HomeMy WebLinkAbout2173 SALK AVE; ; AS090033; PermitCity of Carlsbad
Sprinkler Permit
Permit No: AS090033
Job Address: 2173 SALK AV Status: ISSUED
Permit Type: SPRINK Applied 4/24/2009
Parcel No: 2120210200 Approved: 4/24/2009
Lot #: 0
Reference No.: Issued: 4/24/2009
PC #: Inspector:
Project Title: PACIFIC BUSINESS CENTER T.I. FIRE SPRINKLER PLAN
CHECK & INSPECTIONS
Applicant:
WEST COAST FIRE PROTECTION
271 ROYMAR RD
SUITE F
OCEANSIDE, CA
(760)754-8472
Owner:
RIO SD PLAZA II MASTER LLC
C/O NEWPORT NATIONAL
CORPORATION
1525 FARADAY AVE #100
CARLSBAD CA
Fees ($) Add'I Fees ($) Total ($) Balance ($)
130 0 130 0
WEST COAST FIRE PROTECTION
271 ROYMAR ROAD SUITE F
OCEANSIDE,CA 92054
HYDRAULIC CALCULATIONS
FOR
Ventana Real 2173 Salk
LARGE ORIFICE PROOF CALCULATION
FILE NUMBER:
DATE: APR 23, 2009
-DESIGN DATA-
OCCUPANCY CLASSIFICATION: LIGHT HAZARD
DENSITY: .10 gpm/sq. ft.
AREA OF APPLICATION: CORRIDOR 6 SPRINKLERS sq. ft.
COVERAGE PER SPRINKLER: 400 sq. ft. MAX
NUMBER OF SPRINKLERS CALCULATED: 6 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 247.5 gpm
TOTAL WATER REQUIRED (including hose) : 347.4 gpm
FLOW AND PRESSURE (@ BOR) : 247.4 gpm @ 30.8 psi
EXISTING SYSTEM FLOW DEMAND 332.6 gpm @ 44.84 psi
SPRINKLER ORIFICE SIZE: LARGE ORIFICE
NAME OF CONTRACTOR: WEST COAST FIRE PROTECTION
DESIGN/LAYOUT BY: DAN AMATO
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 110.0 100.0 1250.0 109.1 347.4 36.5
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE 347.4 GPM
TOTAL HOSE STREAM ALLOWANCE AT SOURCE 100.0 GPM
OTHER HOSE STREAM ALLOWANCES 0.0 GPM
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 247.4 GPM
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 24.0 K=14.00 8.2 40.1
1A 24.0 K=14.00 8.2 40.0
2 24.0 K=14.00 8.6 41.0
3 24.0 K=14.00 8.6 41.0
4 24.0 K=14.00 8.9 41.9
5 24.0 K=14.00 9.7 43.5
6 26.0 - - - - 13.1 - - -
6A 26.0 - - - - 13.0 - - -
7 26.0 - - - - 14.5 - - -
8 26.0 - - - - 14.5 - - -
9 26.0 - - - - 14.6 - - -
10 26.0 - - - - 14.6 - - -
A 26.0 - - - - 15.0 - - -
Al 26.0 - - - - 15.0 - - -
A2 26.0 - - - - 15.0 - - -
A3 26.0 - - - - 15.0 - - -
A4 26.0 - -• - - 15.0 - - -
A5 26.0 - - - 15.0 - - -
A6 26.0 - - - - 15.1 - - -
A7 26.0 - - - - 15.1 - - -
A8 26.0 - - - - 15.2 - - -
A9 26.0 - - - - 15.4 - - -
A10 26.0 - - - - 15.5 - - -
All 26.0 - - - - 15.6 - - -
Al2 26.0 - - - - 15.7 - - -
A13 26.0 - - - - 15.8 - - -
A14 26.0 - - - - 15.8 - - -
A15 26.0 - - - - 15.9 - - -
A16 26.0 - - - - 15.9 - - -
A17 26.0 - - - 16.0 - - -
A18 26.0 - - - - 16.0 - - -
A19 26.0 - - - - 16.0 - - -
A20 26.0 - - - - 16.0 - - -
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
NODE ANALYSIS DATA
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
A21 26.0 - - - - 16.0 - - -
A22 26.0 - - - - 16.0 - - -
31 26.0 - - - - 15.4 - - -
32 26.0 - - - - 15.4 - - -
33 26.0 - - - - 15.4 - - -
B4 26.0 - - - - 15.5 - - -
B5 26.0 - - - - 15.5 - - -
B6 26.0 - - - - 15.5 - - -
B7 26.0 - - - - 15.5 - - -
B8 26.0 - - - - 15.5 - - -
B9 26.0 - - - - 15.6 - - -
B10 26.0 - - - - 15.6 - - -
311 26.0 - - - - 15.7 - - -
B12 26.0 - - - - 15.7 - - -
813 26.0 - - - - 15.8 - - -
B14 26.0 - - - - 15.9 - - -
815 26.0 - - - - 15.9 - - -
816 26.0 - - - - 16.0 - - -
317 26.0 - - - - 16.1 - - -
B18 26.0 - - - - 16.2 - - -
B19 26.0 - - - - 16.3 - - -
320 26.0 - - - - 16.4 - - -
B21 26.0 - - - - 16.4 - - -
B22 26.0 - - - - 16.4 - - -
323 26.0 - - - - 16.4 - - -
C 26.0 - - - - 16.4 - - -
TOR 13.0 - - - - 25.2 - - -
BOR 0.5 - - - - 30.8 - - -
Ui 0.0 - - - - 31.1 - - -
U2 0.0 - - - - 31.3 - - -
BF1 6.0 - - - - 28.8 - - -
BF2 6.0 - - - - 33.8 - - -
U3 0.0 - - - - 36.4 - - -
SOURCE 0.0 SOURCE 36.5 247.4
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
PIPE DATA
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 1 -9.8 1.536 PL 78.00 PF 0.5
A 26.0 0.0 15.0 0.0 1.7 120 FTG T PE 0.0
31 26.0 0.0 15.4 0.0 0.005 TL 84.36 PV
Pipe: 2 -9.8 1.536 PL 78.00 PP 0.5
Al 26.0 0.0 15.0 0.0 1.7 120 FTG T PE 0.0
B2 26.0 0.0 15.4 0.0 0.005 TL 84.36 PV
Pipe: 3 -9.9 1.536 PL 78.00 PP 0.5
A2 26.0 0.0 15.0 0.0 1.7 120 FTG T PE 0.0
B3 26.0 0.0 15.4 0.0 0.006 TL 84.36 PV
Pipe: 4 -40.1 1.191 PL 6.00 PF 5.8
1 24.0 14.0 8.2 40.1 11.6 120 FTG 2ET PE -0.9
6 26.0 0.0 13.1 0.0 0.254 TL 22.70 PV
Pipe: 5 51.5 1.536 PL 9.33 PP 1.8
A3 26.0 0.0 15.0 0.0 8.9 120 FTG T PE 0.0
6 26.0 0.0 13.1 0.0 0.117 TL 15.69 PV
Pipe: 5a -40.0 1.191 PL 6.00 PF 5.7
1A 24.0 14.0 8.2 40.0 11.5 120 FTG 2ET PE -0.9
6A 26.0 0.0 13.0 0.0 0.253 TL 22.70 PV
Pipe: 6 11.4 1.536 PL 14.00 PF 0.1
6 26.0 0.0 13.1 0.0 2.0 120 FTG ---- PE 0.0
6A 26.0 0.0 13.0 0.0 0.007 TL 14.00 PV
Pipe: 5A -28.6 1.536 PL 55.00 PF 2.4
6A 26.0 0.0 13.0 0.0 5.0 120 FTG T PE 0.0
34 26.0 0.0 15.5 0.0 0.039 TL 61.36 PV
Pipe: 6 -41.0 1.191 PL 9.00 PF 6.8
2 24.0 14.0 8.6 41.0 11.8 120 FTG 2ET PE -0.9
7 26.0 0.0 14.5 0.0 0.264 TL 25.70 PV
Pipe: 7 25.3 1.536 PL 9.33 PF 0.5
A4 26.0 0.0 15.0 0.0 4.4 120 FTG T PE 0.0
7 26.0 0.0 14.5 0.0 0.031 TL 15.69 PV
Pipe: 7A -15.7 1.536 PL 69.00 PF 1.0
7 26.0 0.0 14.5 0.0 2.7 120 FTG T PE 0.0
B5 26.0 0.0 15.5 0.0 0.013 TL 75.36 PV
Pipe: 8 25.4 1.536 PL 9.33 PF 0.5
A5 26.0 0.0 15.0 0.0 4.4 120 FTG T PE 0.0
8 26.0 0.0 14.5 0.0 0.032 TL 15.69 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 9 -41.0 1.191 PL 9.00 PF 6.8
3 24.0 14.0 8.6 41.0 11.8 120 FTG 2ET PE -0.9
8 26.0 0.0 14.5 0.0 0.265 TL 25.70 PV
Pipe: 10 -15.6 1.536 PL 69.00 PF 1.0
8 26.0 0.0 14.5 0.0 2.7 120 FTG T PE 0.0
B6 26.0 0.0 15.5 0.0 0.013 TL 75.36 PV
Pipe: 11 -9.2 1.536 PL 78.00 PF 0.4
A6 26.0 0.0 15.1 0.0 1.6 120 FTG 2T PE 0.0
87 26.0 0.0 15.5 0.0 0.005 TL 90.72 PV
Pipe: 12 26.4 1.536 PL 9.33 PF 0.5
A7 26.0 0.0 15.1 0.0 4.6 120 FTG T PE 0.0
9 26.0 0.0 14.6 0.0 0.034 TL 15.69 PV
Pipe: 13 -41.9 1.191 PL 7.00 PF 6.5
4 24.0 14.0 8.9 41.9 12.1 120 FTG 2ET PE -0.9
9 26.0 0.0 14.6 0.0 0.275 TL 23.70 PV
Pipe: 14 -15.5 1.536 PL 69.00 PF 1.0
9 26.0 0.0 14.6 0.0 2.7 120 FTG T PE 0.0
88 26.0 0.0 15.5 0.0 0.013 TL 75.36 PV
Pipe: 15 28.0 1.536 PL 9.33 PF 0.6
A8 26.0 0.0 15.2 0.0 4.8 120 FTG T PE 0.0
10 26.0 0.0 14.6 0.0 0.038 TL 15.69 PV
Pipe: 16 -43.5 1.191 PL 3.00 PF 5.8
5 24.0 14.0 9.7 43.5 12.5 120 FTG 2ET PE -0.9
10 26.0 0.0 14.6 0.0 0.295 TL 19.70 PV
Pipe: 17 -15.5 1.536 PL 69.00 PF 1.0
10 26.0 0.0 14.6 0.0 2.7 120 FTG T PE 0.0
39 26.0 0.0 15.6 0.0 0.013 TL 75.36 PV
Pipe: 18 -7.6 1.536 PL 78.00 PF 0.3
A9 26.0 0.0 15.4 0.0 1.3 120 FTG ---- PE 0.0
310 26.0 0.0 15.6 0.0 0.003 TL 78.00 PV
Pipe: 19 -5.4 1.536 PL 90.00 PF 0.2
A10 26.0 0.0 15.5 0.0 0.9 120 FTG 43 PE 0.0
Bli 26.0 0.0 15.7 0.0 0.002 TL 102.72 PV
Pipe: 20 -5.0 1.536 PL 78.00 PF 0.1
All 26.0 0.0 15.6 0.0 0.9 120 FTG ---- PE 0.0
B12 26.0 0.0 15.7 0.0 0.002 TL 78.00 PV
Pipe: 21 -3.2 1.536 PL 90.00 PF 0.1
Al2 26.0 0.0 15.7 0.0 0.6 120 FTG 4E PE 0.0
B13 26.0 0.0 15.8 0.0 0.001 TL 102.72 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 6
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 22 -30.4 4.310 PL 78.00 PF 0.0
A13 26.0 0.0 15.8 0.0 0.7 120 FTG 2T PE 0.0
B14 26.0 0.0 15.9 0.0 0.000 TL 133.75 PV
Pipe: 23 -3.2 1.536 PL 78.00 PF 0.1
A14 26.0 0.0 15.8 0.0 0.5 120 FTG ---- PE 0.0
B15 26.0 0.0 15.9 0.0 0.001 TL 78.00 PV
Pipe: 24 -4.5 1.536 PL 78.00 PF 0.1
A15 26.0 0.0 15.9 0.0 0.8 120 FTG ---- PE 0.0
B16 26.0 0.0 16.0 0.0 0.001 TL 78.00 PV
Pipe: 25 -5.8 1.536 PL 78.00 PF 0.2
A16 26.0 0.0 15.9 0.0 1.0 120 FTG ---- PE 0.0
B17 26.0 0.0 16.1 0.0 0.002 TL 78.00 PV
Pipe: 26 -7.1 1.536 PL 78.00 PF 0.2
A17 26.0 0.0 16.0 0.0 1.2 120 FTG ---- PE 0.0
318 26.0 0.0 16.2 0.0 0.003 TL 78.00 PV
Pipe: 27 -8.5 1.536 PL 78.00 PF 0.3
A18 26.0 0.0 16.0 0.0 1.5 120 FTG ---- PE 0.0
819 26.0 0.0 16.3 0.0 0.004 TL 78.00 PV
Pipe: 28 -9.6 1.536 PL 78.00 PF 0.4
A19 26.0 0.0 16.0 0.0 1.7 120 FTG ---- PE 0.0
320 26.0 0.0 16.4 0.0 0.005 TL 78.00 PV
Pipe: 29 -9.3 1.536 PL 78.00 PF 0.4
A20 26.0 0.0 16.0 0.0 1.6 120 FTG ---- PE 0.0
B21 26.0 0.0 16.4 0.0 0.005 TL 78.00 PV
Pipe: 30 -9.2 1.536 PL 78.00 PF 0.4
A21 26.0 0.0 16.0 0.0 1.6 120 FTG ---- PE 0.0
322 26.0 0.0 16.4 0.0 0.005 TL 78.00 PV
Pipe: 31 -9.1 1.536 PL 78.00 PF 0.4
A22 26.0 0.0 16.0 0.0 1.6 120 FTG ---- PE 0.0
B23 26.0 0.0 16.4 0.0 0.005 TL 78.00 PV
Pipe: 32 9.8 3.314 PL 12.00 PF 0.0
A 26.0 0.0 15.0 0.0 0.4 120 FTG ---- PE 0.0
Al 26.0 0.0 15.0 0.0 0.000 TL 12.00 PV
Pipe: 33 19.6 3.314 PL 12.00 PF 0.0
Al 26.0 0.0 15.0 0.0 0.7 120 FTG ---- PE 0.0
A2 26.0 0.0 15.0 0.0 0.000 TL 12.00 PV
Pipe: 34 29.5 3.314 PL 12.00 PF 0.0
A2 26.0 0.0 15.0 0.0 1.1 120 FTG ---- PE 0.0
A3 26.0 0.0 15.0 0.0 0.001 TL 12.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 35 -22.1 3.314 PL 12.00 PF 0.0
A3 26.0 0.0 15.0 0.0 0.8 120 FTG ---- PE 0.0
A4 26.0 0.0 15.0 0.0 0.001 TL 12.00 PV
Pipe: 36 -47.4 3.314 PL 12.00 PF 0.0
A4 26.0 0.0 15.0 0.0 1.8 120 FTG ---- PE 0.0
A5 26.0 0.0 15.0 0.0 0.002 TL 12.00 PV
Pipe: 37 -72.7 3.314 PL 12.00 PF 0.1
A5 26.0 0.0 15.0 0.0 2.7 120 FTG ---- PE 0.0
A6 26.0 0.0 15.1 0.0 0.005 TL 12.00 PV
Pipe: 38 -63.6 3.314 PL 12.00 PF 0.0
A6 26.0 0.0 15.1 0.0 2.4 120 FTG ---- PE 0.0
A7 26.0 0.0 15.1 0.0 0.004 TL 12.00 PV
Pipe: 39 -90.0 3.314 PL 12.00 PF 0.1
A7 26.0 0.0 15.1 0.0 3.3 120 FTG ---- PE 0.0
A8 26.0 0.0 15.2 0.0 0.008 TL 12.00 PV
Pipe: 40 -117.9 3.314 PL 12.00 PF 0.2
A8 26.0 0.0 15.2 0.0 4.4 120 FTG ---- PE 0.0
A9 26.0 0.0 15.4 0.0 0.013 TL 12.00 PV
Pipe: 41 -110.4 3.314 PL 12.00 PF 0.1
A9 26.0 0.0 15.4 0.0 4.1 120 FTG ---- PE 0.0
A10 26.0 0.0 15.5 0.0 0.011 TL 12.00 PV
Pipe: 42 -105.0 3.314 PL 12.00 PF 0.1
A10 26.0 0.0 15.5 0.0 3.9 120 FTG ---- PE 0.0
All 26.0 0.0 15.6 0.0 0.010 TL 12.00 PV
Pipe: 43 -100.0 3.314 PL 12.00 PF 0.1
All 26.0 0.0 15.6 0.0 3.7 120 FTG ---- PE 0.0
Al2 26.0 0.0 15.7 0.0 0.009 TL 12.00 PV
Pipe: 44 -96.8 3.314 PL 10.00 PF 0.1
Al2 26.0 0.0 15.7 0.0 3.6 120 FTG ---- PE 0.0
A13 26.0 0.0 15.8 0.0 0.009 TL 10.00 PV
Pipe: 45 -66.4 3.314 PL 4.00 PF 0.0
A13 26.0 0.0 15.8 0.0 2.5 120 FTG ---- PE 0.0
A14 26.0 0.0 15.8 0.0 0.004 TL 4.00 PV
Pipe: 46 -63.2 3.314 PL 12.00 PF 0.0
A14 26.0 0.0 15.8 0.0 2.4 120 FTG ---- PE 0.0
A15 26.0 0.0 15.9 0.0 0.004 TL 12.00 PV
Pipe: 47 -58.6 3.314 PL 12.00 PF 0.0
A15 26.0 0.0 15.9 0.0 2.2 120 FTG ---- PE 0.0
A16 26.0 0.0 15.9 0.0 0.004 TL 12.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 8
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Calc
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 48 -52.8 3.314 PL 12.00 PF 0.0
A16 26.0 0.0 15.9 0.0 2.0 120 FTG ---- PE 0.0
A17 26.0 0.0 16.0 0.0 0.003 TL 12.00 PV
Pipe: 49 -45.7 3.314 PL 12.00 PF 0.0
A17 26.0 0.0 16.0 0.0 1.7 120 FTG ---- PE 0.0
A18 26.0 0.0 16.0 0.0 0.002 TL 12.00 PV
Pipe: 50 -37.2 3.314 PL 12.00 PF 0.0
A18 26.0 0.0 16.0 0.0 1.4. 120 FTG ---- PE 0.0
A19 26.0 0.0 16.0 0.0 0.002 TL 12.00 PV
Pipe: 51 -27.6 3.314 PL 12.00 PF 0.0
A19 26.0 0.0 16.0 0.0 1.0 120 FTG ---- PE 0.0
A20 26.0 0.0 16.0 0.0 0.001 TL 12.00 PV
Pipe: 52 -18.3 3.314 PL 12.00 PF 0.0
A20 26.0 0.0 16.0 0.0 0.7 120 FTG ---- PE 0.0
A21 26.0 0.0 16.0 0.0 0.000 TL 12.00 PV
Pipe: 53 -9.1 3.314 PL 12.00 PF 0.0
A21 26.0 0.0 16.0 0.0 0.3 120 FTG ---- PE 0.0
A22 26.0 0.0 16.0 0.0 0.000 TL 12.00 PV
Pipe: 54 -9.8 4.310 PL 12.00 PF 0.0
Bi 26.0 0.0 15.4 0.0 0.2 120 FTG ---- PE 0.0
B2 26.0 0.0 15.4 0.0 0.000 TL 12.00 PV
Pipe: 55 -19.6 4.310 PL 12.00 PF 0.0
B2 26.0 0.0 15.4 0.0 0.4 120 FTG ---- PE 0.0
B3 26.0 0.0 15.4 0.0 0.000 TL 12.00 PV
Pipe: 56 -29.5 4.310 PL 12.00 PF 0.0
B3 26.0 0.0 15.4 0.0 0.6 120 FTG ---- PE 0.0
B4 26.0 0.0 15.5 0.0 0.000 TL 12.00 PV
Pipe: 57 -58.1 4.310 PL 12.00 PF 0.0
B4 26.0 0.0 15.5 0.0 1.3 120 FTG ---- PE 0.0
B5 26.0 0.0 15.5 0.0 0.001 TL 12.00 PV
Pipe: 58 -73.7 4.310 PL 12.00 PF 0.0
B5 26.0 0.0 15.5 0.0 1.6 120 FTG ---- PE 0.0
B6 26.0 0.0 15.5 0.0 0.001 TL 12.00 PV
Pipe: 59 -89.4 4.310 PL 12.00 PF 0.0
B6 26.0 0.0 15.5 0.0 2.0 120 FTG ---- PE 0.0
B7 26.0 0.0 15.5 0.0 0.002 TL 12.00 PV
Pipe: 60 -98.6 4.310 PL 12.00 PF 0.0
B7 26.0 0.0 15.5 0.0 2.2 120 FTG ---- PE 0.0
B8 26.0 0.0 15.5 0.0 0.003 TL 12.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 9
DATE: 4/23/2009 C:\HASS78\VENTANA..SDF
JOB TITLE: Ventana Real Large Orifice Proof Calc
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 61 -114.0 4.310 PL 12.00 PF 0.0
38 26.0 0.0 15.5 0.0 2.5 120 FTG ---- PE 0.0
39 26.0 0.0 15.6 0.0 0.003 TL 12.00 PV
Pipe: 62 -129.6 4.310 PL 12.00 PF 0.1
39 26.0 0.0 15.6 0.0 2.8 120 FTG ---- P3 0.0
310 26.0 0.0 15.6 0.0 0.004 TL 12.00 PV
Pipe: 63 -137.1 4.310 PL 12.00 PF 0.1
310 26.0 0.0 15.6 0.0 3.0 120 FTG ---- PE 0.0
311 26.0 0.0 15.7 0.0 0.005 TL 12.00 PV
Pipe: 64 -142.5 4.310 PL 12.00 PF 0.1
Bil 26.0 0.0 15.7 0.0 3.1 120 FTG ---- PE 0.0
812 26.0 0.0 15.7 0.0 0.005 TL 12.00 PV
Pipe: 65 -147.5 4.310 PL 12.00 PF 0.1
B12 26.0 0.0 15.7 0.0 3.2 120 FTG ---- PE 0.0
313 26.0 0.0 15.8 0.0 0.005 TL 12.00 PV
Pipe: 66 -150.7 4.310 PL 10.00 PF 0.1
B13 26.0 0.0 15.8 0.0 3.3 120 FTC ---- PE 0.0
314 26.0 0.0 15.9 0.0 0.006 TL 10.00 PV
Pipe: 67 -181.1 4.310 PL 4.00 PF 0.0
314 26.0 0.0 15.9 0.0 4.0 120 FTG ---- PE 0.0
315 26.0 0.0 15.9 0.0 0.008 TL 4.00 PV
Pipe: 68 -184.3 4.310 PL 12.00 PF 0.1
B15 26.0 0.0 15.9 0.0 4.1 120 FTG ---- PE 0.0
316 26.0 0.0 16.0 0.0 0.008 TL 12.00 PV
Pipe: 69 -188.8 4.310 PL 12.00 PF 0.1
316 26.0 0.0 16.0 0.0 4.2 120 FTG ---- PE 0.0
317 26.0 0.0 16.1 0.0 0.008 TL 12.00 PV
Pipe: 70 -194.7 4.310 PL 12.00 PF 0.1
817 26.0 0.0 16.1 0.0 4.3 120 FTG ---- PE 0.0
B18 26.0 0.0 16.2 0.0 0.009 TL 12.00 PV
Pipe: 71 -201.8 4.310 PL 12.00 PF 0.1
318 26.0 0.0 16.2 0.0 4.4 120 FTG ---- PE 0.0
319 26.0 0.0 16.3 0.0 0.010 TL 12.00 PV
Pipe: 72 -210.3 4.310 PL 10.00 PF 0.1
819 26.0 0.0 16.3 0.0 4.6 120 FTG ---- PE 0.0
C 26.0 0.0 16.4 0.0 0.010 TL 10.00 PV
Pipe: 72A 37.2 3.314 PL 2.00 PF 0.0
C 26.0 0.0 16.4 0.0 1.4 120 FTG ---- PE 0.0
B20 26.0 0.0 16.4 0.0 0.002 TL 2.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 10
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Caic
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 73 27.6 3.314 PL 12.00 PF 0.0
B20 26.0 0.0 16.4 0.0 1.0 120 FTG ---- PE 0.0
B21 26.0 0.0 16.4 0.0 0.001 TL 12.00 PV
Pipe: 74 18.3 3.314 PL 12.00 PF 0.0
B21 26.0 0.0 16.4 0.0 0.7 120 FTG ---- PE 0.0
322 26.0 0.0 16.4 0.0 0.000 TL 12.00 PV
Pipe: 75 9.1 3.314 PL 12.00 PF 0.0
322 26.0 0.0 16.4 0.0 0.3 120 FTG ---- PE 0.0
B23 26.0 0.0 16.4 0.0 0.000 TL 12.00 PV
Pipe: 76 -247.5 4.310 PL 98.00 PF 3.1
C 26.0 0.0 16.4 0.0 5.4 120 FTG 73T PE 5.6
TOR 13.0 0.0 25.2 0.0 0.014 TL 223.43 PV
Pipe: 77 -247.5 4.310 PL 12.50 PF 0.2
TOR 13.0 0.0 25.2 0.0 5.4 120 FTG ---- PE 5.4
BOR 0.5 0.0 30.8 0.0 0.014 TL 12.50 PV
Pipe: 78 -247.5 6.044 PL 10.00 PF 0.1
BOR 0.5 0.0 30.8 0.0 2.8 140 FTG BE PE 0.2
Ui 0.0 0.0 31.1 0.0 0.002 TL 41.39 PV
Pipe: 79 -247.5 6.090 PL 150.00 PF 0.3
Ui 0.0 0.0 31.1 0.0 2.7 150 FTG ---- PE 0.0
U2 0.0 0.0 31.3 0.0 0.002 TL 150.00 PV
Pipe: 80 -247.5 6.044 PL 6.00 PF 0.0
U2 0.0 0.0 31.3 0.0 2.8 140 FTG ---- PE -2.6
BFi 6.0 0.0 28.8 0.0 0.002 TL 6.00 PV
Pipe: 81 FIXED PRESSURE LOSS DEVICE
BF2 6.0 0.0 33.8 0.0 5.0 psi, 247.5 gpm
BF1 6.0 0.0 28.8 0.0
Pipe: 82 -247.5 6.044 PL 6.00 PF 0.0
3F2 6.0 0.0 33.8 0.0 2.8 140 FTG ---- PE 2.6
U3 0.0 0.0 36.4 0.0 0.002 TL 6.00 PV
Pipe: 83 -247.4 6.090 PL 60.00 PF 0.1
U3 0.0 0.0 36.4 0.0 2.7 150 FTG ---- PE 0.0
SOURCE 0.0 SRCE 36.5 (N/A) 0.002 TL 60.00 PV
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 11
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Calc
NOTES (HASS)
Calculations were performed by the HASS 7.9 computer program
under license no. 27081246 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
The system has been calculated to provide an average
imbalance at each node of 0.003 gpm and a maximum
imbalance at any node of 0.193 gpm.
Total pressure at each node is used in balancing the system.
Maximum water velocity is 12.5 ft/sec at pipe 16.
PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: * MATERIAL: S40 HWC: 120
Diameter Equivalent Fitting Lengths in Feet
(in) E T L C B G A D N
Eli Tee LngEli ChkVlv BfyVlv GatViv AimChk DPViv NPTee
1.191 3.71 9.28 3.71 9.28 11.13 1.86 18.56 18.56 9.28
1.536 3.18 6.36 1.59 7.16 4.77 0.80 7.95 7.95 6.36
3.314 10.19 21.84 7.28 23.29 14.56 1.46 18.93 18.93 21.84
4.310 13.94 27.87 8.36 30.66 16.72 2.79 27.87 27.87 27.87
6.044 13.77 29.50 8.85 31.46 9.83 2.95 27.53 27.53 29.50
6.090 14.28 30.61 9.18 32.65 10.20 3.06 28.57 28.57 30.61
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 12
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Calc
0 0 0
0 0
H
0 -
0
I:Ll
0 C
(14
0 0 0 0 0 0 0
H 0 0 0 0 0 0 0
c.l 0 C'J H
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 13
DATE: 4/23/2009 C:\HASS78\VENTANA.SDF
JOB TITLE: Ventana Real Large Orifice Proof Calc
WATER SUPPLY CURVE
120+
110*\\0\\\
I \\\\\\\
I \\\\\\\
\\\\\\
100+ * <-100.0 psi @ 1250 gpm
I Flow Test Point
90+
P 80+
R
E I
S I
S 70+
U I
R
E
60+
( I
P
S
I 50+
) I
40+
Ix
30+
20+ LEGEND
I if
I X = Required Water Supply
I 36.47 psi @ 347.4 gpm
10+ if
I 0 = Available Water Supply
109.06 psi @ 347.4 gpm
IT
+------+--------+--------+---------+-----------+
400 600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
tqC0 /Fire & Building
I Products
Technical Services: Tel: (800) 381-9312/ Fax: (800) 791-5500
Series EC-1 I & EC-14 - 112 and 140 K-factor
Extended Coverage (Light and Ordinary Hazard)
Upright, Pendent, and Rec. Pendent Sprinklers
General
Description
The Series EC-11 and EC-14 Ex-
tended Coverage Upright and Pendent
Sprinklers are decorative glass bulb
sprinklers designed for use in light or
ordinary hazard occupancies. They
are intended for use in automatic
sprinkler systems designed in accord-
ance with standard installation rules
(e.g., NFPA 13) for a maximum cover-
age area of 400 ft2 (37,2 m2), as com-
pared to the maximum coverage area
of 130 ft2 (12,1 m2) for standard cover-
age sprinklers used in ordinary haz-
ard occupancies or 225 ft2 (20,6 m2)
for standard coverage sprinklers used
in light hazard occupancies.
The Series EC-11 and EC-14 Sprin-
klers feature a UL and C-UL Listing
that permits their use with unob-
structed or non-combustible ob-
structed ceiling construction as de-
fined and permitted by NFPA 13, as
well as a specific application listing for
use under concrete tees.
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers have
been fire tested to compare their per-
formance to that of standard coverage
spray sprinklers. These tests have
shown that the protection provided is
equal to or more effective than stand-
ard coverage spray sprinklers.
IMPORTANT
Always refer to Technical Data
Sheet TFP 700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these corrosion resistant coatings
for any given corrosive environment.
The effects of ambient temperature,
concentration of chemicals, and
gas/chemical velocity, should be con-
sidered, as a minimum, along with the
corrosive nature of the chemical to
which the sprinklers will be exposed.
WARNINGS
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
Impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
SEPTEMBER, 2004
Model/Sprinkler
Identification
Number
TY5137 - Upright, 11.2K
1Y5237 - Pendent, 11.2K
TY6137 - Upright, 14.0K
TY6237 - Pendent,14.OK
TY5137 is a redesignation for C5137,
G1894, and S2510.
TV5237 is a redesignation for C5237,
G1893, and S2511.
TY6137 is a redesignation for C6137,
G1896, and S2610.
TY6237 is a redesignation for C6237,
G1895, and S2611.
TFP22O
OZt c0
nm
Page 2 of 8
1 - Frame
Button
Sealing Assembly
Bulb
5 - Compression Screw
6 - Deflector*
* Temperature rating is
indicated on deflector
Pipe thread
connections per ISO
7/1 can be provided
on special request.
TFP22O
WRENCH 3/4* ** ESCUTCHEON PLATE
FLAT NPT SEATING SURFACE
NOMINAL MAKE-IN CROSS
UPRIGHT PENDENT SECTION
FIGURE 1
SERIES EC-Il AND EC-14 EXTENDED COVERAGE SPRINKLERS
11.2 K-FACTOR (TY5137) UPRIGHT AND (TY5237) PENDENT
14.0 K-FACTOR (TY6137) UPRIGHT AND (TY6237) PENDENT
SPRINKLER FINISH (See Note 5)
HAZARD TYPE TEMP. BULB NATURAL I CHROME WHITES LEAD
LIQUID BRASS PLATED I POLYESTER COATED
1350F/57'C Orange
LIGHT
UPRIGHT
K=11.2 (1Y5137)
PENDENT
1, 2, 3**, 4 155F/68°C Red
175°FI79C Yellow
Refer to Table B for
UL and C-UL
K=11.2 (57)
K=14.0 (TY6237)
1,2,4 1,2,4 200'F/93°C Green
286°F/141°C Blue
135°F/57°C Orange Sensitivity Rating
and
Refer to Table C for
REC. PENOENT
K=1 1.2 (TY5237)
1, 2,3,4
N/A 155FI68°C Red
175°F179°C Yellow FM K=14.0 (TY6237)
Sensitivity Rating With Style 30
Escutcheon
1, 2, 4 200°F/93'C Green
286°F/141°C Blue
UPRIGHT 135F/57'C Orange
ORDINARY
K=11.2(TY5137)
K=14.0 (TY6137)
and
1, 2, 3,4
1,2,3,4 155°F/68°C Red
175°F/79C Yellow
Refer to Table B for
UL and C-UL
Sensitivity Rating
PENDENT
K11.2 (TY5237)
K=14.0 (TY6237)
1, 2, 4 200°F/93'C Green
286'F/141 'C Blue
REC. PENOENT 135°F/57°C Orange and
Refer to Table C for
FM
Sensitivity Rating
c=i 1.2 (TY5237)
K=14.0 (TY6237)
With Style 40
1, 2, 4 N/A
155'F168°C Red
175°F/79°C Yellow
Escutcheon 200°F/93°C Green
NOTES:
11isted by Underwriters Laboratories, Inc. (UL).
21isted by Underwriters Laboratories, Inc. for use in Canada (C-UL).
Approved by Factory Mutual Research Corporation (FM).
Approved by the City of New York under MEA 177-03-E.
Where Polyester Coated or Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers.
*Frame and Deflector only. Listings and approvals apply to color (Special Order).
** Pendent Only.
N/A: Not Available
TABLE A, A, LABORATORY LISTINGS AND APPROVALS
TFP220 Page 3of8
LIGHT HAZARD
135°F 155°F 175°F 200°F 286°F
ORDINARY HAZARD
135°F 155°F 175°F 200°F 286°F
AREA STYLE
14x14 Up. orPend. - - - - - SR SR SR SR
14 x 14 Style 30 Recessed - - - - - SR SR SR SR
14 x 14 Style 40 Recessed - - - - - SR SR SR SR
16 x 16 Up. or Pend. OR* OR* OR* OR* OR* SR SR SR SR
16 x 16 Style 30 Recessed OR* OR* OR' OR* OR* SR SR SR SR
16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR
18x18 Up. orPend. OR OR* OR OR* OR* SR SR SR SR
18x18 Style 30 Recessed OR* OR OR* OR* OR* SR SR SR SR
18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR
20 x 20 Up. or Pend. OR* QIR° OR* SR* SR* SR SR SR SR
20 x 20 Style 30 Recessed OR* SR* QR* SR* SR* SR SR SR SR
20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A SR SR SR SR
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
* Does not apply to Upright K = 14.0
TABLE B
SENSITIVITY RATING FOR UL AND C-UL LISTING OF SERIES EC-1 1 OR EC-14 SPRINKLERS
(SEE TABLED FOR PERMITTED K-FACTOR(AREA COMBINATIONS)
LIGHT HAZARD ORDINARY HAZARD
135°F 155°F 175°F 200°F 286°F 135°F 155°F 175°F 200°F 286°F
AREA STYLE
14 x 14 Up. or Pend. - - - - - SR SR SR SR SR
14 x 14 Style 30 Recessed - - - - - N/A N/A N/A N/A N/A
14 x 14 Style 40 Recessed - - - - - N/A N/A N/A N/A N/A
16 x 16 Up. or Pend. OR* OR* N/A N/A N/A SR SR SR SR SR
16 x 16 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A
16 x 16 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
18 x 18 Up. or Pend. OR* OR* N/A N/A N/A SR SR SR SR SR
18 x 18 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A
18 x 18 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
20 x 20 Up. or Pend. QR* OR* N/A N/A N/A SR SR SR SR SR
20 x 20 Style 30 Recessed OR OR N/A N/A N/A N/A N/A N/A N/A N/A
20 x 20 Style 40 Recessed N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
OR: Quick Response
SR: Standard Response
N/A: Not Applicable
° Pendent Only
TABLE C
SENSITIVITY RATING FOR FM APPROVAL OF SERIES EC-1 1 OR EC-14 SPRINKLERS
(SEE FM LOSS PREVENTION DATA SHEET 2-8N FOR PERMITTED K-FACTOR/AREA COMBINATIONS)
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
SR
N/A
N/A
Page 4 of 8 TFP220
Operation 3.
Technical
Data
Approvals
UL and C-UL Listed. FM Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status. The approvals apply to the
service conditions indicated in the De-
sign Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficients
K = 11.2 GPM/psi'/2
(161,3 LPMIbar"2)
K = 14.0 GPMIpsi1'2
(201,6 LPM/bar112)
Temperature Ratings
135°F/570C to 286°F/1410C
Finish
Sprinkler: Refer to Table A
Recessed Escutcheon: White Coated,
Chrome Plated, and Brass Plated
Physical Characteristics
Frame .............Bronze
Button .............Bronze
Sealing Assembly ..........
Beryllium Nickel wfreflont
Bulb ........Glass (3 mm dia.)
Compression Screw .........
......Bronze
Deflector ............Brass
Patents
U.S.A. Patent Numbers 5,366,022;
5,579,846; 5,584,344; 5,609,211;
5,862,994; and 5,865,256.
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, which then allows the sprin-
kler to activate and flow water.
Design
Criteria
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers must only
be installed in accordance with the ap-
plicable UL and C-UL Listing or FM
Approval requirements as indicated
below. Only the Style 30 or 40 Re-
cessed Escutcheon is to be used for
recessed installation, as applicable
(Ref. Table A, B, and C).
UL and C-UL Listing
Requirements
The Series EC-1 I and EC-14 Sprin-
klers may be used for the coverage
areas shown in Table D, based on
maintaining the minimum specified
flow rate as a function of coverage
area and hazard group for all of the
sprinklers in the design area.
The Series EC-il and EC-14 Sprin-
klers are permitted to be used with
unobstructed or non-combustible
obstructed ceiling construction as
defined and permitted by NFPA 13.
For example:
Unobstructed, combustible or non--
combustible, ceiling construction
with a deflector to ceiling/roof deck
distance of 1 t 12 inches (25 to 300
MM).
Obstructed, non-combustible, ceil-
ing construction with a deflector lo-
cation below structural members of
1 to 6 inches (25 to 150 mm) and a
maximum deflector to ceiling/roof
deck distance of 22 inches (550
mm).
The Series EC-il and EC-14 Sprin-
klers having been specifically tested
and listed for non-combustible ob-
structed construction are permitted
to be used within trusses or bar joists
having non-combustible web mem-
bers greater than 1 inch (25.4 mm)
when applying the 4 times obstruc-
tion criteria rule defined under "Ob-
structions to Sprinkler Discharge
Pattern Development".
The minimum allowable spacing be-
tween the Series EC-li and EC-14
Sprinklers, to prevent cold solder-
ing, is 8 feet (2,4 m) for upright sprin-
klers and 9 feet (2,7 m) for pendent
sprinklers.
The Series EC-11 and EC-14 Sprin-
klers are to be installed in accord-
ance with all other requirements of
NFPA 13 for extended coverage up-
right and pendent sprinklers. For ex-
ample: obstructions to sprinkler dis-
charge, obstructions to sprinkler
pattern development, obstructions
to prevent sprinkler discharge from
reaching hazard, clearance to stor-
age, etc.
UL and C-UL Specific Application
Listing Requirements For
Installation Under Concrete Tees
The Series EC-11 and EC-14 Ex-
tended Coverage Upright and Pendent
Sprinklers (TV5137, TY5237, TY6137
& TY6237) have a UL and C-UL Spe-
cific Application Listing for use under
concrete tees when installed as fol-
lows:
The stems of the concrete tee con-
struction must spaced at less than
7.5 feet (2,3 m) on center but more
than 3 feet (0,9 m) on center. The
depth of the concrete tees must not
exceed 30 inches (762 mm). The
maximum permitted concrete tee
length is 32 feet (9,8 m); however,
where the concrete tee length ex-
ceeds 32 feet (9,8 m), non-combus-
tible baffles, equal in height to the
depth of the tees, can be installed so
that the space between the tees
does not exceed 32 feet (9,8 m) in
length.
The sprinkler deflectors are to be
located in a horizontal plane at or
above 1 inch (25,4 mm) below the
bottom of the concrete tee stems.
When the sprinkler deflectors are
located higher than a horizontal
plane 1 inch (251,4 mm) beneath the
bottom of the concrete tee stems,
the obstruction to sprinkler dis-
charge criteria requirements of
NFPA 13 for extended coverage up-
right sprinklers applies.
FM Approval
Requirements
The Series EC-11 and EC-14 Ex-
tended Coverage Sprinklers are to be
installed in accordance with the appli-
cable Factory Mutual Loss Prevention
Data Sheet for limited use in buildings
of specific roof construction and for the
protection of certain specific ordinary
hazard (non-storage and/or non-flam-
mable or combustible liquid) occupan-
cies. Information provided in the FM
Loss Prevention Data Sheets relate to,
but are not limited to, hydraulic design,
ceiling slope and obstructions, mini-
mum and maximum allowable spac-
ing, and deflector-to ceiling distance.
These criteria may differ from UL
and/or NFPA criteria, therefore the de-
signer should review and become fa-
miliar with Factory Mutual require-
ments before proceeding with design.
2-7/8" DIA.
(73,0 mm) 3/4' (19,1 mm
2-1/4" 01k _ 1/4" (6,4 mm)
(57,2 mm)
1/8"
-( I (3,2 mm)
MOUNTING
PLATE
1-3/8" (34,9 mm)
7/8" (22,2 mm)
5/8±1/4'
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
TFP22O
2-7/8' DIA.
1/2±1/8" (73,0 mm) 1/2" (12,7 mm)
(12,7±3,2 mm) 2-1/4" DIA. 1/4" (6,4 mm)
FACE OF (57,2 mm)
SPRINKLER -r 1/8"
FITTING (3,2 mm)
MOUNTING MOUNTING SURFACE PLATE
CLOSURE -
J 1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
FIGURE 2
SERIES EC-1 1 AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
Page 5 of 8
"FITTING SIDE"
TOWARDS SPRINKLER
FITTING
WRENCH
RECESS
(END "A")
FIGURE 4
W-TYPE 3 SPRINKLER
WRENCH
WRENCH -
RECESS -
WRENCH
HEX
FIGURE 5
W-TYPE 22 RECESSED
SPRINKLER WRENCH
FIGURE 3
SERIES EC-Il AND EC-14 RECESSED PENDENT SPRINKLER ASSEMBLY
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
DESCRIPTION AREA
TY5137 (K=11.2) UPRIGHT 14 x 14
16x 16
18x18
20 x 20
TY5237 (K=11.2) PENDENT 14 x 14
16x 16
18x18
20 x 20
TY6137 (K=14.0) UPRIGHT 14 x 14
16x16
18x 18
20 x 20
TY6237 (K=14.0) PENDENT 14 x 14
16x16
18x 18
ç20x 20
I ft. =0.3048m
1ft2 =0.093m2
1 gpm = 3.785 1pm
1 psi = 0.06895 bar
1 gpm/ft2 = 40.74 mm/mm
GROUP I
ORDINARY HAZARD
0.15 GPM(FT2
GPM PSI
30 7.2
39 12.1
49 19.1
60 28.7
30 7.2
39 12.1
49 19.1
60 28.7
39 7.8
49 12.3
60 18.4
39 7.8
49 12.3
60 18.4
GROUP II
ORDINARY HAZARD
0.20 GPM/FT2
GPM PSI
39 12.1
51 20.7
65 33.7
80 51.0
39 12.1
51 20.7
65 33.7
80 51.0
51 13.3
65 21.6
80 32.7
51 13.3
65 21.6
80 32.7
LIGHT HAZARD
0.10 GPMIFT2
GPM PSI
30 7.2
33 8.7
40 12.8
30 7.2
33 8.7
40 12.8
N/A N/A
N/A N/A
N/A N/A
N/A N/A
37 7.0
37 7.0
40 8.2
Page 6 of 8 TFP22O
TABLED
FLOW CRITERIA FOR UL AND C-UL LISTING OF SERIES EC-1 1 AND EC-14 SPRINKLERS
Step 1. The sprinkler must be installed Installation with the deflector parallel to the mount-
ing surface. Pendent sprinklers must
The Series EC-11 and EC-14 Sprin- be installed in the pendent position,
klers must be installed in accordance and upright sprinklers must be in-
with the following instructions: stalled in the upright position.
NOTES Step 2. After installing the Style 30 or
Do not install any bulb type sprinkler if 40 mounting plate (or other escutch-
the bulb is cracked or there is a loss of eon, as applicable) over the sprinkler
pipe threads and with pipe thread liquid from the bulb. With the sprinkler
held horizontally, a small air bubble sealant applied to the pipe threads,
should be present. The diameter of The hand tighten the sprinkler into the
air bubble is approximately 1/16 inch sprinkler fitting.
(1,6 mm) for the 135°F/570C to 3/32 Step 3. Wrench tighten upright or pen-
inch (2,4 mm) for the 2860F/1410C dent sprinklers using only the W-Type
temperature ratings. 3 (End A) Sprinkler Wrench. Wrench
A leak tight 3/4 inch NPT sprinkler joint tighten the recessed pendent sprin-
klers using only the W-Type 22 Sprin- should be obtained with a torque of 10
to 20 ft.lbs. (13,4 to 26,8 Nm). A maxi- kler Wrench. The wrench recess of the
mum of 30 ft.Ibs. (40.7 Nm) of torque applicable sprinkler wrench (Ref. Fig-
is to be used to install sprinklers. ure 4 and 5) is to be applied to the
sprinkler wrench flats (Ref. Figure 1). Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over-tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
TFP22O Page 7 of 8
Care and
Maintenance
The Series EC-11 and EC-14 Sprin-
klers must be maintained and serviced
in accordance with the following in-
structions:
NOTE
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shutdown the
affected fire protection systems must
be obtained from the proper authori-
ties and all personnel who may be
affected by this action must be notified.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com-
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
JkJf!Il YA'ItL4l
Ordering
Procedure
When placing an order, indicate the full
product name. Please specify the
Sprinkler Identification Number (SIN),
quantity, and temperature rating. Refer
to the Price List for complete listing of
Part Numbers.
Contact your local distributor for avail-
ability.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (specify SIN), (specify K-Fac-
tor), (specify temperature rating),
(specify Pendent or Upright) Extended
Coverage Sprinkler with (specify fin-
ish), P/N (specify - from Table E, where
applicable).
Recessed Escutcheon:
Specify: Style (specify 30 or 40) Re-
cessed Escutcheon with (specify fin-
ish), P/N (specify).
Style 30 Recessed Escutcheon
Chrome Plated ............PSN 58.705.8-011
White Color Coated ........PSN 56-705-4-011
White (RAL90I0)*PSN 56-705-3-011
Brass Plated ..............PSN 56-705-2-011
Style 40 Recessed Escutcheon
Chrome Plated ............PSN 56-700-9-010
White Color Coated ........PSN 56-700.4-010
White (RAL9O1O)' .........PSN 56-700-3-010
Brass Plated ..............PSN 58-700-2-010
*Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 3 Sprinkler Wrench,
P/N 56-895-1-001
Specify: W-Type 22 Recessed Sprin-
kler Wrench, P/N 56-665-7-001
PIN 51- AAA -B-CCC
AAA = 893 (for TY5237
K11.2 Pendent)
AAA = 894 (for TY5137
K11.2 Upright)
AAA = 895 (for TY6237
K14.0 Pendent)
AAA = 896 (for TY6137
K14.0 Upright)
B = 1 (for Natural Brass)
B = 3 (for White [RAL90I0])*
B = 4 (for White Polyester)
B = 7 (for Lead Coated
B = 9 (for Chrome Plated)
CCC = 135 (for 135°F/570C)
CCC = 155 (for 1550F/680C)
CCC = 175 (for 175°F/790C)
CCC = 200 (for 200°F/930C)
*Eastern Hemisphere sales only.
TABLE
PART NUMBERS FOR
EC-il AND EC-14 SPRINKLERS
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
Page 8of8 TFP220
X/ ictauliC V27, K5.6
Models V2703, V2704, V2707 and V2708
Standard Spray
Upright, Pendent and Recessed Pendent
Standard and Quick Response
PRODUCT DESCRIPTION
These Model V27 standard
spray sprinklers are
designed to produce a
hemispherical spray pat-
tern for standard commer-
cial applications. They are V2107
'12708 available with either stan-
Recessed dard or quick response
Pendent bulbs. The design incorpo-
<>
rates state-of-the-art, heat
responsive, frangible glass
eautc bulb design (standard or
publication 10.01 1 for details, quick response) for prompt, V2707 '12708 precise operation.
ture rises causing the liquid
in the bulb to expand.
When the ambient temper-
ature reaches the rated
temperature of the sprin-
kler, the bulb shatters. As a
result, the waterway is
cleared of all sealing parts
and water is discharged
towards the deflector. The
deflector is designed to dis-
tribute the water in a pat-
tern that is most effective
in controlling the fire.
Coverage
For coverage area and
sprinkler placement, refer
to NFPA 13 standards. Pendent
'12703
V2704 I
Upright
The die cast frame is more
streamlined and attractive
than traditional sand cast
frames. It is cast with a
hex-shaped wrench boss to
allow easy tightening from
many angles, reducing
assembly effort. This sprin-
kler is available in various
temperature ratings (see
chart on page 2) and fin-
ishes to meet many design
requirements.
The recessed pendent
should be utilized with a
Model V27 recessed
escutcheon which pro-
vides up to 3/4" (l9 mm) of
adjustments.
Sprinkler Operation
The operating mechanism
is a frangible glass bulb
which contains a heat
responsive liquid. During a
fire, the ambient tempera-
I I
TECHNICAL SPECIFICATIONS
Models: V2703, V2704, V2707
V2708
Style: Pendent, Upright or
Recessed Pendent
Nominal Orifice Size:
½ (13 mm)
K-Factor: 5.6 Imp. (8,1 S.l.')
Nominal Thread Size:
½ NFl (15 mm)
Max. Working Pressure:
175 psi (1200 kPa)
Factory Hydrostatic Test:
100% @ 500 psi (3450 kPa)
Mm. Operating Pressure:
7 psi (48kPa)
Temperature Rating: See
chart on page 2.
MATERIAL
SPECIFICATIONS
Upright Deflector:
Bronze per UNS C22000
Pendent Deflector:
Bronze per UNS C51000
Bulb: Glass with glycerin solu-
tion.
Bulb Nominal Diameter:
U Standard: 5,0 mm
U Quick Response: 3,0 mm
Load Screw: Bronze per UNS
C65100
Pip Cap: Bronze per UNS
C65100
Spring: Beryllium nickel
Seal: Teflon* tape
Frame: Die cast brass 65-30
Lodgement Spring:
Stainless steel per UNS S30200
ACCESSORIES
Installation Wrench:
U Open End: V27
Recessed: V38, V38-3
Socket: V27
Finishes:
O Plain brass
U Chrome plated
U White painted**
U Custom painted**
Q Lead**
155, 200, 286SR Only:
Wax
U Wax over lead**
For cabinets and other accesso-
ries refer to separate sheet.
NOTE: Weather resistant recessed
escutcheons available upon request.
For K-Factor when pressure is mea-
sured in Bar, multiply Si. units by
10.0.
Teflon is a registered trademark of
Dupont Co.
UL Listed for corrosion resistance in
all configurations.
VICTAULIC IS AN ISO 9001 CERTIFIED COMPANY
Victaulic Company of America Victaulic Company of Canada Victaulic Europe Victaulic America Latina Victaulic Asia Pacific
Phone: 1-800-PICK-VIC (1-800-742-5842) Phone: 905-884-1444 Phone: 32-9-381-1500 Phone: 610-559-3300 Phone: 65-6235-3035
Fax: 610-250-8817 Fax: 905-884-9774 Fax: 32-9-380-4438 Fax: 610-559-3608 Fat: 65-6235-0535
e-mail:pickmc@victaulic.com e-mail: viccanada@victaulic.com e-mail: viceuro@victaulic.be e-mail: vicalaviclaultc.com e-mail: vlcap@victaullc.com
2544 ReeD 8/03 5 Registered Trademark of Victaulic 0 Copyright 2003 VictauliC Printed in U.S.A.
:Z'IX'I1 I-i I Ii ii [t
Nominal Approved Temperature Ratings °FI°C
Orifice Size K-Factor
Inches Imperial Deflector
Model millimeters S.I. Response Type UL FM ULC NYCIMEAt CSFM §
½ 5.6 135-360 135-360 135-360 135-360 135-360
V2703 13 8.1 Standard upright 57-182 57.182 57-182 57-182 57-182
1h 5.6 135-360 135-360 135-360 135-360 135-360
V2707 13 8,1 Standard Pendent 57-182 57-182 57-182 57-182 57-182
½ 5.6 Recessed Pendent 135-360 135-200 135-360 135-360 135-360
V2707 13 8,1 Standard Upto 3,4' Adjustment 57-182 57-93 57-182 57-182 57-182
½ 5.6 135-286 135-286 135-286 135-286 135-286
V2704 13 8,1 Quick upright 57-141 57-141 57 -141 57-141 57 -141
½ 5.6 135-286 135-286 135-286 135-286 135-286
V2708 13 8,1 Quick Pendent 57-141 57-141 57-141 57-141 57-141
½ 5.6 Recessed Pendent 135-200 135-200 135-200 135-200 135-200
V2708 13 8,1 Quick Up tow AdjustmcrTt 57-93 57-93 57-93 57-93 57-93
½ 5.6 Recessed Pendent 135-200 No 135-200 135-200 135-200
V2708 13 8,1 Quick UptoWAdjustment 5793 1 57.93
Listings and approval as of printing. 0 All are approved open, except tor areas oesignatco No.
For K-Factor when pressure is measured in Bar, multiply S.I. units by 10.
MEA #52-99-E. § CSFM #7690-0531:112
RATINGS
All glass bulbs are rated for
temperatures from -67°F
(-5 5°C) up to those shown
in adjacent table.
Temperature - °FI°C
Nominal Maximum Sprinkler Victaulic Glass
Temperature Pant Temperature Ambient Temp. Bulb
Classification Identification Rating Allowed Color
Ordinary A 135
57
100
38 Orange
Ordinary C 155 100
68 38 Red
Intermediate E 175 150
65 Yellow
Intermediate F 200
93
150
65 Green
High -
286
141
225 -
107 Blue
Extra High f K 360 300
182 149 Purple
- M Open No Bulb
Standard response only.
All arc approved open, except for areas designated "No".
150165 if wax coated.
ORDERING INFORMATION
Please specify the following
when ordering: 0 Sprinkler Model Number U K-Factor 0 Sprinkler Finish
U Style U Thread Size U Escutcheon Finish
U Temperature Rating 0 Quantity 0 Wrench Model Number
Always read and understand installation, care, and maintenance instructions, supplied with each box of sprinklers, before proceeding with installation
of any sprinklers.
Always wear safety glasses and foot protection.
Depressurize and drain the piping system before attempting to install, remove, or adjust any Victaulic piping products.
Installation rules, especially those governing obstruction, must be strictly followed.
P Painting, plating, or any re-coating of sprinklers (other than that supplied by Victaulic) is not allowed.
Failure to follow these instructions could result in serious personal injury and/or property damage.
The owner is responsible for maintaining the fire protection system and devices in proper operating condition. For minimum maintenance and inspection requirements, refer to the
current National Fire Protection Association pamphlet that describes care and maintenance of sprinkler systems. In addition, the authority having jurisdiction may have additional
maintenance, testing, and inspection requirements that must be followed.
If you need additional copies of this publication, or if you have any questions about the safe installation of this product. contact Victaulic World Headquarters, P.O. Box 31, Easton,
Pennsylvania 18044-0031, 610-559-3300.
40.10-2
1 ?/1 s"
(37 mm)
2W
(60 mm)
I (41 mm)
(25 mm)
Standard Pendent - V2707, V2708
1W
2W (41 mm)
(60 mm)
Standard Upright - V2703, V2704
2% (60 rem)
Max. Hole
?(51 mm)
Mill. Hole
I Is
Typical Calling Tile AP (17 mm) (14 mm)
,27mm)
f I
11¼0 Finished Surface (30 mm) (43 mm)
MAXIMUM RECESS
(75 mm) -
MAXIMUM EXTENSION
½" Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
21/d'(60 mm)
Max. Hole
2" (51 mm)
Mm. Hole
___________ 1Ws
(33 mm)
_____ 'U Typical Ceiling Tile
'h's"
(24 mm)
- Finished Surface ________________________
MAXIMUM RECESS
(75 mm)
MAXIMUM EXTENSION
1144" Adjustment
Recessed - V2707, V2708
(Drawing not to scale)
AVAILABLE WRENCHES
V27
Socket
V38 or V38-3
Recessed
V27
Open End
V2707, V2708 Pendent
V2707,V27O8 Recessed Pendent
V2703, V2704 Upright
40.10 -3
(24 mm)
Pyle
(43 mm)
--;-
m ---—
' N M -M -
\ \
m -
10'
3,0m
8
2.4
6
1,8
4
1,2
2
0.6
C
7ps1 48 kPa
15 psi
103 kPa
30 psi -------
207 kPa
V
DISTRIBUTION PATTERNS
MODELS V2707, V2708
K5.6 STANDARD PENDENT AND RECESSED PENDENT
DISTRIBUTION PATTERNS - TRAJECTORY
10' I I I I I I I I I 3,0 m
8' 2,4 m
7psi 48 kPa
6' 1,8 m
15 psi 103 kPa
4, 1,2 m
30 psi ------- 207 kPa
2' 0,6 m
2' 4' 6' 8' 10' 12' 14
0,6m 1,2m 1,8m 2,4m 30m 3,7m 4,3m
MODELS V2703, V2104
K5.6 STANDARD UPRIGHT DISTRIBUTION PATTERNS - TRAJECTORY
0,6m 1,2m 1,8m 2,4m 30m 3,7m 4,3m 49m
NOTES:
Data shown Is approximate and can vary due to differences In Installation.
These graphs Illustrate approximate trajectories, floor-wetting, and wall-wetting patterns for these specific Victaulic FireLock Automatic Sprinklers. They are
provided as Information for guidance In avoiding obstructions to sprinklers and should not be used as minimum sprinkler spacing rules for installation. Refer to
the appropriate NFPA National Fire Code and the authority having jurisdiction for specific information regarding obstructions, spacing limitations and area of
coverage requirements. Failure to follow these guidelines could adversely affect the performance of the sprinkler and will void all Listings, Approvals and War-
ranties.
All patterns are symmetrical to the centerline of the waterway.
WARRANTY Refer to the Warranty section
of the current Price List or
contact Victaulic for details.
This product shall be manufactured by Victaulic company. PJI products to be instated in accordance with current Victaulic installation/assembly instructions. Victaulic reserves the right to change product specifications, designs and standard equipment without notice and without incurring obligations.
40.10-4