HomeMy WebLinkAbout1940 CAMINO VIA ROBLE; ; FPC2022-0015; PermitPERMIT REPORT
Fire Permit
Print Date: 03/10/2022
Job Address:
Permit Type:
Parcel#:
Valuation:
Occupancy Group:
#of Dwelling Units:
Bedrooms:
Bathrooms:
Project Title:
1940 CAMINO VIDA ROBLE, CARLSBAD, CA 92008-6516
FIRE-Construction Commercial Work Class:
2120921300 Track#:
$0.00 Lot#:
Project#:
Plan#:
Construction Type:
Orig. Plan Check#:
Plan Check#:
Fire Alarm
(city of
Carlsbad
Permit No: FPC2022-0015
Status: Closed -Finaled
Applied: 01/25/2022
Issued: 02/08/2022
Finaled Close Out: 03/10/2022
Inspector:
Final Inspection:
Description: CAL COMP USA -SPRINKLER MONITORING SYSTEM (RESUBMITTAL FOR EXPIRED PERMIT)
Applicant:
BAY ALARM COMPANY
DAN ANDERSON
8205 RONSON RD, # STE F
SAN DIEGO, CA 92111-2014
(618) 718-0186
FEE
FIRE Sprinkler Monitoring
Total Fees: $421.00
. Fire Department
Total Payments To Date: $421.00
FPContractor:
BAY ALARM COMPANY
8205 RONSON RD, # STE F
SAN DIEGO, CA 92111-2014
(858) 586-3803
Balance Due:
1635 Faraday Avenue, Carlsbad CA 92008-7314 I 760-602-4665 I 760-602-8561 f I www.carlsbadca.gov
AMOUNT
$421.00
$0.00
Page 1 of 1
8205 Ronson Rd. Ste F
San Diego, CA 92111
(800) 470-1000
Contractor License# 880138
I. PROTECTED PREMISE
II.
CALCOMP USA
1940 CAMINO VIDA ROBLE
CARLSBAD, CA 92008
MONITORING COMPANY
Bay Alarm Company
5130 Commercial Circle
Concord, CA 94520
800-4 70-1000
California Alarm Operating License
Number: ACO28
III. EQUIPMENT SUPPLIER & INSTALLER
8205 Ronson Road, Suite F
San Diego, CA 92111 1 (800) 4 70-1000
Contractor License# 880138
i"!!!!!!!!!:.-111.1 DMP.coM o o e o Q G @DMPALARMs
Zone Expansion Modules
FEATURES
► Provides Class B zones for ► Easily mount attractive cases ► Data LED on zone expander
burglary and fire on wall or three-gang box indicates good
► Compatible with DMP Panels ► Compatible with all panel panel communication
that allow zone expansion zone types ► Durable and attractive plastic
► Suitable for mounting near ► Easy connection to four-wire or metal housing
protection devices keypad or LX-Bus™ ► Low current draw
► Connect devices using ► Proven design ensures ► Can be powered from panel
four-wire bus stability and performance or auxiliary power supply
BUILD A SYSTEM
714/715 ZONE EXPANDERS
The 714 contains four Class B burglary
zones and is suitable for use with
burglary and fire devices that are
normally opened or normally closed.
Individual zones are supervised with
1 k ohm End-of-Line (EOL) resistors and
can be programmed with any burglary or
fire zone type.
The 715 contains four Class B powered
zones and is suitable for use with
12 VDC, two-wire smoke detectors,
and non-powered fire or burglary
devices. Individual zones on the 715 are
supervised with a 3.3 k ohm EOL resistor
and can be programmed with any
burglary or fire zone type.
OPTIONAL ACCESSORIES
The standard wiring harness can be
replaced with the optional 718T Plug-in
Screw Terminal.
The enclosure can also accommodate the
719T Terminal Boards for the 714 or the
720T Terminal Boards for the 715, which
pass through the wiring of the panel's
LX-Bus. 1 K EOL resistors are included
with the 719T and 3.3 K resistors are
included with the 720T.
714/715 FEATURES
► Four protection zones on each module
► Comes with 12-conductor wire harness
► Optional 12-position screw terminal
714-8, 714-16, 715-8, AND 715-16
The expanders are housed in a model
340 locking metal enclosure suitable
for mounting in a remote location. Each
expander provides screw terminal
strips for zone inputs and data bus
connections, a two position jumper to
designate connection to the keypad bus
or the LX-Bus, and an LED to indicate
communication with the panel. Separate
zone EOL resistors are included with
each expander.
SALES APP
711 DESCRIPTION
The 711 Zone Expansion Module connects
to the panel's four-wire keypad bus or
LX-Bus and is set to an address that
determines the reporting zone number.
The 711 provides one Class B zone for the
connection of detection devices.
711 FEATURES
► Single-zone expander
► Rugged screw terminals accommodate
14-22-AWG wire
714-8/714-16 EXPANDERS ► Board fits in Radionics POPIT housing
The 714-8 Expander contains eight Class ► Easy rotary switch addressing
B zones. The 714-16 Expander contains 16
Class B zones. Both are suitable for use ms DESCRIPTION
with normally open or normally closed The 711S Zone Expansion Module is a
burglary and fire devices. Individual flying lead style, single-zone, addressable
zones are supervised with a 1 k ohm EOL expansion module that allows you to
resistor and can be programmed as any increase the number of reporting zones
zone type. available on XT30/50 and XR150/550
715-8/715-16 EXPANDERS
The 715-8 Expander contains eight Class
B powered zones. The 715-16 Expander
contains 16 Class B powered zones. Both
are suitable for use with 12 VDC two-
wire devices, such as smoke detectors
or with non-powered fire or burglary
devices. Individual zones are supervised
with a 3.3 k ohm EOL resistor and can be
programmed as any zone type.
714-8, 714-16, 715-8, AND
715-16 FEATURES
► 8 or 16 protection zones per expander
► Durable metal enclosure housing with lock and key
► Individual screw terminals accommodate 14-22 -
gauge wire for easy connection
► Suitable for mounting in a remote location
Series panels. It's ideal for smaller
applications, such as installing in a pull
station back-box or even in a recessed
contact hole behind the contact. The
modules connect to the panel is four-
wire keypad bus or LX-Bus and are set to
an address that determines the reporting
zone number. The 711S provides one Type
A Class B zone.
ier Enclosures
and Custom Fabrication
._ Drive-Alert
DUCTS, INC. Vehicle Detection Systems
Custom Desig
and fabrication , ---
800-473-0213 I info@mierproducts.comIwww.mierproducts.com
RATING:
INSTALLATION:
MARKING:
APPROVAL:
NOTE:
1135: Wireless Siren
120 VAC, 0.5 A, 60 Hz
Listing No. 7165-1157:0135
Page 2 of 2
In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
Listee's name, model number, rating and UL label.
Listed as combination fire and burglary alarm control units for use with separately listed
electrically compatible initiating and indicating devices. Refer to listee's Installation
Instructions Manual for details.
1. The Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
2. Burglary and other non-fire functions were not examined.
*Rev 04-05-19 gt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued:
Authorized By:
July 01, 2019
DA V/D CASTILLO, Program Coordinator
Fire Engineering Division
Listing Expires June 30, 2020