HomeMy WebLinkAbout2855 GAZELLE CT; ; FPC2020-0207; PermitPERET REPORT
Cr'city of
Carlsbad
F.iiIr1&eTr1mjt
Print Date: 02/01/2021 Permit No: FPC2020-0207
Job Address: 2855 GAZELLE CT, CARLSBAD, CA 92010-6670 Status: Closed - Fina led
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2091202000 Track #: Applied: 12/08/2020
Valuation: $162,319.90 Lot #: Issued: 12/16/2020
Occupancy Group: Project #: Finaled Close Out: 02/01/2021
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: ION IS -SPRINKLER TI (32 HEADS)
Applicant: FPContractor:
PACIFIC FIRE SYSTEMS INC PACIFIC FIRE SYSTEMS INC
DARIEN MORAN 249 E EMERSON AVE
13142 NELSON ORANGE, CA 92865-3304
CARLSBAD, CA (858) 722-9865
(858) 883-2333
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
Ffu-D -o -O2o1-
MATERIAL DATA SUBMITTAL
lonis Pharmaceuticals
Tenant Improvement
2855 Gazelle Court
Carlsbad, CA 92010
Pacific Fire Systems, Inc.
12316 Oak Knoll Rd. Suite A
Poway, CA 92064
(858) 883-2333 Phone • (858) 883-2334 Fax
April 8, 2011 Sprinkler 54a
MIRAGE® STANDARD AND
QR CONCEALED PENDENT N 1 1(1 N G47 SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
DESCRIPTION
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-pro-
file cover assembly that provides up to 1/2" (12.7 mm) of vertical adjustment. The two-
piece design allows installation and testing of the sprinkler prior to installation of the
cover plate. The 'push-on", "thread-off' design of the concealed cover plate assembly
allows easy installation of the cover plate after the system has been tested and the
ceiling finish has been applied. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out
of service or removing the sprinkler.
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approval: Class 2015
NYC Approved: MEA 89-92-E, Volume 32
VdS Approved: Certificate G4080021
LPCB Approved: Ref. No. 096e112
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032
Refer to Approval Chart 1 and Design Criteria on page 54c for cULus Listing requirements, and refer to Approval Chart 2
and Design Criteria on page 54d for FM Approval requirements that must be followed.
TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum
7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by
locating "250" stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metrict)
Glass-bulb fluid temperature rated to -65°F (-55°C)
Patents Pending
*cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
tMetric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C 19500 for Sprinkler VK462 Viking Technical Data may be found on
Phosphor Bronze UNS-051000 for Sprinkler VK463 The Viking Corporation's Web site at
Deflector Pins: Stainless Steel Alloy http://www.vikinggroupinc.com.
Bulb: Glass, nominal 3 mm diameter The Web site may include a more recent Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel edition of this Technical Data Page. UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Yoke: Phosphor Bronze UNS-051000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Form No. F 103005 Replaces page 54a-f, dated February 25, 2011. (Revised LPCB Approval.
- Removed UL listing from 165 OF Cover 15394. Obsoleted sprinkler 14697.)
Sprinkler 54b April 8, 2011
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Cover Assembly Materials:
Cover: Copper UNS-C11000
Base: Brass UNS-C26000 or UNS-C26800
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Mirage' Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
Sprinkler: Base Part No. 13503A or HP Base Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:
Temperature Suffix (°F/°C): 155°/68° = B, 175°I79° = D, 200°/93° = E
For example, sprinkler VK463 with a 155°F/68°C temperature rating = 13667AB.
Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part No. 15394
(square cover plate, 3-5/16" diameter)
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B,
Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/l, Painted Black = M-/B
Temperature Suffix (°F/°C): 1350/570 UL (1390/590 FM and LPCB) = A, 165°/740 = C
For example, cover 13504 with a Polished Chrome finish and a 165°F/74°C temperature rating = 13504FC.
Note: Square cover plate 15394 cULus Listing is for the 135°F (57°C) temperature rated cover plate only. Refer to the Approval Chart.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Sprinkler Wrenches**:
Heavy Duty Wrench Part No. 14047W/B (available since 2006), or
Head Cabinet Wrench Part No. 14031*** (available since 2006)
Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover
(available since 2007)
—Requires a 1/2" ratchet (not available from Viking). ***Optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
April 8, 2011 Sprinkler 54c
MIRAGE® STANDARD AND
QR CONCEALED PENDENT
sJ W*j SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Temperature Sprinkler Nominal Maximum Ambient Temperature Rating of Cover
Classification Temperature Rating' Ceiling Temperature' Assembly (Required) Bulb Color
Ordinary 155°F (68°C) 100°F (38°C) Red 139'F (59°C) FM and LPCB
Intermediate 175°F (79°C) 150°F (65°C) 165°F (74°C) Yellow
Intermediate 200°F (93°C) 150°F (65°C) 165°F (74°C) Green
Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted
White, Painted Ivory, or Painted Black
Footnotes
1 The sprinkler temperature rating is stamped on the sprinkler deflector.
2 Based on NFPA-1 3. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
CUSTO
zcl 0
Identification of Custom Paint Color:
All custom color pointed cover plates will
have an identifying label affixed to the
inside of the cover that indicates custom
color and will have a representative sample
(a paint dot) of the paint on the label,
Figure 1: Identification of Custom Paint Color for Concealed Covers
DO NOT PAINT
3-5/16" (84,1 mm)
Figure 2: Square Cover Assembly 15394
Sprinkler 54d April 8, 2011
MIRAGE® STANDARD AND
QR CONCEALED PENDENT NIKJWG4j SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
SprnkIer Temperature Rating Approval Chart I (UL) j— coverPlateTemperatureRating
Miragetm Concealed Pendent Sprinklers VK462 and VK463 fAWI4- Cover Plate Finish KEY
I NPT Thread I Nominal I Maximum I Listings and Approvals4 Sprinkler I SIN
I I Size I I K-Factor I
Water Working I (Refer also to Design Criteria below.)
I Inch mm I U.S. I metric' I cULus' I NYC I VdS I LPCB I CE Base Part No.1 Pressure
Standard Response Applications
13503A VK462 1/2" 15 5.6 80.6 1 175 psi (12 bar) I -- -- AYI,CZ1 AY1,BZ1 AY1,CZ17
Quick Response Applications
13503A I VK462 I 1/2" 15 I 5.6 I 80.6 J 175 psi (12 bar) AV1, BX1 AV1, BW16--
13667A I VK463 I 1/2" 15 5.6 80.6 I 250 psi (17.2 bar)' AV1, BX1 I AV1, BW16 -- -- -
Cover Plate Assembly Temperature Ratings8 Cover Plate Assembly Finishes9
Sprinkler Temperature Ratings V - 135°F (57°C) cULus Listed cover 135041, 136421 (large diameter), 1 - Polished Chrome, Brushed Chrome, or 153941 (square cover plate) A- 155°F (68°C) W- 165°F (74°C) cover 135041 or 136421 (large diameter) Bright Brass, Antique Brass,
B - 175°F (79°C) and 200°F (93°C) X - 165°F (74°C) cover 135041, or 136421 (large diameter) Brushed Brass, Brushed Copper,
C - 200°F (93°C) Y - 135°F (57°C) cover 135041 LPCB Approved as 139°F (59°C) Painted White, Painted Ivory, or
Z - 165°F (74°C) cover 135041 Painted Black
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
The Water Working Pressure rating is stamped on the deflector.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any
additional approvals.
Listed by Underwriter's Laboratories for use in the U.S. and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 32.
((Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032.
8 The 135/139°F cover has an orange label. The 165°F cover has a white label.
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA -UL
(Also refer to Approval Chart 1 above.)
cULus Listing Requirements:
Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
For hazard occupancies up to and including Ordinary Hazard, Group II.
Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
Minimum distance from walls is 4 in. (102 mm).
Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SRI-3 or QRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed
in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD,
VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-
dards, whenever applicable.
April 8, 2011 Sprinkler 54e
MIRAGE® STANDARD AND
QR CONCEALED PENDENT
NIKJNG4 SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Approval Chart 2 (FM) SprInMerTemperature Rating
Mirage Standard Response Concealed Pendent Sprinkler VK462 L Awl* Cover Plate Finish KEY
-- Sprinkler Base NPT Thread Size Nominal K-Factor Maximum FM Approvals3
Part No.' SIN Water Working (Refer also to Design Criteria below.) Inch mm U.S. metric2 Pressure
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AWl, BX1
Cover Plate Assembly Temperature Ratings4 Cover Plate Assembly Finishes'
Sprinkler Temperature Ratings w - 139°F (59°C) cover 135041, 136421 (large diameter), 1 - Polished Chrome, Brushed Chrome, Bright
A- 155°F (68°C) or 153941 (square cover plate) Brass, Antique Brass, Brushed Brass,
B - 175°F (79°C) and 200°F (93°C) X - 165°F (74°C) cover 135041, 136421 (large diameter), Brushed Copper, Painted White, Painted
or 153941 (square cover plate) Ivory, or Painted Black
Footnotes
1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional
approvals.
The 139°F cover has an orange label. The 165°F cover has a white label.
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERIA -FM
(Also refer to Approval Chart 2 above.)
FM Aooroval Requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page
SRI-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-
cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
NEVER install the sprinkler
by applying the installation
wrench across the frame arms,
DU NOT over-tighten.
Use only the designated
sprinkler wrench, Viking Part
Number 14047W/B or 14031.
Sprinkler
Wrench
Flat rinkler
cx me
Arms
2-1/4' (57,2 mm)
diameter opening
is required in
the ceRing,
bly
ap
Dr
.ise
)IE)
Sprinkler
Wrench
(Port No.
4047
is shown)
Sprinkler 54f April 8, 2011
MIRAGE® STANDARD AND
QR CONCEALED PENDENT "J II(1I1Gj SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
A 1/2' ratchet
s required (not
ilalole from Viking),
Step 1: Carefully slide the
wrench sideways around
the deflector and pins.
Step 2: Carefully press the
wrench upward and turn slightly
to ensure engagement with the
sprinkler wrench flats.
DO NOT apply more than
25 ft. tbs. of torque. A leak
tight seal should be achieved
by turning the sprinkler
clockwise 1 to 1-1/2 turns
beyond finger tight.
Figure 3: Sprinkler Installation and Correct Use of Wrenches
NPT
(15 mm)
L 29/16 2 -1/16
3 /16; (65 mm) (52 mm)
- Maximum Minimum
_77777714:.
r-LIL
2-3/4" (70 mm) or
3-5/16' (84.1 mm)]
Note: Upon sprinkler activation, the deflector descends
to approximately 13/16" (20,6 mm) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Form No. F_103005 Replaces page 54a-f, dated February 25, 2011. (Revised LPCB Approval.
Removed UL listing from 165 °F Cover 15394. Obsoleted sprinkler 14697.)
YOULL MOOSE'
'TUBE
APPROVALS AND SPECIFICATIONS
ASTM A135, Grade A
ASTM A795, Type E, Grade A
Pressure rated to 300 psi
Underwriters Laboratories-
United States of America
Underwriters Laboratories-Canada
Factory Mutual
NFPA-13
NFPA-13R
NFPA-14
CIVIL DEFENSE APPROVAL-
United Arab Emirates
Made in the United States of America
UL, ULC & FM listed for roll-groove,
plain-end and welded joints for wet, dry,
preaction and deluge sprinkler systems.
LEED v4 Certified
SCHEDULE 10 & 10 SPRINKLER PIPE SUBMITTAL DATA SHEET
FINISHES AND COATINGS
Schedule 10 & 40 Sprinkler Pipe receives an 00 mill coating of water-based
paint which has corrosion protection expected with a painted carbon
steel product, i.e. it would be expected to resist corrosion for an
extended and indefinite period in a clean and dry environment and,
as environmental conditions deteriorate, the corrosion protection
would also diminish.
Schedule 10 & 40 Sprinkler Pipe (black) receives an ID mill coating of Eddy
Guard II MIC preventative coating. EG2 has been tested at
independent laboratories to resist bacterial growth and maintain
minimal bacterial count after multiple flushes (25) of the pipe.
Schedule 10 & 40 Sprinkler Pipe when Hot Dip Galvanized by ASTM A123
and supplied by Bull Moose Tube is UL listed and FM approved.
PRODUCT IDENTIFICATION
Every length of Bull Moose fire sprinkler pipe features large, easy-to-
read, continuous stenciling, clearly identifying the manufacturer, type
of pipe, size, and length.
0 ipy ow 91
1.0. (In) 1.097 1.442 1.682 2.157 2.635 3.260 4260 6.357 8249
Empty WeIght (Ib/ft)
LWater
1.410 1.810 2.090 2.640 3.530 4.340 5.620 9.290 16.940
Filled Weight (lb/ft) 1.800 2.518 3.053 4.223 5.893 7.951 11.796 23.038 40.086
C.R.L* 1527 9.91 7.76 6.27 4,92 3.54 2.50 1.158 1.805
Pieces per Lilt -
-
- 0.0. (in)
91 1 61 61 37 30 1 19 1 19 10 1
1.315 1.660 1.900
-
-
0.0. (In) 1.315 1.660 1.900 2375 2.815 3.500 4.500 6.625 8.625
2.375 2.875 3.500 4.500
- I.D. (IN) 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Empty Welght(lb/ft) 1.680 2.270 2.720 3.660 5.800 1.580 10.800
Water Filled Weight (Ib/ft) 2.055 2.978 3.602 5.114 7.875 10.783 16.316
t.R.R.* 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Pieces per Lift 70 51 44 30 30 19 19
*Calculated using Standard UL CRR formula, UL Fire Protection Directory, Category VIZY
SUBMITTAL INFORMATION (~D C(& <.8>
Project
ContractorL
Engineer
Specification I Reference
System Type Date r
Locations [
Comments
ED Schedule 10- Black C) Schedule 10- Hot Dip Galvanized C) Schedule 40-Black () Schedule 40- Hot Dip Galvanized
BULL]V[DDSETU B E.GDM 1I1I) '3, iAX
Fig. 200 - "Trimline" Adjustable Band Hanger
Fig. 200R (Import) - "Trimline" Adjustable Band Hanger
w/Retainer Ring
C®US USTED
MPOtb
Size Range - 1/2 thru 8" pipe
Material - Carbon Steel, Mil. Galvanized to G90
specifications
Function - For fire sprinkler and other general piping
purposes. Knurled swivel nut design permits hanger
adjustment after installation.
Features -
(1/2" thru 2") Flared edges ease installation for
all pipe types and protect CPVC plastic pipe
from abrasion. Captured design keeps adjusting
nut from separating with hanger. Hanger is eas-
ily installed around pipe.
(21/2' thru 8") Spring tension on nut holds it
securely in hanger before installation. Adjusting
nut is easily removed.
Approvals - Underwriters' Laboratories listed
(1/2" thru 8') in the USA (UL) and Canada (cUL)
for steel and CPVC plastic pipe and Factory Mutual
Engineering Approved (3/4' thru 8"). Conforms to
Federal Specifications WW-H-171E, Type 10 and
Manufacturers Standardization Society SP-69, Type
10.
Maximum Temperature - 650°F
Finish - Mil. Galvanized. Stainless Steel materials will
be supplied with (2) hex nuts in place of a knurl nub.
Order By - Figure number and pipe size
Note - Figure 200R (import) with retainer ring and
non-captured knurl nut.
Dimensions • Weights
Pipe Rod Size Max. Rec. Approx.
Size Inch Metric A B Load Lbs. Wt./100
1/2 3/8 8mm orlomm 31/ 25/8 400 11
3/4 3/8 8mm 0r10mm 31/8 21/2 400 11
1 3/8 8mm or 10mm 3/8 25/8 400 12
11/4 3/8 8mm or 10mm 33/4 2/8 400 13
11/2 3/8 8mm or 10mm 37/8 2/8 400 14
2 3/8 8mm or 10mm 41/2 3 400 15
21/2 3/8 10mm 55/8 41/8 600 27
3 3/8 10mm 57/8 4 600 29
31/2 3/8 10mm 73/8 51/4 600 34
4 3/8 10mm 73/s 5 1000 35
5 1/2 12mm 91/8 61/4 1250 66
6 1/2 12mm 101/8 63/4 1250 73
8 1/2 12mm 131/8 83/4 1250 136
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX: 951.737.0330
CUSTOMER SERVICE • 800.786.5266
www.tolco.com
Fig. 65
Dimensions • Weights
Rod Size Max. Rec. Approx. A B C D E F Load Lbs.* Wt./100
3/8 13A6 3/4 1 7/16 1 610 28
1/2 11/2 3/4 1 9/16 11/4 1130 55
5/8 11/2 3/4 1 9/16 11/4 1130 55
* Max. loads for clamp with set screw in up or down position.
Fig. 66
Dimensions • Weights
Rod Size Max. Rec. Approx. A B C D E F Load Lbs.* WtJ100
3/8 1A6 11/4 1 7/16 1 610 28
1/2 11/2 11/4 1 9/16 11/4 1130 55
5/8 11/2 11/4 1 9/16 11/4 1130 55
* Max. loads for clamp with set screw in up or down position.
Fig. 65 and Fig. 66
Reversible C-Type Beam Clamps 314" and 11/4" Throat Openings
Component of State of
California OSHPD Approved c 1k us LISTED Seismic Restraints System
Size Range - (Fig. 65 and Fig. 66) 3/8, 1/2 and 5/8 rod
Material - Carbon Steel with hardened cup point set screw and
jam nut
Function - Recommended for hanging from steel beam where flange
thickness does not exceed 3/4 (Fig. 65) or 11/4 (Fig. 66).
Features - All steel construction eliminates structural deficiencies
associated with casting type beam clamps. May be used on top or
bottom flange of the beam. (Beveled lip allows hanging from top
flange where clearance is limited.) May be installed with the set
screw in up or down position. Offset design permits unlimited rod
adjustment by allowing the rod to be threaded completely through the
clamp. Open design permits inspection of thread engagement.
Approvals - Underwriters' Laboratories Listed in the USA (UL) and
Canada (cUL). Exceeds requirements of the National Fire Protection
Association (NFPA), Pamphlet 13, 3/8 rod will support 1/2' thru 4
pipe, 1/2 rod will support 1/2 thru 8 pipe. Included in our Seismic
Restraints Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For additional
load, spacing and placement relating to OSHPD proiects, please refer
to the TOLCO Seismic Restraint Systems Guidelines.
Finish - Plain
Note - Available in Electro-Galvanized and HDG finish.
Order By - Figure number, rod size and finish
Fig. 65 Patent #4,570,885
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH 951.737.5599 • FAX 951.737.0330
ii CUSTOMER SERVICE • 800.786.5266
wwwfolco.com
Fig. 69 - Beam Clamp Retaining Strap
Size Range - 3/8 thru 7/8 rod by 4 thru 16 length.*
Material - Pre-Galvanized Steel
Function - To offer more secure fastening of various types
of beam clamps to beam where danger of movement might
be expected. NFPA 13 requires the use of retaining straps
with all beam clamps installed in earthquake areas. Satisfies
requirements of NFPA 13 (2010) 9.3.7.1.
Important Note - Good installation practice of a retaining
strap requires that the strap be held tightly and securely to all
component parts of the assembly. Therefore a locking mech-
anism of some kind such as a hex nut or the beveled locking
slot on the TOLCO® Fig. 69R will provide a more secure
reliable installation.
Approvals - Underwriters' Laboratories listed in the
USA (UL) and Canada (cUL). Approved for use with any
listed beam clamp. Included in our Seismic Restraints
Catalog approved by the State of California Office of
Statewide Health Planning and Development (OSHPD). For
additional load, spacing and placement information relat-
ing to OSHPD projects, please refer to the TOLCO Seismic
Restraint Systems Guidelines.
Finish - Pre-Galvanized
Order By - Figure number, type, length "B" and rod size
being used with beam clamp
Note - Minimum return on Strap: 1
Dimensions
Type Rod Size A Hole Size B
1 3/8 7/16
1/2 9/16
Specify
Specify
2 5/8 11/16
3/4 13/16
Specify
Specify
3 3/8 -7/8 Specify Specify
* Longer lengths are available, consult factory.
Component of State of
California OSHPD Approved I: @L LISTED Seismic Restraints System
OFFICE/MANUFACTURING FACILITY • 1375 SAMPSON AVE. • CORONA, CA 92879 • PH: 951.737.5599 • FAX 951.737.0330
CUSTOMER SERVICE • 800.786.5266 • A
www.tolco.com
0-
DESCRIPTION SAMMYSO MODEL # HANG ROD SIZE 01? MSTR
Hangennate+ For Concrete - Internally Threaded
PFM221 1100 1/4" x 1-5/8" CST 200 Vertical 1/4' 25 125
1/4" x 1-5/8" CST 20 Vertical 3/8' 25 125
PFM221 1250 1/4x2-1/2" CCST516 Vertical 3/8' 25 125
- Hangermate+ For Concrete - Externally Threaded
lDhiJI 1/4" x 1-5/8" - Vertical 3/8" 25 125
1!JEI1IIII 1/4" x 2.1/2" - Vertical 3/8" 25 125
Hangermate+ Pivot For Concrete - Angled Applications
lM5III 1/4 x 2" SH-GST/CST 20 Variable 3/8" 25 125
Hangermate+ Suspender For Concrete - Dual-Directional
- VNJrlhts1II 5/16" x 2-1/4 ' - Vert. & KarL 3/8" 25 125
The Complete Anchoring Solution - histallaUon Accessories and Tools
DESCRIPTION HANGERMATE+ OTY MSTR 01?
1/4" Socket Driver Concrete Rod Hanger 1 5
I1OOflP1øI 3/8" Socket Driver Concrete Rod Hanger 1 5
1/2" Drive Socket Externally Threaded
ccrete Rod Hanger 1 -
- 5'2*IKIl1!I Suspender Driver Suspender 1 5
rP3dPJ!II Pivot Driver Pivot 1 5
1/2 impact Ratedw External 1 - Deep Socket
bk'P1IAlI 1/4" Hex to 1/2" Square Adapter
hIM 1/4" X 6" (4" usable length) SDS+ Full Head Carbide Masonry Dull Bit
IYV.MOhJ Hex Shank SDS-Plus (only for Pivot for Concrete)
1mi1I Adapter for hanging 1/2" rod (3/8" to 1/2' Adapter)
20V MAX* Brushless Rotary Hammer
IIi!W1PJ 20V MAX* XR Brushless 3-Speed Impact Driver
I'
20V MAX* Lithium Ion 3/8" Impact Wrench
Cordless Threaded Rod Cutter
* Maximum initial battery voltage (measured without a workload) Is 20 volts. Nominal voltage Is 18.
\JSTM Product Specifications I Hole-Cut System
MODEL V-723 SADDLE-LET (Small Mechanical Tee)
Ffi~~
The Model 723 Saddle-Let is the ideal outlet fitting for direct connections to sprinkler
heads, drop nipples and or gauges. No need for welding, lust cut or drill a hole at the
desired outlet location. Position the Saddle-Let so that the locating collar fits within the
hole and secure with the U-bolt and nuts. The Saddle-Let comes with a standard black
finish or as an option can be supplied electro zinc plated or painted orange. The Saddle-
Let allows full bore flow and is pressure rated to 300 psi (20 bar).
c®uS <::@> LISTED APPROVED
Hole Dia. Dimensions-mm'n Take-Out
Nominal Size +1.6,-0/+0.063,-0 T Bolt Size Bolt Torque Weight
mm/in mm/in A B C mm/in in N-M/Lb-Ft Kgs/Lbs
32 x 15 30 53.0 89.0 56.0 35.0 3/8e 20-30 0,4
1.25 x 0.5 1.18 2.08 3.50 2.20 1.38 U-Bolt 15 -22 0.9
32 x 20 30 53.0 89.0 56.0 35.0 3/8e 20-30 0.4
1.25 x 0.75 1.18 2.08 3.50 2.20 1.38 U-Bolt 15 -22 0.9
32 x 25 30 56.0 89.0 56.0 38.0 3/8o 20-30 0.4
1.25 x 1 1.18 2.20 3.50 2.20 1.50 U-Bolt 15-22 0.9
40 x 15 30 55.0 89.0 56.0 35.0 3/80 20 -30 0.4
1.5 x 0.5 1.18 2.16 3.50 2.20 1.38 U-Bolt 15-22 0.9
40 x 20 30 55.0 89.0 56.0 35.0 3/8e 20 -30 0.4
1.5 x 0.75 1.18 2.16 3.50 2.20 1.38 U-Bolt 15-22 0.9
40 x 25 30 58.0 89.0 56.0 38.0 3/8e 20 -30 0.4
IS x 1 1.18 2.28 1 3.50 2.20 1.50 U-Bolt 15-22 0.9
sox 15 30 64.0 98.0 56.0 42.0 3/8o 20 -30 0.4
2 x 0.5 1.18 2.51 3.85 2.20 1.65 U-Bolt 15-22 0.9
50 x 20 30 64.0 98.0 56.0 42.0 3/8e 20 -30 0.4
2 x 0.75 1.18 2.51 3.85 2.20 165 U-Bolt 15-22 0.9
SO x 25 30 67.0 98.0 56.0 45.0 3/8o 20 -30 0.4
2 x 1 1.18 2.63 3.85 2.20 1.77 U-Bolt 15-22 0.9
65 x 15 30 69.0 111.0 56.0 51.0 3/8e 20 -30 0.4
2.5 X 0.5 1.18 2.71 4.37 2.20 2.00 U-Bolt 15-22 0.9
65 x 20 30 69.0 111.0 56.0 51.0 3/80 20-30 0.4
2.5 x 0.75 1.18 2.71 4.37 2.20 2.00 U-Bolt IS-22 0.9
65 x 25 30 72.0 111.0 56.0 54.0 3/8e 20 -30 0.5
2.5 x 1 1.18 2.83 4.37 2.20 2.13 U-Bolt 15-22 1.1
Hole diameters listed are suggested hole saw diameters.
1: Take-out (Center of run to end of pipe to be engaged)
Trusted above all TM 25 N ~ YJ W63",