Loading...
HomeMy WebLinkAbout5661 PALMER WAY; ; FS100016; Permit12/1412020 FSI00016 Permit Data City of Carlsbad Fixed Systems Permit Job Address: 5661 PALMER WY Permit Type: FIXSYS Parcel No: Lot #: 0 Permit No: FSI000I6 Status: ISSUED Applied 8/6/2010 Approved: 9/1/2010 Reference No.: Issued: 9/1/2010 PC #: Inspector: Project Title: CREATIVE FLAVORINGS 5661 PALMER WY Applicant: Owner: Fees ($) Add'l Fees ($) Total ($) Balance ($) 130 0 130 0 1/1 f'S [3 (4 System Design CHAPTER 3 SYSTEM DESIGN 3-1 INTRODUCTION This chapter introduces the designer and installer to the process whereby Range Guard® Wet Chemical Systems are designed. It outlines the process, introduces the limitations imposed on design by system hardware, as well as those mandated by performance considerations. As the designer becomes familiar with this material, they should remember that analysis and design is a careful, step-by-step process. All steps must be followed, none can be omitted, and all unique aspects of a given application must be taken into account if the resulting fire-suppression system is to deliver the desired results. All systems must be designed in accordance with the latest edition of NFPA Standard 17A, "Standard for Wet Chemical Systems", and other applicable NFPA standards. All configurations are UL and ULC/ORD 1254.6 Listed to Underwriters Laboratories 300, 1994 Edition, unless otherwise noted. 3-2 DESIGN PROCEDURE This section covers the design aspects of the Karbaloy systems. It contains all the necessary information to design a complete system including nozzle placement, detector placement, cylinder sizing, piping limitations and auxiliary hardware. 3-2.1 General Design Procedure Analysis and design should be approached as a methodical process, and performed step-by-step. Only when all the steps are followed is the resulting system likely to perform as desired. If any step is omitted, it is probable that the system will not function as well as it should. The steps in the analysis and design process are: Hazard analysis Nozzle selection, number and location Cylinders (Number, size, and location of cylinders) Detector selection Piping layout Auxiliary requirements 3-2.1.1 HAZARD ANALYSIS Sketch out the kitchen exhaust hood and appliances, taking note of the path of egress for remote pull station location, discuss with owner the placement of cylinders and control heads, automatic fuel shut down device locations, and any power shutdowns required. Consult NFPA 17A and 96 for design guidelines. Record the following and include in your sketch: Size of exhaust hood(s) and exhaust duct opening(s) Size and fuel type of appliances (take note if open flames are sufficiently separated from combustible cooking media) Size of gas line(s) feeding appliances Building or local alarms P/N 9127100 3-1 January 2007 System Design Make up air or auxiliary equipment Are the correct hand portable fire extinguishers present or are additional extinguishers required 3-2.1.2 NOZZLE SELECTION AND LOCATION Select the number and type(s) of nozzle(s) needed and locate them so that the entire hazard is covered. Use the coverage/distribution specifications for each nozzle type to determine the number of discharge nozzles required to deliver the necessary quantity of wet chemical given nozzle placement appropriate to the hazard. 3-2.1.3 CYLINDER DETERMINATION (NUMBER, SIZE, AND LOCATION OF CYLINDER(S)) Determine the number of nozzles required, whether additional agent or nozzles may be needed, and select the cylinder which will supply the needed amounts wet chemical. After determining the quantity and types of wet chemical needed to control the hazard itself, determine whether any special conditions necessitate additional wet chemical quantities anchor nozzles. For example, it may be necessary to adjust the agent discharge rate in order to offset the effects of ventilation, or it may be necessary to screen openings in an enclosure to prevent wet chemical leakage through those openings. 3-2.1.4 DETECTOR SELECTION Detector selection will depend on the response speed required, the probable heat level and rate of spread of the fire. The detectors sense the heat energy released by the combustion of fuel and oxygen. Upon detection of a fire, the detection system sends a signal to the system control head(s) which initiates the wet chemical discharge. The most commonly used detectors are the: Fixed-temperature thermo-bulb or fusible link Fixed-temperature rate-compensated thermostat 3-2.1.5 PIPING LAYOUT Careful piping layout assures that the agent reaches the distribution nozzles appropriately, and that piping parameters are not exceeded. These parameters involve pipe lengths, the number of elbows, and other factors such as the allowable distances (equivalent/feet) from Cylinder and Valve Assembly. These parameters are discussed in detail in the design examples in Paragraph 3-8. 3-2.1.6 AUXILIARY REQUIREMENTS Controls are required to turn off force-draft ventilation systems, fuel (or combustible-liquid) pumps, conveyors, and so on. January 2007 3-2 P/N 9127100 System Design 3-3 DESIGNING FOR APPLIANCE PROTECTION To determine the number and size of cylinders required for each system, the term 'flow number' is used. A flow number is assigned to each type of nozzle used in the Range Guard system and is a relative indicator of the discharge rate of each nozzle. Refer to Table 3-1 for coverage on a specific appliance. ADP nozzles have a flow number of one. The ADP nozzle is used to protect a variety of cooking appliances. These appliances are solid fuel charbroilers, upright broilers, low proximity Split Vat Deep Fat Fryers, griddles and chain broilers. Additionally, the ADP nozzle is used to protect the duct and plenum areas of the hood. The F' nozzle has a flow number of two and is used to protect fryers and lava rock broilers. The R nozzle has a flow number of one and is used to protect a burner range. The GRW nozzle has a flow number of one and is used to protect a radiant charbroiler or a wok. The LPF nozzle has a flow number of two and is used to protect a deep fat fryer requiring a low nozzle height. The LPR nozzle has a flow number of one and is used to protect a four burner range requiring a low nozzle height (eg. range with a backshelf or an integral broiler). The DM nozzle has a flow number of three and is used to protect the mesquite log charbroiler. After completing your design for locating nozzles over the cooking appliances to be protected, determine the total of the flow numbers required, including those for the plenum and exhaust duct(s). This will render the required cylinder size for the total number of flow points. Note: Protection of combination appliances requires a seperate nozzle for each appliance. While nozzles can be placed anywhere in the areas denoted in the following sections, caution should be exercised regarding placement and aiming of nozzles from the back of CAUTION the appliance toward appliance operators. P/N 9127100 3-3 January 2007 System Design 3-3.1 Nozzle Height Measurement of the nozzle heights are to be from the tip of the nozzle to the top of the appliance. When using the grid style nozzle location the nozzle height is measured from the nozzle tip to the aiming point. When using perimeter style nozzle location the nozzle height is measured from the nozzle tip straight down to the appliance surface. EXCEPTION: Woks are measured to the inside bottom of the wok. 3-3.2 Nozzle Aim Correct aiming of the appliance nozzles is extremely important to the performance of the system. Care should be taken to insure accurate aiming and that the conical spray from the nozzle is not obstructed. Aiming must comply with the parameters outlined in the design section of this manual. 3-3.3 Hazard Area The hazard area is the actual size of the portion of the appliance which can be used for cooking. The physical width of an appliance does not represent the width of the hazard area. The thickness to the appliance wall must be deducted to arrive at the hazard area width. Ak All appliances being protected must be shut off automatically upon system actuation. CAUTION The appliance area is the size of the appliance that includes the cooking area (fry pot or vat) and the integral drip board area. NOZZLE HEIGHT MEASURED FROM TOP OF APPLIANCE Appliance Area Appliance Area * Length 1+ Width —I Hazard Area I I Hazard Area I Length 1*- Width •1 Nozzle Height Measured from Top of Cooking Surface Nozzle Height Measured from Top of Cooking Surface Hazard Area Width/Length e e e eq p ee e q L CHARBROILER nfl. Side View Front Section View FULL VAT DEEP FAT FRYER L.... Hazard Area I Width/Length GAS RANGE Figure 3-1. Examples of Hazard Areas for Typical Appliances January 2007 3-4 P/N 9127100 System Design 3-4 APPLIANCES Table 3-1 lists the various appliances and nozzle type used to protect that appliance. Table 3-1. Appliance References Appliance Reference Nozzle Flow Number Deep Vat Fryer Single Vat Deep Fryer with Drip Boards Paragraph 3-4.1 F 2 18-1/2 in. x 24-1/2 in. Deep Fat Fryer Paragraph 3-4.2 (2) F 4 Split Vat Deep Fat Fryer Paragraph 3-4.3 F 2 14 in. x 14 in. (356 mm x 356 mm) Deep Fat Fryer Paragraph 3-4.4 F 2 Single Vat Deep Fryer with Drip Boards less than 1 in. (25 mm) Paragraph 3-4.5 F 2 Split Vat Deep Fat Fryer (Low Proximity) Paragraph 3-4.6 ADP 1 Deep Fat Fryer (Low Proximity) Paragraph 3-4.7 LPF 2 Krispy Kreme Model 270 d/h Doughnut Fryer Paragraph 3-4.8 ADP 1 Ranges Four-Burner Range Paragraph 3-4.9 R 1 Two-Burner Range Paragraph 3-4.10 R 1 Single Burner Range Paragraph 3-4.11 R 1 Four-Burner Range Paragraph 3-4.12 LPR 1 Broilers Upright Broilers Paragraph 3-4.13 ADP 1 Charbroilers (Lava, Pumice, Ceramic, or Synthetic Rock) Paragraph 3-4.14 F 2 Gas Radiant/Electric Charbroiler Paragraph 3-4.15 GRW 1 Natural or Mesquite Charcoal Charbroiler Paragraph 3-4.16 ADP 1 Mesquite Logs Charbroiler Paragraph 3-4.17 DM 3 Chain Broiler (Closed-Top) Paragraph 3-4.18 ADP 1 Chain Broiler (Open-Top) Paragraph 3-4.19 ADP 1 Griddle - Flat Cooking Surface Paragraph 3-4.20 ADP 1 Wok Paragraph 3-4.21 GRW 1 Tilt Skillets (Braising Pans) Paragraph 3-4.22 F 2 P/N 9127100 3-5 January 2007 System Design 3-4.1 Single Vat Deep Fat Fryer With Drip Boards Table 3-2. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 18 in. x 18 in. (457 mm x 457 mm) Maximum Appliance Area (with drip board) 18 in. x 23 in. (457 mm x 584 mm) Nozzle Aim Midpoint of hazard area Nozzle Location (from top of appliance at an angle of 450 or more from the horizontal) 27 in. (686 mm) Mm. 45 in. (1143 mm) Max. AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 45 in. (1143 mm) AN F NOZZLE MAY BE MAX. DIAGONAL FROM LOCATED ANYWHERE AIM POINT WITHIN THE GRID 45 in. (1143 mm) ro NOZZLE LOCATION 45* OR MORE FROM HORIZONTAL M~IDPOINT OF ( MIN f AREA 18 in. (457 mm) / 23 in. AIM POINT: .- MAX. mm.i - MIDPOINT OF \ 584 MA HAZARD AREA -/---- HAZARD AREA / DRIP BOARD DRIP BOARD —ø-i 4 18 in. (457 mm) 18 in. (457 mm) MAX. MAX 23 in. (584 mm) MAX. APPLIANCE AREA FRONT VIEW SIDE VIEW Figure 3-2. Single Vat Deep Fat Fryer January 2007 3-6 P/N 9127100 System Design 3.4.2 18-1/2 in. x 24-1/2 in. Deep Fat Fryer With Drip Board Table 3-3. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 18-1/2 in. x 18 in. (470 mm x 457 mm) Maximum Appliance Area (with drip board) 18-1/2 in. x 24-1/2 in. (470 mm x 622 mm) Nozzle Aim Midpoint of module area per nozzle Nozzle Location (at an angle of 450 or more from the horizontal above each module) 27-1/2 in. (699 mm) Mm. 45 In. (1143 mm) Max. Module Area (half of hazard area) 18-1/2 in. x 9 in. (470 mm x 229 mm) AN F NOZZLE MAY BE LOCATED 45 iin,AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID '\ (1143 mm) (1143 mm) r ANYWHERE WITHIN THE GRID MAX. MAX. DIAGONAL FROM (11 45 in. MAX. POINT 27-11/2 Vin ARY LINE (699 rnmi DIVIDING MODULES MI DINT OF APPLIANCE MODULEAREA FRONT OF 18-1/2 in ± 9/n. Sin. (229 mm) (229 mm) 24-1/2 in. (622 mm) MAX. SIDE VIEW 2 F NOZZLES ARE REQUIRED FOR THIS APPLIANCE AN F NOZZLE MAY BE AN F NOZZLE MAY BE LOCATED ANYWHERE LOCATED ANYWHERE WITHIN THE GRID WITHIN THE GRID NOZZLE LOCATION / N 450R MORE FROM HORIZONTAL (TYP) AIM POINT: MIDPOINT OF HAZARD AREA HAZARD AREA DRIP BOARD 18-1/2 in. (470 mm) MAX. 24-1/2 in. (622 mm) MAX. APPLIANCE AREA SIDE VIEW Figure 3-3. 18-1/2 in. x 24-1/2 in. (470 mm x 622 mm) Deep Fat Fryer P/N 9127100 3-7 January 2007 AIM P01 NT: 27 in. \/- MIDPOINT OF (686 HAZARD AREA / / j/ 15 in. 21 in. MAX. (381 I DRIP BOARD 4 14 in. (356 mm) 10 MAX. FRONT VIEW AIM POINT: MIDPOINT OF HAZARD AREA DRIP BOARD HAZARD AREA 15 in. (381 mm) MAX. 4 21 in. (533 mm) MAX. APPLIANCE AREA SIDE VIEW System Design 3-4.3 Split Vat Deep Fat Fryer Table 3-4. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 14 in. x 15 in. (356 mm 381 mm) Maximum Appliance Area (with drip board) 14 in. x 21 in. (356 mm x 533 mm) Nozzle Aim Midpoint of module area per nozzle Nozzle Location (at an angle of 450 or more from the horizontal above each module) 27 in. (686 mm) Mm. 45 in. (1143 mm) Max. AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 45 i43mm( MAX. DIAGONAL FROM AIM POINT 45 in. (1143 mm) 45 in. (1143 mm) \/ \'MAX. MAX. NOZZLE LOCATION 45 OR MORE FROM HORIZONTAL AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID Figure 3-4. Split Vat Deep Fat Fryer January 2007 3-8 P/N 9127100 System Design 3-4.4 14 in. x 14 in. (356 mm x 356 mm) Deep Fat Fryer Table 3-5. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 14 in. x 14 in. (356 mm x 356 mm) Maximum Appliance Area (with drip board) 14 in. x 24-1/2 in. (356 mm x 622 mm) Nozzle Aim Midpoint of hazard area Nozzle Location (from top of appliance at an angle of 450 or more from the horizontal) 27-1/2 in. (686 mm) Mm. 45 in. (1143 mm) Max. AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 45 in. (1143 mm) MAX DIAGONAL FROM AIM POINT 45 in. 143 mm) MAX NOZZLE LOCATION OR MORE FROM HORIZONTAL 4 MIDPOINT OF 27.1/2 in. HAZARD AREA (699 mm) MIN _______ AIM POINT: MIDPOINT OF / - HAZARD AREA 14 in. (356 mm) MAX 24-1/2 in. HAZARD AREA \22mmMAX DRIP BOARD II / DRIP BOARD 14 in. (356 mm) MAX. 24-1/2 in. (622 mm) MAX. APPLIANCE AREA 4 14 in. (356 mm) MAX FRONT VIEW SIDE VIEW Figure 3-5. 14 in. x 14 in. (356 mm x 356 mm) Deep Fat Fryer P/N 9127100 3-9 January 2007 System Design 3-4.5 Single Vat Deep Fat Fryer (with Dripboards less than 1 in. [25 mm]) Table 3-6. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 24 in. x 24 in. (610 mm x 610 mm) Maximum Appliance Area (with drip board) 24 in. x 25 in. (6 10 mm x 635 mm) Nozzle Aim Midpoint of hazard area Nozzle Location (at any point on or within the perimeter of the hazard area) 27-1/2 in. (699 mm) Mm. 46 in. (1168 mm) Max. LOCATE THE NOZZLE ANYWHERE WITHIN THE PERIMETER OF THE HAZARD AREA. AIMED AT THE MIDPOINT OF THE HAZARD AREA. 46 in. (1 164 mm) MAX. /24i / -J 25 in. > / 67? MAX. MA DRIP BOARD 24 in. 4 (610 mm) MAX. -'-- TOP OF APPLIANCE AIM POINT: MIDPOINT OF HAZARD AREA 46n / I (1164 mm) MAX. 4 I / I :27-1/2 in. , (699 mm) 441, MIN. SAMPLE NOZZLE PLACEMENT,' ANYWHERE WITHIN THE SHADED AREA FRONT VIEW Figure 3-6. Single Vat Deep Fat Fryer (with Dripboards less than i in. (25mm) January 2007 3-10 P/N 9127100 System Design 3-4.6 Split Vat Fryer (Low Proximity Application) Table 3-7. ADP Nozzle Coverage Area Items Parameters Maximum Hazard Area 14 in. x 15 in. (356 mm x 381 mm) Appliance Area (with drip board) 14 in. x 21 in. (356 mm x 533 mm) Nozzle Aim Midpoint of hazard area Nozzle Location (at any point on or within the perimeter of the hazard area) 16 in. (406 mm) Mm. 27 in. (686 mm) Max. LOCATE THE NOZZLE ANYWHERE WITHIN THE PERIMETER OF THE HAZARD AREA. AIMED AT THE MIDPOINT OF THE HAZARD AREA. 27 in. -T (686 mm) MAX. / 15 in. / 21 in. (381 mm) / - ', 16 in. (533 mm) MAX. / (406 mm) MAX/ / DRIP BOARD 14 in. (356 mm) MAX. TOP OF APPLIANCE AIM POINT: MIDPOINT OF HAZARD AREA N ,/1 I / 27 in. (686 mm) MAX. I I I I / / I 16 in. I , / / (406 mm) / I - SAMPLE NOZZLE PLACEMENT, ANYWHERE WITHIN THE SHADED AREA FRONT VIEW Figure 3-7. Split Vat Fryer (Low Proximity Application) P/N 9127100 3-11 January 2007 System Design 3-4.7 Low Proximity Nozzle for Deep Fat Fryer Table 3-8. LPF Nozzle Coverage Area Items Parameters Maximum Hazard Area 14 in. x 15-1/2 in. (356 mm x 394 mm) longest vat side Maximum Appliance Area (with drip board) 14 in. x 23-1/4 in. (356 mm x 591 mm) Nozzle Aim Midpoint of appliance area (includes drip board) Nozzle Location (top of appliance) 12 in. (305 mm) Mm. - offset from center shall not exceed 3-1/2 in. (89 mm) See Table 3-9 for Nozzle Offset Information and 24 in. (610 mm) Max. - offset from center shall not Table 3-10 for minimum pipe length to prevent splash exceed 13-1/2 in. (343 mm) from the cylinder to a LPF Nozzle protecting a fryer. Table 3-9. Nozzle Offset At Given Heights Nozzle Tip Height Distance From Center 12 in. (305 mm) 3-1/2 in. (89 mm) 14 in. (356 mm) 5-13/64 in. (132 mm) 16 in. (406 mm) 6-13/16 in. (173 mm) 18 in. (457 mm) 8-1/2 in. (216 mm) 20 in. (508 mm) 10-13/64 in. (259 mm) 22 in. (559 mm) 11-13/16 in. (300 mm) 24 in. (6 10 mm) 13-1/2 in. (343 mm) Table 3-10: Pipe Limitations for LPF Nozzle Minimum Pipe From Cylinder Minimum Number of Minimum Total Pipe Required For Pipe Size Discharge Port to First LPF Flows in Complete All Remaining Nozzles Beyond the Nozzle Linear Pipe & Fittings System First LPF Nozzle Linear Pipe & Fittings 1/2 in. 7-1/2 ft. (2 m) and (1) Bull Tee 8 7 in. (178 mm) and One Full Tee (Run and Bull Connections) 3/4 in. and 1 in. 11 Equivalent Feet (3 m) of 8 5-13/64 Equivalent Feet (1.6 m) of 1/2 in. Pipe 1/2 in. Pipe 1 For pipe sizes larger than 1/2-inch, use the formulae below for the equivalent length as measured in 1/2-inch pipe. 1 foot (1 meter) of 3/4-inch (19 mm) pipe equals 0.254 equivalent feet of 1/2-inch (13 mm) pipe. 1 foot (1 meter) of 1-inch (25 mm) pipe equals 0.079 equivalent feet of 1/2-inch (13 mm) pipe. January 2007 3.12 P/N 9127100 AIM POINT: MIDPOINT OF APPLIANCE AREA (INCLUDES DRIP BOARD) HAZARD AREA 15-1/2 in. (394 mm) MAX. 23-1/4 in. (591 mm) MAX. 15-1/2 in. (394 mm) MAX / 4 14 in. (356 mm) MAX DRIP BOARD System Design AN LPF NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 24 in. (610 mm) MAX / 12 in. (305 AIM POINT: MIDPOINT OF (INCLUDES DRIP BOARD) APPLIANCE AREA 13-1/2 in. (343 mm) MAX. OFFSET FROM CENTERLINE AN LPF NOZZLE MAY BE LOCATED / ANYWHERE WITHIN THE GRID _ 24 in. (610 mm) 3-1/2 in. (89 mm) i 12 in. MAX. MAX. OFFSET 1(305 mm) FROM CENTERLINE MIN. 23-1/4 in. (591 mm) MAX. FRONT VIEW APPLIANCE AREA SIDE VIEW Figure 3-8. Low Proximity Nozzle for Deep Fat Fryer (LPF) P/N 9127100 3-13 January 2007 System Design 3-4.8 Krispy Kreme Model 270 d/h Doughnut Fryer Eight ADP nozzles (P/N B 1200 1 1), are dedicated to protect this appliance. Table 3-11. Eight ADP Nozzles Coverage Area Items Parameters Maximum Depth (front-to-back) 33 in. (840 mm) Maximum Length (left-to-right) 93 in. (2362 mm) Nozzle Location (lined up on both sides of the appliance, front and back outside perimeter of the cooking area 3-1/2 inches (89 mm) Mm. 6-1/2 in. (165 mm) Max. Nozzle Height (measured from the top of the appliance to the tip of the nozzle) 22-1/2 in. (572 mm) Mm. 29-1/2 in. (749 mm) Max. Maximum Module (aiming points is the centerline of the hazard area — center of each module of the unit) 33 in. (838 mm) x23-1/4 in. (591 nun) 3-1/2 in. (89 mm) MIN. ---. I I LOCATE NOZZLES 3.1/2 in. (89 mm) TO 33 in 6-1/2 in. (165 mm) OUTSIDE THE (838 mm) PERIMETER OF THE APPLIANCE, ALONG THE FRONT AND BACK EDGE, WITHIN HEIGHT PARAMETERS. IL 6-1/2 in. (16S mm) MAX. - _____ 93 in. T MAXIMUM NOZZLE HEIGHT (2362 mm) I 29-1/2 in. (749 mm) - 93 in. - (2362 mm) t f .................--I -. - 16.5 in. )419 mm) , I 33 in. - - .------------------CENTERLINE (838 mm) -- - •. ------..........- - . - .. ., FRONT-TO-BACK I '"S AIMING POINT TYPICAL DIMENSIONS I I"CENTERLINE ARE MAXIMUMS I I NOZZLE MODULE 23.25 in. ,. . 23.25 in. 23.25 in. .... 23.25 in. (591 mm) (591 mm) (591 mm) (591 mm) MINIMUM NOZZLE HEIGHT 22-1/2 in. (572 mm) - TOP OF APPLIANCE EACH NOZZLE IS AIMED AT MIDPOINT OF MODULE Figure 3-9. Krispy Kreme Model 270 d/h Doughnut Fryer System must use a complete six-gallon RG-600 cylinder for proper protection. Maximum piping limitations can be taken from the listed RG-600 cylinder size piping parameters (see Table 3-12). The minimum pipe length, to prevent splash, that is required between cylinder and closest cooking appliance nozzle is listed below. Table 3-12. Krispy Kreme Model 270 d/h Doughnut Fryer Minimum Pipe Length Piping Size Minimum Allowable Pipe 1/2 in. (13 mm) 39 Equivalent feet 1/2 in. (l3mm) 27 Linear feet January 2007 3-14 - P/N 9127100 System Design 3-4.9 Four Burner Ranges Table 3-13. R Nozzle Coverage Area - Four Burner Range Items Parameters Maximum Hazard Area 28 in. x 28 in. (711 mmx 711 mm) Nozzle Aim Midpoint of Hazard Area Nozzle Location - Anywhere within the area of a circle 20 in. (508 mm) Mm. generated by a 9 in. (229 mm) radius about the midpoint 42 in. (1067 mm) Max. Note: Shape of burner not important. 18 in. (457 mm) DIA. 42 in. (1067 mm) MAX. (FROM TOP OF RANGE) A R' NOZZLE MAYBE LOCATED ANYWHERE WITHIN THE SHADED AREA A 20 in. (508 mm) MIN. - - AIM POINT: MIDPOINT OF (FROM TOP OF HAZARD AREA RANGE) 28 in. (711 14 in. (356 mm) MAX. /BURNER MAX HAZARD CENTERLINE TO CENTERLINE _________ cg ARE2GTH® 14 in. (356 mm) MAX. BURNER CENTERLINE TO CENTERLINE 28 in. (711 mm) MAX. HAZARD AREA WIDTH Figure 3-10. R Nozzle Coverage for a 4-Burner Range P/N 9127100 3-15 January 2007 System Design 3-4.10 Two Burner Ranges Table 3-14. R Nozzle Coverage Area - Two Burner Range Items Parameters Maximum Hazard Length 28 in. (711 mm) Nozzle Aim Midpoint of hazard area Nozzle Location - Anywhere within the area of a circle 20 in. (508 mm) Mm. generated by a 9 in. (229 mm) radius about the midpoint 42 in. (1067 mm) Max. Note: Shape of burner not important. 18 in. (457 mm) DIA. - 42 in. (1067 mm) MAX. (FROM TOP OF RANGE) A 'R' NOZZLE MAY BE ' LOCATED ANYWHERE WITHIN THE SHADED AREA 20 in. (508 mm) MIN. AIM POINT: MIDPOINT OF (FROM TOP / HAZARD AREA OF RANGE) / Il 28 in. (711 mm) MAX. / 14 in. (356 mm) MAX. BURNER HAZARD AREA CENTERLINE TO CENTERLINE LENGTH N I PA Lv- W-.. A Figure 3-11. R Nozzle Coverage for a 2-Burner Range January 2007 3-16 P/N 9127100 System Design 3-4.11 Single Burner Range Table 3-15. R Nozzle Coverage Area - Single Burner Range Items Parameters Nozzle Aim 7 in. (178 mm ) from center of burner Nozzle Location - Anywhere within the area of a circle 20 in. (508 mm) Mm. generated by a 9 in. (229 mm) radius abput the aim 42 in. (1067 mm) Max. point. Note: Shape of burner not important. 18 in. (457 mm) DIA. 20 in. (508 mm) MIN. - (FROM TOP OF RANGE) 7 in. (178 mm) FROM BURNER CENTERLINE TO AIM POINT CENTERLINE Figure 3-12, R Nozzle Coverage for a 1-Burner Range P/N 9127100 3-17 January 2007 42 in. (1067 mm) MAX. (FROM TOP OF RANGE) A 'R' NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE SHADED AREA AIM POINT System Design 3-4.12 Four Burner Ranges (LPR), P/N B120024 The low proximity range top coverage provides protection for a range top that has a back shelf or a broiler integral to the regular range. Table 3-16. LPR Nozzle Coverage Area - Four Burner Range Items Parameters Maximum Hazard Area 24 in. x 24 in. (610 mm 610 mm) Nozzle Aim Midpoint of hazard area Nozzle Location - Dimension A in Figure 3-13 Refer to Table 3-17 Table 3-17. LPR Nozzle Parameters Burner Spacing Centerline to Centerline (Dimension B in Figure 3-13) Nozzle Height (Dimension A) (centrally over the range and under shelf/broiler) Note: Shape of burner not important. 14 in. (356 mm) 16 in. (406 mm) Mm. 20 in. (508 mm) Max. Between 12 in. and 14 in.(305 mm and 432 mm) 16 in. - 17 in. (406 mm —432 mm) Between 10 in. and 12 in. (254 mm and 305 mm) 16 in. (406 mm) DIMENSION "A" (NOZZLE HEIGHT MEASURED TO I TOP OF BURNERS AN LPR NOZZLE MAY BE LOCATED OVER THE CENTER OF THE HAZARD AREA. SEE TABLE FOR NOZZLE HEIGHTS. AIM POINT: MIDPOINT OF HAZARD AREA 24 int;D IMENSION MAXARE "B' DIMENSION "B" 24 in. (610 mm) MAX. HAZARD AREA WIDTH Figure 3-13. LPR Nozzle Coverage for a 4-Burner Range (LPR) January 2007 3-18 P/N 9127100 System Design The minimum pipe length to prevent splash from the cylinder to a LPR nozzle protecting an appliance is defined in Table 3-18. Table 3-18, Piping Parameters 1 Minimum length to LPR nozzle - linear: 9 ft. (2.7 m) 2 Minimum length to LPR nozzle - equivalent: 12 ft. (3.6 m) 3 Minimum total length in system - linear: 11.08 ft. (3.4 m) Note: If the LPR nozzle is disassembled for inspection or cleaning, reassemble the disc/core unit with the center core 'nub' facing upstream. The flat side should face towards the threaded nozzle cap. Refer to Figure 3-14. DISC/CORE LY ASSEMB 7N CAP OZZLE ___/__•_--_j I NOZZLE BODY J NUBI •;,.. FLAT SURFACE Figure 3-14. LPR Nozzle Assembly P/N 9127100 3-19 January 2007 System Design 3-4.13 Upright Broilers Table 3-19. ADP Nozzle Coverage Area Items Parameters Broiler Compartment With Maximum Internal Horizontal 30-1/4 in. x 34 in. (768 mm x 864 mm) Dimensions Nozzle Aim Through grill toward the center of the grease drain-off opening Nozzle Location Within the top 4 in. (102 mm) of space in the broiler compartment. Commonly mounted near the front opening and directed inside the broiler BROILER COMPARTMENT 4 in. (102 mm) - MAX. EXHAUST - DUCT SE '1-OFF (BROILER DOOR REMOVED) RIGHT SIDE NOTE: DIMENSIONS SHOWN ARE INSIDE BROILER COMPARTMENT ADP NOZZLES SHOULD BE MOUNTED ON THE PERIMETER OF THE BROILER TOP (SHADED AREA). IT SHOULD BE DIRECTED THROUGH THE GRILL TOWARD THE CENTER OF THE GREASE DRAIN-OFF OPENING NOZZLE DISCHARGE SHALL NOT BE OBSTRUCTED BY ANY STRUCTURAL PART OF THE BROILER. Figure 3-15. ADP Nozzle Placement for Upright Broilers January 2007 3-20 P/N 9127100 System Design 3-4.14 Charbroilers (Lava, Pumice, Ceramic or Synthetic Rock) Table 3-20. F Nozzle Coverage Area Items Parameters Maximum Appliance Area (maximum of two layers of lava, pumice, or stone) 22 in. x 23 in. (559 mm to 584 mm) Nozzle Aim Midpoint of the hazard area Nozzle Location (at an angle of 450 or more from the horizontal_above grate area) 24 in. (6 10 mm) Mm. 48 in. (1219 mm) Max. AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID DIAGONAL FROM AIM POINT AN F NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 48 in. (1219 mm) MAX. 48 in. (1219 mm) MAX. 24 in. (610 mm) MIN. / 23 in. (584 mm) MAX. / AIM POINT: MIDPOINT OF HAZARD AREA NOZZLE LOCATION \ _.- 45ORMOREFROM .\/ HORIZONTAL AIM POINT: lb MIDPOINT OF HAZARD AREA 23 in. (584 mm) MAX. APPLIANCE AREA 22 in. (559 mm) MAX. SIDE VIEW Figure 3-16. Lava, Pumice, Ceramic, or Synthetic Rock Charbroiler P/N 9127100 3-21 January 2007 System Design 3-4.15 Gas Radiant/Electric Charbroiler Table 3-21 GRW Nozzle Coverage Area Items Parameters Maximum Cooking Surface 21 in. x 24 in. (533 mm to 610 mm) Nozzle Aim Midpoint of the hazard area above cooking surface Nozzle Location (located at an angle of 45° or more from the horizontal) 24 in. (610 mm) Mm. 48 in. (1219 mm) Max. A GRW NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID DIAGONAL FROM AIM POINT ( A GRW NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID NOZZLE LOCATION " 45OR MORE FROM I I HORIZONTAL AIM POINT: MIDPOINT OF HAZARD AREA 48 in. (1219 mm) 48 in. (1219 mm) MAX. MAX. 24 in. (610 mm) MAX. 21 in. (533 mm)/ MAX. I AIM POINT: MIDPOINT OF HAZARD AREA . RADIANT Lb. 12dl GAS AME 21 in. (533 mm) MAX. 4 24 in. (610 mm) APPLIANCE AREA MAX. FRONT VIEW SIDE VIEW Figure 3-17. Gas Radiant/Electric Charbroiler January 2007 3-22 P/N 9127100 System Design 3-4.16 Natural or Mesquite Charcoal Charbroiler The depth of mesquite charcoal pieces or charcoal is limited to 6 in. (152 mm) maximum. Mesquite logs or wood are not acceptable. Table 3-22. ADP Nozzle Coverage Area Items Parameters Maximum Cooking Surface 24 in. x 24 in. (610 mm x 610 mm) Nozzle Aim Midpoint of the hazard area above cooking surface Nozzle Location (at an angle of 45° or more from the horizontal) 24 in. (6 10 mm) Mm. 48m. (1219 mm) Max. 48 in. (1219 mm) MAX. AN ADP NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 48 in. (1219 mm) DIAGONAL FROM AIM POINT 48 in. (1219 mm) —77 < MAX. AN ADP NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID 24 in. (610 mm) MAX. AIM POINT: MIDPOINT OF HAZARD AREA NOZZLE LOCATION 45 OR MORE FROM HORIZON 24 in. AIM POINT: (610 V MIDPOINT OF HAZARD AREA C 4 ' 6in. (152 mm) 24 In. r MAX. FUEL (610 mm) MAX. FRONT VIEW _6 in. (152 mm) A XA'i MAX. FUEL 4 p 24 in. (610 mm) MAX. APPLIANCE AREA SIDE VIEW Figure 3-18. Natural or Mesquite Charcoal Charbroiler P/N 9127100 3-23 January 2007 AQI.. 48 in. (1219 mm) MAX. 24 in. (610 & DM NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID DIAGONAL FROM AIM POINT 48 in. (1219 mm) MAX. A DM NOZZLE MAY BE LOCATED ANYWHERE WITHIN THE GRID AIM POINT: MIDPOINT OF HAZARD AREA System Design 3-4.17 Mesquite Logs Charbroiler Table 3-23. DM Nozzle Coverage Area Items Parameters Maximum Cooking Surface 30 in. x 24 in. (762 mm x 610 mm) Note: If the charbroiler has a blower, it shall be shut off when the Range Guard system operates. Nozzle Aim Midpoint of the hazard area above cooking surface Nozzle Location (located at an angle of 45° or more from the 24 in. (6 10 mm) Mm. horizontal) 48 In. (1219 mm) Max. Mesquite wood charbroiler may use wood chips, chunks, logs Depth of 10 in. (254 mm) Max. (or any combination thereof). The natural-charcoal/mesquite- charcoal charbroiler may use charcoal. 24 in. MZ FUEL 76 ) h (254mm) MAX. FRONT VIEW NOZZLE LOCATION \ ./ I N 45* OR MORE FROM .I HORIZONTAL\T\ AIM POINT: I \ I /•' MIDPOINT OF HAZARD AREA - 10 in. (254 mm) MAX. FUEL 24 in. (610 mm) MAX. APPLIANCE AREA SIDE VIEW Figure 3-19. Mesquite Logs Charbroiler January 2007 3-24 P/N 9127100 1/4 in. (6 mm) System Design 3-4.18 Chain Broiler (Closed-Top) Table 3-24. Single ADP Nozzle Coverage Area Items Parameters Maximum Internal Horizontal Dimensions 28 in. x 29 in. (711 mm x 737 mm) Nozzle Location (centered vertically in the chain broiler tunnel space above the chain) Positioned at one corner of the chain broiler tunnel aimed at opposite diagonal of the tunnel. Pipe drop and fittings 1/4 in. (6 mm) NOZZLE CENTERED VERTICALLY IN OPENING ABOVE CHAIN Figure 3-20. ADP Nozzle Installation for Closed Top Chain Broiler P/N 9127100 3-25 January 2007 System Design 3-4.19 Chain Broiler (Open-Top) Table 3-25. Dual ADP Nozzle Coverage Area Items Parameters Maximum Internal Broiler Tunnel Dimensions 28 in. x 29 in. (711 mm x 737 mm) Maximum External Top Dimensions 28 in. x 29 in. (711 mm x 737 mm) First Nozzle Location Located at one corner of the chain broiler tunnel and aimed toward the opposite diagonal corner of the tunnel - spaced 1-inch (25 mm) back from the tunnel opening. Second Nozzle Location (centered over the top opening of 12 in. (305 mm) Mm. chain broiler) from the top surface 48 in. (1219 mm) Max. Drop pipe and fittings to the chain broiler 1/4 in. (6 mm) 1/4 in PIPE DROI NOZZLE CENTERE VERTICALLY OPENING ABOI CHA SECOND NOZZLE LOCATION - CENTERED OVER TOP OPENING OF BROILER 12 in. (305 mm) MIN. 48 in. (1219 mm) MAX. 1/4 in. PIPE DROP FIRST NOt CENTE VERTICALL OPENING AB C 1/4 in. PIPE DROP ......SECOND NOZZLE: CENTERED OVER TOP OPENING OF BROILER 12 in. (305 mm) MIN. 48 in. 0219 mm) MAX. SECOND NOZZLE: ENTERED OVER rop OPENING OF 3ROILER 12 in. (305 mm) MIN. 18 in. (1219 mm) MAX. FRONT VIEW SIDE VIEW Figure 3-2 1. ADP Nozzle Installation for Open-Top Chain Broiler A CAUTION The second nozzle must be used when there is any exhaust opening on the top of the appliance. January 2007 3-26 PIN 9127100 System Design 3-4.20 Griddle - Flat Cooking Surface (With or without Raised Ribs) Table 3-26. ADP Nozzle Coverage Area Items Parameters Maximum Hazard Area 30 in. x 42 in. (762 mm x 1067 mm) Nozzle Aim At a point 3 in. (76 mm) from the midpoint of hazard area Nozzle Location - any point on the perimeter of 13 in. (330 mm) Mm. appliance 48 in. (1219 mm) Max. Note: Positioning the nozzle directly over the appliance is not permitted. 30 in (762 m MAX 48 in. (1219 mm) MAX. TOP OF APPLIANCE AIM POINT: 3 in. (76 mm) RADIUS FROM THE MIDPOINT OF HAZARD AREA 4 42 in. I (1067 mm) MAX. Figure 3-22. Griddle - Flat Cooking Surface P/N 9127100 3-27 January 2007 System Design 3-4.21 Wok Table 3-27. GRW Nozzle Coverage Area Items Parameters Wok Diameter 14 in. to 28 in. (356 mm to 1829 mm) Wok Depth 3 in. to 8 in. (76 mm to 508 mm) Nozzle Aim Center of Wok Nozzle Location - Must be over center and within 2 in. (51 mm) from center and nozzle height must be measured over center and within 2 in. (51 mm) from center from inside bottom of Wok. Only one nozzle per Wok. 35 in. (889 mm) Mm. 56 in. (1422 mm) Max. - 2 in. (51 mm) MAX. OFFSET ONE GRW NOZZLE MUST BE LOCATED ANYWHERE WITHIN THE SHADED AREA AIMED AT CENTER OF WOK 56 in. (1422 mm) MAX. 14 in. (356 mm) TO 28 in. (711mm) DIAMETER 35 in. (889 mm) MIN. 3 in. (76 mm) I TO 8 in. (203 mm) DEPTH CENTER OF HAZARD AREA AT BASE WOK INSIDE BOTTOM Figure 3-23. Wok January 2007 3-28 P/N 9127100 System Design 3-4.22 Tilt SkilletS (Braising Pans) Table 3-28. F Nozzle Coverage Area Items Parameters Maximum Hazard Area 24 in. x 24 in. (610 mm x 610 mm) Nozzle Aim Midpoint of hazard area and placed so it does not interfere with appliance operation Nozzle Location - At the front perimeter line of the 27-1/2 in. (699 mm) Mm. appliance 46 in. (1168 mm) Max. Note: Appliance cover cannot interfere with distribution of agent from the nozzle. , F NOZZLE / I - / COVER MUST NOT INTERFERE WITH / I EDGE OF EPAUERN / ,,___,' -. . . •1 1• DISCHARG / I - I -. CENTERLINE OF HAZARD ZONE THE NOZZLE IS TO BE PLACED TOWARD THE FRONT OF THE APPLIANCE TO MINIMIZE THE POTENTIAL FOR THE SKILLET OR BRAISING PAN COVER TO INTERFERE WITH THE NOZZLE DISCHARGE. Figure 3-24. Tilt Skillet (Braising Pan) P/N 9127100 3-29 January 2007 System Design 3-5 MODULE PROTECTION (MULTIPLE NOZZLES) For appliances that exceed single nozzle coverage, multiple nozzles can be used to protect that appliance by modularizing (dividing up into smaller sections) the larger appliances hazard area. Exception: for deep fat fryers the maximum protected area for a single vat is 6 ft.2 (1.9 m2) For a deep fat fryer that exceeds single nozzle coverage, multiple F nozzles can be used by dividing the hazard area into smaller modules that meet the limitation of a single nozzle. 3-5.1 Example - Module Protection of Fryers With Dripboards Less Than 1 in. (25 mm) Each module that the larger hazard area is divided into, must not exceed 24 in. x 24 in. (6 10 mm x 610 mm) and appliance area of 24 in. x 25 in. (6 10 mm x 635 mm) if a drip board is included. A single F nozzle is then used to protect each of these smaller modules. See Figure 3-25. The nozzle shall be located anywhere within the perimeter of the hazard area, and aimed at the midpoint of the hazard. LOCATE THE NOZZLES ANYWHERE WITHIN THE PERIMETER OF THE HAZARD AREA. AIMED AT THE MIDPOINT OF EACH MODULE HAZARD AREA., IMAGINARY LINE DIVIDING MODULES -T 46 in. (1168 mm) MAX. 24 (635 mm) MAX. /MODULE f44 A MODULE B DRIBOARD 14— 18 in. —+ I (457 mm) 36 in. 10 (914 mm) 27.1/2 in. (699 mm) MIN. AIM POINT: MIDPOINT OF MODULE HAZARD AREA TOP OF APPLIANCE Figure 3-25. Example of Modular Protection, Single Vat Deep Fat Fryer (Less than 1-inch Dripboard) January 2007 3-30 P/N 9127100 System Design NOZZLE A NOZZLE B NOZZLE CAN BE PLACED ANYWHERE WITHIN THE SHADED AREA DIRECTLY OVER THE MODULE THAT IS BEING PROTECTED BY THE NOZZLE. Figure 3-26. Nozzles for Deep Fat Fryer P/N 9127100 3-31 January 2007 DIAGONAL FROM IM POINT 45 in. (1143 mm) MAX. NOZZLE PLACEMENT SAME AS SINGLE VAT WITH DRIP BOARD COVERAGE 45 in. (1143 mm) MAX. - RY LINE DIVIDING MODULES 27 in. (686 mm) I 23 in. /I :E I 4_—_ 16 in. (406 mm) MAX LIQUID COOKING SURFP 864 in.' (55M cm?) DRIP BOARD 48 in. (1219 mm) System Design 3-5.2 Example - Single Vat Deep Fat Fryer - With Dripboards 1 in. (25 mm) to 6 in. (152 mm) Each module that the larger hazard is divided into, must not exceed 18 in. x 18 in. (457 mm x 457 mm) and an appliance area of 18 in. x 23 in. (457 mm x 584 mm) if a dripboard is included. Asingle F nozzle is then used to protect each of these smaller modules (see Figure 3-27). NOZZLE POSITION (TYPICAL FOR EACH MODULE) FOR MULTIPLE NOZZLE Figure 3-27. Example of Nozzle Position (Typical for each module) for Multiple Nozzle Coverage January 2007 3-32 P/N 9127100 System Design 3-6 VENTILATION 3-6.1 Plenums Table 3-29. Plenum Protection Items Parameters ADP Nozzle No Filter 1 loft. x4 ft. (3 mx 1.2 m) Max. 1 -located atone end of the plenum "V" Filter loft. x 4 ft. (3 m 1.2 ml 20 ft. x 4 ft. (6 m x 1.2 m) 1 - located at one end of the plenum 2 - located at end of plenum pointing inwards Single Bank Filter 10 ft. x 4 ft. (3 mx 1.2 m) 20 ft. x 4 ft. (6 m 1.2 m) 1 - located at one end of the plenum 2 - located at end of plenum pointing inwards 1 When no filters are present, the nozzle protecting the plenum is used to discharge the wet chemical on the under- side of the hood. In this case, the hood may not exceed a length of 10 ft. (3 m) or a width of 4 ft(l.2 m). Longer plenums may be similarly protected with a single ADP nozzle being used for each 10 ft. (3.0 m) of plenum length and each 4 ft. (1.2 m) of plenum width. ADP nozzles may be used in combinations (see Figure 3-28). Multiples may be installed facing in the same direction, and/or at the ends of the plenum pointing in. Each nozzle shall provide a maximum of 10 ft. (3 m) of coverage. ADP nozzles must be centrally located in the plenum with their discharge directed along the length of the plenum and located in relation to the filters as shown in Figure 3-28. Refer to Figure 3-28 for filter height. P/N 9127100 3-33 January 2007 DUCT 4 ft. (1.2 m) NOZZLE NOZZLE 20 ft. (6 m) SINGLE FILTER BANK COVERAGE 20 ft. (6 m) PLENUM System Design NOZZLE "V" FILTER BANK COVERAGE loft. (3m) PLENUM NOZZLE DUCT 4 ft. (1.2m) r 20 ft. 4ft. (1.2 m) m) "V" FILTER BANK COVERAGE 20 ft. (6 m) PLENUM NOZZLE 3/4 H "V" FILTER BANK COVERAGE (END VIEW) DUCT loft. (3 m) NOZZLE SINGLE FILTER BANK COVERAGE 10 ft. (3m) PLENUM -*11/3 wl*- 3/4Hj k-w -i SINGLE BANK FILTER COVERAGE (END VIEW) Figure 3-28. ADP Protection Nozzle, P/N B120011 January 2007 3-34 P/N 9127100 System Design 3-6.1.1 DUCTS The ADP nozzle, P/N B12001 1, is used for protection of the exhaust ductwork. The duct cross section can be any shape, not including obstructions (i.e., round, square, or rectangular) and the duct itself can be of unlimited length. In accordance with NFPA 96, the exhaust fan should be left running at the time of system discharge. This will help to remove smoke and other airborne materials and gases from the hazard area in the event of a fire. Check with the Authority Having Jurisdiction for local requirements. A damper, if present, should be left open at system discharge. However, if the damper is closed, the system designer must insure that additional nozzles are required. 3-6.1.1.1 Protection of Ducts 0 to 50 inches in Perimeter One ADP nozzle, P/N B 120011, is required for protection of a duct with a perimeter up to 50-inches (refer to Figure 3-29). Length of duct is unlimited. The nozzle is located at the geometric center of the cross-sectional area that it is protecting, and is located in the duct within six inches of the entrance. Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or off when the system is discharged. DUCT PERIMETER UP TO AND INCLUDING 50 in. (1270 mm) 11.78 in. (300 mm) 15.91 in. MAX. DIAGONAL (404 mm) 4 (318 mm) M 1— .4— MAX._ 11.78 in. (300 mm) 12.5 in. r I MAX. DIAGONAL AX. + RECTANGULAR DUCT SQUARE DUCT 2 "A" + 2 "B" = 65 in. (1651 mm) ROUND DUCT 1/ ADP NOZZLE (0 -152 mm) DUCT ENTRANCE Q OF VERTICAL DUCT VERTICAL/HORIZONTAL DUCT AIM POINT 4 ADP NOZZLE - I Q OF HORIZONTAL DUCT 2 to 4 in. (51 to 102 mm) NOZZLE TIP to DUCT HIP Figure 3-29. Duct Protection Using Single ADP Nozzle, P/N B120011 P/N 9127100 3-35 January 2007 System Design 3-6.1.1.2 Ducts 50 to 100 inches in Perimeter Two ADP nozzles, P/N B 120011, pointing in the same direction are required for protection of ducts with perimeters greater than 50 inches and less than or equal to 100 inches. Ducts can be of unlimited length (refer to Figure 3-30). For other option of ducts up to 75 perimeter inches (See Figure 3-32). Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or off when the system is discharged. I 4x X 1/4x V4x 1/4d %d MAX. DIAMETER 31.83 in. (809 mm) : 'NOZZLES TOBE ALONG ONE 25 in (635 mm) NOZZLES TO BE 0 -6 in. (0-152 mm) MAX: SIDE I CENTERLINE AT THE 114 POINTS. MAX. DIAGONAL UP FROM ENTRANCE OF VERTICAL DUCT AL 11.78 in. (300 mm) MAX. DIAGONAL TYP. (2) ADP NOZZLES 11.78 in. (300 mm) SQUARE RECTANGULAR ROUND F ADP NOZZLE to 6 in. to 152 mm) DUCTENTRANCE ! L. OF VERTICAL DUCT 2 -4 in. (51 mm -102 mm) NOZZLE TIP TO DUCT HIP OF HORIZONTAL DUCT IM POINT VERTICAL/HORIZONTAL DUCT Figure 3-30. Duct Protection Using Two ADP Nozzles, P/N B120011 January 2007 3-36 P/N 9127100 System Design 3-6.1.1.3 Designing For Large Ducts Large Ducts (Perimeters Greater than 100 Inches) For ducts larger than 100 in. (2540 mm) perimeter, the total perimeter of the duct must be divided by 50. If the answer contains a decimal (or fraction), it must be rounded-up to the nearest whole number. That will provide the number of nozzles necessary for proper protection of the duct. The diagonal dimension (nozzle to corner of duct) of each module must not exceed 11.78 inches (297 mm). If this diagonal dimension is exceeded, additional module divisions must be added until the diagonal dimension is not exceeded. A nozzle must then be centered in each module (refer to Figure 3-3 1). EXAMPLE You have a duct with a perimeter of 156 in. (3962 mm). Take the perimeter: 156 and divide it by the maximum allowable perimeter of a single nozzle: 50. 156/50 = 3.12 Round the 3.12 up to the next highest integer: 4. Four nozzles are required to protect this duct. A2 + B2 = C2 Where A is length, B is width and C is diagonal. Each "section" of the duct is 18L x 15W. 182 + 152 = c2 324 + 225 = 549 The square root of 549 is 23.43 inches (23.43= 549); therefore, the diagonal of each module is 23.43 inches. One-half of 23.43 is 11.71, which is the measurement from the nozzle to the corner of the duct. Our maximum allowable diagonal is 11.78 inches, as stated above. NOZZLE TO CORNER: 11.73 in. (298 mm) MAXIMUM ALLOWABLE is 11.78 in. (299 mm) 18 LARGE DUCT: 18 X 60 in. (457 mm x 1524 mm) TOTAL: 156 PERIMETER INCHES Figure 3-31. Modular Protection of Large Ducts P/N 9127100 3-37 January 2007 System Design Alternative Method: Ducts 0 to 75 Inches in Perimeter Two ADP nozzles can be used in ducts with a perimeter of 0 up to 75 inches (1651 to 1905 mm). The ratio of the longest to shortest perimeter sides shall not exceed 3 to 1. One of these nozzles is pointed into the duct and the other is pointed into the plenum. The tip of the upper nozzle, of the pair of nozzles required for each duct, shall be positioned in the center of the duct opening and above the plane of the hood-duct opening between 1 in. (25 mm) and 24 in. (610 mm). The duct length is unlimited. See Figure 3-32. Note: When a damper is present at the hood duct opening, the duct nozzles are to be located above the damper and should not interfere with the operation of the damper. Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or off when the system is discharged. Figure 3-32. Optional Duct Nozzle Placement January 2007 3-38 P/N 9127100 System Design 3-6.1.1.4 Upper/Lower Plenum Examples Protection of special or unique plenum arrangements should be reviewed by the AHJ (Authority Having Jurisdiction). Badger recommends that upper/lower plenum arrangements be protected as shown below. Note: All Range Guard systems are listed by UL and ULC for use with the exhaust fan either on or off when the system is discharged. 1. If risers are less than 6 in. (152 mm), nozzles are required to protect the upper and lower plenums and in the main exhaust duct. (See Figure 3-33 and Figure 3-34). Example 1 - Riser less than 6 in. (152 mm) in Length SER L Figure 3-33. Special Plenum Arrangements 2. If risers are 6 in. (152 mm) or longer, the risers become the exhaust ducts and there is no upper plenum. Nozzle(s) are required in the lower plenum and also in each such riser. The riser portion is to be treated now as the hood duct opening and protected accordingly. (See Figure 3-34). Example 2 - Riser more than 6 in. (152 mm) in Length ER L Figure 3-34. Special Plenum Arrangements With 6 in. (152 mm) Risers P/N 9127100 3-39 January 2007 CHEN HOOD System Design 3-6.1.2 SPECIAL CONFIGURATIONS 3-6.1.2.1 Protection of Electrostatic Precipitators Electrostatic precipitators (ESP) are designed to remove smoke and other airborne contaminants from the airstream flowing through exhaust ductwork. ESPs are used in restaurant kitchen exhaust systems as a means of pollution control. They are not intended to replace grease filters as the primary means of grease extraction. ESPs obstruct exhaust airflow and therefore require nozzle coverage in addition to a nozzle(s) protecting the ductwork. Exhaust ductwork using ESPs require ADP nozzle(s). The ADP nozzle(s) must be located centrally in the ductwork and should be aimed at the middle of the ESP. Distribution piping to the ADP nozzle located above the ESP and the ADP nozzle aimed at the precipitator must not interfere with the function of the ESP unit. See Figure 3-35. Q j CENTERLINE OF HAZARD ZONE Figure 3-35. Nozzle Placement with Electrostatic Precipitator January 2007 3-40 P/N 9127100 System Design 3-6.1.2.2 Transitional Duct The proposed protection for transitional duct applications should be approved by the AHJ (Authority Having Jurisdiction) prior to starting this system installation. Badger recommends that transitional ducts be protected as follows. Measure the dimensions at six inches into the transition piece. Determine the number of nozzles required by the perimeter measured at the six-inch location. Place the tip of the nozzle(s) at six inches into the transition piece. See Figure 3-36. M) Figure 3-36. Transitional Duct PIN 9127100 3-41 January 2007 System Design 3-7 CYLINDER FLOWS After finding how many nozzles of each type are required for a system, the sum of all the nozzle flow numbers is used to determine the number and size of the cylinders required, in accordance with the cylinder flow number limits given below. Table 3-30. Cylinder Flow Number Limits Maximum Flow Numbers of Cylinders Cylinder Flow Number RG-1.25G 4— Single Cylinder Only (cannot manifold) RG-2.50 8 - Single Cylinder Systems Only (cannot manifold) RG-4G5/RG4GM Can manifold up to 4 cylinders' 1 Cylinder 12 2 Cylinders 24 3 Cylinders 36 4 Cylinders 48 RG6GS Can manifold up to 2 cylinders' 1 Cylinder 18 2 Cylinders 36 'Only like cylinders can be manifolded (i.e., four RG-4G5 or 4GM; two RG6G) January 2007 3-42 P/N 9127100 System Design 3-8 PIPING REQUIREMENTS Range Guard systems do not require balanced piping to achieve proper distribution of wet chemical to all nozzles. Balanced piping is not necessary because a liquid has no difficulty in turning corners or changing directions. Range Guard nozzles come equipped with permanent predetermined orifices. This means that the liquid will be delivered in the exact quantities necessary to the duct, plenum and appliance hazards as required. All pipe shall be schedule 40 (standard weight) black steel. Pipe may be chrome plated. Galvanized pipe shall not be used. All pipe and fittings must be made tight without pipe dope or thread sealant. Pipe fittings shall be standard weight steel, cast iron, malleable iron or ductile iron. Galvanized fittings shall not be used. Branch line connection and individual nozzle connections may be made by using either the outlet or the run of a tee. 3-8.1 Stainless Steel Tubing and Fittings Stainless steel tubing may be used on all Range Guard systems. Fittings may be stainless steel compression or stainless steel flare types. Bending of tubing using mandrels is permissible. 3-8.2 Pipe Sizing Pipe sizes are determined by the total number of flow numbers running through a particular piece of pipe. This is the flow demand for that portion of the system. Note: It is not permissible to drop pipe diameters below the required value. For example, using 1/2- inch pipe to flow 18 flow numbers is not permissible. However, increasing pipe diameter is acceptable (i.e., using 1-inch pipe to flow 18 flow numbers) providing the system complies with internal pipe volume limitations. Table 3-31. Flow Number Range and Pipe Type Flow Number Range Minimum Pipe Size .035 Wall Stainless Steel Tubing Size 1 -2 1/4-inch 3/8-inch 1 -8 - /8-i N/A 1 -12 l/2inch 5/8-inch 13 -24 3/4-inch 7/8-inch 25 -48 1-inch 1-inch 3-8.3 General Rules A maximum of 100 equivalent ft. (30.5 m) but not more than 40 linear ft. (12.2 m) of 1/4-in, pipe may be used from each branch line. The highest point of the system shall not exceed 12 ft. (3.7 rn) above the cylinder outlet. The vertical rise of a branch line above the supply line shall not exceed a maximum of 4 ft. (1.2 m). Maximum discharge pipe volume limitations shall not be exceeded. Maximum equivalent length limitations shall not be exceeded. Maximum flow points for a given pipe shall not be exceeded. There are to be no low points or "traps" present in discharge piping. P/N 9127100 3-43 January 2007 System Design 3-8.4 Discharge Line Volume Limitations There is a discharge line volume limitation in Range Guard systems. Discharge line volume is the total volume of all pipe, tubing, and fittings used in single or multiple cylinder systems. To measure discharge line volume, it is necessary to measure all pipe length from the center of one fitting to the center of the next fitting and multiply by the volume-per-foot factor given in Table 3-32 and Table 3-33. Table 3-32. Piping Discharge Line Volume Size Piping Discharge Line Volume 1/4 in. 1.25 in.3 per linear foot - (67.2 cm3 per linear meter) 3/8 in. 2.29 in.3 per linear foot - (123.1 cm3 per linear meter) 1/2 In. 3.65 in.3 per linear foot- (196.2 cm3 per linear meter) 3/4 in. 6.40 in.3 per linear foot - (344.1 cm3 per linear meter) 1 in. 10.37 in.3 per linear foot - (557.5 cm3 per linear meter) Table 3-33. Tubing Discharge Line Volume Size Piping Discharge Line Volume 3/8 in. 0.88 in.3 per linear foot - (47.3 cm3 per linear meter) 5/8 in. 2.90 in.3 per linear foot- (155.9 cm3 per linear meter) 7/8 in. 6.11 in.3 per linear foot - (328.5 cm3 per linear meter) 1 in. 8.15 in.3 per linear foot - (438.2 cm3 per linear meter) Table 3-34. Maximum Allowable Piping Volume Cylinder Size Total Discharge Pipe Volume Max. per Cylinder Total Discharge Tubing Max. per Cylinder Max. Allowable 3/8-inch Pipe Volume per System RG425 (4.7 L) 72 in.3 (1180 cm3) 1 51 in.3 (836 cm3)' 72 in.3 (1180 cm3) RG250 (9.5 L) 139 in.3 (2278 cm3) 1 99 in.3 (1622 cm3)' 95 in.3 (1557 cm3) RG400 (15 L) 400 in.3 (6555 cm3) 282 in.3 (4621 cm3)' 95 in.3 (1557 cm3) RG600 (22.7 L) 400 in.3 (6555 cm3) 282 in.3 (4621 cm3)1 95 in.3 (1557 cm3) 1 Cannot Manifold Note: The maximum allowable 3/8-inch pipe volume is not in addition to the total discharge line volume, but represents a portion of the total volume which may be dedicated to 3/8-inch pipe alone. January 2007 3-44 PIN 9127100 I I I System Design 3-8.4.1 EQUIVALENT LENGTH LIMITATIONS Equivalent feet is defined as the actual measured length of discharge line plus the equivalent length for each fitting in the line as obtained from the data given in Table 3-35 and Table 3-36. Table 3-35. Pipe Fitting Equivalent Length Equivalent Length Pipe Fittings i 1/4 n. 3/8 in. 1/2 in. 3/4 in. 1 in. (6.3 mm) (9.5 mm) (13 mm) (19 mm) (25.4 mm) 900 Elbow 0.9 ft. 1.3 ft. 1.5 ft. 2.1 ft. 2.7 ft. (.27 m) (.40 m) (.46 m) (.64 m) (.82 m) 45° Elbow 0.4 ft. 0.6 ft. 0.8 ft. 1.0 ft. 1.3 ft. (.12m) (.18m) (.24m) (.30m) (.40m) Tee (Outlet) 2.0 ft. 2.7 ft. 3.5 ft. 4.5 ft. 5.8 ft. (.61 m) (.82 m) (1.07 m) (1.37 m) (1.77 m) Tee (Run) 0.5 ft. 0.8 ft. 1.1 ft. 1.4 ft. 1.7 ft. (.15 m) (.24 ml (.34 m) (.43 m) (.52 m) Red. (1/2 in. to 1/4 in.) 0.3 ft. - - - - (13 mm to 6.3 mm) (.09 m) Red. (1/2 in. to 3/8 in.) - 0.3 ft. - - - (13 mm to 9.5 mm) (.09 m) Red. (3/4 in. to 1/2 in.) - - 0.4 ft. - - (19 mm to 13 mm) (.12 m) Red. (1 in. to 3/4 11i.) - - - 0.5 ft. - (25.4 mm to 19 mm) (.15 m) Equivalent feet is measured from the cylinder (the farthest cylinder in a manifold) to the most remote nozzle. Equivalent feet is also measured between the two most remote nozzles. Equivalent feet is measured only along that branch with the most equivalent feet. Table 3-36 lists the maximum equivalent lengths for each cylinder size. Table 3-36. Tube Fitting Equivalent Length Equivalent Length Tube Fittings i 3/8 n. 5/8 in. 7/8 in. 1 in. (9.5 mm) (16 mm) (22 mm) (25.4 mm) 90° Elbow 1.5 ft. 2.5 ft. 4.0 ft. 4.5 ft. (.46 m) (.76 m) (1.22 m) (1.37 m) 90° Bend 0.5 ft. 1.0 ft. 1.0 ft. 1.0 ft. (.15 m) 00 m) 00 m) (.30 m) 45° Elbow 0.8 ft. 1.3 ft. 2.0 ft. 2.3 ft. (.24 m) (.40 m) (.61 m) (.70 m) 45° Bend 0.5 ft. 0.5 ft. 0.5 ft. 0.5 ft. (.15 m) (.15 m) (.15 m) (.15 ml Tee (Outlet) 1.5 ft. 2.5 ft. 4.0 ft. 4.5 ft. (.46 m) (.76 m) (1.2 m) (1.37 ml Tee (Run) 0.5 ft. 0.5 ft. 1.0 ft. 1.0 ft. (.15 ml (.15 m) 00 m) 00 m) P/N 9127100 3-45 January 2007 System Design 12 in. 4 (.3 m) I I Ii 900 ELBOW 1/2 in. (13 mm) PIPE 900 ELBOW Figure 3-37. 1/2 in. (13 mm) Piping with 900 Elbow Equivalent Feet (from Table 3-35) 90° 1/2 in. (13 mm) Elbow: 1.5 eq. ft. 90° 1/2 in. (13 mm) Elbow: 1.5 eq. ft. 1.0 ft. of 1/2 in. (13 mm) Pipe 4.0 eq. ft. TOTAL A tee can be considered one of two ways, depending on orientation. Figure 3-47 shows the different orientations that can occur. The equivalent feet for a reducing tee is determined by the larger size of the tee. Refer to Table 3-9 or 3-10 for equivalent feet. EXAMPLE TO THE MOST REMOTE NOZZLE TO THE MOST TO A NOZZLE THAT IS ON EITHER SIDE REMOTE NOZZLE NOT THE MOST REMOTE FR CYLINDE FROM -r- FROM CYLINDER OMf TO A NOZZLE THAT IS NOT THE MOST REMOTE CYLINJ DER TO THE MOST REMOTE NOZZLE TEE ON THE BULL (OUTLET) TEE ON THE RUN CONSIDERED A TEE ON THE BULL (OUTLET) Figure 3-38. Tees Table 3-37. Remote Nozzles Cylinder Size Equivalent Feet from Cylinder to Most Remote Nozzle Equivalent Feet Between Most Remote Nozzles RG-125 39 ft. (11.9m) 33 ft. (10.1 m) RG-260 63.4 ft. (14.3 m) 43.7 ft. (13.3 m) RG400 132 ft. (40.2 rn)2 95 ft. (29 rn)2 RG600 75 ft. (22.9 rn)2 80 ft. (24.4 rn)2 2 The maximums listed in Table 3-37 apply to manifold systems as well as single cylinder systems. January 2007 3-46 P/N 9127100 System Design 3-8.4.2 MINIMUM PIPE LENGTH The minimum pipe length, to prevent splash, required between cylinder and closest cooking appliance nozzle used to protect a liquid hazard, such as a deep fat fryer, is given in Table 3-38. For pipe sizes larger than 1/2-inch (1.3 cm) use formulas 1 and 2, to find the equivalent length in 1/2-inch (1.3 cm) pipe. Table 3-38. Minimum Allowable Pipe Pipe Size Minimum Allowable Pipe 1/4-inch and 3/8-inch 8-1/2 (2.6 ml linear feet plus (1) 900 elbow (2.6 m) 1/2-inch Two (2) 900 Elbows and 7 linear feet (2. lm) 3/4-inch and 1-inch 10 equivalent feet of 1/2-inch (13 mm) pipe (see formulas 1 & 2 and Figure 3-39) Formula 1: # equivalent feet (meters) of 1-inch (25 mm) pipe x (0.079) = # of equivalent feet (meters) of 1/2-inch (13 mm) pipe Formula 2: # equivalent feet (meters) of 3/4-inch (19 mm) pipe x (0.254) = # of equivalent feet (meters) of 1/2-inch (13 mm) pipe P/N 9127100 3-47 January 2007 System Design loft. _______ 4 (3m) 6in. (152 mm) 2 ft.) (19 mm) 3/4 in. (. 6m 1/2 in. 1 ft. 6 in. (13 mm) (.5 m) 3/4 in. (19 mm) RG-6G _______ 14- 4 ft. ., 4 10 ft. 4- 4ff. _ (1.2m) (3m) (1.2 m) (.9 m) ( .9 m) EQUIVALENT FEET CYLINDER TO CLOSEST NOZZLE Figure 3-39. Pipe Size and Nozzle Distance 3/4-inch Pipe (1)1/2-inch to 3/4-inch reducer; (1)(0.4) = 0.4 ft. of 3/4-inch Pipe (2) 900 3/4-inch elbow; (2)(2.1) = 4.2 ft. of 3/4-inch Pipe (1) 3/4-inch to 1/2-inch reducing Tee (run); (1)(1.4) = 1.4 ft. of 3/4-inch Pipe Linear Feet of 3/4-inch Pipe: iQ Equivalent Feet of 3/4-inch Pipe; 22 ft. of 3/4-inch Pipe (a) (22.0) x (0.254) = 5.5 eq ft. of 1/2-inch Pipe. (from Formula 2) 3/4-inch Pipe From (a) 5.5FT. of 1/2-inch Pipe (1) 1/2-inch Tee (Outlet); (1)(3.5) = 3.5 ft.. of 1/2-inch Pipe (1) 1/2-inch to 3/8-inch reducer; (1)(0.3) = 0.3 ft. of 1/2-inch Pipe Linear Feet of 1/2-inch Pipe: 5.5 Equivalent Feet of 3/4-inch Pipe; 14.8 ft. of 1/2-inch Pipe Therefore, this example does meet the minimum pipe requirement. January 2007 3-48 P/N 9127100 System Design 3-8.4.3 SPECIAL 3/8-INCH PIPING ONLY SYSTEM On RG-125, RG-260, and RG-400 single cylinder systems only, 3/8-inch discharge piping may be used for the entire piping network following the guidelines in Table 3-39. If a pneumatic release or pressure switch is used, it must be on the upper end of a 12 in, (305 mm) vertical length of black pipe. Table 3-39. 3/8 in. Piping Only System Limitations RG-1.25G RG-2.50G RG-4GS/RG-4GM2 Maximum Discharge Line Volume 72 in.3 99 in.3 161 in.3 (1180 cm 3) (1622 cm 3) (2638 cm 3) Maximum Equivalent Length of Discharge Line 39 ft. 40 ft. 59 ft. Between Cylinder and Most Remote Nozzle (11.9 m) (12.2 m) (18.0m) Maximum Equivalent Length of Discharge Line 33 ft. 42 ft. 50 ft. Between Most Remote Nozzles (10 ml (12.8 m) (15.2 m) Maximum Equivalent Length of 1/2-inch 12 ft. 12 ft. 24 ft. (13 mm) Discharge Pipe Between Cylinder and (3.7 m) (3.7 m) (7.3 m) Hood Minimum Equivalent Length of Discharge Line 8-1/2 ft. (2.6 m) linear 8-1/2 ft. (2.6 m) linear 8-1/2 ft. (2.6 ml linear Between Cylinder and an Appliance Nozzle feet plus 90 elbow feet plus 90° elbow feet plus 90° elbow Protecting a Liquid Hazard, such as Deep Fat Fryer 2 The limitations on this section (Paragraph 3-8.4.3) supersedes all other limitations when designing a system using 3/8-inch pipe originating from the 4-gallon cylinder outlet. P/N 9127100 3.49 January 2007 System Design 3-8.4.4 DETECTOR Detectors using Range Guard approved fusible link detectors are required over cooking appliances and in the ducts of kitchen cooking equipment per NFPA 17A and NFPA 96. For protection of the duct, a detector must be centered either flush with the hood-duct opening or in the duct but not more than 12 feet (3.7 m) downstream from where the duct is connected to the hood. When mounted in the duct, the detector should be oriented so that the bracket does not shield the link from the hot air stream, and the fusible link is centered in the duct. Maximum dimension per detector is 54 in. x 54 in. (1372 mm x 1372 mm). Appliances having a surface area larger than 54 in. x 54 in. (1372 mm x 1372 mm) require additional detectors. When a cooking appliance is under the hood-duct opening, the appliance is protected by the detector mounted at the hood-duct opening or 12 in. (305 mm) maximum into the duct. An additional detector is not needed to protect that appliance. A temperature survey must be performed at all locations where detectors will be installed. The survey must be conducted under maximum cooking or appliance cleaning conditions in order to determine the optimum exhaust air flow locations and to record the peak temperatures that are expected to occur. Once the survey is completed: Select the lowest temperature rated detector that can be used. Make sure the maximum exposure temperature of the link exceeds the maximum temperature obtained from the survey. Make sure links are located in the exhaust air flow, not in dead air spaces. This will provide the fastest detector response. Note: Care must be taken not to install links directly in the exhaust flow of appliance flue gas. 12 in. (305 mm) MAX. IF APPLIANCE IS UNDER HOOD DUCT OPENING Irnir —h --IX1-3/4in. 1i I X I I x I [Ti I X 1 3/41n- 314 in. (19 mm) DISCHARGE PIPING LIQUID SEAL ADAPTERS STOVE IIGRIDDLEH FRYER STOVE II FRYER j STOVE I ICHARBROILERI [ii2 E GRIDD [+301n.~I +__48in.___] I 56in. -*1 (610 mm) (610 mm) (610 mm) (610 mm) (457 mm) (762 mm) (1219 mm) (1422 mm) [- 34 in. +1 (864 mm) Figure 3-40. Positioning Detectors January 2007 3-50 P/N 9127100 System Design 3-9 UCH CONTROL SYSTEM DESIGN AND INSTALLATION PARAMETERS A System Valve Actuator (SVA) is used on every cylinder of the system. 1/4-inch tubing or hose is used to connect from the Control System to each SVA. It has inlet and outlet ports for low profile tubing runs. The following tables define the UCH Control System design and installation parameter limitations. Table 3-40 - Cable Limitations Table 3-41 - Actuation Length Limitations Table 3-40. UCH Control System Cable Limitations Cable Line Max. Cable Length Max. Corner Pulleys Max. Detectors Max. Tee Pulleys Detection and Manual Release-to-Trip Line 1 200 ft. (61 m) 50 40 - Detection and Manual Release-to-Trip Line 2 200 ft. (61 m) 50 40 - Pull-to-Trip Remote Manual Release 100 ft. (31 m) 30 - * Mechanical Gas Valve Release 100 ft. (31 m) T 30 - * Tee pulleys count as two Corner Pulleys. Maximum is from Control System, through the pulley, to each device Table 3-41. UCH Control System Actuation Length Limitations Mm. Operating Number of Max. Total Length of 1/4 in. Max. Number of Pressure Mm. Temp. Extinguishing System O.D. x 0.031 in. Wall High Switches (P/N 486536) in Tubing Cylinders Pressure Tubing Actuation Line 00 F (180 C) 1 -12 106 ft. (32 m) - See Note 6 2 5 ft. (2 m) 00 F (-18° C) 13-20 91 ft. (28 m) - See Note 6 2 5 ft. (2 m) The following are additional information and requirements regarding the actuation line tubing and flex hose. Flex hose (P/N B120045), is required to connect the UCH Control System to the System Valve Actuator when the UCH Control System is cylinder mounted. Copper tubing shall be 1/4-inch O.D. x 0.031-inch wall high pressure tubing. When Control System is cylinder mounted and two or more cylinders are being actuated, a minimum of 5 ft. (1.5 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used for actuation lines. When Control System is wall mounted, a minimum of 5 ft. (2 m) of 1/4-inch O.D. x 0.031-inch wall tubing shall be used in the overall actuation line. In every system, either single cylinder or multiple cylinder, a 1/8-inch NPT plug or vent check (P/N 8 778 10) shall be used in the outlet port of the last System Valve Actuator(s) in the actuation line. High pressure nitrogen tubing (P/N B120045-001 through B120045-003) may be used in place of copper tubing and not to exceed a maximum length of 30 feet (9 m). P/N 9127100 3-51 January 2007 System Design 3-10 A+DESIGN AND INSTALLATION PARAMETERS The following tables define the A+ design and installation parameter limitations. Table 3-42 - Detection Line Limitations Table 3-43 - Actuation Limitations Table 3-42. A+ Detection Line Limitations Item Limitations Detection Line 200 ft. (61 rn)1' 2 Detectors 40 Corner Pulleys 402 Table 3-43. A+ Actuation Limitations Item Limitations Copper Tubing3 I 1/4-inch O.D. x.031 wall thickness x 23 ft. (7 m) Tota13 3 feet (1 m) from A+ to 1st Cylinder (Mm.) SVAs S 1 Includes use of Remote Manual Control. 2 If using Gas Valve, maximum 50 ft. (15 m) cable and 16 Corner Pulleys. 3A combined maximum of 23 ft. total (7 m) of 1/4-inch O.D. x.031 wall thickness copper tubing may be used to con- nect the A+ Control Box to the SVA(s) on the cylinder(s). The 23 ft. (7 m) total is comprised of 3 ft. (1 m) of tubing from the A+ to the 1st cylinder and 20 ft. (6 m) from 1st to the last cylinder. January 2007 3-52 P/N 9127100 I t I + 1! - - GENERAL NOTES 1. The system will be installed in accordance with the current UL 300, NFPA l7A and 96 standard and manufactures requirements i 2. The system has manual actuation from a remote manual pull - 4 4 • I . station. The manual actuator is located in the path of egress less than 48" I4 --- ------------ above finished floor. All discharge nozzles are located instct compliance within -i the manufacturers minimum and maximum distance and covera e guidelines. IXQI7 r 5 All penetrations in the exhaust hood will have a liquid tight continuous external weld or utilize a UL listed seal adaptor. -- + 4-- -t - I I- - 6. Each exhaust duct within the protected hoods has at least one I . : I nozzle and one detector, located per manufacturers guidelines. 7 All fuel and power sources below the protected exhaust hood(s) -t - - - - will be interfaced to automatically shut down upon system activation. I S. The make-up air supply air fans, integral to the exhaust hood(s) - -•-- -• • 4 + . L 1 I . being protected, will be interfaced to automatically shut down upon system activation. Exhaust fan will remain on. I I 9. The system shall be interfaced with the building fire alarm system (if applicable) and annunciate theF.A.C.P. upon system AD 10. ::stall one (1) two and a half (2 V2) gallon Range Guard Fire Suppression System Maximum flow points 8 ADP NOZZLE 6 @lflowpoints 6 - Flowpointsused 8 R NOZZLE 2 @l flow points 2 Vic -- Total 8 ., i.. . .J . {.. SCOPE Upgrading fire protection for the kitchen hood, plenum, ducts, appliances by installing Range Guard wet chemi fire suppression system to meet UL300 standards to maximize hazard protection with automatic and manual _7 __ __ 1 OF cAR +1 1 1 11 II I lI1II II I II' I''I - 1 1 1! I 1 II! I Ij I FIREÔE PART I\AE1JT I I . --- -I...............I i rl I'll Zc F k S A sa I tests, notations cc ndit J _7 T t [ __ woo H L I U FtH I HH t 4 3 1 14 - - -----1 - f --H--- ---r- H- t Htt -Hj -H---Ui -T HrH±LtU H F --F far -- i--t---- . 1 ---- I 1 • ---H -- -- . ... --1 - - - . _._ - -- _. -. H -i L -- - I ----H -H H: •t-t +±± H-1 ti HfiHt-H-HH L {1 r1 HI I I I I I n I I I I I I I I ii I I i__Ij I -L T 4 . _ •__•ff __. .t -I- - -t -i - - - - -- I I1 If:+i3r I II I H I I - -+ -I --__ - -4 ----- -.-.-L----1 - L ------- ------ - - -- I-- r - - J1 I tII Ii 1 HIJJI7J71 rj I 1TII:J:: I 1TI IL IlL: - =L1 fLtc II t t 7:ITrTI1itI 1L/I ' 1i 11:: 1 , FT- I F-t, 1 I I Ly F i i t H li jtl TI l l fIril 'H Ij I I 1 I I 1 I I I I I I I I I Ii IJil 1 111 11 11 I Fire Suppression System Grid System Type: (1) Range Guard 2.5 Gallon Cylinder Qty Nozzle Model # Tip # Flow Pts Total Flow Pts 2 Duct 87-12016-01 ADP 1 2 1 Plenum 87-12016-01 ADP I I 2 Griddles 87-12016-01 ADP 1 2 2 Range 6 Burner 87-120019-04 R 1 2 I Salamander 87-120016-01 ADP 1 1 Total Flow Points Available 8 Total Flow Points Used 8 Badger/Range Guard Wet Chemical Fire Suppression System Component Index Part No. Description 9196903 360 Degree Globe Type Link 60-120002-001 ASSY-CYL/VLV 2.5 GAL Badger 60-9197263-000 Bracket-CYL 2.6 GAL RG 60-120064-001 Kit-Universal Link Bracket WK-844648-900 Pulley-Corner Badger 87-120016-001 ADP Nozzle 87-120019-001 R Nozzle 120018-001 GRW Nozzle 60-9196984-000 ASSY-VENT Plug 60-120099-001 ASSY-Control Unit Badger 60-120099-001 Remote Manual Release-Badger 83-844908-000 Adaptor Kit B 120074 1 '/z in. Mechanical Gas Valve 26499301 Quick Seal Adaptor 3/8 in. 26499302 Quick Seal Adaptor 1/z in. -26199303 26199301 Quick Seal Adaptor. I in.