HomeMy WebLinkAbout2637 JEFFERSON ST; ; FPR2020-0084; PermitPERMIT REPORT Lcity of Carlsbad Print Date: 12/07/2020 Permit No: FPR2020-0084 Job Address: 2637 JEFFERSON ST, CARLSBAD, CA 92008-1440 Status: Closed - Finaled Permit Type: FIRE-Construction Residential Work Class: Multifamily Fire Alarm Parcel #: 1551702500 Valuation: $0.00 Occupancy Group: #of Dwelling Units: Bedrooms: Bathrooms: Track #: Lot #: Project #: Plan #: Construction Type: Orig. Plan Check #: Plan Check #: Applied: 08/18/2020 Issued: 09/04/2020 Finaled Close Out: 12/07/2020 Inspector: Final Inspection: Project Title: Description: ARELLANO -SPRINKLER MONITORING SYSTEM FOR 4-UNIT APTS Applicant: FPContractor: SYMONS FIRE PROTECTION INC SYMONS FIRE PROTECTION INC MICHAEL GULINO 12155 PAINE PL 12155 PAINE PL P0 WAY, CA 92064-7154 POWAY, CA 92064-7154 (619) 588-6364 (619) 588-6364 FEE AMOUNT FIRE Sprinkler Monitoring $383.00 Total Fees: $383.00 Total Payments To Date: $383.00 Balance Due: $0.00 Fire Department Page 1 of 1 1635 Faraday Avenue, Carlsbad CA 92008-7314 1760-602-4665 1760-602-8561 f I www.carlsbadca.gov f 2 2-020 -oo4 wt - IESIcDNJSI\fE • IESLJIEFLJL 4 Fire Sprinkler Monitoring System Complete Material Submittal Prepared for: Arellano 4 Unit Apartments 2637 Jefferson Street, Carlsbad, CA 92008 August 1 1th, 2020 12155 Paine Place • Poway, CA 92064 • (619) 588-6364 • Fax (619) 588-6805 • CA Lic. #682025 a~~-IPOFAI" mWR TABLE OF CONTENTS - FIRE ALARM SYSTEM SUBMITTAL 1. FIRE ALARM SILENT KNIGHT - FIRE ALARM CONTROL PANEL —5104 INTERSTATE - FIRE ALARM BATTERIES 7Ah - 12V - SLA-0124 SPACE AGE— FIRE ALARM DOCUMENT CABINET - ACE- li TELGUARD - FIRE ALARM CELLULAR DIALER - TG7-FS SILENT KNIGHT - FIRE ALARM PULL STATION - SK-PULL-DA SILENT KNIGHT - FIRE ALARM SMOKE DETECTOR - 4W-B 12155 Paine Place Poway, CA 92064 (619) 588-6364 Fax (619) 588-6805 G CA Lic. #682025 5104B Honeywell . SILENT' KNIGHT 51OLiB Fire Control Communicator The Silent Knight Model 5104B is a six-zone fire control communicator providing digital fire reporting over ordinary telephone lines, eliminating the need for costly leased lines. It's UL 864 and NFPA 72 approved for monitoring local evacuation controls. As a stand-alone unit, it can be used to monitor: Sprinkler systems for waterflow, supervisory, and gate valve tamper conditions. Automatic fire detection systems for structures that are not required to have a fire alarm system but want property protection (e.g. to call the fire department after hours). Monitors dry contact alarms, trouble and supervisory outputs, then transmits a separate code for each. The Model 5104B is fully supervised. Its microprocessor constantly runs programs to monitor AC, standby battery, zone inputs and telephone line connections. If a fault condition is detected, it sounds a local trouble audible and reports the condition to the central station. If one of the telephone lines faults for more than 60 seconds, it will automatically switch to the other to report the failure. The communicator will signal activation, restoration and trouble conditions on any of the six inputs. If an application requires a different input configuration, the individual input styles may be changed by using a Model 7181 Fire Zone Converter Module. The 7181 also allows use of two-wire type smoke detectors, instead of the normal four-wire contact type, for automatic fire detection applications. FEATURES & BENEFITS r1JE864[isted as an S1fully supervised Fuseless overload Reports in SIA and A single, NFPA 72 Central inputs: one Class A protection with most major programmable output Station or Remote input, and five Class B automatic reset communications is provided for alarm Station protected inputs circuitry and fault formats or dialer failed premise unit Downloadable for indicators - Operates on loop start conditions (cannot be FM approved remote programming eliminates the cause phone lines ahead of used for evacuation of most field calls. . . purposes). Can be used as a • 60 hours of standby We ng stand-alone or as a power • Dual phone line system. add-on DACT interface Automatic self tests every 24 . hours with report sent to central station 5104B Technical Specifications PHYSICAL Dimensions: 12.25 Wx 14.5"H x 3.0 D (31.1cm W x 36.8 cm H x 7.6cm 0) Weight: 15 tbs. (6.75 kg) Color: Red ENVIRONMENTAL Operating Temperature: 32°F to 120°F (0°C to 49°C) Humidity: 10 to 93°Io relative humidity (non- condensing) ELECTRICAL: Add-on Applications - UL Listed Input: I20VAC 60Hz 40 watts CURRENT: Standby: 50mA Alarm: 135mA STAND ALONE APPLICATIONS Input: I20VAC 60Hz 40 watts Standby: 12V 7 amp hour rechargeable battery 5230 Remote Annunciator: (three maximum per system) Load: 60mA standby, 120mA alarm INDICATOR LIGHTS (LEDS) Power On: (Green) Trouble Silenced: (Yellow) Until Trouble is Cleared/Flashing: Supervisory Dialer Failure: (Yellow) Telephone Line Fault: (2 Red) Inside Cabinet at Li and L2 Inputs TELEPHONE REQUIREMENTS FCC Registration #: AC698R-17462-AL-E RINGER EQUIVALENCE: 0.013 Type of Jack: RJ3IX(2 required) ORDERING INFORMATION 5104B: Fire Alarm Communicator. Four-zone digital communication of fire and trouble. ACCESSORIES 5230: Remote Annunciator/Programmer 7181: Fire Zone Converter Module 7860: Telephone Connecting Cord for RJ3IX Jack (2 required) 6712: 12 volt, 74H rechargeable battery COMMUNICATION FORMATS: SIA, SK 3/1, Sescoa 3/1, Contact ID, SK4/2, Radionics BFSK AGENCY LISTINGS AND APPROVALS UL Listed - UL864/NFPA 72 Central and Remote Supervising Station Fire Alarm System Service FM Approved CSFM Approved MEA For a complete listing of all compliance approvals and certifications, please visit www.sitentknight.com. Microsoft, Windows, and the Windows Logo are registered trademarks or trademarks of Microsoft Corporation. Honeywell" is registered trademarks of Honeywell International, Inc This document is not intended to be used for installation purposes. We try to keep our product information up-to date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. For Technical Support, call 800-446-6444 S For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Northiord, CT 06472 800-328-0103 Doc 350349 l Rev Fl05/08 © 2018 Honeywell International Inc. S CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7165-0559:0114 Page 1 of 1 CATEGORY: 7165 -- FIRE ALARM CONTROL UNIT (COMMERCIAL) LISTEE: SILENT KNIGHT SECURITYOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sisson@honeywell.com DESIGN: Model *510413 Provides automatic, manual and waterfiow service when used as a central station protective premise unit. Intended to monitor various initiating devices and transmit to a central station receiving unit various preprogrammed alarm and trouble signals. Refer to listee's data sheet for detailed product description, electrical rating and operational considerations. *510413 *Sixzone control/communicator control unit 5230 Remote annunciator/keypad INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed control unit for use with separately listed compatible initiating and indicating devices. This control unit does not generate a temporal pattern signal. If the distinctive three-pulse Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition is required, the control unit must be used with appliances that can generate the temporal pattern signal. Refer to manufacturer's Installation Manual for details. This control unit meets the requirements of UL-864, 9th Edition Standards. NOTE: Refer to listee's data sheet for required/optional accessories. When required, accessories shall be CSFM listed. *Rev. 08-01-12 gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division General Purpose The Power of a Perfect Fit IIN7 E fBATi7jERiES) Outrageously O8pendable S Interstate's SLA battery family powers more than devices. They empower the people who use them-and choose them. Part # SLA0826 Volts 4V Ah Capacity* 4.5 Ah 1.89 2.07 11iILh11[.Jfl. 3.70 I: 3.94 Terminal Fl SLA0833 4V 8 3.58 1.97 3.98 3.98 F2 SLA0836 4V 10 4.02 1.97 3.70 3.94 F2 SLA0855 6V 1.1 Ah 2.01 1.65 2.01 2.24 Fl SLA0865 6V 1.2 Ah 3.82 0.98 2.05 2.24 Fl SLA0184 6V 2.0Ah 1.69 1.46 2.99 2.99 Fl SLA0902 6V 2.8Ah 2.60 1.30 3.82 4.06 Fl SLA0885 6V 3.2Ah 5.28 1.34 2.36 2.60 Fl SLA0905 6V 4.5 Ah 2.76 1.85 4.02 4.17 Fl SLA0906 6V 5 Ah 2.64 2.64 3.78 3.98 Fl SLA0916 6V 5 Ah 2.64 2.64 3.82 4.65 SPR SLA0935 6V 7 Ah 3.86 2.20 4.02 4.02 Fl SLA0925 6V 7 Ah 5.94 1.34 3.70 3.94 Fl SLA0945 6V 9 3.86 2.20 4.65 4.72 Fl SLA0955 6V 10 5.94 1.97 3.70 3.90 Fl SLA0959 6V 12 Ah 5.94 1.97 3.70 3.90 F2 SLA0961 6V 12 5.94 1.97 3.70 3.90 Fl SLA0986 6V 20 6.18 3.27 4.92 4.92 NB SLA0993 6V 42 Ah 6.38 3.46 6.42 6.69 F2 SLA0994 6V 42 Ah 6.38 3.46 6.42 6.85 NB SLA0988 8V 3.2Ah 5.28 1.42 2.48 2.72 Fl SLA1000 12V 700 mAh 3.78 0.98 2.44 2.44 Plug SLA1005 12V 1.3Ah 3.82 1.69 2.09 2.28 Fl SLA0218 12V 2 2.76 1.89 3.86 4.09 Fl SLA1020 12V 2 Ah 5.91 0.79 3.54 3.54 Fl SLA1016 12V 2.3Ah 7.01 TAT 1.38 Dimensions H 2.36 I: 2.60 Terminal Fl SLA1015 12V 2.3Ah 7.01 1.34 2.36 2.36 Fl SLA1022 12V 2.9Ah 3.11 2.20 3.90 4.21 Fl SLA0077 12V 2.9 Ah 3.11 2.20 3.90 4.13 Fl SLA1042 12V 3 5.28 2.64 2.36 2.60 F2 SLA1035 12V 3.5Ah 5.28 2.64 2.36 2.60 Fl SLA1041 12V 3.5Ah 5.28 2.64 2.36 2.60 Fl SLA1055 12V 5 Ah 3.54 2.76 3.98 4.21 Fl SLA1056 12V 5 Ah 3.54 2.76 3.94 4.21 F2 SLA1075 12V 8 5.94 2.56 3.70 3.94 Fl SLA1079 12V 8 A 5.94 2.56 3.70 3.94 F2 SLA1080 12V 7.5Ah 5.94 2.56 3.70 3.90 F2 SLA1097 12V 10 5.94 2.56 4.37 4.61 F2 SLA1104 12V 12 5.94 3.86 3.66 3.86 F2 SLA1105 12V 12 5.94 3.86 3.66 3.86 Fl SLA1098 12V 12 5.94 3.86 3.66 4.09 NB SLA1116 12V 18 7.13 2.99 6.57 6.57 NB SLA1115 12V 18 7.13 2.99 6.57 6.57 F2 SLA1146 12V 26 6.50 6.89 4.88 4.88 NB SLA1150 12V 30 6.50 4.88 6.89 6.89 NB SLA1156 12V 35 7.72 5.12 6.22 6.65 INS SLA1155 12V 35 Ah 7.76 5.16 6.26 7.09 Flag SLA1161 12V 44 7.76 6.50 6.69 6.69 INS SLA1165 12V 55A 9.02 5.43 8.07 8.90 Flag SLA1160 12V 55 9.02 5.43 8.27 9.25 NB - Reversed SLA1180 12V 65 13.70 6.61 7.01 7.01 INS SLA1175 12V 75 Ah 10.20 6.61 8.35 8.98 Flag SLA1185 12V 100Ah 12.09 6.61 8.19 9.06 Flag SLA1189 12V 100Ah 12.09 6.61 8.19 8.43 INS 02019 Interstate Batteries I ABC-985 Zq,. Ft L ACE-Il FIRE ALARM DOCUMENTS The FAD is the perfect fit to meet the demanding code requirements today. SAE's number one goal is to manufacture code compliant solutions and this product allows you to do just that. NFPA 72 2007 section 6.2.2.1 states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit." This durable 16 gauge steel enclosure with a solid piano hinge and key lock will keep all of your code required documents in one safe place. With a 4GB USB flash drive it stores your fire alarm software safe and secure eliminating the occurrences of the soft- ware not being on site when technicians arrive to service the system. Along with your fire alarm soft- ware you can store your test & inspection docu- ments, service records, manuals & AS built drawings for the system. Using a standard USB B connector it allows you to plug in with any standard SB printer cable to upload or download information. The FDB is designed to hold critical manuals and documents with a durable steel retainer. It has designated hooks to organize key rings and hold important business cards for easy access and reference. Inside the cover it has a organized note table that allows for documentation for passwords and other critical system information. Standard Features: Installed with a 4 gig digital flash drive with USB B connector 2 Key ring hooks to hold system keys Business card holder for key contacts Overall Dimensions are 12" x 13" tall and 2 14deep 16 gauge steel box and cover for security Durable powercoat baked on finish other colors available Standard %"cat 30 key lock other lock as- semblies available Solid stainless steel piano hinge Permanently screened white ink 1" high "Fire Alarm Documents" Legend sheet for passwords and system information r L ' 091 Space Age Electronics, Inc A Made I.S.A. REGISTERED OMPANY 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax Space Age Electronics, Inc. 2009 ED0549 LT10559 Rev.D 1/2 No Excuses, Just Solutions! JOSPACEAGE ELECTRONICS, INC. Specifications: The fire alarm documents box (FAD) shall be UL Listed, constructed of 18 gauge cold rolled steel. It shall have a red powder coat epoxy finish. The cover shall be permanently screened with 1" high lettering "FIRE ALARM DOCUMENTS" with white indelible ink. The access door shall be locked with a 3/4" barrel lock and the hinge shall be a solid width 12" stainless steel piano hinge. The enclosure will supply 4 mounting holes. Inside the enclosure will accommodate standard 8 1/2 x 11 manuals and loose document records that will be protected within the enclosure. A legend sheet will be permanently attached to the door for system required documentation, key contacts and system information. The FAD will have securely mounted inside a minimum of 4 Gigabyte digital flash memory drive with a standard USB B connector for uploading and downloading information. The drive shall not be accessible without tools to any person whom gains access to the records. The enclosure shall also provide 2 key ring holders with a location to mount standard business type cards for key contact personnel. USB Storage Interface Requires Standard USB-B Connector Property IntorOntlion Mininron, Required 13000n,entotlnn (SIG.FUN) d.oy'6Oy OE,py.oRth50Iat .MOO 60.t.n,ropyro,os0010nrt,00eeotnon400000oyn.tmnloy 16,5 Aothority Hooing Juyd6tion: ro.o yy.e, .Isne. 50,0100 0 00001) 000 50.0005 0 .010000 0005051. 1000 00 .,00todr05050005.50005pny vyo.roor050500000y0050n,.pyon.tsn 555*00 0*1151.0,5 ul5005.001,000 00000*y5505000005,.000501010*0055n? 60.0702 0500 0 00,026,01 00,2 0205,0600 2 62200,00 000 1 56502 7 0 2 ,.2... Eqolpesent Int0ttnttlOfl 0000*0.-006)o.*o. Al 250001_ 060 Sqaoe7723 ,o2oolo..00 1T10044 R-11 Legend sheet for storing system information including contacts, sign-off, maintenance & test information, and alternate locations of additional records. Space Age Electronics, Inc. www.lsae.com 800.486.1723 Toll Free 508.485.0966 Local 508.485.4740 Fax No Excuses, Just Solutions! Ordering Information: Part # Description 55U00685 Fire Alarm Storage Cabinet RED 55U00686 Custom screening with your Logo Check out our Infinity line eFAD single gang 2 Gig digital storage solutions (IAMEFAD) This document is subject to change without notice, see dcc # ED0479 for legal disclaimer ED0549 LT10559 Rev.D 2/2 I CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL _____ S FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-0553:0110 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: SPACE AGE ELECTRONLCS58 Chockett Road, Sterling, MA 01564 Contact: Robert Scholl (508) 485-0966 Fax (508) 485-4740 Email: bobs@lsae.com DESIGN: Models TC2-32, TC1-18, TCX/A 64, TCX/D 128, ACE/A, AC2, ACE/D, IF-2, IF1, IFX/A and IFX/D enclosures. Models ACE-1 i, ACE-12 and ACE-13, *ACE2424 *ACE 3036, *ACE 2436, *ACE 3048 document cabinets. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number and UL label. APPROVAL: Listed as fire alarm equipment enclosures and document cabinets for use with listee's fire alarm equipment. Refer to listee's Installation Instruction Manual for details. 02-09-16 dc This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division TG-7FS LTE-V CELLULAR ALARM COMMUNICATOR FOR LTE NETWORKS TELGUARD P/N: TG7LVFO1 t COMMERCIAL FIRE PRODUCT FEATURES Certified for use on Verizon's LTE network for long, sunset-free installation. : Meets UL 864 requirements for sole, primary or backup path communications. :• Minimizes false alarms by providing dual paths for self-tests. The Telguard TG-717S LTE-V is the ideal cellular alarm communications solution for commercial fire systems. The TG-7FS LTE-V transmits alarm signals from the fire panel over the digital cellular network to the designated monitoring station. Compliant with the 2013 Edition of NFPA 72, the TG-7FS LTE-V can serve as the sole communications path for the fire alarm system. It replaces all of the landlines currently dedicated to the master control unit. On average, cellular monitoring costs the end user significantly less than a dedicated landline. For each landline replaced with a TG-7FS LTE-V, the monthly communications bill decreases. By being able to signal failures to the central station within sixty minutes of an outage, the TG-7FS LTE-V can be installed as the sole path for commercial fire installations. For existing installations, all landlines can be swapped for a single TG-7FS LTE-V because of the new sixty minute supervision mode. The TG-7FS LTE-V can also be installed as a backup path and upgraded to sole path at a later date. f •\ t -' ( Telguard Portal Telguard Cellular Service ' Advanced Reliability Telguard makes adopting cellular easy with a secure Internet portal. The straightforward web interface allows security dealers and central stations to quickly and efficiently access Telguard based services 24/7 This advanced tool has multi-level user authorization and provides total account management of UL Listed Telguard cellular alarm communicators. Telguard Cellular Service provides Verizon LIE network coverage for all Telguard units. Telguard's Communication Center is UL compliant and provides seamless connectivity between the alarm panel, the Telguard family of products and the central station. Telguard Technical Support provides a single point of contact for both cellular service and Telguard product questions. Features the ability to utilize multiple cellular technologies to increase availability and reduce false alarms. Automatic self-tests with central station notification ensure the cellular system is operating. Available relay output for tripping the alarm control panel when a trouble condition occurs. 1. Telguard technology allows full data reporting for unlimited point-to-point signal details and maximum transmitting power for superior in-building penetration. Telguard products are easy to install, economical, and UL Listed. Accessories ACD 12, ACD 35, ACD 50, ACD 100: 12/35/50/100 feet of low loss, high performance cable. HGDL-0: High gain directional antenna. EXDL-0: External antenna. UL Listings Commercial Fire 864 • Control units & accessories for lire alarm systems Commercial Burglary 365 • Police Station connected burglar alarm units and systems 1610 • Central station burglar alarm units: Line security servcies Residential 985 • Household lire warning systems 1023 • Household burglar alarm systems For the most current product specifications and UL Listings visit www.Telguard.com. SECURITY - \_—__• SIGNALING \iI A EL sso ECTRONIC verqn TY i Ciiiorr NFP NETWORK Ot00 A® I/J\ CERTIFIED LISTED INTERNATIONAL TG-7FS CELLULAR ALARM __ COMMUNICATOR LTE-V FOR LTE NETWORKS TELGUARD Power, Transmit Power: 200mW in all bands, Power Consumption: 60mA (Standby) 25OmA (Transmission). Transformer: 12VAC, 800mA UL listed plug-in. Radio Transceiver LTE Bands: 4 & 13. Antenna: 9" dipole with 2dBi gain 12 ft of cable and universal mounting bracket. FCC part 15, 27 and 68 compliant. / Physical Details TG-7FS LTE-V: 7.5" H x 11.5" W x 3.5" D. Shipping Weight: 81bs. Operating Environment: 0°C to +50°C; up to 95% humidity (non-condensing). Standard Features H, Full data reporting. Automatic self-test (60 mm. & daily). Power supply with battery harness. Locking, red metal enclosure. Two programmable supervisory trip outputs. Supports virtually all alarm formats (Contact ID, S1A2, and others) using dial capture for universal panel compatibility. Telephone line monitor built-in, with Standard Line Security. ((it) LT Alerm Porpi TG7FS (I LandI,, (Opt -'I) nIl) Telguard, a Division of Telular Corporation • 3225 Cumberland Blvd SE • Suite 300 Atlanta, GA 30339 • USA 800-229-2326, Option 5 www.Telguard.com • Copyright ©2017 Telular Corporation All Rights Reserved CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7300-1402:0109 Page 1 of 1 CATEGORY: 7300 -- FIRE ALARM CONTROL UNIT ACCESSORIES/MISC. DEVICES LISTEE: TELULAR CORP.3225 Cumberland Blvd, Suite 300, Atlanta, GA 30339 Contact: Tim Masters (678) 264-2012 Fax (678) 264-2062 Email: Tim.Masters@ametek.com DESIGN: Models TG71-AA02, TG7LA001, TG7LAA01, TG7LA002, TG7LAF01, TG7LAF02, *TG7UBLA and TGKITLA2 digital cellular radio alarm transmission system for fire/burglar alarm system control units. Models TG7LAA02 and TG7LA002 are household application. Model TG7LAF01, TG7LAF02, and TGKITLA2 are for commercial application. Refer to listee's printed data sheet for additional detailed product description and operational considerations INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as digital cellular radio alarm transmission devices to provide a standalone transmission path (cellular) for a listed compatible fire and burglar alarm control unit. It may also provide a backup communication path when used in conjunction with a DACT. This product is to be connected to a listed control panel in accordance with the installation instructions provided by the manufacturer. NOTE: Burglary and other non-fire functions were not examined. * Revised 11-27-19gt This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO,, ME., F.P.E. Fire Engineering Division SK-PULL-SA S SK-PULL-DA Instatter can open station without causing an alarm condition Dual-color LED is visible through handle of station blinks green to indicate normal operation and remains steady red in an alarm condition Key operated test and reset lock using lock plate actuator Key matches compatible FACP locks Meets ADA requirement for 5 lbs maximum pull force to active Meets the Americans with Disabilities Act Accessibility Guidelines (ADAAG) controls and operating mechanisms guidelines (Section 4.1.3[13]) Shell, door, and handle molded from durable LEXAN umvoneyweM Ji(eir SK-PULL-SA / S IJ I ntelligent Pull Stations The SK-PULL-SA is a single action putt station requiring only one motion to activate the station. The SK-PULL-DA is a dual action putt station requiring two motions to active the station. The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel (FACP). Extremely easy to operate, the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal. The FACP recognizes each manual putt station by its specific address saving precious seconds in determining the location of an alarm. INSTALLATION The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-I/O surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13(5.40 cm) or double gang or 4(10.61 cm) square electrical box. You can also use the optional (System Sensor PN BG-TR) trim ring if the station is being semi-flush mounted. FEATURES & BENEFITS Reliable analog Handle latches in communications for down position and the trouble-free operation word Activated Braille text on station appears, clearly handle indicating the station has been pulled Rotary address switches for fast UL Listed, including installation UL 38, Standard of Manually Actuated Signaling System CSFM Listed MEA Listed SK-PULL-SA / SK-PULL-DA Technical Specifications Fora complete listing of all compliance approvals and certifications, please visit PHYSICAL ORDERING INFORMATION www.sitentknight.com. Dimensions: 5.5"H x 4"W x 1.45"D (14 x 10.2 x SK-Pull-SA: Single Action Pull Station 3.7cm) SK-Pull-DA: Dual Action Pull Station Microsoft, Windows, and the Windows Logo are Housing Material: LEXAN polycarbonate resin registered trademarks Bi-CoLored LED: ACCESSORIES or trademarks of Blinking Green: Normal BG-TR: Optional trim ring. Microsoft Corporation. Steady Red: Alarm SB-I/O: Surface backbox, indoor/outdoor. Silent Knights, System Switch: Single pole, single throw (SPST) normally * Unless otherwise noted, specifications apply to Sensor* and Honeywell' open (N/O) switch which closes upon activation of SK-Pull-SA and SK-Pull-DA are registered the pull station trademarks of Honeywell COMPATIBILITY International, Inc. ELECTRICAL The SK-PULL-SA AND SK-PULL-DA are This document is not Operating Voltage: 15 - 32VDC compatible with the following Honeywell Silent intended to be used for SLC Standby and Alarm Current: 350A Knight fire alarm control panels: installation purposes. We Wire Gauge: Up to 12AWG (3.1 mm2) 6820: Addressable fire alarm control panel try to keep our product information up-to 6820EV5: Addressable fire alarm control panel date and accurate. We ENVIRONMENTAL with an emergency voice system. cannot cover all specific Operating Temperature: 32°F - 120°F (0°C - 6808: Addressable fire alarm control panel applications or anticipate 49°C) 6700: Addressable fire alarm control panel all requirements. All specifications are subject Humidity: 10°/c - 93°/c non-condensing 5700: Addressable fire alarm control panel to change without notice. 5808: Addressable fire alarm control panel 5820XL: Addressable fire alarm control panel For Technical Support, call 800-446-6444 5820XL-EVS: Addressable fire alarm control panel with an emergency voice system For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com . Honeywell Silent Knight Honeywell Clintonville Road Northford, CT 06472 . SILENT Doc 350135 I Rev El 11/17 8003280103 © 2017 Honeywell International Inc. IJ KNIGHT CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL - FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE S LISTING No. 7150-0559:0161 Page 1 of 1 CATEGORY: 7150 -- FIRE ALARM PULL BOXES LISTEE: SILENT KNIGHT SECURITYOne Fire-Lite Place, Northford, CT 06472-1653 Contact: Megan Sisson (203) 484-6127 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models SK-PULL-SA and SK-PULL-DA single/dual action fire alarm pull boxes. Refer to listee's data sheet for detailed product description and operational considerations. INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. MARKING: Listees name, model number, rating, and UL label. APPROVAL: Listed as fire alarm pull boxes for use with separately listed compatible fire alarm control units. Refer to listee's Installation Instruction Manual for details. * These manual pull boxes meet the requirements of UL Standard 38, 1999 Edition with California amendments. XLF: 7150-0028:0199 04-16-09 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct V' operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division I significant advancement in conventional detecti System Sensor j3" series smoke detectors represer r SYSTEM $ SENSOR The f3 family is founded on three principles: instaL. Photoelectric Smoke Detectors ease, intelligence, and instant inspection. Features Plug-in detector line, mounting base included S • Large wire entry port In-line terminals with SEMS screws Mounts to octagonal and single-gang back boxes, 4-square back boxes, or direct to ceiling Stop-Drop 'N Lock attachment to base Removable detector cover and chamber Built-in remote maintenance signaling Drift compensation and smoothing algorithms Simplified sensitivity measurement Wide-angle, dual-color LED indication Loop testing via EZ Walk feature Built-in test switch Agency Listings S ® €> 0 MEA MSFM LISTED approved approved C us S911 3011446 7272-1653152 290-01-E 2093 3180932 Installation ease.The i3 line redefines installation ease with its plug-in design.This allows an installer to pie-wire bases (included with heads). The large wire entry port and in-line terminals provide ample room for neatly routing the wiring inside the base. The base accommodates a variety of back box mounting methods as well as direct mounting with drywall anchors. To complete the installation, P heads plug into the base with a simple Stop-Drop 'N Lock' action. Intelligence. i3 detectors offer a number of intelligent features to simplify testing and maintenance. Drift compensation and smoothing algorithms are standard with the il line to minimize nuisance alarms. 2-wire i3 detectors can generate a remote LED- indicated maintenance signal when connected to the 2W-MOD2 loop test/maintenance module or a panel equipped with the P protocol. The SENS-RDR, a wireless device, displays the sensitivityof P detectors in terms of percent-per-foot obscuration. Instant inspection. The i3 series provides wide-angle red and green LED indicators for instant inspection of the detector's condition: normal standby, out-of-sensitivity, alarm, or freeze trouble. When connected to the 2W-MOD2 loop test/maintenance module or a panel with the i3 protocol, the EZ Walk loop test feature is available on 2-wire i3 detectors.This feature verifies the initiating loop wiring by providing LED status indication at each detector. lb Smoke Detector Specifications S Smoke detector shall be a System Sensor j3 Series model number listed to Underwriters Laboratories UL 268 for Fire Protection Signaling Systems.The detector shall be a photoelectric type (Model 2W-B, 4W-B) or a combination photoelectric/thermal (Model 2WT-B, 4WT-B) with thermal sensor rated at 135°F (57.2°C).The detector shall include a mounting base for mounting to 31/2-inch and 4-inch octagonal, single-gang, and 4-inch square back boxes with a plaster ring, or direct mount to the ceiling using drywall anchors. Wiring connections shall be made by means of SEMS screws.The detector shall allow pre-wiring of the base and the head shall be a plug-in type.The detector shall have a nominal sensitivity of 2.5 percent-per-foot nominal as measured in the UL smoke box.The detector shall be capable of automatically adjusting its sensitivity by means of drift compensation and smoothing algorithms.The detector shall provide dual- color LED indication that blinks to indicate power up, normal standby, out of sensitivity, alarm, and freeze trouble (Model 2WT-B, 4WT-B) conditions. When used in conjunction with the 2W-MOD2 module, 2-wire models shall include a maintenance signal to indicate the need for maintenance at the alarm control panel and shall provide a loop testing capability to verify the circuit without testing each detector individually. Operating Voltage Nominal: 1 2/24V non-polarized Minimum: 85V Maximum: 35V Maximum Ripple Voltage 30% peak to peak of applied voltage Standby Current 2-wire: 50 pA maximum average; 4-wire: 50 pA maximum average Maximum Alarm Current 2-wire: 130 mA limited by control panel; 4-wire: 20 mA @12 V, 23 mA @24 V Peak Standby Current 2-wire: 100 pA; 4-wire: n/a Alarm Contact Ratings 2-wire: n/a; 4-wire: 0.5 A @30 V AC/DC Physical ii. Dimensions (including base) 5.3 inches (127 mm) diameter; 2.0 inches (51 mm) height Weight 63 oz (178 g) Operating Temperature Range 2W-B and 4W-B: 32°F to 120°F (0°C to 49°C); 2WT-B and 4WT-8: 32°F to 100°F (0°C to 37.8°C) Operating Humidity Range 0 to 95% RH non-condensing Thermal Sensor 135°F (57.2°C) fixed Freeze Trouble 2WT-B and 4WT-B only: 41°F (5°C) Sensitivity 2.5%/ft nominal Input Terminals 14 to 22 AWG Mounting LED Modes LED Mode Green LED 31h-inch octagonal back box 4-inch octagonal back box Single-gang back box 4-inch square back box with a plaster ring Direct mount to ceiling Red LED Power-Up Sequence for LED Indication Condition Duration Power up Blink every 10 seconds Blink every 10 seconds Initial LED status indication 80 seconds Normal (standby) Blink every 5 seconds off Out of sensitivity off Blink every 5 seconds Freeze trouble off Blink every 10 seconds Alarm off Solid Ordering Information Model Thermal 2W-B No ViThit. 2-wire T AlarmTCurrent 130 mA max. limited by control panel 2W7-B Yes . 2-wire 130 mA max. limited by control panel 4W-B No 4-wire 20 mA @ 12 V, 23 mA @ 24 V 4WT-B Yes 4-wire 20 mA@12V, 23 mA@24V Accessories 2W-MOD2 SENS-RDR 2-wire loop test / maintenance module RT Sensitivity reader A77-AB2 Removal / replacement tool Retrofit adapter bracket, 6.6 inch (16.76 cm) diameter 3825 Ohio Avenue. St. Charles, IL 60174 02009 System Sensor ¼___$ SENSOR Phone: 800-SENSOR2 . Fax: 630-377-6495 current product information, including the latest version of this dam shm. CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION . _____ OFFICE OF THE STATE FIRE MARSHAL _____ FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM LISTING SERVICE LISTING No. 7272-1653:0152 Page 1 of 1 CATEGORY: 7272 -- SMOKE DETECTOR-SYSTEM TYPE-PHOTOELECTRIC LISTEE: System Sensor, Unincorporated Div of Honeywell Int'l Inc.3825 Ohio Ave, St. Charles, IL 60174 Contact: Megan Sisson (630) 762-5362 Fax (203) 484-7309 Email: megan.sissonhoneywell.com DESIGN: Models 2W-B, 2WT-B, 4W-B and 4WT-B photoelectric type smoke detectors. Models 2W-B and 2WT-B are 2-wire and model 4W-B and 4Wr-B are 4-wire detectors. Models 2WT-B and 4WT-B employ a thermistor type heat sensor (135°F). The heat sensor is are supplemental to the detector and is not intended for use as a required heat detector. Refer to listee's printed data sheet for additional detailed product description and operational considerations. RATING: 8.5-35 VDC INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and in a manner acceptable to the authority having jurisdiction. For vertical wall or ceiling mount. MARKING: Listee's name, model number, electrical rating and UL label. APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm control units. Suitable for installation in open areas with air velocity range from 0-1000 ft/mm. NOTE: Formerly 7272-1209:210 06-20-05 This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or recommendation of the item listed. This listing should not be used to verify correct V operational requirements or installation criteria. Refer to listee's data sheet, installation instructions and/or other Date Issued: July 01, 2019 Listing Expires August 29, 2020 Authorized By: DAVID CASTILLO, Program Coordinator Fire Engineering Division Property representative: [Jose Arellano Email: ~iosea@ojgrowers.com State: Zip code: Phone: ] [92008 J 908-8945 SYSTEM RECORD OF COMPLETION Fire Alarm & Supplemental Devices 2019 Edition To be tompIbte4 b the system installation contractor at the time of system acceptance and approval. SYMONS FIRE PROTECTION, INC. 12155 Paine Place Poway, CA 92064 Tel: 619-588-6364 Fax: 619-588-6805 www.symonsfp.com Form completion Date: [11/30/2020 PROPERTY INFORMATION -0 I!! Fax: I . INSTALLATION, SERVICE, TESTING, AND MONITORING INFORMATION Installation contractor Address: [ins Fire Protection, Inc. Phone: 1 619-588-6364 Fax: ) ] [12155 Paine Place Email: ] [m9uhmno@mo5f.cm Service organization: Address: [symons Fire Protection. Inc. ] F1 2155 Paine Place Phone: [-588-6364 Fax: 1 [619-588-6805 Email: ] [gulino@sYmonsfp.com Testing organization: [Symons Fire Protection, Inc. Phone: [619-588-6364 Monitoring organization: Fax: ] [i-s-os Address: ] Paine Place, Poway, CA 92064 Email: J [gu1in0@symonsfp.com Address: 1 Effective date for test and inspection contract: ] F09/21/2020 [Crime Alert -Your Monitoring Center ] [690 Lenfest Road, San Jose, CA 95133 1 Phone: [3671094 Fax: ] Email: ] [m9ulino@sYmonsfp.com Account number 1 1 1037 1 Phone line 1: Phone line 2: Means of transmIssIon: Entity to which alarms are retransmitted: Phone: [Contact II) J [ DOCUMENTATION On-she location of the required record documents and site-specific software: [cument Cabinet DESCRIPTION OF SYSTEM OR SERVICE This lsa: Permit number; NFPA72edition: .' New system [FPrt2020.0084 ] Modification to existing system 4.1 Control Unit Manufacturer. Model number [Silent Knight I [sio. 4.2 Software and Firmware [3.64 4.3 Alarm Verification This system does not incorporate alarm verification. S. SYSTEM POWER Number of devices subject to alarm Alarm verification set for (seconds): verification: 1 5.1 Control Unit 5.1.1 Primary Power Input voltage of control panel: Control panel amps: Overcurrent protection type: Overcurrent protection amps: [120 j [1.22 ] [Breaker Lockout 1 [20 Branch circuit disconnecting means location: Number. [use Panel - Under Stairs ] [2 1 5.1.2 Secondary Power Type of secondary power. Location, if remote from the plant: [Sealed Lead Acid Batteries j [Housed within the panel 1 Calculated capacity of secondary power to drive the system: In standby mode (hours): in alarm mode (minutes): [24 ][5 1 5.2 Control Unit Power Extender Panels: Make & Model Location Area Served Power Source Silent Knight 5104b Riser Room Entire Building 120 Dedicated . This system does not have power extender panels CIRCUITS AND PATHWAYS Pathway Type Dual Media Pathway Separate Pathway Class Survivability Level Signaling Line B 2 Device Power Initiating Device Notification Appliance Other (specify): REMOTE ANNUNCIATORS Type Location B. INITIATING DEVICES Type Quantity Addreesthle/Conventlonal Alarm/Supervisory Sensing Technology Manual Pull Stations 1 Conventional Alarm Smoke Detectors 1 Conventional Alarm Photoelectric Duct Smoke Detectors Heat Detectors Gas Detectors Carbon Monoxide Detectors Waterfiow Switches 1 Conventional Alarm Tamper Switches 3 Conventional Supervisory 9. NOTIFICATION APPLIANCES Type Quantity Description 10. SYSTEM CONTROL FUNCTIONS Type Quantity Hold-Opee/Door Aefeasing Devices HVAC Shutdown Fire/Smoke Dampers Door Unlocking Elevator Recall Elevator Shunt Trip INTERCONNECTED SYSTEMS Description Location Purpose . This system does not have interconnected systems. CERTIFICATION AND APPROVALS 12.1 System Installation Contractor This system as specified herein has been installed according to all NFPA standards cited herein. Signature: -----------------------.1 I I I I I I I I I I I I I I I. ------------------------------J Print name: Date: [Michael J 1 [11/30/2020 Organization: Title Phone: { Symons Fire Protection, inc. 1 [Fire Alarm Division Manager [619-588-6364 1 12.2 System Operational Test This system as specified herein has tested according to all NFPA standards cited herein. Signature: ----------------------- I I I I I I I I I I I I I I I I I I I I I I I. ------------------------------.1 Print name: Date: [MichaelJ J[11/30/2020 Organization: Title: Phone: [symons Fire Protection, Inc. ] [Fire Alarm Division Manager 1 [619.588-6364 12.3 Acceptance Test Date and time of acceptance test: Installing contractor representative: [11/30/2020 - 3:00 pm PSI I ( Raul Evangelista Testing contractor representative: __________________________________________________________ Property representative: [Raul Evangelista j// I [iiia Rodriguez AHJ represenat17 VY wormed in with NFPA 72 Standard for the Completion of Installed Fire Protection Systems, 2079 edition. 7 pect performed New Signature - ------------------------------ ------------------------------