 FRXLH & F1 FR28 Recessed Sprinklers should
be inspected and the sprinkler system maintained in accor-
dance with NFPA 25. Do not clean sprinklers with soap and
water, ammonia or any other cleaning fluids. Remove dust
by using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprinklers
should be maintained to allow quick replacement of dam-
aged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging
to minimize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Sprinkler Types
Standard Upright
Standard Pendent
Conventional
Recessed Pendent
Vertical Sidewall
Horizontal Sidewall
Recessed Horizontal sidewall
Concealed pendent
Maximum Working Pressure
175 psi (12 bar)
100% Factory tested hydrostatically to 500 psi (34.5 bar)
*DuPont Registered Trademark
7.
Finishes <1>
Standard Finishes
Snrlnkler Escutcheon Cover Dlate<1>
Bronze Brass Chrome
Chrome Plated Chrome White
Po Ivester Plated
Coated (4l(5l(5l White Painted
SDSC lal Annllcatlon Finishes
SDrlnkler Escutcheon Cover Dlate<1>
Electroless Nickel Electroless Nickel Bright Brass PTFEff eflon®)*(7l PTFE (Teflon®)*
Briaht Brass(3l Briaht Brass Black Platina
Black Plated Black Plated Black Paint
Black Paint(2l(5l Black Paint Off White
Off White(2l(5l Off White Satin Chrome
Chrome Dull Chrome Dull
<1l Other finishes and colors are available on special order. Consult the
factory for details. Custom color painted sprinklers may not retain their
UL Corrosion resistance listing. Coverplate custom paint is semi-gloss,
unless specified otherwise.
<2l cULus Listed only.
<3> 200°F (93°C) maximum.
<4> cULus listed "corrosion resistance" applies to SIN Numbers RA 1435
(HSW), RA1485(VSW), RA1425 (Upright), RA1414 (Pendent) and
RA1415 (Pendent) in standard black or white. Corrosion resistance in
other polyester colors is available upon request.
<5> FM Approvals finish as "Polyester coated" applies to SIN Number
RA 1414, RA 1435 and RA 1425 in standard black or white.
<5l LPCB and VdS Approved finish applies only to RA 1425, RA 1414 and RA 1475.
<7l cULus listed Corrosion Resistant
Ordering Information
Specify:
1. Sprinkler Model
2. Sprinkler Type
3. Orifice Size
4. Deflector Type
5. Temperature Rating
6. Sprinkler Finish
7. Escutcheon Type
8. Escutcheon Finish (where applicable)
9. Cover plate Model
10. Cover plate Thread size
11. Cover plate Temperature
12. Cover plate Adjustment
13. Cover plate Finish
Note: When Model F1 FR56 Recessed sprinklers are ordered, the sprinklers
and escutcheons are packaged separately.
' .. Bulletin 110 August 2019
OJ C
Reliable ',-CD
Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of construc-
tion. The fusible alloy is captured in the cylinder of the
solder capsule by a stainless steel ball. When the fusible
alloy melts, the ball moves into the cylinder allowing the
cylinder to fall away from the sprinkler. When this happens,
the lever is released to spring free from the sprinkler so
that all of the operating parts clear from the waterway al-
lowing the deflector to distribute the discharging water.
Except for the parts in the cylinder as mentioned above,
the sprinkler components are made from copper based
alloys for maximum corrosion protection. Lead plated, wax
coated or wax over lead plated sprinklers are available for
specially severe environments. Chrome plated sprinklers
are available for decorative purposes.
All sprinklers are individually hydrostatically tested. All
sprinklers are identified as to their fusing point by mark-
ings that appear on several of the operating parts and by
an identifying color that appears on the frame.
Sprinkler Types
Standard Upright-This deflector configuration is normal-
ly used with exposed piping installations. Water is distrib-
uted laterally and downward in a wide pattern approximat-
ing a hemisphere which is completely and uniformly filled
with water in the form of small drops or spray.
Standard Pendent -This deflector configuration is nor-
mally used where the space above the piping is limited
or where a concealed piping installation is employed.
The discharge characteristics of the standard pendent
are virtually identical to the standard upright as de-
scribed above.
Large and Small Orifice -By varying the orifice size, a
large or small orifice sprinkler is created that will distrib-
ute as much as 40% more water or 65% less water than
the normal½" (15mm) orifice sprinkler.
Conventional -This deflector configuration is used pri-
marily in those countries where the LPG installation rules
have precedence. The sprinkler is designed to distribute
a portion of its water discharge upward against the ceil-
ing with the balance downward. It may be installed in
either the upright or the pendent position. Sprinklers with
conventional deflectors are available with orifice sizes
corresponding to light, ordinary and extra-high hazard
installations.
Model G Automatic Sprinklers
Spray Upright, Spray Pendent,
And Conventional
Upright
Small Orifice Upright Conventional
Application and Installation
Standard sprinklers are used in fixed fire protection sys-
tems: Wet, Dry, Deluge or Preaction. Care must be exer-
cised that the orifice sizes, temperature ratings, deflector
styles and sprinkler spacings are in accordance with the
latest published standards of the National Fire Protection
Association or the approving authority having jurisdiction.
The sprinklers must be installed with the Reliable Model
W2 Sprinkler Wrench. Any other type of wrench may dam-
age the sprinkler.
The approvals or listings of Reliable Automatic Sprin-
klers by major approving organizations are shown in the
tabulated list provided on the back of this bulletin.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
...... s·
.....L
.....L
0
)> C (C
C se.
~ (0
· Technical Data
Sprinkler Type "K" Factor Sprinkler Approvals
Sprinkler Identification Number
(SIN) •
us Metric Height ssu SSP
Standard-Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
½" (15 mm) Standard Orifice with½" NPT (R1/2) Thread 5.62
7/16" (11 mm) Small Orifice with 1/2'' NPT (R1/2) Thread 4.24
3/a" ( 10 mm) Small Orifice with 1/2'' NPT (R1/2) Thread 2.82
5/16" (8 mm) Small Orifice with 1/2'' NPT (R1/2) Thread 1.98
17/32" (20 mm) Large Orifice with 1/2'' NPT (R¼) Thread 7.96
17/32'' (20 mm) Large Orifice with 3/4'' NPT (R3/4)Thread 8.20
20 mm XHH with 20 mm Thread 8.20
10 mm XLH with 10 mm Thread 4.10
Conventional-Installed in Upright or Pendent Position
10mm XLH with 10mm Thread 4.10
15mm Standard Orifice with (R1/2) Thread 5.62 20mm XHH with (R3/4) Thread 8.20 -_,.■--. -Maximum Sprinkler Ambient Frame !1l Classification Rating Temperature Color
OF oc OF oc
Ordinary 135 57 100 38 Black
Ordinary 165 74 100 38 Uncolored
Intermediate 212 100 150 66 White
Hiah 286 141 225 107 Blue
(ll Frame color does not apply to painted or plated sprinklers
-Use sprinkler rating as identified on operating parts.
Finishes '1,
Standard Finishes
Bronze -All Temperature Ratings
Chrome -All Temperature Ratings
White !2l -All Temperature Ratings
Only Frame and Deflector are Painted
Special Aoolication Finishes
Bright Brass Plated -Only frame, deflector and cap are plated. 135°F
(57°C), 165°F (74°C), 212°F (100°C) Temp. Rating.
Black Plated -Only frame, deflector and cap are plated. All
Polyester Coated !2x4i Temp. Ratings.
Lead Plated -Only frame and deflector are coated.
Wax-Coated !3l -165°F (74°C), 212°F (100°C) and 286°F (141°C)
Wax-Coated Over Temp. Ratings.
Lead Plated !3l -165°F (74°C) Clear Wax, 212°F (100°C) Brown
Wax.
-165°F (74°C) Clear Wax, 212°F (100°C) Brown
Wax.
(ll Other colors and finishes are available. Consult factory for details.
!2l UL listed and NYC MEA Approved only.
!3l 212°F ( 100°C) brown wax may be used on 286°F ( 141 °C)
81.0
61.0
40.6
28.5
114.7
118.2
118.2
59.1
59.1
81.0
118.2
sprinklers when maximum ambient temperatures do not exceed 150°F
(66°C). UL Listed, FM Approved, NYC MEA 258-93-E.
!4l FM Approved for R1027 only.
2 7/a" (73 mm) 1,2,3,4,5,6 R1025 R1015
27/a'' (73mm) 1 R1023 R1013
27/a''(73mm) 1, 2, R1021 R1011
2 7/a" (73 mm) 1, 5 R1022 R1012
2 7/a'' (73mm) 1, 2, R1026 R1016
2 15/16" (75 mm) 1, 2, R1027 R1017
75.4mm 3, 4, R1027 R1017
73mm 3, 4, R1024 R1014
73mm 4 R1074
73mm 3,4,6 R1075
75.4 mm 3,4 R1077
Maintenance
Model G Sprinklers should be inspected and the sprinkler
system maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove any sprinkler that has been painted ( other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation. Use only the
Model W2 Sprinkler Wrench for sprinkler removal and installa-
tion. Any other type of wrench may damage the sprinkler.
Approval Organizations
1. Underwriters Laboratories, Inc. and UL Certified for Can-
ada (cULus).
2. Factory Mutual Research Corporation
3. Loss Prevention Council
4. Pleniere Assembles
5. N.Y.C. BS&A No. 587-75-SA or
N.Y.C. MEA 258-93-E
6. CE Certificate: 1438-CPD-0054 (R1015)
1438-CPD-0053 (R1025)
1438-CPD-0052 (R1075)
1438-CPD-0056 (R1077)
Ordering Information
Specify:
1. Model G
2. Deflector
• Upright
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years.
Manufactured by
Reliabl~
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
,:;,,._ Recycled W Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 08/19 P/N 9999970005