HomeMy WebLinkAbout1966 OLIVENHAIN RD; ; FPC2019-0101; PermitCL7city of Carlsbad Print Date: 12/14/2020 Job Address: 1966 OLIVENHAIN RD, CARLSBAD, CA 92024-5676 Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm Parcel 4*: 2550310300 Track 4*: Valuation: $1,167,147.57 Lot 4*: Occupancy Group: Project 4*: DEV02001 #of Dwelling Units: Plan 4*: Bedrooms: Construction Type: Bathrooms: Orig. Plan Check 4*: Plan Check 4*: Project Title: OLIVENHAIN MUNICIPAL WATER DIST Description: OLIVENHAIN MWD - FIRE ALARM AS-BUILTS Permit No: FPC2019-0101 Status: Closed - Finaled Applied: 04/18/2019 Issued: 05/07/2019 Finaled Close Out: 08/17/2020 Inspector: Final Inspection: Applicant: FPContractor: ELECTRONIC CONTROLS SYSTEM LLC ELECTRONIC CONTROL SYSTEMS LLC RICHARD SAYLORS 12575 KIRKHAM CT 12575 KIRKHAM CT P0 WAY, CA 92064-8844 POWAY, CA 92064-8844 (858) 513-1911 (858) 813-1911 - FEE AMOUNT FIRE Reinspection (per inspection) $193.00 FIRE TI Fire Alarm System $620.00 Total Fees: $813.00 Total Payments To Date: $813.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov ift2-ovi -oic Albireo Energy Partnering for Success Administration Building Olivenhain Water District 1966 Olivenhain Road Encinitas, CA 92024 Product Data Submittal Fire Alarm Tenant Improvement July 13, 2020 Albireo Energy. 12575 Kirkham Ct • Poway, CA 92064 • Phone: 858-513-1911 • www.albireoenergy.com I Albireo Enerev Partnering for Success Table of Contents 1. Equipment ES-200X Fire Alarm Control Panel FCPS-24FS6 NAC Power Supply ANN-80 Annunciator SD355 Photoelectric Smoke Detector SD355R Remote Test Capable Smoke Detector B21OLP Smoke Detector Standard Base D355PL Duct Smoke Detector Housing BG-12LX Manual Pull Station MDF-300 Dual Monitoring Module CRF-300 Control Relay P2RL Wall Mount Horn/Strobe PC2RL Ceiling Mount Horn/Strobe SCRL Ceiling Mount Strobe Albireo Energy• 12575 Kirkham Ct . Poway, CA 92064 • Phone: 858-513-1911 • www.albireoenergy.com I] DF-60957:C .Intelligent Addressable FACP with Communicator ES-200X 0 FIreLITeALarms by Honeywell General The ES-200X is the latest intelligent addressable Fire Alarm Control Panel (FACP) from Fire-Lite Alarms and is a direct replacement for the MS-9200UDLS. The ES-200X comes with a pre-installed com- municator and supports up to 198 addressable devices (99 detec- tors and 99 modules). With an extensive list of powerful features, the ES-200X programs just like Fire-Lite's other addressable products, yet fits into applications previously served only by conventional pan- els. The pre-installed IPOTS-COM is a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator's internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedi- cated business telephone lines. Although not required, the second- ary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using the CELL-MOD or CELL-CAB-FL. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel's USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator. The USB port also allows for the download or upload of the entire program, history file, walk-test data, current status and system volt- ages by means of a USB flash drive. Alarm verification selection per detector point Maintenance alert warns when smoke detector dust accumula- tion is excessive One-person audible or silent walk test with walk-test log and printout System alarm verification selection per detector point PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant) Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules or remote annunciator Upload/Download of program and data via USB with optional FS- Tools Programming Utility SLC COMMUNICATION LOOP Supports LiteSpeedTM and CLIP protocols SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire Single addressable SLC loop which meets NFPA Class B and Class A requirements 198 addressable device capacity (99 addressable detectors and 99 modules) Compatible with Fire-Lite's addressable devices (refer to the SLC Wiring Manual) NOTIFICATION APPLIANCE CIRCUITS (NA CS) Four independently programmable output circuits. Circuits can be configured for the following outputs: - Style V (Class B) - Style Z (Class A) Silence Inhibit and Autosilence timer options Continuous, March Time, Temporal, or California code for main circuit board NACs with two-stage capability Selectable strobe synchronization per NAC 2.5 A special application, 250mA regulated, total power for NACs NOTE: Maximum or total 24VDC system power shared between all NAG circuits and the ANN-BUS is 2.7 A •The power supply and all electronics are contained on a circuit board supported on a new quick install chassis and housed in a metal cabinet. Available accessories include local and remote upload/download software, remote annunciators, and reverse polar- ity/city box transmitter (4XTMF). Features Listed to UL Standard 864, 10th edition Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- phone Service) Central Station Communicator over AlarmNet Optional CELL-MOD or CELL-CAB-FL GSM Central Station Communicator over AlarmNet® Automated activation of the ECC-50/100 Emergency Command Center ECC-FFT Firefighter Telephone option Compatible with SWIFT® wireless devices Auto-programming (learn mode) reduces installation time. Reports two devices set to the same address Four built-in, independently programmable Style Z (Class A) or Style V (Class B) NAC circuits Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices Notification Appliance Circuit End of Line resistor matching Four programmable function keys for ease of maintenance Two programmable relays and one fixed trouble relay Built-in Programmer Integral 80-character LCD display with backlighting Real-time clock/calendar with automatic daylight savings control History file with 1,000 event capacity Addressable sounder base compatibility Multi-criteria detector (smoke, heat, CO) with programmable response Control module delay timer S • Automatic detector sensitivity testing (NFPA 72 compliant) Automatic device type-code verification Point trouble identification Waterflow selection per module point DF-60957:C .7/16/2018—Page 1 of 4 S S PROGRAMMING AND SOFTWARE Autoprogramming (learn mode) reduces installation time Custom English labels (per point) may be manually entered or selected from an internal library file Two programmable Form-C relay outputs 99 software zones Continuous fire protection during online programming Program Check automatically catches common errors not linked to any zone or input point OFFLINE PROGRAMMING: Create the entire program in your office using FS-Tools, a Windows®-based software package, and upload/download system programming locally. Offline program- ming requires an ethernet connection. ES-Tools is available on www.firelite.com. User interface LED INDICATORS Fire Alarm (red) CO Alarm (red) AC Power (green) Supervisory (yellow) Trouble (yellow) Ground fault (yellow) Battery fault (yellow) Disabled (yellow) Maintenance (yellow) Communication (yellow) Alarm Silenced (yellow) F1-F4 Programmable Function Keys (yellow) KEYPAD 16 key alpha-numeric pad Acknowledge Alarm Silence Drill (Manual Evacuate) Four (4) programmable function keys Reset (lamp test) PRODUCT LINE INFORMATION ES-200X: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, pre-installed communicator, chassis with transformer, backbox with door, plastic bag containing screws, cables, key, etc. (For ES-200XC, refer to DF-60958.) FS-Tools: Programming software for Windows®-based PC com- puter. Available for download at www.firelite.com. CELL-CAB-FL/CELL-MOD: Optional GSM communicators. IPOTS-COM: Dual technology (POTS and lP) communicator. (replacement board) DP-ES-R: Optional dress panel for the ES-200X. TR-CE: Optional trim ring for semi-flush mounting. BB-2F: Optional cabinet for one or two modules. BB-6F: Optional cabinet for up to six modules mounted on CHS-6 chassis. BB-26: Battery backbox, holds up to two 25 AN batteries and CHG- 75. BB-55F: Battery box, houses two 55 AH batteries CHS-6: Chassis, mounts up to six multi-modules in a BB-6F cabinet. CHG-75: Battery charger for lead-acid batteries with a rating of 25 to 75AH. CHG-120F: Remote battery charging system for lead-acid batteries with a rating of 55 to 120AH. Requires additional BB-55F for mount- ing. BAT Series: Batteries, see data sheet DF-52397. PRN Series: UL listed compatible event printer. Uses tractor-fed paper. OPTIONAL MODULES 4XTMF Reverse Polarity Transmitter Module: Provides a super- vised output for local energy municipal box transmitter, alarm and trouble. Includes a disable switch and disable trouble LED. PWRMOD24 Power Expander Module: Optional power module. Increases alarm power output to 6 amps. COMPATIBLE ANNUNCIATORS ANN-80: Remote LCD annunciator mimics the information dis- played on the FACP LCD display. Recommended wire type is un- shielded. ANN-IOU: Remote LCD annunciator mimics the information dis- played on the FACP LCD display. Recommended wire type is un- shielded. For use in FM applications only. ANN-I/O: LED Driver Module provides connections to a user sup- plied graphic annunciator. (See DF-52430.) ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF- 6024 1.) ANN-RLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DF-60241.) ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be mounted inside the cabinet. (See DF-52431.) ANN-S/PC: Serial/Parallel Printer Gateway module provides a con- nection for a serial or parallel printer. (See DF-52429.) ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. SD365: Addressable low-profile photoelectric smoke detector. Lite- Speed only. 5D365-IV: Addressable low-profile photoelectric smoke detector. Ivory. LiteSpeed and CLIP mode. 5D365T: Addressable low-profile photoelectric smoke detector with thermal sensor. LiteSpeed only. 5D365T-IV: Addressable low-profile photoelectric smoke detector with thermal sensor. Ivory. LiteSpeed and CLIP mode. 5D365R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. LiteSpeed only. 5D365R-IV: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. Ivory. Lite- Speed and CLIP mode. H365: Low-profile 135°F fixed thermal sensor. LiteSpeed only. H365-IV: Low-profile 135°F fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. H365R: Low-profile, intelligent, rate-of-rise thermal sensor. Lite- Speed only. H365R-IV: Low-profile, intelligent, rate-of-rise thermal sensor. Ivory. LiteSpeed and CLIP mode. H365HT: Low-profile intelligent 190°F/88°C fixed thermal sensor. LiteSpeed only. H365HT-IV: Low-profile intelligent 190°F/88°C fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. Legacy Devices CP355: Addressable low-profile ionization smoke detector. SD355: Addressable low-profile photoelectric smoke detector. 5D355T: Addressable low-profile photoelectric smoke detector with thermal sensor. 50355R: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. SD355C0: Addressable, low-profile device that provides fire, heat, and carbon monoxide (CO) detection. H355: Fast-response, low-profile heat detector. Page 2 of 4— DF-60957:C - 7/16/2016 H355R: Fast-response, low-profile heat detector with rate-of-rise option. S H355H1: Fast-response, low-profile heat detector that activates at 190°F/88°C. AD355: Low-profile, intelligent, Adapt' multi-sensor detector (13350LP base included). B200S: Programmable, addressable sounder base. B200SR: Addressable sounder base. BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitiv- ity test. D355PL: InnovairFiex low-flow non-relay duct-detector housing; includes SD355R. DNR: InnovairFIex low-flow non-relay duct-detector housing. (Order SD355R15D365R separately.) DNRW: InnovairFIex low-flow non-relay duct-detector housing, with NEMA-4 rating. Watertight. (Order SD355R/SD365R separately.) Addressable Modules MMF-300: Addressable Monitor Module for one zone of normally- open dry-contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end-of-line resistor. Mod- ule may be configured for either a Style B (Class B) or Style D (Class A) IDC. MDF-300: Dual Monitor Module. Same as MMF-300 except it pro- vides two Style B (Class B) only lDCs. MMF-301: Miniature version of MMF-300. Excludes LED and Style D option. Connects with wire pigtails. May mount in device backbox. MMF-302: Similar to MMF-300. Addressable Monitor Module for one zone of conventional two-wire detectors. Requires resettable 24 VDC power. Refer to the Device Compatibility Document for listed compatible devices and quantity limitation. • CMF-300: Addressable Control Module for one Style Y/Z (Class BI A) zone of supervised polarized Notification Appliances. Mounts directly to a 4.0" (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. CRF-300: Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SM13500. BG-I2LX: Addressable manual pull station with interface module mounted inside. 1300: This module isolates the SLC loop from short circuit conditions (required for Style 6 or 7 operation). ISO-6: Six-fault isolator module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SMB500: Used to mount all modules except the MMF-301 and M301. MMF-300-10: Ten-input monitor module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. MMF-302-6: Six-zone interface module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CMF-300-6: Six-circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6: Six-relay control module (Form-C relays). Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SWIFT Wireless Devices W-GATE: LiteSpeed Wireless Gateway W-SD355: LiteSpeed intelligent, wireless photo detector. W-H355R: LiteSpeed intelligent wireless rate of rise (135°) heat detector. W-SD355T: Intelligent wireless photo/heat detector. W-H355: LiteSpeed intelligent wireless fixed-temperature (135°) heat detector. W-MMF: LiteSpeed Intelligent wireless monitor module. W-CRF: LiteSpeed Intelligent wireless relay module. W-BGI 2LX: LiteSpeed Intelligent wireless pull station. WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV bases. W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools. SWIFT Tools: Programming and diagnostic utility for the Wireless Gateway and devices. Available for download from firelite.com. NOTE: For more information on Compatible Addressable Devices for use with the ES-200X, see the following data sheets (document num- bers): S0365 Series (DF-61010), H365 Series (DF-61011), A0355 (DF-52386), BG-I2LX (DF-52013), CMF-300-6 (DF-52365), CRF-300-6 (DF-52374), CMF/CRF Series (DF-52 130), CP355 (DF-52383), H355 Series (DF-52385), 1300 (DF-52389), ISO-6 (DF-60485), MMF-300 SerieslMDF-300 (DF-52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), 50355/5D355T (DF-52384), and SLC Wiring Manual (51309). NOTE: Legacy 300 Series detection devices such as the CP300/CP350, SD300(T)/5D350(T) and older modules such as the M300, M301, M302, C304, and BG-IOLX are not compatible with LiteSpeed polling. If the SLC contains one of these devices, polling must be set for standard CLIP protocol. Please consult factory for further information on previous 300 Series devices. ADDRESSABLE DEVICE ACCESSORIES End-of-Line Resistor Assembly (R47K and R-3.91K): The 47k ohm assembly supervises the MMF-300, MDF-300, MMF-301, and CMF-300 module circuits. The 3.9k ohm assembly supervises the MMF-302 module circuit. These resistors are included with each module. Power Supervision Relay: Supervises the power to 4-wire smoke detectors and notification appliances. Wiring Requirements While shielded wire is not required, it is recommended that all SLC wiring be twisted-pair to minimize the effects of electrical interfer- ence. Refer to the panel manual for wiring details. DF-60957:C • 7/16/2018— Page 3 of 4 SYSTEM SPECIFICATIONS S System Capacity Temperature and Humidity Ranges Intelligent Signaling Line Circuits .1 Addressable device capacity..................................................198 Programmable software zones.................................................99 Annunciators.............................................................................16 Electrical Specifications AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto-sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Nonpower-limited, supervised. Battery: Two 12 V 18 A lead-acid batteries. Battery Charger Capacity: 7-I8AH (ES-200X cabinet holds maximum of two 18 A batteries.) Communication Loop: Supervised and power-limited. Notification Appliance Circuits: Terminal Block provides connec- tions for four NACs, Style Y (Class B) or Style Z (Class A). Special Application power. Power-limited, supervised circuitry. Maximum signaling current per circuit: 2.5 amps special application, 250mA regulated. End-of-Line Resistor: 4.7k ohm, 1/2 watt (P/N 71252 UL listed) for Style Y (Class B) NAC; system capable of 1.9 ko - 22 k) ELR range. Refer to the Fire-Lite Device Compatibility Document for listed compatible devices. Two Programmable Relays and One Fixed Trouble Relay: Con- tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A @ 30 VAC (resistive). Form-C relays, non-power-limited, non-supervised. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Shipping Specifications Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) high x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep. This system meets NFPA requirements for operation at 0 - 49°C132 - 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15— 27°C/60 - 80° F. NFPA Standards The ES-200X complies with the following NFPA 72 Fire Alarm Sys- tems requirements: - LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). -AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). -REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervi- sory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTMF is required.) - PROPRIETARY (Automatic, Manual and Waterflow). - CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). - 01, PSDN (Other Technologies, Packet-switched Data Net- work) - IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). - CBC 2007 (Seismic) Agency Listings and Approvals The listings and approvals below apply to the basic ES-200X control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S624 FM approved CSFM: 7165-0075:500 FDNY:COA#6261 NOTE: See DF-60958 for ULC-listed model. AlarmNet®, Fire-Lite® Alarms, SWIFT®, and System Sensor® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. O ISO 9001 We cannot cover all specific applications or anticipate all requirements. 2410113= All specifications are subject to change without notice. SINE311111 & MANIFAC1IRIN QUALITY SYSTEMS For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 6994105. Country of Origin: USA www.firelite.com Page 4 of 4— DF-60957:C • 7/16/2018 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - . FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-0075:0500 Page 1 of 2 CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Megan Sisson (203) 484-6544 Fax (203) 484-709 Email: megan.sissonhoneywell.com DESIGN: Models ES-50X and ES-200X Addressable Fire Alarm Control Units. Automatic, manual, waterflow, sprinkler supervisory, local, remote station (PPU), and central station (PPU) services. The ES-50X is a compact version of the ES-200X. The ES-50X has 50 addressable device capability and 2 Notification Appliance Circuits with a 3.0 amps total 24VDC output in Alarm. The ES-200X has 198 addressable device capability and 4 Notification Appliance Circuits with 3.0amps total 24VDC output in Alarm expandable to 6.0amps with Model PWRMOD24. The Model lPOTS-COM provides Phone and IP communication. *The CELL-MODE has the option to be configured by a compatible control unit for the following pathways: Cellular only without a backup path, primary Cellular communication path, or secondary Cellular communication path. Models ES-50X and ES-200X system components are as follows IPOTS-COM POTS and IP Communicator 4XTMF Transmitter Module • ANN-80 ANN-100 Remote Annunciator Module Remote Annunciator Module ANN-I/O LED Driver Module ANN-S/PG Serial/Parallel Interface Module ANN-RLY Form-C Relay Module ANN-LED Annunciator Module ANN-RLED Annunciator Module CELL-MOD GSM Communicator DP-ES-R Dress Panel Model ES-200X system components are as follows: PWRMOD24 NAC Power Expander Module Refer to the listee's data sheet for additional detailed product description and operational considerations. RATING: 120/240Vac 50/60Hz *Rev 10-01-19 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO, M.E., F.P.E., Program Coordinator Fire Engineering Division Listing No. 7165-0075:0500 Page 2 of 2 . INSTALLATION: In accordance with listees printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as fire alarm control units, emergency alarm system control units and process management equipment for use with separately listed compatible initiating and indicating devices. Refer to Manufacturers Installation Instruction Manual for details. NOTE: For Fire Alarm Verification Feature (Delay of fire alarm), the maximum Retard/Reset/Restart period must be adjusted to 30 seconds or less. *Rev 10-01-19 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO, M.E, F.P.E., Program Coordinator Fire Engineering Division S EI S FCPS-24FS6 24 Volt, 6 Amp Power Supply General The Fire-Lite FCPS-24FS6(C/E) is a compact, cost-effec- tive, 6-amp remote power supplies with battery charger. The FCPS-24F56(C/E) may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may stand-alone. Primary appli- cations include notification appliance (bell) circuit (NAC) expansion (to support ADA requirements and NAC synchroni- zation) or auxiliary power to support 24 volt system accesso- ries. The FCPS provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either two Class B (Style Y) and Class A (Style Z, with ZNAC-4 option module) or four class B only. Alternately, the four outputs may be configured as any combination of resettable/non-resettable power outputs (optimal for powering four-wire smoke detec- tors. The FFCPS-24FS6(C/E) also contains a battery charger capable of charging up to 7.0 Amp hour batteries. FCPS- 24F56(C/E) is ULC-listed. NOTE: Unless otherwise specified, the term FCPS-24FS6 used in this document refers to the standard FCPS-24FS6, FCPS- 24FS6C, FCPS-24FS6E Features UL-Listed Notification Appliance Circuit (NAC) synchroniza- tion using System Sensor, Wheelock, or Gentex "Com- mander2" appliances. Operates as a 'sync-follower" or as a sync-generator" (default). See note on page 2. Contains two fully-isolated input/control circuits - triggered from FACP NAC (NAC expander mode) or jumped perma- nently ON" (stand-alone mode). Two Class B (Style Y) or Class A (Style Z, with ZNAC-4 module) NACs (circuits 1 & 3) 6-amp full load output, with 3 amps maximum/circuit, in NAC expander mode (UL 864). 4-amp continuous output in stand-alone mode (UL 1481). Compatible with coded inputs; signals passed through. Optional power-supervision relay (EOLR-1). In stand-alone mode, output power circuits may be config- ured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two. Fully regulated and filtered power output - optimal for pow- ering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power. Power-limiting technology meets UL power-limiting require- ments. Form-C normally-closed trouble relay. Fully supervised power supply, battery, and NACs. Selectable earth fault detection. AC trouble report selectable for immediate 2-hour delay. Works with virtually any UL 864 fire alarm control which uti- lizes an industry-standard reverse-polarity notification cir- cuit (including unfiltered and unregulated bell power). Requires input trigger voltage of 9 - 32 VDC. Self-contained in compact, locking cabinet - 15"H x 14.5W x 2.75"D (cm: 38.1H x 36.83W x 6.985D). DF-52301 :A2 • D-025 (2) Flre•LITeALarmS by Honeywell Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter- ies. Battery charger may be disabled via DIP switch for applica- tions requiring larger batteries. Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1mm2) wire. Specifications Primary (AC) Power: FCPS-24FS6: 120 VAC, 60 Hz, 3.2A maximum. FCPS-24F56/E: 240 VAC, 50 Hz, 1.6A maximum. Wire Size: minimum #14 AWG (2.0mm2) with 600 V insula- tion. Control Input Circuit: Trigger Input Voltage: 9 to 32 VDC. Trigger Current: 2.0 mA (16-32 V); Per Input: 1.0 mA (9 - 16 V). Trouble Contact Rating: 5 A at 24 VDC. Auxiliary Power Output: Specific application power 500 mA maximum. Output Circuits: +24 VDC filtered, regulated. 3.0 A maximum for anyone circuit. Total continuous current for all outputs (stand-alone mode): - FCPS-24F: 4.0 A maximum. Total short-term current for all outputs (NAC expander mode): - FCPS-24F: 6.0 A maximum. DF-52301 :A2 • 5/17/13 - Page 1 of 4 Secondary Power (Battery) Charging Circuit: • Supports lead-acid batteries only. Float-charge voltage: 27.6 VDC. Maximum current charge: 250 mA. Maximum battery capacity: 7.0 AH. Applications Example 1: Expand notification appliance power an additional 6.0 A. Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP noti- fication appliance circuits will activate the FCPS when reverse- polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit. Example 2: Use the FCPS to expand auxiliary regulated 24- volt system power up to 4.0 A. Both resettable and non-reset- table power options are available. Resettable outputs are cre- ated by connecting the resettable output from the FACP to one or both of the FCPS inputs. Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expanding system architecture in various applications. For example, an addressable control module is used to acti- vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable control module. NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 10,000 feet (3,046 meters). Sync Follower/Generator Note In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS-24FS6 can track (i.e. "follow") the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS. When the FCPS-24F56 is configured (via DIP switch settings) as a sync follower" the FCPS's NAC outputs track the strobe synchronization pulses present at the FCPS's sync input ter- minal. The pulses originate from an upstream FACP or other power supply. When the FCPS-24FS6 is configured (via DIP switch settings) as a "sync generator:' the FCPS's sync input terminals are not used. Rather, the FCPS is the originator of the strobe synchro- nization pulses on the FCPS's NAC outputs. In sync genera- toe' mode, the sync type (System Sensor, Wheelock, or Gentex) is selectable via DIP switch settings. Standards and Codes The FCPS-24F56 complies with the following standards: NFPA 72 National Fire Alarm Code. UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode). UL 1481 Power Supplies for Fire Alarm Systems. [] Page 2 of 4— DF-52301 :A2 • 5/17/13 Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S2424, S1287 ULC Listed: S2424 CSFM Approved: 7315-0076:176 MEA: 387-94E Ordering Information FCPS-24FS6: 6.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24FS6 is ULC-Iisted. FCPS-24FS6E: 6.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. ZNAC-4: Class A (Style Y) NAC option module. EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire smoke detector power. BAT-1270: Battery, 12-volt, 7.0 AH (two required). PS-1270: Battery, 12-volt, 7.0 AH (two required). 90286: Optional module mounting kit, is required to install an addressable module on the power supply main circuit board. AC PowE S NOTE: All NAC outputs can be converted to Style Z with Style Y NAC or ZNAC-4 option module. FCPS Door Holder Trouble Power Style Y NAC Style Y NAC Style Y NAC Contact Output #4 Output #3 Output #2 Output #1 Output 24 VDC Specific Application Power NAC Control Input #2 (from FACP) NAC Control Input #1 (from FACP) Sync Input Battery Charger Simplified Block Diagram DF-52301 :A2 • 5/17/13 - Page 3 of 4 0 4- G W1 - TEl 4- - - 0J2 Im CL 0 a Non-Power-Limited J2: To Transformer #2 Ji: To Transformer #1 LbU 0 0 @010 ¶II1] Battery Fuse l5A,30V JP4 (D rM 0 - Battery LEDs (L to R): + Battery AC Power (green) Ground Fault (yellow) JP4: Supervised, Battery Trouble (yellow) Non-Power-Limited • NAG Trouble (yellow) 18 AH, 24 VDC Charger Trouble/AG Loss (yellow) Auxiliary Output: 10 - -Aux. Common 500 MA Specific- Application Power 9 - + Aux- 24 VDC 8 - - Control Input 2 D 7 - + Control Input 2 6 - —Out Common 5 - + Out/Trouble Contact 4 - - Control Input 1 3 - + Control Input 1 2 --Sync Input SW1 1 - • Sync Input U 111111 I 0 TB4 *NOTE: Auxiliary Power Output is power-limited but NOT supervised. SWI: Programming DIP Switches TB2: Power-Limited, NAC/Out 1 + Supervised in NAC Mode NAG/Out 1 - with Jumpers J5, JP6, NAG/Out 2 + TBI: Supervised JP7, & JPB in positions NAC/Out 2- shown below. - Earth NAC/Out 3 * NAC/Out 3- - AC Neutral __ AC Hot NAG/Out 4 + NAC/Out4- Normally Open Normally Closed Common TB5: Trouble Relay Form Fail-Safe 0 (shown energized) 1Ig1D 3 2 i TB5 .JPI: Ground Fault Detection jpi (cut to disable) - J3: ZNAC-4 JP2 Connector I JP2 & JP3: Coded/Non-Coded Input Selection 0 . . S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7315-0075:0206 Page 1 of 1 CATEGORY: 7315-- POWER UNITS LISTEE: FIRE-LITE ALARMS lNC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Models FCPS-24FS6 and FCPS-24FS8 are power limited power supply/battery chargers used for supervision and expanded power driving capability of up to four Notification Appliance Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable outputs. Model ZNAC-4 Class A converter. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 120 VAC, 24VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product designation, electrical rating and UL label. APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm control units. NOTE: *Rev. 05-06-05JW This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 5 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division S ANN-80 80-Character Serial LCD Annunciator General The ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced conditions. The ANN-80 and the FACP communicate over a two-wire serial interface employ- ing the ANN-Bus communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. The ANN-80 is red; for white, order ANN-80-W. The ANN-80 displays English-language text of system point informa- tion including device type, zone, independent point alarm, trouble or supervisory status, as well as any custom alpha labels programmed into the control panel. It includes control switches for remote control of critical system functions. (A keyswitch prevents unauthorized operation of the control switches.) Up to eight ANN-805 may be connected to the ANN-Bus of each FACP. No programming is required, which saves time during system commissioning. Features Listed to UL Standard 864, 9th Edition Backlit 80-character LCD display (20 characters x 4 lines) Mimics all display information from the host panel S . Control switches for System Acknowledge, Signal Silence, Drill, and Reset Control switches can be independently enabled or disabled at the FACP Keyswitch enables/disables control switches and mechanically locks annunciator enclosure Keyswitch can be enabled or disabled at the FACP Enclosure supervised for tamper System status LEDs for AC Power, Alarm, Trouble, Supervisory, and Alarm Silence Local sounder can be enabled or disabled at the FACP ANN-80 connects to the ANN-Bus terminal on the FACP and requires minimal panel programming Displays device type identifiers, individual point alarm, trouble, supervisory, zone, and custom alpha labels Time-and date display field Surface mount directly to wall or to single, double, or 4" square electrical box Semi-flush mount to single, double, or 4" square electrical box. Use ANN-SB80KlT for angled view mounting Can be remotely located up to 6,000 feet (1,800 m) from the panel Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC) Up to eight ANN-805 can be connected on the ANN-Bus Controls and Indicators S . AC Power Alarm Trouble DF-52417:D • B-90 (2) Fire uTe®ALarms by Honeywell Supervisory Alarm Silenced Specifications Operating voltage range: 18 VDC to 28 VDC Current consumption © 24 VDC nominal (filtered and non- resettable): 40 mA maximum Ambient temperature: 32°F to 120°F (0°C to 49°C) Relative humidity: 93% ± 2% RH (non-condensing) at 32°C ± 2°C (90°F ± 3°F) 5.375" (13.65 cm.) high x 6.875" (17.46 cm.) wide x 1.375" (3.49 cm.) deep For use indoors in a dry location All connections are power-limited and supervised The ANN-Bus POWERING THE DEVICES ON THE ANN-BUS FROM AUXIL- IARY POWER SUPPLY The ANN-Bus can be powered by an auxiliary power supply when the maximum number of ANN-Bus devices exceeds the ANN-Bus power requirements. See the FACP manual for more information. ANN-BUS DEVICE ADDRESSING Each ANN-Bus device requires a unique address (ID Number) in order to communicate with the FACP. A maximum of 8 devices can be connected to the FACP ANN-Bus communication circuit. See the FACP manual for more information. WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT The ANN-80 connects to the FACP ANN-Bus communications cir- cuit. To determine the type of wire and the maximum wiring distance that can be used with FACP ANN-Bus accessory modules, it is nec- essary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. NOTE: For total worst case current draw on a single ANN-Bus refer to appropriate FACP manual. DF-52417:D .3/15/2018—Page 1 of 2 WIRE REQUIREMENTS: POWER CIRCUIT 14 to 18 AWG (0.75 - 2.08 mm2) wire for 24 VDC power circuit is S acceptable. Power wire distance limitation is set by 1.2 volt maxi- mum line drop form source to end of circuit. All connections are power-limited and supervised. A maximum of eight ANN-80 modules may be connected to this circuit. Ordering Options ANN-80: Red 80 character LCD Annunciator. ANN-80-W: White, 80 character LCD Annunciator. ANN-SB80KIT-R: Red surface mount backbox with angled wedge. ANN-SB80K1T-W: White surface mount backbox with angled wedge. Agency Listings and Approvals The listings and approvals below apply to the ANN-80. In some cases, certain modules may not be listed by certain approval agen- cies, or listing may be in process. Consult factory for latest listing status. UL: S2424 FM approved CSFM: 7120-0075:0211 MEA: 442-06-E n Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. ©2018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. I SO 9001 We cannot cover all specific applications or anticipate all requirements. ________ NiU :b d U U All specifications are subject to change without notice. B1INERINS & MANIFRC11IIIN QUALITY SYSTEMS For more information, contact Fire•LiteAlarms. Phone: (800) 627-3473, FAX: (877) 6994105. Country of Origin USA www.firelite.com Page 2 of 2— DF-52417:D • 3/15/2016 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL M'44W4~ S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7120-0075:0211 Page 1 of 1 CATEGORY: 7120 —ANNUNCIATORS LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Model ANN-80 and *ANN80W remote fire annunciators. Unit is a 80-character, supervised backlit LCD fire annunciator. Communication between the control panel and the annunciator is accomplished over a two-wire serial interface employing the ANN-BUS protocol. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING: Listees name, product number, electrical rating and UL label. APPROVAL: Listed as an annunciators for use separately listed compatible fire alarm control units. Refer to Manufacturers Installation Manual for details. S *Rev. 04-28-08 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 5 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division SD355(A) Series Addressable Photoelectric Smoke Detectors General The SD355(A), SD355T(A), and SD355R(A) addressable, low-profile plug-in photoelectric detectors use a state-of-the- art photoelectric sensing chamber with communications to provide open area protection and are used exclusively with Fire-Lite's Addressable Fire Alarm Control Panels (FACP5). The SD355T(A) adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C). Since these detectors are addressable, they will help emergency personnel quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indica- tion. Remote LED annunciator capability is available as an optional accessory, PN RA100Z(A). The SD355R(A) is a remote test capable detector for use with D355PL(A) or DNR(A)/DNRW duct smoke detector housings. Features SLC LOOP Two-wire loop connection. Unit uses base for wiring. ADDRESSING Addressable by device. • Rotary, decimal addressing: 01 - 99 with MS-9200UD(LS), and 01 - 159 with MS-9600UD(LS). ARCHITECTURE Unique single-source, dual-chamber design to respond quickly and dependably to a broad range of fires. Sleek, low-profile design. Integral communications and built-in type identification. Built-in tamper-resistant feature. Removable cover and insect-resistant screen for simple field cleaning. OPERATION Withstands air velocities up to 4,000 feet-per-minute (20 m/ sec.) without triggering a false alarm. Factory preset at 1.5% nominal sensitivity for panel alarm threshold level. Visible LED "blinks" when the unit is addressed (communi- cating with the fire panel) and latches on in alarm. MECHANICALS Sealed against back pressure. Direct surface mounting or electrical box mounting. Mounts to: single-gang box, 3.5" (8.89 cm) or 4.0' (10.16 cm) octagonal box, or 4.0" (10.16 cm) square electrical box (using a plaster ring - included). OTHER SYSTEM FEATURES Fully coated circuit boards and superior RF/transient pro- tection. 94-VO plastic flammability rating. Low standby current. DF-52384:D • E-160 FlreLITeALarms by Honeywell SD355(A) in B2IOLP(A) Base OPTIONS Remote LED output connection, PN RA1 OOZ(A). Applications Use photoelectric detectors in life-safety applications to pro- vide a broad range of fire-sensing capability, especially where smoldering fires are anticipated. Ionization detectors are often better than photoelectric detectors at sensing fast, flaming fires. Construction These detectors are constructed of off-white fire resistant plas- tic. SD355(A) series plug-in, low-profile smoke detectors are designed to commercial standards and offer an attractive appearance. Installation SD355(A) series plug-in detectors use a detachable mounting base to simplify installation, service and maintenance. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059. NOTE: Because of the inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4 (Class B) wiring. SD355R(A) mounts in a 0355PL(A) or DNR(A)/DNR W duct detector housing. Operation Each 5D355(A) series detector uses one of 99 possible addresses on the MS-9200UD(LS) and up to 318 (159 on each loop) on the MS-9600UD(LS) Signaling Line Circuit (SLC). It responds to regular polls from the system and reports its type and status. The addressable photoelectric sensor in the SD355(A) series has a unique unipolar chamber that responds quickly and uni- formly to a broad range of smoke conditions. It can withstand wind gusts up to 4,000 feet-per-minute (20 rn/sec.) without sending an alarm level signal. Because of its unipolar cham- ber, the SD355(A) series is approximately two times more responsive than most photoelectric sensors. This makes it a more stable detector. DF-52384:D • 2/11/2015 - Page 1 of 2 Detector Sensitivity Test Specification Voltage range: 15-32 VDC (peak). Standby current: 300 pA @ 24 VDC. LED current: 6.5 mA @ 24 VDC (latched "ON"). Air velocity: 4,000 ft/mm. (20 rn/sec.) maximum. Size: 2.1' (5.33 cm) high; base determines diameter. - B21OLP(A): 6.1' (15.5 cm) diameter. - B501 (A): 4.1" (10.4 cm) diameter. - B200SR(A): 6.875" (17.46 cm) diameter. - B224RB(A): 6.2" (15.748 cm) diameter. Weight: 3.6 oz. (102 g). Operating temperature range: for S0355(A): 0°C to 49°C (32°F to 120°F); for SD355T(A): 0°C to 38°C (32°F to 100°F). S0355R(A): installed in a DNR(A)/DNRW -20°C to 70°C (-4°F to 158°F). Temperature: 0°C - 49°C (32°F - 1200F). Relative humidity: 10% - 93%, non-condensing. Listings Listings and approvals below apply to the 5D355(A), SD355T(A), and SD355RT(A) detectors. In some cases, cer- tain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S1059. ULC Listed: S1059. CSFM: 7272-0075:0194. MEA: 243-02-E. FM approved. Product Line Information NOTE: "A" suffix indicates ULC Listed model. SD355: Addressable photoelectric detector; B21OLP base included. 5D355A: Sames as SD355 with ULC Listing; B21OLPA base included. SD355T: Same as 5D355 but with thermal element; B21OLP base included. SD355TA: Same as SD355T with ULC Listing; B21OLPA base included. SD355R: Remote test capable addressable photoelectric detector for use with a D355PL(A) or DNRA/DNRW duct detector housing; B21OLP base included. 5D355RA: Same as SD355R with ULC Listing for use with a D355PLA or DNRA duct detector housing; B21OLPA base included. INTELLIGENT BASES NOTE: "A" suffix indicates ULC Listed model. NOTE: The defector's plug-in base can be changed off for special applications. For details about intelligent bases and their mount- ing, see DF-60059. B21OLP(A): Plug-in detector base (included); standard U.S. flanged low-profile mounting base. B210LPBP: Bulk pack of B21OLP; package contains 10. B501(A): Standard European flangeless mounting base. B501 BP: Bulk pack of 8501; package contains 10. B200SR(A): Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Replaces B501BH series bases in retrofit applications. B224RB(A): Plug-in System Sensor relay base. Screw termi- nals: up to 14 AWG (2.0 mm2). Relay type: Form-C. Rating: 2.0 A @ 30 VDC resistive; 0.3 A @ 110 VDC inductive; 1.0 A @ 30 VDC inductive. B224B1(A): Plug-in System Sensor isolator detector base. Maximum 25 devices between isolator bases (see DF-52389). ACCESSORIES F110: Retrofit flange to convert B21OLP(A) to match the B350LP(A) profile, or to convert older high-profile bases to low-profile. Fl 10BP: Bulk pack of F110; package contains 15. F210: Replacement flange for B21OLP(A) base. RA1 OOZ(A): Remote LED annunciator. 3- 32 VDC. Mounts to a U.S. single-gang electrical box. For use with B501 (A) and B21OLP(A) bases only. SMB600: Surface mounting kit M02-04-00:Test magnet. M02-09-00: Test magnet with telescoping handle. XR2B: Detector removal tool. Allows installation and/or removal of detector heads from bases in high ceiling applica- tions. XP-4: Extension pole for XR2B. Comes in three 5-foot (1.524 m) sections. 155-127-010: Detector removal tool without pole. BCK-200B: Black detector covers for use with 5D355(A) only; box of 10. WCK-200B: White detector covers for use with 5D355(A) only; box of 10. FireLite® Alarms is a registered trademark of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/connected to a MS-9200UD(LS) or MS- 9600UD(LS) addressable fire alarm control panel. The results of the sensitivity test can be printed off the MS-9200UD(LS) or MS-9600UD(LS) for record keeping. This document is not intended to be used for installation purposes. Iso 9001 We try to keep our product information up-to-date and accurate. • We cannot cover all specific applications or anticipate all requirements. S IFflIN & MANiMRING All specifications are subject to change without notice. QUALITY SYSTEMS For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2- DF-52384:D • 2/11/2015 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-0075:0194 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Models SD350, SD3501, SD355, 5D355R*, 5D355T and AD355 photoelectric type smoke detectors. Model SD350T and 5D355T has a 135°F supplement integral heat sensor which only assists in a fire situation. The purpose of this thermal circuitry is to increase the sensitivity of the detector. This thermal circuitry is NOT approved for use as a heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 24VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm control units. All units are suitable for open areas and inside duct installations with air velocities between 0-4,000 FPM. Models 5D355 and 5D355R* are also approved for installations inside Fire-Lite Duct Housing D355PL (CSFM Listing No. 3242-0075:221) and S System Sensor Duct Housing DNRW(CSFM Listing No. 3242-1653:210). NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires which smolder for hours before bursting into flame. Sources of these fires may include cigarettes burning in couches or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires which consume combustible materials rapidly and spread quickly. Sources of these fires may include paper burning in a waste container or a grease fire in the kitchen. *Rev. 01-11-2010 fm TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct ' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 0 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division DF-60430:C2 • E-650 D355PL(A)IDNRW InnovairFiex Intelligent Non-Relay Photoelectric Duct Smoke Detector 8 FlreLITeALarms by Honeywell S n General The Fire'Lite InnovairFIex® D355PL(A) intelligent non-relay photoelectric duct smoke detector and DNRW watertight non- relay photoelectric duct smoke detector feature a pivoting housing that fits both square and rectangular footprints capa- ble of mounting to a round or rectangular duct. DNRW duct smoke detector, with its NEMA-4 rating, is listed as a watertight, UV resistant enclosure providing protection against falling dirt, rain, and windblown dust, splashing and hose directed water, allowing operators to use the detector in the most extreme environments. These units sense smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute (0.5 to 20.32 m/s), temperatures of -4°F to 158°F (-20°C to 70°C), and a humidity range of 0 to 95 percent (non-condensing.) An improved cover design isolates the sensor head, which allows for ease of maintenance. A cover tamper feature indi- cates a trouble signal for a removed or improperly installed sensor cover. The Fire-Lite InnovairFIex housing provides a 3/ 4-inch conduit knockout and ample space to facilitate easy wir- ing and mounting of a relay module. The Fire'Lite InnovairFIex duct smoke detector can be custom- ized to meet local codes and specifications without additional wiring. The new InnovairFIex product line is compatible with all previous Innovair models, including remote test accessories. Features Photoelectric, integrated low-flow technology. Air velocity rating from 100 ft/min to 4,000 ft/mm (0.5 m/s to 20.32 m/s). Versatile mounting options: square or rectangular configu- ration. Broad ranges for operating temperature (-4°F to 158°F, - 20°C to 70°C) and humidity (0% to 95% non-condensing). Patented sampling tube installs from front or back of the detector with no tools required. Cover tamper signal. Increased wiring space with a newly added 3/4" conduit knockout. Available space within housing to accommodate mounting of a relay module. Easily accessible code wheels on sensor head (sold sepa- rately). Clear cover for convenient visual inspection. Remote testing capability. Requires corn line power only. Accommodates the installation of an addressable relay module, sold separately, (CRF-300) for applications requir- ing a Form-C relay. Specifications Size: (Rectangle) 14.38 in (37 cm) Length; 5 in (12.7 cm) Width, 2.5 in (6.6 cm) Depth. Size: (Square) 7.75 in (19.7 cm) Length; 9 i (22.9 cm) Width; 2.5 in (6.35 cm) Depth. Weight: 1.6 lb (0.73 kg). Operating Temperature Range: -4°F to 158°F (-20°C to 70°C). Storage Temperature Range: -22°F to 158°F (-30°C to 70°C). Operating Humidity Range: 0% to 95% relative humidity (non-condensing). Air Duct Velocity: 100 to 4,000 ft/min (0.5 to 20.32 m/s). Accessories Fire•Lite provides system flexibility with a variety of accesso- ries, including two remote test stations and different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detectors accessories are UL listed. D355PLs and DNRWs with a date code of 0013 or higher do not require external 24VDC for remote test applications when used with a remote-test-capable detector. ACCESSORY CURRENT LOADS AT24 VDC Device Standby Alarm RA100Z DmA 12 mA Max RTS151/ OmA 12mA Max RTS1 51 KEY Agency Listings and Approvals Consult product manual for lists of compatible UL-Listed devices. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status. UL: S1059. ULC: S1059 DF-60430:C2 • 12/18/2012 - Page 1 of 2 CSFM: 3242-1653:0209. FM approved. S Product Line Information D355PL: Intelligent non-relay photoelectric low flow smoke detector housing. Includes SD355R Detector. DNRW: Watertight intelligent non-relay photoelectric low flow duct smoke detector housing. Does not include detector head. S0355R(A): Remote test capable addressable low-profile photoelectric smoke detector. SD355(A): Addressable low-profile photoelectric smoke detec- tor. DCOIL: Remote test coil. Required for older DNR(W) duct detector housing. DST1: Metal sampling tube duct width up to 1 ft (0.3m). DST1.5: Metal sampling tube duct widths up to 1 ft to 2 ft (0.3 to 0.6 m). DST3: Metal sampling tube duct widths up to 2 ft to 4 ft (0.6 to 1.2 m). DST5: Metal sampling tube duct widths up to 4 ft to 8 ft (1.2 to 2.4 m). DST10: Metal sampling tube duct widths up to 8 ft to 12 ft (2.4 to 3.7 m). DH4000E-1: Weatherproof enclosure. ETX: Metal exhaust tube duct, width 1 ft (0.3 m). M02-04-00: Test magnet. P48-21-00: End cap for metal sampling tubes. RA100Z: Remote annunciator alarm LED. S RTS151: Remote test station. RTS1 51 KEY: Remote test station with key lock. Important Note DNRW duct detector housings with a date code of 0013 or higher do not require a DCOIL or auxiliary 24 VDC for remote test applications when used with a remote test capable detector. DNRW duct detector housings with a date code of 0012 or earlier require a DCOIL and auxiliary 24 VDC power for remote test applications. Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. 02012 by Honeywell International Inc. All rights reserved, unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. Iso 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. S EIGINNIN a M4NITh1ulI All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2— DF-60430:C2 • 12/18/2012 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 3240-0075:0221 Page 1 of 1 CATEGORY: 3240 -- DUCT SMOKE DETECTOR HOUSING/BASE LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Model *D355PL analog photoelectric duct smoke detector housing. Unit consists of a duct detector housing, exhaust tubes, and separately listed Fire-Lite Alarms' Model 5D355 or SD355R detector heads (OSFM Listing No. 7272-0075:194). Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 24 VDC INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, air velocity and UL label. APPROVAL: Listed as conventional photoelectric duct smoke detector housing for use with separately listed fire alarm control units. Refer to listee's Installation Instruction Manual for details. XLF: 3240-1653:0209 01-02-18 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division DF-52013:D • E-100 BG-1 2LX Addressable Manual Pull Station General The Fire-Lite BG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire-Lite's addressable fire alarm control panels (FACP5) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features Maintenance personnel can open station for inspection and address setting without causing an alarm condition. Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. Handle latches in down position and the word ACTIVATED" appears to clearly indicate the station has been operated. Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). Can be surface mounted (with SB-10 or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4' (10.16 cm) square electrical box. Smooth dual-action design. Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. Highly visible. Attractive shape and textured finish. Key reset. Includes Braille text on station handle. Optional trim ring (BG12TR). Meets UL 38, Standard for Manually Actuated Signaling Boxes. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications Shipping Weight: 9.6 oz. (272.15 g) Normal operating voltage: 24 VDC. Maximum SLC loop voltage: 28.0 VDC. Maximum SLC standby current: 375 pA. Maximum SLC alarm current: 5 mA. Temperature Range: 32°F to 120°F (0°C to 49°C) Relative Humidity: 10% to 93% (noncondensing) For use indoors in a dry location Installation (2) Fire tietarms by Honeywell D usually needed for semi-flush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word ACTI- VATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 - 159 with Breakaway Tab removed for MS-9600 Series, 1 - 99 and MS-9200UDLS, 1 —50 for MS-9050UD). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non-coded, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or 4' (10.16 cm) square electrical box, and shall be installed DF-52013:D.4/13/2012—Page 1 of 2 The BG-12LX will mount semi-flush into a single-gang, double- gang, or standard 4' (10.16 cm) square electrical outlet box, or S will surface mount to the model SB-10 or SB-I/O surface back- box. If the BG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations S shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. Product Line Information BG-12LX: Dual-action addressable pull station. Includes key locking feature. (Listed for Canadian and non-Canadian appli- cations.) SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17003; Keys, set of two. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. UL/ULC Listed: S711 (listed for Canadian and non-Cana- dian applications). MEA: 67-02-E. CSFM: 7150-0075:0184. FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. FireLite® Alarms® is a registered trademark of Honeywell International Inc. 02012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. Iso 9001 We try to keep our product information up-to-date and accurate. 933=1=1 We cannot cover all specific applications or anticipate all requirements. S MCINEEKINI a MMMUTINNO All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2— DF-52013:D • 4/13/2012 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM S LISTING SERVICE LISTING No. 7150-0075:0184 Page 1 of 1 CATEGORY: 7150 -- FIRE ALARM PULL BOXES LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Models BG-12, BG-125, BG-12NC, BG-12W, BG-12LW, BG-12WP, BG-12LWP, BG-12L, BG-12LX, BG-12LA, BG-12PS, BG-12LSP, BG-12SP, BG-12LR, BG-12LRA, BG-12LAO, BG-12LAOB, BG-12-LO, BG-12LOB, BG-12LPS, BG-12LPSP, BG-125L, UT-PSi and UT-PS2 fire alarm pull boxes. The BG-12 series is a dual action pull station that has normally open switch contacts. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model number and UL label. APPROVAL: Listed as fire alarm boxes for use with separately listed compatible fire alarm control units. Models BG-12WP, BG-12W, BG-12LW and BG-12LWP are intended for outdoor use when installed with Model WP-10 back box. Models BG-LAOB and BG-12L0B are intended for outdoor use when installed with Model WBB or WP-i 0 back box. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and California amendments. XLF: 7150-0028:0199 *Updated 08-17-09 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 0 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division DF-52121:E• E-325 S MMF.300(A) Series, MDF-300 Addressable Monitor Modules Fire tieetarms by Honeywell S General Four different monitor modules are available for Fire-Lite's intelligent control panels to suit a variety of applications. Moni- tor modules are used to supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (MMF-302(A)). FVIMF-300(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry-contact input devices. MMF-301(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75' (6.985 cm) W x 0.65" (1.651 cm) D that super- vises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the MMF-301(A) to be mounted in a single-gang box behind the device it monitors. MMF-302(A) is a standard-sized module used to monitor and supervise compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. MDF-300(A) is a standard-sized dual monitor module used to monitor and supervise two independent two-wire Style B (Class B) dry-contact initiating device circuits (lDCs) at two separate, consecutive addresses in intelligent, two-wire sys- tems. LiteSpeed T1,1 is a communication protocol developed by Fire-Lite Engineering that greatly increases the speed of com- munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other communication protocols. MMF.300(A) Monitor Module Built-in type identification automatically identifies this device as a monitor module to the control panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry of address: 01 - 159 on MS-9600 series panels, 01 —99 on other compatible systems. LED flashes during normal operation and latches on steady to indicate alarm. The MMF-300(A) Monitor Module is intended for use in intelli- gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro- vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The MMF-300(A) can be used to replace M300(A) modules in existing systems. MMF-300(A) APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special MMF-300(A) (Type H) supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. MMF-300(A) OPERATION Each MMF-300(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-300(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 375 pA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MMF.301 (A) Mini Monitor Module Built-in type identification automatically identifies this device as a monitor module to the panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. DF-52121:E 07130/2015 - Page 1 of 4 Tinned, stripped leads for ease of wiring. Direct-dial entry of address: 01 - 159 on MS-9600 series n panels, 01 - 99 on other compatible systems 31 1415 0 1 ADDRESS 0 1 13 11 4 LOOP 110 6 8 7 6 I TENS ONES o Uj 0 -J q: Lu ca The MMF-301(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF-301(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat- ing device circuit for normally-open-contact fire alarm devices. The MMF-301(A) can be used to replace M301 (A) modules in existing systems. MMF-301(A) APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/ device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor (provided) terminates the circuit. MMF-301(A) OPERATION Each MMF-301(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). MMF-301(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 pA, 1 communication every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 450 pA. EOL resistance: 47K Ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65' (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. S MMF-302(A) Interface Module Supports compatible two-wire smoke detectors. Page 2 of 4— DF-52121 :E .07130/2015 Supervises IDC wiring and connection of external power source. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry entry of address: 01 - 159 on MS-9600 series panels, 01 - 99 on other compatible systems. LED flashes during normal operation. LED latches steady to indicate alarm on command from control panel. The MMF-302(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be UL compatible with the module. The MMF-302(A) can be used to replace M302(A) modules in existing systems. MMF-302 (A) APPLICATIONS Use the MMF-302(A) to monitor a zone of two-wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). Install ELR across terminals 8 and 9 for Style D application. MMF-302(A) OPERATION Each MMF-302(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-302(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 Ohms. Average operating current: 270 pA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.9K Ohms. External supply voltage (between Terminals TIO and 111): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MDF.300(A) Dual Monitor Module The MDF-300(A) Dual Monitor Module is intended for use in intelligent, two-wire systems. It provides two independent two- wire initiating device circuits (lDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panel- controlled LED. NOTE: The MDF-300(A) provides two Style B (Class B) lOC cir- cuits ONLY Style D (Class A) IDC circuits are NOT supported in any application. MDF-300(A) SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 pA (LED flashing). Maximum IDC wiring resistance: 1,500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 pA EOL resistance: 47K Ohms. Temperature range: 32° to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5° (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MDF-300(A) AUTOMATIC ADDRESSING The MDF-300(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the MDF-300(A) is set to address "26", then it will automati- cally assign itself to addresses "26" and "27". NOTE: "Ones" addresses on the MDF-300(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. CAUTION: - Avoid duplicating addresses on the system. S Installation MMF-300(A), MMF-302(A), and MDF-300(A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface-mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regu- lations. These modules are intended for power-limited wiring only. The MMF-301(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S2424. ULC: S2424. FM Approved. CSFM: 7300-0075:0185. MEA:72-01-E. Product Line Information NOTE: "A" suffix indicates ULC-listed model. MMF-300(A): Monitor module. MMF-301(A): Monitor module, miniature. MMF-302(A): Monitor module, two-wire detectors. MDF-300(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN 51309. Architects'/Engineers' Specifications Specifications of these devices and all FireLite products are available from FireLite. OF-52121:E • 07/30/2015 - Page 3 of 4 Fire Lite® is a registered trademark and LiteSpeedTM and FireWatchTm are trademarks of Honeywell International Inc. ©2015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I so ooi This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. • We cannot cover all specific applications or anticipate all requirements. BII&IN &MANIFC1UNG All specifications are subject to change without notice. QUALITY SYSTEMS For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 4 of 4— DF-52121:E • 07/30/2015 S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0075:0185 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: FIRE-LITE ALARMS INC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 15-32VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model designation, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. NOTE: S *Rev. 05-06-05 JW 61I4, This listing is based upon technical data submitted by the the test results and/or other data but does not make an independent applicant. CSFM Fire Engineering verification of any claims. staff has reviewed This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other S Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division df-60379:A1 • E-400 S CRF.300(A) Relay Module (2) FlreLrre°Atarms by Honeywell fl General The CRF-300(A) Addressable Relay Module provides the sys- tem with a dry-contact output for activating a variety of auxil- iary devices, such as tans, door holders, dampers, control equipment, etc. Addressability allows the dry contact to be activated through panel programming, on a select basis. LiteSpeedTM is a communication protocol developed by Fire•Lite Engineering that greatly enhances the speed of com- munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. Features Built-in type identification automatically identifies these devices to the control panel. Internal circuitry and relay powered directly by two-wire SLC loop. Integral LED "blinks" green each time a communication is received from the control panel and turns on in steady red when activated. High noise immunity (EMF/RFl). Wide viewing angle of LED. SEMS screws with clamping plates for wiring ease. Direct-dial entry of address: 01— 159 for MS-9600(A) series panels, 01 —99 on MS-9200UDLS(A) and MS-9050UD(A). Applications The CRF-300(A) may be programmed to operate dry contacts for door holders, Air Handling Unit shutdown, etc., and to reset four-wire smoke detector power. Construction The face plate is made of off-white heat-resistant plastic. Controls include two rotary switches for direct-dial entry of address setting. The CRF-300(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. The CRF-300(A) provides two Form-C dry contacts that switch together. Operation Each CRF-300(A) uses one of the addresses on a SLC loop. It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notification Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. NOTE: Open/short supervision is suspended with the CRF-300. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a control module and a relay module. r1 047W CRF-300(A) Specifications Normal operating voltage: 15 to 32 VDC. Maximum SLC current draw: 6.5 mA (LED on). Average operating current: 230 pA direct poll (CLIP mode), 255 pA group poll (LiteSpeed mode) with LED flashing. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 mm) deep box. Relay Contact Ratings Load Description Application Maximum Current Voltage Rating Resistive Non-Coded 30 VDC 3.0 A Resistive Coded 30 VDC 2.0 A Resistive Non-Coded 110 VDC 0.9 A Resistive Non-Coded 125 VAC 0.9 A Inductive (LIR5ms) Coded 30 VDC 0.5 A Inductive (LIR=2ms) Coded 30 VDC 1.0 A Inductive (PF=0.35) Non-Coded 125 VAC 0.5 A df-60379:A1 • 08/04/09 - Page 1 of 2 Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S2424 ULC: S2424 FM approved CSFM: 7300-0075:185 MEA:72-01-E Product Line Information CRF-300(A): Intelligent addressable relay module. Intelligent addressable relay module, ULC listed model. SMB500: Optional surface-mount backbox. NOTE: For installation instructions, see document /56-1190-005 and refer to the SLC Wiring Manual, document 51309. [1 LiteSpeedTM is a trademark and Fire-Lite® Alarms is a registered trademark of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. Iso 9001 We try to keep our product information up-to-date and accurate. • ., We cannot cover all specific applications or anticipate all requirements. S IMJNI 8 MANIJFAE11JIJN All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 2 of 2— dt-60379:A1 • 08/04/09 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0075:0185 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: FIRE-LITE ALARMS lNC.One Fire-Lite Place, Northford, CT 06410-1653 Contact: Pete Sennett (203) 484-7161 Fax (203) 484-7309 Email: pete.sennett@Honeywell.com DESIGN: Models MDF-300, MMF-301, MMF-300, MMF-302, MCF-300 monitor modules; Models CRF-300 and CMF-300 control modules; and MMF-302-6 six zone interface signaling device module. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 15-32 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model designation, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically compatible fire alarm control units. NOTE: S *Rev. 05-06-05 JW This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 0 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division O SYSTEM $ SENSOR / S Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L -Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features Updated Modern Aesthetics Small profile devices for Horns and Horn Strobes Plug-in design with minimal intrusion into the back box Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 30 candela Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and two volume selections Mounting plate for all standard and all compact wall units Mounting plate shorting spring checks wiring continuity before device installation Electrically compatible with legacy SpectrAlert and SpectrAlert Advance devices Compatible with MDL3 sync module Strobes and Horn Strobes listed for wall mounting only Horns listed for wall or ceiling use The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, standard and compact devices, and plain, FIRE, and FUEGO-printed devices, System Sensor L-Series can meet virtually any application requirement. The L-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time-consuming ground faults. To further simplify installation and protect devices from construction damage, the L-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Agency Listings SIGNALING 0 LISTED APPROVED S5512 FM approved Cocept 71251653,0564 S4015 for ALERT models 7135-1653:0503 3057363. 3057072 - AVDS865-05 • 2/22/2018 • Page 1 Ma Architect/Engineer Specification General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 17/8-inch back box, 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, [-Series products, when used with the SynceCircuif° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor [-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model ______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model ______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync-Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/s-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more S synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltaoe Regulated 12 DC or regulated 24 DC/FWR1 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6'T x 4.7"W x 1.91"D (143 mm L x 119 mm W x 49 mm D) Compact Wall-Mount Dimensions (including lens) 5.26" Lx 3.46" W x 1.91" D (133 mm Lx 88 mm W x 49 mm 0) Horn Dimensions 5.6"L x 4.7'W x 1.25"D (143 mm Lx 119 mm W x 32 mm D) Compact Horn Dimensions 5.25" L x3.45" W x 1.25" D (133 mm Lx 88 mm W x 32 mm D) Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. S AVDS86505 • 2/22/2018 • Page 2 UL Current Draw Data tJJu Strobe Current uDraw zlw..I;Iii tJJu Max. Horn rTCurrent 1uDraw zmy..1 RIMS) 1 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max. Current Draw (rnA RMS), Wall Horn Strobe, Candela Range (15-185 cd) 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd llOcd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.lKTemporal High 93 156 53 73 119 140 164 190 242 3.lKTemporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 16-33 Volts FWR Input 15cd 30cd 75cd 95cd llOcd 135cd 185cd Temporal High 83 107 156 177 198 234 287 W Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.lKTemporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 Horn Tones and Sound Output Data Switch Position Sound Pattern dB 8-17.5 Volts DC 16-33 Volts DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9* Coded High 85 90 90 10* 3.1 KHz Coded High 84 89 89 S * Settings 9 and 10 are not available on 2-wire horn be provided by the NAC. If the NAC voltage is held constantly on. strobes. Temporal coding must constant, the horn output remains AvoSe65-05 • 2/22/2018 • Page 3 .q. Horn L-Series Dimensions 191, - 3.46" —md 48.5 min 88 m I I ______ 125 357 —i 155" _______ 1.25" I 08 MM 32mm 9,1 cm) (3.9 cm) 32mm 1 1.!:. up 5.2? .'.!.!.f4'. s.2r 133.9 mm _ 5W (13.7) —710 133.9mm _ A0548-00 A0547-00 A0557-00 Compact Strobe, Horn Strobe Compact Horn Compact Wall Surface Mount Back Box SBBGRL, SBBGWL 4.70' (11.94 cm) - 1.91" (4.85 cm) 1.25' (3.18 mm) 5.67 (14.4 cm) Strobe, Horn Strobe A0550-00 (12.24 cm) "i 1.85" I I (469 cm) A0554-01 Wall Surface Mount Back Box SBBRLISBBWL S L-Series Ordering Information Model Description CM Wall Horn Strobes Horns* P2RL 2-Wire, Horn Strobe, Red HRL* Horn, Red P2WL 2-Wire, Horn Strobe, White HWL* Horn, White P2GRL 2-Wire, Compact Horn Strobe, Red HGRL* Compact Horn, Red P2GWL 2-Wire, Comp 2 fi)s act Horn Strobe, White HGWL* Compact Horn, White P2RL-P 2-Wire, Horn Strobe, Red, Plain Accessories P2WL-P 2-Wire, Horn Strobe, White, Plain TR-2 Universal Wall Trim Ring Red P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO TR-2W Universal Wall Trim Ring White P2WL-SP 2-Wire, Horn Strobe, White, FUEGO SBBRL Wall Surface Mount Back Box, Red P4RL 4-Wire, Horn Strobe, Red SBBWL Wall Surface Mount Back Box, White P4WL 4-Wire, Horn Strobe, White SBBGRL Compact Wall Surface Mount Back Box, Red Wall Strobes SBBGWL Compact Wall Surface Mount Back Box, White SRL Strobe, Red SWL Strobe, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT Notes: All -P models have a plain housing (no FIRE marking on cover). All -SP models have "FUEGO" marking on cover. All -ALERT models have "ALERT" marking on cover. "Horn-only models are listed for wall or ceiling use. SYSTEM 3825 Ohio Avenue • St. Charles, IL 60174 ©2018 SystemSensor, for current product information, including the latest version of this data sheet. Phone: 800-SENSOR2 • Fax 630-377-6495 Product specifications sUbiect to change WOhOUI notice. Visit systemsensor.com wv. systemsensor.com AV0S865.05 • 2/22/2015 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7135-1653:0503 Page 1 of 2 CATEGORY: 7135 --AUDIBLE DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Pete Sennett (630) 762-5362 Fax (203) 484-7309 Email: pete.sennett©honeywell.com DESIGN: System Sensor Indoor 2-wire and *4..wire Models: HWL, HRL, HGWL and HGRL Horns; CHWL and CHRL Chimes; P2RL, P2WL, P2GRL, P2GWL, P2RL-P, P2WL-P, P2RL-SP, P2WL-SP, *P4RL and *P4WL Wall Horn Strobes; PC2RL, PC2WL, *PC4RL and *PC4WL Ceiling Horn Strobes; CHSRL and CHSWL Wall Chime Strobes; CHSCRL and CHSCWL Ceiling Chime Strobes; Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG, BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, S Ceiling Bezel Parts: BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. Color Lens: LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS-RC2. WallTrim Rings: *TR2 and *TR2W CeilingTrim Rings: *TRC2 and *TRC2W Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: Revision 08-21-2017 dcc øTi This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct V* operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 5 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Listing No. 7135-1653:0503 Page 2 of 2 SBBCRL and SBBCWL MP120KL 120 VAC Adapter Mounting Plate Refer to listee's data sheet for detailed product description and operational considerations. RATING: 12 VDC regulated and 24 VDC/FWR INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as audible devices when used with separately listed compatible fire alarm control units. Suitable for indoor use, wall or ceiling mounted. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. Revision 08-21-2017 dcc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 0 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division O SYSTEM $ SENSOR Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and-modem aesthetics. Features Plug-in design with minimal intrusion into the back box 5 • Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 30 candela Field-selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and two volume selections Universal mounting plate for ceiling units Mounting plate shorting spring feature checks wiring continuity before device installation Electrically Compatible with legacy SpectrAlert and SpectrAlert Advance devices Compatible with MDL3 sync module Listed for ceiling mounting only The System Sensor L-Series otters the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, wall and ceiling mounting options, System Sensor L-Series can meet virtually any application requirement. The entire L-Series product line of ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time- consuming ground faults. To further simplify installation, the L-Series utilizes a universal mounting plate so installers can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Agency Listings SIGNALING S LISTED APPROVED S5512 FM approved except 7125-16530504 S4011 for ALERT models 7135-16500503 3057383 AVDS8SO-02 • 12)0112017 • Page 3 • L-Series Specifications yrniT1IY11Irn1.i. General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 x 4 x 17/8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync.Circuit° Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor [-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor [-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync.Circuit model MD[3 listed to U[ 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11/16 x 4 11/16 x 2 1/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3) 8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) InDut Terminal Wire Gauae 12 to 18 AWG Ceiling-Mount Dimensions (including lens) 6.8" diameter x 2.5" high (173 mm diameter x 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) (SBBCRL, SBBCWL) Notes: 1, Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, 5, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. AVDS868-02 • 12/01/2017 • Page 2 S UL Current Draw Data UL Max. Strobe Current Draw (rnA RMS)IuJu Max. Horn iCurrent Draw :1 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 87 41 60 Temporal High 39 44 54 Range 30 153 63 86 Temporal Low 28 32 54 75 N/A 111 142 Non-Temporal High 43 47 54 95 N/A 134 164 Non-Temporal Low 29 32 54 115 N/A 158 191 3.1 KHz Temporal High 39 41 54 150 N/A 189 228 3.1 KHz Temporal Low 29 32 54 177 N/A 226 264 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max. Current Draw (rnA RMS), Ceiling Horn Strobe, Candela Range (15-177 cd) 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.lKTemporal High 111 164 69 94 147 163 184 229 257 3.lKTemporal Low 103 163 54 88 143 155 185 212 252 3.1 K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 FWR Input 16-33 Volts 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High S 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3,lKTemporal Low 79 101 150 171 196 229 260 3,1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 Horn Strobe Tones Horn Strobe Output (dBA) Switch Position Sound Pattern and Sound Output Data 8-17.5 16-33 Volts Volts dB DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 AVDS868-02 • 12)01/2017 • Page 3 2.47' (62.7 mm) 1.37 (34.8 mm) 6.83 d (173n 6.92 rlir" (175. A0545-00 (64 mm) A0546-00 L-Series Dimensions Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box S -01 1.1 2-Wire Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box L-Series Ordering Information Ceiling Horn Strobes PC2RL 2-Wire, Horn Strobe, Red PC2WL 2-Wire, Horn Strobe, White 4-Wire Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box Ceiling Strobes SCRL Strobe, Red SCWL Strobe, White PC4RL 4-Wire, Horn Strobe, Red SCWL-CLR-ALERT Strobe, White, ALERT PC4WL 4-Wire, Horn Strobe, White Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White For a ceiling-listed horn-only device, see AVDS865 "Indoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications". SSYSTEM 3825 Ohio Avenue • St. Charles, IL 60174 @2017SysternSensor Product sp cii Icetlons subject to change vathout notice Visit systemsensor.com to, current product ntorrsatieri, including the latest version of this data sheet. SENSOR' Phone: 800-SENSOR2 • Fax: 630-377-6495 AVDS868-02 • 12101/2017 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-1653:0504 Page 1 of 2 CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Pete Sennett (630) 762-5362 Fax (203) 484-7309 Email: pete.sennett@honeywell.com DESIGN: System Sensor Indoor 2-wire Models: SRL, SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT Wall Strobes; SCRL, SCWL and SCWL-CLR-ALERT Ceiling Strobes. Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG, BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, Ceiling Bezel Parts: BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. S Color Lens: LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS-RC2. Walllrim Rings: TR2 and TR2W CeilingTrim Rings: TRC2 and TRC2W. Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: SBBCRL and SBBCWL Refer to listee's data sheet for detailed product description and operational considerations. 02-14-17 gt rt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 0 Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Listing No. 7125-1653-.0504 Page 2 of 2 .0 RATING: Regulated 12 VDC setting: 8-17.5 VDC Regulated 24 VDC/fwr setting: 16-33 VDC INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as two wire strobe units used for synchronous application when used with separately listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal ceiling mounted. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. S 02-14-17 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other is Date Issued: July 01, 2018 Listing Expires June 30, 2019 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division ff'CZo9 -otOl SYSTEM RECORD OF COMPLETION This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert NM in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. Form Completion Date: 8/10/2020 Supplemental Pages Attached: 2 PROPERTY INFORMATION Name of property: Olivenhain Water District Offices Address: 1966 Olivenhain Road, Encinitas, CA 92024 Description of property: Office and meeting space Name of property representative: Olivenhain Water District - Marvin Cohen Address: 1966 Olivenhain Road, Encinitas, CA 92024 Phone: 760-415-8744 Fax: E-mail: INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION Installation contractor: Electronic Control System, LLC, DBA Albireo Energy Address: 12575 Kirkham Court, Suite 1, Poway, 92064 Phone: (858).513-1911 Fax: E-mail: Service organization: Electronic Control System, LLC, DBA Albireo Energy Address: 12575 Kirkham Court, Suite 1, Poway, 92064 Phone: (858) 513-1911 Fax: E-mail: Testing organization: Electronic Control System, LLC, DBA Albireo Energy Address: 12575 Kirkham Court, Suite 1, Poway, 92064 Phone: (858) 513-1911 Fax: E-mail: Effective date for test and inspection contract: Monitoring organization: CCS Central Monitoring Address: Phone: 858-748-0211 Fax: E-mail: Account number: 5132209 Phone line 1: Phone line 2: Means of transmission: Cellular Entity to which alarms are retransmitted: CCS Central Monitoring Phone: 858-748-0211 DOCUMENTATION On-site location of the required record documents and site-specific software: at FACP DESCRIPTION OF SYSTEM OR SERVICE This is a: 0 New system 0 Modification to existing system Permit number: FPC20I9-0101 NFPA 72 edition: 2016 4.1 Control Unit Manufacturer: Firelite by Honeywell Model number: ES-200X 4.2 Software and Firmware Firmware revision number: v. 1.02.008 4.3 Alarm Verification This system does not incorporate alarm verification. Number of devices subject to alarm verification: N/A Alarm verification set for N/A seconds Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p.1 of 3) SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: 120v Overcurrent protection: Type: Circuit Breaker Branch circuit disconnecting means location: Fire Control Room Control panel amps: 20 Amps: 20 Number: Panel E Circuit 9 5.1.2 Secondary Power Type of secondary power: Battery Location, if remote from the plant: N/A Calculated capacity of secondary power to drive the system: In standby mode (hours): 24 In alarm mode (minutes): 5 5.2 Control Unit 0 This system does not have power extender panels D Power extender panels are listed on supplementary sheet A CIRCUITS ANfl PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line NO YES B Device Power N/A N/A N/A N/A Initiating Device N/A N/A N/A N/A Notification Appliance NO YES B 1 Other (specify): N/A N/A N/A N/A REMOTE ANNUNCIATORS Location ANN-80 I Main Lobby INITIATING DEVICES Type Quantity Addressable or Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 1 Addressable Alarm Double Action Pull Smoke Detectors 2 Addresdsable Alarm Photoelectric Duct Smoke Detectors 26 Addressable Supervisory Photoelectric Heat Detectors N/A N/A N/A N/A Gas Detectors N/A N/A N/A N/A Waterfiow Switches 2 Conventional Alarm Tamper Switches 4 Conventional Supervisory Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. 2 of 3) SYSTEM RECORD OF COMPLETION (continued) NOTIFICATION APPLIANCES Type Quantity Description Audible N/A N/A Visible 15 Ceiling Mount Strobe Combination Audible and Visible 44 Ceiling and Wall Mount Horn Strobe SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices N/A HVAC Shutdown 21 Fire/Smoke Dampers 5 Door Unlocking N/A Elevator Recall N/A Elevator Shunt Trip N/A INTERCONNECTED SYSTEMS This system does not have interconnected systems. systems are liste on p efficathrysheet CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system ed Fei1rt intalled according to all NFPA standards cited herein. Signed: Chris Vanderburg Printed name: ___ Organization: Albireo Energy Title: Foreman 12.2 System Operational Test This g to all NFPA standards cited herein. n:din Signed: Printed name: Chris Vanderburg _________________________________ Organization: Albireo Energy Title: Foreman 12.3 Acceptance Test Date and time of acceptance test: Installing contractor representative: Testing contractor representative: Property representative: AHJ representative: - Date: 5/26/2020 Phone: 858-967-7525 Date: 5/26/2020 Phone: 858-967-7525 Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p.3 of 3) NOTIFICATION APPLIANCE POWER PANEL SUPPLEMENTARY RECORD OF COMPLETION This form is a supplement to the System Record of Completion. It includes a list of types and locations of notification appliance power extender panels. This form is to be completed by The system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Form Completion Date: 8/7/2020 Number of Supplemental Pages Attached: 1 PROPERTY INFORMATION Name of property: Olivenhain Water District Office Address: 1966 Olivenhain Road, Encinitas, CA 92024 NOTIFICATION APPLIANCE POWER EXTENDER PANELS See Main System Record of Completion for additional information, certifications, and approvals. Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. lof 1) INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING This form is a supplement to the System Record of Inspection and Testing. It includes an initiating device test record. This form is to be completed by the system inspection and testing contractor at the time of the inspection and/or test. It shall be permitted to modifj, this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Inspection/Test Start Date/Time: 8/7/2020 11:30am Inspection/Test Completion Date/Time: 8/7/2020 2:30pm Number of Supplemental Pages Attached: PROPERTY INFORMATION Name of property: Olivenhain Water District Office Address: 1966 Olivenhain Road, Encinitas, CA 92024 INITIATING DEVICE TEST RESULTS Device Type Address Location Test Results Smoke Detector Li D001 Above FACP PASS Pull Station Li M001 At FACP PASS Duct Detector Li D002 FC 1.14 PASS Duct Detector Li D003 FC 1.15 PASS Duct Detector Li D004 FC 1.16 PASS Duct Detector Li D005 FC 1.17 PASS Duct Detector Li D006 FC 1.19 PASS Duct Detector Li D007 FC 1.12 PASS Duct Detector Li 0008 FC 1.11 PASS Duct Detector Li 0009 FC 1.10 PASS Duct Detector Li D010 FC 1.09 PASS Duct Detector Li DO1 i FC 1.08 PASS Duct Detector Li D012 FC 1.06 PASS Duct Detector Li D013 FC 1.05 PASS Duct Detector Li D014 FC 1.03 PASS Duct Detector Li 0015 FC 1.01 PASS Duct Detector Li D016 FC 2.01 PASS Duct Detector Li D017 FC 2.06 PASS Duct Detector Li D018 FC 2.04 PASS Smoke Detector Li 0019 Electrical room above NPS PASS Duct Detector Li D020 FC 2.09 PASS Duct Detector Li 0021 FC 3.02 PASS Duct Detector Li 0022 FC 3.06 PASS Duct Detector Li 0023 I FC 3.05 PASS Duct Detector Li 0024 I FSDI Conference room 132 PASS Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. 1 of 2) INITIATING DEVICE SUPPLEMENTARY RECORD OF INSPECTION AND TESTING (continued) 2. INITIATING DEVICE TEST RESULTS (continued) Device Type Address Location Test Results Duct Detector Li 0025 FSD2 Conference room 132 PASS Duct Detector Li 0026 FSD3 Conference room 132 PASS Duct Detector Li D027 FSD4 Conference room 132 PASS Duct Detector Li 0028 FSD5 Conference room 132 PASS Waterulow Li M020 Fire riser room 165 PASS Tamper Li M021 Fire riser room 165 PASS Tamper Li M025 Backflow OS&Y PASS Waterfiow Li M029 Building J PASS Tamper Li M030 Building J PASS Tamper Li M031 Building J OS&Y PASS See main System Record of Inspection and Testing for additional information, certifications, and approvals. Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. 2 of 2)