Loading...
HomeMy WebLinkAboutPD 15-06; BUILDING 7710 SHELL SITE - EQUINOX; FINAL SOILS REPORT; 2021-01-065710 Ruffin Road | San Diego, California 92123 | p. 858.576.1000 | www.ninyoandmoore.com January 6, 2021 Project No. 107302006 City of Carlsbad 1635 Faraday Avenue Carlsbad, California 92008 Subject: Compaction Testing Summary Equinox 7710 El Camino Real Carlsbad, California Carlsbad Development Project: PD15-06 References: Ninyo & Moore, 2005a, Geotechnical Evaluation, La Costa Towne Center, Proposed Equinox Fitness Center, 7710 El Camino Real, Carlsbad, California, Project No. 107302005: dated April 17. Ninyo & Moore, 2005b, Geotechnical Evaluation, La Costa Towne Center, Tenant Improvements, El Camino Real and La Costa Avenue, Carlsbad, California, Project No. 107302005: dated April 17. R.A. Smith National, 2015, Grading and Erosion Control Plans for: Equinox, 7710 El Camino Real, Carlsbad, CA 92008, Sheets 1 through 18: dated December 13. To Whom It May Concern: Ninyo & Moore provided compaction testing services during the redevelopment of the Equinox project at 7710 El Camino Real in Carlsbad, California. Our services included compaction testing of the earthwork and paving operations performed for the project. This report summarizes our services and presents the results of our field and laboratory testing. PROJECT DESCRIPTION The project included the redevelopment of the site at 7710 El Camino Real in Carlsbad, California. As part of the redevelopment, additional sewer lines were installed beneath the existing building, portions of the building’s interior concrete slab-on-grade were replaced, and the parking lot was reconfigured. The reconfiguration included the construction of new curbs-and-gutters, cross gutters, and asphalt concrete (AC) pavements. Geotechnical & Environmental Sciences Consultants Ninyo & Moore | 7710 El Camino Real, Carlsbad, California | 107302006 | January 6, 2021 2 FIELD COMPACTION TESTING Our field technician was onsite on an on-call basis to test compacted fill soil, sewer trench backfill, subgrade soils, and aggregate base materials. Our field technician was also onsite full-time to observe and test the AC paving operations. Field density tests were performed by our technician in general accordance with the current version of ASTM International (ASTM) D 6938 (Nuclear Gauge Method). The specified relative compaction for compacted fill soil, sewer trench backfill, building pad subgrade, curb-and-gutter subgrade, and aggregate base materials beneath the building’s interior concrete slab-on-grade was 90 percent, as evaluated by ASTM International (ASTM) test method D 1557. The specified relative compaction for cross gutter subgrade, parking lot subgrade, and aggregate base materials placed in the paved areas was 95 percent, as evaluated by ASTM D 1557. The specified relative compaction of AC materials placed during paving operations was 95 percent, as compared to the material’s Hveem unit weight. The results of our field density tests are presented in Attachment A and the test locations are shown on Figure 1. LABORATORY TESTING Laboratory testing was performed on the soils and aggregate base materials used during the earthwork operations to evaluate their modified Proctor and optimum moisture content relationships. The modified Proctor densities and optimum moisture contents were evaluated in general accordance with the ASTM D 1557, and the results are summarized in Table 1. The modified Proctor densities and optimum moisture contents of the aggregate base material represented by Soil Type Numbers 2 and 6, were provided by the material supplier and are also presented in Table 1. The Hveem unit weights for the AC materials were provided by the supplier. Soil Type Number 101, for the paving on April 16, 2016, had a Hveem unit weight of 146.8 pounds per cubic foot (pcf). Soil Type Number 10, for the paving on August 16, 2016, had a Hveem unit weight of 143.1 pcf. SUMMARY The field density tests performed during the earthwork operations for the subject project generally indicated the specified relative compactions, after retesting the reworked areas. Based on our observations and the results of our field and laboratory tests, it is the opinion of Ninyo & Moore that the earthwork and paving operations were performed in general accordance with the referenced reports (Ninyo & Moore, 2015a & 2015b) and the project plans (R.A. Smith National, 2015). Ninyo & Moore | 7710 El Camino Real, Carlsbad, California | 107302006 | January 6, 2021 3 LIMITATIONS The compaction testing services outlined in this report have been conducted in accordance with current practice and the standard of care exercised by geotechnical consultants performing similar tasks in this area. No warranty, expressed or implied, is made regarding the observations and conclusions expressed in this report. The reported test results represent the relative compaction and moisture content at the locations tested. It is important to note that the precision of field density tests and the modified Proctor tests is not exact and variations should be expected. The reported locations and elevations of the density tests were estimated from construction staking and the referenced plans (R.A. Smith National, 2015). Further accuracy is not implied. Respectfully submitted, NINYO & MOORE Jeffrey T. Kent, PE, GE Principal Engineer JTK/RSH/gg Attachments: Figure 1 – Field Density Test Location Map Table 1 – Modified Proctor Density Test Results Attachment A – Summary of Field Density Tests Distribution: (1) Addressee (via e-mail) FIELD DENSITY TEST LOCATION MAPFIGURE 1NOTE: DIMENSIONS, DIRECTIONS AND LOCATIONS ARE APPROXIMATE. I REFERENCE: R.A. SMITH NATIONAL, DATED 12/3/15.0FEET501000N 1 107302006 FDT.DWG AOB EQUINOX7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA107302006 I 1/21Geotechnical & Environmental Sciences ConsultantsF-15S-13FILL FIELD DENSITY TESTSEWER BACKFILL FIELD DENSITY TESTSG-111SUBGRADE FIELD DENSITY TESTLEGENDAGGREGATE BASE FIELD DENSITY TESTASPHALT CONCRETE FIELD DENSITY TESTAB-23AC-24SG-63SG-56,65SG-55SG-97SG-54,66AB-15AB-14AB-16AB-17AB-18AB-19AB-20AB-21AB-22AB-23AC-1AC-2AC-4,8AC-3,7AC-5AC-13AC-14AC-19AC-15AC-16AC-20SG-110SG-111SG-102SG-109SG-108SG-106SG-107SG-78SG-72SG-105SG-103SG-104SG-76SG-77SG-73SG-14SG-8SG-9SG-7SG-100SG-101SG-74SG-94SG-75,83SG-88,93SG-25SG-61SG-99SG-60SG-62SG-58SG-59SG-98SG-57,64AC-24AC-22AC-21AC-23AC-6AC-9AC-10AC-17AC-18AC-12AC-11S-9S-12S-11SG-91SG-15SG-79,90SG-37,48SG-69SG-81SG-96SG-18SG-92SG-71SG-85,87SG-22SG-24,43SG-28SG-52SG-32SG-12SG-11SG-10SG-1SG-2,5SG-3,6SG-4SG-27SG-46SG-30,47SG-29SG-84,86SG-31SG-33,42SG-95SG-89SG-34,41SG-35,40,44SG-82SG-39,50SG-38,51SG-53,67AB-1AB-2,5AB-3AB-4SG-36SG-13SG-26SG-21,45SG-23SG-19SG-20S-13F-15F-5,9,12F-4,8,14F-3,7,11F-2,6,13F-1,10S-3S-7S-6S-5S-4S-8S-10S-1S-2SG-68SG-16,17SG-70SG-80SG-49AB-6,10AB-7,11AB-8,12AB-9,13i--r--1 • ( I I • • • • • I I I I ~ Q:-I I I I I I I JP~· f']~~i rl.Jf'. d.;.d>=> )\ PNl · fT''"i ~f3 -=.-~· NOT A PART I I ARCHITECTURAL PAVING I I I : I I • --ROOF RUNOFF / I BIOFILTRATlON PLANTER 11. • • • • • • • • • r • I I . ! I I ... I • • • • • • • • • • • • • • • • • • • -----------------NOT A PART , __ _ I $ I I I I : I I I I' I . Ninyo & Moore | 7710 El Camino Real, Carlsbad, California | 107302006 | January 6, 2021 1 of 1 Table 1 – Modified Proctor Density Test Results Soil Type Number Description Proctor/Hveem Density (pcf) Optimum Moisture Content (%) 1 Clayey SAND 118.0 12.5 2 Recycled Aggregate Base 125.0* 10.0* 3 Silty SAND 117.5 11.5 4 Clayey SAND 131.5 7.5 5 Aggregate Base 129.0 8.5 6 Recycled Aggregate Base 124.0* 11.0* 101 ½-inch AC Mix (III-C3-PG64-10) 146.8* -- 102 ½-inch AC Mix (III-C3-PG64-10) 143.1* -- Note: pcf = pounds per cubic foot *Provided by material supplier Ninyo & Moore | 7710 El Camino Real, Carlsbad, California | 107302006 | January 6, 2021 ATTACHMENT A Summary of Field Density Tests Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 110.1 107.1 108.2 109.0 92 12.5 90 1 90 1 118.0 103.7 103.3 90 102.6 8789 118.0 12.5 90 104.7 118.0 CF CF CF NG Test Of CF CF CF Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 593 CF CF CF NG DSL DSL DSL WEB WEB WEB WEB WEB DSL Test Of Block No. CF CF CF CF 90 12.5 6 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 52.5 52.8 DSL Soil Type Number 90 93 11 Relative Compaction (%)TEST RESULTS1 118.0 90 88 FAIL 7 MOISTURE 90 118.0 105.8 Corrected Maximum Density (pcf) 1 10/9/15 STANDARD& TEST COUNTS147 Sand in Cone + Hole (lbs) / (DC) 2206 CF CF Test No. 511 Sand + Bottle Before (lbs) / (DS) 10/9/15 52.6 52.8 54.0 CF10/8/15 10/9/15 10/9/15 52.3 52.8 Sand + Bottle After (lbs) / (MS) 11.3 Coarse Fraction (lbs) 117.8 12.5 12.5 9.1 9.6 118.0 98 88 90 90 12.5 92 12.5 12.5 12.512.5 11 90 111 95 91 118.0 118.0118.0 118.0 112.4 11.711.4 11.9 11.0 11.211.4 10.8 115.1 113.7 125.2 121.7120.3123.2 118.9 161145 138 166 172 NG 2206 NGNG 6 CF CF CF 1290672 724 830 609 5 579 555 NG 609 2206 NG 609 121 127 113.1 114.7 Dry Density (pcf) Percent Moisture Laboratory Maximum Density (pcf) 52.3 2206 609 8 See Figure 1 2206 23 10 10/9/15 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 1987 10 NG 1987 1987 1987 9 See Figure 1 See Figure 1 Project Name:EQUINOX Project No:107302006 784 CF Wet Density (pcf) 627627609 580 627 Pass/Fail FAIL Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) FAIL FAIL PASS PASS PASS PASSPASS PASS Retest on (if applicable) 160 627 NG 1987 627 815 168 52.8 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) 4 Test Date 10/8/15 10/8/15 10/8/15 10/8/15 Test No. 1 2 3 5 9 6 7 See Figure 1 See Figure 1 52.6 See Figure 1 See Figure 1 See Figure 1 Finer Fraction (%) 5710 Ruffin Road, San Diego, CA 92123 Test Type:Fill 107302006_FDT_CF Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Fill Finer Fraction (%) 10/9/15 10/9/15 See Figure 1 13 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 15 19 16 17 Coarse Fraction (%) Soil + Rock + Tare (lbs) Retest on (if applicable) Optimum Moisture (%) PASS Specified Relative Compaction (%) 17 1814 CF 846 15 NG PASS PASSPASSPass/Fail Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) 627 See Figure 1 See Figure 1 20 14 Test Date 10/9/15 55.0 Initials 10/9/15 Test No. 11 12 1916 Project Name:EQUINOX Project No:107302006 55.0 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 1987 627 18 1987 12 13 20 627 Percent Moisture Laboratory Maximum Density (pcf) 119.6 120.8 161 173 777 79 NG 627 1987 NG 627 CF 1987 163181 126.0 117.7 14.0 11.2 11 12.5 12.5 90 11 PASS 12.5 12.5 11.1 11.7 1322 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 55.0CF10/9/15 WEB 1987 Test No. 11.5 Coarse Fraction (lbs) 120.5 11 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 166 Sand in Cone + Hole (lbs) / (DC) 91 MOISTURE 92 118.0 108.1 TEST RESULTS1 118.0 Soil Type Number 90 90 90 105.8 90 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 54.0 54.0 WEB 90 12.5 Test Of Block No. CF CF CF CF WEB WEB WEB Test Of CF CF CF NG 821 92 118.0 94 107.7 110.5108.1 118.0118.0 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_CF Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107.0 109.5 108.3 108.7 92 12.5 90 1 90 1 118.0 109.0 106.1 90 105.8 9091 118.0 12.5 90 106.8 118.0 SM SL SM NG Test Of SM SM SM Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 804 SM SM SM NG DSL DSL DSL DSL DSL DSL DSL DSL DSL Test Of Block No. SM SM SM SM 90 12.5 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 54.0 55.0 DSL Soil Type Number 90 91 11 Relative Compaction (%)TEST RESULTS1 118.0 90 92 PASS MOISTURE 96 118.0 113.7 Corrected Maximum Density (pcf) 1 11/25/15 STANDARD& TEST COUNTS179 Sand in Cone + Hole (lbs) / (DC) 2189 SL SM Test No. 649 Sand + Bottle Before (lbs) / (DS) 11/25/15 55.5 55.5 55.5 SM11/24/15 11/25/15 11/25/15 55.5 53.5 Sand + Bottle After (lbs) / (MS) 13.0 Coarse Fraction (lbs) 128.5 12.5 12.5 10.9 13.5 118.0 90 90 90 12.5 92 12.5 12.5 12.512.5 11 90 111 91 93 118.0 118.0118.0 118.0 107.2 14.310.5 11.2 14.8 12.711.4 11.3 118.2 117.8 118.5 124.3122.1119.0 125.7 195150 149 149 148 NG 2189 NGNG 6 SM SM SM 4171470 1457 399 614 5 795 1462 NG 614 2189 NG 614 148 175 120.9 121.2 Dry Density (pcf) Percent Moisture Laboratory Maximum Density (pcf) 55.5 2189 614 8 See Figure 1 2189 23 10 11/25/15 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 2189 10 NG 2189 2189 2189 9 See Figure 1 See Figure 1 Project Name:EQUINOX Project No:107302006 784 SM Wet Density (pcf) 614614614 877 614 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASS PASS PASS PASS PASS PASSPASS PASS Retest on (if applicable) 167 614 NG 2189 614 1302 185 53.5 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) 4 Test Date 11/24/15 11/24/15 11/24/15 11/24/15 Test No. 1 2 3 5 9 6 7 See Figure 1 See Figure 1 55.2 See Figure 1 See Figure 1 See Figure 1 Finer Fraction (%) 5710 Ruffin Road, San Diego, CA 92123 Test Type:Sewer Trench Backfill 107302006_FDT_Sewer Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Sewer Trench Backfill Finer Fraction (%) 12/23/1513 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 15 19 16 17 Coarse Fraction (%) Soil + Rock + Tare (lbs) Retest on (if applicable) Optimum Moisture (%) PASS Specified Relative Compaction (%) 17 1814 15 PASSPass/Fail Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) 700 See Figure 1 20 14 Test Date 12/23/15 55.6 Initials 12/23/15 Test No. 11 12 1916 Project Name:EQUINOX Project No:107302006 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 2155 700 18 12 13 20 Percent Moisture Laboratory Maximum Density (pcf) 124.5 120.8 234 206 1584 2155 NG 700 11 PASS 12.5 12.5 15.9 14.1 1258 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 2155 Test No. 16.5 Coarse Fraction (lbs) 129.0 11 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 253 Sand in Cone + Hole (lbs) / (DC) 91 MOISTURE 94 118.0 110.7 TEST RESULTS1 118.0 Soil Type Number 90 90 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 55.6 55.6 DSL 90 12.5 Test Of Block No. SL SL SL DSL DSL Test Of SL SL SL NG 1405 90 107.4 105.9 118.0 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_Sewer Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 5710 Ruffin Road, San Diego, CA 92123 Test Type:Subgrade Finer Fraction (%) 5 9 6 7 See Figure 1 See Figure 1 55.5 See Figure 1 See Figure 1 See Figure 1 Test Date 11/6/15 11/6/15 11/6/15 11/6/15 Test No. 1 2 3 55.0 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) 4 640 NG 2035 655 1169 640 PASS PASSPASSPASS Retest on (if applicable) 196 Pass/Fail FAIL Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASS PASS PASS PASS Wet Density (pcf) 655655636 374 636 Project Name:EQUINOX Project No:107302006 784 PD 2134 10 NG 1976 2035 2035 9 See Figure 1 See Figure 1 SUMMARY OF FIELD DENSITY TESTS 12/3/15 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA Laboratory Maximum Density (pcf) 55.0 1976 636 8 See Figure 1 1976 23 10 Dry Density (pcf) Percent Moisture 115.7 113.5 226 212 542 676 NG 636 1976 NG 636 6 PD PD PD 1061677 1096 1008 636 5 210 215 216 196 NG 1976 NGNG 193 126.1 129.5 131.6123.5125.1 124.0 124.3 16.0 13.9 13.2 14.216.1 15.6 107.2 12.6 1 91 97 118.0 118.0118.0 118.0 12.5 11 90 11 91 90 90 12.5 99 12.5 12.5 12.512.5 12.5 17.2 16.4 118.0 Sand + Bottle After (lbs) / (MS) 15.6 Coarse Fraction (lbs) 125.1 55.0 55.0 55.0 PD11/6/15 11/6/15 12/3/15 55.5 55.5 PD PD Test No. 390 Sand + Bottle Before (lbs) / (DS) 12/14/15 1 12/3/15 STANDARD& TEST COUNTS202 Sand in Cone + Hole (lbs) / (DC) 1976 MOISTURE 92 118.0 108.2 Corrected Maximum Density (pcf) 90 84 FAIL 6 Relative Compaction (%)TEST RESULTS1 118.0 Soil Type Number 90 94 11 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 55.0 55.0 WEB 90 12.5 5 Test Of Block No. PD PD PD PD WEB WEB WEB PNS MJL WEB MJL MJL WEB NG 516 PD PD PD NG Test Of PD PD PD Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge) PD PD PD NG 90 107.3 9183 118.0 12.5 90 97.5 118.0 118.0 98.7 107.8 92 12.5 90 1 90 1 110.7 114.4 108.1 116.9 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_SG Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 112.2 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 115.9 117.3113.4 118.0118.0 96 118.0 99 118.0 118.0 97 118.0 118.0 112.5 108.7 NG 1152 NG CG CG Test Of PD PD PD PNS PNS CKV CKV CKV CKV CKV PNS Test Of Block No. PD PD PD PD PNS 90 12.5 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 55.0 55.0 90 95 11 118.0 90 90 111.0 94 TEST RESULTS1 118.0 Soil Type Number 90 98 MOISTURE 98 118.0 116.0 11 2/10/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 640 Sand in Cone + Hole (lbs) / (DC) 2134 2/10/16 CG Test No. 11.9 Coarse Fraction (lbs) 129.8 58.2 56.9 54.7 CG2/10/16 2/10/16 2/10/16 CG CKV 1105 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 12.5 12.5 10.7 9.3 90 92 12.5 PASS 12.5 95 12.5 9090 1 90 1111 90 90 11 12.5 12.5 12.5 12.5 106.0 12.715.0 114.6 11.4 13.0 11.111.9 16.8 131.3 129.6 121.9 126.5127.3125.3 122.8 205201262 227 287 2014 640 399799 732 767 CG CG CG NG 2014 CG 1286 1066 NG 640 2134 NG 640 640 640 128.3 123.9 Percent Moisture Laboratory Maximum Density (pcf) 2134 640 18 See Figure 1 2134 12 13 20 731 CG 2/10/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 1916 CG CG Project Name:EQUINOX Project No:107302006 55.0 55.7 14 Test Date 12/14/15 55.0 Initials 12/14/15 Test No. 11 12 640 See Figure 1 See Figure 1 2014 20 NG 2014 NG Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) PASS PASS PASS PASS PASS PASSPASS PASSPass/Fail 17 1814 PD 362 15 NG 731 2014 NG 2014 731 692 Soil + Rock + Tare (lbs) Retest on (if applicable) 185 Optimum Moisture (%) PASS Specified Relative Compaction (%) Coarse Fraction (%) 731731731 13 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 15 19 16 17 12/14/15 12/14/15 See Figure 1 See Figure 1 56.0 See Figure 1 See Figure 1 See Figure 1 56.9 Finer Fraction (%) Subgrade 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Subgrade 29 26 27 See Figure 1 See Figure 1 53.4 See Figure 1 See Figure 1 See Figure 1 2/10/16 2/10/16 Test No. 21 22 23 25 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 731 NG 2014 731 401 2014 266 CG 397 25 NG 731 CG CG 731 PASS FAILFAIL PASS Retest on (if applicable) 212 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) FAIL PASS PASS PASS Wet Density (pcf) 731731731 Project Name:EQUINOX Project No:107302006 53.724 Test Date 2/10/16 2/10/16 2/10/16 2926 CG CG NG See Figure 1 See Figure 1 27 2824 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 2/10/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 53.7 2014 731 28 See Figure 1 2014 22 23 30 30 Percent Moisture Laboratory Maximum Density (pcf) 126.4 127.9 258 243 677 1413 NG 731 2014 NG 731 CG NG 7511054 662 693 NG 2014 2014 2014 238 78 257 185 2014 244 128.9 127.0 123.3126.3119.5 126.8 131.6 16.4 10.6 17.916.1 10.7 15.7 13.3 11 9090 1 90 111 12.5 1 90 12.5 90 89 12.5 12.5 12.5 96 93 4743 90 12.5 253 12.5 12.5 17.0 15.517.5 Coarse Fraction (lbs) 120.6 2/10/16 54.2 53.2 Sand + Bottle After (lbs) / (MS) Test No. 2/10/16 STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC)472 Sand + Bottle Before (lbs) / (DS) 2/10/16 54.9 54.6 53.1 CG2/10/16 21 2014 CG CG MOISTURE 87 118.0 102.6 92 PASS 90 94 TEST RESULTS1 118.0 45 90 Dry Density (pcf) Relative Compaction (%) 118.0 118.0 Corrected Maximum Density (pcf) Soil Type Number 90 99 11 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 54.0 53.8 CKV 90 12.5 Test Of Block No. CG CG CG CG CKV CKV CKV CKV CKV CKV CKV CKV CG CG CG CKV Test Of CG CG CG Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 397 CG NG 114.6 97 113.4 118.0 116.4 118.0 87 118.0 118.0 12.5 109.8 111.5 104.6108.0 102.7110.7 118.0118.0 94 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Subgrade 39 36 37 See Figure 1 See Figure 1 58.1 See Figure 1 See Figure 1 See Figure 1 2/11/16 2/10/16 Test No. 31 32 33 35 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 644 NG 2064 644 1070 2064 177 CG 795 35 NG 644 CG CG 731 FAIL FAILPASS FAIL Retest on (if applicable) 149 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) FAIL FAIL PASS FAIL Wet Density (pcf) 644644731 Project Name:EQUINOX Project No:107302006 56.434 Test Date 2/10/16 2/10/16 2/10/16 3936 CG CG NG See Figure 1 See Figure 1 37 3834 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 2/11/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 54.7 2014 731 38 See Figure 1 2014 32 33 40 40 Percent Moisture Laboratory Maximum Density (pcf) 120.0 121.7 198 253 457 774 NG 731 2014 NG 731 CG NG 778583 945 780 NG 2064 2064 2064 269 203 151 150 2014 202 113.9 120.6 110.7109.5122.9 113.9 131.3 18.5 15.7 12.512.5 11.0 15.2 11.4 11 9090 1 90 111 12.5 1 90 12.5 90 83 12.5 12.5 12.5 99 89 445048 514041 90 12.5 243 12.5 12.5 12.9 17.315.2 Coarse Fraction (lbs) 130.5 2/11/16 58.2 58.0 Sand + Bottle After (lbs) / (MS) Test No. 2/11/16 STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC)354 Sand + Bottle Before (lbs) / (DS) 2/11/16 56.2 58.3 56.2 CG2/10/16 31 2014 CG CG MOISTURE 96 118.0 113.3 90 FAIL 42 90 88 TEST RESULTS1 118.0 90 Dry Density (pcf) Relative Compaction (%) 118.0 118.0 Corrected Maximum Density (pcf) Soil Type Number 90 87 11 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 54.2 54.5 CKV 90 12.5 Test Of Block No. CG CG CG CG CKV CKV LLB LLB LLB LLB LLB CKV CG CG CG CKV Test Of CG CG CG Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 846 CG NG 98.4 83 116.7 118.0 102.6 118.0 88 118.0 118.0 12.5 104.7 98.3 98.4106.3 103.7103.8 118.0118.0 83 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 109.2 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 113.0 113.7109.5 118.0118.0 93 118.0 96 118.0 118.0 93 118.0 118.0 111.0 108.8 NG 679 NG CG CG Test Of CG CG CG LLB LLB LLB LLB LLB LLB LLB LLB Test Of Block No. CG CG CG CG LLB 90 12.5 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 56.4 54.7 90 94 11 118.0 90 90 115.8 98 TEST RESULTS1 118.0 Soil Type Number 90 96 MOISTURE 98 118.0 115.3 41 2/11/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 132 Sand in Cone + Hole (lbs) / (DC) 2064 2/11/16 CG Test No. 9.7 Coarse Fraction (lbs) 126.5 54.0 53.4 58.1 CG2/11/16 2/11/16 2/11/16 CG LLB 687 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 12.5 12.5 11.2 11.6 93 92 12.5 PASS 12.5 93 12.5 9090 1 90 1111 90 90 11 12.5 12.5 12.5 12.5 109.7 14.012.5 110.3 10.0 14.2 14.411.1 12.0 126.3 129.7 123.4 124.5126.2122.1 124.3 2064 165 CG CG CG NG 2064 CG 440 669 NG 644 2064 NG 644 165 162 125.7 122.2 Percent Moisture Laboratory Maximum Density (pcf) 2064 644 48 See Figure 1 2064 42 43 50 644 CG 2/11/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 4946 CG CG Project Name:EQUINOX Project No:107302006 56.2 58.2 44 Test Date 2/11/16 53.7 Initials 2/11/16 Test No. 41 42 644 See Figure 1 See Figure 1 2064 50 NG 2064 NG Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) PASS PASS PASS PASS PASS PASSPASS PASSPass/Fail 47 4844 CG 45 NG 644 2064 NG 2064 644 Soil + Rock + Tare (lbs) Retest on (if applicable) Optimum Moisture (%) PASS Specified Relative Compaction (%) Coarse Fraction (%) 644644644 43 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 45 49 46 47 2/11/16 2/11/16 See Figure 1 See Figure 1 58.2 See Figure 1 See Figure 1 See Figure 1 53.1 Finer Fraction (%) Subgrade 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Subgrade 59 56 57 See Figure 1 See Figure 1 56.5 See Figure 1 See Figure 1 See Figure 1 2/25/16 2/11/16 Test No. 51 52 53 55 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 643 NG 2122 643 1841 2122 97 CG 1139 55 NG 643 CG CG 643 PASS PASSPASS PASS Retest on (if applicable) 210 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) FAIL PASS FAIL FAIL Wet Density (pcf) 643643643 Project Name:EQUINOX Project No:107302006 60.154 Test Date 2/25/16 2/25/16 2/25/16 5956 CG CG NG See Figure 1 See Figure 1 57 5854 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 2/25/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 53.2 2122 644 58 See Figure 1 2122 52 53 60 60 Percent Moisture Laboratory Maximum Density (pcf) 134.5 129.9 125 198 1094 1442 NG 643 2122 NG 643 CG NG 17221217 1183 1095 NG 2122 2122 2122 238 138 134 192 2122 214 126.8 129.8 129.8126.3118.6 128.5 125.9 9.3 8.7 5.98.5 13.5 15.1 14.4 44 9090 4 90 144 7.5 4 90 7.5 90 93 7.5 7.5 12.5 88 96 646566 90 7.57.5 7.5 7.2 13.712.8 Coarse Fraction (lbs) 120.4 2/25/16 60.4 57.1 Sand + Bottle After (lbs) / (MS) Test No. 2/25/16 STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC) Sand + Bottle Before (lbs) / (DS) 2/25/16 60.8 60.7 55.5 CG2/25/16 51 2064 CG CG MOISTURE 90 118.0 106.7 95 FAIL 67 90 87 TEST RESULTS1 131.5 90 Dry Density (pcf) Relative Compaction (%) 131.5 131.5 Corrected Maximum Density (pcf) Soil Type Number 90 85 41 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 58.0 53.6 LLB 90 12.5 Test Of Block No. CG CG CG CG PNS PNS PNS PNS PNS PNS PNS PNS CG CG CG PNS Test Of CG CG CG Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 985 CG NG 118.2 90 116.0 131.5 111.7 131.5 83 118.0 118.0 12.5 112.8 110.4 122.6125.5 108.5114.2 131.5131.5 94 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 125.3 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 109.3 121.3109.4 131.5118.0 93 131.5 92 131.5 131.5 95 131.5 131.5 118.7 124.3 NG 1884 NG PL CG Test Of CG CG CG PNS PNS BHJ BHJ PNS PNS BHJ PNS Test Of Block No. CG CG CG CG PNS 90 7.5 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 55.0 58.7 95 90 44 131.5 90 90 118.6 90 TEST RESULTS4 118.0 Soil Type Number 90 93 MOISTURE 97 131.5 127.3 61 3/2/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 153 Sand in Cone + Hole (lbs) / (DC) 2122 3/2/16 PL Test No. 9.1 Coarse Fraction (lbs) 138.9 60.7 60.1 60.0 CG2/26/16 2/26/16 2/26/16 CG PNS 1411 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 12.5 12.5 14.5 13.6 93 95 7.5 PASS 7.5 95 7.5 9590 4 95 4444 90 90 11 7.5 7.5 7.5 7.5 121.7 7.08.6 124.8 7.7 8.6 5.79.7 8.6 133.1 128.8 132.2 134.1131.9127.8 135.0 130148138 141 126 2122 155 5401626 1788 535 CG CG CG NG 2122 PL 1926 1593 NG 643 2122 NG 643 201 190 125.2 124.3 Percent Moisture Laboratory Maximum Density (pcf) 2122 643 68 See Figure 1 2122 62 63 70 643 PL 3/2/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 6966 PL PL Project Name:EQUINOX Project No:107302006 60.4 58.3 64 Test Date 2/25/16 58.0 Initials 2/25/16 Test No. 61 62 643 See Figure 1 See Figure 1 1869 70 NG 2122 NG Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) PASS PASS PASS PASS PASS PASSPASS PASSPass/Fail 67 6864 CG 1749 65 NG 643 1869 NG 1869 686 562 Soil + Rock + Tare (lbs) Retest on (if applicable) 118 Optimum Moisture (%) PASS Specified Relative Compaction (%) Coarse Fraction (%) 686686643 63 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 65 69 66 67 2/25/16 2/26/16 See Figure 1 See Figure 1 27.5 See Figure 1 See Figure 1 See Figure 1 53.2 Finer Fraction (%) Subgrade 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 111.2 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 125.2 107.1127.6 118.0131.5 97 131.5 91 131.5 118.0 94 131.5 117.5 126.0 127.2 NG 341 NG CG CG Test Of PL CG CG CKV CKV LFV CKV CKV CKV CKV CKV Test Of Block No. PL CG CG CG CKV 95 7.5 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 54.3 54.4 90 96 44 131.5 90 90 108.1 82 TEST RESULTS4 131.5 Soil Type Number 92 90 95 MOISTURE 91 131.5 119.7 71 3/3/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 127 Sand in Cone + Hole (lbs) / (DC) 2013 3/9/16 PL Test No. 6.7 Coarse Fraction (lbs) 127.7 51.1 57.5 58.0 CG3/3/16 3/3/16 3/3/16 CG CKV 1802 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 7.5 7.5 5.7 5.7 93 97 12.5 PASS 9083 11.5 95 7.5 9590 3 95 1441 90 90 44 12.5 7.5 7.5 7.5 122.4 9.84.3 110.7 4.5 4.6 8.514.8 7.7 122.9 116.4 127.7 122.1120.1131.7 133.0 188108249 101 105 2013 227 729362 301 335 CG CG CG NG 2013 PL 2052 2552 NG 739 2013 NG 739 115 116 132.3 134.9 Percent Moisture Laboratory Maximum Density (pcf) 2013 739 78 See Figure 1 2013 72 73 80 739 PL 3/3/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 7976 CG PL Project Name:EQUINOX Project No:107302006 53.4 62.0 74 Test Date 3/3/16 55.4 Initials 3/3/16 Test No. 71 72 739 See Figure 1 See Figure 1 2071 80 NG 2013 NG Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) PASS FAIL PASS PASS PASS PASSFAIL FAILPass/Fail 77 7874 CG 2884 75 NG 739 2013 NG 2013 739 407 Soil + Rock + Tare (lbs) Retest on (if applicable) 141 Optimum Moisture (%) PASS Specified Relative Compaction (%) Coarse Fraction (%) 648739739 73 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 75 79 76 77 3/3/16 3/3/16 See Figure 1 See Figure 1 58.6 See Figure 1 See Figure 1 See Figure 1 60.0 Finer Fraction (%) Subgrade 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Subgrade 89 86 87 See Figure 1 See Figure 1 56.5 See Figure 1 See Figure 1 See Figure 1 3/9/16 3/9/16 Test No. 81 82 83 85 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 664 NG 2012 664 853 2012 170 CG 632 85 NG 648 CG CG 648 PASS PASSPASS PASS Retest on (if applicable) 118 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASS PASS PASS PASS Wet Density (pcf) 664648648 Project Name:EQUINOX Project No:107302006 53.084 Test Date 3/9/16 3/9/16 3/9/16 8986 CG PL NG See Figure 1 See Figure 1 87 8884 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 3/10/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 51.1 2071 648 88 See Figure 1 2071 82 83 90 90 Percent Moisture Laboratory Maximum Density (pcf) 124.0 129.1 146 110 607 625 NG 648 2071 NG 648 CG NG 1178577 570 1380 NG 2071 2071 2012 193 199 18 180 2071 135 129.6 116.6 125.0137.0127.4 126.3 128.4 12.0 13.0 11.010.0 10.5 8.9 7.0 34 9590 1 95 433 11.5 3 90 11.5 90 95 11.5 11.5 11.5 99 91 90 12.5 129 11.5 7.5 9.6 7.511.7 Coarse Fraction (lbs) 129.5 3/9/16 53.0 54.0 Sand + Bottle After (lbs) / (MS) Test No. 3/10/16 STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC)600 Sand + Bottle Before (lbs) / (DS) 3/10/16 53.0 53.0 58.6 CG3/9/16 81 2071 PL PL MOISTURE 99 117.5 115.9 96 PASS 90 91 TEST RESULTS3 117.5 95 Dry Density (pcf) Relative Compaction (%) 117.5 117.5 Corrected Maximum Density (pcf) Soil Type Number 90 100 33 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 58.0 58.0 LFV 95 11.5 Test Of Block No. PL PL CG CG LFV LFV MJL MJL LFV LFV MJL LFV CG CG CG LFV Test Of PL PL CG Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 695 PL NG 111.8 95 116.7 118.0 117.3 117.5 97 117.5 131.5 7.5 107.1 128.0 112.6113.1 113.8120.1 117.5131.5 97 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Subgrade 99 96 97 See Figure 1 See Figure 1 54.5 See Figure 1 See Figure 1 See Figure 1 3/11/16 3/10/16 Test No. 91 92 93 95 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 586 NG 2104 669 1079 1972 158 CG 1001 95 NG 669 PL PL 669 PASS PASSPASS PASS Retest on (if applicable) 193 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASS PASS PASS PASS Wet Density (pcf) 669669664 Project Name:EQUINOX Project No:107302006 53.094 Test Date 3/10/16 3/11/16 3/11/16 9996 PL PL NG See Figure 1 See Figure 1 97 9894 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 3/11/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 54.0 2012 664 98 See Figure 1 2104 92 93 100 100 Percent Moisture Laboratory Maximum Density (pcf) 130.5 121.1 188 156 1421 2616 NG 669 2104 NG 669 PL NG 22831022 974 1048 NG 2104 2104 2104 147 118 134 154 2104 130 136.6 133.8 125.9132.2124.0 135.7 134.9 9.4 6.4 12.37.8 9.3 7.5 12.5 13 9590 1 95 344 11.5 3 95 7.5 95 95 7.5 7.5 7.5 95 95 95 12.5 136 12.5 11.5 12.5 10.47.7 Coarse Fraction (lbs) 135.6 3/11/16 60.0 56.5 Sand + Bottle After (lbs) / (MS) Test No. 3/11/16 STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC)878 Sand + Bottle Before (lbs) / (DS) 4/2/16 55.0 55.8 51.5 PL3/11/16 91 2012 PL PL MOISTURE 96 131.5 125.9 98 PASS 90 93 TEST RESULTS4 118.0 95 Dry Density (pcf) Relative Compaction (%) 131.5 131.5 Corrected Maximum Density (pcf) Soil Type Number 95 95 44 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 56.2 54.3 MJL 95 7.5 Test Of Block No. PL PL CG CG MJL JCG JVC JCG JCG JCG JCG JCG PL PL PL JCG Test Of PL PL CG Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 989 PL NG 127.5 97 125.1 118.0 125.0 131.5 96 131.5 117.5 11.5 124.5 117.5 112.1116.0 113.3109.7 117.5117.5 100 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. 122.3 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 106.7 122.1106.6 129.0118.0 90 129.0 95 129.0 129.0 95 129.0 129.0 128.0 122.3 NG NG PL PL Test Of PL CG CG PNS PNS DJR DJR DJR DJR DJR DJR Test Of Block No. PL CG CG PL JVC 95 12.5 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 51.5 76.4 95 99 55 129.0 90 95 122.8 95 TEST RESULTS1 118.0 Soil Type Number 90 90 MOISTURE 96 118.0 113.3 101 8/11/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 152 Sand in Cone + Hole (lbs) / (DC) 1972 8/11/16 PL Test No. 11.2 Coarse Fraction (lbs) 126.0 80.6 79.0 74.2 PL8/11/16 8/11/16 8/11/16 PL DJR 2233 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 12.5 12.5 10.5 10.0 95 95 8.5 PASS 8.5 95 8.5 9595 5 95 5555 95 95 11 8.5 8.5 8.5 8.5 122.9 7.45.5 122.0 9.7 7.0 6.68.1 6.0 132.0 130.2 129.7 131.3130.0140.4 130.9 12110893 71 123 2100 133 20552111 1724 1558 PL PL PL NG 2100 PL 1519 NG 606 2105 NG 694 117.9 117.3 Percent Moisture Laboratory Maximum Density (pcf) 2105 586 108 See Figure 1 2100 102 103 110 606 PL 8/11/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 109106 PL PL Project Name:EQUINOX Project No:107302006 80.9 79.4 104 Test Date 8/3/16 79.4 Initials 4/2/16 Test No. 101 102 694 See Figure 1 See Figure 1 2100 110 NG 2100 NG Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) PASS PASS PASS PASS PASS PASSPASS PASSPass/Fail 107 108104 PL 2074 105 NG 606 2100 NG 2100 606 2069 Soil + Rock + Tare (lbs) Retest on (if applicable) 114 Optimum Moisture (%) PASS Specified Relative Compaction (%) Coarse Fraction (%) 606606606 103 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 105 109 106 107 8/3/16 8/11/16 See Figure 1 See Figure 1 77.5 See Figure 1 See Figure 1 See Figure 1 78.1 Finer Fraction (%) Subgrade 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. Test Of PL Test Of Block No. PLDJR 95 8.5 Test Location See Figure 1 Elev. or Depth (ft) 76.9 TEST RESULTS5Soil Type Number MOISTURE 95 129.0 122.0 111 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 68 Sand in Cone + Hole (lbs) / (DC) 2100 Test No. 7.1 Coarse Fraction (lbs) 130.7 1995 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) Percent Moisture Laboratory Maximum Density (pcf) 606 118 112 113 120 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 119116 Project Name:EQUINOX Project No:107302006 114 Test Date Initials 8/11/16 Test No. 111 112 120 Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) PASSPass/Fail 117 118114 115 Soil + Rock + Tare (lbs) Retest on (if applicable) Optimum Moisture (%) Specified Relative Compaction (%) Coarse Fraction (%) 113 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 115 119 116 117 Finer Fraction (%) Subgrade 107302006_FDT_SG Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 112.5 114.7 115.1 122.0 89 9.5 95 5 95 5 129.0 108.5 114.0 90 115.5 9292 125.0 10.0 90 114.4 125.0 AB AB AB NG Test Of AB AB AB Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 2079 AB AB AB NG WEB WEB WEB BHJ LLB LLB LLB LLB WEB Test Of Block No. AB AB AB AB 90 10.0 5 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 55.3 55.3 WEB Soil Type Number 95 87 55 Relative Compaction (%)TEST RESULTS2 125.0 90 87 PASS MOISTURE 92 125.0 114.7 Corrected Maximum Density (pcf) 1 4/14/16 STANDARD& TEST COUNTS115 Sand in Cone + Hole (lbs) / (DC) 1976 AB AB Test No. 1883 Sand + Bottle Before (lbs) / (DS) 4/15/16 55.3 57.0 57.0 AB11/6/15 4/14/16 4/14/16 59.0 60.0 Sand + Bottle After (lbs) / (MS) 7.3 Coarse Fraction (lbs) 123.1 10.0 10.0 9.1 10.5 125.0 1311 1210 91 95 95 9.5 95 9.5 9.5 9.510.0 22 90 252 87 89 129.0 129.0129.0 129.0 111.9 9.09.4 9.0 9.1 9.39.2 8.4 124.5 125.2 122.4 133.0125.8122.6 125.1 137 122 NG 1976 NGNG 6 AB AB AB 551 636 5 1746 1869 NG 636 1976 NG 636 132 115 118.4 126.4 Dry Density (pcf) Percent Moisture Laboratory Maximum Density (pcf) 55.3 1976 636 8 See Figure 1 1976 23 10 4/14/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 1899 10 NG 2001 2001 2001 9 See Figure 1 See Figure 1 Project Name:EQUINOX Project No:107302006 784 AB Wet Density (pcf) 662662636 1819 662 Pass/Fail FAIL Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASS PASS FAIL FAIL FAIL PASSPASSFAIL Retest on (if applicable) 696 NG 2001 662 154 55.3 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) 4 Test Date 11/6/15 11/6/15 11/6/15 11/6/15 Test No. 1 2 3 5 9 6 7 See Figure 1 See Figure 1 61.0 See Figure 1 See Figure 1 See Figure 1 Finer Fraction (%) 5710 Ruffin Road, San Diego, CA 92123 Test Type:Aggregate Base 107302006_FDT_AB Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Aggregate Base Finer Fraction (%) 4/15/16 8/12/16 See Figure 1 See Figure 1 78.7 See Figure 1 See Figure 1 See Figure 1 79.4 13 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 15 19 16 17 Coarse Fraction (%) 610610610 2088 610 2298 Soil + Rock + Tare (lbs) Retest on (if applicable) 111 Optimum Moisture (%) PASS Specified Relative Compaction (%) 17 1814 AB 2300 15 NG 610 2088 NG PASS PASS PASS PASS PASS PASSPASS PASSPass/Fail Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) 696 See Figure 1 See Figure 1 2088 20 NG 2088 NG 14 Test Date 4/15/16 61.0 Initials 4/15/16 Test No. 11 12 1916 AB AB Project Name:EQUINOX Project No:107302006 81.0 79.2 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 8/12/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 1899 696 18 See Figure 1 2088 12 13 20 610 AB Percent Moisture Laboratory Maximum Density (pcf) 134.2 134.3 150 144 562 2228 NG 610 1899 NG 696 21022310 2148 2213 AB AB AB NG 2088 AB 140 118 117 2088 123 135 151 130.4 128.4 129.5126.2128.1 126.7 125.9 7.8 9.6 7.59.3 7.3 117.7 10.27.0 117.4 55 11.0 11.0 11.0 11.0 95 6 95 6666 95 95 11.0 95 11.0 95 95 95 11.0 PASS 9.5 9.5 8.8 8.5 538 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 80.5 80.7 78.7 AB8/12/16 8/12/16 8/12/16 AB DJR 1899 8/12/16 AB Test No. 8.7 Coarse Fraction (lbs) 133.6 11 8/12/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 150 Sand in Cone + Hole (lbs) / (DC) 96 MOISTURE 95 129.0 122.9 TEST RESULTS5 129.0 Soil Type Number 95 95 95 118.1 95 95 98 66 124.0 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 59.0 60.0 BHJ 95 9.5 Test Of Block No. AB AB AB AB BHJ BHJ DJR DJR DJR DJR DJR DJR AB AB Test Of AB AB AB NG 546 NG 124.0 121.0 117.2 96 124.0 95 124.0 124.0 95 124.0 123.3 117.2123.8 124.0129.0 117.5 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_AB Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 117.7 117.3 124.0 Test Of AB AB AB Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 2300 DJR DJR Test Of Block No. AB AB AB 95 11.0 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 77.2 77.0 DJR Soil Type Number Relative Compaction (%) Corrected Maximum Density (pcf)TEST RESULTS6 124.0 95 Dry Density (pcf) 95 PASS 95 95 2088 MOISTURE 96 124.0 119.3 2036 Sand + Bottle Before (lbs) / (DS) 21 Sand + Bottle After (lbs) / (MS) Test No.STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC) Coarse Fraction (lbs) 132.2 10.8 151 11.0 11.0 7.2 9.2 66 2280 2088 NG 610 115 141 126.2 128.1 Percent Moisture Laboratory Maximum Density (pcf) 75.0 2088 610 28 22 23 30 30 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 2926 See Figure 1 27 2824 Project Name:EQUINOX Project No:107302006 24 Test Date 8/12/16 8/12/16 Wet Density (pcf) 610 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASS Retest on (if applicable) 25 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 8/12/16 Test No. 21 22 23 25 29 26 27 Aggregate Base 107302006_FDT_AB Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 96 95 101 95 101 146.8 95 9792 146.8 95 146.8 AC AC AC NG Test Of AC AC AC Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 559 AC AC AC NG WEB WEB WEB WEB WEB WEB WEB WEB WEB Test Of Block No. AC AC AC AC 95 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 45.2 50.2 WEB Soil Type Number 95 97 101 101 Relative Compaction (%)TEST RESULTS101 146.8 95 97 FAIL 7 MOISTURE 96 146.8 Corrected Maximum Density (pcf) 1 4/16/16 STANDARD& TEST COUNTS79 Sand in Cone + Hole (lbs) / (DC) 1970 AC AC Test No. 567 Sand + Bottle Before (lbs) / (DS) 4/16/16 53.7 56.2 61.7 AC4/16/16 4/16/16 4/16/16 54.2 50.7 Sand + Bottle After (lbs) / (MS) Coarse Fraction (lbs) 141.3 146.8 8 90 95 95 99 101 101 95 101 101101 99 96 146.8 146.8146.8 146.8 132.8 142.9 145.2 144.7140.6142.5 141.3 9077 77 79 92 NG 1970 NGNG 6 AC AC AC 549545 557 569 636 5 615 638 NG 636 1970 NG 636 82 79 142.4 135.4 Dry Density (pcf) Percent Moisture Laboratory Maximum Density (pcf) 54.2 1970 636 8 See Figure 1 1970 23 10 4/16/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 1970 10 NG 1970 1970 1970 9 See Figure 1 See Figure 1 Project Name:EQUINOX Project No:107302006 784 AC Wet Density (pcf) 636636636 555 636 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) FAIL PASS PASS PASS PASS PASSPASS PASS Retest on (if applicable) 86 636 NG 1970 636 573 83 50.7 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) 4 Test Date 4/16/16 4/16/16 4/16/16 4/16/16 Test No. 1 2 3 5 9 6 7 See Figure 1 See Figure 1 58.7 See Figure 1 See Figure 1 See Figure 1 Finer Fraction (%) 5710 Ruffin Road, San Diego, CA 92123 Test Type:Asphalt Concrete 107302006_FDT_AC Field Density Test Sheet 2013 v 3.0 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. Asphalt Concrete Finer Fraction (%) 8/16/16 8/16/16 See Figure 1 See Figure 1 80.7 See Figure 1 See Figure 1 See Figure 1 63.1 13 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) 15 19 16 17 Coarse Fraction (%) 613613613 2133 613 484 Soil + Rock + Tare (lbs) Retest on (if applicable) 82 Optimum Moisture (%) PASS Specified Relative Compaction (%) 17 1814 AC 483 15 NG 613 2133 NG PASS PASS PASS PASS PASS PASSPASS PASSPass/Fail Coarse/Finer Fraction in Max (%) Wet Density (pcf) Corrected Maximum Density (pcf) Relative Compaction (%) Dry Density (pcf) 636 See Figure 1 See Figure 1 2133 20 NG 2133 NG 14 Test Date 4/16/16 81.5 Initials 4/16/16 Test No. 11 12 1916 AC AC Project Name:EQUINOX Project No:107302006 81.3 63.8 SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 8/16/16 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA 1970 636 18 See Figure 1 2133 12 13 20 613 AC Percent Moisture Laboratory Maximum Density (pcf) 143.0 138.5 88 85 473 488 NG 613 2133 NG 613 489488 491 481 AC AC AC NG 2133 AC 79 78 88 2133 87 95 81 135.3 137.2 136.4136.8136.2 137.0 136.2 101 102 95 102 95 102102 102102 95 95 95 95 95 96 PASS 571 Sand + Bottle Before (lbs) / (DS) Sand + Bottle After (lbs) / (MS) 80.1 79.8 79.0 AC8/16/16 8/16/16 8/16/16 AC DJR 1970 8/16/16 AC Test No. Coarse Fraction (lbs) 140.8 11 8/16/16 STANDARD& TEST COUNTSTest Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG 79 Sand in Cone + Hole (lbs) / (DC) 97 MOISTURE 96 146.8 TEST RESULTS101 146.8 Soil Type Number 95 95 95 96 95 95 102 102 143.1 Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 61.7 64.4 WEB 95 Test Of Block No. AC AC AC AC WEB DJR DJR DJR DJR DJR DJR DJR AC AC Test Of AC AC AC NG 565 NG 143.1 97 143.1 95 143.1 143.1 96 143.1143.1143.1 NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 107302006_FDT_AC Field Density Test Sheet 2013 v 2.9 I Tested material does does NOT meet the requirements of the approved project documents. The material was was NOT sampled and tested as required by the approved project documents. NOTE: Tests results shown bold italicized have been corrected per ASTM D 4718 Section 4.2 for oversize rock content. 143.1143.1 96 Test Of AC AC AC Test Type (SC/SC(SR) = Sand Cone, NG = Nuclear Gauge)NG NG 475 DJR DJR DJR Test Of Block No. AC AC AC AC 95 Initials Test Location See Figure 1 See Figure 1 Elev. or Depth (ft) 78.1 76.9 DJR Soil Type Number Relative Compaction (%) Corrected Maximum Density (pcf)TEST RESULTS102 143.1 95 Dry Density (pcf) 97 PASS 95 97 2133 MOISTURE 95 143.1 486 Sand + Bottle Before (lbs) / (DS) 21 Sand + Bottle After (lbs) / (MS) Test No.STANDARD& TEST COUNTSSand in Cone + Hole (lbs) / (DC) Coarse Fraction (lbs) 136.5 79 102102 102 95 137.1 85 488 479 NG 613 2133 NG 613 83 78 138.2 138.9 Percent Moisture Laboratory Maximum Density (pcf) 75.2 2133 613 28 2133 22 23 30 30 Permit No.: Project Street Address: Jurisdiction:CITY OF CARLSBAD Plan File No.:PD15-06 7710 EL CAMINO REAL, CARLSBAD, CALIFORNIA SUMMARY OF FIELD DENSITY TESTS 5710 Ruffin Road, San Diego, CA 92123 Test Type: 2926 See Figure 1 See Figure 1 27 2824 Project Name:EQUINOX Project No:107302006 77.824 Test Date 8/16/16 8/16/16 8/16/16 Wet Density (pcf) 613 Pass/Fail PASS Specified Relative Compaction (%) Coarse/Finer Fraction in Max (%) Optimum Moisture (%) PASSPASS Retest on (if applicable) AC 25 WET DENSITY & ROCK CONTENTTare (lbs) Sand in Cone (lbs) / (MC) Soil + Rock + Tare (lbs) Coarse Fraction (%) Finer Fraction (%) 8/16/16 Test No. 21 22 23 25 29 26 27 Asphalt Concrete 107302006_FDT_AC Field Density Test Sheet 2013 v 2.9 I