HomeMy WebLinkAbout5750 ORION ST; ; FA100061; Permit1/6/2021 FA100061 Permit Data
City of Carlsbad
Fire Alarm Permit
Job Address: 5750 ORION ST
Permit Type: FALARM
Parcel No: 2090502600
Lot #: 0
Permit No: FAI 00061
Status: ISSUED
Applied 10/12/2010
Approved: 10/12/2010
Reference No.: Issued: 10/12/2010
PC #: Inspector:
Project Title: FIRST RESPONDER FACILITY FIRE ALARM PLAN CHECK &
INSPECTIONS
Applicant: Owner:
SIMPLEX GRINNELL CITY OF CARLSBAD
3568 RUFFIN ROAD
SAN DIEGO CA PUBLIC AGENCY
858-633-9100
Fees () Add'I Fees ($) Total ($) Balance ($)
0 0 0 0
1/1
NFPA Record of Completion Poo0 I
Name of Protected Property Carlsbad First Joint Responder Training Facility
Address 5750 Orion Street Carlsbad CA 92010
Rep. of Protected Property (name/phone)
Authority Having Jurisdiction Carlsbad Fire Department Greg Ryan li1
Address I Phone Number 760-602-4660
1. Type(s) of System or Service:
X NFPA 72, Chapter 3 - Local
if alarm is transmitted to location(s) off premise, list where received:
Rancho Santa Fe Security
N/A NFPA 72, Chapter 3 - Emergency Voice /Alarm Service:
Quantity of voice/alarm channels Single: Multiple:
Quantity of speakers installed: Quantity of speaker zones:
Quantity of telephones or telephone jacks included in the system:
N/A NFPA 72, Chapter 4 - Auxiliary
Indicate type of connection:
Local Energy, Shunt, Parallel Telephone
Location and telephone number for receipt of signals:
N/A NFPA 72, Chapter 4 - Remote Station
Alarm:
Supervisory:
N/A NFPA 72, Chapter 4 - Proprietary
If alarms are retransmitted to public fire service communications center or others, indicate location and
telephone number of the organization receiving alarm:
Indicate how alarm is retransmitted:
N/A NFPA 72, Chapter 4 - Central Statr'77
The prime contractor: j,iO ' !è- (Ag4r.f
Central Station Location:
Means of transmission of signals from the protected premise to the central station:
Mculloh Multiplex One-Way Radio
Digital Alarm Communicator Two-Way Radio Others
Means of transmission of alarms to the public fire service communications center:
a) N/A
b)N/A
System Location:
Organization Name / Phone Representative Name / Phone
Installer SimplexGrinnell Bob Ciereck 858-633-9100
Supplier Simplex Grinnell Mark Walker 858-633-9100
Service Organization SimplexGrinnell Brian Pipkin 858-633-9100
Page 1 of 1
NFPA Record of Completion
Location of (As-Built) Drawings:
City of Carlsbad
Location of Owners Manuals:
Same
Location of Test Reports:
Unknown
A contract, dated N/A , for test and inspection in accordance with NFPA standard(s) No(s),
1'?'
, dated pfe.- , is in effect.
2 Record of System Installation
(Fill out after installation is complete and wiring checked for opens,shorts,ground faults and improper branching
but prior to conducting operational acceptance tests.)
This system has been installed in accordance with the NFPA standards as shown below,was inspected by
SimplexGrinnell on 3/20/2012 , includes the devices shown below and has been in
service since 3/20/2012
X NFPA 72, Chapters 1 3 4 5 6 7 (Circle all that apply)
X NFPA 70, National Electric Code Article 760
X Manufacturer's Instructions
Othor.(-SQecify)
Signed: k, 'i- Date: 3/20/2012
Organization: SimplexGrinnell
Record of System Operation
All operational features and functions of this system were tested by SimplexGrinnell Date: 3/20/2012
and found to be operating properly in accordance with requirements of:
x NFPA 72, Chapters 1 3 4 5 6 7 (Circle all that apply)
x NFPA 70, National Electric Code Article 760
x Manufacturer's Instructions
O..(-.pecify)
Signed: ( 4lfr__ Date: 3/20/2012
Organization: SimplexGrinnell
Alarm Initiating Devices and circuits (Use blanks-to indicate quantity of devices.)
Manual
5 Manual Stations x Noncoded Activating Transmitters Coded
Combination Manual Fire Alarm and Guard's Tour Coded Stations.
Automatic
Coverage: Complete Partial X
49 Smoke/Heat Detectors Ion X Photo
0 Duct Detectors Ion X Photo
31 Heat Detectors FT RR X FT/RR RC
1 Sprinkler Waterfiow Switches Transmitters X Noncoded,Activating Coded
0 Other(list):
5. Supervisory Signal Initiating Devises and Circuits (Use blanks to indicate quantity of devices.)
Guard's Tour
bYA . Coded Stations
N/A Noncoded Stations Activating _Transmitters
N/A Compulsory Guard Tour System Comprised of Transmitter Stations and
Note: Combination devices recorded under 4(b) and 5(a).
Intermediate Stations
Page 1 of 1
3.
4
Sprinkler System
2 Coded Valve Supervisory Signaling Attachments
N/A Valve Supervisory Switches Activating -
N/A Building Temperature Points
N/A Site Water Temperature Points
N/A Site Water Supply Level Points
Electric Fire Pump:
N/A Fire Pump Power
N/A Fire Pump Running
N/A Phase Reversal
Engine Driven Fire Pump:
N/A Selector in Auto Position
N/A Engine or Control Panel Trouble
N/A Fire Pump Running
Engine Driven Generator:
N/A Selector in Auto Position
N/A Control Panel Trouble
N/A Transfer Switches
N/A Engine Running
Other Supervisory Function(s) (Specify)
NONE
C)
k)
Transmitters
NFPA Record of Completion
g)
7.
Alarm Notification Appliances and Circuits
Quantity of indicating appliance circuits connected to the system:
Types and quantities of alarm indicating appliances installed:
Bells Inch
Speakers
9 Horns
Chimes
Other:
35 Visual Signals Type: Xenon
24 with audible 11 w/o audible
I Local Annunciator Admin Lobby
Signaling Line Circuits:
Quantity and Style (See NFPA 72, Table 3-6) of signaling line circuits connected to the system.
Quantity: 8 Style: Y
System Power Supplies
Primary (Main ): Nominal Voltage: 120 VAC Current Rating: 6A
Overcurrent Protection: Type: Circuit Breaker Current Rating: 20A
Location: Panel RECEP Circuit 38
Secondary (Standby):
X Storage Batteries Amp-Hour Rating 25 amp hour
Calculated capacity to drive system, in hours: X 24 60
N/A Engine driven generator dedicated to fire alarm system:
N/A Location of fuel storage:
Emergency/Standby System used as backup to Primary Power Supply, instead of useing a secondary Power supply:
N/A Emergency System described in NFPA 70, Article 700
N/A Legally Required Standby System described in NFPA 70, Article 701
N/A Optional Standby System described in NFPA 70, Article 702, which also meets the performance
requirements of Article 700 or 701
Page 1 of 1
/ 9
NFPA Record of Completion
System Software
Operating System Software Revision Level(s) 11.08
Application Software Revision Level(s): Rev 86
Revision Completed by: Mike Duer SimplexGrinnell
(name) (firm)
10. Comments:
(signed ) for Central Station or Alarm Service Company (title) (date)
Frequency of routine tests and inspections, if other than in accordance with the referenced NFPA standard(s):
NOT IN CONTRACT
System deviations from the referenced NFPA standard(s) are:
NONE
(signed) for Central Station or Alarm Service Company (title) (date)
Upon ompletio e system(s) satisfactory test(s) witnessed (if required by the authority having jurisdiction):
(si ed) re rkerltakve of the authority having jurisdiction (title) ( 'ate)
Page 1 of 1