Loading...
HomeMy WebLinkAbout3200 LIONSHEAD AVE; ; FA150064; Permit11/17/21 11:32 AM FAI 50064 Permit Data City of Carlsbad Fire Alarm Permit Job Address: 3200 LIONSHEAD AV Permit Type: FALARM Parcel No: 2218811100 Lot #: 0 Permit No: FA150064 Status ISSUED Applied 9/29/2015 Approved: 9/30/2015 Reference No.: Issued: 9/30/2015 PC #: Inspector: Project Title: BURKE CARLSBAD BUSINESS CTR 78,530 SF_INSTALL NEW FIRE SPRINKLER MONITORING SYSTEM TO CONSIST OF I FACP, I REMOTE ANNUNCIATOR, I SMOKE DETECTOR, I MANUAL PULL STATION, 2 WATERFLOW DETECTORS, 4 VALVE TAMPER DETECTORS & DUCT DETECTORS Applicant: SCN SECURITY COMMUNICATION NETWORK DBA LAKEWOOD 470 E. HARRISON ST CORONA, CA 92879 951-599-8205 Owner: NINOS I BURKE LANE L L C C/O BURKE REAL ESTATE GROUP 260 BAKER ST E #100 COSTA MESA CA Fees ($) Add'I Fees ($) Total ($) Balance ($) 290 0 290 0 1/1 *ORIGINAL * FIRE ALARM SUBMITTAL PACKAGE BURKE CARLSBAD BUSINESS CENTER 3200 LIONSHEAD AVENUE CARLSBAD, CA INSTALL NEW FIRE SPRINKLER MONITORING SYSTEM SPECIFICA TION DA TA SHEETS & CSFM LISTINGS PRESENTED S CARLSBAD A FIVE )'Atkk PRESENTED BY SCN, SECURITY COMMUNICATION NETWORK, INC. PROJECT ENGINEER JEANNE WIGGINS, SET 951-545-1562 FA150064 FILE COPY a Proven reliability suitable for commercial and industrial installations On-Board 10/100 Network Communication Full range of zone expansion, communication, and relay output capability Flash Updateable: No more firmware chips to replace Adaptive TechnologyTM - Cost-effective supervised cellular backup DMP XR150FC/XR550FC Series panels deliver true flexibility and expandability to cover all your fire needs. K X15OC/X55OFC SERIES COM !L FIRE PPi\ S SYSTEM FEATURES Up to 562 two-wire smoke detector or fire initiating zones on • Multiple on-board status LEDs XR55OFC Up to 100 output schedules to control relays and panel outputs Up to 142 two-wire smoke detector or fire initiating zones on • 32 individual reporting areas, with common areas Output Groups: Maximum functionality—Minimum programming Up to .5 Amps 12 VDC smoke and auxiliary output with OVC protection - Up to .7 Amps 12 VDC supervised bell output • All above listed System Features Up to 506 fully-programmable Form c relays • On-board Ethernet connection for Network MonitoringTM Serial 3 Digital Dialer or CID reporting to multiple receivers • Customizable check-in time and retry time Eight communication paths between the panel and Central Station e Suitable for multi-site applications where the Internet or Built-in remote or on-site feature upgrade capability LAN/WAN is available 12.000 event buffer Multi-lingual menus available by user , - The XR1 5ODFC and XR55ODFC provide basic fire monitoring for any single site application. The XR1 5ODNFC and XR5500NFC panels provide all the same basic fire monitoring as the XR1500FC and XR55ODFC enhanced by the on-board Ethernet connection that allows the use of Network MonitoringTM. Both panels come fully assembled from the factory with the following components: The XR1 50FC and XR550FC Series addressable fire panels provides complete system control for local NAC operation and DAd, NET, or Cell communication to the central station. The microprocessor based panel also provides input for Class A zone expansion, conventional and addressable smoke detectors, pull stations, and heat detectors. The enclosure is comprised of cold rolled steel in Red to distinguish it for fire operation. For added security, the enclosure comes with a lock and key. The Fire Command Center mounted in the door offers a 32-character full text LCD readout that displays system events and menu prompts, making it efficient and easy-to-use. The 16 VAC, 56 VA wire-in transformer is factory installed and features a built-in PTC for power circuit protection. 12 or 24 VDC NAC 1 NAC1 Syncli d 12or24VDC - s e r Mini-Horn 12or24VDC L__ NAC2 12or24VDC I - .- - NAC2 Power Supply Sync Module Hum r b 505-12 or other 12/24VDC UL Motor Bell Commercial Fire Approved Digital Digital SLC Power Supplies Annunciator Bus Loop Digital SLC Additional 630F Any expansion device Loop 1 Fire Command can operate on SLC Loop +__•__ Centers 1 or2 630F Fire Command Center The XR1500NFC and XR550DNFC has transitioned from dialer-focused communications to a true network and cellular communications approach by providing stronger. multi-layered panel communications that ensure a constant link between the panel and Central Station. Installers have the ability to create, configure and manage up to eight communication paths. The unique DMP Serial 3 format supports 16 or 32-character user, zone and area names to decrease the centralstation response time and limit dependence on automation literal tables for message conversion. Built-in 10/100 auto-sensing Ethernet connection enhances both standard and encrypted line security options. Both UDP and TCP are supported. The network option can be used as the primary or backup path to the digital dialer or cellular option. The XR150FC and XR550FC Series Panels may be used with the 263C or 263H Digital Cellular Communicator as the primary path (no backup required) for commercial fire installations. The check-in and fail time settings are programmed for five minutes. As the backup path, the 263C or 263H provides the security of a communication link that continues to function, even when land lines are cut or compromised. The communicators can be used as a stand-alone communicator without the need for a backup. This interface works on digital Cellular data networks over a variety of carriers in the USA and Canada. EIGHT COMMUNICATION PTH Create, configure, and manage up to eight communication paths between the panel and Central Station. Each path has its own panel communication programming parameters, and can be identified as either primary or backup. This enables installers to configure a reliable communication link, offering greater confidence that the panel will always be connected to the Central Station. COMMUNICATION FUNCTION DIAGNOSTICS The enhanced diagnostic menu enables technicians to check network and cellular communication status, cell signal strength, and email status from the keypad. RCUIT OUTPUTS EXPA 0. 1 The XRI50FC and XR550FC allow the use Easily add NAC outputs to the XR150FC/ of two SPOT relay outputs and four open XR550FC system. Up to three Class B modules collector outputs, that may be activated by can be mounted within the FACP. Model 865 or zone or system events, by schedule, through 866 Class B NAC Modules may be combined the User Menu or when a card is presented. with a power supply to provide additional 4 Output Groups allow multiple outputs to Amp NAC outputs. Use an 867 on the SLC activate with a single event and/or can be Loop to further expand NAC circuits. assigned to a particular user profile. OUTPUT SCHEDULES Achieve maximum system flexibility with 100 programmable schedules that simplify planning and operations. Control any contact-activated device with schedules that automatically regulate relays and switched- ground outputs. V\Lh Tr T Users can test fire notification bells using the Fire Drill feature. A special code is also available for installers to test the system. The one-man walk test feature allows a single technician to check the panel response to fire, burglary panic and supervisory zones. FIRE ?ONE PROC R Program zones for fire, fire verify, fire retard, BIJILTtN P4ROGR "AMER For additional flexibility, keypads attached to presignal, cross zoning, or fire supervisory. AND DI? T the XR1 50FC and XR550FC panels can display This flexibility allows the ability to match No programming device is required, enabling keypad Status List and User Menu text using multiple languages. The user has the option individual zone characteristics to the needs installers and service technicians to fully to select the language to use. of any area in the fire installation, program the system and run diagnostics from any OMP LCD keypad. Check the electrical STATUS LIST ZONE EXPANSION state of zones, find individual zone numbers, To provide maximum system flexibility, fire The XR1 50FC and XR550FC provide up to 570 check the LX-Bus for Missing. Overlapping zones may be programmed to display at a zones, programmable for a variety of fire and/or Extra zones, and much more, all from specific keypad. In this manner, all fire zones applications. The system provides Class B any DMP LCD keypad. can be monitored in one location and other 12 VDC powered zones, two on-board and zones can be programmed to display and be four on the 715 Module, plus eight panel FLASH UPL Ai monitored at different keypad locations. burglary zones. Up to 60 zones are available The XR1 5OFC and XR550FC panels accept on 15 keypad addresses and up to 100 zones software updates from a remote location 12,000 EVENT MEMORY are available on each built-in LX_BusTM using using Remote LinkTM software. When new Allows the user to view the last 10,000 Expansion Modules. XR150FCIXR550FC feature updates release, door accesses or 2.000 system events that perform the flash update remotely. occurred over the past 45 days. FIRE VERIFY Used prima rily for smoke detector circuits to REMOTE LINK verify the existence of an actual fire condition. The Remote Link programming software When a Fire Verify zone initiates an alarm, takes advantage of the easy-to-use simplicity the panel performs a Sensor Reset. If any of Microsoft® WindowsTM. The XR150FC and Fire Verify zone initiates an alarm within 120 XR550FC include an interface connection for seconds afterthe reset, an alarm is indicated, installers to use to connect a laptop computer. If an alarm is initiated after another 120 seconds, the cycle is repeated. - IPF.IES ; 505-12/LX 5 Amps © 12 VDC 630F LCD Remote Fire Command 505-12L 5 Amps © 12 VDC 505-12A 5 Amps ©12VDC NSION MODULES 710 Bus Splitter/Repeater 711 Single Zone Expansion 714 4-zone Class-B Expansion 714-8 8-zone Class-B Expansion 714-16 16-zone Class-13 Expansion 715 4-zone 2-wire smoke Expansion 715-8 8-zone 2-wire smoke Expansion 715-16 16-zone 2-wire smoke Expansion 716 Output Expansion, 4 Form C relays. 4 open collector outputs 717 Graphic Annunciator: 20 open collector outputs CELLULAR 263C COMA Cellular Communicator 263H HSPA+ Cellular Communicator 263HCAN HSPA+ Cellular Communicator (All require a 381 cable) t ("- 860 Relay Output Module 865 Style Wi( Notification Circuit Module 866 Style W Notification Circuit Module 867 LX-Bus Notification Circuit Module 869 Style D Class A Initiating Circuit Module 893A Dual Phone Line Module PULL ST IONS 850 Series Pull Stations SMOKE/HEAT DETECTORS 521 B/BXT Conventional Smoke, CleanMe 521 LX/LXT Addressable Smoke/Heat, CleanMe ACCESSORIES 270 Network Transient Suppressor 277 Commercial Fire Buzzer Module 300 Four-wire Harness 303 Silence/Reset Push-Button 305 Plug-in Output Relay 306 Tamper Harness 307-S Screw-On Tamper Switch 3012 Clip-On Tamper Switch 335 Intrusion Siren 370 Lightning Suppressor 374 Surge Voltage Suppressor 381-2 18 Coax Extension 431 Output Harness 861 Power Distribution Module SCS-1R Network Enabled Receiver Compatable with Central Station Receivers that accept Standard dO. DO, or DMP Serial 3 messaging SCS-VR (Virtual Receiver) Software only solution that runs on a server for network IP and cellular communications 35 1100X Receiver 1100XH High Power Receiver 1100R Repeater 1103 Universal Transmitter, External Contact 1165 Commercial Smoke Detector 1165H Commercial Smoke/Heat Detector 1165H5 Commercial Smoke/Heat Detector with Sounder 1181 Post Indicator Valve (UL) 1182 Outside Screw and Yoke Valve Supervisory Switch (UL) 1183-135F Heat Detector 1183-135R Heat Detector 1184 Carbon Monoxide Detector S. RE Remote Link Upload/Download Programming Software System Link End-User Management Software Alarm Monitoring Module Command Center Module Advanced Reporting Module Account Groups Module Link Server Application SYSTEM SPECIFICATIONS . L 1 3$ AND APPROVALS Primary Power (included) 16 VAC 56 VA transformer Refer to the XR1 5OFC/XR55OFC Installation Guide (LT-1297), XR1 5OFC/ Secondary Power 12 VDC Battery XR550FC Programming Guide (LT-1232) and specific compliance listings Models 365, 366. 368 or 369 for installation and programming requirements necessary to meet a Output Rating particular approval. Bell Up to.7 Amps at 12 VDC FCC Part 68 Smoke and Auxiliary Up to .5 Amps at 12 VDC FCC Part 15 For UL installations, total bell, smoke, and auxiliary cannot Underwriters Laboratories (UL) Listed exceed 1.2 Amps using a 56 VA transformer. ANSI/UL 864 Fire Protective Signaling Current Draw 488m* 5ee AVACKCb Enclosure: lA-S.1/1 LL C.AC C.. 5'eT For approval information, access www.dmp.com and select Compliance. Material Cold-rolled steel (Red) OOER(NC INFORMATION XR1500FC-R XR150 Fire Control Panel XR1 5ODNFC-R XR1 50 Fire Control Panel with Network XR550DFC-R XR550 Fire Control Panel XR5500NF0-R XR550 Fire Control Panel with -_ Network., low . . . (c 2500 North Partnership Boulevard Springfield, Missouri 65803-8877 800641.4282 I dmp.com Designed. Engineered & Assembled in Springfield. Missouri DMP Fire Command Keypads provide a variety of fire annunciation solutions for residential and commercial fire applications. The 630F provides 32-characterfull text LCD display of system events and menu prompts for efficient, easy use. The keypad offers simple, one-button access to common features. including: Silence alarms Reset sensors Test the system Perform a fire drill FEATURES Simple harness connection to 4-wire keypad bus At-a-glance system status Powered from panel or auxiliary power supply Optional backboxes for conduit or wall mount applications Attractive non-obtrusive designs 2-button Panic keys 32-character LCD display Flush or Surface mount Keyswitch enables single button operation Full operation with authorized code Built-in diagnostics AC Power, Trouble, Alarm LED Compatible with XR100/XR500 Series System events display in plain English 63U iFICA LO Operating Voltage 8.5 to 15 VOC Current Draw 63mA standby 92mA maximum Trim Frame Dimensions 10.4" W x 7.0" H x 1.7" D Backbox Dimensions 8.75" W x 6.375" H x 2.5" D Panel Compatibility XR1 00 and XR500 Series Panels 63G R' ':Af!NClATOfl The 630F Fire Command Center offers a 32-character full text LCD readout that displays system events and menu prompts, making it efficient and easy-to-use. The backbox and trim frame provide an attractive installation. The keypad can either be flush-mounted or surface-mounted. 630F Keypad SIGLEDUTTON OERATON The 630F Fire Command Center has a factory installed keyswitch that enables the four function buttons—Alarm Silence, System Reset, System Test, and Fire Drill. The user can also access these four functions and many more through the User Menu by entering a valid user code. T iAGOTLC.S An internal diagnostics program lets installers and service technicians test the operation of the keypad at any time without disabling the system. AND UL. .J. The 630F keypad can be programmed for supervised or unsupervised operation on the keypad data bus, increasing the overall number of keypads you can install to provide maximum flexibility. When supervised, the keypad occupies its own address. Unsupervised operation allows you to install multiple keypads on the bus with the same address. STAThS LEDS The Green Power LED turns on when primary AC or DC powerto the panel is at an acceptable level and flashes when its battery is low or missing. A Yellow Trouble LED turns on when either the panel has failed to communicate with the central station receiver or when phone line 1 or 2 is in a bad condition. .AD ACCESSORIES 635 1.75" 630F Alternate Surface Mount Backbox 635F 2.5" 630F Flush Mount Replacement Backbox 300 4-wire Replacement Harness LSTLGSA' California State Fire Marshal (CSFM) New York City (FDNY COA #6055) FCC Part 15 Underwriters Laboratories (UL) Listed ANSI/UL 864 Control Units for Fire Protective Signaling ANSI/UL 985 Household Fire Warning For additional information, access www.dmp.com and select Compliance. UP isted CDMA & HSPA+ Cr C:;.:r;iunicaton for Fr Alarm . ontrol Panels The 263C/263H, when installed with a DMP XR1 50IXR1 50FC or XR550/XR550FC Panel, is UL approved as a primary (standalone) fire communicator with no backup, and is approved as a fire slave communicator. compatible with any FACP. The 263C/263H provides a dependable communications link between your alarm system panel and Central Station. Compared to a dialup communication link, cellular can save significantly in annual telecommunication costs UL Listed as the Primary Communicator and Fire Slave Input for the XR1 50/XR550 in Fire Applications under ANSI/UL 864 Commercial Fire (Meets NFPA 72) Works on digital cellular data networks over a variety of carriers XR550FC with 263C Cellular Communicator DiGIAL TA Fi C . TORS FEATURES 263C/263H enhances system security that conforms with • 263C/263H uses power from panel with low current draw NFPA and UL requirements for long standby battery life Direct reporting to the DMP Central Station receiver, with • Can be equipped with local or remote antenna, offering no relaying of alarm signals more flexibility when installing Fire Slave Input option of the XR1 50/XR550 with • Ability to check signal strength indication at the keypad 263C/263H approved for any FACP • Messaging features transmit alarms/alerts to users via Modular solution means easily updated for newer SMS text messages, and allow users to remotely control technologies their panel via text commands Eight-path redundancy with multiple message delivery available DMP Adaptive TechnologylM switches communication paths while maintaining supervision if the current path - becomes unavailable V / / . .. DIRECT REPORTING The digital cellular communicators transmit IP data packets directly from the panel's processor over the wireless data network. ALL of the messages that are capable of being sent by the control panel are received directly by the DMP Central Station receiver. There are no intermediary servers or network operation centers, and no retransmission or reinterpretation of the information. Direct reporting means faster response, with no concerns about signals not being properly relayed or intermediate communication links failing. AD .. 3 XRbu/XU ,PANE The 263C/263H works as an easy-to- install XR150/XR550 expansion card, with plug-and-play ease of installation. No extra programming is required. It provides full data delivery of DMP Zones. Areas, and Users, with all names and details included. The remarkably compact 263C/263H won't take up a lot of space in your communications closet. The unit directly installs in the panel expansion card slot, which is mounted inside a sturdy UL- listed metal cabinet. Tamper protection is also available for added security. UI. LISTED Install the DMP 263C/263H Digital Cellular Communicator in an XR150/ XR550 Series panel to create a UL listed, primary communication path for commercial fire installations. The Fire Slave Input option of the XR550 has also been approved under ANSI! UL 864 (NFPA 722007 & 2010), allowing it to be used as a Slave Communicator for any FACP. Ji tYSUPEP 'I '.0 You're kept fully informed of system status. The unit sends full reporting messages including Zones. Areas. and Users, with all names and details included. Full supervision ensures that the cellular communication path is intact and functional. CHT PCfl1 RE , Mn' IV Feel more secure with up to eight paths of communication redundancy. Select from ICR UDP, CDMA, HSPA+, Single Line Dialer, Dual Line Dialer with multiple IP numbers, and multiple telephone numbers. You identify and configure your redundant communication links via Remote Link. A DACT (digital alarm communicator transmitter) system may be configured as: Path 1 Type DD Primary and Path 2 Type DO Backup Path 1 Type OD Primary and Path 2 Type CELL Backup Path 1 Type OD Primary and Path 2 Type NET Backup A NET or CELL system may be configured as: Path 1 Type NET Primary with no Backup Path 1 Type CELL Primary with no Backup Path 1 Type NET Primary and Path 2 Type DO Backup Path 1 Type NET Primary and Path 2 Type CELL Backup Path 1 Type CELL Primary and Path 2 Type NET Backup ADAPTIVE TECHNOLOGYT If the primary communication path is compromised or becomes unavailable, Adaptive Technology almost instantly switches to a designated backup path. Where multiple backups are available, communications can be programmed to switch to another path as necessary. The checkin frequency and programming for a backup path adapt to the checkin programming of the primary path. When the primary path becomes available, normal communications are restored. Adaptive Technology provides additional confidence in the integrity of your system, while protecting you from unexpected cellular service charges. RI.. CL.DEQU T With other cellular backup equipment, you need to purchase additional enclosures, power supplies, batteries. cabling, and conduit connections. The 263C/263H reduces the number of pieces of equipment you have to purchase. It comes ready to mount, reducing your initial costs and simplifying both installation and ongoing operation. A CEO COP' CATION rs Adding the cellular communicator to the DMP XR150/XR550 fire alarm control panel can lower costs significantly compared to dial-up connections. Fire systems typically require two dial-up lines that can be eliminated and replaced with a single cellular connection. SLAVE COMMUNICATORS XR1 50/XR550 panels operate as slave communicators via cellular communicaton in fire installations compatible with an FACP. In addition to standard hardwire slave communications that connect via inputs to the DMP panel, 1103 Wireless Transmitters can be installed to communicate FACP status. ANTI MCEMENi' The unit includes both local and remote SMA (S-band multiple access) antenna connections, giving you added freedom and flexibility during installation. ., . •••..-.". S LOW CURRENT DRAiN With its extremely low current drain and long standby battery life, the 263C/263H will continue to provide a communications link for an extended period of time, even during a power failure. It draws half the current of other comparable units. SIMPLE TO INSTALL AND PROGRAM Connect the 263C or 263R to your panel, attach the antenna and power, and installation is complete. Programming the 263C/263H is fast and simple, accomplished within the panel itself. After programming the 263C/263H cellular communications path via Remote Link, you will be presented with the Activate SIM/MEID window to activate your cellular plan. Once activated, the wireless backup connection is immediately online protecting your communications link. No separate programming utility is required. SECURECOM CELLULAR The 263H comes standard with a SIM (Subscriber Identity Module) card ready to use SecureCom Wireless Cellular Service from DMP. The 263C does not include a SIM Card and is activated with the MOD number. With the 263C/263H and SecureCom, you have a one-stop resource for both hardware and cellular service. ENHANCED FIRE PROTECTION Compared to dial-up connections, a digital cellular communication link provides greater reliability, protection from sabotage, and is less prone to being knocked out by weather. Unlike mobile cellular connections. the 263C/263H creates a fixed network connection that minimizes hand-offs and the chance for dropped connections. When trouble conditions occur, they can be more quickly diagnosed and often corrected remotely. The NFPA 72 code requires a test of the entire communications path every five minutes. The DMP Model XR1 50/ XR550 Panel used with DMP 263C/263H Digital Cellular Communicator meets this requirement when check-in and fail time settings are programmed for five minutes. The net result is a higher level of system reliability in comparison with traditional systems that rely on redundant phone lines and the substantially less frequent 24-hour supervision reports associated with that approach. UPDATEABL E In addition to being able to change cellular carriers, you will also be ready to take advantage of technical improvements as they occur. The unit's modular architecture enables seamless upgrades as improved technology becomes available. MOBILE PLATFORMS DMP mobile platforms provide you with the tools you need to build strong connections with your customers, MyAccessTM enables end users to monitor and manage their systems remotely from any mobile phone using simple SMS texting. The Virtual KeypadTM App puts a keypad on the user's Apple iPhone®, iPadTM, or Android compatible devices. Dealers can offer these much- appreciated services to their customers and realize the benefits of additional recurring revenue. MACCESS . . Your customers can send many of the most common system commands to their residential or commercial systems via text messages. They can also choose to have alerts sent to them each time there's an arm/disarm, an alarm, or other selected events. Alerts can be transmitted by the panel as text messages to up to three phones. Users can also use MyAccess to interact with any Z-Wave devices programmed through their DMP panel, enabling them to control lights, thermostats, and more via text commands, THE VIRTUAL KEYPAD APP Dealers can invite their customers to begin using their APP to give them control of their security system. The Virtual Keypad allows them to arm or disarm, and to check the status of their cellular connected DMP security system from anywhere they have cell service. They can also access any Z-Wave home control devices programmed through their DMP panel and DMP cameras. © rA i F 0EVIC'S sui Complete your fire system with other DMP wireless devices that are ANSI/UL 864 Listed for Fire Protective Signaling Systems. TWOWAV COMMUNICATION Superior to traditional wireless devices that just broadcast until the zone is restored, DMP 1100 Series require an acknowledgement from the 1100 Series Receiver, indicating successful communication. This smart technology ensures that each and every communication is received and efficiently processed at the panel. With the 900MHz frequency-hopping spread-spectrum technology, clear and accurate signal transmissions without interference in practically any environment is to be expected. 1100 I IECEIVERS The 1100 Series Receivers: 1100X and 1100XH allowyoutoadd up to 500 transmitters and is required for wireless capability in both regular and harsh environments. 11o. l Model 1103 Universal Transmitter is typically used in commercial fire or burglary door/ window applications. It offers the same look and features as the 1101 transmitter, with the addition of a 470k end-of-line resistor and wall tamper switch. \ 1171165H./11' C(MMERCIAL 1(EDET"CT IS The Model 1165 Smoke Detector, 1165H Smoke/Heat Detector, and 1165H5 Smoke! Heat Detector with Sounder include a tamper switch that sends a trouble signal if the detector is removed from the mounting base. 1,181PC T ' ATOR !P.tVE The model 1181 PIV is a weather proof and tamper resistant wireless switch for monitoring the open position of fire sprinkler control values of the post indicator, butterfly and other types. 182 OS&Y The 1182 OS&Y Switch is used to monitor the open position of an OS&Y (Outside Screw and Yoke) type gate valve. The 1182 mounts conveniently to most OS&Y valves ranging in size from '/2" to 12". The switch operates the external contacts of the wireless transmitter when the valve position is altered from an open state. ACCESSORIES 270 Network Transient Suppressor 277 Trouble Annunciator 318 Battery Harness 381-2 18" Coax Extension 381-12 12' Coax Extension 381-25 25' Coax Extension 383 Rubber Duck Antenna 386 Wall Mount Antenna Bracket 387-1 3dB Fiberglass Antenna w/bracket 387-2 2dB Attack Enclosure Antenna 387-3 3dB MEG Antenna 387-25 SMATO N CABLE. 25FT, LMR195 387-50 SMATO N CABLE, 50FT, LMR195 866 Style W Notification Circuit Module 893A Dual Phone Line Module LISTINGS AND APPR')VI i California State Fire Marshal (CSFM) Underwriters Laboratories (UL) Listed Underwriters Laboratories Canada (ULC) Listed [I1AI[I1E Primary Power 12 VDC from panel Current Draw (263C) Standby 13mA Alarm 13mA Current Draw (263H) Standby 24mA Alarm 28mA COMPATIBILITY DMP XR150 I XR350 I XR550 Series Panels (A 381 cable is required for the XR1 50 1 XR350 I XR550 Series) UHOERING IN :P 263C COMA Cellular Communicator (Verizon) 263C/381-2 COMA Cellular Communicator w/ 381-2 Cable (Verizon) 263H HSPA+ Cellular Communicator (AT&T, T-Mobile, (263HCAN - Rogers)) 263H/381-2 HSPA+ Cellular Communicator w/ 381-2 Cable (AT&T. 1-Mobile, (263HCAN - Rogers)) For additional approval information, access www.dmp.com and - select Compliance. low 2500 North Partnership Boulevard 51 'l ' Springfield. Missouri 65803-8877 800.6414282 I dmp.com Designed. Engineered & Assembled in Springfield, Missouri A" 68 Power Requirements During AC power failure, the XR1 50FC/XR550FC Series panel and all connected auxiliary devices draw their power from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The following table lists the panel power requirements. You must add the additional current draw of keypads, zone expansion modules, smoke detector output, and any other auxiliary devices used in the system for the total current required. The total is then multiplied by the number of standby hours required to calculate the total ampere-hours required. Standby Battery Power Calculations Standby Current Alarm Current XR150FC/XR550FC Series Control Panel Qty I - x 174mA 174 mA Qty 1 x 217mA 217 mA Relay Outputs 1-2 (ON) Qty ______ 30mA Qty ______ 30mA Switch Grounds 3-6 (ON) Qty _______ 5mA ______ Qty _______ 5mA Active Zones 1-8 Qty ______ 1.6mA ______ Qty _______ *2mA Active Zones 9-10 Qty ______ 4mA Qty _______ 30mA 2-Wire Smoke Detectors Qty ______ 0.1mA ______ Qty _______ 0.1mA ______ Panel Bell Output 1 500mA mA 893A Dual Phone Line Module Qty x 12mA Qty _______ x 50mA ______ 263C CDMA Cellular Communicator Qty _______ x 13mA ______ Qty x 13mA ______ 263H HSPA+ Cellular Communicator Qty x 24mA Qty _______ x 28mA ______ 277 Buzzer Module Qty x 5mA Qty _______ x 5mA 1100X Wireless Receiver Qty x 46mA Qty _______ x 46mA ______ 1100XH Wireless High Power Receiver Qty x 160mA ______ Qty x 160mA ______ 860 Relay Output Module (one relay active) Qty x 34mA ______ Qty x 34mA ______ All four relays active 138mA 138mA 865 Style Y or Z Notification Module Qty x 26mA Qty _______ x 85mA 866 Style W Notification Module Qty x 45mA ______ Qty x 76mA 867 LX-Bus Style W Notification Module Qty x 30mA Qty _______ x 86mA ______ 869 Dual Style D Initiating Module Qty x 25mA ______ Qty x 75mA 630F Remote Fire Command Center Qty x 63mA Qty _______ x 92mA 7060/7160 Thinhine/7060AAqualite Keypad Qty x 72mA Qty _______ x 80mA 7063/7163Thinline/7063AAqualite Keypad Qty x 85mA _____ Qty x lOOmA 7070/7170 Thintine/7070AAquaLite Keypad Qty x 72mA Qty _______ x 87mA Active Zones (EOL Installed) 1.6mA Qty _______ x *2mA 7073/7173 Thinline/7073AAqualite Keypad Qty x 85mA _____ Qty x lOOmA Active Zones (EOL Installed) 1.6mA Qty _____ x *2mA 7872 Graphic Touchscreen Keypad Qty x 145mA Qty ______ x 215mA Active Zones (EOL Installed) 1.6mA ______ Qty _______ x *2mA 7873 Graphic Touchscreen Keypad Qty x 143mA ______ Qty x 243mA Active Zones (EOL Installed) 1.6mA ______ Qty _______ x *2mA 734 Wiegand Interface Module Qty x 15mA ______ Qty _______ x 15mA Active Zones (EOL Installed) Qty x 1.6mA ______ Qty x 2mA Annunciator (ON) Qty _______ x 20mA 734N Wiegand Interface Module Qty _______ x 146mA ______ Qty x 148mA Active Zones (EOL Installed) Qty x 1.6mA Qty _______ x *2mA Annunciator (ON) Qty _______ x 20mA Wiegand Reader Qty x 200mA Qty _______ x 200mA 734N-WiFi Wiegand Interface Module Qty x 146mA ______ Qty x 148mA Active Zones (EOL Installed) Qty x 1.6mA Qty _______ x 2mA Annunciator (ON) Qty _______ x 20mA Wiegand Reader Qty x 200mA Qty _______ x 200mA Copy Sub-Totals to next page Sub-Total Standby mA Sub-Total Alarm mA *Based on 10% of active zones in alarm. Digital Monitoring Products XR150FC/XR550FC Series Installation Guide 10 Standby Battery Power Calculations Standby Current Alarm Current 736P PONT Interface Module Qty x 25mA Qty x 25mA Radionics Popex, POPITs, OctoPOPITs Qty x _mA Qty x __mA 738AAdemco Wireless Interface Module Qty ______ x 75mA Qty _______ x 75mA ______ 710 Bus Splitter/Repeater Module Qty x 32mA Qty x 32mA _____ 711 Zone Expansion Module Qty x 11 mA Qty x 11 mA Active Zone (EOL Installed) Qty x 1.6mA Qty x *2mA 714 Zone Expansion Module Qty x 7mA Qty x 7mA Active Zones (EOL Installed) Qty x 1 .6mA Qty _______ x 712-8 Zone Expansion Module Qty x 17mA Qty ______ x 17mA Active Zones (EOL Installed) Qty x 1 .6mA ______ Qty _______ x *2mA 714-8, 714-16 Zone Expansion Module Qty x 20mA ______ Qty x 20mA ______ Active Zones (EOL Installed) Qty x 1 .6mA Qty _______ x *2mA 715 Zone Expansion Module Qty x 7mA ______ Qty x 7mA Active Zones (EOL Installed) Qty x 4mA Qty _______ x *30mA ______ 2-Wire Smokes Qty x .1mA ______ Qty _______ x .1mA 715-8, 715-16 Zone Expansion Modules Qty x 20mA ______ Qty x 20mA Active Zones (EOL Installed) Qty x 4mA Qty _______ x 30mA 2-Wire Smokes Qty x AmA _____ Qty ______ x .1mA 716 Output Expansion Module Qty x 13mA ______ Qty x 13mA Active Form C Relays Qty _______ x 12mA 717 Graphic Annunciator Module Qty x lOmA ______ Qty _______ x lOmA Annunciator Outputs Qty _______ x 1 mA 521 LX, 521 LXT Smoke Detectors Qty x 8.8mA ______ Qty _______ x *28mA Aux. Powered Devices on Terminals 7 and 11 mA mA Other than Keypads and LX-Bus Modules This page only Sub-Total Standby ______mA Sub-Total Alarm ______mA Sub-Totals from previous page Sub-Total Standby ______mA Sub-Total Alarm mA *Based on 10% of active zones in alarm Total Standby mA Total Alarm mA Total Standby mA x number of Standby Hours needed = mA-hours Total Alarm ______mA + mA-hours Total _______mA-hours X .001 = ___Amp-hrs Required Refer to section 6.9 for standby battery seection. XRI50FC/XR550FC Series Installation Guide Digital Monitoring Products 11 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-1157:0135 Page 1 of 2 CATEGORY: 7165-- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803 Contact: Terry Shelton (417) 831-9362 Fax (417) 831-1325 Email: tshelton©dmp.com DESIGN: Models XR150, XR350 and XR550 combination fire and burglary alarm control units. Local, remote station, proprietary and central station services. Models may have a combination of the following suffixes: D (dialer), N (network), E (encryption) or FC (fire control). Refer to listee's data sheet for additional detailed product description and operational considerations. System components: XR150, XR350, XR550: Main Board 341, 349, 350, 350A, 352P 352X: Enclosures 352S: Battery Enclosure 630F: Supervised LCD Keypad 7070, 7070A, 7073, 7073A, 7170, 7170A, 7173, 7173A, 7570, 7570A, 7573, 7573A: LCD Keypads 325: Transformer Bracket 322, 323, 324, 324P, 327: Transformers 711, 714, 714-8, 714-16, 715, 715-8, 715-16: Zone Expanders Output Expander Annunciator Module 860 Relay Module 893A: Dual Phone Line Module 734, 734N: Wiegand Interface 710: Bus Splitter 270: Network Transient Suppression Module 277: Trouble Sounder 9060, 9063: Wireless Keypads 263C, 263H: Cellular Communicator *(May be used as the standalone primary communicator) 865, 866, 867: Indicating Module 869: Initiating Module 303: Reset/Silence Switch hOaX, IIOOXH: RF Wireless Receiver 1100R: Wireless Repeater 1103: Wireless Transmitter 1135: Wireless Siren *Rev 04-08-15 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Listing No. 7165-1157:0135 Page 2 of 2 RATING: 120 VAC, 0.5 A, 60 Hz INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating and UL label. APPROVAL: Listed as combination fire and burglary alarm control units for use with separately listed electrically compatible initiating and indicating devices. Refer to listee's installation Instructions Manual for details. NOTE: 1. The Fire Alarm Verification Feature (delay of fire alarm signal), the maximum Retard/Reset/Restart period shall not exceed 30 seconds. 2. Burglary and other non-fire functions were not examined. Rev 04-08-15 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division Photoelectric Smoke Detectors System Sensor's /3' series smoke detectors represe sign/rican t aavancemen tin conventional aetection. The /3 family is founded on three principles: installation ease, intelligence, and instant inspection. Features Plug-in detector line, mounting base included Large wire entry port In-line terminals with SEMS screws Mounts to octagonal and single-gang backboxes, 4-square backboxes, or direct to ceiling Stop-Drop 'N Lock attachment to base Removable detector cover and chamber Built-in remote maintenance signaling Drift compensation and smoothing algorithms Simplified sensitivity measurement Wide angle, dual color LED indication Loop testing via EZ Walk feature Built-in test switch encv Listincis & <~> 0 MEA MSFM LISTED APPROVED approved approved 5911 3011446 7272-1209210 290-01-0 2093 Installation ease. The P line redefines installation ease with its plug-in design. This allows an installer to pre-wire the bases included with the heads. The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods, as well as direct mounting with drywall anchors. To complete the installation, il heads plug in to the base with a simple Stop-Drop 'N Lock' action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the il line to minimize nuisance alarms. Two-wire i3 detectors needing cleaning can generate a remote maintenance signal, when connected to the 2W-MOD2 loop test/maintenance module, or to a panel equipped with the i1 protocol. This signal is indicated by LEDs located at the module and the panel. The SENS-RDR, a wireless device, displays the sensitivityof i1 detectors in terms of percent per-foot-obscuration. Instant inspection. The P series provides wide-angle red and green LED indicators for instant inspection of the detector's condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on two-wire i3 detectors. This feature verifies the initiating loop wiring by providing LED status indication at each detector. (j) Smoke Detector Specifications Smoke detector shall be a System Sensor il Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems. The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-8, 4WT-B) with thermal sensor rated at 135F (57.2CC). The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal, single gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type. The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box. The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms. The detector shalt provide dual color LED indication which blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shalt include a maintenance signal to indicate the need for maintenance at the alarm control panel, and shall provide a loop testinq capability to verify the circuit without testing each detector individually. Operating Voltage Nominal: 12/24V non-polarized Minimum; 8.5V Maximum: 35V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 pA maximum average; 4-wire: 50 pA maX!FT)urn average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12V, 23mA @ 24V Peak Standby Current 2-wire: 100 pA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @ 30V AC/DC Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 6.3 oz. 078 grams) Operating Temperature Range 2W-B and 4W-B: 32F-120°F (0C-49C); 2WT-B and 4WT-B: 32F-100F (o°C-37.8°C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135F (57.2CC) fixed Freeze Trouble 2WT-B and 4WT-B only: 41F (5C) Sensitivity 2.51/o/ft. nominal InputTerminals 14-22 AWG Mounting 31/2-inch octagonal back box 4-inch octagonal back box Single gang back box 4-inch square back box with a plaster ring Direct mount to ceiling LED Mode Green LED Red LED Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information irr_/ thrnn_ 2W-B No 2-wire 130 mA max. limited by control panel 2WT-B Yes 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 ritA @ 12V, 23mA @ 24V 4WT-8 Yes 4-wire 20 mA @12V, 23mA @ 24V Accessories 2W-MOD2 2-wire loop test /maintenancemodule RT Removal / replacement tool SENS-RDR Sensitivityreader A77-AB2 Retrofit adapter bracket, 6,6 in, (16.76cm)diameter SYS TEM C2006 System Sensor, IL 60174 I5Itj5IR 3825 Ohio Avenue. St. Charles, Phone: 800-SENSOR2. Fax: 630-377-6495 . ; 11,2 Compatible 2-Wire Smoke Detector Chart Manufacturer Model Detector Base Base DC # of Zone Panel ID ID Voltage Detectors Expansion Zones Range (12V/24V) Modules Detection Systems DS230, DS23OF B/A MB2W, MB2WL A 8.5-33 10 725 Detection Systems DS250, DS25OTH B MB2W, M132WL A 8.5-33 10/12 715,715-8, 715-16,725 9&10 Detection Systems DS25OHD B MB2W, MB2WL A 8.5-33 10 715, 715-8, 715-16 9 & 10 Detection Systems DS260 B/A MB2W, MB2WL A 8.5-33 17 725 D5282, DS282TH, 715, 715-8, Detection Systems DS282THC, B 8.5-33 10/12 715-16, 725 9 & 10 DS282THS Hochiki SLR-835B-2 HD-6 N/A 8-35 14 725 SLR-8356H-2 Hochiki SLR-24, SLR-24H HD-3 NS4-220 HB-3 15-33 15 725 Hochiki SIJ-24, DCD-190, HD-3 NS4-220 HB-3 15-33 15 725 DCD-135 Hochiki SLR-24, SLR-24H HD-3 NS6-220 H13-3 15-33 15 725 Hochiki SIJ-24 HD-3 NS6-220 HB-3 15-33 20 725 Hochiki DCD-190, DCD- 135 HD-3 NS6-220 HB-3 15-33 16 725 429AT, 5216, 715, 715-8, Sentrol/ESL S09A 52113)(T 71T 521NB, 6.5-20 12 5-16 9 & 10 521NBXT Sentrol/ESL 429C, 429CT S10A 8.5-33 12 725 521B/BXT Sentrol/ESL 429CRT, 429CST, S11A 8.5-33 12 725 429C55T CRX 521T 711U, 712U, 713- 701E, Sentrol/ESL 5U, 713-6U, 721U, S10A , 702U 70-lU 702E, SOO 8.5-33 12 725 721UT 701E, 701U, Sentrol/ESL 731U, 723U S11A 702E, 702U, SOO 8.5-33 12 725 702RE, 702RU System Sensor 1400 A 8.5-35 10 715,715-8, 715-16 9 & 10 System Sensor 1151, 2151 A B110PL, 6401 8.5-35 10/10 715,715-8, 715-16,725 9 & 10 System Sensor 1451, 245 1TH A B401, 13401B 8.5-35 10 9 & 104O1B 715,715-8, 715-16 System Sensor 1451DH A DH400 8.5-35 10 715, 715-8, 715-16 9 & 10 2100T, 2100B, 715, 715-8, System Sensor 2100TB, 2100D, A 8.5-35 10 71 5-16 9 & 10 2100TD System Sensor 2400, 2400AT, A 8.5-35 10 715, 715-8, 9 & 10 2400A1T, 2400TH 715-16 System Sensor 2451 A 6401, B4O1B, 8.5-35 10 715, 715-8, 9 & 10 DH400 715-16 System Sensor 2W-B, 2WT-B A 8.5-35 10 715 715-8, , 715-16 9 & 10 System Sensor 2WTA-13, 2WTR-B A 8.5-35 10 715 , 715-8, 715-16 9 & 10 System Sensor DH100P, DH100LP A 8.5-35 10 715, 715-8, 715-16, 725 9 & 10 Compatible 2-Wire Smoke Detectors XR1SOFC Series Installation Guide Digital Monitoring Products 15 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-1653:0152 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhartsystemsensor.com DESIGN: Models 2W-B, 2WT-B, 4W-B and 4WT-B photoelectric type smoke detectors. Models 2W-B and 2WT-B are 2-wire and model 4W-B and 4W1-B are 4-wire detectors. Models 2W1-B and 4\.NT-B employ a thermistor type heat sensor (135°F). The heat sensor is are supplemental to the detector and is not intended for use as a required heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 8.5 - 35 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling mount. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/mm. NOTE: Formerly 7272-1209:210 06-20-05 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division r- ) LISTED he 850 series Fire Pull Stations come fully quipped with single or double action manual ull options, SPST contacts, and terminal strip onnections. These specialized SPST contacts are old-plated to avoid corrosion. The 850 complies ith the latestADA requirements. STOP & 8SO ! c rc FEATURES Approvals: UL, FM, and CSFM • Gold-plated SPST contacts ADA compliant • Mounts on standard single-gang box Die-cast metal construction • Optional surface and weatherproof backboxes available Single or dual action • High-gloss red enamel finish Reset key • Scored acrylic breakrod 4 DESCRIPTION The DMP 850 Series Fire Alarm Pull Station is a high quality, die-cast metal manual pull station available in either single-action or dual- action configurations with SPST contacts and terminal strip connections. The normally open contact, which closes when the pull station is activated, is rated for 1 Amp @30 VDC. The contacts are gold-plated to avoid corrosion risks. Scored acrylic breakrods may also be used with the 850 series. COMPLIANCE The 850 series has been tested by UL for compliance to the latest requirements of the Americans with DisabilitiesAct (ADA). MOUNTING OPTIONS A variety of mounting options are available for the 850 series. It can be flush mounted to a standard single gang switch box or surface mounted in two optional configurations. The Model 850-SB Interior Surface Backbox or the Model 850-WP Weatherproof Backbox both allow conduit connection to the 850 Series Pull Stations. 8505 OPERATION The Model 850S Single Action Pull Station is operated by pulling the handle on the front of the station as far down as it goes. When the handle locks into place it is easily visible from up to 50 feet. Reset the handle by opening the station with the supplied key, placing the handle in the normal upright position, and re-locking the station. 8500 OPERATION On the Model 850D Dual Action Pull Station, the push bar rotates inward allowing the PULL handle to be grasped in a one handed motion. PULL Screw Terminals To next To Fire Alarm EOL resistor device or Control Panel Model 850 Wiring Diagram SPECIFICATIONS Switch Rating 1 Amp @ 30 VDC Dimensions 4.75" H x 3.25" W x 2.25" D Color Red w/raised white Letters, white PULL handle w/ raised red letters ORDERING INFORMATION 850S Single-action pull station 850D Dual-action pull station 850-SB Interior surface sheetmetal backbox 850-WP Weatherproof surface die-cast backbox 850-AR Scored acrylic breakrods (1 dozen) 850S/711 Single-action pull station w/addressable module 850D/711 Dual-action pull station w/addressable module Note: All models are supplied with one scored acrylic breakrod and one key. u o 2500 North Partnership Boulevard Springfield, Missouri 65803-8877 'AA' (I1J1Y;1 j CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7150-1157:0112 Page 1 of I CATEGORY: 7150-- FIRE ALARM PULL BOXES LISTEE: Digital Monitoring Products2500 N. Partnership Blvd, Springfield, MO 65803 Contact: Terry Shelton (417) 831-9362 Fax (417) 831-1325 Email: tshelton@dmp.com DESIGN: Models 850D (key lock, push bar) and 850S (key lock, no push bar) noncoded manual pull stations. Suitable for outdoor use when installed with Model 850-WP back box. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 30VDC INSTALLATION: In accordance with listee's printed installation, applicable codes & ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as manual pull stations for use with separately listed and compatible fire alarm control units. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments. XLF: 7150-1408:0107 *Rev 06-22-09 fm TI This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division 4-Wire Photoelectric Duct Smoke Detector The lnnovairFlex'°' Series are the only duct smoke detectors flexible enough to fit configurations from square to rectangular and everything in between. Features Photoelectric, integrated low-flow technology Air velocity rating from 100 ft/min to 4,000 ft/mm (0.5 m/s to 20.32 m/sec) Versatile mounting options: square or rectangular configuration Plug-in sensor offers superb false alarm immunity and the latest sensor technology Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non-condensing) Patented sampling tube installs from front or back of the detector with no tools required Increased wiring space with a newly added 1/4-inch conduit knockout One easy-access Test/Reset button and improved LED status Patented interconnect feature for multi-fan shutdown New high contrast terminal designations Built-in short circuit protection from operator wiring errors Field selectable settings for configuring the detector Two DPDT Form-C relay contacts 24VAC/DC or 120 VAC Backward compatibility with existing Innovair products, including remote accessories InnovCk exft The InnovairFiex D4120 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of —4°F to 158°F, and a humidity range of 0 to 95 percent (non- condensing). A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance. The InnovairFIex housing provides ample wiring space, a 1/4-inch conduit knockout, and built-in short circuit protection to prevent damage to sensitive components during installation. High contrast terminal designations make wiring easy. With its 2:1 sensor-to-power capability, the power board of the D4120 may be used to monitor a second sensor, D4S, simultaneously (i.e., supply and return side). As many as 50 InnovairFIex detectors can be interconnected. When one unit senses smoke, all interconnected detectors will switch their relays; only the detector sensing smoke will go into alarm, thus pinpointing the fire source. An easy-access Test/Reset button makes it possible to test the unit with the cover on. Three DIP switches can be used to configure field selectable settings: cover tamper delay, number of sensors to be controlled, and shut down on trouble option. Each power board has two LEDs that can be used to indicate the status of connected sensors, and a quick reference imprinted on the cover explains the LED status indications (Standby, Maintenance, Trouble, and Alarm). The InnovairFIex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new lnnnvirFlex nroduct line is compatible with all previous Innovair Agency Listings models, including remote test accessories. ZE1i IVISFM WARNING: Duct smoke detectors are NOT a substitute for open area smoke detectors; NOT a substitute for early warning detection; LISTED APPROVED 3029700 3247-1653207 approved 2202 NOT a replacement for a building's regular fire detection system. Refer to NFPA 72 and 90A for additional information. InnovairFlex' Duct Smoke Detector Specifications The air duct smoke detector shall be a System Sensor lnnovairFlex D41 20 Photoelectric Duct Smoke Detector. The detector housing shall be UL listed per DL 268A specifically for use in air handling systems. The flex ble housing of the duct smoke detector fits multiple footprints from square to rectangular. The detector shall operate at air velocities of 100 feet per minute to 4000 feet per minute (0.5 to 20.32 meters/second). The unit shall be capable of controlling up to 50 air handling systems when interconnected with other detectors. The detector shall be capable of providing a trouble signal in the event that the front cover is removed. It shall be capable of local testing via magnetic switch, test button on the cover, or remote testing using the SSK451 Multi-Signaling Accessory or the RTS451 KEY Remote Test Station. Terminal connections shall be of the strip and clamp method suitable for 12-18 AWG wiring. Size: (Rectangular Dimensions) (Square Dimensions) 14.38 in (37 cm) Length; 5 in (12.74cm) Width; 2.5 in (6.36 cm) Depth 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 2.5 1 b (1.14kg) Operating Temperature Range: D4120 & 04S: -4 to 158F (-20 to 70CC); D4P120: -40 to 158SF (-40 to 70CC) Storage Temperature Range: D4120 & D4S: -22 to 158'F (-30 to 70CC); D41`1 20: -40 to 158F (-40 to 70CC) Operating Humidity Range: 0% to 95% relative humidity non-condensing Air Duct Velocity: 100 to 4000 ft/mm (0.5 to 20.32 rn/set) Power supply voltage: I - - 20-29 VDC 24 VAC 50-60 Hz 120 VAC 50-60 Hz Input capacitance: 270 jjF max. 270 pF max. N/A Reset voltage: 3.0 VDC mm. 2.0 VAC mm. 1OVAC mm. Reset time: (with RTS451) .03 to 0.3 sec. .03 to 0.3 set. .03 to 0.3 sec. Reset time: (by power down) 0.6 sec. rrrax. 0.6 sec. max. 06 sec. max. Power up time: 35 sec. max. 35 sec. max. 35 sec. max. Alarm response time: 15 sec. 15 sec. 15 sec. Sensitivity Test: See detector label See detector label See detector label Current Requirements: (Using No Accessories) Max. standby current: 21 mA @ 24VDC 65 mA RMS @ 24VAC 60Hz 20 mA RMS @ 120VAC 60Hz Max. alarm current: 65 mA @ 24VDC 135 mA RMS @ 24VAC 60Hz 35 mA RMS @ 120VAC 60Hz Alarm initiation contacts: (SPST) 2.0A @30 VDC (resistive) Alarm auxiliary contacts: (DPOT) 10A @30 VDC (resistive); 10A @250 VAC (resistive); 1/2 HP @240 VAC; ¼ HP @ 120 VAC Note: Alarm auxiliary contacts shall not be connected to iritiating circuits of control panels. Use the alarm initiation contact for this purpose. Supervisory contacts: (SPOT) Device 2.OA @30 VDC (resistive); 2.OA @ 125 VAC (resistive( Standby Trouble Alarm APA151/APA451 12.5 mA n/a 30mAMax. MHR/MHW OmA n/a 29 mA Max. RA100Z 0 mA n/a 12 mA Max. RTS151/RTS15IKEY 0rnAJ12mA n/a 12mAMax. RTS2/RTS2-AOS 3.0mA max 16 mA Max. with strobe: 55 mA max; without strobe 30 mA max Note: Any combination of accessories maybe used such that the given accessory loads are: 110 mA or less at the Aux output, and 50 mA or less at the Alarm output Installing the InnovairFIex Sampling Tube The InnovairFlex sampling tube may be installed from the front or back of the detector. The tube locks securely into place and can be removed by releasing the front or rear locking tab (front locking tab shown below right). AOS-0419-002 I------------ LAST DETECTOR IN THE LOOP NOTE 3: Supervisory contacts shown in standby position. Open contacts indicate a trouble condition to the panel. See specifications for contact ratings. NOTE 4: Alarm Initiation contacts shown in standby position. Closed contacts indicate an alarm condition to the panel. See specifications for contact ratings. Wiring for 4-wire Duct Smoke Detector and Accessories ------------ I POWER INPUTS (NOTE 1) I I 4vAc/oc 120 I FVAC I& &I 910 I OR I I AUXILIARY CONTACTS I FOR FAN SHUTDOWN, ETC. (NOTE 2) AUXA AUXB I SUPERVISORY CONTACTS I (NOTE 3) I UL/FM LISTED 4-WIRE CONTROL PANEL I I ------------ FIRST DETECTOR IN THE LOOP NOTE 1: 24V Power Inputs accept a non-polarized 24VDC or 24VAC 50-60Hz, 120VAC Power Inputs accept only 12OVAC 50-60Hz. Connect power source to appropriate terminals of each detector. See specifications for additional power supply information. NOTE 2: Auxiliary contacts shown in standby position. Contacts switch during alarm as indicated by arrows. Auxiliary contacts are not to be used for connection to the control panel. See specifications for contact ratings. I POWER INPUTS (NOTE 1) I I FVA 910 I I OR I I AUXILIARY CONTACTS I FOR FAN SHUTDOWN, ETC. (NOTE 2) I AUXA AUXB JN N I SUPERVISORY CONTACTS (NOTE 3) I EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER '1 Please refer to the corresponding installation manual for accessory wiring diagrams. Important Notes on 2:1 Sensor-to-Power Capability - 2:1 sensor-to-power capability is not available for all InnovairElex models. The feature is only available on the 041204-wire conventional models. - 2:1 sensor-to-power capability can be enabled using one 04120 and one D45, or two D4S and one 04P120. lmDortant Interconnect Notes - When using the interconnect feature, all interconnected units must be powered using the same independent supply. - Polarity must be maintained throughout the interconnect wiring. Connect the lNT± terminal on unit 1 t the INT+ terminal on unit 2 and so on. Similarly, connect the lNT/AUX— terminal on unit ito the INT/AUX- terminal on unit 2 and so on. - Up to 5004120 units, 50 D4P1 20 units, or 50 units of combination may be interconnected. - Up to 10 DH t OOACDC units may be interconnected. Please note that each of the 9 OH 100ACDC units interconnected may be replaced by three D4P120 units, Therefore, when using the interconnect feature a single DH100ACDC can drive either 9 DH100ACDCs or 2704120 units. NOTE: Alarm can be reset only at the initiating device and not at the devices interconnected. A05.04r9.2 Accessories System Sensor provides system flexibility with a variety of accessories, including two remote test stations and several different means of visible and audible system annunciation. As with our duct smoke detectors, all duct smoke detector accessories are UL listed. 1 I ' 0 RTS151 UL S4011 RTS151KEYULS2522 APA151 UL54011 RTS2-AOS UL S2522 I I RA OOZ UL 52522 MHW UL 54011 MHR UL 54011 AGS Ordering Information D4120 4-wire photoelectric low-flow duct smoke detector Accessories D4S 4-wire photoelectric sensor component only MHR Mini Horn Red 04P120 4-wire photoelectric power board component only, MHW Mini Horn, White 24VAC/DC, 120 VAC 2D51 4-wire conventional photoelectric sensor head 0511 Metal sampling tube duct width up to lit (0.3m) DST1 .5 Metal sampling tube duct widths lit to 2 ft 10.3 to 0.6 ml 0513 Metal sampling tube duct widths 2 ft to 4 ft (0.6 to 1.2 m) DST5 Metal sampling tube duct widths 4 ft to ft (1.2 to 2.4 m) DSTiO Metal sampling tube duct widths 8 ft to 12 ft (2.4 to 3.7 m) APA151 Remote annunciator with piezo alarm DH400 OE-1 Weatherproof enclosure ETX Metal exhaust tube duct width lit (0.3m) M02-04-00 Test magnet P48-21-00 End cap icr metal sampling tubes RAIOOZ Remote annunciator alarm LED R1S151 Remote test station RTS1 51 KEY Remote test station with key lock RTS2 - ACS Multi-signaling accessory "\SY ©2010 Syttern I ' 3825 Ohio Avenue St. Charles, IL 60174 P,odunt ,penS,tson, tobjent to nhorgeoitbont r,ot,ne \tsynereoeneocornfor 5Et',!5OR Phone: 300-SENSOR2• Fax: 630-377-6495 AOS-0419-002 .2110. #2305 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE $ -10- LISTING No. 3242-1653:0207 Page 1 of I CATEGORY: 3242 -- DUCT SMOKE DETECTOR, PHOTO. (W/ OR W/0 BASE) LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Trish Linhart (630) 762-5025 Fax (630) 377-7245 Email: trish.linhartsystemsensor.com DESIGN: Models D4120, D4240, RD4120, P270-3000PL, TD41203, TD41204, LD4S, LD412OX, LD4120H, D4S, D4P120, CD4P120 LD4P120X, LD4P120H, TD4C, PD4120, YD4120, YD4PI20, and AD4PI20 four-wire conventional photoelectric duct smoke detectors and subassemblies. Unit consists of a duct detector housing, powerboard with electrical components and relays, exhaust tubes, and listed 2D51 detector head (CSFM Listing No. 7272-1653:203). ModelAD4S sensor component. Models *TD4C, LD412OX, LD4I20H, LD4P120X and LD4P120H do not contain a 120 VAC transformer. Refer to listee's data sheet for additional detailed product description and operational considerations. RATING: 20-29 VDC, *24 VAC, 120 VAC (except Models *TD4C, LD412OX, LD4120H, LD4P120X and LD4P120H do not have 120 VAC rating). INSTALLATION: In accordance with listee's printed installation instruction, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, rating, air velocity and UL label. APPROVAL: Listed as conventional photoelectric duct smoke detector for use with separately listed fire alarm control units. Refer to listee's Installation Instruction Manual for details. *Rev. 03-27-13 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD U.S. Pat. No. 3921989 Canadian Pat. No. 1009680 Other Patents Pending Potter Electric, Rd., 1990 GENERAL INFORMATION The Model VSR-F is a vane type waterfiow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2" thru 8" (50mm thru 200mm). LPC approved sizes are 2" thru 8" (50mm thru 200mm). The unit may also be used as a sectional waterfiow detector on large systems. The unit contains two single pole, double throw, snap action switches and an adjustable, instantly recycling pneumatic re- tard. The switches are actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period. ENCLOSURE: The unit is enclosed in a general purpose, die- cast housing. The cover is held in place with two tamper resis- tant screws which require a special key for removal. A field in- stallable cover tamper switch is available as an option,which may be used to indicate unauthorized removal of the cover. See bulletin no. 5400775 for installation instructions of this switch. UL, ULC and CSFM Listed, FM and LPCBApproved, NYMEA Accepted, CE Marked Service Pressure: Up to 450 PSI (31 BAR) Minimum Flow Rate forAlarm: 10 GPM (38 LPM) Maximum Surge: 18 FPS (5,5 m/s) ContactRatings: Two sets of SPDT (Form C) 15.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive Conduit Entrances: Two knockouts provided for 1/2 conduit Environmental Specifications: Suitable for indoor or outdoor use with factory installed gasket and die-cast housing. NEMA 4/I P54 Rated Enclosure - use with appropriate conduit fitting. Temperature Range: 40°F/1 20°F, 4,5°C/49C Non-corrosive sleeve factory installed in saddle. Caution: This device is not intended for applications in explosive environments. Sizes Available: Steel Pipe schedules 10 thru 40, sizes 2" thru 8" BS 1387 pipe 50mm thru 200mm Note: For copper or plastic pipe use Model VSR-CF. Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-13D Residential occupancy up to four stories NFPA-1 3R National Fire Alarm Code NFPA-72 Optional: Cover Tamper Switch Kit, Stock No. 0090018 INSTALLATION: See Fig.2 These devices may be mounted on horizontal or vertical pipe. On horizontal pipe they should be installed on the top side of the pipe where they will be accessible. The units should not be in- stalled within 6" (15cm) of a fitting which changes the direction of the waterfiow or within 24" (60 cm) of a valve or drain. Drain the system and drill a hole in the pipe using a circular saw in a slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices require a hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm ±2mm). All other sizes require a hole with a diameter of 2" ±1/8" (50mm ±2mm). Clean the inside pipe of all growth or other material for a dis- tance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterfiow. Install the saddle strap and tighten nuts alternately to an eventual 50 ft-lbs. (68 n-m) of torque (see Fig. 2). The vane must not rub the inside of the pipe or bind in any way. Specifications subject to change without notice. Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 631464161 • Phone: 800-325-3936/Canada 888-882-1833 www.pottersignal.com PRINTED IN USA MKT. #8800001 - REV W PAGE 1 OF 2 MFG. #5400761 - 7/02 FIG. 2 DO NOT LEAVE COVER OFF FOR EXTENDED PERIOD OF TIME TIGHTEN NUTS ALTERNATELY TO AN EVENTUAL SOFT-LBS (68 -m) OF TORQUE MOUNT ON PIPE SO ARROW ON SADDLE POINTS IN DIRECTION OF WATERFLOW ROLL PADDLE IN OPPOSITE DIRECTION OF WATERFLOW APPROX. RETARD SETTINGS (IN SECS,) 0 0 A711 ' .0 0-2 35-55 0 50-70 E 60_90 OPTIONAL TAMPER SWITCH RETARD ADJUSTMENT: TO CHANGE TIME TURN KNOB (EITHER DIRECTION) FOR DESIRED TIME DELAY. USE THE MINIMUM AMOUNT OF RETARD NECESSARY TO PREVENT FALSE ALARMS, A B" SETTING IS USUALLY ADEQUATE FOR THIS, FACTORY IS SET TO "B". TO INSTALL, DRILL HOLE AS INDICATED: PIPE SIZE HOLE SIZE 2" to 2 1/2' 1 1/4" +1/8" -1/16" (50mm to 65mm) (33mm ±2mm) 3 to 8" 2" ±1/8" (80mm to 200mm) 50mm ±2mm) Cover Tamper (with cover in place) WATERFL ROW OF C NO NC (WAT) (000) (BILK) CIA. INID.IA.2 DWG. #761-30 FIG. 4 To remove knockouts: Place screwdriver at edge of knock- outs, not in the center. DWG. 476I-4 ® POTTER The Symbol of Protection VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD _o FIG. I SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL o J 0 to OWG. #023-3 CAUTION: An uninsulated section of a single conductor should not be looped around the termi- nal and serve as two sepa- rate connections. The wire must be severed, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. FIG. 3 TYPICAL ELECTRICAL CONNECTIONS NOTES: The Model VSR-F has two switches, one can be used to 2 SETS OF operate a central station, pro- NORMALLY OPEN 00414015 CLOSE ON ADARALARM NRTORFLOW COLR FX4 I ZONE ANEL ON ENC prietary or remote signaling 141 unit, while the other contact is __ used to operate a local audible or visual annunciator. A condition of LPC Approval of P050140 this product is that the electri- CRC CC AND CO APRRO4GS OR THE Sv1C4 PRO FOR PR PUPA CODOTON. OR ROT AC cal entry must be sealed to THE COCTPCO PRO REV00500 CODER THE 000CC 5 IN NCGOTTAE XC ______________________ OR NEUTRAL HOD. 1761-2 exclude moisture. THE NORMAL C000IIION. For supervised circuits see "Switch Terminal Connec- tions" drawing and caution note (Fig. 1). APPLICATION WARNING! Due to the possibility of unintended discharges caused by pressure surges, trapped air, or short retard times, waterfiow switches that are monitoring wet pipe sprinkler systems should not be used as the sole initiating device to discharge AFFF, deluge, or chemical suppression systems. TESTING The frequency of inspection and testing for the model VSR-F and its associated protective monitoring system should be in accordance with applicable NFPA Codes and Standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). If provided, the inspector's test valve, that is usually located at the end of the most remote branch line, should always be used for test purposes. If there are no provisions for testing the operation of the flow detection device on the system, application of the VSR-F is not recommended or advisable. A minimum flow of 10 gpm (38 Lpm) is required to activate this device. IMPORTANT NOTICE: Please advise the person responsible for testing of the fire protection system that this system must be tested in accordance with the testing instructions. PRINTED IN USA MKT. #8800001 - REV W PAGE 2 OF 2 MFG. #5400761 - 7/02 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL P1!T1 FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7770-0328:0001 Page 1 of 1 CATEGORY: 7770-- VALVES/SWITCHES LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999 Email: BillW©pottersignal.com DESIGN: Vane and pressure type water flow alarm switches listed below. Refer to listee's data sheet for detailed product description and operational considerations. Vane Types: VSR-CF VSR-D VSR-F VSR-SF VSR-FE-2 VS-SP VS-F VSR-SFG VSR-SFT VSG VSR VSR-S VSR-C VSR-ST VSR-SG Pressure Type: WFS-B WFSR-C WFSPD-B P510 PS-1 OA PS-bOA WFSR-F P5100 INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL or FM label. APPROVAL: Listed as waterflow alarm switches for use with fire sprinkler systems. Vane models may be used in wet pipe systems; pressure models may be used in wet or dry systems. Model VSR-CF is for use on K, L or M copper pipe (2', 2-1/2', 3", 4") and listed CPVC pipe (2", 2-1/2", 3"). Model VSR-SF for use on 1', 1-1/4", 1-1/2" and *2 steel, copper or listed plastic pipe. Model VSG is for low flow rate. Model VSR-SFG and VSR-SFT are for use on 1", 1-1/4", 1-1/2" and *2 plastic pipe. Models VS-F, VSR-F, VSR-FE and VSR-FE-2 is for use on 2", 2-1/2", 3", 3-1/2", 4", 5", 6", 8" and 10" pipe. *Model VSR is for use on steel pipe sizes from 2" through 8". Vane type switches may be used outdoors when the outdoor temperature never falls below 40oF. Rev*5172007 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division r L OSYSU-1 Stock No. 1010106 OSYSU-2 Stock No. 1010206 GENERAL INFORMATION The OSYSU is used to monitor the open position of an OS & Y (outside screw and yoke) type gate valve. This device is available in two models; the OSYSU-1, containing one set of SPDT (Form C) contacts and the OSYSU-2, con- taining two sets of SPOT (Form C) contacts. These switches mount conveniently to most OS & Y valves ranging in size from 2" to 12" (50mm to 300mm). They will mount on some valves as small as 1/2" (12,5mm). The cover is held in place by two tamper resistant screws that require a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replacement or additional cover OSYSU-1, -2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH UL and CSFM Listed, FM Approved, NYMEA Accepted, CE Marked Dimensions: 6.19"L X 2.25WX 5.88H 15,7cm LX 5,7cm W 14,6cm H Weight: 2 lbs. (0,9 kg.) Enclosure: Cover - Die-Cast Finish - Red Spatter Enamel Base - Die Cast Zinc All parts have corrosion resistant finishes. Cover Tamper: Tamper resistant screws, Optional cover tamper kit available. Contact Ratings: OSYSU-1: One set of SPDT (Form C) OSYSU-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Limitations: NEMA 4 and NEMA 6P Enclosure (lP67) when used with appropriate watertight conduit fittings. Indoor or Outdoor use (Not for use in hazardous locations. See bulletin no. 5400705 OSYS-U-EX for hazardous locations.) Temperature Range: -40°F to 140'F (-40°C to 60°C) Conduit Entrances: 2 knockouts for 1/2 conduit provided Service Use: Automatic Sprinkler NFPA-13 One or two family dwelling NFPA-1 30 Residential occupancy up to four stories NFPA-1 3R National Fire Alarm Code NFPA-72 screws and hex keys are available. See ordering informa- tion on page 4. OPTIONAL COVER TAMPER SWITCH A field installable cover tamper switch is available as an option which may be used to indicate removal of the cover. See ordering information on page 4. TESTING The OSYSU and its associated protective monitoring sys- tem should be inspected and tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). Potter Electric Signal Company 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833. www.pottersignal.com PRINTED IN USA MKT. #8820004 - REV P PAGE 1 OF 4 12/01 (! POTTER The Symbol of Protection OSYSU1, 2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG. I SMALL VALVE INSTALLATION - 1/2" THRU 2 1/2" (12,5mm THRU 63,5mm) SIZES THESE SWITCHES MOUNT CONVENIENTLY TO MOST 2' TO 12" OS & Y VALVES. THEY WILL MOUNT ON SOME VALVES AS SMALL AS 1/2" (12,5MM). J-HOOKS MAY BE REQUIRED ON VALVES WITH LIMITED CLEARANCE. CLAMP BAR CARRIAGE BC SLOTTED MOUNTING HOLES MAY BE USED FOR FINE ADJUSTMENT OF SWITCH ON BRACKET BRACKET OWG. fl979-3 SMALL VALVE INSTALLATION Remove and discard "C" washer and roller from the trip rod. With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non- threaded portion of the valve stem. Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the 1" (25mm) long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 procedure. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. On valves with limited clearance use J-hooks supplied instead of the carriage bolts and clamp bar to mount the OSYSU. Mark the valve stem at the center of the trip rod. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered on the mark on the valve stern utilizing a 3/16" (4,8mm) round, nontapered file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. Mount the OSYSU with the trip rod centered in groove. Final adjustment is made by loosening 2 screws (see Fig. 1) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate when the trip rod moves out of the groove. Tighten the adjustment screws and all mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION. PRINTED IN USA MKT. #8820004 - REV P PAGE 2 OF 4 12/01 OSYSU-11 2 OUTSIDE SCREW AND YOKE VALVE SUPERVISORY SWITCH FIG. 2 LARGE VALVE INSTALLATION - 3" THRU 12" (76mm THRU 300mm) SIZES 3" THRU 12" (76mm THRU 300mm) VALVES BRACKET USE CARRIAGE BOLTS. BOLTS MOUNT ON INSIDE OF YOKE, IF THERE - CLAMP BAR IS SUFFICIENT CLEARANCE. CARRIAGE BOLTS SLOTTED MOUNTING (2 REQUIRED) HOLES. MAY BE USED— ROLLER FOR FINE ADJUSTMENT GROOVE OF SWITCH ON BRACKET, YOKE VALVE STEM —TRIP ROD DWG. #979-4 LARGE VALVE INSTALLATION With the valve in the FULL OPEN position, locate the OSYSU across the valve yoke as far as possible from the valve gland, so that the trip rod lays against the non- threaded portion of the valve stem. Mount the OSYSU loosely with the carriage bolts and clamp bar supplied. Loosen the locking screw that holds the trip rod in place and adjust the rod length (see Fig. 4). When adjusted properly, the rod should extend past the valve screw, but not so far that it contacts the clamp bar. Tighten the locking screw to hold the trip rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one 1" (25mm) long notched section (see Fig. 5). Reinstall trip rod and repeat Step 3 proce- dure. Mark the valve stem at the center of the trip rod. Remove the OSYSU. File a 1/8" (3,2mm) deep groove centered on the mark of the valve stem utilizing a 3/8" (9,5mm) round, non-tapered file. Round and smooth the edges of the groove to prevent damage to the valve packing and to allow the trip rod to move easily in and out of the groove as the valve is operated. Mount the OSYSU loosely with the trip rod centered in groove. Final adjustment is made by loosening 2 screws (see Fig. 2) and sliding the OSYSU on the bracket. Adjustment is correct when switches are not activated with the trip rod seated in the valve stem groove and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. Tighten the adjustment screws and mounting hardware. Check to insure that the rod moves out of the groove easily and that the switches activate within one turn when the valve is operated from the FULL OPEN towards the CLOSED position. NOTE: CLOSE THE VALVE FULLY TO DETERMINE THAT THE STEM THREADS DO NOT ACTIVATE THE SWITCH. THE SWITCH BEING ACTIVATED BY THE STEM THREADS COULD RESULT IN A FALSE VALVE OPEN INDICATION. PRINTED IN USA MKT. #8820004 - REV P PAGE 3 OF 4 12/01 ORDERING INFORMATION MODEL DESCRIPTION STOCK NO. OSYSU-1 Outside Screw & Yoke-Supervisory Switch (Single switch) 1010106 OSYSU-2 Outside Screw & Yoke-Supervisory Switch (Double switch) 1010206 - Cover Screw 5490344 - Hex Key for Cover Screws and Installation Adjustments 5250062 - Optional Cover Tamper Switch Kit 0090131 For pressure reducer type valve installation kits (if required) contact valve manufacturer. OPEN VALVE POSITION CON. SW #1 CON._ SW #2 CLOSED VALVE POSITION SW #1 l- C CNO SW #2 r- DWG. #979-2 OSYSU-1 -2 POTTER OUTSIDE SCREW AND' YOKE VALVE — The Symbol of Protection SUPERVISORY SWITCH FIG. 3 DIMENSIONS FIG. 4 PARTS R(W wo SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL 41 ) 106 0UTC0 OWG. 0923-3 CAUTION: An uninsulated section of a single conductor should not be looped around the terminal and serve as two separate connections. The wire must be severed, thereby providing supervi- sion of the connection in the event that the wire becomes dislodged from under the terminal. TYPICAL ELECTRICAL CONNECTIONS LOCAL CIRCUIT NO. INDICATING TO POWER FOR COr-1N.C. DEVICE INDICATING DEVICE TO SUPERVISORY CIRCUIT END OF OF CONTROL PANEL LINE Co.. N.C. I RESISTOR I OWG. #979-1 Contacts shown in normal (valve open) condition. TYPICAL SWITCH ACTION BREAKING EXCESSIVE ROD LENGTH FIG. 5 - PRINTED IN USA MKT. #8820004 - REV P PAGE 4 OF 4 12/01 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7770-0328:0010 Page 1 of 1 CATEGORY: 7770 - VALVES/SWITCHES LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999 Email: BillWpottersignaLcom DESIGN: Supervisory switches listed below to monitor pressure, OS&Y, gate, globe/gate, Ply, tank temperature or water level valves. Refer to listee's data sheet for detailed product description and operational considerations. L HLS-B WLS-W PS-120A OSYSU-2 PTS-B OSYSU-1 P1 VS-B ITS-S WLS PTS-C *RBVS WLS-S PS-40A OSYS-B PMS GVS PCVS-1 TTS-W PCVS-2 PS4O PS12O RATING: INSTALLATION: MARKING: APPROVAL NOTE n accordance with listee's printed instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model designation and FM or UL label. Listed as sprinkler system supervisory switches. Formerly 7738-0328:010 *Rev 5-17-2007 ;w This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct V' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division POTTER The Symbol of Protection PCVS-1 Stock No. 1010107 PCVS-2 Stock No. 1010207 The Model PCVS is a weather proof and tamper resistant switch for monitoring the open position of fire sprinkler control valves of the post indicator, butterfly and other types. Depending on the model, one or two SPDT (Form C) contacts are provided which will operate when the valve position is altered from an open state. The unit mounts in a 1/2" NPT tapped hole in the post indicator or butterfly valve housing. The device is engaged by the indicating assembly of the post indicator or the operating mechanism of the butterfly valve, actuating switch(es) when the valve is fully open. The unit should be installed where it is accessible for service. The cover is held in place by two tamper resistant screws that require PCVS-1, -2 CONTROL VALVE SUPERVISORY SWITCH UL and CSFM Listed, FM Approved, NYMEA Accepted, CE Marked Dimensions: 4.75"L x 2.25"Wx 7.2"H (stem extended) 12,1 cm Lx 5,7cm Wx18,3cm H Weight: 1.35 lb. (0,61 kg.) Enclosure: Cover - Die-cast Finish - Red Spatter Enamel Base - Die Cast Zinc All parts have corrosion resistant finishes. Cover Tamper: Tamper Resistant Screws, Optional cover tamper kit available Mounting: 1/2" NPT Contact Rating: PCVS-1: One set of SPDT (Form C) PCVS-2: Two sets of SPDT (Form C) 15.00 Amps at 125/250VAC 2.50 Amps at 30VDC resistive Environmental Limitations: -40°F to +140°F (-40°C to 60°C) NEMA 4 and NEMA 6P Enclosure (IP67) when used with appropriate watertight conduit fittings. Indoor or Outdoor Use (Not for use in hazardous locations. See bulletin no. 5400694 PIVS-U-EX for hazardous locations.) Conduit Entrances: Two knockouts for 1/2" conduit provided. Service Use: Automatic Sprinkler NFPA-1 3 One or two family dwelling NFPA-1 3D Residential occupancy up to four stories NFPA-1 3R National Fire Alarm Code NFPA-72 a special tool to remove. The tool is furnished with each device and should be left with the building owner or responsible party. Replace- ment or additional cover screws and hex keys are available. See ordering information. OPTIONAL COVER TAMPER SWITCH: A field installable cover tamper switch is available as an option which maybe used to indicate removal of the cover. See ordering information. TESTING: The PCVS and its associated protective monitoring system should be tested in accordance with applicable NFPA codes and standards and/or the authority having jurisdiction (manufacturer recommends quarterly or more frequently). ORDERING INFORMATION MODEL DESCRIPTION STOCK NO. PCVS-1 Potter Control Valve Switch (single switch) 1010107 PCVS-2 Potter Control Valve Switch (double switch) 1010207 -- Cover Screw 5490344 -- Hex Key for Cover Screws and Installation Adjustments 5250062 PBK-S Pratt Butterfly Valve Kit - Up to 12" (300mm) 0090133 PBK-L Pratt Butterfly Valve Kit - 14" (355mm) and Up 0090132 PVK Pratt Valve Kit 1000060 -- Optional Cover Tamper Switch Kit 0090131 KBK Kennedy Butterfly Valve Kit 0090143 For pressure reducer type valve installation kits (if required) contact valve manufacturer. Potter Electric Signal Company 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833° www.pottersignal.com PRINTED IN USA MKT. #8820001 - REV T PAGE 1 OF 4 12/01 VALVE 0-7-- POTTER The Symbol of Protection SUPERVISORY SWITCH FIG. I DIMENSIONS FIG. 2 PARTS (1 - 4.75 - 2,1cm) -3.62 - (9,2cm) -2.25- (5,7cm) -2.00- (5,0cm) 300 (7,6crr) (13, !cm) I .75 I .85 8.20 I (1,9cm) L22cm 1.12 (20(20,8m)Lj oj [J 3 .0cm 1,20 ( ROD RETRACTED ) (2,2crR I ARID BREACAWAR 1,12 (0,30cm) SECIIARI REKOAGO I -1.56- I 3.12 (4,0cm) II (7,9cm) II I II II II ROO EXTENDED U Dwc. #980-I Li KNOCKOUTS FOR ELECTRICAL CONNECTIONS (WHITE) (RED (BLACK GROUND SCREW TRIP ROD LOCKING SCREW CI HEAD SCREW LE NUT TYPICAL INSTALLATIONS ON POST INDICATOR VALVE HOUSINGS (SEE FIGS. 3 THRU 6) Refer to Fig. 2 for the location of parts described in the following instructions. NOTE: If the sprinkler system is in service the owner or authorized representative should be notified, before any work is done on the system, that the valve controlling the water supply to the system may be closed for periods of time during the installation and testing of this device, resulting in all or portions of the system being inoperative during these periods. If the system is not in service and valve is closed, be sure that opening the valve will not allow any unwanted water flow due to openings in the system, such as heads off, broken or incomplete piping, etc. Position the valve to fully open ('OPEN" should appear in the window of the housing). Partially close the valve while observing the direction that the target assembly moves. Reopen the valve. If the valve housing is predrilled with a 1/2" NPT for installation of a monitoring switch, remove the 1/2' plug and fully open the valve. Make sure that OPEN" appears in the window of the housing. GO TO STEP NO. 6. Remove the head and target assembly (consultation with valve manufac- turer is recommended). If the target assembly moved up as the valve was closed, measure the distance from the bottom of the head to the lower part of the target assembly that will contact the trip rod of the PCVS (see Fig. 3). This is usually a plate or bar on the target assembly, on a side adjacent to the "OPEN/SHUT" plates. Subtract 1/8" from the measurement. If the target moved down as the valve was closed, measure the distance from the bottom of the head to the upper portion of the target assembly that will contact the trip rod of the PCVS (see Fig. 4). Add 1/8" (3,2mm) to this measurement. Mark the housing at the proper location. Using a 23/32" (18,2mm) drill bit, drill and then tap a 1/2" NPT in the housing on the side that coincides with the portion of the target assembly that will engage the trip rod of the PCVS. Replace the head and target assembly. Loosen the socket head screw that holds the nipple in the PCVS and remove the nipple. Screw the locknut that is provided onto the nipple. Screw the nipple into the 1/2" NPT hole in the valve housing - hand tighten. Tighten the locknut against the valve housing to secure the nipple firmly in place. Insert a scale or probe thru the nipple to measure the distance from the PRINTED IN USA MKT. #8820001 - REV T PAGE 2 OF 4 12/01 open end of the nipple to the target assembly. Subtract 112" (12,5mm) from this measurement. NOTE: In some cases, it may be necessary to attach an angle bracket to the target assembly to engage the PCVS trip rod. Using the special tool provided,, loosen the two cover screws and remove the cover from the PCVS. Loosen the locking screw that holds the trip rod in place and adjust the rod length, from the end of the collar to the end of the rod, using the dimension determined in Step 9. Tighten the locking screw to hold the rod in place. NOTE: If trip rod length is excessive, loosen the locking screw and remove the trip rod from the trip lever. Using pliers, break off the one (1) inch long notched section (see Fig. 7). Reinstall trip rod and repeat Step 11 procedure. Partially close the valve (3 to 4 revolutions of the handle/hand wheel). Slide the PCVS unit as far as pDssible onto the nipple, observing which direction the rod will move when the valve is closed. Orient the device to actuate the switches when the valve is open. Tighten the socket head screw in the collar. Carefully open the valve to the fully open position. As the target moves to the open position it should engage the trip rod and actuate the switch(es). There should be am nimum overtravel of 1/2 revolution of the handle/hand wheel after the switch(es) actuate (a continuity meter connected to each set of contacts is one method that could be used to determine this). Slowly close the valve. The switch must operate during the first two revolutions of the handle/hand wheel or during 1/5 of the travel distance of the valve control apparatus from its normal condition. NOTE: Small adjustments of the target position may be necessary (consultation with valve manufacturer is recommended). Complete the required electrical wiring, connections and tests. The valve should be operated through the entire cycle of fully closed and fully open to determine the integrity of the PCVS installation and the signaling system. Check that all electrical and mechanical connections are secure. When the installation and testing are complete, return valve to its proper position. Alternative installation forotherpost indicatorvalve housing shown in Fig. 5 and 6. FIG. 4 FIG. 5 METAL PLATE REPLACES GLASS STEEL TAMPER TRIPPING UT SWITCH BLOCK - REPLACES OPEN OPEN MARKER TARGET MOVES DOWN AS SHUT VALVE MARKER TARGET ASSEMBLY IS SHUT TARGET MOVES UP AS VALVE IS SHUT DWG. #960-30 FIG. 6 LOCKNUT Fni FLEXIBLE ii 3/8" CONDUIT (28.9crr) HOOD MOVES DOWN AS VALVE IS SHUT FIG. 3 DWG. 980-13 (E)POTTER CONTROL VALVE The Symbol of Protection SUPERVISORY SWITCH '—"-S Notes: Subject to the approval of the "authority having jurisdiction" the alternate method of installation shown in Fig. 5 may be used. In this method, one of the glass windows of the housing is replaced with a 1/4 thick metal plate that is cut to fit in place of the glass and drilled and tapped to receive the 1/2" NPT pipe nipple. In some cases it may be necessary to attach an angle bracket to the target assembly to engage the PCVS trip rod. If the target is stationary and a hood arrangement is used, such as is shown in Fig. 6, the hood must be drilled with a 23/32' drill and tapped with a 1/2' NPT. The center line of this hole should be 1/8' below the portion of target assembly that strikes the PCVS trip rod. The 11 3/8" dimension shown is for a Clow Valve. Flexible conduit must be used for this type of installation. TYPICAL INSTALLATION ON A BUTTERFLY VALVE (SEE FIGS. 9 AND 10) Refer to Fig. 2 for location of parts described in the following instructions: against the nipple. Remove the 1/2" NPT plug from the gear operator case. NOTE: In some cases it maybe necessary to remove the gearbox cover Loosen the setscrew that holds the nipple in the PCVS and remove the nipple. to ensure correct operation (consultation with the valve manufacturer is B3. Screw the locknut that is provided onto the nipple. recommended). 64. Screwthe nipple intothel/2" NPT hole ln the gear operator- hand tighten. 69. Carefully open the valve to its full open position, as the boss on the gear Tighten the locknut against the case, to secure the nipple firmly in place. hub moves to the open position it must engage the PCVS trip rod and actuate Partially close the valve (3 or 4 revolutions of the hand wheel or crank). the switch(es). There should be a minimum overtravel or revolution of the crank or hand wheel after the switch(es) actuate (a Using the special tool provided, loosen the two cover screws and remove continuity meter connected to each set of contacts is one method that the cover from the PCVS. could be used to determine this). Loosen the locking screw that holds the trip rod in place. Estimate trip rod NOTE: Slight adjustment of gear stops may be necessary to prevent length required and extend slightly past that point. Slide the PCVS unit overtravel of the trip rod (consultation with valve manufacture is recom- as far as possible onto the nipple, observing which direction the rod will mended). move when the valve is closed. Orient the device to actuate switches 810. Carefully close the valve. The switch(es) must operate during the first two when valve is open. revolutions of the crank or hand wheel or during 1/5 of the travel distance NOTE: If trip rod length is excessive, loosen the locking screw and of the valve control apparatus from its normal condition. remove the trip rod from the trip lever. Using pliers, break off the one (1) Bil. Complete the required electrical wiring, connections and tests. The valve inch long notched section (see Fig. 7). Reinstall trip rod and repeat Step should be operated through the entire cycle of fully closed and fully open 87 procedure. to determine the integrity of the PCVS installation and signaling system. 68. Remove device from nipple and withdraw trip rod 1/32" (0,80mm) (this Check that all electrical and mechanical connections are secure. dimension is important). Tighten the locking screw to hold the rod in place. Re-install the device on the nipple. Tighten the screw in the collar B12. When the installation and testing are complete, return valve to its proper position. FIG. 7 BREAKING EXCESSIVE ROD LENGTH SWITCH TERMINAL CONNECTIONS CLAMPING PLATE TERMINAL FIG. 8 I ii , ou T6 ONG " DWG. 923-3 CAUTION: An uninsulated section of a single con- ductor should not be looped around the terminal and serve as two separate connections. The wire must be sev- ered, thereby providing supervision of the connection in the event that the wire becomes dislodged from under the terminal. PRINTED IN USA MKT. #8820001 -REV T PAGE 3 OF 4 12/01 CF)) P OT T E The Symbol of Protection PCVS-1, -2 CONTROL VALVE SUPERVISORY SWITCH ITT GRINNELL/KENNEDY INDICATING BUTTERFLY VALVE FIG. 8 F1 VALVE PARTIALLY CLOSED VALVE OPEN DWG, #980-6 PBK - PRATT IBV BUTTERFLY VALVE KIT FIG. 12 LOC Bol BRACKET AND LOCK NUTS SUPPLIED WITH P8K MOUNTING KIT 0 MODEL PBK-L Stock No. 0090132 (MDT-4S Actuator) MODEL PBK-M Stock No. 0090146 (MDT-3S Actuator) MODEL P6K-S Stock No. 0090133 (MDT-25 Actuator) Pratt Butterfly Valve Kit as used to mount a PCVS on a Pratt Model lBV Valve. Kits contain: Bracket, nuts and instructions Note: This application is subject to the approval of the authority having jurisdiction. PRINTED IN USA DRESSER INDICATING BUTTERFLY VALVE FIG. 10 1/2' DWG. #980-7 (l3nm) PVK - PRATT PIVA POST INDICATOR VALVE KIT (STOCK NO. 1000060) FIG. 13 MACHINE SCREW DWG. #91 Pratt Valve Kit as used to mount a PCVS on a Pratt Model PlVA Valve. Kit contains: Instructions, template, screw and nut. Note: This application is subject to the approval of the authority having jurisdiction. MKT. #8820001 - REV T 12/01 TYPICAL PRESSURE REDUCER TYPE VALVE INSTALLATION FIG. 11 COLLAR LOCKNUT NIPPLE PCVS 1/16"(I,6mr) MIN GAP- DWG. #980-10 This figure shows the Model PCVS mounted on the valve yoke, with a bracket supplied by the valve manufacturer, to supervise a pressure reducer type valve. Note: This application is subject to the approval of the authority having jurisdiction. TYPICAL ELECTRICAL CONNECTIONS Please Note: This device should be wired in accordance with the applicable parts of the National Electrical Code, all state and local codes, applicable NFPA Standards and the requirements of the authority having jurisdiction. FIG. 14 cuIr N.O. TO POWER FOR CO" N.C. Ü INDICATING N DICAT IN C DESCE INDICATING OEVCE TO SUPEISORY CIRCUIT N.O.END OF CONTROL PANEL COM OF LINE I NC K' R ESISTOR DWG. #980- 12 Contacts shown in normal (valve open) condition. TYPICAL SWITCH ACTION OPEN VALVE POSITION CLOSED VALVE POSITION COM COM. SW #1 SW #1 iJN C I1N.C. com COM. SW #2 SW #2 DWG. #980-11 Switches Shown in Valve Open Position PAGE 4 OF 4 CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION . OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7770-0328:0010 Page 1 of I CATEGORY: 7770 -- VALVES/SWITCHES LISTEE: Potter Electric Signal Co1609 Park 370 Place, Hazelwood, MO 63042 Contact: Bill Witherspoon (314) 595-6900 Fax (314) 595-6999 Email: BiIlWpottersignal.com DESIGN: Supervisory switches listed below to monitor pressure, OS&Y, gate, globe/gate, PlV, tank temperature or water level valves. Refer to listee's data sheet for detailed product description and operational considerations. HLS-B WLS-W PS-120A OSYSU-2 PTS-B OSYSU-1 PIVS-B US-S WLS PTS-C *RBVS WLS-S PS-40A OSYS-B PMS GVS PCVS-1 rrS-W PCVS-2 PS4O PS12O RATING: INSTALLATION MARKING: APPROVAL: NOTE: n accordance with listee's printed instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. Listee's name, model designation and FM or UL label. Listed as sprinkler system supervisory switches. Formerly 7738-0328:010 *Rev 5-17-2007 jw This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct v' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division irtA rtii fl t *] Applications: Wiring of Fire-Protective Signaling Circuits. Sunlight Resistant; Code Restrictions OK for use with all Power-Limited Circuits except those in Risers and Plenums. Features: Available in 500 Ft. or 1000 Ft. Tangle-Free Boxes, or Spools. Sequential Footage Markings. Construction: Copper Conductors, Polypropylene Insulation, Polyvinyl -Chloride Jacket. Standard Jacket Color: Red or White, Conductor Color Code Chart 4. FIRE ALARM JACKETED UI'o-,HW Dl-rt 7 C . AWG 4/COND. 22 4,--SOL. SQL NOM. O.D. .122 NOM. CAP. PF/FT 15 LISTINGS UL, FPL AVG. W1. PER MFT 15 (LBS.) PART# 4101* 22 6 SOL. .144 15 UL, FPL 19 (LBS.) 4102 22 8 SQL. .156 15 . - UL, FPL 24 (LBS.) 4103 22 10 SQL. .182. 15 UL, FPL 31 (LBS.) 4104 22 12 SQL. .188 15 UL, FPL . 37 (LBS.) 4105 18 2 SOL. .134 20 UL, FPL 17 (LBS.) 4106 18 4 SOL. .170 20 UL, FPL 29 (LBS.) 4107* 18 6 SOL. .1.9220 UL, FPL -- 41 (LBS.) 4108+ 18 8 SOL. .208 20 UL, FPL 52 (LBS.) 4109+ 18 10 SQL. . .244 20 UL, FPL 68 (LBS.) 4110+ . 16 2 SQL. .15420 UL. FPL 24(LBS.) _4111 164 SQL .18020 UL, FPL -43(LBS.)_____1____4112+ 142__SOL. .18222UL,FPL 35(LBS.)____.4113+ 14 __4_____ SOL, .21422 UL, FPL 64 LBS.) 4114+ 12 2_ SOL. .214 22 UL, FPL 52 (LBS.) 4115+ *Not Twisted +Spools Only rtAi iPI _1(IiiUIiT1 ii *I.• Iiiir1 Applications: Wiring for Outdoor or Underground. Sunlight Resistant. Code Restrictions: OK for use with all Power-Limited Circuits except those in Risers and Plenums, but intended for Outdoor or Underground Use. Features: Available in 500 Ft. or 1000 Ft. Spools. Sequential Footage Markings. Construction: Stranded Copper Conductors, PVC Insulation, High Molecular Weight PVC Jacket Color: Black. Conductor Color Code Chart 4. . FIRE ALARM JACKETED UNSHIELDED, flI000TOIJPiAI. "5 C NOM. NOM. CAP. AVG. WT. AWG #/CQND. STIR O.D. PF/FT LISTINGS PER MFT PART# 182 STR. 26019 FPL, CL2 19(LBS.)4156 184 STR. .29519 FPL,CL2 15(LBS.)4157* 18 6 SIR. .345 19 FPL, CL2 24 (LBS.) . 4158. 16 _2 ____SIR. .282_. _21 FPL,CL2 31(LBS.) 4151 142 __STR. 731023FPLCL2 37(LBS.) _4153 144SIR. _.355 23FPL,CL2 17 (LBS) 4154 Not Twisted 20 Genesis Series Cable toll free 800.222.0060 phone 262.947.0720 fax 262.947.0724 41 V CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM 6 LISTING SERVICE LISTING No. 7161-1487:0100 Page 1 of 1 CATEGORY: 7161 -- CABLES-FIRE PROTECTIVE SIGNALING LISTEE: GENESIS CABLE SYSTEM7701 95TH Street, Pleasant Prairie, WI 53158 Contact: Orville Allen (262) 947-0720 Fax (262) 947-0724 Email: orvillegenesiscable.com DESIGN: Model FPL, FPLP and FPLR power limited fire protective signaling cable. Conductors: In accordance with the standard Insulation: GPT-150, Foam PP, HDPE or LDPE Assembly: 2 to 12 insulated conductors Shield (Optional): Aluminum polyester tape shield Braid (Optional): Metal braid over cable core Jacket: PVC compound Gitto/Global Corp., Grade GA-91-84, GPT-45, GA5033, GA93016 Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances, NEC Article 760, and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, Type 'FPL" and UL label. APPROVAL: Listed as power-limited fire protective signaling cables. Rev. 06-18-2003 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2015 Listing Expires June 30, 2016 Authorized By: JAMES PARSEGIAN, Program Coordinator Fire Engineering Division NP SERIES - NPI8-12 Reliability is your Security :UtiIizing the latest advance design Oxygen Recombination Technology, Yuasa have applied their 80 years experience in the lead acid battery field to produce the optimum design of Sealed Lead Acid batteries. FEATURES Superb recovery from deep discharge. Electrolyte suspension system. Gas Recombination. Multipurpose: Float or Cyclic use. Usable in any orientation. .. Superior energy density. Lead calcium grids for extended life. Manufactured World wide. Application specific designs. Technical Features il Sealed Construction Yuasa's unique construction and sealing technique ensures no electrolyte leakage from case or terminals. Electrolyte Suspension System All NP batteries utilize Yuasa's unique electrolyte suspension system incorporating a microfine glass mat to retain the maximum amount of electrolyte in the cells. The electrolyte is retained in the separator material and there is no free electrolyte to escape from the cells. No gels or other contaminants are added. Control of Gas Generation The design of Yuasa's NP batteries incorporates the very latest oxygen recombination technology to effectively control the generation of gas during normal use. Low Maintenance Operation Due to the perfectly sealed construction and the recombination of gasses within the cell, the battery is almost maintenance free. .Trmin*lc Bolt fastened terminal E - IN(] I = .472 12.00 t i-i .453 11.50 J- 33 11-00 -1'l-- I: [11 .079 2.00 Terminals NP batteries are manufactured using a range of terminals which vary in size and type. Please refer to details as shown. Operation in any Orientation The combination of sealed construction and Yuasa's unique electrolyte suspension system allows operation in any orientation, with no loss of performance or fear of electrolyte leakage. Valve Regulated Design The batteries are equipped with a simple, safe, low pressure venting system which releases excess gas and automatically reseals should there be a build up of gas within the battery due to severe overcharge. Note. On no account should the battery be charged in a sealed container. General Specifications Nominal Capacity (Ah) NPI8-12 20hrto 1.75vpc3011C 17.2 lOhrto 1.75vpc20°C 16 5hrto 1.70vpc200C 14.5 lhrto 1.60vpc200C 10.3 Voltage 12 Energy Density (Mi.L.201u) 94 Speafic Energy (\M1.kg.20hr) 38 Int. Resistance (m.Ohms) 11 Maximum discharge (A) 112 Short Circuit current (A) 500 Dimensions (mm) Length 180 Width 76 Height overall 167 Weight (Kg) 6.2 Terminal E Layout 2 Terminal Torque Nm - 2H. 20 _ - llFEtYFAF)l FLOAT SERVICE LIFE NP RANGE - IVIlOL. I_Cl/SO V/COOING VC/0C/ 0VVPC IAH%} &OI0lThNiF0h000 0'OC SrTO 0/0) 120 p NP SERIES — NPI8-12 Lead Calcium Grids The heavy duty lead calcium alloy grids provide an extra margin of performance and life in both cyclic and float applications and give unparalleled recovery from deep discharge. Long Cycle Service Life Depending upon the average depth of discharge, over a thousand discharge/charge cycles can be expected. Float Service Life The expected service life is five years in float standby applications. Separators The use of the special separator material provides a very efficient insulation between plates preventing inter-plate short circuits and prohibiting the shedding of active materials. CYCLIC RECHARGE REGIME - - Gil CEVqG . LC V V V 10 'S /Y - - / 1 0 0 0 NP DISCHARGE CHARACTERISTICS CURVES AT 25°C (77°F) IVI V) SOY C .l).000coroyo YYY.V .,VOS,00 FOR 100 fo0 6V B0TE1W eArTER" 1a.O - --\-'-- -— VII •\ V\ 100..15.0 . -- j I1iIIi T\WT7177 Yuasa Battery Inc. 2901 Montrose Ave Laureldale, PA 19605 ti II www.yuasabatteries.com U Y UASA Registered number 1548820 Cat.Noi NP7-12 January o8 I K) - Long shelf Life The extremely low self discharge rate allows the battery to be stored for extended periods up to one year at normal ambient temperatures with no permanent loss of capacity. Operating Temperature Range The batteries can be used over a broad temperature range permitting considerable flexibility in system design and location. Charge - 15°C to 50°C Discharge - 20°C to 60°C Storage - 20°C to 50°C (fully charged battery) SELF DISCHARGE CHARACTERISTICS - 05 13201 S K----_ r g G , C VI S ••-) 51/0.000 lMI: I.NOVI0 - FLOAT CHARGE CHARACTERISTICS 01 a' CA-0'7VPCCONV°TASTVU TI_C C )0I AT 0C 08C) iel 7." .00G05 /15 / \ V/tO' 01170 C VY 0 0, 11.0 LIV 5.51 0 0 4 10 2 11 10 In .OIIVANV. 1IYL IVIVOUVI I TYPICAL DISCHARGE CHARAC- TERISTICS NP RANGE CYCLE SERVICE LIFE IN RELATION TO DEPTH OF DISCHARGE TESTING 0050111005 DTSC1IOIVCIF ousr,F.oT (VI IC IVr1V, IV 1.70/OIL CH.40CIS1I /3005510Cbb Or.p.. CVAIV1VINIV VCXCSV/ '?F. OF IIIIV01000V100 tI_poOr? VAr?.) *5114001 I ,-/PEIVAIV.I4i-- V/C IC 111/ CCI- IC) ?OG1 ---'_-----_--- 001) 1)00 05 0151.11 01101. 50/1011000 CYCLES Distributed by State Of California CONTRACTORS STATE LICENSE BOARD ACTIVE LICENSE A.T.- 0 495756 CORP S C N SECURITY COMMUNICATION NETWORK INC DBA LAKEWOOD ALARM C-7C1O UF2 07/31/2016 wcsIb.ca.gOv It 41 U Applicant ID No: 1019563-000 Service Center No: 3 Expires: 2016-03-31 CERTIFICATE OF COMPLIANCE THIS IS TO CERTIFY that the Alarm Service Company indicated below is included by Underwriters Laboratories Inc. (UL) in its Product Directories as eligible to use the UL Listing Mark in connection with Certificated Alarm Systems. The only evidence of compliance with UL's requirements is the issuance of a UL Certificate for the Alarm System and the Certificate is current under UL's Certificate Verification Service. This Certificate does not apply in any way to the communication channel between the protected property and any facility that monitors signals from the protected property unless the use of a UL listed or Classified Alarm Transport Company is specified on the Certificate. Listed Service From: ANAHEIM, CA Alarm Service Company: (1019563-000) Service Center: (1019563-000) SECURITY PARTNERS L L C SECURITY PARTNERS L L C SUITE 401 SUITE 401 401 W LINCOLN AVE 401 W LINCOLN AVE ANAHEIM CA 92805-2950 ANAHEIM CA 92805-2950 The Alarm Service Company is Listed in the following Certificate Service Categories: File - Vol No. CCN Listing Category S26911 UUFX [Signal and Fire Alarm Equipment and Services] (Protective Signaling Services) Central Station ***THIS CERTIFICATE EXPIRES ON 20160331*** "LOOK FOR THE UL ALARM SYSTEM CERTIFICATE" - (.r2jLUTh7 SYSTEM RECORD OF COMPLETION rc This form is to be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this form as needed to provide a more complete and/or clear record. 44 Insert N/A in all unused lines. Attach additional sheets, data, or calculations as necessary to provide a complete record. Form Completion Date: 10106/15 Supplemental Pages Attached: 0 PROPERTY INFORMATION Name of property: BURKE CARLSBAD BUSINESS CENTER Address: 3200 LIONSHEAD AVE, CARLSBAD, CA Description of property: OFFICE/WAREHOUSE SHELL BUILDING Name of property representative: BURKE REAL ESTATE GROUP Address: 260 E BAKER AVE., STE 100, COSTA MESA, CA 92626 Phone: 714-824-5014 Fax: E-mail: INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION Installation contractor: SCN SECURITY COMMUNICATION NETWORK, INC Address: 470 E HARRISON ST, CORONA, CA 92879 Phone: 951-549-8200 Fax: 951-549-8211 E-mail: Service organization: SCN SECURITY COMMUNICATION NETWORK, INC Address: 470 E HARRISON ST, CORONA, CA 92879 Phone: 951-549-8200 Fax: 951-549-8211 E-mail: resting organization: SCN SECURITY COMMUNICATION NETWORK, INC Address: 470 E HARRISON ST, CORONA, CA 92879 Phone: 951-549-8200 Fax: 951-549-8211 E-mail: Effective date for test and inspection contract: 08/24/15 Monitoring organization: SECURITY PARTNERS, LLC Address: 401 W LINCOLN AVE, STE 401, ANAHEIM, CA 92805 Phone: 800-647-2758 Fax: E-mail: Account number: 52534 Phone line 1: N/A Phone line 2: N/A Means of transmission: CELLULAR Entity to which alarms are retransmitted: CARLSBAD FD Phone: (858)756-1126 DOCUMENTATION On-site location of the required record documents and site-specific software: OFFICE DESCRIPTION OF SYSTEM OR SERVICE This is a: 0 New system LI Modification to existing system Permit number: FA1 50064 NFPA 72 edition: 2013 4.1 Control Unit Manufacturer: DMP 4.2 Software and Firmware Firmware revision number: N/A 4.3 Alarm Verification Number of devices subject to alarm verification: Model number: XR1 50 This system does not incorporate alarm verification. Alarm verification set for seconds Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sate or distribution. (p, I of I, 8 SYSTEM RECORD OF COMPLETION (continued) 5. SYSTEM POWER 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: 120VAC Overcurrent protection: Type: BREAKER Branch circuit disconnecting means location: ELEC RM Control panel amps Amps: 20 Number: 20 5.1.2 Secondary Power Type of secondary power: BATTERIES Location, if remote from the plant: Calculated capacity of secondary power to drive the system: In standby mode (hours): 24 5.2 Control Unit Z This system does not have power extender panels LI Power extender panels are listed on supplementary sheet A (I(IIITS MJfl PATHWAV In alarm mode (minutes): 5 Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line 1 B 0 Device Power 0 N/A N/A Initiating Device 12 B 0 Notification Appliance 0 N/A N/A Other (specify): 7. REMOTE ANNUNCIATORS Location LCD I LOBBY R IMlTlTlN( flFVICES Type Quantity Addressable or Conventional Alarm or Supervisory Sensing Technology Manual Pull Stations 1 CONVENTIONAL ALARM Smoke Detectors 1 CONVENTIONAL ALARM PHOTOELECTRIC Duct Smoke Detectors 4 CONVENTIONAL SUPERVISORY PHOTOELECTRIC Heat Detectors 0 Gas Detectors 0 Waterfiow Switches 2 CONVENTIONAL ALARM Tamper Switches 4 CONVENTIONAL SUPERVISORY Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution, p, 2 c SYSTEM RECORD OF COMPLETION (continued) NOTIFICATION APPLIANCES Type Quantity Description Audible 0 Visible 0 Combination Audible and Visible 0 SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Open Door Releasing Devices N/A 1-IVAC Shutdown N/A Fire/Smoke Dampers N/A Door Unlocking N/A Elevator Recall N/A Elevator Shunt Trip N/A INTERCONNECTED SYSTEMS This system does not have interconnected systems. R Interconnected systems are listed on supplementary sheet 0 CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system a 1ecifi 'd 6 in has been installed according to all NFPA standards cited herein. Signed: Printed name: CHAD HUNTER Organization: SCN SECURITY Title: LEAD TECHNICIAN 12.2 System Operational Test This system as ecified herein has tes{ed according to all NFPA standards cited herein. Signe -> OA n^y& 0JA )19iJV1L..rrinted name: JEANNE WIGGINS Organiz n: CNSECURITY Title: SIR PROJECT ENGINEER 12.3 Acceptance Test Date and time of acceptance test: 10 Installing contractor representative: JEANNE WIGGINS Testing contractor representative: JEANNE WIGGINS Property representative: X - AHJ representative: X %7/47 CO Date: 10/13/15 Phone: 951-549-8200 Date: 10/19/15 Phone: 951-549-8200 Copyright © 2012 National Fire Protection Association. This form may be copied for individual use other than for resale. It may not be copied for commercial sale or distribution. <p. 3 ol