Loading...
HomeMy WebLinkAbout1 LEGOLAND DR; ; FPC2019-0168; PermitPERMIT REPORT 4ity of Carlsbad Print Date: 12/02/2020 Permit No: FPC2019-0168 Job Address: 1 LEGOLAND DR, CARLSBAD, CA 92008-4610 Status: Closed - Finaled Permit Type: FIRE-Construction Commercial Work Class Fire Alarm Parcel #: 2111000900 Valuation: $0.00 Occupancy Group: #of Dwelling Units: Bedrooms: Bathrooms: Track #: Lot #: Project #: Plan #: Construction Type: Orig. Plan Check #: Plan Check #: Applied: 07/24/2019 Issued: 09/12/2019 Finaled Close Out: 03/18/2020 Inspector: Final Inspection: Project Title: Description: LEGOLAND 2020 RIDES -REVISION TO NEW FIRE ALARM CONNECTED TO EXISTING ALARM FPContractor: WEST COAST FIRE AND INTEGRATION INC 3199 AIRPORT LOOP DR, # STE D COSTA MESA, CA 92626-3414 (714) 957-5750 FEE AMOUNT FIRE Hourly Services First Hour $159.00 FIRE New Alarm System $1,265.00 FIRE Plan Resub (3rd&Subsequent Submittal/hr) $136.00 FIRE Plan Review Per Hour - Office Hours $204.00 Total Fees: $1,764.00 Total Payments To Date: $1,764.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I ww.w.carlsbadca.gov 4 '0 Ft2c-éS CA West Coast Fire & Integration Fire Alarm • Access Control • Security • CCTV • Nurse Call • Voice/Data Legoland 2020 Rides 1 Legoland Drive Carlsbad, CA 92008 Job# 19-121-03 Fire Alarm System Product Data SALES • DESIGN • INSTALLATION • SERVICE 3199-D Airport Loop Drive Phone (714) 957-5750 Lic.# CIO-989173 Costa Mesa, CA. 92626 Fax (714) 957-5749 ACO# 7407 www.westcoastfireinc.com 0 S )O' DN-60637:H ENF:S.32OSYS(E)) j) NOTI Fl ER® iiteiiigent Addressj e Alikryst[n) by Honeywell Intelligent Fire Alarm Control Panels General [I: The NFS-320SYS intelligent Fire Alarm Control Panel is part of the ONYX® Series of Fire Alarm Controls from NOTIFIER. As a stand-alone small-to-large system, or as a large network, the ONYX Series of products meet virtually every application requirement. The modular design of the ONYX Series makes system plan- ning easier. The panel can be configured with just a few devices for small building applications, or networked with many devices to protect a large campus or a high-rise office block. Simply add additional peripheral equipment to suit the applica- tion. NOTE: Unless called out with a version-specific "E" at the end of the part number, 'NFS-320SYS" refers to models NFS-320SYS and NFS-320SVSE; similarly, "CPU-320SYS" refers to models CPU-320SYS and GPU-320SYSE. Features Certified for seismic applications when used with the appro- priate seismic mounting kit. Approved for Marine applications when used with listed compatible equipment. See DN-60688. One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7. Up to 159 detectors (any mix of ion, photo, thermal, or multi-sensor) and 159 modules (NO. manual stations, two- wire smoke detectors, notification, or relay). 318 devices maximum. Standard 80-character display. Network options: - High-speed network for up to 200 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NFS-3030, NFS-640, and NCA). - Standard network for up to 103 nodes (NFS2-3030, NFS2-640, NFS-320(C), NFS-320SYS, NCA-2, DVC-EM, ONYXWorks, NCS, NFS-3030, NFS-640, NCA, AFP-200, AFP-300/400, AFP-1 010, and AM2020). Up to 54 nodes when DVC-EM is used in network paging. 6.0 A switch mode power supply with four Class A/B built-in Notification Appliance Circuits (NAC). Selectable System Sensor, Wheelock, or Gentex strobe synchronization. Built-in Alarm, Trouble, and Supervisory relays. VeriFire® Tools online/offline program option. Sort Mainte- nance Reports by compensation value (dirty detector), peak alarm value, or address. Autoprogramming and Walk Test reports. Multiple central station communication options: - Standard UDACT - Internet - Internet/GSM 80-character remote annunciators (up to 32). EIA-485 annunciators, including custom graphics. Printer interface (80-column and 40-column printers). History file with 800-event capacity in nonvolatile memory, plus separate 200-event alarm-only file. Alarm Verification selection per point, with automatic counter. NFS-32OSYS Positive Alarm Sequence (PAS) Presignal. Silence irhibit and Auto Silence timer options. March tire/temporal/California two-stage coding/strobe synch ronzation. Field-programmable on panel or on PC, with VeriFire Tools program check, compare, simulate. Full QWEPTY keypad. Charger br up to 200 hours of standby power. Non-alarrr. points for lower priority functions. Remote AK/Signal Silence/System Reset/Drill via monitor modules. Automatic time control functions, with holiday exceptions. Surface Mount Technology (SMT) electronics. Extensive, built-in transient protection. Powerful Boolean logic equations. FLASHSCAr® INTELLIGENT FEATURES Polls up k 318 devices in less than two seconds. Activates p to 159 outputs in less than five seconds. Multicolo LEDs blink device address during Walk Test. Fully dgital, high-precision protocol (U.S. Patent 5,539,383). Manual sensitivity adjustment - up to nine levels. Pre-alarm ONYX intelligent sensing - up to nine levels. Day/Night automatic sensitivity adjustment. Sensitivity windows: - Ion - 0.5 to 2.50/./foot obscuration. - Photo - 0.5 to 2.35%/foot obscuration. - Laser iVIEW®) - 0.02 to 2.0%/foot obscuration. - Acclirrate® PIusTM - 0.5 to 4.0%/foot obscuration. - InteIIiQuadTM - 1.0 to 4.0%/foot obscuration - InteIIiQuadTM PLUS - 1.0 to 4.0%/foot obscuration Drift compensation (U.S. Patent 5,764,142). Degradet mode - ir the unlikely event that the CPU- 320SYS microprocessor fails, FlashScan detectors revert to degraded operation and can activate the CPU-320SYS DN-60637:H • 12/20/2013 - Page 1 of 6 NAC circuits and alarm relay. Each of the four built-in panel circuits includes a Disable/Enable switch for this feature. Multi-detector algorithm involves nearby detectors in alarm decision (U.S. Patent 5,627,515). Automatic detector sensitivity testing. Maintenance alert (two levels). Self-optimizing pre-alarm. FSL-751 (VERY INTELLIGENT EARLY WARNING) SMOKE DETECTION TECHNOLOGY Advanced ONYX intelligent sensing algorithms differentiate between smoke and non-smoke signals (U.S. Patent 5,831,524). Addressable operation pinpoints the fire location. Early warning performance comparable to the best aspira- tion systems at a fraction of the lifetime cost. FAPT-851 ACCLIMATE® PLUSTM LOW-PROFILE INTELLIGENT MULTI-SENSOR Detector automatically adjusts sensitivity levels without operator intervention or programming. Sensitivity increases with heat. Microprocessor-based technology; combination photo and thermal technology. Low-temperature warning signal at 40°F ± 5°F (4.44°C ± 2.77°C). FSC-851 INTELLIQUADTM ADVANCED MULTI-CRITERIA DETECTOR Detects all four major elements of a fire (smoke, heat, CO, and flame). Automatic drift compensation of smoke sensor and CO cell. High nuisance-alarm immunity. FSA -8000 INTELLIGENT FAAST DETECTOR Connects directly to the SLC loop of compatible ONYX series panels Provides five event thresholds that can be individually pro- grammed with descriptive labels for control-by-event pro- gramming; uses five detector addresses. Uses patented particle separator and field-replaceable filter to remove contaminants. Advanced algorithms reject common nuisance conditions FCO-851 INTELLIQUADTM PLUS ADVANCED MULTI-CRITERIA FIRE/CO DETECTOR Detects all four major elements of a fire. Separate signal for life-safety CO detection. Optional addressable sounder base for Temp-3 (fire) or Temp-4(CO) tone. Automatic drift compensation of smoke sensor and CO cell. High nuisance-alarm immunity. RELEASING FEATURES Ten independent hazards. Sophisticated cross-zone (three options). Delay timer and Discharge timers (adjustable). Abort (four options). Low-pressure CO2 listed. Up to 32 remote displays P FSC-851 IntelliQuad FAPT-851 Acclimate PLUS FSL-751 FlashScan VIEW FSP-851 Photo FSI-851 Ion 0000 FST-851 Thermal FDU-80 FSA-8000 etc. ElA-485 SLC Intelligent Loop I DEVICES NBG-I2LX XP6110 I/O Modules FMM-1 I FCM-1 IDC 4, NAC FRM-1 Relay Contact S 2048 annunciator/control points ;ii iu'is.' It'tJ ACM-8R ACM/AEM-24AT LDM-32 Relay Control LED Annunciator Custom Graphics Dual phone lines to Central Station KDM-R2 display OR Optional 318-point UDACT Sample System Options NFS-32OSYS "C" cabinet size shown PRN Series Printer NFS-320SYSdia1-2013.wmf S Page 2 of 6— DN-60637:H • 12/20/2013 I VOICE AND TELEPHONE FEATURES Integrates with FirstCommand Series. See DN-60772. Telephone applications require NFC-FFT HIGH-EFFICIENCY OFFLINE SWITCHING 3.0 A POWER SUPPLY (6.0 A IN ALARM) 120 or 220/240 VAC. Displays battery current/voltage on panel (with display). FlashScan, Exclusive World-Leading Detector Protocol At the heart of the NFS-320SYS is a set of detection devices and device protocol - FlashScan (U.S. Patent 5,539,389). FlashScan is an all-digital protocol that gives superior preci- sion and high noise immunity. In addition to providing quick identification of an active input device, this protocol can also activate many output devices in a fraction of the time required by competitive protocols. This high speed also allows the NFS-320SYS to have the largest device per loop capacity in the industry - 318 points - yet every input and output device is sampled in less than two seconds. The microprocessor-based FlashScan detectors have bicolor LEDs that can be coded to provide diagnostic information, such as device address during Walk Test. ONYX Intelligent Sensing Intelligent sensing is a set of software algorithms that provides the NFS-320SYS with industry-leading smoke detection capa- bility. These complex algorithms require many calculations on each reading of each detector, and are made possible by the very-high-speed microcomputer used by the NFS-320SYS. Drift Compensation and Smoothing: Drift compensation allows the detector to retain its original ability to detect actual smoke, and resist false alarms, even as dirt accumulates. It reduces maintenance requirements by allowing the system to automatically perform the periodic sensitivity measurements required by NFPA 72. Smoothing filters are also provided by software to remove transient noise signals, such as those caused by electrical interference. Maintenance Warnings: When the drift compensation per- formed for a detector reaches a certain level, the performance of the detector may be compromised, and special warnings are given. There are three warning levels: (1) Low Chamber value, usually indicative of a hardware problem in the detector; (2) Maintenance Alert, indicative of dust accumulation that is near but below the allowed limit; (3) Maintenance Urgent, indicative of dust accumulation above the allowed limit. Sensitivity Adjust: Nine sensitivity levels are provided for alarm detection. These levels can be set manually, or can change automatically between day and night. Nine levels of pre-alarm sensitivity can also be selected, based on predeter- mined levels of alarm. Pre-alarm operation can be latching or self-restoring, and can be used to activate special control func- tions. Self-Optimizing Pre-Alarm: Each detector may be set for "Self-Optimizing" pre-alarm. In this special mode, the detector "learns" its normal environment, measuring the peak analog readings over a long period of time, and selling the pre-alarm level just above these normal peaks. Cooperating Multi-Detector Sensing: A patented feature of ONYX intelligent sensing is the ability of a smoke sensor to consider readings from nearby sensors in making alarm or pre-alarm decisions. Without statistical sacrifice in the ability to resist false alarms, it allows a sensor to increase its sensitivity to actual smoke by a factor of almost two to one. Field Programming Options Autoprogram is a timesaving feature. The NFS-320SYS "learns" what devices are physically connected and automati- cally load them in the program with default values for all parameters. Requiring less than one minute to run, this routine allows the user to have almost immediate fire protection in a new installation, even if only a portion of the detectors are installed. Keypad Program Edit (with KDM-R2) The NFS-320SYS, like all NOTIFIER intelligent panels, has the exclusive feature of program creation and editing capability from the front panel keypad, while continuing to provide fire protection. The architecture of the NFS-320SYS software is such that each point entry carries its own program, including control-by-event links to other points. This allows the program to be entered with independent per-point segments, while the NFS-320SYS simultaneously monitors other (already installed) points for alarm conditions. VeriFire® Tools is an offline programming and test utility that can greatly reduce installation programming time, and increase confidence in the site-specific software. It is Win- dows®-based and provides technologically advanced capabili- ties to aid the installer. The installer may create the entire program for the NFS-320SYS in the comfort of the office, test it, store a backup file, then bring it to the site and download from a laptop into the panel. Placement of Equipment in Chassis and Cabinet The following guidelines outline the NFS-320SYS's flexible system design. Rows: The first row of equipment in the cabinet mounts in the chassis shipped with the FACP. Mount the second, third, or fourth rows of equipment in a CHS-4 Series chassis. Other options are available; see your panel's installation manual. Wiring: When designing the cabinet layout, consider separa- tion of power-limited and non-power-limited wiring as dis- cussed in the NFS-320SYS Installation Manual. Positions: A chassis offers four basic side-by-side positions for components; the number of modules that can be mounted in each position depends on the chassis model and the size of the individual module. There are a variety of standoffs and hardware items available for different combinations and config- urations of components. KDM-R2 Controls and Indicators Program Keypad: OWERTY type (keyboard layout, below). 12 LED indicators: Power; Fire Alarm; Pre-Alarm; Security; Supervisory; System Trouble; Signals Silenced; Points Dis- abled; Control Active; Abort; Pre-Discharge; Discharge. Membrane Switch Controls: Acknowledge/Scroll Display; Signal Silence; Drill; System Reset; Lamp Test. LCD Display: 80 characters (2 x 40) with long-life LED back- light. DN-60637:H • 12/20/2013 - Page 3 of 6 Ordering Information 'Configuration Guidelines" on page 4 "Networking Options" on page 4 "Auxiliary Power Supplies and Batteries" on page 4 "Audio Options" on page 4 "Compatible Devices, EIA-232 Ports" on page 4 "Compatible Devices, ElA-485 Ports" on page 4 "Compatible Intelligent Devices" on page 5 "Enclosures, Chassis, and Dress Plates" on page 5 "Other Options" on page 5 CONFIGURATION GUIDELINES NOTE: Stand-alone and network systems require a main display. On stand-alone systems, the panel's keypad provides the required display. On network systems (two or more networked fire panel nodes), at least one NCA-2, NCS, or ONYX Works annunciation device is required. NCA-2: Network Control Annunciator, 640 characters. On net- work systems, the NCA-2 connects to (and requires) an NCM or HS-NCM network communications module. Mounts in a row of FACP node or in two annunciator positions. Non-English versions are available. For marine applications, order NCA-2- M; for non-English Marine applications, order NCA-2-M and the appropriate KP-KIT-XX. See DN-7047. 1U20VAP with integral 3:0 A(6.0A In ali) powe ?supply for an NFS-320SYS system. FACP is factory-mounted (on a chassis with one Signaling Line Circuit; includes 80-char- acter display and documentation kit. Order one per system or (as necessary on a network system. 'Non-EngIish_version alsd (available: CPU-32OSYS-FR.)'. CPU-320SYSE: Same as CPU-320SYS but requires 220 VAC, 1.5 A, (3.0 A in alarm). DP-DISP2: Dress panel for top row in cabinet with CPU- 320SYS/E installed. BMP-1: Blank module for unused module positions. BP2-4: Battery plate, required. NETWORKING OPTIONS INCM-W, NCM-F: Communications v1 (ules. Wire and mum-mode fiber versions available. See HS-NCM-WIMF/SFIWMFIWSF/MFSF: High-speed Network Communications Modules that can connect to two nodes. Wire, single-mode fiber, multi-mode fiber, and media conver- sion models are available. See DN-60454. RPT-W, RPT-F, RPT-WF: Standard-network repeater board with wire connection (RPT-W), multi-mode fiber connection (RPT-F), or allowing a change in media type between wire and fiber (RPT-WF). Not used with high-speed networks. See DN- 6971. ONYXWorks: UL-listed graphics PC workstation, software, and computer hardware. See DN-7048 for specific part num- bers. NFN-GW-EM-3: NFN Gateway, embedded. See DN-60499. NWS-3: NOTI.FIRE.NETTM Web Server. See DN-6928. CAP-GW: Common Alerting Protocol Gateway. See DN- 60576. VESDA-HLI-GW: VESDAnet high-level interface gateway. See DN-60753. LEDSIGN-GW: UL-listed sign gateway. Interfaces with classic and high-speed NOTI.FIRE.NET networks through the NFN Gateway. See DN-60679. OAX2-24V: UL-listed LED sign, used with LEDSIGN-GW. See DN-60679. AUXILIARY POWER SUPPLIES AND BATTERIES ACPS-610: 6.0 or 10 A addressable charging power supply. See DN-60244. APS2-6R: Auxiliary Power Supply. Provides up to 6.0 amperes of power for peripheral devices. Includes battery input and transfer relay, and overcurrent protection. Mounts on two of four positions on a CHS-4L or CHS-4 chassis. See DN-5952. FCPS-24S61-24S8: Remote 6 A and 8 A power supplies with battery charger. See DN-6927. BAT Series: Batteries. NFS-320SYS uses two 12 volt, 18 to 200 AH batteries. See DN-6933. AUDIO OPTIONS NFC-25/50: 25 watt, 25 VRMS, emergency Voice Evacuation Control Panel (VECP) with integral commercial microphone, digital message generator, and single-/dual-channel Class A or Class B speaker circuits. See DN-60772. COMPATIBLE DEVICES, EIA -232 PORTS PRN-6: 80-column printer. See DN-6956. VS4095/S2: Printer, 40-column, 24 V. Mounted in external backbox. See DN-3260. DPI-232: Direct Panel Interface, specialized modem for extending serial data links to remotely located FACPs and/or peripherals. See DN-6870. COMPATIBLE DEVICES, EIA -485 PORTS ACM-24A1: ONYX Series ACS annunciator - up to 96 points of annunciation with Alarm or Active LED, Trouble LED, and switch per circuit. Active/Alarm LEDs can be programmed (by powered-up switch selection) by point to be red, green, or yel- low; the Trouble LED is always yellow. See DN-6862. AEM-24AT: Same LED and switch capabilities as ACM-24A1, expands the ACM-24AT to 48, 72, or 96 points. See DN-6862. ACM-48A: ONYX Series ACS annunciator - up to 96 points of annunciation with Alarm or Active LED per circuit. Active/ Alarm LEDs can be programmed (by powered-up switch selec- tion) in groups of 24 to be red, green, or yellow. Expandable to 96 points with one AEM-48A. See DN-6862. AEM-48A: Same LED capabilities as ACM-48A, expands the ACM-48A to 96 points. See DN-6862. ACM-8R: Remote Relay Module with eight Form-C contacts. Can be located up to 6,000 ft. (1828.8 m) from panel on four wires. See DN-3558. FDIJ-80: 80-character, backlit LCD display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See FDU-80 (DN-6820). LCD2-80: Terminal and ACS mode. 80-character, backlit LCD display. Mounts up to 6,000 ft. (1828.8 m) from panel. Up to 32 per FACP. See DN-60548. LDM: Lamp Driver Modules LDM-32, LDM-E32, and LDM- R32; remote custom graphic driver modules. See DN-0551. SCS: Smoke control stations SCS-8, SCE-8, with lamp drivers SCS-8L, SCE-8L; eight (expandable to 16) circuits (HVAC only). See DN-4818. TM-4: Transmitter Module. Includes three reverse-polarity cir- cuits and one municipal box circuit. Mounts in panel module position (single-address-style) or in CHS2-M2 position. See DN-6860. tUDACT-2.- Universal Digital A-larm,'Communicator Transmitter, ( channel. SPftO686,J C Page 4 of 6- DN-60637:H • 12/20/2013 UZC-256: Programmable Universal Zone Coder provides pos- itive non-interfering successive zone coding. Microprocessor- controlled, field-programmable from IBM®-compatible PCs (requires optional programming kit). Up to 256 programmable codes. See DN-3404. COMPATIBLE INTELLIGENT DEVICES FSA-8000: Intelligent FAAST Fire Alarm Aspiration Sensing Technology®. Intelligent aspirating smoke detector. For Cana- dian applications, order FSA-8000A. See DN-60792. FSB-200: Intelligent beam smoke detector. See DN-6985. FSB-2005: Intelligent beam smoke detector with integral sen- sitivity test. See DN-6895. FSC-851: FlashScan IntelIiQuad Advanced Multi-Criteria Detector. See DN-60412. FCO-851: FlashScan IntelliQuad PLUS Advanced Multi-Crite- ria Fire/CO Detector. See DN-60689. FSI-851: Low-profile FlashScan ionization detector. See DN- 6934. FSP-851: Low-profile FlashScan photoelectric detector. See DN-6935. FSP-851T: Low-profile FlashScan photoelectric detector with 135°F (57°C) thermal. See DN-6935. FSP-851 R: Remote-test capable photoelectric detector for use with DNR(W) duct detector housings. See DN-6935. FST-851: FlashScan thermal detector 135°F (57°C). See DN- 6936. FST-851R: FlashScan thermal detector 135°F (57°C) with rate-of-rise. See DN-6936. FST-851H: FlashScan 190°F (88°C) high-temperature thermal detector. See DN-6936. FAPT-851: FlashScan Acclimate Plus low-profile multi-sensor detector. See DN-6937. FSL-751: FlashScan VIEW laser photo detector. See DN- 6886. DNR: InnovairFlex low-flow non-relay duct-detector housing (order FSP-851/FSP-851 R separately). Replaces FSD-751 PU FSD-751 RPL. See DN-60429. DNRW: Same as above with NEMA-4 rating, watertight. See DN-60429. B224RB: Low-profile relay base. See DN-60054. B224B1: Isolator base for low-profile detectors. See DN-60054. B21OLP: Low-profile base. Standard U.S. style. Replaces B71OLP. See DN-60054. B501: European-style, 4° (10.16 cm) base. See DN-60054. B200S: Intelligent programmable sounder base, capable of producing a variety of tone patterns including ANSI Temporal 3. Compatible with sychronization protocol. See DN-60054. B200SCOA: Based on B200SA, with added CO detector markings in English/French. For Canadian applications only. B200SR: Sounder base, Temporal 3 or Continuous tone. See DN-60054. FMM-1: FlashScan monitor module. See DN-6 720. FDM-1: FlashScan dual monitor module. See DN-6 720. FZM-1: FlashScan two-wire detector monitor module. See DN- 6720. FMM-101: FlashScan miniature monitor module. See DN- 6720. FCM-1: FlashScan control module. See DN-6 724. FCM-1-REL: FlashScan releasing control module. See ON- 60390. FRM-1: FlashScan relay module. See DN-6 724. FDRM-1: FlashScan dual monitor/dual relay module. See ON- 60709. NBG-12LX: Manual fire alarm station, addressable. See DN- 6726. ISO-X: Isolator module. See DN-2243. XP6-C: FlashScan six-circuit supervised control module. See DN-6924. XP6-MA: FlashScan six-zone interface module; connects intelligent alarm system to two-wire conventional detection zone. See DN-6925. XP6-R: FlashScan six-relay (Form-C) control module. See DN-6926. XP10-M: FlashScan ten-input monitor module. See DN-6923. SLC-IM: SLC integration module, for VESDAnet detectors. See DN-60755. ENCLOSURES, CHASSIS, AND DRESS PLATES CAB-4 Series Enclosure: The NFS-320SYS mounts in a CAB-4 Series enclosure (available in three sizes, B-D). The backbox and door are ordered separately. It requires BP2-4 battery plate. A trim ring is available for semi-flush mounting. EQ Series Cabinets: EQ series cabinets will house amplifiers, power supplies, battery chargers and control modules. EQ cabinets are available in three sizes, "B" through "D". See DN- 60229. CAB-BM Marine System: Protects equipment in shipboard and waterfront applications. Also order BB-MB for systems using 100 AH batteries. For a full list of required and optional equipment, see DN-60688. CHS-4: Chassis for mounting optional equipment. CHS-4L: Low-profile four-position Chassis. D13-113: Blank Dress panel. Provides dead-front panel for unused tiers. NFS-LBB: Battery Box (required for batteries larger than 26 AH). NFS-LBBR: Same as above but red. BB-UZC: Backbox for housing the UZC-256 in applications where the UZC-256 will not fit in panel enclosure. Black; for red, order BB-UZC-R. SEISKIT-CAB: Seismic mounting kit. Required for seismic- certified applications with NFS-320SYS and other equipment mounted in CAB-4 Series Enclosures. Includes battery bracket for two 26 AH batteries. SEISKIT-1_1313: Seismic kit for the NFS-LBB. Includes battery bracket for two 55 AH batteries. OTHER OPTIONS 411: Slave digital alarm communicator. See ON-6619. 411UDAC: Digital alarm communicator. See DN-6746. IPDACT-212UD, IPDACT Internet Monitoring Module: Con- nects to primary and secondary DACT telephone output ports for internet communications over customer-provided Ethernet connection. Requires compatible Teldat VisorALARM Central Station Receiver. Can use DHCP or static IR See DN-60408. IPCHSKIT: IP Communicator Chassis Mounting Kit. For mounting an IPDACT-2/2UD onto the panel chassis or CHS-4 series chassis. Use IPENC for external mounting applications. IPSPLT: Y-adapter option allow connection of both panel dialer outputs to one IPDACT-212UD cable input. IPENC: External enclosure for IPDACT, includes IPBRKT mounting bracket. Red; for black, order IPENC-B. DN-60637:H • 12/20/2013 - Page 5 of 6 IPGSM-4G: Internet and Digital Cellular Fire Alarm Communi- cator. Provides selectable configurable paths: cellular only, IP only, or IP primary with cellular backup. Connects to the pri- mary and secondary ports of a DACT. For Canadian applica- tions order IPGSM-4GC. See DH-60769. NOTE: For other options including compatibility with retrofit equip- ment, refer to the panel's installation manual, the SLC manual, and the Device Compatibility Document. System Specifications SYSTEM CAPACITY Intelligent Signaling Line Circuits ......................................1 Intelligent detectors .......................................................159 Addressable monitor/control modules............................159 Programmable software zones.........................................99 Special programming zones.............................................14 LCD annunciators per CPU-320SYS/E (observe power)................................................................32 ACS annunciators per CPU-32OSYS/E ...................... 32 addresses x 64 points SPECIFICATIONS Primary input power, CPU-320SYS board: 120 VAC, 50/60 Hz, 5.0 A. CPU-320SYS/E board: 220/240 VAC, 50/60 Hz, 2.5 A. Current draw (standby/alarm): - CPU-320SYS(E) board: 0.250 A. Add 0.035 A for each NAC in use. - KDM-R2 (Backlight on): 0.100 A. Total output 24 V power: 6.0 A in alarm. NOTE: The power supply has a total of 6.0 Amps of available power. This is shared by all internal circuits. See Installation Man- ual for a complete current draw calculation sheet. Standard notification circuits (4): 1.5 A each. Four-wire detector power: 1.25 A. Non-resettable regulated power outputs: 1.25 A each. Battery charger range: 18 AH —200 AH. Use separate cab- inet for batteries over 26 AH. Float rate: 27.6 V. CABINET SPECIFICATIONS NFS-320SYS systems can be installed in CAB-4 Series cabi- nets (three sizes with various door options, see DN-6857). Shipping Weight: - CPU-320SYS: 16.95 lb (7.69 kg). - CPU-320SYSE: 17.2 lb (7.80 kg). TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 - 49°C and at a relative humidity 93% ± 2% RH (noncondens- ing) at 32°C ± 2°C. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humid- ity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 - 27°C. AGENCY LISTINGS AND APPROVALS The listings and approvals below apply to the basic control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Con- sult factory for latest listing status. UL Listed: S635. ULC Listed: S635. FM Approved. CSFM: 7165-0028:0243. FONY: COA#6085, #6121. NOTE: For additional information on UL-listed model NFS -320 see DN-71 12. For additional information on UL- and ULC-fisted model NFS-320C, see DN-60085. Marine Applications: Marine approved systems must be con- figured using components itemized in this document. (See Main System Components, in "Product Line Information.) Spe- cific connections and requirements for those components are described in the installation document, PN 54756. When these requirements are followed, systems are approved by the fol- lowing agencies: US Coast Guard 161.002/50/0, 161.002/55/0 (Standard 46 CFR and 161 .002). Lloyd's Register 11/600013 (ENV 3 category). American Bureau of Shipping (ABS) Type Approval. NOTE: For information on marine applications, see DN-60688. STANDARDS The NFS-320SYS complies with the following UL Standards and NFPA 72, International Building Code (IBC), and Califor- nia Building Code (CBC) Fire Alarm Systems requirements: UL 864, 9th Edition (Fire). UL 1076 (Burglary). UL 2572 (Mass Notification Systems). LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervisory). AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). REMOTE STATION (Automatic, Manual and Waterflow) (requires 4XTMF). PROPRIETARY (Automatic, Manual and Waterflow). Not applicable for FM. EMERGENCY VOICE/ALARM. OT, PSDN (other technologies, packet switches, data net- work. IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seis- mic). CBC 2007 (Seismic). NOTI.FIRE.NETTM, InteIIlQuadTM, and ONYXWorksTM are trademarks; and Acclimate® PlusTM, FlrstCommandlt, FlashScan®, NOTIFIER®, ONYX®, VeriFlre®, and VIEW® are registered trademarks of Honeywell International Inc. Microsoft® and Windows® are registered trademarks of Microsoft Corporation. IBM® is a registered trademark of IBM Corporation. ©2013 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. .. This document is not intended to be used for installation purposes. ________ I SO 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. I DltlNffIlNI & MANUMCIIUNG All specifications are subject to change without notice. I QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com di Page 6 of 6— DN-60637:H • 12/20/2013 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION [low OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM S LISTING SERVICE LISTING No. 7165-0028:0243 Page 1 of 4 CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models NFS2-640, NFS-320/C (R), and NFS-320SYS fire alarm control units. Local, auxiliary, remote station (PPU), proprietary (PPU), central station (PPU), manual, automatic, waterfowl and sprinkler supervisory services. Also suitable for releasing service, Process Management and Emergency Voice/Alarm communication System * Model numbers may be followed by an "R" suffix representing the enclosure color being red. Refer to listee's data sheet for additional detailed product description and operational considerations. System components: ACM-8R, -16AT, -32A, -24AT, -48A; Annunciator Control Modules ACPS-610, AMPS-24; Addressable power supply/charger ADP-413, -A4, -1, -2, DP-D15P2; Dress Panel AEM-16AT, -32A, -24AT, -48A; Annunciator Expander Modules AFM-16A, -16AT, -32A; Annunciator Fixed Modules AKS-1 B; Annunciator Key Switch APS2-6R; Power supply BB-100, -200, NFS-LBB/-LBBR; Battery Boxes BGRA-SCS, BGRB-SCS; Smoke Control Station BMP-1; Blank Module BP4, BP24; Battery Dress Plates CAB-3/4 Series; Enclosure CAB-RP, CAB-RPR; Cabinets CEF-SCS; Smoke Control Station CHS-4, CHS-4N, CHS-4L; Chassis CPU2-640, CPU-320SYS; CPU Board CRT-2; Display Terminal DP-1B; Blank Panel DPA-1A411/2, DP-D1SP2; Dress Panel DPI-232; Panel Interface DR-A4, DR-A413, DR-A4BR, DR-A4R; Door Assembly DR-AA4, DR-AA413, DR-AA4BR, DR-AA4R; Door Assembly DR-133F; Door Assembly DR-134, DR-B4B, DR-B4BR, DR-B4R; Door Assembly DR-C4, DR-C4B, DR-C4BR, DR-C4R; Door Assembly DR-D4, DR-D413, DR-D4BR, DR-D4R; Door Assembly *Rev. 10-29-13 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Listing No. 7165-0028:0243 Page 2 of 4 EQ Series; Cabinets EQBB-B4, EQBB-C4, EQBB-D4; Backbox Assembly EQDR-B4, EQDR-C4, EQDR-D4; Door Assembly FCM-1, FCM-1-REL; Releasing Control Module FCPS-24S6, -24S8; Field Charger/Power Supply FDM-1; Dual Monitor Module FDRM-1 :Multiple Module with two Relay Outputs FDU-80/-80G; Remote Annunciator FlRSTVlSlON-LCD/ENC; Interactive Firefighters' display/enclosure FRM-1; Relay Module FTM-1; Control Module FZM-1, FMM-1, FMM-101; Monitor Modules HS-NCM-W/-MF/-SF/-WMF/-WSF/-MSSF; High Speed Network Control Modules IPDACT-2/-2UD; lP Fire Alarm Communicator ISO-X; Isolator Module KAPS-24, CPS-24; Power Supply KDM-R2; Keyboard Display Module LCD-80, -160; Annunciators LCD-80TM; Annunciator Terminal Module LCD LCD2-80; Remote Annunciator LDM-32/-E32/-R32; Lamp Driver Module LEM-320/ELEM-320; Loop Expander Module NBG-12LRA; Agent Releasing Abort Station NBG-12LX; Addressable Manual Pull Station NCA, NCA-2; Network Communication Annunciator NCM-W, -F; Network Control Module NCS4-W-ONYX, NCS4-F-ONYX; Network Control Station NCS5-W-ONYX, NCS5-F-ONYX; Network Control Station NFS-LBB/NFS-LBBR; Battery Box/Red NFS-320SYS; Chassis NFV-25/50, NFV-25/50ZS/ZST; Voice Evacuation Control Panels NFV-25/50DA, NFV-25/50DAZS; Distributed Audio Panels ONYXWorks-EW/-NW-/NF/-HNW/-HNMF/-HNSF/-TS/-EW-TS/-NF-15/-HW-TS/ -HNMFT/-HNSFT/-HNWT; PC workstation for NOTI.FIRE.NET, Wire/Fiber/ with Touch screen monitors PRN-6; Printer RKS-S; Remote Security Key Switch RPT-W, -485W; Repeater Wire RPT-F; Repeater Fiber RPT -485FW; Repeater Fiber/Wire RSA-SCS, RSB-SCS, RSC-SCS, RSD-SCS, RSE-SCS; Smoke Control Station SBB-A3F; Backbox Assembly SBB-A4, SBB-A4R, SBB-AA4, SBB-AA4R; Backbox Assembly SBB-B4, SBB-B4R-L8, SBB-C4, SBB-C4R; Backbox Assembly SBB-D4, SBB-D4R; Backbox Assembly *Rev. 10-29-13 gt ø' This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 • Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division S Listing No. 7165-0028:0243 Page 3 of 4 SCE-8; Smoke Control Expander . SCS-8L; Smoke Control Lamp Driver Station SCE-8L; Smoke Control Expander Lamp SCS-8; Smoke Control Station STS-1; Security Tamper Switch TM-4; Transmitter Module TR-A4/-B3NI-B4/-C4/-D3N/-D4; Trim Ring UDACT, UDACT-2; Universal DACT UZC-256; Universal Zone Coder VP-2B; Dress Panel XP5-Cl-M; Transponder Modules XP6-C; Supervised Control Modules XP6-MA; Six Zone Interface Modules XP6-R; Six Relay Control Modules XP10-M(A); Ten Input Monitor Modules XPM-8L; Transponder Monitor Modules The following models are intended for use on NFS2-640 only: AA-30, -100, -120; Amplifiers ACT-1, -2, -4, -25, -70; Audio Coupling Transformer ADDR-B4/-B4R/-C4/-C4R/-D4/-D4R; Door Assemblies AMG-E; Audio Message Generator AVL-1; Audio Voice Link BDA-25V/-70V; Backup Digital Audio Amplifiers CHS2-M2, CA-1, CA-2; Chassis CMIC-11, CMIC-RP; Microphone Assembly DAA-5025/-5070; Digital Audio Amplifiers S DAA-5025F/DAA-5025SF; Digital Audio Amplifiers DAA-5070F/DAA-5070SF; Digital Audio Amplifiers, Fiber Mode DAA-75 Series; Digital Audio Amplifiers DAA-7525, DAA-7525F, DAA-7525SF; Digital Audio Amplifiers DAA2-5025/-5070/-7525; Digital Audio Amplifiers DAX-3525/-3570/-5025/-5070; Digital Audio Amplifiers DS-AMP/E; Digital Series Audio Amplifier DS-BDA; Digital Series Backup Amplifier DS-DB; Digital Series Distribution Board DS-FM, DS-RFM, DS-SFM; Digital Series Fiber Module DVC; Digital Voice Command DVC-EM/-EMF/-EMSF; Digital Voice Command Extended Memory Module DVC-RPU; Remote Paging Unit FFT-7, -7S; Fire Fighter's Telephone FHS; Fireman's Handset FPJ; Fireman's Phone Jack RM-1, RM-1SA; Remote Microphone *Rev. 10-29-13 gt : This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTIL.LO, Program Coordinator Fire Engineering Division Listing No. 7165-0028:0243 Page 4 of 4 TELH-1; Telephone Assembly XPIQ; Transponder Quad Intelligent Audio INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical ratings, and UL Label APPROVAL: Listed as fire alarm control units suitable for use in high-rise applications when used in conjunction with separately listed compatible initiating and indicating devices. *Control units may be used with Notifier's First Command NFC-50/100 emergency voice evacuation panals (CSFM # 6911-0028:0265). This control unit can generate the temporal code pattern fire alarm signal as required per NFPA 72. Refer to manufacturer's Installation Manual for details. This control unit meets the requirements of UL Standard 864, 9th Edition. NOTE: 1. For Fire Alarm Verification feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 Seconds. 2. Combined with 7170-028:244 [I *Rev. 10-29-13 gt 0 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verity correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division DN-60772:A3 (NPT—IFIER FirstCommanjd __C_-i~0 0 __ I[.)dIiJI1; by Honeywell Voice Evacuation & Emergency Communications System Notifier's First Command NFC-50/100 and NFC-50/100E are multipurpose emergency voice evacuation panels for fire appli- cations, mass notification applications, or both. The First Com- mand delivers 50 or 100 watts of audio power for distribution to up to eight speaker circuits (i.e. zones). The NFC-50/100(E) comes standard with a single speaker circuit and a built-in 50 watt, 25V amplifier. A secondary 50 watt amplifier (NFC-BDA- 25170V) can be added for single speaker circuit backup or to increase system capacity to two speaker circuits and an addi- tional 50 watts of audio power. An optional NFC-CE6 module added to the NFC-50/100(E) will upgrade the system to a max- imum of eight speaker circuit outputs. All speaker output cir- cuits can be wired in either Style Y (Class B) or Style Z (Class A) configuration. The NFC-50/100(E) has fourteen field pro- grammable messages (up to 60 seconds each), built-in field configurable pre- and post-announce tone generators and a fully supervised Notification Appliance Circuit (NAC) with 2.0 amps of synchronized NAC power. The NFC-50/100(E) includes three built-in Form-C relay contacts, (AC power, trou- ble and MNS active) a NAC follower and 500mA special appli- cation power. A built-in power supply delivers operational power and on board battery charger supports charging up to 26AH batteries (NFC cabinet holds up to 18AH batteries). For fire protection applications, the NFC-50/100(E) is an adjunct (slave) to any UL listed FACP, providing reverse polar- ity or contact closure; can be used as a stand-alone unit for non-fire applications. For seamless integration between fire and mass notification, the NFC-50/100(E) can be directly acti- vated via serial communication between the NFW2-100(Rev 3), NFS-320 or NFS2-640. Activation of the NFC-50/100(E) via other FACPs uses the eight on board Command Input Circuits (CMD's). Two of the eight CMD circuits (CMD 1 & CMD 2) can be individually field programmed for activation by an FACP Notification Appliance Circuit reverse polarity and all eight can be activated by a contact closure. In addition, the NFC-50/ 100(E) can be activated from a building's Private Branch Exchange (PBX) with the integral night ring feature. All NFC-50/100(E) programming is done by using a simple, built-in programming utility accessed from any laptop. For added flexibility, the NFC-50/100(E) supports both 25V and 70V speaker output operation. By adding a 70V transformer conversion module (NFC-XRM-70V) or an additional 70 volt secondary amplifier (NFC-BDA-25/70V) the system supports 70 volt speaker devices. The NFC-50/100(E) can expand in order to accommodate larger or more complex installations. To add more control and increase system capacity, any combination of up to eight exter- nal remote consoles (including the NFC-LOG, NFC-RPU, and NFC-RM) and up to eight distributed audio amplifiers (includ- ing the NFC-50DA(E), NFC-1000A(E) and NFC-125-DA(E) can be connected on the external data bus and audio riser data bus to create a fully integrated command center. A fully loaded system supports up to 1100 watts of total audio power and up to 24 speaker circuit outputs. TYPICAL APPLICATIONS Schools • Nursing Homes • Factories Theaters • Military facilities • Restaurants Auditoriums • Places of Worship • Office Buildings Features UL Listed to UL 2572 Communication (Control Units Mass Notification Systems) and UL 864 (emergency voice evacu- ation for fire). Modular design for system flexibility and easy expansion. Removable terminal blocks. 50 watts of 25V audio power (expandable to 100 watts) RMS. 2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for System Sensor, Wheelock or Gen- tex protocols. Optional 70V transformer available for the primary amplifier. (Note that speaker wiring continues to be supervised in standby, alarm and when background music is playing with this optional transformer installed). Eight Command Input Circuits to activate messages 1 to 8: - CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or contact closures. - CMD3-CMD8 are activated by contact closures. Speaker Circuits. - Single Style Y (Class B) or Style Z (Class A) speaker Cir- cuit. DN-60772:A3 • 9/29/14 - Page 1 of 8 -Two Style Y (Class B) or Style Z (Class A) speaker cir- cuits (with optional NFC-BDA-25/70V Audio Amplifier installed). - Eight Style V (Class B) or Style Z (Class A) speaker cir- cuits (with optional NFC-BDA-25170V and NFC-CE6 installed). NFC-50/100(E) can be controlled by an FACP via the ANN! ACS (EIA-485) link of the NFW2-100 (Rev 3), and via the ACS (EIA-485) link of the NFS-320 or NFS2-640. The NFS- 320 or NFS2-640 must be firmware version 20.0 or higher. Integral supervised microphone. Microphone time-out feature which reverts back to pre- recorded message if emergency page exceeds the pro- grammed time. 14 recorded messages. Field-selectable message and custom message recording capability using the local microphone, a USB port, or an external audio input. External Audio Input can be used for background music. Up to 60 second message duration for all messages. Integral tone generators field selectable for multiple tone types. Powered by integral AC power supply or batteries during AC fail. Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss. Piezo sounder for local trouble. 100 event history log. Three Form-C relays: - AC Power Loss Relay - TB1. - System Trouble Relay - T132. - MNS Active - T133. 500mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable FACPs and End-of-Line power supervision relays. System Status LEDs (refer to "Controls and Indicators" on product manual LS10001-000NF-E). Integral Dress Panel. Optional TR-CE-B semi-flush trim ring. Any combination of up to eight (8) external remote con- soles: - Optional NFC-RM Remote Microphone (includes cabi- net). See DN-60778. - Optional NFC-RPU Remote Page Unit (includes cabinet). See DN-60775. - Optional NFC-LOC Local operator console (includes cab- inet). See DN-60777. Any combination of up to eight (8) distributed audio amplifi- ers: - Optional NFC-500A(E) distributed amplifier, 50 watts. See DN-60776. -Optional NFC-125DA(E) distributed amplifier, 125 watts. See DN-60776. -Optional NFC-50!100 distributed amplifier with backup capability, 50/100 watts. See DN-60776. Page 2 of 8— DN-60772:A3 • 9/29/14 Optional Internal Expansion Modules NFC-CE6: Circuit Expander Module provides connections for up to six Style Z (Class A) or Style V (Class B) speaker cir- cuits. Circuits are configured through the web-based program- ming utility. NFC-BDA-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total NFC-50!100 power output to 100 watts or can also be used as a backup amplifier. NFC-BDA-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total NFC-50/100 power output to 100 watts or can also be used as a backup amplifier. NFC-XRM-70V: 70V Transformer Conversion Module. Con- verts the NFC-50!100(E) primary amplifier to a 70V output. This transformer mounts directly to the NFC-50/100(E) main control board by two metal brackets. ,I-] I 0 Pt RE SYSTEM AZTIVE FIRESYSTEM OVERRIDE LM SPEAKER SPEAMER ZONE 13 up ZONE I SPEAKER SPEAKER (r Z4514 ZONE SPEAKER (jj)) ZCY4E1S OKIOPAGE SPEAKER ZONE 4 SPSAKER ZONE 16 UtR0PIIS TROUBLE SPEAKER ZONES $MAKER ZONE MEDDADAI SPEAKER ZONE 6 SFIAKER 2ONE i a MESSAGED SPEANER Sr ZONE UESNAGR4 CD SPEAKER ZONE 9 (J) SMAKER ZEE 21 () MESS.- 10KER E22 D MESSAGE N SPEAKER ZONE 11 (M~ SPEAKER ZONE 23 (} MESSAGE? SR S S N ZONE I? MESSAGEM DIAGNOSTIC 1ROWLESiLtHOr mcposstt 0 )' MAM CONSOLE > DINT AMP I oto uu 0 DIST.AMP2 1:s• ci*pIsrsuu 0 LoG? > olsi AMPS ' BAIIERYFAIJU g RPU I E> DINT AMP 4 DATA MiS PAUl RPU S > 0101 AMPS MAC FAULT 0 RPU 3 t: IIST. AMP 6 MAC ACMN ) NM 1 , DINT. AMP ,. SYSIEMIROUIILE PM? 0151 MIPS J> MININAISERSAVLI 0 10. RM3 Control and Indicators PUSH BurroN CONTROLS All Call • Message Select 1-14 MNS Control • Diagnostic Select System Control • Trouble Silence Speaker Select 1-24 • Console Lamp Test LED Status Indicators (visible with door closed) Fire System Active (green) LOC/RPU/RM 1-8 Active (green) MNS Control (green) Main Console Fault (yellow) System Control (green) AC Power (green) System in Use (green) Ground Fault (yellow) Speaker Zone 1-24 Active (green) Charger Fault (yellow) Speaker Zone 1-24 Fault Battery Fault (yellow) (yellow) OK to Page (green) Data Bus Fault (yellow) Microphone Trouble (yellow) NAC Fault (yellow) Message 1-8 Active (red) NAC Active (green) Message 1-8 Fault (yellow) System Trouble (yellow) Remote Amplifier 1-8 Fault (yellow) Audio Riser Fault (yellow) LOCIRPUIRM 1-8 Fault (yellow) LED Indicators (visible with door and dress panel open) Speaker Volume Control Fault (yellow). Option Card Fault (yellow). Amplifier Over Current Fault (yellow). Product Line Information NFC-50/100: (Primary Operating Console) 50 Watt, 25V single speaker zone emergency voice evacuation system, integral microphone, built in tone generator and 14 recordable mes- sages. NFC-50/100E: Export version (Primary Operating Console) 50 Watt, 25V single speaker zone emergency voice evacuation system, integral microphone, built in tone generator and 14 recordable messages. (240 VAC, 50Hz). NFC-CE6: Speaker Circuit/Zone Expander Module. NFC-BDA-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total NFC-50/100 power output to 100 watts or can also be used as a backup amplifier. NFC-BDA-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total NFC-50/100 power output to 100 watts or can also be used as a backup amplifier. NFC-XRM-70V: 70V Transformer Conversion Module. Con- verts the NFC-50/100(E) primary amplifier to a 70V output. This transformer mounts directly to the NFC-50/100(E) main control board by two metal brackets. NFC-LOC: Local Operator Console (Complete user interface), Please refer to the data sheet DN-60777 for more information. NFC-RPU: Remote Page Unit Hand held microphone, 14 mes- sage buttons. Please refer to the data sheet DN-60775 for more information. NFC-RM: Remote Microphone only. Please refer to the data sheet DN-60778 for more information. NFC-50DA: Distributed (Remote) Audio Amplifier, 50 watts. Please refer to the data sheet DN-60776 for more information. NFC-50DAE: Export version. Distributed (Remote) Audio Amplifier, 50 watts. (240 VAC, 50Hz). Please refer to the data sheet DN-60776 for more information. DN-60772:A3 • 9/29/14 - Page 3 of 8 ampiirier 1 i1j1 I dE?b 01, >tOc NFC-CE6 circuit expander (cQiI H ml 110 ~~i NFC -FFT firefighter telephone FE NFC-LOC NFC-RPU NFC-RM local operator console remote paging unit remote microphone S distributed audio 1 B22 1 > => S Z. I Ep- I ZP. flinternal options NFC-BDA-25/70V'(optional NAC Circuit Speaker Circuits TB19 1B20&TB21 r:P remote consoles 7—> TB4 TB1 2 external battery charger - J7 U CHG-120 charger NFC-50DA 50W NFC-125DA 125W remote amplifier remote amplifier — NFC-50/100DA 50/100W remote amplifier CHG-75 charger NFC-50/1 00(E) FirstCommand (Possible Configurations) Page 4 of 8— DN-60772:A3 • 9/29/14 S S NFC-125DA: Distributed (Remote) Audio Amplifier, 125 watts. Please refer to the data sheet DN-60776 for more information. NFC-125DAE: Export version. Distributed (Remote) Audio Amplifier, 125 watts. (240 VAC, 50Hz). Please refer to the data sheet DN-60776 for more information. NFC-50/100DA: Distributed (Remote) Audio Amplifier with back up, 50 watts/1 00 watts at 25Vrms or 70Vrms. Please refer to the data sheet DN-60776 for more information. NFC-50/100DAE: Export version. Distributed (Remote) Audio Amplifier with back up, 50 watts/100 watts (240 VAC, 50Hz). Please refer to the data sheet DN-60776 for more information. NFC-BDA-BU: Expander card for ECC-50BDA remote amplifier for 100 watt primary! 50 watt back up operation. Please refer to the data sheet DN-60776 for more information. NFC-CE4: Distributed Audio Speaker Circuit/Zone expander module. NFC-FFT: Fire Fighter Telephone System. Please refer to the data sheet DN-60779 for more information. NFC-RTZM: Remote Telephone Zone Module. Allows for secure access to the NFC via cell phone or remote telephone means; not UL listed. Please refer to the data sheet DN-60818 for more information. N-FPJ: Remote Phone Jack. FHS-F: Fire Fighters Remote Handset. FHSC-R: Fire Fighters Handset Cabinet Recessed. FHSC-S: Fire Fighters Handset Cabinet Surface Mount TR-CE-B: Optional Trim Ring. TIIUMBLTCH: Optional Thumb Latch. (Non UL-Listed). CHG-75: 25 to 75 ampere-hours (AH) External Battery Charger. CHG-120: 25-120 ampere-hours (AH) External Battery Charger. ECC-MICROPHONE: Replacement Microphone only. BAT-1270: Battery,12 volt,7.0 AH (Two required). BAT•12120: Battery, 12 volt, 12.0 AH (Two required). BAT-12180: Battery,12 volt, 18.0 AH (Two required). BAT-12260: Battery, 12 volt, 26.0 AH (Two required). BB-26: Battery cabinet mounts up to two 26 AH batteries. Wiring Requirements See product manual, part number LS10001-001NF-E for detailed wiring requirements. Total System Capacity: (NFC-50/1 00(E) only) Total Built-in Audio Power: 50 Watts. Total Expandable Audio Power: 100 Watts. Total Built-in Speaker Circuits: 2. Total Expandable Speaker Circuits: 8. Audio Message Max Time Duration: 60 seconds. External Audio Input: i. Total System Capacity: (Fully Loaded System) Total Distributed Audio Power: 1100 Watts. Total Speaker Circuits Per System: 24. Total Remote Consoles Supported: 8. Total Distributed Audio Amplifiers Supported: 8. Electrical Specifications PRIMARY (AC) POWER (TB15) NFC-50/100: 120 VAC, 60 Hz, 3.5 amps. NFC-50/100E: 240 VAC, 50 Hz, 2.0 amps. Wire size: minimum #14 AWG (2.00mm2) with 600 V insulation. SECONDARY POWER (BATTERY) CHARGING CIRCUIT (J7) Supports lead-acid batteries only. Float charge voltage at 27.3V Maximum charge current: 1.0 Amp Maximum battery charge capability: 2.8 Amps, 26AH (NFC cabinet holds max. 18AH battery). Minimum Battery size: 12 Amp Hour. AC Loss RELAY CONTACT RATING (TB3) 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). FORM C - ThOUBLE RELAY CONTACT RATING (TB2) 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive). MNS ACTIVE RELAY CONTACT RATING (TBI) 2.0 amps @ 30 VDC (resistive), 0.5 amps © 30 VAC (resistive). NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT RATING (TB 19) One (i) Style Y (Class B) or Style Z (Class A) circuit. Power-limited circuitry, (Class 2) supervised. Nominal operating voltage: 24 VDC. Maximum signaling current for special application power: 2.OA. Maximum signaling current for regulated power: 200mA. Maximum wiring impedance: i. Current limit: fuse-less, electronic, power-limited. End-Of-Line Resistor: 4.7 K, ½ watt, (P/N 71252) required for Style Y (Class B) operation. Refer to the Device Compatibility Document 15378 for listed compatible devices. NAC FOLLOWER OUTPUT REMOTE SYNC (TBI8) Connections for FACP NAC synchronization trigger signal. Output terminals: pass-through to other system compo- nents. Trigger input voltage: 9 to 32 VDC, 24 VDC rated. Input current draw in Alarm condition: 10 mA at rated volt- age. SPECIAL APPLICATION POWER (AUX. POWER) (TBI7) 500 mA @ 24 VDC. Used for powering addressable modules and associated End-of-Line power supervision relays. Power-limited circuitry. Refer to the Device Compatibility Docu- ment 15378 for a list of compatible devices. SPEAKER VOLUME CONTROL OVERRIDE (TB23) Style Y (Class B) or Style Z (Class A) circuit. Special application power. Power-limited circuitry, supervised. Nominal operating voltage: 24 VDC. Maximum signaling current: 0.25 amps. Current limit: fuse-less, electronic, power-limited. End-Of-Line Resistor: 4.7 K, ½ watt, (P/N 71252) required for Style V (Class B) operation. DN.60772:A3 • 9/29/14 - Page 5 of 8 Speaker Circuits Primary Speaker Circuit (T820) Secondary Speaker Circuit (TB21) (with optional amplifier only). - Circuit can be wired Style Y (Class B) or Style Z (Class A). - Power-limited circuitry. - Normal Operating Voltage: 25 VRMS @ 2 amps max and maximum Load Impedance of 12.5 (70V @ 700 mA max. with maximum load Impedance of 10092 operation possible by plugging optional NFC-XRM-70V conversion transformer into J12 of the main control board). -Output Power: 50 watts (10 watts when background music is employed). - Frequency Range: 400Hz - 4,0001-1z. - Maximum total capacitance for each speaker circuit: 250 uE - End-of-Line Resistor required for Style V circuit: 15 KU 1 watt (P/N: ELR-15K). Command Input Circuits (alarm polari- ties shown) CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Ter- minals 1(-) and 2(+) are output terminals which provide feed through of the NAC circuits to NAC devices down stream. CMD2 - TB5 Terminals 3(+) & 4(-) are input terminals and Ter- minals 1 (-) and 2(+) are output terminals which provide teed through of the NAC circuits to NAC devices downstream. CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for con- tact closure only. CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for con- tact closure only. CMDS - TB7 Terminals 1(+) & 2(-) are input terminals for con- tact closure only. CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for con- tact closure only. CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for con- tact closure only. CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for con- tact closure only. Power-limited and supervised circuitry. Normal Operating Voltage Range: 10.5 VDC - 29 VDC; (Maximum Voltage: 29 VDC). NAC Reverse Polarity Current (requires End-of-Line Resis- tor from NAC): 1.6 mA maximum. Contact Closure Operation Current (requires 4.7KU 1/2 watt End-of-Line Resistor P/N 27072): 6.6 mA maximum. Maximum Wiring Impedance CMD1 - CMD8 (Contact Clo- sure Operation): 20092 NOTE: When the system is programmed for Mass Notification, CMD land CMD2 will be programmed for Reverse Polarity only. See manual P/N LS10001-001NF-E for more details. MAXIMUM INPUT IMPEDANCE: CMD1 & CMD2 (Reverse Polarity Operation): 20K. CMD1 - CMD8 (Contact Closure Operation): 4.75K2 NIGHT RING INPUT - TBI6, TERMINALS I (+) & 2 (-) Contact closure input. Isolated, non-supervised. Operation current: 3.8 mA, maximum. Maximum wiring impedance: 30K. Minimum isolation withstand voltage: 1500 VRMS EXTERNAL OPERATOR INTERFACE POWER OUTPUT (TB24) Non-resettable power for external operator interface com- ponents. Power-limited circuitry, non-supervised. Nominal operating voltage: 24 VDC. Maximum output current: 0.80 amps. Current limit: fuse-less, electronic, power-limited circuit. EXTERNAL DATA BUS (EIA -485) (TBI2) Data connections for external operator interface components. Redundant transceiver circuitry for Class A operability. Power-limited circuitry, supervised. Maximum wiring impedance: 13.2Q FACP DATA Bus (EIA -485) (TB 13) Dedicated connection to FACP serial bus. Output terminals: pass-through to other system components. Isolated, supervised. Minimum isolation withstand voltage: 1500 VRMS. Maximum wiring impedance: 401 (ANN-BUS), 26 (ACS-BUS). External Audio Riser (TB22). Style V (Class B) or Style Z (Class A) audio connections to external operator interface components. Power-limited circuitry, supervised. Audio signal level: 3.85 V, maximum. Frequency range: 400 Hz - 4 KHz RMS. Frequency range (NFC-50/125DA): 800Hz - 2KHz RMS. EXTERNAL AUDIO INPUT (TB5) Input Impedance: 8.51< nominal @1KHz. Input Voltage: 700 mV rms maximum. Input Current: 0.1 mA maximum @ 700 mV. NOTE: Some laptops/personal computers only provide an audio output for headphones. It may be necessary to adjust the head- phone output level for proper recording of voice messages. NFC-CE6 Circuit Expander Module Specifications Power-limited circuitry. Up to six (6) circuits on the NFC-CE6 can be wired as Style V (Class B) or Style Z (Class A). Normal Operating Voltage for Speaker Circuits: 25 V@ 2.0 amps max. (Maximum Load Impedance of 12.5). 70.0 V @ 700 mA max. with maximum Load Impedance of 10092 operation possible for the primary circuit by plugging in an optional NFC-XRM-70V conversion transformer into J12 of the main control board. The same operation is possi- ble for the optional 50W amplifier by selecting the NFC- BDA-70V model. Speaker circuit wiring is supervised during standby, back- ground music, and alarm. Output Power: 50 watts total; Frequency Range: 400Hz - 4,000Hz. Maximum total capacitance: 250 pF. (Note that the total capacitance for the speaker outputs must not exceed the maximum of 250 iiF). End-of-Line Resistor required for Style V (Class B) speaker circuit: 15 KU 1 watt (P/N: ELR-15K)TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP provides programmed speaker control. Page 6 of 8— DN-60772:A3 • 9/29/14 Cabinet Specifications Backbox: 19.0°(48.26 cm) high x 16.65(42.29 cm) wide x S 5.20(13.23 cm) deep. Door: 19.26" (48.92 cm) high x 16.82"(42.73 cm) wide x 0.12"(O.30 cm) deep. Trim Ring (TR-CE-B): 22.00" (55.88 cm) high x 19.65" (49.91 cm) wide. Shipping Specifications Base Unit Weight: 27.85 lbs (12.63 kg). Temperature and Humidity ranges This system meets NFPA requirements for operation at 0-49 C/32-1209 F and at a relative humidity 93% ± 2% RH (non- condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the systems standby batteries and the electronic com- ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-279C/60-809 F Agency Listings and Approvals The listings and approvals below apply to the basic NFC-50/ 100(E) control panel. In some cases, certain modules may not be listed by certain approval agencies or listing may be in pro- cess. Consult factory for latest listing status. UL/ULC Listed S635. Compliant with UFC 4-021-01. CSFM: 6911-0028:0265. NYC Fire Dept. Certificate of Approval: #6163 Standards and Codes The NFC-50/100(E) complies with the following UL Standards and with NFPA 72 Fire Alarm system requirements. UL 864. UL 2572. DN-60772:A3 • 9/29/14 - Page 7 of 8 Notifier@ is a registered trademark of Honeywell International Inc. ©2014 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. ISO 9001 We try to keep our product information up-to-date and accurate. .1 =6 2110 I = 0 3 We cannot cover all specific applications or anticipate all requirements. I I (NGIPffiING A MANUFACTIRINS All specifications are subject to change without notice. I QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203 484-7118. www.notifier.com Page 8 of 8— DN-60772:A3 • 9/29/14 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 6911-0028:0265 Page 1 of 1 CATEGORY: 6911 -- VOICE COMMUNICATION SYSTEMS CONTROL UNITS LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models NFC-50/100 and NFC-50/100E. These are 50-watt audio emergency voice evacuation panels expandable to 100-watt for fire applications, mass notification applications, or both. Refer to listee's data sheet for additional detailed product description and operational considerations. System components: *ECC..LOC: Local Operator Console ECC-MCB; Main Control Board ECC-DKVCM; Display Board NFC-BDA-25V; Amplifier Module 25 VRMS NFC-BDA-70V; Amplifier Module 70 VRMS NFC-CE6; Speaker Circuit Expander Module NFC-XRM-70V; Transformer Module 70.7 VRMS RATING: Primary Operating: 120 V, 60 Hz, 3.5 A or 240 V, 50 Hz, 2 A INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as voice communication systems for use with separately listed compatible fire alarm control units to provide emergency voice evacuation signals. Refer to listee's Installation Instruction Manual for details. XLF: 6911-0075:0226 *12272016 dc To This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division S fl FCPS-24S6(CIE) & FCPS- 24S8(C/E) 6- & 8-Amp 24-Volt Remote Power SuDnhies General The FCPS-24S6E (6-amp) and FCPS-24S8E (8-amp) are remote power supplies with battery charger. The FCPS-24S6/- 24S8 may be connected to any 12 or 24 volt fire alarm control panel (FACP) or may be used as stand-alone supplies. Pri- mary applications include notification appliance (bell) circuit (NAG) expansion (to support ADA requirements and NAG syn- chronization) or auxiliary power to support 24 volt system accessories. The FCPS-24S6/-24S8 provides regulated and filtered 24 VDC power to four notification appliance circuits configured as either four Class B (Style Y) or Class A (Style Z, with ZNAC-4 option module). Alternately, the four outputs may be configured as all non-resettable, all resettable or two non- resettable and two resettable. The FCPS-24S6/-24S8 also contains a battery charger capable of charging up to 18 AH batteries. FCPS-2456C & FCPS-2458C are ULC-listed. NOTE: Unless otherwise specified, the terms FCPS-24S6 and FCPS-24S8 used in this document refers to the standard FCPS- 24S6 and FCPS-24S8, FCPS-2456C and FCPS-24S8C, the FCPS-24S6E and FCPS-24S8E Features UL-Listed NAG synchronization using System Sensor, Wheelock, or Gentex "Commander2" appliances. Operates as a "sync-follower" or as a 'sync-generator" (default). See note on page 2. Contains two fully-isolated input/control circuits - triggered from FACP NAG (NAG expander mode) or jumped perma- nently "ON" (stand-alone mode). Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4 module) NAGs. 6-amp (FCPS-2456) or 8-amp (FCPS-2458) full load out- put, with 3 amps maximum/circuit, in NAC expander mode (UL 864). 4-amp (FCPS-2456) or 6-amp (FCPS-2458) continuous output in stand-alone mode (UL 1481). Compatible with coded inputs; signals passed through. Optional power-supervision relay (EOLR-1). In stand-alone mode, output power circuits may be config- ured as: resettable, (reset line from FACP required), non-resettable, or a mix of two and two. Fully regulated and filtered power output - optimal for pow- ering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power. Power-limiting technology meets UL power-limiting require- ments. Form-C normally-closed trouble relay. Fully supervised power supply, battery, and NAGs. Selectable earth fault detection. AC trouble report selectable for immediate 2-hour delay. Works with virtually any UL 864 fire alarm control which uti- lizes an industry-standard reverse-polarity notification cir- cuit (including unfiltered and unregulated bell power). Requires input trigger voltage of 9 - 32 VDC. Self-contained in compact, locking cabinet - 15"H x 14.5W x 2.75"D (cm: 38.1H x 36.83W x 6.985D). dn-6927:a NOTIFIER® by Honeywell —P-1 .09 Includes integral battery charger capable of charging up to 18 AH batteries. Cabinet capable of housing 7.0 AH batter- ies. Battery charger may be disabled via DIP switch for applica- tions requiring larger batteries. Fixed, clamp-type terminal blocks accommodate up to 12 AWG (3.1mm2) wire. Specifications Primary (AC) Power: FCPS-2456C/-2458C: 120 VAC, 60 Hz, 3.2A maximum. FCPS-24S6E/-2458E: 240 VAC, 50 Hz, 1.15A maximum. Wire Size: minimum #14 AWG (2.0mm) with 600 V insula- tion. Control Input Circuit: Trigger Input Voltage: 9 to 32 VDC. Trigger Current: 2.0 mA (16-32 V); Per Input: 1.0 mA (9 - 16 V). Trouble Contact Rating: 5 A at 24 VDC. Auxiliary Power Output: Specific application power 500 mA maximum. Output Circuits: +24 VDC filtered, regulated. 3.0 A maximum for any one circuit. Total continuous current for all outputs (stand-alone mode): - FCPS-2456: 4.0 A maximum. - FCPS-2458: 6.0 A maximum. Total short-term current for all outputs (NAG expander mode): - FCPS-2456: 6.0 A maximum. - FCPS-24S8: 8.0 A maximum. Secondary Power (Battery) Charging Circuit: Supports lead-acid batteries only. Float-charge voltage: 27.6 VDC. dn-6927:a • 04/30/09 - Page 1 of 2 Maximum current charge: 1.5 A. Maximum battery capacity: 18 AH. Applications Example 1: Expand notification appliance power an additional 6.0 A (FCPS-24S6) or 8.0 A (FCPS-24S8). Use up to four Class B (Style Y) outputs or four Class A (Style Z) outputs (using ZNAC-4). For example, the FACP notification appliance circuits will activate the FCPS when reverse-polarity activation occurs. Trouble conditions on the FCPS are sensed by the FACP through the notification appliance circuit. Example 2: Use the FCPS to expand auxiliary regulated 24- volt system power up to 4.0 A (FCPS-24S6) or up to 6.0 A (FCPS-24S8). Both resettable and non-resettable power options are available. Resettable outputs are created by con- necting the resettable output from the FACP to one or both of the FCPS inputs. Example 3: Use addressable control modules to activate the FCPS instead of activating it through the FACP notification appliance circuits. This typically allows for mounting the FCPS at greater distances* away from the FACP while expanding system architecture in various applications. For example, an addressable control module is used to acti- vate the FCPS, and an addressable monitor module is used to sense FCPS trouble conditions. Local auxiliary power output from the FCPS provides power to the addressable control module. *NOTE: Addressable FACPs are capable of locating control and monitor modules at distances of up to 12,500 feet (3,810 meters). Sync Follower/Generator Note In some installations, it is necessary to synchronize the flash timing of all strobes in the system for ADA compliance. Strobes accomplish this by monitoring very short timing pulses on the NAC power which are created by the FACP. When installed at the end of a NAC wire run, the FCPS-24S6/-24S8 can track (i.e. "follow") the strobe synchronization timing pulses on the existing NAC wire run. This maintains the overall system flash timing of the additional strobes attaches to the FCPS. When the FCPS-24S6/-24S8 is configured (via DIP switch set- tings) as a "sync follower," the FCPS's NAC outputs track the strobe synchronization pulses present at the FCPS's sync input terminal. The pulses originate from an upstream FACP or other power supply. When the FCPS-24S6/-24S8 are configured (via DIP switch settings) as a "sync generator," the FCPS's sync input termi- nals are not used. Rather, the FCPS is the originator of the strobe synchronization pulses on the FCPS's NAC outputs. In "sync generator" mode, the sync type (System Sensor, Whee- lock, or Gentex) is selectable via DIP switch settings. Standards and Codes The FCPS-24S6 and FCPS-24S8 comply with the following standards: NFPA 72 National Fire Alarm Code. UL 864 Standard for Control Units for Fire Alarm Systems (NAC expander mode). UL 1481 Power Supplies for Fire Alarm Systems. Agency Listings and Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S635, S674 ULC Listed: S635 (FCPS-2456C & FCPS-2458C) CSFM Approved: 7315-0028:225 MEA: 299-02-E FM Approved Ordering Information FCPS-24S6: 6.0 A, 120 VAC remote charger powrer supply Includes main printed circuit board, transformers, enclosure ((15 H x 14.5"W x 275 D (cm 38 1Hx 36 83W x 6 985D]) and (installation in FCPS-24S6C: Same as above, ULC-listed. FCPS-24S6R: Same as FCPS-2456 with red enclosure. FCPS-24S6E: 6.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24S8: 8.0 A, 120 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. FCPS-24S8C Same as above, ULC-listed. FCPS-24S8R: Same as FCPS-24S8 with red enclosure. FCPS-24S8E: 8.0 A, 240 VAC remote charger power supply. Includes main printed circuit board, transformers, enclosure (15"H x 14.5W x 2.75"D [cm: 38.1H x 36.83W x 6.985D]), and installation instructions. ZNAC-4: Class A (Style Y) NAC option module. EOLR-1: 12/24 VDC end-of-line relay for monitoring four-wire smoke detector power. BAT-1270: Battery, 12-volt, 7.0 AH (two required, see BAT Series data sheet DN-6933). PS-1270: Battery, 12-volt, 7.0 AH (two required, see PS Series data sheet DN-1 109) I System Sensor® and NOTIFIER® are registered trademarks of Honeywell International Inc. ©2009 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. I ISO 9001 We try to keep our product information up-to-date and accurate. I We cannot cover all specific applications or anticipate all requirements. I I __________________ I ENtINCElINt & MRNIIFACI1RING All specifications are subject to change without notice. I QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com Page 2 of 2 - dn-6927:a • 04/30/09 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7315-0028:0225. Page 1 of 1 CATEGORY: 7315 -- POWER UNITS LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models FCPS-2456 and FCPS-24S8 are power limited power supply/battery chargers used for supervision and expanded power driving capability of up to four Notification Appliance Circuits (FACP Fire Circuits, Signaling Devices) or resettable/non resettable outputs. Model ZNAC-4 Class A converter. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 120 VAC, 24 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as a Power Supply/Battery Charger for use with separately listed compatible fire alarm control units. XLF: 7315-0075:0206 S 1-24-O3KK ør o This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other is Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division C Ll EFDUII8ÔJ 80 Character Liquid Crystal Dispi DN-6820:13 • D-123 NOTIFIER® Honeywell Annunciators t[.j itIi1 [1 The FDU-80 is a compact, cost-effective, 80-character, backlit LCD remote Fire Annunciator for use with the NOTIFIER Fire- Warden-100-2, NFS2-640, and NFS-320 Fire Alarm Control Panels (FACPs). The FDU-80 mimics the display of the control panel and displays complete system point status information. Up to 32 FDU-80s may be connected onto the EIA-485 termi- nal port of each FACP. The FDU-80 requires no programming, which saves time during system commissioning. Features 80-character Liquid Crystal Display. Mimics all display information from the host panel. Control switches for System Acknowledge, Signal Silence, Drill and Reset with enable key. System status LEDs for Power, Alarm, Trouble, Supervisory and Alarm Silenced. No programming necessary - FDU-80 connects to the ter- minal porton the FACP. Displays device type identifiers, individual point alarm, trou- ble or supervisory, zone and custom alpha labels. Time-and-date display field. Aesthetically pleasing design. May be powered from the host FACP or by remote power supply (requires 24 VDC). Up to 32 FDU-80 annunciators per FACP. Plug-in terminal blocks for ease of installation and service. Can be remotely located up to 6,000 feet (1828.8 m) from the FACP. Local piezo sounder with alarm and trouble resound. Semi-flush mounts to 2.188' (5.556 cm) minimum deep, three-gang electrical box (NOTIFIER PN 10103) or three- gangable electrical switchbox. Surface-mounts to NOTIFIER PN SBB-3 surface backbox. Operation The FDU-80 annunciator provides the FACP with point annun- ciation with full display text on an 80-character LCD display. The FDU-80 also provides an array of LEDs to indicate system status, and includes control switches for remote control of criti- cal system functions. The FDU-80 provides the FACP with up to 32 remote serially -connected annunciators. All field-wiring terminations on the FDU-80 use removable, compression-type terminal blocks for ease of wiring and circuit testing. Communication between the FACP and the annunciators is accomplished over an EIA-485 serial interface, which greatly reduces wire and installation cost over traditional systems. Installation The FDU-80 can be semi-flush mounted to a 2.188" (5.556 cm) minimum deep, three-gang electrical box or three-gang- able electrical switchboxes. Alternately, an SBB-3 surface backbox is available for surface-mount applications. 6820fdu8.jpg Ordering Information Itrol switches for remote control of system functions, and key.5 switch lock. FDU-80C: ULC-listed version; see DN-60573 for details. 10103: Three-gang electrical box, minimum 2.188" (5.556 cm) deep, for semi-flush mount applications. SBB-3: Three-gang surface backbox for surface-mount appli- cations. Agency Listings And Approvals These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL Listed: S635 MEA Listed: 245-00-E , FDNY: COA#6038 CSFM: 7120-0028:209 FM Approved NOTE: For ULC-listed version, see DN-60573. DN-6820:B.05/1712010—Page 1 o12 NOTIFIER® is a registered trademark of Honeywell International Inc. 02010 by Honeywell International mi All rights reserved. Unauthorized use of this document is strictly prohibited This document is not intended to be used for installation purposes. Iso 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requiremen:s. I lClNEEIINt & MNUFACTINf All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (203) 484-7118. www.notifier.com 41 Page 2 of 2— DN-6820:B • 05/17/2010 S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7120-0028:0209 Page 1 of 1 CATEGORY: 7120 -- ANNUNCIATORS LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sisson@honeywell.com DESIGN: Models FDU-80 and *FDU80G remote fire annunciators. Units are compact 80-character, backlit LCD fire annunciators. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product number, electrical rating and UL label. APPROVAL: Listed as annunciators for use separately listed compatible fire alarm control units. Refer to manufacturer's installation manual for details. NOTE: S *Rev. 10-03-06 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct IV operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 5 Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division 0 4' SYSTEM RECORD DOCUMENTS The SRD is the perfect item to help you meet demanding code requirements today. NFPA 72 2013 7.7.2.4 states that a cabinet must be "prominently labelled 'SYSTEM RECORD DOCUMENTS'." The SRD is the perfect fit to meet todays demanding code requirements. SAE's number one goal is to manufacture code compliant solutions and this product allows you to do just that. NFPA 72 2013 7.7.2.1 states, "With every new system, a documentation cabinet shall be installed at the system control unit or other approved location at the protected premises." This durable 16 gauge steel enclosure with a solid piano hinge and key lock will keep all of your code required documents in one safe place. With a 4GB USB flash drive it stores your fire alarm software safe and secure eliminating the occurrences of the software not being on site when technicians arrive to service the system. Along with your fire alarm software you can store your test & inspection, service records, manuals & system records. Using a standard USB B connector you may also store you records electronically (See NFPA 722013 7.5.6.7). The SRD has designated hooks to organize key rings and hold important business cards for easy access and reference. Inside the cover it has an organized record for identifying equipment information, required documentation locations (See NFPA 72 2013 7.2.1). 0 Standard Features: Installed with a 4 GB digital flash drive with USB B connector 2 key ring hooks to hold system keys Business card holder for key contacts Overall dimensions are 12" x 13" tall and 2 1/4" deep 18 gauge steel box and cover for security Durable powder coat baked on finish other colors available Standard 3/4" cat 30 key lock. Other lock assemblies available Solid stainless steel piano hinge Permanently screened white ink 1" high "SYSTEM RECORD DOCUMENTS" Legend sheet for documentation, passwords and system information IS09001 R Space Age NFPA COMPANY 800.486.1723 Toll Free MEMEMM MadeIS.A. REGISTERED 40 508.485.0966 Local Space Age Electronics, Inc. 2013 ED0584 LTI 0641 Rev.A 1/2 No Excuses, Just Solutions! WrELECTRONICS, INC. Specifications: The system record documents box (SRD) shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "SYSTEM RECORD DOCUMENTS "with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12" stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure. A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The SRD will have securely mounted inside a minimum of 4 Gigabyte digital flash memory drive with a standard USB B connector for uploading and downloading information. The drive shall not be accessible without toots to any person whom gains access to the records. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. USB Storage Interface Requires Standard USB-B Connector Proporty Internode,, CertifIcatIons and Approvals 16.1 System Installation CanRaclorI lN,RC..p*clvvO.h.sb..,O$.5d.,d 16.5 Authvlity Having Jlolrdlctlon1 sv0,v.vd5dH0b.l,.alwth,lpvoalt aado.1thb,e,vdAS.pdao*vo. 00, Eqalpetent lrfonv,tion Mlnlntsnr Roqolnod Dccon,nntatlon (taG-FUN) 5Covaccd,no.aaee,.*sao.og.,.noa.vveU,lRMs.alc2 It Cav,,I.cc.pcda,.aveve.sv.o,cp000s 110 y.c.aIc550p lap. *15,50.., coft h Sv0O. II .t Sn&oAa.EIv50o lv navololvl000 slnovo,Uovlraa la)4t6-1121 *001.005 LT10644 Real Legend sheet for storing system information including contacts, sign-off, maintenance & test information, and alternate locations of additional records. Ordering Information: Part # Description SSU00689 System Record Documents Cabinet RED SSU00690 Custom screening with your Logo EA0315 10 pack door legend sheet This document is subject to change without notice, see doc # E00479 for legal disclaimer ED0584 LT10641 Rev.A 2/2 Space Age Electronics, Inc. www.lsae.com 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax No Excuses, Just Solutions! CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM S LISTING SERVICE LISTING No. 7300-0553:0110 Page 1 of I CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: SPACE AGE ELECTRONICS58 Chockett Road, Sterling, MA 01564 Contact: Robert Scholl (508) 485-0966 Fax (508) 485-4740 Email: bobs@lsae.com DESIGN: Models TC2-32, TC1-18, TCX/A 64, TCX/D 128, ACE/A, AC2, ACE/D, IF-2, IFi, IFX1A and IFX/D enclosures. ModelsACE-11, ACE-12 and ACE-13, *ACE2424, *ACE 3036, *ACE 2436, *ACE 3048 document cabinets. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as fire alarm equipment enclosures and document cabinets for use with listee's fire alarm equipment. Refer to listee's Installation Instruction Manual for details. C 02-09-16 dc TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct 'v' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division 0 DN-6724:B3 (FCM-1 A) &(RM.i(A) NOTI Fl E R® Series 4 Control and Relay Modules by Honeywell Intelligent / Ar. r .i iDevices General FCM-1(A) Control Module: The FCM-1(A) Addressable Con- trol Module provides Notifier intelligent fire alarm control pan- els a circuit for Notification Appliances (horns, strobes, speakers, etc.). Addressability allows the FCM-1(A) to be acti- vated, either manually or through panel programming, on a select (zone or area of coverage) basis. FRM-1(A) Relay Module: The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for acti- vating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis. FlashScan® (U.S. Patent 5,539,389) is a communication pro- tocol developed by NOTIFIER Engineering that greatly enhances the speed of communication between analog intelli- gent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new infor- mation, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. Features Built-in type identification automatically identifies these devices to the control panel. Internal circuitry and relay powered directly by two-wire SLC loop. The FCM-1 (A) module requires power (for horns, strobes, etc.), or audio (for speakers). Integral LED "blinks" green each time a communication is received from the control panel and turns on in steady red when activated. LED blink may be deselected globally (affects all devices). High noise immunity (EMF/RFI). The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms). Wide viewing angle of LED. SEMS screws with clamping plates for wiring ease. Direct-dial entry of address 01— 159 for FlashScan loops, 01 - 99 for CLIP mode loops. Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z). Applications The FCM-1 (A) is used to switch 24 VDC audible/visual power, high-level audio (speakers). The FRM-1(A) may be pro- grammed to operate dry contacts for applications such as door holders or Air Handling Unit shutdown, and to reset four-wire smoke detector power. NOTE: Refer to the SLC Manual (PN 51253) for details regarding releasing applications with the FCM- 1(A). Refer to the FCM- 1-REL datasheet (DN-60390) for new FlashScan@ releasing applications. Construction (çM-1(A) The FCM-1(A) is configured for a single Class B (Style Y) or Class A (Style Z) Notification Appliance Circuit. The FRM-1(A) provides two Form-C dry contacts that switch together. Operation Each FCM-1 (A) or FRM-1 (A) uses one of 159 possible module addresses on a SLC loop (99 on CLIP loops). It responds to regular polls from the control panel and reports its type and status, including the open/normal/short status of its Notifica- tion Appliance Circuit (NAC). The LED blinks with each poll received. On command, it activates its internal relay. The FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) notification or control circuits. Upon code command from the panel, the FCM-1(A) will dis- connect the supervision and connect the external power sup- ply in the proper polarity across the load device. The disconnection of the supervision provides a positive indication to the panel that the control relay actually turned ON. The external power supply is always relay isolated from the com- munication loop so that a trouble condition on the external power supply will never interfere with the rest of the system. Rotary switches set a unique address for each module. The address may be set before or after mounting. The built-in TYPE CODE (not settable) will identify the module to the con- trol panel, so as to differentiate between a module and a sen- sor address. Specifications for FCM-1 (A) Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). The face plate is made of off-white heat-resistant plastic. Average operating current: 350 pA direct poll, 375 pA group Controls include two rotary switches for direct-dial entry of poll with LED flashing, 485 pA Max. (LED flashing, NAC address (01-159). shorted.) DN-6724:B3• 2/17/2011 —Page 1 of 2 Maximum NAC Line Loss: 4 VDC. External supply voltage (between Terminals T10 and Til): Maximum (NAC): Regulated 24 VDC; Maximum (Speakers): 70.7 V RMS, 50W. Drain on external supply: 1.7 mA maximum using 24 VDC supply; 2.2 mA Maximum using 80 VRMS supply. Max NAC Current Ratings: For class B wiring system, the current rating is 3A; For class A wiring system, the current rat- ing is 2A. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4 (101.6 mm) wide x 1.25 (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125 (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier Specifications for FRM.1(A) Normal operating voltage: 15 to 32 VDC. Maximum current draw: 6.5 mA (LED on). Average operating current: 230 pA direct poll; 255 pA group poll. EOL resistance: not used. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% non-condensing. Dimensions: 4.5" (114.3 mm) high x 4' (101.6 mm) wide x 1.25 (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125 (53.975 mm) deep box. Accessories: SMB500 Electrical Box; CB500 Barrier Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S635 ULC: S3705 (A version only) FM Approved CSFM: 7300-0028:0219 MEA: 14-00-E FDNY: COA #6067, #6065 Contact Ratings for FRM.1 (A) Current Maximum Load Application Rating Voltage Description 3 A 30 VDC Resistive Non-Coded 2 A 30 VDC Resistive Coded .9 A 110 VDC Resistive Non-Coded .9 A 125 VDC Resistive Non-Coded A .5 30 VDC Inductive Coded (UR5ms) 1 A 30 VDC Inductive Coded (LJR=2ms) .3A 125 VAC Inductive Non-Coded (PF=0.35) Inductive 1.5 A 25 VAC (PF0.35) Non-Coded Inductive .7 A 70.7 VAC (PF0.35) Non-Coded Inductive 2 A 25 VAC (PF0.35) Non-Coded NOTE: Maximum (Speakers): 70.7 V RMS, 50 W Product Line Information NOTE: "A" suffix indicates ULC Listed model. (FCM Intelligent Addressable Control Module. iJ)_ Intelligent Addressable Re lod) A2143-20: Capacitor, required for Class A (Style Z) operation of speakers. SMB500: Optional Surface-Mount Backbox. CB500: Control Module Barrier - required by UL for separat- ing power-limited and non-power limited wiring in the same junction box as FCM-1 (A). NOTE: For installation instructions, see the following documents: FCM-l(A) Installation document /56-1169. FRM-1(A) Installation document /56-3502. Notifier SLC Wiring Manual, document 51253. Notifier® and FlashScan® are registered trademarks of Honeywell International Inc. 02011 by Honeywell International Inc. All rights reserved, unauthorized use of this document is strictly prohibited. I sO 9001 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. 001=1=1 We cannot cover all specific applications or anticipate all requirements. UtlEEIlNI & MANUKIIIIIIING All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203)484-7161, FAX: (203) 484-7118. db www.notifier.com Page 2 of 2- DN-6724:133 • 2/17/2011 1~ (FMM.I (A), FMM 4QI (A), FZMIIflA) &(FDM.1(A) Monitor Modules with FlashScan® General Four different monitor modules are available for Notifier's intel- ligent control panels for a variety of applications. Monitor mod- ules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (FZM-1 (A)). FMM-1(A) is a standard-sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class or Style B (Class B) circuit of dry-contact input devices. FMM-101(A) is a miniature monitor module a mere 1.3' (3.302 cm) H x 2.75" (6.985 cm) W x 0.5" (1.270 cm) D that super- vises a Style B (Class B) circuit of dry-contact input devices. Its compact design allows the FMM-1 01(A) to be mounted in a single-gang box behind the device it monitors. FZM-1(A) is a standard-sized module that monitors and super- vises compatible two-wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. FDM-1(A) is a standard-sized dual monitor module that moni- tors and supervises two independent two-wire Style B (Class dry-contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two-wire systems. FlashScan® (U.S. Patent 5,539,389) is a communication pro- tocol developed by NOTIFIER that greatly increases the speed of communication between analog intelligent devices. Intelli- gent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other designs. (MM-1(A) Monitor Module) Built-in type identification automatically identifies this device as a monitor module to the control panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry of address: 01 - 159 on FlashScan loops; 01 —99 on CLIP loops. LED flashes green during normal operation (this is a pro- grammable option) and latches on steady red to indicate alarm. The FMM-1(A) Monitor Module is intended for use in intelli- gent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro- vides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC) for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The FMM-1 (A) can be used to replace MMX-1 (A) modules in existing systems. FMM-1(A) APPLICATIONS Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally- open dry-contact alarm activation devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class DN-6720:C • H-220 NOTIFIER® by Honeywell Ftt(A) (Type H) A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. FMM-1(A) OPERATION Each FMM-1(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita- tions on the loop). FMM-1(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 350 iiA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 40 ohms. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. DN-6720:C • 10/06/2010 - Page 1 of 4 FMM.1 01 (A) Mini Monitor Module Built-in type identification automatically identifies this device as a monitor module to the panel. Powered directly by two-wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. Tinned, stripped leads for ease of wiring. Direct-dial entry of address: 01 - 159 on FlashScan loops; 01 —99 on CLIP loops. 1415 0 1 ADDRESS 13 LOOP LIII10 8 76 8 76 TENS ONES I— o w do -J -J Lu .. - 0:: 0 on ..i The FMM-101(A) Mini Monitor Module can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The FMM-101(A) is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiat- ing device circuit for normally-open-contact fire alarm and security devices. The FMM-1 01(A) can be used to replace MMX-1 01(A) modules in existing systems. FMM-101(A) APPLICATIONS Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special super- visory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the cir- cuit. FMM-101(A) OPERATION Each FMM-101(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). FMM-101(A) SPECIFICATIONS Nominal operating voltage: 15 to 32VDC. Average operating current: 350 pA, 1 communication every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 40 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 400 pA. EOL resistance: 47K ohms. Temperature range: 32°F to 120°F (0°C to 490C). Humidity range: 10% to 93% noncondensing. Page 2 of 4— DN-6720:C • 10/06/2010 Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.65' (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. FZM-1 (A) Interface Module Supports compatible two-wire smoke detectors. Supervises IDC wiring and connection of external power source. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring. Direct-dial entry of address: 01 —159 on FlashScan loops, 01 —99 on CLIP loops. LED flashes during normal operation; this is a programma- ble option. LED latches steady to indicate alarm on command from control panel. The FZM-1(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two- wire conventional smoke detectors. It transmits the status (nor- mal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being moni- tored must be UL compatible with the module. The FZM-1 (A) can be used to replace MMX-2(A) modules in existing sys- tems. FZM-1(A) APPLICATIONS Use the FZM-1 (A) to monitor a zone of two-wire smoke detec- tors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K ohm End-of-Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resis- tance is 25 ohms). Install ELR across terminals 8 and 9 for Style D application. FZM-1(A) OPERATION Each FZM-1 (A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limita- tions on the loop). FZM-1(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 ohms. Average operating current: 300 pA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.91K ohms. External supply voltage (between Terminals T3 and T4): DC voltage: 24 volts power limited. Ripple voltage: 0.1 Vrms maximum. Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. S S S Mi(A),Dual Monitor Module The FDM-1(A) Dual Monitor Module is intended for use in intelli- gent, two-wire systems. It provides two independent two-wire initiating device circuits (lDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices; or either normally open or nor- mally closed security devices. The module has a single panel- controlled LED. NOTE: The FDM- 1(A) provides two Style B (Class B) IDC circuits ONLY. Style 0 (Class A) IDC circuits are NOT supported in any application. F0M-1(A) SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 pA (LED flashing). Maximum IDC wiring resistance: 1,500 ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 pA EOL resistance: 47K ohms. Maximum SLC Wiring resistance: 40 Ohms. Temperature range: 320 to 120°F (0° to 49°C). Humidity range: 10% to 93% (non-condensing). Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 2.125' (5.398 cm) deep. FDM-1(A) AUTOMATIC ADDRESSING The FDM-1 (A) automatically assigns itself to two addressable points, starting with the original address. For example, if the FDM-1(A) is set to address "26", then it will automatically assign itself to addresses "26" and "27". . NOTE: "Ones" addresses on the FDM-1(A) are 0, 2, 4, 6, or 8 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. CAUTION: Avoid duplicating addresses on the system. - 161.002/23/3 (AFP-200: FMM- 11-101, FZM- 1) - 161.002/42/1 (NFS-640: FMM-1I-101) Lloyd's Register: —03/60011/El (FMM-1/-101, FZM-1) - 94/60004/E2 (AFP-200: except FDM- 1) - 02/60007 (NFS-640: FDM-1) FDNY: COA #6038 (NFS2-640, NFS-320), COA# 6058 (NFS2-3030) Product Line Information NOTE: "A" suffix indicates ULC-listed model. tFMM l(A):MtormodiE FMM-101(A): Monitor module, miniature. FZM-1(A): Monitor module, two-wire detectors. (cuits. SMB500: Optional surface-mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, PN51253. Installation FMM-1 (A), FZM-1 (A), and FDM-1 (A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 sur- face-mount box. Mounting hardware and installation instruc- tions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regulations. These modules are intended for power-limited wiring only. The FMM-1 01(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. UL: S635 ULC:S635 FM Approved CSFM: 7300-0028:0219 MEA: 457-99-E U.S. Coast Guard: DN-6720:C • 10/06/2010- Page 3 of 4 S S 0 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE 0 LISTING No. 7300-0028:0219 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models XP6-R relay module, XP6-C, supervising control module, XP10-M input monitor module, XP6-MA six zone interface module, FMM-1, FMM-101, FZM-1, FSM-101,FDM-1, FTM-1 monitor modules, FCM-1, FRM-1'control modules, and *FDRM1 with 2 input/2 output relay module. All devices are intended to be connected between the signaling line circuit of a compatible fire alarm control panel. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 16-33 VDC Primary INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in manner acceptable to the authority having jurisdiction. MARKING: Listee's name, product number and UL label. APPROVAL: Listed as control unit accessories for use with listee's separately listed compatible fire alarm control units. Model FTM-1 is intended to be used with Notifier Models NFS-640, NFS2-640 (CSFM Listing No. 7165-0028:214), NFS-3030, NFS2-3030 (CSFM Listing No. 7165-0028:224) Fire Alarm Control Units. NOTE: . If an external power supply is used for Model XP6-MA, the negative of the external power supply is referenced to the negative of the auxiliary supply of the compatible control panel. This is done in order to detect ground faults on the initiating circuit. *Rev. 10-24-11 mt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct RV' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division S S U -I S I (NBG.l 2LX (Addressable Manual Pull Station) The Notifier NBG-12LX is a state-of-the-art, dual-action (i.e., requires two motions to activate the station) pull station that includes an addressable interface for any Notifier intelligent control panel except FireWarden series panels, and the NSP- 25 panel. Because the NBG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features Maintenance personnel can open station for inspection and address setting without causing an alarm condition. Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. Handle latches in down position and the word "ACTIVATED" appears to clearly indicate the station has been operated. Captive screw terminals wire-ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm2 wire). Can be surface mounted (with SB-la or SB-I/O) or semi- flush mounted. Semi-flush mount to a standard single- gang, double-gang, or 4" (10.16 cm) square electrical box. Smooth dual-action design. Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. Highly visible. Attractive shape and textured finish. Key reset. Includes Braille text on station handle. Optional trim ring (BG12TR). Meets UL 38, Standard for Manually Actuated Signaling Boxes. Up to 99 NBG-12LX stations per loop on CLIP protocol loops. Up to 159 NBG-12LX stations per loop on FlashScan® pro- tocol loops. Dual-color LED blinks green to indicate normal on FlashScan® systems. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications Shipping Weight: 9.6 oz. (272.15 g) . Normal operating voltage: 24 VDC. Maximum SLC loop voltage: 28.0 VDC. Maximum SIC standby ,current: 375 Maximum SLC alarm current: 5 mA. Temperature Range &F to 120°F (0-C to 49-C) Relative Humidity: 10% to 93% (noncondensing) For use indoors in a dry location DN-6726:D • H-240 (9111,NOTIFIER by Honeywell Devices hNBG:12LX Addressable Manual Pull Station Installation The NBG-12LX will mount seni-flush i1to a single-gang, dou- ble-gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to tie model SB-10 or SB-I/O sur- face backbox. If the NBG-12LX is being semi-flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is usually needed for semi-Hush mounting with 4" (10.16 cm) or double-gang boxes (not with single-gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word "ACTI- VATED" (in bright yellow) appears at the top of the handle, while a portion of the handle ptrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically rese:s the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 - 159 on FlashScan® syster-s, 1 —99 on CLIP systems). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non-coded, with a key- operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red-colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the staticns in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-b 0 or SB-I/O; or semi-flush mounting on a standard single-gang, double-gang, or LN-6726:D•4/1312012—Page 1 of 2 4"(10.16 cm) square electrical box, and shall be installed within the limits defined by the Americans with Disabilities Act (ADA) or per national/local requirements. Manual Stations shall be Underwriters Laboratories listed. Manual stations shall connect with two wires to one of the con- trol panel SLC loops. The manual station shall, on command from the control panel, send data to the panel representing the state of the manual switch. Manual stations shall provide address setting by use of rotary decimal switches. The loop poll LED shall be clearly visible through the front of the station. The LED shall flash while in the normal condition, and stay steadily illuminated when in alarm. Product Line Information INBG-12LX: Dual-action addressable pull station. Includes l kockng feature (Listed for Canadian and non Canadian appj (cations) NBG-1 2LXSP: Spanish/English labelled version. NBG-12LXP: Portuguese labelled version. SB-10: Surface backbox; metal. SB-I/O: Surface backbox; plastic. BG12TR: Optional trim ring. 17021: Keys, set of two. NY-Plate: New York City trim plate. Agency Listings and Approvals In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in pro- cess. Consult factory for latest listing status. UL/ULC Listed: S692 (listed for Canadian and non-Cana- dian applications). MEA: 67-02-E. CSFM: 7150-0028:0199. FDNY: COA #6085 (NFS2-640), COA #6098 (NFS2-3030). BSMI: C1313066760047. U.S. Coast Guard. Lloyd's Register. FM Approved. Patented: U.S. Patent No. D428,351; 6,380,846; 6,314,772; 6,632,108. NOTIFIER® and FlashScan® are registered trademarks of Honeywell International Inc. ©2012 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohiLited. This d I so 9001 ccument is not intended to be used for installation purposes. IM We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. FNGlNEEllN &MNIQFACTIRINC All specifications are subject to change without notice. QUALITY SYSTEMS Made in the U.S. A. For more information, contact Notifier. Phone: (203) 484-7161, FAX: (20) 484-7118. www.notifier.com Page 2 of 2— DN-67260 • 4/13/2012 S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM S LISTING SERVICE LISTING No. 7150-0028:0199 Page 1 of 1 CATEGORY: 7150-- FIRE ALARM PULL BOXES LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sissonthoneyweIl.com DESIGN: Models NBG-12, NBG-125, NBG-12LR, NBG-12LRA, NBG-12LAO, NBG-12LAOB, NBG-12-LO, NBG-12LOB, NBG-12W, NBG-12LW, NBG-12NC, NBG-12WP, NBG-12LWP, NBG-12L,NBG-12LX; NBG-12LA, NBG-12P5, NBG-12LSP, NBG-12LPS, NBG-12LPSP, NBG-12SP, NOT-BG12LX, NBG-12LXSP, NBG-12LXBL and NBG-12LXP fire alarm pull boxes. All units except Model NBG-12S are dual action pull stations. Models NBG-12LR and NBG-12LRA are intended for agent releasing device. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, and UL label. APPROVAL: Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units. Models NBG-12WP, NBG-12LW, NBG-12W, NBG-12LWP, NBG-12LAO, NBG-12L0, NBG-12LAOB and NBG-12LOB are intended for outdoor use when installed with Models WBB, SB-I/O, or WP-10 back box. Refer to listee's Installation Instruction Manual for details. S These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition and California amendments which the controls and operating mechanisms required to be operable at no more than 51bs. force with one hand and shall not require tight grasping, pinching, or twisting of the wrist. *Corrected 10-08-12 bh TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division S FSP-951 in B300-6 Base FSP-951 R installed in a DNR/DNRW, -20°C to 70°C (-4°F to 158°F). ULIULC Listed Velocity Range: 0-4000 ft/mm. (1219.2 m/min.), suitable for installation in ducts. Relative Humidity: 10%-93% noncondensing. Thermal Ratings: Fixed-temperature setpoint 135°F (57°C). DETECTOR SPACING AND APPLICATIONS NOTIFIER recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. System Smoke Detector Application Guide, document A05-1003, is available at systemsensor.com ELECTRICAL SPECIFICATIONS Voltage Range: 15-32 volts DC peak. Standby Current (max. avg.): 200pA © 24VDc (one cornmunica-' tion every five seconds with LED enabled). LED Current (max.): 4.5mA© 24 VDC ('ON'). Installation FSP-951 series plug-in detectors use a separate base to simplify installation, service, and maintenance. Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DN-60981. NOTE: 1) Because of inherent supervision provided by the SLC loop, end-of-line resistors are not required. Wiring 7-taps" or branches are permitted for Style 4 (Class 'B") wiring. 2) When using relay or sounder bases, consult the ISO-X(A) installation sheet 156-1380 for device limita- tions between isolator modules and isolator bases. DN-60977:A FSP-951 Series NOTIFIER 8 . Intelligent Plug-In Photoelectric 0 by Honeywell Smoke Detectors Intelligent/Addressable i r i Devices General The NOTIFIER FSP-951 Series intelligent plug-in smoke detectors are designed for both performance and aesthetics. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combus- tion sources in accordance with more stringent code standards. The FSP-951 Series detector sensitivity can be programmed in the con- trol panel software. Sensitivity is continuously monitored and reported to the panel. Point ID capability allows each detector's address to be set with rotary, decimal address switches, providing exact detector location for selective maintenance when chamber contamination reaches an unacceptable level. Dual electronic thermistors add 135°F (57°C) fixed temperature thermal sensing on the FSP-951T. The FSP-951 R is a remote test capable detector for use with DNA Series duct detector housings. FSP-951 series detec- tors are available for both FlashScan® and CLIP applications as designated. Features New modern profile for improved aesthetics. Designed to meet UL268 7th Edition. Stable communication technique with noise immunity. Low standby current. Two-wire SLC connection. Compatible with FlashScan® and CLIP protocol systems. . • Rotary, decimal addressing (1-99 on CLIP systems, 1-159 on FlashScan systems). Optional remote, single-gang LED accessory. Dual LED design provides 3600 viewing angle. Visible bi-color LEDs blink green every time the detector is addressed, and illuminate steady red on alarm (FlashScan sys- tems only). Remote test feature from the panel. Walk test with address display (an address on 121 will blink the detector LED: 12-[pause]-1 (FlashScan systems only). Built-in functional test switch activated by external magnet. Built-in tamper-resistant feature. Sealed against back pressure. Expanded color options. SEMS screws for wiring of the separate base. Optional relay, isolator, and sounder bases. Specifications Sensitivity: UL Applications: 0.5% to 4.0% per foot obscuration. ULC Applications: 0.5% to 3.5% per foot obscuration. Size: 2.0° (5.3 cm) high; base determines diameter. - B300-6: 6.1° (15.6 cm) diameter: - B501: 4° (10.2 cm) diameter., For a complete list of detector bases see DN-60981. Shipping weight: 3.40z (96.4g) Operating Temperature range: S . FSP-951, 0°C to 50°C (32°F to 122°F). FSP-951T, 0°C to 38°C (32°F to 100°F). DN-60977:A • 4/17/18 - Page 1 of 3 Agency Listings and Approvals These listings and approvals apply to the detectors specified in this document. In some cases, certain detectors or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL/ULC Listed: S911 FM Approved CSFM: 7272-0028:0503 Product Line Information NOTE: Detectors must be mounted to one of the Intelligent Bases listed below. "A" suffix indicates ULC Listed model. "IV" suffix indicates FlashScanf9 and CLIP device. FSP-951: White, low-profile intelligent photoelectric sensor, FlashS- can only. FSP-951A: Same as FSP-951 but with ULC listing. FSP-951-IV: Ivory, low-profile intelligent photoelectric sensor. FSP-951A-IV: Same as FSP-951-IV but with ULC listing. FSP-951T: White, same as FSP-951 but includes a built-in 135°F (57°C) fixed-temperature thermal device. FlashScan only. FSP-951TA: Same as FSP-951T but with ULC listing. FSP-951T-IV: Ivory, same as FSP-951T but includes a built-in 135°F (57°C) fixed-temperature thermal device. FSP-951TA-IV: Same as FSP-951T-IV but with ULC listing. FSP-951R: White, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FlashScan only. FSP-951 RA: Same as FSP-951 R but with ULC listing. For use with DNRA. FSP-951R-IV: Ivory, low-profile intelligent photoelectric sensor, remote test capable. For use with DNR/DNRW. FSP-951 RA-IV: Same as FSP-951 R-IV but with ULC listing. For use with DNRA. INTELLIGENT BASES NOTE: For details on intelligent bases, see DN-60981 B300-6: White, 6" base, standard flanged low-profile mounting base. B300-6-IV: Ivory,6" base, standard flanged low-profile mounting base. B300A-6: Same as B300-6, ULC listed. B300A-6-IV: Ivory, 6" standard flanged low-profile mounting base, ULC listed. B300-6-BP: Bulk pack of B300-6, package contains 10 B224B1-WH: White, isolator detector base. B224B1-IV: Ivory isolator detector base. B224B1A-WH: White, isolator detector base, ULC listing. B224B1A-IV: Ivory isolator detector base, ULC listing. B200S-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. B200S-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. B200SA-WH: Same as B200S-WH, ULC listing. 8200SA-IV: Same as B200S-IV, ULC listing. B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with SO Series detector applications. B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with SO Series detector applications, ULC listing. B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +1- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +1- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. B200SRA-WH: Same as B200SR-WH with, ULC listing. B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing. B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B21OLP(A) base. B501-WHITE: White, 4" standard European flangeless mounting TR300-IV: Ivory, replacement flange for B21OLP(A) base. base. UL/ULC listed. RA100Z(A): Remote LED annunciator. 3 — 32 VDC. Mounts to a B501-BL: Black, 4" standard European flangeless mounting base. U.S. single-gang electrical box. For use with B501 (A) and B300(A)- UL/ULC listed. 6. B501-IV: Ivory color, 4" standard European flangeless mounting M02-04-00: Test magnet. base. ULJULC listed. M02-09-00: Test magnet with telescoping handle. B501-WHITE-BP: Bulk pack of B501 -WHITE contains 10. B224RB-WH: White, relay base. B224RB-IV: Ivory, relay base. B224RBA-WH: White, relay base, ULC listing. B224RBA-IV: Ivory, relay base, ULC listing. Page 2 of 3— DN-60977:A • 4/17/18 02018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. I SO 9001 S ___________________ All specifications are subject to change without notice. ENIflflNG & MNUFAC1URIN QUALIT Y SYSTEMS For more information, contact Notifier. Phone: (800) 627-3473, FAX: (203) 484-7118. www.notifier.com Page 3 of 3— DN-60977:A • 4/17/18 S S S 9 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL 0 FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-0028:0503 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megansisson@honeywell.com DESIGN: Models FSP-951, FSP-951R, FSP-951T, FSP-951T-ISO, NP-200, NP-200R, and NP-2001 analog addressable, photoelectric smoke detectors for open area and duct installations. Models FSP-9511, FSP-951T-ISO and NP-200T have complementary heat detectors. All models are similarl except for population/depopulation of components on the Printed Wiring Board for the intended features. All above models may be followed by two digit Suffix indicating the color of the detector enclosure: no suffix for white, -IV for ivory, -BL for black. Refer to listee's Installation and Maintenance Instruction for additional detailed product description and operational considerations. RATING: 24 VDC. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as photoelectric smoke detectors. Detectors are for use with separately listed bases: *Model B71OLP (CSFM No. 7300-0028:0173); System Sensor Models *B224Bl *13224RB (CSFM No. 7300-1653:0126); B200S, B200SR (CSFM No. 7300-1653:0213); B2005-LF, B200SR-LF (CSFM No. 7300-1653:0238); *13501 *132101-P 13300-6, B300-6-IS (CSFM No. 7300-1653:0109). System Sensor duct detector housings Models DNR and DNRW (CSFM No. 3240-1653:0209), Fire-Lite duct detector housing Model D355PL (CSFM No. 3240-0075:0221) and separately listed compatible fire alarm control units. Refer to manufacturer's Installation Manual for details. NOTE: The photoelectric type detectors are generally more effective at detecting slow, smoldering fires that smolder for hours before bursting into flame. Sources of these fire may include cigarettes burning in the couched or bedding. The ionization type detectors are generally more effective at detecting fast, flaming fires that consume combustible materials rapidly and spread quickly. Sources of these fires include paper burning in a waste container or a grease fire in the kitchen. *Rev 02-14-18 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division C 0 Features Bases enable quick and secure detector plug-in SEMS screws provide easy wiring connection Support for 12-24 AWG provides installation flexibility Multiple base formats meet application requirements 5 • Standard white color with ivory and black options UL 268 compliant Mechanical locking feature restricts removal of attached sensor head Specialty Base Features Pre-wired mounting plate simplifies installation Application driven feature sets Sounder bases both UL 268 and UL 464 compliant Agency Listings SIGNALING & A1111.11 J — 4 LISTED S S911 Relay 3062622 4'S 6' bases: 7300-1653:0109 & 1551535 bases: 7300-1653.0126 Osuislar bass: 7135-1653:0213 Low-frequency bases: 7300-1653:0238 SYSTEM SENSOR Select Series Mounting Base Options System Sensor mounting bases and kits provide a variety of installation options for detectors in any application. To meet local code and application requirements, System Sensor offers standard 4" and 6 bases, as well as, specialty base designs including relay, isolator, sounder and low frequency sounder options for Select Series detectors. The standard 4" and 6" bases offer a plug-in detector base intended for use in intelligent systems, with screw terminals provided for power (+ and -), and remote annunciator connections. Communication takes place over the power (+ and -) lines. The 4" base offers a compact design while the 6" base provides compatibility with a wider range of junction boxes. The Select Series specialty bases support application driven requirements. The bases employ a separate mounting plate that installs on various junction box sizes to eliminate unsightly surface-mount boxes. The mounting plate enables pre-wiring of all connections to speed and simplify installation. Relay bases (8224RB-WH/B224RB-IV) provide one form C contact relay for control of auxiliary functions, such as door closure and elevator recall. The relay can operate in two different modes (short and long delay). The activation time for the short delay is 60 ms to 100 ms, while the activation time for the long delay is 6 sec to 10 sec. A shunt with pin headers, located on the base PC board, is used to set the delay timing. Isolator bases (B224B1-WH/B224Bl-lV) allow the Signaling Line Circuit (SLC) loop to operate under fault conditions created from a short circuit preventing an entire communication loop from being disabled. The base isolates the section of the loop containing the short circuit from the remainder of the circuit and automatically restores when the fault is corrected. The Select Series sounder and low frequency sounder bases are designed for new and existing dwelling unit applications. They offer maximum flexibility in installation, configuration, and operation to meet or exceed UL 268 and UL 464 requirements. The tConsult your fire alarm control panel manufacturer for compatibility with the addressable model of the sounder base. SPDS901-00 • 04/0412018 • Page 1 CURRENT RATING MAXIMUM VOLTAGE LOAD DESCRIPTION APPLICATION 2A 25 VAC PF = 0.35 Non-coded 3A 30 VDC Resistive Non-coded 2A 30 VDC Resistive Coded 0.46 A 30 VDC (L/R = 20m5) Non-coded 0.7 A 70.7 VAC PF = 0.35 Non-coded 0.9 A 125 VDC Resistive Non-coded 0.5 A 125 VAC PF = 0.75 Non-coded 0.3 A 125 VAC PF = 0.35 Non-coded Operating Voltage 15 to 32 VDC Standby Current 450 pA max. Isolation Current 15 mA max S Select Series low frequency sounder bases are designed to meet the NFPA 72 sleeping space requirement to produce a fundamental frequency of 520 Hz +1- 10% with a square wave or its equivalent. Studies show that a lower frequency, centered around 520 Hz, is the most ideal to wake sleeping occupants, even those with mild to severe hearing loss. The B200SR sounder and LF sounder bases (B200SR-WH/B200SR-IV/B200SR-LF-WH/ B200SR-LF-IV) are fully compatible with existing B501BH-Series sounder base installations. The device enables users to select one of two B501-supported tones (ANSI Temporal 3 or Continuous) through a jumper. The B200S sounder and LF sounder bases (B200S-WH/B200S-IV/B200S-LF-WH/ B200S-LF-IV) adopt the same address as the detector, but use a unique device type on the loop. The Fire Alarm Control Panel (FACP) can use that address to command an individual sounder - or a group of sounders - to activate. The command set from the FACP can be tailored to multiple event-driven tone outputs allowing selection of volume (75 or 85 dBA), tone (ANSI Temporal 3, ANSI Temporal 4 or March Time) and group. In addition, some FACPs will enable custom tone patterns. The B2005 series sounder bases recognize the System Sensor synchronization protocol. This enables it to be used as a component of the general evacuation signal - along with other System Sensor AV appliances - when connected to a power supply or FACP output capable of generating the System Sensor synchronization pulses. [1 Specifications - Select Series Bases Diameter B501-WHITE, B501-IV, B501-BL: 4.0'(10.2 cm) B2005-WH, B200S-IV, B200S-LF-WH, B200S-LF-IV, B200SR-WH, B200SR-IV, B200SR-LF-WH, B200SR-LF-IV: 6.85' (17.4 cm) B300-6, 13300-6-IV: 6.1(155 mm) B224B1-WH, B224B1-IV, B224RB-WH, B224RB-IV: 6.85(17.4cm) Base Height B501-WHITE, B501-IV, B501-BL: 0.74"(18.8 mm) (without sensor) B200S-WH, B200S-IV, B200S-LF-WH, B200S-LF-IV, B200SR-WH, B200SR-IV, B200SR-LF-WH, B200SR-LF-IV: 1.6"(4.1 cm) B300-6, B300-6-IV: 0.76(19mm) B224B1-WH, B224B1-IV, B224RB-WH, B224RB-IV: 1.61" (4.1 cm) Weight: B501-WHITE 0.32 lb (145 gm) B200S-WH, B200S-IV, B200SR-WH, B200SR-IV: 0.50 lb (227 gm) 8200S-LF-WH, B200S-LF-IV, B200SR-LF-WH, B200SR-LF-IV. Weight: 0.6 lb (272 gm) B300-6, B300-6-IV: 0.32 lb (145 gm) B224RB-WH, B224RB-IV, B224B1-WH, B224B1-IV 0.50 lb (227 gm) Wire Gauge B501-WHITE, B501-IV, B501-BL, B224B1-WH, B224B1-IV, B224RB-WH, B224RB-IV, B300-6, B300-6-IV: 18 AWG (0.823 mm2) to 12 AWG (3.31 mm2) B200S-WH, B200S-IV, B200S-LF-WH, B200S-LF-IV, B200SR-WH, B200SR-IV, B200SR-LF-WH, B200SR-LF-IV: 14 AWG to 12 AWG Temperature Range Refer to applicable sensor Operating Temperature Range using the Base/Sensor Cross Reference Chart at systemsensor.com Humidity Range 10% to 93% RH non-condensing Operating Voltage 15 to 32 VDC Standby Current 150 pA Operating Voltage 15 to 32 VDC Standby Current 170 pA max. Operating Voltage 15 to 32 VDC Standby Current 170 pA max. Set Time Position 1, Short Delay: 60 to 100 ms Position 2, Long Delay: 6 to 10 sec Reset Time 20 ms max. Relay 2 coil latching relay Characteristics 1 Form C contact UL/ULC Rating: S SPDS90100 • 04/04/2018 • Page 2 n External Supply Electrical Ratings External Supply 16 to 33 VDC (VFWR) Voltage Standby Current: 500 pA maximum Alarm Current: 35 mA maximum (at high volume setting); 15 mA maximum (at low volume setting) SLC Electrical Ratings SLC Operating 15 to 32 VDC Voltage: SLC Standby 300 pA maximum Current: Sound Output High Volume: Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) Low Volume: Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) External Supply Electrical Ratings External Supply 16 to 33 VDC (VFWR) Voltage Standby Current: 550 pA maximum VDC Alarm Current, High-volume setting 70 mA maximum @ 33.0 VDC 90 mA maximum @ 24.0 VDC 140 mA maximum @16.0 VDC Alarm Current, Low-volume setting 15 mA maximum @33.0 VDC 20 mA maximum @ 24.0 VDC 25 mA maximum @ 16.0 VDC SLC Electrical Ratings SLC Operating 15 to 32 VDC Voltage: SLC Standby 300 pA maximum (base only, refer to Current: applicable sensor specification) Sound Output High Volume: Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) Low Volume: Greater than 75 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) Electrical Specifications: External Supply Electrical Ratings External Supply 16 to 33 VDC (VFWR) Voltage Standby Current: 1 mA maximum VDC Alarm Current 65 mA maximun @ 33.0 VDC 90 mA maximum @ 24.0 VDC 125 mA maximum @16.0 VDC SLC Electrical Ratings SLC Operating 15 to 32 VDC Voltage: SLC Standby Refer to applicable sensor specification. Current: Sound Output Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) External Supply Electrical Ratings . External Supply Voltage 16 to 33 VDC (VFWR) Standby Current: 500 pA maximum Alarm Current: 35 mA maximum SLC Electrical Ratings SLC Operating Voltage: 15 to 32 VDC SLC Standby Current: 300 pA maximum Sound Output Greater than 85 dBA minimum measured in a UL reverberant room at 10 feet, 24 Volts (in continuous tone) SPDS901-00 • 04/04/2018 • Page 3 S TR300 Trim Ring \\ Select Series Junction Box Selection Guide B501-WHITE, B501-IV, No No Yes No No Yes Yes Yes Yes No B501-BL B200S-WH, B200S-IV, B200S-LF-WH, B200S-LF-IV, B200SR-WH, B200SR-IV, Yes Yes Yes Yes Yes Yes No No No No B200SR-LF-WH, B200SR-LF-IV B300-6, B300-6-IV Yes No Yes Yes Yes Yes No No No No B224B1-WH, 8224B1-IV Yes Yes Yes Yes Yes Yes No No No No B224RB-WH, B224RB-IV Yes Yes Yes Yes Yes Yes No No No No * with 3.0 mud ring Note: Box depth contingent on base and wire size. Refer to National Electric Code or applicable local codes for appropriate recommendations. Ordering Information L'i[.I.[uI White Ivory Black B501-WHITE B501-IV B501-BL 4" Flangeless mounting base Accessories B501-WHITE-BP - - 4" Flangeless mounting base bulk pack, white .B300-6 B300-6-IV - 6" Flanged mounting base RA100Z B300-6-BP - - 6" Flanged mounting base bulk pack, Remote LED white Annunciator B200S-WH B200S-IV - Intelligent addressable sounder base 0 B200S-LF-WH B200S-LF-IV - Inteligent addressable sounder base, low-frequency B200SR-WH B200SR-IV - Standard sounder base (compatible with B501BH series) B200SR LF WH B200SR LF IV - Low frequency sounder base (compatible with B501BH series) CK300-BL B224B1-WH B224131-IV - Isolator base Color Kit B224RB-WH B224RB-IV - Relay base Related Accessories White Ivory Black CK300 CK300-IV CK300-BL Color kit (includes cover and trim ring) CK300-IR CK300-IR-IV CK300-IR-BL PTIR Color kit (includes cover and trim ring) TR300 TR300-IV - Trim ring - SMB600 Surface mounting kit (flanged), ivory RA100Z - - Remote LED annunciator M02-04-00 Detector test magnet M02-09-00 Test magnet with telescoping handle SYSTEM 3825 Ohio Aveiue • St. Charles, IL 60174 02018 Systee Sensor. SENSOR Phone. 800-SENSOR2 • Fax: 630-377-6495 Product spec8icationssubectto change v0out notice. Visit systerrrscnsar.com for current product inlorrnation, including the latest version at this data sheet. . www.systemsensor.com SPDSOOI.00 • 04/04/20t8 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1653:0109 Page 1 of I CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models B401, B401 B, B401 R, B401 BR, B401 BR-750, B401 R-750, B402B, B404B, B404BT, B406B, B501, B501 B, 14506587-002, B501BH, B501 BHT, B401BH, B110LP, 13110RLP, 1311ORLP750, B112LP, B114LP, B114LPBT, B116LP, B21OLP, B501-BL, B501-IV, '13501 -WHITE,, B300-6, B300-6-IV, B300-6-IS detector bases. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, *model number, *electrical rating and UL label. APPROVAL: Listed as detector bases for use with separately listed compatible detectors. *Refer to Manufacturers Installation Instruction Manual for details. NOTE: Formerly 7300-1209:128 S *Rev 04-03-18 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 5 Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTIL.LO, Program Coordinator Fire Engineering Division L-1 Lt 0 6 SYSTEM S SENSOR 4-Wire Photoelectric Duct Smoke Detector The lnnovairFlex' Series are the only duct smoke detectors flexible enough to fit configurations from Innovair" square to rectangular and everything in between. Features Photoelectric, integrated low-flow technology Air velocity rating from 100 ft/min to 4,000 ft/mm (0.5 m/s to 20.32 m/sec) Versatile mounting options: square or rectangular configuration Plug-in sensor offers superb false alarm immunity and the latest sensor technology Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non-condensing) Patented sampling tube installs from front or back of the detector with no tools required Increased wiring space with a newly added 3/4-inch conduit knockout One easy-access Test/Reset button and improved LED status Patented interconnect feature for multi-fan shutdown New high contrast terminal designations Built-in short circuit protection from operator wiring errors Field selectable settings for configuring the detector Two DPDT Form-C relay contacts 24 VAC/DC or 120 VAC Backward compatibility with existing I nnovair products, including remote accessories The InnovairFiex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of —4°F to 158°F, and a humidity range of 0 to 95 percent (non- condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. The InnovairFIex housing provides ample wiring space, a 3/4-inch conduit knockout, and built-in short circuit protection to prevent damage to sensitive components during installation. High contrast terminal designations make wiring easy. With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 InnovairFIex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source. An easy-access Test/Reset button makes it possible to test the unit with the cover on. Three DIP switches can be used to configure field selectable settings: cover tamper delay, number of sensors to be controlled, and shut down on trouble option. Each power board has two LEDs that can be used to indicate the status of connected sensors, and a quick reference imprinted on the cover explains the LED status indications (Standby, Maintenance, Trouble, and Alarm). The InnovairElex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new Innn,iir[Iv nrr,rll ct inc ft rr,mrctikIg wit h 7111 nro,in, ic Innr,nir Agency Listings t' ''•'•'' "' V° "" "11 models, including remote test accessories. MSFM WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors; NOT a substitute for early warning detection; S LISTED APPROVED approved NOT a replacement for a building's regular fire detection system. 5911 3029700 3242.653207 2202 Refer to NEPA 72 and 90A for additional information. InnovairFIef Duct Smoke Detector Specifications The air duct smoke detector shall be a System Sensor lnnovairFlex D4120 Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per UL 268A specifically for use in air handling systems. The flexible housing of the duct smoke detector fits multiple footprints from square to rectangular. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 meters/second).The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the SSK45 1 Multi-Signaling Accessory or the RTS45 1 KEY Remotelest Station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Size: (Rectangular Dimensions) (Square Dimensions) 14.38 in (37 cm) Length; 5 in (12.74 cm) Width; 2.5 in (6.36 cm) Depth 7.75 in (19.7 cm) Length; 9 i (22.9 cm) Width; 2.5 in (635 cm) Depth Weight: 2.5 lbs (1.14 kg) Operating Temperature Range: D4120 & D4S: -4° to 158°F (-20° to 70°C); D4P 120: -40° to 158°F (-40° to 70°C) Storage Temperature Range: D4120 & D45:-22* to 158°F (-30° to 70°C); D4P 120: -40° to 158°F (-40° to 70°C) Operating Humidity Range: 0% to 95% relative humidity non-condensing Air Duct Velocity: Electrical Ratings Power supply voltage: 100 to 4000 It/mm (0.5 to 20.32 m/sec) 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz Input capacitance: 270 pF max. 270 pF max. N/A Reset voltage: 3.0 VDC mm. 2.0 VAC mm. 1OVAC mm. Reset time: (with RTS451) .03 to 0.3 sec. .03 to 0.3 sec. .03 to 0.3 sec. Reset time: (by power down) 0.6 sec. max. 0.6 sec max. 0.6 sec. max. Power up time: 35 sec. max. 35 sec. max. 35 sec max. Alarm response time: 15 sec. 15 sec. 15 sec. Sensitivity Test: See detector label See detector label See detector label Current Requirements: (Using No Accessories) Max. standby current: 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz Max. alarm current: 65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz Alarm initiation contacts: (SPST) 2.OA @30 VDC (resistive) Alarm auxiliary contacts: (DPDT) 10A @30 VDC (resistive); 10A @250 VAC (resistive); ½ HP @ 240 VAC ; 1/4 HP @ 120 VAC Note: Alarm auxiliary contacts shall not be connected to initiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory contacts: (SPDT) LCurrentLoads 2.OA @30 VDC (resistive); 2.OA @ 125 VAC (resistive) Device Accessory Z'I VDC Standby Trouble Alarm APA151/APA451 12.5 mA n/a 30 mA Max. MHR/MHW 0 m n/a 29 mA Max. RA100Z OmA n/a' 12mAMax. RTS151/RTS151KEY 0miV12mA n/a 12 mA Max. RTS2JRTS2-AOS 3.0mA max 16 mA Max. with strobe: 55 mA max; without strobe 30 mA max Note: Any combination of accessories may be used such that the given accessory loads are: 110 mA or less at the Aux output, and 50 mA or less at the Alarm output Installing the InnovairFIex Sampling Tube The InnovairFIex sampling tube may be installed from the front or back of the detector.The tube locks securely into place and can be removed by releasing the front or rear locking tab (front locking tab shown below right). b S r AOS0°19'002 Wiring for 4-wire Duct Smoke Detector and Accessories S - - - - — — - I POWER INPUTS (NOTE 1) I I POWER INPUTS(NOTE1) 120 C I I r4 i 4VAC/Dl I I FVA1 9 10 I 9 10 I I OR I I OR I I AUXILIARY CONTACTS I I AUXILIARY CONTACTS I I FOR FAN SHUTDOWN, ETC. (NOTE 2) FOR FAN SHUTDOWN, ETC. (NOTE 2) I I AUXA AUXB I i AUXA N N N N I I I I I I I EOL RESISTOR SPECIFIED BY SUPERVISORY CONTACTS I SUPERVISORY CONTACTS PANEL I (NOTE 3) I I (NOTE 3) I MANUFACTURER - -i SUP 0. UL/FM LISTED 4-WIRE CONTROL PANEL + ALARM 4 ALARM C. ALARM 4 ALARM C. - ALARM INITIATION INITIATION INITIATION CONTACTS CONTACTS \ c 5 LOOP \\ - (NOTE 4) N.C. ALARM N.O. (NOTE 4) ALARM ------------J ------------J FIRST DETECTOR IN THE LOOP LAST DETECTOR IN THE LOOP NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-601-1z. NOTE 3: Supervisory contacts shown in standby position. Open contacts 120VAC Power Inputs accept only 120VAC 50-60Hz. Connect power indicate a trouble condition to the panel. See specifications for source to appropriate terminals of each detector. See specifications contact ratings. for additional power supply information. NOTE 4: Alarm Initiation contacts shown in standby position. Closed NOTE 2: Auxiliary contacts shown in standby position. Contacts switch contacts indicate an alarm condition to the panel. See specifications during alarm as indicated by arrows. Auxiliary contacts are not to for contact ratings. be used for connection to the control panel. See specifications for contact ratings. Please refer to the corresponding installation manual for accessory wiring diagrams. Important Notes on 2:1 Sensor-to-Power Capability 2:1 sensor-to-power capability is not available for all InnovairElex models. The feature is only available on the D4120 4-wire conventional models. 2:1 sensor-to-power capability can be enabled using one D4120 and one D4S, or two D4S and one D4P120. Important Interconnect Notes When using the interconnect feature, all interconnected units must be powered using the same independent supply. Polarity must be maintained throughout the interconnect wiring. Connect the INT+ terminal on unit ito the INT+ terminal on unit 2 and so on. Similarly, connect the INT/AUX— terminal on unit ito the INT/AUX- terminal on unit 2 and so on. Up to 50 D4120 units, 50 D4P1 20 units, or 50 units of combination may be interconnected. Up to 10 DH 100ACDC units may be interconnected. Please note that each of the 9 DH1 OOACDC units interconnected may be replaced by three D4P120 units. Therefore, when using the interconnect feature a single DH 100ACDC can drive either 9 DH 100ACDCs or 27 D4120 units. . NOTE: Alarm can be reset only at the initiating device and not at the devices interconnected. 00544 19002 Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed. E L J RTS151 ULS4O11 RTS151 KEY UL 52522 APA151 ULS4OII RTS2-AOSULS2522 _ It RA100Z UL 52522 MHW UL 54011 MHR UL 54011 AOS Ordering Information Part No. D4120 4-wire photoelectric low-flow duct smoke detector Accessories D4S 4-wire photoelectric sensor component only D4P1 20 4-wire photoelectric power board component only, 24VAC/DC, 120 VAC 2D51 4-wire conventional photoelectric sensor head DST] Metal sampling tube duct width up to ift (0.3m) DST1 .5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 to 0.6 m) DST3 Metal sampling tube duct widths 2 ft t04 ft (0.6 to 12 m) DSTS Metal sampling tube duct widths 4 ft to ft (12 to 2.4 m) DST1 0 Metal sampling tube duct widths 8 ftto 12 ft (2.4 to 3.7 m) APA1 51 Remote annunciator with piezo alarm DH400 OE-1 Weatherproof enclosure [TX Metal exhaust tube duct width 1 ft (0.3m) M02-04-00 Test maonet MHR Mini Horn, Red MHW Mini Horn, White P48-21-00 End cap for metal sampling tubes RA100Z Remote annunciator alarm LED RTS1 51 Remote test station RTS1 51 KEY Remote test station with key lock RTS2 - ACS Multi-signaling accessory Product specificat— subject to change wid-it notice. Visit systernsensorconn for 02010 Sy,1e, Sensor STEM 3825 Ohio Avenue. St. Charles, IL 60174 SENSOR Phone: 800-SENSOR2 Fax: 630-377-6495 CUrrentproducoinfro—don, including the latest version of this data Sheet CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 3242-1653:0207 Page 1 of 1 CATEGORY: 3242 -- DUCT SMOKE DETECTOR, PHOTO. (W/ OR W/O BASE) LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sisson©honeywell.com DESIGN: ModelsD4120 D4240, RD4120, P270-3000PL, 1D41203, TD41204, LD4S, LD412OX, LD4120H, D4S, D4P120, CD4P120 LD4P120X, LD4P120H, TD4C, PD4120, YD4120, YD4P120, and AD4P120 four-wire conventional photoelectric duct smoke detectors and subassemblies. Unit consists of a duct detector housing, powerboard with electrical components and relays, exhaust tubes, and listed 2D51 detector head (CSFM Listing No. 7272-1653:203). Model AD4S sensor component. Models *TD4C LD412OX, LD4120H, LD4P120X and LD4P120H do not contain a 120 VAC transformer. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 20-29 VDC, *24 VAC, 120 VAC (except Models *TD4C LD412OX, LD4120H, LD4P120X and LD4P120H *do not have 120 VAC rating). INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, air velocity and UL label. APPROVAL: Listed as conventional photoelectric duct smoke detector for use with separately listed fire alarm control units. Refer to listee's Installation Instruction Manual for details. *Rev. 03-27-13 gt T1 This This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires ljune 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division S 0 f SYSTEM $ SENSOR IP Duct Smoke Detector Accessories Expand the versatility of the lnnovairFlex line of duct smoke detectors with System Sensor notification and test accessories. Available Accessories APA1 51 Piezo Annunciator MHR Mini-Horn, Red MHW Mini-Horn, White RA1 OOZIRA100ZA Remote Annunciator RTS1 51 Remote Test Station RTS1 51 KEY Remote Test Station with Key RTS2 Multi-Signaling Accessory AOS Add-On Strobe RTS2-AOS Multi-Signaling Accessory Agency Listings & <~> 0 LISTED APPROVED L.! Duct smoke detector accessories add functionality to the duct smoke detection system by allowing quick, convenient inspections at eye level and effective audible and visible notification options. All System Sensor duct smoke detectors and accessories are UL listed. The APA151 piezo annunciator, which replaces the APA45I with a new, improved look, provides an audible alarm signal, a red LED to indicate alarm status, and a green LED to indicate power status. It is intended for use with System Sensor 4-wire conventional duct smoke detector applications without a system control panel, to comply with NFPA 90A. The Mill and MHW SpectrAlert Advance mini-horns feature temporal or continuous tones at high and low volume settings. Their small footprint allows mounting to single-gang back boxes for applications where a small device is desired. The RA100Z and RA100ZA remote annunciators are designed for both conventional and intelligent applications. Their red LED provides visual indication of an alarm condition. The RTS1 51 and RTS1 51 KEY remote test stations are automatic fire detector accessories designed to test duct smoke detectors from a convenient location. For 4-wire detectors, the RTS1 51 KEY test station features a multi-colored LED that alternates between steady green and red. For 2-wire detectors, the LED illuminates red for alarm. The RTS2 and RTS2-AOS multi-signaling accessories are designed to work with InnovairFiex 4-wire conventional duct smoke detectors. These accessories include a key switch that can be used to select one of two connected sensors to be tested, reset, or both by a push button switch. They also enable sensitivity measurements using the SENS-RDR sensitivity reader (sold separately). The AOS (Add-On Strobe) is an optional accessory included with the RTS2-AOS model. Specifications, Duct Smoke Detector Accessories Voltage Regulated 24 VDC Operating Voltage 16 to 33 VDC Maximum Alarm Current 30 mA Temperature Range 0°C to 49°C (32°F to 120°F) Relative Humidity 10 to 93% non-condensing Wire Gauge 12to18AWG Dimensions 4.6"H x 2.9W x.45- D Voltage Regulated 12 DC or FWR (Full Wave Rectified) or Regulated 24 VDC or FWR Operating Voltage 8 to 33 VDC (9 to 33 VDC with Sync-Circuit Module) Sounder Current Draw 22 mA RMS max. at 8 to 17.5 Volts DC 17 mA RMS max. at 8 to 17.5 Volts FWR 29 mA RMS max. at 16 to 33 Volts DC 25 mA RMS max. at 16 to 33 Volts FWR Temperature Range 0°C to 49°C (32°F to 120°F) Humidity Range 10 to 93% non-condensing Nominal Sounder Frequency 3kHz Wire Gauge 12to18AWG Dimensions 4.6H x 2.9Wx0.45T Voltage Range Conventional System: 3.1 to 32 VDC Intelligent System: 18 to 32 VDC Maximum Alarm Current 12 mA Dimensions 4.6Hx2.8Wx1.31J Power Requirements Alarm LED: 2.8 to 32 VDC, 12 mA max. Total Current: 105 mA max. Test Switch 1 OVA @32 VDC Reset Switch 1 OVA @32 VDC Alarm Response Time 40 seconds max. Temperature Range —10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing Wire Gauge 14to18AWG Dimensions 4.8Hx2.90Wx1.4T RTS 1 S 1 KEY Remote Test Power Requirements Station with Key Power LED (Green): 14 to 35 VDC, 12 mA max. Alarm LED (Red): 2.8 to 32 VDC, 12 mA max. Total Current: 105 mA max. Alarm Response Time 40 seconds max. Temperature Range —10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing Wire Gauge 14to18AWG Dimensions RTS2 and RTS2-AOS Multi Voltage 4.6Hx2.75Wx1.8D -signaling Accessory 20 to 29 VDC Power Requirements Standby: 3.0 mA max. Trouble: 16.0 mA max. Alarm without strobe: 30 mA max. Alarm with strobe: 55 mA max. Sounder 85 dBA at ten feet Temperature Range —10°C to 60°C (14°F to 140°F) Relative Humidity 95% non-condensing WireGauge 14to22AWG Dimensions 4.8Wx 5.3"H xl .6 D S For the very latest product specifications and listing information, please visit the System Sensor Web site at www.systemsensor.com. 0 RTS151KEY UL S2522 I SMOKE APA151 UL S4011 RTS2-AOSULS2522 RTS151 ULS4O11 -------------- RA100Z UL S2522 MHWULS4OI1 MHRULS4OI1 AOS SYSTEIbY 3825 Ohio Avenue St. Charles, IL 60174 Product titnsubjecto for EIIJISOI? Phone: 800-SENSOR2. Fax: 630-377-6495 Cootootrofo,iflofod5 the latest oe,OOflOftho data ohOOt CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1653:0212; Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models RTS1 51, RTS1 51 KEY and RA100Z Duct Smoke Detector accessories. Refer to listee's data sheet for detailed product description and operational considerations. RATING: Refer to the installation manuals. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as control unit accessories for use with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. 04-03-09 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division 0 System Sensor L-Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastic cover prevents nicked wires by covering exposed speaker components. These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 7 field-selectable candela settings for both wall and ceiling speaker strobes. The low total harmonic distortion of the SP speaker offers high fidelity sound output while still offering high volume sound output for use in high ambient noise applications. L-Series makes installation easy Attach a universal mounting plate to a 4 x 4 x 21i8 inch back box. Flush-mount applications do not require an extension ring. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate. Attach the speaker or speaker strobe to the mounting plate by inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product pins into the mounting plate terminals. The device will temporarily hold in place with a catch until it is secured with a captured mounting screw. SYSTEM $ SENSOR® Indoor Selectable. Output Speaker Strobes and Dual Voltage Evacuation Speakers for Ceiling Applications System Sensor L-Series selectable-output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. Features Plug-in design and protective cover reduce ground faults Universal mounting plate with an onboard shorting spring tests wiring continuity before installation No extension ring required Field selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 Automatic selection of 12- or 24-volt operation at 15 and 30 candela Rotary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (1/8, ½, 1 and 2 watts) Speakers offer high fidelity and high volume sound output 520 Hz capable with compatible FACP Compatible with System Sensor synchronization protocol Electrical compatibility with existing SpectrAlert and SpectrAlert Advance products Tamper-resistant construction Updated modern aesthetics Agency Listings SIGNAUNG LISTED S4048 FM approved except 7320-1653 0555 Icr ALERT roodols 3057493 L-Series Speaker and Speaker Strobe Specifications 'ArchitecturallEngineering Specifications General F4s box with Extension tor ease ot installation I L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21,8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, [-Series speaker strobes, when used with the Sync.CircuitTM Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync.Circuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, 177. Speaker The speaker shall be a System Sensor L-Series model ______ dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to UL 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to UL1 480 and UL 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shall have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync.Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlerl strobes at 1 Hz. The mocule shall mount to a 411/16 x 411/16 x 21,8-inch back box. The module shall also control two Style V (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Dimensions, Ceiling-Mount Diameter Depth SPC Speaker 6.8 in, 173 mm 1.0 in, 25 mm With Surface Mount Back Box 6.9 in, 176 mm 3.5 in, 89 mm SPSC Speaker Strobe 6.8 in, 173 mm 2.8 in, 73 mm With Surface Mount Back Box 6.9 in, 176 mm 5.37 in, 136 mm Nominal Voltage (speakers) 25 Volts or 70.7 Volts (nominal) Maximum Supervisory Voltage (speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage (strobes) Regulated 12 VDC or regulated 24 VDC/FWR 1.2 Operating Voltage Range (includes fire 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Frequency Range 400 to 4,000 Hz3 Power 1/4, 1/2, 1, 2 watts Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. Strobe products will operate at 12 V nominal only for 15 and 30 cd. 520Hz capable with compatible FACP. L-Series Dimensions S 6.8O dia UL Current Draw Data S tIJU Strobe la Draw ZIT1:I'Fi 8t0 175 Volts Candela DC 16 to 33 Volts DC FWR 15 87 41 60 30 153 63 86 75 NA 111 142 95 NA 134 164 115 NA 158 191 150 NA 189 228 177 NA 226 264 tCeiling-Mount ISpeaker Setting !Sound TtOutput UL Reverberant (dBA @10 if) UL Anechoic (dBA @10 if) 1/4W 79 79 1/2W 82 82 1W 85 85 2W 88 88 Setting Speaker UL Reverberant (dBA @10 if) UL Anechoic (dBA @10 ft) 1/4 W 77 77 1/2W 80 80 1W 83 83 2W 86 86 Ceiling Speaker 68O dia O Ceiling Speaker Strobe Surface Mounti Ceiling Speaker with Surface Mount Back Box Ceiling Speaker Strobe with Surface Mount Back Box S L-Series Ordering Information Ceiling Mount White Red Description SPCWL SPCRL Speaker only SPSCWL SPSCRL Soeaker Strobe SPSCWL-P - Plain, Speaker Strobe SPSCWL-SP - Fueao, Soeaker Strobe SPSCWL-CLR-ALERT - Alert, Speaker Strobe, Clear Lens Accessories White Red Description SBBCWL SBBCRL Universal Ceiling Surface Mount Back Box TRC-2W TRC-2 Universal Ceilinq Trim Rinq T'\ "STEM Ohio Avenue • St. Charles, IL 60174 02017 Syofern Sensor. .5ALcOR Phone: 8C0-SENSOR2 • Fax: 630-377-6495 Prnductspec/vatrons subject to change vethoutrroSceVoosystenrseosor.ccve for current product mInima/on, including the latest version of this data sheet. www.systemsensor.com AVDS86601 • 03/17 • The System Sensor L.Series of speakers and speaker strobes reduce costly ground faults using a plug-in design and universal mounting plate that allow the installer to pre-wire mounting plates, dress the wires, and confirm wiring continuity before plugging in the speakers. In addition, a protective plastc cover prevents nicked wires by covering exposed speaker components. These devices also enable faster installations by providing instant feedback to ensure that wiring is properly connected, rotary switches to select voltage and power settings, and 7 field-selectable candela settings for wall speaker strobes. The low total harmonic distortion of the speaker offers high fidelity sound output while still offering high volume sound output for use in high ambient noise applications. System Sensor L.Series makes installation easy Attach a universal mounting plate to a 4 x 4 x 21,8 inch back box. Flush-mount applications do not requfre an extension ring. Connect the notification appliance circuit or speaker wiring to the terminals on the mounting plate, Attach the speaker or speaker strobe :0 the mounting plate by inserting the product tabs into the mounting plate grooves. Hinge the device into position to lock the product pins into the mounting plate terminals. The device will tempo arily hold in place with a catch until it is secured with a captured mounting screw. r SYSTEM $ SENSOR® Indoor Selectable. Output Speaker Strobes and Dual Voltage Evacuation Speakers for Wall Applications System Sensor L -Series selectable output speaker strobes and dual-voltage evacuation speakers can reduce ground faults and enable faster installation with lower current draw and modern aesthetics. Features Plug-in design and protective cover reduce ground faults Universal mounting plate with an onboard shorting spring tests wiring continuity before installation No extension ring required Field selectable candela settings on wall units: 15, 30, 75, 95. 110, 135, 185 Automatic selection of 12- or 24-volt operation at 15 and 30 candela Rotary switch simplifies field selection of speaker voltage (25 and 70.7 Vrms) and power settings (14, ½, 1 and 2 watts) Seakers offer high fidelity and high volume sound output Compatible with System Sensor synchronization protocol Electrical compatibility with existing SpectrAlert and SpectrAlert Advance products Tamper-resistant construction Updated modern aesthetics Agency Listings GNAIJNG STED . 04048 FM approved except 7320-1653 0555 for ALERT rrrodels 3057493 L-Series Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General I4s box with Extension for ease of installation I L-Series speaker and speaker strobes shall mount to a 4 x 4 x 21,8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, [-Series speaker strobes, when used with the Sync.CircuitTM Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the SynceCircuit Module, 12-volt rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32°F and 120°F from a regulated DC, or full-wave rectified, unfiltered power supply. Wall- mount speaker strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, 185. Speaker The speaker shall be a System Sensor [-Series model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. It should be listed to U[ 1480 and shall be approved for fire protective service. The speaker shall have a frequency range of 400 to 4,000 Hz and shall have an operating temperature between 32°F and 120°F The speaker shall have power taps and voltage that are selected by rotary switches. Speaker Strobe combination The speaker strobe shall be a System Sensor L-Series model listed to U[1480 and U[ 1971 and be approved for fire protective signaling systems. The speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms selected via rotary switch, and shall have a frequency range of 400 to 4,000 Hz. The speaker shal have power taps that are selected by rotary switch. The strobe shall comply with the NFPA 72 requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Synchronization Module The module shall be a System Sensor Sync.Circuit model MD[3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz. The module shall mount to a 411/16 x 411/16 x 21,8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical Specifications Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Dimensions, Wall-Mount Length Width Depth SPL Speaker 6.5 in, 165 mm S in, 127 mm .97 in,23 mm With Surface Mount Back Box 6.6 in, 168 mm 5.1 in, 130 mm 3.2 in, 82 mm SPSL Speaker/Strobe 6.5 in, 165 mm 5.0 in, 127 mm 2.3 in, 58 mm (including lens and speaker) With Surface Mount Back Box 6.6 in, 168 mm 5.1 in, 130 mm 4.5 in, 116 mm Nominal Voltage (speakers) 25 Volts or 70.7 Volts(nominal) Maximum Supervisory Voltage (speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage (strobes) Regulated 12 VDC or regulated 24 DC/FWR1'2 Operating Voltage Range (includes fire 8 to 1 7.5 V (12 V nominal) or 16 to 33V (24 V nominal) alarm panels with built in sync) Operating Voltage with MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33V (24 V nominal) Frequency Range 400 to 4000 Hz Power %1/2 1,2watts Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. Strobe products will operate at 12 V nominal only fcr 15 and 30 cd 0 UL Current Draw Data tJI li Draw 7m7iI;l'F1 S 8 to 17.5 Volts Candela DC 16 to 33 Volts DC FWR 15 88 43 60 30 143 63 83 75 N/A 107 136 95 N/A 121 155 110 N/A 148 179 135 N/A 172 209 185 N/A Sound Output Speaker Strobe 222 257 ¼W ½W 1W 2W UL Reverberant (dBA @10 ft) 77 80 83 86 ULAnechoic (dBA @loft) 77 Sound Output Speaker 80 83 86 ¼W 1W 2W UL Reverberant (dBA @loft) 79 82 85 88 UL Anechoic (dBA @10 ft) 79 82 85 88 L-Series Dimensions 0 6 .97 1.63 63 6 2.30 1.39 1.63 Wall-Mount Speaker Wall-Mount Speaker Strobe 0 Surface Mounti Walt-Mount Speaker Strobe with SBBSPL Surface Mount Back Box L-Series Ordering Information White Red Description SPWL SPRL Speaker only SPSWL SPSRL Speaker Strobe SPSWL-P SPSRL-P Plain Speaker Strobe SPSWL-ALERT - Speaker Strobe, Amber Lens SPSWL-CLR-ALERT - Speaker Strobe Clear Lens - Accessories SPSRL-SP Speaker Strobe, Fuego White Red Description RFPW RFP 7 in x 9.5 in Retrofit Plate SBBSPWL SBBSPRL Surface Mount Back Box for Speakers and Speaker Strotes TR-2W TR-2 Wall Mount Trim Rinct Notes: All -P models have a plain housing (no FIRE" marking on the cover) T"\ }#çJI_IJ 3825 Ohio Avenue • St. Charles, IL 60174 @2017 System Sensor. EALccJR Phone. 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change rothaut notice, Vail systemsensar.com for current product information, including the latest version of this data shoot. www.systemsensor.com AVDS86701 • 03117 0 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7320-1653:0505 Page 1 of 2 CATEGORY: 7320 -- SPEAKERS LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sissonhoneywelI.com DESIGN: System Sensor Indoor Models: SPRL and SPWL Wall Speakers; SPCRL and SPCWL Ceiling Speakers; SPSRL,SPSWL, SPSRL-P, SPSRL-SP, SPSWL-P, SPSWL-ALERT and SPSWL-CLR-ALERT Wall Speaker Stobes; SPSCRL,:SPSCWL1 SPSCWL-P, SPSCWL-SP and SPSCWL-CLR-ALERT Ceiling Speaker Strobes. Wall Bezel Parts: BZSPR-P, BZSPR-AL, BZSPR-EV, BZSPR-AG, BZSPR-PG, BZSPR-F and BZSPR-SP, BZSPW-P, BZSPW-AL; BZSPW-EV, BZSPW-AG, BZSPW-PG, BZSPW-F and BZSPW-SP, Ceiling Bezel Parts: BZSPRC-P, BZSPRC-AL, BZSPRC-EV, BZSPRC-AG, BZSPRC-PG, BZSPRC-F and BZSPRC-SP, S BZSPWC-P, BZSPWC-AL, BZSPWC-EV, BZSPWC-AG, BZSPWC-PG, BZSPWC-F and BZSPWC-SP, WallTrim Rings for Speaker Strobes: TR2 and TR2W CeilingTrim Rings for Speaker Strobes: TRC2 and TRC2W. Wall Surface Mounted Back Boxes: SBBSPRL and SBBSPWL, Ceiling Surface Mounted Back Boxes: SBBCRL and SBBCWL Refer to listee's data sheet for detailed product description and operational considerations. 02-27-17 gt ø' This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct RV operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other 5 Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Listing No. 7320-1653:0505 Page 2 of 2 RATING: 25 or 70.7 VAC, 1/4, 1/2, 1, 2 Watt outputs. Regulated 12 VDC and 24 VDC/FWR is for 2-wire strobe portion. INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as speakers and speaker-strobes when used with separately listed compatible fire alarm control units. Suitable for indoor use, dry and damp environments. *Listed with software code, S05-0048-001 for low temperature compensation. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. 02-27-17 gt ør This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 S Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division f SYSTEM $ SENSOR® Indoor Selectable. Output Horns, Strobes, and Horn Strobes for Wall Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics, Features Updated Modern Aesthetics Small profile devices for Horns and Horn Strobes Plug-in design with minimal intrusion into the back box Tamper-resistant construction Automatic selection of 12- or 24-volt operation at 15 and 30 candela Field-selectable candela settings on wall units: 15, 30, 75, 95, 110, 135, and 185 Horn rated at 88+ dBA at 16 volts Rotary switch for horn tone and two volume selections Mounting plate for all standard and all compact wall units Mounting plate shorting spring checks wiring continuity before device installation Electrically Compatible with legacy SpectrAlert and SpectAlert Advance devices Compatible with MDL3 sync module Listed for wall mounting only The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industy with lower current draws and moderi aesthetics. With white and red plastic housings, standard and com:Jact devices, and plain, FIRE, and FUEGO-printed devices. System Sensor L-Series can meet virtually any application requiremen:. The [-Series line of wall-mount horns, strobes, and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature plug-in designs with minimal intrusion into the back box, making installations fast and foolproof while virtually elimirating costly and time-consuming ground faults. To further simplify installation and protect devices from construc:ion damage, the [-Series utilizes a universal mounting plate for all models with an onboard shorting spring, so installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Agency Listings SIGNAUNG -. LI!E2D 0 401 S FM approxed except for ALERT roodels 7125-16530504 7135-16530503 3057303. 3057072 L-Series Specifications Architect/Engineer Specifications General L-Series standard horns, strobes, and horn strobes shall mount to a standard 2 x 4 x 1 7/8-inch back box, 4 x 4 x 11/2-inch back box, 4-inch octagon back box, or double-gang back box. L-Series compact products shall mount to a single-gang 2 x 4 x 17/a-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products for all standard models and a separate universal mounting plate shall be used for mounting wall compact models. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync.Circuir Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync-Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 110, 135, and 185. Strobe The strobe shall be a System Sensor L-Series Model listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync.Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize SpectrAlert strobes at 1 Hz and horns at temporal three, Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 411/16 x 411/16 x 21/8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1,2 Operating Voltage Range 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG Wall-Mount Dimensions (including lens) 5.6"L x 4.7"W x 1.91 "D (143 mm Lx 119 mm W x 49 mm D) Compact Wall-Mount Dimensions (including lens) 5.26" L x 3.46" W x 1.91" D (133 mm L x 88 mm W x 49 mm D) Horn Dimensions 5.6"L x 4.7"W x 1.25"D (143 mm Lx 119 mm W x 32 mm D) Compact Horn Dimensions 5.25" Lx 3.45" W x 1.25" D (133mm Lx 88mm W x 32mm D) Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs Strobe products will operate at 12 V nominal only for 15 cd and 30 cd. fl UL Current Draw Data . tIIUMax. HornICurrent1IDraw7lTi1:lF 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts Candela DC DC FWR Sound Pattern dB DC DC FWR Candela 15 88 43 60 Temporal High 39 44 54 Range 30 143 63 83 Temporal Low 28 32 54 75 N/A 107 136 Non-Temporal High 43 47 54 95 N/A 121 155 Non-Temporal Low 29 32 54 110 N/A 148 179 3.1 KHz Temporal High 39 41 54 135 N/A 172 209 3.1 KHz Temporal Low 29 32 54 185 N/A 222 257 3.1 KHz Non-Temporal High 42 43 54 3.1 KHz Non-Temporal Low 28 29 54 Coded High 43 47 54 3.1 KHz Coded High 42 43 54 UL Max. Current Draw (rnA RMS), 2-Wire Horn Strobe, Candela Range (15-115 cd) 8-17.5 Volts 16-33 Volts DC Input 15cd 30cd 15cd 30cd 75cd 95cd llOcd 135cd 185cd Temporal High 98 158 54 74 121 142 162 196 245 Temporal Low 93 154 44 65 111 133 157 184 235 Non-Temporal High 106 166 73 94 139 160 182 211 262 Non-Temportal Low 93 156 51 71 119 139 162 190 239 3.lKTemporal High 93 156 53 73 119 140 164 190 242 3.lKTemporal Low 91 154 45 66 112 133 160 185 235 3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261 3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242 16-33 Volts FWR Input 15cd 30cd 75cd 95cd llocd 135cd 185cd Temporal High 83 107 156 177 198 234 287 S Temporal Low 68 91 145 165 185 223 271 Non-Temporal High 111 135 185 207 230 264 316 Non-Temportal Low 79 104 157 175 197 235 283 3.1K Temporal High 81 105 155 177 196 234 284 3.1K Temporal Low 68 90 145 166 186 222 276 3.1K Non-Temporal High 104 131 177 204 230 264 326 3.1K Non-Temporal Low 77 102 156 177 199 234 291 Horn Tones and Sound Output Data Switch Position Sound Pattern dB 8-17.5 Volts DC 16-33 Volts DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 9* Coded High 85 90 90 10* 3.1 KHz Coded High 84 89 89 * Settings 9 and 10 are not available on the 2-wire horn strobes. Horn 5 L-Series Dimensions 1.91 5.27 LIN Compact Strobe Horn Strobe 3.46 .27 H 1.25 00000 a,, 1,1 Compact Horn C L-Series Ordering Information Wall Horn Strobes Horns P2RL 2-Wire, Horn Strobe, Red HRL Horn, Red P2WL 2-Wire, Horn Strobe, White HWL Horn, White P2GRL 2-Wire, Compact Horn Strobe, Red HGRL Compact Horn, Red P2GWL 2-Wire, Compact Horn Strobe, White HGWL Compact Horn, White P2RL-P 2-Wire, Horn Strobe, Red, Plain Accessories P2WL-P 2-Wire, Horn Strobe, White, Plain TR-2 Universal Wall Trim Ring Red P2RL-SP 2-Wire, Horn Strobe, Red, FUEGO TR-2W Universal Wall Trim Ring White P2WL-SP 2-Wire, Horn Strobe, White, FUEGO SBBRL Wall Surface Mount Back Box, Red Wall Strobes SBBWL Wall Surface Mount Back Box, White SRL Strobe, Red SBBGRL Compact Wall Surface Mount Back Box, Red SWL Strobe, White SBBGWL Compact Wall Surface Mount Back Box, White SGRL Compact Strobe, Red SGWL Compact Strobe, White SRL-P Strobe, Red, Plain SWL-P Strobe, White, Plain SRL-SP Strobe, Red, FUEGO SWL-CLR-ALERT Strobe, White, ALERT Notes: All -P models have a plain housing (no "IRE" marking on cover) All -SP models have "FUEGO" marking on cover All -ALERT models have "ALERT" marking on cover 3825 Ohio Avenue • St. Charles, IL 60174 02017 System Sensor, SENSOR Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specification; subject to change odthout notice, visit systemsenssr.ccrn for current product ifornration, including the latest eersiee at this data sheet. www.systemsensor.com AV0S86503 • 03117 S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7125-1653:0504,: Page 1 of 2 CATEGORY: 7125 -- FIRE ALARM DEVICES FOR THE HEARING IMPAIRED. LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sissonhoneyweIl.com DESIGN: System Sensor Indoor 2-wire Models: SRL,SWL, SGRL, SGWL, SRL-P SWL-P, SRL-SP, SWL-CLR-ALERT and SWL-ALERT Wall Strobes; SCRL, SCWL and SCWL-CLR-ALERT Ceiling Strobes. Wall Bezel Parts: BZR-F, BZR-AL, BZR-AG, BZR-EV, BZR-P, BZR-SP, BZR-PG, BZW-F, BZW-AL, BZW-AG, BZW-EV, BZW-P, BZW-SP, BZW-PG, BZGR-F, BZGR-AL, BZGR-AG, BZGR-EV, BZGR-P, BZGR-SP, BZGR-PG, BZGW-F, BZGW-AL, BZGW-AG, BZGW-EV, BZGW-P, BZGW-SP and BZGW-PG, Ceiling Bezel Parts: BZRC-F, BZRC-AL, BZRC-AG, BZRC-EV, BZRC-P, BZRC-SP, BZRC-PG, BZWC-F, BZWC-AL, BZWC-AG, BZWC-EV, BZWC-P, BZWC-SP and BZWC-PG. Color Lens: S LENS-A2, LENS-132, LENS-G2, LENS-R2, LENS-AC2, LENS-BC2, LENS-GC2 and LENS-RC2. WallTrim Rings: TR2 and TR2W CeilingTrim Rings: TRC2 and TRC2W. Wall Surface Mounted Back Boxes: SBBRL, SBBGRL, SBBWL and SBBGWL, Ceiling Surface Mounted Back Boxes: SBBCRL and SBBCWL Refer to listee's data sheet for detailed product description and operational considerations. *Rev 04-04-19 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listees data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Listing No. 7125-1653:0504 Page 2 of 2 RATING: Regulated 12 VDC setting: 8-17.5 VDC Regulated 24 VDC/fwr setting: 16-33 VDC INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating, and UL label. APPROVAL: Listed as two wire strobe units used for synchronous application when used with separately listed compatible fire alarm control units. Suitable for indoor use, vertical wall or horizontal ceiling mounted. *Listed with software code, S05-0048-001 for low temperature compensation. Authority having jurisdiction should be consulted prior to installation. Refer to listee's Installation Instruction Manual for details. S *Rev 04-04-19 gt rt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installaticn criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires 'June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division 9 SYSTEM $ SENSOR Outdoor, Selectable- Output Speaker Strobes and Dual-Voltage Evacuation Speakers I_ •,-:.• S SpectrAlert Advance outdoor, selectable-output speaker strobes and dual-voltage evacuation speakers meet virtually any outdoor application requirement. Features Plug-in design Electrical compatibility with legacy SpectrAlert products Shorting spring on mounting plate tests continuity before installation Rotary switch simplifies field selection of speaker voltage (25 and 707 Vrms) and power settings (1/4,1/2, 1 and 2 watts) Ceiling- and wall-mount application Universal mounting plate for wall- and ceiling-mount units Weatherproof per NEMA 4X, 1P56 Compatible with System Sensor synchronization protocol Automatic selection of 12- or 24-volt operation at 15 and 15/75 candela Field-selectable candela settings on wall and ceiling units A 6— The SpectrAlert Advance series offers the broadest line of outdoor speakers and speaker strobes in the industry. From metal and plastic outdoor back boxes, to white and red plastic housings, to wall and ceiling mounting options, SpectrAlert Advance can meet virtually any application requirement. SpectrAlert Advance outdoor speakers and speaker strobes can be used indoors or outdoors in wet or dry applications, and can provide reliable operation from —40°F to 151'F. In addition, these speakers provide a broad frequency response range, low harmonic distortion and maintain a high sound pressure level at all tap settings to provide accurate and intelligible broadcast of evacuation messages. The entire SpectrAlert Advance line, including speakers, provides a plug-in design that reduces ground faults by enabling installers to pre-wire mounting plates and dress the wires before plugging in the speakers. To enable faster installation times, a shorting spring on the mounting plate provides instant feedback to ensure that wiring is properly connected. Furthermore, rotary switches simplify the selection of voltage and power settings. Both wall and ceiling speaker strobes include field-selectable candela settings that enable installers to quickly set each device to meet application requirements. S The s pea kers'weatherproof plastic back boxes (shipped with product) and metal back boxes (available separately) are designed to accommodate in-and-out wiring for daisy chaining outdoor devices. Plastic back boxes feature removable side flanges and improved Agency Listings resistance to saltwater corrosion. The screw-hole knock-outs located on the back of the back box eliminate the need to drill holes for SIGNAUNG ___ screw-in mounting. Both weatherproof back boxes come with (" MEA 1/4-inch top and bottom conduit entries and 1/4-inch knock-outs at LISTED approved the back. Included with each back box is a screw-in NPT plug with an 75SO 7320-1653:201 0.08-6 0-ring gasket for a water tight seal. SpectrAlert Advance Outdoor Speaker and Speaker Strobe Specifications Architectural/Engineering Specifications General SpectrAlert Advance outdoor speakers and speaker strobes shall mount to a weatherproof back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit and amplifier wiring shall terminate at the universal mounting plate. Also, SpectrAlert Advance speaker strobes, when used with the Sync-Circuit" Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 0124 volts. When used with the Sync-Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 9 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Outdoor SpectrAlert Advance products shall operate between —40°F and 151°F from a regulated DC, or full-wave rectified, unfiltered power supply. Speaker Speaker shall be a System Sensor SpectrAlert Advance Model dual-voltage transformer speaker capable of operating at 25.0 or 70.7 nominal Vrms. Speaker shall be listed to Underwriters Laboratories Standard S4048 for outdoor fire protective signaling systems. Speaker shall have a frequency range of 400 to 4000 Hz and shall have an operating temperature from —40°F to 150.8°F. Speaker shall have power taps and wattage settings that are selected by rotary switches. The speaker must be installed with its weatherproof back box in order to remain outdoor approved per UL listing S4048. The speaker shall be suitable for use in air handling spaces and wet environments. Speaker Strobe Combination The speaker strobe shall be a System Sensor Model listed to UL 1638 and UL 1480 and be approved for fire protective signaling systems. Speaker shall be capable of operating at 25.0 or 70.7 nominal Vrms and shall have a frequency range of 400 to 4000 Hz. Speaker shall have power taps that are selected by rotary switch. The strobe shall consist of a xenon flash tube with associated lens/reflector system and operate on either 12 or 24 volts. The strobe shall also feature selectable candela output, providing options for 15 or 15/75 candela when operating on 12 volts and 15,15/75, 30, 75, 110, 115, 135, 150,177 or 185 candela when operating on 24 volts. The strobe shall comply with the Americans with Disabilities Act requirement for visible signaling appliances, flashing at 1 Hz over the strobe's entire operating voltage range. The speaker strobe must be installed with its weatherproof back box in order to remain outdoor approved per UL. The speaker strobe shall be suitable for use in wet environments. Operating Temperature —40°F to 151°F (-40°C to 66°C) Dimensions, Wall-Mount SPS Speaker Strobe 6.0" Lx 5.0W x 4.7"D (including lens and speaker) SP Speaker 6.0" Lx 5.0W x 29" D Dimensions, Ceiling-Mount SPS Speaker Strobe 68" Dia. x 4.7"D (including lens and speaker) SP Speaker 68" Dia. x 2.9"D Dimensions, Wall-Mount Weatherproof Back Box 65' Lx 5.5'H x 2.9" D Dimensions, Ceiling-Mount Weatherproof Back Box 7.2" Dia. x 2.9"D Electrical/Operating Specifications Nominal Voltage (speakers) 25 V or 70.7 V (nominal) Maximum Supervisory Voltage (speakers) 50 VDC Strobe Flash Rate 1 flash per second Nominal Voltage (strobes) Regulated 12 VDC/FWR or regulated 24 DC/FWR Operating Voltage Range (includes fire alarm panels 8 to 17.5 V (12 V nominal) or 16 to 33 V (24V nominal) with built in sync) Operating Voltage with MDL Sync Module 9 to 17.5 V (12 V nominal) or 17 to 33 V (24V nominal) Frequency Range 400 to 4000 Hz Power /4,½,1,2watts A05'0425.005 S 7.1 E N Ceiling-Mount Outdoor Speaker Strobe 6 Wall-Mount Outdoor Speaker Strobe UL Current Draw Data Candela Derating S For K series products used at low temperatures, 8 to 17.5 Volts 16 to 33 Volts listed candela ratings must be reduced in rr accordance with this table. Strobe Output (cd) Listed Candela Candela rating at -40F 15 Do not use below 32SF 15/75 30 75 44 95 70 110 110 115 115 135 135 150 150 177 177 185 185 Standard 15 123 128 66 71 Candela Range 15/75 142 148 77 81 30 NA NA 94 96 75 NA NA 158 153 95 NA NA 181 176 110 NA NA 202 195 115 NA NA 210 205 High 135 NA NA 228 207 Candela Range 150 NA NA 246 220 177 NA NA 281 251 Sound Output 185 NA NA 286 258 UL Reverberant (dBA@lOft.) 2W 1W 1/2W ¼W Outdoor Speaker 90 87 84 81 Outdoor Speaker/Strobe 89 86 83 80 S Dimensions 7.19 .97t-2.83 --1 L Ceiling-Mount Outdoor Speaker _ F283h Wall-Mount Outdoor Speaker A05-0425-005 [] Surface Mounting as Ceiling-Mount Speaker Strobe with Plastic Weatherproof Back Box Ceiling-Mount Speaker with Plastic Weatherproof Back Box Wall-Mount Speaker Strobe with Plastic Weatherproof Back Box Wall-Mount Speaker with Plastic Weatherproof Back Box Ceiling-Mount Speaker with Metal Weatherproof Back Box Wall-Mount Speaker Strobe with Metal Weatherproof Back Box Wall-Mount Speaker with Metal Weatherproof Back Box Ordering Information for SpectrAIert Advance Outdoor Speakers and Speaker Strobes White Red Description SPWK SPRK Outdoor Speaker (includes plastic weatherproof back box) SPSWK SPSRK 1 'Outdoor Speaker Strobe, Selectable Candela (15, 15/75,30,75,95, 110, 115) (includes plastic weatherproof back box) - SPSRHK Outdoor Speaker Strobe, Selectable Candela (135,150,177,185) (Includes plastic weatherproof back box) Ceiling Mount White Red Description SPCWK - Outdoor Speaker (includes plastic outdoor back box) SPSCWK - Outdoor Speaker Strobe, Selectable Candela (15,15/75, 30, 75, 95, 110, 115) (includes plastic weatherproof back box) SPSCWHK - Accessories Outdoor Speaker Strobe, Selectable Candela, High cd(i 35, .150, 177, 185) (includes plastic weatherproof back box) White Red Description MWBBW MWBB Wall, Metal Weatherproof Back Box MWBBCW - Ceiling, Metal Weatherproof Back Box Notes: Add "-R' to model number for weatherproof replacement device (no back box included), e.g., SPWK-R. Especially for use with weatherproof outdoor flush mounting pates, WTP-SP and \iVTP-SPW Add "-P"to model number for plain housing (no "FIRE' marking on cover), e.g., SPSWK-P. "\ SYSTEM 3825 SENSOR Phone: System Sensor. Ohio Avenue St. Charles, IL 60174 Producti5tion 800-SENSOR2. Fax: 630-377-6495 current product information, including the West vesionof ""~"'h"L CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM t6- yJ LISTING SERVICE LISTING No. 7320-1653:0201 Page 1 of I CATEGORY: 7320 -- SPEAKERS LISTEE: System Sensor, Unincorporated Div of Honeywell Intl lnc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sisson@honeywell.com DESIGN: Models SPR,SPW,SPRV, and SPWV SpectrAlert Speakers - Rectangular enclosure. Models SPCW, SPCR, SPCWV, and SPCRV SpectrAlert Speakers with round enclosure. Models SPSR, SPSRH, SPSW, SPSW-ALERT, SPSW-CLR-ALERT, *SPSWKCLRALERT SPSWH, SPSRV, and SPSWV SpectrAlert Speaker/Strobe with rectangular enclosure. Models SPSCR, SPSCRH, SPSCW, *SPSCWKCLRALERT SPSCWH, SPSCRV, SPSCRVH, SPSCWV, and SPSCWVH SpectrAlert Speaker/Strobe with round enclosure. Model SPSCW-CLR-ALERT Speaker/Strobe. Model SPSW-ALERT has amber lens and is intended for non-fire use. All models identified are intended for indoor use mounted on the wall or ceiling. Models with aK" in the suffix are suitable for indoor or outdoor use with an operating temperature rating of -40°C to +66°C (-40°F to +151°F) and have a NEMA 4X enclosure rating when used with models PWBB, PWBBW (wall) or the model PWBBCW (ceiling) plastic weatherproof back boxes or with Model MWBBW (Wall), MWBB (Wall) or MWBBCW (Ceiling) metal weatherproof back boxes. Models with a "- P' in the suffix have plain housings with no lettering on the enclosure. Models not containing '- P", in the suffix have English lettering reading 'FIRE" on the housing. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: Nominal Voltage: 25 Vrms or 70 Vrms Power Settings: 1/4,1/2, 1, 2 Watts Frequency Range: 400 - 4000 Hz INSTALLATION: In accordance with listee's printed installation instructions, NFPA 72, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as speaker/strobes when used with separately listed compatible fire alarm control units. Suitable for wall or ceiling mount. These speaker/strobes do not generate a distinctive three-pulse temporal code pattern (for total evacuation) as required per NFPA 72, 2010 edition. If required, the appliances must be used with a fire alarm control unit that can generate the temporal pattern signal. *Corrected 02-06-12 bh This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other is Date Issued: July 01, 2019 Listing Expires June 30, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division 0 'I SYSTEM RECORD OF COMPLETION This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. Insert N/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record Form Completion Date: 2/24/20 Supplemental Pages Attached: PROPERTY INFORMATION Name of property: Legolatid Drop Ride Address: 1 Legoland Dr Description of property: 2020 Rides Name of property representative: Address: Phone: Fax: E-mail: INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION Installation contractor: West Coast Fire Address: 3199-D Airport Loop Rd, Costa Mesa Ca. Phone: 714-674-0355 Fax: 714-957-5749 E-mail: Service organization: Address: Phone: Fax: E-mail: Testing organization: Address: Phone: Fax: E-mail: Effective date for test and inspection contract: Monitoring organization: Pyrocomm Address: Phone: Fax: E-mail: Account number: Phone line 1: Phone line 2: Means of transmission: Dialer Entity to which alarms are retransmitted: Pyrocomm monitoring Phone: DOCUMENTATION On-site location of the required record documents and site-specific software: At Fire Panel DESCRIPTION OF SYSTEM OR SERVICE This is a: 0 New system 0 Modification to existing system Permit number: NFPA 72 edition: 2017 4.1 Control Unit Manufacturer: Notifire 4.2 Software and Firmware Firmware revision number: V26 4.3 Alarm Verification Number of devices subject to alarm verification: Model number: NFS 320 This system does not incorporate alarm verification. Alarm verification set for seconds Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. 1of 3) SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: 120 VAC Overcurrent protection: Type: circuit breaker Branch circuit disconnecting means location Hydraulic Rm 5.1.2 Secondary Power Type of secondary power: 12v 18 AH Batteries Location, if remote from the plant: Calculated capacity of secondary power to drive the system: In standby mode (hours): 24 hr Control panel amps: 13 amps Amps: 20 amps Number: In alarm mode (minutes): 5 5.2 Control Unit o This system does not have power extender panels Z Power extender panels are listed on supplementary sheet A R CIRCUITS AND PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line B 0 Device Power B 0 Initiating Device B 0 Notification Appliance B 0 Other (specify): 7. REMOTE ANNUNCIATORS Location None R lIJITIATIlJ( flFVlCF Type Quantity Addressable or Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 2 Addressable Alarm Manual Smoke Detectors 1 Addressable Alarm photo Duct Smoke Detectors 0 Conventional supervisory photo Heat Detectors Gas Detectors Watertlow Switches 0 Conventional alarm Tamper Switches 0 Conventional supervisory Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. 2of3) SYSTEM RECORD OF COMPLETION (continued) 9. NOTIFICATION APPLIANCES Type Quantity Description Audible 0 speakers Visible 0 strobe Combination Audible and Visible 4 speaker/strobe SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices HVAC Shutdown Fire/Smoke Dampers Door Unlocking Elevator Recall Elevator Shunt Trip INTERCONNECTED SYSTEMS E] This system does not have interconnected systems. C] Interconnected systems are listed on supplementary sheet CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system as specified herein has been installed according to all NFPA standards cited herein. Signed: Printed name: Jay Bobbitt Organization: West Coast Fire Title: Foreman Date: 7/30/19 Phone: 619-674-0355 12.2 System Operational Test This system as specified herein has tested according to all NFPA standards cited herein. Signed: Printed name: Jay Bobbitt Date: 7/30/19 Organization: West Coast Fire Title: Foreman Phone: l O7AJV. 12.3 Acceptance Test Date and time of acceptance test: Installing contractor representative: Testing contractor representative: Property representative: AHJ representative: Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. (p. 3o13)