Loading...
HomeMy WebLinkAbout6160 INNOVATION WAY; ; AS130152; Permit10/28/211 3:06 PM AS130152 Permit Data City of Carlsbad Sprinkler Permit 6160 INNOVATION Job Address: WY Permit Type: SPRINK Parcel No: 2132621423 Permit No: AS130152 Status: APPROVED Applied 8/23/2013 Approved: 9/6/2013 Lot #: 0 Reference No.: Issued: 9/6/2013 PC #: Inspector: Project Title: ACCY INC TI 23 HEAD TI FOR FLOOR I & 2 Applicant: Owner: VANGUARD FIRE PROTECTION ACCY INC 1604 LA MIRADA DR #105 12823 CALLE DE LA SIENA SAN MARCOS CA SAN DIEGO CA 760-727-8540 Fees ($) Add'I Fees ($) Total ($) Balance ($) 268 0 J 268 0 1/1 tqC0 /Fire & Building / )Products FILE COPY Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-FRB - 2.8,4.2,5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description The Tyco€ Series TY-FRB, 2.8, 4.2, 5.6, and 8.0 K-factor, Upright and Pen- dent Sprinklers described in this data sheet are quick response - standard coverage, decorative 3 mm glass bulb type spray sprinklers designed for use in light or ordinary hazard, commercial occupancies such as banks, hotels, shopping malls, etc. The recessed version of the Series TY-FRB Pendent Sprinkler, where ap- plicable, is intended for use in areas with a finished ceiling. It uses either a two-piece Style 10 (1/2 inch NPT) or Style 40 (3/4 inch NPT) Recessed Es- cutcheon with 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush pendent position, or a two-piece Style 20(1/2 inch NPT)or Style 30(3/4 inch NPT) Recessed Escutcheon with 1/4 inch (6,4 mm) of recessed adjust- ment or up to 1/2 inch (12,7 mm) of total adjustment from the flush pen- dent position. The adjustment pro- vided by the Recessed Escutcheon re- duces the accuracy to which the fixed pipe drops to the sprinklers must be cut. Corrosion resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be ob- IMPORTANT Always refer to Technical Data Sheet TFP700 for the "INSTALLER WARNING" that provides cautions with respect to handling and instal- lation of sprinkler systems and com- ponents. Improper handling and in- stallation can permanently damage a sprinkler system or its compo- nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. tamed when exposed to corrosive at- mospheres. Although corrosion resis- tant coated sprinklers have passed the standard corrosion tests of the appli- cable approval agencies, the testing is not representative of all possible cor- rosive atmospheres, Consequently, it is recommended that the end user be consulted with respect to the suitability of these coatings for any given corro- sive environment. The effects of ambi- ent temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed. An intermediate level versions of the Series TY-FRB Pendent Sprinklers are detailed in Technical Data Sheet TFP356, and Sprinkler Guards are de- tailed In Technical Data Sheet TFP780 WARNINGS The Series TY-FRB Sprinklers de- scribed herein must be installed and maintained in compliance with this document, as well as with the applica- ble standards of the National Fire Pro- tection Association, in addition to the standards of any other authorities hav- ing jurisdiction. Failure to do so may impair the performance of these de- vices. The owner is responsible for maintain- ing their fire protection system and de- vices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Model/Sprinkler Identification Numbers TYII3I - Upright 2.81K, 1/2"NPT TY1231 - Pendent 2.81K, 112"NPT TY2131 - Upright 4.2K, 112"NPT TY2231 - Pendent 4.2K, 112"NPT TY3131 -TY3231 - Upright 5.61K, 112"NPT Pendent 5.6K, 112"NPT 1Y4131 - Upright 8.01K, 314'NPT TY4231 - Pendent 8.0K, 3/4"NPT TY4831- Upright 8.01K, 1!2"NPT TY4931- Pendent 8.0K, 112"NPT