HomeMy WebLinkAbout2875 LOKER AVE E; ; AS160175; Permit12/8/2020 AS160175 Permit Data
City of Carlsbad
Sprinkler Permit
Permit No: AS160175
2875 LOKER AV
Job Address: Status: ISSUED
EAST
Permit Type: SPRINK Applied 6/1/2016
Parcel No: 2090831000 Approved: 6/8/2016
Lot #: 0
Reference No.: Issued: 6/8/2016
PC #: Inspector:
Project Title: ZEST ANCHORS II T.I.
Applicant:
WESTERN FIRE PROTECTION
13630 DANIELSON ST
P0 WAY CA 92064
858-513-4949
Owner:
TECHBILT CONSTRUCTION CORP
P 0 BOX 80036
SAN DIEGO CA
L Fees ($) Add'l Fees ($) Total ($) Balance
325.5 0 325.5 0
1/1
_ -
- Western Fire Protection Inc.
Material Submittal
Zest Anchor Phase II
2875 Loker Avenue
San Diego, CA 92010
Job#TIC- 1441
AS160175
2875 LOKER AV EAST
13630 Danielson Street • Poway, CA 92064 • Phone: (858) 513-4949 • Fax: (858) 513-1322
GL& Eamn
UUM
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A U TOMA TI C SPRINKLERS
GL SERIES
UPRIGHT. PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response GL Series Sprinklers are a low profile
yet durable design which utilizes a 3mm frangible glass ampule as the ,----
thermosensitive element. This provides sprinkler operation approxi-
mately six times faster than ordinary sprinklers. While the Quick
Response Sprinkler provides an aesthetically pleasing appearance, it
can be installed wherever standard spray sprinklers are specified when
allowed by the applicable standards. It offers the additional feature of
greatly increased safety to life and is available in various styles,
orifices, temperature ratings and finishes to meet many varying design QUICK RESPONSE requirements. Quick Response Sprinklers should be used advisedly UPRIGHT CONVENTIONAL and under the direction of approving authorities having jurisdiction.
The heart of Globe's GL Series sprinkler proven actuating
assembly is a hermetically sealed frangible glass ampule that contains -
a precisely measured amount of fluid. When heat is absorbed, the
liquid within the bulb expands increasing the internal pressure. At the
prescribed temperature the internal pressure within the ampule ex-
ceeds the strength of the glass causing the glass to shatter. This results
in water discharge which is distributed in an approved pattern depend-
ing upon the deflector style used.
QUICK RESPONSE
TECHNICAL DATA PENDENT VERTICAL
See reverse side for Approvals and Specifications. SIDEWALL
*Temperature Ratings - 135°F (57°C), 155°F (68°C),
175°F (79°C), 200°F (93°C), 286°F (141°C)
Water Working Pressure Rating -175 psi (12 Bars)
*Factory tested hydrostatically to 500 psi (34 Bars)
*Maximum low temperature glass bulb rating is -67°F (-55°C)
*Frame - bronze • Deflector - brass • Screw - brass
*Bulb seat - copper • Spring - nickel alloy • Seal - teflon QUICK RESPONSE
Bulb - glass with alcohol based solution, 3mm size HORIZONTAL SIDEWALL
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE SPRINKLER N.F.P.A. MAXIMUM CLASSIFICATION BULB COLOR TEMPERATURES CEILING TEMPERATURE
ORDINARY 1350F/155°F 57°C/68°C ORANGE/RED 100°F 38°C
INTERMEDIATE 175°F/200°F 79°C/930C YELLOW/GREEN 150°F 66°C
HIGH 286°F 141°C BLUE 225°F 107°C
4077AIRPARK DRIVE, STANDISH, MICHIGAN 48658 989-846-4583 9 FAX 989-846-9231
MAY 2011 A-20 BULLETIN GL5615, REV. #7
989-846-4583
1-800-248-0278
GLAS
FIRE SPRINKLER CORPORATION
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
FAX 989-846-9231
www.globesprinkler.com
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT. PENDENT. VERTICAL SIDEWALL
HORIZONTAL SIDEWALL. CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH ' FINISHES
2.8 (39 metric) 1/2" NPT 2 1/4' (5.7 cm) Factory Bronze
4.2 (59 metric) 1/2" NPT 2 1/4" (5.7 cm) Bright Chrome
Satin Chrome 2
5.6 (80 metric) 1/2" NPT 2 1/4" (5.7 cm) White Polyester
7.8 (111 metric) 1/2" NPT 2 1/4" (5.7 cm) Black Polyester 2,3
8.1 (116 metric) 3/4" NPT 2 7/16" (6.2 cm) Lead Coated 2.3
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'HORIZONTAL SIDEWALL IS 2 9/16'.
2 FINISHES AVAILABLE ON SPECIAL ORDER.
3 AVAILABLE AS cULus LISTED CORROSION
APPROVALS RESISTANT WHEN SPECIFIED ON ORDER.
STYLE SIN K 135°F 155°F 175°F 200°F 286°F cULus F. M. LPC CE NYC - DOB MEl
MODEL FACTOR 57°C 68°C 79°C 93°C 141°C 101-92-E
GL2815 2.8 X X X X X X - - - X
GL4215 4.2 X X X X X X - X
UPRIGHT GL5615 5.6 X X X X X X X X X X
GL8115 7.8* X X X X X X -- - - X
GL8118 8.1 X X X X X X X X X X
GL2801 2.8 X X X X X X -- - - X
GL4201 4.2 X X X X X X -- - X
PENDENT GL5601 5.6 X X X X X X X X X X
GL8101 7.8° X X X X X X X - X
GL8106 8.1 X X X -X X X X X X X
VERTICAL GL5632 5.6 X X X X X X X - - -
SIDEWALLt GL8133 8.1 X X X X X X - - -
GL2826 2.8 X X X X X X - - X
HORIZONTAL GL4226 4.2 X X X X X X - - - X
SIDEWALL § GL5626 5.6 X X X X X X X - - X
GL8127 8.1 X X X X X X - -
CONVENTIONAL GL5624 5.6 X X X X X - - X X
(OLD STYLE) GL8125 8.1 X X X X X - - X X -
*1/2 NPT
t VERTICAL SIDEWALL SPRINKLER cULus LISTED FOR LIGHT HAZARD ONLY.
PENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
UPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
§ HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW
THE CEILING, FM APPROVED 4" TO 6'.
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufac-
tured products found to be defective in material or workmanship
for a period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
ORDERING INFORMATION
SPECIFY
Quantity • Model Number • Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Wrenches - P/N 325390 (1/2');
P/N 312366 (L.O.)
MAY 2011 PRINTED U.S.A. BULLETIN GL5615, REV. #7
F P P I
Description
Recessed Canopy Coverage Extensions provider increased coverage of the
recessed canopy flange against the ceiling or wall material where it is installed.
The primary purpose is to allow for increased distance between the finished
surface of the building interior and the recessed sprinkler assembly. AHJs within
certain earthquake zones require a minimum of 1" space between the sprinkler
or sprinkler drop and the material it penetrates. Can also be used to provide
coverage for oversized holes cut in finish material from previous sprinkler
placements. Fits most existing recess sprinkler canopies and is compatible with
all FPPI Recessed Canopys.
Installation
No tools are required for installation of the Recessed Canopy Coverage
Extension. Simply slide the recessed escutcheon skirt through the ID of the
coverage extension then install or re-install the recessed escutcheon skirt on to
the retainer. Press the recessed skirt firmly into place against the interior surface
the sprinkler penetrates without causing the interior surface to be moved or
lifted by the recessed skirt/coverage extension. Follow sprinkler manufacturers
instructions regarding the installation of sprinklers in recessed applications. May
be used either horizontally or vertically.
Specifications
Material:
.020" Cold Rolled Steel
Standard finishes:
Chrome
White
Coverage:
5" x 115/16" ID
Item Numbers:
01-491 5" Coverage Chrome
01-493 5" Coverage White
GL6 EAman
UUMN
FIRE SPRINKLER CORPORATION
DESCRIPTION AND OPERATION
,,,,THE INCH"
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
MODEL GL5606
ONE INCH ADJUSTABLE
CONCEALED PENDENT
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile,
aesthetically pleasing design. It provides sprinkler operation approximately six times faster than
ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are
specified when allowed by the applicable standards. It offers the additional feature of greatly
increased safety to life and should be used advisedly and under the direction of approving
authorities having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low
profile cover plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an
optional 2%" diameter ceiling plate colorfinished to match the specifier's exact requirements. The
GL Series Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow"
of the ceiling. Globe's Concealed Sprinkler utilizes its 3mm frangible glass ampule which is located
above the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper
wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be
installed. The "push on - screw off' designed cover plate is easily installed and with a nominal 1"
inch of adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate
to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes
the 3mm glass bulb to burstallowing the deflectorto drop down and distribute water in an approved
pattern to extinguish or control the fire.
TECHNICAL DATA
'See reverse side for Approvals and Specifications.
'Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
'Water Working Pressure Rating -175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
'Maximum low temperature glass bulb rating is -67°F (-55°C)
'Frame - bronze ' Deflector - brass ' Screw - brass
3 5/16" diameter plate
'Bulb seat - brass • Spring - nickel alloy 'Seal - teflon 2 3/4" diameter plate
'Bulb - glass with alcohol based solution, 3mm size QUICK RESPONSE
'Drop Pin - stainless steel WHITE ADJUSTABLE
'Cover Plate - brass CONCEALED PENDENT
'Upper Escutcheon Assembly - plated steel
NOTE: Globe's wrench P/N 332765 must be used to install this sprinkler.
'SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
AVAILABLE BULB N.F.P.A. MAXIMUM CEILING CLASSIFICATION SPRINKLER TEMPERATURES COLOR TEMPERATURE
ORDINARY 135°F/155°F 57°C/68°C ORANGE/RED 100°F 38°C
INTERMEDIATE 175°F/200°F 790C/930C YELLOW/GREEN 150°F 66°C
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658 (989) 846-4583 • FAX 989-846-9231
MAY 2012 A-38 BULLETIN GL5606 REV#6
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
MODEL GL5606 ONE INCH
ADJUSTABLE CONCEALED PENDENT
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH FINISHES
Bright Chrome
White Painted
5.6 (80 metric) 1/2'NPT 21/2(6.4cm) Bright Brass'
Satin Chrome'
Other Painted Finishes'
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'FINISHES AVAILABLE ON SPECIAL ORDER. FOR PAINTED PLATES OTHER
THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS.
APPROVALS
**1350F (57°C) 155°F (68°C) **1550F (68°C) 175°F (79°C) 200°F (93°C) NYC-DOB
STYLE SIN K with plate with plate with plate with plate with plate cULus *FM MEA MODEL FACTOR 135°F (57°C) 135°F (57°C) 155°F (68°C) 155°F (68°C) 155°F (68°C) 101-92-E
Adjustable
Concealed GL5606 5.6 X X X X X X X X
Pendent
*FM APPROVED AS STANDARD RESPONSE
**NO FM APPROVALS
CROSS SECTIONS
supP
CEIU
OPTIONAL COVER WHlTE135°F WHITEI55°F CHROMEI35°F CHROMEI55°F
PLATE SIZE PART # PART # PART # PART #
2 3/4" 332726 332731 332724 332729
35/16" 332706 332711 332704 332709
ORDERING INFORMATION
SPECIFY
Quantity • Model Number • Style
Orifice • Thread Sizes • Temperature
Finishes desired
Quantity - Adjustable Concealed Wrenches - P/N 332765
GL;BE
FIRE SPRINKLER CORPORATION
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for
a period of one year from date of shipment.
For specific details of our warranty, please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.globesprinkIer.com
MAY 2012 PRINTED U.S.A. BULLETIN GL5606 REV#6
GIkBE
FIRE SPRINKLER CORPORATION
COVER PLATE
WITH GASKET SEAL
FOR CLEAN ROOM
APPLICATIONS
COVER PLATES
The Seal is intended for areas where it is desirable to
stop air travel through the cover plate from the area
above the ceiling.
For "The Inch" Standard Response GI-5653, For Full
Description See Pages: A-69-CR
Finish/Part No. 135 0
Chrome: 332739
*White: 332737
Finish/Part No. 1550 ADJUSTABLE "CLEAN ROOM"
Chrome: 332740 COVER PLATE
White: 332741
cULus Approved: GL5653 -135°F (57°C) with plate 135°F (57°C);
155°F (68°C) with plate 135°F (570C); 155°F (68°C) with plate (680C);
175°F (79°C) with plate 155°F (680C); 200°F (93°C) with plate 155°F
(68°C)
MAY 2009 BULLETIN: CLEAN ROOM