HomeMy WebLinkAbout2525 EL CAMINO REAL; 101; FPC2018-0214; PermitPERJiET REPORT
Csity of
Carlsbad
Print Date: 12/13/2021 Permit No: FPC2018-0214
Job Address: 2525 EL CAM INO REAL, U 101, CARLSBAD, CA 92008-1204 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel U: 1563020900 Track U: Applied: 07/17/2018
Valuation: $388,773.46 Lot U: Issued: 08/13/2018
Occupancy Group: Project #: Finaled CIoe Out: 02/01/2021
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U: Inspector:
Plan Check U: Final Inspection:
Project Title:
Description: TEXAS DE BRAZIL -SPRINKLER TI (66 HEADS)
Applicant: FPContractor:
VFS FIRE & SECURITY SERVICES VFS FIRE AND SECURITY SERVICES
SALVADOR JASSO 501 W SOUTHERN AVE
501 W SOUTHERN AVE ORANGE, CA 92865-3217
ORANGE, CA 92865-3217 (714) 778-6070
(714) 919-8351
FEE AMOUNT
FIRE NFPA 13 or 13R System 7- 100 heads $536.00
Total Fees: $536.00 Total Payments To Date: $536.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
I ffC2-Di'S-02-(+
FIRE & SECURITY SERVICES
VFS FIRE AND SECURITY
501 W. SOUTHERN AVE.
ORANGE, CA 92865
714 778 6070
Job Name : TEXAS DE BRAZIL
Building : SPACE 101
Location : 2525 EL CAMINO REAL CARLSBAD, CA
System : SYS-1 AREA I
Contract : 183167
Data File : VFS FIRE TdeB.WXF
Computer Programs by Hydratec Inc. Revision: 50.52.1
4.
VFS FIRE AND SECURITY Page
TEiXAS DE BRAZIL Date 07/10/2018
HYDRAULIC CALCULATIONS
for
Project name: TEXAS DE BRAZIL
Location: 2525 EL CAMINO REAL CARLSBAD, CA
Drawing no: SPACE 101
Date: 07/10/18
Design
Remote area number: SYS-1 AREA 1
Remote area location: TEXAS DE BRAZIL
Occupancy classification: L.H / O.H1
Density: .15 - Gpm/SqFt
Area of application: 1500 - SqFt
Coverage per sprinkler: 130 - SqFt
Type of sprinklers calculated: SEE ATTACHED HEAD SPECS.
No. of sprinklers calculated:
In-rack demand: 0 - GPM
Hose streams: 250 - GPM
Total water required (including hose streams): 78.21 - GPM @ 890.99 - Psi
Type of system: WET
Volume of dry orpreaction system: -Gal
Water supply information
Date: 04-05-2017
Location: MARRON RD. WEST OF PLAZA DRIVE (WESTFIELD PLAZA)
Source: HYDRANT NUMBER; H60994
Name of contractor: VFS Fire & Security Services
Address: 501 W. Southern Ave. / Orange, CA 92865 I
Phone number: (714)778-6090
Name of.designer: SAL JASSO
Authority having jurisdiction: CARLSBAD FIRE DEPARTMENT
Notes: (Include peaking information orgridded systems here.) -10% FROM PRESSURES
-10% WAS DEDUCTED FROM EXISTING STATIC AND RESIDUAL PRESSURES
LIGH HAZARD AREAS IN BACK OF KITCHEN WHERE CALCULATED AT .15/1500 & 130SQFT MAX
HOWEVER THIS AREA IS LIGH HAZARD. (WORST CASE BEING USED)
Computer Programs by Hydratec Inc. Revision: 50.52.1
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: The Shoppes at Carlsbad SRU:
(Assigned upon plan submittal)
PROJECT ADDRESS: CITY: Carlsbad
PHONE: ( 714 ) 778.6070 (yES Fire & Security Services) FAX NUMBER:
Largest Building (ft.2): Sprinkled? Construction TypE
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY, CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): Marron Road west of Plaza Dr. (Westfield Plaza)
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 92 PSI Hydrant Number (if applicable):H60994
Elevation of test: 43 Feet Date/lime of Test:--------------------- ____________- .-
°itot PSI Corresponding Flow GPM
Total Flow: 6,050 GPM Residual Pressure 42 PSI
Atpeakdemand, this water system is capable of providing afire flow discharge at 20 psi of 7,350 gpm. However, this
exceeds the District's maximum velocity criteria of 15 fps. Therefore, the maximum allowable fire flow for this site is
6,050 gpm.
'Test to be performed as close as possible to the time the most conservative flows and pressures are expected.
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here:
Name: J ennifer R. Mael, P.E. Eng. Lic. No. (if applicable): C69606
Signature:__________________________________________
Title/Org: P '!_ctManager Date: 04/05/2017
Water Supply Curve C
VFS FIRE AND SECURITY Page 2
TEXAS DE BRAZIL Date 07/10/2018
City Water Supply: Demand:
Cl - Static Pressure : 82.8 Dl - Elevation : 6.930
C2 - Residual Pressure: 37.8 D2 - System Flow .640.99
C2 - Residual Flow : 6050 D2 - System Pressure : 78.212
Hose ( Demand) : 250
D3 - System Demand : 890.99
Safety Margin : 3.287
150
140
130
120
R°
E10°
90
s 80 V
U 70
R 60
50 ---
40
30
20
- a Dl .a.&L.4.a VVVI I I I
10
I I I I
750 1500 2250 3000 3750 4500 5250 6000 6750
FLOW (NA1.85)
Computer Programs by Hydratec Inc. Revision: 50.52.1
Flow Summary - NFPA 2007
VFS FIRE AND SECURITY Page 3
TEXAS DE BRAZIL Date 07/10/2018
SUPPLYANALYSIS
Node at Static Residual Available
Source Pressure Pressure Flow Pressure Total Demand Required Pressure
CON 82.8 37.8 6050.0 81.499 890.99 78.212
NODE ANALYSIS
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
HD1 12.0 5.6 12.13 19.5
1 12.0 5.21 13.99 19.5 K=K @ HD2
2 12.0 5.21 14.01 19.51 K=K @ HD2
3 12.0 5.21 14.07 19.56 K=K @ HD2
4 12.0 5.21 14.25 19.68 K=K @ HD2
5 12.0 5.21 14.92 20.14 K=K @ HD2
6 12.0 5.21 17.91 22.06 K=K @ HD2
7 12.0 5.21 16.49 21.17 K=K @ HD2
8 12.0 5.21 16.51 21.19 K=K @ HD2
9 12.0 5.21 16.58 21.23 K=K @ HD2
10 12.0 5.21 17.62 21.89 K=K@ HD2
11 12.0 20.01
12 12.0 5.21 20.7 23.72 K=K@ HD2
12A 12.0 21.04
14 12.0 5.21 20.93 23.85 K=K @ HD2
15 12.0 22.43
16 12.0 5.21 22.7 24.84 K=K @ HD2
16A 12.0 24.18
16B 12.0 5.21 24.58 25.85 K=K @ HD2
13 12.0 5.21 24.37 25.74 K=K @ HD2
17 12.0 5.21 25.38 26.27 K=K @ HD2
20 12.0 5.21 26.6 26.89 K=K @ HD2
21 12.0 5.21 26.63 26.9 K=K@ HD2
22 12.0 5.21 28.65 27.91 KK@ HD2
23 12.0 32.19
24 12.0 35.93
30 12.0 5.21 32.37 29.66 KK@ HD2
31 12.0 5.21 32.41 29.68 K=K @ HD2
32 12.0 5.21 32.64 29.79 K=K @ HD2
33 12.0 5.21 33.26 30.07 K=K @ HD2
40 12.0 5.21 24.64 25.88 K=K @ HD2
41 12.0 5.21 28.47 27.82 K=K @ HD2
42 12.0 5.21 33.53 30.19 K=K @HD2
43 12.0 42.06
44 12.0 57.56
45 12.0 58.37
34 12.0 36.62
25 12.0 37.89
18 12.0 38.17
45A 12.0 58.61
46 12.0 61.17
47 12.0 62.26
Computer Programs by Hydratec Inc. Revision: 50.52.1
Flow Summary - NFPA 2007
VF FIRE AND SECURITY Page 4
TEXAS DE BRAZIL Date 07/10/2018
NODE ANALYSIS (cont.)
Pressure Discharge
Node Tag Elevation Node Type at Node at Node Notes
48 12.0 63.7
113 12.0 64.24
TRS 4.0 68.41
BRS 2.0 69.49
UG -4.0 72.32
UG1 -4.0 72.79
UG2 -4.0 72.81
DC1 -4.0 72.83
DC2 -4.0 78.13
CON -4.0 78.21 250.0
Computer Programs by Hydratec Inc. Revision: 50.52.1
EOD
VFS FIRE AND SECURITY Page 5
TEXAS DE BRAZIL Date 07/10/2018
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes
Node2 Etev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
HDI 1 2 5.60 19.50 1 T 5.0 6.000 120 12.125
to 2E 4.0 9.000 0.0
HD2 12 19.5 1.049 0.0 15.000 0.1242 1.863 Vel 7.24
0.0
HD2 19.50 13.988 KFactor= 5.21
1 12 . 5.21 19.50 1.5 0.0 1.500 120 13.988 K= K@ HD2
to 0.0 0.0 0.0
2 12 19.5 1.682 0.0 1.500 0.0127 0.019 Vet = 2.82
2 12 5.21 19.51 1.5 0.0 1.500 120 14.007 K= K@HD2
to 0.0 0.0 0.0
3 12 39.01 1.682 0.0 1.500 0.0447 0.067 Vel = 5.63
3 12 5.21 19.56 1.5 0.0 1.833 120 14.074 K= K@ HD2
to 0.0 0.0 0.0
4 12 58.57 1.682 0.0 1.833 0.0955 0.175 Vel = 8.46
4 12 5.21 19.68 1.5 0.0 3.333 120 14.249 K= K@ HD2
to 0.0 0.0 0.0
5 12 78.25 1.61 0.0 3.333 0.2013 0.671 Vel = 12.33
5 12 5.21 20.14 1.5 0.0 9.708 120 14.920 K= K@ HD2
to 0.0 0.0 0.0
6 12 98.39 1.61 0.0 9.708 0.3080 2.990 Vel = 15.51
6 12 5.21 22.07 1.5 0.0 7.000 120 17.910 K= K@ HD2
to 0.0 0.0 0.0
12A 12 120.46 1.61 0.0 7.000 0.4476 3.133 Vel = 18.98
0.0
12A 120.46 21.043 KFactor= 26.26
7 12 5.21 21.17 1.25 0.0 0.500 120 16.491 K= K@ HD2
to 0.0 0.0 0.0
8 12 21.17 1.38 0.0 0.500 0.0380 0.019 Vet = 4.54
8 12 5.21 21.19 1.25 0.0 0.500 120 16.510 K=K@HD2
to 0.0 0.0 0.0
9 12 42.36 1.38 0.0 0.500 0.1380 0.069 Vel = 9.09
9 12 5.21 21.23 1.25 0.0 3.583 120 16.579 K= K@ HD2
to 0.0 0.0 0.0
10 12 63.59 1.38 0.0 3.583 0.2908 1.042 Vet = 13.64
10 12 5.21 21.88 1.25 0.0 4.750 120 17.621 K= K@ HD2
to 0.0 0.0 0.0
11 12 85.47 1.38 0.0 4.750 0.5027 2.388 Vel = 18.33
11 12 0.0 1.5 0.0 2.917 120 20.009
to 0.0 0.0 0.0
12 12 85.47 1.61 0.0 2.917 0.2372 0.692 Vet = 13.47
12 12 5.21 23.73 1.5 0.0 0.917 120 20.701 K= K@ HD2
to 0.0 0.0 0.0
12A 12 109.2 1.61 0.0 0.917 0.3730 0.342 Vet = 17.21
12A 12 120.45 1.5 0.0 2.250 120 21.043
to 0.0 0.0 0.0
13 12 229.65 1.61 0.0 2.250 1.4773 3.324 Vet = 36.19
0.0
13 229.65 24.367 K Factor= 46.52
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Cal culations - Hazen-Williams
VFS FIRE AND SECURITY Page 6
TEXAS DE BRAZIL Date 07/10/2018
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes
Node2 EIev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
14 12 5.21 23.85 1 0.0 8.333 120 20.927 K= K@ HD2
to 0.0 0.0 0.0
15 12 23.85 1.049 0.0 8.333 0.1802 1.502 Vel = 8.85
15 12 0.0 1 0.0 1.500 120 22.429
to 0.0 0.0 0.0
16 12 23.85 1.049 0.0 1.500 0.1800 0.270 Vel = 8.85
16 12 5.21 24.84 1.25 T 6.0 2.333 120 22.699 K= K@ HD2
to 0.0 6.000 0.0
16A 12 48.69 1.38 0.0 8.333 0.1775 1.479 Vel = 10.44
16A 12 -37.95 1.25 T 6.0 11.375 120 24.178.
to 0.0 6.000 0.0
13 12 10.74 1.38 0.0 17.375 0.0109 0.189 Vel = 2.30
0.0
13 10.74 24.367 KFactor 2.18
16A 12 37.95 1.25 0.0 3.625 120 24.178
to 0.0 0.0 0.0
16B 12 37.95 1.38 0.0 3.625 0.1120 0.406 Vel= 8.14
16B 12 ' 5.21 25.85 1.25 E 3.0 10.292 120 24.584 K = K @ HD2
to 0.0 3.000 0.0
41 12 63.8 1.38 0.0 13.292 0.2927 3.891 Vel = 13.69
0.0
41 63.80 28.475 KFactor 11.96
13 12 5.21 266.13 2.5 0.0 5.750 120 24.367 K = K @ HD2
to ' 0.0 0.0 0.0
17 12 266.13 2.635 0.0 5.750 0.1762 1.013 Vel = 15.66
17 12 5.21 26.27 2.5 T 16.474 44.542 120 25.380 K = K @ HD2
to 0.0 16.474 0.0
18 12 292.4 2.635 ' 0.0 61.016 0.2096 12.792 Vel = 17.20
0.0
18 292.40 38.172 KFactor= 47.33
20 12 5.21 26.89 1.25 0.0 0.500 120 26.597 K = K @ HD2
to . 0.0 0.0 0.0
21 12 26.89 1.38 0.0 0.500 0.0600 0.030 Vel = 5.77
21 12 5.21 26.90 1.25 0.0 9.458 120 26.627 K= K@ HD2
to . 0.0 0.0 0.0
22 12 53.79 1.38 0.0 9.458 0.2135 2.019 Vel = 11.54
22 12 5.21 27.91 1.25 2E 6.0 1.667 120 28.646 K= K@ HD2
to 0.0 6.000 0.0
23 12 81.7 1.38 0.0 7.667 0.4624 3.545 Vel = 17.52
23 12 0.0 1.25 0.0 8.083 120 32.191
to 0.0 0.0 . 0.0
24 12 81.7 1.38 0.0 8.083 0.4625 3.738 Vel = 17.52
24 12 0.0 2 T 10.0 20.375 120 35.929
to 0.0 10.000 0.0
25 12 81.7 2.067 0.0 30.375 0.0646 1,963 Vel = 7.81
0.0
25 81.70 37.892 KFactor= 13.27
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
VFS FIRE AND SECURITY Page 7
TEXAS DE BRAZIL Date .07/10/2018
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftngs Pe ******* Notes
Node2 Etev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf
30 12 5.21 29.66 2 0.0 5.000 120 32.366 K= K@ HD2
to 0.0 0.0 0.0
31 12 29.66 2.157 0.0 5.000 0.0080 0.040 Vel = 2.60
31 12 5.21 29.68 2 0.0 8.000 120 32.406 . K = K @ HD2
to 0.0 0.0 0.0
32 12 59.34 2.157 0.0 8.000 0.0291 0.233 Vet = 5.21
32 12 5.21 29.79 2 0.0 10.000 120 32.639 K = K @ HD2
to 0.0 0.0 0.0
33 12 89.13 2.157 0.0 10.000 0.0617 0.617 Vel = 7.83
33 12 5.21 30.07 2 T 12.307 19.500 120 33.256 K= K@ HD2
to 0.0 12.307 0.0
34 12 119.2 2.157 . 0.0 31.807 0.1057 3.361 Vet = 10.47
0.0
34 119.20 . 36.617 K Factor = 19.70
40 12 5.21 25.88 1 E 2.0 11.292 120 24.640 K=K@HD2
to T 5.0 7.000 0.0
41 12 25.88 1.049 0.0 18.292 0.2097 3.835 Vel = 9.61
41 12 5.21 91.63 1.25 0.0 5.583 120 28.475 K= K@ HD2
to 0.0 0.0 0.0
42 12 117.51 1.38 0.0 5.583 0.9058 5.057 VeI= 25.21
42 12 5.21 30.19 1.25 0.0 6.167 120 33.532 K= K@ HD2
to . 0.0 0.0 0.0
43 12 147.7 1.38 0.0 6.167 1.3828 8.528 Vet = 31.68
43 12 0.0 1*5 0.0 23.750 120 42.060
to 0.0 0.0 0.0
44 12 147.7 1.61 0.0 23.750 0.6528 15.504 Vet = 23.28
44 12 0.0 2 0.0 4.167 120 57.564
to 0.0 0.0 0.0
45 12 147.7 2.067 0.0 4.167 0.1932 0.805 Vet = 14.12
45 12 0.0 4 E 10.0 1.750 120 58.369
to T 20.0 30.000 0.0
45A 12 147.7 4.026 0.0 31.750 0.0075 0.239 Vet = 3.72
0.0
45A 147.70 58.608 K Factor = 19.29
34 12 119.20 2.5 3E 24.711 7.292 120 36.617
to . 0.0 . 24.711 0.0
25 12 119.2 2.635 0.0 32.003 0.0398 1.275 Vet = 7.01
25 12 81.70 2.5 0.0 2.667 120 37.892
to 0.0 0.0 0.0
18 12 200.9 2.635 0.0 2.667 0.1050 0.280 Vet = 11.82
18 12 292.39 2.5 E 8.237 12.333 120 38.172
to T 16.474 24.711 0.0
45A 12 493.29 2.635 0.0 37.044 0.5517 20.436 Vet = 29.02
45A 12 147.70 4 T 20.0 2.542 120 58.608
to 0.0 20.000 0.0
46 12 640.99 4.026 0.0 22.542 0.1137 2.562 Vel = 16.15
46 12 0.0 5 0.0 28.917 120 61.170
to 0.0 0.0 0.0
47 12 640.99 5.047 0.0 28.917 0.0378 1.093 Vet = 10.28
Computer Programs by Hydratec Inc. Revision: 50.52.1
Final Calculations - Hazen-Williams
VFS FIRE AND SECURITY Page 8
TEXAS DE BRAZIL Date 07/10/2018
Nodel Elevi K Qa Nom Fitting Pipe CFact Pt
to or Ftng's Pe ******* Notes
Node2 EIev2 Fact Qt Act Eqv. Ln. Total PfIFt Pf
47 12 0.0 6 T 30.0 34.833 120 62.263
to 2E 28.0 58.000 0.0
48 12 640.99 6.065 0.0 92.833 0.0155 1.435 Vel = 7.12
48 12 0.0 6 E 17.603 26.333 120 63.698
to 0.0 17.603 0.0
113 12 640.99 6.357 0.0 43.936 0.0123 0.540 Vel = 6.48
113 12 0.0 8 3E 63.423 108.583 120 64.238
to 3F 31.712 95.135 3.465
TRS 4 640.99 8.249 0.0 203.718 0.0035 0.703 Vel = 3.85
TRS 4 0.0 8 G 4.0 5.000 120 68.406
to S 45.0 49.000 0.866
BRS 2 640.99 7.981 0.0 54.000 0.0041 0.220 Vel = 4.11
BRS 2 0.0 8 E 21.405 5.000 120 69.492
to T 41.62 63.025 2.599
UG -4 640.99 8.27 0.0 68.025 0.0034 0.231 Vel = 3.83
UG -4 0.0 8 0.0 114.708 120 72.322
to 0.0 0.0 0.0
UG1 -4 640.99 7.98 0.0 114.708 0.0041 0.466 Vel = 4.11
UG1 -4 0.0 8 0.0 10.000 140 72.788
to 0.0 0.0 0.0
UG2 -4 640.99 8.27 0.0 10.000 0.0026 0.026 Vel = 3.83
UG2 -4 0.0 8 0.0 5.000 150 72.814
to 0.0 0.0 0.0
DC1 -4 640.99 7.98 0.0 5.000 0.0026 0.013 Vel = 4.11
DC1 -4 0.0 8 5E 142.34 6.000 140 72.827
to 0.0 113.872 5.000 *Fixed Loss =5
DC2 -4 640.99 8.27 0.0 119.872 0.0026 0.308 Vel = 3.83
DC2 -4 0.0 10 T 67.474 10.000 150 78.135
to 0.0 67.474 0.0
CON -4 640.99 9.79 0.0 77.474 0.0010 0.077 Vel = 2.73
250.00 Qa = 250.00
CON 890.99 78.212 K Factor = 100.75
Computer Programs by Hydratec Inc. Revision: 50.52.1
Fittings Used Summary
VFS FIRE AND SECURITY Page 9
TEXAS DE BRAZIL Date 07/10/2018
Fitting Legend
Abbrev. Name % % 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
E NFPA 13 90 Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 40 45 50 61
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
G NFPA 13 Gate Valve 0 0 0 0 0 1 1 1 1 2 2 3 4 5 6 7 8 10 11 13
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA139O Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Unit Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Revision: 50.52.1
Flow Diagram
VFS FIRE AND SECURITY Page 10
TEXAS DE BRAZIL Date 07/10/2018
19.5
HDI<- HD2
19.5 58.6 98.4
1 <-2 <-3 <-4 <-5 <-6 <-12A
39 78.3 120.5
21.2 63.6 85.5 229.7
7 <- 8 <- 9 <-- 10 <- 11 <-- 12 <- 12A<._ 13
42.4 85.5 109.2
23.9 48.7
14 <- 15 <- 16 <-- 16A<- 13
23.9 10.7
38
16A<- 16B<_ 41
- 63.8
I 10.7
I 266.1
13 <-- 17 <- 18
292.4
26.9 81.7 81.7
20 <-. 21 <-- 22 <- 23 <- 24 <- 25
53.8 81.7
29.7 89.1
30 <- 31 <- 32 <-_ 33 <- 34
59.3 119.2
25.9 147.7 147.7
40 <- 41 <- 42 <- 43 <-- 44 <_ 45 <-- 45A
117.5 147.7 147.7
119.2 493.3 641 641 641 641 641 641
34 <-25 <-18 <-45A<-46 <-47 <-48 <-113<- TRS<-BRS<- UG<- UGI<- UG2<- DCI<- DC2<- CON
200.9 641 641 641 641 641 641
Computer Programs by Hydratec Inc. Revision: 50.52.1
. ....
I
QUICK RESPONSE
SERIES GL-QR SERIES GL-QRJCNV
UPRIGHT CONVENTIONAL
QUICK RESPONSE
SERIES GL-QR SERIES GL-QRJSW
PENDENT VERTICAL
SIDEWALL
Coca MD
FIRE SPRINKLER CORPORATION
QUICK RESPONSE
A U TO MA TIC SPRINKLERS
GL SERIES
UPRIGHT -PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Quick Response Series GL-QR Sprinklers are
a low profile yet durable design which utilizes a 3mm frangible
glass ampule as the thermosensitive element. This provides
sprinkler operation approximately six times faster than ordinary
sprinklers. While the Quick Response Sprinkler provides an
aesthetically pleasing appearance, it can be installed wherever
standard spray sprinklers are specified when allowed by the ap-
plicable standards. It offers the additional feature of greatly in-
creased safety to life and is available in various styles, orifices,
temperature ratings and finishes to meet many varying design
requirements. Quick Response Sprinklers should be used ad-
visedly and under the direction of approving authorities having
jurisdiction.
The heart of Globe's Series GL-QR sprinkler proven ac-
tuating assembly is a hermetically sealed frangible glass ampule
that contains a precisely measured amount of fluid. When heat is
absorbed, the liquid within the bulb expands increasing the inter-
nal pressure. At the prescribed temperature the internal pressure
within the ampule exceeds the strength of the glass causing the
glass to shatter. This results in water discharge which is distrib-
uted in an approved pattern depending upon the deflector style
used.
TECHNICAL DATA
See reverse side for Approvals and Specifications. 1. Temperature Ratings - 135°F (570C), 155°F (680C),
175°F (790C), 200°F (93°C), 286°F (141°C)
Water Working Pressure Rating - 175 psi (12 Bars) QUICK RESPONSE Factory tested hydrostatically to 500 psi (34 Bars) HORIZONTAL LPCB/CE Maximum low temperature glass bulb rating is -67°F (-55°C) SIDEWALL HORIZONTAL
Frame - bronze • Deflector - brass Screw - brass SERIES GL-QRISW SIDEWALL
Lodgement Wire - stainless steel • Bulb seat - copper SERIES GL-QRISW
Spring - nickel alloy • Seal - teflon
Bulb - glass with alcohol based solution, 3mm size
SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
s CLASSIFICATION AVAILABLE SPRINKLER co BULB COLOR N.F.P.A. MAXIMUM
TEMPERATURES CEILING TEMPERATURE
ORDINARY I 135 F/155F 57t68 (J ORANGE/RED 100 38C
INTERMEDIATE 175F/200F 79'C/93C YELLOW/GREEN 1501 86'C
HIGH 286F 141C BLUE 2251 107C
MAR 2018 GFS-lUoa (Formerly A-20)
QUICK RESPONSE
A UTOMA TIC SPRINKLERS
UPRIGHT PENDENT VERTICAL SIDEWALL
HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (40 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm)
4.2 (60 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Factory Bronze
5.6 (80 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Chrome -
White Polyester'
8.0 (115 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Black Polyester23
8.0 (115 metric) 3/4"NPT (20mm) 2 7/16" (6.2cm)
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
'HORIZONTAL SIDEWALL IS 29/16".
2FINISHES AVAILABLE ON SPECIAL ORDER.
'AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
LISTINGS/APPROVALS
TEMPERATURE NYC-DOB
STYLE SIN K
FACTOR HAZARD' cULus FM LPCB2 CE MEA ____ 135°F 155°F 175°F 200°F 286°F,
(57°C) (68°C) (79°C) (93°C) (141°C)
-
101-92-E
GL2815 2.8 LH X X X X X X X
GL4215 4.2 LH X X X X X X X
UPRIGHT GL5615 5.6 LH/OH X X X X X X X X X X
GL8115* 8.0* (W NPT) LH/OH X X X X X X -- --- --- X
GL8118 8.0 LH/OH X X X X X X X X X X
GL2801 2.8 LH X X X X X X --- --- --- X
GL4201 4.2 LH X X X X X X --- --- --- x
PENDENT GL5601 5.6 LH/OH X X X X X X X X X X
GL8101* 8.0* (W' NPT) LH/OH X X X X X X --- --- --- X
GL8106 8.0 LH/OH X X X X X X X X X X
VERTICAL GL5632 5.6 LH X X X X X X X
SIDEWALLt GL8133 8.0 LH X X X X X X --- --
GL2826 2.8 LH X X X X X X --- --- --- x
GL4226 4.2 LH X X X X X X -- --- --- X HORIZONTAL GL5626 5.6 LH/OH X X X X X X X X SIDEWALL GL5627a 5.6 LH/OH X X X X X --- -- X X
GL8127 8.0 LH/OH X X X X X X ---
CONVENTIONAL GL5624 5.6 LH/OH
(OLD STYLE) GL8125 8.0 LH/OH X X X X X --- -- --- X
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA1 3 AND ANY OTHER RELATED DOCUMENTS.
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING.
PINSTALL IN ACCORDANCE TO B55306 AND ANY OTHER RELATED DOCUMENTS.
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING.
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING.
OH: ORDINARY HAZARD
LH: LIGHT HAZARD
*1I2 NPT, FOR RETROFIT ONLY
2 LPCB REF. NO. 147c105
ORDERING INFORMATION GLOBE® PRODUCT WARRANTY
SPECIFY Globe agrees to repair or replace any of its own manufactured
Quantity • SIN Style q Orifice products found to be defective in material or workmanship for a
Thread Size . Temperature • Finishes desired period of one year from date of shipment.
Quantity - Wrenches - PIN 325390 (1/2"); For specific. details of our warranty please refer to Price List
P/N 312366 (L.O.) Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
GM6MM 1-800-248-0278 www.gIobesprinkler.com
FIRE SPRINKLER CORPORATION
MAR 2018 PRINTED U.S.A. GFS-100a (Formerly A-20)
rj r I
C1101C CflOIMP1I CJ tf%V3flAVATItkM
"THE INCH"
QUICK RESPONSE
AUTOMATIC SPRINKLER
GL5606
I JV I LUVUIIJ% WI UU4 I IUI ONE INCH ADJUSTABLE
FLAT PLATE CONCEALED PENDENT
DEscRIPTIoN AND OPERATION
The Globe Quick Response GL5606 Adjustable Concealed Pendent Sprinkler has a low profile,
aesthetically pleasing design. It provides sprinkler operations approximately six times faster than
ordinary sprinklers and can be installed wherever standard concealed spray sprinklers are specified
when allowed by the applicable standards. This sprinkler offers the additional feature of greatly in-
creased safety to life and should be used advisedly and under the direction of approving authorities
having jurisdiction. The sprinkler is available with a nominal 1" of adjustment and a low profile cover
plate assembly. All that is seen at the ceiling is a 3 5/16" diameter ceiling plate or an optional 2 3/4"
diameter ceiling plate color finished to match the specifier's exact requirements. The Series GL-QR
Concealed Sprinkler may be virtually invisible as it does not interrupt the "smooth flow" of the ceiling.
Globe's GL5606 Concealed Sprinkler utilizes a 3mm frangible glass ampule which is located above
the ceiling and concealed from view by the ceiling plate.
The provided protective cap needs to be removed in order to install the sprinkler with the proper
wrench. The protective cap must be replaced on the sprinkler until the time the cover plate is to be
installed. The "push on - screw off' designed cover plate is easily installed and with a nominal 1" of
adjustment makes it easier to get a proper fit at the ceiling.
Operation of the sprinkler occurs when heat build up causes the solder holding the cover plate
to the support shell to melt allowing the cover plate to fall clear. Continued heat build up causes the
3mm glass bulb to burst allowing the deflector to drop down and distribute water in an approved
pattern to extinguish or control the fire.
TECHNICAL DATA I
See reverse side for Approvals and Specifications
Temperature Ratings -
135°F (57°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 135°F (57°C) Cover Plate
155°F (68°C) Sprinkler, 155°F (68°C) Cover Plate 35/16" diameter plate
175°F (79°C) Sprinkler, 155°F (68°C) Cover Plate 'fl
200°F (93°C) Sprinkler, 155°F (68°C) Cover Plate
Water Working Pressure Rating -175 psi (12 Bars)
Factory tested hydrostatically to 500 psi (34 Bars)
Maximum low temperature glass bulb rating is -67°F (-55°C)
Frame - bronze • Deflector - brass • Screw - brass
Lodgement Wire - stainless steel • Bulb seat - copper 2 3/4" diameter plate
Spring - nickel alloy• Seal - teflon Drop Pin - stainless steel SERIES GL-QR/INCH
Bulb - glass with alcohol based solution, 3mm size WHITE FLAT PLATE
Cover Plate - brass• Upper Escutcheon Assembly - steel CONCEALED PENDENT
NOTE: Globe's wrench P/N 332765 must be used to install this sprinkler.
-SPRINKLER TEMPERATURE RATING/CLASSIFICATION and COLOR CODING
CLASSIFICATION AVAILABLE SPRINKLER BULB COLOR N.F.P.A. MAXIMUM CEILING
TEMPERATURES TEMPERATURE
ORDINARY 35 Ff155 F 57'C/WC ORANGE/RED 100 F C
INTERMEDIATE 75F/200F 79CJ93C YELLOW/GREEN 150F 66C
MAR 2018 GFS-1 50a (Formerly A-38)
"THE INCH" QUICK RESPONSE A U TOMA TIC SPRINKLER
ONE INCH ADJUSTABLE FLAT PLATE CONCEALED PENDENT
GL5606
SPECIFICATIONS
NOMINAL THREAD SIZE LENGTH FLAT COVER
"K" FACTOR PLATE FINISHES*
5.6 1/2"NPT 2 1/2" Chrome
(80 metric) (15mm) (6.4cm) White Painted
Other Finishes12
NOTE: METRIC CONVERSIONS ARE APPROXIMATE.
1FINISHES AVAILABLE ON SPECIAL ORDER.
,FOR PLATES OTHER THAN WHITE, CONTACT GLOBE FOR ORDERING SPECIFICATIONS.
***FACTORY PAINTED COVER PLATES MUST NOT BE REPAINTED. NON-FACTORY APPLIED PAINT MAY ADVERSELY DELAY
OR PREVENT SPRINKLER OPERATION IN THE EVENT OF A FIRE.
APPROVALS
STYLE SIN HAZARD'
135°F (57°C) Flat Cover Plate 155°F (68°C) Flat Cover Plate
cULus *FM
NYC-DOB
MEA **1350F (57°C) 155°F (68°C) **155F (68°C) 175°F (79°C) 200°F (93°C)
Sprinkler Sprinkler Sprinkler Sprinkler Sprinkler 10192E
Adjustable
Concealed GL5606 LH/OH X X X X X X X X
Pendent
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPA13 AND ANY OTHER RELATED DOCUMENTS.
*FM APPROVED AS STANDARD RESPONSE
**NO FM APPROVALS
OH: ORDINARY HAZARD
LIGHT HAZARD CROSS SECTIONS
2 1/4 DIA. MIN. -j
rIDLE
2/4"DIA.MIN.
HOLE INCEUNG IN CEILING
-17/8 OIA.-1 ----17/8" DIA.-
lx 1/2'-..1 F? I 1 lx
2 3/46 MAX. 2 3/4
DROP PIN
MAX.
1 7/8" MIN. 1 7/8" MIN,
DEFLECTOR SUPPORT DEFLECTOR
I DROP PIN SHELL
" - \
2 3/4"DIA. 1/8" I 3 5/16 OLA.
FLAT COVER PLATE FLAT COVER PLATE
1" ADJUSTMENT FLAT PLATE CONCEALED PENDENT
FLAT COVER
PLATE SIZES
WHITE 135°F (57°C)
PART#
WHITE 155°F (68°C)
PART#
CHROME.135°F (57°C)
PART#
CHROME 155°F (68°C)
PART#
2 3/4" DIA. 332726 332731 332724 332729
35/16"DIA. 332706 - 332711 332704 332709
ORDERING INFORMATION GLOBE® PRODUCT WARRANTY
SPECIFY Globe agrees to repair or replace any of its own manufactured
Quantity ° SIN ° Style Orifice products found to be defective in material or workmanship for a
Thread Size Temperature. Finishes desired period of one year from date of shipment.
° Quantity - Wrenches - P/N 332765 For specific details of our warranty please refer to Price List
Quantity - Protective Caps - P/N 332695 Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
016Lcom
0 . 989-846-4583 FAX 989-846-9231
ISPRINKLERCOPPORAUON
1-800-248-0278 www.globesprinkIer.com FIR
MAR 2018 PRINTED U.S.A. GFS-150a (Formerly A-38)
FIRE SPRINKLER CORPORATION
STANDARD RESPONSE
A UTOMA TIC SPRINKLERS
GL SERIES
UPRIGHT PENDENT
VERTICAL SIDEWALL
HORIZONTAL SIDEWALL
CONVENTIONAL (OLD STYLE)
DESCRIPTION AND OPERATION
The Globe Standard Response Series CL-SR Sprinklers are a
low profile yet durable design which utilizes a 5mm frangible glass ./
ampule as the thermosensitive element. While the Standard
Response Sprinkler provides an aesthetically pleasing appear- j L ance, it can be installed wherever standard spray sprinklers are '
specified when allowed by the applicable standards. It offers
the additional feature of greatly increased safety to life and is
available in various styles, orifices, temperature ratings and fin-
ishes to meet varying design requirements. Standard Response STANDARD RESPONSE
Sprinklers should be used advisedly and under the direction of SERIES GL-SR SRlESGLSRJCNV
approving authorities having jurisdiction. UPRIGHT CONVENTIONAL
The heart of Globe's Series GL-SR sprinkler proven actuat-
ing assembly is a hermetically sealed frangible glass ampule that .
contains a precisely measured amount of fluid. When heat is '7
absorbed, the liquid within the bulb expands increasing the f)
internal pressure. At the prescribed temperature the internal Li
pressure within the ampule exceeds the strength of the glass
causing the glass to shatter. This results in water discharge which is 1 -z distributed in an approved pattern depending upon the deflector . '.
style used. . STANDARD RESPONSE
The sprinkler and escutcheon are not factory assembled. SERIES GL-SR SERIES CL-SR/SW
Assembly is done in the field. PENDENT VERTICAL
TECHNICAL DATA SIDEWALL
See reverse side for Approvals and Specifications.
Temperature Ratings - 135°F (57°C), 155°F (68°C), -
175°F (79°C), 200°F (93°C), 286°F (141°C), 360°F (182°C) " 500'F (260°C) Available Upon Request Without Approvals Water Working Pressure Rating -175 psi (12 Bars) '
Factory tested hydrostatically to 500 psi (34 Bars) STANDARD RESPONSE Maximum low temperature glass bulb rating is -67°F (-55°C) SERIES CL-SR/SW SERIES GL-SR/SW
Frame - bronze • Deflector - brass • Screw - brass LPCB/CE HORIZONTAL
Lodgement Wire - stainless steel • Bulb seat - copper HORIZONTAL SIDEWALL
Spring - nickel alloy• Seal - teflon SIDEWALL
Bulb - glass with glycerin solution, 5mm size
Escutcheon Assembly - steel
.cPPINKI FR TFMPFRATIIRF RATIN(/(N A.c.cIFI(ATInN anri COLOR CODINC
CLASSIFICATION AVAILABLE SPRINKLER
TEMPERATURES BULB COLOR N.F.P.A. MAXIMUM
CEILING TEMPERATURE
ORDINARY — 135F/155 5710681 ORANGE/RED 10O'F 38C
INTERMEDIATE 115F2QO 79093C YELLOW/GREEN 150E 66C
HIGH 266'F 141'C BLUE 225'F 107'C
EXTRA HIGH 360F 187C MAUVE 300'F 149C
ULTRA HIGH 50OF 260C BLACK 475'F- 24,6C
MAR 2018 GFS-100b (Formerly A-65)
STANDARD RESPONSE
AU TOMA TIC SPRINKLERS
SERIES GL-SR
UPRIGHT PENDENT • VERTICAL SIDEWALL
HORIZONTAL SIDEWALL CONVENTIONAL (OLD STYLE)
SPECIFICATIONS
NOMINAL "K" FACTOR THREAD SIZE LENGTH' FINISHES
2.8 (40 metric) 1/2"NPT (1 5mm) 21/4" (5.7cm) Factory Bronze
4.2 (60 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Chrome
5.6 (80 metric) 1/2"NPT(15mm) 2 1/4" (5.7cm) White Polyester3
8.0 (115 metric) 1/2"NPT (15mm) 2 1/4" (5.7cm) Black Polyester23
8.0 (115 metric) 3/4"NPT (20mm) 2 7/16" (6.2cm) Wax Coated23'4
NOTE: METRIC CONVERSIONS ARE APPROXIMATE. 'AVAILABLE AS cULus LISTED CORROSION RESISTANT WHEN SPECIFIED ON ORDER.
'HORIZONTAL SIDEWALL IS 9/16", 'WAX COATING cULus LISTED UP TO 200°F (93°C) ONLY,
'FINISHES AVAILABLE ON SPECIAL ORDER.
LISTINGS/APPROVALS
TEMPERATURE
STYLE SIN FACTOR HAZARD' cULus FM LPCB2 CE MEAIOI.92.E 135°F 155°F 175°F 200°F "°286°F "360°F
(57°C) (68°C) (79°C) (93°C) (141°C) (182°C)
GL2861 2.8 LH X X X X X X X --- --- X
GL4261 4.2 LH X X X X X X X --- --- --- X
UPRIGHT GL5661 5.6 ALL X X X X X X X X X X X
GL8161° 8.0° (W NPT) ALL X X X X X X X --- --- --- X
GL8164 8.0 ALL X X X X X X X X X X X
GL2851 2.8 LH X X X X X X X --- --- --- X
GL4251 4.2 LH X X X X X X X --- --- X
PENDENT GL5651 5.6 ALL X X X X X X X X X X X
GL8151° 8.0"(WNPT) ALL X X X X X X X --- --- --- x
GL8156 8.0 ALL X X X X X X X X' X X X
VERTICAL GL5675 5.6 LH X X X X X X X X
SIDEWALLt GL8176 8.0 LH X X X X X X X
GL2870 2.8 LH X X X X X X X - --- --- X
GL4270 4.2 LH X X X X X X X --- --- --- X HORIZONTAL GL5670 5.6 LH/OH X X X X X X X X --- --- X SIDEWALL GL56710 5.6 ' LH/OH X X X X X X --- --- X X
GL8171 8.0 LH/OH X X X X X X X ---
CONVENTIONAL GL5668 5.6 LH/OH X X X X X X --- --- X X
(OLD STYLE) G_ 8169 8.0 LH/OH X X X X X X --- --- --- X
'SPRINKLERS SHALL BE LIMITED AS PER THE REQUIREMENTS OF NFPAI 3 AND ANY OTHER RELATED DOCUMENTS. 'BRASS FINISH ONLY WHEN RECESSED
§HORIZONTAL SIDEWALL cULus LISTED FOR DEFLECTOR 4" TO 12" BELOW THE CEILING, FM APPROVED 4" TO 6" BELOW THE CEILING. ""NO FM APPROVALS FOR RECESSED
SINSTALL IN ACCORDANCE TO B55306 AND ANY OTHER RELATED DOCUMENTS. "NO FM APPROVALS
tPENDENT VERTICAL SIDEWALL cULus LISTED FOR 6' MIN. SPACING. OH: ORDINARY HAZARD
tUPRIGHT VERTICAL SIDEWALL cULus LISTED FOR 9' MIN. SPACING. LH: LIGHT HAZARD
500"F (260°C) AVAILABLE UPON REQUEST WITH NO APPROVALS. ALL: ALL HAZARDS
°1/2"NPT; RETRO-FIT ONLY
'LPCB REF. NO. 147c104
ORDERING INFORMATION
SPECIFY
Quantity" SIN" Style' Orifice
° Thread Size "Temperature. Finish desired
Quantity - Wrenches/Recessed Wrenches -
P/N 325390/325391 (1/2"); P/N 312366/325401 (L.0.)
"Quantity Protective Caps - P/N 327109-CAP (Friction Fit Recessed)
Wnbm—,
FIRE SPRINKLER CORPORATION
MAR 2018
GLOBE® PRODUCT WARRANTY
Globe agrees to repair or replace any of its own manufactured
products found to be defective in material or workmanship for a
period of one year from date of shipment.
For specific details of our warranty please refer to Price List
Terms and Conditions of Sale (Our Price List).
4077 AIRPARK DRIVE, STANDISH, MICHIGAN 48658
989-846-4583 FAX 989-846-9231
1-800-248-0278 www.gIobesprinkler.com
PRINTED U.S.A. GFS-100b (Formerly A-65)