PERMIT REPORT Cdisb
( i of
ad
Print Date: 01/26/2022 Permit No: FPC2019-0247
Job Address: 3457 VIA MONTEBELLO, # 158, CARLSBAD, CA 92009-8491 Status: Closed - Finaled
Permit Type: FIRE-Construction Commercial Work Class: Fire Sprinklers
Parcel #: 2230530900 Track #: Applied: 10/23/2019
Valuation: $43,300.81 Lot #: Issued: 11/21/2019
Occupancy Group: Project #: Finaled Close Out: 02/28/2020
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #: Inspector:
Plan Check #: Final Inspection:
Project Title:
Description: EAST HOLISTIC MASSAGE -SPRINKLER TI (15 HEADS)
FPContractor:
BRIAN SULLIVAN
1975 SPANISH OAK WAY
VISTA, CA 92081-7383
(760) 716-9226
FEE AMOUNT
FIRE NFPA 13 or 13R System 7 - 100 heads $553.00
Total Fees: $553.00 Total Payments To Date: $553.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 1 760-602-8561 1 I www.carlsbadca.gov
I
Not less than Wood Floodng 2 noimnal width Product Features
4L4 I No pre-drilling required.
L11P
Not less than 'Quick to install using the Sammy 3' flsnsflal
7Do-01.Sheetrock
Nut Driver with an 18V cordless thickness (2-1/21
(depth or ode Wood Jest drill/driver.
of ne&ei member) - - F..:: Saves time from traditional
methods. I Ceiling
'Reduces installation cost
Made in the U.S.A.
'?'/'Z-'-1' •.lr.j •od
ffi5f
i ig 8IkU/ 'M0
1/4' 8002957 GST 100 1/4 xl' 210 (7/16 OSB) 25 125
- -
114 8003957 GST 200 114x2 1760 (Fir) 25 125
1/4" 8004957 GST300 114x3' 2060 (Fir) 25 125
318' 8006957 GST .75 1/4 x 3/4' 564 (3/4' Ply) - - - 25 125
3/8' 8007957 GST 10 1/4 x1' 300 25 125
Cc> 3/8'.: 8008957 GST 20 1I4x2' 1760 (Fir) - - .850 -- .147525 125)
3/8 8068925 GST2O-SS 1/4x2 1760 (Fir) - 850 25 - 125
3/8' 8009925 GST 25-380 318x2-112' 2113 (Fir) 1500 25 125
3/8' 8010957 GST 30 - 114x3' 2060 (Fir) 1500 1475 25 125
318' 8069925 GST 30-SS 1/4 x 3' 2060 (Fir) . . - 25 125
8 V 8011925 GST 40 V 114x4' . - 2180 (Fir) .. - - . V 125
3/8" 8012925 GST 60 1/4x 6' 2230 (Fir) - . - 25 125
V 1/4' 8013925 GST2 - 114x2' 1760 (Fir) V - •V -. 25 125
1/2' 8014925 GST 2.5-380 318x2-11Z 2113 (Fir) 25 125
1/2' 8015925 GST3 114x3' 2275 (Fir) - 25 125
1/2' 8016925 GST4 114x4' 2180 (Fir) - 25 125
1/2 8017925 GST6 1/4x6 2230 (Fir) 25 125
A #14 Black
Nut Driver
Part # 8113910
— i
#14 SW Red
Nut Diiver
Part# 8114910
Product Features
Eliminates distortion of threaded rod. • Saves time from traditional methods.
'Accommodates up to 3W x 12 pitch roof. • Reduces installation cost.
'Allows 17 deflection from vertical. • Made in the U.S.A. I
r V 11 ILL litp lsirKw
Lhl 4 J14 '1il1 3tTt 10y
- 3/8 8139957 SN-GST20 1/4x2" 1.257 (Fir) 1050 - 1475 25 125 125
318 8141957 SH-GSI30 1/4x3' 1720 (Fir) 1500 1475 25 125
#14 Black
V V V Nut Driver SPECIAL NO DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe instatlabon each time. When the face of the driver comes into Pant #8113910
contact with the material you are installing into, continue drilling until nut driver spins free. Installafon is then complete. Warranty requires the use of the appropriate nut driver for installations.
TI51,
A
Not less than ' nominal width ' Product Features
(1-1121 up to 3-112' pipe; not less than
3' (2-1/2') nominal width 4' & r pipe 'No pre-drilling required.
Minimum 2-112'fmm bottom for
Floorjoist Quick to install using the Sammy
brarroti toes. Minimum 3' from Nut Driver with an 18V cordless
bottom for main lines. Exception: This drill/driver.
requirement that not apply to Tor
thither nailing strips renting on top of
steel beams. • Saves time from traditional
f
methods.
'Reduces installation cost.
Made in the U.S.A.
L Ii 1
ffllUrIffI 1a8 0s
1 Car8Efl Gt1IId0 itiflj
'I
1/4' - 8018957 SWG 100 1/4x1' 622 (Fir) 25 125
1/4" 8019957 SWG 200 1/4x2' 1725 (Fir) 25 125
. 3/8' V 8020957 SWG 10 1/4x1" - - 622 (Fir) 300
V
25 125
-
3/8 8021957 SWG 20 114x2 1725 (Fir) 1050 25 125
8073925 V SWG 20-SS 114x2' - 1725 (Fir) 850 25 - 125 -
#14 SW Red - , 3/8' 8022925 - - SWG 25-380 3/8 x 2-112' 2249 (Fir) V 1500 V V 25 125
Nut Driver 3/8' 8023925 SWG 30 1/4 x 3" 1884 (Fir) 25 125
Part#8114910 -
iA1U1IONEPS !A JMTOVWOOOV&ST€EL: 1t4STALLATJON STEPS 8 UMMR,INTO WOOD & STEEL
Insert the appropriate nut driver into a 3/8" or 1/2" portable drill.
Insert the SAMMYS into the #14 (black) nut driver (p/n 8113910). Drill
should be in a vertical position.
Push the face of the nut driver tight to the member When the
nut driver spins freely on the SAMMYS, stop drill and remove.
The SAMMYS is now ready to receive 1/4", 3/8", 1/2" or metric
all thread rod, bolt stock. (The 1/2' requires the #14S W red nut driver)
Note: When installing DSTR, follow the above instructions,
then add retainer nut and torque to 20 foot lbs. for maximum
pullout in purlin steel.
Insert the appropriate nut driver into a 318" or 1/2" portable drill.
Insert the SAMMYS into the #I4SW(red) nut driver (p/n 8114910). With drill
unit in a horizontal position and at a right angle to the structural member
begin installation.
When the nut driver spins free on the SAMMYS, stop the drill and
remove.
The unit is now ready to receive 1/4", 318" or metric all thread rod or
bolt stock
Note: When installing SWDR, follow the above instructions, then add retainer nut
and torque to 20 foot lbs. for maximum pullout in purlin steel.
SPECIAL NUT DRIVER SYSTEM: The nut drivers were designed with a unique spin-off feature which provides a fast and safe installation each time. When the face of the driver comes into
contact with the material you are installing into, continue drilling unril nut driver spins free. Installation is then complete. Warranty requires the use of the appropriate nut driver for Installations.
SiWLifYS® [FOR 'R5OOI
MtTht
~fz ~~
od ________________________________________
___________
i,IcIcnLesSd
8007957 GST 10 318' Vertical CPVC 1-1/7 300 1-1/2"
8020957 SWG 10 3/8' Horizontal CPVC 1-1/2" 300 1-112"
8008957 GST2O 3/8" Vertical 2-1/2" 850 1-1/7 4' 1475 1-117
8068925 GST2O-SS 3/8" Vertical 2-1/2" 850 1-1/7
8010957 GST3O 3/8" Vertical 4" 1500 1-1/2" 4' 1475 1-112"
8009925 GST25-380 3/8" Vertical 4' 1500 1-1/2"
8022925 SWG 25-380 318" Horizontal 3-1/2' -4" 1500 1-1/2"
8021957 SWG 20 3/8" Horizontal 2-1/7-3""" 1050 1-1/2" -
8073925 SWG 20-SS 3/8" Horizontal 2-1/2" 850 1-1/2"
8139957 SH-GST2O 3/8' 17" Angle off Vertical 1050 1-1/2" If 1475 1-1/2"
8141957 SH-GST3O 3/8' Ir Angle off Vertical 1500 1-112" 4" 1475 1-1/2"
SIkI1YS® FOR STEEL yi:HsLIL
t1o M5IR M6UIit ax
Size Direction pipe Size [hickness
8038957 DSTR 1 3/8' Vertical 4" 1500 .035' 4" 1475 .105'
8037957 DSTR 1-1/2 3/8" Vertical 4' 1500 .035" 4" 1475 .105"
8039957 DSTR 516 3/8' Vertical 4" 1500 .037" 4' 1475 .105"
8045957 DST 516 3/8" Vertical 4' 1500 .188" 4' 1475 .188"
8046957 TEKSO 3/8" Vertical 4" 1500 .250" 4' 1475 .188"
8055957 SWDR1 3/8' Horizontal 4" 1500 .037" 4" 1475 .060"
8056957 SWOR 516 3/8" Horizontal 4' 1500 .037' 4' 1475 .060"
8054957 SWDR 1-1/2 3/8" Horizontal 4" 1500 .037" 4' 1475 .060"
8137957 SH-DSTRI 3/8" 17" Angle off Vertical 4' 1500 - .035" 4" 1475 .105"
8150922 XP 20 3/8" Vertical 2-1/2' 850 .027"
8153922 XP 35 3/8" Vertical 4' 1500 .060"
8294922 SXP 20 3/8" Vertical or up to 45" 2" 750 .027" 2" 635 :029"
8295922 SXP35 3/8" Vertical orupto89" 3-1/2" 1250 .060" 2" 635 .029'
8293957 SWXP35 3/8' Horizontal 3-1/2" 1250 .060'
SAIkflflIYS® FOR COflCRETE 1I9 1lI!
@39 MM 1!J
a.ft Ramol J((D)
8059957 CST 20 3/8" Vertical 4" 1475 3000
8061957 SWC 20 3/8' Horizontal 4" 1475 3000
8150922 XP 20 3/8" Vertical 2-1/2" 850 Pro-Pour Structural @ 3000psi
8150922 XP 20 3/8" Vertical 2-1/2" 850 Post-Pour Range II LWC 15 35 PCF Øbs/t13)
TRUSS-7
8296900 HD38TC 3/8" Top Chord 1200 6075 Maximum 4' Schedule 40pipe
8297900 HD38BC 3/8" Bottom Chord 1200 6075 Maximum 4' Schedule 40 pipe
8198900 HD12CZP 1/2" Bottom Chord 1200 6075 Maximum 8" Schedule 40 Pipe
8298900 HD12TC 1/2" Top Chord 1200 6075 Maximum 8" Schedule 40Pipe
8299900 HD12BC 1/2" Bottom Chord 1200 6075 Maximum 8" Schedule 40 Pipe
"SWG 25-380 Maximum pipe size in composite wood joist allowed by UL is 3-112' LII. compliance with NEC Standards.
SWG 25-380 Maximum pipe size in wood Umber sijeist allowed by UL is 4" 'UL and FM texts were peifonned in coinpience with NFPA 13 Sbendeidx
"SWG 20 Maximum pipe size in composite wood joist allowed by UI. is 2-112" Fastening requirement 5 tines weight of water-filled schedule 40 pipe phis 250 pounds.
SWG 20 Maximum pipe size in wood limber orjciut allowed by UL is 3'
LISTED PIPE HA5ER
ALSO LOTSDAS CONDO AND CABLE HARDWARE APPROVED
ALSO LISTED As ANCHOR FOR LuM1NAaBl • owe
tqca Worldwide
I www.tyco-fire.com Contacts
Series TYFRB, 56 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (1Y323)
Sprinklers described in this data sheet
are quick response, standard coverage,
decorative 3 mm glass bulb-type spray
sprinklers designed for use in tight or
ordinary hazard, commercial occupan-
cies such as banks, hotels, and shop-
ping malls.
The recessed version of the Series
TY-FRB Pendent Sprinkler, where
applicable, is intended for use in areas
with a finished ceiling. This recessed
pendent sprinkler uses one of the
following:
A two-piece Style 15 Recessed
Escutcheon with recessed adjust-
ment up to 5/8 in. (15,9 mm) from
the flush pendent position.
A two-piece Style 20 Recessed
Escutcheon with recessed adjust-
ment up to 1/2 in. (12,7 mm) from
the flush pendent position.
The adjustment provided by the
Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Intermediate level versions of Series
TY-FRB Sprinklers are described in
Technical Data Sheet TFP357. Sprin-
kler guards and shields are described
in Technical Data Sheet TFP780.
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinklersystems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fall
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
NOTICE
The TYCO Series TY-FRB Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards of the National
Fire Protection Association, in addition
to the standards of any other authori-
ties ha ving jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
Sprinkler
IdentiXff fication
Number (SIN)
TY313.... Upright 5.6K, 1/2 in. NPT
TY323 .... Pendent 5.6K, 1/2 in. NPT
Technical
Data
Approvals
Refer to Table A
Maximum Working Pressure
175 psi (12.1 bar)
250 psi (17.2 bar)*
* The maximum working pressure of 250 psi (17.2 bar) only applies to the listing by Underwriters Laborato-ries. Inc. (UL).
Discharge Coefficient
K=5.6 GPM/psi/2 (80,6 LPM/bar½)
Temperature Rating
Refer to Table A
Finishes
Sprinkler: Refer to Table B
Recessed Escutcheon: White Coated,
Black Coated, Chrome Plated, or Brass
Plated
Physical Characteristics
Frame ............................Bronze
Button ......................Brass/Copper
Sealing Assembly . . . Stainless Steel wITEFLON
Bulb...............................Glass
Compression Screw .................Bronze
Deflector ..........................Bronze
AUGUST 2018
Operation
The glass bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass bulb, allowing the sprinkler to
activate and water to flow.
Design
Criteria
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers are intended for fire protec-
tion systems designed in accordance
with the standard installation rules
recognized by the applicable Listing or
Approval agency (such as, UL Listing
is based on the requirements of NFPA
13, and FM Approval is based on the
requirements of FM's Loss Prevention
Data Sheets). Only the Style 15 or Style
20 Recessed Escutcheon is to be used
for recessed pendent installations.
TFPI72
2-7/8" (73,0 mm) DIA.
TFPI72
Page 2 of 4
Components:
1 - Frame
2 - Button
3 - Sealing
Assembly
* Temperature rating is ** Pipe thread connections per ISO 7-1 4 - Bulb indicated on Deflector. can be provided on special request. 5 - Compression
Screw ESCUTCHEON PLATE 1/2 7/16" (11,1 mm)
6 - Deflector* DEFLECTOR* SEATING SURFACE NPT** NOMINAL MAKE-IN
I 7/16' I (111mm)
NOMINAL 2"
MAKE-IN ______ (50,8 mm)
2" 1-3/8'
(50,8 mm) (34,9 mm)
WR
1I
1/2' NPT** DEFLECTOR*
STYLE 15 or 20
RECESSED
ESCUTCHEON
CROSS SECTION UPRIGHT PENDENT RECESSED PENDENT
FIGURE 1
SERIES TY-FRB UPRIGHT (TY313) AND PENDENT (TY323) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE
Installation
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be installed in accor-
dance with this section.
General Instructions
Do not install any bulb-type sprin-
kler if the bulb is cracked or there is
a loss of liquid from the bulb. With the
sprinkler held horizontally, a small air
bubble should be present. The diam-
eter of the air bubble is approximately
1/16 in. (1,6 mm) for the 135°F (57°C) and
3/32 in. (2,4 mm) for the 286°F (141°C)
temperature ratings.
A leak-tight 1/2 in. NPT sprinkler joint
should be obtained by applying a
minimum to maximum torque of 7 to
14 lb-ft (9,5 to 19,0 N•m). Higher levels
of torque can distort the sprinkler Inlet
with consequent leakage or impairment
of the sprinkler.
Do not attempt to compensate for
insufficient adjustment in the Escutch-
eon Plate by under- or over-tightening
the sprinkler. Re-adjust the position of
the sprinkler fitting to suit.
Upright and Pendent Sprinklers
The Series TY-FRB Upright and
Pendent Sprinklers must be installed
in accordance with the following
instructions.
Step 1. Install Pendent sprinklers in the
pendent position. Install upright sprin-
klers in the upright position.
Step 2. With pipe-thread sealant
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler
fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Figure 2). With ref-
erence to Figure 1, apply the W-Type 6
Sprinkler Wrench to the wrench flats.
Torque sprinklers 7 to 14 lb-ft (9,5 to
19,0 Nm).
Recessed Pendent Sprinklers
The Series TY-FRB Recessed Pendent
Sprinklers must be installed in accor-
dance with the following instructions.
Step A. After installing the Style 15
or Style 20 Mounting Plate over the
sprinkler threads, and with pipe-thread
sealant applied to the pipe threads,
hand-tighten the sprinkler into the
sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Figure
3). With reference to Figure 1, apply the
W-Type 7 Recessed Sprinkler Wrench
to the sprinkler wrench flats. Torque
sprinklers 7 to 14 lb-ft (9,5 to 19,0 Nm).
Step C. After ceiling installation and
finishing, slide on the Style 15 or Style
20 Closure over the Series TY-FRB
Sprinkler and push the Closure over the
Mounting Plate until its flange comes in
contact with the ceiling.
/ WRENCH RECESS
/ (USE ONLY
FIGURE 2
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 3
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFPI72
Page 3 of 4
Care and
Maintenance
The TYCO Series TY-FRB, 5.6 K-factor,
Upright (TY313) and Pendent (TY323)
Sprinklers must be maintained and ser-
viced in accordance with this section.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
that it controls, obtain permission to
shut down the affected fire protection
systems from the proper authorities
and notify all personnel who may be
affected by this action.
Absence of the outer piece of an
escutcheon, which is used to cover
a clearance hole, can delay sprinkler
operation in afire situation.
The owner must assure that the sprin-
klers are not used for hanging any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be
leaking or exhibiting visible signs of
corrosion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or other-
wise altered after leaving the factory.
Modified sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid
damage to the sprinklers before,
during, and after installation. Sprin-
klers damaged by dropping, striking,
wrench twist/slippage, or the like, must
be replaced. Also, replace any sprin-
kler that has a cracked bulb or that has
lost liquid from its bulb. (Ref. Installa-
tion Section.)
The owner is responsible for the
inspection, testing, and maintenance of
their fire protection system and devices
in compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation (e.g., NFPA 25), in addition to
the standards of any other authorities
having jurisdiction. Contact the install-
ing contractor or product manufacturer
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Limited
Warranty
For warranty terms and conditions, visit
www.tyco-fire.com.
Ordering
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate
the full product name and Part Number
(P/N).
Sprinkler Assemblies with NPT
Thread Connections
Specify: Series TY-FRB Upright or
Pendent (specify) Sprinkler, SIN
(specify), K=5.6, Quick Response,
(specify) temperature rating, (specify)
finish, P/N (specify, refer to Table A).
Recessed Escutcheon
Specify: Style 15 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770
Sprinkler Wrench
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001
2-7/8' DIA.
(73,0 mm)
2-1/4 DIA.
FACE OF (57,2 mm)
SPRINKLER
FITTING
\ ___ __ _________ FLUSH
3/8±5/16 _________
5/8 (15,9 mm)
(9,5±7,9 mm) _______
\ . J MOUNTING
SURFACE 4(3,2 _______
(3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8 (34,9 mm)
TY-FRB PLATE 3/4" (19,1 mm)
FIGURE 4
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 5/8 INCH TOTAL ADJUSTMENT STYLE 15
RECESSED ESCUTCHEON
- 2-7/8" DIA.
(73,0 mm)
FACE OF
SPRINKLER - 2-1/4" DIA.
FITTING (57,2 mm)
5/16±1/4 1/2" (12,7 mm) (7,9±6,4 mm) FLUSH
MOUNTING / I SURFACE /
\
(3,2 mm)
CLOSURE SERIES MOUNTING 1-3/8" (34,9 mm)
TY-FRB PLATE 7/8" (22,2 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT SPRINKLER ASSEMBLY (TY323)
WITH TWO PIECE 1/2 INCH TOTAL ADJUSTMENT STYLE 20
RECESSED ESCUTCHEON
S. £
TFPI72
Page 4 of 4
SPRINKLER FINISH (See Note 7)
K
FACTOR TYPE TEMPERATURE BULB LIQUID
COLOR
NATURAL
BRASS
I CHROME
PLATED 1 POLYESTER-
135°F (57°C) Orange
UPRIGHT
(TY313) 155°F (68°C) Red
175°F (79°C) Yellow and 1, 2, 3, 4, 5, 6
5.6
1/2 in. NPT
PENDENT
(TY323) 200°F (93°C) Green
286°F (141°C) Blue
_______________
135°F (57°C) Orange
RECESSED
PENDENT
(TY323)
Figures 4a and 5b
1,2,3,4 155°F (68°C) Red
175°F (79°C) Yellow
200°F(93°C) Green
Notes:
Listed by Underwriters Laboratories, Inc., (UL) as Quick Response Sprinklers.
Listed by Underwriters Laboratories, Inc., for use in Canada (C-UL) as Quick Response Sprinklers.
Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
Approved by the City of New York under MEA 354-01-E.
VdS Approved (For details. Contact Johnson Controls, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-54-428-3377.)
Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion-Resistant Sprinklers.
Installed with Style 15 (1/2 in. NPT) 5/8 in. Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20(1/2 in. NPT) 1/2 in. Total Adjustment Recessed Escutcheon, as applicable.
Frame and Deflector only. Listings and approvals apply to color (Special Order).
TABLE A
LABORATORY LISTINGS AND APPROVALS FOR
5.6 K-FACTOR SPRINKLERS
P/Na_77XXXXX_________
SIN SPRINKLER
I
TEMPERATURE
FINISH I RATINGS
1 NATURAL BRASS
- PURE WHITE (RAL901O)a
POLYESTER
SIGNAL WHITE (RAL9003)
POLYESTER
- JET BLACK (RAL9005)
POLYESTER
9 CHROME PLATED
Notes:
a. Eastern Hemisphere sales only
135 135-F (57-C)
155 155-F (68-C)
175 175°F(79°C)
200 200-F (93-C)
286 286-F (141-C)
370 1 5.6K UPRIGHT (1/21n.NPT) I TY313
371 I 5.6K PENDENT (1/21n.NPT) I 1Y323
Notes:
a. Use suffix "I" for ISO 7-1 Connection; for example,
77-370-4-175-I
TABLE B
SERIES TY-FRB UPRIGHT AND PENDENT SPRINKLERS
PART NUMBER SELECTION
1400 Pennbrook Parkway, Lansdale, PA 19446 (Telephone +1-215-362-0700
0 2018 Johnson Controls. All rights rosornad. Alt specifications and other information shown ware oan'ont as of doarnont roniolo,, date and ore subject to change without notiAo. Johnson Olt$
NATIONAL FIRE PROTECTION ASSOCIATION And NFPA on ,ngonornd tradomn,ka of National Fire ProfocSonAoAAcioSon Controls TEFLON isa ,ogiznorod vedano,k of DuPOnt