HomeMy WebLinkAbout6128 INNOVATION WY; ; AS130217; Permit7/28/22, 3:01 PM AS 130217 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address:
6128 INNOVATION
WY
Permit Type: SPRINK
Parcel No: 2132621301
Lot#: 0
Reference No.:
Permit No: AS130217
Status: ISSUED
Applied 12/10/2013
Approved: 12/13/2013
Issued: 12/13/2013
PC #: Inspector:
Project Title: LABRUM WEALTH Tl Tl INSTALL NEW TENANT PIPING AND
(29) SPRINKLERS. 1627 SF
Applicant: Owner:
INDUSTRIAL FIRE SPRINKLER CO INC
3845 IMPERIAL AV
SAN DIEGO CA
619-266-6030 619-266-6035
Fees($) Add'I Fees ($)
268 0
about:blank
LABRUM CAPITAL ADVISORS L L C
5650 EL CAMINO REAL #230
CARLSBAD CA
Total($) Balance($)
268 0
1 /1
.,
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
FIRE SPRINKLER CORPORATION
UPRIGHT• PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL ·-<·
DESCRIPTION AND OPERATION
CONVENTIONAL (OLD STYLE)
The Globe Quick Response GL Series Sprinklers are a low profile
yet durable design which utilizes a 3mm frangible glass ampule as the
thermosensitive element. This provides sprinkler operation approxi-
mately six times faster than ordinary sprinklers. While the Quick
Response Sprinkler provides an aesthetically pleasing appearance, it
can be installed wherever standard spray sprinklers are specified when
allowed by the applicable standards. It offers the additional feature of
greatly increased safety to life and is available in various styles, orifices,
temperature ratings and finishes to meet many varying design require-
ments. Quick Response Sprinklers should be used advisedly and under
the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains
a precisely measured amount of fluid. When heat is absorbed, the liquid
within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure within the ampule exceeds
the strength of the glass causing the glass to shatter. This results in
water discharge which is distributed in an approved pattern depending
upon the deflector style used.
The sprinkler and escutcheon are not factory assembled. As-
sembly is done in the field.
TECHNICAL DATA
• See reverse side for Approvals and Specifications.
QUICK RESPONSE
UPRIGHT CONVENTIONAL
QUICK RESPONSE
PENDENT VERTICAL
SIDEWALL
• Temperature Ratings -135°F (57°C), 155°F (68°C), 175°F (79°C),
200°F (93°C), 286°F (141 °C)
• Water Working Pressure Rating -175 psi (12 Bars)
• Factory tested hydrostatically to 500 psi (34 Bars)
• Maximum low temperature glass bulb rating is -67°F (-55°C)
• Frame -bronze • Deflector -brass • Screw -brass
• Bulb seat -copper • Spring -nickel alloy • Seal -teflon
• Bulb -glass with alcohol based solution, 3mm size QUICK RESPONSE
HORIZONTAL SIDEWALL
• SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES
ORDINARY 135°F/155°F 57°C/68°c
INTERMEDIATE 175°F/200°F 79°C/93°C
HIGH 286°F 141°c \
4077 AIRPARKDRIVE, STANDISH, MICHIGAN 48658
DECEMBER 2006 A-20
BULB
COLOR
ORANGE/RED
YELLOW/GREEN
BLUE
N.F.P.A. MAXIMUM
CEILING TEMPERATURE
100°F 38°C
150°F 66°C
.225°F 107°C
989-846-4583 • FAX 989-846-9231
BULLETIN GL5615, REV. #6
AS130217
QUICK RESPONSE
AUTOMATIC SPRINKLERS
GL SERIES
UPRIGHT • PENDENT • VERTICAL SIDEWALL
HORIZONTAL SIDEWALL • CONVENTIONA L (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH 1 FINISHES
2.8 (39 metric) 1/2" NPT 2 1/4" (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Satin Chrome 2
Bright Chrome
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 _ cm) White Polyester 3
7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Black Polyester 3
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Lead Coated 2
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 1 HORIZONTAL SIDEWALL IS 2 9/16".
STYLE SIN K 135°F
MODEL FACTOR s1°c
GL2815 2.8 X
GL4215 4.2 X
UPRIGHT GL5615 5.6 X
GL8115 7.8* X
GL8118 8.1 X
GL2801 2.8 X
GL4201 4.2 X
PENDENT GL5601 5.6 X
GL8101 7.8* X
GL8106 8.1 X
VERTICAL GL5632 5.6 X
SIDEWALLt GL8133 8.1 X
GL2826 2.8 X
HORIZONTAL GL4226 4.2 X
SIDEWALL§ GL5626 5.6 X
GL8127 8.1 X
CONVENTIONAL GL5624 5.6 X
(OLD STYLE) GL8125 8.1 X
2 FINISHES AVAILABLE ON SPECIAL ORDER
3 AVAILABLE AS cULus LISTED CORROSION APPROVALS RESISTANT WHEN SPECIFIED ON ORDER
155°F 175°F 200°F 286°F NYC -DOB
68°C 1s0c 93°c 141°c cULus F.M. LPC CE MEA 101-92-E
X X X X X -----X
X X X X X ----X
X X X X X X X X X
X X X X X X ---X
X X X X X X X X X
X X X X X ----X
X X X X X -----X
X X X X X X X X X
X X X X X X --X
X X X X X X X X X
X X X X X X ----
X X X X X -------
X X X X X ------X
X X X X X -----X
X X X X X X ----X
X X X X X --------
X X X X ------X X --
X X X X ---X X -
§ HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6".
t VERTICAL SIDEWALL SPRINKLER cULus LISTED FOR LIGHT HAZARD ONLY.
ORDERING INFORMATION
SPECIFY
• Quantity • Model Number • Style
• Orifice • Thread Sizes • Temperature
• Finishes desired
• Quantity -Wrenches -P/N 325390 (1/2");
P/N 312366 (LO.)
FIRE SPRINKLER CORPORATION
DECEMBER 2006
PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
*1/2" NPT.
GLOBE!SJ PRODUCT WA RRANTY
Globe agrees to repair or replace any of its own
manufactured products found to be defective in mate-
rial or workmanship for a period of one year from date
of shipment.
For specific details of our warranty please refer to
Price List Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkler.com
PRINTED U.S.A. BULLETIN GL5615, REV. #6
RECESSED ESCUTCHEONS
AND COVER PLATES
FIRE SPRINKLER co:RPORATION
TO MEET
IBC-ASCE/SEI 7 CODES FOR
SEISMIC AREAS C, D, & E
RECESSED ESCUTCHEONS
2 PC RECESSED
1 /2" Adjustable
• Finish/Part No. 1/2" NPT
Chrome: 326201
White: 326203-W
/4" tustable
• Finish/Part No. 1/2" NPT
~hmme: 326170
W ite-326172-W
Finish/Part No. 3/4" NPT
Chrome: 326208
White: 326210-W
Finish/Part No. 3/4" NPT
Chrome: 326177
White: 326179-W
1/2" Adjustable Recessed Model Numbers
• cULus Approved: 2810,4110,4210,4230,4231,
4234,4710,5628,5630,5631,8101,8107,8128,8129,
8151 & 8174
.cULUs & FM Approved: 5601,8106, 8156 & 5635
3/4" Adjustable Recessed Model Numbers Seismic
• cULus Approved: 2801,2826,2851,2870,4201,4226,
4231,4251,4270,5601,5602,5626,5628,5635,5636,5641,
5642,5652,5670,5680,5685,5686,8101,8102,8152,8106,
8107,8109,8127,8128,8129,8135,8141,8157,8159,8171,
8174,8179,8185
•cULus & FM Approved: 5651, 8156, 8151 & 5679
• FOR FULL DESCRIPTIONS SEE PAGES: A-24-EQ,
A-41-EQ, A-55-EQ, A-67-EQ, A-76-EQ & A-90-EQ
CONCEALED COVER PLATES
For "The Inch" Quick Response GL5606&
Standard Response GL5653
• Finish/Part No. 135°
Chrome: 332821
White: 332822
• Finish/Part No. 155°
Chrome: 332827
White: 332828
• cULus Approved: GL5653 -135°F (57°C) with plate 135°F
(57°C); 155°F (68°C) with plate 135°F (57°C); 155°F (68°C)
with plate (68°C); 175°F (79°C) with plate 155°F (68°C); 200°F
(93°C) with plate 155°F (68°C)
OPTIONAL IBC SEISMIC
RECESSED ESCUTCHEON
OPTIONAL
4 1/2" diameter
WHITE ADJUSTABLE
CONCEALED COVER PLATE
• FOR FULL DESCRIPTIONS SEE PAGES: A-38-EQ, & A-69-EQ
MAY 2009 BULLETIN: EQ ESCUTCHEON B-3
TO
ATT
STREET
CI1Y
PHONE
INDUSTRIAL
FIRE SPRINKLER CO., INC.
3845 IMPERIAL AVE., SAN DIEGO, CA, 92113
C-16 558084
Phone (619) 266-6030 Fax (619) 266-6035
Carlsbad Fire Department
I STATE I I ZIP I I FAX I
GENTLEMEN:
WE ARE SENDING YOU {
181 HEREWITH 0 UNDER SEPARATE COVER VIA
0 PRELIM. DRAWINGS 181 PRINTS 0 APPROVED PLANS
DATE 12-4-13 I JOB# I 13-?so
JOB Labrum Wealth TI-Bressi Ranch
,,
STREET
CITY I STATE I I ZIP I
PHONE I FAX I
} THE FOLLOWING ITEMS:
0 SAMPLES
181 MATERIAL CUT SHEETS 0 CALCULATIONS 0 SAFETY DATA SHEETS
0 COPY OF LETTER
0 OTHER:
QUANTITY SHEETS DESCRIPTION
3 1 Bressi TI Piping Plan (sheet 1 of 1)
1 3 Material cut sheets (Globe Quick Response sprinklers, Globe seismic escutcheon)
THESE ARE TRANSMITTED:
181 FOR APPROVAL . 0 FOR YOUR USE O AS REQUESTED 0 FOR REVIEW AND COMMENT
0 OTHER 0 DISTRIBUTION TO ARCHITECT O DISTRIBUTION TO MEP TRADES
REMARKS:
CC: FROM: Kira Sandage
SIGNED: ______________ _
IF ENCLOSURES ARE OTHER THAN INDICATED,
PLEASE CONTACT OUR OFFICE AT ONCE.
__ --{ Deleted:
AS130217