Loading...
HomeMy WebLinkAbout2251 FARADAY AVE; ; FA100014; Permit11/3/21, 3:13 PM FA100014 Permit Data City of Carlsbad Fire Alarm Permit Job Address: 2251 FARADAY AV Permit Type: FALARM Parcel No: 2120610400 Lot #: 0 Reference No.: Permit No: FAI 00014 Status: ISSUED Applied 4/5/2010 Approved: 4/5/2010 Issued: 4/5/2010 PC #: Inspector: Project Title: ABBOTT IBIS T.I. FIRE ALARM PLAN CHECK & INSPECTION Applicant: COSCO FIRE PROTECTION 10695 TREENA ST SAN DIEGO, CA 858-444-2000 Owner: CARLSBAD RESEARCH CENTER L L C 5155 FIGUEROA FL #16 LOS ANGELES CA Fees ($) Add'I Fees ($) Total ($) Balance ($) 125 L 0 125 0 1/1 FA10oo14 Abbott Bioscience Alarm TI Review Comments. Page 2 ., Review Comments Abbott Bioscience Alarm TI, 2551 Farraday Avenue, Carlsbad, CA Device AV7-0 1 on sheet FA-1.01 must be located no more than 15'-0" from either end of the north-south corridor #1008. The device can be field relocated to achieve this position, however, this will require an additional notification device in the east-west corridor between electrical room #1007 and the workroom #1026A. This can also be field provided, as the battery calculations reveal enough power to allow an additional device, and still maintain the required safety margin of 20%. Field verify that device AV3 -13 in the pilot lab #1150 is not greater than 14'-0" from either east or west wall, as the maximum spacing for a 30 cd device on a single wall is 28'x 28', per NFPA- 72. If the lintel depth at the west end of corridor #1159 blocks the view of device AV3-15, an additional device must be added inside the corridor within 15'-0" of the west end. This can also be field provided, as the battery calculations reveal enough power to allow an additional device, and still maintain the required safety margin of 20%. A notification device must be added within 15'-0" of the west end of corridor #1203 on sheet FA-1.02, again, only if the apparent wall or lintel at that end blocks the view of device AV 1-05. If that device can be clearly seen from the corridor, no revision is required. The charging capacity of the i0500 FACP is shown as 26 aH in catalog data sheets, as opposed to 40 aH shown on sheet FA-2.01. Plans have been redlined with the correct value. No revision required. We strongly recommend the following operational tests be performed once the system installation has been completed. A "power off' test, where the normal power supply is shut off, and the system is left to function on battery power alone for a period of 24 hours, at which time the system should still be functioning and operational. At the end of the end of the above test, prior to the primary power being restored, the system should be placed in an "alarm" condition for a period of not less than five minutes, during which time all notification appliances, including the off-station notification, are to function as designed. Once the two prior tests have been completed, the current level in the batteries should be checked, the primary power restored, and at the end of 48 hours the current level checked again to verify that the charging function of the panel is both operational, and able to recharge the batteries within the time period specified by NFPA-72. d. Once the test in item "c" has been completed, one of the leads to the battery should be disconnected, to determine that the system will provide notification of an "off-normal" power condition to the monitoring company. rA i00014 ......,I I cosco Fire Protection San Diego Branch Office 10695 Treena Street., Suite #105 San Diego, CA 92131 (858) 444-2000 fax: 444-2056 Stale License No: C-16 & C-10-577621 www.coscofire.com MATERIAL SUBMITTAL Date:3/1/2010 Abbott Labs IBIS 2251 Faraday Ave, Carlsbad, CA 92008 JOB # I O.Cd-5279 FILE copy All material submitted, maybe substituted by material of equal performance & design, & shall be deemed acceptable by purchaser. CTOF CARLSBAD '4C DEPARTMENT APPROVED "W"ctTC Ieid irspectjon and required r; 1IShereon, conditions in n' ince and coflfbrmance with r jyit. reaulatjons The Stamping 1flS shall not be h d to permJ PProethevioIat,onn, Date Submitted By: Stuart Vernon 0 Los Angeles 0 San Francisco • Orange 0 Fresno • San Diego • Seattle S 'GE' EST Fire & Life Safety Security QuickStart Multiplexed/Hardwired Overview GE Security's QS1 life safety control panel brings big-system intel- ligent control to small applications. Designed for easy setup and simple installation, QuickStart lives up to its name in every respect. QS1's exclusive QuickStart auto-learn function, and the option of configuring the panel using convenient front panel programming or from a PC, makes short work of system setup. Devices come on-line in no time as well, thanks to QS1's built-in barcode scanner port. A simple pass of the optional scanner is all it takes to store device in- formation in the QuickStart database. The scanner can also be used for quick and easy text entry when assembling custom messages. QS1's setup routine is deceptively simple, considering this sys- tem's robust features. Supporting up to 250 intelligent detectors and modules, QS1 takes full advantage of GE Security's exclusive Signature Series technology, which provides electronic addressing, automatic device mapping, environmental compensation, and true multisensor detection. QuickStart's innovative design makes it easy to add a dialer or extra auxiliary relays. Quick-Lok option cards snap onto 051's easily-ac- cessible DIN mounting rails. QS1 also supports as many as eight remote annunciators and up to 30 programmable front panel switches with dual LEDs for system control and display. QS1 is as simple to operate as it is to set up. Its large 14-line backlit LCD display provides easy-to-understand details concerning up to 1,000 system events, while bright system status LEDs and large, tactile control buttons present the user with a clean, crystal clear interface. Four password levels limit control and information retrieval to authorized personnel. A priority access keyswitch gives Level 2 ac- cess without a password to management and emergency personnel. Standard atures Supports p to 250 Signature Series intelligent de Combines t nature' 14 easing module with Signa- ture multisensor detectors for reliable suppression Failsafe mode ensures uncompromised reliability Class A (Style 7) or Class B (Style 4) wiring options Capacity for eight serial annunciators Four built-in system relays Optional dual line dialer supports Contact ID and 4/2 formats Three methods of programming: QuickStart "auto-learn," front panel and personal computer (PC) Supports optional barcode scanner for direct device data entry Optional bank of 30 front panel switches with dual LEDs Up to 20 adjustable pre-alarm settings for Signature smoke detectors Wallboxes available in red or gray with optional trim ring for semi-flush mounting. Large 14-line (224 character) backlit LCD display Four password levels, plus priority access keyswitch Message routing by event type or by individual message Alarm sensitivity by time of day or manual selection 1,000 event history buffer, plus alarm history counter 6 amp Power Supply, 4.75 amps available for external use Envoy graphics compatible Compare utility identifies system changes and simplifies testing C Intelligent Single Loop Life Safety Control Panel QSI. 'T1'5 4 1 -19 fl -- .. NUMW ----:. -I MEA Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page 1 of 8 Mounting 2.2" (5.6 cm) Semi-flush Mounting (12.4 cn) Optional f'F 1 Vandal- Resistant Door I L 1.68" Walt H (4.27 cm) Surface Mounting Application Thanks to its flexibility and simple setup and operation, QS1 is ideal for new installations in schools, apartment buildings, hospitals, of- fice buildings, and retail facilities. The benefits brought by QS1 to retrofit applications underscores the true potential of this powerful system. As an intelligent panel, QS1 supports Signature Series devices, which can use existing wiring in most retrofit applications. This makes upgrading from a conven- tional system to analog control a simple operation with minimal disruption to normal operations at the site. Which Qwcks tort Panel is right for you? Qsc QS1 QS4 Signature Series devicessupported 0 1 t<250 4 x 250 Conventional class B Circuits supported 3 x 16 0 3 x 16 Conventional class A circuits supported 5 x 8 0 5 x 8 LCD display hines x characters) 4 x 20 14 x 16 14 a 16 Optional Zone Switch/LEDs on front panel 2 x 30 1 a 30 2 a 30 Option card spaces 5 or 12 1 5 or 12 For more information, see Data Sheet ... 85005 -0112 85005 -0113 85005 -0114 Dimensions o 0 0 o 0 I4Y? (36.2 cm) I 18" (45.72 cm) CPU / LCD Display The QS1 front panel display provides 14 lines by 16 characters of text detailing event, device, diagnostic, and programming infor- mation. Its large backlit LCD screen is easy to read and always provides at-a-glance indication of the system's state of operation. The CPU/Display Unit houses the CPU card and mounting space for one optional LED/Switch card. 7fl - kjI . [y] Display with two alarms shown fl Semi-flush mount- ing requires an optional trim ring, which adds Y4" to all sides of the Panel. Specifications Control Panel Standby Current 199mA Alarm Current: 235 mA Remote annunciator Standby Current 154 mA (Full control versions) Alarm Current: 166 mA SRA Series Standby Current 70 mA • Alarm Current: 90 mA Operating Temperature: 32-120°F (0-49'C) environment Humidity: 93 %RH, non-condensing Failsafe Mode If the CPU loses communication with other circuit cards, the power supply card continues to monitor the system for any alarm events. If an alarm occurs on any device or circuit during a communica- tions failure, the power supply activates all alarm outputs and instructs the dialer to transmit a default alarm message to the monitoring station. S Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page 2 of 8 QS1 Annunciator QS1 remote annunciators connect directly to the PS6 Power Supply Card or an external 24 Vdc filtered supply. They are available with wallboxes for - .----- -. flush or surface mounting. Annuncia- tors are available with one annuncia- tor option space for a display card with 30 dedicated switches and LEDs. See the Ordering Table for more information. Class B Wiring Class A Wiring J Mounting o Field wiring Electrical box Mounting ring Annunciator Reriiote Annunciators QS1 supports up to eight remote annunciators, which provide mirrored or customized S annunciation of front panel messages and status indicators. Two models are available: The QSA Series, and the SRA Series. SRA Annunciator The QuickStart SRA Remote Annunciator is a single-loop standalone unit that can be powered by the control panel or by an approved power supply. Annunciators support Class A or Class 8 connection to the sys- tem RS-485 data line, but do not provide ground fault isolation. The SRA annunciator includes an RJ-12 modular jack to allow sys- tem database downloads from a laptop computer. Connection requires a programming cable (model number PROGCABLE-1, ordered separately). Annun- ciators are mounted to North American 2-gang or 4-inch square electrical boxes. CH2 CH2 RA RA CHI I I CHI X485 100001 TB . r-;1;-- Class A Wiring II I + + - I I T_2!2(-(-)ouT I 0 CH2(-)OUT CH2 Cl-Il cii+ou I 0 CU2(+)OUT NT-A 0 CM2(-)IN 0 CH2(-)IN RS-485 CARD 0 CH2(*)IN I 0 CIi2()IN Dimensions CH2- GIi1(.)OUT Ø CHI (-)OUT Model Height Width Depth dM2 I? CHI ( )OUT 0 CIII( )ouT QSA-1-S 7.6 (19.46 cm) 14.25'(36.20 cm) 2.9'(7.3 cm) CHI- Ø IpCHI(-)IN I O CHI (-)IN QSA-1-F (roughin) 6.56 (16.66 cm) 13.25"(33.66 cm) 2.1 (5.33 cm) CH2 • 0 CHI(+)IN 0 CHI+)IN .j I .819.B1cm)]cml 1 crn( LISTED 24 VOC I Rough-in dimensions reflect the size of the cabinet where it enters the wall, SUPPLY COMMON OUT I 0 COMMON OUT Finished dimensions reflect the size of the cabinet that protrudes from the wall. 24 +24VDC IN 0 24VDC IN 24 VDC - COMMON IN I 0 COMMON IN ?EARTHGND ?EVThGND XGD Graphics Driver Card The XGD Graphics Driver Card is an interface device that connects a QuickStart annunciator to an Envoy Graphic Annunciator. The XGD provides the electronics required to support 24 LEDs and 12 switches on the Envoy display panel. Multiple XGD cards can be chained together in one graphic annunciator cabinet to control S larger displays. The QuickStart SRA Series annunciators can support a maximum of six XGD cards. Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page 3 of 8 Class B Wiring Annunciator Annunciator 1 0 CH2(-)OUT 0 CH2(-)OUT 0 CH2(+)OUT 1 0 CH2(+)OUT 0 CH2(-)IN 1 0 CH2(-)IN 0 C142(*)IN 0 CH2(+)IN CHl(-)OUT CHI (-)OUT PS6 ? CHI (-)OUT 0 CI-11(*)OUT R9485- p I 0 CHI ON I 0 CHI(-)IN RS484 0 Clii MIN 0 CMI (*)IN LISTED 24 VOC *24VC OUT 1 0 +24V0C OUT SUPPLY COMMON OUT 1 0 COMMON OUT 24 VOC -Ø .24V0C IN 0 24VDC IN 24 VOC - 0 COMMON IN 1 0 COMMON IN [EARTI1GND EARTHGND Controls Reset button: . Allows devices or zones in alarm or trouble to restore . . to their standby condition. The LED indicates that the panel is resetting. Alarm Silence button: Turns active notification appliances off depending on panel programming. Pressing Alarm Silence a second time turns them back on. The LED indicates that the panel is in alarm and operating with notification appliances turned off. 15. Drill button: Activates notification appliances depending on panel programming but does not place the panel in alarm. The LED indicates that the panel is in Drill Mode. Menu button: Displays the operator menus. Delete button: Returns to the previous menu or backspaces the cursor. Enter button: Press the Enter button to accept information or continue to the next item. Numeric keypad: Numbered buttons for entering values and making menu selections. Barcode scanner jack: Input for optional barcode scanner. Priority Access keyswitch: Enables control functions reserved for access level 2 and above without requiring a password. S Operation P ..j I T"TTITTT Indicators 1. Text display and controls: Displays iWA system messages, status information, t and programming menus. Arrow buttons move the display cursor. Alarm LED: Indicates a fire or life threatening emergency. Supervisory LED: Indicates an off-normal condition with the fire suppression system or related equipment. Disable/Test LED: Indicates part of the system is disabled or be- ing tested. Disabled components also signal a system trouble. Monitor LED: Indicates the operation of on ancillary system function (door closures, fan pressure switches). Trouble LED: Indicates an off-normal condition or wiring fault that compromises the integrity of the system. Ground Fault LED: Indicates a ground fault in the system wir- ing. Ground faults also signal a system trouble. CPU Fail LED: Indicates an unexpected reboot or failure with the microprocessor. CPU failures also signal a system trouble. Power LED: Indicates the panel has power. Help button: Provides additional information about the device selected on the display. Status button: Displays the Status Menu from which you can identify active or disabled points in the system. Panel Silence/Acknowledge button and LED: Acknowledges all events posted in the display queues and turns off the panel buzzer. The panel silenced LED indicates that off normal events have been acknowledged. Data Sheet 85005-0113 issue 6 Not to be used for installation purposes. Page 4 of 8 Enhanced Integrity End-of-Line lJ Horn-Strobe Resistor Genesis lJ] Programmable lI Horn-Strobe I/O Module a Genesis j.J Universal Signal Master I/O Module 2 Smoke l Dual Circuit Detector Input Module 2-Wire Control Relay ti Smoke Detector Module Smoke Detector j Signal 'ms with Relay Base Module Smoke Detector Signal Module with Isolator Base (synchronization) J Manual Riser Monitor Pull Station Module Junction Monitor Module Box More wiring suggestions can be found in the QSI Fire Alarm Control Panel Installa- tion, Operation, and Maintenance Manual, P/N 3100184. Typical Wiring Class A Signature Data Circuit RM CR1 Class A Notification Appliance Circuit with Genesis Signals and Signal Master for Independent Horn and Strobe Control and Synchronization over two conductors. Class A Fire ature Data Damper Circuit 2nd Floor Class B Notification LcQi ApplianceCiit H -<--i 10 I --(----(}--' il' I I V. Critical Process Waterfiow . - Monitoring Switch with Control Sprinkler Supervisory Switch CR 77 N~7 7K7 Elevator OLC3SO5 Capture Class AN Appliance Circuit OSI Panel 21. Class B Signature Data Circuit rR.M1 24 Vft 21 Horn and Strobe Synchronization with Audible Silence Class BNotification Appliance Circuit with V —\7 Genesis Signals and 11 Signal Master for Signature i Circuit (I pr.) D. 're per 2nd Floor Horn and Strobe _____ pr) Control (2 r-21 Vd Critical Process I Waterfiow t. Monitoring - Switch - - CT2 Sprinlder Supervisory Switch CR Elesstor Capture j Horn and Strobe Synchronlzation with Audible Silence OS1 Panel Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page of 8 P56 Power Supply Card Description The PS6 provides primary dc power to all the circuit cards installed in the cabinet. There are four 24 Vdc power output circuits - three for powering auxiliary applications, and one for powering four-wire smoke detectors - and a charging circuit for standby batteries. The PSIS also provides common alarm, supervisory, and trouble relays, as well as a fourth relay that is user programmable. Wiring ___ RxYYYwR s.c. aLsYovea R.,,,a SOa&b. ______ 0110 OURE CON OUXU REM TB2 -- I 11-c I® 0000000000000000 1TB1 * RELAY I RELAY 0 RELAYS RELAY I SNORE 05400 00232 SO C NC C NO C NO C 00501 * - * - 01510 ROCON EEC P320 Relay 1: Form C. Contacts change position when the control panel processes an alarm signal and remain changed until all active alarm inputs restore and the control panel resets. Relay 2: Form A. Contacts change position when the panel processes a supervisory signal and remains changed until all active supervisory inputs restore. Relay 3: Form A. Contacts change position when the panel lanes power or processes a trouble signal and remains changed until power returns or the trouble clears. Relay 4: Form A. Relay closes and opens according to panel programming. Smoke/Accessory Power: Jumper setting determines if the 24 Vdc inconstant or resettobie. SLIC Signature Loop Intelligent Controller Description The SLIC provides one doss A or Class B data circuit (loop) for connecting Signature Series detectors and modules. The SLIC also provides two programmable Class A or Class B notifica- tion appliance circuits (NACs) for connecting polarized 24 Vdc notification appliances such as horns and strobes. QS1 supports one SLIC. Wiring class A Class A OUT IN LOOP - A - Ac A.. BY B- eo.i coil I® 000001 I Iii II H I I I 1111 ii III 00000000lisi I cl BY B- Ax A- BY B- AU A- L_Ji NAC1 NAC2 Class 81 82 Signaling Line circuit and NACs are super- vised and power- limited. Standard Components and Option Cards QS1 panels come standard with a CPU/Display Unit, an SLIC Signature Loop Controller, and a PS6 Power Supply (see ordering information for details). Available QS1 option cards provide dialing capability or extra relays for ancillary control. Quick-Lok option cards snap onto DIN mounting rails for fast, no-fuss installation. One op- tion card space is available. Cabinet with option card and batteries motel/nd [I Standard Component Specifications Main supply circuit AC input: 115 or 230 Vac, 50/60 Hertz DC input: 24 Vdc batteries Charge current: 2 amps Battery charging circuit charge capacity: 40 amp hours (UL) 30 amp hours lULCl. —. Smoke/Accessory Voltage: 24 Vdc, regulated Current 250 mA power output circuit Wire size: 12 to 1810.75 to 2.5 mm') Quantity: 3 Auxiliary power output Voltage: 24 vdc full wove rectified circuits Current: 1.5 amps each • Style: Form C Common alarm relay Contact rating: lamp Wire size: 12 to 18 AWG 10.75 to 2.5 mm') Trouble, Supervisory Style: Form A IN/0) and programmable Contact rating: 1 amp relays Wire size: 12 to 18 AWG 10.75 to 2.5 mm') Operating environment Temperature: 32 - 120° F 10- 49° Cl Humidity: 93 %RH,_non-condensing Current requirements Standby current: 72 mA Alarm current: 96 mA Standard Component Specifications Configuration: Class 8 (Style 41 or Class A (Style 71 SignalingIIn e Capacity: 125 Signature detectors circuit 125 Signature modules Wire size: 18 to 12 AWG 10.75 to 2.5 mm') Circuit resistance: 65ohms Circuit capacitance: 0.3 pf Configuration: Class B or Class A Notification Output voltage: 24 Vdc, nominal appliance Output current 2.0 A at 24 Vdc for #1 circuits #1 and 0.8 A at 24 Vdc for #2 and #2 Wire size: 18 to 12 AWG 0.75 to 2.5 mm') End of line resistor: 10k ohms, ½ W NAC power Voltage: 24 Vdc, nominal input circuit Wire size: 18 to 12 AWG 10.75 to 2.5 mm°l Operating Temperature: 32 - 120° F 10 - 49° Cl environment Humidity: 93 %RH, non-condensing Current Standby current: 33 mA requirements Alarm current: 57 mA (Both NACs on) Card spaces Requires one card space. Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page 6 of 8 OLD Dialer Wiring RJI,X 4(GREEN) TO PHONE UNOIO IPIN MACALAN ONNECTO FM )VOREOSNJENA PHONE UNE 01) • 4 GREEM t IPINMOELtAC - S CONNECTOR FOR RCA PHONE LPEE2 -, - AnNl ® PREMIONS PHONES f 00 000 00 TB) NIP RNG TIP ORG TIP RING liP RING IN OUT OUT LINE I IN LINE 2 - -, .. •I. •Option Card. Specifications Operating Temperature: 32 - 120° F 10-49 °Cl environment Humidity: 93% RH, non-condensing Current Standby: 13 mA requirements Alarm. 20 mA Dialing: 26 mA Phone Lines Two loop start lines on switched telephone network. Pulse or DTMF dialing. Wall Connector RJ31x/cA31A equiv. or RJ38X/CA38A equiv. Communications Contact ID (SIA Dc-05), 4/2 1SlA DC-02 1331. Protocol Programming Via QuickStart, Front Panel or PC. Communications Communications Canada cs-03Fcc/cFR 47 Ports Compliance 15 and 68, NFPA 72, ULI 864, ULC 5527-M87 Receivers Signals can be transmitted to either or both of two receivers. Telephone #s Two 24-digit numbers per receiver. Card spaces Requires one card space. Description . The DLD is a ULI/ULC listed dual line Digital Alarm Communicating Transmitter (DACT). it provides two phone line connections for send- ing system messages to a compatible Digital Alarm Communicator Receiver. The DLD supports 4/2 and Contact ID formats. It occupies one card space on the chassis rail. ZR8 Relay Card Option Cord Description The ZR8 provides eight dry-contact relays that can be independently configured as Form A or Form B relays. It occupies one card space on the chassis rail. Wiring +RS- _____ 0000000ØTB. V OR). C112- +113- +R4-. Specifications Style: Form A IN/0) or Form B (N/c) (jumper configurable) Output relays Contact rating: 1 amp © 30 Vdc resistive. Wire size: 18 to 12 AWG (0.75 to 2.5 mm2) Operating Temperature: 32 - 120° F (0-49°C) environment Humidity: 93 %RH, non-condensing Current Standby current: 11 mA requirements Alarm current: 18 ma per active relay Card spaces Requires one card space X485 Class A RS-485 Card and QS432 Port Description Wiring The NT-A, which includes the )<485/ RS-485 card and QS-232/UART port, provides one Class A serbl remote an- nunciator bus for connecting remote annunciator panels. Control panels require the X485 card and OS-232 port, which also serves as a laptop or printer port. The X485 occupies one card space on the chassis rail. The OS- - - 232 port plugs into the panel CPU. 012 Ciii SL30 SL30-1 SL20LSS SL30L LED/Switch Cords Description The SL30 and SL30-1 provide thirty circuits for zone annunciation Each circuit comprises two Ut ut LEDs and a push button switch. The SL30 push button switches are numbered from 1 t 30 and Uil 11L the SL30-1 push button switches are numbered from 31 to 60 The SL20L5S provides 20 cir- cuits for point annunciation and five circuits for . ......... custom control functions. The SL30L provides S 30 circuits for point annunciation. SL20L5S and SL30L circuits are labeled using inserts provided with the cards. : Option Cards. Specifications Wire size 12 to 18 AWG (0.75 to 2.5 mm2) twisted pair (6 twists per foot minimum) Circuit resistance 100 Ohms Circuit capacitance 0.4 iF Operating Temperature: 32 - 120° F 10-49°C) environment Humidity: 93 %RH, noncondensing Current Standby: 60 mA requirements Alarm: 60 mA Cord Spaces Requires one space for the NT-A Option Cords Specifications Temperature: 32 - 120°F (0-49°C) Operating environment Humidity: 93% RH, non-condensing current requirements Standby: 1mA Alarm: 0.75 mA per active LED Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page 7 of 8 GE Ordering Information ecu ri L Security Part . . . Description Ship Wt. Number lb (kg.) Basic Package - Enclosure, SLIC, Power Supply, CPU and Display... U.S. Q51-1-G-1 Single loop system. 1 option card space. Gray enclosure, 115v transformer. 17.0 (7.71) 1888-378-2329 F 866-503-3996 QS1-1-R-1 Single Loop System. loption card space. Red enclosure, 115v transformer. 17.0 17.711 Note: SLIC Card includes One Signature Loop Intelligent Controller for up to 250 devices and one Class A or two Class B NACs. Canada T 519 376 2430 Enclosure Accessories F519 376 7258 OS-i-yR -............................................................................................................ Vandal-resistant cabinet door, gray 3.011.361 Asia QS-1-VR-R Vandal-resistant cabinet door, red 3.0(1.36) T 852 2907 8108 TRIM-1 Trim Kit - gray 5.0(2.27) F 852 2142 5063 Trim Kit - red 'ri 11 __•••_••_-__ ----__•__ .................. Australia T 613 9259 4700 Option Cards F 61 392594799 DLD Dual Line Dialer. Supports 4/2 and Contact ID formats. 1.0 10.451 Europe ZR8 Relay Card. 8 programmable Form A contacts. 1.010.451 13227251120 F3227218613 Display Options Latin America SL30 Annunciator module. Numbered 1 t 30. Two LEDs and one switch per zone. 1.0 (0.45) 13055934301 F 305 593 4300 SL20L5S Annunciator module. 20 circuits for point or zone annunciation, 5 1.0(0.45) circuits for custom functions. Circuits labeled with insert card. www.gesecurity.com/est ,39,L Annunciator module. 30 circuits. Circuits labeled with insert card -1.010,451 051-CPU-1 Single Loop CPU/Display, one annunciator option space 4.0 11.811 ©2006 General Electric Company All Rights Reserved EST-SRA1 Intelligent/Conventional CPU/Display it - switches. 4 square box mount. NT-A RS-485 option card. Required for Class A remote annunciation. Includes 1010451 QuickStart and Signature Series are UART card. Trademarks of GE Security. Q5232 UART option card. Plugs into CPU. Required for PC Programming/ 1.010.451 printer port. Included in NT-A package Remote Annunciator Cabinets (c/w Interface Assembly; Require CPU/Display)... Ordering options QSA-1-S Surface Remote Annunciator Cabinet. Space for one SL30 display card. 4.011.811 - pa ce 4.011.811 (Apply to basic packages and CPU/displays only) QSA-1-5-VR Surface Remote Annunciator Cabinet. Vandal Resistant. Space for one 4.011.811 SL30 display card. Languages QSA-1•FVR Flush Remote Annunciator Cabinet. Vandal Resistant. Space for one 4.011.811 No suffix = American English ------ ....- -------------.-----.--- SL30 display card. --------------------------.---- ........ SP= Spanish (23Ovorll5vl PG = Portuguese 1230v only) . ..... Programming Tools FR = French Canadian (120v only) QS-CU QuickStart Panel Configuration Utility. 1.010.451 OS-Scan QuickStart scanner and programming guide. 2.010.911 Power Supplies Thrgcab1i - . ------------' ------------- Scanner port upload/download cable iiöl' : transformer 2 = 230v transformer 260097 .PrograrnrningcaIe(PC to QSC,Q51.QS4) 1.0(0.45) Colors Accessories G = Grey enclosure 1230v or 1150 PT-IS SystemPrinter - Desktop Style 14.016.351 R = Red enclosure (115v only)Roomone or two 24 A batteries. 22.0 19.981 Examples MFC-A MultiFunction Cabinet 7.0 13.11 QS1-1-G-2-SP = Q51 basic package 0.PARS-2.21s0.lotor Mo..le.3.011.361 with one option card space, grey .RPM ....Reverse Polarity Module. 3.0(1.36) enclosure, 230v transformer, Span- 2-CTM City Tie Module. 1.0 (0.45) ish language. API-8/232ME Alphanumeric Pager Interface. 11.0(5.0) QS1-CPU-FR = QS1 CPU/display, BPS6A 6.5 Amp Booster Power Supply, 110V - ....- ........................................................................13.0 (9) French Canadian BPS10A - ............10.Amp Booster Power Supply, 110 V 13.0(5.9) CDR-3 PSNI Coder Module 1.010.451 imagination at work S Data Sheet 85005-0113 Issue 6 Not to be used for installation purposes. Page 8 of 8 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM 0 OFFICE • USTING SERVICE LISTING No. 7165-1657:207 Page 1 of I CATEGORY: Fire Alarm Control Unit (Commercial) LISTEE: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 Fax (941) 308-8123 Rhonda.Micochero@GE.com DESIGN: Models QSC, -QS1 and -QS4 fire alarm control units, followed by -1 or -2 followed by -BR, -SP, -FR, -PG or no suffix. Local, local with shunt, auxiliary, remote station, releasing service or central station. Power limited. Non-coded, coded, shunt, reverse polarity, DACT, manual, automatic waterfiow, and sprinkler supervisory service. System Components QSC, QS S4 Control Units 7200001-01, -02; 7200004-01, -02 Enclosures 7200005-01, —02 Enclosures PS6 V Power supply ZB16-4 Class B zone card ZA8-2 Class A zone card DLD Dialer (DACT) card ZR8 Relay card NT-A Class A, RS485 communications card QS232, 232 Port for download or printer functions SL30 LED/Switch card with switch 1-30 SL-30-1 LED/Switch card with switch 31-60 SLIC • Signature expansion loop card. QS-1-VR, -R, QS-2-VR, -R Vandal resistant doors SL30L LED Cards 30 Zones SL20L5S LED/Switch Cards 25 Zones RATING: 120/220 VAC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as fire alarm control units for use with separately listed compatible initiating and indicating devices. Units can also generate the temporal code pattern fire alarm signal as required per NFPA 72, 2002 Edition. Referto listee's Installation Instruction Manual for details. This control unit meets the requirements of UL-864, *9th Edition Standard. NOTE: 1. For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. 2. Formerly 7165-1591:207 and 7165-1388:237 *Updated 05-05-09 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JULY 1, 2009 Listing Expires June 30, 2010 Authorized By: FRANCIS MATEO, Program Coordinator Fire Engineering Division EDWARDS SYSTEMS TECHNOLOGY ZW5' INTERNATIONAL ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES Control Relay Modules Model SIGA-CR, SIGA-MCR, SIGA-CRR, SIGA-MCRR Features I Provides one no/nc contact (SIGA-CR/MCR) Form "C" dry relay contact can be used to control external appliances such as door closers, fans, dampers etc. Allows group operation of sounder bases The SIGA-CRR/MCRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop. Plug-in (UIO) or standard 1-gang mount UIO versions allow quick installation where multiple modules are required. The 1-gang mount version is ideal for remote locations that require a single module. Automatic device mapping Signature mod Liles transmit information to the loop controller regarding their circuit locations with respectto other Signature devices on the wire loop. U Electronic Addressing Programmable addresses are downloaded from the loop controller, a PC, orthe SIGA-PRO Signature Program/Service Tool. There are no switches or dials to set. Intelligent device with microprocessor All decisions are made at the module to allow lower communi- cation speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties; twisted or shielded wire is not required. Ground fault detection by address Detects ground faults right down to the device level. U Non-volatile memory Permanently stores serial number, type of device, and job number. Automatically updates historic information including hours of operation, last maintenance date, number of alarms and troubles, and time and date of last alarm. I Diagnostic LEDs Flashing GREEN shows normal polling; flashing RED shows alarm/active state. High ambient temperature operation Install in ambient temperatures up to 120°F (49°C). Designed to ISO 9001 standards All Signature products are manufactured to strict international quality standards to ensure highest reliability. SIGA A If L; Patented MEA SIGA-MCRx (VI) ( Description The Control Relay Module and the Polarity Reversal Relay Module are part of EST's Signature Series system. They are intelligent analog addressable devices available in either plug-in (UIO) versions, or standard 1-gang mountversions. The SIGA-CR/MCR Control Relay Module provides a Form °C" dry relay contact to control external appliances such as door closers, fans, dampers etc. This device does not provide supervision of the state of the relay contact. Instead, the on-board microprocessor ensures that the relay is in the proper ON/OFF state. Upon command from the loop controller, the SIGA-CR/MCR relay activates the normally open or normally-closed contact. The SIGA-CRR/MCRR Polarity Reversal Relay Module provides a Form "C" dry relay contact to power and activate a series of SlGA- AB4 Audible Sounder Bases. Upon command from the Signature loop controller, the SIGA-CRR reverses the polarity of its 24 Vdc output, thus activating all Sounder Bases on the data loop. Standard-mount versions (SIGA-CR and SIGA-CRR) are installed to standard North American 1-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module. Plug-in UIO versions (SIGA.MCR and SlGA-MCRR) are part of the UIO family of plug-in Signature Series modules. Theyfunction identically to the standard mount versions, buttake advantage of the modular flexibility and easy installation that characterizes all UIO modules. Two- and six-module UIO motherboards are available. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in EST enclosures. EST INTERNATIONAL 201 CITY CENTRE DRIVE SUITE 500, MISSISSAUGA, ONTARIO, CANADA 1.513 2T4 PHONE: (001)905-270-1711 - FAX: (001)905-270-9553 • WORLDWIDE WEB: WWW.ESTINTERNATIONAL.COM U.S. SALES: SARASOTA, FL; PHONE 941-739-4638; FAX 941-727-1214 • CANADA SALES: OWEN SOUND, ON; PHONE 519-376-2430; FAX 519-376-7258 Issue 5 Literature Sheet #85001-0239 Page 1 of 8 Not to be used for installation purposes. Installation SIGA-CR and SIGA-CRR: modules mount to North American 2'/2 inch (64 mm) deep 1-gang boxes and 1'/2 inch (38 mm) deep 4 inch square boxes with 1-gang covers. The terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. Compatible Electrical Box Wall Plate. White (1-Gang) 1-1 J Opnon - SeIf-Adhaa -, F,enthI.,e 1) SIGA-MCR and SIGA-MCRR: mountthe UIO motherboard inside a suitable EST enclosure with screws and washers provided. Plug the module into any available position on the motherboard and secure the module to the motherboard with the captive screws. Wiring connections are made to the terminals on the motherboard .(see wiring diagram). UIO motherboard terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. UIO Motherboard 6-32 Self-tapping screws Plug-in (UIO) Captive .,Module Sc— #6 Flat washers Cabinet or electrical enclosure Application The operation of Signature Series control relays is determined by their sub-type code or "Personality Code." Personality Code 8: CONTROL RELAY (SlGA-CR/MCR) - Dry Contact Output. This setting configures the module to provide one Form "C" DRY RELAY CONTACT to control Door Closers, Fans, Dampers, etc. Contact rating is 2.0 amp @24 Vdc; 0.5 amp @ 120 Vac (or 220 Vac for non-UL applications). Personality Code 8 is assigned at thefactory. No user configuration is required. Personality Code 8: POLARITY REVERSAL RELAY MODULE (SlGA-CRR/MCRR). This setting configures the module to reverse the polarity of its 24 Vdc output. Contact rating is 2.0 amp @24 Vdc (pilot duty). Personality Code 8 is assigned at the factory. No user configuration is required. Compatibility The Signature Series modules are compatible only with EST's Signature Loop Controller. Warnings 8-Cautions This module will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist. Testing El- Maintenance The module's automatic self-diagnosis identifies when it is defective and causes a trouble message. The user-friendly maintenance program shows the current state of each module and other pertinent messages. Single modules may be turned off (deactivated) temporarily, from the control panel. Availability of maintenance features is dependent on thefire alarm system used. Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meetthe requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards. Electronic Addressing - The loop controller electronically ad- dresses each module, saving valuable time during system com- missioning. Setting complicated switches or dials is not required. Each module has its own unique serial number stored in its on- board memory. The loop controller identifies each device on the loop and assigns a "soft" address to each serial number. If desired, the modules can be addressed using the SIGA-PRO Signature Program/Service Tool. EST recommends that this module be installed according to latest recognized edition of national and local fire alarm codes. EST INTERNATIONAL Page 2 of 6 Literature Sheet #85001-0239 Issue 5 Typical Wiring Modules will accept #18 AWG (0.75mm2), #16(1.0mm2), #14AWG (1.50mm2) and #12 AWG (2.5mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. Normally- Normally- Open Common Closed TB2_ 876 S •0 Red LED ,-., _____ Green LED (Alarm/Active) ' (Normal) 4321 TB1 _ Notes Refer to Signature Loop Controller Installation Sheet for wiring specifications. SlGA-CR/MCR must be installed within the same room as the device it is controlling. The SlGA-U106R and the SlGA-Ul02R do not come with T814. The SlGA-Ul06 does not come with TB8 through TB 13. A Supervised and power-limited. If the source is nonpower-limited, maintain a space of 1/4 inch from power-limited wiring or use FPL, FPLP, FPLR, or an equivalent in accordance with the National Electrical Code. 7) Maximum #12 AWG (2.5mm2) wire. Mm. #18 (0.75mm2). I DATA IN (+) >-- DATA OUT (+) 1. DATA IN(-) )r DATA From Signature Controller To Next Device or Previous Device SIGA-CR Control Relay Normally Open Common Normally Closed I-- t __ A 1234 Data In + +JP Data Out 4....J Green LED (Normal) Red LED (Active) No connections required for SIGA-MCR. Other modules may require connections. No connections required for SIGA-MCR. Other modules may require connections. SIGA-MCR Control Relay EST INTERNATIONAL Issue 5 Literature Sheet #85001-0239 Page 3 of 6 aignarum Data Data Out Circuit iti < ULJ1JLC Listed + 24Vdcpower —— supply — or 124 Jt I II • • S For normal operation I I SIGA-CTI For General Fire I i II Alarm Operation I I II 0 0 AA Data out* Signature Data e 2 Circuit Data In Grown LED (Normal) •_/' ,f Red LED (Active) I 1 2 3 4 1 23 4 A Optional slGA-MCRR or SIGA-MCR to ___ disablingidisconnecling No connecitons required for SIGA-MCRR. an audible base. Other modules may require connections. Green LED (Normal) Red LED (Active) No connections required for SIOA-MCRR. Other modules may require connections. --f- StGA.UtO(R) series motherboard No connections required for T1314 I SIGA-MC RR. Other modules may require connections. Typical Wiring Modules will accept #18 AWG (0.75mm2), #16 (1 .0mm2), #14 AWG (1 .50mm2) and #12 AWG (2.50mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog sheet for detailed wiring requirement specifications. SlGA-AB4 SIGA-AB4 SlGA-AB4 Audible Base Audible Base Audible Base Signature + Controller _ 1j1 J2 1ji .J '2 1 6254A-003 II EOL Relay A1Ij1 LS14 a 0 slGA-cT1 SIGA-CRR 0 0 Listed 24 VDC I + Nominal Power Supply .. . I • S SGA-CR lGA-CF 00, 00 Optional SlGA-CR for disabling/disconnecting sounder base SIGA-MCRR S SIGA-CRR Schematic Power F Poser Out P2bhp Resernea Gtb0tOd 75 E I SlGA-MCRR Schematic Power 1. Power Out Polarity reverses — + when octluated. Audible Bases — JW1 .tW2 6254A.003 EOL Relay - required for supevluion IA . so utoo 0 Notes Al Refer to the Signature controller installation sheet for wiring. One Pair of Wires (24 Vdc power). One Pair of Wires (Signature Data). Single Wire (24 Vdc power). The SlGA-UI06R and the SlGA.U102R do not come with TB14. The SlGA-Ul06 does not come with TB8 through TB13. Supervised and power-limited. If the source is noripower-limited, maintain a space of 1/4inchfrom power-limited wiring cruse FPL, FPLP, FPLR,oran equivalent in accordance with the National Electrical Code. 9 Maximum #12AWG (2.5mm2) wire; Minimum #18 AWG (0.75 mm2 ). 10 End-of-Line Relay must monitorand report power supplytrouble to control panel. 11 Class B Data wiring may be "T .tapped." EST INTERNATIONAL Page 4 of 6 Literature Sheet #85001-0239 Issue 5 Specifications Catalog Number SIGA-CR I SIGA-MCR I SIGA-CRR I SIGA-MCRR Description Control Relay Polarity Reversal Relay Type Code Personality Code 8 (Factory Set) Address Requirements Uses 1 Module Address Operating Current Standby = 100pA Activated 100pA\ Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) Form "C" Relay Type and Rating 24 VDC = 2 amps (pilot duty) 120 Vac = 0.5 amps 220 Vac (non-UL) = 0.5 amps North American 21/2 inch North American 21/2 inch (64 mm) deep 1-gang boxes Plugs into (64 mm) deep 1-gang boxes Plugs into Mounting and 11/2 inch (38 mm) deep UI0211, U106R or U106 and 11/2 inch (38 mm) deep 010213, U106R or U106 4 inch square boxes Motherboards 4 inch square boxes. Motherboards with 1-gang covers with 1-gang covers Construction 8 Finish High Impact Engineering Polymer Storage and Operating Operating Temperature: 32°F to 120°F (0°C to 49°C) Environment Storage Temperature: -4°F to 140°F (-20°C to 60°C) Humidity: 0 to 93% RH LED Operation On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm/active Compatibility Use With: Signature Loop Controller Agency Listings UL, ULC (See Ordering Table), CSFM, MEA Ordering Information Catalog Number Description Ship Weight. lbs (kg) SIGA-CR Control Relay Module (Standard Mount) - UL/ULC Listed 0.4 (0.15) SIGA-MCR Control Relay Module (010 Mount) - UL Listed 0.18 (0.08) SlGA-CRR Polarity Reversal Relay Module (Standard Mount) - UL/ULC Listed 0.4 (0.15) SIGA-MCRR Polarity Reversal Relay Module (UIO Mount) - UL Listed 0.18 (0.08) Related Equipment 27193-21 Surface Mount Box - Red, 1-gang 1 (0.6) 27193-26 Surface Mount Box - White, 1-gang 1(0.6) SIGA-MB4 Module Mounting Bracket for installing two 1-gang modules in a single North American 4-inch square box. . .5 (.3) SIGA-0102R Universal Input-Output Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15) SIGA-U106R Universal Input-Output Module Board w/Riser inputs - Six Module Positions 0.62 (0.28) SIGA-0106 juniversal Input-Output Module Board - Six Module Positions 0.56 (0.25) EST INTERNATIONAL Issue 5 Literature Sheet #85001-0239 Page of 6 0 Description (Signature Overview) The Signature Series intelligent analog-addressable system from Edwards Systems Technology is an entire family of multi-sensor detectors and mounting bases, multiple-function input and output modules, network and non-network control panels, and user- friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals. An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm. The microprocessor in each Signature device provides four additional benefits - Self-diagnos- tics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Self-diagnostics and History Log - Each Signature Series device constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in its non-volatile memory. This information is accessible for review any time at the control panel, PC, or using the SlGA-PRO Signature Program/Service Tool. The information stored in device memory includes: Device serial number, address, and type Date of manufacture, hours of operation, and last maintenance date Number of recorded alarms and troubles2 Time and date of last alarm' Most recent trouble code logged by the detector - 32 possible trouble codes may be used to diagnose faults. Automatic Device Mapping-The Signature Data Controller (SDC) .learns where each device's serial number address is installed relative to other devices on the circuit. The SDC keeps a map of all Signature Series devices connected to it. The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or"as-built" drawing information showing branch wiring (r-taps), device types and their address are stored on disk for printing hard copy. This takes the mystery outof the installation. The preparation of as-built drawings is fast and efficient. Device mapping allows the Signature Data Controller to discover: Unexpected additional device addresses Missing device addresses Changes to the wiring in the circuit. Most Signature modules use a personality code selected by the installer to determine their actual function. Personality codes are downloaded from the SDC during system configuration and are indicated during device mapping. Standalone Operation - A decentralized alarm decision by the device is guaranteed. Onboard intelligence permits the device to operate in standalone (degrade) mode. If Signature loop controller CPU communications fail for more than four seconds, all devices on that circuit go into standalone mode. The circuit acts like a conventional alarm receiving circuit. Each Signature device on the circuit continues to collect and analyze information from its slave devices. When connected to a panel utilizing standalone operation, modules with their "personality" set as alarm devices ((DC) will alarm should their slave alarm-initiating device activate. Fast Stable Communication- Built-in intelligence means less information needs to be sent between the device and the Signature Data Controller (SDC). Other than regular supervisory polling response, Signature devices only need to communicate with the SDC when they have something new to report. This provides very fast control panel response and allows a lower baud rate (speed) to be used for communication on the circuit. The lower baud rate offers several advantages including: Less sensitivity to circuit wire characteristics Less sensitivity to noise glitches on the cable Less emitted noise from the data wiring Twisted or shielded wiring is not required. Diagnostic LEDs -Twin LEDs on most Signature devices provide visual indication of normal and alarm-active conditions. A flashing green LED shows normal system polling. A flashing red LED means the module is in alarm-active state. Both LEDs on steady indicates alarm-active state - standalone mode. Testing & Maintenance -Automatic self-diagnosis identifies when a Signature device is defective and causes a trouble message. The user-friendly maintenance program shows the current state of each device and other pertinent information. Single devices may be turned off temporarily, from the control panel. Scheduled mainte- nance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/ULC 536 standards. Quality and Reliability- EST Signature devices are manufactured in North America to strict international (SO 9001 standards. All electron- ics utilize surface mount technology (SMT) for smaller size and greater immunity to RF noise. A conformal coating is used for humidity and corrosion resistance. 1 EST3 V.2 only. 2 Retrievable with SIGA-PRO programming tool. EST INTERNATIONAL It is our intention to keep the product information current and accurate. We can not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact EST International, C 1999 EST Printed in Canada Page 6 of 6 Literature Sheet #85001-0238 Issue 5 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. CATEGORY: LISTEE: 7300-1657:121 Misc. Devices/Control Unit Accessories GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 Fax (94)) 308-8123 Rhonda.micochero@ge.com / Page 1 of 1 DESIGN: RATING: INSTALLATION: MARKING: APPROVAL: NOTE: Models SJGA-CC1, SIGA-CC2 SIGA-CTI lGA-CT2, SlGA-CR, SIGA-CRR, SIGA-UM, SlGA-MM1, SIGA-WTM, SIGA- - DM, SIGA-MAB, SIGA-MCT2, SIGA-MCC1, SlGA-MCC2, SIGA-MCR and SIGA-MCRR remote transponders. Models SIGA-M30 and SlGA-AA50 audio amplifiers. Models SIGA-APS and SlGA-APS-220 power supplies. Models SIGA-MB4, SIGA-MP1, SIGA-MP2 and SIGA-MP2L mounting plates. Models SIGA-U102R, SlGA-U106 and SlGA-UI06R motherboards. Model CS-SIGA-CC1P releasing module. Models SIGA-CCI S and SIGA-MCCI S Auto-Sync Output Modules.. Models MFC-A and MFC-AD Enclosures. Model SlGA-CR2 Control Relay Module *Model SlGA-CT1HT; Signature Series High Temperature Single Input Module Refer to listee's data sheet for additional detailed product description and operational consideration. 15.2 - 19.95 VDC In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model number, electrical rating, and UL label. Listed as control unit accessories for use with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. Formerly 7300-1591:121 and 7300-1388:178 *Rev. 12-09-2009 fm II This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: DECEMBER 11, 2009 Authorized By: FRANCIS MATEO, Program Coordinator Fire Engineering Division Listing Expires June 30, 2710 I • COWSYOS SYSTEMS TECHNOLOGY Part of GE Security NOTIFICATION APPLIANCES CompotibiIit9 1 Quickstart I FiroShield I EST2 f EST3 Field Configurable Horns and Strobes G Series Features Unique low-profile design - The most compact U L-197 1/ULC-S526 listed strobe available - Ultra-slim -protrudes less than one inch from the wall - Attractive appearance - No visible mounting screws Four field-configurable options in one device - Select 15, 30, 75, or 110 cd strobe output - Select high (default) or low dB horn output - Select temporal (default) or steady horn output - Select public mode flash rate (default) or private mode temporal flash Unparalleled performance - Industry's most even light distribution - Meets tough synchronizing standards for strobes - Single microprocessor controls both horn and strobe - Low current draw minimizes system overhead - Independent horn control over a single pair of wires - Highly regulated in-rush current - Multiple frequency tone improveswa)l penetration - Industry's first temporal strobe output Description The Genesis line of signals are among the smallest, most compact audible-visible emergency signaling devices in the world. About the size of a deck of playing cards, these devices are designed to blend with any decor. Thanks to patented breakthrough technology, GE Security Genesis strobes do not require bulky specular reflectors and lenses. Instead, an exclusive cavity design conditions light to produce a highly controlled distribution pattern. Significant development efforts employing this new technology have given rise to a new benchmark in strobe performance - FullLight technology. FullLight strobe technology produces a smooth light distribution pattern without the spikes and voids characteristic of specular reflectors. This Selectable IS, 30,75, 76 orll0cdstrobe' High, r low dO hofl' I - - Listings - - pending One or more patents pending. ensures the entire coverage area receives consistent illumination from the strobe flash. As a result, Genesis strobes with FullLight technology go well beyond the minimum UL-required "T" pattern, significantly exceeding UL-1971 and ULC-5526 light distribution requirements. Although all Genesis strobes are self-synchronizing, when installed with an optional synchronization module, strobe flashes from devices on the some circuit synchronize to within 10 milliseconds of each other indefinitely. This exceeds the two-hour minimum specified in the UL standards. Only one synchronization module is required per circuit. Genesis strobes and horn-strobes offer 15 to 110 candela output, which is selectable with a conveniently-located switch on the side of the device. The candela output setting remains clearly visible even after final installation, yet it stays locked in place to prevent unauthorized tampering. Genesis horn output reaches as high as 99 dB and features a unique multiple frequency tone that results in excellent wall penetration and an unmistakable warning of danger. Horns may be configured for either coded or non-coded signal circuits. They can also be set for low dB output with ojumper cut that reduces horn output by about 5 dB. Genesis signals feature textured housings in architecturally neutral white ortraditional fire red. An ingenious iconographic symbol indicates the purpose of the device. This universal symbol is code-compliant and is easily recognized by all building occupants regardless of what language they speak. Models with "FIRE" markings are also available. I Easy to install - Fits standard 1-gang electrical boxes - no trim plate needed - Optional trim plate accommodates oversized openings - Pre-assembled with captive hardware - #12AWG terminals -ideal for long runs or existing wiring 0 imagination at work www.gesecurity.com 8985 TOWN CENTER PARKWAY, BRADENTON, FL 34202 PHONE: 888-378-2329 • FAX: 866-503-3996 CANADA SALES: OWEN SOUND, ON 519-376-2430; FAX 519-376-7258 INTERNATIONAL SALES: 10011905-270-1711; FAX 001)905-270-9553 Literature Sheet #85001-0573 issue 3 Not to be used for installation purposes. Page 1 of 6 NOT TO BE USED FOR INSPALLAnON PURPOSES. Application Genesis strobes are UL 1971-listed for use indoors as wall-mounted public-mode notification appliances for the hearing impaired. Prevailing codes require strobes to be used where ambient noise conditions exceed 105 dBA (87dBA in Canada), where occupants use hearing protection, and in areas of public accommodation as defined in the Americans with Disabilities Act (see application notes - USA). Combination horn-strobe signals must be installed in accordance with guidelines established for strobe devices. Strobes The following guidelines are based on ANSI/NFPA 72 National Fire Alarm Code (1999). When applied and installed in accordance with that code, GE Security strobes meet or exceed the illumination produced by the ADA-specified 75 candela (cd) strobe at 50 feet.* Non-Sleeping Rooms EST wall mounted strobes* Up to 20'x 20'(6.1 m 6.1 m) One 15 cd strobe Up to 30'x 30'(9.1 mx 9.1 m) One 30 cd or two 15 cd strobes Up to 40' x 40(12.2 mx 12.2 m) One 75 cd or two 30 cd strobes Up to 50 x 50' (15.2 m 15.2 ml One 110 cd or two 75 cd strobes Corridors Any length. Maximum width: 20'(6.1m). 15 cd strobes spaced at 100' (30.5 m) max. Strobes must be placed within 15'(4.5m) of each end of the corridor. * ADA suggests using 75 cd strobes throughout an area, with spacing that never exceeds 50 If from the strobe to any point in the protected space. Non-Sleeping Rooms and Corridors: GE Security strobes rated at less than 110 cd per UL 1971 are intended for use in non-sleeping areas only. Install with the bottom of the device at least 80 inches 12.0 ml and no more than 96 inches 12.1; ml above the finished floor. No point in any space (including corridors) required to have strobes should be more than 50 feet (15.2 ml from the signal (in the horizontal plane). For detailed spacing requirements, consult The Handbook of Visible Notification Appliances for Fire Alarm Applications published by GE Security Press, or contact your local GE Security representative. Sleeping rooms: GE Security 110 cd strobes are intended for use in sleeping rooms and should be installed along with a smoke detector. It must be wall mounted at least 80" 12.03 ml above floor level, but no closer than 24" (610 mm) to the ceiling. The distance from the strobe to the pillow must not exceed 1614.8 ml. Sleeping Rooms ST wall mounted strobe Any size 110 cd within 16 feet of pillow Horns The suggested sound pressure level for each signaling zone used with alert or alarm signals is at least 15 dB above the average ambient sound level, or 5 d above the maximum sound level having a duration of at least 60 seconds, whichever is greater, measured 5 feet 11.5 ml above the floor. The average ambient sound level is, A-weighted sound pressure measured over a 24-hour period. Doubling the distance from the signal to the ear will theoretically result in a 6 dB reduction of the received sound pressure level. The actual effect depends on the acoustic properties of materials in the space. A 3 dBA difference represents a barely noticeable change in volume. Application Notes - USA Audible signals in the public mode should never have a sound level less than 75 dBA at 1013 ml per NFPA 72. Signals cannot exceed 120 dBA per ADA and NFPA 72 at the minimum hearing distance to audible appliance. Strobe and combination horn/strobe devices should be installed with the bottom of the device at least 80 inches (2.0 ml and no more than 96 inches (2.4 ml above the finished floor. Horns should be installed with their tops not less than 6 inches (152 mm) below the ceiling and not less than 90 inches 12.3 ml above the finished floor. Strobes must be used to supplement audible signals wherever the average ambient sound level exceeds 105 dBA. Combination audible/ visual signals must be installed in accordance with NFPA guidelines established for strobes. ADA requires visible signals in the following areas: rest rooms, meeting rooms, and other common use areas. sleeping rooms intended for use by persons with hearing impairment (in accordance with Title 1 o ADA). work areas used by a person with a hearing impairment (per Title 1 of ADA). Application Notes - Canada IBosed in part on 1995 Canada National Building Code) The fire alarm signal sound pressure level shall not exceed 110 dBA in any normally occupied area. The sound pressure level from an audible signal in a floor area used for occupancies other than residential occupancies shall not be less than 10 dBA above ambient levels, and never less than 65 dBA. In sleeping rooms the sound pressure level from an audible signal shall not be less than 75 dBA when any interven- ing doors between the device and the sleeping room are closed. Audible signal devices shall be installed not less than 1.8 m to the center of the device above the floor (per CAN/ULC S524). The fire alarm audible signal shall be supplemented by fire alarm strobes in any floor area where the ambient noise level exceeds 87 dBA, or where the occupants of the floor area use ear protective devices, are located within on audiometric booth, or are located within sound insulating enclosures. This also applies to assembly occupancies in which music and other sounds associated with performances could exceed 100 dBA Strobes shall be installed in a building so that the flash from one device is visible throughout the floor area or portion thereof in which they are installed. For maximum safety, GE Security recommends that strobes be installed as per the guidelines shown here under Strobe Spacing. C www.gesecurity.com Page 2 of 6 Literature Sheet #85001-0573 Issue 3 S Genesis Horn/Strobe with Optional trim plate next device end of line device Polarity alarm FA NOT TO BE USED TOP. INS TALLAflON PURPOSES. E Installation Genesis horns and strobes mount to any standard one-gang surface or flush electrical box. Matching optional trim plates are used to cover oversized openings and can accommodate one-gang, two-gang, four- inch square, or octagonal boxes, and European 100 mm square. All Genesis signals come pre-assembled with captive mounting screws for easy installation. Two tabs at the top of the signal unlock the cover to reveal the mounting hardware. The shallow depth of Genesis devices leaves ample room behind the signal for extra wiring. Once installed with the cover in place, no mounting screws are visible. Field Configuration Temporal horn and horn-strobe models are factory set to sound in a three-pulse temporal pattern. Units may be config- ured for use with coded systems by cutting ajumper on the circuit board. This results in a steady output that can be turned on and off (coded) as the system applies and removes power to the signal circuit. A Genesis Signal Master is required when horn-strobe models are configured for coded systems. Non- temporal, horn-only models sound a steady tone. Genesis strobes and horn-strobes are shipped from the factory ready for use as UL 1971 compliant signals for public mode operation. These signals may be configured for temporal flash by cutting ajumper on the circuit board. This battery-saving feature is intended for private mode signaling only. Genesis strobes and horn-strobes may be set for 15, 30, 75, or 110 candela output The output setting is changed by simply opening the device and sliding the switch to the desired setting. The device does not have to be removed to change the output setting. The setting remains visible through a small window on the side of the device after the cover is closed. Horns and horn-strobes are factory set for high dB output Low dB output may be selected by cutting ajumper on the circuit board. This reduces the output by about 5dB. Wiring Field wiring terminals accommodate #18 to #12 AWG (0.75 mm2 to 2.5 mm') wiring. Horns, strobes, and combination horn-strobes are interconnected with a single pair of wires as shown below. Note: Strobes must have continuous voltage. Pi www.gesecurity.com Issue 3 Literature Sheet #85001-0573 Page 3 of 6 NOT TO REUSE U FOR 114STALLATON PURPOSES. Specifications Housing Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Lens Optical grade polycarbonate (clear) Mounting Flush mount: 21/2 inch (64 mm) deep one-gang box (indoor wait mount only) Surface mount: EST model 27193 surface mount box, wiremold box, or equivalent surface-mount box With optional trim plate: One-gang, two-gang, four-inch square, octagonal, or European single-gang box Wire connections Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm2 to 2.5 mm2) wire size Operating environment Indoor only: 32-120°F (0-49°C) ambient temperature. 93% relative humidity Agency UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CSFM, CE, FCC, (MEA, FM pending). listings/approvals (All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.) Dimensions (HxWxD) Signal: 4-1/2 x 2-3/4' x 13/16° (113 mm x 68 mm x 21 mm) Trimplate: 5" (127 mm); Height - 5-7/8 (149 mm); Depth - ½" (13 mm) G1-HD series temporal-tone horns: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded when horn set to steady tone) Operating voltage p g g G1-HDVM series temporal-tone horn-strobes: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded (audible NAC only) when used with optional G1M Genesis Signal Master) G1-VM series strobes: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR G1-P series steady-tone horns: coded or non-coded, filtered 20-31 Vdc or unfiltered 20-27 Vfwr Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output G1-VM strobes and G1-HDVM series temporal-tone horn-strobes: one flash per second synchronized with Strobe flash rate optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) Temporal setting (private mode only): synchronized to temporal output of horns on same circuit Compatible synchronization G1M, G1M-RM, SIGA-CC1S, SIGA-MCC1S G1-HD temporal-tone horns and G1-HDVM series temporal-tone horn-strobes: temporal rate synchronized Horn pulse rate p with optional G1M Genesis Signal Master indefinitely within 10 milliseconds (or self-synchronized within 200 milliseconds over thirty minutes on a common circuit without G1M Genesis Signal Master) G1-P steady-tone horns: continuous, steady tone only Temporal audible pattern ½ sec ON, ½ sec OFF, ½ sec ON, ½ sec OFF, ½ sec ON, 11/2 sec OFF, then repeat cycle dBA output Temporal Horns. Horn-strobes (G1-HD. G1-HDVM series) - Hiah dB Settina UL464 Average Peak Temporal I Steady Temporal/Steady Temporal/Steady 16 Vdc— 81.4 85.5 91.4 94.2 24 Vdc 84.4 88.6 94.5 97.6 33 Vdc 86.3 90.4 96.9 99.5 Temporal Horns. Horn-strobes 1131-HD. G1.HDVM sane 1 - Low d8 Settinci UL464 Average Peak Temporal I Steady Temporal/Steady Temporal/Steady 16 Vdc 76.0 80.1 86.3 89.2 24 Vdc 79.4 83.5 89.8 92.5 33 Vdc 82.1 86.5 92.5 95.3 Steady Tone Horns (GI-P series) UL464 Average Peak 16 Vdc 77 90 91 24 Vdc 77 90 91 33 Vdc 77 90 91 Notes All values shown are d8A measured at 10 feet 13.01ml. UL464 values measured in reverberation room, Average and Peak values are measured in anechoic chamber, Average Sound Output (d BA) (High dB setting, onechoic, 24V, measured at loft) 1, ,• Light output - (effective cd) Percent of UL rating versus angle \\ www.gesecurity.com Page 4 of 6 Literature Sheet #85001-0573 Issue 3 Measured by EST I RMS __TIM I 24 Vdc 10 10 24 Vdc 11 11 31 Vdc 12 12 20 Vfwr 9 8 24 Vfwr 10 9 NOT TO BE USED FOR INSTALLATION PURPOSES. Current Draw Strobes, Horn-Strobes Multi-cd Wall Strobes (G1-VM) LIL Namp.nletp Rqtinn (Ill 15171 Fffertive Mev 2nnA1 15 c 30 c 75 c 110 c RMS RMS RMS RMS 16 Vdc 103 141 255 311 16 Vfwr 125 179 346 392 lvaical Current (Measured by EST) 15 c 30 c 75 c 110 Cd RMS Mean RMS Mean RMS Mean RMS Mean 16 Vdc 85 79 127 124 245 243 285 283 20 Vdc 71 66 98 96 188 186 240 238 24 Vdc 59 55 82 80 152 150 191 190 33 Vdc 46 44 64 63 112 111 137 136 16 Vfwr 119 64 1 169 97 1 332 203 376 1 240 20 Vfwr 103 51 143 76 253 150 331 198 24 Vfwr 94 44 129 65 218 121 262 152 33 Vfwr 87 37 112 52 179 89 205 106 Multi-cd Wall Temporal Horn-strobes (G1-HDVM) - High dB Setting UL Nameolate Retina (UL1971 Effective May 20041 15 c 30 c 75 c 110 Cd RMS RMS RMS RMS 281 337 397 443 15 c 30 c 75 c 110 Cd RMS Mean RMS Mean RMS Mean RMS Mean 16 Vdc 102 89 135 129 246 242 309 305 20 Vdc 88 77 109 104 193 190 248 243 24 Vdc 81 71 94 90 161 158 203 200 33 Vdc 74 64 72 74 124 121 154 151 16 Vfwr 144 77 182 106 352 212 393 249 20 Vfwr 141 68 162 87 274 158 362 210 24Vtwr 136 65 152 76 235 133 282 165 33 Vfwr 125 54 144 65 201 101 232 123 Multi-cd Wall Temporal Horn-strobes (G1-HDVM) - Low dB Setting UL Nameolate Retina WI-1971. Effective May 20041 15 c 30 c 75 c 110 c RMS RMS RMS RMS 274 330 383 429 15 c 30 c 75 c 110 c RMS Mean RMS Mean RMS Mean RMS Mean 16 Vdc 96 84 130 124 243 240 302 297 20 Vdc 79 70 104 99 189 186 241 237 24 Vdc 68 61 88 84 156 154 197 193 33 Vdc 1 56 52 71 68 118 116 146 143 16 Vfwr 128 69 180 104 344 204 389 244 20 Vfwr 118 60 157 84 266 156 343 200 24 Vfwr 113 54 144 74 230 128 279 161 33 Vfwr 112 48 137 64 197 99 226 117 Horns Wall Temporal Horns (G1-HD) UL Name.nlete Retina 1UL464 Effective May 20041 High dB Low dB RMS RMS 16 Vdc 26 19 24 Vdc 36 27 33 Vdc 41 33 16 Vfwr 51 37 24 Vfwr 69 52 33 Vfwr 76 70 Tvoical Current (Measured by EST) High dB Low dB RMS Mean RMS Mean 16 Vdc 22 17 17 14 20 Vdc 24 19 19 16 24 Vdc 27 21 22 18 33 Vdc 32 25 26 22 16 Vfwr 34 15 30 14 20 Vfwr 1 40 19 34 16 24 Vfwr 45 21 38 18 33 Vfwr 52 24 47 22 Wall Horns (G1-P) UL Nameplate Rating F RMS Mean 16 Vdc 9 7 24 Vdc 11 9 33 Vdc 13 11 16 Vfwr 9 5 24 Vfwr 10 7 33 Vfwr 11 1 9 Notes and Comments Current values are shown in mA. UL Nameplate Rating can vary from Typical Current due to measurement methods and instruments used. GE Security recommends using the Typical Current for system design including NAC and Power Supply loading and voltage drop calculations. Use the Vdc RMS current ratings for filtered power supply and battery AN calculations, Use the Vfwr RMS current ratings for unfiltered power supply calculations. S. Fuses, circuit breakers and other overcurrent protection devices are typically rated for current in RMS values. Most of these devices operate based upon the heating affect of the current flowing through the device. The RMS current (not the mean current) determines the heating affect and therefore, the trip and hold threshold for those devices. 6. Our industry has used 'mean' currents over the years. However, UL will direct the industry to use the 2004 RMS values in the future. S 129 167 176 230 16 Vdc 16 Vfwr Tvnical Current (Measured by EST( 122 160 162 216 16 Vdc 16 Vfwr Tvoical Current (Measured by EST( www.gesecurity.com Issue 3 Literature Sheet #85001-0573 Page 5 of 6 JO'F TO RE USED FOR NsrALATION PURPOSES. Ordering Information Catalog Number Description Ship Wt. lbs (kg) White Finish Red Finish G1-HDVM G1R-HDVM Genesis Horn-Strobe (selectable 15, 30, 75, or 110 cd output, selectable high/low dB output) G1-VM G1R-VM Genesis Strobe (selectable 15, 30, 75, or 110 cd output) G1-HD G1R-HD Genesis Temporal Horn (selectable high/low dB output) G1-P G1R-P Genesis Steady Horn (not compatible with Genesis Signal Master) G1FHDVM G1RF-HDVM Genesis Horn-Strobe (selectable 15, 30, 75, or 110 cd output, selectable high/low dB output) —with FIRE marking 0.25 (0:11) G1F-VM G1RF-VM Genesis Strobe (selectable 15, 30, 75, or 110 cd output) —with 'FIRE marking G1F-HO G1RF-HD Genesis Temporal Horn (selectable high/low dB output)—with 'FIRE marking G1F-P G1RF-P Genesis Steady Horn with "FIRE marking (not compatible with Genesis Signal Master) Mounting Accessories G1T GiRT Genesis Trim Plate (for two-gang or 4" square boxes) 0.15 (0.7) G1T-FIRE GiRT-FIRE Genesis Trim Plate (for two-gang or 4 square boxes) with 'FIRE" markings 0.15 (0.7) 27193-16 27193-11 One-gang surface mount box 1(0.4) Synchronization Modules G1M Genesis Signal Master - Snap-on Mount 0.2(0.1) G1M-RM Genesis —_ Remote -gang) _Signal _Master _Mount _(1 SIGA-CC1S Intelligent Synchronization Output Module (2-gang) 0.5 (0.23) SIGA-MCC1S Intelligent Synchronization Output Module (Plug-in UIO) 0.18 (0.08) Genesis Horn-Strobes may be ordered in red or white, with orwithout FIRE marking. C WARNING: These devices will not operate without electrical power. As fires frequently cause power interruptions, we suggest you discuss further safeguards with your local fire protection specialist. These visible signal appliances' flash intensity may not be adequate to alert or awaken occupants in the protected area. Research indicates that the intensity of strobe needed to awaken 90% of sleeping persons is approximately 100 cd. GE Security recommends that strobes in sleeping rooms be 110 cd minimum. Genesis and FullLight Strobe Technology are trademarks of GE Security, Inc. www.gesecurity.com It is our intention to keep the product information current and accurate. We con not cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet, contact GE Security. 10 2005 GE security Printed in uSA Page 6 of 6 Literature Sheet #85001-0573 issue 3 S S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-1657202 Page 1 of I CATEGORY: Fire Alarm Devices for the Hearing Impaired LISTEE: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 FAX (941) 308-8123 DESIGN: Models "EST" G1-HV15, -HV30, -HV60, -HV-75, G1-HOV1 5, -HOV30, -HOV60, -HOW5, -HOVIIO, GIF-HOV15, -HOV30, -HOV60, -HQL7.5-- -HOV1 10, GIRF-HOV15, -HOV30, -HOV60, -HOW5, -HOVI 1 c(G1-HDV)j, GI R-H DVM, GI F-HDVM, GI RF-HDVM, GC-HDVM, GC-HDVMH, GCF-HD, -HDVM, GCF- HDVMH, GI-HDV1575, Gi R-HDV1 575, G1 F-HDVI 575, and GI RF-HDVI 575 horn/strobes with or without suffixes -R and -F. Models with HO as part of the model number are a high audible output version of the standard output model. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: , Electrical: 24-30 Vdc 16-33 VdcNfwr - Models GI-HDVM, GIR-HDVM, G1F-HDVM, G1RF- HDVM, GC-HDVM, GC-HDVMH, GCF-HDVM, *GCFR..HDVM GCF- HDVMH, GI-HDV1575, G1R-HDV1575, GIF-HDV1575, G1RF-HDV1575 Candela: 15cd, 30cd, 60cd, 75cd, 110cd 15-95 multi-cd - Models GC-HDVM, GCF-HDVM, *GCFR..HVDM 95-177 multi-cd-Models GC-H DVM H, GCF-HDVMH 15/75cd -Models G1-HDV1575, G 1 R-HDV1575, Gi F-H0V1575, GI RF-HDV1575 INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical/candela rating, and UL label. APPROVAL: Listed as horns and horn/strobe lights for use with separately listed compatible fire alarm control units. Suitable for use with Audible Signal Appliances (CSFM Listing No. 7135- 1657:230). For indoor use and wall mount only. Models GC-HDVM, *GCFR..HDVM and GCF-HDVM for ceiling mount only. Refer to listee's Installation Instruction Manual for details. These units can generate a distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. NOTE: Formerly 7125-1591:202 *112706kv This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results tffi; and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or ;'+ recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JULY 1, 2009 Listing Expires June 30, 2010 Authorized By: FRANCIS MATEO, Program Coordinator Fire Engineering Division E~M~ 'D EDWAROS SYSTEMS TECHNOLOGY Part of GE Security ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES S Releasing Module SIGA-REL Features Ideal for sprinkler, pre-action and deluge systems Suitable a wide range of sprinkler applications and extinguishing agents such as CO2 and Halon. Built-in timers Selectable durations for abort, manual, and automatic delays. Fourabortmodes Field-configurable abort routines determine howthe timers operate when the abort function is initiated. Supervised circuitry you can rely on Two Class B release circuits and two pre-release circuits provided. U Manual operation keeps ultimate control in plain view The SIGA-REL features a manual release input circuit as well as a manual abort inputcircuit. U Fully automated response leaves nothing to chance This module's Form C relay is ideal for room preparation routines. U Unprecedented compatibility The SIGA-REL is compatible with any solenoid that is bot UL-listed and FM-approved. U Automatic device mapping simplifies installation Signature modules transmit directly to the loop controller their circuit locations with respect to other Signature devices on the wire loop. Electronic addressing cuts setup time Programmable addresses are easily downloaded from the loop controller, a PC, or the SIGA-PRO Signature Program/Service Tool. There are no address switches or dials to set. U On-board intelligence ensures rock-solid performance All decisions are made at the module to allow lower communication speed with substantially improved control panel response time and less sensitivity to line noise and loop wiring properties. Twisted or shielded wire is not required. Non-volatile memory maintains a wealth of information Permanently stores serial number, type of device, and job number. It automatically updates history information including hou:s of opera- tion, last maintenance date, number of alarms and troubles, and time and date of last alarm. U High ambienttemperature operation Installable in ambient temperatures up to 120°F 1490Cl. U Designed in accordance with ISO 9001 quality standards All Signature products are manufactured in accordance with strict international quality standards to ensure highest reliability. Description The SIGA-REL is an analog addressable module that communicates directly with the fire alarm panel Signature loop controller. The SIGA-REL controls sprinkler, pre-action and deluge systems, and may also be used to release extinguishing agents such as CO2, Halon, or foam. The module is easily configured in the field and offers a wide range of options that ensure dependable service, while preventing the unneces- sary release of extinguishing agent. In addition to being an intelligent network component, the SIGA-REL interfaces with a number of conventional devices. These provide manual actuation of abort, release, and service disconnect functions' Together with the SIGA-REL, they comprise a complete fire suppression package. There is no need for a separate releasing panel because the SIGA-REL takes full advantage of the existing control panel communica- tions infrastructure. This ensures low-cost installations with all the benefits of Signature Series analog initiation and control. Seven on-board circuits provide added flexibility. Each SIGA-REL hosts: Two supervised Class B release circuits Two supervised Class B pre-release NACs One supervised Class B manual release input circuit (latching) One supervised Class B abort circuit for normally-open abort switch (non-latching) One first alarm output relay (Form C contact) The SIGA-REL also includes a series of built-in timers that determine the duration of abort routines and release sequences. These timers are easily configured in the field and provide a highly flexible range of options. 0 imagination at work www.gesecurity.com 8985 TOWN CENTER PARKWAY, BRADENTON, FL 34202 PHONE: 888-378-2329 • FAX: 866-503-3996 CANADA SALES: OWEN SOUND, ON 519-376-2430; FAX 519-376-7258 INTERNATIONAL SALES: 10011905-270-1711; FAX 10011905-270-9553 Literature Sheet #85001-0531 Issue 4 Not to be used for installation purposes. Pages of 8 S ------------------------------ Fire alarm control panel Signature Series smoke detectors Signature Series modules [II]z1 horn circuit Strobe circuit [] Service Disconnect Station A7 Manual Abort Station Manual Release Station FirstAiami Output Relay Releasing Module RELAJ- Release Circuit I RELij- I Release Circuit 2 Pl01 'TO BEUS to FOR 1 NsrALLArios PURPOSES. • Application Understanding fire suppression Fire suppression today is an important part of a growing number of life safety installations. With an ever-increasing reliance on mission-critical computer systems and record high capital investment in high-tech production facilities, businesses large and small are looking for a means of protecting their investments and ensuring a fire won't cripple their operations. While fire detection remains the first line of defense against the risks of fire to people, building owners are looking to fire suppression as a means of protecting their property and assets. But it's a well known fact that fire suppression is a double-edged sword: water can snuff out a mission-critical computer system as easily as it can a fire. Alternatives towater, including carbon dioxide and other extinguishing agents can endanger lives, while the release of even the most inert extinguishing agents can disrupt operations and cost millionsof dollars in down-time and lost production. UnderstandingtheSlGA REL The SIGA-REL Releasing Module is a network component that provides control for fire suppression routines It fulfils much the some purpose as .0 standalone releasing panel but supports Signature Series detectors as an integral part of the suppression system The SIGA-REL is easy to set up and accepts programming via the control panel's SDU Rules Editor. The diagram below represents typical application of the SIGA-REL The explanations thatfollow summarize each element of the module Release Circuits. The SIGA-REL includes two supervised release circuits, each of which provides fire suppression control to different areas of a protected space. The releasing circuits actuate solenoids on the suppression agent tanks according to pre-defined release routines. These solenoids release the agent into the protected area. Both circuits operate together. A primary goal of any fire suppression system is to prevent the release of extinguishing agent unless it is absolutely necessary. There is no margin for error. But no matter what measures are taken to prevent the unwanted release of extinguishing agent, the fact remains that no suppression system is any better than the detectors it relies on for input. The foundation of an effective suppression system, therefore, rests firmly on the quality and reliability of its smoke detectors. Signature Series detectors form an integral part of the suppression system built around the SIGA-REL releasing module. These detectors provide unsurpassed reliability and immunity from false alarms. The SIGA-REL is engineered to the same exacting standards of quality and performance. With a robust set of features designed to eliminate any unwanted release of extinguishing agent, the SIGA-REL provides all the benefits of a dedicated releasing panel without the extra expense, and equally important, all the proven advantages of the Signature Series family of products. [1f First Alarm Relay. This on board relay provides a Form C contact that activates at the first alarm input or manual release. The relay is typically used for room preparation such as controlling fans and dampers in advance of the release of suppression agent. IN all Pre-release. Pre-release circuits are used to provide power to notification appliances located within the protected are.Two supervised pre-release circuits are provided: one (steady) for visual notification appliances, and one (pulsed) for audible notification appliances. The pre-release circuits activate with the start of the automatic delay timer. Manual Release The manual release circuit is used to activate the suppression system by means of a connected normally open release station This initiates the manual release sequence according to a pre defined routine The manual release circuit is supervised and latching. Input from this circuit is processed at the module -communi- cation with the control panel is not necessary. LI1 Abort. The abort circuit is used to prevent the release of agent into the protected area after the release sequéncehasbegun, but before the automatic delay timer expires. A connected normally-open release station provides manual control overthis circuit The abort circuit is supervised and non-latching. L1 Service Disconnect. The service disconnect switch is used to temporarily disable the fire suppression system. There is no dedicated circuit for this switch Instead it is installed on both release circuits between the SIGA-REL and the RELA-EOL end-of-line relay. Opening the Service Disconnect Switch allows the fire alarm system to be tested without activating the fire suppression system. The operation of this switch causes a trouble signal at the control panel. Data. The Signature data circuit provides an input and an outputto the data loop that communicates with the Signature loop controller at the control panel The SIGA-REL resides on the some data boo asthé Sianature Series detectors that initiate the automatic release sequence. This close association offers the most reliable performance and ensures compliance with prevailing life safety codes. Power. The SIGA-REL requires 24 Vdc (power limited). See the specification table for details. www.gesecurity.com Page 2of8 Literature Sheet #85001-0535 Issue 4 NO', TO BE USED FOR INSTAL! ATI0N PURPOSES. Operation The SIGA-REL has several built-in safeguards to prevent the unwanted release of extinguishing agent. All release sequences are subject to configurable delay timers that provide the opportunitj for on occupant of the area to manually abort the release sequence. If no abort signal is received before the delay timer expires, the suppression agent is released. The SIGA-REL includes three delay timers: one for manual release sequences (up to 30 seconds); one for automatic release sequences )up to 50 seconds); and one for abort sequences (10 seconds). Normal State In its normal operating state the SIGA-REL supervises bath of its release circuits and both of its pre-release NAC circuits for faults. Should a short or open occur on any of these circuits, a Trouble condition is reported to the control panel. A trouble condition on any of these circuits may prevent the operation of that circuit, but it won't inhibit the operation of any other fault-free circuit Manual Release Sequence The operation of a manual release station initiates the manual release sequence. The diagram below outlines the manual release sequence. Une (see detailsi> relay Manual delay timer Pee-release sircolta "I-1 Release circuits Selectable manual e— delay time - Manual release activated ----------------------- -. seconds) Agent release ........................................................ System reset (manually at the control panel) .............................................. Note: A manual release sequence cannot be aborted. Manual Release Time Line An active manual release station disables automatic operation and the abort function and simultaneously activates the: Manual delay timer Pre-release circuit Pre-release strobe circuit (steady On) Pre-release horn circuit (60 pulses per minute) O Ten seconds before the expiration of the manual delay timer, the pre-release horn changes from 60 pulses per minute to steady On. O The manual delay timer expires and the release circuits activate. O A manual reset at the fire alarm control panel deactvotes the release solenoids and the Releasing Module returns to the normal state. Now Misapplication of the SIGA-REL can have serious consequences. Descriptions provided herearefor information only, are subjecttochange, and should notbeusedasaguidetofieldinstallation of equipment Always consult the SIGA-REL installation manual when setting uporconfiguring this component. Automatic Release Sequence The automatic release sequence requires an AND group (cross zone) or a matrix group (counting zone). AND groups and matrix groups require fire alarm signals from designated Signature Series devices. These logic groups are programmable through a laptop computer and the System Definition Utility )SDU). Note: EST2 systems do not support matrix groups. See Programming the SIGA-REL for AND group rules. To create AND groups and matrix groups, see the System Programming Manual and the SDU Online Help for your system. The diagram below outlines the automatic release sequence lime Une (see details below)> 9 V 9 First alum relay —j - Automatic delay timer I Pre.eeleasecticutis I Release circuits - ____L___J__________J_J. First alarm ----------------------------------- -' e— daisy lime I 1101050aeco ActIve signal from AND group (e.g: Second alarm) ----- Agentrelease ------------------------------------------------- System reset ---------------------------------------------------- Automatic Release Time Line A detector signals the first alarm. This event simultaneously activates the: Firstalarm relay Pre-release strobe circuit (steady On) Pre-release horn circuit (15 pulses per minute) O A detector in the protected area signals a second alarm and meets the AND group conditions.* The automatic delay timer then starts its countdown and the pre-release horn circuit changes to 60 pulses per minute. * AND group and matrix group conditions depend on programming. 10 seconds before the automatic delay timer expires, the pre- release (horn) circuit changes to steady On. 0 The automatic delay timer expires and the release circuits activate. O A manual reset at the fire alarm control panel deactivates the release solenoids and the Releasing Module returns to the normal state. www.gesecurity.com Issue 4 Literature Sheet #85001-0531 Page 3 of 8 S NOT TO RE 1iSEU FOR INSTALLAlION PURPOSES. Abort Sequences The SIGA-REL provides four abort modes. Aborts do not terminate the release of fire suppression agents. They merely offer a limited exten- sion of the automatic timer delay period. Abort Mode 1 (factory default) If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will continue to run while the abort is active. When the abort switch is restored, the release will occur with the expiration of the automatic delay timer or the abort delay timer, whichever occurs lost. Abort Mode 2 If the abort is initiated before the automatic time delay expires, it will prevent the releasing action. The automatic delay timer will stop running. When the abort switch is restored, the automatic delay timer Compatibility Sprinkler systems The SIGA-REL works with two types of sprinkler systems: deluge and pre-action. The primary difference between both systems is the type of sprinkler head (or nozzle) that terminates the pipes. Tablel-1 outlines the Factory Mutual Research Corporation IFMRCI requirements for deluge and pre-action systems. FM approval requirements for deluge and pre-action sprinkler systems Standby operation 90 hours Alarm operation 10 minutes . NFPA style Class A (Style D or E( or Class A (Style 2, 5, 6, or 7) FMRCdocumentation FMRC Approval Guide (Volume 1) Deluge sprinkler systems In Deluge sprinkler systems, open-valve sprinkler heads terminate pipes connected to a water supply controlled by a single valve. When the system detects a fire it automatically opens the valve to allow the waterflow through all of the sprinkler heads. Deluge sprinklers are useful for applications that require the simultaneous discharge of water through every sprinkler. The following fire detection systems meet FRMC requirements for deluge systems: Wet pilot sprinkler line Dry pilot sprinkler line Hydraulic rote-of-rise Pneumatic rate-of-rise Electric Pre-action sprinkler systems In Pre-action sprinkler systems, closed-valve sprinkler heads terminate pipes connected directly to a water supply. The water supply is usually in the some area as the sprinklers and the pipes are supervised for air pressure. Pre-action sprinklers are useful where it is important to prevent the accidental discharge of water. will continue from the stop point and the release will occur with the expiration of the timer. Abort Mode 3 Industrial Risk Insurers (IRlI Mode: To be recognized as valid, the abort must be active when the second alarm is received. When the abort switch is restored, the release will occur with the expiration of the abort delay timer (set for 10 sec). Abort Mode 4 International applications: If the abort is initiated before the automatic time delay expires, itwill prevent the releasing action. The automatic delay timer will stop running. When the abort switch is restored, the automatic delay timer will reset and commence time from t = 0. The release will occur with the expiration of the timer setting minus 10 seconds. The following fire detection systems meet FRMC requirements for pre- action systems: 'Hydraulic rate-of-rise 'Pneumatic rate-of-rise 'Electric Automaticfire extinguishing systems Automaticfire extinguishing systems automatically detectand extin- guish fires. They require no manual input because detectors automati- cally activate releasing solenoids or sprinkler valves. The table below provides a list of the fire suppression agents and the applicable NFPA documents. Fire suppression agents and NFPA documentation Agent NFPAdocumentation Low-expansion foam NFPA 11 Medium- and high-expansion foam NFPA 11A CO2 NFPA 12 Sprinklers NFPA 13 Water spray NFPA 15 Foam-water NFPA 16 Dry chemicals NFPA 17 The table below outlines the FMRC requirements for automatic fire extinguishing systems. FM approval requirements forautomatic fire extinguishing systems Standby operation 2' hours Alarm operation 10 minutes NFPAsty(e BarD FMRC documentation FM RC Approval Guide (Volume 1) Worningi Improper applications of fire suppression agents can lead to property damageinjury, or loss of life consult the applicable NFPA documents and the S authority having jurisdiction AHJI for more information. www.gesecurity.com Page 4 of 8 Literature Sheet #85001-0531. Issue 4 11112] [7](8] Service Disconnect Switch— Release circuit I RELA.EOL :3 (11(2] [71 [8 Service —Disconnect Switch Release circuit 2 2 3 4 2 3 4 LED Operation LED Color Pattern Function DS1 Red Flashing Data (alarm conditions) 0S2 Green Flashing Data (normal conditions)* DS3 Red Steady Alarm DS4 Green Steady Power DS5 Yellow I eady IAbort DS6 Yellow I Steady ITrouble DS7 Red I Steady I Release Active *Note: During a loss of communications, the Releasing Module will go into a standby condition, which will cause DSI and DS2 to change to a steady pattern during an alarm condition. Mounting /MFC.A Releasing Module #8-32 set-tapping screws #6 Flat Washers I NOT TO BE USED FOR INSTALLATION PURPOSES. Compatible panels and devices Panels. The SIGA-REL is compatible with EST2 and EST3 fire alarm control panels. You may install the SIGA-REL in any of the following enclosures: 2-WBlXl series • 2-CAB series 3-CAB series • RACCR series MFC-A Note: Maintain a 1-inch 125.4 mm) minimum clearance all around the SIGA-REL. The clearance space must also comply with the National Electrical Code. Power supplies. The SIGA-REL is compatible with the following power supplies: 2-PPS(-2201 • 2-PPS/6Al-2201 SIGA-APSl-2201 • 3-BPS/M 3-PPS/M • BPS6*, BPS10* *Not compatible with FMRC sprinkler applications that require 90 hours of standby. Solenoid polarizing relays. Use the RELA-EOLwith the SIGA-REL. For more information, see the RELA-EOL installation sheet. Manual release Wiring Signature - Data Circuit in(' Out{ [8] Abort circuit First alarm output [9] 1TB2 2 4 3 2 L Releasing Module JLRJ, MNSWIRM0111 - 18] } 24Vdcin - 24Vdcout +1 2 3 4 Abort stations. The SIGA-REL is only compatible with normally-open, momentary-action abortstations. Abort stations must be listed with the appropriate agencies in your area. See Listing agencies. Service disconnect stations. The SIGA-REL is only compatiblewith service disconnect stations thotare normally-closed (minimum 2.0 Amps). Service discon- nect stations must be listed with the appropriate agencies in your area. See Listing agencies. Releasing solenoid valves. Releasing solenoid valves must be listed with the appropriate agencies in your area. See Listing agencies. Listing agencies. Listing agencies include: Factory Mutual Research Corporation(FMRC) Underwriters Laboratories, Inc. (UL) Underwriters Laboratories Canada IULCI Switch Settings Abort mode and time delay settings are configured by means of dip switches an the module. Abort mode 12111110 Denotes default settings. Pre-release Circuit 2 (visual) (steady) [8] [5] (21 Pre-release Circuit 1 (audible) (pulsed 15160/Steady) [8] ]5]]2) Four RELA-EOLs per circuit, roes. Class B, 24 Vdc output Class B, normally-open manual release station Class B, normally-open abort station Listed 47 k51 EoL resistor Nonpolarized valve. The releasing solenoid valve wiring is not supervised for wire-to-wire shorts. Run the connection to the valve in conduit within 20 feet of the RELA-EOL Solenoid Polarizing Relay. Polarity of circuit shown in supervisory state. On alarm, polarity reverses. Supervised and power-limited. Power-limited when connected toe power- limited source. If nonpower.limited, maintain 1/4 inch (6.4 mm) separation. Otherwise, use FPL, FPLR, or FPLP in accordance with the National Electric Code (NEC). Destroy power-limited markings. 10 Installations, which include other wiring, require FPL, FPLR, FPLP, or equivalent NEC-approved wiring for all power-limited wiring. Mode SW1 110' 1 0 SW2 0 Routines that determine how 2 0 1 the abort function interacts 3 with the timers. 4 1 1 Manual time delay (seconds) Delay SW3 SW4 The length of time that the 0 0 QID' 10 0 0 1 deluge ssinhibited when the 20 1 0 releasina function is manually 30 1 initiated: Automatictime delay (seconds) Delay SW5 SW6 5W7 The length of time that the 10 0 0 0 deluge is inhibited when 20 0 0 1 the releasing function is 30 0 1 0 initiated by the control 40 0 1 1 panel (i.e.:afterreceiving ]lIil 50 1 0 0 on alarm). Aborttime delay (seconds) Delay 5W8 The length of time that the deluge is 0 0 inhibited when the abort function is Ull' 10 1 restored (i.e.: cancelled). - www.gesecurity.com Issue 4 Literature Sheet #85001-0531 Page 5of8 JOT TO BE USED FOR N~ T. ALI ATiON PURPOSES. 0 Specifications Input voltage ,24 Vdc (power limited) Power Supervisory current 25 mA, max. riser Riser input current '4 amps maximum Alarm 170 mA min.; 4 A max. Output rating 2 A @ 24 Vdc (for each circuit) Valves per circuit 4 valves, max. Release Max. supervisory current 0.4 mA (short circuit) circuits Nominal supervisory current 0.18 mA Supervisory voltage 26 Vdc, max. (open circuit) End of line device 47k Ohm EOL Output rating 2 A @ 24 Vdc (for each circuit) Pre-release Max. supervisory current 0.4 mA (short circuit) alarm circuits Nominal supervisory current 0.18 mA Supervisory voltage 26 Vdc. max. (open circuit) End of line device 47k Ohm resistor Max. supervisory current 0.4 mA (short circuit) Nominal supervisory current 0.18 mA Manual release Supervisory voltage 26 Vdc, max. (open circuit) Input circuit End of line device 47k Ohm resistor Circuit type Class B N.O. latching Circuit capacitance 0.1 iF, max Max. supervisory current 0.4 mA (short circuit) Nominal supervisory current 0.18 mA Abort circuit Supervisory voltage 26 Vdc, max. (open circuit) End of line device 47k Ohm resistor Circuit type Class B N.O. non- latching Circuit capacitance 0.1 iF, max First alarm Contact rating 3A@24Vdc output relay (0.6 power factor) Form C Signature Operating voltage 15.210 19.95 Vdc Data line Supervisory current 1000 VA Alarm current 1000 iA Environmental Operating temperature 32° F to 120° F (0° C to 49° C) condiltions Storage temperature -4° F to 140° F (-20° C to 60° C) Humidity 0 to 93% Non-condensing Wiring Terminals Suitable for #1810 #12 AWG (2.5 mm' to .75 mm') Type Code Factory Set Addressing Requirements Uses six module addresses Agency Listings UL. ULC, and FM Compatible Solenoids Must be both UUULC-listed and FM-approved Note: Output circuits are power-limited when the riser circuit is power-limited. Line Resistance Power riser Total riser current (Amps) Distance from SIGA-REL to power supply Wire resistance (Ohms per wire) #12 AWG 2.5 mm' #14 AWG 1.5 mm2 4.0 29 It 8.84 m 20 it 6.10 m 0.050 3.5 34 It 10.36m 23 It 7.01 m 0.057 3.0 39 It 11.89m 27 ft 8.23m 0.067 2.5 47 ft 14.33 m 32 It 9.75 m 0.080 2.0 59 ft 17.98m 40 ft 12.19m 0.100 1.5 78 it 23.77m 53 it 16.15m 0.133 1.0 11811 35.97m 80 it 24.38m 0.200 nd -.nile Inn.. r.i+5 Total riser current (Amps) Distance from SIGA-REL to power supply Wire resistance (Ohms per wire) #12 AWG F2.5 mm' #14 AWG 1.5 mm' 2.00 176 It 53.64m 120 ft 36.58m 0.300 1.75 202 ft 61.57m 13711 41.76m 0.343 1.50 23511 71.63m 16011 48.77m 0.400 1.25 282 ft 85.95 m 192 It 58.52 m 0.480 1.0 35311 107.59m 240 It 73.15m 0.600 0.50 706ft 215.19m 480ft 146.30m 1.200 Ordering Information Model Description Ship Wt. SIGA-REL Analog addressable releasing module 0.52 (0.23) Manual releasing station (single-action). 276A-REL English markings, black text on yellow 1.0 (0.45) polycarbonate body. Manual releasing station (double-action). 278A-REL English markings, black text on yellow 1.0 (0.45) polycarbonate body. RELA-ABT Manual Abort Station. English markings, 1.0 (0.45) black text on yellow polycarbonate body. Service Disconnect Switch. English RELA-SRV markings, white text on blue 1.0 (0.45) polycarbonate body. RELA-EOL Polarized end-of-line relay. English 0.2 (0.1) markings on stainless steel cover. UL listed cabinet for mounting releasing MFC- A modules, red with white 'FIRE". 1 HWD: 8 x 14"x 3%" NWD (203mm x 356mm x 89mm) I www.gesecuritg.com Page 6of8 Literature Sheet #85001-0535 Issue 4 Signature Series smoke detectors _________________ Horn Strobe Abori] Release Station Station Releasing Module Lted in MFC-A cabinet) Release circuit 2 Agent Fire alarm control panel nozzle releas Signature loop con7tollr :: Release circuit 1 RELA-EOL RELA-EOL 2 I Extinguishing agent storage cylinder Raised floor —<J Agent release nozzle —Signature Series smoke detectors I Slab Release station l,eoroewl End-of-Line Relay LEE' The End-of-Line Relay facilitates the connection of a non-polarized releasing solenoid to a supervised, polarized releasing circuit. One relay is required per release solenoid. Module Enclosure - The M FC-A cabinet is UL-listed for use with Signature modules. tI-I Shown herewith plug-in style I/O modules, the MFC-A also meets UL requirements for spacing and clearance around the SIGA-REL Releasing Module. The cabinet features red epoxy finish with white "FIRE" markings. NOT TO BE USED FOP INSTALLATION- PURPOSES. Accessories Typical application of SIGA-REL accessories (computer room) AbortStation RELEASE 1 '1ifnv C t RELEASE 124 mm) box _ HOLD The abort station is a normally-open, non-latching device. It is used to prevent the release of agent into the protected area after the release sequence has begun. Service DisconnectSwitch (82 mm) lRlnhld box Manual Release Station The manual release station isa normally-open, dry contactsignal initiating device. The 276A-REL is single-action station that requiresthe userto pull the release handle to initiate the release of a fire suppression agent. The 278A-RELlshownl is a double-action station that requiresthe userto raise the upper door, then pull the release handle to initiate the release. FiOrd View Semi-Flush Surface flT r 4 ROe b kbo 4 WIth 2ThBRsa plaster cover with single 000ldios gang opening having ocecot In. depth of 2.114, .I/4 (57mm,) www.gesecurity.com Issue 4 Literature Sheet #85001-0531 Page 7of8 The service disconnect switch is used to temm releasing porarily disable the fire POO suppression system. One switch is installed on each of the two release lent device circuits between the SIGA-REL and the RELA-EOL end-of-line relay. Opening uthnereutntor the Service Disconnect Switch allows the fire alarm system to be tested without activating the fire suppression system. The operation of this switch causes a trouble signal at the control panel. C CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL Vulda FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTENG SERVICE LISTING No. 7300-1657:205 Page 1 of I CATEGORY: Misc. Devices/Control Unit Accessories LISTEE: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 FAX (941) 308-8123 RATING: 24 VDC DESIGN: Model SIGA-REL releasing module and Model RELA-EOL end-of-line relay. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed Models EST-2, EST-3, QS1 and QS4 fire alarm control units. NOTE: Formerly 7300-1591:205 and 7300-1388:235 08-17-05 BH This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JULY 1, 2009 Listing Expires June 30, 2010 Authorized By: FRANCIS MATEO, Program Coordinator Fire Engineering Division Description Signature Series Universal Input-Output Module Motherboards provide mounting and wiring terminations for up to six Signature Series plug-in UIO qW lSlGA-"M" series) modules. UIO motherboards slide into a rigid extruded track (included) with mounting pads for convenient mounting into a variety of equipment enclosures. UIO modules plug into the board and are held securely in place with captive machine screws. All field wiring connects to terminal blocks on the motherboard, which permits rapid removal and replacementof modules for troubleshooting. The SIGA-UI02R provides mounting and wiring terminations for up to two UIO modules, and the SIGA-lJl06R provides mounting and wiring termina- tions for up to six UIO modules. Both motherboards feature a riser #1 input and a riser #2 input bus. Jumpers on riser #1 input, between modules, facilitate sharing a single riser among more than one module. This significantly reduces wiring requirements. Removing thejumpers provide separate riser inputs to each adjacent module. Riser #2 input is fixed to each module position and cannot be split. The SlGA-UlO6 provides mounting and wiring terminations for up to six UIO modules. This motherboard provides two riser inputs that are common to all modules. EDWPOS SYSTEMS TECHNOLOGY Part of GE Security INTELLIGENT INPUT/OUTPUT DEVICES Universal Input/Output Module Motherboards Models: SIGA-U102R, SIGA-UI06R, SlGA-U106 Features Modular flexibility Wide assortment of multi-function plug-in modules provides total flexibility. Minimum wiring requirements Integral jumpers between modules allow sharing of risers to reduce installation wiring. Easy installation #12 AWG (2.5 mm') terminal blocks and sturdy mounting pads ensure quick installation into GE Security enclosures. Supports automatic device mapping All compatible UIO modules transmit information to the loop controller regarding their circuit locations with respect to other Signature devices on the wire loop. Supports intelligent devices On-board modules make decisions and input an alarm from initiating devices connected to them even if the loop control- lers polling interrogation stops. Twisted or shielded wire not required Because all decisions are made at the on-board modules, lower communication speeds are possible. This results in substan- tially improved control panel response time and less sensitivity to line noise and loop wiring properties. Supports electronic addressing Programmable addresses are downloaded to compatible UIO modules from the loop controller, a PC, or the SlGA-PRO Signa- ture Program/Service Tool. There are no switches or dials to set. High ambient temperature operation Install in ambient temperatures up to 120°F 1490Cl. Designed to ISO 9001 standards All Signature products are manufactured to strict international quality standards to ensure highest reliability. 0 imagination at work www.gesecurity.com 10 8985 TOWN CENTER PARKWAY, BRADENTON, FL 34202 PHONE: 888-378-2329 • FAX: 866-503-3996 CANADA SALES: OWEN SOUND, ON 519-376-2430; FAX 519-376-7258 INTERNATIONAL SALES: 10011905-270-1711; FAX 10011905-270-9553 Literature Sheet #85001-0365 Issue 3.1 Not to be used for Installation purposes. Page lof 4 The MFC-A cabinet is UL listed for use with UIO motherboards and meets requirements for spacing and clearance around the components. UIO Motherboard 1, 6-32 Self-tapping . screws Plug-in (UIO). Captive MndHIe A' screws td #6 Flat washers NOT TO BE USED POR N'rALLAToN PURPOSES. . Mounting and Installation Mount the UIO motherboard inside an GE Security MFC-A cabinet or other suitable electrical enclosure with screws and washers provided Each MFC-A will hold one U102R motherboard or one U106 or U106R motherboard complete with their full complementof modules. Plug a Signature Series UIO module into any available position on the motherboard and secure the module to the motherboard with the captive screws. Wiring connections are made to the terminals on the motherboard (see wiring diagram). UIO motherboard terminals are suited for #12 to #18 AWG (2.5 mm' to 0.75 mm2) wire size. GE Security recommends that all boards and modules be installed according to latest recognized edition of national and local fire alarm codes. -Cabinet or electrical enclosure Opecifications Catalog Number SIGA-U102R I SIGA-U106R I SIGA-Ul06 Module Capacity Two J Six Dimensions (with module installed) 5.4 inch L (across mounting feet) x 4.3 inch W x 3.2 inch H 9.56 inch L (across mounting feet) x 4.3 inch W x 3.2 inch H Address Requirements no address required Type Code none Compatible Modules All SIGA-Mxxx Signature Series Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) Mounting (cabinets) Wiring Terminals Directly into suitable EST enclosures (e.g.: MFC-A) - Notes 1, 2, 3. #12 AWG (2.5mm2) to #18 AWG (0.75mm2) Storage and Operating Environment Operating Temperature: 32°F to 120°F (0°C to 49°C) Storage Temperature: -4°F to 140°F (-20°C to 60°C) Operating and Storage Humidity: 0 to 93% RH Agency Listing UL, ULC, MEA, CSFM Notes: Allow a minimum clearance of one inch around all sides of the UIO motherboard. On-site drilling of mounting holes may be required. Self-tapping mounting screws are provided. Suitable cabinets: MFC-A, 2-W8, 2-WB3, 2-WB7, CA132, 3-CAB5, 3-CAB7, 3-CAB14, 3-CAB21, 3-RCC series, RACC series. www.gesecurity.com Page 2of4 LlterotureSheet#85001-0365 Issue 3.1. SIGA-U106R Module Input/Output Wiring Refer to individual arm/ste installation sheet for wiring details. Detain + — 8— Sane/ste Data Ct/colt Data Out' Jumpers caere common sputa outputs betwea modules. Input/Output Bus Canrrrron to all SIGA-M series modules (maximum current 108 Mips) Module Input/Output Wiring (maximum current 128 Amps) Refer to individual module Installation sheet for wiring details. SIGA-U106 Module Input/Output Wiring Refer to individual module installation sheet for wiring details, 234 2214 1134 2234 1234 I2 a 4 5IGA4tlOe us Data In + T13 14 Inputioutput Bus I 4 Cormon to all 8-i 2' SIGA-M sense Sore/ste L3 I IS II II SI IS I : Olnent 108Data I r modulos)ma)lmum dart/c) c1nulI4___J'j1 t 2. f IIpetIOulpt Bus 2 D.ta Out It j.. j.. I 1 ; Ir 1"modules ImaaImcm I NOT TO BE USED FOR lNs'rALLAllolri PURPOSES. Typical Wiring 0 Signature Series Universal Input/Output Motherboards have terminal blocks to accept #18 AWG (0.75mm2 ), #16 AWG (1.0mm2), #1ri AWG 11.5mm2 I. and #12 AWG (2.5mm2) wire sizes. See Signature Data Controller catalog sheets for detailed wiring requirements and specifications. SIGAUIO2R A Module Input/Output Whnt9 1 .234 234 1 TBI T82 Data In L-_ TB Signature a I Data Circort I Common inputlootFn4t + 4 2 1 — tam for SIGA.M oeree modutes Data Out — _______ . A TUB W11I I I . Jumpers connect comm A Module Input/Output t/lnttg modules AA Notes Jumpers may be used to make the inputs/outputs between modules common. 21 Not all modules use the SIGA-UI02R terminals for the some functions. Refer to individual SIGA-M series installation sheets for jumper settings and wiring information. Installations with multiple SIGA-ulo motherboards or enclosures (which include other wiring) require FPL, FPLR, FPLP, or equivalent NEC-approved wire for all power limited wiring. Observe the details of supervision and power limited versus non-power limited circuits. Refer to the SlGA-M series installation sheets. 41 Do not mix incompatible signals. Maximum current is 8 Amps. 61 Refer to IOMC Manual (P/N 2701441 for maximum wire resistance and maximum wire distances. 71 Refer to Signature Data controller Installation Sheets for wiring specifications. Testing & Maintenance The modules automatic self-diagnosis identifies when it is defective and causes a trouble message. The user-friendly maintenance program shows the current state of each module and other pertinent messages. Single modules may be turned off (de-activated) temporcrily, from the control panel. Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction IAHJL Refer to current NFPA 72 and ULC CAN/ULC 536 standards. Compatibility Signature Series Universal Input/Output Module Boards are compatible only with SlGA-"M" Series I/O Modules, which require EST's Signature Data Controller. Warnings & Cautions Signature devices will not operate without electrical power. As fires frequently cause power interruption, we suggest you discuss further safeguards with your fire protection specialist. Ordering Information Catalog Number Description Ship Wt. - lb (kg) SIGA-UI02R Universal Input-Output Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15) SIGA-UI06R Universal Input-Output Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28) SIGA-U106 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25) MFC-A UL listed cabinet for mounting UIO motherboards, red with white "FIRE" 8 inch H X 14 inch W X 3.5 inch 0_(203_mmH X 356mmWX89mm_ID) 7.0(3.1) www.gesecurity.com Issue 3.1. Literature Sheet #85001-0365 Page 3 sf4 NOT; TO BE USED FOR INSTAL: .A1ION PURPOSES. Is Description (Signature Overview) The Signature Series intelligent analog-addressable system from GE Security is an entire family of multi-sensor detectors and mounting bases, multiple-function input and output modules, network and non- network control panels, and user-friendly maintenance and service tools. Analog information from equipment connected to Signature devices is gathered and converted into digital signals. An onboard microprocessor in each Signature device measures and analyzes the signal and decides whether or not to input an alarm. The microproces- sor in each Signature device provides four additional benefits - Self- diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Self-diagnostics and History Log - Each Signature Series device constantly runs self-checks to provide important maintenance informa- tion. The results of the self-check are automatically updated and permanently stored in its non-volatile memory. This information is accessible for review any time at the control panel, PC, or using the SIGA-PRO Signature Program/Service Tool. The information stored in device memory includes: Device serial number, address, and type. Date of manufacture, hours of operation, and last maintenancedate.2 Number of recorded alarms and troubles.' Time and date of last alarm.' Most recent trouble code lagged by the device - 32 possible trouble codes may be used to diagnose faults. Automatic Device Mapping -The Signature Data Controller (SDC) learns where each device's serial number address is installed relative to other devices on the circuit. The SDC keeps a map of all Signature Series .devices connected to it. The Signature Series Data Entry Program also uses the mapping feature. With interactive menus and graphic support, the wired circuits between each device can be examined. Layout or "as-built" drawing information showing branch wiring (T-taps), device types and their address are stored on disk for printing hard copy. This takes the 'mystery' out of the installation. The preparation of as-built drawings is fast and efficient. Device mapping allows the Signature Data Controller to discover Unexpected additional device addresses. Missing device addresses. Changes to the wiring in the circuit. Most Signature modules use a "personality code" selected by the installer to determine their actual function. Personality codes are downloaded from the SDC during system configuration and are indicated during device mapping. Standalone Operation - A decentralized alarm decision by the device is guaranteed. Onboard intelligence permits the device to operate in standalone (degrade) mode. If Signature loop controller CPU communi- cations fail for more than four seconds, all devices on that circuit go into standalone mode. The circuit acts like a conventional alarm receiving circuit. Each Signature device on the circuit continues to collect and analyze information from its slave devices. When connected to a panel utilizing standalone operation, modules with their "personality" set as alarm devices llDCl will alarm should their slave alarm-initiating device activate. Fast Stable Communication - Built-in intelligence means less informa- tion needs to be sent between the device and the Signature Data Controller (SDC). Other than regular supervisory polling response, Signature devices only need to communicate with the SDC when they have something new to report. This provides very fast control panel response and allows a lower baud rate (speed) to be used for commu- nication on the circuit. The lower baud rate offers several advantages including: Less sensitivity to circuit wire characteristics. Less sensitivity to noise glitches on the cable. Less emitted noise from the data wiring. Twisted or shielded wiring is not required. Diagnostic LEDs - Twin LEDs on most Signature devices provide visual indication of normal and alarm-active conditions. Aflashing green LED shows normal system polling. A flashing red LED means the module is in alarm-active state. Both LEDs on steady indicates alarm-active state - standalone mode. Testing & Maintenance -Automatic self-diagnosis identifies when a Signature device is defective and causes a trouble message. The user- friendly maintenance program shows the current state of each device and other pertinent information. Single devices may be turned off temporarily, from the control panel. Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and ULC CAN/IJLC 536 standards. Quality and Reliability - GE Security Signature devices are manufac- tured in North America to strict international ISO 9001 standards. All electronics utilize surface mount technology ISMTI for smaller size and greater immunity to RF noise. A conformal coating is used for humidity and corrosion resistance. 1 EST3 V.2 only. 2 Retrievable with SIGA-PRO programming tool. 9 www.gesecurity.com It is our intention to keep the product information current and accurate. We cannot cover specific applications or anticipate all requirements. All specifications are subject to change without notice. For more information or questions relative to this Specification Sheet. contact GE Security. (0 1999 GE Security Printed in U.S.A. Page4of4 Literature Sheet #85001-0365 Issue 3.1 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1483:115 Page 1 of 1 CATEGORY: Misc. Devices/Control Unit Accessories LISTEE: Mirtone, 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 Fax (941) 308-8123 DESIGN: Models GSA-CCI, GSA-CC2, GSA-CT1, GSA-CT2, GSA-CR, GSA-CRR, GSA-UM, GSA-MMI, GSA-WTM, GSA-IM, GSA-MCC2, GSA-MCT2, GSA-MCR, GSA-MCRR, GSA-MAB, GSA-MCC I, GSA-MDM remote transponders; Models GSA-UI06, GSA- U106R and GSA-Ul02R motherboards. Models MFC-A and MFC-AD enclosures. Models GSA-MP1, GSA-MP2 and GSA-MP2L mounting plates. *Model GSA-CR2 Control Relay Module. Refer to listee's data sheet for additional detailed product description and operational consideration. RATING: 15.2 — 19.95 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. n APPROVAL: Listed as remote transponders for use with separately listed compatible fire alarm control units. XL: 7300-1657:121 *Rev. 08-22-07 mt ° This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or ";•'+ recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JUNE 23, 2009 Listing Expires June 30, 2010 Authorized By: FRANCIS MATEO, Program Coordinator Fire Engineering Division Stations SIGA-270, SJGA-270P, SIGA-278 Manual Pull atented 0 MEA Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page 1 of 4 GE EST Fire & Life Safety Security Intelligent Initiating Devices S Overview The SIGA-270 and SIGA-278 series Manual Pull Stations are part of GE Security's Signature Series system. The SIGA-270 Fire Alarm Manual Pull Stations feature our very familiar teardrop shape. They are made from die-cast zinc and finished with red epoxy pow- der-coat paint complemented by aluminum colored stripes and markings. With positive pull-lever operation, one pull on the station handle breaks the glass rod and turns in a positive alarm, ensuring protection plus fool-proof operation. Presignal models (SIGA-270P) are equipped with a general alarm (GA) keyswitch for applications where two stage operation is required. The up-front highly visible glass rod discourages tampering, but is not required for proper operation. GE Security's double action single stage SlGA-278 station is a contemporary style manual station mode from durable red colored lexan. To initiate on alarm, first lift the upper door marked "LIFT THEN PULL HANDLE", then pull the alarm handle. Standard Features Note: Some features described here may not be supported by all control systems Check your control panel's Installation and Operation Guide for details. Traditional familiar appearance SIGA-270 models feature our familiar teardrop design with simple positive pull action and sturdy die-cost metal body. One stage (GA), two stage (pro-signal), and double action models SIGA-270 models are available for one or two stage alarm sys- tems. The single stage double action SIGA-278 features a rugged Lexan housing with keyed reset mechanism. Break glass operation An up-front visible glass rod on the SIGA-270 discourages tam- pering. Intelligent device with integral microprocessor All decisions are made at the station allowing lower communica- tion speed while substantially improving control panel response time. Less sensitive to line noise and loop wiring properties; twisted or shielded wire is not required. ADA Compliant Meets ADA requirements for manual pull stations. Electronic Addressing with Non-volatile memory Permanently stores programmable address, serial number, type of device, and job number. Automatically updates historic information including hours of operation, lost maintenance date, number of alarms and troubles, and time and date of last alarm. Automatic device mapping Each station transmits wiring information to the loop controller regarding its location with respect to other devices on the circuit. Stand-alone operation The station inputs an alarm even if the loop controller's polling interrogation stops. Diagnostic LEDs Status LEDs; flashing GREEN shows normal polling; flashing RED shows alarm state. Designed for high ambient temperature operation Install in ambient temperatures up to 120 °F (49 °Cl. Ctorrn/Acnve) f DATA IN DA1AOUTFr) 1 DATA IN(-) ). DATA C: From Signature ControNer To Next Device or Previous Device A Figure 4. Single Stage Systems REAR VIEW 1JL.J Of 270P270PB CD T22 Red LED • C - Green LED (Alarm/Active) - lL (Normal) 0 P1 Application The operating characteristics of the fire alarm stations are deter- mined by their sub-type code or "Personality Code". NORMALLY- OPEN ALARM - LATCHING (Pesonality Code 1) is assigned by the factory; no user configuration is required. The device is configured for Class B IDC operation. An ALARM signal is sent to the loop con- troller when the station's pull lever is operated. The alarm condition is latched at the station. Typical Wiring The fire alarm station's terminal block accepts #18 AWG (0.75mm2) to #12 AWG 12.5mm21 wire sizes. See Signature Loop Controller cata- log sheet for detailed wiring requirement specifications. Wiring Notes Refer to Signature Loop Controller manual for maximum wire distance. 2. All wiring is power limited and supervised. Compatibility REAR VIEW ot 276 Signature Series manual stations are compatible only with GE Secu- rity's Signature Loop Controller. 0 o — Warnings & Cautions This device will not operate without electrical power. As fires fre- quently cause power interruption, we suggest you discuss further safeguards with your local fire protection specialist. Testing & Maintenance To test (or reset) the station simply open the station and operate the exposed switch. The SIGA-270 series are opened with a tool; the SIGA-278 requires the key which is supplied with that station. The station's automatic self-diagnosis identifies when it is defec- tive and causes a trouble message. The user-friendly maintenance program shows the current state of each Signature series device and other pertinent messages. Single devices may be deactivated temporarily, from the control panel. Availability of mainterance features is dependent on the fire alarm system used. Scheduled maintenance (Regular or Selected) for proper system operation should be planned to meet the requirements of the Au- thority Having Jurisdiction (AHJI. Refer to current NFPA 72 and ULC CAN/ULC 536 standards. f DATA iN(v) I I DATA OUT 1 DATA iN (.) > DATA Oct C-) From Signature Controller Y To Next Device or Previous Device A Figure 5. Two Stage Systems Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page 2of4 Installation Single-stage Signature Series fire alarm manual pull stations mount to North American 2½ inch (64 mm) deep 1-gang boxes. Two stage presignal (270P) models require 1½ inch (38 mm) deep 4-inch square boxes with 1-gang, ½-inch raised covers. Openings must be angular. Rounded openings are not acceptable. Recommended box: Steel City Model 52-C-13; in Canada, use Iberville Model Cl-52-C-49-1/2. All models include terminals are suited for #12 to #18 AWG (2.5 mm' to 0.75 mm') wire size. GE Security recommends that these fire alarm stations be installed according to latest recognized edition of national and local fire alarm codes. Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system commission- ing. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board memory. The loop controller identifies each device on the loop and assigns a 'soft' address to each serial number. If desired, the stations can be addressed using the SIGA-PRO Signature Program/Service Tool. Key-Latch r Compatible Electrical Box Compatible Electrical Box Cover Release . . - - - .—- Cover . L Release Screw I Switch Back 41 Back Plate Plate pot Switch Glass Rod Glass Pod 1'. .- -. •1 .,. &Release Lever OPEN . LE " Figure 1. SlGA-278 installation Figure 2. SIGA-270, SlGC-270F, SlGC-270B installation Cover Release Scrtw , cT Eiectricai Box with ~-inch K '1 roisedcovers—p\ '=:; - plate T le IAL 110, Glass Rod Release Lever Do not use rounded openings. Figure 3. SIGA-270P, SIGC-270P8 installation Data Sheet 85001-0279 issue 8 Not to be used for installation purposes. Page 3 of 4 GE Security S Specifications S)GA-270, SlGC-270F 1 S(GA-2701P, Cota)oà Number SIGC-2708 S)GC-270PB SIGA-278 ' Description Single Action Single Action -Two Double Action - One Stage Stage lPresignall - One Stage Addressing Uses 1 Module Uses 2 Module Uses 1 Module Requirements - Address Addresses Address Operating c nt Current Standby = 250pA Standby = 396pA - Standby= 250pA Activated = 400pA Activated=680pA Activated =400pA Construction & Finish Diecost Zinc - Red Epoxy Lexon - Red with with aluminum markings white markings Type Code Factory Set Operating Voltage 15.2 to 19.95 Vdc 119 Vdc nominal) Storage and Operating Operating Temperature: 32°F to 120°F 10°C to 49°Cl Environment Storage Temperature: -4°F to 140°F 1-20°C to 60°C) Humidity: 0 to 93% RH On-board Green LED - Flashes when polled LED Operation On-board Red LED - Flashes when in alarm Both LEDs -Glow steady when in alarm (stand-alone) Compatibility Use With: Signature Loop Controller Agency Listings UL, ULC (note 1), MEA, CSFM Note: SIGC-270F, SIGC-2 708 and SIGC-270P8 are ULC listed only. Suffix "F' indicates French markings. Suffix "B" indicates English/French biling ual markings. Ordering Information Catalog Ship Wt Number Description lbs (kg) SlGA-270 One Stage Fire Alarm Station, English Markings - UL/ULC Listed SIGC-27CF One Stage Fire Alarm Station, French Markings - ULC Listed SlGC-27CB One Stage Fire Alarm Station, French/English Markings - ULC Listed SlGA-270P Two Stage IPresignall Fire Alarm Station, English Markings - UL/ULC Listed 1(05) SIGC-270P8 Two Stage IPresignall Fire Alarm Station, French/English Markings - ULC Listed SIGA-27S Double Action (One Stage) Fire Alarm Station, English Markings - UL/ULC Listed U.S. 1888-378-2329 F 866-503-3996 Canada 15193762430 F519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 613 9259 4700 F 613 9259 4799 Europe 13227251120 F 32 2 72186 13 Latin America 1305 593 4301 F 305 593 4300 www.gesecurity.com/est © 2007 General Electric Company All Rights Reserved Signature Series is a Trademark of GE Security. Accessor es 32997 GA Key w/Tag - for pre-signa) station (CANA 1. DA ONLY) 276-K2 GA Key - for pre-signal station (USA ONLY) Stoon Reset Key, Supplied with a Key Reset --- 0.1 (.05) 27165 12 Glass Rods - for SlGA-270 series (CANADA ONLi') 270-GLR 20 Glass Rods - far SIGA-270 series (USA ONLY) 276-GLR 20 Glass Rods - for SIGA-278 series 276B-RSB Surface Mount Box, Red - for SIGA pull stations 1(0.6) imagination at work Data Sheet 85001-0279 Issue 8 Not to be used for installation purposes. Page 4 of 4 S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7150-1657:129 Page 1 of I CATEGORY: Boxes/Pull Stations* LISTEE: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 Fax (941) 308-8123 Rhonda.Micochero@GE.com DESIGN: Models SIGA-270, SlGA-270P, and SIGA-278 noncoded, intelligent manual pull stations*. Unit consists of a listed pull station and a remote transponder. Refer to listee's data sheet for additional detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as manual pull stations for use with separately listed compatible fire alarm control units. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments. NOTE: Formerly 7150-1591:129 and 7150-1388:194 *Updated 07-14-2009 fm This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or '+ recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JULY 14, 2009 Listing Expires June 30, 2010 Authorized y: FRANCIS MATEO, Program Coordinator Fire Engineering Division L(E Application Notes Available Data Sheet 85001-0269 Issue 6 Not to be used for installation purposes. Page 1 of 4 0 ' GE EST Fire & Life Safety Security Intelligent Initiating Devices Overview The Signature Series Model SIGA-PS Intelligent Photoelectric Smoke Detector gathers analog information from its smoke sensing ele- ment and converts it into digital signals. The detector's on-board microprocessor measures and analyzes these signals. It compares the information to historical readings and time patterns to make an alarm decision. Digital filters remove signal patterns that are not typical of fires. Unwonted alarms are virtually eliminated. The microprocessor in each detector provides four additional benefits - Self-diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and Fast, Stable Communication. Self-diagnostics and History Log - Each Signature Series detec- tor constantly runs self-checks to provide important maintenance information. The results of the self-check are automatically updated and permanently stored in the detector's non-volatile memory Automatic Device Mapping - The loop controller learns where each device's serial number address is installed relative to other devices on the circuit. The mapping feature provides supervision of each device's installed location to prevent a detector from being rein- stalled (after cleaning etc.) in a different location from where it was originally. Stand-alone Operation - A decentralized alarm decision by the detector is guaranteed. On-board intelligence permits the detector to operate in stand-alone mode. If loop controller CPU communica- tions fail for more than four seconds, all devices on that circuit go into stand-alone mode. The circuit acts like a conventional alarm receiving circuit. Fast Stable Communication - On-board intelligence means less information needs to be sent between the detector and the loop controller. Other than regular supervisory polling response, the detector only needs to communicate with the loop controller when it has something new to report. Standard Features Integral microprocessor Non-volatile memory Automatic mapping device Electronic addressing Environmental compensation Intelligent detector Wide 0.67% to 3.77%/ft. sensitivity range Twenty pre-alarm sensitivity values, set in 5% increments Identification of dirty or defective detectors Automatic day/night sensitivity adjustment Twin RED/GREEN status LEDs Standard, relay, fault isolator, and audible mounting bases Designed and manufactured to ISO 9001 standards Intelligent Photoelectric Smoke Detector I j SIGA-PS S Installation Signature Series detectors mount to North American 1-gong boxes, 3-1/2 inch or 4 inch octagon boxes, and to 4 inch square electrical boxes 1-1/2 inches (38 mm) deep. They mount to European BESA and 1-gang boxes with 60.3 mm fixing centers. 0.8 (20 mm) 2.0'(61 mm) F I 4.4' (112 mm) Tamper-Resist Lover Arm - Break off to disable - (Located on Bose) Access Slot for Tamper-Resist Mechanism - Testing & Maintenance Each detector automatically identifies when it is dirty or defective and causes a "dirty detector message. The detector's sensitiv- ity measurement can also be transmitted to the loop controller. A sensitivity report can be printed to satisfy NFPA sensitivity measure- ments which must be conducted at the end of the first year and every two years thereafter. The user-friendly maintenance program shows the current state of each detector and other pertinent messages. Single detectors may be turned off temporarily from the control panel. Availability of maintenance features is dependent on the fire alarm system used. Scheduled maintenance (Regular or Selected) for proper detector operation should be planned to meet the requirements of the Au- thority Having Jurisdiction lAHJl. Refer to current NFPA 72 and ULC CAN/ULC 536 standards. Compatibility The SIGA-PS detectors are compatible only with the Signature Loop Controller. Warnings & Cautions This detector will not operate without electrical power. As fires fre- quently cause power interruption, we suggest you discuss further safeguards with your fire protection specialist. This detector will NOT sense fires that start in areas where smoke cannot reach the detector. Smoke from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector to alarm it. Accessories All detector mounting bases have wiring terminals that are acces- sible from the "room-side" after mounting the base to the electrical box. The bases mount to North American 1-gang boxes and to 31/2 inch or 4 inch octagon boxes, 11h inches (38 mm) deep. They also mount to European BESA and 1-gong boxes with 60.3 mm fixing centers. The SIGA-S84, SlGA-R84, and SlGA-lB4 mount to North American 4 inch sq. electrical boxes in addition to the above boxes. They include the SIGA-TS4 Trim Skirt which is used to cover the "mounting ears" on the base. The SlGA-AB4G mounts to a 4" sqare box only. SIGA-AB4G SIGA-SB SICA-10 SIGA-RB SIGA-LED Audible Base Standard Base Isolator Bose Relay Base Remote LED Standard Base SIGA-SB, SIGA-SB4 - This is the basic mounting base for GE Security Signature Series detectors. The SlGA-LED Remote LED is supported by the Standard Base. Relay Bose SIGA-RB, SIGA-RB4 - This base includes a relay. Nor- mally open or closed operation is selected during installation. The dry contact is rated for lamp (pilot duty) @ 30 Vdc. The relay's position is supervised to avoid accidentally jarring it out of position. The SIGA- RB can be operated as a control relay if programmed to do so at the control panel (EST3 V.? only). The relay base does not support the SlGA-LED Remote LED. Audible Base SlGA-AB4G - This base is designed for use where localized or group alarm signaling is required. When the detector senses an alarm condition, the audible base emits a local alarm signal. The optional SlGA-CRR Polarity Reversal Relay can be used for sounding to other audible bases on the same 24 Vdc circuit. Relay and Audible Bases operate as follows: - at system power-up or reset, the relay is de-energized - when a detector is installed in the base with the power on, the relay energizes for four seconds, then de-energizes - when a detector is removed from a base with the power on, the relay is de-energized when the detector enters the alarm state, the relay is energized Isolator Base SIGA-113, SlGA-184 - This base includes a built-in line fault isolator for use on Class A circuits. A detector must be installed for it to operate. The isolator base does not support the SlGA-LED Remote LED. The isolator operates as follows: - a short on the line causes all isolators to open within 23 msec - at 10 msec intervals, beginning on one side of the Class A circuit nearest the loop controller, the isolators close to provide the next isolator down the line with power - when the isolator next to the short closes, reopens within 10 msec. The process repeats beginning on the other side of the loop con- troller. Remote LED SIGA-LED - The remote LED connects to the SIGA-SB or SlGA-SB4 Standard Base only. It features a North American size 1-gong plastic faceplate with a white finish and red alarm LED. SlGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also be ordered separately to use with the other bases to help hide surface imperfections not covered by the smaller bases. Data Sheet 85001-0269 Issue 6 Not to be used for installation purposes. Page 2 of 4 Remote LED (SIGA-LED) Max. Resistance per Wire Must NOT Exceed 15 Term Description 1 Not Used 2 DATA lN/OUTlA 3 Not Used 4 - ) DATAINI 5 Remote LED I-I 6 Remote LED 1+1 7 Not Used 8 DATAOuTl - l IN (-) I . L) Z11 x I DATA our (-) DATA IN (+) DATA OUT (+) From Signature Controller To Next Device or Previous Device OUT (-) OUT (+) To Next Device Term Description 1 Not Used 2 DATA iN/OUTl+l 3 DATAIN)l - l 4 Not Used 5 Not Used 6 DATA OUT 7 Not Used Volume setting Default a High volume Cut for tow volume 24 Vdc In - From power supply or previous base Data In - From Signature controller or previous device + Torte setting Default = Temporal pattern Cut for steady tone re configure output volume or tone, cot the dronit board as shown. 24 Vdc out To next base or EOL relay Data out To next Signature device DA1 DA1,- UN From Signature Controller or Previous Device I • Application Although photoelectric detectors have a wide range of fire sensing capabilities they are best suited for detecting slow, smoldering fires. The table below shows six standard test fires used to rate the sensitivity of smoke and heat detectors. The table indicates that no single sensing element is suited for all test fires. GE Security recommends that this detector be instated according to latest recognized edition of national and local fire alarm codes. SlGAHRS and SIGA- HFS Rote-of-Rise/ SIGAPHS SIGA-IPHS Test Fire SIGA-IS Ion SIGA-PS Photo Fixed Temp. PhotoHeot 3D Ion/Photo/Heat 40 Open Wood optimum unsuitable optimum very suitable optimum Wood Pyrolysis suitable optimum unsuitable optimum optimum Smouldering Cotton very suitable optimum unsuitable optimum optimum Poly Urethane Foam very suitable very suitable suitable very suitable optimum n-Heptane optimum very suitable very suitable optimum optimum Liquid Fire without Smoke unsuitable unsuitable optimum very suitable very suitable Typical Wiring The detector mounting bases accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.5mm2), and #12 AWG (2.5mm2) wire sizes. Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Sigrature Loop Controller catalog sheet for detailed wiring requirement specifications. Standard Detector Base, SIGA-SB, SIGA-SB4 Relay Detector Base, SIGA-RB, SIGA-R84 Normalty- Normally- CAT -It ON 5*) From Signature Controller or Previous Device Term Description 1 Normally Open 2 DATA IN/OUT 1+1 3 Common 4 DATA INI-1 5 Not Used 6 Normally-closed 7 DATA OUT I-I CONTACT RATING 1.0 Amp © 30 VDC OUT (-) (Pilot Duty) OUT (+) To Next Device C Isolator Detector Base, SlGA-IB, SIGA-I134 Audible Detector Base, SIGA-AB4G Data Sheet 85001-0269 Issue 6 Not to be used for installation purposes. Page 3 of 4 n Specifications 1888-378-2329 F 866-503-3996 Sensing Element Photoelectric - Light Scattering Principle Canada Storage & Operating Air Velocity Range: 0 to 5,000 ft/mm (0 to 25.39 m/s); Humidity: 0 to 93% 15193762430 . Environment RH, Non-Condensing Operating Temp: 32°F to 120°F (0°C to 490C); Stor- r 519 376 7258 age Temp: -4°F to 140°F (-20°Cto 60°C) Asia Sensitivity Range UU/ULC -0.67% t03.77% obscuration/foot T 852 2907 8108 User Selected Alarm Most Sensitive: 1.0%/ft.; More Sensitive: 2.0%/ft.; Normal: 2.5%/ft.; Less F 852 2142 5063 Sensitivity Settings Sensitive: 3.0%/ft.; Least Sensitive: 3.5%/ft. Pre-alarm Sensitivity 5% increments, allowing up to 20 pre-alarm settings Australia T 613 9259 4700 Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal) F 613 9259 4799 Operating Current Quiescert 45pA @ 19 V; Alarrh: 45pA @ 19 V Emergency Stand-alone Alarm Mode: 18mA Pulse Current: 100 pA 1100 msecl; During Communi- Europe cation: 9 mA max. 13227251120 F 322 72186 13 .......................... ...._._-_....1.-_-_._.___ ........._ .........................._. ......... ........ .._. Construction & Finish -- High Impact Engineering Polymer White Compatible Mounting SIGA-SB Standard Base, SIGA-RB Relay Base, SIGA-113 Isolator Bose, SIGA- Latin Americo Bases A84, SIGA-AB4G Audible Bases T 305 593 4301 LED Operation On-board Green LED - Flashes when polled; On-board Red LED - Hashes F 305 593 4300 when in alarm Both LEDs - Glow steady when in alarm (stand-alone) www.gesecurity.com Compatible Remote Red LED (model SlGA-LED Hashes when in alarm Compatibility Use With; SIGNATURE Loop Controller © 2006 General Electric Company Address Requirements Uses one Device Address - ............- All Rights Reserved Agency Listings UL, ULC, MEA, CSFM UL Listed Spacing 30 ft Signature Series is a Trademark of GE Security, Ordering Information • Catalog Description Ship Wt. Number lbs (kg) SIGA-PS Intelligent Photoelectric Detector - UL/ULC Listed 0.5(.23) Accessories . .. . . . . . .., . .. SIG Detector Mounting Base - Standard SIGA-SB4 4-inch Detector Mounting Base c/w SIGA-TS4 Trim Skirt SIGA-RB Detector Mounting Bose w/Relay SIGA-RB4 4-inch Detector Mounting Base w/Relay, c/w SIGA-TS4 Trim Skirt 0.2 1.09) SIGA-18 Detector Mounting Base w/Fault Isolator SIGA-I84 4-inch Detector Mounting Base w/ Fault Isolator, c/w SIGA-TS4 Trim Skirt SIGA-LED Remote Alarm LED SIGA-AB4G Audible (Sounder) Base .3(0.15) SIGA-TS4 Trim Skirt (supplied with 4-inch bases) .1 f.04) O imagination at work Data Sheet 85001-0269 Issue 6 Not to be used for installation purposes. Page 4 of 4 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-1657:126 Page 1 of 1 CATEGORY: Photoelectric Smoke Detector ICAL i FIRE M5 LISTEE: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 FAX 941) 308-8123 DESIGN: Models SIGA-PS and SlGA-PHS photoelectric smoke detectors. Model SIGA-PHS employs an integral 135°F fixed temperature heat sensor. This heat sensor is a supplementary device to the smoke detector and is not approved as a required heat detector. Refer to listee's printed data sheet for additional detailed product description, installation and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with listee's listed fire alarm control units and Model SIGA Series bases (CSFM Listing No. 7300-1657:120). Model SlGA-PS may be suitable for installation directly in the duct with the velocity range from 0-5000 feet/mm. NOTE: 1. Model SlGA-PHS is not intended for use in lieu of a required heat detector. 2. Formerly 7272-1591:126 and 7272-1388:186 08-15-05 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or ;•• recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. Date Issued: JULY 1, 2009 Listing Expires June 30, 2010 Authorized By: FRANCIS MATEO, Program Coordinator S Fire Engineering Division I CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1651:120 Page 1 of I CATEGORY: Misc. Devices/Control Unit Accessories LISTEE: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202 Contact: Jewell Micochero (941) 739-4358 FAX (941) 308-8123 DESIGN: Detector Bases. Refer to listee's data sheet for detailed product description and operational considerations. Base models are as follow: BASES 5963B, 5964 BIBR 624113-002, 624913-001 6251, 6251B-001A,-001, -002, -003, -004, 6251B-100, -200, -R100, -R200 and 6251-2 Models 6251 B-001, -002, -003 and -004 suitable for releasing device service. P-847674-0022, -0024, -0042, -0043, -0044, -0045, -0046, -0047 SlGA-SB, -SB4, -RB, -RB4, -lB, -I134 and —AB4 The —RB series are suitable for releasing device service. Model AB4G-SB surface mount back box for use with listee's SlGA series sounder bases. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as mounting bases for use with separately listed compatible detectors and fire alarm control units. Refer to listee's Installation Instruction Manual for details. NOTE: Formerly 7300-1591:120 and 7300-1388:170 08-15--05 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other suitable information sources. 5 Date Issued: JULY 1, 2009 Listing Expires June 30, 2010 Authorized By: FRANCIS MATEO, Program Coordinator Fire Engineering Division S S