HomeMy WebLinkAbout3062 VILLETA AVE; ; FPR2017-0258; PermitPERMIT REPORT (city
of
Carlsbad
Print Date: 01/26/2022
Job Address: 3062 VILLETA AVE. CARLSBAD, CA
Permit Type: FIRE-Construction Residential Work Class:
Parcel #: Track #:
Valuation: $0.00 Lot #:
Occupancy Group: Project #:
#of Dwelling Units: Plan #:
Bedrooms: Construction Type:
Bathrooms: Orig. Plan Check #:
Plan Check #:
Permit No: FPR2017-0258
Status: Closed - Finaled
Single Family Fire Sprinki
Applied: 06/22/2017
Issued: 08/22/2017
DEV2016-0060 Finaled Close Out: 01/26/2022
Inspector:
Final Inspection:
Project Title: CYPRESS AT THE PRESERVE
Description: CYPRESS AT THE PRESERVE / MODEL / PLAN 2 /LOT 16- SPRINKLER
FPContractor:
NP MECHANICAL INC
P0 BOX 309
CORONA, CA 92878-0309
(951) 667-4220
FEE AMOUNT
FIRE NFPA 13D Single Family System (lnsp/Bldg) $121.00
FIRE NFPA 13D Single Family System (Plan Review) $239.00
Total Fees: $360.00 Total Payments To Date: $360.00 Balance Due: $0.00
Fire Department Page 1 of 1
1635 Faraday Avenue, Carlsbad CA 92008-7314 1 760-602-4665 760-602-8561 f I www.carlsbadca.gov
f12,o 1- 025'
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : CYPRESS AT THE PRESERVE
Building : PLAN 2
Location : CALC AREA 1
System : 1
Contract
Data File : PLAN2 CAl 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page
CYPRESS ATTHE PRESERVE Date 5/25/17
HYDRAULIC DESIGN INFORMATION SHEET
Name - CYPRESS AT THE PRESERVE Date - 5/25/17
Location - CALC AREA 1
Building - PLAN 2 System No. - 1
Contractor - NP MECHANICAL Contract No. -
Calculated By - MG Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9T_0T
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )1 (X)2 ( )4
S ( )Other
T ( )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 ( ) Deluge ( ) PreAction
E Domestic Flow Added - Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 26.069 Psi Required 44.659 At BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - 9 Psi Elev.
E Static (Psi) - 94 Elev.
R Residual (Psi) - 66 Other Well
Flow (Gpm) - 3750 Proof Flow Gpm
S Elevation - 114
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C \
NP Mechanical Page 2
CYPRESS AT THE PRESERVE Date 5/25/17
City Water Supply: Demand:
Cl - Static Pressure : 84.6 Dl - Elevation : 12.127
C2 - Residual Pressure: 59.4 D2 - System Flow : 26.069
C2 - Residual Flow : 3750 D2 - System Pressure : 73.505
Hose ( Demand) : 5
D3 - System Demand : 31.069
Safety Margin : 11.092
150
140
130
P 120
R 11
E 100
590
S 80 - ___ _____ _______
u 70 - -
C2
R 60
E5°
40
30
20
10 --Dl—
U
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW (N " 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
CYPRESS ATTHE PRESERVE Date 5/25/17
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCCouplinglee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA139O' Flow thruTee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 10 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for C Factors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Row Summary - STANDARD
NP Mechanical Page 4
CYPRESS AT THE PRESERVE Date 5/25/17
Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Rea
Hi 9.0 4.9 7.04 na 13.0
H2 9.0 4.9 7.11 na 13.07
H3 19.0 15.05 na
H4 19.0 16.17 na
H5 19.0 17.23 na
Dl 10.0 7.36 na
D2 10.0 7.44 na
10.0 8.78 na
2 20.0 10.26 na
3 20.0 12.48 na
4 20.0 13.49 na
D3 20.0 14.62 na
5 20.0 14.62 na
6 20.0 18.33 na
7 20.0 18.73 na
12 20.0 22.01 na
D5 20.0 16.8 na
8 20.0 16.8 na
D4 20.0 15.74 na
9 20.0 15.74 na
10 20.0 14.25 na
11 20.0 13.12 na
13 10.0 32.15 na
14 10.0 33.46 na
TR 10.0 35.24 na
BR 2.0 44.66 na 5.0
X 2.0 45.73 na
EL -3.0 48.32 na
Mi -3.0 53.84 na
M2 -3.0 58.05 na
CM -3.0 66.57 na
100 -3.0 66.57 na
101 -3.0 66.57 na
102 -3.0 66.57 na
103 -3.0 66.57 na
104 -3.0 66.57 na
FT -19.0 73.5 na
0.05 256 7.039
0.05 256 7.0
The maximum velocity is 13.94 and it occurs in the pipe between nodes 1 and 2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 'C' or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 13.00 0.874 N 7.0 1.000 7.039 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
Dl 13.0 0.0944 0.0 8.000 0.755 Vet = 6.95
0.0
13.00 7.361 K Factor = 4.79
H2 13.07 0.874 N 7.0 1.000 7.113 K Factor =4.90
to 150.0 0.0 7.000 -0.433
D2 13.07 0.0954 0.0 8.000 0.763 Vet = 6.99
0.0
13.07 7.443 K Factor = 4.79
H3 0.0 0.874 N 7.0 1.000 15.049
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vet = 0
0.0
0.0 14.616 K Factor =0
H4 0.0 0.874 N 7.0 1.000 16.174
to 150.0 0.0 7.000 -0.433
D4 0.0 -0.0001 0.0 8.000 -0.001 Vet = 0
0.0
0.0 15.740 K Factor =0
H5 0.0 0.874 N 7.0 1.000 17.229
to 150.0 0.0 7.000 -0.433
D5 0.0 0.0 0.0 8.000 0.0 Vet = 0
0.0
0.0 16.796 K Factor = 0
Di 13.00 0.874 N 7.0 5.000 7.361
to 150.0 0 3.0 10.000 0.0
1 13.0 0.0944 0.0 15.000 1.416 Vet = 6.95
0.0
13.00 8.777 K Factor = 4.39
D2 13.07 0.874 N 7.0 6.000 7.443
to 150.0 R 1.0 8.000 0.0
1 13.07 0.0953 0.0 14.000 1.334 Vel= 6.99
1 13.00 0.874 N 7.0 10.000 8.777
to 150.0 0.0 7.000 -4.331
2 26.07 0.3420 0.0 17.000 5.814 Vet = 13.94
2 0.0 0.874 0 3.0 3.500 10.260
to 150.0 0.0 3.000 0.0
3 26.07 0.3422 0.0 6.500 2.224 Vet = 13.94
3 -13.94 0.874 N 7.0 5.167 12.484
to 150.0 0.0 7.000 0.0
4 12.13 0.0830 0.0 12.167 1.010 Vet = 6.49
4 0.0 0.874 3R 3.0 10.500 13.494
to 150.0 0.0 3.000 0.0
5 12.13 0.0831 0.0 13.500 1.122 Vel = 6.49
0.0
12.13 14.616 K Factor = 3.17
D3 0.0 0.874 0 3.0 6.750 14.616
to 150.0 0.0 3.000 0.0
5 0.0 0.0 0.0 9.750 0.0 Vet = 0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 'C" or Ftngs Fe Pv Notes
Point Ot Pf/Ft Eqv. Ln. Total Pf Pn
5 12.13 0.874 4R 4.0 26.667 14.616
to 150.0 2N 14.0 18.000 0.0
6 12.13 0.0831 0.0 44.667 3.711 Vel= 6.49
6 0.0 0.874 0 3.0 1.833 18.327
to 150.0 0.0 3.000 0.0
7 12.13 0.0832 0.0 4.833 0.402 Vel = 6.49
7 13.94 0.874 N 7.0 2.583 18.729
to 150.0 0.0 7.000 0.0
12 26.07 0.3420 0.0 9.583 3.277 Vel = 13.94
12 0.0 0.874 N 7.0 10.000 22.006
to 150.0 0.0 7.000 4.331
13 26.07 0.3420 0.0 17.000 5.814 Vel = 13.94
0.0
26.07 32.151 K Factor = 4.60
7 -13.94 0.874 R 1.0 14.000 18.729
to 150.0 0 3.0 4.000 0.0
8 -13.94 -0.1074 0.0 18.000 -1.933 Vel = 7.45
0.0
-13.94 16.796 K Factor = -3.40
D5 0.0 0.874 N 7.0 7.667 16.796
to 150.0 R 1.0 8.000 0.0
8 0.0 0.0 0.0 15.667 0.0 Vet = 0
8 -13.94 0.874 R 1.0 8.833 16.796
to 150.0 0.0 1.000 0.0
9 -13.94 -0.1074 0.0 9.833 -1.056 Vel = 7.45
0.0
-13.94 15.740 K Factor = -3.51
D4 0.0 0.874 0 3.0 1.500 15.740
to 150.0 0.0 3.000 0.0
9 0.0 0.0 0.0 4.500 0.0 Vel = 0
9 -13.94 0.874 N 7.0 6.917 15.740
to 150.0 0.0 7.000 0.0
10 -13.94 -0.1074 0.0 13.917 -1.494 Vel = 7.45
10 0.0 0.874 N 7.0 3.500 14.246
to 150.0 0.0 7.000 0.0
11 -13.94 -0.1073 0.0 10.500 -1.127 Vel = 7.45
11 0.0 0.874 2R 2.0 3.917 13.119
to 150.0 0.0 2.000 0.0
3 -13.94 -0.1073 0.0 5.917 -0.635 Vel = 7.45
0.0
-13.94 12.484 K Factor = -3.95
13 26.07 1.101 N 7.0 4.750 32.151
to 150.0 0.0 7.000 0.0
14 26.07 0.1111 0.0 11.750 1.306 Vel= 8.79
14 0.0 1.101 R 1.0 8.083 33.457
to 150.0 N 7.0 8.000 0.0
TR 26.07 0.1110 0.0 16.083 1.786 Vel= 8.79
0.0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. C or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
26.07 35.243 K Factor = 4.39
TR 26.07 1.101 2R 2.0 8.000 35.243
to 150.0 S 9.563 18.562 6.465 * * Fixed Loss = 3
BR 26.07 0.1111 Fsp 0.0 26.562 2.951 Vel = 8.79
N 7.0
BR 5.00 1.101 0 5.0 2.000 44.659 Qa=5
to 150.0 0.0 5.000 0.0
X 31.07 0.1537 0.0 7.000 1.076 Vel= 10.47
X 0.0 1.244 0.0 5.000 45.735
to 150.0 0.0 0.0 2.166
EL 31.07 0.0846 0.0 5.000 0.423 Vel = 8.20
EL 0.0 1.244 0.0 65.000 48.324
to 150.0 0.0 0.0 0.0
Ml 31.07 0.0848 0.0 65.000 5.512 Vel = 8.20
Ml 0.0 1.025 0.0 1.000 53.836
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 31.07 0.2180 0.0 1.000 0.218 Vel= 12.08
M2 0.0 0.995 T 5.841 28.000 58.054
to 150.0 0.0 5.841 0.0
CM 31.07 0.2516 0.0 33.841 8.516 Vel= 12.82
CM -14.03 7.98 3F 40.774 324.000 66.570
to 150.0 T 52.855 93.629 0.0
100 17.04 0.0 0.0 417.629 0.001 Vel = 0.11
100 0.87 7.98 T 52.855 295.000 66.571
to 150.0 0.0 52.855 0.0
101 17.91 0.0 0.0 347.855 0.001 Vel = 0.11
0.0
17.91 66.572 K Factor = 2.20
100 -0.87 7.98 2T 105.71 381.000 66.571
to 150.0 0.0 105.710 -1.299
105 -0.87 0.0 0.0 486.710 0.0 Vel = 0.01
0.0
-0.87 65.272 K Factor = -0.1 1
101 17.91 11.65 F 17.441 175.000 66.572
to 150.0 T 80.498 97.939 0.0
102 17.91 0.0 0.0 272.939 0.0 Vel = 0.05
102 -31.07 11.65 F 17.441 532.000 66.572
to 150.0 1 80.498 97.939 0.0
103 -13.16 0.0 0.0 629.939 0.0 Vel = 0.04
103 0.0 7.98 T 52.855 542.000 66.572
to 150.0 0.0 52.855 0.0
104 -13.16 0.0 0.0 594.855 -0.001 Vel = 0.08
104 14.03 11.65 T 80.498 207.000 66.571
to 150.0 0.0 80.498 -1.299
105 0.87 0.0 0.0 287.498 0.0 Vel = 0
0.0
0.87 65.272 K Factor = 0.11
104 -14.03 7.98 T 52.855 542.000 66.571
to 150.0 0.0 52.855 0.0
CM -14.03 0.0 0.0 594.855 -0.001 Vel = 0.09
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical
CYPRESS AT THE PRESERVE
Page 8
Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-14.03 66.570 K Factor = -1.72
102 31.07 11.65 3T 241.494 1439.000 66.572
to 150.0 0.0 241.494 6.930
FT 31.07 0.0 0.0 1680.494 0.003 Vel = 0.09
0.0
31.07 73.505 K Factor = 3.62
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : CYPRESS ATTHE PRESERVE
Building : PLAN 2
Location : CALC AREA 2
System : 1
Contract
Data File : PLAN2 CA2 20X20.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page 1
CYPRESS AT THE PRESERVE Date 5/25/17
HYDRAULIC DESIGN INFORMATION SHEET
Name - CYPRESS AT THE PRESERVE Date - 5/25/17
Location - CALC AREA 2
Building - PLAN 2 System No. - 1
Contractor - NP MECHANICAL Contract No. -
Calculated By - MG Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9T_0T
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: (X)l ( )2 ( )4
S )Other
T )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 20 GPM System Type
Listed Pres. at Start Point - 16.7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 20 x 20 Deluge ( ) PreAction
H Domestic Flow Added - GPM Sprinkler or Nozzle
S Additional Flow Added - GPM Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation GPM Required 20.024 Psi Required 43.761 At BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test:
A Date of Test -
T Time of Test -
E Static (Psi) - 94
R Residual (Psi) - 66
Flow (GPM) - 3750
S Elevation - 114
P Location:
P
L Source of Information:
Y
Pump Data: Tank or Reservoir:
Rated Cap. Cap.
@ Psi Elev.
Elev.
Other Well
Proof Flow GPM
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
CYPRESS AT THE PRESERVE Date 5/25/17
City Water Supply: Demand:
Cl - Static Pressure : 84.6 Dl - Elevation : 16.458
C2 - Residual Pressure: 59.4 D2 - System Flow : 20.024
C2 - Residual Flow : 3750 D2 - System Pressure : 67.411
Hose ( Demand) : 5
D3 - System Demand : 25.024
Safety Margin : 17.186
150
140
130
p120
R 11
E10°
s 90
D2
80
U 70 -
C2
R 60D3
E5°
40
30
20
Dl
__•._ ...t I I
10
I I I ______________________________ •
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW (N "1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
CYPRESS ATTHE PRESERVE Date 5/25/17
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCCouplingTee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square liih
Note: Fitting Legend provides equivalent pipe lengths for fittings typos of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fIttings not marked wIth a will be adjusted In the calculatIon
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
NP Mechanical Page 4 CYPRESS ATTHE PRESERVE Date 5/25/17
Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req.
Hi 9.0 25.88 na
H2 9.0 25.88 na
H3 19.0 4.9 16.7 na 20.02 0.05 400 16.7 H4 19.0 22.89 na H5 19.0 23.32 na
Dl 10.0 25.45 na
D2 10.0 25.45 na
10.0 25.45 na
2 20.0 21.12 na
3 20.0 21.12 na
4 20.0 20.59 na
03 20.0 17.95 na
5 20.0 19.99 na
6 20.0 23.32 na
7 20.0 23.68 na 12 20.0 25.69 na D5 20.0 22.88 na
8 20.0 22.88 na
D4 20.0 22.45 na
9 20.0 22.45 na 10 20.0 21.84 na
ii 20.0 21.38 na 13 10.0 33.59 na 14 10.0 34.39 na
TR 10.0 35.48 na
BR 2.0 43.76 na 5.0 X 2.0 44.48 na EL -3.0 46.93 na
Mi -3.0 50.63 na
M2 -3.0 54.77 na
CM -3.0 60.48 na
100 -3.0 60.48 na
101 -3.0 60.48 na
102 -3.0 60.48 na
103 -3.0 60.48 na
104 -3.0 60.48 na
FT -19.0 67.41 na
The maximum velocity is 10.71 and it occurs in the pipe between nodes H3 and D3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 0.0 0.874 N 7.0 1.000 25.885
to 150.0 0.0 7.000 -0.433
Di 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 25.452 K Factor = 0
H2 0.0 0.874 N 7.0 1.000 25.885
to 150.0 0.0 7.000 -0.433
D2 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 25.452 K Factor = 0
H3 20.02 0.874 N 7.0 1.000 16.700 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D3 20.02 0.2099 0.0 8.000 1.679 Vel= 10.71
0.0
20.02 17.946 K Factor = 4.73
H4 0.0 0.874 N 7.0 1.000 22.886
to 150.0 0.0 7.000 -0.433
D4 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 22.453 K Factor = 0
H5 0.0 0.874 N 7.0 1.000 23.318
to 150.0 0.0 7.000 -0.433
D5 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 22.885 K Factor = 0
Dl 0.0 0.874 N 7.0 5.000 25.452
to 150.0 0 3.0 10.000 0.0
1 0.0 0.0 0.0 15.000 0.0 Vel = 0
0.0
0.0 25.452 K Factor = 0
D2 0.0 0.874 N 7.0 6.000 25.452
to 150.0 R 1.0 8.000 0.0
1 0.0 0.0 0.0 14.000 0.0 Vel = 0
1 0.0 0.874 N 7.0 10.000 25.452
to 150.0 0.0 7.000 -4.331
2 0.0 -0.0001 0.0 17.000 -0.001 Vel = 0
2 0.0 0.874 0 3.0 3.500 21.120
to 150.0 0.0 3.000 0.0
3 0.0 0.0 0.0 6.500 0.0 Vel = 0
3 -8.60 0.874 N 7.0 5.167 21.120
to 150.0 0.0 7.000 0.0
4 -8.6 -0.0439 0.0 12.167 -0.534 Vel = 4.60
4 0.0 0.874 3R 3.0 10.500 20.586
to 150.0 0.0 3.000 0.0
5 -8.6 -0.0439 0.0 13.500 -0.593 Vel = 4.60
0.0
-8.60 19.993 K Factor = -1.92
D3 20.02 0.874 0 3.0 6.750 17.946
to 150.0 0.0 3.000 0.0
5 20.02 0.2099 0.0 9.750 2.047 Vel = 10.71
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical
CYPRESS ATTHE PRESERVE Page
Date
6
5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
5 -8.59 0.874 4R 4.0 26.667 19.993
to 150.0 2N 14.0 18.000 0.0
6 11.43 0.0744 0.0 44.667 3.323 Vet = 6.11
6 0.0 0.874 0 3.0 1.833 23.316
to 150.0 0.0 3.000 0.0
7 11.43 0.0743 0.0 4.833 0.359 Vel = 6.11
7 8.59 0.874 N 7.0 2.583 23.675
to 150.0 0.0 7.000 0.0
12 20.02 0.2100 0.0 9.583 2.012 Vel = 10.71
12 0.0 0.874 N 7.0 10.000 25.687
to 150.0 0.0 7.000 4.331
13 20.02 0.2099 0.0 17.000 3.569 Vel = 10.71
0.0
20.02 33.587 K Factor = 3.45
7 -8.60 0.874 R 1.0 14.000 23.675
to 150.0 0 3.0 4.000 0.0
8 -8.6 -0.0439 0.0 18.000 -0.790 Vel = 4.60
0.0
-8.60 22.885 K Factor = -1.80
D5 0.0 0.874 N 7.0 7.667 22.885
to 150.0 R 1.0 8.000 0.0
8 0.0 0.0 0.0 15.667 0.0 Vel = 0
8 -8.60 0.874 R 1.0 8.833 22.885
to 150.0 0.0 1.000 0.0
9 -8.6 -0.0439 0.0 9.833 -0.432 Vel = 4.60
0.0
-8.60 22.453 K Factor = -1.81
D4 0.0 0.874 0 3.0 1.500 22.453
to 150.0 0.0 3.000 0.0
9 0.0 0.0 0.0 4.500 0.0 Vel = 0
9 -8.60 0.874 N 7.0 6.917 22.453
to 150.0 0.0 7.000 0.0
10 -8.6 -0.0439 0.0 13.917 -0.611 Vel = 4.60
10 0.0 0.874 N 7.0 3.500 21.842
to 150.0 0.0 7.000 0.0
11 -8.6 -0.0440 0.0 10.500 -0.462 Vel = 4.60
11 0.0 0.874 2R 2.0 3.917 21.380
to 150.0 0.0 2.000 0.0
3 -8.6 -0.0439 0.0 5.917 -0.260 Vel = 4.60
0.0
-8.60 21.120 KFactor= -1.87
13 20.02 1.101 N 7.0 4.750 33.587
to 150.0 0.0 7.000 0.0
14 20.02 0.0682 0.0 11.750 0.801 VeI= 6.75
14 0.0 1.101 R 1.0 8.083 34.388
to 150.0 N 7.0 8.000 0.0
TR 20.02 0.0682 0.0 16.083 1.097 Vet = 6.75
0.0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Oa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point at Pf/Ft Eqv. Ln. Total Pt Pn
20.02 35.485 K Factor = 3.36
TR 20.02 1.101 2R 2.0 8.000 35.485
to 150.0 S 9.563 18.562 6.465 * * Fixed Loss = 3
BR 20.02 0.0682 Fsp 0.0 26.562 1.811 Vet = 6.75
N 7.0
BR 5.00 1.101 0 5.0 2.000 43.761 Qa=5
to 150.0 0.0 5.000 0.0
X 25.02 0.1030 0.0 7.000 0.721 Vet = 8.43
X 0.0 1.244 0.0 5.000 44.482
to 150.0 0.0 0.0 2.166
EL 25.02 0.0568 0.0 5.000 0.284 Vet = 6.60
EL 0.0 1.244 0.0 65.000 46.932
to 150.0 0.0 0.0 0.0
Ml 25.02 0.0568 0.0 65.000 3.693 Vet = 6.60
Ml 0.0 1.025 0.0 1.000 50.625
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 25.02 0.1460 0.0 1.000 0.146 Vet = 9.73
M2 0.0 0.995 T 5.841 28.000 54.771
to 150.0 0.0 5.841 0.0
CM 25.02 0.1686 0.0 33.841 5.707 Vet = 10.32
CM -11.30 7.98 3F 40.774 324.000 60.478
to 150.0 1 52.855 93.629 0.0
100 13.72 0.0 0.0 417.629 0.001 Vet = 0.09
100 0.70 7.98 T 52.855 295.000 60.479
to 150.0 0.0 52.855 0.0
101 14.42 0.0 0.0 347.855 0.001 Vet = 0.09
0.0
14.42 60.480 K Factor = 1.85
100 -0.70 7.98 21 105.71 381.000 60.479
to 150.0 0.0 105.710 -1.299
105 -0.7 0.0 0.0 486.710 0.0 Vet = 0
0.0
-0.70 59.180 K Factor = -0.09
101 14.42 11.65 F 17.441 175.000 60.480
to 150.0 T 80.498 97.939 0.0
102 14.42 0.0 0.0 272.939 0.0 Vet = 0.04
102 -25.02 11.65 F 17.441 532.000 60.480
to 150.0 T 80.498 97.939 0.0
103 -10.6 0.0 0.0 629.939 0.0 Vet = 0.03
103 0.0 7.98 1 52.855 542.000 60.480
to 150.0 0.0 52.855 0.0
104 -10.6 0.0 0.0 594.855 -0.001 Vet = 0.07
104 11.30 11.65 T 80.498 207.000 60.479
to 150.0 0.0 80.498 -1.299
105 0.7 0.0 0.0 287.498 0.0 Vet = 0
0.0
0.70 59.180 K Factor = 0.09
104 -11.30 7.98 1 52.855 542.000 60.479
to 150.0 0.0 52.855 0.0
CM -11.3 0.0 0.0 594.855 -0.001 Vet = 0.07
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 8
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-11.30 60.478 K Factor = -1.45
102 25.02 11.65 3T 241.494 1439.000 60.480
to 150.0 0.0 241.494 6.930
FT 25.02 0.0 0.0 1680.494 0.001 Vel = 0.08
0.0
25.02 67.411 K Factor = 3.05
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : CYPRESS ATTHE PRESERVE
Building : PLAN 2
Location : CALC AREA 3
System : 1
Contract
Data File : PLAN2 CA3 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page
CYPRESS ATTHE PRESERVE Date 5/25/17
HYDRAULIC DESIGN INFORMATION SHEET
Name - CYPRESS AT THE PRESERVE
Location - CALC AREA 3
Building - PLAN 2
Contractor - NP MECHANICAL
Calculated By - MG
Construction: (X) Combustible
OCCUPANCY - LIGHT HAZARD
Date - 5/25/17
System No. - 1
Contract No. -
Drawing No. - 1
Non-Combustible Ceiling Height 9T_0
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )l (X)2 ( )4
S )Other
T )Specific Ruling Made by Date
E
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 Deluge ( ) PreAction
E Domestic Flow Added - Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 26.647 Psi Required 38.847 At BR
Summary C-Factor Used: Overhead 150 Underground 150
Pump Data: Tank or Reservoir:
Rated Cap. Cap.
@ Psi Elev.
Elev.
Other Well
Proof Flow Gpm
W Water Flow Test:
A Date of Test -
T Time of Test -
E Static (Psi) - 94
R Residual (Psi) - 66
Flow (Gpm) - 3750
S Elevation - 114
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
CYPRESS ATTHE PRESERVE Date 5/25/17
City Water Supply: Demand: Cl -Static Pressure : 84.6 Dl - Elevation : 16.458
C2 - Residual Pressure: 59.4 D2 - System Flow : 26.647
C2 - Residual Flow : 3750 D2 - System Pressure : 68.239
Hose ( Demand) : 5
D3 - System Demand : 31-647
Safety Margin : 16.360
150
140
130
p120
R 11
E10°
90 C1
80 -
D2
-_
U 70 -
C2
R 60D3
E5°
40
30
20
Dl
10
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW (N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
CYPRESS ATTHE PRESERVE Date 5/25/17
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
F NFPA 13 45' Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90Ell Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCCouplingTee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 13 90' Flowthru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for C Factors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
NP Mechanical Page 4
CYPRESS ATTHE PRESERVE Date 5/25/17
Node Elevation K-Fact Pt Pn Flow Density Area Press
No. Actual Actual Req.
Hi 9.0 14.44 na
H2 9.0 14.44 na
H3 19.0 11.0 na
H4 19.0 4.9 7.76 na 13.65 0.05 256 7.0
H5 19.0 4.9 7.04 na 13.0 0.05 256 7.039
Dl 10.0 14.0 na
D2 10.0 14.0 na
10.0 14.0 na
2 20.0 9.67 na
3 20.0 9.67 na
4 20.0 10.09 na
D3 20.0 10.57 na
5 20.0 10.57 na
6 20.0 12.12 na
7 20.0 12.29 na
12 20.0 15.7 na
D5 20.0 7.36 na
8 20.0 8.84 na
D4 20.0 8.15 na
9 20.0 8.61 na
10 20.0 9.1 na
ii 20.0 9.46 na
13 10.0 26.09 na
14 10.0 27.45 na
TR 10.0 29.31 na
BR 2.0 38.85 na 5.0
X 2.0 39.96 na
EL -3.0 42.56 na
Mi -3.0 48.27 na
M2 -3.0 52.49 na
CM -3.0 61.3 na
100 -3.0 61.3 na
101 -3.0 61.31 na
102 -3.0 61.31 na
103 -3.0 61.31 na
104 -3.0 61.3 na
FT -19.0 68.24 na
The maximum velocity is 14.25 and it occurs in the pipe between nodes 7 and 12
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 0.0 0.874 N 7.0 1.000 14.435
to 150.0 0.0 7.000 -0.433
Dl 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 14.002 K Factor = 0
H2 0.0 0.874 N 7.0 1.000 14.435
to 150.0 0.0 7.000 -0.433
D2 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 14.002 K Factor = 0
H3 0.0 0.874 N 7.0 1.000 10.998
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 10.565 K Factor =0
H4 13.65 0.874 N 7.0 1.000 7.756 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D4 13.65 0.1032 0.0 8.000 0.826 Vel = 7.30
0.0
13.65 8.149 K Factor= 4.78
H5 13.00 0.874 N 7.0 1.000 7.039 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D5 13.0 0.0944 0.0 8.000 0.755 Vel = 6.95
0.0
13.00 7.361 K Factor = 4.79
Dl 0.0 0.874 N 7.0 5.000 14.002
to 150.0 0 3.0 10.000 0.0
1 0.0 0.0 0.0 15.000 0.0 Vel = 0
0.0
0.0 14.002 K Factor = 0
D2 0.0 0.874 N 7.0 6.000 14.002
to 150.0 R 1.0 8.000 0.0
1 0.0 0.0 0.0 14.000 0.0 Vel = 0
1 0.0 0.874 N 7.0 10.000 14.002
to 150.0 0.0 7.000 -4.331
2 0.0 0.0 0.0 17.000 0.0 Vel = 0
2 0.0 0.874 0 3.0 3.500 9.671
to 150.0 0.0 3.000 0.0
3 0.0 0.0 0.0 6.500 0.0 Vel = 0
3 7.58 0.874 N 7.0 5.167 9.671
to 150.0 0.0 7.000 0.0
4 7.58 0.0348 0.0 12.167 0.424 Vel = 4.05
4 0.0 0.874 3R 3.0 10.500 10.095
to 150.0 0.0 3.000 0.0
5 7.58 0.0348 0.0 13.500 0.470 Vel = 4.05
0.0
7.58 10.565 K Factor = 2.33
D3 0.0 0.874 0 3.0 6.750 10.565
to 150.0 0.0 3.000 0.0
5 0.0 0.0 0.0 9.750 0.0 Vel = 0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Oa Dia. Fitting Pipe Pt Pt
Ref. 'C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
5 7.58 0.874 4R 4.0 26.667 10.565
to 150.0 2N 14.0 18.000 0.0
6 7.58 0.0349 0.0 44.667 1.557 Vel = 4.05
6 0.0 0.874 0 3.0 1.833 12.122
to 150.0 0.0 3.000 0.0
7 7.58 0.0348 0.0 4.833 0.168 Vel = 4.05
7 19.07 0.874 N 7.0 2.583 12.290
to 150.0 0.0 7.000 0.0
12 26.65 0.3562 0.0 9.583 3.413 Vel = 14.25
12 0.0 0.874 N 7.0 10.000 15.703
to 150.0 0.0 7.000 4.331
13 26.65 0.3562 0.0 17.000 6.055 Vel = 14.25
0.0
26.65 26.089 K Factor = 5.22
7 -19.06 0.874 R 1.0 14.000 12.290
to 150.0 0 3.0 4.000 0.0
8 -19.06 -0.1917 0.0 18.000 -3.450 Vel = 10.19
0.0
-19.06 8.840 K Factor = -6.41
D5 13.00 0.874 N 7.0 7.667 7.361
to 150.0 R 1.0 8.000 0.0
8 13.0 0.0944 0.0 15.667 1.479 Vel = 6.95
8 -19.06 0.874 R 1.0 8.833 8.840
to 150.0 0.0 1.000 0.0
9 -6.06 -0.0230 0.0 9.833 -0.226 Vel = 3.24
0.0
-6.06 8.614 K Factor = -2.06
D4 13.65 0.874 0 3.0 1.500 8.149
to 150.0 0.0 3.000 0.0
9 13.65 0.1033 0.0 4.500 0.465 Vel = 7.30
9 -6.07 0.874 N 7.0 6.917 8.614
to 150.0 0.0 7.000 0.0
10 7.58 0.0348 0.0 13.917 0.485 Vel = 4.05
10 0.0 0.874 N 7.0 3.500 9.099
to 150.0 0.0 7.000 0.0
11 7.58 0.0349 0.0 10.500 0.366 Vel = 4.05
11 0.0 0.874 2R 2.0 3.917 9.465
to 150.0 0.0 2.000 0.0
3 7.58 0.0348 0.0 5.917 0.206 Vel = 4.05
0.0
7.58 9.671 K Factor = 2.44
13 26.65 1.101 N 7.0 4.750 26.089
to 150.0 0.0 7.000 0.0
14 26.65 0.1157 0.0 11.750 1.359 Vel= 8.98
14 0.0 1.101 R 1.0 8.083 27.448
to 150.0 N 7.0 8.000 0.0
TR 26.65 0.1157 0.0 16.083 1.861 Vel= 8.98
0.0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
26.65 29.309 K Factor = 4.92
TR 26.65 1.101 2R 2.0 8.000 29.309
to 150.0 S 9.563 18.562 6.465 * * Fixed Loss = 3
BR 26.65 0.1157 Fsp 0.0 26.562 3.073 Vet = 8.98
N 7.0
BR 5.00 1.101 0 5.0 2.000 38.847 Qa=5
to 150.0 0.0 5.000 0.0
X 31.65 0.1590 0.0 7.000 1.113 Vel= 10.67
X 0.0 1.244 0.0 5.000 39.960
to 150.0 0.0 0.0 2.166
EL 31.65 0.0876 0.0 5.000 0.438 Vet = 8.35
EL 0.0 1.244 0.0 65.000 42.564
to 150.0 0.0 0.0 0.0
Ml 31.65 0.0877 0.0 65.000 5.703 Vel = 8.35
Ml 0.0 1.025 0.0 1.000 48.267
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 31.65 0.2260 0.0 1.000 0.226 Vet = 12.31
M2 0.0 0.995 T 5.841 28.000 52.493
to 150.0 0.0 5.841 0.0
CM 31.65 0.2604 0.0 33.841 8.811 Vet = 13.06
CM -14.30 7.98 3F 40.774 324.000 61.304
to 150.0 T 52.855 93.629 0.0
100 17.35 0.0 0.0 417.629 0.001 Vet= 0.11
100 0.89 7.98 T 52.855 295.000 61.305
to 150.0 0.0 52.855 0.0
101 18.24 0.0 0.0 347.855 0.001 Vet = 0.12
0.0
18.24 61.306 K Factor = 2.33
100 -0.89 7.98 2T 105.71 381.000 61.305
to 150.0 0.0 105.710 -1.299
105 -0.89 0.0 0.0 486.710 0.0 Vet = 0.01
0.0
-0.89 60.006 K Factor = -0.11
101 18.24 11.65 F 17.441 175.000 61.306
to 150.0 T 80.498 97.939 0.0
102 18.24 0.0 0.0 272.939 0.0 Vet = 0.05
102 -31.65 11.65 F 17.441 532.000 61.306
to 150.0 T 80.498 97.939 0.0
103 -13.41 0.0 0.0 629.939 0.0 Vet = 0.04
103 0.0 7.98 T 52.855 542.000 61.306
to 150.0 0.0 52.855 0.0
104 -13.41 0.0 0.0 594.855 -0.001 Vet = 0.09
104 14.30 11.65 T 80.498 207.000 61.305
to 150.0 0.0 80.498 -1.299
105 0.89 0.0 0.0 287.498 0.0 Vet = 0
0.0
0.89 60.006 K Factor = 0.11
104 -14.29 7.98 T 52.855 542.000 61.305
to 150.0 0.0 52.855 0.0
CM -14.29 0.0 0.0 594.855 -0.001 Vet = 0.09
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 8
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
-14.29 61.304 KFactor= -1.83
102 31.65 11.65 3T 241.494 1439.000 61.306
to 150.0 0.0 241.494 6.930
FT 31.65 0.0 0.0 1680.494 0.003 Vel = 0.10
0.0
31.65 68.239 K Factor = 3.83
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
1!'t2D iL c2
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : CYPRESS AT THE PRESERVE
Building : PLAN 2
Location : ALT. CALC AREA 1
System : 1
Contract
Data File : ALT. PLAN2 CAl 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Listed Flow at Start Point - 13 Gpm
Listed Pres. at Start Point - 7 Psi
MAXIMUM LISTED SPACING 16 x 16
Domestic Flow Added - Gpm
Additional Flow Added - Gpm
Elevation at Highest Outlet - Feet
Note:
System Type
(X) Wet ( ) Dry
Deluge ( ) PreAction
Sprinkler or Nozzle
Make RELIABLE Model RFC49
Size 7/16 K-Factor 4.9
Temperature Rating 165
Page 1
Date 5/25/17
NP Mechanical
CYPRESS AT THE PRESERVE
HYDRAULIC DESIGN INFORMATION SHEET
Name - CYPRESS AT THE PRESERVE Date - 5,'25/17
Location - ALT. CALC AREA 1
Building - PLAN 2 System No. - 1
Contractor - NP MECHANICAL Contract No. -
Calculated By - MG Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9!_0
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )l (X)2 ( )4
S ( )Other
T ( )Specific Ruling Made by Date
E
M
D
B
S
I
G
N
Calculation Gpm Required 26.069 Psi Required 52.020 At BR
Summary C-Factor Used: Overhead 150 Underground 150
Pump Data: Tank or Reservoir:
Rated Cap. Cap.
@ Psi Elev.
Elev.
Other Well
Proof Flow Gpm
W Water Flow Test:
A Date of Test -
T Time of Test -
B Static (Psi) - 94
R Residual (Psi) - 66
Flow (Gpm) - 3750
S Elevation - 114
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical Page 2
CYPRESS AT THE PRESERVE Date 5/25/17
City Water Supply: Demand:
Cl - Static Pressure : 84.6 Dl - Elevation : 12.127
C2 - Residual Pressure: 59.4 D2 - System Flow : 26.069
C2 - Residual Flow : 3750 D2 - System Pressure : 80.866
Hose ( Demand) : 5
D3 - System Demand : 31.069
Safety Margin : 3.733
150
140
130
p120
R11°
E10°
s 9°
80
D 3 U 70 -
C2
R 60 - _____ _______ _________ ___________ _____________ _______________ _________________ __________________
E5°
40
30
20
10 --Dl—
U
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N I 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
CYPRESS AT THE PRESERVE Date 5/25/17
Fitting Legend
Abbrev. Name 1/2 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
F NFPA 13 45'Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N* CPVC9O'EllHarvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCCouplinglee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 1390' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors; of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure / Flow Summary - STANDARD
NP Mechanical Page 4
CYPRESS AT THE PRESERVE Date 5/25/17
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow Density Area Press
Actual Req.
Hi 9.0 4.9 7.04 na 13.0 0.05 256 7.039
H2 9.0 4.9 7.11 na 13.07 0.05 256 7.0 H3 19.0 14.84 na
H4 19.0 16.46 na
H5 19.0 17.61 na
Dl 10.0 7.36 na
D2 10.0 7.44 na
1 10.0 8.78 na
2 20.0 10.26 na
3 20.0 12.48 na
4 20.0 13.4 na
D3 20.0 14.41 na
5 20.0 14.41 na
6 20.0 17.76 na
7 20.0 18.57 na
12 20.0 25.18 na
D5 20.0 17.18 na
8 20.0 17.18 na
D4 20.0 16.03 na
9 20.0 16.03 na
10 20.0 14.4 na
11 20.0 13.18 na
13 10.0 35.33 na
14 10.0 38.77 na
15 10.0 41.41 na
TRA 10.0 42.6 na
BR 2.0 52.02 na 5.0
X 2.0 53.1 na
EL -3.0 55.69 na
Ml -3.0 61.2 na
M2 -3.0 65.42 na
CM -3.0 73.93 na
100 -3.0 73.93 na
101 -3.0 73.93 na
102 -3.0 73.93 na
103 -3.0 73.93 na
104 -3.0 73.93 na
FT -19.0 80.87 na
The maximum velocity is 13.94 and it occurs in the pipe between nodes 1 and 2
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 13.00 0.874 N 7.0 1.000 7.039 K Factor= 4.90
to 150.0 0.0 7.000 -0.433
Di 13.0 0.0944 0.0 8.000 0.755 Vel = 6.95
0.0
13.00 7.361 K Factor = 4.79
H2 13.07 0.874 N 7.0 1.000 7.113 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D2 13.07 0.0954 0.0 8.000 0.763 Vel = 6.99
0.0
13.07 7.443 K Factor = 4.79
H3 0.0 0.874 N 7.0 1.000 14.841
to 150.0 0.0 7.000 -0.433
D3 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 14.408 K Factor = 0
H4 0.0 0.874 N 7.0 1.000 16.462
to 150.0 0.0 7.000 -0.433
D4 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 16.029 K Factor = 0
H5 0.0 0.874 N 7.0 1.000 17.611
to 150.0 0.0 7.000 -0.433
D5 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 17.178 K Factor =0
Di 13.00 0.874 N 7.0 5.000 7.361
to 150.0 0 3.0 10.000 0.0
1 13.0 0.0944 0.0 15.000 1.416 Vel = 6.95
0.0
13.00 8.777 K Factor = 4.39
D2 13.07 0.874 N 7.0 6.000 7.443
to 150.0 R 1.0 8.000 0.0
1 13.07 0.0953 0.0 14.000 1.334 Vel = 6.99
1 13.00 0.874 N 7.0 10.000 8.777
to 150.0 0.0 7.000 -4.331
2 26.07 0.3420 0.0 17.000 5.814 Vel = 13.94
2 0.0 0.874 0 3.0 3.500 10.260
to 150.0 0.0 3.000 0.0
3 26.07 0.3422 0.0 6.500 2.224 Vel = 13.94
3 -14.59 0.874 N 7.0 5.167 12.484
to 150.0 0.0 7.000 0.0
4 11.48 0.0750 0.0 12.167 0.912 Vel= 6.14
4 0.0 0.874 3R 3.0 10.500 13.396
to 150.0 0.0 3.000 0.0
5 11.48 0.0750 0.0 13.500 1.012 Vel= 6.14
0.0
11.48 14.408 K Factor = 3.02
D3 0.0 0.874 0 3.0 6.750 14.408
to 150.0 0.0 3.000 0.0
5 0.0 0.0 0.0 9.750 0.0 Vel = 0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
5 11.48 0.874 4R 4.0 26.667 14.408
to 150.0 2N 14.0 18.000 0.0
6 11.48 0.0750 0.0 44.667 3.350 Vel= 6.14
6 0.0 0.874 R 1.0 6.833 17.758
to 150.0 0 3.0 4.000 0.0
7 11.48 0.0750 0.0 10.833 0.812 Vel= 6.14
7 14.59 0.874 2N 14.0 5.333 18.570
to 150.0 0.0 14.000 0.0
12 26.07 0.3420 0.0 19.333 6.612 Vel = 13.94
12 0.0 0.874 N 7.0 10.000 25.182
to 150.0 0.0 7.000 4.331
13 26.07 0.3421 0.0 17.000 5.815 Vel = 13.94
0.0
26.07 35.328 K Factor = 4.39
7 -14.59 0.874 0 3.0 8.917 18.570
to 150.0 0.0 3.000 0.0
8 -14.59 -0.1168 0.0 11.917 -1.392 Vel = 7.80
0.0
-14.59 17.178 K Factor = -3.52
D5 0.0 0.874 N 7.0 7.667 17.178
to 150.0 R 1.0 8.000 0.0
8 0.0 0.0 0.0 15.667 0.0 Vel = 0
8 -14.59 0.874 R 1.0 8.833 17.178
to 150.0 0.0 1.000 0.0
9 -14.59 -0.1169 0.0 9.833 -1.149 Vel= 7.80
0.0
-14.59 16.029 K Factor = -3.64
D4 0.0 0.874 0 3.0 1.500 16.029
to 150.0 0.0 3.000 0.0
9 0.0 0.0 0.0 4.500 0.0 Vet = 0
9 -14.59 0.874 N 7.0 6.917 16.029
to 150.0 0.0 7.000 0.0
10 -14.59 -0.1169 0.0 13.917 -1.627 Vel= 7.80
10 0.0 0.874 N 7.0 3.500 14.402
to 150.0 0.0 7.000 0.0
11 -14.59 -0.1169 0.0 10.500 -1.227 Vel = 7.80
11 0.0 0.874 2R 2.0 3.917 13.175
to 150.0 0.0 2.000 0.0
3 -14.59 -0.1168 0.0 5.917 -0.691 Vel = 7.80
0.0
-14.59 12.484 K Factor = -4.13
13 26.07 1.101 R 1.0 11.000 35.328
to 150.0 2N 14.0 20.000 0.0
14 26.07 0.1111 0 5.0 31.000 3.444 Vel = 8.79
14 0.0 1.101 R 1.0 10.750 38.772
to 150.0 N 7.0 13.000 0.0
15 26.07 0.1111 0 5.0 23.750 2.638 Vel= 8.79
15 0.0 1.101 N 7.0 3.750 41.410
to 150.0 0.0 7.000 0.0
TRA 26.07 0.1111 0.0 10.750 1.194 Vel = 8.79
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
26.07 42.604 K Factor = 3.99
TRA 26.07 1.101 2R 2.0 8.000 42.604
to 150.0 S 9.563 18.562 6.465 * * Fixed Loss = 3
BR 26.07 0.1111 Fsp 0.0 26.562 2.951 Vel = 8.79
N 7.0
BR 5.00 1.101 0 5.0 2.000 52.020 Qa=5
to 150.0 0.0 5.000 0.0
X 31.07 0.1537 0.0 7.000 1.076 Vel= 10.47
X 0.0 1.244 0.0 5.000 53.096
to 150.0 0.0 0.0 2.166
EL 31.07 0.0846 0.0 5.000 0.423 Vel = 8.20
EL 0.0 1.244 0.0 65.000 55.685
to 150.0 0.0 0.0 0.0
Ml 31.07 0.0848 0.0 65.000 5.512 Vel = 8.20
Ml 0.0 1.025 0.0 1.000 61.197
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 31.07 0.2180 0.0 1.000 0.218 Vel= 12.08
M2 0.0 0.995 T 5.841 28.000 65.415
to 150.0 0.0 5.841 0.0
CM 31.07 0.2516 0.0 33.841 8.516 Vet = 12.82
CM -14.03 7.98 3F 40.774 324.000 73.931
to 150.0 T 52.855 93.629 0.0
100 17.04 0.0 0.0 417.629 0.001 VeI= 0.11
100 0.87 7.98 T 52.855 295.000 73.932
to 150.0 0.0 52.855 0.0
101 17.91 0.0 0.0 347.855 0.001 Vel= 0.11
0.0
17.91 73.933 K Factor = 2.08
100 -0.87 7.98 2T 105.71 381.000 73.932
to 150.0 0.0 105.710 -1.299
105 -0.87 0.0 0.0 486.710 0.0 Vel = 0.01
0.0
-0.87 72.633 KFactor= -0.10
101 17.91 11.65 F 17.441 175.000 73.933
to 150.0 T 80.498 97.939 0.0
102 17.91 0.0 0.0 272.939 0.0 Vet = 0.05
102 -31.07 11.65 F 17.441 532.000 73.933
to 150.0 T 80.498 97.939 0.0
103 -13.16 0.0 0.0 629.939 0.0 Vet = 0.04
103 0.0 7.98 1 52.855 542.000 73.933
to 150.0 0.0 52.855 0.0
104 -13.16 0.0 0.0 594.855 -0.001 Vet = 0.08
104 14.03 11.65 T 80.498 207.000 73.932
to 150.0 0.0 80.498 -1.299
105 0.87 0.0 0.0 287.498 0.0 Vet = 0
0.0
0.87 72.633 K Factor = 0.10
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 8
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf!Ft Eqv. Ln. Total Pf Pn
104 -14.03 7.98 1 52.855 542.000 73.932
to 150.0 0.0 52.855 0.0
CM -14.03 0.0 0.0 594.855 -0.001 Vel = 0.09
0.0
-14.03 73.931 K Factor = -1.63
102 31.07 11.65 3T 241.494 1439.000 73.933
to 150.0 0.0 241.494 6.930
FT 31.07 0.0 0.0 1680.494 0.003 Vel= 0.09
0.0
31.07 80.866 K Factor = 3.46
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : CYPRESS AT THE PRESERVE
Building : PLAN 2
Location ALT. CALC AREA 2
System : 1
Contract
Data File : ALT. PLAN2 CA2 20X20.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page 1
CYPRESS AT THE PRESERVE Date 5/25/17
HYDRAULIC DESIGN INFORMATION SHEET
Name - CYPRESS AT THE PRESERVE Date - 5/25/17
Location - ALT. CALC AREA 2
Building - PLAN 2 System No. - 1
Contractor - NP MECHANICAL Contract No. -
Calculated By - MG Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 91_0fl
OCCUPANCY - LIGHT HAZARD
Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Number of Sprinklers Flowing: (X)1 ( )2 ( )4
)Other
)Specific Ruling Made by Date
Listed Flow at Start Point - 20 Gpm System Type
Listed Pres. at Start Point - 16.7 Psi (X) Wet ( Dry
MAXIMUM LISTED SPACING 20 x 20 ( ) Deluge ( ) PreAction
Domestic Flow Added - Gpm Sprinkler or Nozzle
Additional Flow Added - Gpm Make RELIABLE Model RFC49
Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
Note: Temperature Rating 165
Calculation Gpm Required 20.024 Psi Required 48.491 At BR
Summary C-Factor Used: Overhead 150 Underground 150
W Water Flow Test: Pump Data: Tank or Reservoir:
A Date of Test - Rated Cap. Cap.
T Time of Test - @ Psi Elev.
E Static (Psi) - 94 Elev.
R Residual (Psi) - 66 Other Well
Flow (Gpm) - 3750 Proof Flow Gpm
S Elevation - 114
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
S
Y
S
T
E
M
D
E
S
I
G
N
Water Supply Curve C
NP Mechanical Page 2
CYPRESS AT THE PRESERVE Date 5/25/17
City Water Supply: Demand:
Cl - Static Pressure : 84.6 Dl - Elevation : 16.458
C2 - Residual Pressure: 594 D2 - System Flow : 20.024
C2 - Residual Flow : 3750 D2 - System Pressure : 72.141
Hose ( Demand) : 5
D3 - System Demand : 25.024
Safety Margin : 12.457
150
140
130
P 120
R11°
E10°
s 9° el
80 D2
u 70
DA
-
C2
R 60
E5°
40
30
20
Dl
U MdJh.I I I
10
I I I I
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW (N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
CYPRESS ATTHE PRESERVE Date 5/25/17
Fitting Legend
Abbrev. Name /2 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
F NFPA 13 45 Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90EII Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R* CPVCcouplingTee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 13 90 Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Units Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with The fittinqs marked with a show equivalent lengths valii
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values tor fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Hi 9.0 26.01 na
H2 9.0 .26.01 na
H3 19.0 4.9 16.7 na
H4 19.0 23.16 na
H5 19.0 23.64 na
Dl 10.0 25.58 na
D2 10.0 25.58 na
10.0 25.58 na
2 20.0 21.25 na
3 20.0 21.25 na
4 20.0 20.65 na
D3 20.0 17.95 na
5 20.0 19.99 na
6 20.0 23.05 na
7 20.0 23.79 na
12 20.0 27.85 na
D5 20.0 23.21 na
8 20.0 23.21 na
D4 20.0 22.73 na
9 20.0 22.73 na
10 20.0 22.05 na
11 20.0 21.54 na
13 10.0 35.75 na
14 10.0 37.86 na
15 10.0 39.48 na
TRA 10.0 40.21 na
BR 2.0 48.49 na
X 2.0 49.21 na
EL -3.0 51.66 na
Mi -3.0 55.36 na
M2 -3.0 59.5 na
CM -3.0 65.21 na
100 -3.0 65.21 na
101 -3.0 65.21 na
102 -3.0 65.21 na
103 -3.0 65.21 na
104 -3.0 65.21 na
FT -19.0 72.14 na
20.02 0.05 400 16.7
1øJ
Pressure / Flow Summary - STANDARD
NP Mechanical Page 4 CYPRESS AT THE PRESERVE Date 5/25/17
Node Elevation K-Fact Pt Pn Flow Density Area Press No. Actual Actual Req.
The maximum velocity is 10.71 and it occurs in the pipe between nodes H3 and D3
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
Hi 0.0 0.874 N 7.0 1.000 26.010
to 150.0 0.0 7.000 -0.433
Di 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 25.577 K Factor = 0
H2 0.0 0.874 N 7.0 1.000 26.010
to 150.0 0.0 7.000 -0.433
D2 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 25.577 K Factor = 0
H3 20.02 0.874 N 7.0 1.000 16.700 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D3 20.02 0.2099 0.0 8.000 1.679 Vel = 10.71
0.0
20.02 17.946 K Factor = 4.73
H4 0.0 0.874 N 7.0 1.000 23.161
to 150.0 0.0 7.000 -0.433
D4 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 22.728 K Factor = 0
H5 0.0 0.874 N 7.0 1.000 23.641
to 150.0 0.0 7.000 -0.433
D5 0.0 0.0 0.0 8.000 0.0 Vel = 0
0.0
0.0 23.208 K Factor = 0
Di 0.0 0.874 N 7.0 5.000 25.577
to 150.0 0 3.0 10.000 0.0
1 0.0 0.0 0.0 15.000 0.0 Vel = 0
0.0
0.0 25.577 K Factor = 0
D2 0.0 0.874 N 7.0 6.000 25.577
to 150.0 R 1.0 8.000 0.0
1 0.0 0.0 0.0 14.000 0.0 Vel = 0
1 0.0 0.874 N 7.0 10.000 25.577
to 150.0 0.0 7.000 -4.331
2 0.0 0.0 0.0 17.000 0.0 Vel = 0
2 0.0 0.874 0 3.0 3.500 21.246
to 150.0 0.0 3.000 0.0
3 0.0 0.0 0.0 6.500 0.0 Vel = 0
3 -9.10 0.874 N 7.0 5.167 21.246
to 150.0 0.0 7.000 0.0
4 -9.1 -0.0488 0.0 12.167 -0.594 Vel = 4.87
4 0.0 0.874 3R 3.0 10.500 20.652
to 150.0 0.0 3.000 0.0
5 -9.1 -0.0488 0.0 13.500 -0.659 Vel = 4.87
0.0
-9.10 19.993 K Factor = -2.04
D3 20.02 0.874 0 3.0 6.750 17.946
to 150.0 0.0 3.000 0.0
5 20.02 0.2099 0.0 9.750 2.047 Vel = 10.71
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Oa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
5 -9.10 0.874 4R 4.0 26.667 19.993
to 150.0 2N 14.0 18.000 0.0
6 10.92 0.0684 0.0 44.667 3.055 Vel = 5.84
6 0.0 0.874 R 1.0 6.833 23.048
to 150.0 0 3.0 4.000 0.0
7 10.92 0.0684 0.0 10.833 0.741 Vel = 5.84
7 9.10 0.874 2N 14.0 5.333 23.789
to 150.0 0.0 14.000 0.0
12 20.02 0.2100 0.0 19.333 4.059 Vel = 10.71
12 0.0 0.874 N 7.0 10.000 27.848
to 150.0 0.0 7.000 4.331
13 20.02 0.2099 0.0 17.000 3.569 Vel = 10.71
0.0
20.02 35.748 K Factor = 3.35
7 -9.10 0.874 0 3.0 8.917 23.789
to 150.0 0.0 3.000 0.0
8 -9.1 -0.0488 0.0 11.917 -0.581 Vel = 4.87
0.0
-9.10 23.208 KFactor= -1.89
D5 0.0 0.874 N 7.0 7.667 23.208
to 150.0 R 1.0 8.000 0.0
8 0.0 0.0 0.0 15.667 0.0 Vel = 0
8 -9.10 0.874 A 1.0 8.833 23.208
to 150.0 0.0 1.000 0.0
9 -9.1 -0.0488 0.0 9.833 -0.480 Vel = 4.87
0.0
-9.10 22.728 KFactor= -1.91
D4 0.0 0.874 0 3.0 1.500 22.728
to 150.0 0.0 3.000 0.0
9 0.0 0.0 0.0 4.500 0.0 Vel = 0
9 -9.10 0.874 N 7.0 6.917 22.728
to 150.0 0.0 7.000 0.0
10 -9.1 -0.0489 0.0 13.917 -0.680 Vel = 4.87
10 0.0 0.874 N 7.0 3.500 22.048
to 150.0 0.0 7.000 0.0
11 -9.1 -0.0489 0.0 10.500 -0.513 Vel= 4.87
11 0.0 0.874 2R 2.0 3.917 21.535
to 150.0 0.0 2.000 0.0
3 -9.1 -0.0488 0.0 5.917 -0.289 Vel = 4.87
0.0
-9.10 21.246 KFactor= -1.97
13 20.02 1.101 R 1.0 11.000 35.748
to 150.0 2N 14.0 20.000 0.0
14 20.02 0.0682 0 5.0 31.000 2.114 Vel= 6.75
14 0.0 1.101 R 1.0 10.750 37.862
to 150.0 N 7.0 13.000 0.0
15 20.02 0.0682 0 5.0 23.750 1.620 Vel = 6.75
15 0.0 1.101 N 7.0 3.750 39.482
to 150.0 0.0 7.000 0.0
TRA 20.02 0.0682 0.0 10.750 0.733 Vel = 6.75
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftngs Pe Pv ******* Notes
Point at Pf/Ft Eqv. Ln. Total Pf Pn
0.0
20.02 40.215 K Factor = 3.16
TRA 20.02 1.101 2R 2.0 8.000 40.215
to 150.0 S 9.563 18.562 6.465 * * Fixed Loss = 3
BR 20.02 0.0682 Fsp 0.0 26.562 1.811 Vet = 6.75
N 7.0
BR 5.00 1.101 0 5.0 2.000 48.491 0a=5
to 150.0 0.0 5.000 0.0
X 25.02 0.1030 0.0 7.000 0.721 Vel = 8.43
X 0.0 1.244 0.0 5.000 49.212
to 150.0 0.0 0.0 2.166
EL 25.02 0.0566 0.0 5.000 0.283 Vel = 6.60
EL 0.0 1.244 0.0 65.000 51.661
to 150.0 0.0 0.0 0.0
Ml 25.02 0.0568 0.0 65.000 3.694 Vel = 6.60
Ml 0.0 1.025 0.0 1.000 55.355
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 25.02 0.1460 0.0 1.000 0.146 Vel= 9.73
M2 0.0 0.995 T 5.841 28.000 59.501
to 150.0 0.0 5.841 0.0
CM 25.02 0.1686 0.0 33.841 5.707 Vel = 10.32
CM -11.30 7.98 3F 40.774 324.000 65.208
to 150.0 T 52.855 93.629 0.0
100 13.72 0.0 0.0 417.629 0.001 Vel = 0.09
100 0.70 7.98 T 52.855 295.000 65.209
to 150.0 0.0 52.855 0.0
101 14.42 0.0 0.0 347.855 0.001 Vel = 0.09
0.0
14.42 65.210 K Factor= 1.79
100 -0.70 7.98 2T 105.71 381.000 65.209
to 150.0 0.0 105.710 -1.299
105 -0.7 0.0 0.0 486.710 -0.001 Vel = 0
0.0
-0.70 63.909 K Factor = -0.09
101 14.42 11.65 F 17.441 175.000 65.210
to 150.0 T 80.498 97.939 0.0
102 14.42 0.0 0.0 272.939 0.0 Vel = 0.04
102 -25.02 11.65 F 17.441 532.000 65.210
to 150.0 T 80.498 97.939 0.0
103 -10.6 0.0 0.0 629.939 0.0 Vet = 0.03
103 0.0 7.98 1 52.855 542.000 65.210
to 150.0 0.0 52.855 0.0
104 -10.6 0.0 0.0 594.855 -0.001 Vel = 0.07
104 11.30 11.65 T 80.498 207.000 65.209
to 150.0 0.0 80.498 -1.299
105 0.7 0.0 0.0 287.498 -0.001 Vel = 0
0.0
0.70 63.909 K Factor = 0.09
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical
CYPRESS AT THE PRESERVE
Page 8
Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. C" or Ftng's Pe Pv ******* Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
104 -11.30 7.98 T 52.855 542.000 65.209
to 150.0 0.0 52.855 0.0
CM -11.3 0.0 0.0 594.855 -0.001 Vel = 0.07
0.0
-11.30 65.208 K Factor = -1.40
102 25.02 11.65 3T 241.494 1439.000 65.210
to 150.0 0.0 241.494 6.930
FT 25.02 0.0 0.0 1680.494 0.001 Vel = 0.08
0.0
25.02 72.141 K Factor = 2.95
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
MECHANICAL
NP Mechanical
9225 Stellar Court, Suite A
Corona, CA 92883
951-667-4220
Job Name : CYPRESS AT THE PRESERVE
Building : PLAN 2
Location : ALT. CALC AREA 3
System : 1
Contract
Data File : ALT. PLAN2 CA3 16X16.WXF
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
NP Mechanical Page
CYPRESS ATTHE PRESERVE Date 5/25/17
HYDRAULIC DESIGN INFORMATION SHEET
Name - CYPRESS AT THE PRESERVE Date - 5/25/17
Location - ALT. CALC AREA 3
Building - PLAN 2 System No. - 1
Contractor - NP MECHANICAL Contract No. -
Calculated By - MG Drawing No. - 1
Construction: (X) Combustible ( ) Non-Combustible Ceiling Height 9!_011
OCCUPANCY - LIGHT HAZARD
S Type of Calculation: ( )NFPA 13 Residential ( )NFPA 13R (X)NFPA 13D
Y Number of Sprinklers Flowing: ( )l (X)2 ( )4
S )Other
T )Specific Ruling Made by Date
B
M Listed Flow at Start Point - 13 Gpm System Type
Listed Pres. at Start Point - 7 Psi (X) Wet ( ) Dry
D MAXIMUM LISTED SPACING 16 x 16 Deluge ( ) PreAction
E Domestic Flow Added - Gpm Sprinkler or Nozzle
S Additional Flow Added - Gpm Make RELIABLE Model RFC49
I Elevation at Highest Outlet - Feet Size 7/16 K-Factor 4.9
G Note: Temperature Rating 165
N
Calculation Gpm Required 26.584 Psi Required 45.660 At BR
Summary C-Factor Used: Overhead 150 Underground 150
Pump Data: Tank or Reservoir:
Rated Cap. Cap.
8 Psi Elev.
Elev.
Other Well
Proof Flow Gpm
W Water Flow Test:
A Date of Test -
T Time of Test -
E Static (Psi) - 94
R Residual (Psi) - 66
Flow (Gpm) - 3750
S Elevation - 114
P Location:
P
L Source of Information:
Y
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Water Supply Curve C
NP Mechanical
CYPRESS AT THE PRESERVE
Page 2
Date 5/25/17
City Water Supply: Demand: Cl -Static Pressure : 84.6 Dl - Elevation : 16.458 C2 - Residual Pressure: 59.4 D2 - System Flow :26.584 C2 - Residual Flow : 3750 D2 - System Pressure : 74.992
Hose ( Demand) : 5
D3 - System Demand : 31.584
Safety Margin : 9.604
150
140
130
p120
R°
E10°
s 90
-_
el
80 - ______ -
u 70 D3 - C2
R 60
E5°
40
30
Dl
20
I.I.I.I.I
10
... .. .. I.... I.... ....
400 800 1200 1600 2000 2400 2800 3200 3600
FLOW ( N A 1.85)
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Fittings Used Summary
NP Mechanical Page 3
CYPRESS ATTHE PRESERVE Date 5/25/17
Fitting Legend
Abbrev. Name ½ 3/4 1 11/4 11/2 2 21/2 3 31/2 4 5 6 8 10 12 14 16 18 20 24
F NFPA 1345Elbow 1 1 1 1 2 2 3 3 3 4 5 7 9 11 13 17 19 21 24 28
Fsp Flow Switch Potter VSR Fitting generates a Fixed Loss Based on Flow
N * CPVC 90EH Harvel-Spears 7 7 8 9 11 12 13 0 0 0 0 0 0 0 0 0 0 0 0
0* CPVCTee - Branch 3 3 5 6 8 10 12 15 0 0 0 0 0 0 0 0 0 0 0 0
R * CPVC Coupling Tee - Run 1 1 1 1 1 1 2 2 0 0 0 0 0 0 0 0 0 0 0 0
S NFPA 13 Swing Check 0 0 5 7 9 11 14 16 19 22 27 32 45 55 65
T NFPA 13 90 Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121
Units Summary
Diameter Units Inches
Length Uiiis Feet
Flow Units US Gallons per Minute
Pressure Units Pounds per Square Inch
Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters.
Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors
of 120 except as noted with * The fittings marked with a * show equivalent lengths values
supplied by manufacturers based on specific pipe diameters and CFactors and they require no
adjustment. All values for fittings not marked with a * will be adjusted in the calculation
for CFactors of other than 120 and diameters other than Sched 40 per NFPA.
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Pressure I Flow Summary - STANDARD
NP Mechanical Page 4
CYPRESS AT THE PRESERVE Date 5/25/17
Node
No.
Elevation K-Fact Pt
Actual
Pn Flow Density
Actual
Area Press
Req.
Hi 9.0 14.07 na
H2 9.0 14.07 na
H3 19.0 10.39 na
H4 19.0 4.9 7.68 na 13.58 0.05 256 7.0
H5 19.0 4.9 7.04 na 13.0 0.05 256 7.039
Dl 10.0 13.64 na
D2 10.0 13.64 na
10.0 13.64 na
2 20.0 9.31 na
3 20.0 9.31 na
4 20.0 9.62 na
D3 20.0 9.96 na
5 20.0 9.96 na
6 20.0 11.1 na
7 20.0 11.38 na
12 20.0 18.23 na
D5 20.0 7.36 na
8 20.0 8.84 na
D4 20.0 8.07 na
9 20.0 8.53 na
10 20.0 8.89 na
11 20.0 9.15 na
13 10.0 28.59 na
14 10.0 32.16 na
15 10.0 34.9 na
TRA 10.0 36.14 na
BR 2.0 45.66 na 5.0
X 2.0 46.77 na
EL -3.0 49.37 na
Ml -3.0 55.05 na
M2 -3.0 59.28 na
CM -3.0 68.06 na
100 -3.0 68.06 na
101 -3.0 68.06 na
102 -3.0 68.06 na
103 -3.0 68.06 na
104 -3.0 68.06 na
FT -19.0 74.99 na
The maximum velocity is 14.21 and it occurs in the pipe between nodes 7 and 12
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 5
CYPRESS AT THE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftng's Pe Pv Notes
Point Ot Pf/Ft Eqv. Ln. Total Pf Pn
Hi 0.0 0.874 N 7.0 1.000 14.070
to 150.0 0.0 7.000 -0.433
Dl 0.0 -0.0001 0.0 8.000 -0.001 Vet = 0
0.0
0.0 13.636 K Factor = 0
H2 0.0 0.874 N 7.0 1.000 14.070
to 150.0 0.0 7.000 -0.433
D2 0.0 -0.0001 0.0 8.000 -0.001 Vet = 0
0.0
0.0 13.636 K Factor =0
H3 0.0 0.874 N 7.0 1.000 10.394
to 150.0 0.0 7.000 -0.433
D3 0.0 -0.0001 0.0 8.000 -0.001 Vet = 0
0.0
0.0 9.960 K Factor = 0
H4 13.58 0.874 N 7.0 1.000 7.684 K Factor = 4.90
to 150.0 0.0 7.000 -0.433
D4 13.58 0.1025 0.0 8.000 0.820 Vet = 7.26
0.0
13.58 8.071 K Factor = 4.78
H5 13.00 0.874 N 7.0 1.000 7.039 K Factor =4.90
to 150.0 0.0 7.000 -0.433
D5 13.0 0.0944 0.0 8.000 0.755 Vet = 6.95
0.0
13.00 7.361 K Factor = 4.79
Dl 0.0 0.874 N 7.0 5.000 13.636
to 150.0 0 3.0 10.000 0.0
1 0.0 0.0 0.0 15.000 0.0 Vet = 0
0.0
0.0 13.636 K Factor = 0
D2 0.0 0.874 N 7.0 6.000 13.636
to 150.0 R 1.0 8.000 0.0
1 0.0 0.0 0.0 14.000 0.0 Vet = 0
1 0.0 0.874 N 7.0 10.000 13.636
to 150.0 0.0 7.000 -4.331
2 0.0 0.0 0.0 17.000 0.0 Vet = 0
2 0.0 0.874 0 3.0 3.500 9.305
to 150.0 0.0 3.000 0.0
3 0.0 0.0 0.0 6.500 0.0 Vet = 0
3 6.41 0.874 N 7.0 5.167 9.305
to 150.0 0.0 7.000 0.0
4 6.41 0.0256 0.0 12.167 0.311 Vet= 3.43
4 0.0 0.874 3R 3.0 10.500 9.616
to 150.0 0.0 3.000 0.0
5 6.41 0.0255 0.0 13.500 0.344 Vet = 3.43
0.0
6.41 9.960 K Factor = 2.03
D3 0.0 0.874 0 3.0 6.750 9.960
to 150.0 0.0 3.000 0.0
5 0.0 0.0 0.0 9.750 0.0 Vet = 0
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 6
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Oa Dia. Fitting Pipe Pt Pt
Ref. "C' or Ftng's Pe Pv Notes
Point at Pt/Ft Eqv. Ln. Total Pt Pn
5 6.41 0.874 4R 4.0 26.667 9.960
to 150.0 2N 14.0 18.000 0.0
6 6.41 0.0255 0.0 44.667 1.140 Vel = 3.43
6 0.0 0.874 R 1.0 6.833 11.100
to 150.0 0 3.0 4.000 0.0
7 6.41 0.0256 0.0 10.833 0.277 Vet = 3.43
7 20.17 0.874 2N 14.0 5.333 11.377
to 150.0 0.0 14.000 0.0
12 26.58 0.3546 0.0 19.333 6.855 Vet = 14.21
12 0.0 0.874 N 7.0 10.000 18.232
to 150.0 0.0 7.000 4.331
13 26.58 0.3546 0.0 17.000 6.029 Vet = 14.21
0.0
26.58 28.592 K Factor = 4.97
7 -20.17 0.874 0 3.0 8.917 11.377
to 150.0 0.0 3.000 0.0
8 -20.17 -0.2129 0.0 11.917 -2.537 Vet= 10.79
0.0
-20.17 8.840 K Factor = -6.78
D5 13.00 0.874 N 7.0 7.667 7.361
to 150.0 R 1.0 8.000 0.0
8 13.0 0.0944 0.0 15.667 1.479 Vel= 6.95
8 -20.17 0.874 R 1.0 8.833 8.840
to 150.0 0.0 1.000 0.0
9 -7.17 -0.0314 0.0 9.833 -0.309 Vel = 3.83
0.0
-7.17 8.531 K Factor = -2.45
D4 13.58 0.874 0 3.0 1.500 8.071
to 150.0 0.0 3.000 0.0
9 13.58 0.1022 0.0 4.500 0.460 Vet = 7.26
9 -7.17 0.874 N 7.0 6.917 8.531
to 150.0 0.0 7.000 0.0
10 6.41 0.0255 0.0 13.917 0.355 Vel = 3.43
10 0.0 0.874 N 7.0 3.500 8.886
to 150.0 0.0 7.000 0.0
11 6.41 0.0255 0.0 10.500 0.268 Vet = 3.43
11 0.0 0.874 2R 2.0 3.917 9.154
to 150.0 0.0 2.000 0.0
3 6.41 0.0255 0.0 5.917 0.151 Vet = 3.43
0.0
6.41 9.305 K Factor = 2.10
13 26.58 1.101 R 1.0 11.000 28.592
to 150.0 2N 14.0 20.000 0.0
14 26.58 0.1152 0 5.0 31.000 3.570 Vet = 8.96
14 0.0 1.101 R 1.0 10.750 32.162
to 150.0 N 7.0 13.000 0.0
15 26.58 0.1152 0 5.0 23.750 2.736 Vel = 8.96
15 0.0 1.101 N 7.0 3.750 34.898
to 150.0 0.0 7.000 0.0
TRA 26.58 0.1152 0.0 10.750 1.238 Vet = 8.96
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 7
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. 0 or Ftngs Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
0.0
26.58 36.136 K Factor= 4.42
TRA 26.58 1.101 2R 2.0 8.000 36.136
to 150.0 S 9.563 18.562 6.465 * * Fixed Loss = 3
BR 26.58 0.1152 Fsp 0.0 26.562 3.059 Vet= 8.96
N 7.0
BR 5.00 1.101 0 5.0 2.000 45.660 Qa=5
to 150.0 0.0 5.000 0.0
X 31.58 0.1586 0.0 7.000 1.110 Vet= 10.64
X 0.0 1.244 0.0 5.000 46.770
to 150.0 0.0 0.0 2.166
EL 31.58 0.0872 0.0 5.000 0.436 Vet = 8.34
EL 0.0 1.244 0.0 65.000 49.372
to 150.0 0.0 0.0 0.0
Ml 31.58 0.0874 0.0 65.000 5.682 Vet = 8.34
Ml 0.0 1.025 0.0 1.000 55.054
to 150.0 0.0 0.0 4.000 * * Fixed Loss = 4
M2 31.58 0.2250 0.0 1.000 0.225 Vel= 12.28
M2 0.0 0.995 T 5.841 28.000 59.279
to 150.0 0.0 5.841 0.0
CM 31.58 0.2594 0.0 33.841 8.778 Vet = 13.03
CM -14.26 7.98 3F 40.774 324.000 68.057
to 150.0 T 52.855 93.629 0.0
100 17.32 0.0 0.0 417.629 0.002 Vel= 0.11
100 0.88 7.98 1 52.855 295.000 68.059
to 150.0 0.0 52.855 0.0
101 18.2 0.0 0.0 347.855 0.001 Vet = 0.12
0.0
18.20 68.060 K Factor = 2.21
100 -0.88 7.98 2T 105.71 381.000 68.059
to 150.0 0.0 105.710 -1.299
105 -0.88 0.0 0.0 486.710 -0.001 Vel = 0.01
0.0
-0.88 66.759 K Factor = -0.11
101 18.20 11.65 F 17.441 175.000 68.060
to 150.0 1 80.498 97.939 0.0
102 18.2 0.0 0.0 272.939 0.0 Vet = 0.05
102 -31.58 11.65 F 17.441 532.000 68.060
to 150.0 T 80.498 97.939 0.0
103 -13.38 0.0 0.0 629.939 0.0 Vet = 0.04
103 0.0 7.98 T 52.855 542.000 68.060
to 150.0 0.0 52.855 0.0
104 -13.38 0.0 0.0 594.855 -0.001 Vet = 0.09
104 14.26 11.65 T 80.498 207.000 68.059
to 150.0 0.0 80.498 -1.299
105 0.88 0.0 0.0 287.498 -0.001 Vet = 0
0.0
0.88 66.759 K Factor = 0.11
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Final Calculations - Hazen-Williams
NP Mechanical Page 8
CYPRESS ATTHE PRESERVE Date 5/25/17
Hyd. Qa Dia. Fitting Pipe Pt Pt
Ref. "C" or Ftng's Pe Pv Notes
Point Qt Pf/Ft Eqv. Ln. Total Pf Pn
104 -14.26 7.98 T 52.855 542.000 68.059
to 150.0 0.0 52.855 0.0
CM -14.26 0.0 0.0 594.855 -0.002 Vel = 0.09
0.0
-14.26 68.057 K Factor= -1.73
102 31.58 11.65 3T 241.494 1439.000 68.060
to 150.0 0.0 241.494 6.930
FT 31.58 0.0 0.0 1680.494 0.002 Vel = 0.10
0.0
31.58 74.992 K Factor = 3.65
Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087
Bulletin 006 Rev. I
Alllllllllllll Model RFC30 (SIN RA0611)
— ® Model RFC43 (SIN RA0612) Reliable Model RFC49 (SIN
Residential Flat Concealed
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2 with
low GPM requirements.
Features
Very low water flow requirements.
Cover plate attachment (Plain or Perforated)
with ½" (13mm) Total adjustment.
Thread-OniTh read -Off or Push-On/Thread
Off cover attachment option.
Smooth aesthetic ceiling profile.
Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VK KW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has
demonstrated, in fire testing, an ability for controlling
residential fires, and thereby providing significant evacu-
ation time for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and ½" (13mm) of cover adjustment for ease
of installation. The small diameter cover plate is easily
Plain Uover Plate
Perforated Cover Plate
and positively attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residen-
tial Sprinklers to be installed in the residential portions
of any occupancy in accordance with NFPA 13, 13R, &
13D.
The RFC30, RFC43 and RFC49 can reduce the need
for precise cutting of drop nipples. The threaded cover
plate assembly can be adjusted without tools to fit ac-
curately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover
plate assembly.
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Application and Installation
The RFC30, RFC43 and RFC49, for residential instal-
lations, use a 165°F (74°C) fusible solder link in a tun-
ing fork style sprinkler frame with a drop-down deflector.
This assembly is recessed into the ceiling and concealed
by a flat cover plate. The cover plate is attached to the
skirt, using 135°F (57°C) ordinary temperature classifica-
tion solder. When the ceiling temperature rises, the solder
holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
inside to ceiling temperature. The subsequent operation
of the solder link opens the waterway and causes the de-
flector to drop into position to distribute the discharging
water in a hemispherical pattern below the sprinkler de-
flector. Any adjustment of thread engagement between
the cover plate and cup will assure that the drop-down
deflector is properly located below the ceiling. The resi-
dential distribution pattern contains a finer droplet size
than a standard sprinkler, and the pattern produces sig-
nificantly higher wall wetting.
After a 2 /8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexago-
nal body of the sprinkler frame. The Wrench must bottom
out against the cup in order to ensure proper, safe instal-
lation. The sprinkler is then tightened into the pipe fitting.
When inserting or removing the wrench from the sprin-
kler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL
RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COV-
ERS.
Note: A leak tight ½" NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2" (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option,
the cover assembly is pushed onto the cup and final ad-
justment is made by turning the cover clockwise until the
skirt flange makes full contact with the ceiling. Cover re-
moval requires turning in the counter-clockwise direction.
In ceilings that have a plenum space above the
sprinkler, the plenum space may have neutral or neg-
ative pressurization but must not be positively pres-
surized. Inspect all sprinklers after installation to en-
sure that the gap between the cover plate and ceiling
and the 4 slots in the cup are all open and free from
any air flow impediment.
Model Thread Nominal Sprinkler CCP Assembly Max.
Ambient K Max.
(SIN) Size Orifice Temp Rating Temp. Rating
______ Temp. Factor Pressure
Inch (mm) Inch (mm) psi (bar) °F °C °F °C °F °C
RFC 30
(RA0611) 1/2" (15) 21/64(82) 165 74 135 57 100 38 3.0 (43.2) 175 (12)
RFC 43 ½"(15) /8(10) 165 74 (RA0612)
135 57 100 38 4.3(62) 175 (12)
RFC49
(RA 0616) ½ " (15) /16(11) 165 74 135 57 100 38 4.9 (70.6) 175 (12)
Note: 1 bar = 100 Kpa
RFC 30
Ordinary Temp. Rating Max. Coverage Max. Spacing (1165-17174-C)) T op of Deflector Installation Minimum
area
Ft x Ft (m x m) Ft (m) to Ceiling
Inch (mm) Type Spacing
Ft (m) Flow Pressure
GPM (Llmin) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 9(34,1) 9.0 (0,62) Smooth Ceilings 1/2 to 1(13 to 25.4)
Beamed ceilings per NFPA 130, 13R or Concealed 8(2,4)
14 x 14(4,3 x 4,3) 14(4,3) 10(37,8) 11.0 (0,76) 13 installed in beams 1/2 to 1(13 to 25.4)
For Ceiling types refer to NFPA 13, 13R or 130
2.
RFC 43
Ordinary Temp. Rating Max. Coverage Max. Spacing (1650F174°C) Top of Deflector Installation Minimum
area
FtxFt(mxm) Ft (m) to Ceiling
Inch (mm) Type Spacing
Ft (m) Flow Pressure
GPM (1/mm) PSI (bar)
12 x 12(3,6 x 3,6) 12(3,6) 12(4,5) 7.8 (0,54)
Smooth Ceilings 1/2 to 1(13 to 25.4)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 9.1 (0,63)
16 x 16(4,9 x 4,9) 16(4,9) 13(49) 9.1 (0,63) Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams ½ to 1(13 to 25.4)
Concealed 8(2,4)
18 x 18(5,5 x 5,5) 18(5,5) 18(68) 17.5(1,21)
20x20(6,1 x6,1) F 20(6,1) 21 (79) 23.8(1,64)
For Ceiling types refer to NFPA 13, 13R or 130
RFC49
Max. Coverage Max. Spacing
Ordinary Temp. Rating
(165' 4-C) Top of Deflector Minimum
area Ft (m) to Ceiling Installation
ype T Spacing Flow Pressure Ft x Ft (m x m) GPM (L/min) PSI (bar)
Inch (mm) Ft (m)
12 x 12(3,6 x 3,6) 12(3,6) 13(49) 7.0 (0,48)
Smooth Ceilings 1/2 to 1(13 to 25.4)
14 x 14(4,3 x 4,3) 14(4,3) 13(49) 7.0 (0,48)
16 x 16 (4,9 x 4,9) 16(4,9) 13 (49) 7.0(0,48) Beamed Ceilings per NFPA 130, 13R or
13 installed in beams ½ to 1(13 to 25.4)
Concealed 8(2,4)
18 x 18 (5,5 x 5,5) 18(5,5) 17 (64,3) 12.0 (0,83)
20 x 20 (6,1 x 6, 1) 20(6,1) 20(75,73) 16.7(1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprin-
klers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler cover plate as-
sembly which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non-operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specification
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a ½" NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler K-
factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6)
having a 3/8" and 7A6" orifice. Temperature rating
shall be Ordinary 165°F (74°C); cover plate temperature
rating to be 135°F (570C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a ½" cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty - specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA061 1
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
CI
Ordering Information
Specify:
Sprinkler Model
Cover Plate Finish
Thread-On or
Push-On Feature
Cover Plate Finishes0t
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint is
semi-gloss, unless specified
otherwise.
For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-
tom finishes.
1 x 1/2' REDUCING
TEE OR ELBOW I
-----:----t-------
rAccc 7
(58.42mm] D14
CUP
'(12.7OmmJAW(.
COVER ADJUSTMENT
I/2
1 (25.4mm] MAX
DROPPED DEFLECTOR
TO CEILING
FLAT COVER PLATE
ASSEMBLY
HOLE IN CEILING
2 [50.8mm] MAX
FACE OF FITTING
ID FACE OF CEIUNG
DIMENSION
CEiLING
' [4.6mm]
.J (84.21mm] D14.
COVER PLATE: 1/2" t12. 7mm] ADJUSTMENT
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordiiances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the united States, Canada and foreign countries.
Manufactured by
Reliable Automatic Sprinkler Co., Inc. Recycled
Rel (800) 431-1588 Sales Offices Paper
(800) 848-6051 Sales Fax Revision lines indicate updated or new data.
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address EG. Frir(ed in U.S.A. 11/14 P/N 9999970261
Fl Res 30,49,58&76
Recessed Pendent/ F1
R a bil 0
Bulletin 135 Rev.G
Model Fl
Residential Sprinklers for
Design Density of .05 gpmlft
Model Fl Res Sprinklers engineered for the lowest flows
to meet the minimum design density of .05 gpm/ft2
Fl Res 30,49,58 & 76
Recessed Pendent/ EP
El Res 30, 49, 58 & 76 Fl Res 44&58
CCP Pendent Recessed HSW/F2
Fl Res 44 SWC Fl Res 40 Recessed
HSW/F2
The low flow Fl Res sprinklers are specially
engineered for fast thermal response to meet the
sensitive fire protection application needs of the latest
residential market standards (UL 1626 Standard). Upon
fire conditions, rising heat causes a sprinkler's
heat-sensitive glass-bulb to shatter, releasing the
waterway for water flow onto the deflector, evenly
distributing the discharged water to control a fire.
Technical Data:
Thermal Sensor: Nominal 3mm glass-bulb
Sprinkler Frame: Brass Casting
Sprinklers' Pressure Rating : 175 psi
Factory Hydrostatically Tested to 500 psi
Thread Size: ½" NPT (R½)
K-Factor: 3.0 (Actual) - El Res 30 Pendent Sprinkler
4.9 (Actual) - Fl Res 49 Pendent Sprinkler
5.8 (Actual) - Fl Res 58 Pendent & HSW Sprinkler
7.6 (Actual) - El Res 76 Pendent Sprinkler
4.4 (Actual) - El Res 44 HSW Sprinkler
4.0 (Actual) - Fl Res 40 HSW Sprinkler
Density: Minimum 0.05 gpm/ft2
Application
Model El Res Sprinklers are used for Residential Fire
Protection according to UL 1626 Standard*. Be sure
that orifice size, temperature rating, deflector style and
sprinkler type are in accordance with the latest
published standards of The National Fire Protection
Association or the approving authority having
jurisdiction.
103 Fairview Park Drive, Elmsford, New York 10523
Types:
Fl Res 30 Pendent
Fl Res 30 Recessed Pendent/F2
Fl Res 30 Recessed Pendent/FP
Fl Res 49 Pendent
Fl Res 49 Recessed Pendent/Fl
Fl Res 49 Recessed Pendent/FP
Fl Res 58 Pendent
Fl Res 58 Recessed Pendent/Fl
Fl Res 58 Recessed Pendent/FP
Fl Res 76 Pendent
Fl Res 76 Recessed Pendent/Fl
Fl Res 76 Recessed Pendent/FP
Fl Res 30 COP Pendent
Fl Res 49 COP Pendent
Fl Res 58 COP Pendent
16, Fl Res 76 COP Pendent
Fl Res 44 HSW
Fl Res 44 Recessed HSW/F2
Fl Res 58 HSW
Fl Res 58 HSW Recessed HSW/F2
F1 Res 44SWO
Fl Res 40 HSW
Fl Res 40 Recessed HSW/F2
Listings & Approvals
Listed by Underwriters Laboratories Inc. and
UL Certified for Canada (cULus)
NYC MEA 258-93-E
Slope Ceiling Approvals: Refer to Bulletin 035
Sprinklers for .10 Density: Refer to Bulletin 176
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Patents
US Patent No. 6,516,893 applies to the
Model Fl Res 49 & 58 Pendent Sprinklers
Product Description
Model Fl Res Pendent sprinklers (Figs. 1, 2, 3, & 4) are
fast response sprinklers combining excellent durability
high sensitivity glass-bulb and low profile decorative
design. The Fl Res Horizontal Sidewall sprinklers (Figs
5, 6 & 7) are equally attractive when above ceiling piping
cannot be used.
The 3mm glass-bulb pendent sprinklers permit the
efficient use of residential water supplies for sprinkle i
coverage in residential fire protection design.
The Reliable Automatic Sprinkler Co., Inc.,
Installation
Models Fl Res sprinklers are to be installed as
shown. Model Fl, F2 and FR Escutcheons, illustrated
herewith, are the only recessed escutcheons to be used
with Model Fl Res sprinklers. Use of any other
recessed escutcheon will void all approvals and
warranties. For installing Model Fl Res Pendent
sprinklers use only the Model D sprinkler Wrench; for
installing Models Fl Res Recessed Pendent, COP &
Model Fl Res 30, 49, 58 & 76 Pendent
SWC sprinklers use only the Model GFR2 sprinkler
wrench; for installing Model Fl Res Recessed HSW
sprinklers use only the Model GFR2 Sprinkler Wrench.
Use of wrenches other than those specified may
damage these sprinklers. Install Fl Res 44 and 40 HSW
with a ceiling to deflector distance of 4" - 12". Flow arrow
on deflector must point away from near wall and "Top"
marking must face ceiling.
Model Fl Res 30 Recessed
Pendent /172
Model Fl Res 49, 58 & 76
Recessed Pendent/ Fl
'
r9
1 escutcheon, 3/4 (19mm) adjustmer
IJ5FGOJ
Fig. 1 Fig. 2
Fl or F2. Data:
Type Adjustment "A" Face of fitting to
Inch (mm) Inch (mm) ceiling
Inch (mm)
Fl %(19.0) Min,=3/4" (19.1)
Max.=1" (38.1)
3/ 1/ (4.7-24.0) 16 16
F2 Y2 (12.7) Min. 15/" (23.8)
Max. =1%" (38.1)
/6 -1X6 (4.7- 17.4)
* Note: Escutcheons Fl or F2 may be used with
Model Fl Res 49, 58 & 76 Recessed Pendent
2.
Technical Data: Fl Res 30 Pendent and Recessed Pendent
Nominal Sprinkler Max. Max. Actual Sprinkler
Thread Orifice Temp. Pressure Ambient K Length
Size Inch Rating psi Temp. Factor Inch
°F I °c °F 0 (mm) (bar) (mm)
/2"NPT 2)/6 " (8.2) 155
175
68
I 79 175 (12) 100 38 3.0 2.25 (57)
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler Flow Pressure Sprinkler
Spacing gpm (Lpm) psi (bar) Identification
ft (m) Number (SIN)
12 x 12 (3.6x3.6) 8(30.3) 7.0 (0.48) R3511 11(0.76) 14 x 14 (4.3x4.3) 10 (37.8)
Technical Data: Fl Res 49 Pendent and Recessed Pendent
Nominal Sprinkler Max. Max. ACtUal Sprinkler
Thread Orifice Temp. Pressure Ambient K Length
Size Inch Rating psi Temp. Factor Inch
°F I °c °F I °c (mm) (bar) (mm)
2"NPT ''(11) 155
175
68
79 175(12) 100
1501
38
66 Q 2.25(57)
Deflector - to - ceiling
Maximum 1" (25mm) to 4" (100mm)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 13 (49) 7.0 (0.48)
R3516
16.7 (1.14)
14 x 14 (4.3x4.3) 13(49) 7.0 (0.48)
16 x 16 (4.9x4.9) 13 49 7.0 (0.48)
18 x 18 (5.5x5.5) 17(64.3) 12.0(0.83)
20 x 20 (6,1x6.1) 20(75.7)
*Deflector - to - ceiling
Maximum 4" (100mm) to 8" (203mm)
Max. Sprinkler
Spacing
ft_(m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 15 (57) 9.4 (0.65)
R3516
20.2(1.4)
14 x 14 (4.3x4.3) 16(60.5) 10.6 (0.73)
16 x 16 (4.9x4.9) 17(64.3) 12.0(0.83)
18 x 18 (5.5x5.5) 19(72) 15.0(1.0)
20 x 20 (6.1x6.1) 22(83.2)
*Note: The Fl Res 49 pendent and recessed pendent
residential sprinklers can be installed per NFPA 13 in
beamed ceilings meeting the following criteria;
Maximum beam depth = 7" (178mm)
Beam spacing at or greater than 7.5 ft. (2.3m) on center.
Technical Data: Fl Res 58 Pendent and Recessed Pendent
Nominal Sprinkler Max. Max. Sprinkler
Thread Orifice Temp. Pressure Ambient K Length
Size Inch Rating pi Temp. Factor Inch
°F °C °F (mm) (bar) (mm)
½" NPT
(R½)
/' (13) 155
175
68
79 175(12) 100
1501
38
66
5.8 2.25 (57)
Max. Sprinkler Flow Pressure Ceiling -to- Sprinkler
Spacing gpm (Lpm) psi (bar) Deflector Identification
ft (m) Inch (mm) Number (SIN)
12 x 12 (3.6x3.6) 16(61) 7.6 (0.53)
1-4
(25-100) R3513
14x14(4.3x4.3) 16(61) 7.6(0.53)
16 x 16 (4.9x4.9) 16(61) 7.6 (0.53)
18 x 18 (5.5x5.5) 19 (72) 10.8 (0.75)
14.4(1.0) 20 x 20 (6.1x6.1) 22(83.3)
3.
Technical Data: Fl Res 76 Pendent and Recessed Pendent
Nominal Sptlder Max max S13"dw
Thread Orifice Ten3 Ressure Antient K Length
Size Inch
(mm)
Ring psi
(bar)
Ten!,. i:aor hch
(mm) OF 00 OF
3/41 NFl
(R3/4)
732 (13.5)
155
175
68
I 79 175(L4 ) 100
150
38
66
7.6 225 (57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 21 7.6 (0.53)
R7618
9.2 (0.63)
14 x 14 (4.3x4.3) 21 7.6(0.53)
16 x 16 (4.9x4.9) 21 7.6 (0.53)
18 x 18 (5.5x5.5) 21 7.6(0.53)
20 x 20 (6.1x6.1) 23
Model Fl Res 30, 49, 58 & 76 Model Fl Res 30, 49, 58 & 76
Recessed Pendent / FP
FP oush-on/thread-off
escutcheon
2 5/16" 0/A.
[58.7mm]
CUP
CUP
CEILING
A
"A" J COVER ADJUSTMENT
2 5/8" [68. 7mm] 0/A.
HOLE IN CEILING
l"xl/2" REDUCER
1 1/4" /'3/.5mmJ
MAX. FACE OF FITTING
TO FACE OF CEILING
OIMENS'ON
I "8"
2 5/80r., [56.
HOLE IN CEILING
2 5/I5 GEL (5&m0,,I
(VP
CEILING
l/2 (t3,,,,,J MA
FP ADJUSTMENt
3 5/16" 0/A.
135FC04D [84.1mm]
Fl RES 30, 49, 58 & 76 CCP PEND.
IX I/:- REDUCER
I 1/2j'J&Irnn1 MAX.
FACE 3F FITI1NG
IV FACE OF CEILING DIMENSION
Fig, 3 Fig.4
NOTE: The Fl Res 76 will use a 1 x 3/4" reducer,
0
CCP ODtions Data:
Cover Adjustment CCP Height
Inch (mm) Inch (mm)
/2(12.7) 15/6 (24)
/6(79) /4 (19)
FP Data "A":
FP Position Inch (mm)
Max. Recessed /5(11)
Mm. Recessed 15/6 (24)
Technical Data: Fl Res 30 CCP Pendent and Recessed Pendent I FP
CCP
ASSen Sprinklerr
K Max Ma Sprinkler
Thread Orifice Teni
FactorTen!1 PRem"kidi
Length Size Inch Rating Teni
(mm) (MM) OF 00 °F 00 I
NPT 2)/'(82) 155168 1351 57 175 (12) 100138 3.0
(R½)
Max. Sprinkler Flow Pressure Sprinkler
Spacing gpm(Lpm) I psi (bar) Identification I
ft (m) I Number (SIN)--
12 x 12 (3,6x3.6) 8(30.3) 7.0(0.48') R3511 I 13.4 (0.92) 14x_14(4.3x4.3) 11_(41.6')
Technical Data: Fl Res 49 CCP Pendent and Recessed Pendent I FP
Nominal Sprinkler CCP
Assen31y Max. Max. Spder
Thread Orifice Temp.Teni Temp. PressureAmbient K Length
Size Inch Rating r h
(mm) 00 OF I -C OF I
½"
NPT <6(h1) 155168 1351
I
57 175 (12) 100138 4.9 25
(R½) I
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
_
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 13(49) 7.0(0.48)
R3516
14 x 14 (4.3x4.3) 13 (49) 7.0(0.48)
16 x 16 (4.9x4.9) 14 (53) 8.2(0.56)
18 x 18 (5.5x5.5) 18(68.1) 13.5(0.93')
20x20(6.1x6.1) 20(75
Technical Data: Fl
Nominal Sprinkler CCP J Max. Max.
Orifice Ten
j
Sprinkler
Thread I Piessue Ambient K Length
Size Inch Rating I psi Inch
Teni Factor
(mm) (bar) (RIM) °F I 0( I 00 OF I 0(
1/2"NPT (13) 15568I135_57 175(12) 10038 5.8 2.25(57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar )
Sprinkler
Identification
Number (SIN) ____
12x12(3.6x3.6) 16(61) 7.6(0.53)
R3513
1
14 x 14 (4.3x4.3) 16(61) 7.6(0.53)
16 x 16 (4.9x4.9) 16(61) 7.6 (0.53)
18 x 18 (5.5x5.5) 19(72) 1 10.8(0.75)
20 x 20 (6,1x6.1') 22(83.3') 1 14.4(1.0')
Ll)_ 16.7(1.14')' Note: Sprinklers shown in Fig. 3 and Fig. 4 are not
suitable for installation in ceilings which have
positive pressure in the space above.
Res 58 CCP Pendent and Recessed Pendent/FP
Technical Data: Fl Res 76 CCP Pendent and Recessed Pendent/FP
Nominal Sprinkler CCP Max. Max
Thread Orifice Ten. TOTP Piessue Ambient K Sprinkler Length Size Inch Rating psi Temp, Factor Inch (mm) (mm) (bar) I 00 OF 00 OF I 0 OF
3/," NPT
(R3/4')
1%2
(13.5')
15568
1751 79 135 57 175(12) iool
150166
38 7.6 2.25(57)
Max. Sprinkler
Spacing
ft (m)
Flow
gpm (Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6) 21 7.6(0.53)
R7618
14 x 14 (4.3x4.3) 21 7.6(0.53)
16 x 16 (4.9x4.9) 21 7.6(0.53)
18 x 18 (5.5x5.5) 22 8.4(0.58)
20x20(6,1x6.1') 25 10.8(0.74')
5.
Escutcheon, F2, Data:
Type Adjustment I Face of Fitting
to wall Inch (mm) Inch (mm)
F2 (13) 3/1y(47174)I
Model Fl Res 44 & 58 HSW Model Fl Res 44 & 58
Recessed HSW/F2
F2 escutcheon, /2" (1
adjustment
Technical Data: Fl Res 44 HSW & HSW/F2
Nominal Spmkler Max. Max. SpIder
iliead Orifice TenMi Presate Ambient K Lengti
Sim Inch Fti,g psi Ten. Factor Inch
°F I °c p I cc (mm) (bar) (mm)
1/2"NPT Y811 155
1 1751
68 175(12) 100
1501
38 4.4 66
2.45(62)
Max. Sprinkler
spacing
ft (m)
Ceiling
Deflector
Inch (mm)
Sprinkler Temp.
Rating
°F (°C)
Flow
gpm
(Lpm)
Pressure
psi (bar)
Sprinkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
155 (68) 175(79) 12(45.4) 7.5(0.52)
R3531
14 x 14 (4.3x4.3) 155 (68) 175 (79) 14(53.0) 10.2 (0.71)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 16(60.6) 13.3(0.92)
16 x 18 (4.9x5.5) 155 (68) 175(79) 18(68.1) 16.8 (1.16)
18x 18(5.5x5.5) 155(68) 175(79) 19 (72.0) 18.7(l.29)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23(87.1) 27.4(1.89)
12 x 12 (3.6x3.6)
16-12
52-305)
155 (68) 175(79) 14(53.0) 10.2 (0.71)
27.4 (1.89)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 16(60.6) 13.3 (0.92)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 17(64.4) 15.0(1.04)
16 x 18 (4.9x5.5) 155 (68) 175(79) 20(75.7) 20.7(1.43)
16 x 20 (4.9x6.1) 155 (68) 175(79) 23(87.1)
6.
Escutcheon, F2, Data:
Type Adjustment Face of Fitting
to wall Inch (mm) Inch (mm)
F2 (13) 3/1y(47174)
Technical Data: Fl Res 58 HSW & HSW/F2
Nominal Sprnkler Max Max Spñier
Thiead Orifice Ten,. ReSum Ambient K LengUi
Slin Inch Ratiiq psi Tx Factor Inch
OF cc - OF (mm) (bar) cc (mm)
(13)
_
155
175
68 79 175 (12) 100
150
38
I 66 5.8 2.45 (62)
Max. Sprinkler
Spacing
ft (m)
ceiling --
Deflector
Inch (mm)
Sprinkler Temp.
Rating
OF (°c)
Flow
gpm
(Lpm)
Pressure
psi (bar)
Spnnkler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
_
155 (68) 175 (79) 16 (60.6) 7.6 (0.53)
R3533
14 x 14 (4.3x4.3) 155 (68) 175 (79) 18(68.2) 9.7 (0.67)
16 x 16 (4.9x4.9) 155 (68) 175 (79) 21(79.5) 13.2(0.91)
16x 18(4.9x5.5) 155(68) 175(79) 25(94.7) 18.6 (1 .28)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 29(109.8) 25(1.73)
12x 12(3.6x3.6)
6-12
(152-305)
155(68) 175(79) 22(83.3) 14.4(l.0)
28.6(1.97)
14x 14(4.3x4.3) 155(68) 175(79) 22(83.3) 14.4(1.0)
16x 16(4.9x4.9) 155(68) 175(79) 26(98.4) 20.1 (1.39)
16 x 18 (4.9x5.5) 155 (68) 175 (79) 31(117.4)
7.
Model Fl Res 44 SWC rt
4 to t2 (IO7.60,rnn To
__________ I I/4 [if. 75 Mosimum 304.80mm)
Face Of fitting
To Wall Dimension PUSH ON COVER. THEN / TURN TO ADJUST UNtIL
J lIGHT AGAINST WALL.
I S I/2 Reducer
Recommended
Woll
r
2 5116-
TURN COLLAR UNTIL -'
T
WRENCH [42.07mm]
IGHT AGAINSr SPRINKLER 1 21132-
- AdJus
112-
Fl RES 44 SWC
Fig. 5
Technical Data: Fl Res 44 SWC
Thread
Nominal
Orifice
Spriikler
Temp. CTerT
Ratlig
Max.
AntientTeni K
Spvkler
Length
Size Inch F1Iq _________ psi ___________ Factor hJi
OF cc CF I cc (mm) (bar) OF
½" NPT
(R½) 3/"(10) 155 68 135 57 175 (12) 100 38 4.4 2.45 (62)
Max. Sprinkler
Spacing
ft (m)
"A"
Ceiling --
Deflector
Inch (mm)
Flow
gpm
(Lpm)
Pressure
si (b
Sprin kler
Identification
Number (SIN)
12 x 12 (3.6x3.6)
(101-1
4 -
6 52)
13(49.2) 8.7 (0.60;
R3531
20.7(1.43)
14 x 14 (4.3x4.3) 14(53.0) 10.2 (0.71)
16 x 16(4.9x4.9) 17(64.3) 15.0(1.1:
16 x 18 (4.9x5.5) 19(71.8) 18.7(1.13)
16 x 20 (4.9x6.1) 23(87.1) 27.4(l.89)
12 x 12 (3.6x3.6)
6-12
(152-305)
14(52.9) 10.2 (0.71)
14x 14(4.3x4.3) 15(56.7) 11.7(0.81)
16 x 16 (4.9x4.9) 18(68.1) 16.8 (1.16)
16x 18(4.9x5.5) 20(75.6)
11
1 35FG05
Fig. 6
Technical Data: Fl Res 40 HSW & HSW/F2
Nominal SflhIdEr Max Max. Spriiiciej
111 Orifice TetT1 Piessue Ambient K ingth
Size Inch Riiq psi TCITp. Factor hch
°F p
____
(mm) (bar)
___
(mm)
1/2"NPT U (10) 155
175
68 I 79 175(12) 100
150
38
66
4.0 2.45 (62)
2. • Model Fl Res 40 Recessed
ociei i-i ties HSW/F2
F2 escutcheon, " (13mm
aajustment
FACE OF FITTING TO
WALL DIMENSION I
I 1/4 MIN.
(31.8mm] -2 1/4 HOLE 014. l/8 [57.2mm] 2mm] CEILING TO
DEFLECTOR
I" x 1/2 REDUCER DIMENSION
I I5/I6 O14.4
[492mm] 2 27/32 Okk i [72. 2mm]
TURN COLLAR UNTIL
TIGHT AGAINST SPRINKLER
WRENCH BOSS.
- - 1/2 [73mm] 735F006-C ADJUSTMENT
Fl RES 58, 44 & 40 HSW/F2
Fig. 7
Escutcheon. F2. Data:
Type Adjustment Face of Fitting
to wall I Inch (mm) Inch (mm) I
F2 X(13) 1y(47174)
Max. Sprinkler ceiling -to- Sprinkler Temp. Flow Pressure Sprinkler
Spacing Deflector Rating gpm psi (bar) Identification
ft (m) Inch (mm) °F (°C) (Lpm) Number (SIN)
12 x 12 (3.6x3.6)
4-6
(101-152)
155(68) 175 (79) 13(49.0) 10.6 (0.73)
14 x 14 (4.3x4.3) 155 (68) 175 (79) 16(60.5) 16.0(1.10)
16 x 16 (4.9x4.9) 155 (68) 17(64.3) 18.1 (1.24)
16 x 16 (4.9x4.9) 175 (79) 18(68.1) 20.2 (1.39)
_______
16x 18(4.9x5.5) 155(68) 175(79) 20(75.7) 25.0(1.72) R3538 30.2(2.00 8) 18 x 18 (5.5x5.5) 155 (68) 175 (79) 22(83.3)
25.0(1.72)
16 x 20 (4.9x6.1) 155 (68) 175 (79) 23(87.0) 33.1 (2.28)
12 x 12 (3.6x3.6)
6-12
(152-305)
_
155 (68) 175 (79) 13(49.0) 10.6(0.73)
14x14(4.3x4.3) 155(68) 175(79) 17(64,3) 18.1 (1.24)
16x 16(4.9x4.9) 155(68) 175(79) 20(75.7)
Finishes(l)
Standard Finishes
Sprinkler Fl, F2, FP Cover Plates Escutcheons
Bronze Brass White Painted
Chrome Plated Bright Chrome Plated Chrome
White Polyester White Painted
Coated I
Special Application Finishes
Sprinkler Fl, F2, Cover Plates Escutcheons
Bright Brass Bright Brass Bright Brass
Black Plated Black Plated Black Plated
Black Paint Black Paint Black Paint
Off White Off White Off White
Satin Chrome Satin Chrome Satin Chrome
Other finishes and colors are available on special order.
Consult factory for details.
Note: Paint or any other coating applied over the factory finish will
void all approvals and warranties.
Maintenance
Model Fl Res 30, 49, Fl Res 58, Fl Res 76, Fl Res 44
and Fl Res 40 Sprinklers should be inspected quarterly,
and the sprinkler system maintained in accordance with
NFPA 25, 13, 13D, and 13R. Do not clean sprinkler with
soap and water, Ammonia or any other cleaning fluids.
Remove dust by using a soft brush or gentle vacuuming.
Remove any sprinkler which has been painted (other than
factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick
replacement of damaged or operated sprinklers. Prior to
installation, sprinklers should remain in the original cartons
and packaging until used. This will minimize the potential
for damage to sprinklers that could cause improper
operation or non-operation.
Model Fl Res 30, 49 & 58 Pendent
Sprinkler Specifications
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential pendent
sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch from [4/12] to
[8/12], the sprinklers shall be listed for such use.
Deflector-to-ceiling distance listing shall be 1" to 8"
maximum. Sprinkler frame and deflector shall be of bronze
frame construction having a 1/2" NPT thread. Water seal
assembly shall Consist of a Teflon-coated Belleville spring
washer with top-loaded extruded or cold head cup with 3
mm glass bulb containing no plastic parts, and having a
temperature rating of [155°F (680C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 3.0, 4.9 and 5.8.
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential pendent
sprinklers shall be Reliable Model Fl Res 30, 49 & 58, SIN
R3511, R3516 & R3513 (Bulletin 135).
Ordering Information
Specify:
Sprinkler Model
Sprinkler Type
Temperature Rating
Sprinkler Finish
Escutcheon Finish
Cover Plate Finish
Model Fl Res 49 & 58 Recessed Pendent/F1,
Model Fl Res 30,49 & 58 Recessed Pendent/F2,
Model Fl Res 30,49 & 58 Recessed PendentlFP
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential recessed
pendent sprinklers engine9red to provide a minimum
design density of 0.05 gpmTh over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall be
installed in conformance with the manufacturer's installation
guidelines and the applicable installation standard. Where
pendent residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the sprinklers
shall be listed for such use. Deflector-to-ceiling distance
listing shall be 1" to 8" maximum. Sprinkler frame and
deflector shall be of bronze frame construction having a ½"
NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with top-loaded
extruded or cold head cup with 3 mm glass bulb containing
no plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (790C)]. Sprinklers shall have a nominal
K-factor of 3.0, 4.9 & 5.. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish- specify].
Recessed escutcheon assembly shall be a steel, two-piece
escutcheon [with ½" adjustment (Model F2)] [with 3/4"
adjustment (Model Fl)] [of push-on and thread off design
with ½" adjustment (Model FP)]. Standard finish shall be
[brass][bright chrome] [white painted]. Residential
recessed pendent sprinklers shall be Reliable [Model El
Res 3.0, 49 & 58 Recessed Pendent/Fi] [Model Fl Res 30,
49 & 58 Recessed PendentfF2] [Model Fl Res 30, 49 & 58
Recessed Pendent/FP] SIN R3511, R3516 & R3513
(Bulletin 135).
10.
Model Fl Res 30,49 & 58 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential concealed
sprinklers engineered to provide a minimum design
density of 0.05 gpm/ft2 over the listed coverage area.
Listed flows as specified by the manufacturer's technical
data sheets are to be used. Residential sprinklers shall
be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Where pendent residential sprinklers are
installed under sloped ceilings having a pitch from [4/12]
to [8/12], the sprinklers shall be listed for such use.
Sprinkler frame and deflector shall be of bronze frame
construction having a ½" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville
spring washer with top-loaded extruded or cold head
cup with 3 m glass bulb containing no plastic parts, and
having a temperature rating of 155°F (681C). Cover plate
assembly shall consist of a brass cover plate and copper
alloy retainer flange. Method of attaching the cover plate
to the sprinkler cup shall be a push-on and thread-off
design allowing a ½" cover plate adjustment. Cover
plate temperature rating shall be 135°F (570C). A plastic
protective cap shall be provided and factory installed
inside the sprinkler cup to protect the sprinkler from
damage, which could occur during construction before
the cover plate is installed. Standard cover plate finish:
[White] [Custom Color- specify]. ]. Concealed pendent
sprinklers shall be Reliable Model Fl Res 30, 49 & 58
CCP, SIN R3511, R3516 & R3513 (Bulletin 135).
Model Fl RES 40 and Fl Res 44 Horizontal Sidewall
Residential Sprinkler Specifications
Model Fl Res 40 Horizontal Sidewall Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the applicable
installation standard. Where horizontal sidewall
residential sprinklers are installed under sloped ceilings
having a pitch from [4/12] to [8/12], the sprinklers shall be
listed for such use. Sprinkler frame and deflector shall be
of bronze frame construction having a ½" NPT thread.
Water seal assembly shall consist of a Teflon-coated
Belleville spring washer with top-loaded extruded or cold
head cup with 3 mm glass bulb containing no plastic
parts, and having a temperature rating of [155°F (680C)]
[175°F (791C)]. Sprinklers shall have a nominal K-factor of
4.0 (57.1). Standard finish: [Bronze] [Chrome-plated]
[White Polyester] [Special finish- specify]. Residential
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 40, SIN R3538 (Bulletin 135).
Model Fl Res 40 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 40 horizontal
sidewall sprinkler with the following modifications: Replace
"horizontal sidewall sprinkler" with "recessed horizontal
sprinkler." Add: Recessed escutcheon assembly shall be
a steel, two-piece escutcheon with ½" adjustment (Model
F2). Standard finish shall be [brass][bright chrome] [white
painted] [Special finish- specify]. Residential recessed
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 40/F2, SIN R3538 (Bulletin 135).
Model Fl Res 44 Horizontal Sidewall Sprinkler
Sprinklers shall be [cULus Listed] [New York City MEA
Approved (258-93-E)] low flow residential horizontal
sidewall sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturer's installation guidelines and the
applicable installation standard. Where horizontal
sidewall residential sprinklers are installed under sloped
ceilings having a pitch from [4/12] to [8/12], the
sprinklers shall be listed for such use. Sprinkler frame
and deflector shall be of bronze frame construction
having a ½" NPT thread. Water seal assembly shall
consist of a Teflon-coated Belleville spring washer with
top-loaded extruded or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a
temperature rating of [155°F (681C)] [175°F (790C)].
Sprinklers shall have a nominal K-factor of 4.4 (62.8).
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish- specify]. Residential
horizontal sidewall sprinklers shall be Reliable Model Fl
Res 44, SIN R3531 (Bulletin 135).
Model Fl Res 44 Recessed
Horizontal Sidewall Sprinkler
Use description for the Model Fl Res 44 horizontal
sidewall sprinkler with the following modifications:
Replace "horizontal sidewall sprinkler" with "recessed
horizontal sprinkler." Add: Recessed escutcheon
assembly shall be a steel, two-piece escutcheon with ½"
adjustment (Model F2). Standard finish shall be
[brass][bright chrome] [white painted] [Special finish-
specify]. Residential recessed horizontal sidewall
sprinklers shall be Reliable Model Fl Res 44/F2, SIN
R3531 (Bulletin 135).
Model Fl Res 76 Pendent
Sprinklers shall be [cULus Listed] low flow residential
pendent sprinklers engineered to provide a minimum
design density of 0.05 gpmlft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential
sprinklers shall be installed in conformance with the
manufacturers installation guidelines and the applicable
installation standard. Sprinkler frame and deflector shall be
of bronze frame construction having a 3%" NPT thread.
Water seal assembly shall consist of a Teflon-coated
Belleville spring washer with machined or cold head cup
with 3 mm glass bulb containing no plastic parts, and
having a temperature rating of [155°F (681C)] [175°F
(790C)]. Sprinklers shall have a nominal K-factor of 7.6.
Standard finish: [Bronze] [Chrome-plated] [White
Polyester] [Special finish— specify]. Residential pendent
sprinklers shall be Reliable Model Fl Res 76, SIN R7618
(Bulletin 135).
Model Fl Res 76 Recessed Pendent/Fl,
Model Fl Res 76 Recessed Pendent/F2,
Model Fl Res 76 Recessed Pendent/FP
Sprinklers shall be [cULus Listed] low flow residential
recessed pendent sprinklers engineerd to provide a
minimum design density of 0.05 gpm/ft over the listed
coverage area. Listed flows as specified by the
manufacturer's technical data sheets are to be used.
Residential sprinklers shall be installed in conformance
with the manufacturer's installation guidelines and the
applicable installation standard. Sprinkler frame and
deflector shall be of bronze frame construction having a
3/4" NPT thread. Water seal assembly shall consist of a
Teflon-coated Belleville spring washer with machined or
cold head cup with 3 mm glass bulb containing no
plastic parts, and having a temperature rating of [155°F
(68°C)] [175°F (790C)]. Sprinklers shall have a nominal
K-factor of 7.6. Standard finish: [Bronze]
[Chrome-plated] [White Polyester] [Special finish—
specify]. Recessed escutcheon assembly shall be a
steel, two-piece escutcheon [with ½" adjustment (Model
F2)] [with 3%" adjustment (Model Fl)] [of push-on and
thread off design with ½" adjustment (Model FP)].
Standard finish shall be [brass][bright chrome] [white
painted]. Residential recessed pendent sprinklers shall
be Reliable [Model Fl Res 76 Recessed Pendent/F1]
[Model Fl Res 76 Recessed Pendent/F2] [ModelF1 Res
76 Recessed Pendent/FP] SIN R7618 (Bulletin 135).
Model Fl Res 76 CCP Pendent (Concealed)
Sprinklers shall be [cULus Listed] low flow residential
concealed sprinklers engineered to provide a minimum
design density of 0.05 gpm/ft2 over the listed coverage
area. Listed flows as specified by the manufacturer's
technical data sheets are to be used. Residential sprinklers
shall be installed in conformance with the manufacturer's
installation guidelines and the applicable installation
standard. Sprinkler frame and deflector shall be of bronze
frame construction having a 3%" NPT thread. Water seal
assembly shall consist of a Teflon-coated Belleville spring
washer with machined or cold head cup with 3 mm glass
bulb containing no plastic parts, and having a temperature
rating of 155°F (680C). Cover plate assembly shall consist
of a brass cover plate and copper alloy retainer flange.
Method of attaching the cover plate to the sprinkler cup
shall be a push-on and thread-off design allowing a 1/2"
cover plate adjustment. Cover plate temperature rating
shall be 135°F (570C). A plastic protective cap shall be
provided and factory installed inside the sprinkler cup to
protect the sprinkler from damage, which could occur
during construction before the cover plate is installed.
Standard cover plate finish: [White] [Custom Color—
specify]. ]. Concealed pendent sprinklers shall be Reliable
Model Fl Res 76 CCP, SIN R7618 (Bulletin 135).
The equipment presented in this bulletin is to be installed in accordance with the latest pertinent Standards of the National Fire Protection Association, Factory Mutual Research
Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances, whenever applicable.
Products manufactured and distributed by RELIABLE have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable
sprinkler contractors located throughout the united Stares, Canada and foreign countries.
Manufactured by
The Reliable Automatic Sprinkler Co., Inc.
I (800) 431-1588 Sales Offices j Recycled I 'Iel"lableo
(800) 848-6051 Sales Fax .Z1 Paper
(914) 829-2042 Corporate Offices Revision lines indicate updated or new data.
ww.reliablesprinkler.com Internet Address EG. Printed in U.S.A. 06/08 PIN 9999970235
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
510
CPVC - STEEL - COPPER
HANGER
SIZE - 3/4" thru 3" pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTING/APPROVAL -
cXm 203 - EX 4231, EX 2551
FUNCTION - To support horizontal piping - CPVC, Copper or Steel.
Hanger in listed mounting positions - Top, Bottom or Side.
Also, provides stability on vertical piping.
INSTALLATION - Per NFPA 13,13R, 13D and CPVC manufacturers
instructions on top, bottom or side of building element. Space by pipe type.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
in WOOD:
3/4" - 3" CPVC pipe - #905 screw - no pre-drill.
3/4" - 3" Copper pipe - #905 screw - no pre-drill.
3/4" -3" Steel pipe - 1/4"xl1/2" lag screw - no pre-drill.
in STEEL - mm. 18 GA.
3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 3" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 3" Steel pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON#905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
*CAN ALSO BE USED TO REPLACE - #500 Pipe Strap
#520 Tin Strap
Specific AFCON products are exclusively designed to be compatible ONLY with other ,4FCON products including parts and fasteners, resulting in listed sway brace, restrainer or hanger assembly. Be advised the following warranty restriction will apply. DISCLAIMER - AFC'ON will NOT warrant against the failure of its products when used in combination with other products, parts or systems not manufactured or sold by AFCON. ,4FCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-,IFCON products have been, or are used.
2/08
Side View - For
Drawings Below
Hanger - Wood Stud Hanger - Metal Stud
pm rZo 0~7r4
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
511
SIDE MOUNT
CPVC - COPPER
HANGER
SIZE - 3/4" thru 2" pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized.
LISTING/APPROVAL -
203 - EX 4231, EX 2551
FUNCTION - Hanger on CPVC and Copper pipe.
INSTALLATION - Per NFPA 13,13R, 13D and CPVC
manufacturers instructions on top or bottom of beam.
Space by pipe type
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre-drill.
3/4" - 2" Copper pipe - #905 screw - no pre-drill.
in STEEL - mm. 18 GA.
3/4" - 2" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
FEATURES
* Offset edge eliminates abrasion.
* Retainer dimples secure hanger to pipe during installation.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
Specific AFCON products are exclusively designed to be compatible ONLY with other ,4FCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. OISCLAIMR - AFCON will NOT warrant against the failure of its products when used in combination with other products. parts or systems
not manufactured or sold by ,4FCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
2/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
513
CPVC — STEEL — COPPER
HANGER
SIZE - 3/4" thru 2" pipe.
MATERIAL - Carbon Steel.
FINISH - Mil. Galvanized.
LISTING/APPROVAL —
203 — EX 4231, EX 2551
FUNCTION - To support horizontal piping - CPVC, Copper or Steel.
Tab up = Hanger.
INSTALLATION - Per NFPA 13,13R and 13D on
side or top of beam. Space by pipe type.
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13.
in WOOD:
3/4" - 2" CPVC pipe - #905 screw - no pre-drill.
3/4" - 2" Copper pipe - #905 screw - no pre-drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre-drill.
FEATURES
* Offset edge eliminates abrasion.
* Required AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
Specific APCON products are exclusively designed to be compatible ONLY with otberAFCO,V products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised the following warranty restriction will apply. DISCLAIMER - AFCON suit! NOT warrant against the failure of its products when used in combination with oilier products, parts or systems
not manufactured or sold by ,4FCON. AFC'ON shalt NOT be liable under any circumstances whatsoever for any director indirect, incidental or consequential damages of any kind, including but not
limited to loss of business or profit, when non-A FCON products have been, or are used.
2/08
P.O. Box 3365 South El Monte, CA 91733 626.444.0541 Fax 626.444.3887 www. Afcon.org
514
OFFSET CPVC HANGER
SIZE - 3/4" thru 3"pipe.
MATERIAL - Carbon Steel.
FINISH - Mu. Galvanized..
LISTING/APPROVAL -
®I 203 - EX 4231, EX 2551
PATENT - No. 6,648,278.
FUNCTION - 3/4"-2" Hanger/restrainer for horizontal CPVC, Copper or Steel pipe.
Listed hanger/restrainer in all 3 mounting positions, i.e. vertical surface and both top and
bottom of horizontal surface. Provides listed vertical/lateral restraint and prevents upward
movement of pipe that supplies a pendent sprinkler below a ceiling.
Size 2 Y2" Hanger for horizontal CPVC pipe. Listed hanger in all 3 mounting positions.
i.e. vertical surface and both top and bottom of horizontal surface.
Size 3" Hanger for horizontal CPVC pipe in two mounting positions, side and bottom.
i.e. vertical surface and bottom of horizontal surface.
Stabilizes vertical piping by providing horizontal restraint.
INSTALLATION - Per NFPA 13,13R and 13D.
Space by pipe type. install on wood, concrete or steel - See Drawings.
Snap over pipe then squeeze strap back allowing pipe to slide freely. Listed
When #905 threads are exposed in wood, install #906 backing nut. 3/4'
SPECIAL NOTE: When installing on CPVC sprinkler system pipe:
Verify that all assembly components are cleaned of any surface oil.
FASTENERS - UL Listed per NFPA 13
WOOD - 3/4" - 3" CPVC pipe - #905 screw- no pre-drill.
3/4" - 2" Copper pipe - #905 screw- no pre-drill.
3/4" - 2" Steel pipe - 1/4"x1 1/2" lag screw - no pre-drill.
Thru 5/8" gypsum board - 1/4" x 2" lag screw.
STEEL - mm. 18 GA. - 3/4" - 3" CPVC pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Copper pipe - 1/4" or #14 Tek Screw.
3/4" - 2" Steel pipe - 1/4" or #14 Tek Screw.
CONCRETE: Required minimum load each fastener = 5(wt)+2501bs.
2
FEATURES
* 1 1/2" Offset - loose fit allows pipe to slide.
* 3/4" and 1" pipe size made with common center-line.
* Patented design for superior strength.
* Offset edge eliminates abrasion.
* AFCON #905 screw has 5/16" hex head - included.
ORDERING - Part # and pipe size.
AFCON #906 backing nut sold separately.
#906
Listed Restraint
3/4" thru 2"
Specific ,4FCON products are exclusively designed to be compatible ONLY with other AFCON products including parts and fasteners, resulting in a listed sway brace, restrainer or hanger assembly.
Be advised use following warranty restriction will apply. DISCLAIMER - .4 FCON will NOT warrant against the failure of its products when used in combination with other products, parts or systems
not manufactured or sold by AFCON. AFCON shall NOT be liable under any circumstances whatsoever for any direct or indirect, incidental or consequential damagc-s of any kind, including but not
limited to loss of business or profit, when non-AFCON products have been, or are used.
6/08
Tee
Reducing Tee
Pipe
Manufactured for Viking SupplyNet by Viking Plastics, LLC (Huntsville, Alabama USA.)
s ê
009
So ~OS VIP
- T
Size
3/4"
t Number
34PIPE
Bag Qty.
240 ft
1PIPE 150 ft
1-1/4" 114PIPE 105 It
1-1/2" 112PlPE 75 It
2PIPE 601t
2-1/2" 212PIPE 30 ft
3PIPE 15 ft
BlazeMaster® CPVC fittings are manufactured/supplied for Viking SupplyNet by NIBCO, Inc.
Standard Fittings
Size
3/4"
Part Number ix.i'j
V5011-007 250
1" V5011-010 100
1-1/4" V5011-012 25
1-1/2" V5011-015 25
Size
3/4"x3/4"xl"
iNumber
V5011 R-102
i
10
1"x3/4"x3/4" V5011 R-125 100
1"x3/4"xl" V5011 R-126 10
1"xl"x3/4" V5011 R-131 100
1-1/4"xl"x314" V5011 R-157 5
1-1/4"xl"x1" V5011 R-158 25
1-1/4"xl"xl-1/4" V5011 R-159 5
1-1/4"xl-1/4"x3/4" V5011R-167 25
1-1/4"xl-1/4"xl" V5011 R-168 25
1-1/4"xl-1/4"x1-1/2" V5011 R-169 5
1-1/2"xl-1/4"0/4" V5011 R-201 5
1-1/2"xl-1/4"xl" V5011 R-202 5
1-1/2"xl-1/2"x3/4" V5011 R-210 25
1-1/2"xl -1/2"xl " V5011 R-211 25
Size I Part Number I Box Qty.
Tee (continued)
V5011-020 2
2-1/2" V5011-025
V5011-030 1
Size I rt Number Box Qty.
Reducing Tees (continued)
1-1/2"xl-1/2"xl-1/4" V5011 R-212 5
1-1/2"xl-1/2"x2" V5011 R-213 5
2"x2"x3/4" V5011 R-248 2
2"x2"xl" V5011 R-249 10
2"x2"xl-1/4" V5011R-250 2
2"x2"xl-1/2" V5011 R-251 2
2-1/2"x2-1/2"xl" V5011 R-289 1
2-1/2"x2-1/2"xl-1/4" V5011 R-290 1
2-1/2"x2-1/2"xl-1/2" V5011 R-291 1
2-1/2"x2-1/2"x2" V5011 R-292 1
3"x3"xl-1/2" V5011 R-337 1
3"x3"x2" V5011 R-338 1
3"x3"x2-1/2" V5011 R-339 1
www.vikinggroupinc.com Refer to manufacturer's DESIGN AND INSTALLATION GUIDE for technical specifications and installation instructions.
Size Part Number
3/4" V5007-007 250
V5007-010 100
1-1/4" V5007-012 25
1-1/2" V5007-015 25
V5007-020 10
900 Elbow
Standard Fittings continued from Page 1
Size Part Number •Box
450 Elbow "
3/4" V5006-007 250 450 Elbow (continued)
V5006-010 100 2" V5006-020 2
V5006-012 5 2-1/2" V5006-025 1
1-1/2" V5006-015 5 3" V5006-030 1
Size Part Number I
3/4" V5035-007
Box Qty.
10
1" V5035-010 100
1-1/4" V5035-012 5
1-1/2" V5035-015 6
2" V5035-020 4
TiErr! I Box Ii11'
Coupling
Size
3/4" V5001-007 250
C4
1" : V5001-010 100
1-1/4" V5001-012 25
1-1/2" V5001-015 25
Size •1 I i11'j
Reducing Coupling
1Ffl
1"x3/4" V5001 R-131 10
ElI
1-1/4" x 1" V5001 R-168 5
1-1/2" x 3/4" V5001 R-210 5
1-1/2" x 1" V5001 R-211 5
Size I •Part Number lT
Cross (continued)
2-1/2" V5035-025 4
3" V5035-030 1
1"xl"x3/4"x3/4" V503511-131 10
Size I -1Part Number . Box iQty.
Coupling (continued)
2" V5001-020 10
2-1/2" V5001-025 1
3" V5001-030 1
Size •Pail Number Box Qty. i
Reducing Coupling (continued)
1-1/2"x 1-1/4" V5001 R-212 5
2" x V5001 R-249 2
2" x 1-1/2" V5001 R-251 2
Cross
Bushing
ci
Size Part Number
lx 3/4" V5018-131
Box Qty.
100
1-1/4" x 3/4" V5018-167 25
1-1/4" x 1" V5018-168 25
1-1/2" x 3/4" V5018-210 5
1-1/2" x 1" V5018-211 25
1-1/2" x 1-1/4" V5018-212 25
2" x 3/4" V5018-248 2
2" x 1" V5018-249 2
Size I Part Number I Box Qty.
Bushing (continued)
2" x 1-1/4" V5018-250 2
x 1-1/2" V5018-251 2
2-1/2" x 1-1/4" V5018-290 1
2-1/2" x 1-1/2" V5018-291
2-1/2" x 2" V5018-292 1
3" x 2" V5018-338 1
x 2-1/2" V5018-339 1
Cap Size
3/4"
Part Numberix,i,j
V5017-007 250
1" V5017-010 100
1-1/4" V5017-012 S
1-1/2" V5017-015 5
Size I _Part Number I Box I.1I,j
Cap (continued)
V5017-020 2
2-1/2" V5017-025 1
V5017-030 1
www.vikinggroupinc.com
Sprinkler Head Adapters
BRASTIC° Sprinkler -j Part Number Box Qty. -
Head Adapter
3/4" x 1/2" V5003SBT-101 100
1" x 1/2" V5003SBT-130 50
- * Brass starter thread molded into plastic, virtually eliminating cress-threading.
Female Sprinkler Head
Adapter with Metal
_______ Size Part NumberBox Qty.
Thread Insert 3/4" X 1/2" V50035B1-101 100
1" x 1/2" V5003SBI-130 50
1" x 3/4" V50035B1-131 10
L - J
Spigot Female Sprinkler I __________ 1P •t Number Box Qty. Head Adapter with Metal
Thread Insert 3/4" x 1/2" V500325B1-101 100
I I
%P~
V_
1" x 1/2" V50032SB1-130 50
Metal Thread Insert
Sprinkler Head 90 with Size
3/4" x 1/2"
Part NumberBox
V500735B1-101
Qty.
100
1" x 1/2" V500735B1-130 50
1" x 3/4" V500735B1-131 10
1-1/4" x 1/2" V500735B1-166 5
Sprinkler Head Tee with
Metal Thread Insert
Am
1~ft
Size
l"xl'xl"
Part Number
V5012SBI-010
I Box i!wj
50
3/4"x3/4"xl/2" V50125B1-101 10
1"xl"xl/2" V5012SB1-130 50
1-1/4"xl-1/4"xl/2" V5012SB1-166 5
1-1/2"xl-1/2"xl/2" V5012 BI-209 5
2"x2"x1/2" V5012SBI-247 2
Size Part Number I Box Qty.
Sprinkler Head Tee w/Metal Thread Inserts (continued)
1"0/4"xl/2" V5012RSB1-124 10
1-1/4"xl"xl/2" V5012R5B1-156 5
1-1/2"xl-1/4"xl/2" V5012R5B1-199 5
2"xl-1/2"x112" V5012RSBI-237 2
1x1/2 11 x1* V5014RSBl122* 10
*Socket x APT x Socket
Sprinkler Head Back to 'ire Part Number Box Qty. Back Cross with Metal
Thread Insert lxl"xl/2"xl/2" 1-1/8" V503535B15-130 I 1
1x1"x1/2"x1/2" 1-15/16" V503535B1L-130 1
Back to Back Tee with 'ia' Part Number Box Qty.
Metal Threads Insert 1/2"xl/2"xl" 1-1/8" V501133SBIS-075 48
-
1/2"xl/2"xl" 1-15/16" V5011335B1L-075 48
Size Part Number I Test Plug Box Qty.
1/2" V450-005 50
U
www.vikinggroupinc.com
Size I Part Number i Box Qty.
Standard Union (continued)
V5033E-020 1
2-1/2" V5033E-025 1
V5033E-030 1
Standard Union
Transition Fittings
Female Adapter with Size Part Number I Box iiwj Size Part Number I Box Qty.
Metal Thread Insert 3/4" V5003B1-007 10 Female Adapter w/Metal Thread Inserts (continued)
(—, 1" V5003B1-010 50 1-1/2" V5003131-015 5
1-1/4" V5003Bl-012 5 2" V5003B1-020 2
Spigot Female Adapter ISize ParttNumber Box City.
with Metal Thread Insert
I 3/4" V50032B1-007 10
1" V50032B1-010 1
C~
Male Adapter with Size Part Number City.I Box t Size Part Number I Box Qty.
Metal Thread Insert 3/4" V5004Bl-007 10 Male Adapter w/Metal Thread Inserts (continued)
1" V5004B1-010 10 1-1/2" V5004Bl-015 5
1-1/4" V5004B1-012 5 2" V5004BI-020 2
Grooved Coupling Size Part Number Box Qty.Size I PartNumber I Box1•fIS11]
Adapter 1-1/4" V5001 G-012 30 Grooved Coupling Adapter (continued)
1-1/2" V5001 G-015 25 2-1/2" V5001 G-025 10
C j
2" V5001 G-020 15 3" V5001 G-030 8
Accessories
Solvent Cement Size Part Number Box Qty Size Part Number Box Qty
rj Quart V5097Q 12
Pint V5097P 12
Dauber Size _Part Number I Box Qty ________
Small V5093-S 100
Large V5093-L 100
Size Part Number Box Qty
Refer to manufacturer's DESIGN AND INSTALLATION GUIDE for technical specifications and installation instructions.
c®us AWROVED wwwvikinggroupinc.com
September 2010
CARLSBAD FIRE DEPARTMENT
Fire Prevention Division
1635 Faraday Avenue - Carlsbad, CA 92008
760.602.4665
WATER AVAILABILITY FORM
SECTION A: TO BE COMPLETED BY CUSTOMER
PROJECT NAME: Quarry Creek SR#:
(Assigned upon plan submittal)
PROJECT ADDRESS: CITY: Carlsbad
PHONE: ( 951 ) 667-4220 (NP Mechanical, Inc.) FAX NUMBER: (951) 667
Largest Building (ft. 2 Sprinkled? Construction Type:
SECTION B: TO BE COMPLETED BY LOCAL WATER COMPANY. CUSTOMER TO PROVIDE RESULTS TO CFD.
Water Purveyor: City of Carlsbad
Location of test (reference map required): (See attached.)
TEST INFORMATION IS VALID FOR 6 MONTHS FROM DATE PERFORMED
Flow Test Results
Static pressure: 94 PSI Hydrant Number (if applicable):New
Elevation of test: 114 Feet Date/Time of Test':
'itot Tube Readin PSI Corresponding Flow: GPM
Total Flow: 3,750 GPM Residual Pressure 66 PSI
At peak demand, this water system is capable of providing a fire flow discharge @ 20 psi of greater than 8,000 GPM.
However the velocity exceeds the maximum criteria of 10 fps. Therefore, the maximum available fire flow for this
location is 3,750 GPM.
Test to be performed as close as possible to the time the most conservative flows and pressures are expected
Note: If the water availability information was obtained in a manner other than a flow test (i.e. computer
modeling), fill out the information above as applicable and check here: x
Name: Jennifer R. Mael, P.E. Eng. Lic. No. (if applicable):C69606
Signature:__________________________________________
TitIe/Org:ect Manager Date: 7/7/2017
'-3
4 w_Hydrant
Pipe
ZONE
-330
- 446
- 580
Legend
0
Flow Test
Location
Road
Quarry Creek - Fire Flow Analysis
12 .
Dennis Grubb and Associates, LLC
Assisting cities Build Safe Communities
PLAN CORRECTIONS (FIRE)
DGA #: C7214 Carlsbad Permit #: FPR20I 7-0258 Checked by: D. Grubb
Jurisdiction: Carlsbad Applicant: NP Mechanical Phone#: 951-454-2107
Date of Review:6/30/17 Project Name: Cypress at the Preserve
Project Address: Model plan 2
The plans submitted for the project referenced above have been reviewed. The
following information is needed to show compliance with the 2016 California Building
and Fire Codes (CBC and CFC), and other codes as adopted and amended by state
regulation and the City of Carlsbad. It will be necessary to reevaluate the project after
the receipt of additional information as specified below.
INSTRUCTIONS
Resubmit three sets of the revised plans along with one set of the original plans.
Provide a written response for each correction on this correction list. You may write
directly on this list, or you may provide a separate "Response List" which addresses
each correction item by item.
Incorporate all corrections into the blue/black line drawings; cloud or call out all
corrections.
Return plans to Dennis Grubb & Associates, 6550 Van Buren Blvd, Ste E, Riverside,
CA. 92503
CORRECTIONS
ON THE PLANS THE FOLLOWING SHALL BE PROVIDED:
The water flow test report is over 12 months old. Provide a water flow report
within the last 12 months. Revise hydraulic calculations accordingly.
6550 Van Buren Blvd, Ste E, Riverside, CA. 92503
(800) 975-7395 * (951)772-0007
Confidential Page 1 7/11/2017
NP Mechanical Inc.
9225 SteCoixt ste. A
Camrka, CIL 92883
July 11, 2017
D. Grubb
Dennis Grubb and Associates, LLC
6550 Van Buren Blvd, Ste E
Riverside, CA 92503
Hello,
In regards to the correction sheet you provided for Cypress at the preserve the following
corrections have been made:
Provided new water flow.
Hydraulic calculations have been revised accordingly. (See FP2)
If you have any questions feel free to call me at any time.
Juan Aguirre
Fire Sprinkler Engineer
NP Mechanical Inc.
951-667-4220 Ext. 351