HomeMy WebLinkAbout3657 MONROE ST; ; FPR2017-0361; Permit4City of
PERMIT REPORT Carlsbad
Print Date: 01/25/2022 Permit No: FPR2017-0361
Job Address: 3657 MONROE ST, CARLSBAD, CA 92008-2731 Status: Closed - Finaled
Permit Type: FIRE-Construction Residential Work Class:
Parcel #: 2052302300 Track #:
Valuation: $422,980.00 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Single Family Fire Sprinkli
Applied: 10/30/2017
Issued: 11/07/2017
DEV2017-0089 Finaled Close Out: 12/14/2020
Inspector:
Final Inspection:
Project Title: ST. JOHN GRADING PLAN
Description: ST. JOHN RESIDENCE -SPRINKLER (SFD)
Applicant: FPContractor:
PREMIER FIRE PROTECTION PETRICORP
STEVE PETRI P0 BOX 2027
P0 BOX 2027 LAKESIDE, CA 92040-0921
LAKESIDE, CA 92040 (619) 871-9795
(619) 871-9795
FEE AMOUNT
FIRE NFPA 13D Single Family System (lnsp/Bldg) $121.00
FIRE NFPA 130 Single Family System (Plan Review) $239.00
Total Fees: $360.00 Total Payments To Date: $360.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 f I www.carlsbadca.gov
HYDRONICS: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (63.9)390-5047.
ADDRESS : 12651 RidgetQn Drive, Lakeside CA 92040.
LICENSE : 939040
DESIGNER : STEVE PETRI
PATE : 10-29-2017
FILE
,30 NAM. ST, JOHN RES. TWO H. CALC 1. X 16
LOCATION 3657 MONEQE STREET
FPR20I7-0361
DESIGN DATA,
DESIGN CRITERION: 13D
MIN $PR FLOW 13 Gpm
AREA PER SPRINKLER : 256 Sq Ft
TOTAL CALCULATED AREA : 512 Sq Ft
TOTAL SPRINKLERS CALCULATED : 2
3657 MONROE ST
FLOW DATA
TOTAL SPRINKLER FLOW 26.3 Opm
DOMESTIC DEMAND : 5,0 GPM
TOTAL WATER REQUIRED : 31.3 Gpiu
BASE OF RISER NODE z B
FLOW : 26.3 Gp
PRESS : 22.4 Psi
AUTHORITY HAVING jURISDICTION ; CJ..LSBAD FIRE
PHONE
HYDRONICS; RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL. Page 1
ENGINEERS : PRMIER FIRE PROTECTION. (619)3905047.
ADDRESS : 12651 Ridgeton Drive, Lakeside Ch 92040.
JOB ; ST. JOHN RES. TWO HEAD CALC 16 X 16
DATE: 10-29-2017 FILE: C:\RE$DEN58\STJOHN,RES
I SPRINKLER MUF VIKING
MODEL : VK494
I DENSITY 0.05 Gpa/Sq Ft FIXED PRESS : 6.0 Psi
AREA /$PR 256 SqFt DESIGN AREA :512 SqFt
I SPRINKLER Q ; 1.0 GPM
NODES : 10 PIPES : 9
SOURCE I STATIC : 48 Psi RESIDUAL 47 Psi FLOW : 31 Gpm
NODE ELEVATION K-FACTOR PRESSURE DISCHARGE
NO. Feet Psi. GPM ----------------------------------------- ----------------
1 910 4.90 7.0 13.0
2 9.0 4.90 7,3 13.3
3 9.0 8.3
4 9.0 14.2
T 9.0 16.4
8 0.0 22.4
A 0.0 2611 DONE 5.0
Al 0.0 26.9
N 0.0 32.9
S 0.0 SOURCE 35.4 31.3
SPRINKLERS FLOWING
AREA PER SPRINKLER
TOTAL DESIGN AM
MIN SPRINKLER FLOW
REQUIRED DENSITY
COMPUTED DENSITY
TOTAL SPRINKLER FLOW
TOTAL DOMESTIC FLOW
TOTAL WATER REQUIRED
TOTAL SPRINKLER PRESS
FIXED PRESS L088
2
256
512 8q Ft
13 Gm
0.051 Gpin/Sq Ft
0.051 Gprn/Sq Ft
26.3
519 GPM
31.3 opm
29.4 Psi
6.0 Psi
Copyright (2012)
SUPPLY PRESS AVAILABLE : 47.0 Psi bY
DEMAND PRESS REQUIRED : 35.4 Psi Hydronics Engineering
PRESSURE CUSHION : 11.6 Psi 34119 Fremont 81, Suite 609
Frernont, CA, 94555
MAXIMUM VELOCITY .2.9 If/S (800) 845-9819
HYDRONICS: RESIDENTIAL FIRE SPRINLER HYDRAULICS 5.8 - SUBMITTAL. Page 2
ENGINEERS ; PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : ST. JOHN RES. TWO HEAD CALC 16 X 16
DATE: 10-29-2017 FILE: C:\RE$DEN58\STJOHN.RES
PIPE BEG FLOW Kr-FACTOR LENGTH C-FACTOR PRESSURE
NO. GPM FITTING TYPE FTG FRI-LOSS (Psi)
END DIAMETER TOTAL (Psi/Ft) ------------------------ - ----------------- ------------------------------------
q,- 13.0 Km 4.90 L= 33.0 Pt 7.0 Pt 7,0
Q= 13.0 F4R3 9.0 C= 150 Ps 0,0 PV -0.3.
Vel= 4.4 P 1.101 TL. 42.0 0,0307 Pf 1.3 Pn 6.9
3 Pt 8.3
- --------
2 q 3.3.3 Km 4.90 Lm 24.0 Pt 7.3 Pt 7.3
2 Qm 13.3 F B2R 7.0 C= 3.50 Ps 0.0 Pv -0.3.
Velw, 4.5 Pm 1,3.01 TL= 31.0 0.033.9 Pf 1.0 Pn 7.2
3 Pt 8.3
----------------------------------- - ----------------------------------------
3 0.0 0.00 L= 39.0 Pt 8.3 Pt 8.3
3 Q 26.3 F 9R F= 14.0 Cp 3.50 Fe 0.0 Pv -0.5
Ve3. 8,9 D= 1.103. TI .0 0,13.27 Pf 6.0 Pn 7.8
4 Pt 3.4.2
--------- --------------- . ----------- rp.--------------- --------------------
4 cr 0.0 K= 0.00 L= 13,0 Pt 3.4.2 Pt 14.2
4 Q= 26.3 F= LR 6.0 C= 150 Fe 0.0 Pv -0.5
Vol;;.9 Dw 1.3.01 TTiv7 19.0 0.3.127 Pf 2.1 Pr 13.7
T Pt 3.6.4
-------.----------p -------------------- --- -pC' ?' - - -p 'PP ------------ -----------------
T 04 K= 0.00 L= 9.0 Pt 3.6.4 Pt 16.4
6 Q 26.3 Fm SCRR F 10.0 C= 150 Pe 3.9 Pv -0.5
Velzp 8.9 P 1.103. TL= 19.0 0.1127 Pf 2.1 Pn 15.8
B Pt 22.4
--- - - - - - - - ------------ --- - -
0.0 K 0.00 L= 5.0 Pt 22,4 Pt 22.4
7 Q 26.3 F LLL FM 3.5.0 c 150 Ps 0.0 Pv -0.0
Vol 3.0.8 pm 0,995 TL= 20.0 0.1846 Pf 3.7 Pn 21.6
A Pt 26.3.
-------p.'----------------------------------- ---------------------------
era 5.0 PO L 20.0 Pt 26.1 Pt 26.3.
8 Q 31.3 F= LLEECC F 3.2.0 C= 10 Ps 0.0 Pir -0.2
Val 5.3. D= 1,590 TL= 32.0 0.0260 Pf 0.8 Pn 25.9
Al Pt 26.9
--------------------------------- ----------------------------------------
Al Qp 31.3 Pt 26.9
MET FIXED PRESSURE LOSS Valve 6.0
N Pt 32.9
It - - -p -------------------- ". -------- -p ,, -p - - -p - - -p - - -p -------
N q 0.0 K 0.00 LVA 10.0 Pt 32.9 Pt 32.9
8 Q- 31.3 F= G F 0.0 C 150 Ps 0.0 Vv -1.3.
Ve3. 3.2.9 Dm 0.995 TZ 10.0 0,2547 Pf 2.5 Pn $1.8
S Pt 35.4
p.fl
- ----- --------------
Q $1.3 <<< 50URC-9- >>> Pt 35.4
..............................................................................
E45-Elb LxPO-Zlb BT ecb RTeeRw CCoi.P19 SSwgChk GGatVlv
HYDRONIC$: RESIDENTIAL FIRE SPRINKLER HYDRAULICS 5.8 - SUBMITTAL.
ENGINEERS : PREMIER FIRE PROTECTION. (619)-390-5047.
ADDRESS : 12651 Ridgeton Drive, Lakeside CA 92040.
JOB : ST. JOHN RES. TWO HEAD CAIC 16 X 16
FILE : C:\RESDEN58\STJQBN.RES
DATE 10-29-2017
PSI FIRE SPRINKLER HYDRAULIC GRAPH
100
90
80
70
60
50
40
30
20
3.0
Q 100 150 00 250 300 350 400 450 500
FLOW GPM
0- -Q Water Supply
Static : 4. Psi
Resid : 47 Psi
Flow ; 31 Gm
Water Demand
Av3. press : 47.0 Psi 0 33. opm
Req Press 35.4 Psi @ 31 Gn.
Press Cuss; 11.6 Psi
Copyright; Hydronics Engineering, 2012.
34119 Fremont Bi, Suite 609
Fremont, CA 94555.
(800) 045-9819
Page 1 of 6
The ViKing Corporation, 210 N Industrial Park Drive Hastings MI 49058
Telephone: 269-9459501 Technical Serve 87$e45464 Fax; 209-010,1600 Email; techsvcsViKiflgCOrP.cQm
I. DESCRIPTION
The Viking Microfastl QulqK Reponsa Pendant prinidar VKQ a
therrnosensltive glass bulb spray sprinkler available with yrious finishes
and temperature ratings to meat design requirements The spec PQlyeter
Polytetrafluoreethelyne (PTFE) and Eleotrolass Nickel PTFE (N 1) omatings
can be used in decorative applications where colors era desired. In addition,
these coatings have been Investigated for inctallation in corrosive atmospheres
and are listed/approved as corrosion resistant. as Indicated In the Approval
Charts, (Note: FM Global approves lIRNT finIsh as earroIon resisanL IM
Global has fl3 approval classification far WE and Polyetar coengs oa Qorro
alan resiatent)
2. LISTINGS AND APPROVALS
£ .
ct$Lus Listed: Category VNIV
. M Approved; Class Sorles, 20Q
VdS Approved: Certificates 04494QO9 and 0414010
LPC8 Approved
CE ertifie; Standard EN 1221 CertIficeta of conform 0e32CPD2001
Rafr toApprovol Chart I and agn Criteria cLJLua Listing requirements, and rater to Approval Chart 2 and Design Criteria
for FM Approval requirements that r, ust be foflwad
. TECHNICAL. PATA
specifications:
Minimum Operting Pressure: I poi (M bar) VIking TechnIcal Data may be found an
Rated to 175 psi (12 bar) water worKg pressure The Viking CorporatIon's Web site at
Factory tested hydrostatIcally to SQQ psi (4 bar) hflp;llwww,vikhlggrouPiflcQm.
Thread size: lIZ NPT, 15 mm BSP The Web site may Include a more recent
Nominal K-Factor: 5.6 U. (60 matric) edition of this Technical Pata Page.
Glassbulh fluid temperature rated to 65 QF (55 C)
Overall Length: 21/4" (58 mm)
WLus Listing, FM Approval and NFPA 15 installs recipre a minimum of V psi (0,0 ar), I he rcllrurnum operating pressure for LP013 and CE
Approvals ONLY is 5 psi (05 her).
Material Standards;
Frame CastIng; Brass UN484400 or QM Dron
Deflector: Phosphor 5ronz#4 1)NS0.50O0 or Copper UNC1500
Glass nominal 3 mm diameter
8elleville Spring $ellng Assembly: Nickel Alloy, coated on both sides with PTF Tap
Screw: Prp.53 UNS 56000
Pip Cap and Insert Assembly: Cpper UNSi 1000 end Stainless Steal U 0400
For LCoated iksBelleville Spring 1pQS rewNleIal Plated Pip Ca PTF Coated
jQato orinl elleville Spring$xposed
Bellevilleor ENT Coated rio~ler% SprIngxposed Screw and Pipcap NT plated.
Ordering Information; (Also refr t the current Viking price list)
Order Quick Response Pendant Sprinklers by firt adding the appropriate suffix for the sprinkler finish and then the appropriate
suffix for the temperature rating to the sprinkler base part number.
Finish Suffix; Brass A, Chrome q F, White Polyester M-/W, Black Polyester F, M/B, Slack PTFB N, and ENT = JNJ
Temperature Suffi: 15 9F (68 *C)z A. 155 OF (68 C) 0, 175 F (7 Q) w D 200 F (95 C) , 256 IF (141 °C) P G
For example, sprinkler Vr302 with a Brass finish and a I55 or, ss 'C) temperture rating t., Part No 12979A6
Available Finishpai And TemperatureRatings: Refer to Table 1.
Accessories (Also refer to the "Sprinkler Accassorias! section of the Mking, data bock)
Form No P033514 Rev 142 (Added 08662B and 18021)
Page 2 of 6
N
MICROFAST® QUICK
*TECHNIGAL DATA RESPONSE PENDENT
SPRINKLER VK302 (K5.6)
-
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone; 699454501 Technical Services 8773845464 Fax 26M18.1680 Email:
Sprinkler Wrenches:
Standard Wrench: Part No. 10896W/B (available since 000).
Wrench for Recessed Pendent Sprinklers-, Part No. 16036WI8* (available since 2011)
C Optional Protective Sprinkler Cap Remover/Escutcheon Installer Too Part No 15915 (available since 2010) *4 W ratchet is required (not available from Viking).
*"Allows use from the floor by attaching a length of V diameter CPVC tubing to the tool. ldcal for sprinkler cabinets, Refer to Byliotia F05180e.
-Sprinkler Cabinets:
A. Six-head capacity; Part No, 0174A (available since 1971)
B, Twelve-head capacity: Pail No. 01725A (available since 1971)
4. INSTALLATION
Refer to appropriate NFPA Installation Standards.
S. OPERATION
During fire conditions, the heat-sensitive liquid in the glass bulb expends, causing the glass to shatter, releasing the pip cap and
sealing spring assembly, Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern
to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements,
AVAILABILITY
The Viking Microfase Quick Response Pendent Sprinkler VKSOZ Is available through a network of domestic and international dis-
tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation,
3. GUARANTEE
For details of warranty, refer to Vikings current list price schedule or contact Viking directly,
Protective Sprinkler .Wrench Flat
Clip
-i.-. - Protective Sprinkler
Cap
Figure 1: Standard Sprinkler Wrench 1086W/3
Form No, F033314 Rev 14.2
Page 3 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-945-9501 Technical Services: 877-3845464 Fax: 269-818-1680 Email: techsvcsvikingcorpcom
1 Ordinary 155.9F (57 OC) 100OF (38 OC)Orange
Ordinary 156 (68 00) 100 OF (38 C) Red
Intermediate 176 OF (79 00) 150 OF (65 °C) Yellow
Intermediate 200 °F (93 QQ) . 160 °F (65 °C) Green
.._ High 286 °F (141 °C) 225 °F (107 00) Blue
-.-.,---
Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black. PTF, and ENT
CorrosIgnResIstant Coatings': White Polyester, Black Polyester, and Black PTF. ENT in all temperature ratings except 136 OF
Footnotes
The sprinkler temperature rating is stamped on the deflector,
Based on NFPA-1. Other limits may apply, depending on fire loading, pprinRlef location and other requirements of the Authority Having jurisdiction,
Refer to specific installation standards,
The corrosion-resistant coatinge have passed the standard corrsipn teat required by the approving agencies indicated in the Approval Charts. These
tests cannot and do not represent all pD5slle corrosive environments Prior to Installation, verify through the end-user that the coatings are com
patible with or suitable for the proposed environment. For automatic sprinklers the coatings indicated are applied to the exposed exterior surfaces
only. Note that the spring Is exposed on sprinklers with Polyester, PTFE, and ENT catinga. For ENT coated automatic sprinklers, the waterway is
coated
..-.-........-
Sprinkler wrench 1
for recessed pc
sprinklers
A 1/2" ratchet is
(not available fror
,
Carefully Wide the wrench sideways around -4111114 the protective cap, ensuring engagement witF
the sprinkler wrench flats
Figure 2: Wrench 1506WIa for Recessed Perdent Sprinklers
Form No. FQ33314 Rev 14,2
Page 1 of 5
The Viking Corporation, 210 N industrial Park Drive, Hastings MI 49058
Telephone; 2699459501 Technical Services,. 8774045464 Fax: 269-8181680E-mail, techsvcsvlkingcorp.com
Visit the Viking vebsite for the latest edition of this technical data pager
1, DESCRIPTION
Viking Freedo mP Residential Concealed Peridert Sprluller 'JK494 is a small
theimosensitive, glass-bulb residential .prinkle.rdesignad for intailation on concealed
pipe systems where the appearance of a smooth ceiling is desired. The or!tice design,
with a K-Factor 014.9 (70.6 metric*), allows the sprinkler's efficient use of available
water supplies for the hydraulically designed fire-protection system. The fast
response glass bulb operating element and special detltor characteristics meet
the challenges of residential sprinkler standards.
The sprinkler is preassembled with a threaded adaptor for installation with a
low..profile smalldiameter cover assembly installed flush to the ceiling. The two-
piece design allows instailation and testing of the sprinkler prior to intal!ation of
the cover plate. The push-on', thread-off' design of the concealed cover plate
assembly allows easy installation of the cover plate after the system has been
tested and the ceiling finish has been applied, while also providing up to W (13
mm) of vertical adjustment. The cover assembly can be removed and reinstalled,
allowing temporary removal of ceiling panels without taking the sprinkler system out
of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating
has been investigated for installation in corrosive atmospheres and is CUL-US-EU
Listed as corrosion resistant as indicated in the Approval Charts. The E.NT finish is
only available for the sprinkler assembly, the cover plate is not plated.
LISTINGS AND APPROVAL
Q UL Listed (CULUSEU): Category VKKW
u Refer to the Approval Charts and Design Criteris on for ULU$=U Listing
requirements that must be followed,
3 TECHNICAL DATA
Specifications
Minimum Operating Pressure: Refer to the Approval Chart
Maximum Working Pressure: 17§ psi 02 bar), Factory tasted hydrotaticeliy to 500
psi (34.5 bar).
Thread size: 1/2" (15 mm) NFl
Nominal KFactor: 4.9 U$, (70.6 metric*)
Glass-bulb fluid temperature rated to .65 F 05 °C)
Metc K4actpr measurement shown is In Bpi, When pressure is measured In We, divide the metric
K-factor shown by 100,
Material Standards:
Sprinkler Body; Brass LJNSC84400 or QM Brass
Deflector: Phophor Bronze UN$051000
Deflector Pins; Stainless Steel UNSS30200
Buttqn: Brass LJN$..036000
Pip Cap and insert Assembly: Copper UFSC11000 and $5 UN8430400
Compression Screw: 18..8 Stainless Steel
Yoke: UN$S43000 Stainless Steel
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape
Cover Adapter Cold Rolled Steel LJNS 1Q080, Finish Clear Chromate over zinc Plating
Shipping Cap: Polyethylene
Cover Plate Materials:
Cover Plato Assembly: Copper UNSC11000 and Brass UNSQ28800
Spring: Beryllium Nickel
Solder: Eutectic
Ordering Information: (Al refer to the current Viking price list.)
Viking Freedoms Residential Concealed Pendant $pnnkler VK494 and Cover Plate Assembly mast he ordered separately
Sprinkler; Order Sprinkler VK494 by first addipg the apprprlte suffix for the prinkler finish and then the appropriate suffix for the
temperature rating to the prinKler base part number.
Finish Suffix: Brass A and NT 4N
Temperature Suffix: 155 F (88 .) B, 175 F (79 ) D, 00 ¶ aa C)
For example sprinkler VK494 with a Brass finish and 'a 200 F (93 °C) temperature rating Part No 20759AE
Cover Plate Assembly: Base Part No. 13104 (23I4' diameter) Base Pert No, 1642 (35/16" diameter), or Base Part No, 15394
(square cover plate, 35I16" diameter)
Form No, F012116 16.06.27 Rev 161 (New product, new page)
Page 2 of 5
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone; 2699459501 Technical Services; 77384"5464 Fax., 269-8181680 Email: techsvcs@vikingcorpcom
Visit the Viking website for the latest edition of this technical data page.
Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover
temperature rating to the base part nurnbr:
Finish Suffix: Polished Chrome q F. Brushed Chrorno Bright Brass = B, Antique Brass B4A, Brushed Brass B'/B, Brushed
Copper = E-I8, Painted White M,/W, Painted Ivory M/i, Painted Black M../B
Temperature Suffix: 135 °F167 °C = A
For example cover 13504 with a Polished Chrome finish and a 135"F,157 C temperature rating 13504FA
Available Finishes And Temperature Ratings: Refer to Table I
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book) $prinkler Wrenches**:
A. Heavy Duty Part No, 14047W/B (available since 006), or
5. Head Cabinet 'Wrench Part No. 14031 (available since 006)
C, Optional Concealed Cover Plato Installer Tool Part No. 1441 (available since 2007)
D Optional Large Concealed Cover Plate Installer Tool Part No. 14867(availaple since 2007)
**Requires a W ratchet (not available from Viking), Optional for removal of the prtective cap. Ideal fr sprinkler cabinets.
Sprinkler Cabinet: Part NQ. 01731A (available since 1971)
INSTALLATION
Refer to appropriate NFPA Installation Standard
OPERATION
Durinre conditions, when the temperature around The eprinklr epproches it operating temperature, the cover plate detaches,
releasg fire the deflector. Continued heating of the exposed sprink.10 causes the hoatenitive liquid in the glass bulb to expand,
causing the glass to shatter, releasing the yoke and pip cap and sealing spring assembly.. Water flowing through the sprinkler
orifice strikes the deflector, forming a uniform spray pattern over a specific area of coverage determined by the water supply pres-
sure at the sprinkler to extinguish or control the fire.
INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements,
AVAILABILITY
Viking prinkIer Model VK494 Is available throughp network of domestic and international distributQrs, See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation,
GUARANTEE
For details of warranty, refer to Viking's current list price schedule or contact Viking directly,
f _ •. : 'hj. . - ¶
Ordinary 155°F(68°C) 100°F(38"C) 135°F(57QC) 13504 13642 15394 f Red
Intermediate 175 OF (79 C) 150 °F (65 "C) 135 OF (57 "C) 13504 13642 15394 Yellow
intermediate 200 OF (93 "C) 150F(65_°C) 135 OF (57 "C) 13504 13642 15394 Green
-
Sprinkler Finishes: Brass and ENT _______
Cover Plate Finishes Polished ChrQme Brushed Chrome Bright Bless Antique Brass, Brushed Brass Brushed Copper Painted
White, Painted Ivory, or Painted Black
Corrosion Resistant Coatings5: ENT
Footnotes
'The sprinkler temperature rating is etamped on the deflector.
Based on NFPA-13, NFPA 13R, and NFPA 130. Other limits may apply, depndiny on "ire loading, sprinkler location, ad other requirements of the Authority Having
Jurisdiction, Refer to specific Installation standards.
Maximum ambient temperature for cover assembly is 100 OF (38 "C),
Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.
The corrosion resistant coatings have passed the 6tanqaro corrosion test reqilred by the approving agenolpq lnda.ted in the Approval Charts., These teats cannot and
do not represent all possible corrosive environments, Pclr to Installation, verify through the enduser that thO coetinas are compatible with or suitable for the prpposd
environment. For automatic sprinkloro., the ENT coating is applied to all exposed exterior surfaces, including the waterway. For ENT coated sprinklers, the Belleville spring
is exposed.
Form No, F 012116 16.06.27 Rev 16.1
Page a Qf 5
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269945.9501 Technical Services; 877484-5464 Fax: 269.818-1680 Email: techsvcsvikingcorp.com
Visit the Viking website for the latest edition of this technical data page.
-rreT-rwIv.
Sprinkler Base
.- T SIN NPT Thread Size r - .. -—r'— -.---
r—r— T
- Nominal K-Factor Maximum Water Wor-
.- Part Number 1 I Inches I mm UPS. metric 2 king Pressure
20759 4J :J ... V2L 15 49 70.6 175 psi (12 bar) -
Max. Coverage
8
Flow Pressure Listings and Minimum Area
(LPM) PI 'b (bar) Deflector to Installation A I " pprova S Spacing
.,
Ft. X Ft. Ceiling Type Ft.
155 °F8 175°F ç OP. 200°F93°G -
(m X m) Temperature Rated Sprinklers
12X12 13 7.0
49.2)(48)
14X14 13 TO
(4.3X4.3) (49.2) (0.48)
Refer to. Figure 2
Concealed with
Cover Plate & See Footnotes 7,10, 11 8 16 X 16 .-.
--.
13 7,0
(4.9 X 4.9) (49.2) (0.48)
See Footnote 9.
Assembly.
17 -.
(5X5.5) (64,4)
20X20 20 16.7
(..1X6.1) (75.7) (1.15)
- -. - ----------------------------------------n. -.---..-- n . —n-- --. ---- -------. -- -
Footnotes
Part number shown is the base part number, For complete pert number, refer to current Viking price schedule.
2 Metric 1(-factor measurement shown is when pressure is measured in Bar. Wnii pressure is measured in kPa, divide the metric K-factor shown by 10.0.
This chart shows the listings and approvals available at the time of printing. Other approvals may be in process, Check with the manufacturer for any additional approvals,
Refer also to Design Criteria,
Listed by Underwriter's Laboratories, Inc. for use in the U.S., Canada, and Puropean Union.
Meets New York City requirements, effective July 1, 2000.
6 For areas of coverage smaller than shown, use the 'Flow' and Pressure' for the next larger area listed. Flows and pressures listed are per sprinkler. The ditance from
sprinklers to walls shall not exceed Qne hglf the sprinkle!- spacing indicated for the minimum "Flow" and "Pressure" used,
Cover Temperature Rating is 135°F (67 CC). Cover Part No. 136041, 136421 (large diameter), or 153941 (square cover plate).
Other paint colors are available on request with the same listings as the standard finish colors, Listings and approvals apply for any paint manufacturer, Contact Viking
for additional information, Custom colors are Indicatad on a label inside the cover aasembly. Refer to Figure 3.
'° Accepted Cover Plate Finishes re Polished Chrome, Biuhed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted lvo, or
Painted Black
11
.
C-UL•-US-EU Listed as corrosion resistant. Eleatroless NicKel PTFE (ENT)
Form No, F012116 16,0627 Rev 16,1
Page 4 of 5
N IKI FREEDOM5 RESIDENTIAL TECHNI'CAL DATA CONCEALED PENDENT
- SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 269-9454501 Technical Services: 877-384-5464 Fax: 69-818-1680 email: techsvcsvikingcorp.com
Visit the Viking websita for the latest edition of this technical data page.
UL,Uta
When using Viking Residential Concealed Pendant Sprinkler VK494 for systems designed to NFPA 130 or NFPA 1 3R, apply the listed area of cover
age and minimum water supply requiremnts shown in the Approval Chart,
or s ems desioned to NFPA The number of design sprinkler Is to be the four contiguous most hydraulically demanding sprinkler. The minimum
required discharge from each a the four sprinklers is to be the greeter of the following:
The flow rates given in the Appraval Chart for NFPA 130 and NFPA 13R applications for each listed area of coverage, er
Calculated based on a minimum discharge of 0 1 ppm/sq ft over the design area in accordance with sections 8.542.1 or 8.42.1.2 of NFPA 13
Minimum distance between residential sprinklers: 8 ft. (2.4 m),
NOTE: Concealed sprinklers must be Installed In neutral or negative pressure plenums only.
IMPORTANT Always refer to Bulletin Form No F 08041 Best Practices for Residential Sprinkler Handling and Installation
Also refer to Form No. F 080614 for general care, installation, and maintenance information. Viking sprinklers are to be In-
stalled in accordance widi the latest edition of Viking technical data, the appropriate standards of NFPA and any other similar
Authorities Having Jurisdiction, and also with the provisions of governmental codes, ordinanc, and standards, whenever
applicable. Final approval and acceptance of all residential sprinkler installations must be obtained from the Authorities
Having Jurisdiction.
Sprinkler and Adapter Assembly
Protective cap removed
Use wrench 14047W/13'*
w .
Sprinkler Wrench
. Part No. 14047 WiB
Step 1:
Carefully slide the
wrench sideways around
the deflector and pins
2-1/4" (57 mm)
diameter opening
required In the
coiling,
Step 2, t t
Carefully press the wrench upward and
turn slightly to ensure engagement with
the sprinkler wrench flats.
NEVER install the sprinklr by applying the Installation
wrench across the frame arms DO NOT overtigh.ten.
Use only the designated sprinkler wrenches, Viking
Part Numbers 14047W18** or 14031**. A leek tight seal
should be achieved by turning the sprinkler clockwise
I to 1e112 turns beyond finger tight
Sprinkler
wrench flat
Sprinkler
frame arms
Figure 1 Sprinkler Installation and Proper Wrench Usage
** A 1/2" ratchet Is requirpd (Not available from Viking)
Form No. F_012116 18.0627 Rev 161
Page 5 of 5
FREEDOM® RESIDENTIAL IF(I CONCEALED PENDENT
U - SPRINKLER VK494 (K4.9)
The Viking Corporation, 210 N Industrial Park Drive, Hastings Ml 49058
Telephone: 26$-9459801 Technical Services: 877-3844464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the Viking webte for the latest edition of this technical data page,
RL
1/211 05 mm) NPT 29Ii6" (65 mm)
Maximum 2-1/18" (52 mm)
Minimum
2-3/411 (70 mm) or
NOTE: Upon sprinkler activation, the deflector descends 35i16" (84 mm)
to approximately 13/16" (21 mm) below the sprinkler body.
Figure 2: Sprinkler Dimensions and Cover installation
All custom color painted cover plates will have en
identifying label affixed to the inside of the cover that
indicates the custom color and will have a representative
sample (a paint dot) of the paint on the label.
Figure 3: ldenficatIon of Custom Paint for Concealed Covers I
34/16" (84 mm)
Figure 4; Square Cover Assembly 15394
Form No. F_012116 16.06.27 Rev 18,1 (New product, new page)