HomeMy WebLinkAbout221 NORMANDY LN; ; FPR2019-0029; Permit(ity of
Carlsbad
Print Date: 12/14/2020
Job Address: 221 NORMANDY IN, CARLSBAD, CA 92008-2223
Permit Type: FIRE-Construction Residential Work Class:
Parcel U: 2030231600 Track U:
Valuation: $0.00 Lot #:
Occupancy Group: Project U:
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U:
Plan Check U:
Project Title:
Description: SCHIFF RESIDENCE -NEW 13D SPRINKLER SYSTEM
Permit No: FPR2019-0029
Status: Closed - Finaled
Single Family Fire Sprinkl
Applied: 03/28/2019
Issued: 04/10/2019
Finaled Close Out: 07/06/2020
Inspector:
Final Inspection:
Applicant: FPContractor:
VANGUARD FIRE PROTECTION INC VANGUARD FIRE PROTECTION INC
MAX HICKMAN 417 CARLSBAD VILLAGE DR
417 CARLSBAD VILLAGE DR CARLSBAD, CA 92008-2302
CARLSBAD, CA 92008-2302 (760) 727-8540
(760) 727-8540
FEE AMOUNT
FIRE NFPA 13D Single Family System (Insp/Bldg) $125.00
FIRE NFPA 13D Single Family System (Plan Review) $246.00
Total Fees: $371.00 Total Payments To Date: $371.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
f f&2.619 -,o 002,1
SCHIFF RESIDENCE Drawing Date:2-27-19
Page 1 HYDRAULIC DESIGN INFORMATION SHEET
Job Name: SCHIFF RESIDENCE
Location: 221 NORMANDY LN
CARLSBAD, CA 92008
Drawing Date: 2-27-19
Contractor: VANGUARD FIRE PROTECTION
P0 BOX 1300
VISTA CA 92085-1300
760-727-8540
Designer: SB
Calculated By: SprinkCAD
www.sprinkcad.com
451 N. Cannon Ave.
Lansdale, PA 19446
Construction: V-B
Reviewing Authorities : CFD
Remote Area Number: 1
Telephone:
Occupancy: RES
SYSTEM DESIGN
Code:NFPA 13D Hazard: System Type:WET
Area of Sprinkler Oper. 512 sq ftl Sprinkler or Nozzle
Density (gpm/sq ft) RES I Make: SENJU
Area per Sprinkler 256.0 sq ftl Model: RCRES
Hose Allowance Inside 0 gpm I K-Factor: 4.90
Hose Allowance Outside 5 gpm Temperature Rating: 162
CALCULATION SUMMARY 2 Flowing Outlets
gpm Required: 31.6 psi Required: 47.0 @ Source
WATER SUPPLY
Water Flow Test I Pump Data
Date of Test 2-27-19 I Rated Capacity 0 gpm.
Static Pressure 74.0 psi I Rated Pressure 0.0 psi I
Residual Pres 73.9 psi I Elevation 0
At a Flow of 31 gpm I Make: I
Elevation 0" Model: I
Location: METER
Source of Information: CWD
SYSTEM VOLUME 19 Gallons
Notes:
SCHIFF RESIDENCE Drawing Date:2-27-19
Page 2 HYDRAULIC CALCULATION DETAILS
HYDRAULIC
QTY DESCRIPTION LENGTH C ID
TOTALS
Hydr Ref W Required at Hyd Area 1
26.3 psi
1 1" CPVC 90 Eli 5' 150 1.101
1 Pipe 1" PV 8' 150 1.101
Elevation Change 8'0"
1 1" Thrd Check Valve Generic NFPA Va 5' 120 1.049
Hydr Ref BOR Required at BASE OF RISER
33.2 psi
1 i" Sweatd 90 Eli 3' 150 0.995
1 Pipe 1" Kx21 Copper 3' 150 0.995
1 1" Sweatd 90 Eli 3' 150 0.995
Fixed Flow Outside Hose Allow.
1 Pipe 1-1/4" PVx15 60' 150 1.380
3 1-1/4" CPVC 90 Eli 18' 150 1.380
1 1" Thrd Other Valve METER " " w/Bai CHART LOSS
1 Pipe 1" Kx21 Copper 5' 150 0.995
Elevation Change 2'0"
FLOW LOSS
gpm psi
27
27 1.4
27 0.9
3.5
27 1.1
27
27 0.7
27 0.6
27 0.7
5 gpm
32 3.0
32 2.3
32 4.3
32 1.3
0.9
Hydr Ref SC Required at Source
47.0 psi
Water Source 74.0 psi static, 73.9 psi residual S 31 gpm 32 gpm
73.9 psi
SAFETY PRESSURE
26.9 psi
Available Pressure of 73.9 psi Exceeds Required Pressure of 47.0 psi
This is a safety margin of 26.9 psi or 36 % of Supply
Maximum Water Velocity is 9.1 fps
SCHIFF RESIDENCE Drawing Date:2-27-19
Page 3
FITTING NAME TABLE
ABBREV. NAME
C Coupling
E 90' Standard Elbow
F 45' Elbow
S Straight Flow Thru Tee
T 90' Flow Thru Tee
V Valve
LEGEND
HYD REF Hydraulic reference. Refer to accompanying flow diagram.
K FACTOR Flow factor for open head or path where Flow (gpm) = K x -\/P
Qa Flow added or subtracted
Qt Total flow
DIA Actual internal diameter of pipe
C Hazen Williams pipe roughness factor
Pf/ft Friction loss per foot of pipe
PIPE Length of pipe
FTNG'S Number of fittings. See table above.
TOTAL Total length (PIPE + FTNG'S)
Pt Total pressure (psi) at fitting
Pe Pressure due to change in elevation
where Pe = 0.433 x change in elevation
Pf Friction loss (psi) to fitting
where Pf = 1 x 4.52 x (Q/C)"1.85 / ID'4.87
Pv Velocity pressure (psi)
where Pv = 0.001123 x Q"2/ID"4
Pn Normal pressure (psi), where Pn = Pt - Pv
NOTES:
- Pressures are balanced to 0.01 psi. Pressures are listed to
0.1 psi. Addition may vary by 0.1 psi due to accumulation of
round off.
- Calculations conform to NFPA 13.
- Velocity Pressures are not considered in these Calculations
SCHIFF RESIDENCE Drawing Date:2-27-19
Page 4
NODE ELEVATION SPRINKLER PRESSURE ACTUAL MINIMUM
ACTUAL
NUMBER K-FACTOR FLOW FLOW
DENSITY
(FT) (GPM/(PSI"*)) (PSI) (GPM) (GPM)
(GPM/SQ. FT)
1 27.50 7.0
is 27.00 4.90 7.0 13.0 13.0
0.05
2 27.50 7.7
2S 27.00 4.90 7.7 13.6 13.0
0.05
10 27.50 8.7
W 8.50 26.3
Max velocity of 9.05 occurs in the pipe from 10 TO W
Nodes with "S" indicate a node at the top of a sprig or bottom
of drop pendent. The node without an "5" is on the branch.
SCHIFF RESIDENCE Drawing Date:2-27-19
Page 5
HYD. Qa DIA. FITTING PIPE Pt Pt
REF "C" TYPES FTNG'S Pe Pv ******* NOTES
*******
POINT Qt Pf/ft TOTAL Pf Pn
PATH 1 FROM HYDRAULIC REFERENCE 1 TO W (PRIMARY PATH)
12.98 1.101 1E 0.50 7.0 7.0 K = 4.90
is C=150 5.00 -0.2 0.0
12.98 0.031 5.50 0.2 7.0 Vel = 4.42
1.101 4E
-------------------------------------------------------------------------
30.52 7.0 7.0 EqK = 4.92
1 C=150 iT 26.00 0.0 0.0
12.98 0.031 is 56.52 1.7 7.0 Vel = 4.42
13.63 1.101 3E
-------------------------------------------------------------------------
45.47 8.7 8.7
10 C=150 4T 36.00 8.2 0.0 See PATH 2
26.61 0.115 is ------------------------------------------------------------------------- 81.47 9.4 8.7 Vel = 9.05
W 26.61 26.3 K = 5.18
PATH 2 FROM HYDRAULIC REFERENCE 2 TO 10
13.63 1.101 1E 0.50 7.7 7.7 K = 4.90
2S C=150 5.00 -0.2 0.0
13.63 0.033 5.50 0.2 7.7 Vel = 4.64
1.101 iT
-------------------------------------------------------------------------
20.71 7.7 7.7 EqK = 4.91
2 C=150 4S 9.00 0.0 00
13.63 0.033 ------------------------------------------------------------------------- 29.71 1.0 7.7 Vel = 4.64
10 13.63 8.7 K = 4.62
UNITS - DIAMETER (INCH) LENGTH (FOOT) FLOW (GPM) PRESSURE (PSI)
FPK2019,00
tyco Fire & Building
IjProducts
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
,a
rapid response TU
HOME FIRE SPRINKLER SYSTEM
BlazeMaster
CPVC Fire Sprinkler Pipe & Fittings
Submittal Sheet
General
Description
Tyco® CPVC Pipe and Fittings pro-
duced by Tyco Fire & Building Prod-
ucts (TFBP) are designed exclusively
for use in wet pipe automatic fire sprin-
kler systems. The Tyco CPVC Pipe
and Fittings are produced from Blaze-
Master® CPVC compound that is a
specially developed thermoplastic
compound composed of post chlorin-
ated polyvinyl chloride (CPVC) resin
and state of the art additives. Tyco
CPVC Pipe and Fittings are easier to
install than traditional steel pipe sys-
tems, and at the same time, provide
superior heat resistance and strength
as compared to traditional CPVC and
PVC piping materials used In the
plumbing trade. Various adapters are
available to connect CPVC pipe to me-
tallic piping. All female pipe thread
adapters have brass inserts for dura-
bility. Grooved adapters connect di-
rectly to grooved end valves and me-
tallic pipe, with flexible grooved end
couplings.
NOTICE]
Tyco® CPVC Pipe and Fittings pro-
duced with BlazeMaster® CPVC com-
pound described herein must be in-
stalled and maintained in compliance
with this document and with the appli-
cable standards of the National Fire
Protection Association, in addition to
the standards of any authorities having
jurisdiction. Failure to do so may im-
pair the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Technical
Data
Sizes
3/4" to 3"
Maximum Working Pressure
175 psi
Approvals
UL, FM, C-UL, NSF, LPCB MEA, and
the City of Los Angeles. (Refer to In-
stallation Handbook 111-1900 dated
June 2008 for exact listing/approval
information.)
Manufacture Source
U.S.A.
Material
Pipe: ASTM F442, SDR 13.5
Fittings: ASTM F438 (Sch. 40) and
ASTM F439 (Sch. 80), ASTM F1970
Color
Orange
Blaz&MastetO is a registered trademark
of The Lubrizol Corporation
Page lof2 JUNE, 2008 TFPI9I5
Page 2 of 2 TFP19IS
Installation
Tyco® CPVC Pipe and Fittings pro-
duced by Tyco Fire & Building Prod-
ucts (TFBP) are to be installed in
accordance with installation Hand-
book 111-1900 dated June 2008.
Care and
Maintenance
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any
authority having jurisdiction. The in-
stalling contractor or product manufac-
turer should be contacted relative to
any questions.
Automatic sprinkler systems should be
inspected, tested, and maintained by a
qualified Inspection Service in accord-
ance with local requirements and/or
national codes.
NOTICE
Before closing a fire protection system
control valve for inspection or mainte-
nance work on the fire protection sys-
tem that it controls, permission to shut
down the affected fire protection sys-
tem must first be obtained from the
proper authorities and all personnel
who may be affected by this action
must be notified.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
toring proprietary and/or central sta-
tion alarms.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
®Porrw RESIDENtiAL RISER
The Symbction ..
Service Pressure: Up to 175 PSi (12,07 BAB) O Minimum Flow Rate for Alarm .8-lOGPM(30.38 I-PM).
Maximum Surge:. 18 FPS (5,5 rn/a)
a, Usage: Listed CPVC plastic piping systems manufactured by
Central Sprinkler Corp., Grinnell Sprinkler Corp., Spears I Manufacturing Co., Hervel and lP( (Scepter).
Fltspip&zes..l',1.1/41-i/2'and2'
Environmental Specifications:
) Indoor use only
-.
Temperature range: 40t92Q,(4;5°çIo4C)
Service Use:
One or two family dwelling NFPA.130
Flow Switch
Enclosure: Die-cast, red powdetat finish
Cover held In place with tamper resistant screws.
ContactRtings: TWO sets of8PDT (Form C)
I.i . .,. 15.0 Amps at 125/250 VAC
• ....... . . 2.0 Amps at30 VW'
Conduit Entrances Two knockouts provided for 1/2. conduit.
Switch Contacts: SPOT (Form C)
Contact Rating: 3 Arhpa at 260VAC ............
Terminatloner 8' No. 22 AWO Wlre Leads
Caution:. This device is gist Intended for applications In explosive
environments.
FIG. 1
to NOT ttait cuwi ,•
wren
WQWI 50
CiTt i5
AMSTWG
MAN ci
SW 0-w ou MOOS a Som
arm - ci
I/a. ci
APPROX. RETARD SETTINGS ON SEC.)
0 A B C 0 E
0 10.25 20.40....3555 5040 60-90
Retard Adjustment:
To change time, turn retard adjusting knob (either direction) for desired time
delay. Use the minimum amount of retard necessary to prevent false alarms
A -B' setting Is usually adequate for this. Factory set at W.
FIG.2 OPTIONAL
REUEF
VALVE K)T
sac assa
Main Riser
® .Pów-$wflcti ..... . -
,® Test and Drain.
iir NPT female filling for relief valve
m. roes-s
7 07 1
- SENJU SPRINKLER CO., LTD
Residential Lead Free Flat Concealed Sprinkler,
Pendent,
Model: RC-RES, K-Factor: 4.9, SIN: SS8464
GENERAL DESCRIPTION
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. They
are decorative and fast responding. The Cover Plate Assembly hides the Deflector, Heat Responsive. Element etc., which is
concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small. (2-5/8 inch, 68mm). The
push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy installation of the cover plate.
Therefore, the Màdel RC-RES should be your first choice when aesthetics is the major consideration for ultimate appeal and
unbeatable performance is desired. The Model RC-RES is designed for residential occupancies and is perfect for use in homes,
hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential• sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 130; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per NFPA 13.
The Model RC-RES has a 4.9 (70.6 LPM/bar12) K-factor that meets the required residential flow rates ,ith minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements.
For extended installation flexibility, the Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of
pipe lengths. .
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape or
evacuate in case of a fire. However, residential fire sprinkler systems are not a substitute for fire safety awareness or fire safety
construction required by building codes.
Lead Free" is defined In the Reduction of.Lead in Drinking Water Act (S.3874) endorsed by AWWA's Water Utility Council, and
California Assembly Bill #1953 as having.less than or equal to a weighted average of 0.25% lead in wetted surface of pipes,
plumbing fittings and fixtures.
WARNINGS -
The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as In
compliance with the applicable standards of the National Fire Protection Association regulations and the standards of
any other authorities having June dlctlon
In the event of this condition, consult the authorities having jurisdiction for guidance and approval.
Failure to do so may impair the integrity of these devices.
It Is the responsibility of the installing contractor to provide a copy of this document to the owner or their
representative, and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner.
The owner Is responsible for maintaining their fire protection system and devices in proper operating condition. The
Installing contractor or sprinkler manufacturer should be contacted with any related questions.
Document No. U085165 Date : Jan/11/2019
Page 2 of 8
TECHNICAL DATA
Approvals: 0UL9 Listed, NSF-61 .6
Sprinkler Identification Number (SIN): SS8464
Maximum Working Pressure: 175ps1 (12.1 bar)
Discharge Coefficient (Nominal K-Factor):
K=4.9 GPM/psi112 (70.6 LPM/bar112)
Temperature Rating:
162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate
175°F (79°C) Sprinkler with 140°F (60°C) Cover Plate
175°F (79°C) Sprinkler with 162°F (72°C) Cover Plate
Color Code (Sprinkler)
162°F (72°C): Uncolored
175°F (79°C) White
Color Code (Cover Plate)
140°F (60°C): No Mark
162°F (720C): White-Colored Mark
Vertical Adjustment: 112 inch (12.8 mm)
Cover Plate Finishes:
Standard Finishes-
White, Ivory, Beige, Brown, Black, Nickel,
Wood Grain
Custom Finishes-
Custom color and custom pattern cover plates are
available on special order. Contact a Senju
Sprinkler representative with any custom orders.
Please see chart on Page 8 for more detail.
Physical Characteristics: Ref. Figures 1 and 1-1
1-1'IO tQDmm)
Marking
Year of Mavuracture - -
'::
rk
F19C
Me £' Control No. _- 607
(Copper Alloy), -
. Deflector (Pttosptorus Broyze)
Casket P1FE) 25/8 ('68mm) (4 Fusible Metal (Solder) or 3 1/4 (0 83nsi,) l) Heat Collector (Copper)
,rfjoare (06nm) (Si Cover Plate As
FIGURE 1. Model RC-RES K-4.9
OPERATION
In case of fire, the solder component that holds together the Cover Plate and the Retainer melts. Then the, Cover Plate is
released at once. As a result, the Deflector drops down to the intended position. Two Heat Collectors are exposed to fire, and
when sufficient heat from the fire Is reached, internal components of the sprinkler fall apart. This leads to the water flow to be
distributed on the affected fire area. (Ref. Figure 2)
Document No.U085165 Date : Jan/11/2019
Page 3 of 8
DESIGN CRITERIA
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
NOTES
Residential Fire Sprinkler Systems should only be designed and Installed by Individuals who are completely familiar
with automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it Is recommended that the
sprinkler system designer review and develop a working understanding of the complete fist of criteria prior to initiating
the design of the sprinkler system.
Questions concerning sprInkler installation and usage criteria, which are not covered by the following instructions
should be submitted to your contracted company. Include sketches and technical details, as appropriate.
In some Instances, the requirements of this document may concern specifications which are more stringent, and which
take precedence over those specified in NFPA 13, 130, 13R, or by the authority having jurisdiction.
The Model RC-RES must not be used In applications where the air pressure above the ceiling Is greater than that below.
Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the
cup are open and free from any air flow Impediment
The spray from the sprinkler Is distributed radially outward and downward from the sprinkler deflector. Consequently,
the sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers,
overhangs or other parts of the dwelling structure.
The number of sprinklers within each compartment (as defined by NFPA 13, 13D, or 13R) must be kept as few as
possible. Do NOT use more sprinklers thaA necessary to cover a particular space.
Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured In place by firmly fastening the
sprinkler system piping to the structure. If the sprinkler is not property secured In position, reaction forces resulting
from sprinkler operation could alter its orientation and its water distribution pattern.
Obstruction to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers.
General Service Conditions
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Heat Source Criteria
Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to the exposure of a heat source other than an actual fire.
Available Sprinkler Temperature Ratings
Sprinkler Temperature
Classification
Sprinkler Nominal
Temperature Rating
Maximum Ambient Ceiling
Temperature
Temperature Rating of the
Cover Plate Assembly
Ordinary 162°F (72°C) 100°F (38°C) 140°F (60°C)
Intermediate 175°F (79°C) ,150°F(66°C) 140°F (6OC)"
Intermediate 175°F (79°C) 150°F (66°C) 162°F (72°C)
1) Maximum ambient temperature for the Cover Plate Assembly is 100°F. (38°C).
Precautionary Warnings for Corrosive Environments
Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the
following:
Chlorine ion and Chloride environment
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to this
environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an actual fire.
Sprinkler system piping with Copper.
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for copper
piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828, and CDA
(Copper Development Association) - Solder Joint)
All residual flux must be removed from the interior and exterior of the copper piping by thoroughly flushing before
installation of the Sprinkler Heads. Otherwise, residues of flux may cause corrosion and/or leakage in the sprinkler system.
Document No. U085165 Date : Jan/11/2019
Page :4 of B
Hydraulic Design Criteria
The minimum required sprinkler flow rates for systems designed to NFPA 13D or 13R are given in TABLE A as a function of
temperature rating and the maximum allowable coverage area. The sprinkler flow rate is the minimum required discharge from
the most hydraulically demanding sprinkler from each of the total number of "design sprinklers" as specified in. NFPA 130 or
13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding sprinklers.
The minimum required discharge from each of the four sprinklers is to be the greater of the following:
The flow rates given in TABLE A for NFPA 13D and 1.3R as a function of temperature rating and maximum allowable
coverage area.
A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.mj over the "design area" comprised of the four most hydraulically
demanding sprinklers for the actual coverage area being protected by the four sprinklers.
TABLE A. NFPA 13D & 13R WET PIPE HYDRAULIC DESIGN CRITERIA for Model SS8464
For systems with ceiling types smooth flat horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as
applicable. I -
Ordinary Intermediate . Maximum Maximum Temperature Rating Temperature Rating Minimum Coverage
Area Spacing 162°F (72°C) 175°F (79°C) Deflector Installation Spacing
Ft. x Ft. Ft. to
Ceiling Type Ft. Flow Pressure Flow Pressure
(m xm) (m) GPM PSI GPM PSI (m)
(LPM) (bar) (LPM) (bar)
12x12 12 13 7.0 13 7.0
(3.7x3.7) (3.7) (49.2) (0.48) (49.2) (0.48) Smooth
Ceilings
1014 14 13 7.0 13 7.0 3/8 to 718
(4.3x4.3) (4.3) (49.2) (0.48) (49.2) (0.48) Inches.
Beamed 15x15 15 13 7.0 13 7.0
(4.6x4.6) (4.6) (49.2) (0.48) (49.2) (0.48) Ceilings
per NFPA
13D, 13R Concealed 8
(2.4) 16x16 16 13 7.0 14 8.2 or 13
(4.9x4.9) (4.9) (49.2) (0.48) (53.0) (0.57) Installed
in beam
3/8 to 7/8
18x18 18 17 12.0 18 13.5 inches
(5.5x5.5) (5.5)- (64.3) (0.83) (68.1) (0.93) below -
bottom of
beam. 20x20 20 21 18.4
(6.14.1) (6.1) (79.5) (1.27) - -
For coverage area dimensions less than the above mentioned, it needs to use the minimum required flow for the
Next Higher Coverage Area listed. -
Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
Sprinkler Spacing Criteria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond the
coverage area calculated by using the specific hydraulic factors. (Ref. TABLE A)
Document No. U085165 Date . Jan/11/2019
Page:50f8
INSTALLATION
The Model RC-RES must be installed in accordance with the following instructions:
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which
show deformation or cracking in either the Sprinkler or the Protective Cap.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the
potential for damage to the sprinklers that could cause improper operation or non-operation.
The Protective Cap must remain on the sprinkler during installation. After the Installation is completed, the Protective
Cap must be removed to place the sprinkler in service.
Use a torque of 7 to 14 ft•Ibs (9.5 to 19.0 Nm) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended
maximum torque, this could result In damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is
prohibited and may cause damage to the sprinkler.
In case of insufficient adjustment in Cover Plate Installation, do not try to overly tighten, screw the sprinkler too loosely
or make any modification to the cover plate assembly., Readjust the sprinkler fitting for a better fit.
Do not rotate the Cap Remover RC to the left with force when, placing the two hook arms into place. The Installed
sprinkler may become loosened, which may cause water leakage.
Installing Procedure
Step I
The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the waterway
perpendicular to the ceiling. Install the sprinkler fitting so that the distance from the face of the fitting to the mounting surface
will be nominally 2 inches (50.8mm) as shown in Figure 3.
Step 2
With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler fitting. Then tighten it with the
Socket NR-H or Ratchet (318" drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must fit perfectly
with the grooves on the Sprinkler for proper Installation (Ref. Figure 4).
Step 3
If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the ceiling
material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation can be
started with a 2-318 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the "Vertical Adjustment" indicator on the
Protective Cap to check for proper installation height (Ref. Figure 3).
Step 4
Use the Cap Remover RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover Plate Assembly on
the Cup of the Sprinkler by hand until its flange just has contact with the ceiling (Ref. Figure 6 and Figure 7). Stop tightening
the Cover Plate Assembly once the flange has contact with the ceiling If the ceiling has been lifted from its normal position in
the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as necessary. If the flange of the Cover
Plate Assembly cannot contact the ceiling sufficiently, readjust the sprinkler fitting as necessary. When properly installed,
there Is nominal 1116 inch (1.6mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 6.
Document No.U085165 Date . Jan/11/2019
or
77
I - \Surface E - rew
Def1ectO/ . 4
(tbo$oon)j
or 3-1/4" (83mm)
or 2-5/8'souare (068mm>
IINCQRREthI CORRCT1 IINCORRECTI
Document No. U085165 Date : Jan/11/2019
Page :7 o18
CARE AND MAINTENANCE
The following instructions must be implemented for the maintenance and service of the Model RC-RES.
NOTES
Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F/40C to prevent freezing and bursting
of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. Operation of the heat respàsive element can result.
Absence of a Cover Plate Assembly may delay the response time of the sprinkler In case of a fire.
Install the cover plate assembly properly, as shown In Figure 6. Improper installation of the cover platiassembly may
cause Improper operation or non-operation.
If the ceiling Is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint
does not seal off any of the air gap.
Factor,' painted Cover Plates must not be repainted. They should be replaced, If necessary, by factory painted cover
plates.. Non-factory applied paint may adversely delay or prevent sprinkler operation in case of a fire.
Do not pull the Covr Plate. Separation may result
In preparation for maintenance of the fire protection system, permission to close the main control valve must be
obtained from the proper authorities, and all affected parties by this action, and must be Informed before the
maintenance session can commence.
Do NOT enclose any sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning fluids, or other, chemicals. Remove
dust, lint cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a
soft bristle (i.e., dusting) brush attachment. -
Exercise suitable safety precautions in the use and storage of highly flammable materials. The rapid rate of The
development and spread of these materials can reduce the ability of the sprinkler system to aid in the control of a fire
Involving such hazards.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must be kept in a cool and dry place.
Automatic sprinklers must never be physically altered, such as painted, plated, or coated, once shipped from the
factory. If the sprinklers have been in any way modified, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation.
Damaged units because of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential fire protection service
and which have the same nominal K-Factor, the same coverage area, and the same or lower flow ratings (as indicated
under TABLE A "Hydraulic Design Criteria").
When remodeling, such as by adding false beams or light fixtures or changing the location of compartment walls, first
verify that the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter
the new construction and/or the sprinkler system to suit the requirements of this document and the applicable NFPA
regulations.
The owner Is responsible for the maintenance of the sprinkler system, including inspection and testing of its
compliance with this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25),
and the regulations of any other authorities having Jurisdiction. The owner should direct any questions regarding the
above rules and regulations to the Installing contractors or the sprinkler manufacturer. It is recommended that
automatic sprinkler systems be Inspected, tested, and maintained by a qualified Inspection Service in accordance with
NFPA 25.
Document No. U085165 Date : Jan/11/2019
Page 8 of 8
ORDER PROCEDURE
When placing an order, please contact a local distributor with the following information (Model Name, Temperature Rating and
Finish).
Sprinkler
Model: RC-RES
(SIN: SS8464, Residential Fiat Concealed Sprinkler, Pendent, K4.9, Temperature: 162°F (72°C) or 175°F (79°C))
Cover Plate Assembly, .,
2-5/8 inch (68mm) or 3-1/4 inch (t83mm) or 2-5/8 inch square (068mm), Order Separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and finishes. -
Standard Finishes Custom Finishes
White Ivory Beige Brown Black Nickel Copper Wood Grain Custom Color Custom Pattern
2-5/8° Round, 140°F o a - - - - - - 0 0
3-1/4° Round, 140°F o o o - a o o a a o o
2-5/8" Square, 140°F o - - - - - - - a
2-5/8° Round, 162°F
3-1/4" Round, 162°F
Toots for Installation of Model RC-RES
Socket NR-H
For use with a 3/8" drive ratchet (not included)
Socket NR-H Plastic
For use with a 1/2" drive ratchet (not included)
Cap Remover RC
11 Document No. U085165 Date : Jan/11/2019
tqca Worldwide I Contacts www.tyco-fire.com
Series TY-FRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in light or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces • the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet 1FP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertai ning to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
Identification.
Number (SIN)
TY313.... Upright 5.6K, 1/2 in. NPT
TV323 .... Pendent 5.6K, 1/2 in. NPT
Technical
Dätä
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi (17.2 bar)
only applies to the listing by Underwriters Laborato-. ries, Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psl (80,6 LPM/bar)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Rècéssed Escutcheon: White Coated
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Sealing Assembly . . . Stainless Steel w/TEFLON
Bulb...............................Glass
Compression Screw .................Bronze
Deflector ..........................Bronze
AUGUST 2018
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
TFPI72
2-7/8 (73,0 mm) DIA. -.
TFPI72
Page 2 of 4
Components:
1 - Frame
2 - Button
3 - Sealing
Assembly
* Temperature rating is ** Pipe thread connections per ISO 7-1 4 - Bulb indicated on Deflector. can be provided on special request. 5 - Compression
Screw ESCUTCHEON PLATE 1/2° 7/16° (11,1 mm)
6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN
7/16°
I (11,1mm)
NOMINAL 2
MAKE-IN _____ (50,8 mm)
I
2" 1-3/8°
(50,8 mm) -- (34,9 mm)
WF
U"
1/2" NPT** DEFLECTOR*
STYLE 15 or 20
RECESSED
ESCUTCHEON
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
WRENCH RECESS e?
(USE ONLY
END °A)
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
f,.
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not Install any bulb-type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm)forthe 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 N.m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 N'm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 Nm).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
TFPI72
Page 3 of 4
Care and
Maintenance
The TYCO Series TV-FR B, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible-for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
"Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
- 2-7/8° DIA.
(73,0 mm)
2-1/4° DIA.
FACE OF (57,2 mm)
5/8(15,9mm)
SPRINKLER
FITTING
3/8±5/16 I
(9,5±7,9 mm)
FLUSH
MOUNTING 1/8"
SURFACE —__(3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm)
TYFRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER 2-1/4° DIA.
1/2" (12,7 mm) 5/16±1/4° \
#(3,2
FIlliNG (57,2 mm)
(7,9*6,4 mm) FLUSH
717,
MOUNTING
SURFACE m)
CLOSURE SERIES MOUNTING 1-3/8° (34,9 mm)
TV-FRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
TFPI72
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR TYPE TEMPERATURE BULB UQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED I POLYESTER-
135°F(570C) Orange
UPRIGHT
(1Y313) 155°F(68°C) Red
175°F (79°C) Yellow and 1i 2, 3,4, 5,.6
5.6
1/2 in. NPT
PENDENT
(TY323)
________________
200°F (93°C) Green
286°F (141°C) Blue
135°F (57°C) Orange
RECESSED
PENDENT
(1Y323)
Figures 45 and 5b
1, 2,3,4 55°F (68°C) Red
75°F (790C)
r2,00-F
Yellow
(93°C) Green
Notes:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details, contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-44.44/Fax 31-54-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094aJ06) as Quick Response Sprinklers.
Where Polyester Coated Sprinklers are noted to be UL and C-Ut. Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Installed with Style 15(1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20(1/2 in. NPT) 1/2 In. Total Adjustment Recessed Escutcheon, as applicable.
C. Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLEA
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na77_X)X__XXX_________
F SPRINKLER TEMPERATURE S N FINISH RATINGS
I 370 I 5.6K UPRIGHT (1/2 in.NPT) I TY313 I
371 1 5.6K PENDENT (1/2 in.NPT) 1Y323
Notes:
a. Use suffix "I" for ISO 7-1 connection: for example,
77-370-4-175-I
1 I NATURAL BRASS
PURE WHITE (RAL9010)a
POLYESTER
SIGNAL WHITE (RAL9003)
POLYESTER
JET BLACK (RAL9005)
POLYESTER
9 I CHROME PLATED
135 135-F (57-C)
155 155-F (68-C)
175 175-F (79-C)
200 200°F (93°C)
286 286-F (141-C)
Notes:
a. Eastern Hemisphere sales only
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway, Lansdale, PA 194461 Telephone +1-215-362-0700
02018 Joh,,o,, Controls. AR rieht. re,wvod. *11 o8I.tin..nd oth b,fon,,e80,, .how,, --t -.f d o,o.droloIon d.t.nd or. .obl.ol to 0..gvwftWA ootioo, Johnson
Controls TEFL.ONI 0 098to,odt,udwwl,olooPwt