Series TY-FRB -2.8, 4.2, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY-FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response -standa~d cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19, 1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the ReGessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob.:.
tained when · exposed to corrosive at-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY-FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Nu,nbers
TY1131 -
TY1231 -
TY2131 -
TY2231 -
TY3131 -
Upright 2.BK, 1/2"NPT
Pendent 2.BK, 1/2"NPT
Upright 4.2K, 1/2"NPT
Pendent 4.2K, 1/2"NPT
Upright 5.6K, 1/2"NPT
JULY,2004
TY3231 -
TY4131 -
TY4231 -
Pendent 5.6K, 1/2"NPT
Upright 8.0K, 3/4"NPT
Pendent 8.0K, 3/4"NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1l2)
K = 4.2 GPM/psj1/2 (60,5 LPM/bar1l2)
K = 5.6 GPM/psj1/2 (80,6 LPM/bar1l2)
K = 8.0 GPM/psi1/2 (115,2 LPM/bar1l2)
Temperature Ratings
Refer to Table A and B
TFP171
AOo:S-OZ-45
Page 2 of 8
ESCUTCHEON
PLATE SEATING
SURFACE
2-1/4"
(57,2 mm)
7115• (11,1 mm)
NOMINAL
MAKE-IN
l
STYLE 10 or 20
RECESSED
ESCUTCHEON ssu*
DEFLECTOR
7115•
(11,1 mm)
NOMINAL
MAKE-IN
TFP171
.... ~ ... ~n1t~""t~a;,~.-./ 6
rt:::..::~--s
----4
t--,--2
3
WRENCH
FLATS iiii~ 2-3/16.
(55,6 mm)
l
SSP DEFLECTOR*
PENDENT
1 -Frame
2 -Button
3-Sealing
Assembly
2-7/8" (73,0mm) DIA __J
RECESSED PENDENT
4-Bulb
5 -Compression
Screw
6 -Deflector
7 -Bushing
FIGURE 1
7
UPRIGHT CROSS SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
** Pipe thread connections per ISO 7 /1 can be provided on
special request.
QUICK RESPONSE SERIES TY-FRB UPRIGHT {TY1131) AND PENDENT {TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16.
(55,6mm)
7/16" (11,1 mm)
NOMINAL
MAKE-IN
'
STYLE 10 or 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
ssu*
DEFLECTOR
7115•
(11,1 mm)
NOMINAL
MAKE-IN
2-3/16·
(55,6 mm)
SSP DEFLECTOR*
PENDENT
2-7/8" (73,0 mm) DIA. __J
RECESSED PENDENT
1/2" NPT**
UPRIGHT
l
CROSS SECTION
4 -Bulb 6 -Deflector 1 -Frame
2 -Button
3 -Sealing
Assembly 5 -Compression-
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
** Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT {TY2131) AND PENDENT {TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
Finishes
Sprinkler: Refer to Table A and B
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame . . . . . . . . . . . . . Bronze
Button . . . . . . . . . Brass/Copper
Sealing Assembly . . . . . . . . . .
. . . . . Beryllium Nickel w/Teflont
Bulb .............. Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . Copper/Bronze
Bushing (K=2.8) . . . . . . . Bronze
Operation _
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
.:it! ai E ~ .=
i a> 1ii O> Q) a:
c 0 a.. :J 0
~
TFP171
ESCUTCHEON
PLATE SEATING
SURFACE
2-3/16.
{55,6 mm)
7/16. {11,1 mm)
NOMINAL
MAKE-IN
I
STYLE 10 or 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
ssu*
DEFLECTOR
7/16.
{11,1 mm)
NOMINAL
MAKE-IN
~ 2-3/16·
(55,6 mm)
Page 3 of 8
SSP DEFLECTOR*
PENDENT
2-7/8" (73,0 mm) DIA. -I
RECESSED PENDENT
112• NPT**
UPRIGHT
!
CROSS SECTION
4 -Bulb 6 -Deflector 1 -Frame
2 -Button
3 -Sealing
Assembly 5 -Compression
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT {TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-5/16.
{58,7mm)
112• {12,7 mm)
NOMINAL
MAKE-IN
_J_
STYLE 30 or 40
RECESSED
ESCUTCHEON
WRENCH
FLATS
ssu*
DEFLECTOR
112·
{12,7 mm)
NOMINAL
MAKE-IN
2-114•
(57,2 mm)
2
3
SSP DEFLECTOR*
PENDENT
2-7/8" {73,0mm) DIA J
RECESSED PENDENT
3/4"NPT~
UPRIGHT CROSS SECTION
4-Bulb 6 -Deflector 1 -Frame
2 -Button
3 -Sealing
Assembly 5 -Compression
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4131) AND PENDENT {TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
Page 4 of 8
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL I CHROME I WHITE"-
LIQUID BRASS PLATED POL VESTER
135°F/57°C Orange
PENDENT 155°F/68°C Red (TY1231) 1,2,3,5
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
2.8 (TY1131) 286°F/141 °C Blue
112·
NPT 135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT
(TY1231)* 175°F/79°C Yellow
Figure 5 200°F/93°C Green 1, 2, 5
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT
(TY1231)** 175°F/79°C Yellow
Flgure6 200°F/93°C Green
135°F/57°C Orange
PENDENT 155°F/68°C Red (TY2231)
and 175°F/79°C Yellow
UPRIGHT 200°F/93°C Green
4.2 (TY2131)
286°F/141 °C Blue 112· 1, 2
NPT 135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT
(TY2231)* 175°F/79°C Yellow
Figure 7 200°F/93°C Green
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT
(TY2231)** 175°F/79°C Yellow
Figures 200°F/93°C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (112• NPn or Style 40 (3/4• NPT) 3/4• Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2• NPT) or Style 30 (3W NPn 112• Total Adjustment
Recessed Escutcheon, as applicable.
*** Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/ A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
TFP171
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. ( 40, 7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under-or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1 , 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Serles TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TFP171 Page 5 of 8
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL I CHROME WHITe** LEAD
LIQUID BRASS PLATED POLYESTER COATED
135°F/57°C Orange
PENDENT 155°F/68°C Red (TY3231) 1,2,3,4,5,6, 7 1, 2, 3, 5
and 175°Fll9°C Yellow
UPRIGHT 200°F/93°C Green
5.6 (TY3131)
286°F/141°C Blue 112·
NPT 135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT 1, 2, 4, 5 N/A
(TY3231)* 175°Fll9°C Yellow
Agure9 200°F/93°C Green
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT 1,2,3,4,5 1,2,4,5 N/A
(TY3231,-175°Fll9°C Yellow
Agure 10 200°F/93°C Green
135°F/57°C Orange
PENDENT 155°F/68°C Red (TY4231) 1,2,5
and 175°Fll9°C Yellow 1,2,3,4,5,6, 7
UPRIGHT 200°F/93°C Green
8.0 (TY4131)
286°F/141°C Blue 3W
NPT 135°F/57°C Green
RECESSED 155°F/68°C Orange PENDENT 1, 2, 4, 5 NIA (TY4231)* 175°Fll9°C Red
Figure 11 200°F/93°C Yellow
135°F/57°C Orange
RECESSED 155°F/68°C Red PENDENT 1,2,3,4,5 N/A (TY4231)** 175°Fll9°C Yellow
Figure 12 200°F/93°C Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-Ul listed, the sprinklers are UL and C-UL listed as
Corrosion Resistant Sprinklers. Where lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2• NPT) or Style 40 (3/4• NPT) 314• Total Adjustment Recessed Escutcheon, as applicable.
** Installed with Style 20 (112• NPT) or Style 30 (3/4• NPT) 112• Total Adjustment Recessed Escutcheon, as applicable.
*** Frame and Deflector only. listings and approvals apply to color (Special Order).
N/ A: Not Available
TABLES
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8 TFP171
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
2-7/8" DIA. ;i (73,0mm)
2-1/4" DIA. --:I
(57.2mm) r I
3/4" 19,1 mm
1/4" (6,4 mm)
MOUNTING
PLATE
1/8" =Im)
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA. ;i (73,0mm)
2-1/4" DIA. --j
(51.2mm) r I
1/2" 12,7 mm
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2mm)
\
~~~-I.
.;.,c.,,r;..~~=~~::.=-:i~, _j_
MOUNTING
SURFACE
CLOSURE SERIES
TY-FRB
1-5/16" (33,3 mm
13/16" (20,6 mm) CLOSURE SERIES
TY-FRB
1-5/16" 33,3 mm
1-1/16" (27,0 mm)
FIGURES RGURE6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT 2.8 K-FACTOR, 1/2 INCH NPT
5/8±1/4"
(15,9±6.4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
2-7/8" DIA. ;i (73,0 mm)
2-1/4" DIA. 7 (57,2mm) r I
SERIES
TY-FRB
FIGURE7
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1-1/4" (31,8 mm
3/4" (19,1 mm)
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA. ;i (73,0mm)
2-1/4" DIA. 7 (57,2mm) r I
1/2" (12,7 mm
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2mm)
\
~d.111~~=1
~~-t:::;:;;.:::j;~
MOUNTIN
SURFAC
CLOSURE SERIES
TY-FRB
FIGURES
1-1/4" 31,8 mm
1" (25,4 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT 4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers -before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twisVslippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFP171
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
2-7/8" DIA. ;l (73,0mm)
2-1/4" DIA. --:i
(57,2mm) r I
SERIES
TY-FRB
RGURE9
314" 19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1-1/4" (31,8 mm)
314" (19,1 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 112 INCH NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/B"DIA.11 (73,0mm)
2-1/4" DIA. -1
(57,2 mm) _J I
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
MOUNTING
SURFACE
CLOSURE SER .. l~ESa::::a::z::,ii!ba . 1-511~ l~,J
TY-FRB 13116" (20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 314 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
\
MOUNTING
SURFACE
CLOSURE
2-7/8" DIA. ;l (73,0mm)
2-1/4" DIA. --:i
(57,2mm) r I
SERIES
TY-FRB
FIGURE 10
Page 7 of 8
1/2" 12,7 mm
1/4" (6,4 mm)
MOUNTING
PLATE
1-1/4" (31,8mm)
1• (25,4mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
\
MOUNTING
SURFACE
CLOSURE
2-7/8" DIA.
(73,0mm)
2-1/4" DIA.
(57,2mm)
SERIES
TY-FRB
FIGURE 12
1/2" 12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1-5/16" 33,3 mm
1-1/16" (27,0 mm)
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 112 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 314 INCH NPT
WRENCH
RECESS
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
WRENCH RECESS
(END "A" USED FOR
112• NPT MODELS)
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
WRENCH RECESS
(END •s• USED FOR
3W NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
local requirements and/or national
codes.
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8 TFP171
P/N 57-XXX-X-XXX
I I
I MODEUSIN
TEMPERATURE
RATING
SPRINKLER
330 2.8K UPRIGHT (1/2.NPl) TY1131 135 135°F/57°C
331 2.8K PENDENT (1/2.NPT} TY1231 1 NATURAL BRASS 155 155°F/68°C
340 4.2K UPRIGHT (1/2.NPT} TY2131 4 WHITE POL VESTER 175 175°F/79°C
341 4.2K PENDENT (1/2.NPl) TY2231 3 WHITE (RAL9010)* 200 200°F/93°C
370 5.6K UPRIGHT (1/2.NPT} TY3131 9 CHROME PLATED 286 286°F/141°C
371 5.6K PENDENT (1/2.NPT} TY3231 7 LEAD COATED
390 8.0K UPRIGHT (3/4.NPl) TY4131
391 8.0K PENDENT (3/4.NPT} TY4231 * Eastern Hemisphere sales only.
TABLEC
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Li,nited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten ( 10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
OTHER WARRANTIES EXPRESS OR
IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
ffJS.E.
Ordering
Procedure
®Dflt•i}fo~ l@cal distributor for avail-
abifftsJ_indicate the tufr' product
name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2" (15 mm)
Style 10
Chrome Plated ............ PIN 56-701-9-010
White Coated ............. PIN 56-701-4-010
White RAL9010* ........... P/N 56-701-3-010
Brass Plated .............. PIN 56-701-2-010
1/2" (15 mm)
Style 20
Chrome Plated . . . . . . . . . . . . PIN 56-705-9-010
White Coated ............. PIN 56-705-4-010
White RAL9010• ........... PIN 56-705-3-010
Brass Plated . . . . . . . . . . . . . . P/N 56-705-2-01 O
3/4" (20 mm)
Style 30
Chrome Plated . . . . . . . . . . . . PIN 56-705-9-011
White Coated ............. P/N 56-705-4-011
White RAL9010• ........... P/N 56-705-3-011
Brass Plated .............. P/N 56-705-2-011
314" (20 mm)
Style 40
Chrome Plated ............ P/N 56-700-9-010
White Coated ............. P/N 56-700-4-010
White RAL9010• . . . . . . . . . . . PIN 56-700-3-010
Brass Plated .............. PIN 56-700-2-010
* Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P /N 56-850-4-001 .
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446