HomeMy WebLinkAbout2525 EL CAMINO REAL; 119; FPC2018-0205; PermitPERMIT REPORT
(~7 ity of
Carlsbad
Print Date: 12/13/2021 Permit No: FPC2018-0205
Job Address: 2525 EL CAMINO REAL, # 119, CARLSBAD, CA 92008-1206 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel if: 1563020900 Track if: Applied: 07/10/2018
Valuation: $82,648.27 Lot if: Issued: 07/19/2018
Occupancy Group: Project if: Finaled Close Out: 02/01/2021
ifof Dwelling Units: Plan if:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check if: Inspector:
Plan Check if: Final Inspection:
Project Title:
Description: SOHA LIVING -SPRINKLER TI (23 HEADS)
FPContractor:
BRADSHAW ENGINEERING CORP
8645 ARGENT ST
SANTEE, CA 92071-4179
(619) 448-4300
FEE AMOUNT
FIRE NFPA 13 or 13R System 7- 100 heads $536.00
Total Fees: $536.00 Total Payments To Date: $536.00 Balance Due: $0.00
Fire Department Page _1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
FFc20 -O2-o5
Page 1 of 7
MIRAGE® STANDARD AND
QR CONCEALED PENDENT N I 1(1 NG i : ii u SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
DESCRIPTION
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462
and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for
installation on concealed pipe systems where the appearance of a smooth ceiling is
desired.
The sprinkler is pre-assembled with a threaded adapter for installation with a low-
profile cover assembly that provides up to 1/2 (12.7 mm) of vertical adjustment. The
two-piece design allows installation and testing of the sprinkler prior to installation of
the cover plate. The 'push-on", "thread-off' design of the concealed cover plate assem-
bly allows easy installation of the cover plate after the system has been tested and the
ceiling finish has been applied. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out of
service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been
investigated for installation in corrosive atmospheres and is cULus Listed as corrosion
resistant as indicated in the Approval Charts. The ENT finish is only available for the
sprinkler assembly, the cover plate is not plated.
LISTINGS AND APPROVALS
cULus Listed: Category VNIV
FM Approval: Class 2015
NYC Approved: MEA 89-92-E, Volume 32
VdS Approved: Certificate G4080021
LPCB Approved: Ref. No. 096e112
CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032
CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF)
Refer to Approval Chart 1 Design Criteria for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on
page for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2006.
Minimum Operating Pressure: 7 psi (0.5 bar)*
Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum
7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by
locating "250" stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp.
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" (15 mm) NPT
Nominal K-Factor: 5.6 U.S. (80.6 metrict)
Glass-bulb fluid temperature rated to -65°F (-55°C)
Patents Pending .cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
tMetric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass UNS-C84400
Deflector: Copper UNS-C19500 for Sprinkler VK462
Phosphor Bronze UNS-051000 for Sprinkler VK463
Deflector Pins: Stainless Steel Alloy
Bulb: Glass, nominal 3 mm diameter
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Button: Brass UNS-C36000
Screws: 18-8 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Form No. F_103005 18.04.12 Rev 18.1 Replaces Form No. F_103005 Rev 17.1
(added stainless steel cover plates)
Page 2 of 7
MIRAGE® STANDARD AND J I K] 4 QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Yoke: Phosphor Bronze UNS-051000
Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating
Cover Assembly Materials:
Cover: Copper UNS-C11000 or Stainless Steel UNS-530400
Base: Brass UNS-C26000 or UNS-C26800
Springs: Nickel Alloy
Solder: Eutectic
Ordering Information: (Also refer to the current Viking price list.)
Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:
Sprinkler: Base Part No. VK462 - 13503A for Brass finish and 13503JN for ENT finish. VK463 - HP Base Part No. 13667A
Specify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:
Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E
For example, sprinkler VK463 with a 155 °F (68 °C) temperature rating = 13667AB.
Standard Cover Plate Assembly: Base Part No. 13504 (2-3/4" diameter), Base Part No. 13642 (3-5/16" diameter), or Base Part
No. 15394 (square cover plate, 3-5/16")
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part number:
Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B,
Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/l, Painted Black = M-/B
Temperature Suffix: 135 °F (57 °C) UL (139 °F (59 °C) FM and LPCB) =A, 165 °F (74 °C) = C
For example, cover 13504 with a Polished Chrome finish and a 165 °F (74 'C) temperature rating = 13504FC.
Stainless Steel Cover Plates (not availbie with any finish or paint): Base Part No. 21876 (2-3/4" diameter) or Base Part No.
21875 (3-5/16" diameter).
Temperature Suffix: 135°F (57 °C) UL (139°F (59 °C) FM and LPCB) =A, 165°F (74 °C) = C
For example, cover 21876 with a 165 °F (74 °C) temperature rating = 21876C
NOTE: The cULus Listings for the square cover plate 15394 are for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval
Chart.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches**:
Heavy Duty Wrench Part No. 14047W/B (available since 2006), or
Head Cabinet Wrench Part No. 14031*** (available since 2006)
Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover
(available since 2007)
**Requires a %" ratchet (not available from Viking). ***Optional for removal of the protective cap. Ideal for sprinkler cabinets.
Sprinkler Cabinet: Part No. 01731A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches.
Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter,
releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector,
forming a uniform spray pattern to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking
Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
Form No. F_103005 18.04.12 Rev 18.1
Page 3 of 7
MIRAGE® STANDARD AND
l:IIEuyM QR CONCEALED PENDENT K11 SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
TABLE 1. LABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES
Sprinkler Sprinkler MaxImri
Nominal Ambit Cover Plate Temperature Rating of Cover Large Cover Square Cover
Temperature Temperature CeIli Base Part Assembly (Required) Plate Base Part Plate Base Part Bulb Cole
Classification Rating, Tamperaür&
Number" Number3 Number3
Ordinary 155 °F (68° C) 100 °F (38 °C) 135°F (57 °C) cULus 13504 or 218761 13642 or 218755 15394 Red 139 °F (59 °C) FM and LPCB
Intermediate 175 °F (79° C) 150 °F (65° C) 165 °F (74 °C) 13504 or 21876 13642 or 21875 15394 1 Yellow
Intermediate 200 °F (93° C) 150 °F (65° C) 165 °F (74 °C) 13504 or 21876 13642 or 2187551 15394 1 Green
Cover Plate Finishes': Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted
Ivory, or Painted Black
Sprinkler Finishes: Brass and ENT
Corrosion Resistant Coatings4: ENT
Footnotes
1 The sprinkler temperature rating is stamped on the sprinkler deflector.
2 Based on NFPA-1 3. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-
ible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including
the waterway, but the Belleville spring is exposed.
Stainless Steel versions are not available with any finishes or paint.
CUSO
--
.,., I, /
0 I— 0
laf
All custom color painted cover plates will have an
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 1: Identification of Custom Paint for Concealed Covers
)
I
3-5/16" (84 mm)
Figure 2: Square Cover Assembly 15394
Form No. F103005 18.04.12 Rev 18.1
Page 4 of 7
r fl fl/1 P [17 : MIRAGE® STANDARD AND
I:II['L'iv_____ QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart I (UL) -
Mirage Concealed Pendent Sprinklers VK462 and VK463 AW1 Cow PWA, V°'øs KEY
Thread Nominal Maximum Listings and Approvals Sprinkler SIN Size K-Factor Water Working (Refer also to Design Criteria)
Inch mm U.S. metric2 cULus5 NYC VdS LPCB () Base Part No.' Pressure
Standard Response Applications
13503A VK462 1/2" -- 5.6 80.6 175 psi (12 bar) -- -- AY1,CZI AY1,BZ1 AY1,CZ16 --
19785A VK462 1/2" -- 5.6 80.6 175 psi (12 bar) -- -- - - -- AY2, CZ2
21356A VK462 -- 15 5.6 80.6 175 psi (12 bar) -- -- - -- -- AY2, CZ2
Quick Response Applications
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AVI, BX1,AV1, BX16 - - -- --
AV1, BX1, 13503JN1 VK462 1/2" 15 5.6 80.6 175 psi (12 bar) AV1, BX16 - - -- --
__________ AS3, BT3
13667A VK463 1/2" 15 5 80.6 1 250 psi (17.2 bar)' 1 AV1, BX1 AV1, BX16 -- -- -- --
Cover Plate Assembly Temperature Ratings',
S - 135 °F (57 °C) cover 21876 or 21875 (large diameter) Cover Plate Assembly Finishe&°
Sprinkler Temperature Ratings I - 165 °F (74 °C) cover 21876 or 21875 (large diameter) 1 - Polished Chrome, Brushed Chrome, Bright Brass,
A - 155 °F (68 °C) V -135°F (57 °C) cULus Listed cover 13504, 13642 (large diameter), Antique Brass, Brushed Brass, Brushed Copper,
B -175°F (79 °C) and 200°F (93 °C) or 15394 (square cover plate) Painted White, Painted Ivory, or Painted Black
C -200 °F (93 °C) X - 165 °F (74 °C) cover 13504, or 13642 (large diameter) 2 - Brass
Y - 135 °F (57 °C) cover 13504 LPCB Approved as 139 °F (59 °C) 3 - Stainless Steel
Z - 165 °F (74 °C) cover 13504
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
The Water Working Pressure rating is stamped on the deflector.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals.
Listed by Underwriter's Laboratories for use in the U.S. and Canada.
6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 32.
VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 +A1:2001 +A2:2004 +A3:2006, Certificate G4080021.
8 CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032.
The 135/139 °F cover has an orange label. The 165 °F (74 °C) cover has a white label.
IS Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
cULus Listed as corrosion resistant.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
Form No. F103005 18.04.12 Rev 18.1
Page 5 of 7
MIRAGE® STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
-1 SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
DESIGN CRITERIA - UL
(Also refer to Approval Char 1)
cULus Listing Requirements:
Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of
NFPA 13 for standard coverage pendent spray sprinklers as indicated below.
For hazard occupancies up to and including Ordinary Hazard, Group II.
Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m).
Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13.
Minimum distance from walls is 4 in. (102 mm).
Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured
perpendicular to the wall.
The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed.
NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only.
VdS Approval Requirements:
The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials.
This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight.
Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-
cies, except in 0H4.
NOTES: Due to the design the sprinkler type Domed-CCP' shall not be installed in false ceilings in which the false ceiling space is protected by a
water extinguishing system.
Due to the design the sprinkler type Domed-CCP' shall not be installed in false ceilings in which during a fire the pressure above the false ceiling
may be assumed to be higher than the pressure below the false ceiling.
The criterion for the dropping of the cover relevant for this approval is heat.
Steps of installation:
Prepare the sprinkler key.
Remove the plastic cover.
Hold the sprinkler with the wrench and fasten it.
Replace the plastic cover and do not remove until the cover is installed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_103005 18.04.12 Rev 18.1
Page 6 of 7
MIRAGE® STANDARD AND
QRCONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Approval Chart 2 (FM)
MIrageSthridard Response Concealed Pendent Sprinkler VK462 j AW14 Q,1w Pble FJ mm KEY
Maximum - FM Approvals' Sprinkler Base NPT Thread Size Nominal SIN Water Working Part No.' I I (Refer also to Design Criteria below.)
J
I Inch mm U.S. metric2 Pressure
13503A VK462 1/2" 15 5.6 80.6 175 psi (12 bar) Awl, BX1,AY2, BZ2
Cover Plate Assembly Temperature Ratings1'4 Cover Plate Assembly Finishes' Y - 139°F (59 "C) cover 21875 or 21876
Sprinkler Temperature Ratings z - 165 °F (74 °C) cover 21875 or 21876 - Polished Chrome, Brushed Chrome, Bright
A - 155 °F (68 °C) W - 139 °F (59 °C) cover 13504, 13642 (large diameter), or Brass, Antique Brass, Brushed Brass,
B - 175 °F (79 °C) and 200 °F (93 °C) 15394 (square cover plate) Brushed Copper, Painted white, Painted
X - 165 "F (74 °C) cover 13504, 13642 (large diameter), or Ivory, or Painted Black
15394 (square cover plate) 2 - Stainless Steel
Footnotes
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional
approvals.
The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label.
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information.
NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1.
DESIGN CRITERiA, EN
(AIsD re er to Approv~)l Chart 2 above.)
FM AeDroval Requirements:
Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM
Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data
Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic
design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F_103005 18.04.12 Rev 18.1
Page 7 of 7
MIRAGE® STANDARD AND
QR CONCEALED PENDENT
SPRINKLER VK462 AND HP
SPRINKLER VK463 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Sprinkler and
U.-
2-1/4" (57 mm) AdapterAssembly diameter opening Protective cap Sprinkler Wrench / required in the
removed Part No. 14047W/B** ceiling.
Use wrench
°''
Step 1: Step 2:
Carefully slide the Carefully press the wrench upward and
wrench sideways around turn slightly to ensure engagement with
the deflector and pins the sprinkler wrench flats.
NEVER install the sprinkler by applying the installation Sprinkler
wrench across the frame arms. DO NOT overtighten. wrench fla
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W/B** or 14031**. A leak tight seal
should be achieved by turning the sprinkler clockwise
I to 1-1/2 turns beyond finger tight.
Sprinkler
frame arms
Figure 3: Sprinkler Installation and Proper Wrench Usage
** A 1/2" ratchet is required (Not available from Viking)
-
1/2"(lS mm) NPT 2-9/16"(6Maximum ?
2.1/16(52_I? Minimum
F__rT
zo
'- E .
in -.
in-
U .
- - _ -
- -
----
-- j
-,-
- - 2-3/4" 170 mm) or 4
NOTE: Upon sprinkler activation, the deflector descends 3-5/16" (84 mm)
to approximately 13/16" (21 mm) below the sprinkler body.
Figure 4: Sprinkler Dimensions and Cover Installation
Form No. F_103005 18.04.12 Rev 18.1 Replaces Form No. F_103005 Rev 17.1
(added stainless steel cover plates)
.1'
Page 1 of 6
'\ KE
MICROMATIC® STANDARD
1 [\.•çfl l.l:II[...1u'YM RESPONSE UPRIGHT
L] SPRINKLER VKIOO (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
DESCRIPTION
The Viking Micromatic® Standard Response Upright VK100 Sprinkler is a small, ther-
mosensitive, glass-bulb spray sprinkler available in several different finishes and tem-
perature ratings to meet design requirements. The special Polyester and Electroless
Nickel PTFE (ENT) coatings can be used in decorative applications where colors are
desired. In addition, these coatings have been investigated for installation in corrosive
atmospheres and are listed/approved as corrosion resistant as indicated in the Approval
Charts. (Note: FM Global approves the ENT coating as corrosion resistant. FM Global has
no approval classification for Polyester coatings as corrosion resistant.)
Viking standard response sprinklers may be ordered and/or used as open sprinklers (glass
bulb and pip cap assembly removed) on deluge systems. Refer to Ordering Instructions.
LISTINGS AND APPROVALS
c®us cULus Listed: Category VNIV
FM Approved: Classes 2001, 2002, 2015, 2017, 2043
NOTE: Other International approval certificates are available upon request.
Refer to Approval Charts and Design Criteria for listing and approval requirements that must be followed.
TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)t
Maximum Working Pressure: 175 psi (12 bar) wwp
Factory tested hydrostatically to 500 psi (34.5 bar)
Thread size: 1/2" NFl, 15 mm BSP
Nominal K-Factor: 5.6 U.S. (80.6 metric**)
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
Overall Length: 2-3/8" (60 mm)
t cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE
Approvals ONLY is 5 psi (0.35 bar).
** Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Frame Casting: Brass UNS-C84400 or QM Brass
Deflector: Brass UNS-C23000 or Copper UNS-C19500
Bulb: Glass, nominal 5 mm diameter
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Screw: Brass UNS-C36000
Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
For Polyester Coated Sprinklers: Belleville Spring-Exposed
For ENT coated Sprinklers: Belleville Spring - Exposed, Screw and Pipcap - ENT plated.
ttNot for FM Approval.
Ordering Information: (Also refer to the current Viking price list.)
Order Micromatic® Standard Response Upright VK100 by first adding the appropriate suffix for the sprinkler finish and then the
appropriate suffix for the temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A, Chrome = F, White Polyester = M-M, Black Polyester = M-/B, Wax Coated = C, Wax Over Polyester = V-1W,
ENT = JN
Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B. 175 °F (79 °C) = D, 200 °F (93 °C) = E, 212 °F (100 °C) = M, 286 °F
(141 °C) = G, 360 °F (182 °C) = H, 500 °F (260 °C) = L.
For example, sprinkler VK100 with a 1/2" thread, Brass finish and a 155°F (68 'C) temperature rating = Part No. 12986AB
Available Finishes And Temperature Ratings: Refer to Table 1.
Form No. F052014 17.10.05 Rev 17.1 Replaces Form No. F052014 Rev 16.2
(Added new standard wrench 21475)
Page 2 of 6
MICROMATIC® STANDARD
I.• HI <\ j'\'.l r I:II[u'L'f RESPONSE UPRIGHT
SPRINKLER VKIOO (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Accessories: (Also refer to the Viking website.)
Sprinkler Wrenches:
Standard Wrench: Part No. 21475M/B (available since 2017).
Standard Wrench for Wax Coated Sprinklers: Part No. 10896W/B
Socket Wrench for Wax Coated Sprinklers: Part No. 13577W/B* (available since 2006)
*A 1/2 ratchet is required (not available from Viking).
Sprinkler Cabinets:
Six-head capacity: Part No. 01724A (available since 1971)
Twelve-head capacity: Part No. 01725A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standards.
OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and
sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
AVAILABILITY
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is available through a network of domestic and international
distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly.
1 Protective Sprinkler Cap
Wrench Flat
TR
Standard Sprinkler Standard Sprinkler Wrench for Wax
Wrench 21475M/B Coated Sprinklers 10896W/13
Figure 1:
Standard Sprinkler Wrenches
Form No. F_052014 17.10.05 Rev 17.1
Page 3of6
\ flflFj
Fxlj~Z
ç R: MICROMATIC® STANDARD
1 RESPONSE UPRIGHT "CJL1 SPRINKLER VKIOO (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
. Sprinkler Temperature Sprinkler Nominal Maximum Ambient
e Classification Temperature Rating' Ceiling Temperature2 u Bulb Color,
Ordinary 135 °F (57 00) 100 °F (38 °C) Orange
Ordinary 155 °F (68 00) 100 °F (38 °C) Red
Intermediate 175 °F (79 00) 150 °F (65 °C) Yellow
Intermediate 200 °F (93 °C) 150 °F (65 °C) Green
High 286 °F (141 00) 225 °F (107 00) Blue
Extra High 360 °F (182 00) 300 °F (149 °C) Mauve
Ultra High' 500 °F (260 00) 465 °F (240 °C) Black
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, and ENT
Corrosion-Resistant Coatings4: White Polyester, Black Polyester, and Black PTFE in all temperature ratings. ENT in all temperature
ratings except 135 °F (57 00) Wax-Coated Brass and Wax over Polyester5 for sprinklers with the following temperature ratings:
155 0F (68 00) Lt. Brown Wax 175 °F (79 00) Brown Wax 200 °F (93 00) Brown Wax 286 °F (141 °C) Dk. Brown Wax5
Footnotes
The sprinkler temperature rating is stamped on the deflector.
2 Based on NFPA-1 3. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction.
Refer to specific installation standards.
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 0C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 0C),
response time may be severely retarded.
The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com-
patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring is exposed on sprinklers with Polyester and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated.
Wax melting point is 170 0F (76 °C) for 286 °F (141 0C) temperature rated sprinklers.
Form No. F052014 17.10.05 Rev 17.1
Page 4 of 6
I -
fl fl,,,7fl ®
- MICROMATIC® STANDARD
~Ij
U,6 A
' RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
- Approval Chart I (UL) _______KEY i
MicromatStandard Response Upright Sprinkler VK100
Maximum 175 PSI (12 bar) WWP
Sprinkler Thread Size Nominal K-Factor Overall Length Listings and Approvals3
Base Part SIN (Refer also to UL Design Criteria.)
Number' NPT BSP U.S. metric2 Inches Imm cULus4 VdS LPCB
Standard Orifice
12986 VK100 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B3, C4, D2, E5 -- -- --
12993 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al, B3, C4, D2, E5 -- -- -
10138 VK100 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B3, C4, D2, E5 -- -- --
10193 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al, B3, C4, D2, E5 -- -- --
Approved Temperature Ratings
A- 135°F (57 °C), 155°F (68 °C), 175°F (79 °C),
200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 Approved Finishes
°C) I - Brass, Chrome, White Polyester56, and Black Polyester56
B - 135 °F (57 °C), 155 °F (68 °C), 175°F (79 °C), 2- Brass and Chrome
and 200 °F (93 °C) 3 - Wax-Coated Brass and Wax Over Polyester'
C - 286 °F (141 °C) 4 - High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient tem-
D - 500 °F (260 °C)7 perature allowed at ceiling = 150 °F (65 °C)
E - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 5- ENT
°C), 286 °F (141 °C), 360 °F (182 °C), and 500 °F
(260 °C)7
Footnotes
Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
cULus Listed as corrosion resistant.
Other colors are available on request with the same Listings and Approvals as the standard colors.
Sprinklers of Ultra-High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
(Ao refer to Approval Chart l)
cULus Listing Requirements:
The Viking Micromatic5 Standard Response Upright Sprinkler VK100 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with
the latest edition of NFPA 13 for standard spray sprinklers.
Designed for use in Light, Ordinary, and Extra Hazard occupancies.
The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Bulletin
Form No. F_080614 for general care, installation, and maintenance information. Viking sprinklers are to be in-
stalled in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB,
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and
standards, whenever applicable.
Form No. F_052014 17.10.05 Rev 17.1
Page 5of6
® MICROMATIC® STANDARD
RESPONSE UPRIGHT
SPRINKLER VK100 (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Approval Chart 2 (EM) 1 KEY Mlcronatic Standard Response Upright Sprinkler VKIOQ
Maximum '175 PSI (12 bar) WWP AlLX E1PP!teIJ Maximum
Sprinkler Base Thread Size Nominal K-Factor Overall Length FM Approvals'
Part Number' SIN (Refer also to Design Criteria below.) NPT BSP U.S. I metric2 Inches mm
Standard Orifice
12986 VK100 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, Dl, E4, F6
12993 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al, Dl, E4, F6, G5
10138 VK100 1/2" 15 mm 5.6 80.6 2-1/4" 57 Al, B2, C3, Dl, E4, F6
10193 VK100 -- 15 mm 5.6 80.6 2-1/4" 57 Al, G5, Dl, E4, F6
Approved Temperature Ratings
A- 135°F (57 °C), 155 °F (68 °C), 175°F (79 °C), 200 Approved Finishes pp °F (93 °C), 212 °F (100°C), 286°F (141 °C), and 360°F
(182 °C) 1 - Brass, Chrome, White Polyester4, and Black Polyester4
B - 135 °F (57 °C), 155 °F (68 °C), 175°F (79 °C), 200 °F 2 - Wax-Coated Brass (corrosion resistant)
(93°C) and 2l2°F(100°C)
C - 286 °F (141 °C) 3 - High Temperature 200 F (93 C) Wax Coating (corrosion resistant); maximum ambient
D -500 °F (260 "C)5 temperature allowed at ceiling = 150 °F (65 °C)
E - 155 °F (68 °C) 4 - Wax-Coated Brass and Wax Over Polyester4
F - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F s - White Polyester and Wax-Coated Brass (corrosion resistant)
(141 °C), 360 °F (182 °C), and 500 °F (260 "C)5 6- ENT6 G - 135°F (57 °C), 155°F (68 °C), 175°F (79 °C), and
200 °F (93 °C)
Footnotes
Base part number is shown. For complete part number, refer to Viking's current price schedule.
2 Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
Other colors are available on request with the same Approvals as the standard colors.
Sprinklers of Ultra-High temperature rating are intended for use Inside ovens, dryers, or similar enclosures with normal operating temperatures above
300 °F (149 °C). Where the ambient temperature around the Ultra-High temperature rated sprinkler is significantly reduced below 300 °F (149 °C),
the response time of the Ultra-High temperature rated sprinkler may be severely retarded.
FM approved as corrosion resistant.
DESIGN, CRITERIA - FM
(Also referto Approval Chart 2.)
FM Apøroval Requirements:
The Viking Micromatic® Standard Response Upright Sprinkler VK100 is is FM Approved as standard response Non-Storage upright sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SRI-3 for gen-
eral care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition
of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations,
and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Form No. F052014 17.10.05 Rev 17.1
Page 6 of 6
?fl/7F1
MICROMATIC®STANDARD
RESPONSE UPRIGHT
LU \\Li L SPRINKLER VKIOO (K5.6)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com
Sprinkler wrench 13577W/B**
must be used for installing
wax coated sprinklers.
5:: 1: ::wiy slide the2,
wrench sideways around the ,
deflector, ensuring engage-
-I
ment with the sprinklger
wrench flats.
-
_1 -
I Wax Coated
Upright Sprinkler
-
LJ
** A 1/2" ratchet is required Step 2: Carefully press the wrench downward
(not available from Viking) and ensure engagement with the sprinkler
wrench flats.
Figure 2: Socket Wrench 13577W/B for Wax Coated Sprinklers
Form No. F_052014 17.10.05 Rev 17.1 Replaces Form No. F_052014 Rev 16.2
(Added new standard wrench 21475)