HomeMy WebLinkAbout6112 INNOVATION WAY; ; AS130127; Permit7/28/22, 12:56 PM AS130127 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address:
6112 INNOVATION
WY
Permit Type: SPRINK
Parcel No: 2132621321
Lot#: 0
Reference No.:
Permit No: AS130127
Status: APPROVED
Applied 7/30/2013
Approved : 7 /31/2013
Issued: 7/31 /2013
PC #: Inspector:
Project Title: CAMBRIDGE T.I. INSTALL NEW TENANT PIPING AND
SPRINKLERS . LIGHT HAZARD OCCUPANCY WITH SPACING
FOR NEW OFFICE Tl.
Applicant: Owner:
INDUSTRIAL FIRE SPRINKLER CO INC
3845 IMPERIAL AV
SAN DIEGO CA
619-266-6030 619-266-6035
about:blank
PALOMAR AIRPORT ROAD LLC
C/O RYAN CO US INC/M JINDRA
50 S 10TH ST #300
MINNEAPOLIS MN
1/1
.
Contractor's Material and Test Certificate for Aboveground Piping
AS\~t21-
PROCEDURE
Upon completion of work, inspection and tests shall be made by the contractor's representative and witnessed by an owner's
representative. All defects shall be corrected and system left in service before contractor's personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners, and contractor. It is understood the
owner's representative's signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving
aulhoritv's requirements or local ordinances.
Property name: Date 0 A-111 n ,-; C> c-. ti -r. ( -J'f.1 ·-·~ l .. "'2,c/3
Address: (!, fe(j;j{!,fll) I/ l / -z._ I 11/ /VO V ~ J-.t..:> ,,-, VVAt,f -+ l-J?l
Accepted by approving authorities (names): ' 0 kr J,.-5> 8 ,4-0 F-iL€ f}eyT
Address: P ,,tht.-14-o • .a.<, 1 iv~
Plans Installation conforms to accepted plans ' ~YES □ NO
Equipment used is approved ~ES □ NO
If no, explain deviations
Has person in charge of fire equipment been instructed as [lV'YES □ NO
To location of control valves and care and maintenance
Of this new equipment?
If no, explain
Instructions Have copies of the following been left on the premises? ii ~ES □ NO
I. System components instruction YES □ NO
2. Care and maintenance instructions ~ES D NO
3. NFPA#25 YES □ NO
Location of Supplies buildings:
system
YEAR OF ORIFICE TEMPERATURE
MAKE MODEL MANUFACTURER SIZE QUANTITY RATING
C:;; l,,n tl P /-. 1 .:::,/,,, 0 I ~ '-'17 1 /,., --7_ "3 IS,:;,
SPRINKLERS 0
0
PIPE AND Type of pipe Sched 10/40
FITllNGS Type of fittings Ductile/Cast iron threaded Grooved
MAXIMUM llME TO OPERATE
Al.ARM VALVE AlARM DEVICE --THROUGH TEST CONNECTION
OR FLOW TYPE MAKE (MODEL _/ MINUTES SECONDS
INDICATOR VANE ( VSR-SF __,) 0 45
p ... fr~/1--
HYDROSTATIC: Hydrostatic tests shall be made al not less than 200 psi (13.6 bar) for 2 hours or 50 psi (3.4 bar) above static pressure
TEST in excess of 150 psi (10.2 bar) for 2 hours. Differential dry-pipe valve clappers shall be left open during the test to prevent damage. All
DESCRIPTION aboveground piping leakage shall be stopped. 9-13 -2-0 /3
HYDROSTATIC TEST: ALL PIPING TESTED AT 200 PSI FOR 2 HRS
TESTS lF NO EXPLAIN '\ 1.f >
BELL TEST: ALL BELU TESTED THRU INSPECTORS TEST.
IF NO EXPLAIN L,f e>
HYDRAULIC NAMEPLATE PROVID~· ~ IF NO EXPLAIN:
DATA ~ YES ·, □ NO
REMARKS DATE LEFT IN SERVICE WITT{ ALL CONTROL VALVES OPEN I U -71--zo /;>
____ ,,
,,,,.-::.
NAME OF SPRINKLER CONTRACTOR:<JNDUSTRIAL FIRE SPRINKLER CO. INC. 619-260-ou.>u _/
TESTS WITNESSED BY
FOR ~RTY OW~NED) TITLE: DATE:
SIGNATURES /d .> ~A-V f · JO -3/-/-'j
FOR-SPRINKLER CONTRACTOR (SIGNED) TITLE: I DATE:
ADDITIONAL EXPLANATIONS AND NOTES: