Loading...
HomeMy WebLinkAboutSDP 05-18A; ECR CORPORATE CENTER; WATER ANALYSIS; 2007-07-12- C4% A, 44 OQ/4 4 El Camino Real Corporate Centet4 4,',' 19 Water Analysis SDP 05-18(A) July 12, 2007 Revised: September 18, 2007 Prepared for: ECR Corporate Center, L.P. 5600 Avenida Encinas, Suite 100 Carlsbad, CA 92008 CONTACT: John C. White, President Prepared by: WF RBF CONSULTING 5050 Avenida Encinas, Suite 260 Carlsbad, CA 92008 760.476.9193 CONSULTING Contact Person: Tim Thiele, P.E. RBF iN 55-100293 ECR CORPERATE CENTER WATER MODEL DATA The project site is completely within a 550-pressure zone. Medical Building 1, has a maximum day demand of 76 Gallons Per Minute (GPM)' Medical Building II, has a maximum day demand of 42 GPM' Day Care Center, has a maximum day demand of 3.5 GPM Fire hydrant demand is 3500 GPM for the 4 hydrants within 325 ft of Medical Building I.' Fire hydrant demand is 2500 GPM for the 3 hydrants within 300 ft of Medical Building 11.' Fire hydrant demand is 2750 GPM for the 3 hydrants within 300 of the Day Care Center. ASSUMPTIONS All hydrant laterals will be 6" in diameter Water service to Medical Building I is to be 2-2" diameter pipes Water service to Medical Building II is 2" in diameter Water service to the Day Care Center is 1.5" in diameter A 2" Neptune High Performance water meter will be used for Medical Building I and II A 1.5" Neptune High Performance water meter will be used for the Day Care Center 2" Reduced pressure backflow preventer will be used in Medical Center I and II 1.5" Reduced pressure backflow preventer will be used in the Day Care Center. The elevation head from the 12" water main in the back of the site was 540 ft at the pipe to take into account losses in the system. The elevation head from the 24" water main on El Camino Real was 540 at the pipe to take into account losses in the system All fire sprinkler services will be 6" diameter There will be a 1000 GPM demand for the fire sprinkler service in Medical Bldg 1 There will be a 750 GPM demand for the fire sprinkler service in Medical Bldg II There will be a 500 GPM demand for the fire sprinkler service in Day Care Center MODELS Model 1 was based on an 8" water main, 6" fire hydrant laterals, 2-2" water services to Medical Bldg I, 2" water service to Medical Bldg II, and a 1.5" water service to the Day Care Center. Demands are 76 GPM to Medical Bldg I, 46 GPM to medical Bldg II, 3. GPM to the Day Care Center. The fire flow demand of 3500 GPM total over the 4 i e hydrants nearest to Medical Bldg 1 and a 1000 GPM fire sprinkler demand was place on the fire service for Medical Bldg I in this model. 'Fire Hydrant demands were given by the Deputy Fire Marshal of the Carlsbad Fire Department. Model 2 was based on an 8" water main 6" fire hydrant laterals, 2-2" water services to Medical Bldg I, 2" water service to Medical Bldg II, and a 1.5" water service to the Day Care Center. Demands are 76 GPM to Medical Bldg 1, 46pP_Mto medical Bldg II, 3.5 GPM to the Day Care Center. The fire flow demand of 2509PM total over th 3 f\e hydrants nearest to Medical Bldg II and a fire sprinkrZ1hiand on GPM lace on the fire service for Medical Bldg II in this model. Model 3 was based on an 8" water main, 6" fiIe hydrant laterals, 2-2" water services to Medical Bldg I, 2" water service to Medical Bldg II, and a)1.5"-water service to the Day Care Ceriter. Demands are 76 GPM to Medical Bldg I, 46 GPM to medical Bldg II, 3.5 GPM to the Day Care Center. The fire flow demand of 2750 GPM total over the .iire..hy.&ants nearest to the Day Care Center and aQQ.GPtiie sprinkler demand was place on the fire service for the Day Care Center in this model. SUMMARY OF RESULTS All 3 models were conducted with H20Map Water software and were completed using the pipe alignment received on 6/21/2007. Each of the 3 models was completed using the specifications listed above. Table 1, below, summarizes the results of the modeling analysis. Detailed results for each of the models are included in the following pages. Model Number Maximum Velocity Minimum Velocity Maximum Pressure Minimum Pressure Average Pressure at Hydrants 1 15.42 fps 0.24 fps 103.34 psi 67.50 psi 80.56 psi 2 13.63 fps .48 fps 104.53 psi 69.89 psi 86.29 psi 3 15.53 fps 0.13 fps 1107.78 psi 75.27 psi 93.36 psi Table 1 - Summary of Results 1 Fire Hydrant demands were given by the Deputy Fire Marshal of the Carlsbad Fire Department. MODEL 1 HYDQUA. RPT Page 1 Fri Aug 24 15:57:33 2007 H2OMAP Water GIS Comprehensive Analysis of Water Distribution Piping Network Version 5.0 ECR Corp Center Max. Day Demands Input Data File ................... MODEL. OUT\SCENARIO\RUN14\-INP Number of Junctions................ Number of Reservoirs............... Number of Tanks ................... Number of Pipes ................... Number of Pumps ................... Number of Valves .................. Headloss Formula .................. Hydraulic Timestep ................ Hydraulic Accuracy ................ Maximum Trials .................... Quality Analysis .................. Specific Gravity .................. Relative Kinematic Viscosity ...... Relative Chemical Diffusivity ..... Demand Multiplier ................. Total Duration .................... Reporting Criteria: All Nodes All Links Analysis began Fri Aug 24 15:57:33 2007 H:\PDATA\55100293\CALCS\WATER\ECR MAIN 54 2 0 44 0 11 Hazen-Williams 1.00 hrs 0.001000 100 None 1.00 1.00 1.00 1.65 0.00 hrs Hydraulic Status: -------------------------------------------------------------- 0:00:00: Balanced after 4 trials Total Supplied: 4621.32 gpm Total Demanded: 4621.32 gpm Total Stored: 0.00 gpm 0:00:00: Reservoir 2000 is emptying 0:00:00: Reservoir 2002 is emptying Node Results: -------------------------------------------------- Demand Head Pressure Node -------------------------------------------------- gpm ft psi 3-10 0.00 506.48 87.30 3-12 0.00 506.52 87.32 3-14 0.00 506.51 87.96 3-16 0.00 505.57 87.56 3-170 0.00 469.80 70.76 3-172 1000.07 464.54 68.48 3-18 0.00 496.00 83.41 3-182 0.00 506.76 86.99 3-184 0.00 506.76 86.99 3-186 0.00 498.76 83.52 3-188 0.00 498.76 83.52 3-2 0.00 522.72 93.47 Page 1 HYDQUA. RPT 3-20 0.00 466.64 70.69 3-22 42.08 466.42 70.59 3-24 0.00 506.51 88.40 3-26 0.00 506.51 88.83 3-30 0.00 488.80 78.77 3-32 0.00 487.26 78.11 3-34 0.00 486.13 77.83 3-36 0.00 486.13 77.83 3-38 0.00 485.66 77.63 3-4 0.00 517.76 91.32 3-40 0.00 476.29 73.57 3-42 0.00 462.29 67.50 3-44 37.95 462.11 67.43 3-46 0.00 486.13 77.83 3-48 0.00 507.41 87.70 3-50 0.00 508.54 88.63 3-52 0.00 516.00 100.09 3-54 0.00 517.40 100.70 3-56 0.00 518.49 103.34 3-58 0.00 536.07 98.39 3-6 0.00 506.97 87.08 3-60 874.99 517.10 91.04 3-62 874.99 505.82 87.02 3-64 874.99 506.53 87.32 3-66 0.00 506.51 88.40 3-68 874.99 486.39 77.73 3-70 0.00 506.81 87.01 3-72 0.00 506.76 86.99 3-74 0.00 506.73 86.97 3-76 0.00 496.23 82.43 3-78 3.30 496.22 82.42 3-8 0.00 506.37 87.26 3-80 0.00 486.13 77.83 3-82 0.00 485.67 77.64 3-84 0.00 476.30 73.58 3-86 0.00 462.30 67.51 3-88 37.95 462.00 67.38 3-90 0.00 498.51 84.50 3-92 0.00 498.51 84.93 3-94 0.00 506.51 88.40 3-96 0.00 484.51 77.13 3-98 0.00 470.01 70.85 2000 -1330.73 540.00 0.00 2002 -3290.59 540.00 0.00 Link Results: Flow velocity Headloss Link --------------------------------------------------- gpm fps ft P-i 1330.73 3.77 1.08 P-101 -42.07 0.27 0.01 P-li 413.66 2.64 0.04 P-13 413.66 2.64 0.10 P-17 42.08 4.30 0.94 P-19 42.08 4.30 0.22 P-21 0.00 0.00 0.00 P-23 0.00 0.00 0.00 P-25 -461.34 2.94 0.38 P-27 -2415.59 15.42 10.78 P-29 -3290.59 21.00 4.96 Page 2 Reservoir Reservoir HYDQUA. RPT P-3 1330.73 8.49 1.40 P-31 -3290.59 21.00 13.35 P-33 874.99 9.93 0.66 P-35 1950.96 12.45 1.54 P-37 1075.96 6.87 1.13 P-39 75.90 0.48 0.00 P-41 0.00 0.00 0.00 P-43 37.95 3.88 0.46 P-45 37.95 3.88 0.18 P-47 874.99 9.93 0.87 P-49 874.99 9.93 0.88 P-s 1330.73 8.49 7.46 P-Si 874.99 9.93 0.55 P-53 1950.96 12.45 18.17 P-57 -464.64 2.97 0.16 P-59 3.30 0.60 0.05 P-61 3.30 0.60 0.01 P-63 1330.73 3.77 21.51 P-65 3290.59 2.33 3.93 P-67 37.95 0.24 0.00 P-69 37.95 3.88 0.45 P-73 37.95 3.88 0.30 P-75 0.00 0.00 0.00 P-77 0.00 0.00 0.00 P-79 1000.07 .11.35 1.62 P-81 1000.07 11.35 0.21 P-83 1000.07 11.35 5.26 P-9 455.73 2.91 0.89 P-93 0.00 0.00 0.00 P-97 0.00 0.00 0.00 1000 37.95 1.72 9.37 GPVFLV 1002 37.95 3.88 14.00 GPVFLV 1004 3.30 0.60 0.03 GPVFLV 1006 3.30 0.60 10.49 GPVFLV 1008 42.08 4.30 9.57 GPVFLV 1010 42.08 2.75 29.36 GPVFLV 1012 37.95 3.88 9.37 GPVFLV 1014 37.95 3.88 14.00 GPVFLV 1016 0.00 0.00 8.00 GPVFLV 1018 1000.07 11.35 14.50 GPVFLV 1022 0.00 0.00 8.00 GPVFLV Analysis ended Fri Aug 24 15:57:33 2007 Page 3 MODEL 2 HYDQUA. RPT Page 1 Fri Aug 24 15:21:04 2007 H20MAP Water GIS Comprehensive Analysis of Water Distribution Piping Network Version 5.0 ECR Corp Center Max. Day Demands Input Data File ................... MODEL . OUT\SCENARIO\RUN14\-INP Number of Junctions ................ Number of Reservoirs ............... Number of Tanks ................... Number of Pipes ................... Number of Pumps ................... Number of valves .................. Headloss Formula .................. Hydraulic Timestep ................ Hydraulic Accuracy ................ Maximum Trials .................... Quality Analysis .................. Specific Gravity .................. Relative Kinematic Viscosity ...... Relative Chemical Diffusivity ..... Demand Multiplier .................. Total Duration .................... Reporting Criteria: All Nodes All Links Analysis began Fri Aug 24 15:21:04 2007 H:\PDATA\55100293\CALCS\WATER\ECR MAIN 54 2 0 44 0 11 Hazen-Wi lii ams 1.00 hrs 0.001000 100 None 1.00 1.00 1.00 1.65 0.00 hrs Hydraulic Status: ----------------------------------------------------------------------- 0:00:00: Balanced after 4 trials Total Supplied: 3371.44 gpm Total Demanded: 3371.45 gpm Total Stored: 0.00 gpm 0:00:00: Reservoir 2000 is emptying 0:00:00: Reservoir 2002 is emptying Node Results: --------------------------------------------------- Demand Head Pressure Node --------------------------------------------------- gpm ft psi J-10 0.00 511.14 89.32 3-12 0.00 510.86 89.20 J-14 0.00 504.89 87.26 J-16 0.00 503.95 86.86 J-170 0.00 513.38 89.64 J-172 0.00 513.38 89.64 J-18 0.00 494.38 82.71 J-182 0.00 518.00 91.86 J-184 0.00 518.00 91.86 J-186 0.00 510.00 88.39 J-188 0.00 510.00 88.39 J-2 0.00 532.24 97.60 Page 1 HYDQUA. RPT 3-20 0.00 465.02 69.99 3-22 42.08 464.80 69.89 3-24 0.00 502.55 86.68 3-26 0.00 499.89 85.96 3-30 0.00 521.39 92.89 J-32 0.00 521.38 92.89 3-34 0.00 521.38 93.11 3-36 0.00 521.38 93.11 3-38 0.00 520.91 92.91 3-4 0.00 530.01 96.63 :j-40 0.00 511.54 88.84 3-42 0.00 497.54 82.78 3-44 37.95 497.36 82.70 3-46 0.00 521.38 93.11 3-48 0.00 511.57 89.51 3-50 0.00 512.56 90.37 3-52 0.00 519.06 101.42 3-54 0.00 520.29 101.95 3-56 0.00 521.23 104.53 3-58 0.00 538.24 99.33 3-6 0.00 521.43 93.35 3-60 0.00 530.01 96.63 3-62 833.41 511.42 89.44 3-64 833.41 510.77 89.16 3-66 833.41 501.65 86.29 3-68 0.00 521.38 92.89 3-70 0.00 518.85 92.23 3-72 0.00 518.80 92.21 -74 0.00 518.77 92.19 3-76 0.00 508.27 87.64 3-78 3.30 508.26 87.64 3-8 0.00 511.92 89.66 3-80 0.00 521.38 93.11 3-82 0.00 520.92 92.91 3-84 0.00 511.55 88.85 3-86 0.00 497.55 82.78 3-88 37.95 497.25 82.65 3-90 749.92 483.27 77.90 3-92 0.00 484.23 78.74 3-94 0.00 497.89 84.66 3-96 0.00 521.38 93.11 3-98 0.00 513.38 89.64 2000 -1236.13 540.00 0.00 Reservoir 2002 -2135.31 540.00 0.00 Reservoir Link Results: Flow velocity Headloss Link --------------------------------------------------- gpm fps ft P-i 1236.13 3.51 0.95 P-101 -1625.42 10.37 5.97 P-il -1222.70 7.80 0.28 P-13 -1222.70 7.80 0.78 P-17 42.08 4.30 0.94 P-19 42.08 4.30 0.22 P-21 1583.34 10.11 2.33 P-23 749.92 8.51 2.66 P-25 -2056.12 13.12 6.07 P-27 -2135.31 13.63 8.58 Page 2 HYDQUA. RPT P-29 -2135.31 13.63 2.23 1236.13 7.89 1.22 P-31 -2135.31 13.63 5.99 P-33 0.00 0.00 0.00 P-35 75.90 0.48 0.00 P-37 75.90 0.48 0.01 P-39 75.90 0.48 0.00 P-43 37.95 3.88 0.46 P-45 37.95 3.88 0.18 P-47 0.00 0.00 0.00 P-49 833.41 9.46 0.80 p-s 1236.13 7.89 6.51 P-Si 833.41 9.46 0.50 P-53 75.90 0.48 0.04 P-57 -2059.42 13.14 2.58 P-59 3.30 0.60 0.05 P-61 3.30 0.60 0.01 P-63 1236.13 3.51 18.77 P-65 2135.31 1.51 1.76 P-67 37.95 0.24 0.00 P-69 37.95 3.88 0.45 P-73 37.95 3.88 0.30 P-75 749.92 8.51 2.00 P-77 749.92 8.51 0.95 P-79 0.00 0.00 0.00 P-81 0.00 0.00 0.00 P-83 0.00 0.00 0.00 P-9 402.71 2.57 0.71 P-93 0.00 0.00 0.00 P-97 0.00 0.00 0.00 1000 37.95 1.72 9.37 GPVFLV 1002 37.95 3.88 14.00 GPVFLV 1004 3.30 0.60 0.03 GPVFLV 1006 3.30 0.60 10.49 GPVFLV 1008 42.08 4.30 9.57 GPVFLV 1010 42.08 2.75 29.36 GPVFLV 1012 37.95 3.88 9.37 GPVFLV 1014 37.95 3.88 14.00 GPVFLV 1016 749.92 8.51 13.67 GPVFLV 1018 0.00 0.00 8.00 GPVFLV 1022 0.00 0.00 8.00 GPVFLV Page 3 MODEL'3 HYDQUA.RPT H2OMAP Water GIS Comprehensive Analysis of Water Distribution Piping Network Version 5.0 ECR Corp Center Max. Day Demands Input Data File ................... MODEL . OuT\SCENARIO\RuN14\-INP Number of Junctions................ Number of Reservoirs............... Number of Tanks ................... Number of Pipes ................... Number of Pumps ................... Number of valves .................. Headloss Formula .................. Hydraulic Timestep ................ Hydraulic Accuracy ................ Maximum Trials .................... Quality Analysis .................. Specific Gravity .................. Relative Kinematic Viscosity ...... Relative Chemical Diffusivity ..... Demand Multiplier ................. Total Duration .................... Reporting Criteria: All Nodes All Links Analysis began Fri Aug 24 15:26:31 2007 Hydraulic Status: 0:00:00: Balanced after 4 trials Total Supplied: 3371.61 gpm Total Demanded: 3371.61 gpm Total Stored: 0.00 gpm 0:00:00: Reservoir 2000 is emptying 0:00:00: Reservoir 2002 is emptying Node Results: H:\PDATA\55100293\CALCS\WATER\ECR MAIN 54 2 0 44 0 11 Hazen-Williams 1.00 hrs 0.001000 100 None 1.00 1.00 1.00 1.65 0.00 hrs --------------------------------------------------- Demand Head Pressure Node --------------------------------------------------- gpm ft psi 1-10 0.00 519.54 92.96 J-12 0.00 519.54 92.96 3-14 0.00 517.29 92.64 J-16 0.00 516.36 92.23 J-170 0.00 514.67 90.20 J-172 0.00 514.67 90.20 3-18 0.00 506.78 88.08 1-182 0.00 520.96 93.14 J-184 0.00 520.31 92.86 J-186 0.00 507.47 87.30 3-188 500.11 507.30 87.22 3-2 0.00 530.12 96.68 J-20 0.00 477.42 75.36 Page 1 HYDQUA. RPT 3-22 42.08 477.20 75.27 3-24 0.00 516.44 92.70 3-26 0.00 516.44 93.14 3-30 0.00 522.69 93.46 3-32 0.00 522.68 93.45 3-34 0.00 522.67 93.67 3-36 0.00 522.67 93.67 3-38 0.00 522.21 93.47 3-4 0.00 527.28 95.45 3-40 0.00 512.84 89.41 3-42 0.00 498.84 83.34 3-44 37.95 498.66 83.26 3-46 0.00 522.67 93.67 3-48 0.00 522.93 94.43 3-50 0.00 523.53 95.12 3-52 0.00 527.43 105.05 3-54 0.00 528.17 105.36 3-56 0.00 528.73 107.78 3-58 0.00 537.75 99.12 3-6 0.00 522.73 93.91 3-60 916.74 526.56 95.14 3-62 916.74 518.94 92.70 3-64 0.00 522.93 94.43 3-66 916.74 515.37 92.24 3-68 0.00 522.68 93.45 3-70 0.00 521.40 93.33 3-72 0.00 521.35 93.31 -74 0.00 521.31 93.30 3-76 0.00 510.82 88.75 3-78 3.30 510.81 88.74 3-8 0.00 519.54 92.96 3-80 0.00 522.67 93.67 3-82 0.00 522.22 93.47 3-84 0.00 512.85 89.41 3-86 0.00 498.85 83.35 3-88 37.95 498.55 83.22 3-90 0.00 508.44 88.80 3-92 0.00 508.44 89.24 3-94 0.00 516.44 92.70 3-96 0.00 522.67 93.67 3-98 0.00 514.67 90.20 2000 -938.43 540.00 0.00 2002 -2433.18 540.00 0.00 Link Results: Flow velocity Headloss Link --------------------------------------------------- gpm fps ft p-i 938.43 2.66 0.57 P-101 -958.81 6.12 2.25 p-li -20.38 0.13 0.00 P-13 -20.38 0.13 0.00 P-17 42.08 4.30 0.94 P-19 42.08 4.30 0.22 P-21 916.74 5.85 0.85 P-23 0.00 0.00 0.00 P-25 -937.12 5.98 1.42 P-27 -1516.44 9.68 4.55 P-29 -2433.18 15.53 2.84 P-3 938.43 5.99 0.73 Page 2 Reservoir Reservoir HYDQUA. RPT P-31 -2433.18 15.53 7.63 P-33 916.74 10.40 0.72 P-35 75.90 0.48 0.00 P-37 75.90 0.48 0.01 P-39 75.90 0.48 0.00 P-41 0.00 0.00 0.00 P-43 37.95 3.88 0.46 P-45 37.95 3.88 0.18 P-47 0.00 0.00 0.00 P-49 0.00 0.00 0.00 P-s 938.43 5.99 3.91 P-Si 916.74 10.40 0.60 P-53 75.90 0.48 0.04 P-57 -1440.54 9.19 1.33 P-59 3.30 0.60 0.05 P-61 3.30 0.60 0.01 P-63 938.43 2.66 11.27 P-65 2433.18 1.73 2.25 P-67 37.95 0.24 0.00 P-69 37.95 3.88 0.45 P-73 37.95 3.88 0.30 P-75 0.00 0.00 0.00 P-77 0.00 0.00 0.00 P-79 0.00 0.00 0.00 P-81 0.00 0.00 0.00 P-83 0.00 0.00 0.00 P-9 938.43 5.99 3.39 P-93 500.11 5.67 0.65 P-97 500.11 5.67 0.17 1000 37.95 1.72 9.37 GPVFLV 1002 37.95 3.88 14.00 GPVFLV 1004 3.30 0.60 0.03 GPVFLV 1006 3.30 0.60 10.49 GPVFLV 1008 42.08 4.30 9.57 GPVFLV 1010 42.08 2.75 29.36 GPVFLV 1012 37.95 3.88 9.37 GPVFLV 1014 37.95 3.88 14.00 GPVFLV 1016 0.00 0.00 8.00 GPVFLV 1018 0.00 0.00 8.00 GPVFLV 1022 500.11 5.67 12.83 GPVFLV Page 3