Job Address: 961 PALOMAR AIRPORT RD, # 112, CARLSBAD, CA 92011-1106
Permit Type: FIRE-Construction Commercial Work Class: Fire Alarm
Parcel #: 2110403400 Track #:
Valuation: $65,690.80 Lot U:
Occupancy Group: Project U:
#of Dwelling Units: Plan U:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check U:
Plan Check U:
Permit No: FPC2021-0135
Status: Closed - Finaled
Applied: 07/23/2021
Issued: 08/04/2021
Finaled Close Out: 11/01/2021
Inspector:
Final Inspection:
Project Title:
Description: KOTIJA JR. TACO SHOP -ALTERATION TO FIRE ALARM SYSTEM (1 ADDRESSABLE MINI MODULE)
FPContractor:
JJJ ENTERPRISES
SALOMON GOMEZ
115 MARKET PL
ESCONDIDO, CA 92029-1353-SAN DIEGO
(760) 747-3050 x216
FEE AMOUNT
FIRE TI Fire Alarm System $620.00
Total Fees: $620.00 Total Payments To Date: $620.00 Balance Due: $0.00
1
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
qfqfqp ENUEPppmEg
FIRE ALARM - SECURITY - LOW VOLTAGE SYSTEMS
KOTIJA JR TACO SHOP
961 PALOMAR AIRPORT RD.
SUITE #112
CARLSBAD, CA 92011
FIRE ALARM SYSTEM
¶MATERIAL DATASHE ET$1
DN-6999:E
NOTIFIER®
by _Honeywell
P- —.:-
Monitor Modules
NMM.100(A), NMM.IOOP(A), NZM.100(A),
and NDM.1 00(A) for FireWarden Series
General
Four different monitor modules are available for Notifier's
FireWarden Series intelligent control panels for a variety of
applications. Monitor modules supervise a circuit of dry-con-
tact input devices, such as conventional heat detectors and
pull stations, or monitor and power a circuit of two-wire
smoke detectors (NZM-100(A)).
NMM-100(A) is a standard-sized module (typically mounts to
a 4" [10.16 cm] square box) that supervises either a Style D
(Class A) or Style B (Class B) circuit of dry-contact input
devices.
NMM-IOOP(A) is a miniature monitor module a mere 1.3"
(3.302 cm) H x 2.75' (6.985 cm) W 0.65' (1.651 cm) D that
supervises a Style B (Class B) circuit of dry-contact input
devices. Its compact design allows the NMM-IOOP(A) to be
mounted in a single-gang box behind the device it monitors.
NZM-100(A) is a standard-sized module that monitors and
supervises compatible two-wire, 24 volt, smoke detectors on
a Style D (Class A) or Style B (Class B) circuit.
NDM-100(A) is a standard-sized dual monitor module that
monitors and supervises two independent two-wire Style B
(Class B) dry-contact initiating device circuits (lDCs) at two
separate, consecutive addresses in intelligent, two-wire sys-
tems.
LiteSpeedTm is a communication protocol that greatly
increases the speed of communication between analog intel-
ligent devices. Intelligent devices communicate in a grouped
fashion. If one of the devices within the group has new infor-
mation, the panel CPU stops the group poll and concentrates
on single points. The net effect is response speed greater
than five times that of other communication protocols.
NMM.100(A) Monitor Module
Built-in type identification automatically identifies this
device as a monitor module to the control panel.
Powered directly by two-wire SLC loop. No additional
power required.
High noise (EMF/RFI) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry of address: 01 - 99 on FireWarden-100-
2, 01 -50 on FireWarden-50.
LED flashes during normal operation and latches on
steady to indicate alarm.
The NMM-100(A) Monitor Module is intended for use in intel-
ligent, two-wire systems, where the individual address of
each module is selected using the built-in rotary switches. It
provides either a two-wire or four-wire fault-tolerant Initiating
Device Circuit (IDC) for normally-open-contact fire alarm and
supervisory devices. The module has a panel-controlled LED
indicator.
NMM-100(A) APPLICATIONS
Use to monitor a zone of four-wire smoke detectors, manual
fire alarm pull stations, waterflow devices, or other normally-
open dry-contact alarm activation devices. May also be used
NMM-100(A) (Type H)
to monitor normally-open supervisory devices with special
supervisory indication at the control panel. Monitored circuit
may be wired as an NFPA Style B (Class B) or Style D (Class
A) Initiating Device Circuit. A 47K Ohm End-of-Line Resistor
(provided) terminates the Style B circuit. No resistor is
required for supervision of the Style D circuit.
NMM-100(A) OPERATION
Each NMM-100(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/
normal/short) of its Initiating Device Circuit (IDC). A flashing
LED indicates that the module is in communication with the
control panel. The LED latches steady on alarm (subject to
current limitations on the loop).
NMM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.0 mA (LED on).
Average operating current: 375 pA (LED flashing), 1 com-
munication every 5 seconds, 47k EOL.
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
NMM-1 OOP(A) Mini Monitor Module
Built-in type identification automatically identifies this
device as a monitor module to the panel.
DN-6999:E • 07/30/2015— Page 1 of 4
Powered directly by two-wire SLC loop. No additional Wire length: 6(15.24 cm) minimum.
power required.
High noise (EMF/RFI) immunity. NZM1 00(A) Interface Module
Tinned, stripped leads for ease of wiring. • Supports compatible two-wire smoke detectors.
Direct-dial entry of address: 01 —99 on FireWarden-100-2, • Supervises IDC wiring and connection of external power
01 —50 on FireWarden-50. source.
1415 0 1 ADDRESS 0 1
13 2
2
15
LOOP
____
I a 76 8 76
I TENS ONES
II Il II • oH 1I °H o jII II-j 1 -'I 110
H II
The NMM-100P(A) Mini Monitor Module can be installed in a
single-gang junction directly behind the monitored unit. Its
small size and light weight allow it to be installed without rigid
mounting. The NMM-100P(A) is intended for use in intelli-
gent, two-wire systems where the individual address of each
module is selected using rotary switches. It provides a two-
wire initiating device circuit for normally-open-contact fire
alarm and security devices. NMM-100P(A)
NMM-IOOP(A) APPLICATIONS
Use to monitor a single device or a zone of four-wire smoke
detectors, manual fire alarm pull stations, waterflow devices,
or other normally-open dry-contact devices. May also be
used to monitor normally-open supervisory devices with spe-
cial supervisory indication at the control panel. Monitored cir-
cuit/device is wired as an NFPA Style B (Class B) Initiating
Device Circuit. A 47K Ohm End-of-Line Resistor (provided)
terminates the circuit.
NMM-IOOP(A) OPERATION
Each NMM-100P(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/
normal/short) of its Initiating Device Circuit (IDC).
NMM-IOOP(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Average operating current: 350 pA, 1 communication
every 5 seconds, 47k EOL; 600 pA Max. (Communicating,
IDC Shorted).
Maximum IDC wiring resistance: 1500 Ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 450 pA.
EOL resistance: 47K Ohms.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x
0.65" (1.651 cm) deep.
High noise (EMF/RFl) immunity.
SEMS screws with clamping plates for ease of wiring.
Direct-dial entry entry of address:, 01 —99 on FireWarden-
100-2, 01 —50 on FireWarden-50.
LED flashes during normal operation.
LED latches steady to indicate alarm on command from
control panel.
The NZM-100(A) Interface Module is intended for use in
intelligent, addressable systems, where the individual
address of each module is selected using built-in rotary
switches. This module allows intelligent panels to interface
and monitor two-wire conventional smoke detectors. It trans-
mits the status (normal, open, or alarm) of one full zone of
conventional detectors back to the control panel. All two-wire
detectors being monitored must be UL compatible with the
module.
NZM-100(A) APPLICATIONS
Use the NZM-100(A) to monitor a zone of two-wire smoke
detectors. The monitored circuit may be wired as an NFPA
Style B (Class B) or Style D (Class A) Initiating Device Cir-
cuit. A 3.9 K Ohm End-of-Line Resistor (provided) terminates
the end of the Style B or D (class B or A) circuit (maximum
IDC loop resistance is 25 Ohms). Install ELR across termi-
nals 8 and 9 for Style D application.
NZM-100(A) OPERATION
Each NZM-100(A) uses one of the available module
addresses on an SLC loop. It responds to regular polls from
the control panel and reports its type and the status (open/
normal/short) of its Initiating Device Circuit (IDC). A flashing
LED indicates that the module is in communication with the
control panel. The LED latches steady on alarm (subject to
current limitations on the loop).
NZM-100(A) SPECIFICATIONS
Nominal operating voltage: 15 to 32 VDC.
Maximum current draw: 5.1 mA (LED on).
Maximum IDC wiring resistance: 25 Ohms.
Average operating current: 270 pA, 1 communication and
1 LED flash every 5 seconds, 3.9k eol.
EOL resistance: 3.9K Ohms.
External supply voltage (between Terminals TIO and
Til):
DC voltage: 24 volts power limited.
Ripple voltage: 0.1 Vrms maximum.
Current: 90 mA per module maximum.
Temperature range: 32°F to 120°F (0°C to 49°C).
Humidity range: 10% to 93% noncondensing.
Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125" (5.398 cm) deep box.
Page 2 of 4— DN-6999:E • 07/30/2015
NDM.100(A) Dual Monitor Module CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-
The NDM-100(A) Dual Monitor Module is intended for use in 100); 7300-0028:0237 (NDM-100).
intelligent, two-wire systems. It provides two independent two- • MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100);
wire initiating device circuits (lDCs) at two separate, consecutive 22703E Vol. 3 (NDM-100).
addresses. It is capable of monitoring normally open contact fire
alarm and supervisory devices. The module has a single panel- Product Line Information
controlled LED.
NOTE: The NDM-100(A) provides two Style B (Class B) lDC cir-
cuits ONLY. Style D (Class A) IDC circuits are NOT supported in
any application.
NDM-100(A) SPECIFICATIONS
Normal operating voltage range: 15 to 32 VDC.
Maximum current draw: 6.4 mA (LED on).
Average operating current: 750 pA (LED flashing).
Maximum IDC wiring resistance: 1,500 Ohms.
Maximum IDC Voltage: 11 Volts.
Maximum IDC Current: 240 pA
EOL resistance: 47K Ohms.
Temperature range: 32° to 120°F (0° to 49°C).
Humidity range: 10% to 93% (non-condensing).
Dimensions: 4.5° (11.43 cm) high x 4" (10.16 cm) wide x
1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x
2.125(5.398cm) deep box.
NDM-100(A) AUTOMATIC ADDRESSING
The NDM-100(A) automatically assigns itself to two address-
able points, starting with the original address. For example, if
the NDM-100(A) is set to address "26", then it will automati-
cally assign itself to addresses "26" and "27".
NOTE: "Ones" addresses on the NDM-100(A) are 0, 2, 4, 6, or 8
only. Terminals 6 and 7 use the first address, and terminals 8 and
9 use the second address.
CAUTION:
Avoid duplicating addresses on the system.
NOTE: "A" suffix indicates ULC-listed model.
NMM-100(A): Monitor module.
NMM-10OP(A): Monitor module, miniature.
NZM-100(A): Monitor module, two-wire detectors.
NDM-100(A): Monitor module, dual, two independent Class
B circuits.
SMB500: Optional surface-mount backbox.
NOTE: See installation instructions and refer to the SLC Wiring
Manual, PN 52304.
Installation
NMM-100(A), NZM-100(A), and NDM-100(A) modules mount
directly to a standard 4" (10.16 cm) square, 2.125" (5.398
cm) deep, electrical box. They may also be mounted to the
SMB500 surface-mount box. Mounting hardware and instal-
lation instructions are provided with each module. All wiring
must conform to applicable local codes, ordinances, and reg-
ulations. These modules are intended for power-limited wir-
ing only.
The NMM-100P(A) module is intended to be wired and
mounted without rigid connections inside a standard electri-
cal box. All wiring must conform to applicable local codes,
ordinances, and regulations.
Agency Listings and Approvals
In some cases, certain modules may not be listed by certain
approval agencies, or listing may be in process. Consult fac-
tory for latest listing status.
UL: S635.
ULC: S635.
FM Approved.
DN-6999:E • 07/30/2015 - Page 3 of 4
NotifierV and FireWardenOD are registered trademarks and LiteSpeedTm and
FireWatchTM are trademarks of Honeywell International Inc.
02015 by Honeywell International Inc. All rights reserved. Unauthorized use
of this document is strictly prohibited.
This document is not intended to be used for installation purposes. I SO 000i
We try to keep our product information up-to-date and accurate.
• We cannot cover all specific applications or anticipate all requirements.
IINI All specifications are subject to change without notice.
QUALITY SYSTEMS
For more information, contact Notifier. Phone: (203) 484-7161 FAX: (203) 484-7118.
www.notifier.com
Page 4 of 4— DN-6999:E• 07/30/2015
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
7MIW4~
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM
LISTING SERVICE
LISTING No. 7300-0028:0230 Page 1 of I
CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES
LISTEE: NotifierOne Fire-Lite Place, Northford, CT 06472-1653
Contact: Lisa Brant (203) 484-6105 Fax (203) 484-7309
Email: lisa.brant@honeywell.com
DESIGN: Models NMM-100P, NMM-100, and NZM-100 monitor modules; Models NC-100R and
NC-100 control modules; and *NzM100.6 six zone interface signaling device module. Refer
to listee's data sheet for additional detailed product description and operational
considerations.
RATING: 15-32 VDC
INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.
MARKING: Listee's name, model number, electrical rating, and UL label.
APPROVAL: Listed as control unit accessories for use with listee's separately listed electrically
compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details.
XLF: 7300-0075:0185
08-23-11 rev. mt
This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed
the test results and/or other data but does not make an independent verification of any claims. This listing is not
an endorsement or recommendation of the item listed. This listing should not be used to verify correct
operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other
Date Issued: July 01, 2021 Listing Expires June 30, 2022
Authorized By: DAVID CASTILLO,, ME., F.P.E.
Fire Engineering Division