HomeMy WebLinkAbout2200 FARADAY AVE; ; FA130017; Permit11/3/21, 12:33 PM FA130017 Permit Data
City of Carlsbad
Fire Alarm Permit
Job Address: 2200 FARADAY AV
Permit Type: FALARM
Parcel No: 2121206000
Lot #: 0
Reference No.:
PC #:
Project Title: ROCKSTAR T. 1.
Permit No: FA130017
Status: ISSUED
Applied 3/19/2013
Approved: 3/19/2013
Issued: 3/19/2013
Inspector:
Applicant:
RIVER FIRE & SECURITY INC.
8920 ACTIVITY RD
STEJ
SAN DIEGO, CA
858-752-6250
Owner:
D L FARADAY L P
C/O DRA ADVISORS LLC
220 E 42ND ST 27TH FLOOR
NEW YORK NY
Fees ($) Add'I Fees ($) Total ($) Balance ($)
286 0 286 0
1/1
ROCKSTAR
SUITE 200
2200 FARADAY AVE. CARLSBAD, CA. 92008
Fire Alarm Submittal
03-17-13
FILE COPY
Submitted By;
0)11 N$VA
SECURITY
8779 Cottonwood Ave. Suite 103
Santee, CA. 92071
619-448-3007
Cont. Lic. C-10 # 802053
ROCKSTAR
Fire Alarm Submittal
Equipment List
Description Model
Fire Alarm Power Supply PSN-106
Strobe Multi-cd cig mnt STC
Strobe Multi-cd wall mnt ST
Horn/Strobe Multi-cd cig mnt HSC
Horn/Strobe Multi-cd wall mnt HS
Horn/Strobe WEATHERPROOF ASWP-1275
Manufacture CSFM#
POTTER SIGNAL 77135-0328:189
COOPER 7125-0785:168
COOPER 7125-0785:168
COOPER 7125-0785:168
COOPER 7125-0785:168
COOPER 7125-0785:131
(E)POTTER
The Symbol of Protection
PSN SLS
POWER SUPPLY'
UL, cUL, CSFM Listed
.,. • PSN-64 has 6 amps regulated with 4 Outputs
PSN 106 has 10 amps regulated with 6 Outputs
- • Outputs Rated at 3 amps maximum each
patent pdiiig
c®us (1
LISTED
S2930 7315-0328:0189
Product includes a 5 year warranty,
Dimenions: 16 1/8W x 16 3/4H x 3 1/2"D
May be configured as up to three class "A" Style "Z" notification circuits
3 amp, 24 VDC programmable output power
Supervised Battery Charger: 27.3 @. IA (supports 7-55 AH batteries):
Easy to install cabinet with leveling mounts and key lock
Wiring knockouts provided on sides and top of cabinet
Two Trouble Relays (5A at 30VDC)
General System Trouble (programmable for AC delay)
Low AC Trouble with optional delay settings
Diagnostic LED's
Status LED's for Active NAC and NAC trouble conditions
StatusLED's forEarth Fault(Amber).AC (Green), Battery
Fault (Amber)
Trouble Memory feature captures troubles which have previously restored
Synchronized notification appliance circuits
Potter/AMSECO®, Wheelock®. Gentex®. System Sensor®
Configurable output circuits (DIP switch sets options for each circuit)
15 mA at 8-33 VDC input trigger
Reference EOL allows 2K - 27K EOL value to be used
(iadra'nc provides panel wide synchronization of same or multiple brands
PassThru mode allows the Outputs to match the Input Signal
Electrical Specs:
Stock Number: 3006436 PSN-64 Red Enclosure • 120/240 VAC 50-60 Hz input
3006437 PSN-106 Red Enclosure • 5.1 Amps @ 120 VAC or 2.5 Amps @240 VAd'
3006446 PSN-106 Black Enclosure '• Standby Current 60 mA
Alarm Current 200 mA*j
external load
Description
The PSN series of notification power supplies offers reliable notification Sensor® strobe devices. Each output can be configured the same sync
power with unprecedented versatility. The power supplies offer either protocol or set independently.
6 or 10 amps of continuous power through 4 or 6 outputs respectively.
Each output is rated at 3 amps and it may be used continuously without
any derating.
The power supply operates on either 120 VAC 01220 VAC power input
and has a regulated 24 VDC output. In addition, the panel can charge
up to 55 AH batteries and leads the industry in housing up to 18 AH
batteries. The cabinet is constructed out of 18 gauge cold rolled steel and
has a durable red powder coat finish. In addition, a key lock is provided
for securing the door. Ample electrical knockouts are provided on the
sides and the top, allowing the installer options for running wires and
maintaining the correct separations.
The power supply offers an industry leading Quadrasync function that
allows for multiple strobe circuits of different brands to be synchronized
to flash at the same time. The panel can have four different brands each
connected to its own circuit and all of the strobes flash together.
Each output can independently be configured to provide one of
four synchronizations or steady power. This provides unequivocal
flexibility in new and retrofit installations. The panel can be configured
to synchronize Potter/AMSECO®, Gentex®, Wheelock® and System
Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support: 866-956-1211 • Canada 888-882-1833. www.pottersigna1.com
PRINTED IN USA MKT. #8910013-REV C2 PAGE 1 OF 2
11/12
In addition, the panel has an input PassThru mode allows the outputs
to follow the input signal and sync up the input flash. The panel will
recognize the type of input being supplied and pass this through to the
outputs with the same pattern. This input pass through can be selected
on each output independently.
The power supply contains simple dipswitch programming and LED
indications providing the installer indications of the operation and the
ability to correct any faults. A Trouble Memory is provided to allow an
installer to review past troubles and make the necessary repairs. Each
output has an LED to pin point the exact circuit where a problem may
have occurred. Relays are provided for monitoring the general system
and AC failure.
Each output and be independently configured for various applications
and installations. Each output can be independently configured for Class
A or Class B operation, constant power, ANSI Temporal Code 3, Single,
Multiple or Combo Inputs or Door Holder Power.
(DPOTTER The Symbol of Protection
1• -
BSN SL2S
POWER SUPPLY'
PSN-106 Wiring Diagram
? Rl 120/240 VAC GND FAULT CA [j Juniper Position DETECT ENABLE
ON OFF
120 VAC 50Hz-60Hz
240VAC S0Hz-6011z Black
Whi Connect to separate te
unswitched AC circuit Gronnd Ss LED's
TEl =nn
_
I I —
nlerorav AC L _..... U. RU — —
Low Battery M,
w—. E1 •••••• • I rnlI
I11 Z'sI U]
NC COM NO NC COMNO 'Battery +
Common relays are p —Battery - Optiorni &OL
non-power limited. Rd000
E.O.L
eo.L DC Power Trigger
Battery consecii1(non.power limited). Note: PSN-64 and PSN-106 draw 15 in when polarity reverses and the power
Use two (2) 12V batteries consoled in soles, supply is triggered. There is no current draw in Standby Mode.
Engineering Specification
The contractor shall supply and install the Potter PSN power supply. The
power supply shall operate on either 120 or 240 VAC input. The panel
shall be capable of continuous load power without any degradation to
the main supply or the distribution board. The cabinet shall be capable of
housing up to 18 AH batteries and the panel shall be capable of charging
up to 55 AH batteries in an external cabinet.
The panel shall have dip switches for simplistic configuration of the
system and LEDs to provide visual indication to the installer of the status
of the system. The dip switches shall allow for AC power delay selection,
Class A/B operation per output, Door Holder Power options, constant
auxiliary power, trigger input type, ANSI Code 3 Temporal Code, Pass
Thru (input tracking), Potter/AMSECOa sync, Gentexa Sync, System
Sensor' Sync or Wheelock® sync. The LEDs shall provide indication
of communication between the power supply and distribution circuit
assemblies. The LEDs shall have distinct flash patterns to provide further
indication ofthetroubles present. The panel shall have selectable Trouble
Memory to provide the installer an indication that a past trouble existed
on a circuit for diagnostic purposes.
Each output of the power supply shall be capable of 3 amps of continuous
power without degradation overtime. The power supply shall provide for
multiple circuits of strobe appliances. The power supply shall synchronize
the flashes of any of the above listed strobe appliances on a per circuit
basis. Up to four different strobe circuits may be connected and all of
the strobes shall flash in unison as required by UL 864. In addition to
this Quadrasync feature, the panel shall allow any of the four above
mentioned sync patterns as an input and pass this signal through and
synchronize the outputs to match the input flash pattern.
PRINTED IN USA MKT. #8910013 - REV C2 PAGE 2 OF 2
11/12
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION r.I
OFFICE OF THE STATE FIRE MARSHAL .
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM ...
LISTING SERVICE
LISTING No. ,7315-O328:618 Pae 1 of
CATEGORY p7315— POWER UNITS
LISTEE: Potter Elect dc Sign Coll Park 370 Place, Hazelwood, MO 6304
Contact: Biil1Witherspoon (314) 595-6900 Fax (314) 595-6999
Email: BiUWpottersignal.com
DESIGN: ModelsPSN-106,PSN-64, PSB-10 Notification Appliance Circuit (NAC) Power Supply Units.
Refer to listee's data sheet for additional detailed product description and operational
considerations.
RATING: Input 120/240 VAC 50/60Hz
Output 24VDC @ 1 OA
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. For fire alarm use, the unit
must provide battery backup suitable for at least 24 hours.
MARKING: Listee's name, model number, electrical rating and UL label.
APPROVAL: Listed as power supply units for use with separately listed compatible fire alarm control units
and notification appliances. Authority having jurisdiction should be consulted prior to
installation. The unit can be programmed to generate the three-pulse temporal fire alarm
evacuation signal (for total evacuation) in accordance with NFPA 72, 2002 edition.
01-27-2010 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2012 'Listing Expires) une 30 201
Authorized By: JASON DEWI1T, Deputy State Fire Marshal
Fire Engineering Division
(ç g 8 Candela Settings
Wall - 15/1575/30/75/95/110/135/185
Ceiling - 15/30160/75/95/115/150/177
Universal Mounting Base U Ceiling and Wall
Mounts to 5 Backbox Types
Environmentally Friendly
Low Current Draw
Multiple Voltages
3 Audible Settings
90, 95,99 dB
/Strobe, Horn Strobe, and Horn" E4 ~ ~dE, ~M
,"Notification Appliances,,,
-
I R E / t.,p ,-,c••
...- ' c
- -
.r
OW Ceiling Wall
Description:
The Wneelocka ExcederTM Series of notification appliances feature
a sleek modern design that will please building owners with reduced
total cost of ownership. Installers will benefit from its comprehensive
feature list, including the most candela options in one appliance,
low current draw, no tools needed for setting changes, voltage test
points, 12/24 VDC operation, universal mounting base and multiple
mounting options for both new and retrofit construction.
The Wheelocka ExcederTM Series incorporates high reliability and
high efficiency optics to minimize current draw allowing for a greater
number of appliances on the notification appliance circuit. All strobe
models feature an industry first of 8 candela settings on a single
appliance. Models with an audible feature 3 sound settings (90, 95,
99 dB). All switches to change settings, can be set without the use
of a tool and are located behind the appliance to prevent tampering.
Wall models feature voltage test points to take readings with a
voltage meter for troubleshooting and AHJ inspection.
The Wheelock5 Excederrm Series of wall and ceiling notification
appliances feature a Universal Mounting Base (UMB) designed
to simplify the installation and testing of horns, strobes, and
combination horn strobes. The separate universal mounting
base can be pre-wired to allow full testing of circuit wiring before
the appliance is installed and the surface is finished. It comes
complete with a Contact Cover for protection against dirt, dust, paint
and damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common wiring issues.
The Contact Cover is polarized to prevent it from being installed
incorrectly and prevents the appliance from being installed while
it is on the UMB. When the Contact Cover is removed the circuit
will show an open until the appliance is installed. The UMB allows
for consistent installation and easy replacement of appliances if
required. Wall models provide an optional locking screw for extra
secure installation, while the ceiling models provide a captivated
screw to prevent the screw from falling during installation.
Compatibility and Requirements
- Save up to 48% in current draw*
- Up to 9 models now in 1 appliance
- Save up to 14% cost of installation**
91
Sleek Modern Aesthetics
17. Finger Slide Switches
vo
Voltage Test Points
- Synchronize using the Wheelock Sync Modules or panels with built-in Wheelock Patented Sync Protocol
- Compatible with UL "Regulated Voltage" using filtered VDC or unfiltered VRMS input voltage
- Strobes produce 1 flash per second over the "Regulated Voltage" range
Compared to competitive models ** Patented
Compared to previous models
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bold capital letters.
A WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING
OR APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER NOTIFICATION FOR THE CURRENT INSTALLATION
INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND
SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
General Notes:
General Notes:
Strobes are designed to flash at I flash per second minimum over their Regulated Voltage Range.
All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range of 32'F to 120'F (lJC to 49CC) and
maximum humidity of 93% (± 2%) UL 464(85% UL 1971).
Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Horn Strobe Ratings'per UL 1971 & Anechoic at 24VDC
UL Max Currentl- at Anechoic 99 dBA
24VDC 12VDC
7 777
' 15/75 30) èo 75 95 110 115 135 150 177 185 15 15/75
--
HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159
HSC 80330 ö082' 0102 'b141 0.148 0.176
UL Max Current*
0.197 0242 b282
at Anechoic 95 dBA
0125
24VDC 12VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC
HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153
HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122
UL Max Current' at Anechoic 90 dBA
24VDC 12VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75 Range VDC
HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120
HornRatings per UL Anechoic
- -
Model Regulated Voltage
Range VDC 99 dB 95 dB 90 dB
HN 16-33.0 0.064 0.044 0.022
HNC 16-33.0 0.084 0.044 0.022
HN 8.0-17.5 0.047 0.026 0.017
HNC 8.0-17.5 0.047 1 0.026 0.017
* UL may current rating is the maximum RMS current within the listed voltage range (16-33 VDC for 24 VDC units). For strobes the
UL max current is usually at the minimum listed voltage (16 VDC for 24 VDC units). For audibles the max current is usually at the
maximum listed voltage (33 VDC for 24 VDC units). For unfiltered ratings, see installation instructions.
Specification & Ordering Information
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc., dba Cooper Notification standard terms and conditions.
Notification Wheelock (IwDCJ SAFEPATW WAV
Architects and Engineers Specifications
The notification appliances shall be Wheelock Exceder Series HS Audible Strobe appliances, Series ST Visual Strobe appliances
and Series HN Audible appliances or approved equals. The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency
Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard
464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with
standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP) with the ability to operate from 8 to 33 VDC.
Indoor wall models shall incorporate voltage test points for easy voltage inspection.
The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated
Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan® lens. The Series shall be of low current design.
Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110,
135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting
the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with
75 candela on-axis is required (e.g. ADA compliance). Appliances with candela settings shall show the candela selection in a visible
location at all times when installed.
The audible shall have a minimum of three (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal
(Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow
mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire
appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to
attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of
an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel (FACP). The mounting base shall be the same
base among all horn, strobe, horn strobe, wall and ceiling models. All notification appliances shall be backwards compatible.
The Series HS and ST wall models shall have a low profile measuring 5.24" H x 4.58" W x 2.19" D. Series HN wall shall measure 5.24"
H x 4.58" W x 1.6" D. The Series HSC and SIC shall been round and have a low profile with a diameter of 6.68" x 2.63" D. Series
HNC ceiling shall have a diameter of 6.68" x 1.50" D.
When synchronization is required, the appliance shall be compatible with Wheelock's DSM Sync Modules, Wheelock Power Supplies
or other manufacturer's panels with built-in Wheelock® Patented Sync Protocol. The strobes shall not drift out of synchronization at any
time during operation. If the sync protocol fails to operate, the strobe shall revert to a non-synchronized flash-rate and still maintain (1)
flash per second over its Regulated Voltage Range. The appliance shall also be designed so that the audible signal may be silenced
while maintaining strobe activation when used with Wheelock® synchronization protocol.
Wall Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Ceiling Appliances - UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM
Member
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
Exceder - Spec Sheet 6/11
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION .
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. ,7125-0785:0168 Page 1 of 1
CATEGORY: 7125-- FIRE ALARM DEVICES FOR THE HEARING IMPAIRE
LISTEE: 'Cooper Wheelock lnd.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Exceder Series: Models ST strobe, HS horn stroband HN horn. Model ST is a synchronous
and non-synchronous strobe light. Model HS a visual/audible appliance and Model HN is an
audible signal appliance. All units followed by R (red) or W (white). Additionally, a 'C' may be
added for ceiling models and/or a -NR' may be added for non-resettable models. For non
-NR models and optional 'S for silver fascia may be added * Refer to listee's data sheet for
additional detailed product description and operational considerations.
RATING: Electrical: 12 VDC/24VDC/FWR
Candela (wall)*: 15, 15/75, 30, 75, 95, 110, 135 & 185
Candela (ceiling)*: 15, 30, 60, 75, 95, 115, 150, & 177
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. All models are for indoor use
and for wall mount only or ceiling mount only*
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as horn for fire alarm signaling and strobe, horn/strobe for the hearing impaired when
used with separately listed electrically compatible fire alarm control units. Refer to listee's
Installation Instructions Manual for details.
*Rev. 9-24-09 fm
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2012 ',Listing Expire 2une 30,'201S
Authorized By: JASON DEWITT, Deputy State Fire Marshal
Fire Engineering Division
Weatherproof Appliances - Series AH Audibles,(AS Audible Strobes, MT Multitone Strobes,
RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories
L1'
T Ei
Description:
Designed for life safety, performance and reliability, Cooper
Notification's Wheelock cost effective weatherpoof notification
appliances include:
Weatherproof Appliances Series
Strobes RSSWP
Horn Strobes' 'ASWP
Horns AH-24WP, AH-1 2WP
Multitone Horn Strobes MTWP
Multitone Horns MT
Speaker Strobes ET70WP
Speakers ET-1010
All strobe models are UL dual listed - meeting both UL1638
and UL1971 requirements. As dual listed appliances, these
weatherproof strobes, horn strobes and speaker strobes are listed
for outdoor applications under UL 1638 as well as under UL 1971,
the Standard for Safety Signaling Devices for Hearing Impaired.
With an extended temperature range of —31°F to 150°F (-35°C
to 66°C), Wheelock weatherproof appliances meet or exceed UL
outdoor test requirements for rain, humidity and corrosion resistance
while providing multiple strobe intensity options, including the
highest strobe ratings available for area coverage per NFPA 72
strobe spacing tables (up to 185 candela for wall mounting and 177
candela for ceiling mounting).
To enable weatherproof mounting, Cooper Notification provides
the industry's widest choice of mounting options for surface or
unique semi-flush installation. Models are available for surface
mounting to Wheelock weatherproof backboxes on walls or ceilings.
The optional WP-KIT allows the weatherproof backboxes (lOB,
WPBB or WPSBB) to be mounted to a recessed electrical box
for concealed conduit installation. For semi-flush installation, the
WPA* and WFPA* kits allow a customer to mount the weatherproof
appliances to a recessed electrical box without the need for an
external weatherproof backbox. See the Backboxes, Plates and
Gaskets Table on page three of this document for a summarization
of these mounting options and the required accessories.
UOL MEA APPROVED
85946 151-92-E 1125-0785:131 (ASWP)
S5391 7125.0785:146 (ET70WP)
S2652 7125-0785:156 (MTWP)
7300-0785:154 (RSSWP)
All models may be synchronized using the Wheelock DSM Sync
Modules, Wheelock Power Supplies or other manufacturers
panels incorporating the Wheelock Patented Sync Protocol. The
horn output of horn strobes can be independently controlled on
2-wire circuits using the Wheelock patented sync protocol. MTWP
horn strobe models are 4-wire appliances; the strobes can be
synchronized while the audible can be connected to a coded fire
alarm system or can be set to produce any of eight selectable
tones.
Features:
Approvals include: UL Standards 1971, 1638, 464 and 1480
California State Fire Marshal (CSFM), New York City
(MEA), Factory Mutual (FM), Chicago (BFP) and ULC. See
agency approvals by model number on page two of this
document
Compliance with the following requirements: NFPA, UFC,
ANSI 117.1, OSHA Part 29,1910.165, ADA
Weatherproof with extended temperature range of —40°F to
150°F (-40°C to 66C)*
Dual Listed strobe models (UL 1638 and UL 1971)
Industry's highest strobe candela options
Synchronize using the Wheelock Sync Modules or panels
with built-in Wheelock Patented Sync Protocol
Models with field selectable tone, dBA and candela settings
Wall or ceiling mounting options
Surface of semi-flush mounting
IN/OUT wiring termination accepting two #12-18AWG wires
at each terminal
The series RSSWP. ASWP, AH-24WP, MTWP-2475W, and MT-12124 have UL/
ULC approval down to -40°F. The ET-1010 and ET70WP have UL approval down
to-40'F The AH-12WP has UL approval down to -31°F
NOTE: All CAUTIONS and WARNINGS are identified by the symbol A. All warnings are printed in bald capital letters.
A. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR
APPLYING THIS PRODUCT. VISIT WWW.COOPERNOTIFICATION.COM OR CONTACT COOPER WHEELOCI( FOR THE CURRENT INSTALLATION INSTRUCTIONS.
FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR
OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU
AND/OR OTHERS.
General Notes:
Strobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range.
All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table.
Wall Mount Ceiling Mount Wall or Ceiling Mount
F,R
tiflRE
_ J RSSWP MTWP j RSS P MTWP MT
-- \ AH
ASWP ET70WP ET-1010
Strobe Order Code Strobe Order Code
RSSWP-2475W-FR Red 9013 RSSWP-2475C-FR Red 4338 Audible Order Code RSSWP-2475W-FW White 3034 RSSWP-2475C-FW White 4446 AH-24WP-R Red 7416 RSSWP-24MCWH-FR Red 5161 RSSWP-24MCCH-FR Red 5167 AH-12WP-R Red 7415 RSSWP-24MCWH-FW White 5165 RSS WP-24MCCH-FW White 5187
Speaker Strobe
ET70WP-2475W-FR Red
ET70WP-2475W-FW White
ET70WP-24185W-FR Red
ET70WP-24185W-FW White
ET70WP-24 135W-FR Red
ET70WP-24135W-FW White
Audible Strobe
ASWP-2475W-FR
ASWP-24MCWH-FR
ASWP-24MCWH-FW
Multi-tone Strobe
MTWP-2475W-FR
MTWP-2475W-FW
MTWP-24MCWH-FR
MTWP-24MCWH-FW
Audible Strobe
Red 9012 'ASWP-2475C-FFf. Red 4251
Red 5137 ASWP-2475C-FW White 4502
White 5140 ASWP-24MCCH-FR Red 5149
ASWP-24MCCH-FW White 5157
Red
White
Red
White
8420 Multi-tone Strobe
3112 MTWP-2475C-FR Red
5132 MTWP-2475C-FW White
5134 MTWP-24MCCH-FR Red
MTWP-24MCCH-FW White
9077 Speaker Strobe
3179 ET70WP-2475C-FR Red
4885 ET70WP-2475C-FW White
4891 ET70WP-24177C-FR Red
4872 ET70WP-24177C-RN White
4875 ET70WP-24115C-FR Red
ET70WP-24115C-FW White
Horn
MT-1 2/24-R Red 5023
Speaker
ET-1010-R Red 3135
ET-1010-W White 3137
UL Max. Current AH
24 VDC 12 VDC
High (99) dBA 0.080 0.192
Med (95) dBA 0.043 0.108
Low (90) dBA 0.021 0.058
UL Reverberant dBA @ 10 Feet
Vans 1/8 1/4 1/2 1 2 4 8
ET-1010 77 80 83 86 87 92 94
ET70WP 78 81 84 187 190 93 195
4457
4478
5102
5122
4452
4454
4845
4859
4550
4732
Candela Ratings
Series UL 1971 UL 1638
@ 77°F
UL 1638
@ -40°F
RSS, ET70WP and
MTWP UL Max Current
(Strobe Only)
swP
High Med Low
2475 '30° 180 115 0.138 b.168 0.155 0.150
135 135 56 0.300 0.355 0.340 0.335 MCWH 185 185 77 0.420 0.480 0.465 0.460
115 115 47 0.300 0.355 0.340 0.335 MCCH
177 177 73 0.420 0.480 1 0.465 0.460
24185 185 185 77 0.420 **Wall mount rating only
24177 177 177 73 0.420
UL Max. Current
(Audible)
MTWP/MT
24 VDC
MT
12 VDC
IBA HI STD HI STD
Horn 0.108 0.044 0.177 0.034
Bell 0.053 0.024 0.095 0.020
March Time 0.104 0.038 0.142 0.034
Code 3 Horn 0.091 0.035 0.142 0.034
Code 3 Tone 0.075 0.035 0.105 0.021
Slow Whoop 0.098 0.037 0.142 0.035
Siren 0.104 0.036 0.152 0.030
Hi/Lo 0.057 0.025 0.114 0.026
Model Number Agency Approvals
Strobe UL MEA CSFM FM BFP
RSSWP-2475 X X X X -
RSSWP-24MCWH X - X - -
RSSWP-24MCCH X - X - -
Audible Strobe
ASWP-2475, X X X X X
ASWP-MCWH X - X - -
ASWP-MCCH X - X - -
Multitone Strobe
MTWP-2475 X X X X -
MTWP-MCWH X - X - -
MTWP-MCCH X . X - -
Horns/Audibles
AH-24WP X X X X X
AH-12WP X X X X X
MT-12/24 X X X X X
Speaker Strobe
ET70WP-2475 X - X X -
ET70WP-185 X - X X -
ET70WP-177 X - X X -
ET70WP-115 X - X X -
ET7OWP-135 X - X X -
Mounting Accessories
E3i
-
E1:'& t
WFP WFPA lOB WPSBB WPBB WBB
Mounting Options: Backboxes, Plates, Gasket Kits
Surface Mount Flush
Mount Exposed Conduit Concealed Conduit
RSSWP Strobes WPSBB WPSBB + WP-KIT WFP
ET70WP Speaker Strobes lOB lOB + WP-KIT WFP
Horn Strobes WPBB WPBB + WP-KIT WFPA
AHWP Horns WBB - WFP
ET-1010 Speakers WBB - WFP
MTWP Multitone Horn Strobes lOB lOB + WP-KIT WFP
Multitone Horn lOB lOB + WP-KIT I WFP
*IOB, WPSBB and WPBB models include weep holes and plug in the event that
moisture may have entered the appliance
Gasket Kit Order Code
WP-KIT 4486
Flush Plates
WFPA-R Red 4698
WFPA-W White 4101
WFP-R Red 4696
WFP-W White 4697
Backboxes
IOBR* Red 5046 lOBW* White 5047 WPSBBR* Red 9751
WPSBB-W White 3033
WPBBR* Red 9014 WPBBW* White 4692
WBB-R Red 2959
WBB-W White 2960
Wiring Diagrams
SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE
IN UNISON. RED AND BLACK SHUNT-WIRES ARE SUPPLIED.
FROM ____ ______ + TO NEXT
APPLIANCE -
W
OREOLR
PRECEDING +1 RED APPLIANCE
ORFACP
STROBE AUDIBLE
I SERIES RSSWP, ASWP, AHWP, MTWP AND MT-1 2/24 I APPLIANCES
I PRECEDING
I FROM
APPLIANCE - I APPLIANCE OR
- t-t•i +
+ TO NEXT
OR EOLR I FACP
SERIES MTWP APPLIANCES SYNCHRONIZED STROBE
OPERATION WITH CODED FACP
MW
5robe arit
Module
or AC#i 0
PS I 0
rcu
FACP aippiy
BLAC#2
Note: Strobe circuit requires constant voltage.
SERIES RSSWPIASWP APPLIANCES SYNCHRONIZED WI
DSM MODULE SINGLE CLASS "A" NAC CIRCUIT DSM
STROISE
NAC SYNC
OUT K
()MINNUSI
CIJT1
sr
0
FACP0
.E
''
NAC
aJlT
flJR
Note: Models are available in Red or White. Contact Customer Service for Order Code and Delivery.
#Refer to Data Sheet S7000 for Mounting Options
NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance
with Cooper Wheelock Inc. dba Cooper Notification standard terms and conditions.
ARCHITECTS AND ENGINEERS SPECIFICATIONS
General
Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard
1638 (Standard for Visual Signaling Appliances) for Indoor/Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices
for Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using
either exposed conduit or concealed conduit, or semi-flush mounting to a recessed electrical box in walls or ceilings using Wheelock
mounting accessories.
Weatherproof Strobes
Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range
of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings
up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77°F shall be available. The
strobes shall operate over an extended temperature range of —40°F to 150°F (-40°C to 66°C) and be listed for maximum humidity of
95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm
Control Panel (FACP).
Weatherproof Audibles and Audible/Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor/Outdoor
use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized.
The horns shall have at least 3 sound level settings. Horn/Strobe combinations shall be able to be synchronized on a single NAC.
Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone
Audible/Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized.
The audibles shall be able to be coded when operated on a separate NAC.
Weatherproof Speakers and Speaker/Strobes
Weatherproof speakers and speaker/strobes shall be listed for Indoor/Outdoor use under UL Standard 1480. All speakers shall provide
field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back
construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET-1 010. They shall be
listed to produce up to 94 dBA and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series
ET70WP. They shall be available for surface or semi-flush mounting to walls or ceilings and shall be listed to produce up to 93 dBA.
Synchronization Modules
When synchronization of strobes or temporal code-3 audibles is required, the appliances shall be compatible with the Wheelock Series
DSM Sync Modules, Wheelock Power Supplies or other manufacturers panels with built-in Wheelock Patented Sync Protocol. The
strobes and audibles shall not drift out of synchronization at any time during operation.
Series ASWP audibles and strobes shall be able to be synchronized on a 2-wire circuit with the ability to silence the audible if required.
The strobes on Series MT multitone audible/strobe appliances shall be able to be synchronized and shall be able to be operated on a
separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAG.
Weatherproof Mounting Accessories
Weatherproof mounting options shall include surface mounting or semi-flush mounting to walls or ceilings. Surface mounted appliances
shall mount to Wheelock lOB, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit.
For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock's WP-KIT to provide a
weatherproof seal for the electrical box. Semi-flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP
or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance.
111wo NOW DRUM
fl
WE ENCOURAGE AND SUPPORT NICET CERTIFICATION
3 YEAR WARRANTY
S9004 WP 06111
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
-
LISTING SERVICE
LISTING No. 17125-0785:0131) Page 1 of 2
CATEGORY: 7125 -- FIREALARM DEVICES FOR THE HEARING IMPAIRED
LISTEE: CooperWheelock'Inc.7246 16th St. E., Ste. 105, Sarasota, FL 34243
Contact: Tom Conover (941) 487-2336
Email: thomas.conover@cooperindustries.com
DESIGN: Models AS-1215, -2415, -1230,-2430, -121575, -241575, -2475 and -24110 audible/strobes
for the hearing impaired followed by any three alpha/numeric characters indicating lens
orientation, lettering and color.
Models AS-1215W, -2415W, -1230W, -2430W, -121575W, -241575W, -2475W and -24110W
audible/strobes for the hearing impaired followed by any three alpha/numeric characters
indicating lens orientation, lettering and color. These units with suffix -Ware for wall mount
only. *Models AS-121575W and AS-241575W lens color may be white, red, blue, green, or
amber.
Models AS-2415C, -2430C, -2475C and -24100C audible/strobes for the hearing impaired
followed by two alpha/numeric characters indicating lens lettering, orientation and color.
These units are intended for ceiling mount only.
Model AH-12, -24, AH-I2WP, -24WP audible appliances (no strobe), followed by an alpha or
numeric character indicating product color.
Model AS-24MCW and AS-24MCC audible/strobe, followed by any two alpha or numeric
character indicating lettering and product color. *Lens color may be white, red, blue, green,
or amber.
Models ASWP-2475V and ASWP-24C audible/strobe with integral private mode
fire/emergency visual signaling for non-hearing impaired applications. Lens color may be
white, red, blue, green, and amber. Both models are suitable for outdoor use when mounted
on the Model WPBB back box.
Models AS-24M CWH, AS-24MCCH, *Aswp24McwH and *ASWP24M CCH
audible/strobes for the hearing impaired followed by two alpha/numeric characters indicating
lens lettering and product color. Units with suffix CH are for ceiling mount only. Units with
suffix WH are for wall mount only. *Lens color may be white, red, blue, green, or amber.
Refer to the listees data sheet for detailed product description and operational
considerations.
Rev. 10-01-07
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2012 'Dsting Expires June 30, 2613'
Authorized By: JASON DEWflT, Deputy State Fire Marshal
Fire Engineering Division
Listing No. 7125-0785:0131
Page 2 of 2
RATING: Electrical: 8-17.5/16-33 VDC/VFWR
Flash Rate: 60 flashes/minute
Candela: 15:l5cd, 1575:15/75cd,30:30cd,75:75cd,95:95cd,100:100cd, 110:llOcd
MCW: Selectable 15cd, 30cd, 75cd,110cd
MCC: Selectable 15cd, 30cd,75cd,95cd
MCWH: Selectable 135cd,185cd (65cd, 90cd at -40 C)
MCCH: Selectable 115cd,177cd (50cd, 75cd at-40 C)
INSTALLATION: In accordance with listee's printed installation instructions applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction. Models ASWP-2475W,
ASWP-24MCWH, AS-24MCW and AS-24MCWH are for wall mount only. Models
ASWP-2475C, ASWP-24MCCH, AS-24MCCH, AND AS-24MCC are for ceiling mount only.
Models with suffix -w or WH are for wall mount only. Models with suffix -C or -CH are for
ceiling mount only.
MARKING: Listee's name, model number, electrical/candela rating, and UL label.
APPROVAL: Listed as audible and audibleMsual signaling devices suitable for the hearing impaired when
used in conjunction with separately listed electrically compatible fire alarm control units. For
indoor use only except Models AH-12WP, AH-24WP, *Aswp.2475w ASWP-2475C,
ASWP-24MCWH, and ASWP-24MCCH audible appliances are suitable for indoor/outdoor.
For synchronization, Models AS Series must be used with Model SM -12/24, SMX-12/24,
DSM-12/24 or DSMX-12/24 sync control module (CSFM Listing No. 7300-0785:132). Refer to
listee's Installation Instruction Manual for details.
These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.
NOTE: Models AH-12, AH-24, -12WP and -24WP audible devices are not suitable for the hearing
impaired applications.
*Rev. 10-01-07
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2012 Listing Expires une 30, 201 3
Authorized By: JASON DEWITT, Deputy State Fire Marshal
Fire Engineering Division