HomeMy WebLinkAboutCUP 2017-0008; OAKMONT OF CARLSBAD; OAKMONT SENIOR LIVING PROJECT WATER STUDY; 2019-08-23. RECORD COPY OLA-(4, Ia-I-t Initial Date OAKMONT SENIOR LIVING PROJECT WATER STUDY CITY OF CARLSBAD CUP 2017-0008 GR 2019-0013 DWG 517-4A August 23, 2019 Prepared by: Dexter Wilson Engineering, Inc. 2234 Faraday Avenue Carlsbad, CA 92008 760-438-4422 JobNo. 528-039 DEXTER WILSON ENGINEERING, INC. DEXTER S. WILSON, P.E. ANDREW M. OVEN, P.E. STEPHEN M. NIELSEN, P.E. 0 NATALIE J. FRASCHETrI, P.E. STEVEN .i: HENDERSON, P.E. August 23, 2019 528.039 Affiance Land Planning & Engineering, Inc. 2248 Faraday Avenue Carlsbad, CA 92008 Attention: Jason Vroom, P.E., Vice President Subject: Water Study for the Oakmont Senior Living Project in the City of Carlsbad This report will address aspects of the domestic water, private fire protection, and recycled water supply systems for the Oakmont. Senior Living project. These are: Sizing of the domestic water system service lateral, meter, backflow preventer, and onsite private distribution system. Sizing of the fire protection system service laterals, detector check backflow preventers, and onsite private fire protection water system to ensure that the onsite private fire hydrants can deliver the necessary fire hydrant flow at. greater than 20 psi residual pressure. 0 Sizing of the three fire sprinkler service laterals serving the proposed buildings comprising the Oakmont Senior Living project. The fire sprinkler laterals will be connected to the private onsite fire protection system piping outlined in Item 2 above. . 0 2234 FARADAY AVENUE • CARLSBAD, CA 92008 . e (760) 438-4422 • FAX (760) 438-0173 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems 4. Sizing of the recycled water system service lateral, meter, and backflow preventer. The Oakmont Senior Living project is comprised of three buildings: the Marketing Building having four dwelling units, the Assisted and Independent Living Building (Independent Living Building) having 95 units, and the Memory Care Building having 52 units. The project has a total of 151 dwelling units plus ancillary facilities as expected for senior care/assisted living housing. The project is on approximately 6.4 acres located in the eastern portion of the City of Carlsbad. The project is located northeast of the intersection of Faraday Avenue and El Fuerte Street. Access to the project will be from Faraday Avenue. Private streets and drives will provide access throughout the project. Figure 1 presents a vicinity map of the project. Water System Overview The domestic and fire protection system laterals for the Oakmont Senior Living project will be connected to the existing 16-in6h 550 Pressure Zone public water system piping in Faraday Avenue fronting the project site on its southern boundary. The domestic system will have one 6-inch water service lateral connection.: The fire protection system will have two, 12-inch connections. A recycled water system overview is provided later in this report. Based on finished floor elevations on the project site ranging from 254 feet to 261 feet, the maximum static pressure from the 550 Pressure Zone will be 128 psi; Pressure regulators will be required on all the building services to maintain building pressures below 80 psi in accordance with the California Plumbing Code. DEXTER WILSON ENGINEERING, INC. PAGE 2 7 i NO SCALE PROJECT LOCATION LIF L FARAJ 1WAP I wy I Tf 10 0 10 Q z 0 4: 0 0 -J I a) ro 0 co I VICINITY MAP DEXTER WILSON ENGINEERING, INC CONSULTING ENGINEERS 780 438 4422 OAKMONT OF CARLSBAD Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems Public System Pressure The proposed project will be served by the Carlsbad Municipal Water District (CMWD). The available hydraulic grade line for the 550 Pressure Zone supplying domestic water for the Oakmont Senior Li',ing project is set at 550 feet HGL at the intersection of Palomar Airport Road and El Camino Real. At this intersection an existing pressure reducing station regulates the 700 Pressure Zone in Palomar Airport Road down to the 550 Pressure Zone in El Camino Real. Additional data which provides available pressure in the public water system adjacent to the Oakmont Senior Living project. is a fire flow analysis prepared by the City of Carlsbad. This Water Availability Form identifies a flow and pressure at an existing fire hydrant on the existing public water system. This fire flow analysis is provided in Appendix A. The Water Availability Form, dated August 9, 2019, indicates a residual pressure of 106 psi for a flow of 4,025 gpm at the hydrant near the project's southeast corner on Faraday Avenue. Project Water Demand The water demand for the Oakmont Senior Living project is estimated based on the building square footage instead of using the number of living units. This is done to capture the ancillary water uses for this type of a living facility which differs from a typical apartment or multi-family residential building. From the City of Carlsbad Engineering Standards, Volume 2, Potable and Recycled Water Standards, 2016 Edition, Section 3.2.1.B, the water demand factor for average daily flow is 2,300 gpdi10,000 SF. The square footage of the three buildings within the Oakmont Senior Living project was obtained from the architectural plans. The following summarizes each building's total area which includes the garage space where applicable. Assisted and Independent Living Building 160,823 SF Memory Care Building 63,670 SF Marketing Building 5,338 SF TOTAL S . 229,831 SF DEXTER WILSON ENGINEERING. INC. . PAGE 4 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems The Oakmont Senior Living project water demand is calculated as: (229,831 SF -- 10,000 SF) x 2,300 gpdl10,000 SF = 52,861.gpd Average Day Maximum Day Demand is 1.65 times Average = 87,221 gpd Maximum Day Peak Hour Demand is 2.9 tines Average = 153,297 gpd Peak Hour Domestic Demands Domestic water demands for the project were calculated based on Water Fixture Units (WFUs). The total number of WFUs in the project was estimated by counting the individual water fixtures on the preliminary architectural floor plans. The preliminary architectural floor plans were provided by the project architect via Alliance Land Planning and Engineering, Inc. After floor plans for the project are finalized, the project's water fixture unit count will need to be verified. Using the preliminary architectural plans, a total water fixture unit count of 1,662 for the project was estimated. The WFUs and are summarized in Table 1. The water fixture unit count breakdown for each building is provided in Appendix B of this report. Based on Chart A103.1 in the 2016 California Plumbing Code, a water fixture unit count of 1,662 converts to a peak flow of 288 gpm for the project. Private fire protection and recycled water system demand requirements are discussed in subsequent sections of this report. TABLE 1 OAKMONT SENIOR LIVING PROJECT WATER FIXTURE UNIT SUMMARY Building WFUs Marketing 58 Memory Care 406.5 Independent Living 1,197.5 TOTAL 1,662 DEXTER WILSON ENGINEERING, INC. PAGE 5 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems Private Domestic Water System Sizing The Oakmont Senior Living project's private domestic water system will consist of one domestic water meter connected to the existing 16-inch water line in Faraday Avenue. The domestic water meter will be followed by a reduced pressure principle backflow preventer. The domestic water system after the meter will be a private system and the responsibility of the project owner. Internal to the project, each building will be connected to the private domestic water main. The sizing of the project's water meter and private domestic water system distribution piping is presented in the following sections. Water Meter Sizing. One meter will provide service to the Oakmont Senior Living project. The meter size was determined based on the total demand served by the meter. Irrigation internal to the project is proposed to be connected separately; therefore, only domestic demands are being met by the domestic water service meter. The peak domestic demand for the project is 288 gpm. A 3-inch domestic water meter is recommended as the safe maximum operating capacity of a typical 3-inch turbine type or compound type meter per C700 of the AWWA Standards is 350 gpm. In either case, a 3- inch meter will be sufficient to accommodate the peak domestic demand. The meter will be followed by a 3-inch reduced pressure principle backflow preventer. Appendix C provides a copy of a candidate reduced pressure principle backflow preventer. Domestic Water System Pipe Sizing. The private domestic water system piping for the Oakmont Senior Living project has been sized in accordance with the Uniform Plumbing Code and the Installation Standard for PVC Cold Water Building Supply and Yard Piping (IAPMO IS 8-2006). The Installation Standard requires that the maximum pipeline velocity be limited to eight feet per second (8 fps). At a maximum flowrate of 288 gpm, the flow velocity in a 4-inch line is 7.4 fps. The Marketing Building's 2-inch supply lateral will experience a flow velocity of 3.3 fps at a maximum flowrate of 32 gpm The flowrate is based on the building's water fixture unit count of 58 WFUs presented. in Table 1. DEXTER WILSON ENGINEERING. INC. . PAGE 6 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems Figure 2 presents a graphic of the recommended private domestic water line sizes throughout the project. The domestic water line sizes shown on Figure 2 are the recommended pipe sizes. The pipe sizes shown comply with the 2016 California Plumbing Code and will supply adequate flow and pressure to each building within the Oakmont Senior Living project. Available Pressure at the Base of the Domestic Service Risers. The available pressures at the Base of the Risers for the domestic services are based on a 6-inch domestic service lateral connection, a 3-inch meter, a 3-inch reduced pressure principle backflow assembly, and distribution piping that is either 2-inches or 4-inches in size depending on the buildings being served. Exhibit A, located at the beginning of Appendix D, presents a Node and Pipe Diagram that shows a system schematic for the domestic water system. Using the data provided by the hydrant flow test, an extrapolation calculation determined that an available HGL of 549.2 feet in the public water main in Faraday Avenue at a peak domestic demand of 288 gpm. Pressure loss calculations were performed to determine the residual pressure at the base of each building's riser. Minor losses for pipe fittings were included in the calculations as equivalent lengths of pipe. The minor equivalent length table and the calculations for pressure loss are included in Appendix D of this report. The friction loss produced by the 3- inch meter is based on Chart A102.2 in the 2016 California Plumbing Code and a peak flow of 288 gpm. The friction loss incurred by the 3-inch backflow preventer is based on the candidate backflow 's data sheet presented in Appendix C and a peak flow of 288 gpm. The result of the pressure loss calculations is that the available domestic service pressure at the Base of the Riser for the Marketing Building is 104.4 psi. The available domestic service pressure at the Base of the Riser for the Independent Living Building is 99.8 psi. The available domestic service pressure at the Base of the Riser for the Memory Care Building is 99.7 psi. Table 2 presents a summary of the working pressures and maximum static pressures for each of the buildings. Since the static pressures are greater than 80 psi, a pressure regulator will need to be included in each of the building plans to maintain internal building service pressures below 80 psi in accordance with the Plumbing Code. DEXTER WILSON ENGINEERING, INC. PAGE 7 It 000, 7 - 6" PUBLIC WATER \\ SERViCE LATERAL \\\\ LEGEND PROJECT BOUNDARY PROPOSED WATER EXISTING WATER EXISTING FIRE HYDRANT BACKFLOW ASSEMBLY \\ 1 i = 80' FEET I- I 0 I - MEMORY < I CARE - ' /Th BUILDING Y \ , I ) F.F. 261.0 \ • ______/ 6 , * 0 II 6 (N I co I I - - 0 C, - I' 0 U I I 6• (N w -. o - - cr D01 0• PROJECT BOUNDARY T PROPOSED DOMES11C WATER METER 1 FIGURE 2I PRIVATE DOMESTIC WATER SYSTEM DEXTER WILSON ENGINEERING, INC. CONSULTING ENGINEERS (760) 438-4422 OAKMONT OF CARLSBAD Jason Vroom, P.E. August 23, 2019 S Oakmont Carlsbad Private Water Systems TABLE 2 OAKMONT SENIOR LIVING PROJECT BUILDING PRESSURES Building Base of Riser. . Maximum Static Working Pressure, Elevation, ft. Pressure, psi psi Marketing 254.5 128.0 104.4 Memory Care 261.0 ' 125.2 99.7 Independent Living . 260.0 125.6 . 99.8 Private Fire Protection System Sizing An onsite private fire protection system is being designed for the Oakmont Senior Living project in order to provide fire flow service to the four onsite private fire hydrants. This system is designed to deliver the required fire hydrant flow to the' four onsite fire hydrants as, well as supply the building fire sprinkler systems. For fire hydrant flow, minimum residual pressure in the onsite system must be greater than 20 psi. Fire Hydrant Flow Requirement. The required fire hydrant flow for the Oakmont Senior Living project is based, on the building square footage and type of construction. Table 3 summarizes the building sizes and types of construction and determines the fire hydrant flow requirements based on the 2016 California Fire Code. The fire flow requirement for the Oakmont Senior Living project is calculated to be 50 percent of the Fire Code flow based on the' allowable reduótion for having fire sprinkler systems in each building. The largest fire, hydrant flow needed for the site is 3,625 gpm. DEXTER WILSON ENGINEERING, INC.. S PAGE 9 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems TABLE 3 OAKMONT SENIOR LIVING PROJECT FIRE HYDRANT FLOW REQUIREMENTS Building Building Area, Construction Fire Flow Requirement, Fire Flow with• Sprinkler Square Feet Type g pm m Syste, gpml Marketing 5,338 V-A 1,500 1,500 Memory Care 58,670 V-A 4,250 2,125 Independent Living 160,823 V-A 7,250 3,625 nasea on ou7o reaucuon or total tire now requIrement. Fitting and Valve Losses. To simulate minor losses through pipe fittings and valves, equivalent lengths of piping were added to the straight pipe lengths and included in the hydraulic model. Appendix E provides the equivalent length reference table utilized for the determination of minor losses within the computer modeling analysis. Minor losses for the fire sprinkler system piping include accounting for the PN and FDC risers. Backflow Assembly Losses. The pressure losses through the double check detector assembly devices were modeled as minor losses using a "k" value large enough to result in the expected pressure loss through these devices. A candidate double check detector assembly backflow. preventer device is presented in Appendix E. The manufacturer's literature includes charts which show pressure loss through the backflow preventer as a function of flow. These charts were used to approximate the pressure losses which were reflected in the computer modeling and show up as minor losses calculated in feet. Fire Protection System Analysis. Appendix F presents the computer modeling results for the onsite private fire protection system serving the onsite fire hydrants. Exhibit B at the back of this report shows the Node and Pipe Diagram for the onsite private fire protection system. The first hydraulic run in Appendix F presents the estimated static pressure at every computer model node modeled for the Oakmont Senior Living project. The maximum static pressure at any node within the project site is 129 psi. The maximum static pressure at a building is 128 psi as presented in Table 3. DEXTER WILSON ENGINEERING, INC. PAGE 10 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems Next, the fire flow requirement for the Oakmont Senior Living project of 3,625 gpm was modeled at two fire hydrant locations within the project site. A total of three hydraulic runs were performed. In each of the runs the total fire flow was divided between two fire hydrants with a flow of 2,000 gpm at one hydrant and a flow of 1,625 gpm at the other fire hydrant. The results show that the residual pressure at any onsite fire hydrant for every hydraulic run is at least 79 psi,. which is well above the minimum requirement of 20 psi residual. The onsite private fire protection system is recommended to be connected to the existing 16- inch public water main in Faraday Avenue at two locations as.shown in Exhibit B. Each connection includes a fire service lateral and a double check detector assembly (DCDA) in accordance with City of Carlsbad and the Carlsbad Fire Department backflow prevention requirements. There will be two 12-inch fire service laterals. Each lateral will include an 8-inch DCDA. A 10-inch onsite private fire protection system main ioops between both DCDAS. Eight-inch, 6-inch and 4-inch piping is supplied by the 10-inch main loop as shown in Figure 3. Figure 3 presents a graphic of the recommended private fire protection system line sizes throughout the project. Available Fire Flow at 20 psi Residual. Fire flow available at each of the four fire hydrants serving the Oakmont Senior Living project was extrapolated to 20 psi residual. Table 4 shows the theoretical available fire flow at each fire hydrant when flowing individually. Appendix G presents the computer model calculation results. TABLE 4 AVAILABLE FIRE FLOW AT EACH FIRE HYDRANT Fire Flow Residual Pressure Node Number Hydrant Type Capability, gpm at Fire Hydrant psi Node 116 Private Onsite 4,007 22.7 Node 120 Private Onsite 6,134 25.6 Node 140 Private Onsite 4,431 23.2 Node 148 Private Onsite 5,295 24.3 DEXTER WILSON ENGINEERING, INC. PAGE I I it / MEMORY CARE BUILDING 60 F.F. 261.0 1IRE 'SPRINKLER .—ERVICE LATERAL bslo 12" PUBLIC WATER SERVICE LATERAL PROJECT BOUNDRY FIRE SPRINKLER SERVICE LATERAL FIRE. SPR NILER - SERVICE RA Th- )>-'' PUBLIC WATER SERVICE LATERAL 1 N LEGEND PROJECT BOUNDARY 1" 80' PRIVATE FIRE SYSTEM \ EXISTING WATER 0 80 PROPOSED FIRE HYDRANT FEET EXISTING FIRE HYDRANT BACKFLOW ASSEMBLY FIGURE 3 PRIVATE ARE PROTEC11ON SYSTEM DEXTER WILSON ENGINEERING, INC. OAKMONT OF CARLSBAD CONSULTING ENGINEERS (760) 436-4422 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems The available fire flow at each fire hydrant is qualified as theoretical because the calculated flows cannot be extracted from a single fire hydrant. It is more correct to describe the extrapolated flows at 20 psi residual to be indicative of what the water distribution system theoretically can deliver to. a certain area with the residual pressure in the water system of 20 psi. Fire Stirinkler Service Laterals to the Oakmont Senior Living Buildings The second portion of the Oakmont Senior Living project private fire system analysis is to determine the required sizes for the individual fire sprinkler service laterals to each of the three buildings in the Oakmont Senior Living project. The individual fire service laterals are to be connected to the private onsite fire protection system piping. Each fire sprinkler lateral will be installed with a PIV and FDC in accordance with the City of Carlsbad Fire Department requirements. Per the project designer, the Marketing Building has a fire sprinkler flow demand requirement of 200 gpm at a minimum pressure of 40 psi at the Base of Riser elevation. The Memory Care Building has a fire sprinkler flow demand requirement of 430 gpm at a minimum pressure of 55 psi at the Base of Riser elevation. The Independent Living Building has a fire sprinkler flow demand requirement of 430 gpm at a minimum pressure of 65 psi at the Base of Riser elevation. Email correspondence presenting the fire sprinkler system requirements is provided in Appendix H for reference. Appendix H also presents the results of the computer modeling for the fire sprinkler system laterals. Table 5 summarizes th results of the analyses. A 4-inch lateral is recommended I for the Marketing Building. Six-inch laterals are recommended for the Memory Care Building and Independent Living Building. I . . I DEXTER WILSON ENGINEERING, INC. . PAGE 13 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems TABLE FIRE SPRINKLER SYSTEM LATERAL DATA Fire Sprinkler Lateral Size, Base of Riser Residual Building Flow, gpm in Elevation, ft Pressure at BOR, psi Marketing 200 4 254.5 118.0 Memory Care 430 6 261.0 114.7 Independent Living 430 6 260.0 115.1 - Recycled Water Service The proposed recycled water system for the project will be served by the Carlsbad Municipal Water District (CMWD). The available hydraulic grade line for the 550 Pressure Zone supplying recycled water for the Oakmont Senior Living project is set at 550 feet HGL by the Twin D Pump Station located near the intersection of Poinsettia Lane and Black Rail Road. The recycled water system lateral for the Oakmont Senior Living project will be connected to the existing 12-inch 550 Pressure Zone public recycled water system piping in Faraday Avenue. Project Demands. Recycled water demands for the project were provided by the Designer/Landscape Architect for the Oakmont Senior Living project. A summer peak demand of 35 gpm is estimated for the project. Water Meter Sizing. One meter will provide service to the Oakmont Senior Living project. The meter size was determined based on the total demand served by the meter. The peak recycled water demand for the project is 35 gpm. A 1-inch recycled water meter is recommended as the safe maximum operating capacity of a 1-inch displacement type or turbine type meter per C700 of the AWWA Standards is 50 gpm. In either case; a 1-inch meter will be sufficient to accommodate the peak domestic demand. The meter will be followed by a 1-inch reduced pressure principle backflow preventer. DEXTER WILSON ENGINEERING, INC. PAGE 14 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems Available Static Pressure. Based on a graded pad elevation of approximately 260 feet at the street, the 550 Recycled Water Pressure Zone will supply a static pressure of approximately 125 psi. Conclusion Three private system connections will be made to the existing 16-inch public water main in Faraday Avenue for the Oakmont Senior Living project. There will be one 6-inch lateral for the 3-inch domestic water meter, and two 12-inch laterals for the private fire protection system. The proposed domestic system includes a 3-inch water meter and a 3-inch backflow preventer. The proposed system layout and pipe sizing for the domestic water system is shown in Figure 2. The proposed private fire protection. system includes two 8-inch backflow preventers. The proposed system layout and pipe sizing for the private fire protection system is shown in Figure 3. Fire sprinkler service laterals are recommended to be 6-inch diameter for the Memory Care Building and the Independent Living Building, and 4-inch for the Marketing Building based on each building's expected maximum fire sprinkler flow. Available fire flow at any single one of the four proposed onsite private fire hydiants is at least 4,000 gpm at a residual pressure of 20 psi. One 1-inch recycled water lateral connection will be made to the existing 12-inch public recycled water main in Faraday Avenue for the Oakmont Senior Living project. A 1-inch recycled water meter and a linch backflow are recommended to supply the onsite landscape irrigation system. .. DEXTER WILSON ENGINEERING, INC. . . PAGE I 5 Jason Vroom, P.E. August 23, 2019 Oakmont Carlsbad Private Water Systems Thank you for the opportunity to provide domestic, private fire protection, and recycled water system sizing analysis services for this project. Please feel free to contact us to discuss further. any aspect of the information presented in this water study for the Oakmont Senior Living project. Dexter Wilson Engineering, Inc. Andrew Oven, P.E. AO:FF:sc Attachments DEXTER WILSON ENGINEERING, INC. PAGE 16 APPENDIX A FIRE FLOW ANALYSES FROM CITY OF CARLSBAD WATER AVAILABILITY FORM AND EXTRAPOLATION CALCULATION o C - CARLSBAD FIRE DEPARTMENT Fire Prevention Division 1635 Faraday Avenue - Carlsbad, CA 92008 760.602.4565 WATER AVAILABILITY FORM SECTION A: TO BE COMPLETED BY CUSTOMER PROJECT NAME: Oakmont of Carlsbad SR#: (Assigned upon plan submittal) PROJECT ADDRESS: Faraday Avenue at El Fuerte Street (APN: 209-120-01-00) CITY: Carlsbad CONTACT: Alliance Land Planning & Engineering / Attn: Ashley Holland PHONE: (760) 431-9896 Largest Building (ft.2 ): 128,745 (Livable) / 160.823 Total Sprinkled? Yes Construction Type: VA' SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.. Water Purveyor: City of Carlsbad Location of test (reference map required): On Faraday Ave (next to corner of El Fuerte Street) TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED Flow Test Results Static pressure: 132 PSI Hydrant Number (if applicable):H61663 Elevation of test: 245 Feet 'Date/Time of Test': 1 Pitot Tube Reading: Psi Corresponding Flow: GPM Total Flow: 4.025 GPM [Residual Pressure 106 PSI At peak demand , this water system is capable of providing a fire flow discharge at 20 psi of 5,400 gpm. However, this flow rate exceeds the District's maximum velocity criteria of 10 fps. Therefore, the maximum allowable fire flow at criteria is 4,025 gpm. 1Test to be performed as close as possible to the time the most conservative flows and pressures are expected. Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer modeling), fill out the information above as applicable and check here: Name: Jennifer R. Mael, P.E. Eng. Lic. No. (if applicable): C69606 Date: 08/09/2019 Title/Org: Project Manager Oakmc LLU psi 4bU 130 psi 1,006 140 psi Residual Pressure Exceeds Static Pressure 150 psi Residual Pressure Exceeds Static Pressure 160 psi Residual Pressure Exceeds Static Pressure 170 psi Residual Pressure Exceeds Static Pressure 180 psi Residual Pressure Exceeds Static Pressure 190 psi Residual Pressure Exceeds Static Pressure \\artic\eng\528039\2019-08-21 Fire Flowlest Equivalent HGLxIsx APPENDIX B WATER FIXTURE UNIT COUNT Oakmont of Carlsbad 6/27/2017 528-039 Water Fixture Units The basis for the Water Fixture Units is the 2016 California Plumbing Code. Marketing Building FIXTURE TOTAL QUANTITY UNITS FIXTURE EACH UNITS 1 4 4 1 4 4 1 2.5 2.5 _1 I I 5 2 10 4 1.5. 6 1 1.5 1.5 9 1 9 8 2.5 20 1 0 58 Independent Living Building FIXTURE TOTAL QUANTITY . UNITS FIXTURE EACH UNITS 147 2.5 367.5 155 1 155 3 1.5 4.5 I 2.5 2.5 3 1 3 4 . 4 16 105 2 210 9. 4 36 10 1.5 15 1 1.5 1.5 109 1.5 163.5 9 1.5 13.5 65 3 195 3 1.5 4.5 1 10 10 1 0 1197.5 Memory Care Building FIXTURE TOTAL QUANTITY UNITS FIXTURE EACH UNITS 66 2.5 165 66 1 66 2 1.5 3 1 2.5 2.5 2 1 2 4.5 4 18 54 2 108 1 4 4 12 1.5 18 2 1.5 3 2 4 8 5 1.5 7.5 1 1.5 1.5 1 0 406.5 DESCRIPTION CLOTHES WASHER TUB/SHOWER HOSE BIBB HOSE BIBB, ADDITIONAL SHOWER KITCHEN SINK DISHWASHER LAVATORY WATER CLOSET (1.6 GPF) OTHER TOTAL DESCRIPTION WATER CLOSET (1.6 GPF) LAVATORY MOP SINK HOSE BIBB HOSE BIBB, ADDITIONAL CLOTHES WASHER SHOWER COMBO BATH/SHOWER SINK LAUNDRY SINK KITCHEN SINK DISHWASHER LAUNDRY GROUP BEAUTY SINK POOL OTHER TOTAL DESCRIPTION WATER CLOSET (1.6 GPF) LAVATORY MOP SINK HOSE BIBB HOSE BIBB, ADDITIONAL CLOTHES WASHER SHOWER COMBO BATH/SHOWER SINK LAUNDRY SINK BATH TUB KITCHEN SINK DISHWASHER OTHER TOTAL Water System2017406-27 l.terFixtureUnitEstimatePerCltyofSD11-02DataCard-water.xIs/Sheet1 APPENDIX C CANDIDATE BACKFLOW PREVENTER ASSEMBLY FOR DOMESTIC WATER SYSTEM In "E. = 1.1, Materials PJI internal metal parts: 300 Series stainless steel Main valve body 300 Series stainless steel Check assernbly. Noryf Flange dimension in accordance with AWWA Class D Capacity Senes4000SSperformanceasestablishedbyanindependenttestinglabo- ratory (1996 UL). UL certified flow characteristics. Documented flow characteristics (including shutoff valves). UL Rated "UL Tested I4L I-.- - liii d flil I__I Fi1Ijl ______•i I--. - kPa pal 40 (100mm) 145 21 1103 15 - 41 6 0 100 200 300 400 500 600 700 gpm 0 380 760 1140. 1520 1900 2280 26601pm Flaw Rate Pressure - Temperature Temperature Range: 33°F - 110°F (0.5°C - 43°C) Maximum Working Pressure: 175p51 (12.1 bar) kPa psi 6" (150mm) * 145 2 21 3 124 18 IM 15 83 12 62 41 0 250 500 750 1000 1250 1500 gpm 0 950 1900 2850 3800 4750 5700 1pm Flaw Rate lipa psi 8" (200mm) 138 20 124 18 110 16 96 14 93 12 69 10 55 A 0 400 800 1200 1600 2000 2400 gpm O 1520 3040 4560 6080 7600 9120 1pm Raw Rate "a psi 10(250mm) 138 20 124 18 110 16 96 14 93 12 7 69 10 55 8 6 0 5110 1000 1500 2000 2500 3000 gpm 0 1960 3800 5700 7600 9500 11400lpm Hew Rate _____ I & . C(ope Dimensions - Weights Note: Strainer sold separately _1p1_ DIMENSIONS NET WEIGHTi In. mm A in. mm C (0S in. • mm C(NRS) in. mm 0 in mm ía F mm L in. mm w/Gates lb kg w/o Gates j kg. 21h 65 37 940 16% 416 9% 238 10½ 267 7 178 22 559 148 67 60 27 3 80 36 965 18,4 479 101I4 260 10½ 267 71h 191 22 559 226 103 62 28 4 100 40 1016 22% 578 1 12/,o 310 1 10½ 267 9 229 22 559 235 107 65 30 6 150 481h 1232 301A 765 16 406 11½ 292 11 279 271h 699 50 8 200 52½ 1334 37~ 959 1915/16 506 12½ 318 13½ 343 29½ 749 571 380t 3511 81 10 250 55½ 1410 45% 1162 2313/,6 605 12½ 318 16 .406 29½ 749 773 86 Norvf6 is reaistered trademark of General Electric Comnanv, A Inquire with governing authorities for local installation AM ES requirements FIRE&WATERWORKS A Watts Water Technologies Company USA: Backfiow Tel: (978) 689-6066 • Fax: (978) 975-8350 • Aj'nesFlreWater.com USA: Control Valves Tel: (713) 943-0688 • Fax (713)944-9445. ArnesFireWater.con, Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • AmesfireWater.ca Latin America: Tel: (52)81-1001-8600 • Fax: (52)81-8000-7091 • AmesFireWater.com ES-A-4000SS 1410 S 0 2014- Ames Fire & Waterworks APPENDIX D EXHIBIT A AND CALCULATION OF MINOR LOSSES FOR FITTINGS AND VALVES AND PRESSURE LOSS CALCULATIONS FOR DOMESTIC WATER SYSTEM __------cç - 240 • 3') MEMORY CARE ' BUILDING 224 , F.F. 261.0 2 1L1 PROJECT BOUNDRY — :- i5.40 ® afi LEGEND PROJECT BOUNDARY PROPOSED DOMESTIC WATER EXISTING WATER EXISTING FIRE HYDRANT BACKFLOW ASSEMBLY PROPOSED DOMESTIC WATER METER 1 \ i 1"\= 80' FEET ® EJ COMPUTER MODEL NODE NUMBER COMPUTER PIPE NUMBER EXHIBIT A PRIVATE DOMESTIC WATER SYSTEM NODE DEXTER WILSON ENGINEERING, INC CONSULTING ENGINEERS (760) 438-4422 AND PIPE DIAGRAM OAKMONT OF CARLSBAD Oakmont of Carlsbad 8/22/2019 528-039 Pipe No. Gate Valve, Open Check Valve Standard tee , Branch Standard tee, Through 900 Elbow, std. 450 Elbow Pipe Length (ft) I Pipe Size, in Equivalent Length of Additional Pipe Elements Total Length I (ft) Pipe No. 201 1 1 3 43 6 88.5 132 201 205 (Meter) 10 3 0 10 205 (Meter) 209 2 17 4 4.6 22 209 213 (Bkflw) S 20 3 0 20 213 (Bkflw) 217 2 3 72 4 37.6 110 217 221 1 1 2 3 300 2 31.5 332 221 225 1 S 1 - 161 4 24.3 185 225 - 229 1 1 1 74 4 29.3 103 229 233 1 1 3 135 4 24.2 159 233 237 1 2 58 4 16.9 75 237 241 2 55 4 22 77 241 \\ARTIC\Eng\528039\Domestic Water System\2019-08-22 Domestic MinorLoss_EquivalentLengthCalcs.xlsx / Equivalent Length J DEXTER WILSON ENGINEERING, INC. iA - ec :t E,ctc4i lk c H(L - '5(' 4 ZMc4F r ZD& Ct crc4.bl4 LD9; (W;vto' (os,ec tctuLc.( e ciLc+ L&*1Lc) • • . . • • : S P :1b CIzb S • • ... •• S • • • • • •• S 1b) Lx 0.b7,• S 'H(2L r(j c9Z4 -°I•• I OwtQ1 uX t4e('Qt— VDLM€5I-C iiJ4' CeIcs. I9/] ¶/•- JO8NO. SUBJECT SlEET NO. DEXTER WILSON ENGINEERING, INC. I L4 j . lev :H1 IIE IF I e-1, vil .i -•---1- -•-H .... Tv :._. . ...--.-.---..-----..-.--t-.....- ... .... LJ_iJ.......... .J ... LJ.. ........... ill 1 .1 .f.......... ..................................................J....J.... L.L: ....... L_...__..L_J ......... . ...............4.i.... la L .................... ..... ........................ ......... 11 I±ItIJffIILII1iITI1. .JTFTr II _ .. .... .LJ..L.L.L.L.J....L.L....L.I:.Ll.L4........lii....... f .LJ....I.... +i ,ILL I---------. Ii I' ...I....... H ...........................__ L....1H I Oo iIiL ow€ihc ___ ___ DEXTER WILSON ENGINEERING,*INC. f - )g I I I oe NO. suejecr J SHEET NO. DEXTER WILSON ENGINEERING, INC. S t4t o C)1 4- H u.ro - H&Lot 50114 (.ev 591) Q 32. 1rw1,6,q 5,c l It c HA 4- e ZCL G CP c:c)tT tot Loss. (.i;i.toi (u5.e.c. :i.tcLJ. r(11L&tr 1.,4ltr) L.: 33 -4tt . . at .309 • : •• . S ••• ••12o• • • • •.. • • I •:t+ S • • • IO.3. .• • - q.ç i..3 • z.5')/ • • 5 z -o31I o Cib1'cto& 1h Wok-' (Ls. /zzhgj JOB NO.• DATE SHEET NO. DEXTER WILSON ENGINEERING, INC & Vc.I—. -o H(L o'4 t%.at L vmy kMo'T (- iIy '( (4 iOlb (?i Pv:c4oi L.oe,s. (I4utol (o14c te -7, tvcLei&# t.e.tct Lc) Li i, tO L H .• S. . .9I'. • . S S •• •• • : • • .. . S. • 11.! . . S . To L055 IL) X • • - z') ço 9?O ., • 55 SUBJECt ____ ____ Joe NO. BY DA1E T NO. DEXTER WILSON ENGINEERING, -INC. %kak \ L: : 1L5 o.. er 40 ! M: •• •7' LD5 :(ioi . . L . v 4. via . . k 103 :QjY1144 . . . Tzo t1L.q L34 T0l 9i - (4qo.5. I- MAI,3v. ps _____ Ct-*I; c',tt,. JV7td4i 1- JO BB 1O BY SUBJECT . DA NO. DEXTER WILSON ENGINEERING, INC. MQ.440/7 u.- C. tU ¶34e. 1- - H'L -)1i 4- D51') th.: - rrckt Lo5s (it4 tACL4t.e..'t q5 d Z L4 0 re 4LE I.ei.i.,ti) iOii L •. j7' (Z/ I • . • L 3i . •. :Q IITM • : • •. . •: Q • . . .. L&. . • . . ... f Lor • - fl &L . . at'): :••.=> F •. o Cit94,q— Thtc( c Lvci j- SUBJECT OA APPENDIX E CALCULATION OF MINOR LOSSES FOR FITTINGS AND VALVES AND CANDIDATE BACKFLOW PREVENTER ASSEMBLY FOR PRIVATE FIRE PROTECTION SYSTEM NODE AND PIPE DIAGRAM REFERENCE: Exhibit .B in the back of the report. Oakmont of Carlsbad 8/21/2019 528-039 Pipe No. Gate Valve, Open Check Valve Standard tee, Branch Standard tee, Through 900 Elbow, std. 450 Elbow Pipe Length (ft) Pipe Size, In Equivalent Length of Additional Pipe Elements Total Length (ft) Pipe No. 101 1 - 1 2 17 12 135.9 153 101 105 (Bkflw) 20 8 0 20 105 (Bkflw) 109 - 1 1 2 2 120 10 140.8 261 109 113 1 3 195 8 74 269 113 115 1 1 2, 38 4 46.3 84 115 117 1 1 1 2 201 8 59.5 261 117 121 1 25 10 5.8 31 121 125 1 1 - 130 10 23.8 154 125 129 1 4 168 10° 57.8 226 129 133 1 1 41 8 24 65 133 135 1 1 2 45 6 71.5 117 135 137 0 1 34 8 10 44 137 139 1 1 1 1 53 6 61.9 115 139 141 1 1 1 2 156 8 59.5 216 141 145 1 2 169 10 31.8 201 145 149 1 1 2 44 8 90.5 135 149 153 1 0 1 2 52 10 114.8 167 153 157 (Bkflw) 0 20 8 0 20 157 (Bkflw) 161 1 1 2 25 12 135.9 • 161 161 \\artic\eng\528039\Fire Protection System\2019-08-21 Fire Sys Minor Loss Equivalent Length Calcsxlsx / Equivalent Length Pressure - Temperature Temperature Range: 33°F - 110°F (0.5°C - 43°C) Maximum Working Pressure: 175ps1 (12 bar) Capacity Flow curves as tested by Underwriters Laboratory per UL 1469, 1996. Rated flow UL Tested _____•._..____ ._. !• u ______. I__p p_• --.U--I '•! !•U ia Pd 4" (100mm) * ** .......... .... MEMENEENEEMENEW •••••••• .._. I l I_I•--_-_....... •• rZ F I Il 1rrT i ' 11P I I A Standards ASSE 1048, AWWA C510-92, CSA B64.5, UL 1469 Approvals UL Classified (OSY only), FM (sizes 21/a° - 10, OSY only) 8868 F 400 o-® 1l'TTT1 _•_•_.___...__. MMMMMMIMMM _•__.___I I... I .--_p ______I .__. --- I I Iig -i71 MMMMMMMMMIN F 4 •••••i ._. I -------— I_i i!•i —----- i..I _1j::$: C (Open) Ltp I SIZE (ON)DIMENSIONS NETL21sJ,u1. NET WEIGHT in. mm A In. mm C (OSY) In. mm 0 in. . mm 6 in. mm L In. mm P In. mm wlGates lb. kg, w/o Gates lb. kg. 2½ 65 37 965 16% 416 3½ 89 10 250 22 559 121h 318 155 70 68 31 _3 80 38 965 IN 479 3% 95 10 250 22 559 13 330 230 104 70 32 4 100 40 1016 22% 578 41h 114 10 250 22 559 14½ 368 240 109 73 33 _6 150 481h 1232 301A 765 51h 140 15 381 27½ 699 151h 394 390 177 120 54 _8 200 521h 1334 3734 959 6% 171 15 381 291h 749 181h 464 572 259 180 82 10 250 55½ 1410 45Y4 1162 8 200 15 381 29½ 749 191h 495 774 351 190 86 12 300 571h 1461 53½ 1349 91h 241 15 381 291h 749 21 533 1044 474 220 100 A M E S FIRE & WATERWORKS A WAITS Brand USA: Backflow Tel: (978) 689-6066 • Fax: (978) 975-8350 • AmesFlreWate.com USA: Control Valves Tel: (713) 943-0688 • Fax: (713) 944-9445 • AmesFireWater.com Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • AmesflreWater.ca Latin America: Tel: (52) 81-1001-8600 • AntesFireWater.com ES-A-3000SS 1744 © 2016 Ames Fire & Waterworks APPENDIX F COMPUTER MODEL ANALYSES FOR FIRE HYDRANT FLOW REQUIREMENT NODE AND PIPE DIAGRAM REFERENCE: Exhibit B in the back of the report. CONDITIONS MODELED: Static pressures. Fire flow of 3,25 gpm split between Node 116 (1,625 gpm) and Node 140 (2,000 gpm). Fire flow of 3,625 gpm split between Node. 120 (1,625 gpm) and Node 140 (2,000 gpm). Fire flow of 3,625 gpm split between Node 140 (1,625 gpm) and Node 148 (2,000 gpm). Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants FLOWRATE IS EXPRESSED IN GPM AND PRESSURE IN PSIG A SUMMARY OF THE ORIGINAL DATA FOLLOWS PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE (FEET) (INCHES) 13 0 16 45.0 16.0 120.0 .00 550.00 17 16 20 160.0 16.0 120.0 .00 21 20 24 460.0 16.0 120.0 .00 25 24 28 140.0 16.0 120.0 .00 101 20 100 153.0 12.0 120.0 .00 105 100 104 20.0 8.0 120.0 8.00. THERE IS A CHECK VALVE IN LINE NUMBER105 109 104 108 261.0 10.0 120.0 .00 113 120 112 229.0 8.0 120.0 .00 115 112 114 84.0 4.0 120.0 . .00 117 112 116 261.0 8.0 120.0 .00 121 108 120 . 31.0 10.0 120.0 .00 125 108 124 154.0 10.0 120.0 .00 129 124 128 226.0 10.0 120.0 .00 133 128 132 65.0 8.0 120.0 .00 135 132 134 117.0 6.0 120.0 .00 137 132 136 44.0 . 8.0 120.0 .00 139 .136 138 115.0 6.0 120.0 .00 141 136 140 216.0 8.0 120.0 .00 145 144 128 201.0 10.0 120.0 .00 .149 144 148 135.0 8.0 120.0 .00 153 152 144 167.0 10.0 120.0 .00 157 156 152 20.0 8.0 120.0 12.00 THERE IS A CHECK VALVE IN LINE NUMBER157 161 28 156 161.0 12.0 120.0 .00 JUNCTION NUMBER DEMAND ELEVATION CONNECTING PIPES 16 .00 245.00 13 17 20 . .00 254.00 17 21 101 24 .00 248.00 21 25 28 .00 245.00 25 161 100 .00 254.00 101 105 104 .00 254.00 105 109 108 . .00 255.00 109 121 125 112 1.00 254.00 113 115 117 114 .OP 254.50 115 116 .00 257.00 117 120 .00 257.00 113 121 124 .00 259.00 125 129 128 .00 258.00 129 133 145 132 .00 260.00 133 135 137 134 .00 261.00 135 136 .00 260.00 137 139 141 138 . .00 260.00 139 140 .00 260.00 141 Page 1 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants 144 .00 253.00 145 149 153 148 .00 255.00 149 152 .00 251.00 153 157 156 .00 . 251.00 157 161 OUTPUT SELECTION: ALL RESULTS ARE OUTPUT EACH PERIOD 5 VALUES ARE OUTPUT FOR MAXIMUM AND MINIMUM PRESSURES THIS SYSTEM HAS 23 PIPES WITH 22 JUNCTIONS , 1 LOOPS AND 1 FGNS THE RESULTS ARE OBTAINED AFTER 7 TRIALS WITH AN ACCURACY = .00155 Oakmont of Carlsbad File: 528039A8 Private Fire Protection System Analysis Static Pressures PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 1.00 .00 .00 .00 .00 .00 17 16 20 1.00 .00 .00 .00 .00 .00 21 20 24 .40 .00 .00 .00 .00 .00 25 24 28 .40. .00 .00 . .00 .00 .00 101 20 100 .60 .00 0.00 .00 .00 .00 105 100 104 .60 .00 .00 . .00 .00 .00 109 104 108 .60 .00 .00 .00 .00 .00 113 120 112 . 1.00 .00 .00 .00 .01 .00 115 112 114 .00 .00 .00 .00 .00 .00 117 112 116 .00 .00. .00 0 .00 .00 .00 121 108 120 1.00 .00 .00 .00 .00 .00 125 108 124 -.40 .00 .00 .00 .00 .00. 129 124 128 -.40 .00 .00 .00 .00 .00 133 128 132 .00 .00 .00 .00 .00 .00 135 132 134 .00 .00 .00 .00 .00 .00 137 132 136 .00 .00 .00 .00 .00 .00 139 136 138 .00 .00 .00 .00 .00 .00 141 136 140 .00 .00 .00 .00 .00 .00 145 144 128. .40 .00 . .00 .00 .00 .00 149 144 148 .00 .00 .00 .00 . .00 .00 153 152 144 .40 .00 .00 .00 .00 .00 157 . 156 152 0 .40 .00 .00 .00 .00 .00 161 28 156 .40 .00 .00 .00 .00 .00 JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 16 .00 550.00 245.00 132.17 20 . .00 550.00 254.00 128.27 24 .00 550.00 248.00 130.87 Page 2 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants 28 .00 550.00 245.00 132.17 100 .00 550.00 254.00 128.27 104 .00 550.00 254.00 128.27 108 .00 550.00 255.00 127.83 112 1.00 550.00 254.00 128.27 114 . .00 550.00 254.50 128.05 116 .00 550.00 257.00 126.97 120 .00 550.00 257.00 126.97 124 ;00 550.00 259.00 126.10 128 .00 550.00 258.00 126.53 132 .00 550.00 260.00 125.67 134 .00 550.00 261.00 125.23 136 .00 550.00 260.00 125.67 138 .00 550.00 260.00 125.67 140 .00 550.00 260.00 125.67 144 .0.0 550.00 253.00 128.70 148 .00 550.00 . 255.00 127.83 152 .00 550.00 251.00 129.57 156 .00 550.00 251.00 129.57 MAXIMUM PRESSURES 16 .00 550.00 245.00 132.17 28 .00 550.00 245.00 132.17 24 .00 550.00 248.00 130.87 152 .00 550.00 251.00 129.57 156 .00 550.00 251.00 129.57 MINIMUM PRESSURES 134 .00 550.00 261.00 125.23 132 .00 550.00 260.00 125.67 136 .00 550.00 260.00 125.67 138 . .00 550.00 260.00 125.67 140 .00 550.00 260.00 125.67 THE NET SYSTEM DEMAND = 1.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 1.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 1.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE JUNCTION NUMBER DEMAND 116 1625.00 • 140 2000.00 12 • .00 Page 3 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants THE FOLLOWING CHANGES IN PIPE DATA ARE SPECIFIED FOR PIPE NUMBER 13 THE VALUE OF THE FIXED GRADE IS CHANGED TO 500.2 THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00013 Oakmont of Carlsbad 3625 gpm Fire Flow Split Between Nodes 116 and 140 1625 gpm at Node 116 and 2000 gpm at Node 140 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 3626.00 .35 .00 .00 5.79 7.87 17 16 20 3626.00 1.26 .00 .00 5.79 1.87 21 20 24 1637.17 .83 .00 .00 2.61 1.81 25 24 28 1637.17 .25 .00 .00 2.61 1.81 101 20 100 1988.83 1.61 .00 .00 5.64 10.51 105 100 104 1988.83. 1.51 .00 20.01 12.69 75.70 109 104 1.08 1988.83 6.66 .00 .00 8.12 25.53 113 120 112 1626.00 11.94 .00 .00 10.38 52.13 115 112 114 .00 . .00 .00 .00 .00 .00 117 112 116 1625.00 13.59 .00 .00 10.37 52.07 121 108 120 1626.00 .55 .00 .00 6.64 17.58 125 108 124 362.83 .17 .00 .00 1.48 1.09 129 124 128 362.83 .25 .00 .00 1.48 1.09 133 128 132 2000.00 4.97 .00 .00 12.76 76.49 135 132 134 .00 .00 .00 .00 .00 .00 137 132 136 2000.00 3.37 .00 .00 12.76 76.49. 139 136 138 .00 .00 .00 .00 .00 .00 141 136 140 2000.00 16.52 .00 .00 12.76 76.49 145 144 128 1637.17 3.58 .00 .00 6.69 17.81 149 144 148 .00 .00 .00 .00 . .00 .00 153 152 . 144 1637.17 2.97 .00 .00 6.69 17.81 157 156 152 1637.17 1.06 .00 . 20.34 10.45 52.79 161 28 156 1637.17 1.18 .00 .00 4.64 7.33 JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 16 .00 .• 499.85 245.00 110.43 20 .00. 498.59 254.00 105.99 24 .00 497.76 2.48.00 108.23 28 .00 497.50 245.00 109.42 . 100 .00 496.98 254.00 105.29 104 .00 475.45 254.00 95.96 108 . .00 468.79 255.00 92.64 112 1.00 . 456.30 254.00 87.67 114 .00 456.30 254.50 87.45 116 1625.00 .442.71 257.00 80.48 120 .00 468.24 257.00 91.54 124 .00 468.62 259.00 90.83 128 . .00 468.37 258.00 91.16. Page 4 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants 132 .00 463.40 260.00 88.14 134 .00 463.40 261.00 87.71 136 .00 460.03 260.00 86.68 138 .00 460.03 260.00 86.68 140 2000.00 443.51 260.00 79.52 144 .00 471.95 253.00 94.88 148 .00 471.95 255.00 94.01 152 .00 474.93 251.00 97.03 .156 .00 496.32 251.00 106.31 MAXIMUM PRESSURES 16 .00 499.85 245.00 110.43 28 .00 497.50 245.00 109.42 24 .00 497.76 248.00 108.23 156 .00 496.32 251.00 106.31 20 .00 498.59 254.00 105.99 MINIMUM PRESSURES 140 2000.00 443.51 260.00 79.52 116 1625.00 442.71 257.00 80.48 136 .00 460.03 260.00 86.68 138 .00 460.03 260.00 86.68 114 .00 456.30 254.50 87.45 THE NET SYSTEM DEMAND = 3626.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 3626.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 3626.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE JUNCTION NUMBER DEMAND 120 1625.00 140 2000.00 12 .00 THE FOLLOWING CHANGES IN PIPE DATA ARE SPECIFIED PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE 105 100 104 20.0 8.0 120.0 8.60 .00 THERE IS A CHECK VALVE IN LINE NUMBER105 157 156 152 •20.0 8.0 120.0 12.60 .00 THERE IS A CHECK VALVE IN LINE NUMBER157 THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00000 Page 5 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants Oakmont of Carlsbad 3625 gpm Fire Flow Split Between Nodes 120 and 140 1625 gpm at Node 120 and 2000 gpm at Nodes 140 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 3626.00 .35 .00 .00 5.79 . 7.87 17 16 20 3626.00 1.26 .00 .00 5.79 7.87 21 20 24 1644.07 .84 .00 . .00 2.62 1.82 25 24 28 1644.07 .25 .00 .00 2.62 1.82 101 20 100 1981.93 1.60 .00 .00 5.62 10.44 105 100 104 1981.93 1.50 .00 21.36 . 12.65 75.21 109 104 108 1981.93 6.62 .00 .00 8.10 25.37 113 120 112 1.00 .00 .00 .00 .01 .00 '115 112 114 .00 . .00 .00 .00 .00 .00 117 112 116 . .00 .00 .00 .00 .00 .00 121 108 120 1626.00 .55 .00 .00 6.64 17.58 125 108 124 355.93 .. .16 .00 .00 1.45 1.05 129 124 128 355.93 .24 .00 .00. 1.45 1.05 133 128 132 2000.00 4.97 .00 .00, 12.76 76.49 135 132 134 .00 .00 .00 .00 .00 .00 137 132 136 2000.00 3.37 .00 .00 12.76 76.49 139 136 138 .00 .00 .00 .00. .00 .00. 141 136 140 2000.00 ' 16.52' .00 .00 12.76 76.49 145 144 128 1644.07 3.61 .00 .00 6.72 17.95 149. 144 148 .00 .00 .00 .00 .00 .00 153 152 144 1644.07 3.00 .00 .00 6.72 17.95 157 156 152 1644.07 1.06 .00 . 21.54 10.49 53.21 161 28 156 1644.07 1.19 .00 .00 4.66 .7.39 JUNCTION NUMBER DEMAND ' GRADE LINE ELEVATION PRESSURE 16 .00 499.85 245.00 110.43 20 .00 498.59 254.00 105.99 24 .00 497.75 248.00 108.22 28 .00 497.49 245.00. 109.41 100 . .00 496.99 254.00 105.30 104 .00 474.12 254.00 95.39 108 .00 467.50 255.00 92.08 112 1.00 466.95 254.00 92.28 114 .00 466.95 254.50 92.06 116 .00 466.95 ' 257.00 - 90.98 120 1625.00 466.95 257.00 90.98 124 .00 467.34 259.00 90.28 128 .00 467.10 258.00 90.61 132 .00 462.13 260.00 87.59 134 .00 462.13 261.00 87.15 136 .00 458.76 ' 260.00 86.13 138 .00 458.76 260.00 86.13 140 2000.00 442.24 260.00 78.97 144 .00 470.70 253.00 . 94.34 148 . .00 470.70 255.00 93.47 . Page 6 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire' Hydrants 152 .00 473.70 ' 251.00 96.50 156 .00 496.31 251.00 106.30 MAXIMUM PRESSURES 16 .00 499.85 245.00 110.43 28 .00, 497.49 245.00 109.41 24 .00 497.75 248.00 108.22 1516 .00 496.31 251.00 106.30 20 .00 , 498.59 254.00 105.99 MINIMUM PRESSURES 140 2000.00 442.24 260.00 78.97 136 .00 458.76 260.00 86.13 138 ' , .00 458.76 260.00 86.13 134 .00 462.13 261.00 87.15 132 .00 462.13 260.00 87.59 THE NET SYSTEM DEMAND = 3626.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 3626.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 3626.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE JUNCTION NUMBER DEMAND 140 1625.00 148 2000.00 12 .00 THE FOLLOWING CHANGES IN PIPE DATA ARE SPECIFIED PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE 105 100 104 20.0 8.0 ' 120.0 13.60 .00 THERE IS A CHECK VALVE IN LINE NUMBER105 157 156 152 20.0 8.0 120.0 8.10 .00 THERE IS A CHECK VALVE IN LINE NUMBER157 THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00000 Page 7 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528039 Onsite Private Fire Protection System for Onsite Fire Hydrants Oakmont of Carlsbad 3625 gpm Fire Flow Split Between Nodes 140 and 148 1625 gpm at Node 140 and 2000 gpm at Node 148 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 3626.00 . .35 .00 .00 5.79 7.87 17 16 20 3626.00 1.26 .00 .00 5.79 7.87 21 20 24 2091.10 1.31 .00 .00 3.34 2.84 25 24 28 2091.10 .40 .00 .00 3.34 2.84 101 20 100 1534.90 .99 .00 .00 4.35 6.50 105 100 104 1534.90 .94 .00 20.26 9.80 46.85 109 104 108 1534.90 4.12 .00 .00 6.27 15.80 113 120 112 1.00 .00 .00 .00 .01 .00 115 112 114 .00 .00 .00 .00 .00 .00 117 112 .116 .00 .00 .00 .00 .00 .00 121 108 120 1.00 .00 .00 .00 .00 .00 125 108 124 1533.90 2.43 .00 .00 6.27 15.78 129 124 128 1533.90 3.57 .00 .00 . 6.27 15.78 133 128 132 1625.00 3.38 .00 .00 10.37 52.07 135 132 134 .00 .00 .00 .00 .00 .00 137 132 136 1625.00 2.29 .00 .00 10.37 52.07 139 136 138 .00 .00 .00 .00 .00 .00 141 136 140 1625.00 11.25 .00 .00 10.37 52.07 145 144 128 91.10 .02 .00 .00 .37 .08 149 144 148 2000.00 10.33 .00 00 12.76 76.49 153 152 144 2091.10 4.68 .00 .00 8.54 28.02 157 156 152 2091.10 1.66 .00 22.40 13.35 83.06 161 28 156 2091.10 1.86 .00 .00 5.93 11.53 JUNCTION NUMBER . . DEMAND GRADE LINE ELEVATION PRESSURE 16 .00 499.85 245.00 110.43 20 .00 498.59 254.00 105.99 24 .00 497.28 248.00 108.02 28 .00 496.88 245.00 .109.15 100 .00 497.59 254.00 105.56 104 . .00 476.39 254.00 96.37 108 . .00 472.27 255.00 94.15 112 1.00 47227 254.00 94.58 114 .00 472.27 254.50 94.37 116 .00 472.27 257.00 93.28 120 .00 . 472.27 257.00 93.28 124 .00 469.83 259.00 91.36 128 .00 466.27 258.00 90.25 132 . .00 462.88 260.00 87.92 134 .00 462.88 261.00 87.48 136 .00 460.59 260.00 86.92 138 .00 460.59 260.00 86.92 140 1625.00 449.35 260.00 82.05 144 .00 466.28 253.00 92.42 148 2000.00 455.96 255.00 87.08 Page 8 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Private Fire Protection System for Onsite Fire Hydrants 152 .00 470.96 251.00 95.32 156. .00 495.03 251.00 105.74 MAXIMUM PRESSURES 16 .00 499.85 245.00 110.43 28 .00 496.88 245.00 109.15 24 .00 497.28 248.00 108.02 20 .00 498.59 254.00 105.99 156 .00 495.03 251.00 105.74 MINIMUM PRESSURES 140 1625.00 449.35 260.00 82.05 136 .00 460.59 260.00 86.92 138 .00 460.59 260.00 86.92 148 .2000.00 455.96 2.55.00 87.08 134 .00 462.88 . 261.00 87.48 THE NET SYSTEM DEMAND = 3626.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 3626.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 3626.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 Page 9 of 9 APPENDIX G COMPUTER MODEL CALCULATIONS FOR. AVAILABLE FIRE FLOW AT 20 PSI RESIDUAL. AT PROPOSED FIRE HYDRANTS NODE AND PIPE DIAGRAM REFERENCE: Exhibit B in the back of the report. CONDITIONS MODELED: Available Fire Flow at Node 116 at 20 psi. Available Fire Flow at Node .120 at 20 psi. Available Fire Flow at Node 140 at 20 psi. Available Fire Flow at Node 148 at 20 psi. APPENDIX H COMPUTER MODEL CALCULATIONS FOR FIRE SPRINKLER FLOW NODE AND PIPE DIAGRAM REFERENCE: Exhibit B in the back of the report. ATTACHMENT INCLUDED: Email correspondence showing fire sprinkler system requirements. CONDITIONS MODELED: Static pressures. Fire sprinkler flow of 200 gpm at Marketing Building Node 114 Fire sprinkler flow of 430 gpm at Memory Care Building Node 134. Fire sprinkler flow of 430 gpm at Independent Living Building Node 138. Fernando Fregoso From: Gregg Wanke <gregg.wanke@oakmontsl.com> Sent: Friday, June 16, 2017 2:09 PM To: Fernando Fregoso Subject: . RE: 1672 - Water Hydraulic Questions - Fire Sprinkler Follow Up Fernando, you are correct. below are the numbers you can use. Sorry for the confusion. 3-story building = 430 GPM '@ 65 psi 2-story building = 430 GPM @ 55 psi Marketing bldg. = 200 GPM @ 40 psi Gregg Wanke Project Design 707-535-32.34 We have Moved 9240 Old Redwood Hwy. Suite 200 Windsor, Ca. 95492 From: Fernando Fregoso [mailto:Fernando@dwilsoneng.com] Sent: Friday, June 16, 2017 11:01 AM To: Gregg Wanke <gregg.wanke@oakmontsl.com> Subject: RE: 1672 - Water Hydraulic Questions - Fire Sprinkler Follow Up Gregg, I called earlier but can you double check the fire sprinkler flow and pressure requirements for each of the buildings? The' numbers presented below seem to be fire hydrant flow and pressure requirements instead of fire sprinkler requirements. I'm asking you to double check because a typical fire sprinkler requirement is 800 gpm at 70 psi. Attempting to supply a building with 3,250 gpm via a fire sprinkler lateral would put us at a 12" fire sprinkler lateral. Thank you, Fernando Fregoso Dexter Wilson Engineering, Inc. 2234 Faraday Avenue Carlsbad, CA 92008 P: (760) 438-4422 E: fernando@dwilsoneng.com 1 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis . Dexter Wilson Eng., Inc. 528-039 Onsite Fire Sprinkler System Laterals Analysis FLOWRATE IS EXPRESSED IN GPM AND PRESSURE IN PSIG A SUMMARY OF THE ORIGINAL DATA FOLLOWS PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE (FEET) (INCHES) 13 . 0 16 45.0 16.0° 120.0 .00 550.00 17 16 20 160.0 16.0 120.0 .00 21 20 24 . 460.0 16.0 120.0 .00 25 24 .28 140.0 16.0 120.0 .00 101 20 100 153.0 12.0 120.0 .00 105 100 104 20.0 8.0 120.0. 8.00 THERE IS A CHECK VALVE IN LINE NUMBER105 109 104 108 261.0 10.0 120.0 .00 113 120 112 229.0 8.0 120.0 .00 115 112 114 84.0 4.0 120.0 .00 117 112 116 261.0 8.0 120.0 .00 121 108 120 31.0 10.0 120.0 .00 125 108 124. 154.0 10.0 120.0 .00 129 124 128 226.0 10.0 120.0 .00 133 128 132 65.0 8.0 120.0 .00 135 132 134 117.0 6.0 120.0 .00 137 132 136 44.0 8.0 120.0 .00 139 136 138 115.0 6.0 120.0 .00 141 136 140 216.0 8.0 120.0 . .00 145 144 128 201.0 10.0 . 120.0 .00 149 144 148 135.0 8.0 120.0 .00 153 152 144 167.0 10.0 120.0 .00 157 156 152 20.0 8.0 ° 120.0 12.00 THERE IS A CHECK VALVE IN LINE NUMBER157 161 28 156 161.0 12.0 120.0 .00 JUNCTION NUMBER DEMAND ELEVATION CONNECTING PIPES 16 .00 245.00 13 17 20 .00 254.00 17 21 101 24 .00 248.00 21 25 28 .00 . 245.00 . 25 161 100 .00 254.00 101 105 104 .00 254.00 105 109 108 .00 255.00 109 121 125 112 / 1.00 254.00 113 115 117 114 .00 254.50 115 116 .00 257.00 117 120 .00 257.00 113 121 124 .00 259.00 125 129 128 .00 258.00 129 133 145 132 .00 260.00 133 135 137 134 . ° . .00 261.00 135 136 . .00 260.00 137 139 141 . 138 . .00 260.00 139 140 .00 260.00 141 Page 1 of 9 6 JO z abed L383I 00'PSZ 00099 00 001 LT3ET O0SP3 00099 00 83 L80ET 008PZ 00099 00 P3 L3831 00P53 00055 00 03 L13E1 0O.5P3 00099 00 91 3USS3d NOLLVA37 1N1'•I 3UV1D GNVNU .U2BNUN NOLL3Nflf 00 . 00 00 00 00 0P 951 83 191 00 00 00 . 00 00 OP 351 951 LST 00 00 00 00 00 0P Pt'I 351 £51 00 00 00 00 00 00 8P1 PVT 6P1 00 00 00 00 00 0V 831 PPI SPI 00 00 00 00 00 00 OPT 9E1 IPT 00 00 00 00 00 00 . 8E1 9E1 6E1 00 00 00 00 00 00 9E1 3E1 LET 00 00 00 00 00 00 PET 3E1 SET 00 00 00 00 00 00 3E1 831 EEl 00 00 00 00 00 OP- 831 P31 631 00 00 00' 00' .00 OP'- P31 801 S31 00' 00 00 00' 00' 00'I 031 801 131 00' 00 00' 00 00' 00' 911 311 LIT 00' 00' 00' 00' 00' 00 P11 311 511 00' 10' 00' 00 00 00'T 311 031 ElI 00' 00' 00 00 06 09 801. POT 601 00' 00' 00' 00' 00' 09' P01 001 501 00' 00' 00' 00' 00' 09 001 03 101 00' 00' . 00' 00 00' 0P 83 P3 Sz 00 00 00' 00' 00' OP , P3 03 13 00 . 00' 00' . 00' 00 001 03 91 LT 00' 00' 00 00' 00 001 91 0 El 000I/1H ALI0013A sso'I HONIW UVH dNOd.sSO1 UV1H 3,LVEMOrl.3 SON 1GON 0N 3dId BøXflSSø1d s!BXTuV ue:B&S uot;oeoi et eAt2d 6Y6EO8S :9TTJ PcsTeD 90 ;UOm(eO 55100' = A3VU3DV NY HJIIM STIL L U11.Y O2NIVIBO 3Y SJrInS3d 3HJ1 SNOS I CMV SdOOI 1 ' SMOIJ,3Nflf 33 FhLIM SdId £3 SVH N31SAS SIHJI S1flSS1d NflNINIW CRY NUNIXYN 1102 LfldLflO 3Y S2IYIYA S COI2d HDY3 J1fldLflO UV SIUS2E rIrIV :NOI,1:)3rI3S jlfldLOO 191 LSI OO'153 00' 991 LST EST 00'153 00' 3S1 6P1 00553 00' 8P1 EST 6P1 SPI 00E53 00' PVT ssjuy sui;wi ma;sAs leptuudS 6CO-8g9 'uI"ua UOSHAA .iaxaj ssCjvuy wa;s&s u0I1310.i aiij 01MAIJd 6I0 'Tg ;snny puqsj.iwj jO £113 aq; Ul ;8101d NUTAIrI JOTUOS $UOUflUØ ( Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Fire Sprinkler System Laterals Analysis 104 .00 550.00 254.00 128.27 108 .00 550.00 2.55.00 127.83 112 1.00 550.00 254.00 128.27 114 .00 550.00 254.50 128.05 116 .00 550.00 257.00 126.97 120 .00 550.00 257.00 126.97 124 .00 550.00 259.00 126.10 128 .00 550.00 258.00 126.. 53 132 .00 550.00 260.00 125.67 134 .00 550.00 261.00 125.23 136 .00 550.00 260.00 . 125.67 138 . .00 550.00 260.00 125.67 140 .00 550.00 260.00 125.67 144 .00 550.00 253.00 128.70 148 .00 550.00 255.00 127.83 152 .00 550.00 251.00 129.57 156 .00 5.50.00 251.00 129.57 MAXIMUM PRESSURES 16 .00 550.00 245.00 132.17 28 .00 550.00 245.00 132.17 24 . .00 550.00 248.00 130.87 152 .00 550.00 251.00 129.57 156 .00 550.00 251.00 129.57 MINIMUM PRESSURES . 134 .00 550.00 261.00 125.23 132 . .00 550.00 260.00 125.67 136 . .00 550.00 260.00 125.67 .138 .00 550.00 260.00 125.67 140 .00 550.00 260.00 125.67 THE NET SYSTEM DEMAND = 1.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 1.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 1.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS. THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE JUNCTION NUMBER DEMAND 114 200.00 THE FOLLOWING CHANGES IN PIPE DATA ARE SPECIFIED FOR PIPE NUMBER 13 THE VALUE OF THE FIXED GRADE IS CHANGED TO 549.4 Page 3 9f• 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Fire Sprinkler System Laterals Analysis PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE 105 100 104 20.0 8.0 120.0 1900.00 .00 THERE IS A CHECK VALVE IN LINE NUMBER105 157 156 152 20.0 8.0 120.0 .5800.00 .00 THERE IS A CHECK VALVE IN LINE NUMBER157 THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00100 Oakmont of Carlsbad Fire Sprinkler Flow To Marketing Building 200 gpm at Node 114 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 201.00 .00 .00 .00 .32 .04 17 16 20 201.00 .01 .00 .00 .32 .04 21 20 24 73.18 .00 .00 .00 .12 .01 25 24 28 73.18 .00 .00 .00 .12 .01 101 20 100 127.82 .01 .00. .00 .36 .07 105 100 104 127.82 .01 .00 . 19.63 .82 .47 109 104 108 127.82 .04 .00 .00 .52 .16 113 120 .112 201.00 .25 .00 .00 1.28 1.09 115 112 114 200.00 2.64 .00 .00 5.11 31.45 117 112 116 .00 .00 .00 .00 . .00 .00 121 108 120 201.00 .01 .00 .00 .82 .37 125 108 124 -73.18 -.01 .00 .00 -.30 -.06 129 124 128 -73.18 -.01 .00 .00 -.30 -.06 133 128 132 .00 .00 .00 .00 .00 .00 135 132 134 .00 .00 .00 .00 .00 .00 137 132 136 .00 .00 .00 .00 .00 .00 139 136 138 . .00 .00 .00 .00 .00 . .00 141 136 140 . .00 .00 .00 .00 .00 .00 145 144 128 73.18' .01 .00 .00 .30 .06 149 144 . 148 .00 .00 .00 .00 .00 .00 153 152 144 73.18 . .01 .00 .00 .30 .06 157 156 152 73.18 .00 .00 19.64 .47 ' .17 161 28 156 73.18 .00 , .00 .00 .21 .02 JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 16 .00 549.40 245.00 131.91 20 . .00 , 549.39 254.00 128.00 24 .00 549.39 248.00 130.60 28 .00 549.39 245.00 131.90 100 .00 549.38 254.00 128.00 104 .00 529.74 254.00 119.49 . 108 .00 529.70 255.00 119.04 112 1.00 529.44 254.00 119.36' 114 200.00 526.80 254.50 118.00 Page 4 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Fire Sprinkler System Laterals Analysis 116 .00 529.44 257.00 118.06 120 .00 529.69 257.00 118.16 124 .00 529.71 259.00 117.31 128 .00 529.72 258.00 117.75 132 .00 529.72 260.00 . 116.88 134 .00 529.72 261.00 116.45 136 .00 529.72 260.00 116.88 138 .00 529.72 260.00 116.88 140 .00 529.72 260.00 116.88 144. .00 529.73 253.00 119.92 148 .00 529.73 255.00 119.05 152 .00 529.74 251.00 . 120.79 156 .00 549.39 251.00 129.30 MAXIMUM PRESSURES 16 .00 549.40 245.00 131.91 28 .00 549.39 245.00 131.90 24 .00 549.39 248.00 130.60 156 .00 549.39 251.00 129.30 20 .00 549.39 254.00 128.00 MINIMUM PRESSURES 134 .00 529.72 261.00 116.45 132 .00 529.72 260.00 116.88 136 .00 529.72 260.00 116.88 138 .00 529.72 260.00 116.88 140 .00 529.72 260.00 116.88 THE NET SYSTEM DEMAND = 201.00 SUMMARY OF INFL0WS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 201.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 201.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE JUNCTION NUMBER DEMAND 134 . 430.00 THE FOLLOWING CHANGES IN PIPE DATA ARE SPECIFIED FOR PIPE NUMBER 13 THE VALUE OF THE FIXED GRADE IS CHANGED TO 548.7 PIPE NO. NODE NOS. LENGTH DIAMETER ROUGHNESS MINOR LOSS K FIXED GRADE 105 100 104 20.0 8.0 120.0 500.00 .00 THERE IS A. CHECK VALVE IN LINE NUMBER105 . Page 5 of 9 Oakmont Senior Living Project in the City of Carlsbad Private Fire Protection System Analysis Onsite Fire Sprinkler System Laterals Analysis 157 156 152 20.0 8.0 120.0 THERE IS A CHECK VALVE IN LINE NUMBER157 August 21, 2019 Dexter Wilson Eng., Inc. 528-039 1000.00 .00 THE RESULTS ARE OBTAINED AFTER 3 TRIALS WITH AN ACCURACY = .00034 Oakmont of Carlsbad Fire Sprinkler Flow to Memory Care Building 430 gpm at Node 134 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 431.00 .01 .00 .00 .69 .15 17 .16 20 431.00 .02 .00 .00 .6 .9 .15 21 20. 24 179.20 .01 .00. .00 .29 .03 25 24 28 179.20 . . .00 .00 .00 .29 .03 101 20 100 251.80 .03 .00 .00 .71 .23 105 1.00 104 251.80 .03 .00 20.05 1.61 1.65 109 104 108 251.80 .15 .00 .00 1.03 .56 113 . 120 112 1.00 .00 .00 .00 .01 .00 115 112 114 .00 .00 .00 .00 .00 .00 117 112 116 .00 .00 .00 .00 .00 .00 121 108 120 1.00 .00 .00 .00 .00 .00 125 108 124 250.80 .08 .00 .00 1.02 .55 129 124 128 250.80 .12 .00 .00 1.02 .55 133 128 132 430.00 .29 .00 . .00 2.74 4.44 135 132 134 430.00 2.11 .00 .00 4.88 18.02 137 132 136 .00 .00 .00 .00 .00 .00 139 136 138 .00 .00 .00 .00 .00 .00 141 136 140 .00 .00 .00 .00 . .00 .00 145 144 128 179.20 .06 . .00 .00 .73 .30 149 144 148 .00 .00 .00 .00 .00 .00 153 152 144 179.20 .05 .00 .00 .73 .30 157 156 152 179.20 .02' .00 20.31 1.14 .88 161 28 156 179.20 .02 .00 .00 .51 .12 JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 16 . .00 548.69 245.00 131.60 20 .00 548.67 254.00 127.69 24 .00 548.65 248.00 130.28 28 . .00 548.65 245.00 131.58. 100 . .00 548.63 254.00 127.67 104 .00 528.55 254.00 118.97 108 .00 528.41 255.00 118.48 112 1.00 528.41 254.00 118.9.1 114 . .00 528.41 254.50 118.69 116 , .00 528.41 257.00 . 117.61 120, .00 528.41 257.00 117.61 124 .00 528.32 259.00 116.71 128 .00 528.20 258.00 117.08 132 .00 527.91 260.00 ' 116.09 Page 6 of 9 Oakmont Senior Living Project in the City of Carlsbad Private Fire Protection System Analysis Onsite Fire Sprinkler System Laterals Analysis August 21, 2019 Dexter Wilson Eng., Inc. 528-039 134 430.00 525.80 261.00 114.75 136 .00 527.91 260.00 116.09 138 .00 527.91 260.00 116.09 140 .00 527.91 260.00 116.09 144 . .00 528.26 253.00 119.28 148. .00 528.26 255.00 118.41 152 . .00 528.30 251.00 120.17 156 .00 548.63 251.00 128.97. MAXIMUM PRESSURES 16 .00 548.69 245.00 131.60 28 .00' 548.65 .245.00 131.58 24 .00 548.65 248.00 130.28 156 .00 548.63 251.00 128.97 20 .00 548.67 254.00 127.69 MINIMUM PRESSURES . S 134 430.00 525.80 261.00 114.75 132 .00 527.91 260.00 116.09 136 .00 527.91 260.00 116.09 138 .00 527.91 260.00 116.09 140 .00 527.91 260.00 116.09 THE NET SYSTEM DEMAND = 431.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE 13 431.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 431.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES= .00 A SUMMARY OF CONDITIONS SPECIFIED FOR THE NEXT SIMULATION FOLLOWS THE FOLLOWING SPECIFIC DEMAND CHANGES ARE MADE JUNCTION NUMBER DEMAND 138 430.00 THE RESULTS ARE OBTAINED AFTER 2 TRIALS WITH AN ACCURACY = .00000 Page 7 of 9 Oakmont Senior Living Project in the City. of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Fire Sprinkler System Laterals Analysis Oakmont of Carlsbad Fire Sprinkler Flow to Independent Living Building 430 gpm at Node 138 PIPE NO. NODE NOS. FLOWRATE HEAD LOSS PUMP HEAD MINOR LOSS VELOCITY HL/1000 13 0 16 431.00 .01 .00 .00 .69 .15 17 16 20 431.00 .02 .00 .00 .69 .15 21 20 24 179.20 .01 .00 .00 .29 .03 25 24 28 179.20 .00 .00 .00 .29 .03 101 20 100 251.80 .03 .00 .00 .71 .23 105 100 104 251.80 .03 .00 20.05 1.61 1.65 109 104 108 251.80 .15 .00 .00 1.03 .56 113 120 112 1.00 .00 .00 .00 .01 .00 115 112 114 .00 .00 .00 . .00 .00 .00 117 112 116 .00 .00 .00 .00 .00 .00 121 108 120 1.00 .00 .00 .00 .00 .00 125 108 124 250.80 .08 .00 .00 1.02 .55 129 124 128. 250.80 .12 :00 .00 1.02 .55 133 128. 132 430.00 .29 .00. .00 2.74 4.44 135 132 134 .00 .00 .00 .00 .00 .00 137 132 136 430.00 .20 .00 .00 2.74 4.44 139 136 138 430.00 2.07 .00 .00 4.88 18.02 141 136 140 .00 .00 .00 .00 .00 .00 145 144 128 179.20 .06 .00 .00 .73 .30 149 144 148 .00 .00 .00 .00 .00 .00 153 152 144 179.20 .05 . .00 .00 .73 .30 157 . 156 152 179.20 .02 .00 20.31 1.14 .88 161 28 156 179.20 .02 .00 .00 .51 .12 JUNCTION NUMBER DEMAND GRADE LINE ELEVATION PRESSURE 16 .00 548.69 245.00 131.60 20 . .00 548.67 254.00 127.69 24 .00 548.65 248.00 130.28 28 .00 548.65 245.00 131.58 100 .00 548.63 254.00 127.67 104 : .00 528.55 254.00 118.97 108 . .00 528.41 255.00 118.48 112 1.00 528.41 254.00 118.91 114 .00 .528.41 254.50 118.69 116 .00 528.41 257.00 117.61 120 .00 528.41 257.00 117.61 124 .00 528.32 259.00 116.71 128 .00 528.20 258.00 117.08 132 .00 527.91 260.00 116.09 134 .00 527.91 261.00 115.66 136 .00 527.71 260.00 116.01 138 430.00 525.64 260.00 115.11 140 .00 527.71 260.00 116.01 144 .00 528.26 253.00 .119.28 148 .00 528.26 255.00 118.41 152 .00 528.30 251.00 120.17 Page 8 of 9 Oakmont Senior Living Project in the City of Carlsbad August 21, 2019 Private Fire Protection System Analysis Dexter Wilson Eng., Inc. 528-039 Onsite Fire Sprinkler System Laterals Analysis 156 .00 548.63 251.00 128.97 MAXIMUM PRESSURES 16 .00 548.69 245.00 131.60 28 .00 548.65 245.00 131.58 24 .00 548.65 248.00 130.28 156 .00 548.63 251.00 128.97 20 .00 548.67 254.00 127.69 MINIMUM PRESSURES 138 430.00 525.64 260.00 115.11 134 .00 527.91 261.00 115.66 136 .00 527.71 260.00 116.01 140 .00 527.71 260.00 116.01 132 .00 527.91 260.00. 116.09 THE NET SYSTEM DEMAND = 431.00 SUMMARY OF INFLOWS(+) AND OUTFLOWS(-) FROM FIXED GRADE NODES PIPE NUMBER FLOWRATE. S 13 431.00 THE NET FLOW INTO THE SYSTEM FROM FIXED GRADE NODES = 431.00 THE NET FLOW OUT OF THE SYSTEM INTO FIXED GRADE NODES = .00 LI Page 9 of 9 __-----c_--çç - PROJECT BOUNDRY \ 16 FIRE SPRINKLER ________----------- \ SERVICE LATERAL ) — — — — — c I 0 12 I I 16 I 140 ARE SP NKLLN 1 \ - ----- SERVICE ---- WR' - low120 100 04 138 I ,- \ - 108 (I \ \ 20 136 I MEMORY ri >- 105 \ I ' BUILDING BF CARE 135 \ \ \ -J co 134 128 ( ) F.F. 261.0 124 Y RE SPRINKLER ERV10E LATERAL -, I LEGEND 0) / __ TI ______ - - PROJECT BOUNDARY c..1 Co -. — \ \ I --- PRIVATE ARE SYSTEM I 49 EXISTING WATER I 144 0 : 152 pm PROPOSED ARE HYDRANT BACKFLOW ASSEMBLY I 156 \ lxxi EXISTING ARE HYDRANT \ 1 80' Ln \ 28 COMPUTER MODEL NODE NUMBER IJ \ 0 80 — \ _____ — 11491 COMPUTER PIPE NUMBER \ FEET \ - - 0) I.., 0 EXHIBIT B Co c..1 In / PRIVATE FIRE PROTECTION SYSTEM NODE AND PIPE 0 I DEXTER WILSON ENGINEERING INC DIAGRAM CONSUL11NG ENGINEERS / • (760) 438-44a2 OAKMONT OF CARLSBAD / —