HomeMy WebLinkAbout2200 FARADAY AVE; ; AS090006; Permit11/3/21, 12:37 PM AS090006 Permit Data
City of Carlsbad
Sprinkler Permit
Job Address: 2200 FARADAY AV
Permit Type: SPRINK
Parcel No: 2121204100
Lot #: 0
Permit No: AS090006
Status: ISSUED
Applied 1/16/2009
Approved: 1/16/2009
Reference No.: Issued: 1/16/2009
PC #: Inspector:
Project Title: SIERRA WIRELESS FIRE SPRINKLER PLAN CHECK &
INSPECTIONS
Applicant:
PARAMOUNT FIRE SYSTEMS, INC
P.O. BOX 713194
SANTEE, CA
619-562-6247
Owner:
D L FARADAY L P
C/a DRA ADVISORS LLC
220 E 42ND ST #27
NEW YORK NY
Fees ($) Add'I Fees ($) Total ($) Balance
130 0 130 0
1/1
ASOI000(a
PARAMOUNT FIRE SYSTEMS, INC.
P.O. BOX 713194
SANTEE, CA 92072
C16-788204
HYDRAULIC CALCULATIONS
FOR
SIERRA WIRELESS
2200 FARADAY
CARLSBAD, CALIFORNIA
1ST FLOOR
DATE: JAN 18, 2009
REMOTE AREA "A" 1ST FLOOR
CONVERSION TO LIGHT HAZARD SPACE
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: Light Hazard
DENSITY: .10 gpm per sq. ft.
AREA OF APPLICATION: 1851 sq. ft.
COVERAGE PER SPRINKLER: Varies
NUMBER OF SPRINKLERS CALCULATED: 5 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 204.2 gpm
TOTAL WATER REQUIRED (including hose): 304.2 gpm
FLOW & PRESSURE (at base of riser) 204.2 gpm @ 46.8 psi
(at node BOR)
SPRINKLER ORIFICE SIZE: 17/32" K= 8.00
NAME OF CONTRACTOR: PARAMOUNT FIRE SYSTEMS, INC.
DESIGN/LAYOUT BY: TT
AUTHORITY HAVING JURISDICTION: CARLSBAD FIRE MARSHAL
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 1/18/2009 C:\HASS77\FILES\PARAMOUNT\SIERRA WIRELESS\SIERRA.SDF
JOB TITLE: SIERRA WIRELESS REMOTE AREA A .10/1851 EXT COV HEADS
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ!D
NODE PRESS. PRESS. 8 PRESS. 8 DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
FLOWTEST 110.0 100.0 1546.0 109.5 304.2 48.8
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 304.2 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 204.2 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
A 16.5 - - - - 39.6 - - -
B 16.5 - - - - 39.4 - - -
1 16.5 - - - - 39.6 - - -
2 12.0 K= 6.50 37.9 40.0
3 12.0 K= 6.54 37.8 40.2
4 12.0 K= 6.50 38.0 40.1
5 16.5 - - - - 39.4 - - -
6 16.5 - - - - 39.6 - - -
7 12.0 K= 6.71 39.6 42.2
8 12.0 K= 6.63 39.6 41.7
9 16.5 - - - - 39.4 - - -
10 16.5 - - - - 39.6 - - -
11 16.5 - - - - 39.4 - - -
12 16.5 - - - - 39.6 - - -
13 16.5 - - - - 39.4 - - -
14 16.5 - - - - 39.6
FLOWTEST -4.0 SOURCE 48.8 204.2
16 16.5 - - - - 39.6 - - -
17 16.5 - - - - 39.5 - - -
18 16.5 - - - - 39.6 - - -
19 16.5 - - - - 39.5 - - -
20 16.5 - - - - 39.6 - - -
21 16.5 - - - - 39.5 - - -
TOR 16.5 - - - - 39.8 - - -
BOR 0.5 - - - - 46.8 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 1/18/2009 C:\HASS77\FILES\PARAMOUNT\SIERRA WIRELESS\SIERRA.SDF
JOB TITLE: SIERRA WIRELESS REMOTE AREA A .10/1851 EXT COV HEADS
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT), SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 8.2 2.067 PL 192.46 PP 0.2
A 16.5 0.0 39.6 0.0 0.8 120 FTG 4T PE 0.0
B 16.5 0.0 39.4 0.0 0.001 TL 232.46 PV
Pipe: 2 8.2 6.065 PL 10.00 PP 0.0
1 16.5 0.0 39.6 0.0 0.1 120 FTG ---- FE 0.0
A 16.5 0.0 39.6 0.0 0.000 TL 10.00 PV
Pipe: 3 -8.2 4.026 PL 10.00 PP 0.0
5 16.5 0.0 39.4 0.0 0.2 120 FTG ---- PE 0.0
B 16.5 0.0 39.4 0.0 0.000 TL 10.00 PV
Pipe: 4 53.3 2.067 PL 105.46 PP 3.7
1 16.5 0.0 39.6 0.0 5.1 120 FTG 2T PE 1.9
2 12.0 6.5 37.9 40.0 0.029 TL 125.46 PV
Pipe: 5 13.3 2.067 PL 14.00 PP 0.0
2 12.0 6.5 37.9 40.0 1.3 120 FTG ---- PE 0.0
3 12.0 6.5 37.8 40.2 0.002 TL 14.00 PV
Pipe: 6 -26.9 2.067 PL 18.00 PP 0.1
3 12.0 6.5 37.8 40.2 2.6 120 FTG ---- FE 0.0
4 12.0 6.5 38.0 40.1 0.008 TL 18.00 PV
Pipe: 7 -66.9 2.067 PL 54.96 PP 3.4
4 12.0 6.5 38.0 40.1 6.4 120 FTG 2T FE -1.9
5 16.5 0.0 39.4 0.0 0.045 TL 74.96 PV
Pipe: 8 61.6 6.065 PL 10.00 PP 0.0
6 16.5 0.0 39.6 0.0 0.7 120 FTG ---- PE 0.0
1 16.5 0.0 39.6 0.0 0.000 TL 10.00 PV
Pipe: 9 8.0 2.067 PL 192.46 PP 0.2
6 16.5 0.0 39.6 0.0 0.8 120 FTG 4T PE 0.0
9 16.5 0.0 39.4 0.0 0.001 TL 232.46 PV
Pipe: 10 58.7 4.026 PL 10.00 PF 0.0
9 16.5 0.0 39.4 0.0 1.5 120 FTG ---- PE 0.0
5 16.5 0.0 39.4 0.0 0.001 TL 10.00 PV
Pipe: 11 69.6 6.065 PL 10.00 PF 0.0
10 16.5 0.0 39.6 0.0 0.8 120 FTG ---- PE 0.0
6 16.5 0.0 39.6 0.0 0.000 TL 10.00 PV -
Pipe: 12 7.8 2.067 FL 192.46 PP 0.2
10 16.5 0.0 39.6 0.0 0.7 120 FTG 4T PE 0.0
11 16.5 0.0 39.4 0.0 0.001 TL 232.46 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 1/18/2009 C:\HASS77\FILES\PARAMOUNT\SIERRA WIRELESS\SIERRA.SDF
JOB TITLE: SIERRA WIRELESS REMOTE AREA A .10/1851 EXT COV HEADS
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 13 50.7 4.026 PL 10.00 PF 0.0
11 16.5 0.0 39.4 0.0 1.3 120 FTG ---- PE 0.0
9 16.5 0.0 39.4 0.0 0.001 TL 10.00 PV
Pipe: 14 77.4 6.065 PL 12.00 PH 0.0
12 16.5 0.0 39.6 0.0 0.9 120 FTG ---- PE 0.0
10 16.5 0.0 39.6 0.0 0.000 TL 12.00 PV
Pipe: 15 36.0 2.067 PL 120.96 PH 2.0
12 16.5 0.0 39.6 0.0 3.4 120 FTG 2T PE 1.9
7 12.0 6.7 39.6 42.2 0.014 TL 140.96 PV
Pipe: 16 -6.2 2.067 PL 18.00 PH 0.0
7 12.0 6.7 39.6 42.2 0.6 120 FTG ---- PE 0.0
8 12.0 6.6 39.6 41.7 0.001 TL 18.00 PV
Pipe: 17 -47.9 2.067 PL 54.96 PH 1.8
8 12.0 6.6 39.6 41.7 4.6 120 FTC 2T PE -1.9
13 16.5 0.0 39.4 0.0 0.024 TL 74.96 PV
Pipe: 18 42.9 4.026 PL 12.00 PF 0.0
13 16.5 0.0 39.4 0.0 1.1 120 FTG ---- PH 0.0
11 16.5 0.0 39.4 0.0 0.001 TL 12.00 PV
Pipe: 19 113.5 6.065 PL 9.71 PH 0.0
14 16.5 0.0 39.6 0.0 1.3 120 FTG T PE 0.0
12 16.5 0.0 39.6 0.0 0.001 TL 39.71 PV
Pipe: 20 -90.7 6.065 PL 2.29 PH 0.0
16 16.5 0.0 39.6 0.0 1.0 120 FTG T PE 0.0
14 16.5 0.0 39.6 0.0 0.000 TL 32.29 PV
Pipe: 21 7.2 2.067 PL 192.46 PH 0.2
16 16.5 0.0 39.6 0.0 0.7 120 FTC 4T PE 0.0
17 16.5 0.0 39.5 0.0 0.001 TL 232.46 PV
Pipe: 22 90.7 4.026 PL 12.00 PF 0.0
17 16.5 0.0 39.5 0.0 2.3 120 FTG ---- PE 0.0
13 16.5 0.0 39.4 0.0 0.003 TL 12.00 PV
Pipe: 23 -83.6 6.065 PL 12.00 PF 0.0
18 16.5 0.0 39.6 0.0 0.9 120 FTG ---- PE 0.0
16 16.5 0.0 39.6 0.0 0.000 TL 12.00 PV
Pipe: 24 6.3 2.067 PL 192.46 PH 0.1
18 16.5 0.0 39.6 0.0 0.6 120 FTG 4T PH 0.0
19 16.5 0.0 39.5 0.0 0.001 TL 232.46 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 1/18/2009 C:\HASS77\FILES\PARAMOUNT\SIERRA WIRELESS\SIERRA.SDF
JOB TITLE: SIERRA WIRELESS REMOTE AREA A .10/1851 EXT COV HEADS
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 25 83.6 4.026 PL 12.00 PF 0.0
19 16.5 0.0 39.5 0.0 2.1 120 FTG ---- PE 0.0
17 16.5 0.0 39.5 0.0 0.003 TL 12.00 PV
Pipe: 26 -77.3 6.065 PL 5.58 PF 0.0
20 16.5 0.0 39.6 0.0 0.9 120 FTG L PE 0.0
18 16.5 0.0 39.6 0.0 0.000 TL 14.58 PV
Pipe: 27 77.3 6.065 PL 189.46 PF 0.1
20 16.5 0.0 39.6 0.0 0.9 120 FTG T PE 0.0
21 16.5 0.0 39.5 0.0 0.000 TL 219.46 PV
Pipe: 28 77.3 4.026 PL 5.58 PF 0.1
21 16.5 0.0 39.5 0.0 1.9 120 FTG T FE 0.0
19 16.5 0.0 39.5 0.0 0.002 TL 25.58 PV
Pipe: BULKMAIN -204.2 6.065 PL 47.18 PF 0.2
14 16.5 0.0 39.6 0.0 2.3 120 FTG 4L PE 0.0
TOR 16.5 0.0 39.8 0.0 0.002 TL 83.18 PV
Pipe: RISER -204.2 6.065 PL 16.00 FE' 0.1
TOR 16.5 0.0 39.8 0.0 2.3 120 FTG C PE 6.9
BOR 0.5 0.0 46.8 0.0 0.002 TL 48.00 PV
Pipe: 8"-UG1 -204.2 8.390 PL 110.00 PF 0.1
BOR 0.5 0.0 46.8 0.0 1.2 140 FTG TLG FE 1.9
FLOWTEST -4.0 SRCE 48.8 (N/A) 0.000 TL 199.00 PV
NOTES:
Calculations were performed by the HASS 7.6 computer program
under license no. 3808132110 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
The system has been calculated to provide an average
imbalance at each node of 0.002 gpm and a maximum
imbalance at any node of 0.037 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 6.4 ft/sec at pipe 7.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 1/18/2009 C:\HASS77\FILES\PARAMOUNT\SIERRA WIRELESS\SIERRA.SDF
JOB TITLE: SIERRA WIRELESS REMOTE AREA A .10/1851 EXT COV HEADS
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A U N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
2.067 5.00 10.00 3.00 11.00 6.00 1.00 10.00 10.00 10.00
PAGE: A MATERIAL: DTHRD HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEll ChkVlv BfyVlv GatVlv AlmChk DPVlv NPTee
4.026 10.00 20.00 6.00 22.00 12.00 2.00 20.00 10.00 20.00
6.065 14.00 30.00 9.00 32.00 10.00 3.00 28.00 19.00 30.00
PAGE: D MATERIAL: DIRON HWC: 140
Diameter Equivalent Fitting Lengths in Feet
(in) B T L C B G N
Eli Tee LngEll ChkVlv BfyVlv GatVlv NPTee
8.390 31.00 60.00 22.00 78.00 21.00 7.00 60.00
120. 0
WATER SUPPLY ANALYSIS
Static: 110.00 psi Resid: 100.00 psi Flow: 1546.0 gpm
G
A
U
G
P
R
E
S
S 60.0
U
R
E
40.0
p
S
±
20.0
-14.7
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
S
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 1/18/2009 C:\HASS77\FILES\PARAMOUNT\SIERRA WIRELESS\SIERRA.SDF
JOB TITLE: SIERRA WIRELESS REMOTE AREA A .10/1851 EXT COV HEADS
WATER SUPPLY CURVE
120+
\\\\\\\\\\
100+ * <-100.0 psi @ 1546 gpm
I Flow Test Point
90+
P 80+
R I
B
S I
S 70+
U I
R I
E I
60+
P
S I
I50+X
40+
30+
20+ LEGEND
I I,
I X = Required Water Supply
I 48.82 psi @ 304.2 gpm
10+ U
0 = Available Water Supply
I 109.51 psi 8 304.2 gpm
+------+--------+--------+---------+-----------+
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
ASo'oeo7
tqCLl IF/re & Building 0
1 ,Products
Technical Services: Tel: (800) 381-9312 I Fax: (800) 791-5500
Series EC-8 - 8.0 K-factor
Extended Coverage (Light Hazard)
Pendent and Recessed Pendent Sprinklers
General
Description
The Series EC-8 Extended Coverage
Pendent Sprinklers are decorative
glass bulb sprinklers designed for use
in light hazard occupancies. They are
intended for use in automatic sprinkler
systems designed in accordance with
standard installation rules (e.g., NFPA
13) for a maximum coverage area of
400 ft2 (37,2 m2), as compared to the
maximum coverage area of 225 ft2
(20,6 m2) for standard coverage sprin-
klers used in light hazard occupancies.
The recessed version of the EC-8, in-
tended for use in areas with a finished
ceiling, uses either the two-piece Style
30 or 40 Recessed Escutcheon. The
Style 30 Recessed Escutcheon pro-
vides up to 1/2 inch (12,7 mm) of total
adjustment from the flush pendent po-
sition, whereas, the Style 40 provides
3/4 inch (19,1 mm) of vertical adjust-
ment from the flush pendent position.
The adjustment provided by the Re-
cessed Escutcheons reduces the ac-
curacy to which the fixed pipe drops to
the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
WARNINGS
The Series EC-8 Extended Coverage
Sprinklers described herein must be
installed and maintained in compli-
ance with this document, as well as
with the applicable standards of the
National Fire Protection Association,
in addition to the standards of any
other authorities having jurisdiction.
Failure to do so may impair the per-
formance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Number
TY4232 - Pendent, 8.0K
TY4232 is a redesignation for C4232.
JANUARY, 2005
Technical
Data
Approvals
UL and C-UL Listed. FM and NYC Ap-
proved. (Refer to Table A for complete
approval information including corro-
sion resistant status. The approvals
apply to the service conditions indi-
cated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficients
K = 8.0 GPM/psi112
(115,2 LPM/barl'2)
TFP223
Page 2 of 6 TFP223
Components: 3/4" ** ESCUTCHEON PLATE
1 - Frame NPT j SEATING SURFACE
2 - Button
Sealing Assembly
Bulb 1 -M I J8" Compression _________ 2 Screw 3 1/2' _ (54,0 mm) Deflector *
* t f1 (l2,7mm)1i11 '1111 I
Temperature rating is NOMINAL 1-7" /16 I indicated on Deflector. i:i MAKE-IN mm)
** Pipe thread
connections per ISO
7/1 can be provided 6*
on special request.
FIGURE 1
SERIES EC-8 (TY4232) EXTENDED COVERAGE PENDENT SPRINKLERS
SPRINKLER FINISH (See Note 4)
HAZARD TYPE TEMP. BULB NATURAL I CHROME WHITE
BRASS PLATED
I
LIQUID POLYESTER
LIGHT PENDENT 135F/57°C Orange
Refer to Table B for UL and C-UL ______________
1,2,3,5 155°F/68°C Red
REC. PENDENT 135°F/57C Orange Sensitivity Rating
and W/ Style 30 Esc. 1, 2, 3, 5
Refer to Table C for FM 155OF/680C Red
REC PENDENT 135°F/57°C Orange Sensitivity Rating
w/ Style 40Esc. 1,2,5 155°F/68°C Red
NOTES:
Listed by Underwriters Laboratories, Inc. (UL).
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion
Resistant Sprinklers.
Approved by the City of New York under MEA 113-04-E. *Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS
(Refer to the Design Criteria Section)
Temperature Ratings
135°F/57°C and 155°F168°C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame .............Bronze
Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ........Glass (3 mm dia.)
Compression Screw .........
.......Bronze
Deflector ............Brass
t Registered trademark of DuPont
Operation
The glass bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series EC-8 Extended Coverage
Pendent Sprinklers must only be in-
stalled in accordance with the applica-
ble UL and C-UL Listing or FM Ap-
proval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installation, as applicable
(Ref. Table A, B, and C)..
UL and C-UL Listing
Requirements
The Series EC-8 Sprinklers may be
used for the coverage areas shown
in Table D, based on maintaining the
minimum specified flow rate as a
function of coverage area and haz-
ard group for all of the sprinklers in
the design area.
With respect to heat sensitivity, the
Series EC-8 Sprinklers can be used
with unobstructed construction con-
sisting of flat, smooth ceilings (in-
cluding bar joists) with a maximum
pitch of one in six as defined and
permitted by NFPA 13.
The minimum allowable spacing be-
TFP223
135°F 155°F
AREA STYLE
16x16 Pendent OR OR
16 x 16 Style 30 Recessed OR OR
16 x.16 Style 40 Recessed OR OR
18x18 Pendent OR OR
18 x 18 Style 30 Recessed OR SR
18 x 18 Style 40 Recessed OR SR
20x20 Pendent OR SR
20 x 20 Style 30 Recessed OR SR
20 x 20 Style 40 Recessed SR SR
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
135°F 155°F
AREA STYLE
16x16 Pendent OR OR
16 x 16 Style 30 Recessed OR N/A
16 x 16 Style 40 Recessed N/A N/A
18x18 Pendent OR OR
18 x 18 Style 30 Recessed OR N/A
18 x 18 Style 30 Recessed N/A N/A
20 x 20 Pendent OR OR
20 x 20 Style 30 Recessed OR N/A
20 x 20 Style 40 Recessed N/A N/A
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
TABLE C
SENSITIVITY RATING FOR FM APPROVAL
OF SERIES EC-8 SPRINKLERS
Page 3 of 6
Installation
The Series EC-8 Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak tight 3/4 inch NPT sprinkler joint
should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi-
mum of 30 ft.lbs. (40,7 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment of an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
Step 1. The sprinkler must be installed
with the deflector parallel to the mount-
ing surface. Pendent sprinklers must
be installed in the pendent position.
Step 2. After installing the Style 30 or
40 mounting plate (or other escutch-
eon, as applicable) over the sprinkler
pipe threads, and with pipe thread
sealant applied to the pipe threads,
hand tighten the sprinkler into the
sprinkler fitting.
Step 3. Wrench tighten pendent sprin-
klers using only the W-Type 3 (End A)
Sprinkler Wrench. Wrench tighten the
recessed pendent sprinklers using
only the W-Type 4 Sprinkler Wrench.
The wrench recess of the applicable
sprinkler wrench (Ref. Figure 4 and 5)
is to be applied to the sprinkler wrench
flats (Ref. Figure 1).
tween the Series EC-8 Sprinklers, to
prevent cold soldering, is 8 feet (2,4
m).
4. The Series EC-8 Sprinklers are to be
installed in accordance with all other
requirements of NFPA 13 for ex-
tended coverage pendent sprin-
klers.
FM Approval
Requirements
The Series EC-8 Extended Coverage
Sprinklers are to be installed in ac-
cordance with the applicable Factory
Mutual Loss Prevention Data Sheet.
Information provided in the FM Loss
Prevention Data Sheets relate to, but
are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spacing,
and deflector-to ceiling distance.
Page 4 of 6 TFP223
DESCRIPTION AREA GPM PSI
TY4232 (K=8.0) PENDENT 16 x 16 26 10.6
18x18 33 17.0
20x20 40 25.0
1 ft. = 0.3048 m
1 ft2 = 0.093 m2
1 gpm = 3.785 1pm
1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/mm
TABLED
FLOW CRITERIA FOR UL AND C-UL LISTING
OF SERIES EC-8 SPRINKLERS
- 2-7/8" DIA.
1/2±1/8' (73,0 mm) 1/2(12,7mm) r (12,7±3,2 mm) 2-1/4' DIA. 1/4' (6,4 mm)
FACE OF II (57,2 mm)
SPRINKLER /8" I FITTING (3,2 mm)
/JL MOUNTING MOUNTING SURFACE
TIN
PLATE
CLOSURE
1-1/4' (31,8 mm)
1" (25,4 mm)
FIGURE 2
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
2-7/8 DIA. -
9/16±1/4" (73,0 mm) 3/4(19,1 mm) r (14,3±6,4 mm) _ 2-1/4' DIA. 1/4(64mm)
FACE OF I (57,2 mm)
SPRINKLER I •7J I 1/8'
FITTING L._I (3,2mm)
/
\
MOUNTING
SURFACE// OUNTING
OUNTING
PLATE
CLOSURE
6"33,3mm
13/16(20,6mm)
FIGURE 3
SERIES EC-8 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
(END "A")
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH
WRENCH
RECESS
L fl
I U
WRENCH
LUGS
FIGURE 5
W-TYPE 4 RECESSED
SPRINKLER WRENCH
Care and
Maintenance
The Series EC-8 Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
the affected fire protection systems
must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers that are found to be leaking
or exhibiting visible signs of Corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
TFP223 Page 5 of 6
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
IMPLIED, INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS FOR A PARTICULAR PUR-
POSE.
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Refer
to the Price List for complete listing of
Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: TY4232, (specify temperature
rating), Extended Coverage Pendent
Sprinkler with (specify finish), P/N
(specify).
135°F157°C
Natural Brass .............PSN 50-801-1-135
White Coated .............PSN 50-801-4-135
White (RAL9O1O). .......... PSN 50-801-3-135
Chrome Plated ............PSN 50-801-9-135
l55°FI68C
Natural Brass .............PSN 50-801-1-155
White Coated .............PSN 50-801-4-155
White (RAL9O1O). .......... P5W 50-801-3-155
Chrome Plated ............PSN 50-801-9-155
Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style (30 or 40) Recessed
Escutcheon with (specify finish), P/N
(specify).
Style 30 Recessed Escutcheon
Chrome Plated ............PSN 56-705-9-011 White Color Coated ........PSN 56-705-4-011
White (RAL9O1O). .......... PSN 56-705-3.011
Brass Plated ..............PSN 56-705-2-011
Style 40 Recessed Escutcheon
Chrome Plated ............PSN 56-700.9-010
White Color Coated ........PSN 56-700-4-010 White (RAL9O1O). .......... PSN 56-700-3-010
Brass Plated ..............PSN 56-700-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1 -001
Specify: W-Type 4 Recessed Sprinkler
Wrench, P/N 56-875-4-001
Page 6 of 6 TFP223
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqCD /Fire & Building
/ Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series TY-FRB - 2.8,4.2,5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Tyco® Series TY-FRB, 2.8, 4.2,
5.6, and 8.0 K-factor, Upright and Pen-
dent Sprinklers described in this data
sheet are quick response - standard
coverage, decorative 3 mm glass bulb
type spray sprinklers designed for use
in light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20(1/2 inch NPT) or Style 30(3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment pro-
vided by the Recessed Escutcheon re-
duces the accuracy to which the fixed
pipe drops to the sprinklers must be
cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
tamed when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TV-FRB Pendent Sprinklers
are detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TYII3I - Upright 2.8K, 1/2"NPT
TY1231 - Pendent 2.81K, 1/2"NPT
TY2131 - Upright 4.21K, 1/2"NPT
TY2231 - Pendent 4.21K, 1/2"NPT
TY3131 - Upright 5.61K, 1/2"NPT
TY3231 - Pendent 5.61K, 1/2"NPT
TY4131 - Upright 8.0K, 3/4"NPT
TY4231 - Pendent 8.0K, 314"NPT
TY4831- Upright 8.0K, 1/2"NPT
TY4931- Pendent 8.0K, 1/2"NPT
Page 1 of 10 AUGUST, 2007 TFPI7I
Page 2 of 10 TFPI7I
ESCUTCHEON
PLATE SEATING
SURFACE
-r-
2-1/4"
(57,2 mm)
1-9/16"
(39,7 mm)
7/16(11,1 mm) STYLE 10 or 2(
NOMINAL RECESSED
MAKE-IN ESCUTCHEON DEFLECTOR
6
(11,1mm)
H
/
7/16" 1
_5
NOMINAL
MAKE-IN
2-3/16" "
(55,6 mm)
I
I/2"NPT f SSP DEFLECTOR * 1- 2-7/8' (73,0 mm) DIA. -1
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3 - Sealing 4 - Bulb 6 - Deflector * Temperature rating is indicated on deflector or adjacent to 2 - Button Assembly 5 - Compression 7 - Bushing orifice seat on frame. Screw
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TYI 13 1) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 7/16"(11,1 mm)
PLATE SEATING NOMINAL
SURFACE 12 MAKE-IN
23il6'
NPT
(55,6 mm)
f
1-1/2"
(38,1mm)
STYLE 10 or 20
RECESSED *
ESCUTCHEON I]II(SJ
NOMINAL 4
NOMIr
FLATS
4
SSP DEFLECTOR ( 2-7/8" (73,0 mm) DIA,
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
1 - Frame 3- Sealing 4 - Bulb 6- Deflector 2 - Button Assembly 5 - Compression
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 112 INCH NPT
1/2"
(12,7 mm)
NOMINAL
MAKE-IN
2-1/4"
(57,2 mm)
CROSS SECTION
TFPI7I Page 3 of 10
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING NOMINAL
SURFACE 1/2 MAKE-IN NPT
F_
2-3/16° \ A
(55,6 mm)
1-1/2"
(38,1mm)
STYLE 100r20
RECESSED
ESCUTCHEON SSU
DEFLECTOR
1
7/16" I (11,1 mm)
NOMINAL
;
MAKE-IN
2-3/16°
WRENCH ______ __ 55,6 mm
FLATS
1/2"NPT t SSP DEFLECTOR - 2-7/8 (73,0 mm) DIA.
PENDENT RECESSED PENDENT UPRIGHT CROSS SECTION
'1 - Frame 3 - Sealing 4 - Bulb 6- Deflector
2 - Button Assembly 5 - Compression
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
FIGURE 3
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON 1/2"(12,7 mm)
PLATE SEATING NOMINAL
SURFACE a" MAKE-IN NPT
2-5/16"
_
(58,7 mm)
1-9/16"
(39,7 mm)
/
3/4' NPT
UPRIGHT
WRENCH
FLATS
SSP DEFLECTOR * I 2-7/8" (73,0 mm) DIA.
PENDENT RECESSED PENDENT
STYLE 30 or 40
RECESSED SSU* ESCUTCHEON DEFLECTOR
1 - Frame 3 - Sealing 4- Bulb 6- Detector
2 - Button Assembly 5 - Compression
Screw
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
FIGURE 4
QUICK RESPONSE SERIES TV-FRB UPRIGHT (TY4131) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 314 INCH NPT
PENDENT
1 - Frame 3 - Sealing 4 - Bulb 6- Deflector
2 - Button Assembly 5 - Compression
Screw
-r-
2-1/4"
(57,2 mm)
1-9116"
(39,7 mm)
- ssP*
DEFLECTOR CROSS
UPRIGHT SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
!hli CH
S
Page 4 of 10 TFPI7I
1/2'
NPT
7/16(11,1 mm)
NOMINAL
MAKE-IN
ssu *
DEFLECTOR
FIGURE 5
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY4831) AND PENDENT (TY4931) SPRINKLERS
8.0 K-FACTOR, 1/2 INCH NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A and B for complete
approval information including corro-
sion resistant status.)
Maximum Working Pressure
Refer to Table C.
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/bar1l2)
K = 4.2 GPM/psil/2 (60,5 LPM/bar112)
K = 5.6 GPM/psi1/2 (80,6 LPM/bar1l2) K = 8.0 GPM/p51112 (115,2 LPM/bar1I2)
Temperature Ratings
Refer to Table A and B
Finishes
Sprinkler: Refer to Table A and B.
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated.
Physical Characteristics
Frame .............Bronze
Button .........Brass/Copper
Sealing Assembly ..........
Beryllium Nickel w/Teflont
Bulb ...............Glass
Compression Screw .....Bronze
Deflector .......Copper/Bronze
Bushing (K2.8) .......Bronze
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
TFPI7I
SPRINKLER FINISH (See Note 7)
K TYPE TEMP. BULB NATURAL I CHROME I WHITE"
LIQUID BRASS PLATED IPOLYESTER
135"F/57°C Orange
PENDENT
(TY1231)
and 12,3,5
155"F/68"C Red
175°F/79°C Yellow
2.8
1/2"
UPRIGHT
(TY1131) 200°F193°C Green
286"F/141"C Blue
NPT 135°F/57°C Orange
RECESSED
PENDENT
155"F/68°C Red
175°F/79°C Yellow (1Y1231)*
Figure 6 1, 2, 5 200°F/93°C Green
135°F157°C Orange
RECESSED
PENDENT 155°F/68°C Red
175°F/79°C Yellow (TY1231)
Figure 7 200"F/93°C Green
135"F/57°C Orange
PENDENT
(TY2231) "F/68° 155 C Red
175"F179"C Yellow and
UPRIGHT 200°F/93°C Green
4.2
1/2"
(TY2131)
1,2 286"F/141°C Blue
135°F/57"C Orange NPT RECESSED
PENDENT 155"F168"C Red
175"F/79°C Yellow Y2231)*
Figure 8 200°F/93"C Green
135"F/57°C Orange
RECESSED
PENDENT 155"F168°C Red
175°F179°C Yellow (TY2231)
Figure 9 200°F/93°C Green
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Re-
sponse Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
** Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
Page 6 of 10 TFPI7I -
SPRINKLER FINISH (See Note 8)
K TYPE TEMP. BULB NATURAL CHROME I WHITE LEAD I
LIQUID BRASS PLATED IPOLYESTER COATED
135°F/57°C Orange
PENDENT
(TY3231)
and 1,23,45,6,7 1,2,3,5
155°F/68"C Red
175F/79°C Yellow
5.6
UPRIGHT
(TY3131)
1/2"
200"F/93"C Green
286°F/141°C Blue
NPT 135"F/57"C Orange
1,2,4,5 N/A
RECESSED
PENDENT
(TY3231)*
155"F/68°C Red
175"F/79°C Yellow
Figure 10 200"F/93°C Green
135F/57°C Orange
1,2, 3,4, 5 N/A
RECESSED
PENDENT
(TY3231)"
155°F/68"C Red
175°F/79°C Yellow
Figure 11 200"F193°C Green
135"F/57°C Orange
PENDENT
(1Y4231)
and
UPRIGHT 1,2, 3,4, 5,6, 7
1,2,5
155°F/68°C Red
175°F/79°C Yellow
200°F/93"C Green
8.0
3/4,,
(1Y4131)
286"F/141°C Blue
NPT 135F/57°C Green
1,2,4,5 N/A
RECESSED
PENDENT
(TY4231)*
155"F/68°C Orange
175°F/79°C Red
Figure 12 200F/93°C Yellow
135"F/57°C Orange
1,2, 3,4, 5 N/A
RECESSED
PENDENT
(TY4231)
155F/68°C Red
175°F/79°C Yellow
Figure 13 2007/93°C Green
135°FI57C Orange
8.0
1/2"
NPT
PENDENT
(TY4931)
and
UPRIGHT
(TY4831)
1,2,4,5,6
1,2,5
155°F/68"C Red
175°F/79"C Yellow
200°F/93"C Green
286"F/141"C Blue
NOTES:
Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers: however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377).
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4' NPT) 3/4' Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2' Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
TFPI7I Page 7 of 10
SPRINKLER FINISH
K TYPE NATURAL CHROME I WHITE LEAD
BRASS
I
PLATED POLYESTER COATED
PENDENT (TY3231)
and
2.8 UPRIGHT (TY3131) 175 PSI (12,1 BAR) N/A
1/2' RECESSED PENDENT NPT (TY323)
PENDENT (TY4231)
and
4.2 UPRIGHT (TY4131) 175 PSI (12,1 BAR) N/A
3/4,, RECESSED PENDENT NPT (TY4231)
PENDENT (TY3231)
and 250 PSI (17,2 BAR) 175 PSI (12,1 BAR)
5.6 UPRIGHT (TY3131) OR
1/2' 175 PSI (12,1 BAR) RECESSED PENDENT NPT (TY3231) (SEE NOTE 1) N/A
PENDENT (TY4231)
and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
8.0 UPRIGHT (TY4131)
3/4,, RECESSED PENDENT NPT (TY4231) N/A
8.0 PENDENT (TY4931)
1/2" and 175 PSI (12,1 BAR) 175 PSI (12,1 BAR)
NPT UPRIGHT (TY4831)
NOTES:
1. The maximum working pressure of 250 psi (17,2 bar) only applies to the Listing by Underwriters Laboratories Inc. (UL); the Listing by
Underwriters Laboratories, Inc. for use in Canada (C-UL); and , the Approval by the City of New York.
TABLE C, MAXIMUM WORKING PRESSURE
Installation
The Series TY-FRB Sprinklers must
be installed in accordance with the fol-
lowing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 1/2 inch NPT sprinklerjoint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over-tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 14).
With reference to Figures 1, 2, 3, 4,
and 5, the W-Type 6 Sprinkler Wrench
is to be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 15). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Page 8 of 10
- 2-7/8" DIA. -
518±1/4" (73,0 mm) 3/4"(19,11 mm)
(15,9±6,4 mm) - 2-1/4" DIA. 1/4"(6.4 mm)
FACE OF mm)
1
*(3.u2
NTING I SPRINKLER ATEFITTING
/8"
3,2 mm)
MOUNTING SURFACE
CLOSURE SERIES
TY-FRB 13/16(20,6 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. -
5/811/4"
(73,0 mm) 3/4"(19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. I 1/4" (6,4 mm)
FACE OF 2mm) I MOUNTING I SPRINKLER PLATE
FITTING
1/8"
MOUNTING
SURFACE/ •.'.
CLOSURE SERIES 1-1/4(31,8 mm)1
TY-FRB 3/4"(19,11 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
TFP171
- 2-7/8" DIA.
1/2±1/8" I (73.0 mm) 1I2"(12,7mm)
[(12,7±3,2 mm) 2-1/4" DIA. I 1/4" (6,4 mm) 1
FACE OFqR 572 mm) i1 I MOUNTING SPRINKLE _PLATE FITTING
1/8"
(32mm)
SURFACE
1-5/16"(33,3 mm)
MOUNTIN
CLOSURE SERIES
TY-FRB 1-1/16" (27,0mm).
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA. -
1/2±1/8" (73.0 mm) 1/2"(12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. I 1/4" (6.4 mm) I
FACE OF (57 2mm) MOUNTING I I SPRINKLER PLATE I I
/ 1/8"
(32
FITTING ?
mm) I
T__\ MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31.8 mm)1
1Y-FRB 1"(25,4 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
Care and
Maintenance
The Series TY-FRB Sprinklers must
be maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
The owner must assure that the sprin-
klers are not used for hanging of any
objects; otherwise, non-operation in
the event of a fire or inadvertent opera-
tion may result.
Absence of an escutcheon, which is
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic Sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler
that has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been corn-
TFPI7I
- 2-7/8' DIA. -
5/8±1/4" (73,0 mm) 3/4" (19,1 mm)
(15,9±6,4 mm) - 2-114" DIA. 1/4" (6,4 mm)
I
FACE OF
MOUNTING
(57,2
SPRINKLER PLATE FITTING
1/8"
(3,2mm)
MOUNTING t
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
TYFRB 3/4"(19,1 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
- 2-7/8" DIA.
5/8±1/4" (73,0 mm) 3/4"(19,1 mm)
(15,9±6,4 mm) 2-1/4" DIA. I 1/4"(6,4 mm)
(57,2 mm) I I
FACE OF I MOUNTING
PLATE SPRINKLER
FITTING
_______ 1/8" I _____
__ _________________
(3,2 mm)
/k/
L
H MOUNTING
SURFACE
CLOSURE SERIES 1-5/16"(33,3 mm)
TY-FRB 13/16"(20,6 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
Page 9 of 10
- 2-7/8" DIA. -
1/2±1/8" (73,0 mm) 1/2'(12.7 mm) r (12,7±3,2 mm) H— 2-1/4" DIA. 1/4"(6.4 mm)
FACE OF (57,2 mm) MOUNTING SPRINKLER PLATE
1/8"
FITTING
mm) I
f \
MOUNTING
SURFACE
CLOSURE SERIES 1-1/4"(31,8 mm)
TY-FRB 1"(25,4 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
2-7/8" DIA.
1/2±1/8" (73,0 mm) 1/2'(12,7 mm)
E (12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm) MOUNTING
PL I SPRINKLER ATE
I FITTING 1/8
2 m
" I , ( 3,m)
T-7- MOUNTING
SURFACE
CLOSURE SERIES 1-5/16" (33,3 mm)
TY-FRB 1-1/16"(27,0 mm)
FIGURE 13
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-Up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
WRENCH RECESS
(END "A" USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4" NPT MODELS)
FIGURE 14
W-TYPE 6 SPRINKLER
WRENCH
facturer should be contacted relative
to any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
WRENCH
RECESS
PUSH WRENCH
INTO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 15
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Inspection Service in accordance with
local requirements and/or national
codes.
330 2.8K UPRIGHT (1/2"NPT) TY1131
331 2.8K PENDENT (1/2"NPT) TY1231
340 4.2K UPRIGHT (1/2"NPT) TY2131
341 4.2K PENDENT (1/2°NPT) TY2231
370 5.6K UPRIGHT (1/2'NPT) TY3131
371 5.6K PENDENT (112NPT) TY3231
390 8.0K UPRIGHT (3/4°NPT) 1Y4131
391 8.0K PENDENT (3/4'NPT) TY4231
360 8.0K UPRIGHT (1/2NPT) 1Y4831*
361 8.0K PENDENT (1/2"NPT) TY4931*
PIN 57-XXX-X-XXX
I
I - MODEL/SIN
TEMPERATURE
RATING
* Eastern Hemisphere sales only.
SPRINKLER
1 NATURAL BRASS
4 WHITE POLYESTER
3 WHITE (RAL9010)*
9 CHROME PLATED
rmmw_l 816107A11101
135 135°FI57C
155 155°F/68°C
175 175°F179°C
200 200°F193°C
286 I 286°F/141°C
Page 10 of 10 TFPI7I
TABLED
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
of merchantability and fitness for a oar-
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
Ordering
Procedure
When placing an order, indicate the
full product name. Refer to the Price
List for complete listing of Part Num-
bers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table D).
Recessed Escutcheon:
Specify: Style (10, 20, 30, or 40) Re-
cessed Escutcheon with (specify*) fin-
ish, P/N (specify*).
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446